This solicitation notice seeks proposals for renovation services at Building Six at Camp Atterbury in Edinburgh, Indiana. The firm fixed-price contract will provide all labor, materials, equipment, and supervision to complete renovations to the West wing on the first and second floors. Scope of work includes selective demolition, new interior walls, plumbing fixtures and piping, bathroom exhaust systems, ceramic and vinyl flooring, door and hardware installation, and surface preparation and finishing. The pre-bid conference is September 9th and the bid opening is September 25th. The contract duration is 270 days from notice to proceed. The project is set aside for small businesses under NAICS code 236220 with a $1-5 million magnitude. Proposals must be submitted through the beta.SAM website and offerors must register with SAM which takes approximately 15 business days.

View the file

Other files for this federal contract opportunity

Show all 16

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Ed inb ur gh

, In dia na

7 G atl ing S tre et

APRIL 16

2020-001

Ca m p At te rb ur y J oin t M an eu ve r T ra ini ng C en te r (

CA

JM

TC

Re gio na l T ra ini ng

In sti tu te

B uil din g

Re no va tio n

TJW TJW

Ph as e

A000

Architect:MEP Engineers:

Enlarged Site Map

Regional Training Institute Building 6, Camp Atterbury Joint Maneuver Training Center (CAJMTC) Edinburgh, IN 46124-5000

(PROJECT SITE)

Vicinity Map - Indiana

Project Title:

Regional Training Institute Building 6 - Phase 4

NN

Camp Atterbury

Northern Indiana Office 409 Broadway St.

New Haven, Indiana 46774 Tel: 260.437.4404 Fax: 317.536.3930

Corporate Office 7172 N. Keystone Ave., Suite G

Indianapolis, Indiana 46240 Tel: 317.466.9520 Fax: 317.536.3930

Camp Atterbury Joint Maneuver Training Center (CAJMTC) Edinburgh, Indiana 46124-5000

April 16, 2020 Construction Documents for Construction

Governor Eric Holcomb, State of Indiana BG R. Dale Lyles, Adjutant General of State of Indiana

COL Felicia Browkaw, Post Commander MAJ Chris Johanningsmeier, Director of Public Works

Mrs. Sheri Herrin, Contracting Specialist

Primary Entrance

Camp Atterbury Map N

COVER

Mr. Jeff Kernodle, Senior Project Manager CPT Gary Huffman, Contracting Officer's Representative

FIRST FLOOR CODE COMPLIANCE PLAN

ARCHITECTURAL SYMBOLS

ARCHITECTURAL ABBREVIATIONS:

MATERIAL INDICATIONS

FLOOR PLAN

ARCHITECTURAL SYMBOLS

GENERAL NOTES:

SHEET INDEX:

EXIT

EXITEXIT

EXIT EXIT

EXIT

EXITEXIT

EXIT

CODE COMPLIANCE NOTES:

GENERAL NOTES:

EXIT

Ed inb ur gh

, In dia na

7 G atl ing S tre et

APRIL 16

2020-001

Ca m p At te rb ur y J oin t M an eu ve r T ra ini ng C en te r (

CA

JM

TC

Re gio na l T ra ini ng

In sti tu te

B uil din g

Re no va tio n

TJW TJW

Ph as e

G101

INDEX, GENERAL

INFORMATION AND

CODE COMPLIANCE

ur gh

, In dia na

7 G atl ing S tre et

APRIL 16

2020-001

Ca m p At te rb ur y J oin t M an eu ve r T ra ini ng C en te r (

CA

JM

TC

Re gio na l T ra ini ng

In sti tu te

B uil din g

Re no va tio n

TJW TJW

Ph as e

G102

WORK PHASE PLANS

FIRST FLOOR PHASING PLAN - PHASE 1

BARRACKS BUILDING 6

PHASE 1

PHASE 1 PHASE 1

PHASE 1PHASE 1

PHASE 1

PHASE 5

PHASE 4

PHASE 2

PHASE 3

PHASE 3

PHASES 2, 3, 4 AND 5

SECOND FLOOR PHASING PLAN - PHASE 1

BARRACKS BUILDING 6

PHASE 1

PHASE 1

PHASE 1

PHASE 1

PHASE 1

PHASE 1

SECOND FLOOR PHASING PLAN - PHASES 2, 3, 4 AND 5

BARRACKS BUILDING 6

PHASE 1

FIRST FLOOR PHASING PLAN - PHASES 2, 3, 4 AND 5

BARRACKS BUILDING 6

PHASE 4

PHASE 2

PHASE 3

PHASE 3

PHASE 1

PHASE 5

PHASE 3 PHASE 4PHASE 4

PHASE 2

PHASE 5

PHASE 5 PHASE 3

PHASE 2

PHASE 3

PHASE 4

PHASES 2, 3, 4 AND 5

FIRST FLOOR DEMOLITION AND EXISTING CONDITIONS PLAN LEGEND:

GENERAL NOTES:

KEY NOTES:

ROOM GROUP TYPE A DEMOLITION PLAN

ROOM GROUP TYPE B DEMOLITION PLAN ROOM GROUP TYPE C DEMOLITION PLAN

KEY NOTES:KEY NOTES:

Ed inb ur gh

, In dia na

7 G atl ing S tre et

APRIL 16,

2020-001

Ca m p At te rb ur y J oin t M an eu ve r T ra ini ng C en te r (

CA

JM

TC

Re gio na l T ra ini ng

In sti tu te

B uil din g

Re no va tio n

TJW TJW

Ph as e

AD101

FIRST FLOOR

DEMOLITION AND

EXISTING

CONDITIONS PLAN

SECOND FLOOR DEMOLITION AND EXISTING CONDITIONS PLAN LEGEND:

GENERAL NOTES: KEY NOTES:

ADDITION TO CORRIDOR 1-ND

DEMOLITION RELATED TO

Ed inb ur gh

, In dia na

7 G atl ing S tre et

APRIL 16

2020-001

Ca m p At te rb ur y J oin t M an eu ve r T ra ini ng C en te r (

CA

JM

TC

Re gio na l T ra ini ng

In sti tu te

B uil din g

Re no va tio n

TJW TJW

Ph as e

AD102

SECOND FLOOR

DEMOLITION AND

EXISTING

CONDITIONS PLAN

FIRST FLOOR PROPOSED FLOOR PLAN

LEGEND:

GENERAL NOTES:

KEY NOTES:

ROOM GROUP TYPE B ENLARGED FLOOR PLAN

ROOM GROUP TYPE A ENLARGED FLOOR PLAN

KEY NOTES:

Ed inb ur gh

, In dia na

7 G atl ing S tre et

APRIL 16

2020-001

Ca m p At te rb ur y J oin t M an eu ve r T ra ini ng C en te r (

CA

JM

TC

Re gio na l T ra ini ng

In sti tu te

B uil din g

Re no va tio n

TJW TJW

Ph as e

A101

FIRST FLOOR

PROPOSED

FLOOR PLAN

SECOND FLOOR PROPOSED FLOOR PLAN LEGEND:

KEY NOTES:

ADDITION TO CORRIDOR 1-ND

KEY NOTES:

ROOM GROUP TYPE C ENLARGED FLOOR PLAN

KEY NOTES:KEY NOTES:

Ed inb ur gh

, In dia na

7 G atl ing S tre et

APRIL 16

2020-001

Ca m p At te rb ur y J oin t M an eu ve r T ra ini ng C en te r (

CA

JM

TC

Re gio na l T ra ini ng

In sti tu te

B uil din g

Re no va tio n

TJW TJW

Ph as e

A102

PROPOSED

FLOOR PLAN

SECOND FLOOR

FIRST FLOOR REFLECTED CEILING PLAN

ROOM GROUP TYPE B REFLECTED CEILING PLAN

ROOM GROUP TYPE A REFLECTED CEILING PLAN

ROOM GROUP TYPE C REFLECTED CEILING PLAN

LEGEND:

Ed inb ur gh

, In dia na

7 G atl ing S tre et

APRIL 16

2020-001

Ca m p At te rb ur y J oin t M an eu ve r T ra ini ng C en te r (

CA

JM

TC

Re gio na l T ra ini ng

In sti tu te

B uil din g

Re no va tio n

TJW TJW

Ph as e

A103

FIRST FLOOR

REFLECTIVE CEILING

PLAN

SECOND FLOOR REFLECTED CEILING PLAN

LEGEND:

ADDITION TO CORRIDOR 1-NDCEILING DETAILCEILING DETAIL

Ed inb ur gh

, In dia na

7 G atl ing S tre et

APRIL 16

2020-001

Ca m p At te rb ur y J oin t M an eu ve r T ra ini ng C en te r (

CA

JM

TC

Re gio na l T ra ini ng

In sti tu te

B uil din g

Re no va tio n

TJW TJW

Ph as e

A104

SECOND FLOOR

REFLECTIVE CEILING

PLAN

ROOF PLAN

LEGEND

KEY NOTES:KEY NOTES:

W/ TIE IN TO EXISTING MODIFIED

TYPICAL EQUIPMENT CURB

Ed inb ur gh

, In dia na

7 G atl ing S tre et

APRIL 16

2020-001

Ca m p At te rb ur y J oin t M an eu ve r T ra ini ng C en te r (

CA

JM

TC

Re gio na l T ra ini ng

In sti tu te

B uil din g

Re no va tio n

TJW TJW

Ph as e

A105

ROOF PLAN

BUILDING 6 SOUTH ELEVATION

KEY NOTES:

BUILDING 6 EAST ELEVATION

BUILDING 6 NORTH ELEVATION

BUILDING 6 WEST ELEVATION

KEY PLAN

GENERAL NOTES:

A201

EXTERIOR

ELEVATIONS

BUILDING

Ed inb ur gh

, In dia na

7 G atl ing S tre et

APRIL 16

2020-001

Ca m p At te rb ur y J oin t M an eu ve r T ra ini ng C en te r (

CA

JM

TC

Re gio na l T ra ini ng

In sti tu te

B uil din g

Re no va tio n

TJW TJW

Ph as e

BUILDING 6 COURTYARD NORTH ELEVATION

KEY NOTES

BUILDING 6 COURTYARD EAST ELEVATION

BUILDING 6 COURTYARD SOUTH ELEVATION

BUILDING 6 COURTYARD WEST ELEVATION

KEY PLAN

GENERAL NOTES:

A202

COURTYARD

BUILDING

ELEVATIONS

Ed inb ur gh

, In dia na

7 G atl ing S tre et

APRIL 16,

2020-001

Ca m p At te rb ur y J oin t M an eu ve r T ra ini ng C en te r (

CA

JM

TC

Re gio na l T ra ini ng

In sti tu te

B uil din g

Re no va tio n

TJW TJW

Ph as e

TYPICAL WALL SECTION

TYPICAL WALL SECTION AT CORRIDORTYPICAL WALL SECTIONWALL SECTION AT LOBBY 1NA & 2NA

GENERAL NOTES:

PARAPET DETAIL

HEAD DETAIL

SILL DETAIL

HEAD DETAIL

EXISTING

PROPOSED

SILL DETAIL

PROPOSEDEXISTING

KEY NOTES - CONTINUED:

ROOF FLASHING DETAIL

PATCHING DETAIL

TYPICAL JAMB

PATCHING DETAIL

TYPICAL SILL

Ed inb ur gh

, In dia na

7 G atl ing S tre et

APRIL 16,

2020-001

Ca m p At te rb ur y J oin t M an eu ve r T ra ini ng C en te r (

CA

JM

TC

Re gio na l T ra ini ng

In sti tu te

B uil din g

Re no va tio n

TJW TJW

Ph as e

A301

AND

WALL SECTIONS

DETAILS

TYP. WALL ELEVATION - RM GROUP ATYP. WALL ELEVATION - RM GROUP BTYP. WALL ELEVATION - RM GROUP CTYP. WALL ELEVATION - RM GROUP C

TYP. WALL ELEVATIONS - ROOM GROUPS A & B

BATHROOM

ABCD

TYP. WALL ELEVATIONS - ROOM GROUP C - ROOMS 185, 187, 101, 103, 102 AND 104

BATHROOMS

ABC

TYPICAL REQUIREMENTS FOR ROOM GROUP C ACCESSORIES

D

TYP. WALL ELEVATIONS - ROOM GROUP C - ROOMS 181 AND 183

BATHROOM

ABCD

ENLARGED PLAN

ROOM GROUP B

ENLARGED PLAN

ROOM GROUP A

ENLARGED PLAN

ROOM GROUP C

MIRRORED ENLARGED PLAN

ROOM GROUP C

ROOM GROUP TYPES "A" & "B"

BATHROOM WALL WITH DOOR AT

TYPICAL:

GENERAL NOTES:

Ed inb ur gh

, In dia na

7 G atl ing S tre et

APRIL 16,

2020-001

Ca m p At te rb ur y J oin t M an eu ve r T ra ini ng C en te r (

CA

JM

TC

Re gio na l T ra ini ng

In sti tu te

B uil din g

Re no va tio n

TJW TJW

Ph as e

A401

ELEVATIONS,

RESTROOM

ROOM ELEVATIONS

AND ENLARGED

FLOOR PLANS

GENERAL NOTES:KEY NOTES:

PHASE 1 ROOM FINISH SCHEDULE

B

WALL TYPE SCHEDULE:

ROOM FINISH SCHEDULE

MATERIALS

PHASE 2 ROOM FINISH SCHEDULEPHASE 3 ROOM FINISH SCHEDULE

KEY NOTES:

A

WALL TYPE SCHEDULE:

Ed inb ur gh

, In dia na

7 G atl ing S tre et

APRIL 16,

2020-001

Ca m p At te rb ur y J oin t M an eu ve r T ra ini ng C en te r (

CA

JM

TC

Re gio na l T ra ini ng

In sti tu te

B uil din g

Re no va tio n

TJW TJW

Ph as e

A601

SCHEDULES FOR

ROOM FINISH

PHASES 1, 2 AND 3

GENERAL NOTES:KEY NOTES:

ROOM FINISH SCHEDULE

MATERIALS

PHASE 4 ROOM FINISH SCHEDULEPHASE 5 ROOM FINISH SCHEDULE

KEY NOTES:KEY NOTES:KEY NOTES:

HEAD DETAIL

GYPSUM BOARD

JAMB DETAIL

GYPSUM BOARD

SILL DETAIL

GYPSUM BOARD

TYPICAL WINDOW

BULKHEAD DETAIL

CEILING

CASEWORK DETAIL

CASEWORK DETAIL

ROOM GROUPS TYPE A & B

ROOM GROUP TYPE C

WAINSCOT DETAIL

Ed inb ur gh

, In dia na

7 G atl ing S tre et

APRIL 16,

2020-001

Ca m p At te rb ur y J oin t M an eu ve r T ra ini ng C en te r (

CA

JM

TC

Re gio na l T ra ini ng

In sti tu te

B uil din g

Re no va tio n

TJW TJW

Ph as e

A602

SCHEDULE FOR

ROOM FINISH

PHASES 4 AND 5

PHASE 1 DOOR SCHEDULE

GLAZING SCHEDULE

DOOR HARDWARE SETS

PHASE 2 DOOR SCHEDULE

PHASE 3 DOOR SCHEDULE

PHASE 4 DOOR SCHEDULE

PHASE 5 DOOR SCHEDULE

DOOR ELEVATIONSDOOR FRAME ELEVATIONS

ABCF-1F-2 DE

DOOR HEAD / JAMB DETAILDOOR SILL DETAIL DOOR SILL DETAILNOT USED

HEAD DETAIL

JAMB DETAILJAMB DETAIL

DOOR SILL WITH PORCH SLAB CONNECTION DETAIL

DOOR HEAD / JAMB DETAILDOOR HEAD / JAMB DETAILDOOR SILL DETAIL

EAST ELEVATION - NEW WALL

WALL EXPANSION JOINT DETAIL

Ed inb ur gh

, In dia na

7 G atl ing S tre et

APRIL 16,

2020-001

Ca m p At te rb ur y J oin t M an eu ve r T ra ini ng C en te r (

CA

JM

TC

Re gio na l T ra ini ng

In sti tu te

B uil din g

Re no va tio n

TJW TJW

Ph as e

A603

AND DETAILS

DOOR SCHEDULES

FOR ALL PHASES

ur gh

, In dia na

7 G atl ing S tre et

APRIL 16,

20039

Ca m p At te rb ur y J oin t M an eu ve r T ra ini ng C en te r (

CA

JM

TC

Re gio na l T ra ini ng

In sti tu te

B uil din g

Re no va tio n

Ph as e

M001

MECHANICAL

SYMBOLS,

ABBREVIATIONS,

GENERAL NOTES

DAM DSJ

GENERAL SYMBOLS:

DEMOLITION NOTE

POINT OF REMOVAL

POINT OF CONNECTION

PLAN NOTE

NOTE: ALL SYMBOL DESCRIPTIONS ARE SUBJECT TO MODIFICATION ON THE DRAWINGS. ALL SYMBOLS NOT NECESSARILY USED ON THIS PROJECT.

DUAL DUCT TERMINAL BOX:

FD

VERTICAL FIRE DAMPER

HORIZONTAL FIRE DAMPER

VOLUME BALANCE DAMPER

FLEXIBLE DUCT

DUCT TURN 90°

DUCT DEPTH

DUCT WIDTH

16x14

FILTER (INLINE)

PIPE ELBOW UP (RISER)

PIPE ELBOW DOWN

UNION

PIPE TEE DOWN

PIPE TURN 90°

CAP OR PLUG

REDUCER, CONCENTRIC

REDUCER, ECCENTRIC

PIPE GUIDE

PIPE ANCHOR

FLANGES

LINE BREAK

Y-STRAINER

FLEXIBLE CONNECTION

STEAM TRAP

PRESSURE SENSOR

BALL VALVE

VALVES & FITTINGS:

GLOBE VALVE

GATE VALVE

PLUG VALVE

NEEDLE VALVE

THERMAL EXPANSION VALVE

BUTTERFLY VALVE

BALANCING VALVE

CHECK VALVE

CONTROL VALVE

PRESSURE REDUCING,

PRESSURE REDUCING,

SOLENOID VALVE

SELF CONTAINED VALVE

RELIEF, PILOT OPERATED

THREE WAY BALL VALVE

THREE WAY GLOBE VALVE

THREE WAY PLUG VALVE

PILOT OPERATED VALVE

VALVE

AUTOMATIC FLOW CONTROL

VALVE

THREE WAY CONTROL VALVE

ANGLE GLOBE VALVE

PRESSURE RELIEF,

ANGLE TYPE VALVE

BACK FLOW PREVENTER

DUCTWORK:

SUPPLY ARROW

GAUGE

VOLUME DAMPER

RETURN/EXHAUST ARROW

SUPPLY UP

SUPPLY UP

SUPPLY DOWN

SUPPLY DOWN

RETURN/EXHAUST UP

RETURN/EXHAUST UP

RETURN/EXHAUST DOWN

RETURN/EXHAUST DOWN

ROUND UP

ROUND UP

ROUND DOWN

ROUND DOWN

OVAL SUPPLY UP

OVAL SUPPLY UP

OVAL SUPPLY DOWN

OVAL SUPPLY DOWN

SINGLE LINE REPRESENTATION:

90° MITERED ELBOW WITH

DUCT END CAP

ELBOW

w

(r=w) r

HORIZONTAL FIRE DAMPER

FD

FD VERTICAL FIRE DAMPER

ACCESS DOORAD

DUCT END CAP

FLEXIBLE DUCT

SUPPLY DIFFUSER:

RETURN/EXHAUST GRILLE:

LINEAR BAR & SLOT DIFFUSER:

FD

THERMOSTAT

DUCTWORK:

TURNING VANES

MECHANICAL ABBREVIATIONS:

SANITARY

PIPE SLOPES IN DIRECTION OF ARROW

HOT WATER RETURN

EXISTING PIPING TO REMAIN

EXISTING PIPING TO BE REMOVED

POTABLE COLD WATER

POTABLE HOT WATER (TEMPERATURE AS NOTED)

SANITARY VENT

INLINE PUMP

REVISION

MOTORIZED DAMPER

THERMOMETER

PIPING DESIGNATIONS:

NEW PIPING

DETAIL BUBBLE

SECTION BUBBLE

M

SD-4

SHADING INDICATES BLANKED-OFF

QUADRANT OF DIFFUSION PATTERN

DIFFUSER TYPE

DIFFUSER SIZE

DIFFUSER CFM

RG-3

GRILLE TYPE

GRILLE SIZE

GRILLE CFM

LD-6

DIFFUSER TYPE

DIFFUSER SIZE

DIFFUSER CFM

SEE SCHEDULE FOR

RUNOUT SIZE

SEE SCHEDULE FOR

RUNOUT SIZE

SEE SCHEDULE FOR

RUNOUT SIZE

ARROW INDICATES

DIRECTION OF AIR FLOW

MOTORIZED DAMPER

M

BACKDRAFT DAMPER

BDD

VAV-1

TYPE OF TERMINAL BOX

TERMINAL BOX SIZE

SEE SCHEDULE

FOR RUNOUT SIZE

VAV-1

TYPE OF TERMINAL BOX

TERMINAL BOX SIZE

SUPPLY DIFFUSER:

RETURN/EXHAUST GRILLE:

LINEAR BAR & SLOT DIFFUSER:

SD-4

DIFFUSER TYPE

DIFFUSER SIZE

DIFFUSER CFM

RG-3

GRILLE TYPE

GRILLE SIZE

GRILLE CFM

LD-6

DIFFUSER TYPE

DIFFUSER SIZE

DIFFUSER CFM

SEE SCHEDULE FOR

RUNOUT SIZE

SEE SCHEDULE FOR

RUNOUT SIZE

SEE SCHEDULE FOR

RUNOUT SIZE

ARROW INDICATES

DIRECTION OF AIR FLOW

BACKDRAFT DAMPERBDD

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AHU AIR HANDLING UNIT

AD ACCESS DOOR

BDD BACK DRAFT DAMPER

BHP BRAKE HORSEPOWER

BLDG BUILDING

BOD BOTTOM OF DUCT

BOS BOTTOM OF STEEL

BTU BRITISH THERMAL UNIT

CA COMPRESSED AIR

CHWR CHILLED WATER RETURN

CHWS CHILLED WATER SUPPLY

CO CLEANOUT

CR CONDENSATE RETURN

CS CAST SINK

CSS CLINIC SERVICE SINK

CW DOMESTIC COLD WATER

DB DRY BULB

DCV DOUBLE CHECK VALVE

DIA DIAMETER

DN DOWN

DW DEIONIZED WATER

EES EMERGENCY EYE AND SHOWER WASH

EEW EMERGENCY EYE WASH

EF EXHAUST FAN

EG EXHAUST GRILLE

EL ELEVATION

ES EMERGENCY SHOWER

EXIST EXISTING

GL GLYCOL

FCU FAN COIL UNIT

FD FIRE DAMPER OR FLOOR DRAIN

FDC FIRE DEPARTMENT CONNECTION

FLA FULL LOAD AMPS

HB HOSE BIBB

HKSP HOUSEKEEPING

HNDCP HANDICAPPED

HPR HIGH PRESSURE STEAM RETURN

HPS HIGH PRESSURE STEAM SUPPLY

HW DOMESTIC HOT WATER

HWR DOMESTIC HOT WATER RETURN

HWRP HOT WATER RECIRCULATION PUMP

HHWR HEATING HOT WATER RETURN

HHWS HEATING HOT WATER SUPPLY

IE INVERT ELEVATION

JS JANITOR SINK

JT JOINT

LAV LAVATORY

LPSR LOW PRESSURE STEAM RETURN

LPSS LOW PRESSURE STEAM SUPPLY

MB MOP BASIN

MF MIXING FAUCET

MPR MEDIUM PRESSURE STEAM RETURN

MPS MEDIUM PRESSURE STEAM SUPPLY

NC NORMALLY CLOSED

NO NORMALLY OPEN

PIV POST INDICATING VALVE

PRV PRESSURE RELIEF VALVE

PSIA POUNDS PER SQUARE INCH ABSOLUTE

PSIG POUNDS PER SQUARE INCH GAUGE

RF RETURN FAN

RG RETURN GRILLE

RO REVERSE OSMOSIS

RPBP REDUCED PRESSURE BACKFLOW PREVENTER

SAN SANITARY

SD SUPPLY DIFFUSER

SF SUPPLY FAN

SG SUPPLY GRILLE

SH SHOWER

SI SEDIMENT INTERCEPTOR

SK SINK

STM STEAM

TD TRENCH DRAIN

TMV THERMOSTATIC MIXING VALVE

TSP TOTAL STATIC PRESSURE

V SANITARY VENT

VD VOLUME DAMPER

VTR VENT THROUGH ROOF

WB WET BULB

WC WATER CLOSET

WH WALL HYDRANT

DIFFUSERS & REGISTERS

TERMINAL BOXES

SINGLE-DUCT TERMINAL BOX

HUMIDISTAT

SENSOR

DUCT TRANSITION -

SLOPED ON BOTH SIDES

DUCT TRANSITION -

FLAT ON ONE SIDE

DUCT TRANSITION -

SQUARE TO ROUND

DUCT TRANSITION -

SQUARE TO ROUND

DUCT TRANSITION -

SLOPED BOTH SIDES

DUCT TRANSITION -

FLAT ON ONE SIDE

15° MAX

15° MAX

CONTROL PANEL

SEE SCHEDULE

FOR RUNOUT SIZE

CONTROL PANEL(S)

SHADING INDICATES BLANKED-OFF

QUADRANT OF DIFFUSION PATTERN

S

H

A M-501

T

T

S

P

1. PROVIDE AND INSTALL ALL EQUIPMENT, PIPING, DUCTWORK AND

APPURTENANCES AS DESCRIBED BY THESE DRAWINGS AND AS REQUIRED

TO PROVIDE COMPLETE AND OPERATIONAL SYSTEMS TO THE OWNER

UNDER THIS CONTRACT.

2. REFER TO THE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS

RELATING TO THE QUALITY, CONSTRUCTION AND FINISH OF MATERIALS.

3. THESE DRAWINGS INDICATE REQUIRED SIZE AND POINTS OF TERMINATION

FOR PIPING, DUCTWORK, CONDUIT, ETC. THE EQUIPMENT SHOWN

ILLUSTRATES SUGGESTED ROUTING, BUT ALL NECESSARY OFFSETS MAY

NOT BE SHOWN. INSTALL WORK IN A MANNER THAT WILL CONFORM WITH

THE STRUCTURE. AVOID OBSTRUCTIONS, PRESERVE HEADROOM AND

MAINTAIN MAXIMUM CLEARANCE WITHOUT FURTHER INSTRUCTION FROM

THE ARCHITECT/ENGINEER OR ADDITIONAL COST TO THE OWNER.

4. THE DRAWINGS ARE A COMPLIMENTARY PART OF THE CONTRACT

DOCUMENTS. THE PROVISIONS OF ANY CONTRACT DOCUMENT ARE

BINDING AS IF BY ALL. IF INFORMATION ON A DRAWING CONFLICTS WITH

ANOTHER CONTRACT DOCUMENT, THE PROVISIONS GRANTING GREATER

RIGHTS TO THE OWNER, IMPOSING GREATER RESPONSIBILITY TO THE

CONTRACTOR OR REQUIRING GREATER QUANTITY OR HIGHER QUALITY

SHALL GOVERN.

5. ALL VALVES, COILS, DAMPERS, TRAPS ETC. SHALL BE INSTALLED

ALLOWING EASY ACCESS FOR OPERATION AND MAINTENANCE. AREA

ADJACENT TO THE ACCESS PANELS SHALL BE CLEAR OF ANY

OBSTRUCTIONS.

6. ARROWS ON THE CHILLED WATER MAINS INDICATE THE DIRECTION OF

FLOW; PITCH MAINS UPWARD A MINIMUM OF 1" PER 60' IN THE DIRECTION

OF FLOW. ARROWS ON STEAM AND CONDENSATE PIPING AND DRAIN LINE

INDICATE THE DOWNWARD PITCH OF THE PIPING; PITCH PIPING

DOWNWARD A MINIMUM OF 1” PER 40'.

7. INSTALL AIR VENTS AT ALL HIGH POINTS AND DRAINS AT ALL LOW POINTS

OF WATER PIPING SYSTEM(S).

8. PIPING BRANCHES TO EQUIPMENT SHALL HAVE SAME SIZE VALVES AND

FITTINGS AS THAT OF THE LINE SIZE WITH THE EXCEPTION OF THE

TEMPERATURE CONTROL VALVES AND STEAM TRAPS.

9. DUCT OR PIPING PENETRATING FLOOR SLABS AND/OR WALLS SHALL BE

SEALED WEATHERTIGHT AND MATCH EXISTING CONSTRUCTION. DUCTS

OR PIPING PENETRATING FIRE RATED WALL AND/OR FLOOR SHALL BE

SEALED PER FIRE CODE. OPENINGS AROUND DUCT OR PIPES SHALL BE

SEALED WITH A MATERIAL HAVING THE SAME FIRE RATING AS THE WALL

OR FLOOR.

10. SHEET METAL DUCT SIZES ARE INSIDE DIMENSIONS. WHERE DUCT LINER

SPECIFIED, SHEET METAL DUCT SIZES INDICATE INSIDE DUCT LINER

DIMENSIONS.

11. INSTALL VOLUME DAMPER AT EACH BRANCH TAKE-OFF FROM MAIN

SUPPLY DUCTS.

12. ALL WALL THERMOSTATS, TEMPERATURE SENSORS, AND/OR HUMIDISTATS

SHALL BE LINED UP VERTICALLY WITH LIGHT SWITCHES UNLESS

OTHERWISE NOTED OR DIRECTED BY THE ARCHITECT/ENGINEER.

13. NO PLASTIC WATER LINES SHALL BE USED.

14. COORDINATE ALL WORK TO BE INSTALLED WITH ANY AND ALL OTHER

CONTRACTORS TO BE AFFECTED BY SUCH WORK, PRIOR TO ORDERING

ANY OF THE EQUIPMENT. THIS SHALL INCLUDE BUT NOT LIMITED TO

ELECTRICAL CHARACTERISTICS, CONNECTIONS REQUIRED, PENETRATION

SIZES AND LOCATIONS, PHYSICAL SIZE, COLOR AND FIT. ALSO REFER TO

SPECIFICATIONS.

15. ALL EQUIPMENT SHALL BE OF, AND CONSIST OF, AT LEAST MINIMUM SIZES

SELECTED, AND SHALL PERFORM TO OR SURPASS THE MINIMUM

REQUIREMENTS, SCHEDULES, NOTED AND SPECIFIED.

16. THE CONTRACTOR SHALL PROVIDE MISCELLANEOUS STEEL, PIPE

SUPPORTS, HANGERS, AND ADDITIONAL BRACING TO SUPPORT THE PIPE

AND EQUIPMENT. SEE STRUCTURAL DRAWINGS AND SPECIFICATIONS FOR

ADDITIONAL REQUIREMENTS.

17. MAINTAIN PROPER CLEARANCES AROUND TELECOMMUNICATIONS

SKELETAL AND INFRASTRUCTURE DURING AND AFTER CONSTRUCTION

18. WORK IS TO BE PERFORMED IN PHASES SEE ARCHITECTURAL DRAWINGS

FOR PHASING OF WORK.

19. REFER TO GENERAL NOTES ON DRAWING G101 FOR ADDITIONAL

INFORMATION.

GENERAL NOTES:

1. REPAIR AND PATCH ANY DAMAGE TO EXISTING OR NEW FACILITIES,

INCLUDING SURFACES, SIDEWALKS, STREETS, FLOORS, WALLS, ROOFS,

CEILING AND PAVEMENT. REPAIRS SHALL MATCH EXISTING

INSTALLATION.

2. ALL EXISTING EQUIPMENT (HVAC & PLUMBING), DUCTWORK, AND PIPING

(HVAC & PLUMBING) LOCATIONS, ROUTINGS, CLEARANCES AND SIZES OF

ITEMS TO BE REMOVED OR REUSED SHALL BE FIELD VERIFIED AT THE JOB

SITE. THIS ALSO INCLUDES ITEMS THAT MAY BE IN CONFLICT WITH NEW

WORK. ALL DISCREPANCIES BETWEEN THE DRAWINGS AND FIELD

SURVEY SHALL BE DOCUMENTED FOR REVIEW BY THE

ARCHITECT/ENGINEER.

3. ON DEMOLITION DRAWINGS, DASHED LINE ITEMS ARE ITEMS THAT SHALL

BE REMOVED.

4. ALL EQUIPMENT, PIPING, DUCTWORK, ETC MARKED FOR DEMOLITION

SHALL BE REMOVED COMPLETE, UNLESS OTHERWISE NOTED.

CONTRACTORS SHALL VERIFY EXACT DEMOLITION REQUIREMENTS PRIOR

TO BID AS ALL ITEMS MAY NOT BE SHOWN THAT MUST BE REMOVED. ALL

DEMOLISHED MATERIALS SHALL BECOME THE PROPERTY OF THE

CONTRACTOR. ALL DEMOLISHED MATERIALS ARE TO BE REMOVED FROM

THE OWNER'S SITE. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE

PROPER DISPOSAL OF ALL DEMOLISHED MATERIALS.

5. ALL PNEUMATIC CONTROL LINES SHALL BE REMOVED BACK TO THE

PNEUMATIC CONTROL AIR MAIN AND CAPPED.

6. REFER TO "SELECTIVE DEMOLITION" SPECIFICATION FOR ADDITIONAL

INFORMATION INCLUDING DISPOSAL AND RECYCLING.

