This is a comprehensive set of electrical system construction specifications for the Whiteriver Hospital Construction project prepared by SmithGroup on behalf of the Indian Health Service (IHS). The 407,000 square-foot hospital facility is located on the Fort Apache Indian Reservation in Whiteriver, Arizona, and will serve a projected primary service area population of 19,088 by 2030. The specifications encompass Division 26 (Electrical) through Division 46 (Water and Wastewater Equipment) and detail all electrical infrastructure, power distribution, lighting controls, communications systems, grounding and bonding, cable trays, raceways, surge protection, electrical monitoring and control systems, and wastewater treatment plant (WWTP) electrical requirements.
The construction specifications require the contractor to furnish all materials, equipment, and labor necessary to install complete operational electrical systems including main and backup power distribution, emergency lighting controls, fire suppression and alarm systems, HVAC controls, data communications networks, security and access control systems, medical gas systems, and sophisticated electrical power monitoring and control (SCADA) systems. Key technical requirements include compliance with the National Electrical Code (NFPA 70), IEEE standards, and ASHRAE guidelines; installation of multifunction energy meters and power monitoring equipment with web-based monitoring capabilities; network lighting controls with daylight harvesting and occupancy sensors; grounding systems designed for the 6,600-foot altitude location with specific resistance requirements; cable specifications for both power and communications with extensive identification and labeling protocols; and comprehensive testing, commissioning, and operator training. The contractor must demonstrate system integration across multiple disciplines, coordinate with HVAC building automation systems, and provide maintenance support including 12 months of full maintenance service beginning at substantial completion, plus two years of software technical support and upgrades. All electrical work must maintain compliance with LEED certification standards and include detailed documentation of as-built conditions, testing reports, relay settings, protective device coordination studies, arc-flash hazard analyses, and complete operation and maintenance manuals.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Prepared for: INDIAN HEALTH SERVICE
100% CONSTRUCTION DOCUMENTS
Project No: 14904.000
5 MARCH 2026
VOLUME 4
Prepared by:
SMITHGROUP 14904.000 INDIAN HEALTH SERVICE
WHITERIVER HOSPITAL
FINAL CONSTRUCTION DOCUMENTS
23 JANUARY 2026
SEALS PAGE 000107 - 1
DOCUMENT 000107 - SEALS PAGE
Include on this Seals Page Document the seals of the design professionals of record required by statute to affix their seal to the documents. Where required, include a description of the Specification Sections prepared under the direction of each design professions *EDIT FOR YOUR PROJECT-USE DIVISION AND/OR SECTION NUMBERS*.
If such listing is required, you may alternatively use the MasterSpec seals page instead of this SmithGroup seals page.
Architect SmithGroup, Inc.
Phoenix, AZ Matthew Hess, AIA, NCARB
Responsible for Divisions 01-49 Sections except where indicated as prepared by other design professionals of record.
Structural Engineer PK Associates and Pimara Paul Koehler Scottsdale, Arizona Christa Chau, PE, SE Responsible for: Division 03, Sections 030000 and 032000; Division 04, Section 042000; Division 05, Sections 051200 and 053100; and Division 31, Section 316329
Civil Engineer Dibble & Associates Consulting Engineers, Inc.
Phoenix, Arizona
Christina Shannon Mauck, PE
Responsible for: Division 01, Section 015713, Division 02, Section 024100, Division 09, Section 099713, Division 31, Sections 312213, 312300, 312316.16, 312323.13, 312333, 312500, Division 32, Sections 321123, 321216, 321313, 321315, Division 33, Sections 331000, 331623, 333000, 333213, 333723, 334213
Fire Protection Engineer
Phoenix, AZ Andrew Ochsankehl, PE Responsible for: Division 13, Section 131200*; Division 21, Sections 211300, 213000, 210533; Division 27, Section 273226; Division 28, Section 283111
*Fire Protection Related Requirements Only
SEALS PAGE 000107 - 2
Electrical Engineer
Phoenix, AZ Daniel L. Peterson, PE Responsible for: Division 26, except for those Sections labeled with “WWTP”
Communications (AV, IT, Security) Designer
Washington, DC David K. Glenn, RCDD Responsible for: Division 27, Sections 270413, 270526, 270528, 270536, 270544, 270553, 271100, 271300, 271500, 272100, 273226, 274116, 275113, 275119, 275123, 275223, 275313, 275316 and 275319; and Division 28, Sections 280413, 280513, 280526, 280528, 281300, 281600, 282300 and 285000
Landscape Architect
Phoenix, AZ Richard P. Jones, PLA Responsible for: Division 32, Sections 321316, 321373, 321716, 321723, 323113, 323119, 323213, 324020, 328000, 329100, 329220, 329300
Civil Engineer Dibble & Associates Consulting Engineers, Inc.
Phoenix, Arizona
Ian B. Mowry, PE
Responsible for: Division 31, Sections 312213, 312300, 312316, 312323, 312500; Division 32, Sections 321123, 321216, 321315; Division 33, Section 4213; Division 34, Sections 340114, 347113, 347116
SEALS PAGE 000107 - 3
Structural Engineer Morrison-Maierle Phoenix, Arizona
Michael Brennan, PE Responsible for structural specifications for the WWTPs:
Division 03: 033000; Division 05: 051400, 055000, 055200, 055300; Division 13: 133419; Division 41:
413313, 413313.01
Electrical Engineer
Phoenix, Arizona Michael Brandt, PE
Responsible for electrical specifications for the WWTPs:
Division 26: 260400, 260519, 260523, 260526, 260529, 260533, 260536, 260543, 260544, 260548.16, 260553, 260573.13, 260573.16, 260573.19, 260913, 260923, 262213, 262413, 262416, 262419, 262713, 262726, 262813, 262816, 262923, 263213, 263353, 263600, 264313, 265100, 265600
Plumbing Engineer
Phoenix, Arizona Jody Waverek, PE
Responsible for plumbing specifications for the WWTPs:
Division 22: 220517, 220518, 220519, 220523.12, 220523.14, 220529, 220548, 220553, 220719, 221116, 221119, 221123, 221123.13, 221316, 221429, 223300, 224213.13, 224213.16, 224216.13, 224216.16, 224223, 224500
Mechanical Engineer
Phoenix, Arizona Jody Waverek, PE Responsible for mechanical specifications for the WWTPs: Division 23: 230513, 230529, 230548, 230553, 230593, 230713, 230716, 230900, 233113, 233300, 233423, 233713, 237416.11, 238126, 238239
SEALS PAGE 000107 - 4
Environmental Engineer
Phoenix, Arizona Ulrike Lashley, PE
Responsible for the following specifications for the WWTPs: Division 09: 099600; Division 10: 101400.01, 104352; Division 40: 400205, 400510, 400510.03, 400510.04, 400510.09, 400510.12, 400510.13, 400510.30, 400553, 400555, 400557, 406110, 406115, 406116, 406120, 406120.01, 406120.02, 406120.03, 406120.04, 406121, 406124, 406127, 406128, 406140, 406160, 406171, 406176, 406177, 406180, 406181, 406182, 406191; Division 41: 413313.17; Division 43:
431030, 431111, 432256, 432321, 432331, 432331.01, 432358, 433230, 433269, 434010; Division 46: 460754, 460754.01, 460754.02, 460754.03, 460754.04, 460754.05, 460754.06, 460754.07, 460754.08, 460754.09, 460754.10, 461155, 461155.01, 461155.02, 461155.03, 461155.04, 462113, 462113.01, 462113.02, 462113.03, 465035, 465035.01, 465035.02, 465131, 465131.01, 465131.02
Hazardous Building Materials
Mabbett & Associates, Inc.
