Bldg 25 Electrical.pdf
PDF 3 MB Posted
- Attached to
- Y1DA--PN: 636A6-26-201, Patient Ceiling Lifts Install & Testing (DM) AP: 36C263-26-AP-1431
- Solicitation number
- 36C26326R0059
About this file
This is a comprehensive set of electrical construction drawings and specifications for a renovation project at a VA Des Moines facility involving multiple buildings (Buildings 1, 1W, 12, and 25) and steam/utility tunnels. The project includes new electrical systems for an approximately 60,000+ square foot area with resident rooms, medical facilities, kitchens, and support spaces.
The scope encompasses complete electrical infrastructure including power distribution from transformers (15KV primary loop systems with redundancy), panelboards rated from 60A to 400A, lighting systems with occupancy sensors and dimmers, emergency/exit lighting, fire alarm systems with multiple zones and loops, nurse call systems, access control and door operator systems, telecom infrastructure with data outlets and fiber optic cables, voice/data cabling with cable trays, security camera systems, and medical equipment connections. Specific equipment includes HVAC units, pumps, compressors, fans, domestic hot water systems, split system cooling units, and various receptacles rated for 120V to 480V service. The designs mandate dual-technology occupancy sensors, manual-on/automatic-off lighting control, all conduit minimum 3/4" diameter, plenum-rated cables, fire-rated wall penetration sealing, and coordination with mechanical systems and phasing plans. Construction documents reference panelboard schedules (EP601/EP602), luminaire schedules (EL601), architectural reflected ceiling plans, and require contractor verification of existing conditions, circuit information, and proper restoration of surfaces affected by demolition work, with the owner retaining rights to salvageable materials and contractor responsible for PCB ballast and hazardous lamp removal.
View the file
Other files
Show all 42
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A. SEE ARCHITECTURAL SHEETS FOR EXACT AREAS AND WALLS
AFFECTED BY THE DEMOLITION AND REMODEL.
B. DEMOLITION SHOWN IS AS REQUIRED FOR THE COMPLETE PROJECT.
THE CONTRACTOR SHALL COORDINATE THE DEMOLITION EFFORT PER
THE PHASING PLANS. COORDINATE DEMOLITION WITH THE WORK OF
OTHER TRADES. PROVIDE TEMPORARY POWER AND LIGHTS AS
REQUIRED TO ALLOW THE WORK OF OTHER TRADES TO PROCEED OR
AS REQUIRED TO ALLOW THE OWNER TO OCCUPY THE SPACE.
C. ALL OF THE EQUIPMENT AND DEVICES SHOWN ON THIS DRAWING ARE
EXISTING. THE LOCATIONS OF THE EQUIPMENT AND DEVICES WERE
OBTAINED FROM EXISTING DRAWING AND FIELD INVESTIGATION. THE
LOCATIONS OF THE EXISTING EQUIPMENT AND DEVICES ARE SHOWN
FOR THE CONVENIENCE OF THE CONTRACTOR. ACCURACY OF THE
INFORMATION SHOWN IS NOT GUARANTEED. THE CONTRACTOR IS
RESPONSIBLE FOR THE VERIFICATIONS OF ALL EXISTING CONDITIONS
PRIOR TO SUBMITTING BIDS. SITE VISITS PRIOR TO SUBMISSION OF
BIDS NEED TO BE FULLY COORDINATED WITH THE OWNER.
D. CIRCUIT INFORMATION FOR ALL AFFECTED CIRCUITS SHALL BE
VERIFIED PRIOR TO COMMENCING WORK. ACCURACY OF THE
INFORMATION SHOWN AND INCLUDED ON THE PANEL SCHEDULES IS
NOT GUARANTEED.
E. LUMINAIRES AND DEVICES INDICATED TO BE REMOVED, WHICH ARE
LOCATED ON CEILINGS OR WALLS, SHALL HAVE LUMINAIRES, DEVICE
AND ALL ASSOCIATED CIRCUIT WIRING AND CONDUIT REMOVED BACK
TO NEAREST JUNCTION BOX, OR DEVICE NOT INDICATED TO BE
REMOVED. ACTUAL CIRCUITING MUST BE DETERMINED IN THE FIELD.
THE CONTRACTOR SHALL PROVIDE ALL NECESSARY WIRE, CONDUIT,
DEVICES AND CONNECTIONS NECESSARY TO ENSURE CIRCUIT
CONTINUITY OF THE REMAINING DEVICES.
F. THE OWNER HAS THE RIGHT TO RETAIN ALL SALVAGEABLE MATERIAL.
ANY MATERIAL THE OWNER CHOOSES NOT TO ACCEPT SHALL BE
REMOVED FROM THE SITE AND PROPERLY DISPOSED OF BY THE
CONTRACTOR. CONTRACTOR IS RESPONSIBLE FOR THE REMOVAL OF
ANY PCB BALLAST OR HAZARDOUS LAMPS.
G. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE
LABELING OF SPARE OR ABANDONED CIRCUITS AND/OR CIRCUIT
BREAKERS IN ALL PANELS AFFECTED BY THE DEMOLITION. SPARE
CIRCUITS AND/OR CIRCUIT BREAKERS MAY BE REUSED FOR THE
CIRCUITING OF THE NEW OR REMODELED AREA AS SPACE AND PANEL
LOADING WILL ALLOW.
H. THE CONTRACTOR SHALL BE HELD FULLY RESPONSIBLE FOR THE
PROPER RESTORATION OF ALL EXISTING SURFACES REQUIRING
PATCHING, PLASTERING, PAINTING AND/OR OTHER REPAIR DUE TO
THE DEMOLITION WORK DONE BY THE ELECTRICAL CONTRACTOR,
UNDER THE TERMS OF THIS SPECIFICATION. CLOSE AND SEAL ALL
OPENINGS, REPAIR ALL SURFACES, ETC., AS REQUIRED.
I. SEE PHASING PLAN.
J. EXISTING FIRE ALARM DEVICES, EMERGENCY LIGHTS AND EXIT SIGNS
SHALL BE COMPLETE AND OPERABLE AT ALL TIMES. PROVIDE
TEMPORARY DEVICES IN AREAS BEING WORKED ON TO ALLOW FOR A
WORKABLE SYSTEM DURING CONSTRUCTION.
K. PROTECT EXISTING FURNITURE, CARPET AND OTHER
APPURTENANCES FROM DAMAGE DURING THE COURSE OF
CONSTRUCTION. REPLACE DAMAGED ITEMS FREE OF COST TO THE
OWNER.
L. ITEMS WHICH ARE INTENDED TO BE REMOVED, RELOCATED, OR
SALVAGED ARE SHOWN AS FULL-TONE LINES ON DEMO PLANS. ALL
OTHER ITEMS ARE INTENDED TO REMAIN IN PLACE AND ARE SHOWN
AS HALF-TONE.
A. COORDINATE LOCATION OF SWITCH HEIGHTS WITH CASEWORK,
FURNITURE AND EQUIPMENT LAYOUTS PRIOR TO ROUGH-IN. SEE
ARCHITECTURAL CASEWORK ELEVATIONS FOR CABINET HEIGHTS
AND LAYOUTS.
B. ALL OCCUPANCY SENSORS AND OCCUPANCY SENSOR SWITCHES
SHALL BE DUAL TECHNOLOGY (INFRARED AND ULTRASONIC).
OCCUPANCY SENSORS DO NOT SHOW RELAYS AND TOTAL WIRING
REQUIRED FOR PROPER OPERATION. PROVIDE A COMPLETE AND
FULLY FUNCTIONAL SYSTEM.
C. EMERGENCY, EXIT, AND NIGHT LIGHTS IN PATHS OF EGRESS SHALL
BE CONNECTED TO AN UNSWITCHED HOT LEG OF CIRCUIT SHOWN
UNLESS NOTED OTHERWISE.
D. ALL AREAS SHALL BE MANUAL-ON / AUTOMATIC-OFF UNLESS NOTED
OTHERWISE. AUTOMATIC-ON / AUTOMATIC-OFF PERMITTED IN
BATHROOMS AND SECURITY AREAS.
A. ALL DEVICES SHOWN SHALL BE MOUNTED AT 18" A.F.F. UNLESS
INDICATED OTHERWISE.
B. EACH LOW VOLTAGE CABLE SHALL HAVE INDIVIDUAL RUN BACK TO
TERMINATION POINT IN IT CLOSET. LEAVE 10' SERVICE DROP FOR
EACH HOMERUN.
C. ALL AUXILIARY CABLE ABOVE CEILING SHALL BE PLENUM RATED
WHERE REQUIRED.
D. CEILING MOUNTED DEVICES SHALL BE CENTERED IN CEILING TILE
WHERE INSTALLED IN ACOUSTICAL TILE CEILING.
E. PROVIDE 120 VOLT POWER CIRCUIT(S) FOR AUXILIARY SYSTEMS AS
REQUIRED FOR COMPLETE AND OPERATIONAL SYSTEMS.
A. DRAWINGS DO NOT SHOW TOTAL NUMBER OF CONDUCTORS FOR
CIRCUITS REQUIRED. PROVIDE THE NUMBER OF CONDUCTORS
NEEDED TO COMPLETE INSTALLATION OF SPECIFIC EQUIPMENT
FURNISHED. A GREEN GROUND CONDUCTOR, SIZED PER NEC, SHALL
ALSO BE INCLUDED IN EACH CIRCUIT. ADJUST CONDUCTOR SIZES AS
NEEDED TO LIMIT VOLTAGE DROP TO LEVELS RECOMMENDED BY
NEC. THE CONTRACTOR SHALL ALSO COORDINATE INSPECTIONS
WITH THE AHJ.
B. SEE SHEET EL601 FOR LUMINAIRE SCHEDULE.
C. SEE SHEETS EP601 & EP602 FOR PANELBOARD SCHEDULES.
D. SEE ARCHITECTURAL SHEETS FOR REFLECTED CEILING PLANS.
E. NO BOXES SHALL BE MOUNTED BACK-TO-BACK.
F. CONTRACTOR TO SEAL ALL PENETRATIONS THROUGH FIRE OR
FIRE/SMOKE RATED WALLS AND FLOORS.
G. ALL RACEWAYS SHALL BE SEALED AS REQUIRED BY AND IN
ACCORDANCE WITH NEC AND NFPA.
H. CABLE AND CONDUIT SHALL NOT INTERFERE WITH EQUIPMENT
ACCESS.
I. ALL CABLING ABOVE CEILING SHALL BE PROPERLY SUPPORTED (NOT
FROM CEILING SYSTEM).
J. IN VIEWING THESE DRAWINGS, THE CONTRACTOR SHALL PAY CLOSE
ATTENTION TO THE MATCH LINES. SOME WORK AND NOTE
REFERENCES MAY BE REPEATED, BUT DO NOT ALWAYS SHOW ON
BOTH SIDES OF THE MATCH LINE.
K. CONTRACTOR SHALL COORDINATE FINAL PANEL DIRECTORIES WITH
OWNER.
L. COORDINATE ALL TUNNEL WORK WITH VA COR.
A. ALL ELECTRICAL CONDUITS SHALL BE A MINIMUM OF 3/4" DIAMETER.
B. SIGNAL CABLES SHALL BE ROUTED IN CABLE TRAY OR CONDUITS,
MINIMUM OF 3/4" DIAMETER.
