Attachment O_SVH_DOM_Family Dwellings.pdf

PDF 128 KB Posted

Attached to
R499--State Veterans Home (SVH) Nursing Homes
Solicitation number
36C10G24R0016
Issued by

About this file

This is a Physical Environment Inspection Report checklist used by the VHA State Veterans Home Per Diem Program to assess one- and two-family dwellings for compliance with NFPA 101-2012 Life Safety Code requirements per 38 CFR Part 51.350.

The checklist covers four primary inspection categories. Multiple Occupancies (Items 1-0 through 1-2) addresses egress requirements when residential units share buildings with nonresidential spaces, including fire barrier ratings and sprinkler system protections. Means of Escape Requirements (Items 2-1 through 2-21) evaluate primary and secondary escape routes from sleeping rooms and living areas, door specifications (minimum widths of 28 inches, heights of 6 feet 6 inches), accessibility of latching mechanisms (34-48 inches above floor), stairs and ramps with minimum 36-inch clear widths, hallway dimensions (36-inch width, 7-foot height minimum), and interior wall/ceiling finish ratings not exceeding Class C. Secondary means of escape options include remote doors/stairways, passages through non-lockable adjacent spaces, or operable windows meeting specific dimensional requirements (5.7 square feet minimum opening, 20-inch width, 24-inch height, 44-inch maximum sill height, with proximity to grade or approved rescue apparatus). Detection, Alarm, and Communications Systems (Items 3-1 through 3-3) mandate smoke alarms or detection systems in sleeping rooms, outside sleeping areas, and on each dwelling level, with monthly testing required. Heating, Ventilating, and Air-Conditioning (Items 4-1 through 4-2) requires proper installation per Section 9.2 and venting of fuel-fired heaters or use of approved unvented units. The checklist includes detailed NFPA 101-2012 code references for door operating forces and latching device specifications applicable to residential occupancies.

View the file

Other files

File Type Posted
36C10G24R0016 0002.docx DOCX document
Attachment A_SVH Master Survey Schedule Listing 01.pdf PDF
Past Performance Questionnaire Fillable.pdf PDF
36C10G24R0016 0001.docx DOCX document
36C10G24R0016 SVH.pdf PDF
Attachment Z_Survey Deficiency Summary Report Format 01.pdf PDF
Attachment U_ Final Survey Report Format 01.pdf PDF
Attachment C Observation Record - informational.pdf PDF
Answers Amendment 1 SVH.pdf PDF
Attachment BB Estimated Pricing Sheet.xlsx XLSX spreadsheet
Attachment W_Quick Reference Guide_Nursing Home.pdf PDF
Attachment N_SVH NH_DOM_ADHC_Combine Life Safety Checklist.pdf PDF
Attachment V_Life Safety Code Headings.pdf PDF
Attachment Z_Survey Deficiency Summary Report Format.pdf PDF
Attachment C_Observation Record.pdf PDF
Attachment H_VA Form 10-0144A.pdf PDF
Attachment R_Existing Day Care Occupancy Checklist.pdf PDF
36C10G24R0016.pdf PDF
Attachment P_SVH DOM Large Board and Care Life Safety Checklist.pdf PDF
Attachment D_Table of Surveyor Component Guide.pdf PDF
Attachment I_ VA Form 10-3567 Staffing Profile.pdf PDF
36C10G24R0016.docx DOCX document
Attachment Q_SVH DOM Small Board and Care Life Safey Checklist.pdf PDF
Attachment CC Detailed Price Cost Sheet.xlsx XLSX spreadsheet
Attachment M_SVH NH_DOM_Combine Life Safety Checklist.pdf PDF
Attachment S_Scope and Severity Matrix.pdf PDF
Attachment F_VA Form 10-0143A.pdf PDF
Attachment G_VA Form 10-0144.pdf PDF
Attachment A_SVH Master Survey Scheduling Listing.pdf PDF
Attachment Y_Quick Reference Guide_ADHC.pdf PDF
Attachment X_Quick Reference Guide_Domiciliary.pdf PDF
Attachment K_VA NFPA Interpretation for the SVH Program.pdf PDF
Attachment E_VA Form 10-0143.pdf PDF
Attachment J_VA Form 10-3567 Staffing Profile Reference.pdf PDF
Attachment T_IJ Template.pdf PDF
Attachment U_ Final Survey Report Format.pdf PDF
Attachment AA -Business Associate Agreement.docx DOCX document
Attachment B_Corrective Action Request Procedure and Form.pdf PDF
Attachment L_SVH NH_Life Safety Checklist.pdf PDF
Show all 39

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Page 1 of 6 (Revised 6/19)

VHA State Veterans Home Per Diem Program

Physical Environment Inspection Report

Checklist for One- and Two-Family Dwellings - NFPA 101-2012

All Code References are from NFPA 101-2012 according to 38 CFR Part 51.350

This checklist is a summation of the requirements found in Chapter 24, One and Two-Family Dwellings of the

2012 Edition of the Life Safety Code. This checklist is not intended to be comprehensive. The user is cautioned to consult the code prior to answering the following questions. (current as of 1-10-2021)

Facility Name:

Facility Address:

Date Inspected:

Inspected By:

Number of Residents:

Item Standard Reference Yes No N/A

Multiple Occupancies:

1-0 Is this a multiple occupancy? (If no, mark Items 1-0, 1-1, and 1-2 “N/A” and proceed to 2-1)

24.1.3

1-1 Does the sole means of egress of the dwelling unit go directly to the outside without passing through a nonresidential occupancy? OR, (if YES, stop right here and go to item 1-2.)

