About this file

This is a comprehensive set of electrical construction drawings and specifications for a renovation project at a VA Des Moines facility involving multiple buildings (Buildings 1, 1W, 12, and 25) and steam/utility tunnels. The project includes new electrical systems for an approximately 60,000+ square foot area with resident rooms, medical facilities, kitchens, and support spaces.

The scope encompasses complete electrical infrastructure including power distribution from transformers (15KV primary loop systems with redundancy), panelboards rated from 60A to 400A, lighting systems with occupancy sensors and dimmers, emergency/exit lighting, fire alarm systems with multiple zones and loops, nurse call systems, access control and door operator systems, telecom infrastructure with data outlets and fiber optic cables, voice/data cabling with cable trays, security camera systems, and medical equipment connections. Specific equipment includes HVAC units, pumps, compressors, fans, domestic hot water systems, split system cooling units, and various receptacles rated for 120V to 480V service. The designs mandate dual-technology occupancy sensors, manual-on/automatic-off lighting control, all conduit minimum 3/4" diameter, plenum-rated cables, fire-rated wall penetration sealing, and coordination with mechanical systems and phasing plans. Construction documents reference panelboard schedules (EP601/EP602), luminaire schedules (EL601), architectural reflected ceiling plans, and require contractor verification of existing conditions, circuit information, and proper restoration of surfaces affected by demolition work, with the owner retaining rights to salvageable materials and contractor responsible for PCB ballast and hazardous lamp removal.

View the file

Other files

File Type Posted
36C26326R0059 0003.docx DOCX document
36C26326R0059 0002.docx DOCX document
Final PWS_636A-26-201.docx DOCX document
36C26326R0059 0001.docx DOCX document
Phase 1 Question and Answers.docx DOCX document
36C26326R0059.docx DOCX document
Bldg 1 Full Set_Part4.pdf PDF
Bldg 12 Full Set_Part1.pdf PDF
Bldg 12 Full Set_Part2.pdf PDF
Bldg 12 Full Set_Part5.pdf PDF
Bldg 25 HVAC.pdf PDF
Copy of Ceiling Lifts Replacements and Additions-CI.pdf PDF
Letter of Commitment Key Subcontractors.pdf PDF
Bldg 1 Full Set_Part1.pdf PDF
Bldg 1 Full Set_Part5.pdf PDF
Bldg 12 Full Set_Part4.pdf PDF
Bldg 12 Full Set_Part6.pdf PDF
Bldg 25 Architectural 1.pdf PDF
Equipment Compliance Matrix.pdf PDF
Installation Relocation Checklist.pdf PDF
Specifications 636A626201.pdf PDF
Wage Determination IA20250071 05.18.2026.pdf PDF
Key Personnel Resume Form.pdf PDF
Bldg 1 Full Set_Part2.pdf PDF
Bldg 1 Full Set_Part3.pdf PDF
Bldg 1 Full Set_Part6.pdf PDF
Bldg 1 W Full Set.pdf PDF
Bldg 4 Full Set.pdf PDF
Bldg 12 Full Set_Part7.pdf PDF
Bldg 12 Full Set_Part8.pdf PDF
Bldg 25 Architectural 2.pdf PDF
Bldg 25 Plumbing.pdf PDF
Bldg 25 Structural Drawings.pdf PDF
Directive 1611.pdf PDF
ICRA Table.docx DOCX document
PPQ Form.pdf PDF
Letter of Commitment for Design Firm Teaming Arrangement.pdf PDF
VAAR 852.219-75 LoS.docx DOCX document
Bldg 12 Full Set_Part3.pdf PDF
Bldg 25 Medical Gas.pdf PDF
Preventative Maintenance Checklist.pdf PDF
Letter of Commitment for Key Personnel.pdf PDF
Show all 42

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

A. SEE ARCHITECTURAL SHEETS FOR EXACT AREAS AND WALLS

AFFECTED BY THE DEMOLITION AND REMODEL.

B. DEMOLITION SHOWN IS AS REQUIRED FOR THE COMPLETE PROJECT.

THE CONTRACTOR SHALL COORDINATE THE DEMOLITION EFFORT PER

THE PHASING PLANS. COORDINATE DEMOLITION WITH THE WORK OF

OTHER TRADES. PROVIDE TEMPORARY POWER AND LIGHTS AS

REQUIRED TO ALLOW THE WORK OF OTHER TRADES TO PROCEED OR

AS REQUIRED TO ALLOW THE OWNER TO OCCUPY THE SPACE.

C. ALL OF THE EQUIPMENT AND DEVICES SHOWN ON THIS DRAWING ARE

EXISTING. THE LOCATIONS OF THE EQUIPMENT AND DEVICES WERE

OBTAINED FROM EXISTING DRAWING AND FIELD INVESTIGATION. THE

LOCATIONS OF THE EXISTING EQUIPMENT AND DEVICES ARE SHOWN

FOR THE CONVENIENCE OF THE CONTRACTOR. ACCURACY OF THE

INFORMATION SHOWN IS NOT GUARANTEED. THE CONTRACTOR IS

RESPONSIBLE FOR THE VERIFICATIONS OF ALL EXISTING CONDITIONS

PRIOR TO SUBMITTING BIDS. SITE VISITS PRIOR TO SUBMISSION OF

BIDS NEED TO BE FULLY COORDINATED WITH THE OWNER.

D. CIRCUIT INFORMATION FOR ALL AFFECTED CIRCUITS SHALL BE

VERIFIED PRIOR TO COMMENCING WORK. ACCURACY OF THE

INFORMATION SHOWN AND INCLUDED ON THE PANEL SCHEDULES IS

NOT GUARANTEED.

E. LUMINAIRES AND DEVICES INDICATED TO BE REMOVED, WHICH ARE

LOCATED ON CEILINGS OR WALLS, SHALL HAVE LUMINAIRES, DEVICE

AND ALL ASSOCIATED CIRCUIT WIRING AND CONDUIT REMOVED BACK

TO NEAREST JUNCTION BOX, OR DEVICE NOT INDICATED TO BE

REMOVED. ACTUAL CIRCUITING MUST BE DETERMINED IN THE FIELD.

THE CONTRACTOR SHALL PROVIDE ALL NECESSARY WIRE, CONDUIT,

DEVICES AND CONNECTIONS NECESSARY TO ENSURE CIRCUIT

CONTINUITY OF THE REMAINING DEVICES.

F. THE OWNER HAS THE RIGHT TO RETAIN ALL SALVAGEABLE MATERIAL.

ANY MATERIAL THE OWNER CHOOSES NOT TO ACCEPT SHALL BE

REMOVED FROM THE SITE AND PROPERLY DISPOSED OF BY THE

CONTRACTOR. CONTRACTOR IS RESPONSIBLE FOR THE REMOVAL OF

ANY PCB BALLAST OR HAZARDOUS LAMPS.

G. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE

LABELING OF SPARE OR ABANDONED CIRCUITS AND/OR CIRCUIT

BREAKERS IN ALL PANELS AFFECTED BY THE DEMOLITION. SPARE

CIRCUITS AND/OR CIRCUIT BREAKERS MAY BE REUSED FOR THE

CIRCUITING OF THE NEW OR REMODELED AREA AS SPACE AND PANEL

LOADING WILL ALLOW.

H. THE CONTRACTOR SHALL BE HELD FULLY RESPONSIBLE FOR THE

PROPER RESTORATION OF ALL EXISTING SURFACES REQUIRING

PATCHING, PLASTERING, PAINTING AND/OR OTHER REPAIR DUE TO

THE DEMOLITION WORK DONE BY THE ELECTRICAL CONTRACTOR,

UNDER THE TERMS OF THIS SPECIFICATION. CLOSE AND SEAL ALL

OPENINGS, REPAIR ALL SURFACES, ETC., AS REQUIRED.

I. SEE PHASING PLAN.

J. EXISTING FIRE ALARM DEVICES, EMERGENCY LIGHTS AND EXIT SIGNS

SHALL BE COMPLETE AND OPERABLE AT ALL TIMES. PROVIDE

TEMPORARY DEVICES IN AREAS BEING WORKED ON TO ALLOW FOR A

WORKABLE SYSTEM DURING CONSTRUCTION.

K. PROTECT EXISTING FURNITURE, CARPET AND OTHER

APPURTENANCES FROM DAMAGE DURING THE COURSE OF

CONSTRUCTION. REPLACE DAMAGED ITEMS FREE OF COST TO THE

OWNER.

L. ITEMS WHICH ARE INTENDED TO BE REMOVED, RELOCATED, OR

SALVAGED ARE SHOWN AS FULL-TONE LINES ON DEMO PLANS. ALL

OTHER ITEMS ARE INTENDED TO REMAIN IN PLACE AND ARE SHOWN

AS HALF-TONE.

A. COORDINATE LOCATION OF SWITCH HEIGHTS WITH CASEWORK,

FURNITURE AND EQUIPMENT LAYOUTS PRIOR TO ROUGH-IN. SEE

ARCHITECTURAL CASEWORK ELEVATIONS FOR CABINET HEIGHTS

AND LAYOUTS.

B. ALL OCCUPANCY SENSORS AND OCCUPANCY SENSOR SWITCHES

SHALL BE DUAL TECHNOLOGY (INFRARED AND ULTRASONIC).

OCCUPANCY SENSORS DO NOT SHOW RELAYS AND TOTAL WIRING

REQUIRED FOR PROPER OPERATION. PROVIDE A COMPLETE AND

FULLY FUNCTIONAL SYSTEM.

C. EMERGENCY, EXIT, AND NIGHT LIGHTS IN PATHS OF EGRESS SHALL

BE CONNECTED TO AN UNSWITCHED HOT LEG OF CIRCUIT SHOWN

UNLESS NOTED OTHERWISE.

D. ALL AREAS SHALL BE MANUAL-ON / AUTOMATIC-OFF UNLESS NOTED

OTHERWISE. AUTOMATIC-ON / AUTOMATIC-OFF PERMITTED IN

BATHROOMS AND SECURITY AREAS.

A. ALL DEVICES SHOWN SHALL BE MOUNTED AT 18" A.F.F. UNLESS

INDICATED OTHERWISE.

B. EACH LOW VOLTAGE CABLE SHALL HAVE INDIVIDUAL RUN BACK TO

TERMINATION POINT IN IT CLOSET. LEAVE 10' SERVICE DROP FOR

EACH HOMERUN.

C. ALL AUXILIARY CABLE ABOVE CEILING SHALL BE PLENUM RATED

WHERE REQUIRED.

D. CEILING MOUNTED DEVICES SHALL BE CENTERED IN CEILING TILE

WHERE INSTALLED IN ACOUSTICAL TILE CEILING.

E. PROVIDE 120 VOLT POWER CIRCUIT(S) FOR AUXILIARY SYSTEMS AS

REQUIRED FOR COMPLETE AND OPERATIONAL SYSTEMS.

A. DRAWINGS DO NOT SHOW TOTAL NUMBER OF CONDUCTORS FOR

CIRCUITS REQUIRED. PROVIDE THE NUMBER OF CONDUCTORS

NEEDED TO COMPLETE INSTALLATION OF SPECIFIC EQUIPMENT

FURNISHED. A GREEN GROUND CONDUCTOR, SIZED PER NEC, SHALL

ALSO BE INCLUDED IN EACH CIRCUIT. ADJUST CONDUCTOR SIZES AS

NEEDED TO LIMIT VOLTAGE DROP TO LEVELS RECOMMENDED BY

NEC. THE CONTRACTOR SHALL ALSO COORDINATE INSPECTIONS

WITH THE AHJ.