C. ALL ELECTRICAL DISTRIBUTION PANELS SHALL BE LABELED WITH
RESPECTIVE POWER SOURCE INFORMATION (CIRCUIT FEEDING IT).
ARC FLASH LABELS SHALL BE ADDED TO COMPLY WITH CODE
REQUIREMENTS AND ARC FLASH STUDY.
D. LABEL THE COVER PLATES OF ALL ELECTRICAL RECEPTACLES BOTH
INSIDE AND OUTSIDE WITH RESPECTIVE CIRCUIT NUMBER.
E. ALL FIRE ALARM HORNS AND STROBES SHALL BE RED IN COLOR AND
BE WALL-MOUNTED.
F. NEW EQUIPMENT SHALL BE ASSESSED FOR LOCKOUT-TAGOUT
REQUIREMENTS, AND HAVE A PROCEDURE WRITTEN AND ADDED TO
THE VA CENTRAL IOWA LOTO DATABASE.
G. THESE STANDARDS SHALL BE USED IN TANDEM WITH DRAWINGS AND
SPECIFICATIONS. WHERE CONFLICTS OCCUR, LOCAL STANDARDS
SHALL TAKE PRIORITY.
Drawing Title
Approved:
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management
6"
6"
6" 6"
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
TSA PROJECT
NO.:
Department of Veterans Affairs
CONSTRUCT CLC
COTTAGES - COTTAGE 1
636-123
3600 30TH ST. DES MOINES, IA
4/13/2018
ELECTRICAL INFO SHEET
BTF MTB
E000
80 97 06054.032
D1 SECURITY CAMERA TO BE REMOVED AND STORED FOR
RE-INSTALLATION; EXISTING WIRING TO BE PRESERVED.
D2 MANUAL PULL STATION TO BE REMOVED AND STORED FOR
RE-INSTALLATION; EXISTING WIRING TO BE PRESERVED.
D3 PA HORN TO BE REMOVED AND STORED FOR RE-INSTALLATION;
EXISTING WIRING TO BE PRESERVED.
D4 SPEAKER TO BE REMOVED AND STORED FOR RE-INSTALLATION;
EXISTING WIRING TO BE PRESERVED.
D5 SMOKE DETECTOR TO BE REMOVED AND STORED FOR
RE-INSTALLATION; EXISTING WIRING TO BE PRESERVED.
D7 STAIRWELL LIGHTING (INTERIOR / EXTERIOR) TO BE REMOVED
AND STORED FOR RE-INSTALLATION; EXISTING WIRING TO BE
PRESERVED.
D8 REMOVE BACK-TO-BACK CABINET UNIT HEATERS AND DEMO ONE
CIRCUIT BACK TO PNL R1C-G-1; OTHER CIRCUIT WIRING TO BE
PRESERVED.
D9 ABANDONED EQUIPMENT; COORDINATE WITH OWNER PRIOR TO
DEMO AND RETURN TO OWNER.
L1 LOCATE REFLECTOR TO MAXIMIZE LIGHT AT MED CABINET.
L2 PROVIDE PHOTOCELL FOR CONTROL OF CANOPY LIGHTING.
L3 PROVIDE 8-BUTTON OVERRIDE SWITCH FOR CONTROL OF ALL LCP
RELAYS.
L4 PROVIDE 2-BUTTON OVERRIDE SWITCH FOR CONTROL OF
CORRIDOR LIGHTING.
L5 LOCATE SWITCH NEAR TUNNEL ENTRANCE (VERIFY).
L6 INDICATES CIRCUITS SERVING RESIDENT ROOM.
L7 EXISTING STAIRWELL LIGHTING (INTERIOR / EXTERIOR) TO BE
RE-INSTALLED; CONNECT TO EXISTING WIRING.
L8 CONNECT LIGHTING IN CORRIDOR TO EXISTING LIFE SAFETY /
NORMAL CIRCUITS (VERIFY).
L9 SHIFT LIGHTING AS REQUIRED TO AVOID CONFLICTS WITH HVAC
DUCTWORK, PIPING, ETC.
P1 INDICATES CIRCUITS SERVING RESIDENT ROOM.
P2 PROVIDE CONTROL WIRING AS REQUIRED FROM BLDG 25
AUTOMATIC TRANSFER SWITCHES TO GENERATOR MASTER
CONTROL LOCATED IN BUILDING 1W.
P3 CONNECT DOOR OPERATOR TO PNL R1S-G-1 (LIFE SAFETY).
P4 TO CONTRACTOR STAGING AREA. CONTRACTOR SHALL PROVIDE
STEP-DOWN TRANSFORMERS, DISCONNECTS, ETC. AS REQUIRED.
P5 TEMPORARY POWER LOCATION. CONTRACTOR SHALL PROVIDE
BREAKER AS REQUIRED.
P6 PROVIDE 250A BREAKER IN EMERGENCY SWITCHBOARD FOR
SERVING BUILDING 25.
P7 PROVIDE CONNECTIONS AS REQUIRED TO ADD BUILDING 25
AUTOMATIC TRANSFER SWITCHES.
P8 PROVIDE ELECTRIC POWER QUALITY MONITORING METER
COMPLETE WITH MAIN DISPLAY AND (3) FEEDER DISPLAYS (ONE
FOR EACH TRANSFER SWITCH FEEDER). MAIN DISPLAY SHALL BE
CAPABLE OF MONITORING AND DISPLAYING TOTAL BUILDING
LOAD AS WELL AS SUMMATION OF (3) FEEDERS. PROVIDE CTS,
CONTROL WIRING, ETC. AS REQUIRED FOR CONTROL SCHEME.
P9 PROVIDE L5-30R LOCKING RECEPTACLE AND MOUNT TO BOTTOM
OF CABLE TRAY. (TYP. 2)
P10 .CONNECT CABINET UNIT HEATER TO EXISTING WIRING.
P11 MEDIUM VOLTAGE CABLES BETWEEN XFMR 11 AND XFMR 12 TO
BE RE-USED AND CONNECTED BETWEEN XFMR 25 AND XFMR 12.
Y1 EXISTING SECURITY CAMERA TO BE RE-INSTALLED; CONNECT TO
EXISTING WIRING.
Y2 EXISTING MANUAL PULL STATION TO BE RE-INSTALLED; CONNECT
TO EXISTING WIRING.
Y3 EXISTING PA HORN TO BE RE-INSTALLED; CONNECT TO EXISTING
WIRING.
Y4 EXISTING SPEAKER TO BE RE-INSTALLED; CONNECT TO EXISTING
WIRING.
Y5 EXISTING SMOKE DETECTOR TO BE RE-INSTALLED; CONNECT TO
EXISTING WIRING.
Y6 PROVIDE ACCESS CONTROL PER ROUGH-IN DETAIL; CONNECT TO
EXISTING WIRING. PROVIDE ADDITIONAL WIRING, MODULES, ETC.
AS REQUIRED TO CONNECT TO EXISTING CONTROL PANELS
LOCATED IN BUILDING 12 BASEMENT IT CLOSET.
Y7 PROVIDE SMOKE DETECTOR AS REQUIRED AND CONNECT TO
BUILDING 12 FIRE ALARM SYSTEM; MATCH EXISTING.
Y8 CONTRACTOR SHALL VISIT SITE PRIOR TO BID TO LOCATE FINAL
TERMINATION LOCATIONS OF SPECIALTY SYSTEMS IN THIS
SPACE.
Y9 PROVIDE CONNECTIONS AS REQUIRED TO EXTEND CAMPUS FIRE
ALARM LOOP TO BUILDING 25.
Y10 EXTEND EXISTING CABLE TRAY AS SHOWN.
Y11 PROVIDE (2) GANGED EZ PATH SERIES 44 PATHWAYS AT ALL
DOOR CROSSINGS AND ENTRANCES INTO IT ROOMS.
Y12 PROVIDE DUCT DETECTOR AND ACCESSORIES AS REQUIRED TO
SHUTDOWN HVAC EQUIPMENT 2000 CFM OR GREATER PER NFPA
AND AHJ.
E000 ELECTRICAL INFO SHEET
EC001 SITE PLAN - DEMOLITION
EC101 SITE PLAN - ELECTRICAL
EC102 BASEMENT FLOOR PLAN - BUILDINGS 2, 1W, & 1 + STEAM TUNNEL - COMPOSITE
EC103 BASEMENT FLOOR PLAN - BUILDING 12 + STEAM TUNNEL- COMPOSITE
EC104 FIRST FLOOR PLAN - BUILDINGS 25 AND 12 - COMPOSITE
EL101 FLOOR PLANS & TUNNEL - LIGHTING
EL601 SCHEDULES AND DIAGRAMS - LIGHTING
EP101 FLOOR PLANS & TUNNEL - POWER
EP501 DETAILS - POWER
EP601 SCHEDULES AND DIAGRAMS - NORMAL PANEL SCHEDULES
EP602 SCHEDULES AND DIAGRAMS - EMERGENCY PANEL SCHEDULES
EP603 SCHEDULES AND DIAGRAMS - POWER
EY101 FLOOR PLANS - AUXILIARY SYSTEMS
EY102 ROOF PLAN - LIGHTNING PROTECTION
EY501 DETAILS - AUXILIARY SYSTEMS
EY601 SCHEDULES AND DIAGRAMS - AUXILIARY SYSTEMS
EY602 SCHEDULES AND DIAGRAMS - AUXILIARY SYSTEMS
S
TRUE
NORTH
PLAN
NORTH
NORTH
NORTH
ARROW
SYMBOL LEGEND
MATCHLINE
AREA A
AREA B
EXISTING
COLUMN
NEW
COLUMN
X
X
X
SIM
X
XX-XX
XXXX
DX
X
SECTION/
DETAIL
PLAN
DETAIL
REFERENCE
NOTE
REFERENCE
DEMOLITION
NOTE
EQUIPMENT
NUMBER
ROOM NAME
150 SF
ROOM
NUMBER
LETTER
INDICATES NEW
COLUMN LINE
LETTER INDICATES
EXISTING COLUMN
LINE
SECTION/DETAIL NUMBER
SHEET NUMBER
INDICATES DIRECTION OF VIEW
DETAIL NUMBER
SHEET NUMBER
REFERENCE
DESIGNATION
DEMOLITION
DESIGNATION
EQUIPMENT
NUMBER
ROOM NAME DESIGNATION
ROOM NUMBER DESIGNATION
ROOM AREA DESIGNATION
REFERENCE LEGEND
NAME
ELEVATIONLEVEL
TITLE
MARKER
VIEW NAME
SCALE: 1/8" = 1'-
0"
DETAIL NUMBER
LEVEL CALLOUT
DESIGNATION
ELEVATION
DESIGNATION
GRAPHIC AREA FOR
DRAWING
TITLE
SCALE OF THE DRAWING
REF. DEMO NOTES ( )
ELECTRICAL SHEET LIST
PROJECT ELECTRICAL REFERENCED DEMOLITION NOTES
GENERAL NOTES XDXGENERAL DEMO NOTESABBREVIATIONS REF. NOTES ( )
PROJECT ELECTRICAL REFERENCED NOTES
