Attachment I - H.08.04_BOF HEC Original Documents Drawings Vol 2 29 October 2021.pdf

PDF 47 MB Posted

Attached to
SOF BATTALION OPERATIONS FACILITY, HEC, ALEXANDRIA, VIRGINIA Federal contract opportunity
Solicitation number
W912DR22R0030
Issued by
Department of the Army Corps of Engineers Engineering District Baltimore

About this file

This solicitation is for construction services for the SOF Battalion Operations Facility (BOF1) at the HEC in Alexandria, Virginia. The U.S. Army Corps of Engineers, Baltimore District has been tasked with soliciting and awarding a competitive, firm-fixed-price construction contract using a best value tradeoff source selection process. The proposed project involves building the SOF Battalion Operations Facility according to the attached solicitation and drawings. Responses are due by the date specified in the solicitation, and award of the contract will occur shortly after.

View the file

Other files for this federal contract opportunity

Other files attached to SOF BATTALION OPERATIONS FACILITY, HEC, ALEXANDRIA, VIRGINIA, newest first.
File Type Posted
B.08.03 Amendment W912DR22R0030 0002.pdf PDF
Amendment 0002 Files.zip ZIP file
B.08.03 RFI Responses.pdf PDF
I.01.11 BOF1 Site Visit Attendance Roster - 25MAY22.pdf PDF
B.08.03 Amendment W912DR22R0030 0001.pdf PDF
Attachment K - BOF HEC Original Douments FFE Binder 29 October 2021.pdf PDF
Attachment E - Vol_2_BOF HEC Original Documents Submittal Specifications 29 October 2021.pdf PDF
Attachment D - Vol_1_BOF HEC Original Documents Submittal Specifications 29 October 2021.pdf PDF
Attachment L - Site Visit Visitor Authorization Form for HECSA.xlsx XLSX spreadsheet
Attachment H.1 - BOF HEC Original Documents Drawings Vol 1 29 October 2021.pdf PDF
Attachment C - SBPP Proposal Format.pdf PDF
Attachment B - Past Performance Questionnaire.pdf PDF
Attachment H.2 - BOF HEC Original Documents Drawings Vol 1 29 October 2021.pdf PDF
Attachment G - Vol_4_BOF HEC Original Documents Submittal Specifications 29 October 2021.pdf PDF
B.08.02 Solicitation_W912DR22R0030.pdf PDF
Attachment A - Experience in Relevant Projects.pdf PDF
Attachment J - BOF HEC Original Documents SID Binder 29 October 2021.pdf PDF
Attachment F - Vol_3_BOF HEC Original Documents Submittal Specifications 29 October 2021.pdf PDF
Show all 18

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

US Army Corps of Engineers

BALTIMORE DISTRICT

801 JONES FRANKLIN ROAD, SUITE 300

RALEIGH, NC 27606-3394

(919) 851-6866

(919) 851-7024 FAX

LICENSE # F-0672

ARCHITECTURAL MECHANICAL ELECTRICALCIVIL STRUCTURAL LIFE SAFETY &

FIRE PROTECTION

VICINITY MAP

~1" = 400'

LOCATION MAP

N.T.S.

SOLICITATION NO.: XXXXXX-XX-X-XXX

CONTRACT NO.: XXXXXX-XX-X-XXXX

ISSUE DATE: 29 OCTOBER 2021

VOLUME II OF II

PROJECT LOCATION

HUMPHREYS ENGINEER CENTER

CHARLOTTE | 704.295.4263

705 EAST MOREHEAD STREET, 28202

RALEIGH | 919.816.2907

3737 GLENWOOD AVENUE, SUITE 100, 27612

NC License No: C-2848

AME Project No: 17047

12359 SUNRISE VALLEY DRIVE

SUITE 350

RESTON, VA 20191

Phone: 703.476.5034 Fax: 703.476.5038 Web: www.rhinofpe.com

Rhino Fire Protection Engineering, PLLC

ENTRY GATE

TELECOMMUNICATIONS

APPROXIMATE HEC

PROPERTY LIMITS

HEC PROPERTY

BOUNDARY

PROJECT SITE

(7910 JOHN J. KINGMAN RD)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

A

B

C

D

E

F

G

H

J

K

L

M

N

P

SU

BM

IT

TE

D B

Y:

C H

EC

KE

D B

Y:

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

IS

SU

E D

AT

E:

SI

ZE

M

AR

K

D

ES

C R

IP

TI

O N

D

AT

E

SHEET ID

D R

AW

IN

G N

O

FI

LE

N

AM

E:

US Army Corps of Engineers

CONTROLLED UNCLASSIFIED INFORMATION

O

C

TO

BE

R

AN

SI

D

PROPERTY OF UNITED STATES GOVERNMENT, CONTROLLED UNCLASSIFIED INFORMATION (CUI). COPYING, DISSEMINATION, AND DISTRIBUTION TO UNAUTHORIZED INDIVIDUALS PROHIBITED

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S

BA

LT

IM

O R

E D

IS

TR

IC

T

H

O

PK

IN

S

PL

AZ

A

BA

LT

IM

O R

E M

AR

YL

AN

D

JO

NE

S

FR

AN

KL

IN

R

D, S

UI

TE

R

AL

EI

G

H , N

C

-3

(9

)8

-6

(9

) 8

-7

FA

X

LI

C

EN

SE

F -0

F1

-2 9-

XX

X-

XX

X-

XX

X

XX

X-

XX

X-

XX

X

H U

M

PH

R

EY

S

EN

G

IN

EE

R

C

EN

TE

R

, A

LE

XA

N

D R

IA

, V

IR

G

IN

IA

BA

TT

AL

IO

N O

PE

R

AT

IO

N S

FA

C

IL

IT

Y

PN

/ P

G-001

C O

VE

R

S H

EE

T

VO

LU

M E

II

O

F

II

M . B

EN

N

ET

T

M . B

EN

N

ET

T

W . B

YN

U

M

D . S

AL

TS

M

AN G

-0

_V

O L

II

O

F

II.

D W

G

HUMPHREYS ENGINEER CENTER, ALEXANDRIA, VIRGINIA

PN 91018 / P2 477925, BATTALION OPERATIONS FACILITY

10/29/2021

C O

M

MONWEALTH OF VIRGINIA

P

R O

FESSIONAL ENGIN

EE

R

PETER Q. LOMAX

Lic. No. 0402062554

10/29/2021

TITLESHEET ID. FILENAME TITLESHEET ID. FILENAMETITLEFILENAMESHEET ID.

FIRE ALARM AND MASS NOTIFICATION

FA001 FA001.DWG LEGEND, ABBREVIATIONS, AND FIRE ALARM GENERAL NOTES

FA101 FA101.DWG FIRE ALARM PLAN - LEVEL 1

FA102 FA102.DWG FIRE ALARM PLAN - LEVEL 2

FA103 FA103.DWG FIRE ALARM PLAN - LEVEL 3

FA501 FA501.DWG FIRE ALARM DETAILS

FA502 FA502.DWG FIRE ALARM RISER DIAGRAM

FA503 FA503.DWG FIRE ALARM OPERATING MATRIX

PLUMBING

P-001 P-001.DWG PLUMBING - GENERAL NOTES AND LEGENDS

PL121 PL121.DWG PLUMBING - LEVEL 1 PLAN - WASTE & VENT

PL122 PL122.DWG PLUMBING - LEVEL 2 PLAN - WASTE & VENT

PL123 PL123.DWG PLUMBING - LEVEL 3 PLAN - WASTE & VENT

PL131 PL131.DWG PLUMBING - LEVEL 1 PLAN - WATER AND GAS

PL132 PL132.DWG PLUMBING - LEVEL 2 PLAN - WATER

PL133 PL133.DWG PLUMBING - LEVEL 3 PLAN - WATER

PL141 PL141.DWG PLUMBING - ROOF PLAN

P-401 P-401.DWG PLUMBING - ENLARGED PLANS

P-402 P-402.DWG PLUMBING - ENLARGED PLANS

P-403 P-403.DWG PLUMBING - ENLARGED PLANS

P-501 P-501.DWG PLUMBING - DETAILS

P-502 P-502.DWG PLUMBING - DETAILS

P-601 P-601.DWG PLUMBING - SCHEDULES

P-701 P-701.DWG PLUMBING - SYSTEM CALCULATIONS

P-901 P-901.DWG PLUMBING - WASTE AND VENT RISER

P-902 P-902.DWG PLUMBING - WATER AND NATURAL GAS RISER

P-903 P-903.DWG PLUMBING - STORM RISER

MECHANICAL

M-001 M-001.DWG MECHANICAL - GENERAL NOTES AND LEGENDS

M-002 M-002.DWG MECHANICAL - GENERAL NOTES AND SEISMIC

MH101 MH101.DWG MECHANICAL - LEVEL 1 PLAN - DUCT & PIPE

MH102 MH102.DWG MECHANICAL - LEVEL 2 PLAN - DUCT & PIPE

MH103 MH103.DWG MECHANICAL - LEVEL 3 PLAN - DUCT & PIPE

MH104 MH104.DWG MECHANICAL - ROOF PLAN - DUCT & PIPE

MH201 MH201.DWG MECHANICAL - ENLARGED PLANS & SECTIONS

M-401 M-401.DWG MECHANICAL - PIPING DIAGRAMS

M-402 M-402.DWG MECHANICAL - PIPING DIAGRAMS

M-501 M-501.DWG MECHANICAL - DETAILS

M-502 M-502.DWG MECHANICAL - DETAILS

M-503 M-503.DWG MECHANICAL - DETAILS

M-504 M-504.DWG MECHANICAL - DETAILS

M-601 M-601.DWG MECHANICAL - SCHEDULES

M-602 M-602.DWG MECHANICAL - SCHEDULES

M-603 M-603.DWG MECHANICAL - SCHEDULES

M-701 M-701.DWG MECHANICAL - CONTROLS

M-702 M-702.DWG MECHANICAL - CONTROLS

M-703 M-703.DWG MECHANICAL - CONTROLS

M-704 M-704.DWG MECHANICAL - CONTROLS

M-705 M-705.DWG MECHANICAL - CONTROLS

M-706 M-706.DWG MECHANICAL - CONTROLS

M-707 M-707.DWG MECHANICAL - CONTROLS

M-801 M-801.DWG MECHANICAL - OUTDOOR AIR CALCULATIONS

M-802 M-802.DWG MECHANICAL - OUTDOOR AIR CALCULATIONS

INDEX OF DRAWINGS

ELECTRICAL

E-001 E-001.DWG ELECTRICAL - GENERAL NOTES AND LEGENDS

E-002 E-002.DWG ELECTRICAL - SYMBOL LEGEND & ENERGY SUMMARY

ES101 ES101.DWG ELECTRICAL - PARTIAL SITE PLAN

EG101 EG101.DWG ELECTRICAL - LIGHTNING PROTECTION AND GROUNDING

EG102 EG102.DWG ELECTRICAL - LEVEL 2 - RAISED FLOOR GROUNDING

EG103 EG103.DWG ELECTRICAL - LEVEL 3 - RAISED FLOOR GROUNDING

EL101 EL101.DWG ELECTRICAL - LEVEL 1 - LIGHTING PLAN

EL102 EL102.DWG ELECTRICAL - LEVEL 2 - LIGHTING PLAN

EL103 EL103.DWG ELECTRICAL - LEVEL 3 - LIGHTING PLAN

EL401 EL401.DWG ELECTRICAL - SECTIONS - LIGHTING PLANS

EP101 EP101.DWG ELECTRICAL - LEVEL 1 - POWER PLAN

EP102 EP102.DWG ELECTRICAL - LEVEL 2 - POWER PLAN

EP103 EP103.DWG ELECTRICAL - LEVEL 3 - POWER PLAN

EP401 EP401.DWG ELECTRICAL - ENLARGED - POWER PLANS

EP402 EP402.DWG ELECTRICAL - ENLARGED - POWER PLANS

E-501 E-501.DWG ELECTRICAL - DETAILS

E-502 E-502.DWG ELECTRICAL - DETAILS

E-503 E-503.DWG ELECTRICAL - DETAILS

E-504 E-504.DWG ELECTRICAL - DETAILS

E-505 E-505.DWG ELECTRICAL - DETAILS

E-506 E-506.DWG ELECTRICAL - DETAILS

E-601 E-601.DWG ELECTRICAL - POWER RISER DIAGRAM

E-602 E-602.DWG ELECTRICAL - GROUNDING RISER DIAGRAM

E-603 E-603.DWG ELECTRICAL - PANEL SCHEDULES

E-604 E-604.DWG ELECTRICAL - PANEL SCHEDULES

E-605 E-605.DWG ELECTRICAL - PANEL SCHEDULES

E-606 E-606.DWG ELECTRICAL - PANEL SCHEDULES

E-607 E-607.DWG ELECTRICAL - PANEL SCHEDULES

E-608 E-608.DWG ELECTRICAL - PANEL SCHEDULES

E-609 E-609.DWG ELECTRICAL - PANEL SCHEDULES

E-610 E-610.DWG ELECTRICAL - SCHEDULES

E-611 E-611.DWG ELECTRICAL - SCHEDULES

FIRE PROTECTION

FX001 FX001.DWG LEGEND, ABBREVIATIONS, AND SPRINKLER GENERAL NOTES

FX101 FX101.DWG FIRE PROTECTION PLAN - LEVEL1

FX102 FX102.DWG FIRE PROTECTION PLAN - LEVEL 2

FX103 FX103.DWG FIRE PROTECTION PLAN - LEVEL 3

FX501 FX501.DWG SPRINKLER DETAILS

FX502 FX502.DWG SPRINKLER DETAILS AND RISER DIAGRAM

G-003

IN

D

EX

O

F D

R

AW

IN

G

S

VO

LU

M

E

II

O F

II

M . B

EN

N

ET

T

M . B

EN

N

ET

T

W . B

YN

U

M

D . S

AL

TS

M

AN G

-0

_V

O L

II

O

F

II.