B. SEE SHEET EL601 FOR LUMINAIRE SCHEDULE.

C. SEE SHEETS EP601 & EP602 FOR PANELBOARD SCHEDULES.

D. SEE ARCHITECTURAL SHEETS FOR REFLECTED CEILING PLANS.

E. NO BOXES SHALL BE MOUNTED BACK-TO-BACK.

F. CONTRACTOR TO SEAL ALL PENETRATIONS THROUGH FIRE OR

FIRE/SMOKE RATED WALLS AND FLOORS.

G. ALL RACEWAYS SHALL BE SEALED AS REQUIRED BY AND IN

ACCORDANCE WITH NEC AND NFPA.

H. CABLE AND CONDUIT SHALL NOT INTERFERE WITH EQUIPMENT

ACCESS.

I. ALL CABLING ABOVE CEILING SHALL BE PROPERLY SUPPORTED (NOT

FROM CEILING SYSTEM).

J. IN VIEWING THESE DRAWINGS, THE CONTRACTOR SHALL PAY CLOSE

ATTENTION TO THE MATCH LINES. SOME WORK AND NOTE

REFERENCES MAY BE REPEATED, BUT DO NOT ALWAYS SHOW ON

BOTH SIDES OF THE MATCH LINE.

K. CONTRACTOR SHALL COORDINATE FINAL PANEL DIRECTORIES WITH

OWNER.

L. COORDINATE ALL TUNNEL WORK WITH VA COR.

A. ALL ELECTRICAL CONDUITS SHALL BE A MINIMUM OF 3/4" DIAMETER.

B. SIGNAL CABLES SHALL BE ROUTED IN CABLE TRAY OR CONDUITS,

MINIMUM OF 3/4" DIAMETER.

C. ALL ELECTRICAL DISTRIBUTION PANELS SHALL BE LABELED WITH

RESPECTIVE POWER SOURCE INFORMATION (CIRCUIT FEEDING IT).

ARC FLASH LABELS SHALL BE ADDED TO COMPLY WITH CODE

REQUIREMENTS AND ARC FLASH STUDY.

D. LABEL THE COVER PLATES OF ALL ELECTRICAL RECEPTACLES BOTH

INSIDE AND OUTSIDE WITH RESPECTIVE CIRCUIT NUMBER.

E. ALL FIRE ALARM HORNS AND STROBES SHALL BE RED IN COLOR AND

BE WALL-MOUNTED.

F. NEW EQUIPMENT SHALL BE ASSESSED FOR LOCKOUT-TAGOUT

REQUIREMENTS, AND HAVE A PROCEDURE WRITTEN AND ADDED TO

THE VA CENTRAL IOWA LOTO DATABASE.

G. THESE STANDARDS SHALL BE USED IN TANDEM WITH DRAWINGS AND

SPECIFICATIONS. WHERE CONFLICTS OCCUR, LOCAL STANDARDS

SHALL TAKE PRIORITY.

Drawing Title

Approved:

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management

6"

6"

6" 6"

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

TSA PROJECT

NO.:

Department of Veterans Affairs

CONSTRUCT CLC

COTTAGES - COTTAGE 1

636-123

3600 30TH ST. DES MOINES, IA

4/13/2018

ELECTRICAL INFO SHEET

BTF MTB

E000

80 97 06054.032

D1 SECURITY CAMERA TO BE REMOVED AND STORED FOR

RE-INSTALLATION; EXISTING WIRING TO BE PRESERVED.

D2 MANUAL PULL STATION TO BE REMOVED AND STORED FOR

RE-INSTALLATION; EXISTING WIRING TO BE PRESERVED.

D3 PA HORN TO BE REMOVED AND STORED FOR RE-INSTALLATION;

EXISTING WIRING TO BE PRESERVED.

D4 SPEAKER TO BE REMOVED AND STORED FOR RE-INSTALLATION;

EXISTING WIRING TO BE PRESERVED.

D5 SMOKE DETECTOR TO BE REMOVED AND STORED FOR

RE-INSTALLATION; EXISTING WIRING TO BE PRESERVED.

D7 STAIRWELL LIGHTING (INTERIOR / EXTERIOR) TO BE REMOVED

AND STORED FOR RE-INSTALLATION; EXISTING WIRING TO BE

PRESERVED.

D8 REMOVE BACK-TO-BACK CABINET UNIT HEATERS AND DEMO ONE

CIRCUIT BACK TO PNL R1C-G-1; OTHER CIRCUIT WIRING TO BE

PRESERVED.

D9 ABANDONED EQUIPMENT; COORDINATE WITH OWNER PRIOR TO

DEMO AND RETURN TO OWNER.

L1 LOCATE REFLECTOR TO MAXIMIZE LIGHT AT MED CABINET.

L2 PROVIDE PHOTOCELL FOR CONTROL OF CANOPY LIGHTING.

L3 PROVIDE 8-BUTTON OVERRIDE SWITCH FOR CONTROL OF ALL LCP

RELAYS.

L4 PROVIDE 2-BUTTON OVERRIDE SWITCH FOR CONTROL OF

CORRIDOR LIGHTING.

L5 LOCATE SWITCH NEAR TUNNEL ENTRANCE (VERIFY).

L6 INDICATES CIRCUITS SERVING RESIDENT ROOM.

L7 EXISTING STAIRWELL LIGHTING (INTERIOR / EXTERIOR) TO BE

RE-INSTALLED; CONNECT TO EXISTING WIRING.

L8 CONNECT LIGHTING IN CORRIDOR TO EXISTING LIFE SAFETY /

NORMAL CIRCUITS (VERIFY).

L9 SHIFT LIGHTING AS REQUIRED TO AVOID CONFLICTS WITH HVAC

DUCTWORK, PIPING, ETC.

P1 INDICATES CIRCUITS SERVING RESIDENT ROOM.

P2 PROVIDE CONTROL WIRING AS REQUIRED FROM BLDG 25

AUTOMATIC TRANSFER SWITCHES TO GENERATOR MASTER

CONTROL LOCATED IN BUILDING 1W.

P3 CONNECT DOOR OPERATOR TO PNL R1S-G-1 (LIFE SAFETY).

P4 TO CONTRACTOR STAGING AREA. CONTRACTOR SHALL PROVIDE

STEP-DOWN TRANSFORMERS, DISCONNECTS, ETC. AS REQUIRED.

P5 TEMPORARY POWER LOCATION. CONTRACTOR SHALL PROVIDE

BREAKER AS REQUIRED.

P6 PROVIDE 250A BREAKER IN EMERGENCY SWITCHBOARD FOR

SERVING BUILDING 25.

P7 PROVIDE CONNECTIONS AS REQUIRED TO ADD BUILDING 25

AUTOMATIC TRANSFER SWITCHES.

P8 PROVIDE ELECTRIC POWER QUALITY MONITORING METER

COMPLETE WITH MAIN DISPLAY AND (3) FEEDER DISPLAYS (ONE

FOR EACH TRANSFER SWITCH FEEDER). MAIN DISPLAY SHALL BE

CAPABLE OF MONITORING AND DISPLAYING TOTAL BUILDING

LOAD AS WELL AS SUMMATION OF (3) FEEDERS. PROVIDE CTS,

CONTROL WIRING, ETC. AS REQUIRED FOR CONTROL SCHEME.

P9 PROVIDE L5-30R LOCKING RECEPTACLE AND MOUNT TO BOTTOM

OF CABLE TRAY. (TYP. 2)

P10 .CONNECT CABINET UNIT HEATER TO EXISTING WIRING.

P11 MEDIUM VOLTAGE CABLES BETWEEN XFMR 11 AND XFMR 12 TO

BE RE-USED AND CONNECTED BETWEEN XFMR 25 AND XFMR 12.

Y1 EXISTING SECURITY CAMERA TO BE RE-INSTALLED; CONNECT TO

EXISTING WIRING.

Y2 EXISTING MANUAL PULL STATION TO BE RE-INSTALLED; CONNECT

TO EXISTING WIRING.

Y3 EXISTING PA HORN TO BE RE-INSTALLED; CONNECT TO EXISTING

WIRING.

Y4 EXISTING SPEAKER TO BE RE-INSTALLED; CONNECT TO EXISTING

WIRING.

Y5 EXISTING SMOKE DETECTOR TO BE RE-INSTALLED; CONNECT TO

EXISTING WIRING.

Y6 PROVIDE ACCESS CONTROL PER ROUGH-IN DETAIL; CONNECT TO

EXISTING WIRING. PROVIDE ADDITIONAL WIRING, MODULES, ETC.

AS REQUIRED TO CONNECT TO EXISTING CONTROL PANELS

LOCATED IN BUILDING 12 BASEMENT IT CLOSET.

Y7 PROVIDE SMOKE DETECTOR AS REQUIRED AND CONNECT TO

BUILDING 12 FIRE ALARM SYSTEM; MATCH EXISTING.

Y8 CONTRACTOR SHALL VISIT SITE PRIOR TO BID TO LOCATE FINAL

TERMINATION LOCATIONS OF SPECIALTY SYSTEMS IN THIS

SPACE.

Y9 PROVIDE CONNECTIONS AS REQUIRED TO EXTEND CAMPUS FIRE

ALARM LOOP TO BUILDING 25.

Y10 EXTEND EXISTING CABLE TRAY AS SHOWN.

Y11 PROVIDE (2) GANGED EZ PATH SERIES 44 PATHWAYS AT ALL

DOOR CROSSINGS AND ENTRANCES INTO IT ROOMS.

Y12 PROVIDE DUCT DETECTOR AND ACCESSORIES AS REQUIRED TO

SHUTDOWN HVAC EQUIPMENT 2000 CFM OR GREATER PER NFPA

AND AHJ.

E000 ELECTRICAL INFO SHEET

EC001 SITE PLAN - DEMOLITION

EC101 SITE PLAN - ELECTRICAL

EC102 BASEMENT FLOOR PLAN - BUILDINGS 2, 1W, & 1 + STEAM TUNNEL - COMPOSITE

EC103 BASEMENT FLOOR PLAN - BUILDING 12 + STEAM TUNNEL- COMPOSITE

EC104 FIRST FLOOR PLAN - BUILDINGS 25 AND 12 - COMPOSITE

EL101 FLOOR PLANS & TUNNEL - LIGHTING

EL601 SCHEDULES AND DIAGRAMS - LIGHTING

EP101 FLOOR PLANS & TUNNEL - POWER

EP501 DETAILS - POWER

EP601 SCHEDULES AND DIAGRAMS - NORMAL PANEL SCHEDULES

EP602 SCHEDULES AND DIAGRAMS - EMERGENCY PANEL SCHEDULES

EP603 SCHEDULES AND DIAGRAMS - POWER

EY101 FLOOR PLANS - AUXILIARY SYSTEMS

EY102 ROOF PLAN - LIGHTNING PROTECTION

EY501 DETAILS - AUXILIARY SYSTEMS

EY601 SCHEDULES AND DIAGRAMS - AUXILIARY SYSTEMS

EY602 SCHEDULES AND DIAGRAMS - AUXILIARY SYSTEMS

S

TRUE

NORTH

PLAN

NORTH

NORTH

NORTH

ARROW

SYMBOL LEGEND

MATCHLINE

AREA A

AREA B

EXISTING

COLUMN

NEW

COLUMN

X

X

X

SIM

X

XX-XX

XXXX

DX

X

SECTION/

DETAIL

PLAN

DETAIL

REFERENCE

NOTE

REFERENCE

DEMOLITION

NOTE

EQUIPMENT

NUMBER

ROOM NAME

150 SF

ROOM

NUMBER

LETTER

INDICATES NEW

COLUMN LINE

LETTER INDICATES

EXISTING COLUMN

LINE

SECTION/DETAIL NUMBER

SHEET NUMBER

INDICATES DIRECTION OF VIEW

DETAIL NUMBER

SHEET NUMBER

REFERENCE

DESIGNATION

DEMOLITION

DESIGNATION

EQUIPMENT

NUMBER

ROOM NAME DESIGNATION

ROOM NUMBER DESIGNATION

ROOM AREA DESIGNATION

REFERENCE LEGEND

NAME

ELEVATIONLEVEL

TITLE

MARKER

VIEW NAME

SCALE: 1/8" = 1'-

0"