Stoneham, Massachusetts
Michael Delaney, Asbestos Designer
Responsible for: 028200, 028313
END OF DOCUMENT 000107
TABLE OF CONTENTS TOC - 1
TABLE OF CONTENTS
Volume 1
DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS
SECTION 001000 - SOLICITATION, CONTRACT LINE-ITEM NUMBER (CLIN) SCHEDULE
SECTION 002000 - INSTRUCTIONS FOR PROCUREMENT
SECTION 002100 - INSTRUCTIONS
SECTION 002113 - INSTRUCTIONS TO BIDDERS
SECTION 002116 - INSTRUCTIONS TO PROPOSERS
SECTION 002200 - SUPPLEMENTARY INSTRUCTIONS
SECTION 002216 - SUPPLEMENTARY INSTRUCTIONS TO PROPOSERS
SECTION 003000 - AVAILABLE INFORMATION
SECTION 004000 - PROCUREMENT FORMS AND SUPPLEMENTS
SECTION 004300 - BID BOND FORM
SECTION 004373 - PROPOSED CONSTRUCTION SCHEDULE FORM
SECTION 004500 - REPRESENTATIONS AND CERTIFICATIONS
SECTION 005000 - CONTRACTING FORMS AND SUPPLEMENTS
SECTION 005100 - NOTICE OF AWARD
SECTION 005200 - AGREEMENT FORMS
SECTION 006000 - PROJECT FORMS
SECTION 006100 - BOND FORMS
SECTION 006200 - CERTIFICATES
SECTION 007000 - CONDITIONS OF THE CONTRACT
SECTION 007100 - CONTRACTING DEFINITIONS
SECTION 007200 - GENERAL CONDITIONS
SECTION 007300 - SUPPLEMENTAL CONDITIONS
DIVISION 01 - GENERAL REQUIREMENTS
SECTION 011000 - SUMMARY
SECTION 012300 - OPTIONS
SECTION 012500 - SUBSTITUTION PROCEDURES
SECTION 012510 - SUBSTITUTION REQUEST FORM
SECTION 012600 - CONTRACT MODIFICATION PROCEDURES
SECTION 012614 - REQUESTS FOR INFORMATION
SECTION 012900 - PAYMENT PROCEDURES
SECTION 012973 - SCHEDULE OF VALUES
SECTION 013100 - PROJECT MANAGEMENT AND COORDINATION
TABLE OF CONTENTS TOC - 2
SECTION 013200 - CONSTRUCTION PROGRESS DOCUMENTATION
SECTION 013233 - PHOTOGRAPHIC DOCUMENTATION
SECTION 013300 - SUBMITTAL PROCEDURES
SECTION 013330 - SUBMITTAL COMPLIANCE FORM
SECTION 013526 - GOVERNMENT SAFETY REQUIREMENTS
SECTION 013573 - DELEGATED DESIGN REQUIREMENTS AND PROCEDURES
SECTION 014200 - REFERENCES
SECTION 014339 - EXTERIOR WALLS MOCKUPS
SECTION 014500.00 10 - QUALITY CONTROL
SECTION 015000 - TEMPORARY FACILITIES AND CONTROLS
SECTION 015713 - TEMPORARY EROSION AND SEDIMENT CONTROL
SECTION 015731 - INDOOR AIR QUALITY (IAQ) MANAGEMENT
SECTION 016000 - PRODUCT REQUIREMENTS
SECTION 017300 - EXECUTION
SECTION 017419 - CONSTRUCTION WASTE MANAGEMENT AND DISPOSAL
SECTION 017700 - CLOSEOUT PROCEDURES
SECTION 017823 - OPERATION AND MAINTENANCE DATA
SECTION 017839 - PROJECT RECORD DOCUMENTS
SECTION 017900 - DEMONSTRATION AND TRAINING
SECTION 018113 - SUSTAINABLE DESIGN REQUIREMENTS
SECTION 018900 - SITE CONSTRUCTION PERFORMANCE REQUIREMENTS
SECTION 019113 - GENERAL COMMISSIONING REQUIREMENTS
SECTION 019119 - BUILDING ENCLOSURE COMMISSIONING
SECTION 019200 - FACILITY OPERATION, MAINTENANCE, AND TROUBLESHOOTING
MOBILE GRAPHICAL INFORMATION MANAGEMENT PLATFORM
DIVISION 02 - EXISTING CONDITIONS
SECTION 024100 - SITE DEMOLITION
SECTION 028200 - ASBESTOS ABATEMENT
SECTION 028313 - LEAD HAZARD CONTROL
TABLE OF CONTENTS TOC - 3
DIVISION 03 – CONCRETE
SECTION 032000 - CONCRETE REINFORCEMENT
SECTION 033000 - CAST-IN-PLACE CONCRETE
SECTION 033000 - CAST-IN-PLACE CONCRETE - WWTP
SECTION 033543 - POLISHED CONCRETE FINISHING
SECTION 035400 - CAST UNERLAYMENT
DIVISION 04 – MASONRY
SECTION 042000 - UNIT MASONRY ASSEMBLIES
SECTION 042500 - TERRA COTTA RAINSCREEN SYSTEM
SECTION 042505 - STABILIZED RAMMED EARTH
SECTION 042613 - MASONRY VENEER
DIVISION 05 – METALS
SECTION 051200 - STRUCTURAL STEEL FRAMING
SECTION 051400 - STRUCTURAL ALUMINUM
SECTION 053100 - STEEL DECKING
SECTION 054000 - COLD FORMED METAL FRAMING
SECTION 054300 - SLOTTED CHANNEL FRAMING
SECTION 055000 - METAL FABRICATIONS
SECTION 055000 - METAL FABRICATIONS-WWTP
SECTION 055113 - METAL PAN STAIRS
SECTION 055119 - METAL GRATING STAIRS
SECTION 055200 - HANDRAILS AND RAILIINGS
SECTION 055300 - FABRICATED GRATING
DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES
SECTION 061053 - MISCELLANEOUS ROUGH CARPENTRY
SECTION 061600 - SHEATHING
SECTION 064116 - PLASTIC-LAMINATE-CLAD ARCHITECTURAL CABINETS
SECTION 066119 - QUARTZ SURFACING FABRICATIONS
SECTION 066400 - PLASTIC PANELING
SECTION 068300 - COMPOSITE PANELING
TABLE OF CONTENTS TOC - 4
DIVISION 07 - THERMAL AND MOISTURE PROTECTION
SECTION 071113 - BITUMINOUS DAMPPROOFING
SECTION 071326 - SELF-ADHERING SHEET WATERPROOFING
SECTION 071413 - HOT FLUID-APPLIED RUBBERIZED ASPHALT WATERPROOFING
SECTION 071900 - WATER REPELLENTS
SECTION 072100 - THERMAL INSULATION
SECTION 072600 - VAPOR RETARDERS
SECTION 072726 - FLUID-APPLIED MEMBRANE AIR BARRIERS
SECTION 074213.13 - FORMED METAL WALL PANELS
SECTION 074213.23 - METAL COMPOSITE MATERIAL WALL PANELS
SECTION 074213.33 - FORMED METAL SCREENWALL PANELS
SECTION 074293 - SOFFIT PANELS
SECTION 075419 - POLYVINYL-CHLORIDE (PVC) ROOFING
SECTION 076200 - SHEET METAL FLASHING AND TRIM
SECTION 077129 - MANUFACTURED ROOF EXPANSION JOINTS
SECTION 077200 - ROOF ACCESSORIES
SECTION 077273 - VEGETATED ROOF SYSTEMS
SECTION 078100 - APPLIED FIREPROOFING
SECTION 078123 - INTUMESCENT FIREPROOFING
SECTION 078413 - PENETRATION FIRESTOPPING
SECTION 078443 - JOINT FIRESTOPPING
SECTION 079200 - JOINT SEALANTS
SECTION 079219 - ACOUSTICAL JOINT SEALANTS
SECTION 079513.13 - INTERIOR EXPANSION JOINT COVER ASSEMBLIES
SECTION 079513.16 - EXTERIOR EXPANSION JOINT COVER ASSEMBLIES
Volume 2
DIVISION 08 – OPENINGS
SECTION 081113 - HOLLOW METAL DOORS AND FRAMES
SECTION 081216 - ALUMINUM FRAMES
SECTION 081416 - FLUSH WOOD DOORS
SECTION 081473 - SLIDING WOOD DOORS
SECTION 083113 - ACCESS DOORS AND FRAMES
SECTION 083313 - COILING COUNTER DOORS
SECTION 083323 - OVERHEAD COILING DOORS
SECTION 083343 - OVERHEAD COILING SMOKE CURTAINS
TABLE OF CONTENTS TOC - 5
SECTION 083516 - SIDE-FOLDING SECURITY GRILLES
SECTION 084123 - INTERIOR ALUMINUM-FRAMES ENTRANCES AND STOREFRONTS
SECTION 084126 - ALL-GLASS ENTRANCES
SECTION 084229.23 - SLIDING AUTOMATIC ENTRANCES
