The document is a comprehensive set of structural engineering calculations and design analyses prepared by PSE Consulting Engineers Inc. for the Billy Cordova Memorial Park Restroom project located at 142 Raven Way in Buena Vista, Colorado. The calculations cover multiple structural components including roof decking, rafters, roof extension beams, masonry shear walls, wall bond beams, and pad and column footings. The calculations are dated April 26, 2024, and utilize various design standards including the 2021 International Building Code, ASCE 7-16 standards, and National Design Specification (NDS) guidelines. The engineering analyses assess structural load capacities, wind and seismic design parameters, snow load considerations, and material stress tolerances for different building elements.
The calculations demonstrate detailed technical evaluations of structural integrity, including wind load analyses ranging from 105-115 mph, seismic design category C requirements, and snow load considerations of 36 psf for the flat roof. The design uses materials such as Douglas Fir lumber, glue-laminated timber (Glu-Lam), concrete, and concrete masonry unit (CMU) walls. The project involves a prefabricated restroom structure with specific engineering requirements for lateral forces, foundation design, and material stress limits. The structural design accounts for various load combinations including dead loads, live loads, wind loads, and seismic forces, ensuring the building meets local building codes and safety standards for the Buena Vista climate and geological conditions.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PSE Consulting Engineers Inc.
250-A Main Street E-Mail: info@structure1.com ph. (541) 850-6300 Klamath Falls, OR. 97601 Web: www.structure1.com fax (541) 850-6233
STRUCTURAL
ENGINEERING
CALCULATIONS
PROJECT: Billy Cordova Memorial Park Restroom
PROJECT LOCATION: 142 Raven Way Buena Vista, CO 81211
PSE PROJECT NUMBER: Romtec 224-032
DATE: April 26, 2024
BY: Ralph Hall, P.E.
Ex. 10-31-2025
4-26-2024 mailto:info@structure1.com
Project #: Romtec 224-032
250-A Main Street E-Mail: info@structure1.com ph. (541) 850-6300 Klamath Falls, OR. 97601 Web: www.structure1.com fax (541) 850-6233
Table of Contents:
Subject: Page:
Page
1- References / Software: 10-99
2- Design Criteria: 100-199
3- Analysis & Design: 1,000 – 1,999
250-A Main Street E-Mail: info@structure1.com ph. (541) 850-6300 Klamath Falls, OR. 97601 Web: www.structure1.com fax (541) 850-6233
References:
1- Literature:
a. 2021 International Building Code (IBC) with local amendments
b. Design of Wood Structures, Donald E. Breyer 4th ED.
c. Building Code Requirements for Masonry Structures, TMS 402
d. Building Code Requirements for Concrete, ACI 318
2- Software:
a. Wood Works Design Office, American Forest & Paper Association
b. Engineering International Spreadsheets Daniel T. Li
250-A Main Street E-Mail: info@structure1.com ph. (541) 850-6300 Klamath Falls, OR. 97601 Web: www.structure1.com fax (541) 850-6233
Design Criteria:
1- Location: 142 Raven Way
Buena Vista, CO 81211 (Lat. 38o 49’ 54” Long. 106o 09’ 07”)
2- Seismic: RC II
SDC C
Site Class D
SS 0.359
S1 0.094
SDS 0.362
SD1 0.150
IE 1.0
R 5
3- Wind: Ultimate wind speed 115 mph (3 s. gust) Exposure C
RC II
4- Snow: 43 psf (ground) 36 psf (flat roof)
5- Soil Bearing Capacity: 3500 psf (presumptive value from IBC)
6- Gravity Loads: DL Floor: 15 psf LL Floor: 40 psf DL Roof: 15 psf CMU Walls: 81 psf
7- Deflection Criteria: Floor LL Deflection: L/480 Roof TL Deflection: L/180
**Other criteria assumed as stated in design calculations.
ASCE Hazards Report Address:
142 Raven Way Buena Vista, Colorado 81211
Standard: ASCE/SEI 7-16 Latitude: 38.831667
Risk Category: II Longitude: -106.153448
Soil Class: D - Default (see Section 11.4.3)
Elevation: 8061.221723621816 ft
(NAVD 88)
Wind
Results:
Wind Speed 105 Vmph
10-year MRI 76 Vmph
25-year MRI 83 Vmph
50-year MRI 87 Vmph
100-year MRI 92 Vmph
Data Source: ASCE/SEI 7-16, Fig. 26.5-1B and Figs. CC.2-1–CC.2-4, and Section 26.5.2
Date Accessed: Mon Apr 22 2024
Value provided is 3-second gust wind speeds at 33 ft above ground for Exposure C Category, based on linear interpolation between contours. Wind speeds are interpolated in accordance with the 7-16 Standard. Wind speeds correspond to approximately a 7% probability of exceedance in 50 years (annual exceedance probability = 0.00143, MRI = 700 years).
Site is not in a hurricane-prone region as defined in ASCE/SEI 7-16 Section 26.2.
Page 1 of 4https://ascehazardtool.org/ Mon Apr 22 2024
115 mph per Buena Vista Municipal Code https://ascehazardtool.org/
SS : 0.359
S1 : 0.094
Fa : 1.513
Fv : 2.4
SMS : 0.543
SM1 : 0.225
SDS : 0.362
SD1 : 0.15
TL : 6
PGA : 0.196
PGA M : 0.276
FPGA : 1.409
Ie : 1
Cv : 0.939
Seismic Design Category: C Design Response Spectrum
S (g) vs T(s)a
MCE Response SpectrumR
S (g) vs T(s)a
Design Vertical Response Spectrum
S (g) vs T(s)a
MCE Vertical Response SpectrumR
S (g) vs T(s)a
Seismic
D - Default (see Section 11.4.3)Site Soil Class:
Results:
Data Accessed: Mon Apr 22 2024
Date Source:
USGS Seismic Design Maps based on ASCE/SEI 7-16 and ASCE/SEI 7-16 Table 1.5-2. Additional data for site-specific ground motion procedures in accordance with ASCE/SEI 7-16 Ch. 21 are available from USGS.
Page 2 of 4https://ascehazardtool.org/ Mon Apr 22 2024
Snow
Results:
Mapped Elevation:
Data Source:
Date Accessed: Mon Apr 22 2024
In "Case Study" areas, site-specific case studies are required to establish ground snow loads. Extreme local variations in ground snow loads in these areas preclude mapping at this scale.
Ground snow load determination for such sites shall be based on an extreme value statistical analysis of data available in the vicinity of the site using a value with a 2 percent annual probability of being exceeded (50-year mean recurrence interval).
Site is outside ASCE/SEI 7-16, Table 7.2-2 boundaries. For ground snow loads in this area, see SEAC Snow Load Committee. (2016). Colorado Design Snow Loads, Structural Engineers Association of Colorado.
Statutory requirements of the Authority Having Jurisdiction are not included.
Snow load values are mapped to a 0.5 mile resolution. This resolution can create a mismatch between the mapped elevation and the site-specific elevation in topographically complex areas. Engineers should consult the local authority having jurisdiction in locations where the reported ‘elevation’ and ‘mapped elevation’ differ significantly from each other.
Page 3 of 4https://ascehazardtool.org/ Mon Apr 22 2024 http://seacolorado.org/wp-content/uploads/2010/01/2016-Colorado-Design-Snow-Loads.pdf http://seacolorado.org/wp-content/uploads/2010/01/2016-Colorado-Design-Snow-Loads.pdf
The ASCE Hazard Tool is provided for your convenience, for informational purposes only, and is provided “as is” and without warranties of any kind. The location data included herein has been obtained from information developed, produced, and maintained by third party providers; or has been extrapolated from maps incorporated in the ASCE standard. While ASCE has made every effort to use data obtained from reliable sources or methodologies, ASCE does not make any representations or warranties as to the accuracy, completeness, reliability, currency, or quality of any data provided herein. Any third-party links provided by this Tool should not be construed as an endorsement, affiliation, relationship, or sponsorship of such third-party content by or from ASCE.
ASCE does not intend, nor should anyone interpret, the results provided by this Tool to replace the sound judgment of a competent professional, having knowledge and experience in the appropriate field(s) of practice, nor to substitute for the standard of care required of such professionals in interpreting and applying the contents of this Tool or the ASCE standard.
In using this Tool, you expressly assume all risks associated with your use. Under no circumstances shall ASCE or its officers, directors, employees, members, affiliates, or agents be liable to you or any other person for any direct, indirect, special, incidental, or consequential damages arising from or related to your use of, or reliance on, the Tool or any information obtained therein. To the fullest extent permitted by law, you agree to release and hold harmless ASCE from any and all liability of any nature arising out of or resulting from any use of data provided by the ASCE Hazard Tool.