D W

G

TELECOMMUNICATIONS

T-001 T-001.DWG TELECOM/SECURITY - LEGEND & ABBREVIATIONS

T-002 T-002.DWG TELECOM/SECURITY - GENERAL NOTES

TS101 TS101.DWG TELECOM - SITE PLAN

TN101 TN101.DWG TELECOM - LEVEL 1 - PLAN

TN102 TN102.DWG TELECOM - LEVEL 2 - PLAN

TN103 TN103.DWG TELECOM - LEVEL 3 - PLAN

TN112 TN112.DWG TELECOM - LEVEL 2 - UNDERFLOOR PLAN

TN113 TN113.DWG TELECOM - LEVEL 3 - UNDERFLOOR PLAN

TN401 TN401.DWG TELECOM - ENLARGED PLANS

TN402 TN402.DWG TELECOM - ENLARGED PLANS

TN403 TN403.DWG TELECOM - ENLARGED PLANS

TN404 TN404.DWG TELECOM - ENLARGED PLANS

TN405 TN405.DWG TELECOM - ENLARGED PLANS

TN501 TN501.DWG TELECOM - DETAILS

TN502 TN502.DWG TELECOM - DETAILS

TN503 TN503.DWG TELECOM - DETAILS

TN504 TN504.DWG TELECOM - DETAILS

TN505 TN505.DWG TELECOM - DETAILS

TN506 TN506.DWG TELECOM - DETAILS

TN507 TN507.DWG TELECOM - DETAILS

TN601 TN601.DWG TELECOM - RISERS

TN602 TN602.DWG TELECOM - RISERS

TN603 TN603.DWG TELECOM - RISERS

TY101 TY101.DWG SECURITY - LEVEL 1 PLAN

TY102 TY102.DWG SECURITY - LEVEL 2 PLAN

TY103 TY103.DWG SECURITY - LEVEL 3 PLAN

TY501 TY501.DWG SECURITY - DETAILS

TY502 TY502.DWG SECURITY - DETAILS

TY503 TY503.DWG SECURITY - DETAILS

TY504 TY504.DWG SECURITY - DETAILS

TY601 TY601.DWG SECURITY - RISERS

TY602 TY602.DWG SECURITY - RISERS

AUDIO VISUAL

TA001 TA001.DWG AUDIO VISUAL - SYMBOLS & ABBREVIATIONS

TA101 TA101.DWG AUDIO VISUAL - LEVEL 1 PLAN

TA102 TA102.DWG AUDIO VISUAL - LEVEL 2 PLAN

TA103 TA103.DWG AUDIO VISUAL - LEVEL 3 PLAN

TA401 TA401.DWG AUDIO VISUAL - ENLARGED PLANS

TA402 TA402.DWG AUDIO VISUAL - ENLARGED PLANS

TA501 TA501.DWG AUDIO VISUAL - LOGICAL DIAGRAMS

TA502 TA502.DWG AUDIO VISUAL - LOGICAL DIAGRAMS

TA503 TA503.DWG AUDIO VISUAL - TYPICAL ELEVATION DETAILS

TA504 TA504.DWG AUDIO VISUAL - RISER DIAGRAMS

GENERAL

G-001 G-001.DWG COVER SHEET - VOLUME II OF II

G-002 G-002.DWG INDEX OF DRAWINGS - VOLUME I OF II

G-003 G-003.DWG INDEX OF DRAWINGS - VOLUME II OF II

G-004 G-004.DWG INSTALLATION MAP AND PROJECT LOCATION MAP

G-005 G-005.DWG GENERAL CONSTRUCTION NOTES

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

A

B

C

D

E

F

G

H

J

K

L

M

N

P

SU

BM

IT

TE

D B

Y:

C H

EC

KE

D B

Y:

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

IS

SU

E D

AT

E:

SI

ZE

M

AR

K

D

ES

C R

IP

TI

O N

D

AT

E

SHEET ID

D R

AW

IN

G N

O

FI

LE

N

AM

E:

US Army Corps of Engineers

CONTROLLED UNCLASSIFIED INFORMATION

O

C

TO

BE

R

AN

SI

D

PROPERTY OF UNITED STATES GOVERNMENT, CONTROLLED UNCLASSIFIED INFORMATION (CUI). COPYING, DISSEMINATION, AND DISTRIBUTION TO UNAUTHORIZED INDIVIDUALS PROHIBITED

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S

BA

LT

IM

O R

E D

IS

TR

IC

T

H

O

PK

IN

S

PL

AZ

A

BA

LT

IM

O R

E M

AR

YL

AN

D

JO

NE

S

FR

AN

KL

IN

R

D, S

UI

TE

R

AL

EI

G

H , N

C

-3

(9

)8

-6

(9

) 8

-7

FA

X

LI

C

EN

SE

F -0

F1

-2 9-

XX

X-

XX

X-

XX

X

XX

X-

XX

X-

XX

X

H U

M

PH

R

EY

S

EN

G

IN

EE

R

C

EN

TE

R

, A

LE

XA

N

D R

IA

, V

IR

G

IN

IA

BA

TT

AL

IO

N O

PE

R

AT

IO

N S

FA

C

IL

IT

Y

PN

/ P

FIRE ALARM GENERAL NOTES LEGEND ABBREVIATIONS

A AMP

ABV ABOVE

ACU AUTONOMOUS CONTROL UNIT

A/E ARCHITECT/ENGINEER (OF RECORD)

ANSI AMERICAN NATIONAL STANDARDS INSTITUTE

A/S AUTOMATIC SPRINKLER

AWG AMERICAN WIRE GAGE

BLDG BUILDING

BOB BOTTOM OF BEAM

BOJ BOTTOM OF JOIST

C CEILING

CLO CLOSET

CMU CONCRETE MASONRY UNIT

COM COMMUNICATIONS

CONT CONTINUED

CORR CORRIDOR

DS DRY SPRINKLER

E EXISTING DEVICE

EC EXTENDED COVERAGE SPRINKLER

ELEC ELECTRIC

EOLR END OF LINE RESISTOR

EXIST EXISTING

FACP FIRE ALARM CONTROL PANEL

FDC FIRE DEPARTMENT CONNECTION

FPL NON-PLENUM ALARM CABLE

GPM GALLONS PER MINUTE

IDC INITIATING DEVICE CIRCUIT

IN INCH

J.C. JANITOR'S CLOSET

LAT LAY-IN ACOUSTICAL TILE

LED LIGHT EMITTING DIODE

MACH MACHINE

MECH MECHANICAL ROOM

MI MINERAL INSULATED

MFG MANUFACTURER

MNS MASS NOTIFICATION SYSTEM

MPS MANUAL PULL STATION

NAC NOTIFICATION APPLIANCE CIRCUIT

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NO. NUMBER

NOS. NUMBERS

NPT NATIONAL PIPE THREAD

NTS NOT TO SCALE

OPG OPENING

OS&Y OUTSIDE STEM AND YOKE

P PHASE

P.S. PIPE SHAFT

PSI POUNDS PER SQUARE INCH

QR QUICK RESPONSE

RM ROOM

SLC SIGNALING LINE CIRCUIT

SPKLR SPRINKLER

SSU STANDARD SPRAY UPRIGHT

STDP STANDPIPE

SF SQUARE FOOT

SPD SURGE PROTECTION DEVICE

STO STORAGE

TC TERMINAL CABINET

THHN-THWN THERMOPLASTIC HEAT AND WATER-RESISTANT NYLON COATED WIRE

TOJ TOP OF JOIST

UL UNDERWRITERS LABORATORIES

UNO UNLESS NOTED OTHERWISE

VAC VOLTS ALTERNATING CURRENT

WP WEATHER PROOF

W/ WITH

ADDRESSABLE SMOKE DETECTOR, CEILING MOUNTED

ADDRESSABLE HEAT DETECTOR

ADDRESSABLE DUCT SMOKE DETECTOR

CARBON MONOXIDE DETECTOR

MANUAL PULL STATION

STROBE, WALL MOUNTED, WITH CANDELA RATING

STROBE, CEILING MOUNTED, WITH CANDELA RATING

SPEAKER

SPEAKER STROBE, WITH CANDELA RATING

ADDRESSABLE INTERFACE

ADDRESSABLE RELAY

WATER FLOW SWITCH

SUPERVISORY TAMPER SWITCH

REMOTE LED AND TEST SWITCH

FIRE ALARM CONTROL PANEL WITH INTEGRATED MASS

NOTIFICATION SYSTEM ACU

FIRE ALARM TERMINAL CABINET

LOCAL OPERATING CONSOLE

FIRE ALARM ANNUNCIATOR PANEL

SPEAKER CIRCUIT AMPLIFIER

LED MESSAGE BOARD

TRANSIENT SURGE SUPPRESSOR

NOTIFICATION APPLIANCE CIRCUIT

DIGITAL ALARM RADIO TRANSMITTER

SECURE AREA PERIMETER

1 HOUR FIRE BARRIER

END OF LINE RESISTOR

SUBSCRIPTS

WEATHER PROOF

ELEVATOR DESIGNATION

CEILING MOUNTED

JO

NE

S

FR

AN

KL

IN

R

D, S

UI

TE

R

AL

EI

G

H , N

C

-3

(9

1-

(9

) 8

-7

FA

X

LI

C

EN

SE

F -0

US Army Corps of Engineers ®

SHEET ID

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

1 2 3 4 5 6 7 8 9 10

A

D

AT

E M

AR

K

D

ES

C R

IP

TI

O N

BA

LT

IM

O

R E

D

IS

TR

IC

T

H O

PK

IN

S

PL

AZ

A

BA

LT

IM

O

R E

M

AR

YL

AN

D

FI

LE

N

AM

E:

FOR OFFICIAL USE ONLY

XX

X-

XX

X-

XX

X

XX

X-

XX

X-

XX

X

B

C

D

E

F

G

H

J

K

L

M

N

P

11 12 13 14 15 16 17 18 19 20

D R

AW

IN

G N

O

F1

-2 9-

FA001

LE

G

EN

D

, A

BB

R

EV

IA

TI

O N

S, A

N D

F

IR

E

AL

AR

M

G

EN

ER

AL

N O

TE

S

H U

M

PH

R

EY

S

EN

G

IN

EE

R

C

EN

TE

R

, A

LE

XA

N

D R

IA

, V

IR

G

IN

IA

PL

O

M

AX

H N

IC

KL

E/

BH

AN

BI

C

KI

W

BY

N U

M

FE

SC

AL

AN

TE

O

C

TO

BE

R

FA

1.

D

W G

BA

TT

AL

IO

N O

PE

R

AT

IO

N S

FA

C

IL

IT

Y

PN

/ P

S

AMP

RM

FACP

FATC

LOC

S

F

S

AI

AR

WF

VS

LED

SS

1. SCOPE OF WORK INCLUDES PROVIDING A NEW INTEGRATED ANALOG ADDRESSABLE FIRE ALARM AND MASS NOTIFICATION SYSTEM THROUGHOUT THE BUILDING. THE SCOPE INCLUDES BUT IS NOT LIMITED TO A NEW FIRE ALARM/MASS NOTIFICATION CONTROL PANEL/MODULES/POWER SUPPLIES, SPRINKLER SYSTEM SUPERVISION, ALARM NOTIFICATION DEVICES, MANUAL PULL STATIONS, SYSTEM SMOKE/HEAT DETECTORS, SPEAKER AND STROBES FOR OCCUPANT NOTIFICATION, WIRING, CONDUIT AND ALL OTHER ASSOCIATED EQUIPMENT. THE WORK INCLUDES ALL LABOR, EQUIPMENT AND MATERIALS, SOFTWARE, AND PROGRAMMING WHETHER MENTIONED OR NOT FOR A COMPLETE SYSTEM PER THE RFP AND APPLICABLE CODES, INCLUDING SMOKE SENSORS, ADDRESSABLE INTERFACE AND RELAY DEVICES, TERMINAL CABINETS, CONDUIT, WIRE, JUNCTION BOXES, FASTENERS, HANGERS, ETC. ALL ENGINEERING DESIGN WORK AND INSTALLATION SHALL

CONFORM WITH THE APPLICABLE PROVISIONS OF THE FOLLOWING CODES:

-UFC 3-600-01, FIRE PROTECTION ENGINEERING FOR FACILITIES, CHANGE 3, MAY 2019

-UFC 4-021-01, DESIGN AND O&M: MASS NOTIFICATION SYSTEMS, CHANGE 1, JANUARY 2010

-NFPA 70, NATIONAL ELECTRIC CODE, 2017 EDITION

-NFPA 72, NATIONAL FIRE ALARM AND SIGNALING CODE, 2019 EDITION

-OTHER CODES AND STANDARDS INDICATED IN THE SPECIFICATIONS

2. PROVIDE CLASS B NOTIFICATION APPLIANCE CIRCUITS, AND CLASS B SLC CIRCUITS.

3. PROVIDE NEW ADDRESSABLE SIGNALING LINE CIRCUITS (SLC) TO MONITOR FIRE ALARM DEVICES, SPRINKLER SYSTEM WATER FLOW AND SUPERVISORY DEVICES. PROVIDE NEW NOTIFICATION APPLIANCE CIRCUITS (NAC)

TO MONITOR AND CONTROL NOTIFICATION APPLIANCES.