GENERAL DEMOLITION NOTES:

AI ANALOG INPUT

AO ANALOG OUTPUT

BI BINARY INPUT

BO BINARY OUTPUT

CO2 CARBON DIOXIDE SENSOR

CS CURRENT SENSOR

P DIFFERENTIAL PRESSURE SENSOR

S DUCT SMOKE DETECTOR

ES END SWITCH

H HUMIDITY SENSOR

LL LOW LIMIT TEMPERATURE SENSOR

P PRESSURE SENSOR

T TEMPERATURE SENSOR

VARIABLE FREQUENCY DRIVEVFD

AIR HANDLER FAN

AIR FLOW MEASURING STATION

CONTROL VALVE

HYDRONIC PUMP

MOTOR STARTER

FLOW/CONTROL SYMBOLS:

MS

EP ELECTRO-PNEUMATIC SWITCH

FS FLOAT SWITCH

DUCT LINER

1 1

3 3

M

3 1

M

T

PHASE 4

WORK SHOWN IS TYPICAL

FOR STAFF ROOM PAIR.

WORK SHOWN IS TYPICAL

FOR STUDENT ROOM PAIR.

WORK SHOWN IS TYPICAL

FOR STUDENT ADA ROOM PAIR.

1 2

Ed inb ur gh

, In dia na

7 G atl ing S tre et

APRIL 16,

20039

Ca m p At te rb ur y J oin t M an eu ve r T ra ini ng C en te r (

CA

JM

TC

Re gio na l T ra ini ng

In sti tu te

B uil din g

Re no va tio n

Ph as e

M101

FIRST FLOOR

HVAC DEMOLITION

PLAN

SCALE:

FIRST FLOOR HVAC DEMOLITION PLAN

1/8" =1'-0"

1. ALL WORK MUST COMPLY WITH CURRENT MECHANICAL

CODE.

2. REPORT ALL MAINTENANCE CONCERNS TO OWNER AND

ENGINEER.

3. BUILDING TO REMAIN OCCUPIED AND OPERATIONAL

DURING CONSTRUCTION. COORDINATE ALL

SHUTDOWNS AND OUTAGES WITH OWNER MIN. 10 DAYS

IN ADVANCE.

4. CONTRACTOR SHALL COMPLY WITH ALL SAFETY AND

SECURITY PROCEDURES AND PROTOCOLS AS

DESIGNATED BY THE OWNER.

5. REFER TO GENERAL NOTES ON DRAWING G101 FOR

ADDITIONAL INFORMATION.

6. REFER TO "SELECTIVE DEMOLITION" SPECIFICATION

SECTION FOR ADDITIONAL INFORMATION INCLUDING

DISPOSAL AND RECYCLING REQUIREMENTS.

7. WORK TO BE COMPLETED IN PHASES REFER TO

ARCHITECTURAL DOCUMENTS FOR PHASING OF WORK.

GENERAL NOTES:

1. ALL WORK RELATED TO PTAC UNITS TO BE

COMPLETED IN PHASE 1. REMOVE EXISTING PTAC

UNIT INCLUDING WALL SLEEVE AND LOUVER.

PROTECT OPENING PRIOR TO INSTALLATION OF NEW

UNIT - REPORT MAINTENANCE CONCERNS TO GC AND

OWNER.

2. ALL WORK RELATED TO TOILET ROOM EXHAUST FANS

TO BE COMPLETED IN PHASE ASSOCIATED WITH

ROOM. REMOVE EXISTING CEILING EXHAUST FAN

AND DUCTWORK BACK TO EXHAUST RISER

COMPLETE.

3. REMOVE EXISTING ELECTRIC CABINET HEATER

COMPLETE INCLUDING WIRING AND CONTROLS.

4. REMOVE EXISTING FAN COIL UNIT - CAP HEATING

WATER PIPING FOR EXTENSION IN NEW WORK.

5. REMOVE EXISTING FLUE COMPLETE. PATCH

OPENINGS TO MATCH EXISTING SURFACES.

6. REMOVE EXISTING MOTORIZED DAMPER AND

ASSOCIATED CONTROLS. COORDINATE WITH NEW

WORK FOR EXTENT OF DEMOLITION.

7. EXISTING EXHAUST DUCT AND GRILLE TO REMAIN.

8. EXISTING TRANSFER DUCT AND GRILLE(S) TO

REMAIN. CLEAN AND PAINT CEILING AND WALL

GRILLES TO MATCH ADJACENT SURFACES.

9. REMOVE EXISTING PTAC UNIT COMPLETE INCLUDING

WALL SLEEVE, LOUVER, CONTROLS, AND WIRING.

10. REMOVE EXISTING EXHAUST FAN THERMOSTAT.

11. MECHANICAL WORK ASSOCIATED WITH THESE

ROOMS TO BE COMPLETED IN PHASE 1 WORK.

DEMOLITION NOTES:#

DAM DSJ

20039

M

T

7 7

M T

M M

WORK SHOWN IS TYPICAL

FOR STUDENT ROOM PAIR.

1 1

WORK SHOWN IS TYPICAL

FOR STAFF ROOM PAIR.

11 11

WORK SHOWN IS TYPICAL

FOR VISITOR'S QUARTERS

COORDINATE WORK IN THESE

ROOMS WITH OWNER. ANY

FINISHES DISTURBED BY THIS

WORK TO BE RESTORED TO

MATCH EXISTING FINISHES.

T

Ed inb ur gh

, In dia na

7 G atl ing S tre et

APRIL 16,

20039

Ca m p At te rb ur y J oin t M an eu ve r T ra ini ng C en te r (

CA

JM

TC

Re gio na l T ra ini ng

In sti tu te

B uil din g

Re no va tio n

Ph as e

M102

SECOND FLOOR

HVAC DEMOLITION

PLANSCALE:

SECOND FLOOR HVAC DEMOLITION PLAN

1/8" =1'-0"

DAM DSJ

1. ALL WORK MUST COMPLY WITH CURRENT MECHANICAL

CODE.

2. REPORT ALL MAINTENANCE CONCERNS TO OWNER AND

ENGINEER.

3. BUILDING TO REMAIN OCCUPIED AND OPERATIONAL

DURING CONSTRUCTION. COORDINATE ALL

SHUTDOWNS AND OUTAGES WITH OWNER MIN. 10 DAYS

IN ADVANCE.

4. CONTRACTOR SHALL COMPLY WITH ALL SAFETY AND

SECURITY PROCEDURES AND PROTOCOLS AS

DESIGNATED BY THE OWNER.

5. REFER TO GENERAL NOTES ON DRAWING G101 FOR

ADDITIONAL INFORMATION.

6. REFER TO "SELECTIVE DEMOLITION" SPECIFICATION

SECTION FOR ADDITIONAL INFORMATION INCLUDING

DISPOSAL AND RECYCLING REQUIREMENTS.

7. WORK TO BE COMPLETED IN PHASES REFER TO

ARCHITECTURAL DOCUMENTS FOR PHASING OF WORK.

GENERAL NOTES:

1. ALL WORK RELATED TO PTAC UNITS TO BE

COMPLETED IN PHASE 1. REMOVE EXISTING PTAC

UNIT INCLUDING WALL SLEEVE AND LOUVER.

PROTECT OPENING PRIOR TO INSTALLATION OF NEW

UNIT - REPORT MAINTENANCE CONCERNS TO GC AND

OWNER.

2. ALL WORK RELATED TO TOILET ROOM EXHAUST FANS

TO BE COMPLETED IN PHASE ASSOCIATED WITH

ROOM. REMOVE EXISTING CEILING EXHAUST FAN

AND DUCTWORK BACK TO EXHAUST RISER

COMPLETE.

3. REMOVE EXISTING ELECTRIC CABINET HEATER

COMPLETE INCLUDING WIRING AND CONTROLS.

4. EXISTING EXHAUST DUCT DOWN TO FIRST FLOOR TO

REMAIN.

5. REMOVE EXISTING FLUE COMPLETE. PATCH

OPENINGS TO MATCH EXISTING SURFACES.

6. REMOVE EXISTING MOTORIZED DAMPER AND

ASSOCIATED CONTROLS. COORDINATE WITH NEW

WORK FOR EXTENT OF DEMOLITION.

7. EXISTING EXHAUST DUCT AND GRILLE TO REMAIN.

8. EXISTING TRANSFER DUCT AND GRILLE(S) TO

REMAIN. CLEAN AND PAINT CEILING AND WALL

GRILLES TO MATCH ADJACENT SURFACES.

9. NOT USED.

10. REMOVE EXISTING EXHAUST FAN THERMOSTAT .

11. MECHANICAL WORK ASSOCIATED WITH THESE

ROOMS TO BE COMPLETED IN PHASE 1 WORK.

DEMOLITION NOTES:#

20x10 UP TO SECOND FLOOR TRANSITION TO 20x20 BELOW 2ND FLOOR

ECUH-2

ECUH-3

ECUH-2

ECUH-2

18x16

CEF-1

PTAC-11 PTAC-1 1

4"Ø

ECUH-1

FCU-1

PTAC-11 PTAC-1 1

CEF-13

4"Ø

ECUH-2

20x10 UP TO SECOND FLOOR TRANSITION TO 20x20 BELOW

2ND FLOOR

18x30

PTAC-21

ECUH-2

4"Ø

CEF-1 3CEF-13

T

PTAC-1 1PTAC-11

T

T

20x10 UP TO SECOND FLOOR TRANSITION TO 20x20 BELOW 2ND FLOOR 6

18x16

ECUH-1

ECUH-2

20x10 UP TO SECOND FLOOR TRANSITION TO 20x20 BELOW 2ND FLOOR

18x16

ECUH-1

ECUH-2

ECUH-3

PTAC-2 1

T

T

T

PTAC-11

FCU-211

WORK IN PHASE 4

PTAC-2 1

PTAC-2 1

T

M

RGA RGA

SEE ARCHITECTURAL PHASING

PLAN FOR THIS AREA.

WORK SHOWN IS TYPICAL

FOR STAFF ROOM PAIR.

WORK SHOWN IS TYPICAL

FOR STUDENT ADA ROOM PAIR.

4"Ø

CEF-1

CEF-1

PTAC-1

PTAC-1

T

T

WORK SHOWN IS TYPICAL

FOR STUDENT ROOM PAIR.

T

T

EGA 500

Ed inb ur gh

, In dia na

7 G atl ing S tre et

APRIL 16,

20039

Ca m p At te rb ur y J oin t M an eu ve r T ra ini ng C en te r (

CA

JM

TC

Re gio na l T ra ini ng

In sti tu te

B uil din g

Re no va tio n

Ph as e

M301

FIRST FLOOR

HVAC PLAN

SCALE:

FIRST FLOOR HVAC PLAN

1/8" =1'-0"

1. ALL WORK MUST COMPLY WITH CURRENT MECHANICAL

CODE.

2. RIGID AND FLEXIBLE DUCTWORK FABRICATION SHALL

CONFORM TO THE LATEST EDITION OF SMACNA "HVAC

DUCT CONSTRUCTION STANDARDS - METAL AND

FLEXIBLE". MINIMUM ALLOWABLE SHEETMETAL GAUGE

SHALL BE 22 GAUGE.

3. DUCTWORK SHALL BE CONSTRUCTED, AT MIN., TO THE

FOLLOWING CLASSES:

a. SUPPLY: PRESSURE 0-4"WC, LEAK 12 VELOCITY 2000

FPM.

b. RETURN AND EXHAUST: PRESSURE -1" TO +1"WC, LEAK

24, VELOCITY 1500 FPM.