Page 4 of 4https://ascehazardtool.org/ Mon Apr 22 2024
JOB NUMBER
DESIGNER
Design Information
DATA VALUE
Site Class D-Default
Ss= 0.359
S1= 0.094
SMS= 0.543
SM1= 0.226
IE 1.0
Risk
Category 2 IE : Seismic importance factor
R 5 hn 11
Ct 0.02
TL 6
1) Design spectral response acceleration
SDS: 5% Damped spectral response acceleration at short periods
SD1: 5% Damped spectral response acceleration at 1 second period
SDS=2/3(Sms) SDS= 2/3 X 0.543095 SDS= 0.362 [ ASCE 7-16 Eq. 11.4-3 ]
SD1=2/3(Sm1) SD1= 2/3 X 0.2256 SD1= 0.150 [ ASCE 7-16 Eq. 11.4-4 ]
2) Seismic design category
From Table 11.6-1 ASCE 7-16 = C
From Table 11.6-2 ASCE 7-16 = C
3) Determine design base shear (V)
A. ASCE 7-16, 11.4.8 Exception
Ts= 0.4153968
Ta : Approximate Fundamental Period
0.75
T= 0.020 X11 T= 0.121
For Site Class D/D-Default: T is < 1.5 Ts
For site class D/-default Cs shall be calculated per Eq. 12.8-2
Equivalent Force Procedure Cs : Seismic Response Coefficient
[ ASCE 7-16, 12.8.1] V= Cs x W W : Total dead load and other applicable loads
SDS 0.362
R / I 5
C. Nor greater than
SD1 OR SD1*TL
T ( R / I ) T ( R / I )
0.150 X 1 0.150 X 6 X1
0.121 X 5 0.015 X 5
CS= 0.249 CS= 12.367
D. Nor less than [ ASCE 7-16, 12.8.1.1, Eq. 12.8-5]
CS = 0.044 (SDS) ( I ) CS = 0.044
X 0.362 X1
CS=
0.01593
Governing Cs = 0.072
V= Cs x W Refer to sheet two for W and Calculated V
T = Ta = Ct ( hn x
[ ASCE 7-16, 12.8.1.1, Eq. 12.8-3]
Site conditions, geotech report
Long-period Transition period (Software)
CS = [ ASCE 7-16, 12.8.1.1, Eq. 12.8-4]
CS= 0.072
Seismic Design Parameters (Calculated)
SMS: Max considered spectral response acceleration for short periods
B. [ ASCE 7-16, 12.8.1.1, Eq. 12.8-2 ]
[ ASCE 7-16, 12.8.2.1, Eq. 12.8-7]
ASCE 7-16 Table 1.5-1
CS =
Height per ASCE 7-16
ASCE 7-16 Table 12.8-2
SM1: Max considered spectral response acceleration for
1-second period
R: Response modification factor
Seismic Design Parameters (Software)
V = 0.072 X W
2018 IBC SEISMIC DESIGN
CS = CS =
Governing
Design
Category
CS =
1.0
CS =
EQUIVALENT LATERAL FORCE PROCEDURE
Seismic Design Parameters (Software)
C
ASCE 7-16 Table 12.2-1
Romtec 224-032
RMH
Seismic Design Parameters (Calculated)
ASCE 7-16 Table 1.5-2
SOURCE
JOB NUMBER Romtec 224-032
DESIGNER RMH
1. Determine dead load at each level of building.
DL (PSF) Area (SF) Length (FT) Height (FT)
a) Roof 8
Roof 15 775 NA NA
20% SL Misc. 35 775 0.2 1
Misc. (LBS) 0 NA NA NA
c) 5th floor 0
Ext. Walls 15 NA 0 0
Int. Walls 10 NA 0 0
Floor 15 0 NA NA
Misc. 0 0 0 0
Misc. (LBS) 0 NA NA NA
d) 4th floor 0
Ext. Walls 15 NA 0 0
Int. Walls 10 NA 0 0
Floor 15 0 NA NA
Misc. 0 0 0 0
Misc. (LBS) 0 NA NA NA
e) 3rd floor 0
Ext. Walls 15 NA 0 0
Int. Walls 10 NA 0 0
Floor 15 0 NA NA
Misc. 0 0 0 0
Misc. (LBS) 0 NA NA NA
f) 2nd floor 0
Ext. Walls 0 NA 0 0
Int. Walls 0 NA 0 0
Floor 0 0 NA NA
Misc. 0 0 0 0
Misc. (LBS) 0 NA NA NA
g) 1st floor CMU Walls 81 NA 88 10
Walls 10 NA 0 0
Misc. 0 0 0 0
TOTAL DEAD LOAD (LB) =
2) Determine verticle force distribution at each level ASCE 7-16 12.8.3
F x = C vx x V ASCE 7-16 Eq. 12.8-11 w x x h x k
S w i h i k
F x : Lateral seismic force at any level
V: Seismic base shear (Kips) w x & w i : The portion of the total gravity load of the structure (W) located or assigned to level i or x h x & h x : The height (ft) from the base to level i or x diaphram.
k : An exponent related to the structures period (T) as follows;
T < 0.5 sec k = 1 T > 2.5 sec k = 2 0.5 < T < 2.5 Interpolate between 1 & 2
Refer to sheet one for V (kips) T= 0.1208
V= 6.396 k= 1
Level (floor) Wall Height
(ft)
Diaphram
Height (Ft) Wx (kips) Wx*hx k C vx Fx (kips)
Allowable
Fx (kips)
Roof 10 8 52.690 422 1.000 6.40 4.57
5 0 0 0.000 0 0.000 0 0.00
4 0 0 0.000 0 0.000 0 0.00
3 0 0 0.000 0 0.000 0 0.00
2 0 0 0.000 0 0.000 0.00 0.00
52.690 422 1.000 6.40 4.6
Note: The Total Shear shown in the right hand column is an "allowable" load.
V = 0.072 X W V = 0.072 X 88330
Diaphram elevation from the base level in ft
C vx =
Diaphram elevation from the base level in ft
Total Weight (LB)
11625
Structural portion
Diaphram elevation from the base level in ft
Diaphram elevation from the base level in ft
71280
ASCE 7-16 Eq. 12.8-12
88330
IBC SEISMIC DESIGN
Diaphram elevation from the base level in ft
VERTICLE FORCE DISTRIBUTION EQUIVALENT LATERAL FORCE PROCEDURE
ProjectInformation
MecaWind v2470 Developed by Meca Enterprises Inc.,www.mecaenterprises.com, Copyright © 2024
Company/CustomerInfo
Calculations Prepared by:
Date: Apr 22, 2024
FileInformation
File Location: Current Project Not Saved
General
General:
Wind Load Standard = ASCE 7-16 Basic Wind Speed = 115.0 mph Exposure Classification = C Risk Category = II Structure Type = Building Design Basis for Wind Pressures = ASD MWFRS Analysis Method = Ch 27 Pt 1 C&C Analysis Method = None Dynamic Type of Structure = Rigid Show Advanced Options = False
Building
Building:
Roof = Roof Type = Monoslope Encl = Enclosure Classification = Enclosed Help = Help on Building Roof Type = Help Pitch = Pitch of Roof = 3.0 :12 θ = Slope of Roof = 14.04 Deg RHt = Ridge Height = 12.176 ft EHt = Eave Height = 8.000 ft W = Building Width = 16.700 ft L = Building Length = 16.700 ft OH = Type of Overhang = None Par = Parapet = None HTover = Override Mean Roof Height = False Htman = Mean Roof Height = 10.088 ft RAover = Override Roof Area = False GCpi_o = Override GCpivalue = False =
ExposureConstants
Exposure Constants [Tbl 26.11-1]:
α = 3-s Gust-speed exponent = 9.500 Zg= Nominal Ht of Boundary Layer = 900.000 ft â = Reciprocol of α = 0.105 b = 3 sec gust speed factor = 1.000 αm= Mean hourly Wind-Speed Exponent = 0.154 bm= Mean hourly Windspeed Exponent = 0.650 c = Turbulence Intensity Factor = 0.200 ε = Integral Length Scale Exponent = 0.2000
MWFRSWindCalculationsperCh27Pt1
Main Wind Force Resisting System (MWFRS) Wind Calculations per Ch 27 Pt1 h = Mean structure height = 10.088 ft hgrade = Elevation from Grade to Top of Structure = 10.088 ft Kh = 2.01•(15/Zg)2/α[Tbl 26.10-1] = 0.849 Kzt = No Topographic feature specified = 1.000 Kd = Wind Directionality Factor per Tbl 26.6-1 = 0.85 +GCpi = Enclosed Positive Internal Pressure Tbl 26.13-1 = +0.18 -GCpi = Enclosed Negative Internal Pressure Tbl 26.13-1 = -0.18 LF = Load Factor based upon ASD Design = 0.60 Ke = Ground Elev Factor [Tbl 26.9-1] = 1.000 qh = 0.00256•Kh•Kzt•Kd•Ke•V2*LF [Eq 26.10-1] = 14.66 psf RA = Roof Area = 287.48 ft2 qh = 0.00256•Kh•Kzt•Kd•Ke•V2*LF [Eq 26.10-1] = 14.66 psf qin = Negative Internal Pressure: qh•LF = 14.66 psf qip = Positive Internal Pressure: qh•LF = 14.66 psf
MWFRSWindLoads[NormaltoRidge]
MWFRS Wind Loads [Normal to Ridge] h = Mean Roof Height Of Building = 10.088 ft
Http://www.mecaenterprises.com