4. ALL WIRING AND CIRCUITS SHALL BE PROVIDED IN ELECTRICAL METALLIC TUBING CONCEALED ABOVE THE CEILING OR BEHIND THE WALLS. MINIMUM TRADE SIZE IS 3/4 IN. NO CIRCUITS SHALL BE SUPPORTED FROM SPRINKLER PIPING. ALL CIRCUITS SHALL HAVE PATHWAYS SURVIVABILITY LEVEL 1 PER NFPA 72 SECTION 12.4.2.

5. SEE DETAIL SHEET FA503 FOR FIRE ALARM OPERATING SEQUENCE.

6. AUDIBLE (SPEAKERS) AND VISUAL (STROBES) NOTIFICATION APPLIANCES SHALL BE PROVIDED THROUGHOUT THE BUILDING IN ACCORDANCE WITH NFPA 72, UFC 3-600-01 SECTION 9-18.6, AND UFC 4-021-01 SECTION 4-6.

INSTALL WALL MOUNTED STROBES SO THAT THE ENTIRE STROBE LENS IS BETWEEN 80 AND 96 INCHES ABOVE THE FINISHED FLOOR. STROBES SHALL HAVE CLEAR LENSES AND BE PROVIDED WITH AN "ALERT" LABEL.

7. PULL STATION SHALL BE DOUBLE-ACTION, INSTALLED WITH OPERATING LEVER MOUNTED AT 44-INCHES AFF

WITHIN 5 FEET OF EACH EXIT DOORWAY.

8. PROVIDE SMOKE DETECTOR WITHIN 5 FEET OF NEW FIRE ALARM CONTROL PANEL AND FIRE ALARM

TRANSPONDER PANELS.

9. DRAWINGS AND REFLECTED CEILING PLANS ARE PROVIDED FOR REFERENCE ONLY; SEE ARCHITECTURAL AND STRUCTURAL DRAWINGS FOR CEILING TYPES, CEILING HEIGHTS, FIXTURE LOCATIONS, BEAMS, AND

OBSTRUCTIONS.

10. FIRE ALARM CONTRACTOR TO MAKE ALL ELECTRICAL CONNECTION TO ALL CONTROL VALVES, WATERFLOW SWITCHES, AND TAMPER SWITCH DEVICES AS WELL AS PROVIDE ALL DEVICES RELATED TO SPRINKLER

SYSTEM.

11. THE NEW FIRE ALARM CONTROL PANEL SHALL BE CAPABLE OF MONITORING ALL OF THE ADDRESSABLE DEVICES, STROBE BOOSTER POWER SUPPLIES, AND AMPLIFIERS TO POWER ALL SPEAKERS. THE NEW FIRE ALARM CONTROL PANEL SHALL ALSO PROVIDE SUFFICIENT POWER AND AMPLIFICATION FOR ALL NEW SLC DEVICES, STROBES, SPEAKERS, ANNUNCIATOR PANEL, AS WELL AS 24VDC FOR DUCT SMOKE DETECTORS.

THE FACP SHALL HAVE INTEGRATED BATTERY BACKUP SIZED FOR 48 HOURS OF SUPERVISORY CONDITIONS FOLLOWED BY 60 MINUTES OF MASS NOTIFICATION AT THE MAXIMUM CONNECTED LOAD. FACP WILL BE ABLE TO ACCEPT LOW-LEVEL AUDIO INPUT FOR MASS NOTIFICATION MESSAGING. PRE-PROGRAMMED MASS

NOTIFICATION MESSAGES WILL BE COORDINATE WITH INSTALLATION OFFICIALS.

12. THE FACP WILL BE TIED INTO THE INSTALLATION WIDE REPORTING SYSTEM VIA A KING-FISHER TRANSCEIVER.

THE KING-FISHER TRANSCEIVER CONNECTS THE FIRE ALARM SYSTEM TO THE FIRE DEPARTMENT RECEIVING

STATION LOCATED AT 6100 ABBOTT ROAD.

13. PROVIDE REMOTE GRAPHIC ANNUNCIATOR. INSTALL ANNUNCIATOR SEMI-FLUSH ONTO WALL NEAR MAIN

ENTRANCE.

14. A LABEL SHALL BE PROVIDED AT ALL MEANS OF DISCONNECT INDICATING THE SOURCE CIRCUIT AND

EQUIPMENT THEY SERVE.

15. PROVIDE A MNS/FIRE ALARM SUBPANEL WITHIN THE SECURE AREA WITH OPTICAL FIBER BACKBONE TO THE BUILDING SYSTEM. OPTICAL FIBER SHALL HAVE NO METALLIC SHIELDING, CLADDING, OR STRENGTH

MEMBERS.

16. EXTERIOR WEATHERPROOF FIRE ALARM/MNS SPEAKER SHALL NOT BE PROVIDED/WIRED FROM A SECURE AREA. THIS SHALL REQUIRE EXTERIOR SPEAKERS TO BE FED BY RIGID CONDUIT FROM A REMOTE LOCATION.

WP

E

C

DART

xxCD xxCD xxCD

FAA

NAC

EOLR

O

FESSIONAL ENGIN

EE

R

PETER Q. LOMAX

Lic. No. 0402062554

F

F F

S

S

F

S

S

S

F

S

S

SS

S

S

F

F

S

S S S

S

S S

F F F F FF

F

GSB (STE) 3 BAY

GARAGE

GSB FCC

LOGISTICS AREA

& SECURE

LOADOUT

LOADOUT

GSB FCC MISSION

SUPPORT

DMARC

FCO TEAM CAGE

GSB MISSION

TEAM CAGE

FCO TEAM CAGE

FCO TEAM CAGE

MECHANICAL

ELEVATOR

EL-1

MEN

WOMEN

ENTRY

VESTIBULE

CORRIDOR

COLLATERAL

FIRE

ELECTRICAL

CONFERENCE

MEETING AREA

CORRIDOR

CORRIDOR

PERSONAL

CAGES

STAIR 1

S-1

STAIR 2

S-2

SALLY PORT

WELLNESS

TR

CORRIDOR

S4 STORAGE

STORAGE

JC

CORRIDOR

RECEPTION AREA

108ELEVATOR LOBBY

CORRIDOR

GE.5CBA D EB.5 F

3.5

2.9

2.3

FAA LOC

FACPDARTAMP

NAC

S

15cd 15cd

30cd

15cd 75cd

15cd

15cd

15cd

15cd

30cd

15cd

15cd

15cd

15cd

15cd

30cd

110cd

30cd

75cd

15cd

15cd

15cd

75cd

75cd

110cd

75cd

AI AI

WFVS

AI

AIWF

VS

AIVS

AI

VS3 1

E

AI

AI AR

ARAR

AI

AIWF

VS

FA

C

P

AM

P N

AC

S

LOC

S S

AR

S

AR

WP

WP WP

WP

WP

WP

LE

D

10 11

WP

15cd

15cd

15cd

15cd

15cd

15cd

15cd

15cd

S

LEDLED

LE

D

S

LED

15cd

15cd

15cd

75cd

15cd

C

C

C

C

C

C

75cd

ELECTRICAL

AI 14

JO

NE

S

FR

AN

KL

IN

R

D, S

UI

TE

R

AL

EI

G

H , N

C

-3

(9

1-

(9

) 8

-7

FA

X

LI

C

EN

SE

F -0

US Army Corps of Engineers ®

SHEET ID

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

1 2 3 4 5 6 7 8 9 10

A

D

AT

E M

AR

K

D

ES

C R

IP

TI

O N

4' 8' 16'

PROJECT

NORTH

TRUE

NORTH

BA

LT

IM

O

R E

D

IS

TR

IC

T

H O

PK

IN

S

PL

AZ

A

BA

LT

IM

O

R E

M

AR

YL

AN

D

FI

LE

N

AM

E:

FOR OFFICIAL USE ONLY

XX

X-

XX

X-

XX

X

XX

X-

XX

X-

XX

X

B

C

D

E

F

G

H

J

K

L

M

N

P

11 12 13 14 15 16 17 18 19 20

D R

AW

IN

G N

O

F1

-2 9-

FA101

FI

R

E

AL

AR

M

P

LA

N

LE

VE

L

H U

M

PH

R

EY

S

EN

G

IN

EE

R

C

EN

TE

R

, A

LE

XA

N

D R

IA

, V

IR

G

IN

IA

PL

O

M

AX

H N

IC

KL

E/

BH

AN

BI

C

KI

W

BY

N U

M

FE

SC

AL

AN

TE

O

C

TO

BE

R

FA

1.

D

W G

BA

TT

AL

IO

N O

PE

R

AT

IO

N S

FA

C

IL

IT

Y

PN

/ P

1/8" = 1'-0"FA101

1 FIRE ALARM PLAN - LEVEL 1

# SHEET NOTES

1. PROVIDE ADDRESSABLE INTERFACES TO

MONITOR BACKFLOW PREVENTER.

2. PROVIDE ADDRESSABLE INTERFACE TO

MONITOR SPRINKLER SYSTEM RISER

FLOW SWITCH.

3. PROVIDE ADDRESSABLE INTERFACE TO

MONITOR CONTROL VALVE OF THE

BACKFLOW PREVENTER TEST HEADER

SUPERVISED IN NORMALLY CLOSED

CONDITION.

4. PROVIDE ADDRESSABLE INTERFACES TO

MONITOR SPRINKLER SYSTEM CONTROL

VALVE AND FLOW SWITCH.

5. ALL INCOMING WIRING SHALL BREACH

THE SECURE PERIMETER AT ONE POINT.

PROVIDE A DIELECTRIC BREAK WHERE

THE FIRE ALARM CONDUIT PENETRATES

THE SECURE AREA PERIMETER.

6. PROVIDE ADDRESSABLE RELAY FOR THE

ELEVATOR PRIMARY AND ALTERNATIVE

RECALL, FIREMAN'S HAT AND MONITOR

SHUNT TRIP POWER.

7. PROVIDE MASTER CONTROL OVER HVAC

POWER AT LOC.

8. PROVIDE ADDRESSABLE INTERFACE TO

MONITOR ZONE CONTROL VALVE FOR

NON-SECURE AREA.

9. COORDINATE DUCT SMOKE DETECTORS

WITH MECHANICAL DRAWINGS.

10. EXTERIOR WEATHERPROOF SPEAKERS

LOCATED ON SECURE AREA WALLS SHALL

BE PIPED IN RIGID CONDUIT FROM A

REMOTE LOCATION AND NOT BE WIRED

FROM A SECURE SPACE. EXTERIOR

WEATHERPROOF SPEAKER TO BE PIPED

THROUGH WALL AT ROOM #118 AND

ACROSS THE EXTERIOR WALL.

11. THE SECURE AREA BOUNDARY SHALL BE

PENETRATED IN ONLY ONE LOCATION AS

REQUIRED PER UFC 4-010-05.

12. DEVICES, APPLIANCES, AND ASSOCIATED

CONDUIT MOUNTED INSIDE THE SECURE

AREA BOUNDARY WALLS ARE TO BE

SURFACE MOUNTED TO COMPLY WITH

UFC 4-010-05. MEMBRANE PENETRATIONS

ARE NOT PERMITTED.

13. MANUAL PULL STATION SHALL BE

SURFACE MOUNTED.

14. PROVIDE ADDRESSABLE INTERFACE TO

MONITOR THE POST-INDICATOR VALVE.