4. ALL SUPPLY DUCTWORK TO BE EXTERNALLY INSULATED,

UNLESS OTHERWISE NOTED. OUTDOOR DUCTWORK TO

HAVE DOUBLE LAYER OF CLOSED CELL ELASTOMERIC

INSULATION WITH BONDED ALUMINUM CLADDING.

5. ALL NEW AIR SYSTEMS TO BE TESTED, ADJUSTED AND

BALANCED BY LICENSED TAB AGENCY.

6. ALL EXPOSED DUCTWORK, TO BE PREPARED AND

PRIMED FOR PAINTING.

7. CONTRACTOR TO COORDINATE INSTALLATION OF NEW

WORK WITH ALL OTHER TRADES TO MAINTAIN PROPER

ACCESS AND CLEARANCES FOR SERVICE AND

MAINTENANCE.

8. PROPERLY SUSPEND ALL EQUIPMENT, DUCTWORK,

DIFFUSERS AND GRILLES, ETC. FROM STRUCTURE.

9. PROVIDE 3 SETS OF FILTERS FOR EACH RTU. 1 SET FOR

CONSTRUCTION, 1 SET FOR TAB AND 1 SET TO BE

INSTALLED AT SUBSTANTIAL COMPLETION OF PROJECT

PHASE.

10. BUILDING TO REMAIN OCCUPIED AND OPERATIONAL

DURING CONSTRUCTION. COORDINATE ALL

SHUTDOWNS AND OUTAGES WITH OWNER MIN. 10 DAYS

IN ADVANCE.

11. CONTRACTOR SHALL COMPLY WITH ALL SAFETY AND

SECURITY PROCEDURES AND PROTOCOLS AS

DESIGNATED BY THE OWNER.

12. REFER TO GENERAL NOTES ON DRAWING G101 FOR

ADDITIONAL INFORMATION.

13. WORK TO BE COMPLETED IN PHASES REFER TO

ARCHITECTURAL DOCUMENTS FOR PHASING OF WORK.

GENERAL NOTES:

1. ALL WORK RELATED TO PTAC UNITS TO BE

COMPLETED IN PHASE 1. INSTALL NEW PTAC UNIT

WITH NEW WALL SLEEVE AND LOUVER. PROVIDE

EXTERNAL DRAIN TUBE EXTENDED 4" BEYOND FACE

OF WALL.

2. ALL WORK RELATED TO TOILET ROOM EXHAUST FANS

TO BE COMPLETED IN PHASE ASSOCIATED WITH

ROOM. CONNECT NEW 4" EXHAUST DUCTS TO

EXISTING 10x3 WALL STACK. NEW EXHAUST TO BE

RIGID METAL DUCTWORK WITH MAXIMUM 12" OF

FLEXIBLE DUCT AT CONNECTION TO FAN-SECURE FLEX

DUCT WITH METAL DRAW BAND CLAMPS.

3. NEW CEILING EXHAUST FAN WITH INTEGRAL CEILING

GRILLE. FAN TO HAVE INTEGRAL BACKDRAFT DAMPER.

4. REMOTE TEMPERATURE AND HUMIDITY SENSOR -TIE

INTO NEW BMS. ROUTE WIRING DOWN IN STUD WALL

AND AROUND TO UNIT IN SURFACE MOUNTED

RACEWAY ON WALL JUST ABOVE BASE MOLDING.

5. HEAVY DUTY WALL SUPPLY GRILLE, 18x16 DOUBLE

DEFLECTION LIKE "TITUS" 300RL-HD. INSTALL WITH

TAMPER PROOF HARDWARE BOTTOM OF GRILLE AT 12"

ABOVE FINISHED FLOOR.

6. PROVIDE REMOTE CABLE OPERATED DAMPER IN DUCT

BELOW 2ND FLOOR. BALANCE TO 1250 CFM FOR EVEN

DISTRIBUTION BETWEEN FLOORS. MOUNT OPERATOR

IN ACCESSIBLE LOCATION ON CHASE WALL.

7. HEAVY DUTY WALL SUPPLY GRILLE, 18x30 DOUBLE

DEFLECTION LIKE "TITUS" 300RS-HD. INSTALL WITH

TAMPER PROOF HARDWARE BOTTOM OF GRILLE AT 12"

ABOVE FINISHED FLOOR.

8. CONNECT EXISTING HEATING WATER PIPING TO NEW

UNIT. PROVIDE NEW SPECIALTIES PER DETAIL.

9. REBALANCE EXISTING GRILLE TO 500 CFM.

10. REBALANCE EXISTING WALL GRILLE TO 300 CFM.

11. WORK IN PHASE 4 COORDINATED WITH NEW

CONSTRUCTION - FCU-2: WALL MOUNTED DUCTLESS

UNIT, MOUNTED WITH BOTTOM AT 6' 0" A.F.F. ROUTE

REFRIGERANT PIPING AND WIRING PER

MANUFACTURER'S RECOMMENDATIONS. ENCLOSE IN

METAL PIPE ENCLOSURE PAINTED TO MATCH WALL.

ROUTE DRAIN OVER AND DOWN IN NEW WALL TO SPILL

ON GRADE AT APPROX. 18" ABOVE FINISHED GRADE.

PROVIDE REMOTE CONTROLLER FOR WALL MOUNTING.

REMOVE PTAC UNIT IN THIS ROOM COMPLETE

INCLUDING WIRING, HARDWARE, CONTROLS ETC.

PROTECT UNIT AND TURN OVER TO OWNER IN GOOD

CONDITION.

12. PROVIDE NEW 24x12 MOTORIZED DAMPER IN EXISTING

DUCT - FIELD VERIFY PRIOR TO ORDERING. PROVIDE

LINE VOLTAGE THERMOSTAT AND INTERLOCK WITH

REF-7 AND DAMPER.

13. MODIFY OPENING THROUGH 2ND FLOOR AS REQUIRED

TO ROUTE 10x10 EXHAUST UP. PROVIDE TYPE "EGA"

GRILLE AT BOTTOM OF DUCT AND BALANCE TO 500

CFM.

14. WORK IN THIS SPACE TO BE COMPLETED UNDER

PHASE 1 WORK.

PLAN NOTES:#

A M501

E M501

PTAC-2

ECUH-1

ECUH-1

518x16

PTAC-1 1

18x16

PTAC-21

ECUH-1

CEF-13

CEF-13

T

T

PTAC-1

PTAC-1

T

CEF-1 3CEF-13

PTAC-1

T

T

20x10 UP TO SECOND FLOOR TRANSITION TO 20x20 BELOW 2ND FLOOR 6

518x16

ECUH-1

20x20 UP TO UNIT ON ROOF 20x10 DN TO FIRST FLOOR

18x16

ECUH-1

ECUH-1

PTAC-2 1

ECUH-1

T

20x20 UP TO UNIT ON ROOF 20x10 DN TO FIRST FLOOR

BALANCE SUPPLY AIR AT UNIT TO SCHEDULED CFM

USE BALANCING DEVICE ABOVE 2ND FLOOR TO

EVENLY DISTRIBUTE AIR BETWEEN FLOORS.

20x20 UP TO UNIT ON ROOF 20x10 DN TO FIRST FLOOR

T

7T

M

BALANCE SUPPLY AIR AT UNIT TO SCHEDULED CFM

USE BALANCING DEVICE ABOVE 2ND FLOOR TO

EVENLY DISTRIBUTE AIR BETWEEN FLOORS.

PTAC-2 1

T

T

PTAC-2 1

FCU-312

WORK IN PHASE 4

PTAC-1 1

PTAC-1 1

PTAC-1 1

PTAC-1 1

T

T

T

T

3" PVC VENT FOR WATER HEATERS WH-1 ,2,3,4

COORDINATE WITH WATER HEATERS TERMINATE WITH CONCENTRIC

VENTING KIT PROVIDED WITH WATER HEATERS. PROVIDE NEW ROOF

PENETRATIONS AND FLASH WEATHERTIGHT. WORK TO BE COMPLETED

IN PHASE 4 TO MATCH INSTALLATION OF WATER HEATERS.

EGA-500

PTAC-11

14 14

WORK SHOWN IS TYPICAL

FOR STAFF ROOM PAIR.

WORK SHOWN IS TYPICAL

FOR STUDENT ROOM PAIR.

UP TO

REF-9

UP TO REF-10 UP TO REF-12 UP TO REF-11

UP TO REF-6

UP TO REF-7

Ed inb ur gh

, In dia na

7 G atl ing S tre et

APRIL 16,

20039

Ca m p At te rb ur y J oin t M an eu ve r T ra ini ng C en te r (

CA

JM

TC

Re gio na l T ra ini ng

In sti tu te

B uil din g

Re no va tio n

Ph as e

M302

SECOND FLOOR

HVAC PLANSCALE:

SECOND FLOOR HVAC PLAN

1/8" =1'-0"

1. ALL WORK MUST COMPLY WITH CURRENT MECHANICAL

CODE.

2. RIGID AND FLEXIBLE DUCTWORK FABRICATION SHALL

CONFORM TO THE LATEST EDITION OF SMACNA "HVAC

DUCT CONSTRUCTION STANDARDS - METAL AND

FLEXIBLE". MINIMUM ALLOWABLE SHEETMETAL GAUGE

SHALL BE 22 GAUGE.

3. DUCTWORK SHALL BE CONSTRUCTED, AT MIN., TO THE

FOLLOWING CLASSES:

a. SUPPLY: PRESSURE 0-4"WC, LEAK 12 VELOCITY 2000

FPM.

b. RETURN AND EXHAUST: PRESSURE -1" TO +1"WC, LEAK

24, VELOCITY 1500 FPM.

4. ALL SUPPLY DUCTWORK TO BE EXTERNALLY INSULATED,

UNLESS OTHERWISE NOTED. OUTDOOR DUCTWORK TO

HAVE DOUBLE LAYER OF CLOSED CELL ELASTOMERIC

INSULATION WITH BONDED ALUMINUM CLADDING.

5. ALL NEW AIR SYSTEMS TO BE TESTED, ADJUSTED AND

BALANCED BY LICENSED TAB AGENCY.

6. ALL EXPOSED DUCTWORK, TO BE PREPARED AND

PRIMED FOR PAINTING.

7. CONTRACTOR TO COORDINATE INSTALLATION OF NEW

WORK WITH ALL OTHER TRADES TO MAINTAIN PROPER

ACCESS AND CLEARANCES FOR SERVICE AND

MAINTENANCE.

8. PROPERLY SUSPEND ALL EQUIPMENT, DUCTWORK,

DIFFUSERS AND GRILLES, ETC. FROM STRUCTURE.

9. PROVIDE 3 SETS OF FILTERS FOR EACH RTU. 1 SET FOR

CONSTRUCTION, 1 SET FOR TAB AND 1 SET TO BE

INSTALLED AT SUBSTANTIAL COMPLETION OF PROJECT

PHASE.

10. BUILDING TO REMAIN OCCUPIED AND OPERATIONAL

DURING CONSTRUCTION. COORDINATE ALL

SHUTDOWNS AND OUTAGES WITH OWNER MIN. 10 DAYS

IN ADVANCE.

11. CONTRACTOR SHALL COMPLY WITH ALL SAFETY AND

SECURITY PROCEDURES AND PROTOCOLS AS

DESIGNATED BY THE OWNER.

12. REFER TO GENERAL NOTES ON DRAWING G101 FOR

ADDITIONAL INFORMATION.

13. WORK TO BE COMPLETED IN PHASES REFER TO

ARCHITECTURAL DOCUMENTS FOR PHASING OF WORK.