RHt = Ridge Height Of Roof = 12.176 ft B = Horizontal Dimension Of Building Normal To Wind Direction = 16.700 ft L = Horizontal Dimension Of building Parallel To Wind Direction = 16.700 ft L/B = Ratio Of L/B used For Cp determination = 1.000 h/L = Ratio Of h/L used For Cp determination = 0.604 Slope = Slope Of Roof = 14.04 Deg
GustFactorforWind[NormaltoRidge]
Gust Factor Calculation for Wind: [Normal to Ridge] *Gust Factor Category I Rigid Structures - Simplified Method* G1 = Simplified: For Rigid Structures can use 0.85 = 0.85 *Gust Factor Category II Rigid Structures - Complete Analysis* Zm = Equiv Struc Height: Max(0.6•h, Zmin) = 15.000 ft Izm = Turbulence Intensity: c•(33/Zm)1/6[Eq 26.11-1] = 0.228 Lzm = Turbulence Integral Length Scale: ℓ•(Zm/33)ε[Eq 26.11-9] = 427.057 ft B = Building Width Width Normal to Wind Direction = 16.700 ft Q = [1/(1+0.63•[(B+h)/Lzm]0.63)]0.5[Eq 26.11-8] = 0.949 G2 = Detailed: 0.925•[(1+1.7•gq•Izm•Q)/(1+1.7•gv•Izm)] [Eq 26.11-6] = 0.898 *Gust Factor Used in Analysis* G = Gust Factor: Min(G1, G2) = 0.850
CpWW = Windward Wall Coefficient (All L/B Values) = 0.800 CpLW = Leeward Wall Coefficient using L/B = -0.500 CpSW = Side Wall Coefficient (All L/B values) = -0.700
WindPress[NormaltoRidge]
Wind Pressures [Normal to Ridge] All wind pressures include a Load Factor (LF) of 0.6
Elev ft
GCpi
Windward GCpi
Leeward qi psf
Kz Kzt qz psf
Windward Press psf
Leeward Press psf
Side Press psf
Total Press psf
Minimum Pressure* psf
12.176 +0.18 +0.18 14.66 0.849 1.000 14.66 7.33 -8.87 -11.36 16.20 9.60
10.088 +0.18 +0.18 14.66 0.849 1.000 14.66 7.33 -8.87 -11.36 16.20 9.60
8.000 +0.18 +0.18 14.66 0.849 1.000 14.66 7.33 -8.87 -11.36 16.20 9.60
12.176 -0.18 -0.18 14.66 0.849 1.000 14.66 12.61 -3.59 -6.08 16.20 9.60
10.088 -0.18 -0.18 14.66 0.849 1.000 14.66 12.61 -3.59 -6.08 16.20 9.60
8.000 -0.18 -0.18 14.66 0.849 1.000 14.66 12.61 -3.59 -6.08 16.20 9.60
Kz = 2.01•(15/Zg)2/α[Tbl 26.10-1] Kzt = No Topographic feature specified GCpi = Enclosed Internal Pressure Tbl
26.13-1 qz = 0.00256•Kz•Kzt•Kd•Ke•V2*LF [Eq 26.10-1] qip = Positive Internal Pressure: qh•LF qin = Negative Internal Pressure: qh•LF Side = qh•G•CpSW-qip•(+GCpi) [Eq 27.3-1] Leeward = qh•G•CpLW-qip•(+GCpi) [Eq 27.3-1] Windward = qz•G•CpWW-qip•(+GCpi) [Eq 27.3-1] Total = Windward - Leeward
• Minimum Pressure: § 27.1.5 no less than 9.60 psf (Incl LF) applied to Walls
• Positive Pressures Act TOWARD Surface and Negative Pressures Act AWAY from Surface
RoofWindPressures[NormaltoRidge]
Roof Wind Pressures [Normal to Ridge] All wind pressures include a Load Factor (LF) of 0.6
Component Description Location Start ft
End ft
GCpi CpMin CpMax PCpMin psf PCpMax psf Pmin psf Roof Roof Leeward 4 All All +0.18 -0.525 -0.525 -9.18 -9.18 4.80
Roof Roof Leeward 4 All All -0.18 -0.525 -0.525 -3.90 -3.90 4.80
Roof Pressures based upon Ch 27 Pt1:
Component = The building component for pressures Location = Reference Graphic in Output for Values
Start = Start Dist from Windward Edge End = End Dist from Windward Edge CpMin = Smallest Coefficient Magnitude CpMax = Largest Coefficient Magnitude PCpMin = qh•G•CpMin-qip•GCpi[Eq 27.3-1] PCpMax = qh•G•CpMax-qin•GCpi[Eq 27.3-1]
Pmin = Min Press projected on vertical plane [§ 27.1.5]
• 0.895 Reduction Factor applied for h/L>=1 & 10=Slope=15 Deg
• The smaller uplift pressures due to CpMincan become critical when wind is combined with roof live load or snow load; load combinations are given in ASCE 7
• Positive Pressures Act TOWARD Surface and Negative Pressures Act AWAY from Surface
MWFRSWindLoads[NormaltoEave]
MWFRS Wind Loads [Normal to Eave] h = Mean Roof Height Of Building = 10.088 ft RHt = Ridge Height Of Roof = 12.176 ft B = Horizontal Dimension Of Building Normal To Wind Direction = 16.700 ft L = Horizontal Dimension Of building Parallel To Wind Direction = 16.700 ft L/B = Ratio Of L/B used For Cp determination = 1.000 h/L = Ratio Of h/L used For Cp determination = 0.604 Slope = Slope Of Roof = 14.04 Deg
GustFactorforWind[NormaltoEave]
Gust Factor Calculation for Wind: [Normal to Eave] *Gust Factor Category I Rigid Structures - Simplified Method* G1 = Simplified: For Rigid Structures can use 0.85 = 0.85 *Gust Factor Category II Rigid Structures - Complete Analysis*
Zm = Equiv Struc Height: Max(0.6•h, Zmin) = 15.000 ft Izm = Turbulence Intensity: c•(33/Zm)1/6[Eq 26.11-1] = 0.228 Lzm = Turbulence Integral Length Scale: ℓ•(Zm/33)ε[Eq 26.11-9] = 427.057 ft B = Building Width Width Normal to Wind Direction = 16.700 ft Q = [1/(1+0.63•[(B+h)/Lzm]0.63)]0.5[Eq 26.11-8] = 0.949 G2 = Detailed: 0.925•[(1+1.7•gq•Izm•Q)/(1+1.7•gv•Izm)] [Eq 26.11-6] = 0.898 *Gust Factor Used in Analysis* G = Gust Factor: Min(G1, G2) = 0.850
CpWW = Windward Wall Coefficient (All L/B Values) = 0.800 CpLW = Leeward Wall Coefficient using L/B = -0.500 CpSW = Side Wall Coefficient (All L/B values) = -0.700
WindPress[NormaltoEave]
Wind Pressures [Normal to Eave] All wind pressures include a Load Factor (LF) of 0.6
Elev ft
GCpi
Windward GCpi
Leeward qi psf
Kz Kzt qz psf
Windward Press psf
Leeward Press psf
Side Press psf
Total Press psf
Minimum Pressure* psf
8.000 +0.18 +0.18 14.66 0.849 1.000 14.66 7.33 -8.87 -11.36 16.20 9.60
8.000 -0.18 -0.18 14.66 0.849 1.000 14.66 12.61 -3.59 -6.08 16.20 9.60
Kz = 2.01•(15/Zg)2/α[Tbl 26.10-1] Kzt = No Topographic feature specified GCpi = Enclosed Internal Pressure Tbl
26.13-1 qz = 0.00256•Kz•Kzt•Kd•Ke•V2*LF [Eq 26.10-1] qip = Positive Internal Pressure: qh•LF qin = Negative Internal Pressure: qh•LF Side = qh•G•CpSW-qip•(+GCpi) [Eq 27.3-1] Leeward = qh•G•CpLW-qip•(+GCpi) [Eq 27.3-1] Windward = qz•G•CpWW-qip•(+GCpi) [Eq 27.3-1] Total = Windward - Leeward
• Minimum Pressure: § 27.1.5 no less than 9.60 psf (Incl LF) applied to Walls
• Positive Pressures Act TOWARD Surface and Negative Pressures Act AWAY from Surface
RoofWindPressures[NormaltoEave]
Roof Wind Pressures [Normal to Eave] All wind pressures include a Load Factor (LF) of 0.6
Component Description Location Start ft
End ft
GCpi CpMin CpMax PCpMin psf PCpMax psf Pmin psf Roof Roof Windward 3 All All +0.18 -0.180 -0.805 -4.88 -12.67 4.80
Roof Roof Windward 3 All All -0.18 -0.180 -0.805 0.40 -7.39 4.80
Roof Pressures based upon Ch 27 Pt1:
Component = The building component for pressures Location = Reference Graphic in Output for Values
Start = Start Dist from Windward Edge End = End Dist from Windward Edge CpMin = Smallest Coefficient Magnitude CpMax = Largest Coefficient Magnitude PCpMin = qh•G•CpMin-qip•GCpi[Eq 27.3-1] PCpMax = qh•G•CpMax-qin•GCpi[Eq 27.3-1]
Pmin = Min Press projected on vertical plane [§ 27.1.5]
• 0.895 Reduction Factor applied for h/L>=1 & (0 to h/2)
• The smaller uplift pressures due to CpMincan become critical when wind is combined with roof live load or snow load; load combinations are given in ASCE 7
