BL6 WORK ORDERS SA PEAR Jan 1 2018 thru Nov 1 2020 No PMs.pdf

PDF 543 KB Posted

Attached to
Amendment 0003 Full Maintenance Services Contract San Antonio, Pearsall, and New Federal Courthouse
Solicitation number
47PH0221R0004
Issued by

View the file

Other files

File Type Posted
SF30 Solicitation Amendment 47PH0221R0004 0003 2021 04 16.pdf PDF
San Antonio_Pearsall FM Spec 2021 04 15.pdf PDF
Changes to Solicitation 47PH0221R0004 Amendment 0002.pdf PDF
EXHIBIT C.1 Building Information Sheet_TX0501 San Antonio Federal Building_revised.pdf PDF
SF30 Solicitation Amendment 47PH0221R0004 0002 2021 04 15.pdf PDF
EXHIBIT C.1 Building Information Sheet_TX0503 AA Spears Judge Training Center_revised.pdf PDF
8 SA PROCUREMENT QUESTIONS ANSWERS.pdf PDF
9. Solicitation 47PH0221R0004 Pre-Proposal Conference Slides San Antonio & Pearsall.pptx.pdf PDF
3. RIVISED Figure B-3 Pricing of Services 47PH0221R0004.xlsx XLSX spreadsheet
5. SAN ANTONIO SITE VISIT SIGN IN SHEET 1.jpg JPG image
2. US Courthouse Commissioning Inspection Schedule.pdf PDF
4. SECOND SA SITE VISIT PHOTOS Zip File.zip ZIP file
7. Experience Worksheet - 47PH0221R0004 San Antonio Pearsall (1).pdf PDF
5. Second SAN ANTONIO SITE VISIT SIGN IN SHEET 2.jpg JPG image
10. SF30 Solicitation Amendment 47PH0221R0004 0001.pdf PDF
6. Changes to Solicitation 47PH0221R0004.pdf PDF
1. UPDATED Figure L-1 Combined Management Plan.xlsx XLSX spreadsheet
OM Photos 4-2-21-20210412T211125Z-001.zip ZIP file
Exhibit C3 Recycle Solid Water Trash Report.pdf PDF
ATTACHMENT 2 SF98 Request Wage Determination Bexar and Frio Counties New San Antonio Buy.pdf PDF
Exhibit BL3 - TX0501HS FED BLDG INFO SHEET.pdf PDF
Exhibit BL3 - TX398ZZ NEW USCH INFO SHEET (Data not Complete at this time).pdf PDF
Exhibit BL3 - TX0231ZZ PEARSALL BLDG INFO SHEET.pdf PDF
Figure L 1 Combined Management Plan.xlsx XLSX spreadsheet
Exhibit C4 - GSA Form 3638 Pest Control Work and Inspection Report.pdf PDF
Exhibit M10- PV Service Schedule V5.pdf PDF
BL2 TX0164ZZ GARCIA INVENTORY.pdf PDF
BL2 TX0503HS SPEARS INVENTORY.pdf PDF
Exhibit M5 - Smart Buildings.pdf PDF
Exhibit M3 - Environmental Sustainable Products.pdf PDF
BL7 Energy and Water Monthly Report template.docx DOCX document
ATTACHMENT 1 Mechanical CBA PMI IOEU July 2020.pdf PDF
Figure B 3 Pricing of Services.xlsx .xlsx XLSX spreadsheet
EXHIBIT C.1 BLDG INFO SHEET - Hipolito Garcia Federal Courthouse - TX0164ZZ.pdf PDF
Exhibit M9 - 2018 GSA PM Guide FINAL.pdf PDF
Exhibit BL3 - TX0503HS SPEARS BLDG INFO SHEET (To be Disposed).pdf PDF
ATTACHMENT 3 WD 2015 5291 Rev 16 date 12 21 2020 Frio County.pdf PDF
EXHIBIT C.1 BLDG INFO SHEET_Federal Parking Garage - TX0441ZZ.pdf PDF
Figure B 1 Contractors Staffing Declaration.xlsx XLSX spreadsheet
Exhibit BL3 - TX0502HS WOODS BLDG INFO SHEET (To be Disposed).pdf PDF
ATTACHMENT 1 Custodial CBA PMI LIUNA July 2020 Fully Executed FINAL.pdf PDF
EXHIBIT C.1 BLDG INFO SHEET - US Courthouse San Antonio - TX0398ZZ.pdf PDF
EXHIBIT C.1 BLDG INFO SHEET - Pearsall Federal Post Office Building - TX0231ZZ.pdf PDF
ATTACHMENT 3 WD 2015 5253 Rev 12 date 12 21 2020 Bexar County.pdf PDF
Exhibit BL3 - TX0164ZZ GARCIA BLDG INFO SHEET.pdf PDF
BL2 TX0441ZZ FED GARAGE INVENTORY.pdf PDF
EXHIBIT C.1 BLDG INFO SHEET - AA Spears Judge Training Center - TX0503HS.pdf PDF
EXHIBIT C.1 BLDG INFO SHEET - J Woods Federal Courthouse - TX0502HS.pdf PDF
Exhibit M6 - Water Treatment .pdf PDF
BL1 Fire Extinguisher Report SA and Pearsall.xlsx XLSX spreadsheet
Show 40 more

Latest 50 of 65 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

11/27/20 10:25 AM 1 / 193

Work Order List

Site: 07

Work Order Description Type Status Priority Lead Location: Asset Job Plan Parent WO Schedule Start Schedule

Finish

18-31862196 GSAI-TX0502-7.6.18 QA

Inspection-2nd floor water fountain near bldg. directory flow needs to be increased

GSAI CLOSE 3 60570

18-33163900 GSAI- Spare Fire Sprinkler Heads is missing the Wrench in room FRG1

Ground Floor

GSAI CLOSE 3 60570

18-33163910 GSAI- No Electrical IR Scan Test Tags on Emergency Disconnects

GSAI CLOSE 3 60570

18-33163931 GSAI- Air Compressor Pressure Switch is leaking air causing compressor to short cycle runtime.

GSAI CLOSE 3 60570

18-33163934 GSAI- Air Compressor Air Dryer is leaking oil, possible contamination to the system. Also lines are not cool possibly low on Refrigerant charge.

GSAI CLOSE 3 60570

18-33163938 GSAI- Rotunda Entrance is very warm, not all floor registers are supplying cool air. AHU-3X zone-01

GSAI CLOSE 3 60570

18-33163958 GSAI- H/C Railing is broken from it mount at the ramp, should be re-welded. Remove rust and touch up railing

GSAI CLOSE 3 60571

18-33352818 GSAI URGENT- IRRIGATION

SYSTEM IS IN VERY BAD DIS-

REPAIR, FRONT 2 ZONES ARE ON

ALL THE TIME BECAUSE OF BAD

SOLENOID VALVES, MOST ALL

ROTATOR AND STANDARD

SPRINKLER HEADS NEED

ADJUSTMENT OR REPLACED AS

THEY ARE SPRAYING OUT TO THE

SIDEWALKS, ON BUILDING AND

LEAKING, GREEN GRASS PATCH

INDICATED THAT THERE IS A

POSSIBLE LEAK IN THE GROUND

THAT HAS NOT SURFACED, THIS

IS A KNOWN DISTRIBUTION

CONNECTION POINT FOR MANY

ZONES ON THE WEST SIDE THAT

HAS BEEN WORKED ON BEFORE

BY THE O&M.

GSAI CLOSE 2 61269

11/27/20 10:25 AM 2 / 193

Site: 07

Work Order Description Type Status Priority Lead Location: Asset Job Plan Parent WO Schedule Start Schedule

Finish

18-33352842 GSAI- CONDENSER’S #1 & #2

WERE OBSERVED TO HAVE

BUBBLES IN THE LIQUID LINE

SIGHT GLASS, POSSIBLY LOW ON

REFRIGERANT CHARGE. UNITS

ARE UNDER WARRANTY AND

CONTRACTOR SHOULD BE

CONTACTED FOR ANY

TROUBLESHOOTING

GSAI CLOSE 61269

18-33352866 GSAI- POST IRRIGATION

SCHEDULE AND SITE DIAGRAM OF

ALL ZONE LOCATIONS

GSAI CLOSE 61269

18-33352892 GSAI ACTION- NEED TO

RECOMMEND THAT THE POST

OFFICE INSTALL MORE

RECEPTACLES AT AGENCY

EXPENSE IF THEY REQUIRE THIS

MANY OUTLETS IN THIS LOCATION

(REAR POSTAL WORK AREA)

GSAI CLOSE 61269

18-33549219 GSAI- BAS TRENDING IS NOT

TRENDING 14 DAYS FOR THE

SUMP BASIN LEVEL ON

CONDENSATE SYSTEM

GSAI CLOSE 2 63075

18-34287144 GSAI- SD-2C-04 IS NOT MEETING

SA FLOW SP AND HUMIDITY DATA

IS MISSING FROM THE BANNER.

DA TEMP IS READING 0.0°

GSAI CLOSE 2 63068 376212

18-34287219 GSAI- SD-2C-07 IS NOT MEETING

SA FLOW SP AND HUMIDITY DATA

IS MISSING FROM THE BANNER.

DA TEMP IS READING 0.0°

GSAI CLOSE 2 63068 376212

18-34287259 GSAI- FP-2C-09 IS NOT MEETING

SA FLOW SP AND HUMIDITY DATA

IS MISSING FROM THE BANNER.

BUTTON ICONS MISSING FROM

SCHEDULE AND ENABLE

BUTTONS, BOX_ENABLE POINT IS

FAULTED

GSAI CLOSE 2 63068 376212

18-34376975 GSAI *URGENT* CONDENSERS

ARE VERY DIRTY NEED TO BE

PM'D ASAP!

GSAI CLOSE 2 63190 1822138

18-34493166 GSA - Elevator landings in basement SW stairway paint is chipping

GSAI CLOSE 3 63064

11/27/20 10:25 AM 3 / 193

Site: 07

Work Order Description Type Status Priority Lead Location: Asset Job Plan Parent WO Schedule Start Schedule

Finish

18-34517588 #2 boiler alarm. "Flame lost early in run". Igniter failure.