O

FESSIONAL ENGIN

EE

R

PETER Q. LOMAX

SS

S

S

SS S

ELEVATOR

EL-1

FCC LAB

STAIR 1

S-1

FARADAY CAGE

IT/COMMS

STORAGE

MECHANICAL

TR

WOMEN

MEN

FCC TEAM 4

FCC TEAM 3

STAIR 2

S-2

FCC TEAM 1

FCC TEAM 2

BREAK AREA

OPEN OFFICE

CORRIDOR

UPS

O4 PRIVATE

OFFICE

O4 PRIVATE

OFFICE

O4 PRIVATE

OFFICE

CONFERENCE

ROOM

FCC CUBES

GE.5CBA D EB.5 F

3.5

2.9

2.3

WP WP

WP

AI AI

WFVS

FA

TC

E

C C

C C C

C

C

C

C C

C

C C

C

C

C

C

C

C

C

C

C

15cd30cd 15cd

15cd

75cd

30cd

30cd

15cd

30cd

30cd

30cd

15cd

15cd

30cd

30cd

30cd

30cd

30cd

30cd

30cd

30cd

30cd

N

AC

C 15cd

S

LO

C

S

AR

S

AR

LE

D

S

LED

15cd

15cd

5 S

WP

75cd

15cd

WP

15cd

JO

NE

S

FR

AN

KL

IN

R

D, S

UI

TE

R

AL

EI

G

H , N

C

-3

(9

1-

(9

) 8

-7

FA

X

LI

C

EN

SE

F -0

US Army Corps of Engineers ®

SHEET ID

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

1 2 3 4 5 6 7 8 9 10

A

D

AT

E M

AR

K

D

ES

C R

IP

TI

O N

4' 8' 16'

PROJECT

NORTH

TRUE

NORTH

BA

LT

IM

O

R E

D

IS

TR

IC

T

H O

PK

IN

S

PL

AZ

A

BA

LT

IM

O

R E

M

AR

YL

AN

D

FI

LE

N

AM

E:

FOR OFFICIAL USE ONLY

XX

X-

XX

X-

XX

X

XX

X-

XX

X-

XX

X

B

C

D

E

F

G

H

J

K

L

M

N

P

11 12 13 14 15 16 17 18 19 20

D R

AW

IN

G N

O

F1

-2 9-

FA102

FI

R

E

AL

AR

M

P

LA

N

LE

VE

L

H U

M

PH

R

EY

S

EN

G

IN

EE

R

C

EN

TE

R

, A

LE

XA

N

D R

IA

, V

IR

G

IN

IA

PL

O

M

AX

H N

IC

KL

E/

BH

AN

BI

C

KI

W

BY

N U

M

FE

SC

AL

AN

TE

O

C

TO

BE

R

FA

2.

D

W G

BA

TT

AL

IO

N O

PE

R

AT

IO

N S

FA

C

IL

IT

Y

PN

/ P

1/8" = 1'-0"FA102

1 FIRE ALARM PLAN - LEVEL 2

# SHEET NOTES

1. PROVIDE ADDRESSABLE INTERFACES TO

MONITOR SPRINKLER SYSTEM CONTROL

VALVE AND FLOW SWITCH.

2. SPEAKER/STROBE PLACED IN

CONJUNCTION WITH DATA FILTER.

3. COORDINATE DUCT SMOKE DETECTORS

WITH MECHANICAL DUCTS.

4. PROVIDE MASTER CONTROL OVER HVAC

POWER AT LOC.

5. DEVICES, APPLIANCES, AND ASSOCIATED

CONDUIT MOUNTED ON SECURE AREA

BOUNDARY WALLS ARE TO BE SURFACE

MOUNTED TO COMPLY WITH UFC 4-010-05.

MEMBRANE PENETRATIONS ARE NOT

PERMITTED.

O

FESSIONAL ENGIN

EE

R

PETER Q. LOMAX

S

S

S

S

S

S

SSSSSSS

SS

SS

S

S

S

S

F

S

S

ELEVATOR

EL-1

MEN

WOMEN

MECHANICAL

TR

G4 PRIVATE

OFFICE

G4 PRIVATE

OFFICE

SPO PRIVATE

OFFICE

SPO PRIVATE

OFFICE

S3 PRIVATE

OFFICE

S3 PRIVATE

OFFICE

HHT PRIVATE

OFFICE

CG CONFERENCE

ROOM

CONFERENCE

ROOM

CG PRIVATE

OFFICE

TOILET

CG PRIVATE

OFFICE

CG PRIVATE

OFFICE

BREAK AREA

PSYCH OFFICE

CG PRIVATE

OFFICE

STAIR 1

S-1

STAIR 2

S-2

SCT SERVICE

AREA

WAITING AREA

OPEN OFFICE

AREA

CLASSROOM

S4 CUBES

CHAPLAIN OFFICE

CORRIDOR

GE.5CBA D EB.5 F

3.5

2.9

2.3 30cd

30cd 15cd 15cd

15cd

30cd

15cd

30cd

30cd

15cd

15cd

15cd

75cd

30cd

30cd

WP WP

WP WP

75cd75cd

WP

AI

AI

AI

AI

WF

WF

VS

VS

FA

TC

E

C

C

C C C C C C C

C C

C

C

CC

C

C

CC

C

C

C

C

CC

CC

C

N

AC

30cd

C C

LO

C

S

S

AR

AR

LE

D

S

LED

15cd 15cd

6 7

AI 8

WP

15cd

JO

NE

S

FR

AN

KL

IN

R

D, S

UI

TE

R

AL

EI

G

H , N

C

-3

(9

1-

(9

) 8

-7

FA

X

LI

C

EN

SE

F -0

US Army Corps of Engineers ®

SHEET ID

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

1 2 3 4 5 6 7 8 9 10

A

D

AT

E M

AR

K

D

ES

C R

IP

TI

O N

4' 8' 16'

PROJECT

NORTH

TRUE

NORTH

BA

LT

IM

O

R E

D

IS

TR

IC

T

H O

PK

IN

S

PL

AZ

A

BA

LT

IM

O

R E

M

AR

YL

AN

D

FI

LE

N

AM

E:

CONTROLLED UNCLASSIFIED INFORMATION

XX

X-

XX

X-

XX

X

XX

X-

XX

X-

XX

X

B

C

D

E

F

G

H

J

K

L

M

N

P

11 12 13 14 15 16 17 18 19 20

D R

AW

IN

G N

O

F1

-2 9-

PROPERTY OF UNITED STATES GOVERNMENT, CONTROLLED UNCLASSIFIED INFORMATION (CUI), DISSEMINATION, AND DISTIBUTION TO AUTHORIZED INDIVIDUALS PROHIBITED

FA103

FI

R

E

AL

AR

M

P

LA

N

LE

VE

L

H U

M

PH

R

EY

S

EN

G

IN

EE

R

C

EN

TE

R

, A

LE

XA

N

D R

IA

, V

IR

G

IN

IA

PL

O

M

AX

H N

IC

KL

E/

BH

AN

BI

C

KI

W

BY

N U

M

FE

SC

AL

AN

TE

O

C

TO

BE

R

FA

3.

D

W G

BA

TT

AL

IO

N O

PE

R

AT

IO

N S

FA

C

IL

IT

Y

PN

/ P

1/8" = 1'-0"FA103

1 FIRE ALARM PLAN - LEVEL 3

# SHEET NOTES

1. PROVIDE ADDRESSABLE INTERFACES TO

MONITOR SPRINKLER SYSTEM CONTROL

VALVE AND FLOW SWITCH.

2. PROVIDE ADDRESSABLE INTERFACES TO

MONITOR ELEVATOR FLOW SWITCH AND

TAMPER SWITCH.

3. COORDINATE DUCT SMOKE DETECTORS

WITH MECHANICAL DUCTS.

4. PROVIDE MASTER CONTROL OVER HVAC

POWER AT LOC.

5. DEVICES, APPLIANCES, AND ASSOCIATED

CONDUIT MOUNTED ON SECURE AREA

BOUNDARY WALLS ARE TO BE SURFACE

MOUNTED TO COMPLY WITH UFC 4-010-05.

MEMBRANCE PENETRATIONS ARE NOT

PERMITTED.

6. PULL STATION FOR EXTERIOR USE.

7. SPEAKER STROBE AND PULL STATION TO

BE FED FROM THE NON-SECURE FIRE

EQUIPMENT CIRCUITS.

8. SUPERVISE ELEVATOR POWER FOR

SHUNT TRIP PURPOSES.

hnickle

VA - BLACK

FINISHED FLOOR

CONDUIT AND INITIATING CIRCUIT TO

MANUAL PULL STATION. CONCEAL ABOVE

FINISHED CEILING

ALL WIRING AND CIRCUITS

SHALL BE PROVIDED IN EMT

OR RIGID METAL CONDUIT

CONCEALED ABOVE THE

CEILING OR BEHIND WALLS.

FINISHED CEILING

44" AFF

FIRE

WHITE LABEL

WITH DEVICE

ADDRESS

STANDARD OR

DEEP 4"

OCTAGON WIRING

BOX

DETECTOR

IDENTIFICATION

CLEAR LED LENS

CEILING OR SOFFIT

JUNCTION BOX

PROVIDE PRINTED

CIRCUIT LABEL ON ALL

NAC DEVICES

SPEAKER

STROBE

CEILING

SPECIAL WALL PARTITION

SCHEDULE 80 PVC PIPE/FITTINGS

EXTEND GROUND WIRE TO BUILDING

STRUCTURAL STEEL OR NEAREST GROUND

BAR

(NOT LOCATED WITHIN AN ELECTRICAL PANEL).

METALLIC CONDUIT

PACKAGING AND SEALANT FOR FIRE RATED CONSTRUCTION

WHERE APPLICABLE - WHERE FIRESTOPPING IS REQUIRED

PACK

SOLID WITH HIGH STRENGTH GROUT - SEAL WITH ACOUSTICAL

CAULKING

PIPE CLAMP WITH GROUND WIRE

ATTACK SIDE

METALLIC CONDUIT

SECURE SIDE

12" MIN.

6" MAX.

JO

NE

S

FR

AN

KL

IN

R

D, S

UI

TE

R

AL

EI

G

H , N

C

-3

(9

1-

(9

) 8

-7

FA

X

LI

C

EN

SE

F -0

US Army Corps of Engineers ®

SHEET ID

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

1 2 3 4 5 6 7 8 9 10

A

D

AT

E M

AR

K

D

ES

C R

IP

TI

O N

BA

LT

IM

O

R E

D

IS

TR

IC

T

H O

PK

IN

S

PL

AZ

A

BA

LT

IM

O

R E

M

AR

YL

AN

D

FI

LE

N

AM

E:

FOR OFFICIAL USE ONLY

XX

X-

XX

X-

XX

X

XX

X-

XX

X-

XX

X

B

C

D

E

F

G

H

J

K

L

M

N

P

11 12 13 14 15 16 17 18 19 20

D R

AW

IN

G N

O

F1

-2 9-

FA501

FI

R

E

AL

AR

M

D

ET

AI

LS

H U

M

PH

R

EY

S

EN

G

IN

EE

R

C

EN

TE

R

, A

LE

XA

N

D R

IA

, V

IR

G

IN

IA

PL

O

M

AX

H N

IC

KL

E/

BH

AN

BI

C

KI

W

BY

N U

M

FE

SC

AL

AN

TE

O

C

TO

BE

R

FA

1.

D

W G

BA

TT

AL

IO

N O

PE

R

AT

IO

N S

FA

C

IL

IT

Y

PN

/ P

NOT TO SCALEFA501

1 PULL STATION WITH CONDUIT

NOT TO SCALEFA501

2 CEILING MOUNTED SMOKE DETECTOR

NOT TO SCALEFA501

3 CEILING MOUNTED SPEAKER/STROBE

NOT TO SCALEFA501

4 CONDUIT THROUGH SECURE AREA PENETRATION

O

FESSIONAL ENGIN

EE

R

PETER Q. LOMAX

DART

FACP

FS

15cd 15cd 15cd

WP

LEVEL 1

0'-0"

32'-0"

47'-0"

16'-0"

LEVEL 2

LEVEL 3

ROOF

AMP

FATC

FATC

FACP

S E

S

30cd 75cd

WP

FS

WF

AI

VS

AI

15cd 15cd S

E

STAIR #1

S

30cd 75cd

WP

F

WF

AI

VS

AI S

E

STAIR #1

15cd

S

30cd

75cd110cd

15cd15cd

S

30cd

FS

LOC LOCWF

AI

VS

AI

FIRE ROOM 112

VS

AI

VS

AI

SECURE AREA NON-SECURE AREA

WF

AI

VS

AI

NAC

NAC

FIBER OPTIC CONNECTION

FAA

LOC

LOC

LOC

S AR

SUPPLY UNIT SCU-1

(MECH ROOM 117)

SAR

SUPPLY UNIT SCU-2

(MECH. ROOM 204)

SAR

SUPPLY UNIT SCU-3

(MECH. ROOM 304)

30cd

AMP

WF

AI

VS

AI

STAIR #1

NAC NAC

LED

LED

LED

S

WP

STAIR 2

S

S

WP

EXTERIOR BALCONY

F

WP

AMP

AMP

AI

EOLR

EOLR

EOLR

EOLR

EOLR

EOLR

JO

NE

S

FR

AN

KL

IN

R

D, S

UI

TE

R

AL

EI

G

H , N

C

-3

(9

1-

(9

) 8

-7

FA

X

LI

C

EN

SE

F -0

US Army Corps of Engineers ®

SHEET ID

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

1 2 3 4 5 6 7 8 9 10

A

D

AT

E M

AR

K

D

ES

C R

IP

TI

O N

BA

LT

IM

O

R E

D

IS

TR

IC

T

H O

PK

IN

S

PL

AZ

A

BA

LT

IM

O

R E

M

AR

YL

AN

D

FI

LE

N

AM

E:

FOR OFFICIAL USE ONLY

XX

X-

XX

X-

XX

X

XX

X-

XX

X-

XX

X

B

C

D

E

F

G

H

J

K

L

M

N

P

11 12 13 14 15 16 17 18 19 20

D R

AW

IN

G N

O

F1

-2 9-

FA502

FI

R

E

AL

AR

M

R

IS

ER

D

IA

G

R

AM

H U

M

PH

R

EY

S

EN

G

IN

EE

R

C

EN

TE

R

, A

LE

XA

N

D R

IA

, V

IR

G

IN

IA

PL

O

M

AX

H N

IC

KL

E/

BH

AN

BI

C

KI

W

BY

N U

M

FE

SC

AL

AN

TE

O

C

TO

BE

R

FA

2.