• Positive Pressures Act TOWARD Surface and Negative Pressures Act AWAY from Surface
MWFRSWindLoads[ParalleltoRidge]
MWFRS Wind Loads [Parallel to Ridge] h = Mean Roof Height Of Building = 10.088 ft RHt = Ridge Height Of Roof = 12.176 ft B = Horizontal Dimension Of Building Normal To Wind Direction = 16.700 ft L = Horizontal Dimension Of building Parallel To Wind Direction = 16.700 ft L/B = Ratio Of L/B used For Cp determination = 1.000 h/L = Ratio Of h/L used For Cp determination = 0.604 Slope = Slope Of Roof = 14.04 Deg
GustFactorforWind[ParalleltoRidge]
Gust Factor Calculation for Wind: [Parallel to Ridge] *Gust Factor Category I Rigid Structures - Simplified Method* G1 = Simplified: For Rigid Structures can use 0.85 = 0.85 *Gust Factor Category II Rigid Structures - Complete Analysis* Zm = Equiv Struc Height: Max(0.6•h, Zmin) = 15.000 ft Izm = Turbulence Intensity: c•(33/Zm)1/6[Eq 26.11-1] = 0.228 Lzm = Turbulence Integral Length Scale: ℓ•(Zm/33)ε[Eq 26.11-9] = 427.057 ft B = Building Width Width Normal to Wind Direction = 16.700 ft Q = [1/(1+0.63•[(B+h)/Lzm]0.63)]0.5[Eq 26.11-8] = 0.949 G2 = Detailed: 0.925•[(1+1.7•gq•Izm•Q)/(1+1.7•gv•Izm)] [Eq 26.11-6] = 0.898 *Gust Factor Used in Analysis* G = Gust Factor: Min(G1, G2) = 0.850
CpWW = Windward Wall Coefficient (All L/B Values) = 0.800 CpLW = Leeward Wall Coefficient using L/B = -0.500 CpSW = Side Wall Coefficient (All L/B values) = -0.700
WindPress[ParalleltoRidge]
Wind Pressures [Parallel to Ridge] All wind pressures include a Load Factor (LF) of 0.6
Elev ft
GCpi
Windward GCpi
Leeward qi psf
Kz Kzt qz psf
Windward Press psf
Leeward Press psf
Side Press psf
Total Press psf
Minimum Pressure* psf
12.176 +0.18 +0.18 14.66 0.849 1.000 14.66 7.33 -8.87 -11.36 16.20 9.60
10.088 +0.18 +0.18 14.66 0.849 1.000 14.66 7.33 -8.87 -11.36 16.20 9.60
8.000 +0.18 +0.18 14.66 0.849 1.000 14.66 7.33 -8.87 -11.36 16.20 9.60
12.176 -0.18 -0.18 14.66 0.849 1.000 14.66 12.61 -3.59 -6.08 16.20 9.60
10.088 -0.18 -0.18 14.66 0.849 1.000 14.66 12.61 -3.59 -6.08 16.20 9.60
8.000 -0.18 -0.18 14.66 0.849 1.000 14.66 12.61 -3.59 -6.08 16.20 9.60
Kz = 2.01•(15/Zg)2/α[Tbl 26.10-1] Kzt = No Topographic feature specified GCpi = Enclosed Internal Pressure Tbl
26.13-1 qz = 0.00256•Kz•Kzt•Kd•Ke•V2*LF [Eq 26.10-1] qip = Positive Internal Pressure: qh•LF qin = Negative Internal Pressure: qh•LF Side = qh•G•CpSW-qip•(+GCpi) [Eq 27.3-1] Leeward = qh•G•CpLW-qip•(+GCpi) [Eq 27.3-1] Windward = qz•G•CpWW-qip•(+GCpi) [Eq 27.3-1] Total = Windward - Leeward
• Minimum Pressure: § 27.1.5 no less than 9.60 psf (Incl LF) applied to Walls
• Positive Pressures Act TOWARD Surface and Negative Pressures Act AWAY from Surface
RoofWindPressures[ParalleltoRidge]
Roof Wind Pressures [Parallel to Ridge] All wind pressures include a Load Factor (LF) of 0.6
Component Description Location Start ft
End ft
GCpi CpMin CpMax PCpMin psf PCpMax psf Pmin psf Roof Roof (0 to h/2) All 0.000 5.044 +0.18 -0.955 -0.180 -14.53 -4.88 4.80 Roof Roof (h/2 to h) All 5.044 10.088 +0.18 -0.858 -0.180 -13.33 -4.88 4.80 Roof Roof (h to 2*h) All 10.088 16.700 +0.18 -0.542 -0.180 -9.39 -4.88 4.80
Roof Roof (0 to h/2) All 0.000 5.044 -0.18 -0.955 -0.180 -9.26 0.40 4.80 Roof Roof (h/2 to h) All 5.044 10.088 -0.18 -0.858 -0.180 -8.06 0.40 4.80 Roof Roof (h to 2*h) All 10.088 16.700 -0.18 -0.542 -0.180 -4.11 0.40 4.80
Roof Pressures based upon Ch 27 Pt1:
Component = The building component for pressures Location = Reference Graphic in Output for Values
Start = Start Dist from Windward Edge End = End Dist from Windward Edge CpMin = Smallest Coefficient Magnitude CpMax = Largest Coefficient Magnitude PCpMin = qh•G•CpMin-qip•GCpi[Eq 27.3-1] PCpMax = qh•G•CpMax-qin•GCpi[Eq 27.3-1]
Pmin = Min Press projected on vertical plane [§ 27.1.5]
• 0.895 Reduction Factor applied for h/L>=1 & (0 to h/2)
• The smaller uplift pressures due to CpMincan become critical when wind is combined with roof live load or snow load; load combinations are given in ASCE 7
• Positive Pressures Act TOWARD Surface and Negative Pressures Act AWAY from Surface
Project Location
In no case shall the roof snow load be reduced to less than 35 psf
PROJECT NUMBER
DESIGNER
Ps : Sloped roof snow load (PSF)
CS : Slope factor [ ASCE-7, Fig 7.4-1 ]
Pf : Flat roof snow load (PSF)
Ce : Exposure factor [ ASCE-7, Table 7.3-1 ]
Ct : Thermal factor [ ASCE-7, Table 7.3-2 ] δ: Density of snow
I : Snow load importance factor [ ASCE-7, Table 1.5-1 ] hd: Drift Height [ASCE-7, Fig 7-8, lu=W from windward side]
Pg : Ground snow load S: roof slope for a rise of 1 =
1) Flat Roof Snow Load
Pf = 0.7 x Ce x Ct x I x Pg [ ASCE-7, Eq 7.3-1 ]
Cat., Exposure
Ce = I =
Ct = Pg =
Pf = .7 x 1 x 1.2 x 1 x 43 = 36 (PSF)
2) Sloped Roof Snow Load
Ps = CS x Pf [ ASCE-7, Eq 7.4-1 ]
Roof slope = 3 / 12 = 14 o
Cs = [ASCE-7 Fig 7.4-1]
Ps = 1.00 x 36
Ps = (PSF)
Enter values from Code Calculated Values
IBC SNOW LOAD
SLOPED ROOF
1.00
0.9
1.0 43
1.0
RMH
Romtec 224-032
250-A Main Street E-Mail: info@structure1.com ph. (541) 850-6300 Klamath Falls, OR. 97601 Web: www.structure1.com fax (541) 850-6233
ANALYSIS & DESIGN:
Pages 1,000 - 1,999
Project Number
Project Name RMH Date
Subject Date
Spacing: 6 " O.C.
L: 5 ft
Distributed Load (D):
15 psf * 0.50 ft = 7.50 plf
36 psf * 0.50 ft = 18.00 plf
USE
Trib.: 5 ft.
Roof Slope: 3 to 12 L: 16 ft
Distributed Load (D):
15 psf * 5.00 ft = 75.00 plf
36 psf * 5.00 ft = 180.00 plf
USE
Trib.: 9.5 ft.
L: 20 ft
Distributed Load (D):
15 psf * 9.50 ft = 142.50 plf
36 psf * 9.50 ft = 342.00 plf
USE
Analysis Checked by
PSE Consulting Engineers Inc.
Romtec 224-032
Billy Cordova Memorial Park Restroom Designed by 4/22/2024
Snow Load =
Roof Extension Beams
Dead Load =
5 1/8" x 13 1/2" Glu-Lam 24F-1.8E WS
Dead Load =
Snow Load =
5 1/8" x 9" Glu-Lam 24F-1.8E WS
Roof Decking
Dead Load =
Snow Load =
Flat 2x6 DF-L #2 T&G
Rafters
COMPANY
Apr. 22, 2024 13:35
PROJECT
Roof Decking
Design Check Calculation Sheet WoodWorks Sizer 2023
Loads:
Load Type Distribution Pat- Location [ft] Magnitude Unit tern Start End Start End Load1 Dead Full Area 10.00(6.0") psf Load2 Snow Full Area 36.00(6.0") psf Self-weight Dead Full UDL 2.0 plf
Maximum Reactions (lbs), Bearing Capacities (lbs) and Bearing Lengths (in) :
5'
4.958'0'
Unfactored:
Dead 17 17 Snow 45 45 Factored:
Total 62 62 Bearing:
Capacity Joist 469 469 Support 586 586 Des ratio Joist 0.13 0.13 Support 0.11 0.11 Load comb #2 #2 Length 0.50* 0.50* Min req'd 0.50* 0.50* Cb 1.00 1.00 Cb min 1.00 1.00 Cb support 1.25 1.25 Fcp sup 625 625
*Minimum bearing length setting used: 1/2" for end supports
Lumber-soft, D.Fir-L, No.2, 2x6 (1-1/2"x5-1/2") Supports: All - Timber-soft Beam, D.Fir-L No.2
Roof joist spaced at 6.0" c/c; Total length: 5.0'; Clear span: 4.938'; Volume = 0.3 cu.ft.
