These are architectural and engineering drawings for a modernized surveillance system installation at the Air Force Research Laboratory's Rome Research Site in New York. The documents include detailed floor plans, communications infrastructure diagrams, electrical specifications, and security device locations across multiple buildings at the facility.
The project involves installing fiber optic backbone conduits, cable management systems, and surveillance camera infrastructure throughout Buildings 101, 106, 1411, and 1609. Key requirements include providing two conduits for fiber optic backbones between the main communications room and classified/unclassified spaces, installing color-coded cable trays (black for CAT cable, red for fiber optic cable) with proper separation and grounding to telecommunications ground bars, and establishing camera locations marked on floor plans with associated detail sheets. The drawings specify cable routing through existing building electrical systems, coordination with site security vendors for access control and video surveillance integration, and precise hardware specifications for splice connectors, stiffeners, bracing supports, hangers, and water fall components. Installation details address conduit enclosure from the communications room to various end points, cable terminations in cabinets, and integration with existing telecommunications infrastructure. The documents include amendments dated July 9, 2015, indicating design revisions and updates to camera and conduit locations throughout the facility.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DRAWING NO: SHEET: FACILITY NO:
OF
SHEET TITLE:
PROJECT TITLE:
DATE:
BLDG #
PROJECT MNGR:
PROJECT NO:
DRAFTER:
DESIGNER:
B106
C
CT
P
N
106\055TC1C \055 Room E\055140
N
CR
CT
CT
CR
CR
N
CR
C
P
FA8751-15-R-0024 - ATTACHMENT 2 - AMENDMENT NUMBER 2, 9 JULY 2015
AMENDED 9 JUL 2015
C
C
C
C
C
P
C
P
C
C
C
C
C
PS
C
C
PS
C
C
R
PS
PS
R
C
C
R
R
R
R
PS
R
R
R
R
PS
PS
R
R
R
R
PS
R
R
C
C
R
C
C
C
Station 28
Station 29
Station 25
R
P
C
C
C
C
C
C
C
C
R
C
C
C
C
C
C
C
All outdoor RLAB cams can be reached with a 24™ ladder but this one is unhandy
C
4th gate camera
C
C
New P3719 Camera
Old M3024 Camera
P
N
C
C
D
M
C
Station 24
R
M
See SSO Sheet for updated info
V
C
C
C
C
Sw
P
P
N
R
R
PS
P
C
C
C
C
C
PS
P
D
D
P
P
C
C
C
C
New web cam
C
C
C pole cam
C
D
C
C
New webcam Feb22
C
N
C
C
Splice for both cameras in 1st floor bathroom ceiling
N
C
C
C
C
C
P
C
P
P
R
PS
R
PS
PS
R
R
PS
R
PS
PS
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
P
C
C
N
C
C
C
C
C
C
C
C
C
C
C
C
AutoCAD SHX Text
PANEL MDP
AutoCAD SHX Text
COMMUNICATIONS JUNCTION BOX
AutoCAD SHX Text
VEHICLE BAY
AutoCAD SHX Text
AutoCAD SHX Text
COMM.
AutoCAD SHX Text
AutoCAD SHX Text
MACHINE ROOM
AutoCAD SHX Text 102A
AutoCAD SHX Text
LAB
AutoCAD SHX Text
AutoCAD SHX Text
LAB
AutoCAD SHX Text
AutoCAD SHX Text
LAB
AutoCAD SHX Text
AutoCAD SHX Text
RESTROOM
AutoCAD SHX Text
AutoCAD SHX Text
%%UTDME/JAN
AutoCAD SHX Text
UTILITY ROOM
AutoCAD SHX Text
AutoCAD SHX Text
ROOM
AutoCAD SHX Text 100B
AutoCAD SHX Text
CONFERENCE
AutoCAD SHX Text
OFFICES
AutoCAD SHX Text
AutoCAD SHX Text
VESTIBULE
AutoCAD SHX Text 100A
AutoCAD SHX Text
LAB
AutoCAD SHX Text
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
AutoCAD SHX Text
BREAK
AutoCAD SHX Text
PANEL P-1
AutoCAD SHX Text DUCTLESS HEAT PUMP INDOOR UNIT, DHPIU-1 MITSUBISHI ELECTRIC CORP. MODEL PKA-A36KA4
AutoCAD SHX Text
COMMUNICATIONS RACKS
AutoCAD SHX Text
NEW PANEL EP-1
AutoCAD SHX Text
NEW AUTOMATIC TRANSFER SWITCH, ATS-1
AutoCAD SHX Text
CONCRETE CURB
AutoCAD SHX Text
PRIMARY TRANSFORMER CURB
AutoCAD SHX Text
PRIMARY TRANSFORMER
AutoCAD SHX Text
BOLLARD (TYPICAL)
AutoCAD SHX Text
ASPHALT
AutoCAD SHX Text
GRASSED AREA
AutoCAD SHX Text
FENCE
AutoCAD SHX Text
CONCRETE SIDEWALK
AutoCAD SHX Text
NEW BOLLARD (TYPICAL)
AutoCAD SHX Text
ACCESS DOORS (TYPICAL)
AutoCAD SHX Text
NEW EQUIPMENT PAD
AutoCAD SHX Text
AIR
AutoCAD SHX Text
INTAKE
AutoCAD SHX Text
AIR
AutoCAD SHX Text
DISCHARGE
AutoCAD SHX Text
NEW OSPS-1
AutoCAD SHX Text
UNDERGROUND PROPANE TANK 1000 GALLONS
AutoCAD SHX Text
NEW OSPS-1 REMOTE ANNUNCIATOR (COORDINATE EXACT LOCATION WITH OWNER)
AutoCAD SHX Text
PANEL GL-1
AutoCAD SHX Text
FACP-1
AutoCAD SHX Text
EXIST.