CM CLOSE 2 63064

18-34551685 GSAI REWORK-SD-2C-04

DISCHARGE AIR TMP= 0.0

GSAI CLOSE 2 63068

18-34551763 GSAI REWORK-SD-2C-07

DISCHARGE AIR TMP= 0.0

GSAI CLOSE 2 63068

18-34697185 GSAI- MAIN ELECTRIC METER IS

NOT RECORDING DATA ON BAS

GRAPHICS UTILITY ROOM

GSAI CLOSE 2 61269

18-35521305 GSAI- ALARM- Hipolito Hot Water System/Boiler 2 Alarm

GSAI CLOSE 2 63064 376252

18-35545908 GSAI- RAILING AT THE

HANDICAPPED RAMP HAS

BROKEN WELD FROM THE MOUNT

NEAR LOADING ZONE EAST RAMP

NEAREST TO TX502

GSAI CLOSE 3 92346

18-35546641 GSAI- EXTERIOR TREES NEED

TRIMMING

GSAI CLOSE 3 92374

18-35725946 GSAI- 2ND FLOOR WOMEN

RESTROOM North Side next to room

218 - Stained ceiling tile

GSAI CLOSE 3 63611

18-35853204 GSAI- WOMEN'S RESTROOM BY

ROOM 218 GROUT DISCOLORED

GSAI CLOSE 3 63611

18-36533226 GSAI- 5TH FLOOR LOCATED IN

HALL OUTSIDE OF ROOM 546

CEILING PAINT PEELING

GSAI CLOSE 3 63071

18-36533228 GSAI- 5TH FLOOR NORTHEAST

STAIRWAY PAINT PEELING

GSAI CLOSE 3 63071

18-36533231 GSAI- 3RD FLOOR LANDINGS

ACROSS FROM SOUTHWEST

STAIRWAY PAINT CHIPPING ON

ELEVATOR

GSAI CLOSE 3 63069

18-36533236 GSAI- THE CORNER OF THE

CONCRETE BASE AT THE BOTTOM

OF THE HANDRAIL IN THE WELL

NEXT TO SPOT #14 IS CRACKED

AND FALLING APART

GSAI CLOSE 3 63603

18-36533240 GSAI- HAND RAILS GOING DOWN

TO THE WELL HAVE RUST SPOTS

GSAI CLOSE 3 92346

11/27/20 10:25 AM 4 / 193

Site: 07

Work Order Description Type Status Priority Lead Location: Asset Job Plan Parent WO Schedule Start Schedule

Finish

18-36547883 GSAI- TX0501- BAS Please notice that ahu-14 is not controlling to set point in the respective zones, please have investigated and corrected.

GSAI CLOSE 2 60569

18-36547887 GSAI- TX0501- BAS Please notice that AHU-15 is not controlling to set point in the respective zones, please have investigated and corrected.

GSAI CLOSE 2 60569

18-36548793 GSAI- TX0501 BAS IT APPEARS

THAT THE ELECTRIC WATER

HEATER IS ENERGIZED BUT WE

HAVE 168 DEG WATER FROM THE

HEAT EXCHANGER, ALSO THE

HWV SAYS 0%. PLEASE

INVESTIGATE WATER HEATER &

HW VALVE OPS.

GSAI CLOSE 2 63589

18-36736569 GSAI- BAS AHU-12 SA TEMP IS 48

DEG WITH UNIT OFF AND CHWV

AT 0%, PLEASE INVESTIGATE

CHWV OPERATIONS

GSAI CLOSE 2 60569

18-36740901 GSAI- CHAIN MISSING UNDER THE

BUILDING NORTH AND SOUTH SIDE

GSAI CLOSE 3 92374

18-36741707 GSAI- BASEMENT ELEVATOR

LANDINGS SW STAIRWAY PAINT

CHIPPING

GSAI CLOSE 3 63064

18-36741732 GSAi- WATER LEAK OUTSIDE OF

HUB BREAK ROOM ON THE 3RD

FLOOR ROOM 323

GSAI CLOSE 2 63069

18-36742130 GSAI-BASEMENT OUTSIDE OF ST

B-3 PAINT PEELING

GSAI CLOSE 3 63064

18-36742492 GSAI- MISSING COMPONENT ON

1ST FLOOR MEN'S RESTROOM

DOOR CLOSURE

GSAI CLOSE 3 63591

18-37018897 GSAI-Two fire extinguishers were not checked NUMBERS 210

GSAI CLOSE 3 92378

18-37018931 GSAI-Adjust presidential portraits to the same height

GSAI CLOSE 3 63604

18-37018943 GSAI- Door will not stay open (ground floor near G-84)

GSAI CLOSE 3 63601

18-37018963 GSAI- 2 MUSHROOM LIGHTS ARE

OUT ON THE PLAZA

11/27/20 10:25 AM 5 / 193

Site: 07

Work Order Description Type Status Priority Lead Location: Asset Job Plan Parent WO Schedule Start Schedule

Finish

18-37949952 GSAI- WALL COVERING IS

PEELING ABOVE WATER

FOUNTAIN ON THE 2ND FLOOR

NORTH SIDE PUBLIC SIDE

GSAI CLOSE 3 63611

18-37950156 GSAI- T-7-2 WOMEN'S RESTROOM

GROUT DISCOLORED

GSAI CLOSE 3 63597

18-37952482 GSAI- MAIN ENTRANCE

REVOLVING DOOR HAS VERTICAL

STRIP LOOSE

GSAI CLOSE 3 63067

18-37953989 GSAI- Concrete cracked on the railing at the landing on the stairs leading down to the well

GSAI CLOSE 3 63603

18-37954193 GSAI- MUSHROOM LIGHT OVER

PARKING SPOT NUMBER 155 IS

OUT

GSAI CLOSE 3 63603

18-37954290 GSAI- PARKING STOP IN PARKING

SPACE 131

GSAI CLOSE 3 63603

11/27/20 10:25 AM 6 / 193

Site: 07

Work Order Description Type Status Priority Lead Location: Asset Job Plan Parent WO Schedule Start Schedule

Finish

18-38233753 TX0502_Courthouse Pecan Tree Pruning as required

GSAI CLOSE 3 63603

19-38786220 GSAI- T-3-3 CHECK NO HOT WATER GSAI CLOSE 3 63593

19-38786871 GSAI- T-3-3 LIGHT LENS COVER IS

CRACKED

GSAI CLOSE 3 63593

19-38787980 GSAI- T-3-3 LIGHT OUT OVER SINK GSAI CLOSE 3 63593

19-38788590 GSAI- B-308C WALL STAINED GSAI CLOSE 3 63593

19-38789584 GSAI- B-306D TRASH PICK UP NOT

DONE

GSAI CLOSE 3 63593

19-38790278 GSAI- B-302-E LIGHT OUT IN

BREAKROOM

GSAI CLOSE 3 63593

19-38790918 GSAI- B-302-E NO HOT WATER

CHECK WATER PRESSURE

GSAI CLOSE 3 63593

19-38791661 GSAI- B-207 BREAK ROOM VCT

SCUFFED FLOORS

GSAI CLOSE 3 63593

19-38792214 GSAI- ELEVATOR 3 PLASTIC

ANNOUNCEMENT HOLDER IS

CROOKED

GSAI CLOSE 3 63591

19-38795475 GSAI- G-37 BREAK ROOM FLOOR

IS SCUFFED

GSAI CLOSE 3 63601

19-38797441 GSAI- HIGH WATER PRESSURE IN

T-M-1-2

GSAI CLOSE 3 63604

19-38800890 GSAI- AHU 1 DEBRIS FOUND BY

MOTOR

GSAI CLOSE 3 63190

19-38802267 GSAI- AHU-1 SEAL COMING OFF

BY AIR FILTERS

GSAI CLOSE 3 63190

19-38802714 GSAI- AHU 1 INSULATION COMING

OFF

GSAI CLOSE 3 63190

19-38804278 GSAI- MECHANICAL ROOM WATER

TREATMENT UNIT IS SPOILED

GSAI CLOSE 63189

19-38805139 GSAI- WATER HEATER IN

MECHANICAL ROOM APPEARS TO

HAVE RUST SPOTS

GSAI CLOSE 3 63190

19-38806189 GSAI- NO HOT WATER IN POST

MASTERS RESTROOM

GSAI CLOSE 3 63190

11/27/20 10:25 AM 7 / 193

Site: 07

Work Order Description Type Status Priority Lead Location: Asset Job Plan Parent WO Schedule Start Schedule

Finish

19-38818469 GSAI- CHECK WATER PRESSURE

IN POST OFFICE MASTER

RESTROOM APPEARS TO

FLUCTUATE

GSAI CLOSE 3 63190

19-38819534 GSAI- POST OFFICE RUST STAINS

IN JANITORS CLOSET IN SINK AND

FIXTURE

GSAI CLOSE 3 63190

19-38820449 GSAI- POST OFFICE ESCUTCHEON

IS LOOSE

GSAI CLOSE 3 63190

19-39171163 GSAI- 3RD FLOOR CORRIDOR

DEBRIS AND FOREIGN PARTICALS

THROUGHOUT FLOOR BY CHAIRS

GSAI CLOSE 3 63069

19-39171183 GSAI- 3RD FLOOR ROOM 333

HEARING ROOM CARPET STAINS

THROUGHOUT

GSAI CLOSE 3 63069

19-39171212 GSAI- 3RD FLOOR ELECTRICAL

ROOM BY ROOM 332 BREAK

PANEL DOORS ARE OPEN AND

NOT SECURED

GSAI CLOSE 3 63069

19-39171229 GSAI- DOL OFFICE SPACE DUST

ON HORIZONTAL SURFACES AND

PARTITIONS DEBRIS FOREIGN

PARTICALS ON CARPET IN

CONFERENCE ROOM

GSAI CLOSE 3 63067

19-39171487 GSAI- 3RD FLOOR UNISEX

RESTROOM NO SOAP IN

DISPENSER AND DOOR DOES NOT

CLOSE PROPERLYQ

GSAI CLOSE 3 63069

19-39247402 GSAI- There are multiple issue's with AHU-4B, RH not reading correctly, Bldg Static is negative, SA SP not meeting setpoint.

GSAI CLOSE 3 63068

19-39339037 1ST FLOOR LOBBY REVOLVING

DOORS SWINGING OPEN

WR CLOSE 3 63591 385809

19-39402818 GSAI- THROUGH OUT ENTIRE

BUILDING FIRE EXTINGUISHER

TAGS ARE TORN

GSAI CLOSE 3 61262

19-39405261 FB: ITC entrance gate is OOC GSAI CLOSE 3 92310

19-40244097 BLINDS IN SUITE 569 REPORTED

STUCH IN HALF WAY UP

WR CLOSE 3 63071

11/27/20 10:25 AM 8 / 193

Site: 07

Work Order Description Type Status Priority Lead Location: Asset Job Plan Parent WO Schedule Start Schedule

Finish

19-40256498 QC- 4TH FLOOR MEN'S

RESTROOM SOAP DISPENSER

NEEDS BATTERIES

WR CLOSE 3 63594

19-40265508 3RD FLOOR ROOM 359 LOCK

MAGNESIUM NOT ATTACHING

WR CLOSE 3 63069

19-40268469 1ST FLOOR LOBBY AREA SPILLED

COFFEE BY SECURITY GUARD

STATION

WR CLOSE 3 63067

19-40390524 GSAI- The Domestic Hot Water at the J Woods CH is in Alarm and @ a scalding 131 deg. This has potential to harm someone, the set point is 120 deg. that's 11 deg OVER SET POINT, and why are we not getting this

Alarm? The control valve does appear to be reacting and is at 100% open.