Lateral support: top = continuous, bottom = continuous Oblique angle: 76.0 deg; Repetitive factor: applied where permitted (refer to online help);
This section PASSES the design code check.
WoodWorks® Sizer SOFTWARE FOR WOOD DESIGN
WoodWorks® Sizer 2023Roof Decking Page 2
Analysis vs. Allowable Stress and Deflection using NDS 2018 :
Criterion Analysis Value Design Value Unit Analysis/Design Shear x-x fv = 3 Fv' = 180 psi fv/Fv' = 0.01 y-y fv = 10 Fv' = 180 psi fv/Fv' = 0.06 Bending(+) x-x fb = 29 Fb' = 1345 psi fb/Fb' = 0.02 y-y fb = 433 Fb' = 1547 psi fb/Fb' = 0.28 Biaxial 3.9-3: fb1/Fb1'+fb2/Fb2'/(1-(fb1/FbE)^2) = 0.30 Live Defl'n 0.10 = L/619 0.33 = L/180 in 0.29 Total Defl'n 0.15 = L/392 0.50 = L/120 in 0.31
Additional Data:
FACTORS: F/E(psi) CD CM Ct CL CF Cfu Cr Cfrt Ci LC# Fv' 180 1.00 1.00 1.00 - - - - 1.00 1.00 2 Fvy' 180 1.00 1.00 1.00 - - - - 1.00 1.00 2 Fb'+ 900 1.00 1.00 1.00 1.000 1.300 - 1.15 1.00 1.00 2 Fby' 900 1.00 1.00 1.00 1.000 1.300 - 1.15 1.00 1.00 2 Fcp' 625 - 1.00 1.00 - - - - 1.00 1.00 - E' 1.6 million 1.00 1.00 - - - - 1.00 1.00 2 Emin' 0.58 million 1.00 1.00 - - - - 1.00 1.00 2 Ey' 1.6 million 1.00 1.00 - - - - 1.00 1.00 2 Emin' 0.58 million 1.00 1.00 - - - - 1.00 1.00 2 Custom duration factor for Snow load = 1.00
CRITICAL LOAD COMBINATIONS:
Shear : LC #2 = D + S Bending(+): LC #2 = D + S Deflection: LC #2 = D + S (live) LC #2 = D + S (total) Bearing : Support 1 – LC #2 = D + S Support 2 – LC #2 = D + S D=dead S=snow All LC's are listed in the Analysis output Load combinations: ASD Basic from ASCE 7-16 2.4
CALCULATIONS:
V max = 62, Vx design = 14, Vy design = 57 lbs; M(+) = 77 lbs-ft EI = 33.27e06 lb-in^2 EIy = 2.47e06 lb-in^2 "Live" deflection is due to all non-dead loads (live, wind, snow…) Total deflection = 1.50 permanent + "live"
Design Notes:
1. Analysis and design are in accordance with the ICC International Building Code (IBC 2021) and the National Design Specification (NDS 2018), using Allowable Stress Design (ASD). Design values are from the NDS Supplement.
2. Please verify that the default deflection limits are appropriate for your application.
3. Sawn lumber bending members shall be laterally supported according to the provisions of NDS Clause 4.4.1.
4. Oblique angle: Shear is checked in planes perpendicular to the axes only, but maximum shear occurs at an angle.
Apr. 22, 2024 13:37
Roof Rafters
WoodWorks Sizer 2023
Loads:
Load Type Distribution Pat- Location [ft] Magnitude Unit tern Start End Start End Load1 Dead Full Area 15.00(5.00') psf Load2 Snow Full Area 36.00(5.00') psf Self-weight Dead Full UDL 10.6 plf
Maximum Reactions (lbs), Bearing Capacities (lbs) and Bearing Lengths (in) :
16.492'
15.948'0'
Unfactored:
Dead 706 706 Snow 1440 1440 Factored:
Total 2146 2146 Bearing:
F'theta 674 674 Capacity Beam 2155 2155 Support 2146 2146 Des ratio Beam 1.00 1.00 Support 1.00 1.00 Load comb #2 #2 Length 0.62 0.62 Min req'd 0.62** 0.62** Cb 1.00 1.00 Cb min 1.00 1.00 Cb support 1.07 1.07 Fcp sup 625 625
**Minimum bearing length governed by the required width of the supporting member.
Glulam-Unbalan., West Species, 24F-1.8E WS, 5-1/8"x9" Supports: All - Timber-soft Beam, D.Fir-L No.2
Total length: 16.69'; Clear span(horz): 15.875'; Volume = 5.3 cu.ft.; Pitch: 3/12; 6 laminations, 5-1/8" maximum width, Lateral support: top = continuous, bottom = at supports;
This section PASSES the design code check.
WoodWorks® Sizer 2023Roof Rafters Page 2
Analysis vs. Allowable Stress and Deflection using NDS 2018 :
Criterion Analysis Value Design Value Unit Analysis/Design Shear fv = 61 Fv' = 265 psi fv/Fv' = 0.23 Bending(+) fb = 1479 Fb' = 2400 psi fb/Fb' = 0.62 Live Defl'n 0.50 = L/397 0.82 = L/240 in 0.60 Total Defl'n 0.86 = L/228 1.10 = L/180 in 0.79
Additional Data:
FACTORS: F/E(psi) CD CM Ct CL CV Cfu Cr Cfrt Notes Cvr LC# Fv' 265 1.00 1.00 1.00 - - - - 1.00 1.00 1.00 2 Fb'+ 2400 1.00 1.00 1.00 1.000 1.000 - - 1.00 1.00 - 2 Fcp' 650 - 1.00 1.00 - - - - 1.00 - - - E' 1.8 million 1.00 1.00 - - - - 1.00 - - 2 Eminy' 0.85 million 1.00 1.00 - - - - 1.00 - - 2 Custom duration factor for Snow load = 1.00
CRITICAL LOAD COMBINATIONS:
Shear : LC #2 = D + S Bending(+): LC #2 = D + S Deflection: LC #2 = D + S (live) LC #2 = D + S (total) Bearing : Support 1 – LC #2 = D + S Support 2 – LC #2 = D + S D=dead S=snow All LC's are listed in the Analysis output Load combinations: ASD Basic from ASCE 7-16 2.4
CALCULATIONS:
V max = 2075, V design = 1879 (NDS 3.4.3.1(a)) lbs; M(+) = 8528 lbs-ft EI = 560.41e06 lb-in^2 "Live" deflection is due to all non-dead loads (live, wind, snow…) Total deflection = 1.50 permanent + "live" Bearing: Allowable bearing at an angle F'theta calculated for each support as per NDS 3.10.3
Design Notes:
1. Analysis and design are in accordance with the ICC International Building Code (IBC 2021) and the National Design Specification (NDS 2018), using Allowable Stress Design (ASD). Design values are from the NDS Supplement.
2. Please verify that the default deflection limits are appropriate for your application.
3. Glulam design values are for materials conforming to ANSI 117-2015 and manufactured in accordance with ANSI A190.1-2012
4. GLULAM: bxd = actual breadth x actual depth.
5. Glulam Beams shall be laterally supported according to the provisions of NDS Clause 3.3.3.
6. GLULAM: bearing length based on smaller of Fcp(tension), Fcp(comp'n).
7. SLOPED BEAMS: level bearing is required for all sloped beams.
Apr. 22, 2024 13:40
Roof Extension Beams
WoodWorks Sizer 2023
Loads:
Load Type Distribution Pat- Location [ft] Magnitude Unit tern Start End Start End Load1 Dead Full Area 15.00(9.50') psf Load2 Snow Full Area 36.00(9.50') psf Self-weight Dead Full UDL 15.9 plf
Maximum Reactions (lbs), Bearing Capacities (lbs) and Bearing Lengths (in) :
20.253'
20.127'0'
Unfactored:
Dead 1603 1603 Snow 3463 3463 Factored:
Total 5067 5067 Bearing:
Capacity Beam 5067 5067 Support 5228 5228 Des ratio Beam 1.00 1.00 Support 0.97 0.97 Load comb #2 #2 Length 1.52 1.52 Min req'd 1.52 1.52 Cb 1.00 1.00 Cb min 1.00 1.00 Cb support 1.07 1.07 Fcp sup 625 625
Glulam-Unbalan., West Species, 24F-1.8E WS, 5-1/8"x13-1/2" Supports: All - Timber-soft Beam, D.Fir-L No.2
Total length: 20.25'; Clear span: 20'; Volume = 9.7 cu.ft.; 9 laminations, 5-1/8" maximum width, Lateral support: top = 5'-0 bottom = at supports; (in);
This section PASSES the design code check.