DETAIL NUMBER

LEVEL CALLOUT

DESIGNATION

ELEVATION

DESIGNATION

GRAPHIC AREA FOR

DRAWING

TITLE

SCALE OF THE DRAWING

REF. DEMO NOTES ( )

ELECTRICAL SHEET LIST

PROJECT ELECTRICAL REFERENCED DEMOLITION NOTES

GENERAL NOTES XDXGENERAL DEMO NOTESABBREVIATIONS REF. NOTES ( )

PROJECT ELECTRICAL REFERENCED NOTES

GENERAL LIGHTING NOTES

GEN. POWER & AUX SYSTEMS NOTES

XX-XX

PC

J

J

OS

MS

IC

S

S

M

N

TV

VC

N EA

N SA/CB

N

N 37

N E

G

K1

V

A

R

M

M

T

WALL MOUNTED STRIP LUMINAIRE

SYMBOL NOTES:

PHOTOCELL

VOICE AND DATA

JUNCTION BOX - CEILING MOUNT

JUNCTION BOX - WALL MOUNT

VOICE OUTLET

DATA OUTLET

OCCUPANCY SENSOR

MOTION SENSOR

CEILING FAN

POLE MOUNTED SITE LUMINAIRE

FLOOD LIGHT

NURSE CALL

SPEAKER

PATIENT STATION

INTERCOM SPEAKER STATION

VOLUME CONTROL STATION

MICROPHONE JACK

TELEVISION OUTLET

CCTV CAMERA

SOUND, TELEVISION, AND SECURITY

FUSE

EMERGENCY STATION W/ AUDIO

DISCONNECT SWITCH

2-BUTTON STATION

37 PIN BED RECEPTACLE

DOME LIGHT

MASTER STATION

EMERGENCY GENERATOR

POWER DISTRIBUTION ONE LINE

CONDUIT UP

CONDUIT DOWN

INDICATES BUSHED CONDUIT

VOICE/DATA OUTLET

EMERGENCY STATION

DRAW OUT VACUUM CIRCUIT BREAKER

LIGHTNING SURGE ARRESTOR

THERMAL OVERLOAD RELAY

PLUG-IN OR DRAWOUT CONNECTOR

CIRCUIT BREAKER

FUSED DISCONNECT SWITCH

VOLTMETER

AMMETER

X:Y CURRENT TRANSFORMER - (RATIO)

KIRK KEY INTERLOCK

"C" INDICATES CEILING MOUNTED

"F" INDICATES FLOOR MOUNTED

"S" INDICATES SURFACE MOUNTED

"G" INDICATES GROUND FAULT INTERRUPTING

"IG" INDICATES ISOLATED GROUND

"AC" INDICATES MOUNTING 6" ABOVE COUNTERTOP OR

BACKSPLASH

"WP" INDICATES WEATHERPROOF

"XP" INDICATES EXPLOSION PROOF

"R" INDICATES EXISTING DEVICE REMOVED AND

RELOCATED

LOWER CASE LETTER BY SWITCHES AND FIXTURES

INDICATE ASSOCIATED UNIT FOR SWITCHING

LIGHTING

LUMINAIRE

WALL MOUNTED LUMINAIRE

RECESSED LUMINAIRE

WALL MOUNTED LUMINAIRE

SURFACE MOUNTED LUMINAIRE

TRACK LIGHTING

DIMMER SWITCH

TIMER SWITCH

WIRING DEVICES - SWITCHES

SINGLE POLE SWITCH

KEY OPERATED SWITCH

SINGLE POLE SWITCH WITH PILOT

THERMAL ELEMENT SWITCH

FOUR-WAY SWITCH

TWO POLE SWITCH

THREE-WAY SWITCH

STRIP / INDUSTRIAL LUMINAIRE

LUMINAIRE - NIGHT LIGHT

LUMINAIRE - EMERGENCY SYSTEM

EMERGENCY BATTERY PACK LUMINAIRE

REMOTE EMERGENCY HEAD

WALL WASH LUMINAIRE

PENDANT MOUNTED LUMINAIRE

POWER POLE

METER SOCKET

POWER EQUIPMENT

WIRING DEVICES - RECEPTACLES

COMBINATION STARTER SAFETY SWITCH

RELAY - CONTROL AS NOTED

PUSHBUTTON STATION

MOTOR CONNECTION

SIMPLEX RECEPTACLE

DUPLEX RECEPTACLE

QUADRUPLEX RECEPTACLE

EMERGENCY RECEPTACLE

SPECIAL PURPOSE RECEPTACLE, NEMA

CONFIGURATION NOTED

PLUG-IN STRIP - LENGTH AND QUANTITY

OF OUTLETS AS SHOWN

SAFETY SWITCH

DROP CORD RECEPTACLE ASSEMBLY

FUSIBLE SWITCH (FUSETRON)

PANELS AND CABINETS

DISTRIBUTION PANEL

SWITCHBOARD, SWITCHGEAR, MCC

EQUIPMENT OR TERMINAL CABINET

DRY TYPE TRANSFORMER

BRANCH CIRCUIT PANEL

CONDUIT AND BOXES

HORN (PA, PUBLIC ADDRESS)

TRANSFORMER

EXIT LIGHT - WALL MOUNT WITH

DIRECTIONAL ARROWS AS INDICATED,

FILLED-IN QUARTERS INDICATE

ILLUMINATION SIDES

EXIT LIGHT - CEILING OR PENDANT

MOUNT WITH DIRECTIONAL ARROWS AS

INDICATED, FILLED-IN QUARTERS

INDICATE ILLUMINATION SIDES

EMERGENCY EXIT LIGHT COMBO

LOW VOLTAGE MOMENTARY

CONTACT SWITCH

N TV TV CONNECTION

FB FLOOR BOX

FP FLOOR POKE-THROUGH DEVICE

N M

WIRELESS ACCESS POINT

S S2

S3

S4

SD

SK

SP

STE

ST

SFT

X

CONTROLLED RECEPTACLE

WB WALL AV BOX

F

F

F

F

FS

D

PS

TS

DH

STROBE

HORN

MANUAL PULL STATION

HORN STROBE

HEAT DETECTOR

SMOKE DETECTOR

REMOTE INDICATOR LIGHT

SPRINKLER TAMPER SWITCH

DUCT SMOKE DETECTOR

FLOW SWITCH

POST INDICATING VALVE SWITCH

MAGNETIC DOOR HOLDER

FIRE ALARM SYSTEM

H

S

S

F SPEAKER STROBES

F SPEAKERS

ACSR ALUMINUM CONDUCTOR

STEEL REINFORCED

AFF ABOVE FINISH FLOOR

AIC AMPS INTERRUPTING

CAPACITY (SYM RMS)

AL ALUMINUM

ALT ALTERNATE

AMP AMPERE

ANSI AMERICAN NATIONAL

STANDARDS INSTITUTE

APPROX APPROXIMATE

AUTO AUTOMATIC

AVG AVERAGE

L ANGLE

BKR BREAKER

C OR CL CENTER LINE

C OR CND CONDUIT (ELECTRICAL

SHEETS)

CKT CIRCUIT

CLG CEILING

COL COLUMN

CONC CONCRETE

CONF CONFERENCE

DC DIRECT CURRENT

DEG DEGREE

DEMO DEMOLITION

DIA DIAMETER

DIM DIMENSION

DISC DISCONNECT

DIST DISTRIBUTION

DN DOWN

DWG DRAWING

E EAST

EA EACH

EL OR

ELEV

ELEVATION - GRADE OR

BUILDING

ELEC ELECTRIC OR

ELECTRICAL

ELEV ELEVATOR

EMD ESTIMATED MAXIMUM

DEMAND

ENCL ENCLOSURE

EQUIP EQUIPMENT

EST ESTIMATE

EWC ELECTRIC WATER

COOLER

EXIST EXISTING

EXP EXPOSED

EXT EXTERIOR

FA FIRE ALARM

FLA FULL LOAD AMPS

FLEX FLEXIBLE

FLUOR FLUORESCENT

AWG GAUGE

HP HORSE POWER

HR HOUR

HTG HEATING

HTR HEATER

HZ HERTZ

ID INSIDE DIAMETER

IES ILLUMINATING

ENGINEERING SOCIETY

IN INCH

INSUL INSULATION

INT INTERIOR

KCMIL KCM KILO CIRCULAR MIL

KV KILOVOLTS

KVA KILOVOLT AMPERES

KVAR KILOVOLT AMPERES

REACTIVE

KW KILOWATT

LBS POUNDS

LRA LOCKED ROTOR AMPS

LTG LIGHTING

MAX MAXIMUM

MECH MECHANICAL

MFR MANUFACTURER

MG MOTOR GENERATOR

MH MANHOLE

MIN MINIMUM

MISC MISCELLANEOUS

FAAP FIRE ALARM

ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL

PANEL

FAEP FIRE ALARM EXTENDER

PANEL

GFCI GROUND FAULT CIRCUIT

INTERRUPTER

CUH CABINET UNIT HEATER

EMI ELECTROMAGNETIC

INTERFERENCE

MCCB MOLDED CASE CIRCUIT

BREAKER

GFI GROUND FAULT CIRCUIT

INTERRUPTER

QTY QUANTITY

REC RECEPTACLE

REFR REFRIGERATOR

REINF REINFORCEMENT

REQD REQUIRED

N NORTH

NC NORMALLY CLOSED

NEC NATIONAL ELECTRICAL

CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURERS

ASSOCIATION

NFPA NATIONAL FIRE

PROTECTION

ASSOCIATION

NIC NOT IN CONTRACT

NO NORMALLY OPEN

NO NUMBER

NTS NOT TO SCALE

OD OUTSIDE DIAMETER

PH PHASE

PIV POST INDICATING VALVE

PNL PANEL

PSI POUNDS PER SQUARE IN.

OCPD OVERCURRENT

PROTECTIVE DEVICE

RFI RADIO FREQUENCY

INTERFERENCE

TEL TELEPHONE

TEMP TEMPERATURE

TVSS TRANSIENT VOLTAGE

SURGE SUPPRESSOR

TYP TYPICAL

UG UNDERGROUND

UH UNIT HEATER

UL UNDERWRITERS

LABORATORIES

UPS UNINTERRUPTIBLE

POWER SYSTEM

VFD VARIABLE FREQUENCY

DRIVE

W WEST

W/ WITH

W/O WITHOUT

WHM WATTHOUR METER

WT WEIGHT

XFMR TRANSFORMER

SOUTH

SCHED SCHEDULE

SF SQUARE FOOT (FEET)

SPEC SPECIFICATIONS

SPKR SPEAKER

SQ SQUARE

STD STANDARD

STL STEEL

SW SWITCH

SWBD SWITCH BOARD

SYM SYMMETRICAL

S

SCCR SHORT CIRCUIT

CURRENT RATING

SPD SURGE PROTECTIVE

DEVICE

SPDT SINGLE POLE, DOUBLE

THROW

VFC VARIABLE FREQUENCY

CONTROLLER

P

C/W COMPLETE WITH

VA DES MOINES CONSTRUCTION

DESIGN STANDARDS

CONSULTANTS: ARCHITECT/ENGINEERS:

on e ei gh th in ch o ne fo ot

B

A

C

D

E

F th re e in ch es o ne fo ot 6"

6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot

6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

CONSULTANTS: ARCHITECT/ENGINEERS:

on e ei gh th in ch o ne fo ot

B

A

C

D

E

F th re e in ch es o ne fo ot 6"

6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot

6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

97 8654321

P

G

IN

G

U N

IT

B A

T T

E R

IE

S

R E

C T

T E

LE

C

O M

M G

N T

S T

A T

IO

N

PBX

PBX

PBX

T E

LE

W

IR

IN

G P

U N

C H

D O

W N

B

LO

C K

S C

S U

R A

C K

S E

R V

E R

M G

N T

S E

R V

E R

M G

N T

ICN

RACKS

N E

T W

O R

K M

A N

A G

E M

E N

T

S E

R V

E R

M G

N T

V M

S V

M S

V M

S T

E S

T A

C C

T.