Please investigate ASAP! SAFETY

ISSUE

GSAI CLOSE 3 60570

19-40390778 GSAI- BOILER 6 OVER SET POINT

OF 142 DEGREE BURNER IS AT 100

PERCENT

GSAI CLOSE 3 92376 1286359

19-40391303 1ST FLOOR NURSE EKG ROOM

DOOR KNOB IS COMING APART

WR CLOSE 3 63591

19-40391359 2ND FLOOR REPAIR US MARSHAL

DOOR IS NOT WORKING

PROPERLY

WR CLOSE 3 63604

19-40472129 GSA- Cacked and stained ceiling tile ground floor womens rest room

GSAI CLOSE 3 63601

19-40472130 GSAI- SECOND FLOOR ROTUNDA

AREA 2 LIGHTS OUT

GSAI CLOSE 3 63605

19-40472131 GSAI- Cacked ceiling tiles ground floor back of the house

GSAI CLOSE 3 63601

19-40472133 GSAI- Carpet stains east and west ramp

GSAI CLOSE 3 63609

19-40472134 GSAI- Dead insect in front of room 224 GSAI CLOSE 3 63611

19-40472135 GSAI- 3RD FLOOR SUITE 340

CARPET POTENTIAL TRIPPING

HAZARD

GSAI CLOSE 3 63069

19-40472136 GSA- SITTING AREA GROUND

LEVEL TRASH

GSAI CLOSE 3 63586

11/27/20 10:25 AM 9 / 193

Site: 07

Work Order Description Type Status Priority Lead Location: Asset Job Plan Parent WO Schedule Start Schedule

Finish

19-40472137 GSAI- UPPER AND LOWER LEVEL

TRASH AND FLOORS DIRTY

GSAI CLOSE 3 61284

19-40473047 REMOVE BROKEN BRICKS FROM

PARKING SPACE 106. TRIPPING

HAZARD

WR CLOSE 1 92310

19-40473112 GSAI- 1ST FLOOR MEDCOM

WOMEN'S RESTROOM FACE

PLATE COMING OFF

GSAI CLOSE 3 63067

19-40473129 GSAI- 1ST FLOOR OUTSIDE OF

ROOM 157 CEILING TILE STAINS

GSAI CLOSE 3 63067

19-40473273 GSAI- 3RD FLOOR ROOM 333

LIGHT FIXTURE LIGHT OUT

GSAI CLOSE 3 63069

11/27/20 10:25 AM 10 / 193

Site: 07

Work Order Description Type Status Priority Lead Location: Asset Job Plan Parent WO Schedule Start Schedule

Finish

19-40473717 3RD FLOOR ROOM 333 CARPET

HAS BLACK STAINS

GSAI CLOSE 3 63069

19-40709829 GSAI- ALARM BAS-Federal Bldg, San Antonio TX:Hot Water System/

Blr1Gen_Alarm

GSAI CLOSE 2 60569

19-40746420 GSAI- stained ceiling tile in center conference room (208)

GSAI CLOSE 3 63611

19-40757094 GSAI- BAS Hipolito Garcia Federal Bldg - San Antonio, TX:Condenser

Water Treatment/ pH_Level

GSAI CLOSE 2 63075

19-40757135 GSAI- ALARM BAS-Hipolito Garcia Federal Bldg - San Antonio, TX:Condenser Water Treatment/ Conductivity

GSAI CLOSE 2 61262

19-40768478 1ST FLOOR US REP WILL HURD

OFFICE BLINDS TO WINDOWS NOT

OPENING

WR CLOSE 3 63591

19-40769760 ITC GATE IS NOT WOKRING

PROPERLY

WR CLOSE 2 92310 982052

19-40807950 Jury Rm #365 is extremely warm WR CLOSE 2 60570

19-40903000 Low Limit alarm on Liebert Unit CM CLOSE 3 63599 385980

19-40990753 3RD FLOOR ROOM 347

REUESTING TENANT BY THE

NAME CHERYL UBOGY CARPET IN

WORK SPACE TO BE CLEANED

WR CLOSE 3 63069

19-40990771 ALL ELEVATORS IN J WOODS

BUILDING ARE NOT WORKING

REPORTED BY PATRICIA ORTIZ

WR CLOSE 2 63602

19-40990784 2ND FLOOR OFFICE 275

REPORTED BY ASHLEY MORALES

LIGHTS OUT

WR CLOSE 3 63068

19-40991174 GSAI- SS-8A IS MISSING

LIGHTNING PROTECTION

GROUNDING CABLE. THIS SHOULD

BE GROUNDED TO THE VENT PIPE

AND THE PIPE TO THE CABLE TO

THE COOLING TOWER- THIS HAS

BEEN WRITTEN UP BEFORE W/O#

25203464

GSAI CLOSE 2 61262

11/27/20 10:25 AM 11 / 193

Site: 07

Work Order Description Type Status Priority Lead Location: Asset Job Plan Parent WO Schedule Start Schedule

Finish

19-40991183 GSAI- CONDENSATE

NEUTRALIZATION TANKS ON BOTH

BOILERS ARE CONTAMINATED

AND NEED TO REPLACE

LIMESTONE, CLEAN TANKS AND

TEST pH ON A REGULAR BASIS, THERE ARE NO RECORDS OF THIS

BEING DONE. THIS LEADS TO AN

ACIDIC CONDITION WHERE IRON

DRAIN PIPES WILL BE

DETERIORATED.

GSAI CLOSE 2 61262

19-40991186 GSAI- AHU-6G HAS LOOSE BELT

GUARD, COILS ARE DIRTY AND

RETURN AIR DAMPER IS DIRTY

AND NEED TO LUBRICATE ALL

PIVOT POINTS. DO NOT USE ACID

CHEMICALS AS THIS DRAINS INTO

THE COLLECTION TANK

GSAI CLOSE 2 61262

19-40991194 GSAI- AHU-6A COILS NEED TO BE

CLEANED AND RETURN DAMPER

IS DIRTY AND NEEDS ALL PIVOT

POINTS LUBRICATED. DO NOT

USE ACID CHEMICALS AS THIS

DRAINS INTO THE COLLECTION

TANK

GSAI CLOSE 2 61262

19-40991199 GSAI- ALL BACKFLO PREVENTERS

ARE DUE AND NEED TO BE

POSTED AT ALL DEVICES.

GSAI CLOSE 2 61262

19-40991204 GSAI- HUMIDIFIER H-2 HAS

MULTIPLE ALARMS THAT HAVE

BEEN MANUALLY CLEARED AND

NO WORK ORDERS HAVE BEEN

ENTERED WITH EXPLANATION OF

REMEDIATION OF PROBLEM.

FAULTY WATER PROBE, CLEAN

PROBES, TANK NOT DRAINING.

GSAI CLOSE 2 61262

19-40991212 GSAI- HUMIDIFIER H-1 HAS

MULTIPLE ALARMS THAT HAVE

BEEN MANUALLY CLEARED AND

NO WORK ORDERS HAVE BEEN

ENTERED WITH EXPLANATION OF

REMEDIATION OF PROBLEM.

DUCT HIGH LIMIT TRIP

GSAI CLOSE 2 61262

11/27/20 10:25 AM 12 / 193

Site: 07

Work Order Description Type Status Priority Lead Location: Asset Job Plan Parent WO Schedule Start Schedule

Finish

19-40991217 GSAI- AHU-6C SAFETY INDICATOR

LIGHT IS OUT ON MOTOR

CONTROLLER HOA SWITCH

GSAI CLOSE 2 61262

19-40991224 GSAI- ERU-B SPEED CONTROLLER

IS IN HAND POSITION, THIS

SHOULD BE IN AUTO, NEED TO

INVESTIGATE

GSAI CLOSE 2 61262

19-40991227 GSAI- COOLING TOWER MEDIA

FILL IS IN BAD REPAIR, POSSIBLY

BAD CLEANING PRACTICES,

NEEDS CLEANING, RECOMMEND

REPLACING MEDIA FILL

GSAI CLOSE 2 61262

19-40991230 GSAI- EF-10 HAS BAD BELT AND

BEARING IS DIRTY AND NO

INDICATION OF GREASE

GSAI CLOSE 2 61262

19-40991232 GSAI- ERU-A ENTHALPY WHEEL IS

DIRTY AND NEEDS TO CLEANED/

PM’D

GSAI CLOSE 2 61262

19-40991234 GSAI- CU-5 FAN HAS SLIPPED

DOWN ON MOTOR SHAFT AND IS

RUBBING ON THE WEATHER

HOOD FOR THE MOTOR, THE FAN

BLADE HAS WEAR MARKS FROM

FRICTION WHEN SPINNING

GSAI CLOSE 2 61262

19-40991241 GSAI- SOLAR HOT WATER

COLLECTOR, TEMPERATURE

SENSORS ARE LEAKING ON BOTH

BANKS

GSAI CLOSE 2 61262

19-41860633 GSAI- ((RE-WORK)) SEE LONG

DESCRIPTION FOR SCREEN SHOT

Heating Hot Water DP is not meeting set point, needs to be investigated.

GSAI CLOSE 2 61262

19-41861525 BAS-SA Fed Bldg Alarm From SAT Federal Bld - 2nd Floor East

Computer Room Space Temp

GSAI CLOSE 3 60569

19-41866080 4TH FLOOR JOE UVIEDO OFFICE

ROOM NUMBER 457 REPORTED

LIGHT OUT IN OFFICE

WR CLOSE 3 63070

19-41866796 MISC- 1ST FLOOR MEDCOM

REQUESTING WALL HANGING IN

ROOM 118

WR CLOSE 3 63067

11/27/20 10:25 AM 13 / 193

Site: 07

Work Order Description Type Status Priority Lead Location: Asset Job Plan Parent WO Schedule Start Schedule

Finish

19-41867867 3RD FLOOR OFFICE ROOM 341

IONA DUPRE REPORTED WATER

LEAKING IN COMPUTER ROOM

WR CLOSE 3 63069

19-41875709 4TH FLOOR NORTH CORRIDOR IN

PROBATION SPACE HAS 2 SETS

OF IIGHTS OUT. ONE BY ROOM

W409 AND G405. REPORTED BY

RICARDO FRIAS

WR CLOSE 3 63594

19-41876182 AHU_13 - AHU Discharge Temperature Setpoint Unreachable

CM CLOSE 3 92338 981963

19-41876331 GSAI- AVENUE E SIDE OF

BUILDING TRASH ON FLOOR

GSAI CLOSE 3 61284

19-41876346 GSAI- 5TH FLOOR WOMEN

RESTROOM ACROSS FROM ROOM

587 COMMODE FIXTURE LEAKS

WHEN FLUSH

GSAI CLOSE 2 63071

19-41876375 GSAI- CHECK BELT ON AHU 24 GSAI CLOSE 3 92332 981938

19-41876578 GSAI- THERE IS CORROSION BY

COIL ON AHU 24

GSAI CLOSE 3 92332 981938

19-41876589 GSAI- THERE IS CORROSION BY

COIL ON AHU 25

GSAI CLOSE 3 92332 981943

19-41876603 GSAI- 1ST FLOOR MENS

RESTROOM DOOR IS OPEN AND

DOESN'T CLOSE

GSAI CLOSE 3 63591

19-41876618 GSAI- FIRE SPRINKLER VALVE ON

5TH FLOOR EAST STAIRWAY HAS

CORROSION

GSAI CLOSE 3 63595

19-41876651 GSAI- GROUT DISCOLORED IN

T-5-2

GSAI CLOSE 3 63595

19-41876692 GSAI- INSIDE HANDICAP BUTTON

IS OOS IN T-5-2

GSAI CLOSE 3 63595

19-41876711 GSAI- GROUT DISCOLORED IN

T-5-1

GSAI CLOSE 3 63595

19-41876721 GSAI- J-5-B DOOR SPLATER GSAI CLOSE 3 63595

19-41876731 GSAI- THERE IS CORROSION ON

AHU 22

GSAI CLOSE 3 92330 981928

19-41876829 GSAI- 4TH FLOOR ROOM 456 PEST

CONTROL NEEDED

GSAI CLOSE 3 63070

11/27/20 10:25 AM 14 / 193

Site: 07

Work Order Description Type Status Priority Lead Location: Asset Job Plan Parent WO Schedule Start Schedule

Finish

19-41877244 Very cold at the entr. area to the Clerk's Rm (Rm #G-65).