GENERAL LIGHTING NOTES
GEN. POWER & AUX SYSTEMS NOTES
XX-XX
PC
J
J
OS
MS
IC
S
S
M
N
TV
VC
N EA
N SA/CB
N
N 37
N E
G
K1
V
A
R
M
M
T
WALL MOUNTED STRIP LUMINAIRE
SYMBOL NOTES:
PHOTOCELL
VOICE AND DATA
JUNCTION BOX - CEILING MOUNT
JUNCTION BOX - WALL MOUNT
VOICE OUTLET
DATA OUTLET
OCCUPANCY SENSOR
MOTION SENSOR
CEILING FAN
POLE MOUNTED SITE LUMINAIRE
FLOOD LIGHT
NURSE CALL
SPEAKER
PATIENT STATION
INTERCOM SPEAKER STATION
VOLUME CONTROL STATION
MICROPHONE JACK
TELEVISION OUTLET
CCTV CAMERA
SOUND, TELEVISION, AND SECURITY
FUSE
EMERGENCY STATION W/ AUDIO
DISCONNECT SWITCH
2-BUTTON STATION
37 PIN BED RECEPTACLE
DOME LIGHT
MASTER STATION
EMERGENCY GENERATOR
POWER DISTRIBUTION ONE LINE
CONDUIT UP
CONDUIT DOWN
INDICATES BUSHED CONDUIT
VOICE/DATA OUTLET
EMERGENCY STATION
DRAW OUT VACUUM CIRCUIT BREAKER
LIGHTNING SURGE ARRESTOR
THERMAL OVERLOAD RELAY
PLUG-IN OR DRAWOUT CONNECTOR
CIRCUIT BREAKER
FUSED DISCONNECT SWITCH
VOLTMETER
AMMETER
X:Y CURRENT TRANSFORMER - (RATIO)
KIRK KEY INTERLOCK
"C" INDICATES CEILING MOUNTED
"F" INDICATES FLOOR MOUNTED
"S" INDICATES SURFACE MOUNTED
"G" INDICATES GROUND FAULT INTERRUPTING
"IG" INDICATES ISOLATED GROUND
"AC" INDICATES MOUNTING 6" ABOVE COUNTERTOP OR
BACKSPLASH
"WP" INDICATES WEATHERPROOF
"XP" INDICATES EXPLOSION PROOF
"R" INDICATES EXISTING DEVICE REMOVED AND
RELOCATED
LOWER CASE LETTER BY SWITCHES AND FIXTURES
INDICATE ASSOCIATED UNIT FOR SWITCHING
LIGHTING
LUMINAIRE
WALL MOUNTED LUMINAIRE
RECESSED LUMINAIRE
WALL MOUNTED LUMINAIRE
SURFACE MOUNTED LUMINAIRE
TRACK LIGHTING
DIMMER SWITCH
TIMER SWITCH
WIRING DEVICES - SWITCHES
SINGLE POLE SWITCH
KEY OPERATED SWITCH
SINGLE POLE SWITCH WITH PILOT
THERMAL ELEMENT SWITCH
FOUR-WAY SWITCH
TWO POLE SWITCH
THREE-WAY SWITCH
STRIP / INDUSTRIAL LUMINAIRE
LUMINAIRE - NIGHT LIGHT
LUMINAIRE - EMERGENCY SYSTEM
EMERGENCY BATTERY PACK LUMINAIRE
REMOTE EMERGENCY HEAD
WALL WASH LUMINAIRE
PENDANT MOUNTED LUMINAIRE
POWER POLE
METER SOCKET
POWER EQUIPMENT
WIRING DEVICES - RECEPTACLES
COMBINATION STARTER SAFETY SWITCH
RELAY - CONTROL AS NOTED
PUSHBUTTON STATION
MOTOR CONNECTION
SIMPLEX RECEPTACLE
DUPLEX RECEPTACLE
QUADRUPLEX RECEPTACLE
EMERGENCY RECEPTACLE
SPECIAL PURPOSE RECEPTACLE, NEMA
CONFIGURATION NOTED
PLUG-IN STRIP - LENGTH AND QUANTITY
OF OUTLETS AS SHOWN
SAFETY SWITCH
DROP CORD RECEPTACLE ASSEMBLY
FUSIBLE SWITCH (FUSETRON)
PANELS AND CABINETS
DISTRIBUTION PANEL
SWITCHBOARD, SWITCHGEAR, MCC
EQUIPMENT OR TERMINAL CABINET
DRY TYPE TRANSFORMER
BRANCH CIRCUIT PANEL
CONDUIT AND BOXES
HORN (PA, PUBLIC ADDRESS)
TRANSFORMER
EXIT LIGHT - WALL MOUNT WITH
DIRECTIONAL ARROWS AS INDICATED,
FILLED-IN QUARTERS INDICATE
ILLUMINATION SIDES
EXIT LIGHT - CEILING OR PENDANT
MOUNT WITH DIRECTIONAL ARROWS AS
INDICATED, FILLED-IN QUARTERS
INDICATE ILLUMINATION SIDES
EMERGENCY EXIT LIGHT COMBO
LOW VOLTAGE MOMENTARY
CONTACT SWITCH
N TV TV CONNECTION
FB FLOOR BOX
FP FLOOR POKE-THROUGH DEVICE
N M
WIRELESS ACCESS POINT
S S2
S3
S4
SD
SK
SP
STE
ST
SFT
X
CONTROLLED RECEPTACLE
WB WALL AV BOX
F
F
F
F
FS
D
PS
TS
DH
STROBE
HORN
MANUAL PULL STATION
HORN STROBE
HEAT DETECTOR
SMOKE DETECTOR
REMOTE INDICATOR LIGHT
SPRINKLER TAMPER SWITCH
DUCT SMOKE DETECTOR
FLOW SWITCH
POST INDICATING VALVE SWITCH
MAGNETIC DOOR HOLDER
FIRE ALARM SYSTEM
H
S
S
F SPEAKER STROBES
F SPEAKERS
ACSR ALUMINUM CONDUCTOR
STEEL REINFORCED
AFF ABOVE FINISH FLOOR
AIC AMPS INTERRUPTING
CAPACITY (SYM RMS)
AL ALUMINUM
ALT ALTERNATE
AMP AMPERE
ANSI AMERICAN NATIONAL
STANDARDS INSTITUTE
APPROX APPROXIMATE
AUTO AUTOMATIC
AVG AVERAGE
L ANGLE
BKR BREAKER
C OR CL CENTER LINE
C OR CND CONDUIT (ELECTRICAL
SHEETS)
CKT CIRCUIT
CLG CEILING
COL COLUMN
CONC CONCRETE
CONF CONFERENCE
DC DIRECT CURRENT
DEG DEGREE
DEMO DEMOLITION
DIA DIAMETER
DIM DIMENSION
DISC DISCONNECT
DIST DISTRIBUTION
DN DOWN
DWG DRAWING
E EAST
EA EACH
EL OR
ELEV
ELEVATION - GRADE OR
BUILDING
ELEC ELECTRIC OR
ELECTRICAL
ELEV ELEVATOR
EMD ESTIMATED MAXIMUM
DEMAND
ENCL ENCLOSURE
EQUIP EQUIPMENT
EST ESTIMATE
EWC ELECTRIC WATER
COOLER
EXIST EXISTING
EXP EXPOSED
EXT EXTERIOR
FA FIRE ALARM
FLA FULL LOAD AMPS
FLEX FLEXIBLE
FLUOR FLUORESCENT
AWG GAUGE
HP HORSE POWER
HR HOUR
HTG HEATING
HTR HEATER
HZ HERTZ
ID INSIDE DIAMETER
IES ILLUMINATING
ENGINEERING SOCIETY
IN INCH
INSUL INSULATION
INT INTERIOR
KCMIL KCM KILO CIRCULAR MIL
KV KILOVOLTS
KVA KILOVOLT AMPERES
KVAR KILOVOLT AMPERES
REACTIVE
KW KILOWATT
LBS POUNDS
LRA LOCKED ROTOR AMPS
LTG LIGHTING
MAX MAXIMUM
MECH MECHANICAL
MFR MANUFACTURER
MG MOTOR GENERATOR
MH MANHOLE
MIN MINIMUM
MISC MISCELLANEOUS
FAAP FIRE ALARM
ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL
PANEL
FAEP FIRE ALARM EXTENDER
PANEL
GFCI GROUND FAULT CIRCUIT
INTERRUPTER
CUH CABINET UNIT HEATER
EMI ELECTROMAGNETIC
INTERFERENCE
MCCB MOLDED CASE CIRCUIT
BREAKER
GFI GROUND FAULT CIRCUIT
INTERRUPTER
QTY QUANTITY
REC RECEPTACLE
REFR REFRIGERATOR
REINF REINFORCEMENT
REQD REQUIRED
N NORTH
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL
CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS
ASSOCIATION
NFPA NATIONAL FIRE
PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NO NUMBER
NTS NOT TO SCALE
OD OUTSIDE DIAMETER
PH PHASE
PIV POST INDICATING VALVE
PNL PANEL
PSI POUNDS PER SQUARE IN.
OCPD OVERCURRENT
PROTECTIVE DEVICE
RFI RADIO FREQUENCY
INTERFERENCE
TEL TELEPHONE
TEMP TEMPERATURE
TVSS TRANSIENT VOLTAGE
SURGE SUPPRESSOR
TYP TYPICAL
UG UNDERGROUND
UH UNIT HEATER
UL UNDERWRITERS
LABORATORIES
UPS UNINTERRUPTIBLE
POWER SYSTEM
VFD VARIABLE FREQUENCY
DRIVE
W WEST
W/ WITH
W/O WITHOUT
WHM WATTHOUR METER
WT WEIGHT
XFMR TRANSFORMER
SOUTH
SCHED SCHEDULE
SF SQUARE FOOT (FEET)
SPEC SPECIFICATIONS
SPKR SPEAKER
SQ SQUARE
STD STANDARD
STL STEEL
SW SWITCH
SWBD SWITCH BOARD
SYM SYMMETRICAL
S
SCCR SHORT CIRCUIT
CURRENT RATING
SPD SURGE PROTECTIVE
DEVICE
SPDT SINGLE POLE, DOUBLE
THROW
VFC VARIABLE FREQUENCY
CONTROLLER
P
C/W COMPLETE WITH
VA DES MOINES CONSTRUCTION
DESIGN STANDARDS
CONSULTANTS: ARCHITECT/ENGINEERS:
on e ei gh th in ch o ne fo ot
B
A
C
D
E
F th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
CONSULTANTS: ARCHITECT/ENGINEERS:
on e ei gh th in ch o ne fo ot
B
A
C
D
E
F th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
97 8654321
P
G
IN
G
U N
IT
B A
T T
E R
IE
S
R E
C T
T E
LE
C
O M
M G
N T
S T
A T
IO
N
PBX
PBX
PBX
T E
LE
W
IR
IN
G P
U N
C H
D O
W N
B
LO
C K
S C
S U
R A
C K
S E
R V
E R
M G
N T
S E
R V
E R
M G
N T
ICN
RACKS
N E
T W
O R
K M
A N
A G
E M
E N
T
S E
R V
E R
M G
N T
V M
S V
M S
V M
S T
E S
T A
C C
T.