AutoCAD SHX Text
EP-1 1
AutoCAD SHX Text
NEW GENERATOR PANEL, GP-I
AutoCAD SHX Text J
AutoCAD SHX Text
NEW 1 1/2" CONDUIT WITH CONTROL WIRING TO ATS-1 AND REMOTE ANNUNCIATOR
AutoCAD SHX Text
NEW JUNCTION BOX
AutoCAD SHX Text
REMOVE EXIST. BRANCH CIRCUIT AND PROVIDE NEW AS SHOWN
AutoCAD SHX Text
CR
AutoCAD SHX Text
NEW CARD READER (PROVIDE SINGLE GANG JUNCTION BOX)
AutoCAD SHX Text
NEW EMPTY 1" CONDUIT WITH PULL CORD
AutoCAD SHX Text
CONTRACTOR TO FILL INTEGRAL FUEL TANK WITH NO. 1 DIESEL FUEL (KEROSENE)
AutoCAD SHX Text SAW CUT CONCRETE SIDEWALK TO ALLOW FOR INSTALLATION OF NEW CONDUITS AND PATCH TO MATCH EXISTING AT COMPLETION
AutoCAD SHX Text J
AutoCAD SHX Text
LB AT FLOOR (TYPICAL)
AutoCAD SHX Text
NEW JUNCTION BOX
AutoCAD SHX Text
NEW GENERATOR PANEL FEEDER
AutoCAD SHX Text
NEW GENERATOR FEEDER TO ATS-1
AutoCAD SHX Text
UNDERGROUND CONDUITS
AutoCAD SHX Text
EXACT ROUTING OF CONDUITS SHALL BE ADJUSTED FOR FIELD CONDITIONS (TYPICAL)
AutoCAD SHX Text
PROVIDE BUSHED END
AutoCAD SHX Text
CONCRETE PAD
AutoCAD SHX Text
DUCTLESS HEAT PUMP INDOOR UNIT, DHPOU-1
AutoCAD SHX Text
ROME
AutoCAD SHX Text
RESEARCH
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
ROME, NY
AutoCAD SHX Text
SIGNATURE
AutoCAD SHX Text
IFOCO
AutoCAD SHX Text
IFOCC
AutoCAD SHX Text
IFOC
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
COORDINATION
AutoCAD SHX Text
IFOCO
AutoCAD SHX Text
USER
AutoCAD SHX Text
USER
AutoCAD SHX Text
USER
AutoCAD SHX Text
SITE
AutoCAD SHX Text
IFOF
AutoCAD SHX Text
IFOS
AutoCAD SHX Text
DESIGN FIRM
AutoCAD SHX Text Date
AutoCAD SHX Text Drafter
AutoCAD SHX Text
REVISION
AutoCAD SHX Text
BY/DATE
AutoCAD SHX Text
SHEET TITLE
AutoCAD SHX Text
OF
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
PROJECT TITLE
AutoCAD SHX Text Project Number
AutoCAD SHX Text Project Manager
AutoCAD SHX Text Designer
AutoCAD SHX Text
IFOCV
AutoCAD SHX Text Facility Number
AutoCAD SHX Text Drawing Number
AutoCAD SHX Text
ULDF-19-0006AE
AutoCAD SHX Text
UPGRADE EMERGENCY
AutoCAD SHX Text
POWER AND FORCE
AutoCAD SHX Text
APRIL 22, 2020
AutoCAD SHX Text
PROTECTION,
AutoCAD SHX Text
TEST SITES
AutoCAD SHX Text
AutoCAD SHX Text
STAMP
AutoCAD SHX Text
WAK / GHS
AutoCAD SHX Text
WAK / GHS
AutoCAD SHX Text
JRM / WAK
AutoCAD SHX Text 100%%%
AutoCAD SHX Text
SUBMISSION
AutoCAD SHX Text k
AutoCAD SHX Text n
AutoCAD SHX Text
AutoCAD SHX Text S
AutoCAD SHX Text
AutoCAD SHX Text u
AutoCAD SHX Text o
AutoCAD SHX Text h
AutoCAD SHX Text t
AutoCAD SHX Text e
AutoCAD SHX Text S
AutoCAD SHX Text r
AutoCAD SHX Text t
AutoCAD SHX Text e
AutoCAD SHX Text t
AutoCAD SHX Text N
AutoCAD SHX Text a
AutoCAD SHX Text c
AutoCAD SHX Text
AutoCAD SHX Text U
AutoCAD SHX Text t
AutoCAD SHX Text i
AutoCAD SHX Text Y
AutoCAD SHX Text r
AutoCAD SHX Text o
AutoCAD SHX Text e
AutoCAD SHX Text w
AutoCAD SHX Text i
AutoCAD SHX Text g
AutoCAD SHX Text w
AutoCAD SHX Text T
AutoCAD SHX Text o
AutoCAD SHX Text E
AutoCAD SHX Text n
AutoCAD SHX Text n
AutoCAD SHX Text e
AutoCAD SHX Text n
AutoCAD SHX Text i
AutoCAD SHX Text r
AutoCAD SHX Text e
AutoCAD SHX Text e
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text g
AutoCAD SHX Text P
AutoCAD SHX Text
AutoCAD SHX Text C
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
PROPOSED FLOOR PLAN - BUILDING 1477
AutoCAD SHX Text
SCALE: 1/8" = 1'-0"
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text
NORTH
AutoCAD SHX Text W
AutoCAD SHX Text DRAWING INFORMATION WAS PROVIDED BY THE AFRL AND IS NOT FROM A SITE SURVEY, EXACT LOCATION OF ALL BUILDINGS, ROADWAYS, GUY WIRES, MANHOLES, UNDERGROUND UTILITIES, ETC. SHALL BE FIELD VERIFIED. GROUND PENETRATING RADAR AND ELECTROMAGNETIC INDUCTION EQUIPEMENT SHALL BE USED TO FIELD VERIFY ALL UNDERGROUND UTILITIES IN ALL AREAS WHERE NEW WORK IS SCHEDULED TO BE EXECUTED.