GENERAL NOTES:

1. ALL WORK RELATED TO PTAC UNITS TO BE

COMPLETED IN PHASE 1.INSTALL NEW PTAC UNIT WITH

NEW INSULATED WALL SLEEVE AND LOUVER. PROVIDE

EXTERNAL DRAIN TUBE EXTENDED 4" BEYOND FACE

OF WALL WITH ELBOW.

2. ALL WORK RELATED TO TOILET ROOM EXHAUST FANS

TO BE COMPLETED IN PHASE ASSOCIATED WITH

ROOM.EXTEND EXISTING 10x3 WALL STACK TO NEW 12x12 EXHAUST UP THROUGH ROOF. CONNECT 4"

EXHAUST FROM SECOND FLOOR EXHAUST FANS TO

12x12 VERTICAL RISER. MAXIMUM 12" OF FLEXIBLE

DUCTWORK AT CONNECTION TO FAN MAKE

CONNECTIONS WITH METAL DRAW BAND CLAMP.

3. NEW CEILING EXHAUST FAN WITH INTEGRAL CEILING

GRILLE. FAN TO HAVE INTEGRAL BACKDRAFT DAMPER.

4. REMOTE TEMPERATURE AND HUMIDITY SENSOR -TIE

INTO NEW BMS. ROUTE WIRING DOWN IN STUD WALL

AND AROUND TO UNIT IN SURFACE MOUNTED

RACEWAY ON WALL JUST ABOVE BASE MOLDING.

5. HEAVY DUTY WALL SUPPLY GRILLE, 18x16 DOUBLE

DEFLECTION LIKE "TITUS" 300RL-HD. INSTALL WITH

TAMPER PROOF HARDWARE BOTTOM OF GRILLE AT 12"

ABOVE FINISHED FLOOR.

6. REMOTE CABLE OPERATED DAMPER IN DUCT BELOW

2ND FLOOR - BALANCE FOR EVEN DISTRIBUTION

BETWEEN FLOORS.

7. COORDINATE LOCATION WITH EXISTING EQUIPMENT.

8. PROVIDE NEW LINE VOLTAGE THERMOSTAT, AND

CONTROL DAMPER. INTERLOCK EXHAUST FAN, AND

DAMPER WITH THERMOSTAT.

9. EXTEND 12x12 EXHAUST DUCT TO NEW LOCATION AND

MAKE NEW PENETRATION OF ROOF. REFER TO

DRAWING M303

10. BALANCE EXISTING GRILLE TO 500 CFM.

11. BALANCE EXISTING WALL GRILLE TO 300 CFM.

12. WORK IN PHASE 4 COORDINATED WITH NEW

CONSTRUCTION - FCU-3: WALL MOUNTED DUCTLESS

UNIT, MOUNTED WITH BOTTOM AT 6' 0" A.F.F. ROUTE

REFRIGERANT PIPING AND WIRING PER

MANUFACTURER'S RECOMMENDATIONS. ROUTE

DRAIN LINE DOWN ON WALL. ENCLOSE PIPING AND

WIRING IN METAL PIPE ENCLOSURE PAINTED TO

MATCH WALL. ROUTE DRAIN DOWN IN NEW WALL TO

SPILL ON GRADE AT APPROX. 18" ABOVE FINISHED

GRADE. PROVIDE REMOTE CONTROLLER FOR WALL

MOUNTING. CAREFULLY REMOVE PTAC UNIT IN THIS

ROOM COMPLETE INCLUDING WIRING, HARDWARE,

CONTROLS ETC. PROTECT UNIT AND TURN OVER TO

OWNER IN GOOD CONDITION.

13. CREATE ACCESS OPENINGS IN EXISTING CHASE AS

NEEDED TO ROUTE 12x12 EXHAUST UP TO REF-6 AND 10x10 DOWN TO FIRST FLOOR. ROUTE 10x10 THROUGH

CHASE AND PROVIDE TYPE "EGA" GRILLE BALANCED

TO 500 CFM. COORDINATE WITH WALL MOUNTED

EQUIPMENT.

14. WORK IN THIS SPACE TO BE COMPLETED UNDER

PHASE 1 WORK.

PLAN NOTES:# A

M501

UP TO REF-8

20x20

MUA-1

20x20

MUA-2

MUA-320x20

20x20 ROUTED

ABOVE ROOF

MUA-4

1 4

1 4

1 4

1 4

REF-10 5

REF-85

REF-7

REF-65

REF-115

ACCU-1 7

WORK IN PHASE 4

REF-9 5

REF-125

CONCENTRIC VENTS FOR NEW WATER HEATERS

TERMINATE WITH CONCENTRIC VENT CAPS PROVIDED

WITH EQUIPMENT. FLASH NEW ROOF PENETRATIONS

WEATHERTIGHT. WORK TO BE COMPLETED IN PHASE

4 TO MATCH INSTALLATION OF WATER HEATERS.

8 8

SOLAR/WIND COLLECTORS - RELOCATED BY GC.

RH-1

Ed inb ur gh

, In dia na

7 G atl ing S tre et

APRIL 16,

20039

Ca m p At te rb ur y J oin t M an eu ve r T ra ini ng C en te r (

CA

JM

TC

Re gio na l T ra ini ng

In sti tu te

B uil din g

Re no va tio n

Ph as e

M303

ROOF

MECHANICAL

PLANSCALE:

ROOF MECHANICAL PLAN

1/8" =1'-0"

1. ALL WORK MUST COMPLY WITH CURRENT MECHANICAL

CODE.

2. RIGID AND FLEXIBLE DUCTWORK FABRICATION SHALL

CONFORM TO THE LATEST EDITION OF SMACNA "HVAC

DUCT CONSTRUCTION STANDARDS - METAL AND

FLEXIBLE". MINIMUM ALLOWABLE SHEETMETAL GAUGE

SHALL BE 22 GAUGE.

3. DUCTWORK SHALL BE CONSTRUCTED, AT MIN., TO THE

FOLLOWING CLASSES:

a. SUPPLY: PRESSURE 0-4"WC, LEAK 12 VELOCITY 2000

FPM.

b. RETURN AND EXHAUST: PRESSURE -1" TO +1"WC, LEAK

24, VELOCITY 1500 FPM.

4. ALL SUPPLY DUCTWORK TO BE EXTERNALLY INSULATED,

UNLESS OTHERWISE NOTED. OUTDOOR DUCTWORK TO

HAVE DOUBLE LAYER OF CLOSED CELL ELASTOMERIC

INSULATION WITH BONDED ALUMINUM CLADDING.

5. ALL NEW AIR SYSTEMS TO BE TESTED, ADJUSTED AND

BALANCED BY LICENSED TAB AGENCY.

6. ALL EXPOSED DUCTWORK, TO BE PREPARED AND

PRIMED FOR PAINTING.

7. CONTRACTOR TO COORDINATE INSTALLATION OF NEW

WORK WITH ALL OTHER TRADES TO MAINTAIN PROPER

ACCESS AND CLEARANCES FOR SERVICE AND

MAINTENANCE.

8. PROPERLY SUSPEND ALL EQUIPMENT, DUCTWORK,

DIFFUSERS AND GRILLES, ETC. FROM STRUCTURE.

9. PROVIDE 3 SETS OF FILTERS FOR EACH RTU. 1 SET FOR

CONSTRUCTION, 1 SET FOR TAB AND 1 SET TO BE

INSTALLED AT SUBSTANTIAL COMPLETION OF PROJECT

PHASE.

10. BUILDING TO REMAIN OCCUPIED AND OPERATIONAL

DURING CONSTRUCTION. COORDINATE ALL

SHUTDOWNS AND OUTAGES WITH OWNER MIN. 10 DAYS

IN ADVANCE.

11. CONTRACTOR SHALL COMPLY WITH ALL SAFETY AND

SECURITY PROCEDURES AND PROTOCOLS AS

DESIGNATED BY THE OWNER.

12. REFER TO GENERAL NOTES ON DRAWING G101 FOR

ADDITIONAL INFORMATION.

GENERAL NOTES:

1. MAKEUP AIR UNIT ON 30" TALL INSULATED

PRESSURE CURB IF REQUIRED FOR SIDE

DISCHARGE. REFER TO ARCHITECTURAL

DRAWINGS FOR EXACT PLACEMENT AND

FLASHING DETAILS.

2. 20x20 SUPPLY DUCT ROUTED AT 24" ABOVE ROOF

DECK. SUPPORT MIN. 5' 0" O.C WITH SURFACE

MOUNTED DUCT SUPPORTS LIKE "MIRO

INDUSTRIES 6DS" TRANSITION AS REQUIRED TO

UNIT DISCHARGE OPENING.

3. 20x20 SUPPLY DUCT DOWN THROUGH NEW ROOF

CURB. REFER TO ARCHITECTURAL DRAWINGS

FOR FLASHING DETAILS.

4. POWER AND CONTROL WIRING TO BE ROUTED UP

INSIDE UNIT CURB. FOR ANY ROOF

PENETRATIONS OUTSIDE OF CURB, PROVIDE

PIPING PENETRATION CURB AND COLLAR.

5. NEW EXHAUST FAN ON NEW 14" TALL ROOF CURB.

REFER TO ARCHITECTURAL DRAWINGS FOR

FLASHING DETAILS.

6. CAP EXISTING EXHAUST FAN CURB WITH

INSULATED METAL CURB AND SEAL WEATHER

TIGHT. NEW ROOF PENETRATION MIN 15' 0" FROM

INTAKE OF MUA.

7. WORK IN PHASE 4. ACCU-1: HEAT PUMP

CONDENSING UNIT PROVIDED WITH FCU-2, AND

FCU-3. MOUNT ON EQUIPMENT RAILS ON NEW

ROOF OVER CONNECTOR ADDITION. COORDINATE

WITH NEW CONSTRUCTION. ROUTE WIRING,

REFRIGERANT PIPING, AND CONTROLS PER

MANUFACTURER'S RECOMMENDATIONS. ROUTE

EXPOSED PORTIONS IN METAL ENCLOSURE

FINISHED TO MATCH ADJACENT SURFACES.

8. ORIENT AIR INTAKE AWAY FROM EXHAUST FANS.

MAINTAIN MINIMUM 10' FROM EXHAUST FANS OR

PLUMBING VENTS.

PLAN NOTES:#

B M501

DAM DSJ

D M501

F M501

G M501

PTAC-1/PTAC-2

HARDWIRED CONNECTION

TO 265V 1PH POWER, SEE

ELECTRICAL DRAWINGS

WALL SLEEVE 13-3/4" DEEP

WITH INSULATION KIT

ALUMINUM

ARCHITECTURAL

GRILLE

EXTEND EXISTING

JUNCTION BOX, NEW WALL

FACE IN FUTURE PHASE,

SEE ELECTRICAL DRAWINGS

PROVIDE 30" TALL INSULATED

PRESSURE CURB IF REQUIRED FOR

SIDE DISCHARGEREFER TO "A"

SERIES DRAWINGS FOR FLASHING

REQUIREMENTS

ROOF DECK

18x28 SA

20x20 SA

DUCT ROOF SUPPORTS

LIKE "MIRRA" S6

2' -0

MUA

Ed inb ur gh

, In dia na

7 G atl ing S tre et

APRIL 16,

20039

Ca m p At te rb ur y J oin t M an eu ve r T ra ini ng C en te r (

CA

JM

TC

Re gio na l T ra ini ng

In sti tu te

B uil din g

Re no va tio n

Ph as e

M501

MECHANICAL

DETAILS

1. PROVIDE NEW WALL SLEEVE AND INSULATION KIT. SEAL

CASE TO WALL CONSTRUCTION PER MANUFACTURER

REQUIREMENTS.

