c.ATT 2 - SR20190008 ECRD Equipment Load Listing.xls
XLS spreadsheet 49 KB Posted
- Attached to
- Emigrant Creek Interagency Fire Facility Federal contract opportunity
- Solicitation number
- 1204M320R0001
About this file
This document contains an equipment load listing and details of a federal contract opportunity for the construction of a new Emigrant Creek Interagency Fire Facility in Oregon. The equipment load listing provides specifications for over 150 individual items and systems requiring power, such as computers, printers, lighting, appliances, exercise equipment, and communications devices located at the existing fire facility. The federal contract opportunity involves replacing the two existing converted residential structures with a new 14,800 square foot premanufactured fire facility complex on the 7-acre site. Scope of work includes demolition, grading, drainage, utility connection, landscaping and hardscaping. The solicitation was issued by the US Department of Agriculture Forest Service Pacific Northwest Region for the Emigrant Creek Ranger District compound in Hines, Oregon.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Amd002.docx | DOCX document | |
| Amd002_RFI_Responses.docx | DOCX document | |
| Amd001_RFI_Responses.docx | DOCX document | |
| Amd001.docx | DOCX document | |
| c.ATT 2 - 20180406 AE Submission-ECRD.docx | DOCX document | |
| d.ATT 4 - Wage_Determination.docx | DOCX document | |
| c.ATT 2 - 041717_Bldg_Sec_Policy_FINAL.pdf | ||
| c.ATT 2 - SR20190008 ECRD IT Load Listing.xls | XLS spreadsheet | |
| c.ATT 3 - ECIFF 3.0 Drawings.pdf | ||
| c.ATT 2 - ITelectDesignGuide020160310.pdf | ||
| c.ATT 2 - AccessControlSystemDesignGuidelines-20180702.pdf | ||
| a.offerors_packet.doc | DOC document | |
| c.ATT 2 - Room Data Sheet-Emigrant Creek 20200116.pdf | ||
| c.ATT 2 - TOC Section J 20200110.docx | DOCX document | |
| c.ATT 1 - CombinedSpecPackage.pdf | ||
| b.final_solicitation_package.doc | DOC document |
Show all 16
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Work Station & General Loads
| Workstation and General Equipment Load Listing | ||||||||||||||||||
| Forest: | National Forest Name | NP = normal power | ||||||||||||||||
| Location: | ERCD fire facility | IG = isolated ground computer power | Dedicated = 1 outlet, 1 breaker | Individual Equipment Data | Totals Calculated Don’t enter | |||||||||||||
| Date: | 7/24/19 | |||||||||||||||||
| Submitter: | Person Name | single outlet | ||||||||||||||||
| AGENCY | Quan. | Equipment Type | Location - Workstation or Room # | Manufacturer | Make/Model # | Data Outlet at Equipment RJ45 CAT 6 QUANTITY | NP | IGP | Dedicated Circuit | Voltage 120, 208 or 240 | Phase 1 or 3 | Nameplate Current A | Watts Nameplate | Plug Type | Volt-Amps | Total Watts | Total Volt Amps | Total BTU |
| FS | 80 | PC | Rm # ECIFF | Dell | Tower/Laptop | 3 | X | 120 | 1 | 6.0 | 500 | 5-15P | 720 | 40,000 | 57,600 | 136,520 | ||
| FS | 160 | 21" LCD Monitor | Rm# | Samsung | Model # | X | 120 | 1 | 3.5 | 325 | 5-15P | 420 | 52,000 | 67,200 | 177,476 | |||
| FS | 80 | Computer speakers | ECIFF | Dell | X | 115 | 1 | 0.5 | 12 | 5-15P | 58 | 960 | 4,600 | 3,276 | ||||
| FS | 1 | Voice Mail PC | Rm # | Active Voice/DFI | Model # | X | 120 | 1 | 5.0 | 500 | 5-15P | 600 | 500 | 600 | 1,707 | |||
| FS | 15 | Exterior LED lights | Exterior ECIFF | x | 120 | 1 | 5.0 | 500 | 5-15P | 600 | 7,500 | 9,000 | 25,598 | |||||
| FS | 240 | LED Lights | ECIFF | x | 120 | 1 | 0.5 | 500 | 5-15P | 60 | 120,000 | 14,400 | 409,560 | |||||
| FS | 2 | 70" flat TV | Conference room | x | Y | 120 | 1 | 5.0 | 500 | 5-15P | 600 | 1,000 | 1,200 | 3,413 | ||||
| 1 | Small 48" TV | GYM | x | Y | 120 | 1 | 5.0 | 500 | 5-15P | 600 | 500 | 600 | 1,707 | |||||