AutoCAD SHX Text
PROPOSED
AutoCAD SHX Text
FLOOR PLAN
AutoCAD SHX Text
BUILDING 1477
AutoCAD SHX Text
AutoCAD SHX Text 19-0006-1
AutoCAD SHX Text
AutoCAD SHX Text WORK EXECUTED BY FALLS EARTH STATION INSTALLATIONS, INC. UNDER THE ALLOWANCE: FURNISH AND INSTALL NEW CARD READER AT MAIN DOOR OF BUILDING 1477 ALONG WITH NECESSARY FUNCTIONALITY FOR DOOR OPERATION. CONNECT CARD READER TO COMMUNICATION ROOM 104 USING PROVIDED PATHWAY. FURNISH AND INSTALL NEW CARD READERS AT EXISTING GATE ACCESS STATIONS AND INSTALL NEW CARD READERS AT EXISTING GATE ACCESS STATIONS AND INSTALL NEW CARD READERS AT EXISTING GATE ACCESS STATIONS INSTALL NEW CARD READERS AT EXISTING GATE ACCESS STATIONS INSTALL NEW CARD READERS AT EXISTING GATE ACCESS STATIONS NEW CARD READERS AT EXISTING GATE ACCESS STATIONS NEW CARD READERS AT EXISTING GATE ACCESS STATIONS CARD READERS AT EXISTING GATE ACCESS STATIONS CARD READERS AT EXISTING GATE ACCESS STATIONS READERS AT EXISTING GATE ACCESS STATIONS READERS AT EXISTING GATE ACCESS STATIONS AT EXISTING GATE ACCESS STATIONS AT EXISTING GATE ACCESS STATIONS EXISTING GATE ACCESS STATIONS EXISTING GATE ACCESS STATIONS GATE ACCESS STATIONS GATE ACCESS STATIONS ACCESS STATIONS ACCESS STATIONS STATIONS STATIONS FOR INCOMING AND OUTGOING GATE OPERATION. CONNECT CARD READERS TO INCOMING AND OUTGOING GATE OPERATION. CONNECT CARD READERS TO INCOMING AND OUTGOING GATE OPERATION. CONNECT CARD READERS TO AND OUTGOING GATE OPERATION. CONNECT CARD READERS TO AND OUTGOING GATE OPERATION. CONNECT CARD READERS TO OUTGOING GATE OPERATION. CONNECT CARD READERS TO OUTGOING GATE OPERATION. CONNECT CARD READERS TO GATE OPERATION. CONNECT CARD READERS TO GATE OPERATION. CONNECT CARD READERS TO OPERATION. CONNECT CARD READERS TO OPERATION. CONNECT CARD READERS TO CONNECT CARD READERS TO CONNECT CARD READERS TO CARD READERS TO CARD READERS TO READERS TO READERS TO TO TO COMMUNICATIONS ROOM 104 USING EXISTING FIBER CONNECTION BETWEEN THE GATE ROOM 104 USING EXISTING FIBER CONNECTION BETWEEN THE GATE ROOM 104 USING EXISTING FIBER CONNECTION BETWEEN THE GATE 104 USING EXISTING FIBER CONNECTION BETWEEN THE GATE 104 USING EXISTING FIBER CONNECTION BETWEEN THE GATE USING EXISTING FIBER CONNECTION BETWEEN THE GATE USING EXISTING FIBER CONNECTION BETWEEN THE GATE EXISTING FIBER CONNECTION BETWEEN THE GATE EXISTING FIBER CONNECTION BETWEEN THE GATE FIBER CONNECTION BETWEEN THE GATE FIBER CONNECTION BETWEEN THE GATE CONNECTION BETWEEN THE GATE CONNECTION BETWEEN THE GATE BETWEEN THE GATE BETWEEN THE GATE THE GATE THE GATE GATE GATE AND BUILDING 1477. FURNISH AND INSTALL INTERCOM/CAMERA AT EXISTING EXTERIOR TELEPHONE STATION. CONNECT TO BUILDING USING EXISTING FIBER. PROVIDE NOTIFICATION FOR BUILDING 1477 OCCUPANTS FOR ACTIVATION OF INTERCOM/CAMERA DEVICE.