SECTION 084243 - INTENSIVE CARE UNIT/CRITICAL CARE UNIT (ICU/CCU)
ENTRANCES
SECTION 084313 - ALUMINUM-FRAMED STOREFRONTS
SECTION 084413 - GLAZED ALUMINUM CURTAIN WALLS
SECTION 085619 - PASS WINDOWS
SECTION 086200 - UNIT SKYLIGHTS
SECTION 087100 - DOOR HARDWARE
SECTION 088000 - GLAZING
SECTION 088113 - DECORATIVE GLASS GLAZING
SECTION 088300 - MIRRORS
SECTION 088813 - FIRE-RATED GLAZING
DIVISION 09 – FINISHES
SECTION 090561.13 - MOISTURE VAPOR EMISSION CONTROL
SECTION 092116.23 - GYPSUM BOARD SHAFT WALL ASSEMBLIES
SECTION 092216 - NON-STRUCTURAL METAL FRAMING
SECTION 092900 - GYPSUM BOARD
SECTION 093013 - CERAMIC TILING
SECTION 095113 - ACOUSTICAL PANEL CEILINGS
SECTION 095423 - LINEAR METAL CEILINGS
SECTION 095446 - ACOUSTICAL BAFFLE SYSTEM
SECTION 096513 - RESILIENT BASE AND ACCESSORIES
SECTION 096516 - RESILIENT SHEET FLOORING
SECTION 096519 - RESILIENT TILE FLOORING
SECTION 096566 - RESILIENT ATHLETIC FLOORING
SECTION 096623 - RESINOUS MATRIX TERRAZZO FLOORING
SECTION 096723 - RESINOUS FLOORING
SECTION 096813 - TILE CARPETING
SECTION 097200 - WALL COVERINGS
SECTION 097723 - FABRIC-WRAPPED PANELS
SECTION 098316 - ACOUSTICAL CEILING INSULATION
SECTION 098433 - SOUND ABSORBING WALL UNITS
SECTION 099113 - EXTERIOR PAINTING
TABLE OF CONTENTS TOC - 6
SECTION 099123 - INTERIOR PAINTING
SECTION 099600 - HIGH-PERFORMANCE COATINGS
SECTION 099600 - HIGH-PERFORMANCE COATINGS - WWTP
SECTION 099713 - COATINGS FOR WELDED STEEL WATER STORAGE TANK
DIVISION 10 – SPECIALTIES
SECTION 101100 - VISUAL DISPLAY UNITS
SECTION 101400 - SIGNAGE
SECTION 101400.01 - IDENTIFYING DEVICES
SECTION 102113.14 - STAINLESS-STEEL TOILET COMPARTMENTS
SECTION 102123 - CUBICLE CURTAINS AND TRACK
SECTION 102239 - FOLDING PANEL PARTITIONS
SECTION 102600 - WALL AND DOOR PROTECTION
SECTION 102800 - TOILET, BATH, AND LAUNDRY ACCESSORIES
SECTION 103100 - MANUFACTURED FIREPLACES
SECTION 104352 - FIRST AID AND SAFETY EQUIPMENT
SECTION 104413 - FIRE PROTECTION CABINETS
SECTION 104416 - FIRE EXTINGUISHERS
SECTION 105113 - METAL LOCKERS
SECTION 107516 - GROUND-SET FLAGPOLES
SECTION 108219 - EXTERIOR SOUND PANELS
DIVISION 11 – EQUIPMENT
SECTION 110800 - EQUIPMENT COMMISSIONING
SECTION 111313 - LOADING DOCK BUMPERS
SECTION 111316 - LOADING DOCK SEALS
SECTION 111319 - STATIONARY LOADING DOCK EQUIPMENT
SECTION 111326 - LOADING DOCK LIGHTS
SECTION 114000 - FOODSERVICE EQUIPMENT
SECTION 117000 - HEALTHCARE EQUIPMENT
SECTION 117100 - MEDICAL STERILIZING EQUIPMENT
SECTION 117311 - PATIENT LIFTS
SECTION 118129 - FACILITY FALL PROTECTION
SECTION 118201 - HYDRAULIC CART TIPPER
SECTION 118226 - FACILITY WASTE COMPACTORS
TABLE OF CONTENTS TOC - 7
DIVISION 12 – FURNISHINGS
SECTION 122413 - ROLLER WINDOW SHADES
SECTION 123553 - GENERAL REQUIREMENTS FOR LABORATORY CASEWORK AND
FUME HOODS
SECTION 123553.03 - ADAPTABLE LABORATORY CASEWORK SYSTEMS
SECTION 123553.19 - WOOD LABORATORY CASEWORK
SECTION 123570 - HEALTHCARE CASEWORK
SECTION 123623.13 - PLASTIC-LAMINATE-CLAD COUNTERTOPS
SECTION 123661.16 - SOLID SURFACING COUNTERTOPS
SECTION 123661.19 - QUARTZ AGGLOMERATE COUNTERTOPS
SECTION 124816 - ENTRANCE FLOOR GRILLES
SECTION 126100 - FIXED UPHOLSTERED SEATING
DIVISION 13 - SPECIAL CONSTRUCTION
SECTION 131200 - ALUMINUM ROOFTOP HELISTOPS
SECTION 131224 - EXTERIOR WATER FEATURE
SECTION 133419 - METAL BUILDING SYSTEMS
SECTION 134900 - RADIATION PROTECTION
SECTION 134920 - RFI/EMI SHIELDING
DIVISION 14 - CONVEYING EQUIPMENT
SECTION 142100 - ELECTRIC TRACTION ELEVATORS
SECTION 149200 - PNEUMATIC TUBE SYSTEM – 6 INCH
Volume 3
DIVISION 21 - FIRE SUPPRESSION
SECTION 210533 - HEAT TRACING FOR FIRE-SUPPRESSION PIPING
SECTION 210800 - FIRE SUPPRESSION SYSTEMS COMMISSIONING
SECTION 211300 - FIRE SPRINKLER AND STANDPIPE SYSTEMS
SECTION 213000 - FIRE PUMPS, PUMP CONTROLLERS, AND
OTHER APPURTENANCES
TABLE OF CONTENTS TOC - 8
DIVISION 22 – PLUMBING
SECTION 220513 - COMMON MOTOR REQUIREMENTS FOR PLUMBING EQUIPMENT
SECTION 220516 - EXPANSION FITTINGS AND LOOPS FOR PLUMBING PIPING
SECTION 220517 - SLEEVES AND SLEEVE SEALS FOR PLUMBING PIPING
SECTION 220517 - SLEEVES AND SLEEVE SEALS PLUMBING PIPING-WWTP
SECTION 220518 - ESCUTCHEONS FOR PLUMBING PIPING
SECTION 220518 - ESCUTCHEONS FOR PLUMBING PIPING - WWTP
SECTION 220519 - METERS AND GAGES FOR PLUMBING PIPING
SECTION 220519 - METERS AND GAGES FOR PLUMBING PIPING - WWTP
SECTION 220523.12 - BALL VALVES FOR PLUMBING PIPING
SECTION 220523.12 - BALL VALVES FOR PLUMBING PIPING - WWTP
SECTION 220523.13 - BUTTERFLY VALVES FOR PLUMBING PIPING
SECTION 220523.14 - CHECK VALVES FOR PLUMBING PIPING
SECTION 220523.14 - CHECK VALVES FOR PLUMBING PIPING - WWTP
SECTION 220523.15 - GATE VALVES FOR PLUMBING PIPING
SECTION 220529 - HANGERS AND SUPPORTS FOR PLUMBING PIPING AND
EQUIPMENT
SECTION 220529 - HANGERS AND SUPPORTS FOR PLUMBING PIPING AND
EQUIPMENT - WWTP
SECTION 220533 - HEAT TRACING FOR PLUMBING PIPING
SECTION 220548 - VIBRATION AND SEISMIC CONTROLS FOR PLUMBING PIPING AND
EQUIPMENT
SECTION 220548 - VIBRATION AND SEISMIC CONTROLS FOR PLUMBING PIPING AND
EQUIPMENT - WWTP
SECTION 220553 - IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT–
SECTION 220553 - IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT - WWTP
SECTION 220716 - PLUMBING EQUIPMENT INSULATION
SECTION 220719 - PLUMBING PIPING INSULATION
SECTION 220719 - PLUMBING PIPING INSULATION - WWTP
SECTION 220800 - PLUMBING SYSTEMS COMMISSIONING
SECTION 221113 - FACILITY WATER DISTRIBUTION PIPING
SECTION 221116 - DOMESTIC WATER PIPING
SECTION 221116 - DOMESTIC WATER PIPING - WWTP
SECTION 221117 - RECLAIMED-WATER PIPING
SECTION 221119 - DOMESTIC WATER PIPING SPECIALTIES
SECTION 221119 - DOMESTIC WATER PIPING SPECIALTIES - WWTP
SECTION 221123 - DOMESTIC WATER PUMPS
SECTION 221123 - DOMESTIC WATER PUMPS - WWTP
SECTION 221123.13 - DOMESTIC-WATER PACKAGED BOOSTER PUMPS