| FS | 3 | Small 48" TV | Small Conference rooms | x | Y | 120 | 1 | 5.0 | 500 | 5-15P | 600 | 1,500 | 1,800 | 5,120 | ||||
| FS | 3 | Water Heater/on demand | ECIFF | x | Y | 120 | 1 | 5.0 | 500 | 5-15P | 600 | 1,500 | 1,800 | 5,120 | ||||
| FS | 2 | Water Coolers | ECIFF | x | Y | 120 | 1 | 5.0 | 500 | 5-15P | 600 | 1,000 | 1,200 | 3,413 | ||||
| FS | 4 | Ceiling Fan | ECIFF | x | 120 | 1 | 5.0 | 500 | 5-15P | 600 | 2,000 | 2,400 | 6,826 | |||||
| FS | 4 | Exahaust Fans | GYM, restrooms/Break | 120 | 1 | 5.0 | 500 | 5-15P | 600 | 2,000 | 2,400 | 6,826 | ||||||
| FS | 80 | Voice Mail/Phones | ECIFF | Active Voice/DFI | Model # | X | 120 | 1 | 0.0 | 0 | 0 | 0 | 0 | 0 | ||||
| FS | 4 | Coffee pot | Break room/office | Mfr. | Model # | X | Y | 120 | 1 | 8.0 | 960 | 5-15P | 960 | 3,840 | 3,840 | 13,106 | ||
| FS | 1 | Stove/oven | Breakroom | Y | 208 | 1 | 40.0 | 8,320 | 8,320 | 8,320 | 8,320 | 28,396 | ||||||
| FS | 2 | Refridgerator | Breakroom | Y | 120 | 1 | 6.0 | 720 | 720 | 1,440 | ||||||||
| FS | 2 | Microwave | Breakroom | Mfr. | Model # | X | Y | 120 | 1 | 1.0 | 120 | 5-15P | 120 | 240 | 240 | 819 | ||
| FS | 2 | Vending Machine | Breakroom | X | Y | 120 | 1 | 5.0 | 600 | 600 | 1,200 | |||||||
| FS | 2 | FAX machine | ECIFF | X | 120 | 1 | 1.0 | 120 | 120 | 240 | ||||||||
| FS | 3 | Network Printer | ECIFF | Mfr. | Model # | 3 | X | X | Y | 120 | 1 | 10.0 | 1,200 | 5-15P | 1,200 | 3,600 | 3,600 | 12,287 |
| FS | 70 | Desk task Light | ECIFF | Mfr. | Model # | X | 120 | 1 | 1.0 | 120 | 5-15P | 120 | 8,400 | 8,400 | 28,669 | |||
| FS | 10 | Portable radio chargers | ECIFF | X | 120 | 1 | 1.0 | 120 | 5-15P | 120 | 1,200 | 1,200 | 4,096 | |||||
| FS | 5 | FM Radio | ECIFF | Mfr. | Model # | X | 120 | 1 | 1.0 | 120 | 5-15P | 120 | 600 | 600 | 2,048 | |||
| FS | 1 | Plotter | ECIFF | Mfr. | Model # | X | x | Y | 120 | 1 | 5.0 | 600 | 5-15P | 600 | 600 | 600 | 2,048 | |
| FS | 2 | Clothes Washer | GYM | Mfr. | Model # | X | Y | 120 | 1 | 1.0 | 120 | 5-20P | 120 | 240 | 240 | 819 | ||
| FS | 2 | Clothes Dryer | GYM | Mfr. | Model # | X | Y | 120 | 1 | 24.0 | 2,880 | 30A | 2,880 | 5,760 | 5,760 | 19,659 | ||
| FS | 2 | Eliptical | GYM | X | Y | 120 | 1 | 1.0 | 120 | 5-15P | 120 | 240 | 240 | 819 | ||||
| FS | 2 | Box Fan | GYM | X | 120 | 1 | 2.0 | 240 | 5-15P | 240 | 480 | 480 | 1,638 | |||||
| FS | 2 | Excircise Bike | GYM | X | Y | 120 | 1 | 4.0 | 480 | 5-15P | 480 | 960 | 960 | 3,276 | ||||
| FS | 2 | Treadmill | GYM | X | Y | 120 | 1 | 4.0 | 480 | 5-15P | 480 | 960 | 960 | 3,276 | ||||
| FS | 25 | Cell Charger | ECIFF | X | 120 | 1 | 1.0 | 120 | 5-15P | 120 | 3,000 | 3,000 | 10,239 | |||||
| FS | 5 | Individual heaters | ECIFF | X | Y | 120 | 1 | 2.0 | 240 | 5-15P | 240 | 1,200 | 1,200 | 4,096 | ||||
| FS | 2 | Small Fridge | ECIFF | X | Y | 120 | 1 | 4.0 | 480 | 5-15P | 480 | 960 | 960 | 3,276 | ||||
| FS | 1 | Radio Base | ECIFF | need antenna | X | 120 | 1 | 4.0 | 480 | 5-15P | 480 | 480 | 480 | 1,638 | ||||
| FS | 5 | Boot Dryers | ECIFF | X | Y | 120 | 1 | 5.0 | 600 | 5-15P | 600 | 3,000 | 3,000 | 10,239 | ||||
| FS | 1 | Irrigation system | Exterior ECIFF | X | Y | 120 | 1 | 1.0 | 120 | 5-15P | 120 | 120 | 120 | 410 | ||||
| FS | 10 | Exit lights | ECIFF | X | Y | 120 | 1 | 1.0 | 120 | 5-15P | 120 | 1,200 | 1,200 | 4,096 | ||||
| FS | 1 | Outside meeting area | Exterior ECIFF | X | 120 | 1 | 8.0 | 960 | 5-15P | 960 | 960 | 960 | 3,276 | |||||
| FS | 2 | Paper Shreader | ECIFF | Mfr. | Model # | X | Y | 120 | 1 | 6.0 | 75 | 720 | 150 | 1,440 | 512 | |||
| 276,970 | 157,880 | 945,299 | ||||||||||||||||
| Updated 7/24/2019 SDS |
File details come from the government source that posted it. Updated .