D

W G

BA

TT

AL

IO

N O

PE

R

AT

IO

N S

FA

C

IL

IT

Y

PN

/ P

CIRCUIT WIRING SHALL BE AS FOLLOWS OR AS OTHERWISE

RECOMMENDED BY THE MANUFACTURER:

ADDRESSABLE SIGNALING LINE CIRCUITS (SLC) [CLASS B]

#18 AWG, SOLID COPPER CONDUCTORS, TWISTED/SHIELDED

PAIR, TYPE FPL, FPLR, OR FPLP AS APPROPRIATE, MARKED

"POWER LIMITED FIRE PROTECTIVE SIGNALING CIRCUIT CABLE"

AND UL-LISTED FOR THIS INTENDED PURPOSE.

INITIATING DEVICE CIRCUITS (IDC) [CLASS B]

#16 AWG, SOLID COPPER CONDUCTORS, TYPE FPL, FPLR, OR

FPLP AS APPROPRIATE, MARKED "POWER LIMITED FIRE

PROTECTIVE SIGNALING CIRCUIT CABLE" AND UL-LISTED FOR

THIS INTENDED PURPOSE.

NOTIFICATION APPLIANCE CIRCUITS (NAC) - FOR SPEAKERS

[CLASS B]

#16 AWG, SOLID TWISTED PAIR COPPER CONDUCTORS, TYPE

FPL, FPLR, OR FPLP AS APPROPRIATE, MARKED "POWER

LIMITED FIRE PROTECTIVE SIGNALING CIRCUIT CABLE" AND UL-

LISTED FOR THIS INTENDED PURPOSE. PROVIDE SHIELDED IF

REQUIRED BY MFG.

NOTIFICATION APPLIANCE CIRCUITS (NAC) - FOR STROBES

[CLASS B]

#14 AWG, THHN-THWN INSULATED, 600 VAC SOLID COPPER

CONDUCTORS.

24VDC POWER

#14 AWG, THHN-THWN INSULATED, 600 VAC SOLID COPPER

CONDUCTORS.

120 VAC POWER CIRCUITS:

#12 AWG. THHN-THWN INSULATED, 600 VAC SOLID COPPER

CONDUCTORS. ISOLATE SLC'S FROM NAC'S & 24 VDC POWER

PER MANUFACTURER'S RECOMMENDATIONS.

NEW FIRE ALARM/MASS NOTIFICATION PANEL SHALL BE

CAPABLE OF MONITORING 500 DEVICES. PROVIDE ALL

REQUIRED CONNECTIONS, MODULES, POWER, AND

PROGRAMMING FOR NEW DEVICES.

CONTRACTOR SHALL PROVIDE A DEVICE SCHEDULE AND

PROGRAM INTO THE FACP ENGLISH LANGUAGE TITLE AND

DESCRIPTIONS FOR EACH FIRE ALARM DEVICE MONITORED OR

CONTROLLED. INCLUDE DEVICE TYPE, BUILDING ZONE, ROOM

NUMBER AND FLOOR NUMBER FOR EACH DEVICE.

SEE INDIVIDUAL FLOOR PLANS FOR QUANTITIES AND

LOCATIONS OF EQUIPMENT AND DEVICES.

ALL DEVICES AND ACCESSORIES TO BE LISTED FOR THE

EXPECTED ENVIRONMENTAL CONDITIONS FOR THE SPACE IN

WHICH THEY ARE INSTALLED.

PROVIDE LINE ISOLATION MODULES ON THE SLC EVERY 20 OR

25 DEVICES (MANUFACTURER DEPENDENT).

SHEET NOTES

NOT TO SCALEFA502

1 FIRE ALARM RISER DIAGRAM

O

FESSIONAL ENGIN

EE

R

PETER Q. LOMAX

ACTION

IN

D

IC

AT

E

ST

AT

U

S O

N F

AC

P, R

EM

O

TE

F

AC

P, R

EM

TE

AN

N U

N C

IA

TO

R (N

O

TE

, N

O

TE

IN

IT

IA

TE

A

LA

R M

S

TA

TU

S

IN

IT

IA

TE

T R

O U

BL

E

ST

AT

U S

IN

IT

IA

TE

S U

PE

R

VI

SO

R Y

ST

AT

U S

TR

AN

SM

IT

S

YS

TE

M

S

TA

TU

S

SI

G

N

AL

T O

C

EN

TR

AL

S

TA

TI

O

N (N

O

TE

AC

TI

VA

TE

F

IR

E

AL

AR

M

N O

TI

FI

C

AT

IO

N

D

EV

IC

ES

(N O

TE

R

EC

AL

L

EL

EV

AT

O

R T

O P

R

IM

AR

Y

R

EC

AL

L

FL

O

O R

(F

IR

ST

F

LO

O

R

R

EC

AL

L

EL

EV

AT

O

R T

O S

EC

O

N D

AR

Y

FL

O

O R

(S

EC

O N

D F

LO

O

R

AC

TI

VA

TE

FI

R

EM

AN

'S

H

AT

ST

EA

D

Y)

AC

TI

VA

TE

"F

IR

EM

AN

'S H

AT

FL

AS

H

IN

G

SH

U

T D

O W

N A

IR

-H

AN

D

LI

N

G U

N

IT

DEVICE NOTES

MANUAL PULL STATION X X X X

AREA SMOKE DETECTOR X X X X

ELEVATOR LOBBY SMOKE DETECTOR

(PRIMARY RECALL FLOOR) X X X X X X NOTE 4

ELEVATOR LOBBY SMOKE DETECTOR

(OTHER THAN PRIMARY RECALL FLOOR) X X X X X X NOTE 4

ELEVATOR SHAFT SMOKE

DETECTOR X X X X X X

DUCT SMOKE DETECTOR X X X

WIRING FAULT, SYSTEM TROUBLE,

COMMUNICATION FAULT X X X

NOTES:

1. REFER TO PROJECT SPECIFICATIONS FOR FACP AND REMOTE ANNUNCIATOR DISPLAY REQUIREMENTS.

2. FIRE ALARM STATUS WILL BE TRANSMITTED VIA KING-FISHER KFRT-20 DART TO FIRE DEPARTMENT SYSTEM.

3. INCLUDING SPEAKERS, SPEAKER/STROBES, AND STROBES. INCLUDES EXTERIOR SPEAKER/STROBE; EXTERIOR SPEAKER/STROBE SHALL

BE PROGRAMMED AS NON-SILENCEABLE.

4. ELEVATOR LOBBY SMOKE DETECTOR SHALL DISPLAY AS "SMOKE DETECTOR" ON ALARM STATUS REPORT (ON FACP DISPLAY, REMOTE ANNUNCIATOR PANEL DISPLAY, AND IN SYSTEM MEMORY).

X

IN

IT

IA

TE

S H

U N

T

TR

IP

(S

H U

T O

FF

E

LE

VA

TO

R

P O

W

ER

N

O

TE

BR

O

AD

C

AS

T

M N

S

PR

E- R

EC

O

R D

ED

M

ES

SA

G

ES

HVAC SHUTDOWN SWITCH AT LOC

BR

O

AD

C

AS

T

M N

S

AU

D

IO

L

IV

E

VO

IC

E

M N

S O

VE

R

R

ID

E O

F

FA

S

IG

N

AL

MNS - MANUAL VOICE ANNOUNCEMENT

MNS - ACTIVATION OF PRERECORDED

MESSAGES

X X X

X X X X

X X XX X NOTE 5

NOTE 5

5. PROVIDE A SUPERVISORY SIGNAL IF THE MNS IS USED TO OVERRIDE FIRE ALARM AUDIBLE MESSAGES. THE SUPERVISORY SIGNAL SHALL BE ANNUNCIATED AT THE FACP AND REMOTE FIRE ALARM ANNUNCIATORS AND TRANSMITTED TO THE FIRE DEPARTMENT. THIS SUPERVISORY SIGNAL SHALL BE SEPARATE FROM OTHER FIRE ALARM SYSTEM

SUPERVISORY SIGNALS AND VISUAL ANNUNCIATION SHALL BE CLEARLY IDENTIFIED.

CARBON MONOXIDE DETECTOR

WATER FLOW SWITCH

VALVE SUPERVISORY SWITCH

X X

X X X X X

X X X X X X X X

X

6. WATER FLOW SWITCH ASSOCIATED WITH ELEVATOR SHALL ACTIVATE SHUNT TRIP WITH ZERO TIME DELAY. OTHER WATER FLOW SWITCHES SHALL NOT ACTIVATE SHUNT

TRIP. SUPERVISE POWER TO THE ELEVATOR TO ENSURE THAT SHUNT TRIP HAS OCCURED.

7. FIRE ALARM INPUTS AND OUTPUTS TO THE MAIN FIRE ALARM PANEL SHALL BE COMMUNICATED TO THE FIRE ALARM SUBPANEL(S) AS NEEDED FOR THE FIRE ALARM SYSTEM TO FUNCTION FULLY. ADDITIONALLY, FIRE ALARM INPUTS AND OUTPUTS TO THE FIRE ALARM SUBPANEL(S) SHALL BE COMMUNICATED TO THE MAIN FIRE ALARM PANEL AS

NEEDED FOR THE FIRE ALARM SYSTEM TO FUNCTION FULLY.

X

JO

NE

S

FR

AN

KL

IN

R

D, S

UI

TE

R

AL

EI

G

H , N

C

-3

(9

1-

(9

) 8

-7

FA

X

LI

C

EN

SE

F -0

US Army Corps of Engineers ®

SHEET ID

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

1 2 3 4 5 6 7 8 9 10

A

D

AT

E M

AR

K

D

ES

C R

IP

TI

O N

BA

LT

IM

O

R E

D

IS

TR

IC

T

H O

PK

IN

S

PL

AZ

A

BA

LT

IM

O

R E

M

AR

YL

AN

D

FI

LE

N

AM

E:

FOR OFFICIAL USE ONLY

XX

X-

XX

X-

XX

X

XX

X-

XX

X-

XX

X

B

C

D

E

F

G

H

J

K

L

M

N

P

11 12 13 14 15 16 17 18 19 20

D R

AW

IN

G N

O

F1

-2 9-

FA503

FI

R

E

AL

AR

M

O

PE

R

AT

IN

G

M

AT

R

IX

H U

M

PH

R

EY

S

EN

G

IN

EE

R

C

EN

TE

R

, A

LE

XA

N

D R

IA

, V

IR

G

IN

IA

PL

O

M

AX

H N

IC

KL

E/

BH

AN

BI

C

KI

W

BY

N U

M

FE

SC

AL

AN

TE

O

C

TO

BE

R

FA

3.

D

W G

BA

TT

AL

IO

N O

PE

R

AT

IO

N S

FA

C

IL

IT

Y

PN

/ P

NOT TO SCALEFA503

1 FIRE ALARM OPERATING MATRIX

O

FESSIONAL ENGIN

EE

R

PETER Q. LOMAX

CO SD

CI

CI

C

FF

E=4

4.6

C U

R B

C U

TFH

PL

AN

T E D

AR

EA

PL

AN

TE

D

AR

EA

PLANTED AREA

PLANTED AREA

G A

TE

G V

FF

E

L

.7

FF

E

L

.7

FF

E

L

.7

FF

E

L

.7

WALL

WALL

C A

N O

P Y

ASPHALT ENTRANCE ROAD

WOOD STEP

AS

PH

AL

T

PA

R

KI

N

G L

O T

AS

PH

AL

T

R O

AD

AS

PH

AL

T

PA

R

KI

N

G L

O T

4' C

H

AI

N L

IN

K

4' CHAIN LINK

8' CHAIN LINK

8'

CH

AI

N

LI

NK

8'

CHAIN

LI

NK

AS

PH

AL

T

PARKING

G

AT

E

W V

W V

FH

FH

W V

C O

N C.