2. PROVIDE EXTENDED DRAIN KIT WITH 3" HOSE

EXTENSION AND TURN-DOWN ELBOW.

3. PROVIDE TERMINAL STRIP FOR REMOTE THERMOSTAT

AND COVERPLATE FOR UNIT CONTROLS.

NOTES#

SCALE:

PTAC INSTALLATION SECTION

3/4" = 1'-0" A

INSULATED CURB

BY M.C.

NAILER BY M.C.

CURB COVER &

COUNTER FLASHING

BY M.C.

CANT BY G.C.

ROOFING BY G.C.

RUBBER CAP

FOR 2" TO 6"

SIZE LINES

RUBBER

BOOTS

STAINLESS STEEL

CLAMP FOR EACH BOOT

RUBBER CAP FOR

3/8" TO 2" SIZE

LINES

WEATHERTIGHT

SEAL

RUBBER

CURB COVER

CURB WITH

12"x12" I.D.

SCALE:

PIPE PENETRATION DETAIL

NONE

B

SECTION THRU CURB

DUCT PENETRATION THROUGH ROOF

RISER THROUGH ROOF

CONTINUOUS WELD

STORM COLLAR

SECURED TO DUCT

SECURE COUNTER

FLASHING

TO DUCT AND CAULK

2"X14" FRAME & NAILER

HOLE THROUGH ROOF

1" LARGER (BOTH

WAYS) THAN DUCTS

SEE PLAN FOR

DUCT CONTINUATION

ROOF LINE

FLEXIBLE SEALANT

HOT WATER FLUE

CONTINUOUS WELD

STAINLESS STEEL HOOD

WOOD NAILER

SQUARE CURB

BASE FLASHING

4"CANT STRIP

(IF REQUIRED)

ROOF DECK

PACKED INSULATION

SCALE:

ROOF PENETRATION DETAILS

NONE

C

SEE PLANS

FOR DUCT SIZE

PROVIDED HOLE

THROUGH ROOF

PRE-FAB CURB

FLASH AND

COUNTERFLASH

ALUMINUM

HOUSING

BACKDRAFT

DAMPER PROVIDED

WITH FAN

VERIFY ROOF

CONSTRUCTION

ALUMINUM

WIRE POST

BY UNIT

MANUFACTURER

1. MC SHALL VERIFY ACTUAL SIZES OF ROOF CURB, ROOF OPENING, AND

BACKDRAFT DAMPER FOR THE PARTICULAR FAN MANUFACTURER

SELECTED. COORDINATE THESE SIZES WITH ROOFING AND

STRUCTURAL CONTRACTORS.

2. FAN TO BE INSTALLED LEVEL.

3. DAMPER AND LINER ARE SAME SIZE (NOMINAL).

NOTES:

SCALE:

EXHAUST FAN INSTALLATION DETAIL

NONE

D

AIR FLOW

A

1/2" BALL VALVE & MANUAL AIR

VENT EXTENDED THROUGH INSULATION

OFFSET PIPE FOR COIL REMOVAL

BALL VALVE (TYP)

UNION (TYP)

P&T TAP (TYP)

STRAINER WITH BLOW DOWN

SUPPLY

RETURN

AUTOMATIC CONTROL VALVE

REDUCER AS REQUIRED (TYP)

CALIBRATED BALANCING VALVE

1/2" BALL VALVE MANUAL DRAIN

EXTENDED THROUGH INSULATION

FIRST UNION TO BE 12"

MINIMUM FROM HEADER

SCALE:

HYDRONIC COIL PIPING DIAGRAM - 2-WAY VALVE

NONE

E

DISCONNECT

BY UNIT

MANUFACTURER

SCALE:

EQUIPMENT ROOF SUPPORT DETAIL

NO SCALE

F

M

IN

0"

6" MIN

1/

2"

1. FOLLOW MANUFACTURERS RECOMMENDATIONS FOR

RIGGING, SUPPORT, AND INSTALLATION.

2. ARRANGE UNIT AND ACCESSORIES FOR MAINTENANCE

AND OPERATION CLEARANCE AND ACCESSIBILITY.

3. ORIENT UNIT TO MAINTAIN MIN. 10'-0" FROM ALL

EXHAUSTS, FLUES, PLUMBING VENTS ETC.

4. EXTEND ANY PLUMBING VENTS THAT ARE WITHIN 10' OF

INTAKE TO 10'-0" ABOVE ROOF. SUPPORT AT ROOF AND

STABILIZE WITH GUY WIRES.

5. ROUTE CONDENSATE DRAIN LINE(S) TO DIRECT

CONDENSATE TOWARDS ROOF DRAINS.

6. MOUNT REMOTE CONTROLS PANEL AT 5'-0" ABOVE

FINISHED FLOOR IN 2ND FLOOR MECHANICAL ROOM

BELOW UNIT.

NOTES#

SCALE:

ROOFTOP MUA INSTALLATION

None G

FLUE CAP FOR CONCENTRIC

VENT PROVIDED WITH DOMESTIC

WATER HEATERS - FOLLOW MANUFACTURER'S

RECOMMENDATIONS FOR INSTALLATION

ur gh

, In dia na

7 G atl ing S tre et

APRIL 16,

20039

Ca m p At te rb ur y J oin t M an eu ve r T ra ini ng C en te r (

CA

JM

TC

Re gio na l T ra ini ng

In sti tu te

B uil din g

Re no va tio n

Ph as e

M601

MECHANICAL

SCHEDULES

ur gh

, In dia na

7 G atl ing S tre et

APRIL 16,

20039

Ca m p At te rb ur y J oin t M an eu ve r T ra ini ng C en te r (

CA

JM

TC

Re gio na l T ra ini ng

In sti tu te

B uil din g

Re no va tio n

Ph as e

M701

HVAC

CONTROLS

DIAGRAMS

DAM DSJ

EA

SCALE:

GENERAL EXHAUST

NONE

ROOF

EF-1

MS CS BI-41

BO-41

1. GENERAL:

1.1. EXHAUST FAN SHALL BE CONTROLLED BY SPACE TEMPERATURE SENSOR.

1.1.1. ABOVE SETPOINT TEMPERATURE, FAN SHALL BE INDEXED ON.

1.1.2. WHERE SHOWN ON DRAWINGS, ASSOCIATED MOTORIZED DAMPER SHALL OPEN.

1.1.3. BELOW SETPOINT TEMPERATUER, FAN SHALL BE INDEXED OFF AND ASSOCIATED DAMPER (WHERE APPLICABLE

WILL CLOSE.

SEQUENCE OF OPERATIONS:

BINARY INPUT (BI)

BI: SPACE TEMPERATURE

BINARY OUTPUT (BO)

BO: MOTOR STARTER START/STOP

BDD

SEQUENCE OF OPERATIONS:

1. UNIT VENTILATOR TO HAVE INTERNAL CONTROLLER

WITH TERMINAL STRIP FOR REMOTE THERMOSTAT.

2. TERMINAL STRIP TO HAVE CAPABILITY FOR

OCCUPIED/UNOCCUPIED CONTROL, SETPOINT

CONTROL, OUTDOOR AIR DAMPER CONTROL,

STATUS AND ALARM OUTPUT.

3. INTERNAL CONTROLS TO MANAGE REVERSING

VALVE, REFRIGERANT CYCLE, AND FAN OPERATION.

SCALE:

PACKAGED TERMINAL AIR CONDITIONER/HEAT PUMP

NONE

EXTERIOR

WALL

PTAC

T

NEW LAY IN CEILING IN

CORRIDORS

NOTES

1. NEW WALL MOUNTED COMBINATION THERMOSTAT/HUMIDISTAT WITH CAPABILITY

FOR NETWORK CONNECTION TO NEW BAS. THERMOSTAT TO BE HARDWIRED TO

PTAC TERMINAL STRIP. BAS TO COMMUNICATE WITH PTAC THROUGH NETWORKED

THERMOSTAT TO CONTROL OCCUPIED/UNOCCUPIED MODE, SETPOINT ADJUSTMENT.

THERMOSTAT TO BE PROGRAMMABLE FOR LOCAL SETPOINT ADJUSTMENT WITHIN

OWNER SPECIFIED RANGE. THERMOSTAT TO REPORT TO BAS WITH UNIT STATUS,

SPACE TEMPERATURE AND HUMIDITY.

2. CONTROLS WIRING SHALL BE RUN FROM THERMOSTAT DOWN IN EXISTING STUD

WALL. ROUTE IN SURFACE MOUNTED RACEWAY AROUND TO PTAC UNIT. ROUTE

JUST ABOVE BASEBOARD AND COORDINATE WITH EXISTING SERVICES.

3. PROVIDE BLANKOFF PLATE FOR UNIT CONTROLS WITH LABEL STATING UNIT IS

CONTROLLED REMOTELY FROM THERMOSTAT.

TYPICAL

GUEST

ROOM

CORRIDOR

DDC POINTS LIST

TERMINAL STRIP

1. GENERAL:

1.1.1. EXHAUST FAN SHALL BE CONTROLLED BY A LINE VOLTAGE TIMER SWITCH - PROVIDED BY DIVISION 26.

1.1.2. EXHAUST FAN SHALL BE ON WHEN ACTIVATED BY TIMER SWITCH AND OFF AT END OF TIMER DURATION.

1.1.3. EXHAUST FAN CONTROLS ARE LOCAL AND ARE NOT TIED INTO BAS.

SEQUENCE OF OPERATIONS:

SCALE:

TOILET EXHAUST

NONE

BDD

CEILING EXHAUST FAN

TO BAS

ur gh

, In dia na

7 G atl ing S tre et

APRIL 16,

20039

Ca m p At te rb ur y J oin t M an eu ve r T ra ini ng C en te r (

CA

JM

TC

Re gio na l T ra ini ng

In sti tu te

B uil din g

Re no va tio n

Ph as e

P-FP001

PLUMBING & FIRE

PROTECTION

SYMBOLS,

ABBREVIATIONS, &

GENERAL NOTES

GENERAL SYMBOLS:

DEMOLITION NOTE

POINT OF REMOVAL

POINT OF CONNECTION

PLAN NOTE

NOTE: ALL SYMBOL DESCRIPTIONS ARE SUBJECT TO MODIFICATION ON THE DRAWINGS. ALL SYMBOLS NOT NECESSARILY USED ON THIS PROJECT.