TABLE OF CONTENTS TOC - 9
SECTION 221123.13 - DOMESTIC-WATER PACKAGED BOOSTER PUMPS - WWTP
SECTION 221316 - SANITARY WASTE AND VENT PIPING
SECTION 221316 - SANITARY WASTE AND VENT PIPING - WWTP
SECTION 221323 - SANITARY WASTE INTERCEPTORS
SECTION 221413 - FACILITY STORM DRAINAGE PIPING
SECTION 221423 - STORM DRAINAGE PIPING SPECIALTIES
SECTION 221429 - SUMP PUMPS
SECTION 221429 - SUMP PUMPS - WWTP
SECTION 223100 - DOMESTIC WATER SOFTENERS
SECTION 223200 - DOMESTIC WATER FILTRATION EQUIPMENT
SECTION 223300 - ELECTRIC, DOMESTIC-WATER HEATERS
SECTION 223300 - ELECTRIC, DOMESTIC-WATER HEATERS - WWTP
SECTION 224213.13 - COMMERCIAL WATER CLOSETS
SECTION 224213.13 - COMMERCIAL WATER CLOSETS - WWTP
SECTION 224213.16 - COMMERCIAL URINALS
SECTION 224213.16 - COMMERCIAL URINALS - WWTP
SECTION 224216.13 - COMMERCIAL LAVATORIES
SECTION 224216.13 - COMMERCIAL LAVATORIES - WWTP
SECTION 224216.16 - COMMERCIAL SINKS
SECTION 224216.16 - COMMERCIAL SINKS - WWTP
SECTION 224223 - COMMERCIAL SHOWER
SECTION 224223 - COMMERCIAL SHOWER - WWTP
SECTION 224300 - HEALTHCARE PLUMBING FIXTURES
SECTION 224500 - EMERGENCY PLUMBING FIXTURES
SECTION 224500 - EMERGENCY PLUMBING FIXTURES - WWTP
SECTION 224700 - DRINKING FOUNTAINS AND WATER COOLERS
SECTION 226113 - COMPRESSED-AIR PIPING FOR LABORATORY AND HEALTHCARE
FACILITIES
SECTION 226119 - COMPRESSED-AIR EQUIPMENT FOR LABORATORY AND
HEALTHCARE FACILITIES
SECTION 226213 - VACUUM PIPING FOR LABORATORY AND HEALTHCARE
FACILITIES
SECTION 226219 - VACUUM EQUIPMENT FOR LABORATORY AND HEALTHCARE
FACILITIES
SECTION 226313 - GAS PIPING FOR LABORATORY AND HEALTHCARE FACILITIES
TABLE OF CONTENTS TOC - 10
SECTION 226400 - MEDICAL GAS ALARMS
SECTION 226713 - PROCESSED WATER PIPING FOR LABORATORY AND
HEALTHCARE FACILITIES
SECTION 226719 - PROCESSED WATER EQUIPMENT FOR LABORATORY AND
HEALTHCARE FACILITIES
DIVISION 23 - HEATING, VENTILATING, AND AIR-CONDITIONING (HVAC)
SECTION 230130.51 - HVAC AIR-DISTRIBUTION SYSTEM CLEANING
SECTION 230513 - COMMON MOTOR REQUIREMENTS FOR HVAC AND PLUMBING
EQUIPMENT
SECTION 230513 - COMMON MOTOR REQUIREMENTS FOR HVAC AND PLUMBING
EQUIPMENT - WWTP
SECTION 230516 - EXPANSION FITTINGS AND LOOPS FOR HVAC PIPING
SECTION 230517 - SLEEVES AND SLEEVE SEALS FOR HVAC AND PLUMBING PIPING
SECTION 230518 - ESCUTCHEONS FOR HVAC PIPING
SECTION 230519 - METERS AND GAGES FOR HVAC PIPING
SECTION 230523 - GENERAL-DUTY VALVES FOR HVAC PIPING
SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT
SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT -
WWTP
SECTION 230548 - VIBRATION AND SEISMIC CONTROLS FOR HVAC
SECTION 230548 - VIBRATION AND SEISMIC CONTROLS FOR HVAC - WWTP
SECTION 230553 - IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT
SECTION 230553 - IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT - WWTP
SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC
SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC - WWTP
SECTION 230713 - DUCT INSULATION
SECTION 230713 - DUCT INSULATION - WWTP
SECTION 230716 - HVAC EQUIPMENT INSULATION
SECTION 230716 - HVAC EQUIPMENT INSULATION - WWTP
SECTION 230719 - HVAC PIPING INSULATION
SECTION 230800 - HVAC SYSTEMS COMMISSIONING
SECTION 230900 - INSTRUMENTATION AND CONTROL FOR HVAC
SECTION 231113 - FACILITY FUEL-OIL PIPING
SECTION 231126 - FACILITY LIQUEFIED-PETROLEUM GAS PIPING
SECTION 232113 - HYDRONIC PIPING
SECTION 232116 - HYDRONIC PIPING SPECIALTIES
SECTION 232123 - HYDRONIC PUMPS
SECTION 2323000 - REFRIGERANT PIPING
TABLE OF CONTENTS TOC - 11
SECTION 232513 - WATER TREATMENT FOR CLOSED-LOOP HYDRONIC SYSTEMS
SECTION 233113 - METAL DUCTS
SECTION 233113 - METAL DUCTS - WWTP
SECTION 233300 - AIR DUCT ACCESSORIES
SECTION 233300 - AIR DUCT ACCESSORIES - WWTP
SECTION 233416 - CENTRIFUGAL HVAC FANS
SECTION 233423 - HVAC POWER VENTILATORS
SECTION 233423 - HVAC POWER VENTILATORS - WWTP
SECTION 233433 - AIR CURTAINS
SECTION 233600 - AIR TERMINAL UNITS
SECTION 233713 - DIFFUSERS, REGISTERS, AND GRILLES
SECTION 233713 - DIFFUSERS, REGISTERS, AND GRILLES - WWTP
SECTION 233723 - HVAC GRAVITY VENTILATORS
SECTION 234100 - PARTICULATE AIR FILTRATION
SECTION 234200 - GAS-PHASE AIR FILTRATION
SECTION 235213 - ELECTRIC BOILERS
SECTION 235700 - HEAT EXCHANGERS FOR HVAC
SECTION 236423.13 - AIR-COOLED, SCROLL WATER CHILLERS
SECTION 236423.14 - AIR SOURCE CHILLER-HEATER
SECTION 236426 - AIR-COOLED CENTRIFUGAL WATER CHILLERS
SECTION 237200 - AIR-TO-AIR ENERGY RECOVERY EQUIPMENT
SECTION 237323 - CUSTOM OUTDOOR CENTRAL-STATION AIR-HANDLING UNITS
SECTION 237416.11 - PACKAGED, SMALL-CAPACITY, ROOFTOP AIR-CONDITIONING
UNITS
SECTION 237416.11 - PACKAGED, SMALL-CAPACITY, ROOFTOP AIR-CONDITIONING
UNITS - WWTP
SECTION 238123.12 - LARGE CAPACITY (7 TONS (25 KW AND LARGER), COMPUTER-
ROOM AIR-CONDITIONERS
SECTION 238123.13 - COMPUTER-ROOM AIR-CONDITIONERS
SECTION 238126 - SPLIT-SYSTEM AIR-CONDITIONERS
SECTION 238126 - SPLIT-SYSTEM AIR-CONDITIONERS - WWTP
SECTION 238214 - CHILLED BEAMS
SECTION 238216 - AIR COILS
SECTION 238219 - FAN COIL UNITS
SECTION 238239 - UNIT HEATERS
SECTION 238239 - UNIT HEATERS - WWTP
SECTION 238316 - RADIANT-HEATING HYDRONIC PIPING
SECTION 238413 - HUMIDIFIERS
SECTION 238610 - BI-POLAR IONIZATION AIR PURIFICATION SYSTEM
TABLE OF CONTENTS TOC - 12
DIVISION 25 - INTEGRATED AUTOMATION
NOT APPLICABLE
Volume 4
DIVISION 26 – ELECTRICAL
SECTION 260400 - COMMON WORK RESULTS FOR ELECTRICAL
SECTION 260400 - COMMON WORK RESULTS FOR ELECTRICAL - WWTP
SECTION 260519 - LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES
SECTION 260519 - LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES
– WWTP
SECTION 260523 - CONTROL-VOLTAGE ELECTRICAL POWER CABLES
SECTION 260523 - CONTROL-VOLTAGE ELECTRICAL POWER CABLES - WWTP
SECTION 260526 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
SECTION 260526 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS - WWTP