AutoCAD SHX Text
CONDUIT SYSTEMS APPLICATION (UNLESS OTHERWISE NOTED):
AutoCAD SHX Text %%uGENERAL NOTES
AutoCAD SHX Text 9.
AutoCAD SHX Text
a. THE BUILDING ENGINEER MUST BE GIVEN 72 HOURS NOTICE.
AutoCAD SHX Text
b. A STEP BY STEP PROCEDURE INCLUDING AN ESTIMATE OF OUT-OF-SERVICE INTERVALS MUST BE SUBMITTED AND APPROVED BY THE BUILDING ENGINEER.
AutoCAD SHX Text
c. AN AUTHORIZED OWNER'S REPRESENTATIVE MUST BE PRESENT DURING ALL OUT-OF-SERVICE PERIODS. NO SHUTDOWN OF THE SYSTEM SHALL TAKE PLACE WITHOUT THE PRIOR APPROVAL OF THE BUILDING ENGINEER.
AutoCAD SHX Text
d. NO PART OF THE SYSTEM SHALL BE LEFT OUT-OF-SERVICE AT THE END OF THE WORKING DAY.
AutoCAD SHX Text ALL CONDUITS THAT PASS THRU EXTERIOR WALLS OR FROM A CONDITIONED SPACE TO AN UNCONDITIONED SPACE SHALL BE SEALED WATERTIGHT/FIREPROOF WITH CHASE TECHNOLOGY CORPORATION CTCPR-866 SILICONE SEALANT.
AutoCAD SHX Text EACH BRANCH CIRCUIT SHALL BE NO. 12 AWG CONDUCTORS (PHASE, NEUTRAL AND EQUIPMENT GROUND, COMMON OR SHARED NEUTRALS ARE NOT ALLOWED) IN 1/2" CONDUIT WITH 20A-1P CIRCUIT BREAKER (UNLESS OTHERWISE NOTED). ANY BRANCH CIRCUIT WITH A DEVELOPED LENGTH OF 175 FEET OR GREATER SHALL BE NO. 10 AWG CONDUCTORS (PHASE, NEUTRAL AND EQUIPMENT GROUND, COMMON OR SHARED NEUTRALS ARE NOT ALLOWED).
AutoCAD SHX Text PROVIDE ALL REQUIRED CUTTING, PATCHING AND INFILL: THEREAFTER, RESTORE ALL AFFECTED SURFACES TO MATCH EXISTING.
AutoCAD SHX Text MODIFY BRANCH CIRCUITS WHICH ARE DISRUPTED BY ASSOCIATED REMOVALS TO INSURE THE REQUIRED ARRANGEMENT FOR REMAINING EQUIPMENT AND/OR DEVICES.
AutoCAD SHX Text REMOVE ALL BRANCH CIRCUIT WIRE AND CONDUIT ASSOCIATED WITH EQUIPMENT AND DEVICES SHOWN AND/OR NOTED TO BE REMOVED BACK TO SOURCE.
AutoCAD SHX Text PROVIDE "PROTECTION" RELATIVE TO ALL APPLICABLE WORK IN ACCORDANCE WITH THE REQUIREMENTS SET FORTH IN DIVISION 1.
AutoCAD SHX Text EXECUTE ALL WORK IN A FASHION COMPLEMENTARY WITH AND UNOBTRUSIVE TO THE OWNER'S NEEDS AND OPERATIONS, RESPECTIVELY.
AutoCAD SHX Text THOROUGHLY COORDINATE WORK WITH ALL ASSOCIATED WORK EXECUTED BY "OTHER" CONTRACTORS.
AutoCAD SHX Text EXISTING FIRE ALARM SYSTEMS SHALL BE MAINTAINED IN SERVICE AT ALL TIMES. ALTERATIONS OR CONNECTIONS REQUIRING THE SHUTDOWN OF ANY PART OF THE SYSTEM MUST BE SCHEDULED AND THE FOLLOWING PROCEDURES FOLLOWED:
AutoCAD SHX Text BREAKERS DESIGNATED TO SERVE NEW EQUIPMENT (FROM EXISTING PANELS) SHALL BE NEW AND SHALL HAVE CHARACTERISTICS MATCHING EXISTING (BREAKERS) UNLESS OTHERWISE SHOWN OR NOTED.
AutoCAD SHX Text BUSSMAN FUSES, FUSETRON TYPE FRN-R (250 VOLT, DUAL-ELEMENT, TIME DELAY, UL CLASS RK5) SHALL BE USED FOR MOTOR CIRCUITS, LIMITRON TYPE KTN-R (250 VOLT, FAST ACTING, UL CLASS RK-1) SHALL BE USED FOR ALL NON-MOTOR CIRCUITS.