M
G N
T
#2 #1
ELEVATOR "G"
2, F-1
FREIGHT
#3
ELEVATOR "B"
ELEVATOR "B"
ELEVATOR "A" ELEVATOR"A"
ELEVATOR "H"
ELEVATOR "B"
FREIGHT
#4
#3
ELEVATOR "B"
3-1/2"C C/W:
(1) 24 STRAND MM FIBER (DATA)
(1) 12 STRAND SM FIBER (VOICE)
(1) 12 STRAND MM FIBER (NURSE CALL)
(1) 12 STRAND MM FIBER (METASYS)
3-1/2"C C/W:
(1) 100 PAIR CAT3 (TELEPHONE)
(1) 4-PAIR PLTC (PAGING)
(1) RG-11 (MATV)
TO MANHOLE #5
(SEE EC103 FOR
CONTINUATION)
EXISTING MANHOLE #11
3-1/2"C C/W:
(1) 24 STRAND MM FIBER (DATA)
(1) 12 STRAND SM FIBER (VOICE)
(1) 12 STRAND MM FIBER (NURSE CALL)
(1) 12 STRAND MM FIBER (METASYS)
(1) 12 STRAND MM FIBER (SECURITY)
3-1/2"C C/W:
(1) 100 PAIR CAT3 (TELEPHONE)
(1) 4-PAIR PLTC (PAGING)
(1) RG-11 (MATV)
2"C C/W:
(1) 12 STRAND MM FIBER (SECURITY)
UP TO 1ST FLR (IT CLOSET)
(SEE 2/EC102 FOR CONTINUATION)
PULLBOX (TYP.)
EXISTING 3-1/2"C C/W:
(1) 24 STRAND MM FIBER (DATA)
(1) 12 STRAND SM FIBER (VOICE)
(1) 12 STRAND MM FIBER (NURSE CALL)
(1) 12 STRAND MM FIBER (METASYS)
(1) 12 STRAND MM FIBER (SECURITY)
EXISTING 3-1/2"C C/W:
(1) 100 PAIR CAT3 (TELEPHONE)
(1) 4-PAIR PLTC (PAGING)
(1) RG-11 (MATV)
REPLACE
PULLBOX
EXISTING DUCTBANK ADD:
(1) 24 STRAND MM FIBER (DATA)
(1) 12 STRAND SM FIBER (VOICE)
(1) 12 STRAND MM FIBER (NURSE CALL)
(1) 12 STRAND MM FIBER (METASYS)
(1) 12 STRAND MM FIBER (SECURITY)
EXISTING DUCTBANK ADD:
(1) 100 PAIR CAT3 (TELEPHONE)
(1) 4-PAIR PLTC (PAGING)
(1) RG-11 (MATV)
EXISTING DUCTBANK ADD:
(1) 24 STRAND MM FIBER (DATA)
(1) 12 STRAND SM FIBER (VOICE)
(1) 12 STRAND MM FIBER (NURSE CALL)
(1) 12 STRAND MM FIBER (METASYS)
(1) 12 STRAND MM FIBER (SECURITY)
EXISTING DUCTBANK ADD:
(1) 100 PAIR CAT3 (TELEPHONE)
(1) 4-PAIR PLTC (PAGING)
(1) RG-11 (MATV)
TO BLDG 25
(SEE EC103 FOR
CONTINUATION)
EXISTING STEAM TUNNEL ADD:
4#250KCMIL, 1#4G - 3"C (EMERGENCY)
1-1/4"C C/W:
ATS CONTROL WIRING
4#250KCMIL, 1#4G - 3"C (EMERGENCY)
1-1/4"C C/W:
ATS CONTROL WIRING
'SWBD 1W-4E'
GENERATOR MASTER
CONTROL (EXIST)
4#250KCMIL, 1#4G - 3"C
(EMERGENCY)
1-1/4"C C/W:
ATS CONTROL WIRING
P6
P7
Y8
CORE DRILL
CORE DRILL
2"C C/W:
(1) 12 STRAND MM FIBER (SECURITY)
DN TO BASEMENT
(CRAWL SPACE)
(SEE 1/EC102 FOR CONTINUATION)
IT CLOSET
Y8
Drawing Title
Approved:
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management on e ei gh th in ch o ne fo ot th re e in es fo ot 6"
6" on e an d on e ha lf in fo ot on e fo ot
6" 6" th re e qu ar te rs fo ot on e ha lf fo ot th re e ei gh th s fo ot on e qu ar te r fo ot
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
TSA PROJECT
NO.:
Department of Veterans Affairs
CONSTRUCT CLC
COTTAGES - COTTAGE 1
636-123
3600 30TH ST. DES MOINES, IA
4/13/2018
BASEMENT FLOOR PLAN - BUILDINGS 2, 1W, &
1 + STEAM TUNNEL - COMPOSITE
BTF MTB
EC102
83 97 06054.032
SCALE: 1/16" = 1'-0"
BASEMENT FLOOR PLAN - BUILDINGS 2, 1W, & 1 + STEAM TUNNEL - COMPOSITE
NORTHKEY PLAN
E X
IS
T
S
E
M
N
N E
L
EXIS
T C
HILLER TUNNEL
1W
REF. NOTES ( ):X
P6 PROVIDE 250A BREAKER IN EMERGENCY SWITCHBOARD FOR SERVING
BUILDING 25.
P7 PROVIDE CONNECTIONS AS REQUIRED TO ADD BUILDING 25 AUTOMATIC
TRANSFER SWITCHES.
Y8 CONTRACTOR SHALL VISIT SITE PRIOR TO BID TO LOCATE FINAL
TERMINATION LOCATIONS OF SPECIALTY SYSTEMS IN THIS SPACE.
SCALE: 1/16" = 1'-0"
FIRST FLOOR PLAN - BUILDING 1W - COMPOSITE
DN
DN
UP TO 1ST FLR (IT CLOSET)
(SEE EC104 FOR CONTINUATION)
UP TO 1ST FLR (IT CLOSET)
(SEE EC104 FOR CONTINUATION)
EXISTING DUCTBANK ADD:
(1) 24 STRAND MM FIBER (DATA)
(1) 12 STRAND SM FIBER (VOICE)
(1) 12 STRAND MM FIBER (NURSE CALL)
(1) 12 STRAND MM FIBER (METASYS)
(1) 12 STRAND MM FIBER (SECURITY)
EXISTING DUCTBANK ADD:
(1) 100 PAIR CAT3 (TELEPHONE)
(1) 4-PAIR PLTC (PAGING)
(1) RG-11 (MATV)
EXISTING MANHOLE #5
TO MANHOLE #11
(SEE EC102 FOR
CONTINUATION)
1"C C/W:
(1) 6 STRAND MM FIBER (FIRE ALARM LOOP A)
1"C C/W:
(1) 6 STRAND MM FIBER (FIRE ALARM LOOP B)
TO SWBD 1W-4E
(SEE EC102 FOR
CONTINUATION)
TO BLDG 11 XFMR
TO BLDG 12 XFMR
EXISTING STEAM TUNNEL ADD:
4#250KCMIL, 1#4G - 3"C (EMERGENCY)
1-1/4"C C/W:
ATS CONTROL WIRING
SEE POWER RISER
DIAGRAM FOR
CONTINUATION
'SWBD 12-1'
SEE EC104 FOR
CONTINUATION
P5
Y8
BLDG 12
FACP
Y9
BLDG 12 SECURITY
PANELS
DUCTBANK C/W:
4#250KCMIL, 1#4G - 3"C (EMERGENCY)
3#2/0 (15KV), 1#2G (600V) - 4"C (PRIMARY LOOP A)
3#2/0 (15KV), 1#2G (600V) - 4"C (PRIMARY LOOP B)
1-1/4"C C/W:
ATS CONTROL WIRING
3#2/0 (15KV), 1#2G (600V) - 4"C (PRIMARY LOOP A)
3#2/0 (15KV), 1#2G (600V) - 4"C (PRIMARY LOOP B)
UTILITY TUNNEL C/W:
4#250KCMIL, 1#4G - 3"C (EMERGENCY)
3#2/0 (15KV), 1#2G (600V) - 4"C (PRIMARY LOOP A)
3#2/0 (15KV), 1#2G (600V) - 4"C (PRIMARY LOOP B)
1-1/4"C C/W:
ATS CONTROL WIRING
3-1/2"C C/W:
(1) 24 STRAND MM FIBER (DATA)
(1) 12 STRAND SM FIBER (VOICE)
(1) 12 STRAND MM FIBER (NURSE CALL)
(1) 12 STRAND MM FIBER (METASYS)
(1) 12 STRAND MM FIBER (SECURITY)
3-1/2"C C/W:
(1) 100 PAIR CAT3 (TELEPHONE)
(1) 4-PAIR PLTC (PAGING)
(1) RG-11 (MATV)
EC103
MECHANICAL PIPING
(SEE MECHANICAL PLANS)
SECTION THRU TRENCH
1. UTILITY TRENCH PROVIDED BY
MECHANICAL CONTRACTOR.
2. COORDINATE INSTALLATION WITH
MECHANICAL CONTRACTOR.
LOOP B (FROM XFMR 12)
LOOP A (FROM XFMR 11)
EMERGENCY FEED (FROM SWBD 1W-4E)
ATS CONTROL WIRING
Drawing Title
Approved:
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management on e ei gh th fo ot th re e in fo ot 6"
6" on e an d on e ha lf in fo ot on e fo ot
6" 6" th re e qu ar te rs fo ot on e ha lf fo ot th re e ei gh th s fo ot on e qu ar te r fo ot
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
TSA PROJECT
NO.:
Department of Veterans Affairs
CONSTRUCT CLC
COTTAGES - COTTAGE 1
636-123
3600 30TH ST. DES MOINES, IA
4/13/2018
BASEMENT FLOOR PLAN - BUILDING 12 +
STEAM TUNNEL- COMPOSITE
BTF MTB
EC103
84 97 06054.032
SCALE: 1/16" = 1'-0"
BASEMENT FLOOR PLAN - BUILDING 12 + STEAM TUNNEL + UTILITY TUNNEL - COMPOSITE
NORTHKEY PLAN
E X
E
N
N E
L
EXIS
T C
HILLER TUNNEL
1W
REF. NOTES ( ):X
P5 TEMPORARY POWER LOCATION. CONTRACTOR SHALL PROVIDE BREAKER
AS REQUIRED.
Y8 CONTRACTOR SHALL VISIT SITE PRIOR TO BID TO LOCATE FINAL
TERMINATION LOCATIONS OF SPECIALTY SYSTEMS IN THIS SPACE.
Y9 PROVIDE CONNECTIONS AS REQUIRED TO EXTEND CAMPUS FIRE ALARM
LOOP TO BUILDING 25.