SECTION 260529 - HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS
SECTION 260529 - HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS - WWTP
SECTION 260533 - RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS
SECTION 260533 - RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS - WWTP
SECTION 260536 - CABLE TRAYS FOR ELECTRICAL SYSTEMS - WWTP
SECTION 260539 - UNDERFLOOR RACEWAYS FOR ELECTRICAL SYSTEMS
SECTION 260543 - UNDERGROUND DUCTS AND RACEWAYS FOR ELECTRICAL
SYSTEMS - WWTP
SECTION 260543 - UNDERGROUND DUCTS AND RACEWAYS FOR ELECTRICAL
SYSTEMS-WWTP - M-M
SECTION 260544 - SLEEVES AND SLEEVE SEALS FOR ELECTRICAL RACEWAYS AND
CABLING
SECTION 260544 - SLEEVES AND SLEEVE SEALS FOR ELECTRICAL RACEWAYS AND
CABLING - WWTP
SECTION 260548.16 - SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS
SECTION 260548.16 - SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS - WWTP
SECTION 260553 - IDENTIFICATION FOR ELECTRICAL SYSTEMS
SECTION 260553 - IDENTIFICATION FOR ELECTRICAL SYSTEMS - WWTP
SECTION 260573.13 - OVERCURRENT PROTECTIVE DEVICE SHORT-CIRCUIT STUDY
SECTION 260573.13 - OVERCURRENT PROTECTIVE DEVICE SHORT-CIRCUIT STUDY -
WWTP
SECTION 260573.16 - OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY
TABLE OF CONTENTS TOC - 13
SECTION 260573.16 - OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY -
WWTP
SECTION 260573.19 - OVERCURRENT PROTECTIVE DEVICE ARC-FLASH STUDY
SECTION 260573.19 - OVERCURRENT PROTECTIVE DEVICE ARC-FLASH STUDY –
WWTP
SECTION 260800 - ELECTRICAL SYSTEMS COMMISSIONING
SECTION 260913 - ELECTRICAL POWER MONITORING AND CONTROL
SECTION 260913 - ELECTRICAL POWER MONITORING AND CONTROL - WWTP
SECTION 260923 - LIGHTING CONTROL DEVICES
SECTION 260923 - LIGHTING CONTROL DEVICES - WWTP
SECTION 260943 - NETWORK LIGHTING CONTROLS
SECTION 260943.23 - RELAY-BASED LIGHTING CONTROLS
SECTION 262213 - LOW-VOLTAGE DISTRIBUTION TRANSFORMERS
SECTION 262213 - LOW-VOLTAGE DISTRIBUTION TRANSFORMERS - WWTP
SECTION 262300 - LOW-VOLTAGE SWITCHGEAR
SECTION 262313 - PARALLELING LOW-VOLTAGE SWITCHGEAR
SECTION 262413 - SWITCHBOARDS
SECTION 262413 - SWITCHBOARDS - WWTP
SECTION 262416 - PANELBOARDS
SECTION 262416 - PANELBOARDS - WWTP
SECTION 262419 - MOTOR CONTROL CENTERS - WWTP
SECTION 262713 - ELECTRICITY METERING
SECTION 262713 - ELECTRICITY METERING - WWTP
SECTION 262726 - WIRING DEVICES
SECTION 262726 - WIRING DEVICES - WWTP
SECTION 262743 - ELECTRIC-VEHICLE SERVICE EQUIPMENT - AC LEVEL 1 AND
LEVEL 2
SECTION 262813 - FUSES
SECTION 262813 - FUSES - WWTP
SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS
SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS - WWTP
SECTION 262923 - VARIABLE-FREQUENCY MOTOR CONTROLLERS
SECTION 262923 - VARIABLE-FREQUENCY MOTOR CONTROLLERS - WWTP
SECTION 263100 - PHOTOVOLTAIC COLLECTORS
SECTION 263213 - ENGINE GENERATORS
SECTION 263213 - ENGINE GENERATORS - WWTP
SECTION 263233 - ROTARY UNINTERRUPTIBLE POWER UNITS
SECTION 263353 - STATIC UNINTERRUPTIBLE POWER SUPPLY
SECTION 263353 - STATIC UNINTERRUPTIBLE POWER SUPPLY - WWTP
TABLE OF CONTENTS TOC - 14
SECTION 263600 - TRANSFER SWITCHES
SECTION 263600 - TRANSFER SWITCHES - WWTP
SECTION 263650 - GENERATOR DOCKING STATIONS
SECTION 264113 - LIGHTNING PROTECTION FOR STRUCTURES
SECTION 264313 - SURGE PROTECTION FOR LOW-VOLTAGE ELECTRICAL POWER
CIRCUITS - WWTP
SECTION 264313 - SURGE PROTECTION FOR LOW-VOLTAGE ELECTRICAL POWER
CIRCUITS-WWTP
SECTION 265100 - INTERIOR LIGHTING
SECTION 265100 - INTERIOR LIGHTING - WWTP
SECTION 265600 - EXTERIOR LIGHTING
SECTION 265600 - EXTERIOR LIGHTING - WWTP
DIVISION 27 – COMMUNICATIONS
SECTION 270413 - COMMON SUBMITTAL REQUIREMENTS FOR COMMUNICATIONS
SECTION 270526 - GROUNDING AND BONDING FOR COMMUNICATIONS SYSTEMS
SECTION 270528 - PATHWAYS FOR COMMUNICATIONS SYSTEMS
SECTION 270536 - CABLE TRAYS FOR COMMUNICATIONS SYSTEMS
SECTION 270544 - SLEEVES AND SLEEVE SEALS FOR COMMUNICATIONS
PATHWAYS AND CABLING
SECTION 270553 - IDENTIFICATION FOR COMMUNICATIONS SYSTEMS
SECTION 270800 - COMMUNICATIONS SYTEMS COMMISSIONING
SECTION 271100 - COMMUNICATIONS EQUIPMENT ROOM FITTINGS
SECTION 271300 - COMMUNICATIONS BACKBONE CABLING
SECTION 271500 - COMMUNICATIONS HORIZONTAL CABLING
SECTION 272100 - DATA COMMUNICATIONS NETWORK EQUIPMENT
SECTION 273226 - TWO-WAY COMMUNICATIONS SYSTEM
SECTION 274116 - INTEGRATED AUDIOVISUAL SYSTEMS AND EQUIPMENT
SECTION 275113 - PAGING SYSTEMS
SECTION 275119 - SOUND MASKING SYSTEMS
SECTION 275123 - EMERGENCY HELP POINTS AND CALL BOXES
SECTION 275223 - NURSE CALL AND CODE BLUE SYSTEMS
SECTION 275313 - SYNCHRONIZED CLOCK SYSTEM
SECTION 275316 - PATIENT, INFANT, AND EQUIPMENT RFID TRACKING SYSTEMS
SECTION 275319 - DISTRIBUTED ANTENNA STSYTEMS
TABLE OF CONTENTS TOC - 15
DIVISION 28 - ELECTRONIC SAFETY AND SECURITY
SECTION 280413 - COMMON SUBMITTAL REQUIREMENTS FOR ELECTRONIC SAFETY
AND SECURITY
SECTION 280513 - CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND
SECURITY
SECTION 280526 - GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND
SECURITY
SECTION 280528 - PATHWAYS FOR ELECTRONIC SAFETY AND SECURITY
SECTION 280544 - SLEEVES AND SLEEVE SEALS FOR ELECTRONIC SAFETY AND
SECURITY PATHWAYS AND CABLING
SECTION 280800 - ELECTRONIC SAFETY AND SECURITY SYSTEMS COMMISSIONING
SECTION 281300 – ACCESS CONTROL
SECTION 281600 - INTRUSION DETECTION SYSTEM
SECTION 282300 - VIDEO SURVEILLANCE
SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM
SECTION 285000 - SECURITY CONTROL SYSTEM
Volume 5
DIVISION 31 – EARTHWORK
SECTION 312213 - ROUGH GRADING
SECTION 312300 - EXCAVATION AND FILL
SECTION 312316.16 - STRUCTURAL EXCAVATION FOR MINOR STRUCTURES
SECTION 312323.13 - BACKFILL
SECTION 312333 - TRENCHING AND BACKFILL
SECTION 312500 - EROSION AND SEDIMENTATION CONTROLS
SECTION 313116 - TERMITE CONTROL