AutoCAD SHX Text PROVIDE ONE SPARE SET OF FUSES COMPLETE WITH FUSE HOLDER AT EVERY NEW FUSE/FUSED DEVICE (SERVICE DISCONNECT, DISCONNECT SWITCHES, SAFETY SWITCHES, PLUG-FUSE BOX COVER UNITS, ETC.) INSTALLED UNDER THIS CONTRACT.
AutoCAD SHX Text 10.
AutoCAD SHX Text 15.
AutoCAD SHX Text 13.
AutoCAD SHX Text 11.
AutoCAD SHX Text 8.
AutoCAD SHX Text 7.
AutoCAD SHX Text 6.
AutoCAD SHX Text 5.
AutoCAD SHX Text 3.
AutoCAD SHX Text 2.
AutoCAD SHX Text 1.
AutoCAD SHX Text C. TERMINATIONS AT MECHANICAL EQUIPMENT: 1) LIQUIDTIGHT FLEXIBLE METAL CONDUIT (LFMC).
AutoCAD SHX Text
B. EXTERIOR SYSTEMS ABOVE GRADE, ALL SIZES: 1) RIGID STEEL CONDUIT (RSC).
AutoCAD SHX Text
A. INTERIOR SYSTEMS, ALL SIZES: 1) ELECTRICAL METALLIC TUBING (EMT).
AutoCAD SHX Text 12.
AutoCAD SHX Text ALL DISTRIBUTION SYSTEM COMPONENTS (SERVICE DISCONNECT, PANELBOARDS, MANUAL TRANSFER SWITCH, AUTOMATIC TRANSFER SWITCH, ETC.) SHALL BE MOUNTED ON UNISTRUT P 3300 CHANNEL (7/8" x 1 5/8" WIDE) WITH PERMA-GREEN RUST INHIBITING ACRYLIC ENAMEL PAINTED FINISH.
AutoCAD SHX Text 14.
AutoCAD SHX Text 16.
AutoCAD SHX Text PROVIDE NEW TYPED DIRECTORY FOR ANY EXISTING PANELBOARD WHICH IS MODIFIED IN ANY FASHION INCLUDING A BRANCH CIRCUIT REMOVAL OR ADDITION.
AutoCAD SHX Text 17.
AutoCAD SHX Text ALL ELECTRICAL EQUIPMENT, DEVICES, CONDUIT ETC. SHALL BE RECESSED IN PARTITIONS AND CEILINGS WHEREVER POSSIBLE. EXISTING MASONRY PARTITIONS SHALL BE WIRED THROUGH THE USE OF A TWO PIECE NON-METALLIC RACEWAY SYSTEM COMPLETE WITH ALL ACCESSORIES SIMILAR TO WIREMOLD SERIES NM2000.
AutoCAD SHX Text 18.
AutoCAD SHX Text CAREFULLY REMOVE CEILING TILES TO GAIN ACCESS ABOVE CEILINGS IN WORK AREAS, STORE ALL REMOVED CEILING TILES IN A SAFE LOCATION FREE OF ANY DAMAGE CAUSING CONDITIONS AND CAREFULLY REINSTALL AT COMPLETION OF WORK. ANY DAMAGED CEILING TILES SHALL BE REPLACED AT NO COST TO THE OWNER.
AutoCAD SHX Text D. EXTERIOR SYSTEMS BELOW GRADE, ALL SIZES: 1) RIGID NON-METALLIC CONDUIT (RNMC).
AutoCAD SHX Text ALL ELECTRICAL EQUIPMENT SLATED FOR REMOVAL SHALL BE REMOVED IN ITS ENTIRETY INCLUDING ALL ASSOCIATED SUPPORT STRUCTURES, CONCRETE EQUIPMENT PADS, WIRING (POWER AND CONTROL), CONDUIT, DISCONNECT SWITCHES, STARTERS, ETC.
AutoCAD SHX Text 4.
AutoCAD SHX Text 19.
AutoCAD SHX Text
PROVIDE TOPSOIL AND SEED AT ALL GRASS AREAS DISTURBED FROM NEW WORK.
SW
P
P
CR
I
I
Gate info
D
STORAGE ROOM
COMMUNICATION
ROOM
CONFERENCE
ROOM
BREAK ROOM
JANITOR'S CLO.
TOILET ROOM
TOILET ROOM
CORRIDOR
ENTRY
VESTIBULE
VESTIBULE
EXTERIOR
VESTIBULE
LABORATORY
B.1
C
D
E
A.4
A A
A.1
B B
A.0
1 2 3 4 54.91.1 6.25.2 6
AutoCAD SHX Text
SERVICE ENTRANCE DISCONNECT SWITCH
AutoCAD SHX Text T
AutoCAD SHX Text
DAC-1 (64W @ 200V-1~) MOUNT AT 60" AFF
AutoCAD SHX Text
38" RL & " RS58" RS
AutoCAD SHX Text
1" PUMPED CONDENSATE EXTEND TO JANITORS SINK
AutoCAD SHX Text
DISCONNECT SWITCH NEMA 1, FUSED
AutoCAD SHX Text
DACCU-1 19.5A @ 208V-1~ MOUNT AT 60" AFG
AutoCAD SHX Text
DISCONNECT SWITCH NEMA 3R, FUSED
AutoCAD SHX Text
3-#14 & 1-#14 G. IN 1/2" C.