D

IT

C H

LO

ADIN

G

DOCK

TR

ANS

FORM

ER

ORDINARY HAZARD

LIGHT HAZARD

OCCUPANCY

HAZARD

CLASSIFICATION

0.20

0.10

DESIGN

DENSITY

[GPM/SQ. FT.]

AREA

[SQ. FT.]

HOSE

[GPM]

8.0

5.6

K-FACTOR

TEST HYDRANT

NEW 8" FIRE

SERVICE LATERAL

8"

8"

8"

8"

8"

8" 8"

8" 8"

EXISTING WATER MAIN

EXISTING WATER MAIN

8" 8"

8"

NEW POST

INDICATOR VALVE

NEW FIRE DEPARTMENT

CONNECTION

9'

A AMP

ABV ABOVE

A/E ARCHITECT/ENGINEER (OF RECORD)

ANSI AMERICAN NATIONAL STANDARDS INSTITUTE

A/S AUTOMATIC SPRINKLER

AWG AMERICAN WIRE GAGE

BLDG BUILDING

BOB BOTTOM OF BEAM

BOJ BOTTOM OF JOIST

C CEILING

CLO CLOSET

CMU CONCRETE MASONRY UNIT

COM COMMUNICATIONS

CONT CONTINUED

CORR CORRIDOR

DS DRY SPRINKLER

E EXISTING DEVICE

EC EXTENDED COVERAGE SPRINKLER

ELEC ELECTRIC

EOLR END OF LINE RESISTOR

EXIST EXISTING

FACP FIRE ALARM CONTROL PANEL

FDC FIRE DEPARTMENT CONNECTION

GPM GALLONS PER MINUTE

IN INCH

J.C. JANITOR'S CLOSET

LAT LAY-IN ACOUSTICAL TILE

LED LIGHT EMITTING DIODE

MACH MACHINE

1. SCOPE OF WORK: PROVIDE A COMPLETE HYDRAULICALLY CALCULATED AUTOMATIC WET SPRINKLER SYSTEM THROUGHOUT THE BUILDING. PROVIDE ALL EQUIPMENT, LABOR, AND MATERIAL FOR AN COMPLETE AUTOMATIC SPRINKLER SYSTEM, INCLUDING WATER FLOW SWITCHES, VALVE SUPERVISORY SWITCHES, CHECK VALVES, CONTROL VALVES, PIPING, HANGERS, SPRINKLERS, FLEXIBLE COUPLINGS, FDC, DRAINS, AND ALL ASSOCIATED EQUIPMENT INDICATED OR NOT IN THESE DRAWINGS, SPECIFICATIONS, AND THE

APPLICABLE CODES.

2. ALL WORK AND INSTALLATION SHALL CONFORM TO THE APPLICABLE PROVISIONS OF THE FOLLOWING:

- UFC 3-600-01, FIRE PROTECTION ENGINEERING FOR FACILITIES, CHANGE 3, MAY 2019

- NFPA 13, STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS, 2019 EDITION

- NFPA 24, STANDARD FOR INSTALLATION OF PRIVATE FIRE SERVICE MAINS AND THEIR APPURTENANCES, 2019 EDITION

- OTHER CODES AND STANDARDS INDICATED IN THE SPECIFICATIONS.

3. PROVIDE NEW INCOMING WATER SERVICE FOR THE SPRINKLER SYSTEM PER NFPA 24 AND UFC 3-600-01.

4. ALL SPRINKLERS SHALL BE INSTALLED IN CENTER OF TILE IN AREAS WITH 2'x2' SUSPENDED CEILING TILES. SPRINKLER HEADS SHALL BE INSTALLED IN CENTER OF TILE IN AREAS WITH 2'x4' SUSPENDED CEILING TILES. SPRINKLERS SHALL BE INSTALLED AS FOLLOWS:

- AREAS WITH FINISHED CEILINGS: RECESSED OR CONCEALED PENDENT, QUICK RESPONSE, ORDINARY TEMPERATURE

SPRINKLER HEADS

- AREAS WITHOUT FINISHED CEILINGS: UPRIGHT OR PENDANT, BRASH FINISH, QUICK RESPONSE, ORDINARY TEMPERATURE

SPRINKLER HEADS

5. ALL SPRINKLERS SHALL BE UL APPROVED, QUICK RESPONSE SPRINKLERS WITH K-FACTOR OF 5.6 FOR LIGHT HAZARD AREAS AND K-

FACTOR OF 8.0 FOR ORDINARY HAZARD OCCUPANCIES.

6. STEEL PIPE SIZES 2 INCHES AND SMALLER WILL BE SCHEDULE 40. STEEL PIPE SIZES LARGER THAN 2 INCHES WILL BE SCHEDULE 10 OR SCHEDULE 40. PIPING LESS THAN SCHEDULE 40 WILL BE ROLL GROOVED. THREADABLE LIGHTWALL PIPE WILL NOT BE USED.

STEEL PIPING HAVING A CORROSION RESISTANT RATIO LESS THAN 1 WILL NOT BE USED. PLAIN-END FITTINGS WILL NOT BE USED.

PLASTIC PIPE OR VALVES WILL NOT BE USED.

7. PROVIDE HANGERS PER NFPA 13.

8. PROVIDE AUXILIARY DRAINS PER NFPA 13. ALL AUXILIARY VALVES AND LOW POINT VALVES SHALL BE BALL VALVES.

9. PROVIDE A FIRE DEPARTMENT CONNECTION AS REQUIRED BY NFPA 13 AND UFC 3-600-01.

10. ALL DRAINS AND TEST CONNECTION SHALL BE TO THE EXTERIOR. ALL DRAINS SHALL TERMINATE IN A SPLASH BLOCKS.

11. ALL AREAS ARE CONSIDERED LIGHT HAZARD U.N.O. ON THE FLOOR PLAN DRAWINGS. DESIGN AREA SHALL BE PER UFC 3-600-01

TABLES 9-3 AND 9-4.

12. PROVIDE RECESSED PENDENT QUICK RESPONSE SPRINKLERS AND UPRIGHT QUICK RESPONSE SPRINKLERS, K-FACTOR 8.0 IN THE

ORDINARY HAZARD AREA.

13. ALL EQUIPMENT SHALL BE TESTED/APPROVED BY A NATIONAL TESTING LABORATORY AND INSTALLED PER THE LISTING AND

MANUFACTURERS INSTALLATION INSTRUCTIONS AS REQUIRED PER NFPA 13.

14. DRAWINGS AND REFLECTED CEILING PLANS ARE PROVIDED FOR REFERENCE ONLY; SEE ARCHITECTURAL AND STRUCTURAL DRAWINGS FOR CEILING TYPES, CEILING HEIGHTS, FIXTURE LOCATIONS, BEAMS, AND OBSTRUCTIONS. SPRINKLER CONTRACTOR

SHALL COORDINATE WITH ALL TRADES.

15. THE CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND DIMENSIONS ON THE DRAWINGS PRIOR TO THE EXECUTION OF THIS CONTRACT. LOCATION AND SIZES OF PIPING AND LIGHTING FIXTURES ARE APPROXIMATE. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE LOCATION OF ALL SYSTEM COMPONENTS. CONTRACTOR SHALL REPORT ANY DISCREPANCIES WITH THESE DRAWINGS TO THE ENGINEER IMMEDIATELY. THE CONTRACTOR(S) SHALL NOT PROCEED WITH ANY WORK, EXCEPT AT THEIR OWN RISK, UNTIL CLARIFICATIONS OF THE CONFLICTS ARE ISSUED TO THE CONTRACTOR(S) BY THE ENGINEER.

16. PROVIDE GUARDS ON SPRINKLERS THAT ARE INSTALLED AT OR BELOW 7'-0" AND AS INDICATED ON THE DRAWINGS.

17. SPRINKLER PIPING INDICATED ON THE DRAWINGS IS SHOWN FOR PURPOSES OF DESIGN INTENT AND LIMITED FIELD VERIFICATION.

IT IS THE INTENT OF THIS DESIGN NOT TO CORE DRILL STRUCTURAL MEMBERS EXCEPT WHERE INDICATED FOR FLOOR SLABS AND CMU WALLS. THE CONTRACTOR IS RESPONSIBLE FOR ALL CORE DRILLING. ALL WALL PENETRATIONS SHALL BE CORE-DRILLED. ALL PENETRATIONS IN WALLS SHALL BE SEALED TO THE FULL THICKNESS OF THE PENETRATION WITH APPROVED FIRE STOPPING MATERIAL OF EQUAL OR GREATER FIRE RESISTANCE. PROVIDE DIELECTRIC UNIONS FOR PIPING PENETRATING SECURE AREA

WALLS. SEE ARCHITECTURAL DRAWINGS FOR LOCATION OF SMOKE AND FIRE BARRIER WALLS.

18. SPRINKLER CONTRACTOR TO PROVIDE ALL FLOW, VALVE SUPERVISORY, AND PRESSURE SWITCHES. FIRE ALARM CONTRACTOR SHALL MAKE ALL ELECTRICAL CONNECTIONS BETWEEN THESE DEVICES AND THE BUILDING FIRE ALARM SYSTEM.

19. CONTRACTOR SHALL PERFORM A CURRENT FIRE HYDRANT FLOW TEST. FLOW TEST SHALL BE DATED NOT MORE THAN 1 YEAR

PRIOR TO SHOP DRAWINGS SUBMISSION.

20. PROVIDE AIR VENT AT THE TOP OF THE PIPE IN EACH SPRINKLER ZONE.

21. WATER FLOW TEST INFORMATION:

TEST HYDRANT: NE CORNER OF BUILDING 2596

FLOW HYDRANT 1: NW CORNER OF BUILDING 2596

FLOW HYDRANT 2: NE CORNER OF BUILDING 2582

CONDUCT BY: HUY THAI AND MINH NGUYEN - RHINO FIRE PROTECTION ENGINEERING, PLLC

WITNESSED BY: LAWRENCE SHINN JR. - FORT BELVOIR FIRE MARSHALL

DATE: 07/23/2019

STATIC PRESSURE: 117 PSI

RESIDUAL PRESSURE: 110 PSI

FLOW RATE : 1202 GPM

ELEVATION: 37.96

RECESSED PENDENT SPRINKLER

UPRIGHT SPRINKLER

UPRIGHT SPRINKLER WITH GUARD

HYDRAULIC NODE

ORDINARY HAZARD

WATER FLOW SWITCH

SUPERVISORY TAMPER SWITCH

HYDRAULIC CALCULATION AREA

NEW SPRINKLER PIPE

UNDERGROUND SPRINKLER PIPE

SECURE AREA PERIMETER

1 HOUR FIRE BARRIER

90 ELBOW

TEE

TEE DOWN

RISER

REDUCER

PIPE SECTION

PIPE CONTINUATION

BACKFLOW PREVENTER

CHECK VALVE

GENERAL VALVE

BUTTERFLY VALVE

OS&Y VALVE

POST INDICATOR VALVE

FLOOR CONTROL ASSEMBLY

FLOW DETECTOR

ONE WAY FIRE DEPARTMENT CONNECTION

BACKFLOW TEST HEADER

FIRE DEPARTMENT CONNECTION

HOSE VALVE

JO

NE

S

FR

AN

KL

IN

R

D, S

UI

TE

R

AL

EI

G

H , N

C

-3

(9

1-

(9

) 8

-7

FA

X

LI

C

EN

SE

F -0

US Army Corps of Engineers ®

SHEET ID

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

1 2 3 4 5 6 7 8 9 10

A

D

AT

E M

AR

K

D

ES

C R

IP

TI

O N

BA

LT

IM

O

R E

D

IS

TR

IC

T

H O

PK

IN

S

PL

AZ

A

BA

LT

IM

O

R E

M

AR

YL

AN

D

FI

LE

N

AM

E:

FOR OFFICIAL USE ONLY

XX

X-

XX

X-

XX

X

XX

X-

XX

X-

XX

X

B

C

D

E

F

G

H

J

K

L

M

N

P

11 12 13 14 15 16 17 18 19 20

D R

AW

IN

G N

O

F1

-2 9-

FX001

LE

G

EN

D

, A

BB

R

EV

IA

TI

O N

S, A

N D

S

PR

IN

KL

ER

G

EN

ER

AL

N

O

TE

S

H U

M

PH

R

EY

S

EN

G

IN

EE

R

C

EN

TE

R

, A

LE

XA

N

D R

IA

, V

IR

G

IN

IA

PL

O

M

AX

H

TH

AI

W

BY

N U

M

FE

SC

AL

AN

TE

O

C

TO

BE

R

FX

1.