SECTION 316329 - DRILLED CONCRETE PIERS AND SHAFTS
TABLE OF CONTENTS TOC - 16
DIVISION 32 - EXTERIOR IMPROVEMENTS
SECTION 321123 - AGGREGATE BASE COURSES
SECTION 321216 - ASPHALT PAVING
SECTION 321223 - IMPRINTED ASPHALT
SECTION 321313 - CONCRETE PAVING
SECTION 321315 - CONCRETE WALKS, CURBS AND GUTTERS
SECTION 321316 - DECORATIVE CONCRETE PAVING
SECTION 321373 - CONCRETE PAVING JOINT SEALANTS
SECTION 321716 - MANUFACTURED TRAFFIC-CALMING DEVICES
SECTION 321723 - PAVEMENT MARKINGS
SECTION 323113 - CHAIN LINK FENCES AND GATES
SECTION 323119 - DECORATIVE METAL FENCES AND GATES
SECTION 323213 - CAST-IN-PLACE CONCRETE RETAINING WALLS
SECTION 324020 - PIPE AND TUBE RAILINGS
SECTION 328000 - IRRIGATION SYSTEM
SECTION 329100 - SOIL PREPARATION (TOPSOIL)
SECTION 329220 - NATIVE SEEDING
SECTION 329300 - EXTERIOR PLANTINGS
DIVISION 33 - UTILITIES
SECTION 331000 - WATER UTILITIES
SECTION 331623 - WELDED STEEL WATER STORAGE TANK AND FOUNDATION
SECTION 333000 - SANITARY SEWERAGE UTILITIES
SECTION 333213 - PACKAGE LIFT STATION
SECTION 333723 - SLIDE GATE
SECTION 334213 - STORMWATER CULVERTS AND DRAINAGE FACILITIES
DIVISION 34 - TRANSPORTATION
SECTION 340114 - SIGNING AND MARKING
SECTION 344113 - TRAFFIC SIGNALS
SECTION 347100 - ADOT REQUIREMENTS
SECTION 347113 - VEHICLE BARRIERS
SECTION 347116 - IMPACT ATTENUATING DEVICES
TABLE OF CONTENTS TOC - 17
DIVISION 40 - PROCESS INTERCONNECTIONS
SECTION 400205 - PIPING SCHEDULE
SECTION 400510 - PIPING - GENERAL
SECTION 400510.03 - DPS - EPOXY LINED DUCTILE IRON PIPE AND FITTINGS
SECTION 400510.04 - DPS - MILL TYPE STEEL PIPE AND FITTINGS (GENRAL SERVICE)
SECTION 400510.09 - DPS STAINLESS STEEL PIPE AND FITTINGS
SECTION 400510.12 - DPS - POLYVINYL CHLORIDE (PVC) PIPE AND FITTINGS
SECTION 400510.13 - DPS - CHLORINATED POLYVINYL CHLORIDE (CPVC) PIPE
AND FITTINGS
SECTION 400510.30 - DPS HIGH DENSITY POLYETHYLENE (HDPE) PIPE
AND TUBING
SECTION 400533 - MANUAL VALVES
SECTION 400555 - SELF CONTAINED AUTOMATIC VALVES
SECTION 400557 - POWER OPERATED GATE AND VALVE ASSEMBLIES
SECTION 406110 - PROCESS INSTRUMENTATION AND CONTROLS SYSTEM (PICS)
GENERAL
SECTION 406115 - PICS SCOPE OF WORK
SECTION 406116 - PICS ENCLOSURES
SECTION 406120 - PROCESS CONTROL NARRATIVES (PCNs)
SECTION 406120.01- PCN-INFLUENT PUMP STATION
SECTION 406120.02 - PCN-EQ BASIN TRANSFER PUMP STATION
SECTION 406120.03 - PCN-AEORBIC SLUDGE DIGESTER
SECTION 406120.04 - PCN-EFFLUENT PUMPING SYSTEM
SECTION 406121 - PICS PROCESS TAPS AND PRIMARY ELEMENTS
SECTION 406124 - PICS INSTRUMENTATION CABLE
SECTION 406127 - PICS INDUSTRIAL ETHERNET NETWORK
SECTION 406128 - PICS MISCELLANEOUS EQUIPMENT
SECTION 406140 - PICS INSTRUMENTATION REQUIREMENTS
SECTION 406160 - PICS PLC I-O INDEX
SECTION 406171 - INSTRUMENT SPECIFICATIONS
SECTION 406176 - PLANT CONTROL SYSTEM (PCS) SOFTWARE REQUIREMENTS
SECTION 406177 - PLANT CONTROL SYSTEM (PCS) HARDWARE AND SOFTWARE
SECTION 406180 - PICS TESTING, CALIBRATION, AND INSTALLATION VERIFICATION
SECTION 406181 - PICS COMMISSIONING AND START-UP
SECTION 406182 - PICS PERSONNEL TRAINING
SECTION 406191- PICS SPARE PARTS
TABLE OF CONTENTS TOC - 18
DIVISION 41 - MATERIAL PROCESSING AND HANDLING EQUIPMENT
SECTION 412213.17 - DAVIT AND GANTRY CRANES
SECTION 413313 - OVERHEAD TRAVELING CRANES
SECTION 413313.01 - DETAIL SPECIFICATION - TREATMENT PLANT BRIDGE CRANE
DIVISION 43 - PROCESS GAS AND LIQUID HANDLING, PURIFICATION, AND STORAGE
EQUIPMENT
SECTION 431030 - SUBMERSIBLE NON-CLOG CENTIFUGAL PUMPS
SECTION 431111 - BLOWERS
SECTION 432256 - SUBMERSIBLE MIXERS
SECTION 432321 - RECLAIMED EFFLUENT PUMPING SYSTEMS
SECTION 432331 - NPW PUMPING SYSTEMS
SECTION 432331.01 - PCN NON-POTABLE WATER SYSTEM
SECTION 432332 - RECLAIMED WATER PUMPING SYSTEM
SECTION 432358 - POSITIVE DISPLACEMENT ROTARY LOBE PUMPS
SECTION 433230 - ODOR CONTROL BIOTRICKLING SYSTEM
SECTION 433269 - CHEMICAL FEED SKID – PERISTALTIC PUMPS
SECTION 434010 - CHEMICAL STORAGE AND CONTAINMENT
DIVISION 46 – WATER AND WASTEWATER EQUIPMENT
SECTION 460754 - MEMBRANE BIOREACTOR PACKAGE PLANT SYSTEM
SECTION 460754.01 - DES-SKID COMPONENTS
SECTION 460754.02 - DES-SUBMERSIBLE MIXERS
SECTION 460754.03 - DES-FLEXIBLE MEMBRANE DIFFUSERS
SECTION 460754.04 - DES-SUBMERSIBLE PUMPS
SECTION 460754.05 - DES SELF-PRIMING CENTRIFUGAL PUMPS
SECTION 460754.06 - DES-REGENERATIVE BLOWERS
SECTION 460754.07 - DES-PROCESS INSTRUMENTATION
SECTION 460754.08 - PACKAGE MBR SYSTEM - LAYOUT DRAWINGS
SECTION 460754.09 - PACKAGE MBR SYSTEM - P&ID DDRAWINGS
SECTION 460754.10 - DES-CHEMICAL FEED SKIDS
SECTION 461155 - SLUDGE DEWATERING SYSTEM - GENERAL
SECTION 461155.01 - DES VOLUTE PRESS
SECTION 461155.02 - DES POLYMER BLENDING SYSTEM
SECTION 461155.03 - DES SCREW CONVEYOR
SECTION 461155.04 - PCN-SLUDGE DEWATERING SYSTEM
SECTION 462113 - SCREENING AND GRIT REMOVAL SYSTEM - GENERAL
TABLE OF CONTENTS TOC - 19
SECTION 462113.1 - DES - COARSE SCREENING AND GRIT REMOVAL PACKAGE
SYSTEM
SECTION 462113.2 - DES - FINE SCREENING
SECTION 462113.3 - DES - MANUAL BAR SCREEN
SECTION 465035 - WASTEWATER ULTRAVIOLET DISINFECTION SYSTEM
SECTION 465035.01 - DES-HOSPITAL WASTEWATER ULTRAVIOLET DISINFECTION
SYSTEM
SECTION 465035.02 - DES HON-DAH WASTEWATER ULTRAVIOLET DISINFECTION
SYSTEM
SECTION 465131 - AERATION EQUIPMENT – GENERAL
SECTION 465131.01 - DES-FINE BUBBLE AERATION
SECTION 465131.02 - DES-COARSE BUBBLE AERATION
END OF TABLE OF CONTENTS
FINAL CONSTRUCTION DOCUMENTS
23 JANUARY 2026
SECTION 260400 - COMMON WORK RESULTS FOR ELECTRICAL
PART 1 - GENERAL
1.1 SUMMARY
A. Design Intent:
1. The Contract Documents indicate and specify the electrical design intent. The
Contract Drawings are schematic and diagrammatic and are not intended to indicate construction details and routing unless specifically indicated. The specifications establish minimum performance, product and installation requirements.