M

G N

T

#2 #1

ELEVATOR "G"

2, F-1

FREIGHT

#3

ELEVATOR "B"

ELEVATOR "B"

ELEVATOR "A" ELEVATOR"A"

ELEVATOR "H"

ELEVATOR "B"

FREIGHT

#4

#3

ELEVATOR "B"

3-1/2"C C/W:

(1) 24 STRAND MM FIBER (DATA)

(1) 12 STRAND SM FIBER (VOICE)

(1) 12 STRAND MM FIBER (NURSE CALL)

(1) 12 STRAND MM FIBER (METASYS)

3-1/2"C C/W:

(1) 100 PAIR CAT3 (TELEPHONE)

(1) 4-PAIR PLTC (PAGING)

(1) RG-11 (MATV)

TO MANHOLE #5

(SEE EC103 FOR

CONTINUATION)

EXISTING MANHOLE #11

3-1/2"C C/W:

(1) 24 STRAND MM FIBER (DATA)

(1) 12 STRAND SM FIBER (VOICE)

(1) 12 STRAND MM FIBER (NURSE CALL)

(1) 12 STRAND MM FIBER (METASYS)

(1) 12 STRAND MM FIBER (SECURITY)

3-1/2"C C/W:

(1) 100 PAIR CAT3 (TELEPHONE)

(1) 4-PAIR PLTC (PAGING)

(1) RG-11 (MATV)

2"C C/W:

(1) 12 STRAND MM FIBER (SECURITY)

UP TO 1ST FLR (IT CLOSET)

(SEE 2/EC102 FOR CONTINUATION)

PULLBOX (TYP.)

EXISTING 3-1/2"C C/W:

(1) 24 STRAND MM FIBER (DATA)

(1) 12 STRAND SM FIBER (VOICE)

(1) 12 STRAND MM FIBER (NURSE CALL)

(1) 12 STRAND MM FIBER (METASYS)

(1) 12 STRAND MM FIBER (SECURITY)

EXISTING 3-1/2"C C/W:

(1) 100 PAIR CAT3 (TELEPHONE)

(1) 4-PAIR PLTC (PAGING)

(1) RG-11 (MATV)

REPLACE

PULLBOX

EXISTING DUCTBANK ADD:

(1) 24 STRAND MM FIBER (DATA)

(1) 12 STRAND SM FIBER (VOICE)

(1) 12 STRAND MM FIBER (NURSE CALL)

(1) 12 STRAND MM FIBER (METASYS)

(1) 12 STRAND MM FIBER (SECURITY)

EXISTING DUCTBANK ADD:

(1) 100 PAIR CAT3 (TELEPHONE)

(1) 4-PAIR PLTC (PAGING)

(1) RG-11 (MATV)

EXISTING DUCTBANK ADD:

(1) 24 STRAND MM FIBER (DATA)

(1) 12 STRAND SM FIBER (VOICE)

(1) 12 STRAND MM FIBER (NURSE CALL)

(1) 12 STRAND MM FIBER (METASYS)

(1) 12 STRAND MM FIBER (SECURITY)

EXISTING DUCTBANK ADD:

(1) 100 PAIR CAT3 (TELEPHONE)

(1) 4-PAIR PLTC (PAGING)

(1) RG-11 (MATV)

TO BLDG 25

(SEE EC103 FOR

CONTINUATION)

EXISTING STEAM TUNNEL ADD:

4#250KCMIL, 1#4G - 3"C (EMERGENCY)

1-1/4"C C/W:

ATS CONTROL WIRING

4#250KCMIL, 1#4G - 3"C (EMERGENCY)

1-1/4"C C/W:

ATS CONTROL WIRING

'SWBD 1W-4E'

GENERATOR MASTER

CONTROL (EXIST)

4#250KCMIL, 1#4G - 3"C

(EMERGENCY)

1-1/4"C C/W:

ATS CONTROL WIRING

P6

P7

Y8

CORE DRILL

CORE DRILL

2"C C/W:

(1) 12 STRAND MM FIBER (SECURITY)

DN TO BASEMENT

(CRAWL SPACE)

(SEE 1/EC102 FOR CONTINUATION)

IT CLOSET

Y8

Drawing Title

Approved:

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management on e ei gh th in ch o ne fo ot th re e in es fo ot 6"

6" on e an d on e ha lf in fo ot on e fo ot

6" 6" th re e qu ar te rs fo ot on e ha lf fo ot th re e ei gh th s fo ot on e qu ar te r fo ot

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

TSA PROJECT

NO.:

Department of Veterans Affairs

CONSTRUCT CLC

COTTAGES - COTTAGE 1

636-123

3600 30TH ST. DES MOINES, IA

4/13/2018

BASEMENT FLOOR PLAN - BUILDINGS 2, 1W, &

1 + STEAM TUNNEL - COMPOSITE

BTF MTB

EC102

83 97 06054.032

SCALE: 1/16" = 1'-0"

BASEMENT FLOOR PLAN - BUILDINGS 2, 1W, & 1 + STEAM TUNNEL - COMPOSITE

NORTHKEY PLAN

E X

IS

T

S

E

M

N

N E

L

EXIS

T C

HILLER TUNNEL

1W

REF. NOTES ( ):X

P6 PROVIDE 250A BREAKER IN EMERGENCY SWITCHBOARD FOR SERVING

BUILDING 25.

P7 PROVIDE CONNECTIONS AS REQUIRED TO ADD BUILDING 25 AUTOMATIC

TRANSFER SWITCHES.

Y8 CONTRACTOR SHALL VISIT SITE PRIOR TO BID TO LOCATE FINAL

TERMINATION LOCATIONS OF SPECIALTY SYSTEMS IN THIS SPACE.

SCALE: 1/16" = 1'-0"

FIRST FLOOR PLAN - BUILDING 1W - COMPOSITE

DN

DN

UP TO 1ST FLR (IT CLOSET)

(SEE EC104 FOR CONTINUATION)

UP TO 1ST FLR (IT CLOSET)

(SEE EC104 FOR CONTINUATION)

EXISTING DUCTBANK ADD:

(1) 24 STRAND MM FIBER (DATA)

(1) 12 STRAND SM FIBER (VOICE)

(1) 12 STRAND MM FIBER (NURSE CALL)

(1) 12 STRAND MM FIBER (METASYS)

(1) 12 STRAND MM FIBER (SECURITY)

EXISTING DUCTBANK ADD:

(1) 100 PAIR CAT3 (TELEPHONE)

(1) 4-PAIR PLTC (PAGING)

(1) RG-11 (MATV)

EXISTING MANHOLE #5

TO MANHOLE #11

(SEE EC102 FOR

CONTINUATION)

1"C C/W:

(1) 6 STRAND MM FIBER (FIRE ALARM LOOP A)

1"C C/W:

(1) 6 STRAND MM FIBER (FIRE ALARM LOOP B)

TO SWBD 1W-4E

(SEE EC102 FOR

CONTINUATION)

TO BLDG 11 XFMR

TO BLDG 12 XFMR

EXISTING STEAM TUNNEL ADD:

4#250KCMIL, 1#4G - 3"C (EMERGENCY)

1-1/4"C C/W:

ATS CONTROL WIRING

SEE POWER RISER

DIAGRAM FOR

CONTINUATION

'SWBD 12-1'

SEE EC104 FOR

CONTINUATION

P5

Y8

BLDG 12

FACP

Y9

BLDG 12 SECURITY

PANELS

DUCTBANK C/W:

4#250KCMIL, 1#4G - 3"C (EMERGENCY)

3#2/0 (15KV), 1#2G (600V) - 4"C (PRIMARY LOOP A)

3#2/0 (15KV), 1#2G (600V) - 4"C (PRIMARY LOOP B)

1-1/4"C C/W:

ATS CONTROL WIRING

3#2/0 (15KV), 1#2G (600V) - 4"C (PRIMARY LOOP A)

3#2/0 (15KV), 1#2G (600V) - 4"C (PRIMARY LOOP B)

UTILITY TUNNEL C/W:

4#250KCMIL, 1#4G - 3"C (EMERGENCY)

3#2/0 (15KV), 1#2G (600V) - 4"C (PRIMARY LOOP A)

3#2/0 (15KV), 1#2G (600V) - 4"C (PRIMARY LOOP B)

1-1/4"C C/W:

ATS CONTROL WIRING

3-1/2"C C/W:

(1) 24 STRAND MM FIBER (DATA)

(1) 12 STRAND SM FIBER (VOICE)

(1) 12 STRAND MM FIBER (NURSE CALL)

(1) 12 STRAND MM FIBER (METASYS)

(1) 12 STRAND MM FIBER (SECURITY)

3-1/2"C C/W:

(1) 100 PAIR CAT3 (TELEPHONE)

(1) 4-PAIR PLTC (PAGING)

(1) RG-11 (MATV)

EC103

MECHANICAL PIPING

(SEE MECHANICAL PLANS)

SECTION THRU TRENCH

1. UTILITY TRENCH PROVIDED BY

MECHANICAL CONTRACTOR.

2. COORDINATE INSTALLATION WITH

MECHANICAL CONTRACTOR.

LOOP B (FROM XFMR 12)

LOOP A (FROM XFMR 11)

EMERGENCY FEED (FROM SWBD 1W-4E)

ATS CONTROL WIRING

Drawing Title

Approved:

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management on e ei gh th fo ot th re e in fo ot 6"

6" on e an d on e ha lf in fo ot on e fo ot

6" 6" th re e qu ar te rs fo ot on e ha lf fo ot th re e ei gh th s fo ot on e qu ar te r fo ot

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

TSA PROJECT

NO.:

Department of Veterans Affairs

CONSTRUCT CLC

COTTAGES - COTTAGE 1

636-123

3600 30TH ST. DES MOINES, IA

4/13/2018

BASEMENT FLOOR PLAN - BUILDING 12 +

STEAM TUNNEL- COMPOSITE

BTF MTB

EC103

84 97 06054.032

SCALE: 1/16" = 1'-0"

BASEMENT FLOOR PLAN - BUILDING 12 + STEAM TUNNEL + UTILITY TUNNEL - COMPOSITE

NORTHKEY PLAN

E X

E

N

N E

L

EXIS

T C

HILLER TUNNEL

1W

REF. NOTES ( ):X

P5 TEMPORARY POWER LOCATION. CONTRACTOR SHALL PROVIDE BREAKER

AS REQUIRED.

Y8 CONTRACTOR SHALL VISIT SITE PRIOR TO BID TO LOCATE FINAL

TERMINATION LOCATIONS OF SPECIALTY SYSTEMS IN THIS SPACE.

Y9 PROVIDE CONNECTIONS AS REQUIRED TO EXTEND CAMPUS FIRE ALARM

LOOP TO BUILDING 25.