SCALE: 1/2" = 1'-0"
PRECAST UTILITY TRENCH DETAIL
SS
J
JF
F
JJ
S S
J
J
J
S
F
R Q
P
L
M
K J
H
G
F
E
D
B
A
1 2 3 4 5 6 7 9
12 13 14 158
C
N
S
T
U
V
W
Z
8.6 11.3
Y
12.3
N.1
D.4
12.6
IT
FIRE/WATER
SRVC
FACP
EY101
DN TO BASEMENT (STORAGE)
(SEE EC103 FOR CONTINUATION)
DN TO BASEMENT
(SEE EC103 FOR CONTINUATION)
IT CLOSET
IT CLOSET
EXISTING CABLE TRAY ADD:
(1) 24 STRAND MM FIBER (DATA)
(1) 12 STRAND SM FIBER (VOICE)
(1) 12 STRAND MM FIBER (NURSE CALL)
(1) 12 STRAND MM FIBER (METASYS)
(1) 12 STRAND MM FIBER (SECURITY)
EXISTING CABLE TRAY ADD:
(1) 100 PAIR CAT3 (TELEPHONE)
(1) 4-PAIR PLTC (PAGING)
(1) RG-11 (MATV)
1"C C/W:
(1) 6 STRAND MM FIBER (FIRE ALARM LOOP A)
1"C C/W:
(1) 6 STRAND MM FIBER (FIRE ALARM LOOP B)
EXISTING CABLE TRAY ADD:
(1) 24 STRAND MM FIBER (DATA)
(1) 12 STRAND SM FIBER (VOICE)
(1) 12 STRAND MM FIBER (NURSE CALL)
(1) 12 STRAND MM FIBER (METASYS)
(1) 12 STRAND MM FIBER (SECURITY)
EXISTING CABLE TRAY ADD:
(1) 100 PAIR CAT3 (TELEPHONE)
(1) 4-PAIR PLTC (PAGING)
(1) RG-11
1"C C/W:
(1) 6 STRAND MM FIBER (FIRE ALARM LOOP A)
1"C C/W:
(1) 6 STRAND MM FIBER (FIRE ALARM LOOP B)
NEW CABLE TRAY C/W:
(1) 24 STRAND MM FIBER (DATA)
(1) 12 STRAND SM FIBER (VOICE)
(1) 12 STRAND MM FIBER (NURSE CALL)
(1) 12 STRAND MM FIBER (METASYS)
(1) 12 STRAND MM FIBER (SECURITY)
NEW CABLE TRAY C/W:
(1) 100 PAIR CAT3 (TELEPHONE)
(1) 4-PAIR PLTC (PAGING)
(1) RG-11 (MATV)
1"C C/W:
(1) 6 STRAND MM FIBER (FIRE ALARM LOOP A)
1"C C/W:
(1) 6 STRAND MM FIBER (FIRE ALARM LOOP B)
NEW CABLE TRAY C/W:
(1) 24 STRAND MM FIBER (DATA)
(1) 12 STRAND SM FIBER (VOICE)
(1) 12 STRAND MM FIBER (NURSE CALL)
(1) 12 STRAND MM FIBER (METASYS)
(1) 12 STRAND MM FIBER (SECURITY)
NEW CABLE TRAY C/W:
(1) 100 PAIR CAT3 (TELEPHONE)
(1) 4-PAIR PLTC (PAGING)
(1) RG-11 (MATV)
1"C C/W:
(1) 6 STRAND MM FIBER (FIRE ALARM LOOP A)
1"C C/W:
(1) 6 STRAND MM FIBER (FIRE ALARM LOOP B)
PNL R1C-G-1
PNL R1S-G-1
SEE EC103 FOR
CONTINUATION
P4
Y11 (TYP.)
EC104
D3
D2
D7 D8
D1
D2
D4 D5
D3
D9
D9
Drawing Title
Approved:
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management on e ei gh th fo ot th re e in fo ot 6"
6" on e an d on e ha lf in fo ot on e fo ot
6" 6" th re e qu ar te rs fo ot on e ha lf fo ot th re e ei gh th s fo ot on e qu ar te r fo ot
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
TSA PROJECT
NO.:
Department of Veterans Affairs
CONSTRUCT CLC
COTTAGES - COTTAGE 1
636-123
3600 30TH ST. DES MOINES, IA
4/13/2018
FIRST FLOOR PLAN - BUILDINGS 25 AND 12 -
COMPOSITE
BTF MTB
EC104
85 97 06054.032
SCALE: 1/16" = 1'-0"
FIRST FLOOR PLAN - BUILDINGS 25 AND 12 - COMPOSITE
NORTHKEY PLAN
E X
E
N
N E
L
EXIS
T C
HILLER TUNNEL
1W
REF. NOTES ( ):X
P4 TO CONTRACTOR STAGING AREA. CONTRACTOR SHALL PROVIDE
STEP-DOWN TRANSFORMERS, DISCONNECTS, ETC. AS REQUIRED.
Y11 PROVIDE (2) GANGED EZ PATH SERIES 44 PATHWAYS AT ALL DOOR
CROSSINGS AND ENTRANCES INTO IT ROOMS.
SCALE: 1/4" = 1'-0"
BUILDING 12 - DEMOLITION
REF. DEMO NOTES ( ):DX
D1 SECURITY CAMERA TO BE REMOVED AND STORED FOR RE-INSTALLATION;
EXISTING WIRING TO BE PRESERVED.
D2 MANUAL PULL STATION TO BE REMOVED AND STORED FOR
RE-INSTALLATION; EXISTING WIRING TO BE PRESERVED.
D3 PA HORN TO BE REMOVED AND STORED FOR RE-INSTALLATION; EXISTING
WIRING TO BE PRESERVED.
D4 SPEAKER TO BE REMOVED AND STORED FOR RE-INSTALLATION; EXISTING
WIRING TO BE PRESERVED.
D5 SMOKE DETECTOR TO BE REMOVED AND STORED FOR RE-INSTALLATION;
EXISTING WIRING TO BE PRESERVED.
D7 STAIRWELL LIGHTING (INTERIOR / EXTERIOR) TO BE REMOVED AND
STORED FOR RE-INSTALLATION; EXISTING WIRING TO BE PRESERVED.
D8 REMOVE BACK-TO-BACK CABINET UNIT HEATERS AND DEMO ONE CIRCUIT
BACK TO PNL R1C-G-1; OTHER CIRCUIT WIRING TO BE PRESERVED.
D9 ABANDONED EQUIPMENT; COORDINATE WITH OWNER PRIOR TO DEMO
AND RETURN TO OWNER.
OS
OS
OS
OS
OS
OS
OS
OS
OS
PC
PC
OS
OS
OS
PC
EL101
FIRE/WATER
SRVC
CLEAN EQUIP.
CLEAN UTILITY
RESIDENT
(BARIATRIC)
2529 RESIDENT
RESIDENT
RESIDENT
RESIDENT
RESIDENT
MED. STO.
RESIDENT
(BARIATRIC)
RESIDENT
RESIDENT
RESIDENT
RESIDENT
RESIDENT
STAIR 1
IT
STAFF REPORT
ROOM
MEN
WOMEN
NURSE ADMIN.
2545 LOUNGE
CORRIDOR
CORRIDOR
CORRIDOR
SRVC CORR.
FAMILY
FOYER
LIVING ROOM
CORRIDOR
CLEAN LINEN
2528 DEN
DINING
SERVERY
GROUP ROOM
ELECT.
HSKPG
STORAGE
SOILED UTILITY
RESIDENT
LAUNDRY
SPA
PANTRY
2510A
PRODUCTION
KITCHEN
HOME OFFICE
2508A
CORRIDOR
CORRIDOR
CORRIDOR
2 2
A1A1A1
A1
A1
A1
A1
A1
A1
A1
A1A1
A1 A1
A1
A1 A1
A1 A1 A1
A1 A1 A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
2 2
A2
A2 A2
A2
A2
A1
A1
A1
A1 A1
A1
A1
A2 A2
A1
A1
A1 A1
A1
A2
A2
A2
A1
A1
A1
A1 C1
C1
C1
C1
C1
C1
C1
C4
C4
C4
C4
C4
C4
C4C4C4C4C4C4
C2 C2
C2 C2
C2 C2
C2 C2
W1 W1 W1 W1 W1
W1
W1
W1
W1
W1
C2
C2 C2
C2
A2
A2
C1 C1
W2 W2
C1 C1
C1 C1
C1
C1
C1 C3
C3 C3 C3
C3 C3 C3 C3
C3 C3 C3 C3
C3 C3 C3 C3
C4
C4
C4
C4
C2W C2W
C2W C2W
C2W
C2W
C1 C1
1 F1
F1
F1
F1
C3 C3
F2
F2
F1 F1
C1
C2
A2
A2
A2
A2
F1
F1
F1
F1
R
Q
P
L
M
K
J
H
G
F
E
D
B
A
1 2 3 4 5 6 7 9 12 13 14 158
C
N
S
N.1
D.4
12.6
AREA
AREA
A
B
C2
C2
C2
W3
W3
X1
X1
X1X1X1
X1
X1
X1
X1
X1
X1
X1
X1
X1
F1
C1
A5
A5
A5
LCP - 1
EP101
NL1 - 52CRL1 - 26
LCP - 3
LCP - 2
LCP - 5
CRL1 - 26
LSL1 - 1
LSL1 - 3
NL1 - 58 CRL1 - 24
UP
CRL1 - 28
NL1 - 62
CRL1 - 28
NL1 - 62
CRL1 - 28
NL1 - 62
CRL1 - 28
NL1 - 62
CRL1 - 28
NL1 - 62
CRL1 - 28
NL1 - 62
(PART.)
CRL1 - 30
NL1 - 60
CRL1 - 30
NL1 - 60
CRL1 - 30
NL1 - 60
CRL1 - 30
NL1 - 60
CRL1 - 30
NL1 - 60
CRL1 - 26
(PART.)
LCP - 6
L2
L3
OR
OR
L3
OR
L4
L4
OR
OR
L4
OR
L4
L6
(TYP.)
LCP - 4W1
W1 W1
W1
C2 C2C2
X1
(PART.)
L2
9 11
T
U
V
W
Z
8.6 11.3
Y
C1
C1
C1
C1
C1
C1
AREA
AREA
A
B
C2 C2
C2 C2
X1
X1
L2
ORL4
B1 B1 B1
C1 C1X1
STAIR 4
S4
PASSAGE
C1-3E
L7
L8
BLDG 25 BLDG 12
F2 F2
F2
F2 F2 F2
F2
F2
F2 F2
F2 F2
E
D
2 3 4 5 6 7 98
C
D.4
X1W3
MECHANICAL
ELEC.
NL1 - 58CRL1 - 24
DN
NL1 - 54
L9
C2W
C2W
W2
A4
A4
A3
B
A
C
N1
C3WW
L1
READING
AMBIENT
EXAM
EY602
NL1-X CR1-X
1 2 3
V1 V1
L5
NL1 - 56
#10s
+7' AFF
(TYP.)
Drawing Title
Approved:
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management on e ei gh th fo ot th re e in fo ot 6"
6" on e an d on e ha lf in fo ot on e fo ot
6" 6" th re e qu ar te rs fo ot on e ha lf fo ot th re e ei gh th s fo ot on e qu ar te r fo ot
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
TSA PROJECT
NO.:
Department of Veterans Affairs
CONSTRUCT CLC
COTTAGES - COTTAGE 1
636-123
3600 30TH ST. DES MOINES, IA
4/13/2018
FLOOR PLANS & TUNNEL - LIGHTING
BTF MTB
EL101
86 97 06054.032
REF. NOTES ( ):X
L1 LOCATE REFLECTOR TO MAXIMIZE LIGHT AT MED CABINET.
L2 PROVIDE PHOTOCELL FOR CONTROL OF CANOPY LIGHTING.
L3 PROVIDE 8-BUTTON OVERRIDE SWITCH FOR CONTROL OF ALL LCP
RELAYS.
L4 PROVIDE 2-BUTTON OVERRIDE SWITCH FOR CONTROL OF CORRIDOR
LIGHTING.
L5 LOCATE SWITCH NEAR TUNNEL ENTRANCE (VERIFY).
L6 INDICATES CIRCUITS SERVING RESIDENT ROOM.
L7 EXISTING STAIRWELL LIGHTING (INTERIOR / EXTERIOR) TO BE
RE-INSTALLED; CONNECT TO EXISTING WIRING.
L8 CONNECT LIGHTING IN CORRIDOR TO EXISTING LIFE SAFETY / NORMAL
CIRCUITS (VERIFY).