2. In addition to the specified and indicated performance and quality requirements, furnish products and perform installation work consistent with the design intent, industry standards and as necessary to the provision of complete operating electrical systems.
3. Install electrical work in accordance with the National Electrical Code and all applicable local codes in a neat and workmanlike manner.
4. This Section specifies basic electrical requirements applicable to all Divisions unless explicitly excepted.
5. If there is a conflict between applicable documents, then the more stringent requirement shall apply. All documents listed are believed to be the most current releases of the documents. The Contractor has the responsibility to determine and adhere to the most recent release when developing the proposal for installation.
6. Contractor shall thoroughly review entire set of Contract Documents, including all discipline drawings and specifications prior to bidding and include all required electrical work in bid, even if not explicitly shown on electrical Drawings and Specifications.
7. The project is pursuing LEED certification. Contractor shall provide requirements in compliance with LEED standards as identified in the Contract Documents.
1.2 REFERENCES
A. Codes and Standards indicated in General Sheets.
B. American National Standards Institute (ANSI) C2 - National Electrical Safety Code.
C. National Electrical Contractors Association (NECA).
1. 1 - Standard for Good Workmanship in Electrical Construction.
2. 500 - Recommended Practice for Installing Indoor Commercial Lighting Systems.
D. National Fire Protection Association (NFPA).
1. 70 - National Electrical Code (NEC).
2. 70E - Standard for Electrical Safety in the Workplace.
3. 72 - National Fire Alarm and Signaling Code.
4. 99 - Healthcare Facilities Code
5. 101 - Life Safety Code.
6. 111 - Standard for Stored Electrical Energy Emergency and Standby Power
Systems.
E. Leadership in Energy and Environmental Design (LEED).
1. Interior Design and Construction (ID+C) v4 - Commercial Interiors.
COMMON WORK RESULTS FOR ELECTRICAL 260400 - 1
FINAL CONSTRUCTION DOCUMENTS
23 JANUARY 2026
1.3 Submittals
A. General
1. Submit Shop Drawings, Product Data, Samples and other specified submittals on a "system" basis. Retain, and assemble drawings and data from manufacturer or component manufacturers such that each submittal is for a complete system.
2. Refer to Section 013300, "Shop Drawings, Product Data and Samples", for basic definitions and requirements for submittals.
3. Refer to Section 013330 for submittal compliance form.
B. Contract Closeout Submittals
1. Refer to Division 01, "Record Documents", for basic definitions and requirements for record documents.
1.4 Quality Assurance
A. Owner Construction Design Standards
1. Provide an electrical installation in accordance with the Owner's construction design standards and specifications, unless specific written waivers are provided by the Owner.
B. Regulatory Requirements
1. Comply with the applicable requirements of ANSI C2 and the latest NFPA 70.
2. Comply with applicable requirements of city, county, and state laws, ordinances and regulations including modifications and supplements to ANSI C2 and NFPA 70.
3. Comply with the applicable requirements of U.S.Department of Labor, Occupational Safety and Health Administration Standards (OSHA).
4. All materials shall conform with the standards of the Underwriter¢¢s Laboratories in every case where such standards have been established for the particular type of material or assembly .
5. All material and equipment shall be UL listed and bear the UL label where such listing and labeling exists.
6. In the case where two or more Codes conflict or contradict each other, comply with the more stringent Code or standard.
C. Contractor Qualifications and Character of Work
1. Contractor personnel must be knowledgeable in local, state and national codes and regulations. Contractor shall have been in the business of installing electrical systems for a minimum of ten (10) years.
2. Contractor must possess and maintain current liability insurance certificates.
3. Contractor shall obtain and pay for all permits and inspections required by laws, local ordinances, rules, and regulations having jurisdiction for the work. Permits shall be readily available and posted in a prominent place at building site and protected from weather and physical damage.
4. The installation shall be executed in a workmanlike manner and shall present a neat physical appearance when completed.
1.5 PROJECT/SITE CONDITIONS
A. Environmental Requirements
1. Provide products suitable for operation under the following environmental conditions:
COMMON WORK RESULTS FOR ELECTRICAL 260400 - 2
FINAL CONSTRUCTION DOCUMENTS
23 JANUARY 2026
a. Temperature: -18 to 38 degrees C (0 to 100 degrees F).
b. Humidity: 0 to 95 relative percent, non-condensing.
c. Altitude: 2010 meters (6600 feet) above sea level.
d. Outdoor: Products that are UL listed for wet locations.
1.6 WARRANTIES
A. Refer to the Conditions of the Contract for provisions concerning Contract general warranty, Statements of Compliance, correction of Work period, and form of Special Warranty.
B. All electrical systems, equipment and installations shall be provided with a one-year minimum Warranty starting from the date of substantial completion.
C. During the warranty period, and for non-conformities the contractor shall take all necessary and appropriate action; free of charge, to correct any non-conformity with the warranties contained in the manufacturer agreement. During the warranty period, contractor shall provide to Owner, free of costs and charges, all support necessary to ensure that the installation meets the requirements specified in the Contract Documents and performance guarantees provided by the contractors. During the warranty period, contractors shall furnish, or cause to be furnished, all maintenance, service, parts and replacements necessary to maintain the installation in good working condition, at no cost to Owner.
1.7 CONDUCTOR SIZING
A. Feeder and Branch Circuit Sizing
1. Provide feeder and branch circuits per the circuit sizing schedules indicated on
Drawings. Where schedules are not indicated, provide conductors which are sized as required per the NEC for the indicated overcurrent protective device rating. Circuit sizing and installation shall consider the field routing and anticipated voltage drop. Upsize wire, as necessary, to compensate for voltage drop and/or other forms of derating required in accordance with the NEC.
2. Derate conductor ampacities per the NEC for field conditions including but not limited to conduits exposed to sunlight, elevated ambient temperature, and/or more than 3 current carrying conductors in a raceway.
1.8 SYSTEMS INTEGRATION
A. Coordinate with equipment suppliers and ensure integration of systems comprised of disparate equipment which work together to form a complete system.