GSAI CLOSE 3 60570

19-41878609 GSAI- FOH CARPET STAINS IN

ROOM NUMBER A-123-C

GSAI CLOSE 3 63591

19-41878616 GSAI- FOH WALL STAINS A-127-D GSAI CLOSE 3 63591

19-41878629 GSAI- GROUND MAINTENANCE

WEEDS IN FRONT OF BUILDING

GSAI CLOSE 3 92310

11/27/20 10:25 AM 15 / 193

Site: 07

Work Order Description Type Status Priority Lead Location: Asset Job Plan Parent WO Schedule Start Schedule

Finish

19-41878634 GSAI- EXIT GATE BARRIER ARM

BOUNCES AND APPEARS LOW

GSAI CLOSE 2 92310 982063

19-41878664 GSAI- ACESS PANEL T-6-1 HAS

CORROSION

GSAI CLOSE 3 63591

19-41878670 GSAI- T-6-1 SOAP DISPENSER

NEEDS SOAP

GSAI CLOSE 3 63596

19-42009602 GSAI- ALARMS- Federal Bldg, San Antonio TX:ShwS_Temp

GSAI CLOSE 3 60569

19-42009608 GSAI- ALARMS- Hipolito Garcia Federal Bldg - San Antonio, TX:P07Q8ETX0164SANT5:AHU-6A/

SA_Fan_Status

GSAI CLOSE 3 61262

19-42009609 GSAI- ALARMS- Hipolito Garcia Federal Bldg - San Antonio, TX:P07Q8ETX0164SANT5:AHU-6A/

RA_Fan_Status

GSAI CLOSE 3 61262

19-42010964 AHU_26 - AHU Discharge Temperature Setpoint Unreachable

CM CLOSE 3 92339 981948

19-42010975 BLR 03 - Boiler Cycling CM CLOSE 3 63589 1287426

19-42010991 BLR 02 - Boiler Cycling CM CLOSE 3 63589 1287425

19-42011018 BLR 01 - Boiler Cycling CM CLOSE 3 63589 1287424

19-42011042 AHU_15 - AHU Discharge Temperature Setpoint Unreachable

CM CLOSE 3 92312 981934

19-42011053 AHU_10 - AHU Discharge Temperature Setpoint Unreachable

CM CLOSE 3 63589 385759

19-42014458 GSAI- WRR - N side (partition door is seperating)

GSAI CLOSE 3 63610

19-42017356 GSAI- Glass entry doors observed to be dirty.

GSAI CLOSE 3 60571

19-42022626 GSAI-dust observed on the front side (Blue shelf) of the guard desk

GSAI CLOSE 3 63604

19-42022707 GSAI- Ground Floor (debris observed on the floor in front of the door where construction is being performed in the

USDC area)

GSAI CLOSE 3 60570

19-42023203 GSAI- AHU-3 - observed the filter is dirty

GSAI CLOSE 3 92373 982138

11/27/20 10:25 AM 16 / 193

Site: 07

Work Order Description Type Status Priority Lead Location: Asset Job Plan Parent WO Schedule Start Schedule

Finish

19-42023224 GSAI- Fire extinguisher #4-2 - has not been inspected

GSAI CLOSE 3 60570

19-42023241 GSAI- Room #438 - observed the lockset to be loose

GSAI CLOSE 3 63607

19-42023258 GSAI-3rd floor (South side) water fountion - observed no GFI outleT

GSAI CLOSE 3 63606

19-42026745 EMPLOYEE ENTRANCE DOOR

EXTERIOR NOT WORKING

PROPERLY

GSAI CLOSE 3 63591 385784

19-42027476 GSA Office: Re-Configure Existing Cubicle into 2 Sections

WR CLOSE 3 63596

19-42037349 GSAI- ALARMS- Federal Bldg, San Antonio TX:ShwS_Temp

GSAI CLOSE 3 60569

19-42039059 4TH FLOOR OFFICE A407D

SOUTHEAST WING REPORTED

TEMPERATURE ADJUSTMENT TO

HOT READING 79 DEGREES.

REPORTED BY RICARDO FRIAS

WR CLOSE 3 92325 981923

19-42039167 5TH FLOOR DISTRICT COURT

PORTION TEMPERATURE IS TO

WARM NEED ADJUSTMENTS AND

COOLED DOWN. REPORTED BY

ROBERT KERSH

WR CLOSE 3 92332 981938

19-42039315 2ND FLOOR ROOM B-207 CEILING

LIGHT ABOVE CUBICAL IS OUT.

REPORTED BY MAMIE RODRIGUEZ

WR CLOSE 3 63592

19-42039888 2ND FLOOR PUBLIC DEFENDERS

REQUESTING OVERTIME UTILITIES

FOR 03/23 AND 03/24 FROM 10AM

TO 10PM

WR CLOSE 3 92317 981939

19-42041059 4TH FLOOR OFFICE A407D

SOUTHEAST WING REPORTED

TEMPERATURE ADJUSTMENT TO

HOT READING 79 DEGREES.

REPORTED BY RICARDO FRIAS

WR CLOSE 3 92321 981954

19-42041519 7TH FLOOR SOCIAL SECURITY

REQUESTING OVERTIME UTILITIES

FOR 03/23 FROM 7AM TO 12PM

WR CLOSE 3 92338 981953

19-42042372 7TH FLOOR SOCIAL SECURITY

REQUESTING OVERTIME UTILITIES

FOR 03/23 FROM 7AM TO 12PM

WR CLOSE 3 92339 981948

11/27/20 10:25 AM 17 / 193

Site: 07

Work Order Description Type Status Priority Lead Location: Asset Job Plan Parent WO Schedule Start Schedule

Finish

19-42042779 2ND FLOOR ROOM 275 REPORTED

PLUG BOX ON THE OUTER WALL

NEAR WINDOW IS NOT WORKING

REPORTED BY ASHLEY MORALES

WR CLOSE 3 63068

19-42042914 4TH FLOOR NORTH CORRIDOR IN

PROBATION SPACE REPORTED

TWO SETS OF LIGHTS OUT. ONE

IN ROOM W409 AND G405.

REPORTED BY RICARDO FRIAS

WR CLOSE 3 63594

19-42045062 3RD FLOOR CONFERENCE ROOM

B302L REQUESTING

TEMPERATURE ADJUSTMENTS TO

WARM NEED COLD AIR.

REQUESTED BY RICARDO FRIAS

WR CLOSE 3 92322 981949

19-42048753 Central Office Master Fire Alarm Panel Data Request: Follow the two tasks in the Planning Tab.

WR CLOSE 3 60569

19-42048754 Central Office Master Fire Alarm Panel Data Request: Follow the two tasks in the Planning Tab.

WR CLOSE 3 60570

19-42048755 Central Office Master Fire Alarm Panel Data Request: Follow the two tasks in the Planning Tab.

WR CLOSE 3 60571

19-42049271 Central Office Master Fire Alarm Panel Data Request: Follow the two tasks in the Planning Tab.

WR CLOSE 3 61262

19-42049278 Central Office Master Fire Alarm Panel Data Request: Follow the two tasks in the Planning Tab.

WR CLOSE 3 61269

19-42049290 Central Office Master Fire Alarm Panel Data Request: Follow the two tasks in the Planning Tab.

WR CLOSE 3 61284

19-42056887 GSAI- GROUNDS IN FRONT OF

BUILDING SPRINKLER HEADS

APPEARS TO BE HIGH

GSAI CLOSE 90244

19-42056903 GSAI- MECHANICAL ROOM CHECK

BELT ON AHU 2 MAY BE LOOSE

GSAI CLOSE 3 63190 1822214

19-42056921 GSAI- MECHANICAL ROOM LOGS

APPEAR OUT OF DATE

GSAI CLOSE 3 61269

19-42056944 GSAI- MECHANICAL ROOM CHECK

FOR LEAKS

GSAI CLOSE 3 90245

11/27/20 10:25 AM 18 / 193

Site: 07

Work Order Description Type Status Priority Lead Location: Asset Job Plan Parent WO Schedule Start Schedule

Finish

19-42056977 GSAI- SDS OFFICE IS THERE A

LOTO BINDER

GSAI CLOSE 3 63190

19-42056985 GSAI- TEMPERATURE REPORTED

COLD IN ROOM 107

GSAI CLOSE 3 90252

19-42057003 GSAI- TEMPERATURE REPORTED

WARM IN ROOM 103

GSAI CLOSE 3 63190

19-42082601 GSAI- TEMPERATURE REPORTED

COLD IN 104 BREKROOM

GSAI CLOSE 3 90248

19-42082751 GSAI- TOILET IN MEN'S

RESTROOM IS NOT FLUSHING

WELL

GSAI CLOSE 2 63190

19-42138267 AHU_21 - Sensor Out Of Range CM CLOSE 3 92325 981923

19-42138468 AHU_24 - AHU Cooling Valve Unstable

CM CLOSE 3 92332 981938

11/27/20 10:25 AM 19 / 193

Site: 07

Work Order Description Type Status Priority Lead Location: Asset Job Plan Parent WO Schedule Start Schedule

Finish

19-42138567 AHU_09 - AHU Discharge Temperature Setpoint Unreachable

CM CLOSE 3 63589 385773

19-42138588 HWS PLNT - Hot Water System Failure

CM CLOSE 3 60569

19-42171112 7TH FLOOR SOCIAL SECURITY

REQUESTING OVERTIME UTILITIES

FOR 03/30 FROM 7AM TO 12PM

REQUESTED BY ALFONZO

MERCADO

WR CLOSE 3 92339 981948

19-42171113 7TH FLOOR SOCIAL SECURITY

REQUESTING OVERTIME UTILITIES

FOR 03/30 FROM 7AM TO 12PM

REQUESTED BY ALFONZO

MERCADO

WR CLOSE 3 92338 981953

19-42171115 GATE BETWEEN JWOODS AND

FEDERAL BUILDING IS OUT OF

SERVICE

WR CLOSE 2 92346 982233

19-42171116 5TH FLOOR MEN'S PUBLIC

RESTROOM DOOR HAS FILM OF

GREASSE OR VANISH AND

COVERED WITH A STRONG

SMELLING SUBSTANCE.