PIPE ELBOW UP (RISER)

PIPE ELBOW DOWN

UNION

PIPE TEE DOWN

PIPE TURN 90°

CAP OR PLUG

REDUCER, CONCENTRIC

REDUCER, ECCENTRIC

FLANGES

LINE BREAK

STEAM TRAP

PRESSURE SENSOR

BALL VALVE

VALVES & FITTINGS:

GLOBE VALVE

GATE VALVE

BUTTERFLY VALVE

CHECK VALVE

REDUCED PRESSURE BACK FLOW PREVENTER

GAUGE

PLUMBING ABBREVIATIONS:

PIPE SLOPES IN DIRECTION OF ARROW

DOMESTIC HOT WATER RETURN

EXISTING PIPING TO REMAIN

EXISTING PIPING TO BE REMOVED

DOMESTIC COLD WATER

DOMESTIC HOT WATER

SANITARY VENT

INLINE PUMP

REVISION

THERMOMETER

PIPING DESIGNATIONS:

NEW PIPING

DETAIL BUBBLE

SECTION BUBBLE

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AHU AIR HANDLING UNIT

AD ACCESS DOOR

AV ACID VENT

AW ACID WASTE

BDD BACK DRAFT DAMPER

BHP BRAKE HORSEPOWER

BLDG BUILDING

BOD BOTTOM OF DUCT

BOP BOTTOM OF PIPE

BOS BOTTOM OF STEEL

BTU BRITISH THERMAL UNIT

CO CLEANOUT

CS CUP SINK

CSS CLINIC SERVICE SINK

CW DOMESTIC COLD WATER

D CONDENSATE/DRAIN

DB DRY BULB

DCV DOUBLE CHECK VALVE

DIA DIAMETER

DN DOWN

DWH DOMESTIC WATER HEATER

FD FLOOR DRAIN

ESEW EMERGENCY SHOWER AND FACE/EYE WASH

EW EMERGENCY EYE/FACE WASH

EL ELEVATION

ES EMERGENCY SHOWER

EXIST EXISTING

FCO FLOOR CLEANOUT

FLA FULL LOAD AMPS

HB HOSE BIBB

HKSP HOUSEKEEPING

HW DOMESTIC HOT WATER

HWR DOMESTIC HOT WATER RETURN

HWCP HOT WATER RECIRCULATION PUMP

IE INVERT ELEVATION

JS JANITOR SINK

LAV LAVATORY

MB MOP BASIN

NC NORMALLY CLOSED

NO NORMALLY OPEN

PIV POST INDICATING VALVE

PSIA POUNDS PER SQUARE INCH ABSOLUTE

PSIG POUNDS PER SQUARE INCH GAUGE

RO REVERSE OSMOSIS

RPBP REDUCED PRESSURE BACKFLOW PREVENTER

SAN SANITARY

SH SHOWER

SI SEDIMENT INTERCEPTOR

SK SINK

SS STAINLESS STEEL

ST STORM WATER

TD TRENCH DRAIN

V SANITARY VENT

VTR VENT THROUGH ROOF

W WASTE

WC WATER CLOSET

WH WALL HYDRANT

A M-501

T

P

DOMESTIC HOT WATER 140°F RETURN

DOMESTIC HOT WATER 140°F

140°F

140°F

STORM PIPINGST

INDIRECT DRAIND

ACID WASTEAW

ACID VENTAV

DEIONIZED WATERDE

DISTILLED WATERDI

REVERSE OSMOSIS DEIONIZED WATERRODI

LAWN SPRINKLERLS

GASG

FUEL OIL SUPPLYFOS

FUEL OIL RETURNFOR

FUEL OIL VENTFOV

VACUUMVAC

COMPRESSED AIRA

SURGICAL VACUUM

SPECIALTY PIPING

MEDICAL VACUUMMV

SV

LAB VACUUMVAC

NITROGENN

NITROUS OXIDEN2O

CARBON DIOXIDECO2

ARGONAG

MEDICAL AIRMA

LAB AIRA

PRE-ACTION

FIRE PROTECTION PIPING SYMBOLS

FIRE PROTECTIONF

PA

FIRE DRY PIPEFDP

FIRE DEPARTMENT SIAMESE CONNECTION (FREE STANDING)

FIRE DEPARTMENT SIAMESE CONNECTION (WALL MOUNTED)

METER

FLOOR DRAINFD

VALVE IN VERTICAL PIPE

CONTROL VALVE

INDICATED FLOW DIRECTION

FLOW SWITCH

ZONE CONTROL VALVE WITH TAMPER SWITCH

TS

PENDENT SPRINKLER HEAD

CONCEALED SPRINKLER HEAD

UPRIGHT SPRINKLER HEAD

SIDEWALL SPRINKLER HEAD

M

WASTE PIPINGW

GENERAL NOTES:

1. CONTRACTOR TO VERIFY EXISTING CONDITIONS PRIOR TO BID AND

INCLUDE ALL COSTS IN BID.

2. REVIEW THE WORK OF OTHER TRADES, COORDINATE AND PLAN

WORK WITH THE OTHER TRADES AND OWNER. ADJUST AS A

RESULT OF COORDINATION.

3. STORE EQUIPMENT AND COMPONENTS IN A CLEAN, DRY LOCATION

UNTIL READY FOR INSTALLATION. PROTECT FROM WEATHER, DIRT,

WATER, AND CONSTRUCTION DEBRIS, ETC. AT ALL TIMES. ANY

DAMAGED EQUIPMENT OR COMPONENTS SHALL BE RESTORED AS

NEW OR REPLACED.

4. ALL MATERIALS REMOVED AND NOT RELOCATED BECOME THE

PROPERTY OF THE CONTRACTOR. REMOVE MATERIALS FROM THE

PROJECT SITE UNLESS NOTED OTHERWISE.

5. PATCH WALLS, FLOORS, CEILINGS, COLUMNS, ROOF

PENETRATIONS, ETC. WHERE ITEMS ARE REMOVED TO MATCH

ADJACENT SURFACES.

6. DRAWINGS SHOW THE INTENDED ARRANGEMENT AND ROUTING OF

ALL PIPING, EQUIPMENT, AND APPURTENANCES. THEY SHALL BE

FOLLOWED AS CLOSELY AS ACTUAL BUILDING CONSTRUCTION

AND WORK OF OTHER TRADES WILL PERMIT.

7. CLEAN ALL EQUIPMENT TO PRESENT A "LIKE NEW" CONDITION AT

PROJECT COMPLETION.

8. OFFSET PIPING AROUND ELECTRICAL PANELS TO PROVIDE

CLEARANCES AS REQUIRED BY THE NATIONAL ELECTRICAL CODE.

9. CONTRACTOR SHALL INCLUDE IN BID ALL CUTTING AND PATCHING

REQUIRED FOR INSTALLATION OF NEW WORK. CONCRETE WORK

TO BE PERFORMED BY THE GC AND PAID FOR BY THE

PLUMBING/MECHANICAL CONTRACTOR.

10. PIPING SHOWN IS FOR REFERENCE ONLY, CONTRACTOR SHALL

FIELD VERIFY ALL EXISTING PIPE LOCATIONS, ROUTING, SIZES AND

ETC.

11. CONTRACTOR SHALL MAKE REPAIRS TO SPRAY-ON FIRE PROOFING

AFTER MAKING HANGER ATTACHMENTS TO BUILDING STRUCTURE.

12. WORK IS TO BE PERFORMED IN PHASES SEE ARCHITECTURAL

DRAWINGS FOR PHASING OF WORK.

1. SYSTEM DESIGN IS PER NFPA 13, STANDARD FOR THE

INSTALLATION OF SPRINKLER SYSTEMS.

2. ALL WORK AND MATERIALS SHALL CONFORM TO NFPA 13, AND

STATE RULES AND REGULATIONS.

3. ALL MATERIALS, WHERE APPLICABLE SHALL BE U.L. LISTED AND

FACTORY MUTUAL APPROVED FOR THE USE IN AUTOMATIC

SPRINKLER SYSTEMS.

4. PROVIDE A MINIMUM OF 72 HOUR NOTICE TO THE OWNER PRIOR

TO SPRINKLER PIPE TESTING OR LINE PRESSURIZATION.

5. FIRE PROTECTION CONTRACTOR SHALL PREPARE ALL DRAWINGS

AND APPLICATIONS REQUIRED TO OBTAIN APPROVAL OF THE

SYSTEM BY OWNERS INSURANCE UNDERWRITER, STATE AND

LOCAL AUTHORITIES HAVING JURISDICTION. ALL DRAWINGS TO BE

SUBMITTED DURING CONSTRUCTION.

6. FIRE PROTECTION CONTRACTOR SHALL SUBMIT DRAWINGS WITH

ALL SPRINKLER HEAD LOCATIONS. ALL SPRINKLER HEADS TO BE

LAID OUT NEATLY WITHIN THE CEILING SYSTEMS AND BE

COORDINATED WITH ALL BULKHEADS, CEILINGS AND STRUCTURE.

7. CONTRACTOR TO VERIFY EXISTING CONDITION PRIOR TO BID.

8. REVIEW WORK OF OTHER TRADES, COORDINATE AND PLAN WORK

WITH THE OTHER TRADES AND OWNER. ADJUST AS A RESULT OF

COORDINATION.

9. STORE EQUIPMENT AND COMPONENTS IN A CLEAN, DRY LOCATION

UNTIL READY FOR INSTALLATION. PROTECT FROM WEATHER, DIRT,

WATER AND CONSTRUCTION DEBRIS, ETC. AT ALL TIMES. ANY

DAMAGED EQUIPMENT OR COMPONENTS SHALL BE RESTORED AS

NEW OR REPLACED.

10. ALL MATERIALS REMOVED AND NOT RELOCATED BECOME THE

PROPERTY OF THE CONTRACTOR. REMOVE MATERIALS FROM THE

PROJECT SITE UNLESS NOTED OTHERWISE.

11. DRAWINGS SHOW THE INTENDED ARRANGEMENT AND ROUTING OF

ALL PIPING AND EQUIPMENT. THEY SHALL BE FOLLOWED AS

CLOSELY AS ACTUAL BUILDING CONSTRUCTION AND WORK OF

OTHER TRADES WILL PERMIT.

12. OFFSET PIPING AROUND ELECTRICAL PANELS TO PROVIDE

CLEARANCES AS REQUIRED BY THE NATIONAL ELECTRICAL CODE.

13. CONTRACTOR SHALL INCLUDE IN BID ALL CUTTING AND PATCHING

REQUIRED FOR INSTALLATION OF NEW WORK.

14. PIPING SHOWN IS FOR REFERENCE ONLY, CONTRACTOR SHALL

FIELD VERIFY ALL EXISTING PIPE LOCATIONS, ROUTING, SIZES AND

ETC.

15. WORK IS TO BE PERFORMED IN PHASES SEE ARCHITECTURAL

DRAWINGS FOR PHASING OF WORK.

16. REFER TO GENERAL NOTES ON DRAWING G101 FOR ADDITIONAL

INFORMATION.

17. REFER TO "SELECTIVE DEMOLITION" SPECIFICATION FOR

ADDITIONAL INFORMATION INCLUDING DISPOSAL AND RECYCLING.

FIRE PROTECTION GENERAL NOTES:

GENERAL USE COLD WATERGCW

GENERAL USE HOT WATERGHW

NON POTABLE WATERNP

DEIONIZED WATERDIW

EFD EXISTING FLOOR DRAIN

ECO EXISTING CLEAN OUT

1. REPLACE ALL SPRINKLER HEADS THROUGH OUT THE ENTIRE BUILDING.

2. MOVE SPRINKLER HEAD LOCATIONS IN CORRIDORS AND COMMONS AREAS AND ALL

DEFINED WORK AREAS TO AVOID CONFLICT WITH NEW CEILING GRID. PHASE I

3. ADJUST HEADS IN CORRIDOR AND COMMONS AREAS TO FINAL CEILING HEIGHT.

PHASE I

4. ADD SPRINKLERS TO THE ADA ENTRY CONNECTOR CORRIDOR. PHASE I

5. INSPECT THE ENTIRE SPRINKLER SYSTEM INCLUDING PRESSURE TESTING, MAKE

NECESSARY REPAIRS AND RECERTIFY THE…