If the sole means of egress of the dwelling unit does pass through a nonresidential occupancy in the same building, is:

1. The building protected by an automatic sprinkler system, and does the sole means of egress from the dwelling unit of the residential occupancy not pass through a high hazard contents area as defined in 6.2.2.4;

OR,

2. The sole means of egress from the dwelling unit of the residential occupancy to the exterior separated from the remainder of the building by fire barriers having a fire resistance rating of not less than 1 hour in a non-sprinkler protected building, and does the sole means of egress from the dwelling unit of the residential occupancy not pass through a high hazard contents area as defined in

6.2.2.4?

24.1.3.1

24.1.3.2.1

24.1.3.2.2

One- and Two-Family Dwellings - NFPA 101-2012

Page 2 of 6 (Revised 6/19)

1-2 Where dwelling units of a residential occupancy are located above a nonresidential occupancy do they meet one of the following conditions?

1. The dwelling unit of the residential occupancy and exits therefore are separated from the nonresidential occupancy by construction having a fire resistance rating of not less than 1 hour, OR

2. The nonresidential occupancy is protected throughout by an approved, supervised automatic sprinkler system in accordance with Section 9.7, OR

3. The nonresidential occupancy is protected by an automatic fire detection system in accordance with

Section 9.6

24.1.3.3

Means of Escape Requirements:

Primary Means of Escape:

2-1 Does every sleeping room and every living area have at least one primary means of escape and is the primary means of escape a door, stairway, or ramp providing a means of unobstructed travel to the outside of the dwelling unit at street or ground level?

24.2.2.1.1

24.2.2.2

Secondary Means of Escape:

2-2 Does every sleeping room and every living area have a secondary means of escape OR, is one of the following conditions met:

1. The bedroom or living area has a door leading directly to the outside of the building at or to grade level, OR

2. The dwelling unit is protected throughout by an approved automatic sprinkler system in accordance with

24.3.5.

24.2.2.1.2

Is Item 2-3, OR 2-4 OR 2-5 met? Identify which is/are met and mark the other(s) “N/A”.

2-3 Is the secondary means of escape:

A door, stairway, passage, or hall providing a way of unobstructed travel to the outside of the dwelling at street or ground level that is independent of and remote from the primary means of escape, OR, 24.2.2.3.1

2-4 Is the secondary means of escape:

A passage through an adjacent non-lockable space, independent of and remote from the primary means of escape, to any approved means of escape, OR, 24.2.2.3.2

Page 3 of 6 (Revised 6/19)

2-5 Is the secondary means of escape:

An outside window or door operable from the inside without the use of tools, keys, or special effort and provides a clear opening of not less than 5.7 ft2. The width is not less than 20 inches and the height is not less than 24 inches. The bottom of the opening is not more than 44 inches above the floor. Such means of escape are acceptable where one of the following criteria is met:

a. The window is within 20 ft of grade.

b. The window is directly accessible to fire department rescue apparatus as approved by the authority having jurisdiction.

c. The window or door is open onto an exterior balcony.

d. Windows having a sill height below the adjacent ground level are provided with a window well meeting the following criteria:

1) The window well has horizontal dimensions that allow the window to be fully opened.

2) The window well has an accessible net clear opening of not less than 9 ft2 with a length and width of not less than 36 inches.

3) A window well with a vertical depth of more than 44 inches is equipped with an approved permanently affixed ladder or with steps meeting the following criteria:

a.) The ladder or steps do not encroach more than 6 inches into the required dimensions of the window well.

b.) The ladder or steps are not obstructed by the window.

24.2.2.3.3

Arrangement of Means of Escape.

2-6 Do all required paths of travel in the means of escape from any room to the outside pass through spaces that are under the immediate control of the occupant of the first room and not go through a bathroom or space subject to locking?

24.2.3

Doors.

2-7 Are all doors in the path of travel in the means of escape at least 28 inches wide unless, they are bathroom doors or doors serving a room no greater than 70 ft2 (these rooms are permitted to have doors that are no less than 24 inches wide)?

24.2.4.1

2-8 Are all doors at least 6 ft 6 inches nominal height? 24.2.4.3

2-9 Is every closet door latch such that children can open the door from inside the closet?

24.2.4.4

2-10 Can every bathroom door be opened from the outside during an emergency when locked?