Analysis vs. Allowable Stress and Deflection using NDS 2018 :
Criterion Analysis Value Design Value Unit Analysis/Design Shear fv = 96 Fv' = 265 psi fv/Fv' = 0.36 Bending(+) fb = 1953 Fb' = 2379 psi fb/Fb' = 0.82 Live Defl'n 0.67 = L/361 1.01 = L/240 in 0.66 Total Defl'n 1.13 = L/213 1.34 = L/180 in 0.84
WoodWorks® Sizer 2023Roof Extension Beams Page 2
Additional Data:
FACTORS: F/E(psi) CD CM Ct CL CV Cfu Cr Cfrt Notes Cvr LC# Fv' 265 1.00 1.00 1.00 - - - - 1.00 1.00 1.00 2 Fb'+ 2400 1.00 1.00 1.00 0.991 0.992 - - 1.00 1.00 - 2 Fcp' 650 - 1.00 1.00 - - - - 1.00 - - - E' 1.8 million 1.00 1.00 - - - - 1.00 - - 2 Eminy' 0.85 million 1.00 1.00 - - - - 1.00 - - 2 Custom duration factor for Snow load = 1.00 Only the lesser of CL and CV is applied, as per NDS 5.3.6
CRITICAL LOAD COMBINATIONS:
Shear : LC #2 = D + S Bending(+): LC #2 = D + S Deflection: LC #2 = D + S (live) LC #2 = D + S (total) Bearing : Support 1 – LC #2 = D + S Support 2 – LC #2 = D + S D=dead S=snow All LC's are listed in the Analysis output Load combinations: ASD Basic from ASCE 7-16 2.4
CALCULATIONS:
V max = 5036, V design = 4441 (NDS 3.4.3.1(a)) lbs; M(+) = 25340 lbs-ft EI = 1891.38e06 lb-in^2 "Live" deflection is due to all non-dead loads (live, wind, snow…) Total deflection = 1.50 permanent + "live" Lateral stability(+): Lu = 5.00' Le = 10.31' RB = 8.0
Design Notes:
1. Analysis and design are in accordance with the ICC International Building Code (IBC 2021) and the National Design Specification (NDS 2018), using Allowable Stress Design (ASD). Design values are from the NDS Supplement.
2. Please verify that the default deflection limits are appropriate for your application.
3. Glulam design values are for materials conforming to ANSI 117-2015 and manufactured in accordance with ANSI A190.1-2012
4. GLULAM: bxd = actual breadth x actual depth.
5. Glulam Beams shall be laterally supported according to the provisions of NDS Clause 3.3.3.
6. GLULAM: bearing length based on smaller of Fcp(tension), Fcp(comp'n).
Subject Date
L: 12 ft
Trib: 8 ft
15 psf * 8.00 ft = 120.00 plf
36 psf * 8.00 ft = 288.00 plf
Distributed Load(D):
Wind Load = 22.1 psf
USE
Continuous Wall Footing
Trib: 8 ft
15 psf * 8 = 120 plf
36 psf * 8 = 288 plf
Loads from: Wall Height: 12 ft
Dead Load = 81 psf * 12 = 972 plf
USE
Loads from: Roof
Cont. x 24" x 8" Footing W/ 3 - #5 Bars
Masonry Bearing Wall
Load (P):
Dead Load =
Snow Load =
6" CMU W/ #4 Vert Bars @ 32" O.C.
Dead Load =
Snow Load =
Analysis Checked by
PSE Consulting Engineers Inc.
Romtec 224-032
Billy Cordova Memorial Park Restroom Designed by 4/22/2024
PROJECT : PAGE :
CLIENT : DESIGN BY :
JOB NO. : DATE : REVIEW BY :
INPUT DATA
WALL THICKNESS t = 8 in, (203 mm)
PARAPET HEIGHT hp = 0 ft, (0.0 m)
WALL HEIGHT h = 12 ft, (3.7 m) ρ = 125 lbs/ft 3 ( 2001 kg/m
SEISMIC PARAMETER SDS = 0.362
SEISMIC DESIGN CATEGORY SDC = C
DIAPHRAGM FLEXIBLE ? (0=no, 1=yes) 1 Yes
Ie = 1
Iw = 1.0 (ASCE 7 Tab 1.5-2)
BASIC WIND SPEED V = 115 mph, (185 kph), (ASCE 7 Sec 26.5.1)
EXPOSURE CATEGORY (B, C, D) = C
TOPOGRAPHIC FACTOR KZt = 1
DESIGN SUMMARY
Out-of-plane force for wall design w1 = 22.1 psf (Wind governs) N/m
Out-of-plane force for parapet design w2 = 52.5 psf (Wind governs) N/m
Out-of-plane force for anchorage design Fanch = 196 plf (Horizontal direction) N/m )
(The governing seismic & wind forces have been reduced by 0.7 & 0.6 for ASD)
WIND ANALYSIS
Out-of-plane wind force for wall design (ASCE 7-22 Eq. 30.3-1)
= 22.1 psf
Where : Kh = 0.85 , Kd = 0.85 , GCp = -1.33 , GCpi = 0.18
(mean roof h = 12 ft, changeable) Ke = 1.00 (corner ? Yes , TA = 16 ft ) (ASCE 7-22 Tab. 26.13-1)
(ASCE 7-22 26.10-1) (ASCE 7-22 30.3.2)
Out-of-plane wind force for parapet design (ASCE 7-22 Eq. 30.8-1)
= 52.5
Where : Kh = 0.85 , Kd = 0.85 , GCp = -1.40 , GCp = -2.40 GCpi = 0.18
(ASCE 7-22 26.10-1) (ASCE 7-22 26.10-1) = 1.00 roof, (ASCE 7-22 30.3.2) ( ASCE 7-22 Tab. 26.13-1)
(TA = 0 ft wall, (ASCE 7-22 30.3.2)
Out-of-plane wind force for anchorage design
= 133 plf (Horizontal)
SEISMIC ANALYSIS
Out-of-plane seismic force for wall design (ASCE 7, Sec.12.11.1)
= 0.14 Wp = 12.1 psf
Where : Wp = 83.3 psf , Ie = 1.0
(CBC/IBC Tab 1604.5 & ASCE 7 Tab 1.5-2)
Out-of-plane seismic force for parapet design (ASCE 7, Sec. 13.3.1)
= 0.45 Wp = 37.2 psf
Where : CAR = 2.2 , Ip = 1.0 , Rpo = 2.5
(ASCE 7 Tab. 13.5-1) (ASCE 7 Sec. 13.1.3) (ASCE 7 Tab. 13.5-1)
Out-of-plane seismic force for anchorage design
For masonry or concrete under seismic design category A & B, both flexible & rigid diaphragm (ASCE 7 Sec. 12.11.2)
3.36 Wp =
280 plf (Horizontal)
(Not applicable)
Where : Fmin = 280 plf
(ASCE 7 Sec. 12.11.2 & 11.7.3)
For seismic design category C and above, flexible diaphragm (ASCE 7 Sec. 12.11.2.1)
3.36 Wp =
280 plf (Horizontal)
(Applicable)
For seismic design category C and above, rigid diaphragm (ASCE 7 Sec. 12.11.2 & Sec. 13.3.1)
= 3.48 Wp = 290 plf (Horizontal) (Not applicable)
Where : CAR = 2.2 Rpo = 1.5
(ASCE 7 Tab. 13.5-1) (1.5, ASCE 7 13.4.2 or 2.5, ASCE 7 Tab 13.5-1)
Flat, (ASCE 7 Tab 26.8-1) psf, (ASCE 7-22 30.8)
WIND IMPORTANCE FACTOR
SEISMIC IMPORTANCE FACTOR
(ASCE 7 Sec 11.4)
(ASCE 7 Tab 11.5-1)
Lateral Force for One-Story Wall Based on ASCE 7-22 & 2021 IBC
TOTAL WALL DENSITY
, ( 1060
, ( 2516
, ( 2858
( )1, 0.4 ,0.1seismic DS p pMAX Iw S W W=
, 1, 2,1 2 2 p anch wind wind p wind h h w h wF h
2 2
, min0.4 , 0.1 , 400 , 2 2 anch seismic DS p p DS h hh hp p
MAX I IS W W SF F
h h
2 2
, min0.8 , 0.1 , 400 , 2 2 anch seismic DS p p DS h hh hp p
MAX I IS W W SF F
h h
( ) ( ) ( ) ( ) ( )2 1, 0.6 0.00256d h Zt e dwind P Pi P Pih
G G G Gqw C C V C CK K K K K= − = −
( ) ( ) ( ) ( ) ( )2 2, 0.6 0.00256d h Zt e dwind P Pi P Pip
G G G Gqw C C V C CK K K K K= − = −
2, 1.4
0.3 , , 1.6 pAR DS p p pseismic DS p DS p po
C S WI
MAX MINw S W S WI I
R
, min
1.4
0.4 , , 1.6 , 400 , pp DS anch seismic p pDS DS p DS po h h pa S I
MAX MAX MIN IS S W SF I I F
hR
JOB NO. : DATE : REVIEW BY :
INPUT DATA & DESIGN SUMMARY
SPECIAL INSPECTION ( 0=NO, 1=YES ) 1 Yes
TYPE OF MASONRY ( 1=CMU, 2=BRICK ) 1 CMU
MASONRY STRENGTH fm' = 1.5 ksi
REBAR YIELD STRESS fy = 60 ksi
No
SERVICE GRAVITY LOAD P = 408 lbs / ft
SERVICE LATERAL LOAD w1 = 22.1 plf / ft
SERVICE PARAPET LOAD w2 = 0 plf / ft
THICKNESS OF WALL t = 6 in
PARAPET HEIGHT hp = 0 ft
WALL HEIGHT h = 12 ft
ECCENTRICITY e = 0 in γm = 125 pcf [THE WALL DESIGN IS ADEQUATE.]