REPORTED BY ROBERT KERSH

WR CLOSE 3 63595

19-42189575 7TH FLOOR SOCIAL SECURITY

WINDOW 18 CUSTOMER

URINATED ON SEAT AND FLOOR

REPORTED BY MICHAEL VON

FANGE

WR CLOSE 3 63597

19-42189694 GROUND FLOOR ELEVATOR THAT

MARSHAL PRISONERS USE IS NOT

RUNNING

WR CLOSE 2 63604 386103

19-42189731 MISC- HANGING OF MISSING

CHILDREN POSTING

WR CLOSE 3 63067

19-42189739 MISC- HANGING OF MISSING

CHILDREN POSTING

WR CLOSE 3 63591

19-42189745 MISC- HANGING OF MISSING

CHILDREN POSTING

WR CLOSE 3 63604

19-42189749 MISC- HANGING OF MISSING

CHILDREN POSTING

WR CLOSE 3 63190

11/27/20 10:25 AM 20 / 193

Site: 07

Work Order Description Type Status Priority Lead Location: Asset Job Plan Parent WO Schedule Start Schedule

Finish

19-42189754 GSAI- INVESTIGATE IF ANY WATER

LEAKS IN FEDERAL PARKING

GARAGE

GSAI CLOSE 61284

19-42189765 MISC- CLEANING AND

DISINFECTING OF FITNESS

CENTER

WR CLOSE 3 89446

19-42189771 MISC- CLEANING AND

DISINFECTING OF FITNESS

CENTER

WR CLOSE 3 63589

19-42189780 3RD FLOOR ROOM 302F READING

63 DEGREES REQUESTED

TEMPERATURE ADJUSTMENT TO

COLD. REPORTED BY RICARDO

FRIAS

WR CLOSE 3 92321 981954

19-42190858 GSAI- FIRE EXTINGUISHER NOT

CHECKED IN SIESTA ROOM #206

AND #204

GSAI CLOSE 3 63611

19-42190873 GSAI- OBSERVED THE

LANDSCAPE TILES OUT OF PLACE

GSAI CLOSE 3 92374

19-42190880 GSAI- COFFEE STAINS

THROUGHOUT THE GROUND

FLOOR HALLWAY AND ROOM 6-37

EMPLOYEE HALLWAY

GSAI CLOSE 3 63601

19-42190886 GSAI- MISSING SDS SHEETS FOR

CHEMICALS BEING STORED IN

MECHANICAL ROOM G-1

GSAI CLOSE 3 63601

19-42190942 GSAI- EMPLOYEE GROUND FLOOR

HALLWAY LIGHT FIXTURE LENS

NEEDS TO BE ADJUSTED

GSAI CLOSE 3 63601

19-42190964 GSAI- MUSHROOM LIGHTS NEAR

PARKING SPOT 156 IS NOT

WORKING

GSAI CLOSE 3 63604

19-42190980 GSAI- 3RD FLOOR PUBLIC SIDE

WATER FOUNTAIN IS NOT

WORKING SOUTH SIDE

GSAI CLOSE 3 63606

19-42190995 GSAI-4TH FLOOR WOMEN'S

RESTROOM ACROSS FROM 421 H/

C STALL FLUSH FIXTURE LEAKS

GSAI CLOSE 2 63070

11/27/20 10:25 AM 21 / 193

Site: 07

Work Order Description Type Status Priority Lead Location: Asset Job Plan Parent WO Schedule Start Schedule

Finish

19-42191010 GSAI-5TH FLOOR WOMEN'S

RESTROOM ACROSS FROM 563 H/

C STALL FLUSH FIXTURE LEAKS

WHEN USED

GSAI CLOSE 2 63071

19-42191018 GSAI- 5TH FLOOR WOMEN'S

RESTROOM ACROSS FROM 563

2ND STALL FLUSH FIXTURE LEAKS

WHEN USED

GSAI CLOSE 2 63071

19-42192679 GSAI- 1ST NORTHWEST STAIRWAY

SCRATCHES ON WALL

GSAI CLOSE 3 89444

19-42193546 GSAI- TRASH ON AVENUE E SIDE GSAI CLOSE 3 61284

19-42238282 GSAI- BAS ALARMS Hipolito Garcia Federal Bldg - San Antonio, TX:P07Q8ETX0164SANT6:AHU_2C_SA_Temp

GSAI CLOSE 2 61262

19-42238820 3RD FLOOR ROOM 323 GRAND

JURY ROOM REPORTED

EXTREMELY COLD NEED

ADJUSTMENT SET POINTS

ADJUSTED

WR CLOSE 3 92373 982138

19-42239470 1ST FLOOR BACK EMPLOYEE

ENTRANCE BY TRAVIS AND

AVENUE E DOUBLE DOORS TO

POSTAL LOBBY BOLTS ARE

LOOSE ON DOOR

WR CLOSE 3 63067 376413

19-42239890 4TH FLOOR WOMEN'S RESTROOM

PUBLIC RESTROOM AT J WOODS

LIGHTS FLICKERING

WR CLOSE 3 63607

19-42244534 CM- CO2 SENSOR NOT WORKING

ON AIR HANDLER 23 ON THE 5TH

FLOOR

CM CLOSE 3 92329 981933

19-42244558 CM- CARPET TILES COMING

LOOSE IN THE BASEMENT

MARSHALS OFFICE

CM CLOSE 3 63589

19-42244575 CM- CALL BUTTON DOWN ARROW

BETWEEN ELEVATORS 3 AND 4 ON

THE 2ND FLOOR IS BROKEN

CM CLOSE 3 63592

19-42244590 CM- 4TH FLOOR MEN RESTROOM

THE LAST SINK IS NOT WORKING

CM CLOSE 3 63594

19-42244604 CM- 6TH FLOOR HALLWAY BY

ELEVATOR 2 AND US ATTORNEY

OFFICE LIGHTS GOING OUT

CM CLOSE 3 63596

11/27/20 10:25 AM 22 / 193

Site: 07

Work Order Description Type Status Priority Lead Location: Asset Job Plan Parent WO Schedule Start Schedule

Finish

19-42244625 4TH FLOOR PROBATION

REPORTED ONE OF THE TOILETS

IN THE LADIES RESTROOM ADMIN

AREA T-W-5 KEEPS ON FLUSHING

WR CLOSE 3 63594

19-42244651 CM- LIGHT OUT BY THE BACK

EMPLOYEES ENTRANCE DOORS

CM CLOSE 3 63591

19-42244668 CM- LIGHT GOING OUT ON THE

1ST FLOOR HALLWAY BY ROOM

EWCB1

CM CLOSE 3 63591

19-42244700 CM- 3RD FLOOR HALLWAY WATER

FOUNTAIN NEEDS A NEW MOTOR

CM CLOSE 3 63593

19-42244715 CM- 4TH FLOOR SINK IN THE

LADIES RESTROOM ON THE 1ST

FLOOR VERY LOW WITH

PRESSURE

CM CLOSE 3 63591

19-42245411 MISC- MOVE FURNITURE FROM US

TRUSTEES OFFICE ROOM 533

WR CLOSE 3 63071

19-42245827 5TH FLOOR OFFICE 515

RESTROOM OVERFLOWING AND

CLOGGED TOILET

WR CLOSE 2 63071

19-42249685 4TH FLOOR PROBATION SECURE

SPACE DOOR NEXT TO GSA

CONFERENCE ROOM IS NOT

CLOSING AND RETRACTING.

SECURE REASONS

WR CLOSE 3 63594

19-42249711 GROUND FLOOR VINYL FLOORING

CLEANED IN ROOM G-80.

RELOCATING OF EMPLOYEES

WR CLOSE 3 63601

19-42249717 2ND FLOOR PUBLIC DEFENDERS

REQUESTING OVERTIME UTILITIES

FOR 04/07/2019 FROM 10AM TO

6PM

WR CLOSE 3 92317 981939

19-42249720 7TH FLOOR SOCIAL SECURITY

REQUESTING OVERTIME UTILITIES

FOR 04/06/2019 FROM 7AM TO

12PM

WR CLOSE 3 92339 981948

19-42249723 7TH FLOOR SOCIAL SECURITY

REQUESTING OVERTIME UTILITIES

FOR 04/13/2019 FROM 7AM TO

12PM

WR CLOSE 3 92338 981953

11/27/20 10:25 AM 23 / 193

Site: 07

Work Order Description Type Status Priority Lead Location: Asset Job Plan Parent WO Schedule Start Schedule

Finish

19-42257586 GSAI- BAS, BOILER #1 IS SHOWING

FLOW WHEN BOILER AND PUMPS

ARE STOPPED. PLEASE

INVESTIGATE AND REPAIR TO

SHOW "NO FLOW" WHEN

STOPPED.

GSAI CLOSE 2 63064 376247

11/27/20 10:25 AM 24 / 193

Site: 07

Work Order Description Type Status Priority Lead Location: Asset Job Plan Parent WO Schedule Start Schedule

Finish

19-42266519 GSAI- BAS AHU-A, AHU-B UNITS

ARE SCHEDULED FROM 10:00 AM

TO 4:00 PM AND THE UNITS ARE

RUNNING OUT OF THESE TIME

ZONE'S. ENERGY CONSUMPTION

CONCERN, PLEASE REPAIR.

GSAI CLOSE 2 61262

19-42267136 GSAI- BASEMENT NEXT TO B-30

PIPE FITTING WATER LEAK

GSAI CLOSE 2 63064

19-42267147 GSAI- 4TH FLOOR ROOM 416 PIPE

FITTING FOREIGN SUBSTANCE ON

PIPE FITTING

GSAI CLOSE 3 63070

19-42267161 GSAI- BASEMENT IN THE CORNER

OF B20 ROOM MOP IN CORNER.

SAFETY HAZARD

GSAI CLOSE 3 63064

19-42267176 GSAI- BASEMENT ROOM B20

TRASH ON CHEMICALS

GSAI CLOSE 3 63064

19-42267184 GSAI- BASEMENT ROOM B20

TRASH AND INSULATION IN THE

CORNER

GSAI CLOSE 3 63064

19-42267234 GSAI- GSA BREAK ROOM LIGHT

OUT

GSAI CLOSE 3 63596

19-42267240 GSAI- F-R-1-A CWS VALVE HAS

CORROSION

GSAI CLOSE 3 63591

19-42267276 GSAI- A-119 FLOOR STAINED IN

CORNER

GSAI CLOSE 3 63591

19-42267283 GSAI- B-146 WALLS SCUFFED GSAI CLOSE 3 63591

19-42267300 GSAI- PARKING CURBS

UNSECURED

GSAI CLOSE 3 92310

19-42267312 GSAI- 6TH FLOOR MEN'S

HANDICAP TOILET SEAT IS LOOSE

GSAI CLOSE 3 63596

19-42267324 GSAI- FREIGHT ELEVATOR FLOOR

HAS DEBRIS

GSAI CLOSE 3 63591 385855

19-42267331 GSAI- DIRT AND DEBRIS ON

OUTSIDE OF BUILDING

GSAI CLOSE 3 92310

19-42267336 GSAI- TWO LIGHTS OUT IN

PARKING LOT ACROSS THE

STREET FROM THE FOB

GSAI CLOSE 3 92310

19-42267351 GSAI- F-R-5B INTERIOR DOOR

SMUDGES

GSAI CLOSE 3 63595

11/27/20 10:25 AM 25 / 193

Site: 07

Work Order Description Type Status Priority Lead Location: Asset Job Plan Parent WO Schedule Start Schedule

Finish

19-42267378 GSAI- F-R-5A HOT WATER RETURN

VALVE HAS CORROSION. CHECK

FOR LEAKS

GSAI CLOSE 3 63595

19-42267473 GSAI- J-5 B COLD WATER HANDLE

LEAKS WHEN BEING TURNED ON

GSAI CLOSE 2 63595

19-42267661 3RD FLOOR PROBATION SPACE

LIGHT FIXTURE NEAR B304I MAIL

CENTER COVER IS UNLATCHED

WR CLOSE 3 63593

19-42267685 CM- BACK DOOR TO THE WELL

NOT LOCKING

CM CLOSE 3 63601

19-42267822 CA- 3RD FLOOR ROOM 321 LIGHT

OUT

CM CLOSE 3 63606

19-42269657 East Lot ITC Gate is OOS GSAI CLOSE 3 63590

19-42269675 FOB Women's handicap toilet not working - 3rd Flr.