L9 SHIFT LIGHTING AS REQUIRED TO AVOID CONFLICTS WITH HVAC
DUCTWORK, PIPING, ETC.
SCALE: 1/8" = 1'-0"
FIRST FLOOR PLAN - AREA A - LIGHTING
SCALE: 1/8" = 1'-0"
FIRST FLOOR PLAN - AREA B - LIGHTING
SCALE: 1/8" = 1'-0"
ATTIC - LIGHTING
SCALE: 1/4" = 1'-0"
ENLARGED PLAN - TYP. RESIDENT ROOM - LIGHTING
NORTHKEY PLAN
E X
E
N
N E
L
EXIS
T C
HILLER TUNNEL
1W
SCALE: 1/8" = 1'-0"
TUNNEL - LIGHTING
1 3 4
LMSW-101-G-U LMDM-101-G-U DW-311-G-U
DSW-301-G-U
NOTES:
1. WATTSTOPPER USED AS DESIGN BASIS.
LMDC-100-ULMDC-100-U
(AS REQUIRED)
LMRC-101-U
NEUTRAL
UNSWITCHED
HOT
1 1
CAT5E
(TYP.)
RJ-45
(TYP.)
NOTES:
• WATTSTOPPER USED AS DESIGN BASIS.
(AS REQUIRED)
LIGHTING
LOAD
RED
EM / EXIT
LTG
LOAD
H N
LMDC-100-ULMDC-100-U
(AS REQUIRED)
LMRC-211-U
NEUTRAL
UNSWITCHED
HOT
3 3
CAT5E
(TYP.)
RJ-45
(TYP.)
(AS REQUIRED)
LIGHTING
LOAD
RED
0-10V
EM / EXIT
LTG
LOAD
H N
0-10VDC
LUMINAIRE SCHEDULE NOTES:
1. ADDITIONAL 97W FOR EXAM LIGHT.
2. SUFFIX CATALOG NO. REPRESENTS (2) CKTS WITH (1) CKT
CONNECTED TO MOTION SENSOR. CONNECT NORMAL CKT TO
MOTION SENSOR AND CONNECT LIFE SAFETY TO OTHER. ADDITIONAL
34W FOR LIFE SAFETY CKT.
3. PROVIDE HUBBELL EPC-1 (OR EQUAL) TRANSFER DEVICE FOR
LOCATIONS SERVED BY NORMAL AND EMERGENCY POWER AND
CONTROLLED BY A SINGLE SWITCH.
4. SEE FLOOR PLAN FOR SINGLE / DOUBLE FACE LOCATIONS AND
CHEVRON REQUIREMENTS.
5. CATALOG NO. TAKEN FROM AS-BUILT DRAWINGS AND HAS NOT BEEN
FIELD VERIFIED. CONTRACTOR SHALL MATCH EXISTING BASKET-TYPE
LUMINAIRE ON FIRST FLOOR OF BUILDING 12.
GENERAL LUMINAIRE SCHEDULE NOTES:
A. THE SUBMITTAL SHALL BE PREPARED AND SUBMITTED BY THE
AUTHORIZED FACTORY REPRESENTATIVE OR THEY SHALL BE
REJECTED.
Drawing Title
Approved:
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management on e ei gh th in ch o ne fo ot
B
A
C
D
E
F th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
TSA PROJECT
NO.:
Department of Veterans Affairs
CONSTRUCT CLC
COTTAGES - COTTAGE 1
636-123
3600 30TH ST. DES MOINES, IA
4/13/2018
SCHEDULES AND DIAGRAMS - LIGHTING
BTF MTB
EL601
87 97 06054.032
SCALE: NOT TO SCALE
TYPICAL LOW VOLTAGE SWITCHES
SCALE: NOT TO SCALE
ON/OFF ROOM CONTROLLER
SCALE: NOT TO SCALE
ON/OFF OCCUPANCY SENSOR
SCALE: NOT TO SCALE
ON/OFF ROOM CONTROLLER W/ DIMMING
SCALE: NOT TO SCALE
ON/OFF OCCUPANCY SENSOR W/ DIMMING
LUMINAIRE SCHEDULE
TYPE NO DESCRIPTION / SPEC NO
LAMPS TOTAL
WATTS BALLAST MFGR AND TYPE VOLT MOUNTING NOTESNO WATTS TYPES
A1 2X2 - TROFFER - 2000 LUMENS
CREE CR22 20L 40K 10V
- - LED 22 VA - MVOLT RECESSED
A2 2X2 - TROFFER - 3200 LUMENS
CREE CR22 32L 40K 10V
- - LED 32 VA - MVOLT RECESSED
A3 2X4 - TROFFER - PATIENT BED
KENALL MPC24 G 25L/45L/90L40K DCC 120 SYM LVC
- - LED 78 VA - 120 V RECESSED 1
A4 2X2 - TROFFER - PATIENT ROOM
KENALL MAC22 G 45L40K DCC 1 DV
- - LED 45 VA - MVOLT RECESSED
A5 2X2 - SURFACE
CREE FP22 50L 40K 10V (SMK-CR22 SURFACE KIT)
- - LED 50 VA - MVOLT SURFACE
B1 2X4 - BASIC (EXISTING)
LITHONIA 2AV G 2 32 PMW MVOLT GEB10PS
2 32 F032/735/ECO 56 VA - MVOLT CEILING 5
C1 6" RECESSED CAN - 1100 LUMENS
CREE KR6 13L 40K 120V 10V + KR6T SSGC FF
- - LED 18 VA - 120 V RECESSED
C2 6" RECESSED CAN - 1700 LUMENS
CREE KR6 20L 40K 120V 10V + KR6T SSGC FF
- - LED 30 VA - 120 V RECESSED
C2W 6" RECESSED CAN - 1700 LUMENS - WET LOCATION
CREE HADL6 FF 2FW 22L 40K8 M CSS G RIG6 DV DIM1
- - LED 22 VA - MVOLT RECESSED
C3 6" RECESSED CAN - 2550 LUMENS
CREE KR6 30L 40K 120V 10V + KR6T SSGC FF
- - LED 39 VA - 120 V RECESSED
C3WW 6" RECESSED CAN - 2550 LUMENS
CREE KR6 30L 40K 120V 10V + KR6T SSGC FF WW
- - LED 39 VA - 120 V RECESSED
C4 4" RECESSED CAN - 700 LUMENS
CREE KR4 9L 40K 120V 10V + KR4T SSGC FF
- - LED 13 VA - 120 V RECESSED
F1 4' SURFACE
CREE LS4 25L 40K 10V
- - LED 23 VA - MVOLT SURFACE 3
F2 8' SURFACE
CREE LS8 80L 40K 10V + AC-144-Q14B-LP (FINAL HEIGHT TBD)
- - LED 80 VA - MVOLT CABLE
N1 NIGHT LIGHT
KENALL MSL S 1 BSS PP ALL 120 2
- - LED 5 VA - 120 V RECESSED
V1 4' WALL MOUNTED - VAPORTIGHT
CREE WS4 47L 40K 10V FD SSL + WS4MBK
- - LED 50 VA - MVOLT WALL
W1 WALL SCONCE - SLIM
KENALL MAS813 PAN AS WS 1 12L40K-DCC-DV
- - LED 14 VA - MVOLT WALL
W2 4' WALL MOUNT - VANITY
KENALL MLHA5V 48 F MW PP 1 45L40K DCC 1 DV
- - LED 45 VA - MVOLT WALL
W3 WALL MOUNT - STAIRWELL
KENALL MLHA8 F MB PP 1 67L40K DCC 1 120 + 2C MS SP
- - LED 34 VA - 120 V WALL 2
X1 EXIT SIGN
COMPASS CCES/DG
- - LED 5 VA - 120 V WALL/CEILING 4
PROVIDE (2) 20A BREAKERS IN UPSTREAM PANELBOARD FOR SUPPLYING RELAYS.
1. CONTROLLED BY (3) 2-BUTTON OVERRIDE SWITCHES & (2) 8-BUTTON OVERRIDE SWITCHES.
2. CONTROLLED BY (2) 8-BUTTON OVERRIDE SWITCHES.
3. CONTROLLED BY (2) 2-BUTTON OVERRIDE SWITCHES & (2) 8-BUTTON OVERRIDE SWITCHES.
Notes:
LTG 1642 VA 100.00% 1642 VA
Load Classification Connected Load Demand Factor Estimated Demand
14 A
1642 VA
8 SPARE 1 0 VA
7 SPARE 1 0 VA
6 LTG - BLDG 25 FOY LOW 1 90 VA 2
5 LTG - BLDG 12 CONNECTING LINK 1 152 VA 3
4 LTG - BLDG 25 LIV / DIN / FOY HIGH 1 624 VA 2
3 LTG - BLDG 25 WALL SCONCES 1 140 VA 2
2 LTG - BLDG 25 CLC RES COVES 1 156 VA 2
1 LTG - BLDG 25 CORR 1 480 VA 1
CKT Circuit Description # of
Poles Load Remarks
Enclosure: NEMA 1 Mounting: SURFACE Wires: 2
Supply From: NL1 Phases: 1 Location: ELEC 2520 Volts: 120V Single
Panel: LCP
J
J
J
J
J
J
J
J
J
J
EP101
FIRE/WATER
SRVC
CLEAN EQUIP.
CLEAN UTILITY
RESIDENT
(BARIATRIC)
2529 RESIDENT
RESIDENT
RESIDENT
RESIDENT
RESIDENT
MED. STO.
RESIDENT
(BARIATRIC)
RESIDENT
RESIDENT
RESIDENT
RESIDENT
RESIDENT
STAIR 1
IT
STAFF REPORT
ROOM
MEN
WOMEN
NURSE ADMIN.
LOUNGE
CORRIDOR
CORRIDOR
CORRIDOR
SRVC CORR.
FAMILY
FOYER
LIVING ROOM
CORRIDOR
CLEAN LINEN
DEN
DINING
SERVERY
GROUP ROOM
ELECT.
HSKPG
STORAGE
SOILED UTILITY
RESIDENT
LAUNDRY
SPA
2512 PANTRY
2510A
PRODUCTION
KITCHEN
HOME OFFICE
2508A
CORRIDOR
CORRIDOR
CORRIDOR
CRL1 - 1
NL1 - 1
NL1 - 2
CRL1 - 2
NL1 - 3
NL1 - 4
CRL1 - 4
NL1 - 7
NL1 - 8
CRL1 - 5
NL1 - 9
NL1 - 10
CRL1 - 6
NL1 - 11
NL1 - 12
CRL1 - 7
NL1 - 13
NL1 - 14
CRL1 - 8
NL1 - 15
NL1 - 16
CRL1 - 9
NL1 - 17
NL1 - 18
CRL1 - 10
NL1 - 19
NL1 - 20
CRL1 - 11
NL1 - 21
NL1 - 22
CRL1 - 12
NL1 - 23
NL1 - 24
EP101
G G
AC,G
AC,G
G
G
AC,G
AC
EP101
COPIER
AC
FRIDGE
MICROWAVE
AC,GFI
COFFEE
AC,GFI
FRIDGE
+36"
EP101
AC
AC
AC
AC
R
Q
P
L
M
K
J
H
G
F
E
D
B
A
1 2 3 4 5 6 7 9 12 13 14 158
C
N
S
N.1
D.4
12.6
'X25-SD'
AREA
AREA
A
B
'X25'
CART
+48"
CART
+48"
NL1 - 26,28
DRYER
+48"
WASHER
GFI, +48"
NL1 - 30
NL1 - 31
NL1 - 33
NL1 - 35
NL1 - 32
CRL1 - 13
CRL1 - 21
NL1 - 25
NL1 - 27
NL1 - 29
NL1 - 34
G
NL1 - 36
NL1 - 37
NL1 - 39
NL1 - 38
NL1 - 42
CRL1 - 19
CRL1 - 17CRL1 - 23
NL1 - 43
NL1 - 47
NL1 - 44
NL1 - 46
NL1 - 48
NL1 - 49
NL1 - 45
TV +72"
TV +72"
TV +72"
NL1 - 41
EP101
TV +72"
TV +72"
TV +72"
TV +72"
LSL1 - 2
LSL1 - 2
LSL1 - 4
P1
(TYP.)