SCALE: 1/2" = 1'-0"

PRECAST UTILITY TRENCH DETAIL

SS

J

JF

F

JJ

S S

J

J

J

S

F

R Q

P

L

M

K J

H

G

F

E

D

B

A

1 2 3 4 5 6 7 9

12 13 14 158

C

N

S

T

U

V

W

Z

8.6 11.3

Y

12.3

N.1

D.4

12.6

IT

FIRE/WATER

SRVC

FACP

EY101

DN TO BASEMENT (STORAGE)

(SEE EC103 FOR CONTINUATION)

DN TO BASEMENT

(SEE EC103 FOR CONTINUATION)

IT CLOSET

IT CLOSET

EXISTING CABLE TRAY ADD:

(1) 24 STRAND MM FIBER (DATA)

(1) 12 STRAND SM FIBER (VOICE)

(1) 12 STRAND MM FIBER (NURSE CALL)

(1) 12 STRAND MM FIBER (METASYS)

(1) 12 STRAND MM FIBER (SECURITY)

EXISTING CABLE TRAY ADD:

(1) 100 PAIR CAT3 (TELEPHONE)

(1) 4-PAIR PLTC (PAGING)

(1) RG-11 (MATV)

1"C C/W:

(1) 6 STRAND MM FIBER (FIRE ALARM LOOP A)

1"C C/W:

(1) 6 STRAND MM FIBER (FIRE ALARM LOOP B)

EXISTING CABLE TRAY ADD:

(1) 24 STRAND MM FIBER (DATA)

(1) 12 STRAND SM FIBER (VOICE)

(1) 12 STRAND MM FIBER (NURSE CALL)

(1) 12 STRAND MM FIBER (METASYS)

(1) 12 STRAND MM FIBER (SECURITY)

EXISTING CABLE TRAY ADD:

(1) 100 PAIR CAT3 (TELEPHONE)

(1) 4-PAIR PLTC (PAGING)

(1) RG-11

1"C C/W:

(1) 6 STRAND MM FIBER (FIRE ALARM LOOP A)

1"C C/W:

(1) 6 STRAND MM FIBER (FIRE ALARM LOOP B)

NEW CABLE TRAY C/W:

(1) 24 STRAND MM FIBER (DATA)

(1) 12 STRAND SM FIBER (VOICE)

(1) 12 STRAND MM FIBER (NURSE CALL)

(1) 12 STRAND MM FIBER (METASYS)

(1) 12 STRAND MM FIBER (SECURITY)

NEW CABLE TRAY C/W:

(1) 100 PAIR CAT3 (TELEPHONE)

(1) 4-PAIR PLTC (PAGING)

(1) RG-11 (MATV)

1"C C/W:

(1) 6 STRAND MM FIBER (FIRE ALARM LOOP A)

1"C C/W:

(1) 6 STRAND MM FIBER (FIRE ALARM LOOP B)

NEW CABLE TRAY C/W:

(1) 24 STRAND MM FIBER (DATA)

(1) 12 STRAND SM FIBER (VOICE)

(1) 12 STRAND MM FIBER (NURSE CALL)

(1) 12 STRAND MM FIBER (METASYS)

(1) 12 STRAND MM FIBER (SECURITY)

NEW CABLE TRAY C/W:

(1) 100 PAIR CAT3 (TELEPHONE)

(1) 4-PAIR PLTC (PAGING)

(1) RG-11 (MATV)

1"C C/W:

(1) 6 STRAND MM FIBER (FIRE ALARM LOOP A)

1"C C/W:

(1) 6 STRAND MM FIBER (FIRE ALARM LOOP B)

PNL R1C-G-1

PNL R1S-G-1

SEE EC103 FOR

CONTINUATION

P4

Y11 (TYP.)

EC104

D3

D2

D7 D8

D1

D2

D4 D5

D3

D9

D9

Drawing Title

Approved:

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management on e ei gh th fo ot th re e in fo ot 6"

6" on e an d on e ha lf in fo ot on e fo ot

6" 6" th re e qu ar te rs fo ot on e ha lf fo ot th re e ei gh th s fo ot on e qu ar te r fo ot

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

TSA PROJECT

NO.:

Department of Veterans Affairs

CONSTRUCT CLC

COTTAGES - COTTAGE 1

636-123

3600 30TH ST. DES MOINES, IA

4/13/2018

FIRST FLOOR PLAN - BUILDINGS 25 AND 12 -

COMPOSITE

BTF MTB

EC104

85 97 06054.032

SCALE: 1/16" = 1'-0"

FIRST FLOOR PLAN - BUILDINGS 25 AND 12 - COMPOSITE

NORTHKEY PLAN

E X

E

N

N E

L

EXIS

T C

HILLER TUNNEL

1W

REF. NOTES ( ):X

P4 TO CONTRACTOR STAGING AREA. CONTRACTOR SHALL PROVIDE

STEP-DOWN TRANSFORMERS, DISCONNECTS, ETC. AS REQUIRED.

Y11 PROVIDE (2) GANGED EZ PATH SERIES 44 PATHWAYS AT ALL DOOR

CROSSINGS AND ENTRANCES INTO IT ROOMS.

SCALE: 1/4" = 1'-0"

BUILDING 12 - DEMOLITION

REF. DEMO NOTES ( ):DX

D1 SECURITY CAMERA TO BE REMOVED AND STORED FOR RE-INSTALLATION;

EXISTING WIRING TO BE PRESERVED.

D2 MANUAL PULL STATION TO BE REMOVED AND STORED FOR

RE-INSTALLATION; EXISTING WIRING TO BE PRESERVED.

D3 PA HORN TO BE REMOVED AND STORED FOR RE-INSTALLATION; EXISTING

WIRING TO BE PRESERVED.

D4 SPEAKER TO BE REMOVED AND STORED FOR RE-INSTALLATION; EXISTING

WIRING TO BE PRESERVED.

D5 SMOKE DETECTOR TO BE REMOVED AND STORED FOR RE-INSTALLATION;

EXISTING WIRING TO BE PRESERVED.

D7 STAIRWELL LIGHTING (INTERIOR / EXTERIOR) TO BE REMOVED AND

STORED FOR RE-INSTALLATION; EXISTING WIRING TO BE PRESERVED.

D8 REMOVE BACK-TO-BACK CABINET UNIT HEATERS AND DEMO ONE CIRCUIT

BACK TO PNL R1C-G-1; OTHER CIRCUIT WIRING TO BE PRESERVED.

D9 ABANDONED EQUIPMENT; COORDINATE WITH OWNER PRIOR TO DEMO

AND RETURN TO OWNER.

OS

OS

OS

OS

OS

OS

OS

OS

OS

PC

PC

OS

OS

OS

PC

EL101

FIRE/WATER

SRVC

CLEAN EQUIP.

CLEAN UTILITY

RESIDENT

(BARIATRIC)

2529 RESIDENT

RESIDENT

RESIDENT

RESIDENT

RESIDENT

MED. STO.

RESIDENT

(BARIATRIC)

RESIDENT

RESIDENT

RESIDENT

RESIDENT

RESIDENT

STAIR 1

IT

STAFF REPORT

ROOM

MEN

WOMEN

NURSE ADMIN.

2545 LOUNGE

CORRIDOR

CORRIDOR

CORRIDOR

SRVC CORR.

FAMILY

FOYER

LIVING ROOM

CORRIDOR

CLEAN LINEN

2528 DEN

DINING

SERVERY

GROUP ROOM

ELECT.

HSKPG

STORAGE

SOILED UTILITY

RESIDENT

LAUNDRY

SPA

PANTRY

2510A

PRODUCTION

KITCHEN

HOME OFFICE

2508A

CORRIDOR

CORRIDOR

CORRIDOR

2 2

A1A1A1

A1

A1

A1

A1

A1

A1

A1

A1A1

A1 A1

A1

A1 A1

A1 A1 A1

A1 A1 A1

A1

A1

A1

A1

A1

A1

A1

A1

A1

A1

A1

2 2

A2

A2 A2

A2

A2

A1

A1

A1

A1 A1

A1

A1

A2 A2

A1

A1

A1 A1

A1

A2

A2

A2

A1

A1

A1

A1 C1

C1

C1

C1

C1

C1

C1

C4

C4

C4

C4

C4

C4

C4C4C4C4C4C4

C2 C2

C2 C2

C2 C2

C2 C2

W1 W1 W1 W1 W1

W1

W1

W1

W1

W1

C2

C2 C2

C2

A2

A2

C1 C1

W2 W2

C1 C1

C1 C1

C1

C1

C1 C3

C3 C3 C3

C3 C3 C3 C3

C3 C3 C3 C3

C3 C3 C3 C3

C4

C4

C4

C4

C2W C2W

C2W C2W

C2W

C2W

C1 C1

1 F1

F1

F1

F1

C3 C3

F2

F2

F1 F1

C1

C2

A2

A2

A2

A2

F1

F1

F1

F1

R

Q

P

L

M

K

J

H

G

F

E

D

B

A

1 2 3 4 5 6 7 9 12 13 14 158

C

N

S

N.1

D.4

12.6

AREA

AREA

A

B

C2

C2

C2

W3

W3

X1

X1

X1X1X1

X1

X1

X1

X1

X1

X1

X1

X1

X1

F1

C1

A5

A5

A5

LCP - 1

EP101

NL1 - 52CRL1 - 26

LCP - 3

LCP - 2

LCP - 5

CRL1 - 26

LSL1 - 1

LSL1 - 3

NL1 - 58 CRL1 - 24

UP

CRL1 - 28

NL1 - 62

CRL1 - 28

NL1 - 62

CRL1 - 28

NL1 - 62

CRL1 - 28

NL1 - 62

CRL1 - 28

NL1 - 62

CRL1 - 28

NL1 - 62

(PART.)

CRL1 - 30

NL1 - 60

CRL1 - 30

NL1 - 60

CRL1 - 30

NL1 - 60

CRL1 - 30

NL1 - 60

CRL1 - 30

NL1 - 60

CRL1 - 26

(PART.)

LCP - 6

L2

L3

OR

OR

L3

OR

L4

L4

OR

OR

L4

OR

L4

L6

(TYP.)

LCP - 4W1

W1 W1

W1

C2 C2C2

X1

(PART.)

L2

9 11

T

U

V

W

Z

8.6 11.3

Y

C1

C1

C1

C1

C1

C1

AREA

AREA

A

B

C2 C2

C2 C2

X1

X1

L2

ORL4

B1 B1 B1

C1 C1X1

STAIR 4

S4

PASSAGE

C1-3E

L7

L8

BLDG 25 BLDG 12

F2 F2

F2

F2 F2 F2

F2

F2

F2 F2

F2 F2

E

D

2 3 4 5 6 7 98

C

D.4

X1W3

MECHANICAL

ELEC.

NL1 - 58CRL1 - 24

DN

NL1 - 54

L9

C2W

C2W

W2

A4

A4

A3

B

A

C

N1

C3WW

L1

READING

AMBIENT

EXAM

EY602

NL1-X CR1-X

1 2 3

V1 V1

L5

NL1 - 56

#10s

+7' AFF

(TYP.)

Drawing Title

Approved:

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management on e ei gh th fo ot th re e in fo ot 6"

6" on e an d on e ha lf in fo ot on e fo ot

6" 6" th re e qu ar te rs fo ot on e ha lf fo ot th re e ei gh th s fo ot on e qu ar te r fo ot

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

TSA PROJECT

NO.:

Department of Veterans Affairs

CONSTRUCT CLC

COTTAGES - COTTAGE 1

636-123

3600 30TH ST. DES MOINES, IA

4/13/2018

FLOOR PLANS & TUNNEL - LIGHTING

BTF MTB

EL101

86 97 06054.032

REF. NOTES ( ):X

L1 LOCATE REFLECTOR TO MAXIMIZE LIGHT AT MED CABINET.