WR CLOSE 2 63593

19-42276568 CM- FOUND THE TOILET SEAT

COVER DISPENSER ON THE 5TH

FLOOR MEN'S PUBLIC RESTROOM

BROKEN

CM CLOSE 3 63595

19-42276607 INSTALLED WHITE BOARD AND

PICTURES FOR CONGRESS WILL

HURD ON THE 1ST FLOOR ROOM

A-105

WR CLOSE 3 63591

19-42288975 GSAI- BAS ALARM,

P07Q8ETX0164SANT6:AHU_2C_SA_Temp

NOT MEETING SET POINT

GSAI CLOSE 2 61262

19-42290909 GROUND FLOOR JURY ASSEMBLY

ROOM G-13 REPORTED IS TO

WARM

WR CLOSE 3 63601 386035

19-42292017 GSAI- MENS RR URINAL IN REAR

OF POST OFFICE NEEDS TO BE

CLEANED

GSAI CLOSE 61269

19-42292024 GSAI- LIGHT OUT IN MECH ROOM

ABOVE GSA NETWORK SWITCH

GSAI CLOSE 61269

19-42292026 GSAI- INVESTIGATE / TEST RAIN

SENSOR FOR THE IRRIGATION

SYSTEM TO ENSURE THAT THE

SYSTEM IS NOT RUNNING DURING

ANY RAIN EVENTS

GSAI CLOSE 61269

11/27/20 10:25 AM 26 / 193

Site: 07

Work Order Description Type Status Priority Lead Location: Asset Job Plan Parent WO Schedule Start Schedule

Finish

19-42292034 GSAI- BOTH CONDENSING UNITS

HAVE DIRTY COILS AND NEED TO

BE CLEANED

GSAI CLOSE 61269

19-42292040 GSAI- NEST NEEDS TO BE

REMOVED IN FRONT RIGHT SIDE

OF BUILDING

GSAI CLOSE 61269

19-42292051 GSAI- ASSORTED AREAS OF THE

GROUNDS HAVE PAPER AND

WRAPPERS THROUGH OUT

GSAI CLOSE 61269

19-42292057 GSAI- AREA AROUND METER BOX

NEEDS TO BE FILLED IN AND

LEVELED OFF TO PREVENT TRIP

HAZARD.

GSAI CLOSE 61269

19-42293526 GSAI- OAAHU-8 COULD USE THE

FILTERS CHANGED, CURRENTLY

DATED 3/07/19

GSAI CLOSE 3 60569

19-42293589 GSAI- RE-ATTACHED COVER FOR

SPRINKLER LINE FLOW SWITCH

AT FIRE PUMP

GSAI CLOSE 3 60569

19-42293620 GSAI- INSULATION FOR 2ND

FLOOR AUTOMATION LIEBERT

CHW STRAINER NEEDS TO BE RE-

ATTACHED

GSAI CLOSE 3 60569

19-42293628 GSAI- EXHAUST FAN ON THE

ROOF HAS DEBRIS INSIDE, NEEDS

TO BE CLEANED OUT.

GSAI CLOSE 3 60569

19-42293638 GSAI- SSA CONDENSERS ON

ROOF, GSA NEEDS TO CHECK

FOR OTU RWA.

GSAI CLOSE 3 60569

19-42293691 GSAI- OAAHU-12 COULD USE

FILTERS CHANGED, BELT

APPEARS LOOSE, AND FAN HAS

DUST NEEDS TO BE CLEANED

GSAI CLOSE 3 60569

19-42293696 GSAI- INFRARED ELECTRICAL

TESTING HAS NOT BEEN

COMPLETED FOR FY19

GSAI CLOSE 3 60569

19-42293707 GSAI- OAOAHU-13 COULD USE

FILTERS CHANGED LAST DATE

3/17/19

GSAI CLOSE 3 60569

19-42293713 GSAI- MENS RR 7TH FLOOR, DOOR

HINGES NOISY

GSAI CLOSE 3 60569

11/27/20 10:25 AM 27 / 193

Site: 07

Work Order Description Type Status Priority Lead Location: Asset Job Plan Parent WO Schedule Start Schedule

Finish

19-42294719 CM- 1ST FLOOR ROOM 118 2

LIGHTS OUT

CM CLOSE 3 63067

19-42294738 CM- 3RD FLOOR LIGHT OUT BY

ROOM 352

CM CLOSE 3 63069

19-42294746 CM- LIGHT OUT BY NEW FREIGHT

ELEVATOR 4TH FLOOR

CM CLOSE 3 63070

19-42294829 CM- LOBBY POST OFFICE AREA

LIGHT OUT CHANDELIER

CM CLOSE 3 63067

19-42294956 CM- CONDENSER WATER

BOOSTER PUMP PRESSURE TANK

PIPE LEAKING

CM CLOSE 3 63064

19-42295048 CM- 4TH FLOOR DOOR FRAME BY

457 NEEDS REPAIR

CM CLOSE 3 63070

19-42295054 3RD FLOOR SUITE 383 JUDGE

KING LIBRARY LIGHT OUT

WR CLOSE 3 63069

11/27/20 10:25 AM 28 / 193

Site: 07

Work Order Description Type Status Priority Lead Location: Asset Job Plan Parent WO Schedule Start Schedule

Finish

19-42361499 CM- 2ND FLOOR US MARSHALS

REPLACING OF FILTER IN SPOT

COOLER

CM CLOSE 3 63605

19-42361525 CM- 3RD FLOOR ROTUNDA RUG IS

TORN

CM CLOSE 3 63606

19-42361581 CM- OUTSIDE COURTHOUSE

WALK WAY REPLACE OF CRACK

TILE

CM CLOSE 3 92346

19-42361681 CM- NORTH SIDE WOMEN

RESTROOM TOILET IS LEAKING

CM CLOSE 2 63610

19-42635001 GSAI- OBSERVED PARKING STOP

ON IMPROPERLY STORED

GSAI CLOSE 3 92374

19-42635022 GSAI- LEAVES OBSERVED ON THE

RAMPS

GSAI CLOSE 3 92374

19-42635030 GSAI- STAINED TILE AND LEAK IN

THE CEILING IN ROOM J1

GSAI CLOSE 3 63610

19-42635064 GSAI- TRASH OBSERVED

THROUGHOUT THE GRASSY AREA

BETWEEN TX0502 AND TX0503

GSAI CLOSE 3 92346

19-42635079 GSAI- OBSERVED DEBRIS AND

TRASH IN THE WELL

GSAI CLOSE 3 92346

19-42635087 GSAI- AHU 2 FILTERS NOT

CHANGED

GSAI CLOSE 3 92357 982129

19-42635097 GSAI- FR2-7 DAILY LOG NOT

CHECKED SINCE 4.4.19

GSAI CLOSE 3 63605

19-42635131 GSAI- F-R-G-1 DOOR IN THE

EMPLOYEE HALLWAY DOES NOT

LATCH

GSAI CLOSE 3 63604

19-42635148 GSAI- CHAIR RAIL MISSING IN

ROOM 214 USMS CONFERENCE

ROOM

GSAI CLOSE 3 63605

19-42635166 GSAI- WATER OBSERVED ON

FLOOR IN MECHANICAL ROOM G-1

GSAI CLOSE 3 63601

19-42635175 GSAI- RESIDUE FILM OBSERVED

ON THE LAMINATE FLOORS IN

GROUND FLOOR VENDING AREA

GSAI CLOSE 3 63601

19-42635203 GSAI- DRAIN BLOCKED IN THE

WELL

11/27/20 10:25 AM 29 / 193

Site: 07

Work Order Description Type Status Priority Lead Location: Asset Job Plan Parent WO Schedule Start Schedule

Finish

19-42635311 GSAI- GROUNDS MAINTENANCE

WEEDS

GSAI CLOSE 3 90244

19-42635341 GSAI- TRIPPING HAZARD

EXTERIOR GROUNDS

GSAI CLOSE 3 90244

19-42635426 GSAI- TREES NEED PRUNING GSAI CLOSE 3 90244

19-42635458 GSAI- SPRINKLER HOUSING IS

NOT FLUSH WITH THE GROUND

GSAI CLOSE 90244

19-42635468 GSAI-- DEBRIS BY CONDENSING

UNITS

GSAI CLOSE 3 90244

19-42635479 GSAI- CORROSION ON PRESSURE

GAUGE IN MECHANICAL ROOM

GSAI CLOSE 3 90245

19-42635495 GSAI- TEMPERATURE REPORTED

COLD IN 104 BREAKROOM

GSAI CLOSE 2 90248

19-42635533 GSAI- LIGHTS OUT IN POST OFFICE GSAI CLOSE 3 63190

19-42810227 MISC- HANGING OF RECYCLE

FLYERS IN J WOODS AND

FEDERAL BUILDING

WR CLOSE 3 60569

19-42813063 CM- FAN BLADE ON 2C AHU

CONDENSER

CM CLOSE 3 63068 376212

19-42813139 CM- FAN MOTOR NOT RUNNING

ON 2C AHU CONDENSER

CM CLOSE 3 63068 376212

19-42813151 CM- BURNED OUT LIGHT SOUTH

EAST STAIRWELL 1ST FLOOR

CM CLOSE 3 63067

19-42814232 7TH FLOOR SUITE 700 ENTRY

DOOR TENSION NEEDS

ADJUSTMENT

WR CLOSE 3 63597

19-42814259 CM- SUPPLY AIR FAN MOTOR

NOISY ON 6B AHU

CM CLOSE 3 89591 971781

19-42814271 CM- CRAC 5 COMPRESSOR TRIP CM CLOSE 3 89554 971801

19-43204759 GSAI- 4TH FLOOR MEN'S

RESTROOM GROUT IS

DISCOLORED

GSAI CLOSE 3 63594

19-43204887 GSAI- 7TH FLOOR SMUDGES BY

ELEVATORS

GSAI CLOSE 3 63597

19-43205005 GSAI- 4TH FLOOR MEN'S

RESTROOM R-4-1 HANDICAP

TOILET IS NOT FLUSHING

THROUGH

GSAI CLOSE 2 63594

11/27/20 10:25 AM 30 / 193

Site: 07

Work Order Description Type Status Priority Lead Location: Asset Job Plan Parent WO Schedule Start Schedule