D

W G

BA

TT

AL

IO

N O

PE

R

AT

IO

N S

FA

C

IL

IT

Y

PN

/ P

O H

WF

VS

DESIGN DENSITIES

FCA

SPRINKLER GENERAL NOTES LEGEND ABBREVIATIONS

MECH MECHANICAL ROOM

MI MINERAL INSULATED

MNS MASS NOTIFICATION SYSTEM

MPS MANUAL PULL STATION

NAC NOTIFICATION APPLIANCE CIRCUIT

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NO. NUMBER

NOS. NUMBERS

NPT NATIONAL PIPE THREAD

NTS NOT TO SCALE

OPG OPENING

OS&Y OUTSIDE STEM AND YOKE

P PHASE

P.S. PIPE SHAFT

PSI POUNDS PER SQUARE INCH

QR QUICK RESPONSE

RM ROOM

SPKLR SPRINKLER

SSU STANDARD SPRAY UPRIGHT

STDP STANDPIPE

SF SQUARE FOOT

SPD SURGE PROTECTION DEVICE

STO STORAGE

TC TERMINAL CABINET

TOJ TOP OF JOIST

UNO UNLESS NOTED OTHERWISE

VAC VOLTS ALTERNATING CURRENT

WP WEATHER PROOF

W/ WITH

1" = 100'-0"FX001

1 SITE PLAN

O

FESSIONAL ENGIN

EE

R

PETER Q. LOMAX

GE.5CBA D EB.5 F

3.5

2.9

2.3

GSB (STE) 3 BAY

GARAGE

GSB FCC

LOGISTICS AREA

& SECURE

LOADOUT

LOADOUT

GSB FCC MISSION

SUPPORT

DMARC

FCO TEAM CAGE

GSB MISSION

TEAM CAGE

FCO TEAM CAGE

FCO TEAM CAGE

MECHANICAL

ELEVATOR

EL-1

MEN

WOMEN

ENTRY

VESTIBULE

CORRIDOR

COLLATERAL

FIRE

ELECTRICAL

CONFERENCE

MEETING AREA

CORRIDOR

CORRIDOR

PERSONAL

CAGES

STAIR 1

S-1

STAIR 2

S-2

SALLY PORT

WELLNESS

TR

CORRIDOR

S4 STORAGE

STORAGE

JC

CORRIDOR

RECEPTION AREA

ELEVATOR LOBBY

CORRIDOR

FX502

FX502

OH

OH

OH

OH

OH

OH

OH

OH

OH

OH

OH

OH

OH

OH

OH

8" FIRE SERVICE

6"

6"

6" 6"

6"

JO

NE

S

FR

AN

KL

IN

R

D, S

UI

TE

R

AL

EI

G

H , N

C

-3

(9

1-

(9

) 8

-7

FA

X

LI

C

EN

SE

F -0

US Army Corps of Engineers ®

SHEET ID

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

1 2 3 4 5 6 7 8 9 10

A

D

AT

E M

AR

K

D

ES

C R

IP

TI

O N

4' 8' 16'

PROJECT

NORTH

TRUE

NORTH

BA

LT

IM

O

R E

D

IS

TR

IC

T

H O

PK

IN

S

PL

AZ

A

BA

LT

IM

O

R E

M

AR

YL

AN

D

FI

LE

N

AM

E:

FOR OFFICIAL USE ONLY

XX

X-

XX

X-

XX

X

XX

X-

XX

X-

XX

X

B

C

D

E

F

G

H

J

K

L

M

N

P

11 12 13 14 15 16 17 18 19 20

D R

AW

IN

G N

O

F1

-2 9-

FX101

FI

R

E

PR

O

TE

C

TI

O N

P

LA

N

LE

VE

L

H U

M

PH

R

EY

S

EN

G

IN

EE

R

C

EN

TE

R

, A

LE

XA

N

D R

IA

, V

IR

G

IN

IA

PL

O

M

AX

H

TH

AI

W

BY

N U

M

FE

SC

AL

AN

TE

O

C

TO

BE

R

FX

1.

D

W G

BA

TT

AL

IO

N O

PE

R

AT

IO

N S

FA

C

IL

IT

Y

PN

/ P

1/8" = 1'-0"FX101

1 SPRINKLER PLAN - LEVEL 1

# SHEET NOTES

1. PROVIDE ZONE CONTROL ASSEMBLY

INCLUDING A SUPERVISED CONTROL

VALVE, CHECK VALVE, FLOW SWITCH AND

TEST AND DRAIN VALVE WITH PRESSURE

RELIEF VALVE.

2. PROVIDE A SUPERVISED RISER OS&Y

CONTROL VALVE.

3. GROUND THE SPRINKLER PIPE WITHIN 6

INCHES OF THE SECURE AREA

PERIMETER PENETRATION, ON THE

SECURE SIDE, USING A NO. 4 WIRE TO

THE BUILDING GROUND. SEE DETAILS

SHEET FP 501.

4. PROVIDE SPRINKLER WITH GUARD UNDER

THE STAIR. PROVIDE PLUG TO DRAIN THE

LINE.

5. PROVIDE AIR VENT AT THE TOP OF THE

PIPE IN EACH SPRINKLER ZONE.

6. PROVIDE 2 ½" HOSE VALVE.

7. PROVIDE 4" STORZ FIRE DEPARTMENT

CONNECTION WITH CHECK VALVE AND

AUTOMATIC BALL DRIP NEAR BUILDING

ENTRANCE. SEE FX502 FOR DETAILS.

O

FESSIONAL ENGIN

EE

R

PETER Q. LOMAX

ELEVATOR

EL-1

FCC LAB

STAIR 1

S-1

FARADAY CAGE

209IT/COMMS

STORAGE

MECHANICAL

TR

WOMEN

MEN

202FCC TEAM 4

FCC TEAM 3

STAIR 2

S-2

FCC TEAM 1

FCC TEAM 2

BREAK AREA

OPEN OFFICE

CORRIDOR

UPS

O4 PRIVATE

OFFICE

O4 PRIVATE

OFFICE

O4 PRIVATE

OFFICE

CONFERENCE

ROOM

FCC CUBES

GE.5CBA D EB.5 F

3.5

2.9

2.3

DESIGN AREA 2

OH

OH

OH

OH

OH

OH

4"

1"

1" 1"

1"

1.

1"

1.

1"

1"

1" 1"

1"

1.

1"

1.

1"

1"

1" 1"

1"

1.

1"

1.

1"

1"

1"

1"

1"

1"

1" 1"

1"

1.

1"

1.

1"

1"

1" 1"

1"

1.

1"

1.

1"

1"

1" 1"

1"

1"

1" 1"

1"

1.

1"

1"

1" 1"

1"

4"

1"

UP/ DOWN

32282319

OCCUPANCY CLASSIFICATION

DENSITY

TOTAL HOSE STREAMS

FLOWING HEADS

K-FACTOR

TOTAL WATER REQUIRED

TOTAL PRESSURE REQUIRED

SAFETY MARGIN

HYDRAULIC INFORMATION

REMOTE AREA NAME

AREA OF APPLICATION

Ordinary Hazard

0.2 GPM

250 GPM

21 @ 24 GPM

919.674 GPM

79.76 psi

+32.97 (29.25%)

DA 2 LEVEL 2

2500 SF

JO

NE

S

FR

AN

KL

IN

R

D, S

UI

TE

R

AL

EI

G

H , N

C

-3

(9

1-

(9

) 8

-7

FA

X

LI

C

EN

SE

F -0

US Army Corps of Engineers ®

SHEET ID

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

1 2 3 4 5 6 7 8 9 10

A

D

AT

E M

AR

K

D

ES

C R

IP

TI

O N

4' 8' 16'

PROJECT

NORTH

TRUE

NORTH

BA

LT

IM

O

R E

D

IS

TR

IC

T

H O

PK

IN

S

PL

AZ

A

BA

LT

IM

O

R E

M

AR

YL

AN

D

FI

LE

N

AM

E:

FOR OFFICIAL USE ONLY

XX

X-

XX

X-

XX

X

XX

X-

XX

X-

XX

X

B

C

D

E

F

G

H

J

K

L

M

N

P

11 12 13 14 15 16 17 18 19 20

D R

AW

IN

G N

O

F1

-2 9-

FX102

FI

R

E

PR

O

TE

C

TI

O N

P

LA

N

LE

VE

L

H U

M

PH

R

EY

S

EN

G

IN

EE

R

C

EN

TE

R

, A

LE

XA

N

D R

IA

, V

IR

G

IN

IA

PL

O

M

AX

H

TH

AI

W

BY

N U

M

FE

SC

AL

AN

TE

O

C

TO

BE

R

FX

2.

D

W G

BA

TT

AL

IO

N O

PE

R

AT

IO

N S

FA

C

IL

IT

Y

PN

/ P

1/8" = 1'-0"FX102

1 SPRINKLER PLAN - LEVEL 2

# SHEET NOTES

1. PROVIDE ZONE CONTROL ASSEMBLY

INCLUDING A SUPERVISED CONTROL

VALVE, CHECK VALVE, FLOW SWITCH AND

TEST AND DRAIN VALVE WITH PRESSURE

RELIEF VALVE.

2. PROVIDE CORROSION-RESISTANT

COATED SPRINKLERS IN THE MEN AND

WOMEN SHOWER AREAS.

3. PROVIDE AIR VENT AT THE TOP OF THE

PIPE IN EACH SPRINKLER ZONE.

4. PROVIDE 2 ½" HOSE VALVE.

O

FESSIONAL ENGIN

EE

R

PETER Q. LOMAX

ELEVATOR

EL-1

MEN

302 WOMEN

MECHANICAL

TR

G4 PRIVATE

OFFICE

G4 PRIVATE

OFFICE

SPO PRIVATE

OFFICE

SPO PRIVATE

OFFICE

S3 PRIVATE

OFFICE

S3 PRIVATE

OFFICE

HHT PRIVATE

OFFICE

CG CONFERENCE

ROOM

CONFERENCE

ROOM

CG PRIVATE

OFFICE

TOILET

CG PRIVATE

OFFICE

CG PRIVATE

OFFICE

BREAK AREA

PSYCH OFFICE

CG PRIVATE

OFFICE

STAIR 1

S-1

STAIR 2

S-2

SCT SERVICE

AREA

WAITING AREA

OPEN OFFICE

AREA

CLASSROOM

S4 CUBES

CHAPLAIN OFFICE

CORRIDOR

GE.5

C

BA D E

B.5

F

3.5

2.9

2.3

42 43

DESIGN AREA 1

2 2

OH

OH

1"

1" 1"

1"

1"

1" 1"

1"

1" 1"

1"

1" 1"

1"

1"

1" 1"

1"

1" 1"

1"

1"

1"

1" 1"

1"

1" 1"

OCCUPANCY CLASSIFICATION

DENSITY

TOTAL HOSE STREAMS

FLOWING HEADS

K-FACTOR

TOTAL WATER REQUIRED

TOTAL PRESSURE REQUIRED

SAFETY MARGIN

HYDRAULIC INFORMATION

REMOTE AREA NAME

AREA OF APPLICATION

Light Hazard

0.1 GPM

250 GPM

11 @ 19.6 GPM

5.6

508.813 GPM

69.65 psi

+45.93 (39.74%)

DA 1 LEVEL 3

1500 SF

4"

4"

EXTERIOR PATIO

JO

NE

S

FR

AN

KL

IN

R

D, S

UI

TE

R

AL

EI

G

H , N

C

-3

(9

1-

(9

) 8

-7

FA

X

LI

C

EN

SE

F -0

US Army Corps of Engineers ®

SHEET ID

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

1 2 3 4 5 6 7 8 9 10

A

D

AT

E M

AR

K

D

ES

C R

IP

TI

O N

4' 8' 16'

PROJECT

NORTH

TRUE

NORTH

BA

LT

IM

O

R E

D

IS

TR

IC

T

H O

PK

IN

S

PL

AZ

A

BA

LT

IM

O

R E

M

AR

YL

AN

D

FI

LE

N

AM

E:

CONTROLLED UNCLASSIFIED INFORMATION

XX

X-

XX

X-

XX

X

XX

X-

XX

X-

XX

X

B

C

D

E

F

G

H

J

K

L

M

N

P

11 12 13 14 15 16 17 18 19 20

D R

AW

IN

G N

O

F1

-2 9-

PROPERTY OF UNITED STATES GOVERNMENT, CONTROLLED UNCLASSIFIED INFORMATION (CUI), DISSEMINATION, AND DISTIBUTION TO AUTHORIZED INDIVIDUALS PROHIBITED

FX103

FI

R

E

PR

O

TE

C

TI

O N

P

LA

N

LE

VE

L

H U

M

PH

R

EY

S

EN

G

IN

EE

R

C

EN

TE

R

, A

LE

XA

N

D R

IA

, V

IR

G

IN

IA

PL

O

M

AX

H

TH

AI

W

BY

N U

M

FE

SC

AL

AN

TE

O

C

TO

BE

R

FX

3.

D

W G

BA

TT

AL

IO

N O

PE

R

AT

IO

N S

FA

C

IL

IT

Y

PN

/ P

1/8" = 1'-0"FX103

1 SPRINKLER PLAN - LEVEL 3

# SHEET NOTES

1. PROVIDE ZONE CONTROL ASSEMBLY

INCLUDING A SUPERVISED CONTROL

VALVE, CHECK VALVE, FLOW SWITCH AND

TEST AND DRAIN VALVE WITH PRESSURE

RELIEF VALVE.