L2 PROVIDE PHOTOCELL FOR CONTROL OF CANOPY LIGHTING.

L3 PROVIDE 8-BUTTON OVERRIDE SWITCH FOR CONTROL OF ALL LCP

RELAYS.

L4 PROVIDE 2-BUTTON OVERRIDE SWITCH FOR CONTROL OF CORRIDOR

LIGHTING.

L5 LOCATE SWITCH NEAR TUNNEL ENTRANCE (VERIFY).

L6 INDICATES CIRCUITS SERVING RESIDENT ROOM.

L7 EXISTING STAIRWELL LIGHTING (INTERIOR / EXTERIOR) TO BE

RE-INSTALLED; CONNECT TO EXISTING WIRING.

L8 CONNECT LIGHTING IN CORRIDOR TO EXISTING LIFE SAFETY / NORMAL

CIRCUITS (VERIFY).

L9 SHIFT LIGHTING AS REQUIRED TO AVOID CONFLICTS WITH HVAC

DUCTWORK, PIPING, ETC.

SCALE: 1/8" = 1'-0"

FIRST FLOOR PLAN - AREA A - LIGHTING

SCALE: 1/8" = 1'-0"

FIRST FLOOR PLAN - AREA B - LIGHTING

SCALE: 1/8" = 1'-0"

ATTIC - LIGHTING

SCALE: 1/4" = 1'-0"

ENLARGED PLAN - TYP. RESIDENT ROOM - LIGHTING

NORTHKEY PLAN

E X

E

N

N E

L

EXIS

T C

HILLER TUNNEL

1W

SCALE: 1/8" = 1'-0"

TUNNEL - LIGHTING

1 3 4

LMSW-101-G-U LMDM-101-G-U DW-311-G-U

DSW-301-G-U

NOTES:

1. WATTSTOPPER USED AS DESIGN BASIS.

LMDC-100-ULMDC-100-U

(AS REQUIRED)

LMRC-101-U

NEUTRAL

UNSWITCHED

HOT

1 1

CAT5E

(TYP.)

RJ-45

(TYP.)

NOTES:

• WATTSTOPPER USED AS DESIGN BASIS.

(AS REQUIRED)

LIGHTING

LOAD

RED

EM / EXIT

LTG

LOAD

H N

LMDC-100-ULMDC-100-U

(AS REQUIRED)

LMRC-211-U

NEUTRAL

UNSWITCHED

HOT

3 3

CAT5E

(TYP.)

RJ-45

(TYP.)

(AS REQUIRED)

LIGHTING

LOAD

RED

0-10V

EM / EXIT

LTG

LOAD

H N

0-10VDC

LUMINAIRE SCHEDULE NOTES:

1. ADDITIONAL 97W FOR EXAM LIGHT.

2. SUFFIX CATALOG NO. REPRESENTS (2) CKTS WITH (1) CKT

CONNECTED TO MOTION SENSOR. CONNECT NORMAL CKT TO

MOTION SENSOR AND CONNECT LIFE SAFETY TO OTHER. ADDITIONAL

34W FOR LIFE SAFETY CKT.

3. PROVIDE HUBBELL EPC-1 (OR EQUAL) TRANSFER DEVICE FOR

LOCATIONS SERVED BY NORMAL AND EMERGENCY POWER AND

CONTROLLED BY A SINGLE SWITCH.

4. SEE FLOOR PLAN FOR SINGLE / DOUBLE FACE LOCATIONS AND

CHEVRON REQUIREMENTS.

5. CATALOG NO. TAKEN FROM AS-BUILT DRAWINGS AND HAS NOT BEEN

FIELD VERIFIED. CONTRACTOR SHALL MATCH EXISTING BASKET-TYPE

LUMINAIRE ON FIRST FLOOR OF BUILDING 12.

GENERAL LUMINAIRE SCHEDULE NOTES:

A. THE SUBMITTAL SHALL BE PREPARED AND SUBMITTED BY THE

AUTHORIZED FACTORY REPRESENTATIVE OR THEY SHALL BE

REJECTED.

Drawing Title

Approved:

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management on e ei gh th in ch o ne fo ot

B

A

C

D

E

F th re e in ch es o ne fo ot 6"

6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot

6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

TSA PROJECT

NO.:

Department of Veterans Affairs

CONSTRUCT CLC

COTTAGES - COTTAGE 1

636-123

3600 30TH ST. DES MOINES, IA

4/13/2018

SCHEDULES AND DIAGRAMS - LIGHTING

BTF MTB

EL601

87 97 06054.032

SCALE: NOT TO SCALE

TYPICAL LOW VOLTAGE SWITCHES

SCALE: NOT TO SCALE

ON/OFF ROOM CONTROLLER

SCALE: NOT TO SCALE

ON/OFF OCCUPANCY SENSOR

SCALE: NOT TO SCALE

ON/OFF ROOM CONTROLLER W/ DIMMING

SCALE: NOT TO SCALE

ON/OFF OCCUPANCY SENSOR W/ DIMMING

LUMINAIRE SCHEDULE

TYPE NO DESCRIPTION / SPEC NO

LAMPS TOTAL

WATTS BALLAST MFGR AND TYPE VOLT MOUNTING NOTESNO WATTS TYPES

A1 2X2 - TROFFER - 2000 LUMENS

CREE CR22 20L 40K 10V

- - LED 22 VA - MVOLT RECESSED

A2 2X2 - TROFFER - 3200 LUMENS

CREE CR22 32L 40K 10V

- - LED 32 VA - MVOLT RECESSED

A3 2X4 - TROFFER - PATIENT BED

KENALL MPC24 G 25L/45L/90L40K DCC 120 SYM LVC

- - LED 78 VA - 120 V RECESSED 1

A4 2X2 - TROFFER - PATIENT ROOM

KENALL MAC22 G 45L40K DCC 1 DV

- - LED 45 VA - MVOLT RECESSED

A5 2X2 - SURFACE

CREE FP22 50L 40K 10V (SMK-CR22 SURFACE KIT)

- - LED 50 VA - MVOLT SURFACE

B1 2X4 - BASIC (EXISTING)

LITHONIA 2AV G 2 32 PMW MVOLT GEB10PS

2 32 F032/735/ECO 56 VA - MVOLT CEILING 5

C1 6" RECESSED CAN - 1100 LUMENS

CREE KR6 13L 40K 120V 10V + KR6T SSGC FF

- - LED 18 VA - 120 V RECESSED

C2 6" RECESSED CAN - 1700 LUMENS

CREE KR6 20L 40K 120V 10V + KR6T SSGC FF

- - LED 30 VA - 120 V RECESSED

C2W 6" RECESSED CAN - 1700 LUMENS - WET LOCATION

CREE HADL6 FF 2FW 22L 40K8 M CSS G RIG6 DV DIM1

- - LED 22 VA - MVOLT RECESSED

C3 6" RECESSED CAN - 2550 LUMENS

CREE KR6 30L 40K 120V 10V + KR6T SSGC FF

- - LED 39 VA - 120 V RECESSED

C3WW 6" RECESSED CAN - 2550 LUMENS

CREE KR6 30L 40K 120V 10V + KR6T SSGC FF WW

- - LED 39 VA - 120 V RECESSED

C4 4" RECESSED CAN - 700 LUMENS

CREE KR4 9L 40K 120V 10V + KR4T SSGC FF

- - LED 13 VA - 120 V RECESSED

F1 4' SURFACE

CREE LS4 25L 40K 10V

- - LED 23 VA - MVOLT SURFACE 3

F2 8' SURFACE

CREE LS8 80L 40K 10V + AC-144-Q14B-LP (FINAL HEIGHT TBD)

- - LED 80 VA - MVOLT CABLE

N1 NIGHT LIGHT

KENALL MSL S 1 BSS PP ALL 120 2

- - LED 5 VA - 120 V RECESSED

V1 4' WALL MOUNTED - VAPORTIGHT

CREE WS4 47L 40K 10V FD SSL + WS4MBK

- - LED 50 VA - MVOLT WALL

W1 WALL SCONCE - SLIM

KENALL MAS813 PAN AS WS 1 12L40K-DCC-DV

- - LED 14 VA - MVOLT WALL

W2 4' WALL MOUNT - VANITY

KENALL MLHA5V 48 F MW PP 1 45L40K DCC 1 DV

- - LED 45 VA - MVOLT WALL

W3 WALL MOUNT - STAIRWELL

KENALL MLHA8 F MB PP 1 67L40K DCC 1 120 + 2C MS SP

- - LED 34 VA - 120 V WALL 2

X1 EXIT SIGN

COMPASS CCES/DG

- - LED 5 VA - 120 V WALL/CEILING 4

PROVIDE (2) 20A BREAKERS IN UPSTREAM PANELBOARD FOR SUPPLYING RELAYS.

1. CONTROLLED BY (3) 2-BUTTON OVERRIDE SWITCHES & (2) 8-BUTTON OVERRIDE SWITCHES.

2. CONTROLLED BY (2) 8-BUTTON OVERRIDE SWITCHES.

3. CONTROLLED BY (2) 2-BUTTON OVERRIDE SWITCHES & (2) 8-BUTTON OVERRIDE SWITCHES.

Notes:

LTG 1642 VA 100.00% 1642 VA

Load Classification Connected Load Demand Factor Estimated Demand

14 A

1642 VA

8 SPARE 1 0 VA

7 SPARE 1 0 VA

6 LTG - BLDG 25 FOY LOW 1 90 VA 2

5 LTG - BLDG 12 CONNECTING LINK 1 152 VA 3

4 LTG - BLDG 25 LIV / DIN / FOY HIGH 1 624 VA 2

3 LTG - BLDG 25 WALL SCONCES 1 140 VA 2

2 LTG - BLDG 25 CLC RES COVES 1 156 VA 2

1 LTG - BLDG 25 CORR 1 480 VA 1

CKT Circuit Description # of

Poles Load Remarks

Enclosure: NEMA 1 Mounting: SURFACE Wires: 2

Supply From: NL1 Phases: 1 Location: ELEC 2520 Volts: 120V Single

Panel: LCP

J

J

J

J

J

J

J

J

J

J

EP101

FIRE/WATER

SRVC

CLEAN EQUIP.

CLEAN UTILITY

RESIDENT

(BARIATRIC)

2529 RESIDENT

RESIDENT

RESIDENT

RESIDENT

RESIDENT

MED. STO.

RESIDENT

(BARIATRIC)

RESIDENT

RESIDENT

RESIDENT

RESIDENT

RESIDENT

STAIR 1

IT

STAFF REPORT

ROOM

MEN

WOMEN

NURSE ADMIN.

LOUNGE

CORRIDOR

CORRIDOR

CORRIDOR

SRVC CORR.

FAMILY

FOYER

LIVING ROOM

CORRIDOR

CLEAN LINEN

DEN

DINING

SERVERY

GROUP ROOM

ELECT.