AutoCAD SHX Text
EP-1 2 20A-2P 2-#12 & 1-#12 G. IN 1/2" C.
AutoCAD SHX Text
NEW OSPS-1 REMOTE ANNUNCIATOR (COORDINATE EXACT LOCATION WITH OWNER)
AutoCAD SHX Text
EXISTING ABOVEGROUND PROPANE TANK
AutoCAD SHX Text
EXIST. DISCONNECT SWITCH SERVING UPS
AutoCAD SHX Text DISCONNECT EXIST. FEEDER FROM SWITCHBOARD AND EXTEND TO NEW PANEL EP-1, MODIFY AS REQUIRED
AutoCAD SHX Text
EXIST. PANEL T2
AutoCAD SHX Text
EXIST. PANEL T3
AutoCAD SHX Text
EP-1 3 60A-3P 3-#6 & 1-#10 G. IN 1" C.
AutoCAD SHX Text
ACCESS DOORS
AutoCAD SHX Text
AIR
AutoCAD SHX Text
DISCHARGE
AutoCAD SHX Text
AIR
AutoCAD SHX Text
INTAKE
AutoCAD SHX Text
OSPS-1
AutoCAD SHX Text
EQUIPMENT PAD
AutoCAD SHX Text
GENERATOR PANEL, GP-1
AutoCAD SHX Text
GENERATOR PANEL FEEDER
AutoCAD SHX Text
GENERATOR FEEDER TO ATS-1
AutoCAD SHX Text
1 1/2" CONDUIT WITH CONTROL WIRING TO ATS AND REMOTE ANNUNCIATOR PANEL
AutoCAD SHX Text
GENERATOR FEEDER UP TO ATS-1
AutoCAD SHX Text
UP TO PANEL EP-1
AutoCAD SHX Text
JUNCTION BOX
AutoCAD SHX Text
JUNCTION BOX
AutoCAD SHX Text
REFER TO SHEET 4 FOR CONTINUATION
AutoCAD SHX Text
GATE PANEL FEEDER
AutoCAD SHX Text
EMPTY 4" CONDUIT WITH MAXCELL INNERDUCT TO GATE
AutoCAD SHX Text
CR
AutoCAD SHX Text
NEW CARD READER (PROVIDE SINGLE GANG JUNCTION BOX)
AutoCAD SHX Text C
AutoCAD SHX Text
EMPTY 1" CONDUIT WITH PULL CORD
AutoCAD SHX Text
EMPTY 1" CONDUIT WITH PULL CORD
AutoCAD SHX Text
EXACT ROUTING OF CONDUITS SHALL BE ADJUSTED FOR FIELD CONDITIONS (TYPICAL)
AutoCAD SHX Text
1" CONDUIT WITH CONTROL WIRING UP TO ATS-1
AutoCAD SHX Text
EMPTY 4" CONDUIT WITH MAXCELL INNERDUCT TO GATE
AutoCAD SHX Text
EMPTY 1" CONDUIT WITH PULL CORD
AutoCAD SHX Text
JUNCTION BOX
AutoCAD SHX Text
BOLLARD (TYPICAL)
AutoCAD SHX Text
CONTRACTOR TO FILL INTEGRAL FUEL TANK WITH NO. 1 DIESEL FUEL (KEROSENE)
AutoCAD SHX Text
LB AT FLOOR (TYPICAL)
AutoCAD SHX Text
UNDERGROUND CONDUITS
AutoCAD SHX Text COORDINATE EXACT LOCATION OF UNIT WITH RIOS PERSONAL PRIOR TO INSTALLATION AND RELOCATE ACCORDINGLY
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text
PROVIDE BUSHED END (TYPICAL)
AutoCAD SHX Text
ROME
AutoCAD SHX Text
RESEARCH
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
ROME, NY
AutoCAD SHX Text
SIGNATURE
AutoCAD SHX Text
IFOCO
AutoCAD SHX Text
IFOCC
AutoCAD SHX Text
IFOC
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
COORDINATION
AutoCAD SHX Text
IFOCO
AutoCAD SHX Text
USER
AutoCAD SHX Text
USER
AutoCAD SHX Text
USER
AutoCAD SHX Text
SITE
AutoCAD SHX Text
IFOF
AutoCAD SHX Text
IFOS
AutoCAD SHX Text
DESIGN FIRM
AutoCAD SHX Text Date
AutoCAD SHX Text Drafter
AutoCAD SHX Text
REVISION
AutoCAD SHX Text
BY/DATE
AutoCAD SHX Text
SHEET TITLE
AutoCAD SHX Text
OF
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
PROJECT TITLE
AutoCAD SHX Text Project Number
AutoCAD SHX Text Project Manager
AutoCAD SHX Text Designer
AutoCAD SHX Text
IFOCV
AutoCAD SHX Text Facility Number
AutoCAD SHX Text Drawing Number
AutoCAD SHX Text
ULDF-19-0006AE
AutoCAD SHX Text
UPGRADE EMERGENCY
AutoCAD SHX Text
POWER AND FORCE
AutoCAD SHX Text
APRIL 22, 2020
AutoCAD SHX Text
PROTECTION,
AutoCAD SHX Text
TEST SITES
AutoCAD SHX Text
AutoCAD SHX Text
STAMP