Finish

19-43205018 GSAI- WALL SMUDGED BY 7TH

FLOOR ELEVATORS

GSAI CLOSE 3 63597

19-43205045 GSAI- GROUNDS MAINTENANCE

SPARSE GROWTH IN FRONT OF

BUILDING

GSAI CLOSE 3 92310

19-43205055 GSAI- GROUNDS SPARSE

GROWTH AND WEEDS

GSAI CLOSE 3 92310

19-43205075 GSAI- TRASH OBSERVED AROUND

THE PROPERTY

GSAI CLOSE 3 92374

19-43302463 GSAI- LIGHT SWITCHES

THROUGHOUT BUILDING ARE

SOILED

GSAI CLOSE 3 60570

19-43302477 GSAI- IMPROPER STORAGE IN

ELECTRICAL ROOM. IS A FIRE

HAZARD E-W-C-38

GSAI CLOSE 3 63606

19-43302502 GSAI-DOOR WILL NOT SECURE E-

W-C-1-2

GSAI CLOSE 3 63604

19-43302545 GSAI- OBSERVED RUST ON

RAILINGS AT THE COURTYARD

STAIRS ALONG GOLIAD STREET

GSAI CLOSE 3 92346

19-43311664 GSAI- ENTRANCE BASEMENT

LIGHT OUT

GSAI CLOSE 3 63064

19-43311666 GSAI- B30 EQUIPMENT LEFT

UNATTENDED SAFETY VIOLATION

GSAI CLOSE 3 63064

19-43311674 GSAI- OUTSIDE OF ROOM 158

WALL DAMAGE

GSAI CLOSE 3 63067

19-43311677 GSAI- MEDCOM 1ST FLOOR

WOMEN'S RESTROOM SOAP

DISPENSERS LEAKING

GSAI CLOSE 3 63067

19-43315759 GSAI- 6TH FLOOR MEN'S

RESTROOM SINK FAUCET IS NOT

WORKING PROPERLY

GSAI CLOSE 2 63596

19-43315786 4TH FLOOR PROBATION

DIRECTORY REMOVE JOE

SANCHEZ AND REPLACED WITH

JAMES RICK GOLDEN JR

WR CLOSE 3 63594

19-43315806 MISC- REMOVE WHITEBOARD

FROM ROOM I-405 AND INSTALL

NEW WHITEBOARD IN OFFICE

A-309C

WR CLOSE 3 63594

11/27/20 10:25 AM 31 / 193

Site: 07

Work Order Description Type Status Priority Lead Location: Asset Job Plan Parent WO Schedule Start Schedule

Finish

19-43315830 RECONFIGURE TWO CUBICAL IN

6TH FLOOR GSA OFFICE

WR CLOSE 3 63596

11/27/20 10:25 AM 32 / 193

Site: 07

Work Order Description Type Status Priority Lead Location: Asset Job Plan Parent WO Schedule Start Schedule

Finish

19-43426510 GSAI- 3RD FLOOR WEST SIDE

STAIRWELL LIGHTS FLICKERING

GSAI CLOSE 3 63593

19-43433721 4TH FLOOR OFFICE ROOM A429A

PROGRAM NEW CHIEF CIPHER

LOCK

WR CLOSE 3 63593

19-43433722 INVESTIGATE ELECTRICAL

RECEPTACLES IN ROOM G80 AND

COURTROOM 5 ON THE 3RD

FLOOR

WR CLOSE 3 60570

19-43433723 7TH FLOOR SOCIAL SECURITY

REQUESTING OVERTIME UTILITIES

FOR 04/27 FROM 7AM TO 12PM

WR CLOSE 3 92339 981948

19-43484590 Cut (2) Keys for GSA Office on 6th Floor

GSAI CLOSE 3 63596

19-43487079 CM- REVOLVING DOOR FRONT

LOBBY DOOR HINGES COMING

OFF

CM CLOSE 3 63067 376276

19-43492406 GSAI- OBSERVED COBWEBS IN

THE ENTRANCE LOBBY

GSAI CLOSE 3 63610

19-43493663 GSAI- 3RD FLOOR TEMPERATURE

ISSUE IN JUDGE EZRA SUITE IS

EXTREMELY WARM

GSAI CLOSE 3 63601 386063

19-43493840 GSAI- ROOM G-80 ROOM IS WARM GSAI CLOSE 3 63601 386040

19-43493901 GSAI- JERSEY BARRIERS NEEDS

TO BE REFILLED

GSAI CLOSE 3 92346

19-43494021 GSAI- WALL SMUDGES BY ROOM

B-712

GSAI CLOSE 3 63597

19-43494028 GSAI- CHECK LATCH ON BACK

DOORS OF DOD IG. DOES NOT

LOOK LIKE A FIRM LATCH

GSAI CLOSE 3 63597

19-43494042 GSAI- F-R-7A REAR LIGHT IN

MECHANICAL ROOM IS DIM

GSAI CLOSE 3 63597

19-43494052 GSAI- F-R-7A HOT WATER RETURN

VALVE HAS CORROSION

GSAI CLOSE 3 63597

19-43494057 GSAI- NO TOILET SEAT COVERS IN

7TH FLOOR MEN'S RESTROOM

GSAI CLOSE 3 63597

19-43494092 GSAI- STORE ROOM IN SOCIAL

SECURITY 7TH FLOOR HAS SCUFF

MARKS ON HARD FLOOR

GSAI CLOSE 3 63597

11/27/20 10:25 AM 33 / 193

Site: 07

Work Order Description Type Status Priority Lead Location: Asset Job Plan Parent WO Schedule Start Schedule

Finish

19-43494182 GSAI- STAINED CEILING TILE BY

LOBBY FAN SWITCH INSIDE SSA

SPACE

GSAI CLOSE 3 63597

19-43509829 GROUND FLOOR CLERK OFFICE

ADJACENT HEARING OF RATTLING

NOISE TO BE LOOKED AT

WR CLOSE 3 63601

19-43533459 2ND FLOOR PUBLIC DEFENDERS

REQUESTING OVERTIME UTILITIES

FOR APRIL 27TH AND 28TH FROM

10AM TO 8PM

WR CLOSE 3 92322 981949

19-43533483 7TH FLOOR SOCIAL SECURITY

REQUESTING OVERTIME UTILITIES

FOR APRIL 27TH FROM 7AM TO

12PM

WR CLOSE 3 92339 981948

19-43533524 7TH FLOOR SOCIAL SECURITY

REQUESTING OVERTIME UTILITIES

FOR APRIL 20TH FROM 7AM TO

12PM

WR CLOSE 3 92339 981948

19-43533581 2ND FLOOR PUBLIC DEFENDERS

REQUESTING OVERTIME UTILITIES

FOR APRIL 20TH FROM 8AM TO

8PM

WR CLOSE 3 92317 981939

19-43533613 2ND FLOOR PUBLIC DEFENDERS

REQUESTING OVERTIME UTILITIES

FOR APRIL 13TH FROM 12PM TO

8PM

WR CLOSE 3 92317 981939

19-43533668 REPLACE LIGHT BULBS IN OFFICE

G-80 LOCATED IN CLERKS OFFICE

WR CLOSE 3 63601

19-43533694 GSAI- 6TH FLOOR MEN'S

RESTROOM NEEDS REPLACING

OF TOILET PAPER

GSAI CLOSE 3 63596

19-43533711 ELEVATOR NUMBER 3 INSIDE THE

RIGHT PANEL CLOSE DOORS

BUTTON HAS FALLEN OFF

WR CLOSE 3 63591 385845

19-43535624 GSAI- BAS P07Q8ETX0503SANT1 -

Adrian Spears Traning Ctr, San Antonio TX:Hot Water System/

Blr6Gen_Alarm

GSAI CLOSE 3 92376 1286359

11/27/20 10:25 AM 34 / 193

Site: 07

Work Order Description Type Status Priority Lead Location: Asset Job Plan Parent WO Schedule Start Schedule

Finish

19-43535625 GSAI- BAS UTILITY METER ROOM

SHOULD BE MONITORED TO

ENSURE THERE ARE NO SPIKES

OR INCREASE IN USAGE WITH

OCCASIONALLY REVIEWING

TRENDING HISTORIES

GSAI CLOSE 3 92376 1286359

19-43535626 GSAI- BAS THE OA AND HUMIDITY

SENSOR IS NOT REPORTING AND

FLAT LINED, THIS IS AFFECTING

BOILER OPERATIONS AND

ENERGY (GAS) CONSUMPTION

IMPACTING THE RESET

SCHEDULE.

GSAI CLOSE 2 92376 1286360

19-43535629 GSAI- BAS SINCE THE OA AND

HUMIDITY SENSOR HAS FAILED

THE RESET SCHEDULE WAS

STUCK ON 157 DEG. SET POINT

FOR THE BOILERS, GSA HAS PUT

THE SYSTEM IN MANUAL AT 125

DEG REDUCING GAS USE.

GSAI CLOSE 3 92376 1286360

19-43546094 4TH FLOOR OFFICE E405

REQUESTING TO LOWER

TEMPERATURE READING 79

DEGREES

WR CLOSE 2 92325 981923

19-43546126 4TH FLOOR OFFICES E405 AND

G405 NORTH WING REQUESTING

TEMPERATURE ADJUSTMENT TO

BE COOLED DOWN CURRENT

READING IS 79 DEGREES

WR CLOSE 2 92325 981923

19-43546154 4TH FLOOR OFFICE G-405

REQUESTING TEMPERATURE

ADJUSTMENT TO BE LOWERED TO

HOT CURRENT READING IS 79

WR CLOSE 2 92325 981923

19-43546373 3RD FLOOR OFFICE B306C

REQUESTING TEMPERATURE

ADJUSTMENT TO HOT NEED

AIRFLOW

WR CLOSE 2 92321 981954

19-43546643 3RD FLOOR RECEPTION AREA

AND SURROUNDING OFFICES

A311C, A311B. TEMPERATURE TO

HOT

WR CLOSE 2 92321 981954

19-43547975 replace the light bulb in room #368 on the third floor back hallway

GSAI CLOSE 3 63606

11/27/20 10:25 AM 35 / 193

Site: 07

Work Order Description Type Status Priority Lead Location: Asset Job Plan Parent WO Schedule Start Schedule