HSKPG

STORAGE

SOILED UTILITY

RESIDENT

LAUNDRY

SPA

2512 PANTRY

2510A

PRODUCTION

KITCHEN

HOME OFFICE

2508A

CORRIDOR

CORRIDOR

CORRIDOR

CRL1 - 1

NL1 - 1

NL1 - 2

CRL1 - 2

NL1 - 3

NL1 - 4

CRL1 - 4

NL1 - 7

NL1 - 8

CRL1 - 5

NL1 - 9

NL1 - 10

CRL1 - 6

NL1 - 11

NL1 - 12

CRL1 - 7

NL1 - 13

NL1 - 14

CRL1 - 8

NL1 - 15

NL1 - 16

CRL1 - 9

NL1 - 17

NL1 - 18

CRL1 - 10

NL1 - 19

NL1 - 20

CRL1 - 11

NL1 - 21

NL1 - 22

CRL1 - 12

NL1 - 23

NL1 - 24

EP101

G G

AC,G

AC,G

G

G

AC,G

AC

EP101

COPIER

AC

FRIDGE

MICROWAVE

AC,GFI

COFFEE

AC,GFI

FRIDGE

+36"

EP101

AC

AC

AC

AC

R

Q

P

L

M

K

J

H

G

F

E

D

B

A

1 2 3 4 5 6 7 9 12 13 14 158

C

N

S

N.1

D.4

12.6

'X25-SD'

AREA

AREA

A

B

'X25'

CART

+48"

CART

+48"

NL1 - 26,28

DRYER

+48"

WASHER

GFI, +48"

NL1 - 30

NL1 - 31

NL1 - 33

NL1 - 35

NL1 - 32

CRL1 - 13

CRL1 - 21

NL1 - 25

NL1 - 27

NL1 - 29

NL1 - 34

G

NL1 - 36

NL1 - 37

NL1 - 39

NL1 - 38

NL1 - 42

CRL1 - 19

CRL1 - 17CRL1 - 23

NL1 - 43

NL1 - 47

NL1 - 44

NL1 - 46

NL1 - 48

NL1 - 49

NL1 - 45

TV +72"

TV +72"

TV +72"

NL1 - 41

EP101

TV +72"

TV +72"

TV +72"

TV +72"

LSL1 - 2

LSL1 - 2

LSL1 - 4

P1

(TYP.)

SPA TUB

NL1 - 55

NL1 - 59 FIREPLACE

(VERIFY)

EQL1 - 1

FCU-2

EQL1 - 1

FCU-3

NL1 - 61

DBF-1

CRL1 - 25 CRL1 - 27

MISC. +48"

(TYP.)

MISC. +48"

MISC. +48"

EY101

WP,G

WP,G

NL1 - 72

NL1 - 72

CRL1 - 29

CRL1 - 31

9 11

T

U

V

W

Z

8.6 11.3

Y

AREA

AREA

A

B

LSL1 - 6

LSL1 - 6

LSL1 - 4

P3

STAIR 4

S4

PASSAGE

C1-3E

EQL1 - 1

FCU-1

P10

BLDG 25 BLDG 12

EP101

MECHANICAL

ELEC.

E

D

2 3 4 5 6 7 98

C

D.4

EQH1 - 2,4,6

MAC-1

EQH1 - 7,9,11

MVS-1

EQL1 - 3,5,7

HWP-1

EQL1 - 2,4,6

HWP-2

EQL1 - 9

DHWP-1

EQL1 - 9

DHWP-2

EQL1 - 11

CRV-1

EQH1 - 8,10,12

AHU-1

EQH1 - 13,15,17

RF-1

EQL1 - 23

CRV-2

EQL1 - 20,22

SSU-1

EQL1 - 24,26

SSU-2

WP,G

EQH1 - 19,21,23

EF-1

NL1 - 53

NL1 - 53

NL1 - 53

NL1 - 53

EP501

EF-3

NL2 - 25

EF-2

NL1 - 6

+8"

+6" BELOW CLG

CRL1 - 3

AC,G

NL1 - 5

+36"

+60"

B

A

C

+36"

'CRL1''NL1'

E

5 6 7

'LSL1'

CRL1 - 20NL1 - 51

'LCP'

'NL2'

AC,G

AC,G

G

FRIDGE +36"

FRIDGE +36"

MICROWAVE

AC,GFI

G

NL2 - 2,4

DISH

NL2 - 1,3

RANGE

NL2 - 5,7

RANGE

COFFEE

AC,GFI

ICE

AC,GFI

FRIDGE +36"

AC,G

NL2 - 15,17

HOT4

MICROWAVE +24"

GFI

AC,G

F

E

D.4

NL2 - 14

NL2 - 9

NL2 - 11

NL2 - 10

NL2 - 19

NL2 - 13

NL2 - 12

NL2 - 22

NL2 - 20

NL2 - 8

NL2 - 6

NL2 - 21

DISHWASHER

NL2 - 23

EP501

FOOD CART

GFI, +48"

NL2 - 24

+48"

B

A

C

AC,G

CART

GFI, +48"

CART

GFI, +48"

OMNICELL

+48"

OMNICELL

+48"

OMNICELL

+48"

CRL1 - 15

CRL1 - 14

FRIDGE

AC, G

FREEZER

CRL1 - 18

CRL1 - 16

NL1 - 40

G

D

6 7 98

C

'TSLS''TSCR''TSEQ'

'EQL1'

'XLSL1'

'XEQL1'

'XLSL1-PD'

'XLSL1-SD'

'XCRL1'

15 KVA 30 KVA 75 KVA30 KVA

'XNL1'

'XCRL1-PD'

'XCRL1-SD'

'XNL1-SD'

45 KVA

'XNL2'

'XNL2-SD'

'25NH1'

'EQH1'

'MGB'

'25EH1'

150A 60A 30A

'METER'

'ESPD'

'NSPD'

(BOTTOM)

(MIDDLE)

(TOP)

EQL1 - 24,26

SS-2

CRL1 - 22

NL1 - 50

D

3 4

C

EQL1 - 20,22

SS-1

'TMGB'

CRL1 - 36

CRL1 - 38

P9

CRL1 - 32

CRL1 - 32

CRL1 - 34

NL1 - 70

CRL1 - 40

CRL1 - 42

+48"

+48"

+48"

+48"

CRL1 - 32

1 2 3

NL1 - 57

EQL1 - 8,10,12

CRV-3

EQL1 - 13,15,17

CWP-1

EQL1 - 14,16,18

CWP-2

SUMP PUMP

EQL1 - 21

Drawing Title

Approved:

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management on e ei gh th fo ot th re e in fo ot 6"

6" on e an d on e ha lf in fo ot on e fo ot

6" 6" th re e qu ar te rs fo ot on e ha lf fo ot th re e ei gh th s fo ot on e qu ar te r fo ot

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

TSA PROJECT

NO.:

Department of Veterans Affairs

CONSTRUCT CLC

COTTAGES - COTTAGE 1

636-123

3600 30TH ST. DES MOINES, IA

4/13/2018

FLOOR PLANS & TUNNEL - POWER

BTF MTB

EP101

88 97 06054.032

REF. NOTES ( ):X

P1 INDICATES CIRCUITS SERVING RESIDENT ROOM.

P3 CONNECT DOOR OPERATOR TO PNL R1S-G-1 (LIFE SAFETY).

P9 PROVIDE L5-30R LOCKING RECEPTACLE AND MOUNT TO BOTTOM OF

CABLE TRAY. (TYP. 2)

P10 .CONNECT CABINET UNIT HEATER TO EXISTING WIRING.

NORTHKEY PLAN

E X

E

N

N E

L

EXIS

T C

HILLER TUNNEL

1W

SCALE: 1/8" = 1'-0"

FIRST FLOOR PLAN - AREA A - POWER

SCALE: 1/8" = 1'-0"

FIRST FLOOR PLAN - AREA B - POWER

SCALE: 1/8" = 1'-0"

ATTIC - POWER

SCALE: 1/4" = 1'-0"

ENLARGED PLAN - TYP. RESIDENT ROOM - POWER

SCALE: 1/4" = 1'-0"

ENLARGED PLAN - ELEC 2520 - POWER

SCALE: 1/4" = 1'-0"

ENLARGED PLAN - KITCHEN AREA - POWER

SCALE: 1/4" = 1'-0"

ENLARGED PLAN - MED. STO. 2517 - POWER

SCALE: 1/4" = 1'-0"

ENLARGED PLAN - ELEC 2551 - POWER

SCALE: 1/4" = 1'-0"

ENLARGED PLAN - IT 2537 - POWER

SCALE: 1/8" = 1'-0"

TUNNEL - POWER

FIN. GRADE

3" 3"

3" 3"

EQUAL

EQUAL

NOTE 1

3"

4"

3"

3" 3"

NOTES:

1. TOP OF DUCT BANK TO BE A MINIMUM OF 24" BELOW FINISHED GRADE.

2. PROVIDE CONTINUOUS STRIP OF WARNING TAPE WITHIN 3" OF CENTERLINE OF DUCT BANK. PROVIDE MULTIPLE STRIPS OF

WARNING TAPE WHERE DUCT BANK WIDTH EXCEEDS 16" OVERALL.

3. PROVIDE LONG SWEEPS (HORIZONTALLY AND VERTICALLY) WITH MINIMUM RADII EQUAL TO SIX TIMES CONDUIT DIAMETER.

MAXIMUM OF TWO 90 DEGREE BENDS BETWEEN PULL POINTS

4. TRANSITION FROM RNC TO GRC FOR FINAL 5' AND PAINT WITH ASHPALTIC PAINT.

5. PROVIDE 5-DEGREE ANGLE COUPLINGS FOR SMALL CHANGES IN DIRECTION.

6. REFER TO SPEC SECTION 260541 FOR ENCASEMENT REQUIREMENTS.

NOTE 2

DUCT SPACER (TYP.)

NOTE 3

NOTE 4

NOTE 6

NATIVE BACKFILL

NOTE 5

CONCRETE

1'-0" 1'-0"

2'-0"5'-0" 6"

N G

TERMINAL

BAR

A B C

SUPPLY-SIDE

BONDING

JUMPERS

ISOLATED NEUTRAL

TERMINAL

NEAREST

GROUNDING

ELECTRODE

TRANSFORMER

SYSTEM BONDING JUMPER

GROUNDING

ELECTRODE

CONDUCTOR

EQUIPMENT GROUNDING CONDUCTOR

120VAC FIRE SUPPRESSION HOOD

R

208VAC

POWER DISCONNECT BOX

(NEMA 14-50R INCLUDED)

NOTES:

1. POWER DISCONNECT BOX, ADA CONTROLS, AND

CLOCKBOX / DIGITAL TIMER, PROVIDED AS PART

OF HOOD PACKAGE.

2. ELECTRICAL CONTRACTOR TO MAKE ALL FINAL

CONNECTIONS.

3. CONNECT HOOD FIRE ALARM CONTACTS TO FIRE

ALARM CONTROL PANEL.

4. REFER TO MANUFACTURER'S INSTALLATION

INSTRUCTIONS FOR DETAILS.

(8') POWER DISCONNECT CABLE

ADA

CONTROLS

TO EXHAUST FAN

(25') PLENUM CABLE

(8') SHIELDED

CONTROL WIRING

FA

CONTRACTOR FURNISHED

CONTRACTOR INSTALLED

MANUFACTURER FURNISHED

CONTRACTOR INSTALLED

(8') 110 VAC SUPPLY CABLE

CLOCK

BOX

DIGITAL

TIMER

(20') SHIELDED

CONTROL WIRING

KH-2

EF-3

RANGE

INSULATORS (TYP. 2)

BOLT TO WALL

ANCHOR BOLTS

COPPER GROUND BAR

WALL MOUNTING BRACKET

MGB

ERICO EGBA14A24MMT

1' -0

2'-0"

4"

1"

2" 3"

6"

1' -0

1'

-6

12"Ø PIER - TYP.

V E

R

IF

Y W

/ S T

R U

C

5' -0

M

IN

#4 BARS @ 12" O.C.

EA. WAY, TOP & BOT.

12"Ø CONC. PIERS

W/ (4) #6 VERT. BARS

& #3 TIES @ 12" O.C.

3/4" CHAMFER

ALL AROUND CONC. SLAB

NOTE:

VERIFY DEPTH OF PIERS TO

BE AT LEAST 2'-0" BELOW

LOCAL FROST DEPTH.

TYP.