AutoCAD SHX Text
WAK / GHS
AutoCAD SHX Text
WAK / GHS
AutoCAD SHX Text
JRM / WAK
AutoCAD SHX Text 100%%%
AutoCAD SHX Text
SUBMISSION
AutoCAD SHX Text k
AutoCAD SHX Text n
AutoCAD SHX Text
AutoCAD SHX Text S
AutoCAD SHX Text
AutoCAD SHX Text u
AutoCAD SHX Text o
AutoCAD SHX Text h
AutoCAD SHX Text t
AutoCAD SHX Text e
AutoCAD SHX Text S
AutoCAD SHX Text r
AutoCAD SHX Text t
AutoCAD SHX Text e
AutoCAD SHX Text t
AutoCAD SHX Text N
AutoCAD SHX Text a
AutoCAD SHX Text c
AutoCAD SHX Text
AutoCAD SHX Text U
AutoCAD SHX Text t
AutoCAD SHX Text i
AutoCAD SHX Text Y
AutoCAD SHX Text r
AutoCAD SHX Text o
AutoCAD SHX Text e
AutoCAD SHX Text w
AutoCAD SHX Text i
AutoCAD SHX Text g
AutoCAD SHX Text w
AutoCAD SHX Text T
AutoCAD SHX Text o
AutoCAD SHX Text E
AutoCAD SHX Text n
AutoCAD SHX Text n
AutoCAD SHX Text e
AutoCAD SHX Text n
AutoCAD SHX Text i
AutoCAD SHX Text r
AutoCAD SHX Text e
AutoCAD SHX Text e
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text g
AutoCAD SHX Text P
AutoCAD SHX Text
AutoCAD SHX Text C
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
PROPOSED FIRST FLOOR PLAN - BUILDING 1609
AutoCAD SHX Text
SCALE: 1/4" = 1'-0"
AutoCAD SHX Text
PROPOSED
AutoCAD SHX Text
FIRST FLOOR PLAN
AutoCAD SHX Text
- BUILDING 1609
AutoCAD SHX Text
AutoCAD SHX Text 19-0006-6
AutoCAD SHX Text
AutoCAD SHX Text W
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text
NORTH
C
C
C
C
C
C
I
CR
C
De
P
SW
I
AutoCAD SHX Text
EXIST. RECEIVER STANCHION
AutoCAD SHX Text
EXIST. CONCRETE FOUNDATION
AutoCAD SHX Text
EXIST. DRIVE STANCHION
AutoCAD SHX Text
EXIST. ALUMINUM EXTRUDED ARM
AutoCAD SHX Text
CARD READER
AutoCAD SHX Text
EDGE OF ROAD
AutoCAD SHX Text
TO BLDG.
AutoCAD SHX Text
PAVEMENT
AutoCAD SHX Text
CARD READER
AutoCAD SHX Text
INTERCOM STATION
AutoCAD SHX Text
CAMERA SUPPORT POLE
AutoCAD SHX Text
PROVIDE NEW ASPHALT PAVING PER DETAIL
AutoCAD SHX Text
IR BEAM (FURNISHED BY OWNER, CONTRACTOR TO INSTALL COMPLETE)
AutoCAD SHX Text SAFETY CLOSING LOOP 16'-0" LONG x 6'-0" WIDE x 14 AWG (CENTER BETWEEN ROAD AND ON ARM)
AutoCAD SHX Text
GATE PANEL FEEDER
AutoCAD SHX Text
2-#18 (24VDC) IN 1" PVC CONDUIT
AutoCAD SHX Text
LEAD-IN PORTION OF LOOP 2-#14 IN 3/4" PVC CONDUIT
AutoCAD SHX Text
COMMUNICATION JUNCTION BOX
AutoCAD SHX Text
1" PVC CONDUIT
AutoCAD SHX Text
MP-1
AutoCAD SHX Text
MP-2
AutoCAD SHX Text
EXIST. CONCRETE FOUNDATION
AutoCAD SHX Text
EXIST. FENCE
AutoCAD SHX Text
EXIST. FENCE
AutoCAD SHX Text
MOUNTING PEDESTAL, MP-1 (TYPICAL)
AutoCAD SHX Text
1" PVC CONDUIT
AutoCAD SHX Text
1" PVC CONDUIT
AutoCAD SHX Text
EXIST. SPARE 1" CONDUIT
AutoCAD SHX Text
EXIST. SPARE 1" CONDUIT
AutoCAD SHX Text
4" COMMUNICATIONS CONDUIT
AutoCAD SHX Text
GATE FEEDER
AutoCAD SHX Text
120 VOLT FEEDER
AutoCAD SHX Text
EDGE OF ROAD
AutoCAD SHX Text
TO BLDG.
AutoCAD SHX Text
PAVEMENT
AutoCAD SHX Text
FENCE
AutoCAD SHX Text
FENCE
AutoCAD SHX Text
DRIVE STANCHION
AutoCAD SHX Text
RECEIVER STANCHION
AutoCAD SHX Text
CONCRETE FOUNDATION
AutoCAD SHX Text
CONTROL ENCLOSURE
AutoCAD SHX Text SAWCUT AND REMOVE EXISTING ASPHALT PAVING AND ASSOCIATED BASE TO ALLOW FOR INSTALLATION OF NEW WIRING, CONDUIT, SAFETY CLOSING LOOP, ETC.