SPA TUB
NL1 - 55
NL1 - 59 FIREPLACE
(VERIFY)
EQL1 - 1
FCU-2
EQL1 - 1
FCU-3
NL1 - 61
DBF-1
CRL1 - 25 CRL1 - 27
MISC. +48"
(TYP.)
MISC. +48"
MISC. +48"
EY101
WP,G
WP,G
NL1 - 72
NL1 - 72
CRL1 - 29
CRL1 - 31
9 11
T
U
V
W
Z
8.6 11.3
Y
AREA
AREA
A
B
LSL1 - 6
LSL1 - 6
LSL1 - 4
P3
STAIR 4
S4
PASSAGE
C1-3E
EQL1 - 1
FCU-1
P10
BLDG 25 BLDG 12
EP101
MECHANICAL
ELEC.
E
D
2 3 4 5 6 7 98
C
D.4
EQH1 - 2,4,6
MAC-1
EQH1 - 7,9,11
MVS-1
EQL1 - 3,5,7
HWP-1
EQL1 - 2,4,6
HWP-2
EQL1 - 9
DHWP-1
EQL1 - 9
DHWP-2
EQL1 - 11
CRV-1
EQH1 - 8,10,12
AHU-1
EQH1 - 13,15,17
RF-1
EQL1 - 23
CRV-2
EQL1 - 20,22
SSU-1
EQL1 - 24,26
SSU-2
WP,G
EQH1 - 19,21,23
EF-1
NL1 - 53
NL1 - 53
NL1 - 53
NL1 - 53
EP501
EF-3
NL2 - 25
EF-2
NL1 - 6
+8"
+6" BELOW CLG
CRL1 - 3
AC,G
NL1 - 5
+36"
+60"
B
A
C
+36"
'CRL1''NL1'
E
5 6 7
'LSL1'
CRL1 - 20NL1 - 51
'LCP'
'NL2'
AC,G
AC,G
G
FRIDGE +36"
FRIDGE +36"
MICROWAVE
AC,GFI
G
NL2 - 2,4
DISH
NL2 - 1,3
RANGE
NL2 - 5,7
RANGE
COFFEE
AC,GFI
ICE
AC,GFI
FRIDGE +36"
AC,G
NL2 - 15,17
HOT4
MICROWAVE +24"
GFI
AC,G
F
E
D.4
NL2 - 14
NL2 - 9
NL2 - 11
NL2 - 10
NL2 - 19
NL2 - 13
NL2 - 12
NL2 - 22
NL2 - 20
NL2 - 8
NL2 - 6
NL2 - 21
DISHWASHER
NL2 - 23
EP501
FOOD CART
GFI, +48"
NL2 - 24
+48"
B
A
C
AC,G
CART
GFI, +48"
CART
GFI, +48"
OMNICELL
+48"
OMNICELL
+48"
OMNICELL
+48"
CRL1 - 15
CRL1 - 14
FRIDGE
AC, G
FREEZER
CRL1 - 18
CRL1 - 16
NL1 - 40
G
D
6 7 98
C
'TSLS''TSCR''TSEQ'
'EQL1'
'XLSL1'
'XEQL1'
'XLSL1-PD'
'XLSL1-SD'
'XCRL1'
15 KVA 30 KVA 75 KVA30 KVA
'XNL1'
'XCRL1-PD'
'XCRL1-SD'
'XNL1-SD'
45 KVA
'XNL2'
'XNL2-SD'
'25NH1'
'EQH1'
'MGB'
'25EH1'
150A 60A 30A
'METER'
'ESPD'
'NSPD'
(BOTTOM)
(MIDDLE)
(TOP)
EQL1 - 24,26
SS-2
CRL1 - 22
NL1 - 50
D
3 4
C
EQL1 - 20,22
SS-1
'TMGB'
CRL1 - 36
CRL1 - 38
P9
CRL1 - 32
CRL1 - 32
CRL1 - 34
NL1 - 70
CRL1 - 40
CRL1 - 42
+48"
+48"
+48"
+48"
CRL1 - 32
1 2 3
NL1 - 57
EQL1 - 8,10,12
CRV-3
EQL1 - 13,15,17
CWP-1
EQL1 - 14,16,18
CWP-2
SUMP PUMP
EQL1 - 21
Drawing Title
Approved:
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management on e ei gh th fo ot th re e in fo ot 6"
6" on e an d on e ha lf in fo ot on e fo ot
6" 6" th re e qu ar te rs fo ot on e ha lf fo ot th re e ei gh th s fo ot on e qu ar te r fo ot
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
TSA PROJECT
NO.:
Department of Veterans Affairs
CONSTRUCT CLC
COTTAGES - COTTAGE 1
636-123
3600 30TH ST. DES MOINES, IA
4/13/2018
FLOOR PLANS & TUNNEL - POWER
BTF MTB
EP101
88 97 06054.032
REF. NOTES ( ):X
P1 INDICATES CIRCUITS SERVING RESIDENT ROOM.
P3 CONNECT DOOR OPERATOR TO PNL R1S-G-1 (LIFE SAFETY).
P9 PROVIDE L5-30R LOCKING RECEPTACLE AND MOUNT TO BOTTOM OF
CABLE TRAY. (TYP. 2)
P10 .CONNECT CABINET UNIT HEATER TO EXISTING WIRING.
NORTHKEY PLAN
E X
E
N
N E
L
EXIS
T C
HILLER TUNNEL
1W
SCALE: 1/8" = 1'-0"
FIRST FLOOR PLAN - AREA A - POWER
SCALE: 1/8" = 1'-0"
FIRST FLOOR PLAN - AREA B - POWER
SCALE: 1/8" = 1'-0"
ATTIC - POWER
SCALE: 1/4" = 1'-0"
ENLARGED PLAN - TYP. RESIDENT ROOM - POWER
SCALE: 1/4" = 1'-0"
ENLARGED PLAN - ELEC 2520 - POWER
SCALE: 1/4" = 1'-0"
ENLARGED PLAN - KITCHEN AREA - POWER
SCALE: 1/4" = 1'-0"
ENLARGED PLAN - MED. STO. 2517 - POWER
SCALE: 1/4" = 1'-0"
ENLARGED PLAN - ELEC 2551 - POWER
SCALE: 1/4" = 1'-0"
ENLARGED PLAN - IT 2537 - POWER
SCALE: 1/8" = 1'-0"
TUNNEL - POWER
FIN. GRADE
3" 3"
3" 3"
EQUAL
EQUAL
NOTE 1
3"
4"
3"
3" 3"
NOTES:
1. TOP OF DUCT BANK TO BE A MINIMUM OF 24" BELOW FINISHED GRADE.
2. PROVIDE CONTINUOUS STRIP OF WARNING TAPE WITHIN 3" OF CENTERLINE OF DUCT BANK. PROVIDE MULTIPLE STRIPS OF
WARNING TAPE WHERE DUCT BANK WIDTH EXCEEDS 16" OVERALL.
3. PROVIDE LONG SWEEPS (HORIZONTALLY AND VERTICALLY) WITH MINIMUM RADII EQUAL TO SIX TIMES CONDUIT DIAMETER.
MAXIMUM OF TWO 90 DEGREE BENDS BETWEEN PULL POINTS
4. TRANSITION FROM RNC TO GRC FOR FINAL 5' AND PAINT WITH ASHPALTIC PAINT.
5. PROVIDE 5-DEGREE ANGLE COUPLINGS FOR SMALL CHANGES IN DIRECTION.
6. REFER TO SPEC SECTION 260541 FOR ENCASEMENT REQUIREMENTS.
NOTE 2
DUCT SPACER (TYP.)
NOTE 3
NOTE 4
NOTE 6
NATIVE BACKFILL
NOTE 5
CONCRETE
1'-0" 1'-0"
2'-0"5'-0" 6"
N G
TERMINAL
BAR
A B C
SUPPLY-SIDE
BONDING
JUMPERS
ISOLATED NEUTRAL
TERMINAL
NEAREST
GROUNDING
ELECTRODE
TRANSFORMER
SYSTEM BONDING JUMPER
GROUNDING
ELECTRODE
CONDUCTOR
EQUIPMENT GROUNDING CONDUCTOR
120VAC FIRE SUPPRESSION HOOD
R
208VAC
POWER DISCONNECT BOX
(NEMA 14-50R INCLUDED)
NOTES:
1. POWER DISCONNECT BOX, ADA CONTROLS, AND
CLOCKBOX / DIGITAL TIMER, PROVIDED AS PART
OF HOOD PACKAGE.
2. ELECTRICAL CONTRACTOR TO MAKE ALL FINAL
CONNECTIONS.
3. CONNECT HOOD FIRE ALARM CONTACTS TO FIRE
ALARM CONTROL PANEL.
4. REFER TO MANUFACTURER'S INSTALLATION
INSTRUCTIONS FOR DETAILS.
(8') POWER DISCONNECT CABLE
ADA
CONTROLS
TO EXHAUST FAN
(25') PLENUM CABLE
(8') SHIELDED
CONTROL WIRING
FA
CONTRACTOR FURNISHED
CONTRACTOR INSTALLED
MANUFACTURER FURNISHED
CONTRACTOR INSTALLED
(8') 110 VAC SUPPLY CABLE
CLOCK
BOX
DIGITAL
TIMER
(20') SHIELDED
CONTROL WIRING
KH-2
EF-3
RANGE
INSULATORS (TYP. 2)
BOLT TO WALL
ANCHOR BOLTS
COPPER GROUND BAR
WALL MOUNTING BRACKET
MGB
ERICO EGBA14A24MMT
1' -0
2'-0"
4"
1"
2" 3"
6"
1' -0
1'
-6
12"Ø PIER - TYP.
V E
R
IF
Y W
/ S T
R U
C
5' -0
M
IN
#4 BARS @ 12" O.C.
EA. WAY, TOP & BOT.
12"Ø CONC. PIERS
W/ (4) #6 VERT. BARS
& #3 TIES @ 12" O.C.
3/4" CHAMFER
ALL AROUND CONC. SLAB
NOTE:
VERIFY DEPTH OF PIERS TO
BE AT LEAST 2'-0" BELOW
LOCAL FROST DEPTH.
TYP.