8"3"

3"

OPENING

(8) #4 - 2'-0" BARS @ 45° -

(2) EA. CORNER

(8) #4 - 7'-0" BARS -

(2) EA. SIDE OF OPENING

CONCRETE REQUIREMENTS:

SLAB & PIERS TO BE MADE OF

CONCRETE WITH A MINIMUM

28 DAY STRENGTH OF 4,000 PSI

AND 5% AIR CONTENT

6"

2' -6

1'

-6

1'-6" 1'-6"

7'-6"

7' -6

4'-2"1'-8" 1'-8"

4'-6"

Drawing Title

Approved:

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management on e ei gh th in ch o ne fo ot

B

A

C

D

E

F th re e in ch es o ne fo ot 6"

6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot

6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

TSA PROJECT

NO.:

Department of Veterans Affairs

CONSTRUCT CLC

COTTAGES - COTTAGE 1

636-123

3600 30TH ST. DES MOINES, IA

4/13/2018

DETAILS - POWER

BTF MTB

EP501

89 97 06054.032

1 Revision 1 Date 1

SCALE: NOT TO SCALE

UNDERGROUND RACEWAY INSTALLATION DETAIL

SCALE: NOT TO SCALE

SEPARATELY DERIVED SYSTEM

SCALE: NOT TO SCALE

RESIDENTIAL RANGE SUPPRESSION WIRING DIAGRAM

SCALE: NOT TO SCALE

GROUND BAR - DETAIL

SCALE: 3/4" = 1'-0"

TRANSFORMER PAD DETAIL

Drawing Title

Approved:

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management on e ei gh th in ch o ne fo ot

B

A

C

D

E

F th re e in ch es o ne fo ot 6"

6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot

6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

TSA PROJECT

NO.:

Department of Veterans Affairs

CONSTRUCT CLC

COTTAGES - COTTAGE 1

636-123

3600 30TH ST. DES MOINES, IA

4/13/2018

SCHEDULES AND DIAGRAMS - NORMAL PANEL

SCHEDULES

BTF MTB

EP601

90 97 06054.032

1. VERIFY BREAKER AND WIRE SIZE WITH MANUFACTURER.

Notes:

Total Feeder Current: 228 A

Continuous Current @ 125%: 122 A EQP_NON CONT 58574 VA 100.00% 58574 VA Non-Cont. Current @ 100%: 107 A

EQP_CONT 70045 VA 100.00% 70045 VA

REC 50580 VA 59.89% 30290 VA Total Est. Demand Current: 204 A LTG 10824 VA 100.00% 10824 VA Total Est. Demand: 169733 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 240 A 220 A 229 A Total Load: 66114 VA 60905 VA 63004 VA

29 SPACE -- -- 0 0 30

27 SPACE -- -- 0 0 28

25 SPACE -- -- 0 0

3 60 A NSPD (NOTE 1)

23 SPARE 20 A 1 0 0 24

21 SPARE 20 A 1 0 0 22

19 SPARE 20 A 1 0 0

3 125 A SPARE

17 1500 0 18 15 1346 0 16

TSLS 25 A 3

1749 0

3 125 A SPARE

11 9291 12000 12 9 7588 11860 10

TSCR 50 A 3

9504 14520

3 70 A XNL2

5 22893 17321 6 3 22865 17246 4

TSEQ 125 A 3

23885 16457

3 125 A XNL1

CKT Circuit Description Trip P A B C P Trip Circuit Description CKT

Enclosure: NEMA 1 FCB / MCB Rating: 350 A Mounting: SURFACE Wires: 4 Mains Rating: 400 A

Supply From: X25-SD Phases: 3 FCB / MCB: MCB Location: ELEC 2551 Volts: 480Y/277V A.I.C. Rating: 18,000

Branch Panel: 25NH1

1. PROVIDE SHUNT TRIP AND INTERLOCK WITH SUPPRESSION SYSTEM.

2. LOCATE STARTER IN KITCHEN AND INTERLOCK WITH SUPPRESSION SYSTEM.

Notes:

Total Feeder Current: 110 A

Continuous Current @ 125%: 15 A Non-Cont. Current @ 100%: 94 A

EQP_NON CONT 32900 VA 100.00% 32900 VA

EQP_CONT 4400 VA 100.00% 4400 VA Total Est. Demand Current: 107 A REC 1080 VA 100.00% 1080 VA Total Est. Demand: 38380 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 121 A 99 A 100 A Total Load: 14520 VA 11860 VA 12000 VA

41 SPACE -- -- 0 0 1 20 A SPARE 42

39 SPACE -- -- 0 0 1 20 A SPARE 40

37 SPACE -- -- 0 0 1 20 A SPARE 38

35 SPACE -- -- 0 0 1 20 A SPARE 36

33 SPACE -- -- 0 0 1 20 A SPARE 34

31 SPACE -- -- 0 0 1 20 A SPARE 32

29 SPACE -- -- 0 0 1 20 A SPARE 30

27 SPACE -- -- 0 0 1 20 A EQP - KH-1 / LIGHTS 120V 28

25 EQP - EF-2 NOTE 2 20 A 1 500 0 1 20 A EQP - KH-2 / EF-3 120V 26

23 EQP - DISHWASHER (LOCKABLE BKR) 20 A 1 1200 1000 1 20 A EQP - FOOD CART 24

21 EQP_CONT - FRIDGE (GFI BKR) 20 A 1 800 180 1 20 A REC - SERVING COUNTER 22

19 REC - KITCHEN/DINING GENERAL 20 A 1 360 180 1 20 A REC - SERVING COUNTER 20

17 2400 0 1 20 A SPARE 18

EQP - HOT WELL (LOCKABLE BKR) 30 A 2

2400 0 1 20 A SPARE 16

13 REC - KITCHEN COUNTER 20 A 1 180 800 1 20 A EQP_CONT - FRIDGE (GFI BKR) 14

11 EQP - MICROWAVE 20 A 1 1200 1200 1 20 A EQP - MICROWAVE (GFI BKR) 12

9 REC - KITCHEN COUNTER 20 A 1 180 800 1 20 A EQP_CONT - FRIDGE (GFI BKR) 10

7 4000 1000 1 20 A EQP_CONT - COFFEE MAKER 8

EQP - RANGE (GFI BKR) 50 A 2

4000 1000 1 20 A EQP_CONT - ICE MACHINE 6

3 4000 3500 4

EQP - RANGE (GFI BKR) NOTE 1 50 A 2

4000 3500

2 45 A EQP - DISHWASHER (LOCKABLE BKR)

CKT Circuit Description Trip P A B C P Trip Circuit Description CKT

Enclosure: NEMA 1 FCB / MCB Rating: 175 A Mounting: SURFACE Wires: 4 Mains Rating: 225 A

Supply From: XNL2-SD Phases: 3 FCB / MCB: FCB (MLO) Location: PRODUCTION KITCHEN 2510 Volts: 208Y/120V A.I.C. Rating: 10,000

Branch Panel: NL2

1. BALANCE RELAY LOADS BETWEEN PHASES TO EXTENT POSSIBLE.

Notes:

Total Feeder Current: 116 A

Continuous Current @ 125%: 32 A EQP_NON CONT 8777 VA 100.00% 8777 VA Non-Cont. Current @ 100%: 84 A

EQP_CONT 2800 VA 100.00% 2800 VA

REC 33120 VA 65.10% 21560 VA Total Est. Demand Current: 110 A LTG 6327 VA 100.00% 6327 VA Total Est. Demand: 39464 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 137 A 145 A 145 A Total Load: 16457 VA 17246 VA 17321 VA

83 SPACE -- -- 0 0 1 20 A SPARE 84

81 SPACE -- -- 0 0 1 20 A SPARE 82

79 SPACE -- -- 0 0 1 20 A SPARE 80

77 SPACE -- -- 0 0 1 20 A SPARE 78

75 SPACE -- -- 0 0 1 20 A SPARE 76

73 SPACE -- -- 0 0 1 20 A SPARE 74

71 SPACE -- -- 0 360 1 20 A REC - EXTERIOR GENERAL 72

69 SPACE -- -- 0 180 1 20 A REC - IT 2537 70

67 SPACE -- -- 0 0 1 20 A LCP POWER SUPPLY 68

65 SPACE -- -- 0 0 1 20 A LCP RELAYS (NOTE 1) 66

63 SPACE -- -- 0 1642 1 20 A LCP RELAYS (NOTE 1) 64

61 EQP - DBF-1 20 A 1 77 1140 1 20 A LTG - RES. RM 2505,2507,2509,2511,2513,2515 62 59 EQP_CONT - FIREPLACE 20 A 1 1000 1140 1 20 A LTG - RES. RM 2519,2521,2523,2525,2527,2529 60

57 REC - TUNNEL 20 A 1 180 103 1 20 A LTG - ELEC 2520 / 2551 58

55 EQP - SPA TUB (LOCKABLE / GFI BKR) 15 A 1 1000 100 1 20 A LTG - TUNNEL 56

53 REC - MECHANICAL 20 A 1 720 821 1 20 A LTG - MECHANICAL / STAIRWELL (NORMAL) 54

51 REC - ELEC 2520 20 A 1 180 1381 1 20 A LTG - FIRST FLOOR 52

49 REC - FOYER DESK 20 A 1 720 180 1 20 A REC - ELEC 2521 50

47 REC - FAMILY 20 A 1 720 900 1 20 A REC - FOYER DESK 48

45 REC - LIVING 20 A 1 900 900 1 20 A REC - SERVICE CORRIDOR 46

43 REC - DINING 20 A 1 540 720 1 20 A REC - FOYER 44

41 REC - GROUP 20 A 1 720 360 1 20 A REC - HOME OFFICE 42

39 REC - HSKPG/LINEN 20 A 1 360 360 1 20 A REC - MED 40

37 REC - SOILED 20 A 1 180 720 1 20 A REC - EAST CORRIDORS 38

35 REC - WEST CORRIDORS 20 A 1 1260 540 1 20 A REC - FIRE/EQUIP/UTILITY 36

33 REC - SPA GENERAL 20 A 1 360 720 1 20 A REC - TLT/STAFF GENERAL 34

31 REC - LAUNDRY COUNTER 20 A 1 360 540 1 20 A REC - NURSE 32

29 EQP_CONT - STAFF FRIDGE 20 A 1 800 1500 1 20 A EQP - WASHING MACHINE 30

27 EQP_CONT - STAFF COFFEE MAKER 20 A 1 1000 2500 28

25 EQP - STAFF MICROWAVE 20 A 1 1200 2500

2 30 A EQP - DRYER (GFI BKR)

23 REC - RESIDENT 2505 20 A 1 720 900 1 20 A REC - RESIDENT 2505 24

21 REC - RESIDENT 2507 20 A 1 720 900 1 20 A REC - RESIDENT 2507 22

19 REC - RESIDENT 2509 20 A 1 720 900 1 20 A REC - RESIDENT 2509 20

17 REC - RESIDENT 2511 20 A 1 720 900 1 20 A REC - RESIDENT 2511 18

15 REC - RESIDENT 2513 20 A 1 720 900 1 20 A REC - RESIDENT 2513 16

13 REC - RESIDENT 2515 20 A 1 720 900 1 20 A REC - RESIDENT 2515 14

11 REC - RESIDENT 2519 20 A 1 720 900 1 20 A REC - RESIDENT 2519 12

9 REC - RESIDENT 2521 20 A 1 720 900 1 20 A REC - RESIDENT 2521 10

7 REC - RESIDENT 2523 20 A 1 720 900 1 20 A REC - RESIDENT 2523 8

5 REC - RESIDENT 2525 20 A 1 720 900 1 20 A REC - RESIDENT 2525 6

3 REC - RESIDENT 2527 20 A 1 720 900 1 20 A REC -…