Finish

19-43548000 JURY ASSEMBLY ROOM IN THE

BASEMENT IS VERY HOT

REQUESTING TEMPERATURE

ADJUSTMENTS

WR CLOSE 2 63601 386035

19-43548037 CM- REPLACE 3 BULBS IN ROOM

CM CLOSE 3 63606

19-43548054 CM- 2ND FLOOR JAIL CELL TOILET

FLUSHING TOILET WATER COMES

BACK UP

CM CLOSE 2 63605

19-43548088 CM- REPLACE STAINED CEILING

TILE IN THE 7TH FLOOR SOCIAL

SECURITY IT ROOM

CM CLOSE 3 63597

19-43548117 CM- 5TH FLOOR LADIES

RESTROOM SOAP DISPENSER IS

BROKEN

CM CLOSE 2 63595

19-43548141 CM- OLD SOAP DISPENSERS IN

1ST FLOOR NURSE OFFICE TO BE

REMOVED FROM THE WALL IN

NURSE OFFICE

CM CLOSE 3 63591

19-43548152 CM- HALLWAY LIGHT OUT ON THE

1ST FLOOR BY THE OLD CENTER

ROOM A100

CM CLOSE 3 63591

19-43548179 CM- 2ND FLOOR INSIDE

CUSTODIAL CLOSET THE MOP

SINK LEAKS FROM THE SERVICE

HOSE

CM CLOSE 2 63592

19-43548205 CM- REMOUNTED THE WEST SIDE

PULL STATION BOX ON THE 4TH

FLOOR HALLWAY

CM CLOSE 2 63594

19-43548238 4TH FLOOR WEST FIRE PULL

STATION HANGING FROM WIRES

WR CLOSE 3 63594

19-43548265 3RD FLOOR COURTROOM 5

REQUESTING TEMPERATURE TO

BE COOLED DOWN

WR CLOSE 2 92373 982138

19-43548283 2ND FLOOR MARSHAL OFFICE

REPORTED TEMPERATURE IS TO

COLD NEED TEMPERATURE

ADJUSTMENT

WR CLOSE 2 63601 386035

11/27/20 10:25 AM 36 / 193

Site: 07

Work Order Description Type Status Priority Lead Location: Asset Job Plan Parent WO Schedule Start Schedule

Finish

19-43548298 4TH FLOOR HUD OFFICES

REQUESTING TEMPERATURE

ADJUSTMENT TO HOT. REPORTED

BY CHRIS SANCHEZ

WR CLOSE 2 89528 971800

19-43570108 MISC- HANGING OF MISSING

CHILDREN POSTINGS

WR CLOSE 3 63591

11/27/20 10:25 AM 37 / 193

Site: 07

Work Order Description Type Status Priority Lead Location: Asset Job Plan Parent WO Schedule Start Schedule

Finish

19-43570117 MISC- HANGING OF MISSING

CHILDREN POSTINGS

WR CLOSE 3 63604

19-43570124 MISC- HANGING OF MISSING

CHILDREN POSTINGS

WR CLOSE 3 63067

19-43570133 MISC- HANGING OF MISSING

CHILDREN POSTINGS

WR CLOSE 3 63190

19-43570148 MISC- CLEANING AND SANITIZING

OF FITNESS CENTER

WR CLOSE 3 63591

19-43570152 MISC- CLEANING AND SANITIZING

OF FITNESS CENTER

WR CLOSE 3 89446

19-43570165 GSAI- 1ST FLOOR FOH RESTROOM

TOILET HAS STAINS

GSAI CLOSE 3 63591

19-43570176 GSAI- 1ST FLOOR CONGRESSMAN

HURDS OFFICE BOWED CEILING

TILE BY CLOCK

GSAI CLOSE 3 63591

19-43570190 GSAI- 3RD FLOOR WEST

STAIRWAY STAIN ON SPRINKLER

WATER PIPE. POTENTIAL LEAK

GSAI CLOSE 3 92323

19-43570194 GSAI- 3RD FLOOR WEST

STAIRWELL DEBRIS BEHIND

WATER PIPE

GSAI CLOSE 3 92323

19-43570204 GSAI- T-3-3 RUST ON CEILING GRID GSAI CLOSE 3 63593

19-43570213 GSAI- BASEMENT GYM MISSING

ESCUTCHEON

GSAI CLOSE 3 63589

19-43570217 GSAI- BASEMENT GYM FLOOR

STAINED

GSAI CLOSE 3 63589

19-43570227 GSAI- BASEMENT GYM CARPET

HAS DEBRIS

GSAI CLOSE 3 63589

19-43570516 GSAI- LIGHT OUT OVER 605

PARKING STOP

GSAI CLOSE 3 63587

19-43570522 GSAI- LIGHT OUT OVER 610

PARKING STOP

GSAI CLOSE 3 63587

19-43570542 GSAI- LIGHT OUT OVER 626 GOING

OUT

GSAI CLOSE 3 63587

19-43570557 GSAI- 4TH FLOOR U LIGHT OUT GSAI CLOSE 3 61284

19-43570652 GSAI- 5TH FLOOR OFFICE 566

PEST ON THE FLOOR

GSAI CLOSE 3 63071

11/27/20 10:25 AM 38 / 193

Site: 07

Work Order Description Type Status Priority Lead Location: Asset Job Plan Parent WO Schedule Start Schedule

Finish

19-43570665 GSAI- 5TH FLOOR CONGRESSMAN

CUELLAR OFFICE CARPET STAINS

GSAI CLOSE 3 63071

19-43570711 GSAI- WOMEN'S RESTROOM

ACROSS FROM CONGRESSMAN

CUELLAR OFFICE FLUSH FIXTURE

LEAKS WHEN FLUSHED

GSAI CLOSE 2 63071

19-43570736 GSAI- 5TH FLOOR SERVICE

ELEVATOR LANDINGS DRIPPING

STAINS ON WALL

GSAI CLOSE 3 63071

19-43570801 GSAI- 4TH FLOOR ROOM 456

PUDDLE OF WATER ON THE

GROUND

GSAI CLOSE 3 63070

19-43570867 GSAI- HANDICAP NON SLIP

TRIPPING ADHESIVE STRIPS ARE

PEELING OFF AND COMING OFF

GSAI CLOSE 3 92374

19-43570949 GSAI- F-R-G-1 WATER OBSERVED

ON FLOOR

GSAI CLOSE 3 63604

19-43570979 GSAI- G-80 - Quadplex outlet not working

GSAI CLOSE 3 63601

19-43607057 GSAI- BAS, FP-2C-01 HAS FAULTED

POINTS AND POSSIBLE POWER

ISSUE-NEEDS INVESTIGATION

FOR REPAIR

GSAI CLOSE 2 63068 376212

19-43672943 GSAI- BAS FP-2C-12 FAN

COMMAND IS START BUT FAN IS

NOT RUNNING AND THE ALARM IS

NOT WORKING

GSAI CLOSE 2 63068 376212

19-43677348 4TH FLOOR OFFICE A407G

REQUESTING RAISING OF

TEMPERATURE IN OFFICE

WR CLOSE 2 92325 981959

19-43765369 GSAI- 1ST FLOOR LOBBY

HANDICAP DOOR BELL NOT

WORKING

GSAI CLOSE 3 63067

19-43765379 3RD FLOOR LIGHT OUT ABOVE

390B OFFICE

GSAI CLOSE 3 63069

19-43765394 GSAI- 1ST FLOOR MEDCOM

WOMEN'S RESTROOM HANDICAP

STALL TRASH CAN NEEDS TO BE

REMOVED

GSAI CLOSE 3 63067

11/27/20 10:25 AM 39 / 193

Site: 07

Work Order Description Type Status Priority Lead Location: Asset Job Plan Parent WO Schedule Start Schedule

Finish

19-43765404 GSAI- LIGHT OUTSIDE OF MEN'S

RESTROOM 1ST FLOOR

GSAI CLOSE 3 63067

19-43765579 MISC-1ST FLOOR MEDCOM

REQUESTING MOVING OF WORK

STATIONS

WR CLOSE 3 63067

19-43765624 5TH FLOOR SUITE A-500 MEN'S

EMPLOYEE RESTROOM

EXECUTIVE SUITE RESTROOM IS

CLOGGED

WR CLOSE 2 63595

19-43765677 GSAI- 6TH FLOOR WOMEN'S

RESTROOM TOILET SEAT COVER

SUPPLIES NEED TO BE REFILLED

GSAI CLOSE 3 63596

19-43765685 5TH FLOOR SUITE A-500

EXECUTIVE SUITE OFFICE

REPORTED MEN'S RESTROOM IS

ABOUT TO OVERFLOW

WR CLOSE 2 63595

19-43765952 4TH FLOOR RICARDO FRIAS

REQUESTING UPDATING OF

DIRECTORY CHANGE OF

MANAGEMENT

GSAI CLOSE 3 63594

19-43776752 GSAI- WEEDS AND LANDSCAPING

NEED TO BE ADDRESSED

GSAI CLOSE 3 92374

19-43779693 GSAI-Missing ceiling tiles near and in room G-80

GSAI CLOSE 3 63601

19-43781095 GSAI- Debris on the stair in the well (near the generator)

GSAI CLOSE 3 92346

19-43781955 GSAI- Lights over parking space #1 in the well are not operating

GSAI CLOSE 3 92346

19-43783765 GSAI- COURTROOM 5 OUTLET IS

NOT WORKING

GSAI CLOSE 3 60570

19-43784933 2ND FLOOR MARSHALS OFFICE

ROOM 216 REPORTED

TEMPERATURE ADJUSTMENT TO

COLD IN OFFICE

WR CLOSE 2 63601 386035

19-43811863 Remove Ricardo Frias from the 4th Floor Marquee

WR CLOSE 3 63594

19-43819209 6TH FLOOR MEN'S RESTROOM

REPORTED EXCESSIVE AMOUNT

OF TRASH AND DEBRIS

WR CLOSE 3 63596

11/27/20 10:25 AM 40 / 193

Site: 07

Work Order Description Type Status Priority Lead Location: Asset Job Plan Parent WO Schedule Start Schedule

Finish

19-43819651 A FLOW ALARM IN THE SUB

BASEMENT CAUSED THE

BUILDING FIRE ALARM SYSTEM

ACTIVATE

WR CLOSE 3 63075

19-43820882 6th floor GSA office space requesting temperature adjustment to hot reading

74.6 F

GSAI CLOSE 2 92332 981938

19-43821031 3RD FLOOR PROBATION B-306-D

REQUESTING TEMPERATURE

ADJUSTMENT TO HOT READING 78

DEGREES

WR CLOSE 2 92322 981949

19-44408817 GSAI- It appears that the battery in the JACE at Pearsall may be bad, please investigate.

GSAI CLOSE 3 90244

19-44410271 6TH FLOOR MEN'S RESTROOM

REPORTED CLOGGED URINAL

WR CLOSE 2 63596

11/27/20 10:25 AM 41 / 193

Site: 07

Work Order Description Type Status Priority Lead Location: Asset Job Plan Parent WO Schedule Start Schedule

Finish

19-44410279 2ND FLOOR FEDERAL PUBLIC

DEFENDERS REQUESTING

OVERTIME UTILITIES FOR MAY

20TH FROM 6PM TO MIDNIGHT

WR CLOSE 3 92317 981939

19-44415419 4TH FLOOR MARQUEE

DIRECTORY REMOVE SPACE AND

FACILITIES

WR CLOSE 3 63594

19-44416869 2ND FLOOR PUBLIC DEFENDERS

REQUESTING VACUUM SERVICE

OF ROOM B-207-M

WR CLOSE 3 63592

19-44416880 4TH FLOOR PROBATION OFFICE

A407H SOUTHEAST END

REPORTED BURNED OUT…