WALL HORIZ. REINF. 1 # 4 @ 32 in o.c. (at middle)
WALL VERT. REINF. 1 # 4 @ 32 in o.c. (at middle)
ANALYSIS
VERT. REINF. AREA AT EACH SIDE As = 0.08 in
MODULAR RATIO n = 21.48 d = 2.82 in REINFORCEMENT RATIO ρ = 0.0022
WIDTH OF SECTION bw = 12.00 in ALLOWABLE STRESS FACTOR SF = 1.000
EFFECTIVE THICKNESS te = 5.63 in THE NEUTRAL AXIS DEPTH FACTOR IS
MASONRY ELASTICITY MODULUS Em = 1350 ksi
STEEL ELASTICITY MODULUS Es = 29000 ksi
THE ALLOWABLE STRESS DUE TO FLEXURE IS THE ALLOWABLE REINF. STRESS DUE TO FLEXURE IS psi 32000 psi
THE DISTANCE FROM BOTTOM TO M1 IS THE GOVERNING MOMENTS AND AXIAL FORCES ARE
= 6.0 ft = 418 ft-lbs/ft
= lbs / ft
THE GOVERNING SHEAR FORCES ARE
= 0 ft-lbs/ft
= 133 lbs / ft
= lbs / ft
= 133 lbs / ft THE GOVERNING SHEAR STRESS IN MASONRY IS
= 0 lbs / ft = 1.96 psi
DETERMINE THE REGION FOR FLEXURE AND AXIAL LOAD (MDG-3 Tab 12.2.1, Fig 12.2-12 & 13, page 12-25).
1. Wall is in compression and not cracked. 2. Wall is cracked but steel is in compression. 3. Wall is cracked and steel is in tension.
REGION 3 APPLICABLE FOR (M1, P1)
REGION 1 APPLICABLE FOR (M2, P2)
Allowable Stress Design of Masonry Bearing Wall Based on TMS 402-16/13 & 2021 IBC
ALLOWABLE INCREASING ? (IBC/CBC 1605.2)
MASONRY SPECIFIC WEIGHT
= 0.26482
EFFECTIVE DEPTH (TMS 402 6.1.3.5)
( )1.33 1.0 (20) 32S or orF = =
( )1 2 3, , v e w
MAX V V V
f t b
( ) ( )'0.33b m SF fF = =
2k n n nρ ρ ρ= + − eM t
Pd d
2 3 eM t
Pd d
2 3 eM t
Pd d
1 2 2 1 2
1.05 p w Pe h hM w h p p h h Pe S h h h hw
( )1 P wall weightP = + pw h M =
( )2 P wall weightP = +
1 1 p p h h w Pe hV h w h h
2 1 1hV w V= −
3 2pV h w=
(cont'd)
CHECK REGION 1 CAPACITY
2554 ft-lbs / ft > M1 [Not applicable]
2583 ft-lbs / ft > M2 [Satisfactory]
CHECK REGION 2 CAPACITY
178 ft-lbs / ft < M1 [Not applicable]
94 ft-lbs / ft > M2 [Not applicable]
CHECK REGION 3 CAPACITY (The moment maybe limited by either the masonry compression or steel tension, MDG-3 page 12-25).
474 ft-lbs / ft > M1 [Satisfactory]
474 ft-lbs / ft > M2 [Not applicable]
THE ALLOWABLE SHEAR STRESS IS GIVEN BY (TMS 402 8.2.6)
= 43.571 psi > fv [Satisfactory]
Technical References:
1. "Masonry Designers' Guide, Third Edition" (MDG-3), The Masonry Society, 2001.
6 6 w e e m b b t t
PM F
2 3 e m bw t P
PM
b F
2 3 2 3 2 3 e e m b s sw kd kd kdt t MIN kd d P d d PbM F A F
( ) ( )'1.125v m SF fF =
JOB NO. : DATE : REVIEW BY :
INPUT DATA & DESIGN SUMMARY
FOOTING SIZE A = 30 in
B = 8 in
C = 24 in
D = 8 in
E = 8 in
FOOTING CONCRETE STRENGTH fc' = 2.5 ksi
PDL = 1.092 k / ft
PLL = 0.288 k / ft
= 0 Wind,SD
PLAT = 1 k / ft, SD
(holdown force converted to load per linear foot)
SURCHARGE qs = 0.1 ksf
SOIL WEIGHT ws = 0.11 kcf
THE FOOTING DESIGN IS ADEQUATE.
ALLOWABLE SOIL PRESSURE Qa = 3.5 ksf
ANALYSIS
DESIGN LOADS (IBC 1605.2 & ACI 318 5.3)
CASE 1: DL + LL P = 1.38 k / ft 1.2 DL + 1.6 LL Pu = 1.77 k / ft
CASE 2: P = 2.16 k / ft 1.2 DL + LL + 1.0 W Pu = 2.60 k / ft
CASE 3: P = 1.77 k / ft 0.9 DL+ 1.0 W Pu = 1.98 k / ft
CHECK SOIL BEARING CAPACITY (ACI 318 13.3.1.1)
Service Loads CASE 1 CASE 2 CASE 3
P 1.38 2.16 1.77 k / ft e 0.0 0.0 0.0 in (from center of footing) qs C 0.20 0.20 0.20 k / ft, (surcharge load)
(0.15-ws) Area 0.12 0.12 0.12 k / ft, (footing increased)
Σ P 1.7 2.5 2.1 k / ft e 0.0 0.0 0.0 in qmax 0.85 1.24 1.04 ksf
Qa 3.50 3.50 3.50 ksf
Where [Satisfactory]
DESIGN FOR FLEXURE (ACI 318 14.5)
= 1.60 ft-kips / ft where λ = 1.0 (ACI 318 19.2.4) φ = 0.6 (ACI 318 21.2)
S = elastic section modulus of section
= 128 in / ft
DL + LL + 0.6(1.3) W
DL + LL + 0.6(0.65) W
AXIAL DEAD LOAD (per linear foot)
AXIAL LIVE LOAD (per linear foot)
LATERAL LOAD (per linear foot)
LATERAL LOAD (0=WIND, 1=SEISMIC)
Footing Design for Stud Bearing Wall Based on 2021 IBC / ACI 318-19
5 , 0.85n c c
MIN S Sf fMφ λφ φ= max
3(0.5 ) 6 e P
CC
for e
Cq
P C for e
C e
Σ +
Σ
FACTORED SOIL PRESSURE
Factored Loads CASE 1 CASE 2 CASE 3 Pu 1.8 2.6 2.0 k / ft eu 0.0 0.0 0.0 in (from center of footing) γ qs C 0.32 0.32 0.32 k / ft, (factored surcharge load)
0.78 0.78 0.59 Σ Pu 2.87 3.70 2.89 k / ft eu 0.0 0.0 0.0 in
E 8.0 8.0 8.0 in qu, max 1.44 1.85 1.44 ksf qu, VL 1.44 1.85 1.44 ksf qu, ML 1.44 1.85 1.44 ksf qu, MR 1.44 1.85 1.44 ksf qu, VR 1.44 1.85 1.44 ksf qu, min 1.44 1.85 1.44 ksf
M u, L 0.22 0.31 0.22 ft-k / ft
M u, R 0.22 0.31 0.22 ft-k / ft
V u, L 0.00 0.00 0.00 k / ft
V u, R 0.00 0.00 0.00 k / ft
M u, max = 0.31 ft-k / ft < φ M n [Satisfactory]
CHECK FLEXURE SHEAR (ACI 318 14.5)
= 3.84 k / ft where φ = 0.6 (ACI 318 21.2)
V u, max = 0.00 k / ft < φ V n [Satisfactory] k / ft, (factored footing & backfill loads)γ[0.15AC - (0.15-Ws) (C-D) (A-B) ]
'4 n c
BfVφ λφ=
Subject Date
L: 12 ft
Point Load (P):
Dead Load = 1,603 lb
Snow Load = 3,463 lb
USE
Point Load (P):
Dead Load = 1,603 lb
Snow Load = 3,463 lb
USE
PSE Consulting Engineers Inc.
Romtec 224-032
Billy Cordova Memorial Park Restroom Designed by 4/22/2024
Analysis Checked by
Porch Column
24" x 24" x 12" Footing W/ 3 - #5 Bars
6x6 DF-L #2
Porch Column Footing
Apr. 22, 2024 14:05
Porch Posts
WoodWorks Sizer 2023
Loads:
Load Type Distribution Location [ft] Magnitude Unit Start End Start End Load1 Dead Axial (Ecc. = 0.92") 1603 lbs Load3 Snow Axial (Ecc. = 0.92") 3463 lbs Self-weight Dead Axial 86 lbs
Reactions (lbs):
12'
12' 0'
B a s e
T o p
Unfactored:
Lateral:
Dead 10 -10 Snow 22 -22 Axial:
Dead 1689 1689 Snow 3463 3463 Factored:
R->L -32 Load comb #2 L->R 32 Load comb #2 #1
Timber-soft, D.Fir-L, No.2, 6x6 (5-1/2"x5-1/2") Support: Non-wood
Total length: 12.0'; Volume = 2.5 cu.ft.; Post or timber
Pinned base; Load face = width(b); Ke x Lb: 1.0 x 12.0 = 12.0 ft; Ke x Ld: 1.0 x 12.0 = 12.0 ft;
This section PASSES the design code check.