B. Provide all miscellaneous components, wiring, hardware, etc. required for complete and operational equipment and systems whether or not these items are explicitly shown in the Contract Documents.
C. Provide systems which maintain the UL rating of the individual pieces of equipment.
D. Submit system integration wiring diagrams, control diagrams and sequence of operation, as needed.
1.9 COORDINATION
A. Contractor shall participate in the project scheduling, coordination meetings and coordination drawing/modeling activities as specified in Division 01.
COMMON WORK RESULTS FOR ELECTRICAL 260400 - 3
FINAL CONSTRUCTION DOCUMENTS
23 JANUARY 2026
B. All potential coordination issues shall be brought to the attention of the Construction Manager immediately before proceeding with the installation.
C. Contractor shall be responsible for all cross connecting and coordination with vendors and other trade contractors to provide complete operational systems.
D. For purpose of clarify and legibility, drawings are diagrammatic. Locate equipment as close as practical to the locations shown on the drawings. Should field conditions prevent the installation of equipment or materials as indicated on the drawings, make deviations only with the prior approval of the Owner's representative.
E. Coordinate arrangement, mounting, and support of electrical equipment:
1. To allow maximum possible headroom unless specific mounting heights that reduce headroom are indicated.
2. To provide for ease of disconnecting the equipment with minimum interference to other installations.
3. To allow right of way for piping at required slope.
4. To allow connecting raceways, cables, wireways, cable trays, and busways to be clear of obstructions and of the working and access space of other equipment.
F. Coordinate work with other trades to ensure completion is consistent with the project schedule. Ensure the NEC-required working space and dedicated electrical space about electrical equipment is provided. Foreign systems shall not be located within these dedicated zones. Any work that encroaches on the working space or dedicated electrical space shall be relocated at the Contractor's expense.
G. Equipment and device mounting heights and alignment shall adhere to architectural drawings, rules and requirements. Devices of all trades within the same general area shall be coordinated prior to construction. Care shall be taken to align devices horizontally and vertically. Devices that are not aligned properly shall be relocated at the Contractor's expense.
H. Coordinate exact conduit routing in the field with other trades and with building elements such as structural steel members. Conduit and raceways are not explicitly shown. Conduit routing where shown on drawings shall be considered approximate.
Contractor shall be responsible for final routing in the field and shall be responsible for complete coordination with all other trades.
I. Coordinate installation of required supporting devices and set sleeves in cast-in-place concrete, masonry walls, and other structural components as they are constructed.
J. Coordinate location of access panels and doors for electrical items that are behind finished surfaces or otherwise concealed. Access doors and panels are specified in Division 8.
K. Coordinate sleeve selection and application with selection and application of firestopping specified in Division 07.
PART 2 - PRODUCTS
2.1 Manufacturers
A. General
COMMON WORK RESULTS FOR ELECTRICAL 260400 - 4
FINAL CONSTRUCTION DOCUMENTS
23 JANUARY 2026
1. Furnish products by one of the equipment manufacturers listed under the heading "Manufacturers" within the applicable sections. When given, furnish the specified product model or brand for the selected manufacturer.
2. Provide products, for which quantities of two or more are to be furnished, from the same manufacturer and of the same product or model series.
3. Furnish product components designed to be used together and which are physically and electrically compatible.
B. Comparable Products
1. Comparable products may be proposed when the "or as approved" clause is specified under the heading "Manufacturers". Submit such products substitutions for approval per Division 01, "Product Requirements.••
C. Product Substitutions
1. Product substitutions may be requested under the conditions specified in Division
01 'Substitution Procedures'.•• Submit product substitutions for consideration per Division 01, "Substitution Procedures".
2.2 Products
A. Product Listing and Labeling
1. Provide listed and labeled product for which listings and labels exist by
Underwriters Laboratories Inc. (UL), Factory Mutual (FM), or similar independent testing organizations recognized by the authorities having jurisdiction. For products for which there are no such listings and labels, provide listed and labeled components of those products, for which component listing and labels exist.
B. PCB Content Prohibited
1. Provide products which do not contain any amounts of polychlorinated biphenyl
(PCB) compounds.
C. Lead Limits
1. Electrical wire and cable to have lead content less than 300 parts per million.
D. Asbestos Content Prohibited
1. Provide products which do not contain any amounts of asbestos.
E. Access Doors
1. Provide access doors necessary to access devices, whether for control or maintenance, governed by these Basic Electrical Materials and Methods.
Comply with access door requirements specified in Division 08. Access doors are not explicitly shown on the Drawings.
2. Access doors shall be coordinated with other trades and final locations shall be approved by Architect. Access doors not approved by Architect shall be removed or relocated at the Contractors expense.
3. Access doors installed in fire rated floors, walls or ceilings shall be sufficiently rated to maintain the rating of the surface where installed.
2.3 Source Quality Control
A. Factory Tests
1. Permit Architect and Owner to observe factory tests. Provide minimum five working 14 days notice of factory tests.
2. Schedule no more than one equipment or system factory test per week.
COMMON WORK RESULTS FOR ELECTRICAL 260400 - 5
FINAL CONSTRUCTION DOCUMENTS
23 JANUARY 2026
PART 3 - EXECUTION
3.1 CONSTRUCTION PHASING
A. The project will utilize phased construction. Contractor shall account for any and all costs associated with a phased construction schedule in bid.
3.2 SHUTDOWNS
A. Interruption of Existing Service: Do not interrupt electric, communications or fire alarm service to facilities occupied by Owner or others unless permitted under the following conditions and then only after arranging to provide temporary electric service according to requirements indicated:
1. Notify Architect, Construction Manager and Owner no fewer than seven days in advance of proposed interruption of service.
2. Indicate method of providing temporary service.
3. Do not proceed with interruption of service without Architect's, Construction
Manager's and Owner’s written permission.
4. Comply with NFPA 70E.
B. Coordinate all service interruptions with other disciplines and Owner's representative.
Shutdowns shall be performed during off hours, which may include weekends or holidays. This premium time cost shall be included in the Contractor's base bid.
C. Maintain Owner communications and network services operations during construction.
Coordinate all service interruptions with other disciplines and Owner's representative.
D. Maintain Owner fire alarm systems and services operations during construction.
Coordinate all service interruptions with other disciplines and Owner's representative.
3.3 DEMOLITION
A. Protect adjacent building services and materials indicated to remain. Install and maintain barriers to keep dirt, dust, and noise from being transmitted to adjacent areas.
Remove protection and barriers after demolition is complete.
B. “Carefully remove, clean and restore and reinstall items that are relocated during construction to a "like new" condition.
C. Building elements such as walls, partitions, floors and ceilings affected by electrical construction such as conduit penetrations shall be repaired, patched, painted and otherwise restored to a "like new" condition.
D. Lamp and Ballast Recycling.
1. Recycle lamps, ballasts and drivers containing hazardous materials such as mercury during construction. These shall include tubular fluorescent, compact fluorescent, HID, LED, induction and cold cathode lamps. These lamp types, ballasts and drivers associated with these lamps shall not be disposed of as solid municipal waste.
E. Equipment Protection and Cleanup.
1. Protect equipment and materials during shipment, storage and construction against damage, dust and contamination. Items that become damaged, dirty or contaminated during construction shall be restored to a "like new" condition or replaced at the Contractor's expense.
COMMON WORK RESULTS FOR ELECTRICAL 260400 - 6
FINAL CONSTRUCTION DOCUMENTS
23 JANUARY 2026
2. Remove and legally dispose of demolished items, rubbish, debris and construction waste from the construction site daily, and at the completion of the work. The contractor shall maintain a "clean" work site. Failure to do so may result in the cleanup being performed by others and all costs thereof being deducted from the Contractor’s final payment.
3.4 TEMPORARY SERVICE
A. The facility will remain operational during construction. Provide equipment, hardware, wiring, etc. to maintain systems scheduled to remain operational during construction.
Coordinate detailed work phasing plans with the Construction Manager, Architect and Owner prior to commencing work.
B. Provide, maintain and remove all temporary lighting, power and communications required to complete the project.
1. Coordinate temporary service installation with the local utility companies and building landlord prior to construction.
C. In addition to NEC ground fault protection requirements, provide ground fault protection on temporary feeders 200 amps and greater.
D. Temporary…