24.2.4.5

Page 4 of 6 (Revised 6/19)

2-11 Are all doors in any means of escape unlocked against egress when the building is occupied and are all locking devices easily disengaged? {See Item 2-14}

24.2.4.7

2-12 Are the floor surfaces at each side of door openings in the primary means of escape within ½” of each other unless:

1. A door discharges to the outside or to an exterior balcony or exterior exit access where the floor level outside the door shall be permitted to be one step lower than the inside, but shall not be in excess of 7 in, OR;

2. A door at the top of a stair that opens directly at a stair, provided that the door does not swing over the stair and the door serves an area with an occupant load of fewer than 50 persons.

24.2.4.8

2-13 Are the forces to open doors not too difficult? (See

7.2.1.4.5 below.)

24.2.4.9

2-14 Do latching devices for doors comply with 7.2.1.5.10.

(See 7.2.1.5.10 below)

24.2.4.10

Stairs, Ramps, and Guards.

2-15 Do stairs, ramps, guards, and handrails comply with

24.2.5.1?

24.2.5.1

2-16 Are interior stairways properly illuminated? 24.2.5.2

2-17 For interior stairways, are manual lighting controls reachable and operable without traversing any step of the stair?

24.2.5.3

2-18 Is the clear width of stairs, landings, ramps, balconies, and porches not less than 36 inches?

24.2.5.4

Hallways.

2-19 Is the width of hallways, other than existing approved hallways, which shall be permitted to continue to be used, not less than 36 inches?

24.2.6.1

2-20 Is the height of hallways, other than existing approved hallways, which shall be permitted to continue to be used, not less than 7 ft nominal, with clearance below projections from the ceiling not less than 6 ft 8 inches nominal?

24.2.6.2

2-21 Interior Wall and Ceiling Finish. Are the interior wall and ceiling finish materials no worse than Class C?

24.3.3.2

Page 5 of 6 (Revised 6/19)

Detection, Alarm, and Communications Systems.

3-1 Are smoke alarms provided in accordance with 9.6.2.10 as follows: (battery operated smoke alarms are permitted and smoke alarms are not required to be interconnected in existing facilities)

1. In all sleeping rooms, and

2. Outside of each separate sleeping area, in the immediate vicinity of the sleeping rooms, and

3. On each level of the dwelling unit, including basements? OR

24.3.4

3-2 Is a smoke detection system provided in the same locations as above equipped with an approved means of occupant notification?

24.3.4.2

3-3 Are smoke alarms tested monthly in accordance with

NFPA 101 Chapter 72?

9.6.2.10

14.4.6

Heating, Ventilating, and Air-Conditioning.

4-1 Is the heating, ventilating, and air-conditioning equipment installed properly (in compliance with the provisions of Section 9.2.)?

24.5.1.1

4-2 Are fuel-fired heaters vented, OR are unvented fuel fired heaters listed and approved for use?

24.5.1.2

-End-

NFPA 101, 2012 Code References:

7.2.1.4.5 Door Leaf Operating Forces.

7.2.1.4.5.1 The forces required to fully open any door leaf manually in a means of egress shall not exceed 15 lbf

(67 N) to release the latch, 30 lbf (133 N) to set the leaf in motion, and 15 lbf (67 N) to open the leaf to the minimum required width, unless otherwise specified as follows:

(1) The opening forces for interior side-hinged or pivoted-swinging door leaves without closers shall not exceed

5 lbf (22 N).

(2) The opening forces for existing door leaves in existing buildings shall not exceed 50 lbf (222 N) applied to the latch stile.

(3) The opening forces for horizontal-sliding door leaves in detention and correctional occupancies shall be as provided in Chapters 22 and 23.

(4) The opening forces for power-operated door leaves shall be as provided in 7.2.1.9.

7.2.1.5.10* A latch or other fastening device on a door leaf shall be provided with a releasing device that has an obvious method of operation and that is readily operated under all lighting conditions.

7.2.1.5.10.1 The releasing mechanism for any latch shall be located as follows:

(1) Not less than 34 in. (865 mm) above the finished floor for other than existing installations

(2) Not more than 48 in. (1220 mm) above the finished floor

7.2.1.5.10.2 The releasing mechanism shall open the door leaf with not more than one releasing operation, unless otherwise specified in 7.2.1.5.10.3, 7.2.1.5.10.4, or 7.2.1.5.10.6.

7.2.1.5.10.3* Egress door assemblies from individual living units and guest rooms of residential occupancies shall be permitted to be provided with devices, including automatic latching devices, that require not more than one additional releasing operation, provided that such device is operable from the inside without the use of a key or tool and is mounted at a height not exceeding 48 in. (1220 mm) above the finished floor.

Page 6 of 6 (Revised 6/19)

A.7.2.1.5.10.3 Examples of devices that, when used with a latch, can be arranged to require not more than one additional releasing operation include night latches, dead bolts, and security chains.

7.2.1.5.10.4 Existing security devices permitted by 7.2.1.5.10.3shall be permitted to have two additional releasing operations.

7.2.1.5.10.5 Existing security devices permitted by 7.2.1.5.10.3, other than automatic latching devices, shall be located not more than 60 in. (1525 mm) above the finished floor.

7.2.1.5.10.6 Two releasing operations shall be permitted for existing hardware on a door leaf serving an area having an occupant load not exceeding three, provided that releasing does not require simultaneous operations.