Analysis vs. Allowable Stress and Deflection using NDS 2018 :
Criterion Analysis Value Design Value Unit Analysis/Design Shear fv = 2 Fv' = 170 psi fv/Fv' = 0.01 Bending(+) fb = 167 Fb' = 750 psi fb/Fb' = 0.22 Axial fc = 170 Fc' = 428 psi fc/Fc' = 0.40 Combined (axial + eccentric moment) Eq.15.4-3 = 0.50 Axial Bearing fc = 170 Fc* = 700 psi fc/Fc* = 0.24 Live Defl'n 0.04 = < L/999 0.80 = L/180 in 0.05 Total Defl'n 0.07 = < L/999 0.80 = L/180 in 0.09
WoodWorks® Sizer 2023Porch Posts Page 2
Additional Data:
FACTORS: F/E(psi) CD CM Ct CL/CP CF Cfu Cr Cfrt Ci LC# Fv' 170 1.00 1.00 1.00 - - - - 1.00 1.00 2 Fb'+ 750 1.00 1.00 1.00 1.000 1.000 - 1.00 1.00 1.00 2 Fc' 700 1.00 1.00 1.00 0.612 1.000 - - 1.00 1.00 2 E' 1.3 million 1.00 1.00 - - - - 1.00 1.00 2 Emin' 0.47 million 1.00 1.00 - - - - 1.00 1.00 2 Eminy' 0.47 million 1.00 1.00 - - - - 1.00 1.00 2 Fc* 700 1.00 1.00 1.00 - 1.000 - - 1.00 1.00 2 Custom duration factor for Snow load = 1.00
CRITICAL LOAD COMBINATIONS:
Shear : LC #2 = D + S Bending(+): LC #2 = D + S Deflection: LC #2 = D + S (live) LC #2 = D + S (total) Axial : LC #2 = D + S Combined : LC #2 = D + S D=dead S=snow All LC's are listed in the Analysis output Load combinations: ASD Basic from ASCE 7-16 2.4
CALCULATIONS:
V = 32 lbs; M(+) = 387 lbs-ft; P = 5152 lbs EI = 99.13e06 lb-in^2 Combined: Fb' = 750 psi; fb = 0 psi; fbe = (P x e)/S = fc(6e/d) = 167 psi;
FcE = 564 psi "Live" deflection is due to all non-dead loads (live, wind, snow…) Total deflection = 1.50 permanent + "live" Axial b used, l/b = 26.2, l/d = 26.2
Design Notes:
1. Analysis and design are in accordance with the ICC International Building Code (IBC 2021) and the National Design Specification (NDS 2018), using Allowable Stress Design (ASD). Design values are from the NDS Supplement.
2. Please verify that the default deflection limits are appropriate for your application.
3. Axial load eccentricity applied in direction of load face only. It is the designers responsibility to check for effect of eccentricity in the other direction.
JOB NO. : DATE : REVIEW BY :
INPUT DATA DESIGN SUMMARY
COLUMN WIDTH c1 = 6 in FOOTING WIDTH B = 2.00 ft
COLUMN DEPTH c2 = 6 in FOOTING LENGTH L = 2.00 ft
BASE PLATE WIDTH b1 = 6 in FOOTING THICKNESS T = 12 in
BASE PLATE DEPTH b2 = 6 in LONGITUDINAL REINF. 3 # 4 @ 9 in o.c.
FOOTING CONCRETE STRENGTH fc' = 2.5 ksi TRANSVERSE REINF. 3 # 4 @ 9 in o.c.
REBAR YIELD STRESS fy = 60 ksi
AXIAL DEAD LOAD PDL = 1.603 k
AXIAL LIVE LOAD PLL = 3.463 k
LATERAL LOAD (0=WIND, 1=SEISMIC) = 0 Wind,SD
WIND AXIAL LOAD PLAT = 0 k, SD
SURCHARGE qs = 0 ksf
SOIL WEIGHT ws = 0.11 kcf
FOOTING EMBEDMENT DEPTH Df = 2.5 ft
FOOTING THICKNESS T = 12 in
ALLOW SOIL PRESSURE Qa = 3.5 ksf
FOOTING WIDTH B = 2 ft
FOOTING LENGTH L = 2 ft
BOTTOM REINFORCING # 4
THE PAD DESIGN IS ADEQUATE.
ANALYSIS
DESIGN LOADS (IBC 1605.2 & ACI 318 5.3)
CASE 1: DL + LL P = 5 kips 1.2 DL + 1.6 LL Pu = 7 kips
CASE 2: P = 5 kips 1.2 DL + LL + 1.0 W Pu = 5 kips
CASE 3: P = 5 kips 0.9 DL+ 1.0 W Pu = 1 kips
CHECK SOIL BEARING CAPACITY (ACI 318 13.3.1.1)
CASE 1 CASE 2 CASE 3
1.31 ksf, 1.31 ksf, 1.31 ksf q MAX < k Q a , [Satisfactory] where k = 1 for gravity loads, 4/3 for lateral loads.
DESIGN FOR FLEXURE (ACI 318 13.2.7, 21, & 22)
LONGITUDINAL TRANSVERSE
d 8.75 8.50 b 24 24 q u,max 1.87 1.87
Mu 1.05 1.05 ρ 0.000 0.000 ρmin 0.000 0.000
As 0.04 0.04
ReqD 1 # 4 1 # 4
Max. Spacing 18 in o.c. 18 in o.c.
USE 3 # 4 @ 9 in o.c. 3 # 4 @ 9 in o.c.
ρmax 0.013 0.013
Check ρprod < ρmax [Satisfactory] [Satisfactory]
DL + LL +0.6( 1.3) W
DL + LL + 0.6(0.65) W
Porch FootingPad Footing Design Based on ACI 318-19
(0.15 )SMAX S
P Tq q w
BL
'2
0.85 1 1
0.383
Muf c b fd c f y ρ
0.85
MAX
f c u f u ty β ε ρ ε ε
0.0018 , MIN
T
MIN
d ρρ
CHECK FLEXURE SHEAR (ACI 318 13.2.7.2 & 22.5)
LONGITUDINAL TRANSVERSE
Vu 0.08 0.16 φ 0.75 0.75 φVn 15.8 15.3
Check Vu < φVn [Satisfactory] [Satisfactory]
CHECK PUNCHING SHEAR (ACI 318 13.2.7.2, 22.6.4.1, 22.6.4.3, & 8.4.2.3)
= 75.68 kips where φ = 0.75 (ACI 318 21.2) βc = ratio of long side to short side of concentrated load = 1.00 b0 = c1 + c2 + b1 + b2 + 4d = 58.5 in
Ap = b0 d = 504.6 in y = MIN(2 , 4 / βc , 40 d / b0) = 2.0
4.6928 kips < φ V n [Satisfactory]
2 y fV Apn cφ φ= +
1 1 2 21 1,max
2 2 b c b c d dV Puu
BL
2 bd fV n cφ φ=
Subject Date
P: Dead Load = 83 plf H: 12 ft.
Snow Load = 198 plf L: 6 ft.
V: Wind
Roof Load: 0 psf
Pitch: 14 Degrees
Load Area: 0.00 Sq.Ft.
Wall Load: 16 psf
Load Area: 90.00 Sq.Ft.
Seismic
Total: 4570 Lbs
16.7
8.4
WL = 1458 Lbs
EL = 3428 Lbs
USE
PSE Consulting Engineers Inc.
Romtec 224-032
Billy Cordova Memorial Park Restroom Designed by 4/22/2024
Analysis Checked by
Masonry Shearwalls
6" CMU W/ #4 Vert Bars @ 32" O.C. & #4 Horz Bars @ 32" O.C.
Building Length:
Trib. Width
# of Wall Panels:
JOB NO. : DATE : REVIEW BY :
INPUT DATA & DESIGN SUMMARY
SPECIAL INSPECTION ( 0=NO, 1=YES ) 1 Yes
(This option only for local jurisdiction amendments to the code, not part of TMS.)
TYPE OF MASONRY ( 1=CMU, 2=BRICK ) 1 CMU
MASONRY STRENGTH fm' = 1.5 ksi
REBAR YIELD STRESS fy = 60 ksi
ALLOWABLE 30% INCREASING ? (Yes or No, IBC 1605.2) No
SEISMIC PERFORMANCE CATEGORY C Seismic C
( C,D,E, 0=WIND, 5=GRAVITY)
MASONRY LAID IN RUNNING BOND ? (TMS 402 7.3.2.6) Yes
SERVICE AXIAL LOAD P = 1.69 kips, at middle of Lw
SERVICE SHEAR LOAD Vx = 3.43 kips, (in-plane force)
SERVICE MOMENT LOAD Mx = 27.44 ft-kips, (top flange, bf1, compression)
My = 0.2 ft-kips, (out-of-plane, left b11 & b21, compression)
EFFECTIVE HEIGHT OF WALL hw = 12 ft
LENGTH OF SHEAR WALL Lw = 6 ft, (within vertical control joints)
THE WALL DESIGN IS ADEQUATE.