8"3"
3"
OPENING
(8) #4 - 2'-0" BARS @ 45° -
(2) EA. CORNER
(8) #4 - 7'-0" BARS -
(2) EA. SIDE OF OPENING
CONCRETE REQUIREMENTS:
SLAB & PIERS TO BE MADE OF
CONCRETE WITH A MINIMUM
28 DAY STRENGTH OF 4,000 PSI
AND 5% AIR CONTENT
6"
2' -6
1'
-6
1'-6" 1'-6"
7'-6"
7' -6
4'-2"1'-8" 1'-8"
4'-6"
Drawing Title
Approved:
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management on e ei gh th in ch o ne fo ot
B
A
C
D
E
F th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
TSA PROJECT
NO.:
Department of Veterans Affairs
CONSTRUCT CLC
COTTAGES - COTTAGE 1
636-123
3600 30TH ST. DES MOINES, IA
4/13/2018
DETAILS - POWER
BTF MTB
EP501
89 97 06054.032
1 Revision 1 Date 1
SCALE: NOT TO SCALE
UNDERGROUND RACEWAY INSTALLATION DETAIL
SCALE: NOT TO SCALE
SEPARATELY DERIVED SYSTEM
SCALE: NOT TO SCALE
RESIDENTIAL RANGE SUPPRESSION WIRING DIAGRAM
SCALE: NOT TO SCALE
GROUND BAR - DETAIL
SCALE: 3/4" = 1'-0"
TRANSFORMER PAD DETAIL
Drawing Title
Approved:
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management on e ei gh th in ch o ne fo ot
B
A
C
D
E
F th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
TSA PROJECT
NO.:
Department of Veterans Affairs
CONSTRUCT CLC
COTTAGES - COTTAGE 1
636-123
3600 30TH ST. DES MOINES, IA
4/13/2018
SCHEDULES AND DIAGRAMS - NORMAL PANEL
SCHEDULES
BTF MTB
EP601
90 97 06054.032
1. VERIFY BREAKER AND WIRE SIZE WITH MANUFACTURER.
Notes:
Total Feeder Current: 228 A
Continuous Current @ 125%: 122 A EQP_NON CONT 58574 VA 100.00% 58574 VA Non-Cont. Current @ 100%: 107 A
EQP_CONT 70045 VA 100.00% 70045 VA
REC 50580 VA 59.89% 30290 VA Total Est. Demand Current: 204 A LTG 10824 VA 100.00% 10824 VA Total Est. Demand: 169733 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 240 A 220 A 229 A Total Load: 66114 VA 60905 VA 63004 VA
29 SPACE -- -- 0 0 30
27 SPACE -- -- 0 0 28
25 SPACE -- -- 0 0
3 60 A NSPD (NOTE 1)
23 SPARE 20 A 1 0 0 24
21 SPARE 20 A 1 0 0 22
19 SPARE 20 A 1 0 0
3 125 A SPARE
17 1500 0 18 15 1346 0 16
TSLS 25 A 3
1749 0
3 125 A SPARE
11 9291 12000 12 9 7588 11860 10
TSCR 50 A 3
9504 14520
3 70 A XNL2
5 22893 17321 6 3 22865 17246 4
TSEQ 125 A 3
23885 16457
3 125 A XNL1
CKT Circuit Description Trip P A B C P Trip Circuit Description CKT
Enclosure: NEMA 1 FCB / MCB Rating: 350 A Mounting: SURFACE Wires: 4 Mains Rating: 400 A
Supply From: X25-SD Phases: 3 FCB / MCB: MCB Location: ELEC 2551 Volts: 480Y/277V A.I.C. Rating: 18,000
Branch Panel: 25NH1
1. PROVIDE SHUNT TRIP AND INTERLOCK WITH SUPPRESSION SYSTEM.
2. LOCATE STARTER IN KITCHEN AND INTERLOCK WITH SUPPRESSION SYSTEM.
Notes:
Total Feeder Current: 110 A
Continuous Current @ 125%: 15 A Non-Cont. Current @ 100%: 94 A
EQP_NON CONT 32900 VA 100.00% 32900 VA
EQP_CONT 4400 VA 100.00% 4400 VA Total Est. Demand Current: 107 A REC 1080 VA 100.00% 1080 VA Total Est. Demand: 38380 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 121 A 99 A 100 A Total Load: 14520 VA 11860 VA 12000 VA
41 SPACE -- -- 0 0 1 20 A SPARE 42
39 SPACE -- -- 0 0 1 20 A SPARE 40
37 SPACE -- -- 0 0 1 20 A SPARE 38
35 SPACE -- -- 0 0 1 20 A SPARE 36
33 SPACE -- -- 0 0 1 20 A SPARE 34
31 SPACE -- -- 0 0 1 20 A SPARE 32
29 SPACE -- -- 0 0 1 20 A SPARE 30
27 SPACE -- -- 0 0 1 20 A EQP - KH-1 / LIGHTS 120V 28
25 EQP - EF-2 NOTE 2 20 A 1 500 0 1 20 A EQP - KH-2 / EF-3 120V 26
23 EQP - DISHWASHER (LOCKABLE BKR) 20 A 1 1200 1000 1 20 A EQP - FOOD CART 24
21 EQP_CONT - FRIDGE (GFI BKR) 20 A 1 800 180 1 20 A REC - SERVING COUNTER 22
19 REC - KITCHEN/DINING GENERAL 20 A 1 360 180 1 20 A REC - SERVING COUNTER 20
17 2400 0 1 20 A SPARE 18
EQP - HOT WELL (LOCKABLE BKR) 30 A 2
2400 0 1 20 A SPARE 16
13 REC - KITCHEN COUNTER 20 A 1 180 800 1 20 A EQP_CONT - FRIDGE (GFI BKR) 14
11 EQP - MICROWAVE 20 A 1 1200 1200 1 20 A EQP - MICROWAVE (GFI BKR) 12
9 REC - KITCHEN COUNTER 20 A 1 180 800 1 20 A EQP_CONT - FRIDGE (GFI BKR) 10
7 4000 1000 1 20 A EQP_CONT - COFFEE MAKER 8
EQP - RANGE (GFI BKR) 50 A 2
4000 1000 1 20 A EQP_CONT - ICE MACHINE 6
3 4000 3500 4
EQP - RANGE (GFI BKR) NOTE 1 50 A 2
4000 3500
2 45 A EQP - DISHWASHER (LOCKABLE BKR)
CKT Circuit Description Trip P A B C P Trip Circuit Description CKT
Enclosure: NEMA 1 FCB / MCB Rating: 175 A Mounting: SURFACE Wires: 4 Mains Rating: 225 A
Supply From: XNL2-SD Phases: 3 FCB / MCB: FCB (MLO) Location: PRODUCTION KITCHEN 2510 Volts: 208Y/120V A.I.C. Rating: 10,000
Branch Panel: NL2
1. BALANCE RELAY LOADS BETWEEN PHASES TO EXTENT POSSIBLE.
Notes:
Total Feeder Current: 116 A
Continuous Current @ 125%: 32 A EQP_NON CONT 8777 VA 100.00% 8777 VA Non-Cont. Current @ 100%: 84 A
EQP_CONT 2800 VA 100.00% 2800 VA
REC 33120 VA 65.10% 21560 VA Total Est. Demand Current: 110 A LTG 6327 VA 100.00% 6327 VA Total Est. Demand: 39464 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 137 A 145 A 145 A Total Load: 16457 VA 17246 VA 17321 VA
83 SPACE -- -- 0 0 1 20 A SPARE 84
81 SPACE -- -- 0 0 1 20 A SPARE 82
79 SPACE -- -- 0 0 1 20 A SPARE 80
77 SPACE -- -- 0 0 1 20 A SPARE 78
75 SPACE -- -- 0 0 1 20 A SPARE 76
73 SPACE -- -- 0 0 1 20 A SPARE 74
71 SPACE -- -- 0 360 1 20 A REC - EXTERIOR GENERAL 72
69 SPACE -- -- 0 180 1 20 A REC - IT 2537 70
67 SPACE -- -- 0 0 1 20 A LCP POWER SUPPLY 68
65 SPACE -- -- 0 0 1 20 A LCP RELAYS (NOTE 1) 66
63 SPACE -- -- 0 1642 1 20 A LCP RELAYS (NOTE 1) 64
61 EQP - DBF-1 20 A 1 77 1140 1 20 A LTG - RES. RM 2505,2507,2509,2511,2513,2515 62 59 EQP_CONT - FIREPLACE 20 A 1 1000 1140 1 20 A LTG - RES. RM 2519,2521,2523,2525,2527,2529 60
57 REC - TUNNEL 20 A 1 180 103 1 20 A LTG - ELEC 2520 / 2551 58
55 EQP - SPA TUB (LOCKABLE / GFI BKR) 15 A 1 1000 100 1 20 A LTG - TUNNEL 56
53 REC - MECHANICAL 20 A 1 720 821 1 20 A LTG - MECHANICAL / STAIRWELL (NORMAL) 54
51 REC - ELEC 2520 20 A 1 180 1381 1 20 A LTG - FIRST FLOOR 52
49 REC - FOYER DESK 20 A 1 720 180 1 20 A REC - ELEC 2521 50
47 REC - FAMILY 20 A 1 720 900 1 20 A REC - FOYER DESK 48
45 REC - LIVING 20 A 1 900 900 1 20 A REC - SERVICE CORRIDOR 46
43 REC - DINING 20 A 1 540 720 1 20 A REC - FOYER 44
41 REC - GROUP 20 A 1 720 360 1 20 A REC - HOME OFFICE 42
39 REC - HSKPG/LINEN 20 A 1 360 360 1 20 A REC - MED 40
37 REC - SOILED 20 A 1 180 720 1 20 A REC - EAST CORRIDORS 38
35 REC - WEST CORRIDORS 20 A 1 1260 540 1 20 A REC - FIRE/EQUIP/UTILITY 36
33 REC - SPA GENERAL 20 A 1 360 720 1 20 A REC - TLT/STAFF GENERAL 34
31 REC - LAUNDRY COUNTER 20 A 1 360 540 1 20 A REC - NURSE 32
29 EQP_CONT - STAFF FRIDGE 20 A 1 800 1500 1 20 A EQP - WASHING MACHINE 30
27 EQP_CONT - STAFF COFFEE MAKER 20 A 1 1000 2500 28
25 EQP - STAFF MICROWAVE 20 A 1 1200 2500
2 30 A EQP - DRYER (GFI BKR)
23 REC - RESIDENT 2505 20 A 1 720 900 1 20 A REC - RESIDENT 2505 24
21 REC - RESIDENT 2507 20 A 1 720 900 1 20 A REC - RESIDENT 2507 22
19 REC - RESIDENT 2509 20 A 1 720 900 1 20 A REC - RESIDENT 2509 20
17 REC - RESIDENT 2511 20 A 1 720 900 1 20 A REC - RESIDENT 2511 18
15 REC - RESIDENT 2513 20 A 1 720 900 1 20 A REC - RESIDENT 2513 16
13 REC - RESIDENT 2515 20 A 1 720 900 1 20 A REC - RESIDENT 2515 14
11 REC - RESIDENT 2519 20 A 1 720 900 1 20 A REC - RESIDENT 2519 12
9 REC - RESIDENT 2521 20 A 1 720 900 1 20 A REC - RESIDENT 2521 10
7 REC - RESIDENT 2523 20 A 1 720 900 1 20 A REC - RESIDENT 2523 8
5 REC - RESIDENT 2525 20 A 1 720 900 1 20 A REC - RESIDENT 2525 6
3 REC - RESIDENT 2527 20 A 1 720 900 1 20 A REC -…
This is the start of the file's text. The full file is on GovTribe.