AutoCAD SHX Text
CONCRETE FOUNDATION
AutoCAD SHX Text
SPARE 1" CONDUIT
AutoCAD SHX Text
SPARE 1" CONDUIT
AutoCAD SHX Text
ROME
AutoCAD SHX Text
RESEARCH
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
ROME, NY
AutoCAD SHX Text
SIGNATURE
AutoCAD SHX Text
IFOCO
AutoCAD SHX Text
IFOCC
AutoCAD SHX Text
IFOC
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
COORDINATION
AutoCAD SHX Text
IFOCO
AutoCAD SHX Text
USER
AutoCAD SHX Text
USER
AutoCAD SHX Text
USER
AutoCAD SHX Text
SITE
AutoCAD SHX Text
IFOF
AutoCAD SHX Text
IFOS
AutoCAD SHX Text
DESIGN FIRM
AutoCAD SHX Text Date
AutoCAD SHX Text Drafter
AutoCAD SHX Text
REVISION
AutoCAD SHX Text
BY/DATE
AutoCAD SHX Text
SHEET TITLE
AutoCAD SHX Text
OF
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
PROJECT TITLE
AutoCAD SHX Text Project Number
AutoCAD SHX Text Project Manager
AutoCAD SHX Text Designer
AutoCAD SHX Text
IFOCV
AutoCAD SHX Text Facility Number
AutoCAD SHX Text Drawing Number
AutoCAD SHX Text
ULDF-19-0006AE
AutoCAD SHX Text
UPGRADE EMERGENCY
AutoCAD SHX Text
POWER AND FORCE
AutoCAD SHX Text
APRIL 22, 2020
AutoCAD SHX Text
PROTECTION,
AutoCAD SHX Text
TEST SITES
AutoCAD SHX Text
AutoCAD SHX Text
STAMP
AutoCAD SHX Text
WAK / GHS
AutoCAD SHX Text
WAK / GHS
AutoCAD SHX Text
JRM / WAK
AutoCAD SHX Text 100%%%
AutoCAD SHX Text
SUBMISSION
AutoCAD SHX Text k
AutoCAD SHX Text n
AutoCAD SHX Text
AutoCAD SHX Text S
AutoCAD SHX Text
AutoCAD SHX Text u
AutoCAD SHX Text o
AutoCAD SHX Text h
AutoCAD SHX Text t
AutoCAD SHX Text e
AutoCAD SHX Text S
AutoCAD SHX Text r
AutoCAD SHX Text t
AutoCAD SHX Text e
AutoCAD SHX Text t
AutoCAD SHX Text N
AutoCAD SHX Text a
AutoCAD SHX Text c
AutoCAD SHX Text
AutoCAD SHX Text U
AutoCAD SHX Text t
AutoCAD SHX Text i
AutoCAD SHX Text Y
AutoCAD SHX Text r
AutoCAD SHX Text o
AutoCAD SHX Text e
AutoCAD SHX Text w
AutoCAD SHX Text i
AutoCAD SHX Text g
AutoCAD SHX Text w
AutoCAD SHX Text T
AutoCAD SHX Text o
AutoCAD SHX Text E
AutoCAD SHX Text n
AutoCAD SHX Text n
AutoCAD SHX Text e
AutoCAD SHX Text n
AutoCAD SHX Text i
AutoCAD SHX Text r
AutoCAD SHX Text e
AutoCAD SHX Text e
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text g
AutoCAD SHX Text P
AutoCAD SHX Text
AutoCAD SHX Text C
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
TANNER HILL (MAIN GATE)
AutoCAD SHX Text
PROPOSED GATE PLAN -
AutoCAD SHX Text
SCALE: 1/4" = 1'-0"
AutoCAD SHX Text
TANNER HILL WEST (MAIN GATE)
AutoCAD SHX Text
EXISTING GATE PLAN -
AutoCAD SHX Text
SCALE: 1/4" = 1'-0"
AutoCAD SHX Text
GATE PLANS -
AutoCAD SHX Text
TANNER HILL
AutoCAD SHX Text
(MAIN GATE)
AutoCAD SHX Text
AutoCAD SHX Text 19-0006-5
AutoCAD SHX Text
GATE
N
CR
I
CR
I
C
C
C
C
N
N
N
P
C
C
C
C
C
N
C
New Gate
Brooks Road \055 Turnstile 4
Moody/Hanger Turnstile
South Turnstile
VCC Breaker for Power
DFAS Turnstile
D
D
D
N
D
N
C
C
CR
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
N
C
C
CR
C
C
CR
C
C
C
C
M
M
M
N
C
Pole
Pole
Pole
Pole
| B106 ITEC ET-101 |
| BLD. 105 |
| BLDG 3 |
| BLDG 106-101 |
| Depot 2_B1-Gym |
| FPU - Stockbridge Building 1477 |
| FPU - Tanner Hill Building 1609 |
| FPU - Tanner Hill Entrance Gate Detail |
| Irish hill_Newport |
| Turnstile Locations |
| Visitor Center |
File details come from the government source that posted it. Updated .