2. PROVIDE CORROSION-RESISTANT

COATED SPRINKLERS IN THE MEN AND

WOMEN SHOWER AREAS.

3. PROVIDE UPRIGHT SPRINKLER AT TOP OF

THE ELEVATOR.

4. PROVIDE SEPARATE ZONE CONTROL

ASSEMBLY TO FEED SPRINKLERS AT TOP

OF ELEVATOR HOISTWAY. PROVIDE

SUPERVISED SHUT-OFF VALVE, CHECK

VALVE, WATER FLOW SWITCH WITH ZERO

TIME DELAY CAPABILITY, AND INSPECTOR

TEST AND DRAIN VALVE TO BE

CONNECTED TO THE MAIN DRAIN IN STAIR

#1. ACTUATION OF THE WATERFLOW

SWITCH SHALL TRIGGER SHUNT TRIP

BREAKER TO REMOVE POWER TO THE

ELEVATOR.

5. SPRINKLERS AT TOP OF STAIR TO BE FED

BY 3RD FLOOR SYSTEM.

6. PROVIDE DIELECTRIC UNION FOR STAIR

SPRINKLER PENETRATION.

7. PROVIDE AIR VENT AT THE TOP OF THE

PIPE IN EACH SPRINKLER ZONE.

8. PROVIDE 2 ½" HOSE VALVE.

hnickle

VA - BLACK

1" 90° ELBOW

1" PIPING

TYPICAL BRANCH-

LINE SIZE MAY VARY

SEE FLOOR PLAN

FOR SIZES AND

LOCATION

1" x ½" REDUCER

CUT CEILING TO

ACCOMMODATE

ESCUTCHEON

CEILING

RECESSED PENDENT SPRINKLER

ALL ARM-OVERS > 12"

HANGER REQUIRED

ALL ARM-OVERS < 12"

NO HANGER REQUIRED

1" PIPING

TYPICAL BRANCH-

LINE SIZE MAY VARY

SEE FLOOR PLAN

FOR SIZES AND

LOCATION

1" x ½" REDUCER

CUT CEILING TO

ACCOMMODATE

ESCUTCHEON

CEILING

RECESSED PENDENT SPRINKLER

TYPICAL BRANCH-

LINE SIZE MAY VARY

SEE FLOOR PLAN

FOR SIZES AND

LOCATION

1" VARIOUS THREADED

NIPPLE LENGTHS

1" x 1/2" REDUCER

QUICK RESPONSE

UPRIGHT SPRINKLER

UL LISTED AND FM

GLOBAL APPROVED

2"-12" MAX

HANGER RING

BEAM CLAMP

A.T.ROD

(LENGTH)

ST

EE

L

HANGER TAKEOUT (A)

ROD DIAMETER (B)

SIZE OF BOLT / LAG SCREW

NOMINAL PIPE SIZEALL SIZES IN INCHES

2" 3"2 1/2"1 3/4"1 1/4"1"3/4"1/2" 3/8"

1/2" 5/8"

5 1/4"3 3/4" 6"5"2 1/2"1 1/2"1 1/4"

B

A

1" 2" 3" 4" 8"

3/8" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" 1/2" 1/2" 1/2" 1/2"

1/2" 1/2" 1/2" E (MIN)

A (M

IN

IM

U M

D

IS

TA

N

C E)

THREADED

HANGER ROD

AT LEAST ONE FULL

THREAD OF ROD

MUST BE EXPOSED

SPRINKLER PIPE

ADJUSTABLE

HANGER RING

F (DRILL DIA.)

D (ANCHOR SIZE)

INSERT

1 1/4 1 1/2

2 1/2

3 1/4 3 1/2 3 3/4 4 3/4

5 3/4 6 1/2 7 1/2

1/2 3/4

1 1/4 1 3/4

2 1/2

3 3/4

5 1/4

3/8 3/8 X 1 9/16 5/8 7/16 3/8 3/8 3/8 3/8

3/8 3/8 1/2 1/2 1/2

3/8 X 1 9/16 3/8 X 1 9/16 3/8 X 1 9/16

3/8 X 2

1/2 X 2 1/2

3/8 X 2 3/8 X 2 1/2 X 2 1/2 X 2

5/8 5/8 5/8 5/8

13/16 13/16 13/16 13/16 1 3/16

7/16 7/16 7/16 7/16

7/16 7/16 9/16 9/16 9/16

N O

M

IN

AL

PI

PE

S

IZ

E

M

IN

IM

U

M D

IS

TA

N C

E

H

AN

G

ER

TA

KE

O U

T

R O

D D

IA

M

ET

ER

AN

C

H O

R

SI

ZE

M

IN

. T H

R

EA

D D

IS

TA

N C

E

D R

IL

L

D

IA

M

ET

ER

A B C D E F

FLOOR SLAB

PIPE RISER

PIPE CLAMP

PIPE CLAMP

PIPE RISER

BOLT SQUARE HEAD

INDICATING TYPE

ZONE CONTROL VALVE

WITH TAMPER SWITCH

CHECK VALVE

WATER FLOW SWITCH

TO SPRINKLER SYSTEM

ZONE-SEE FLOOR PLAN

FOR LOCATION AND SIZE

TEST-DRAIN VALVE WITH

PRESSURE RELIEF VALVE

ZONE TEST-DRAIN PIPING SIZED

PER NFPA 13

SPRINKLER-STANDPIPE RISER

EXPRESS DRAIN RISER

PRESSURE GAUGE

PIPE CLAMP WITH

GROUND WIRE

GROOVED

COUPLING

SECURE AREA WALL

NEW CONT. ALUMINA

SILICA FIBER OR

MINERAL WOOL BATT.

PACKING, MIN, 2: DEPTH

EXTEND GROUND WIRE

TO BUILDING

STRUCTURAL STEEL OR

NEAREST GROUND BAR

(NOT LOCATED WITHIN

AN ELECTRICAL PANEL)

FIRE STOPPING (PER

MANUFACTURER'S

INSTRUCTION (TYP.

BOTH SIDES)

STEEL PIPESTEEL PIPE STEEL PIPE

SECURE SIDEATTACK SIDE

MIN. 6"

1" 90° ELBOW

1" PIPING

TYPICAL BRANCH-

LINE SIZE MAY VARY

SEE FLOOR PLAN

FOR SIZES AND

LOCATION

CUT CEILING TO

ACCOMMODATE

ESCUTCHEON

RECESSED PENDENT SPRINKLER

ALL ARM-OVERS > 12"

HANGER REQUIRED

ALL ARM-OVERS < 12"

NO HANGER REQUIRED

RECESSED PENDENT

SPRINKLER

ESCUTCHEON

CEILING

1" x ½" REDUCER

JO

NE

S

FR

AN

KL

IN

R

D, S

UI

TE

R

AL

EI

G

H , N

C

-3

(9

1-

(9

) 8

-7

FA

X

LI

C

EN

SE

F -0

US Army Corps of Engineers ®

SHEET ID

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

1 2 3 4 5 6 7 8 9 10

A

D

AT

E M

AR

K

D

ES

C R

IP

TI

O N

BA

LT

IM

O

R E

D

IS

TR

IC

T

H O

PK

IN

S

PL

AZ

A

BA

LT

IM

O

R E

M

AR

YL

AN

D

FI

LE

N

AM

E:

FOR OFFICIAL USE ONLY

XX

X-

XX

X-

XX

X

XX

X-

XX

X-

XX

X

B

C

D

E

F

G

H

J

K

L

M

N

P

11 12 13 14 15 16 17 18 19 20

D R

AW

IN

G N

O

F1

-2 9-

FX501

SP

R

IN

KL

ER

D

ET

AI

LS

H U

M

PH

R

EY

S

EN

G

IN

EE

R

C

EN

TE

R

, A

LE

XA

N

D R

IA

, V

IR

G

IN

IA

PL

O

M

AX

H

TH

AI

W

BY

N U

M

FE

SC

AL

AN

TE

O

C

TO

BE

R

FX

1.

D

W G

BA

TT

AL

IO

N O

PE

R

AT

IO

N S

FA

C

IL

IT

Y

PN

/ P

NOT TO SCALEFX501

1 SPRINKLER ARMOVER RECESSED PENDENT

NOT TO SCALEFX501

2 SPRINKLER RECESSED PENDENT

NOT TO SCALEFX501

3 SPRINKLER UPRIGHT

NOT TO SCALEFX501

4 PIPE HANGER TOP OF BEAM

NOT TO SCALEFX501

5 PIPE HANGER CONCRETE SLAB

NOT TO SCALEFX501

6 RISER CLAMP

NOT TO SCALEFX501

7 ZONE CONTROL ASSEMBLY

NOT TO SCALEFX501

8 SECURE AREA WALL GROUND WIRE

NOT TO SCALEFX501

9 SPRINKLER GOOSENECK RECESSED PENDENT

O

FESSIONAL ENGIN

EE

R

PETER Q. LOMAX

LEVEL 1

0'-0"

32'-0"

47'-0"

FCA

FCA

DRAIN TO BUILDING

EXTERIOR STAIR 1STAIR 2

TO LEVEL 3

SPRINKLER SYSTEM FCA

16'-0"

ELEVATOR

FCA

LEVEL 2

LEVEL 3

ROOF

TO SPRINKLER

TOP OF ELEVATOR

TO LEVEL 2

SPRINKLER SYSTEM

TO LEVEL 1 SECURE

SPRINKLER SYSTEM

FC

A

TO LEVEL 1 NON-SECURE

SPRINKLER SYSTEM

FIRE ROOM

TO LEVEL 3

SPRINKLER SYSTEM

TO SPRINKLERS AT

TOP OF STAIR

TEST AND DRAIN TO

BUILDING EXTERIORFIRE

DEPARTMENT

CONNECTION

F

FX502

6" FIRE SERVICE

TO SPRINKLER SYSTEM

TO LEVEL 1 NON- SECURE

SPRINKLER SYSTEM AREA

FIRE

TO FIRE DEPARTMENT

CONNECTION

LEVEL 1

0' - 0"

LEVEL 2

16' - 0"

LIFT CLR ZONE

12' - 0"

TO SPRINKLER

SYSTEM

NEW 6" FIRE SERVICE

TO LEVEL 1

NON- SECURE

SPRINKLER

SYSTEM AREA

LEVEL 1

0' - 0"

LEVEL 2

16' - 0"

LIFT CLR ZONE

12' - 0"

A

TO FIRE SERVICE ROOM

JO

NE

S

FR

AN

KL

IN

R

D, S

UI

TE

R

AL

EI

G

H , N

C

-3

(9

1-

(9

) 8

-7

FA

X

LI

C

EN

SE

F -0

US Army Corps of Engineers ®

SHEET ID

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

1 2 3 4 5 6 7 8 9 10

A

D

AT

E M

AR

K

D

ES

C R

IP

TI

O N

BA

LT

IM

O

R E

D

IS

TR

IC

T

H O

PK

IN

S

PL

AZ

A

BA

LT

IM

O

R E

M

AR

YL

AN

D

FI

LE

N

AM

E:

FOR OFFICIAL USE ONLY

XX

X-

XX

X-

XX

X

XX

X-

XX

X-

XX

X

B

C

D

E

F

G

H

J

K

L

M

N

P

11 12 13 14 15 16 17 18 19 20

D R

AW

IN

G N

O

F1

-2 9-

FX502

SP

R

IN

KL

ER

D

ET

AI

LS

A

N D

R

IS

ER

D

IA

G

R

AM

H U

M

PH

R

EY

S

EN

G

IN

EE

R

C

EN

TE

R

, A

LE

XA

N

D R

IA

, V

IR

G

IN

IA

PL

O

M

AX

H

TH

AI

W

BY

N U

M

FE

SC

AL

AN

TE

O

C

TO

BE

R

FX

2.

D

W G

BA

TT

AL

IO

N O

PE

R

AT

IO

N S

FA

C

IL

IT

Y

PN

/ P

N.T.SFX502

1 SPRINKLER RISER DIAGRAM

3/8" = 1'-0"FX502

2 SPRINKLER PLAN - LEVEL 1 - ENLARGED FIRE ROOM

3/8" = 1'-0"FX502

3 RISER DETAIL

3/8" = 1'-0"FX502

4 FIRE DEPARTMENT CONNECTION

# SHEET NOTES

1. PROVIDE 6" BACKFLOW PREVENTER ASSEMBLY.

PROVIDE TAMPER SWITCHES FOR THE OS&Y VALVES.

2. PROVIDE 6" SUPERVISED BUTTERFLY VALVE IN

CLOSED POSITION FOR THE BACKFLOW PREVENTER

TEST HEADER.

3. PROVIDE 4" CHECK VALVE.

4. PROVIDE 6" ZONE RISER MODULAR ASSEMBLY

INCLUDING FLOW SWITCH, TEST AND DRAIN VALVE

WITH PRESSURE RELIEF VALVE.

5. PROVIDE 2" DRAIN PIPE TO EXTERIOR.

6. PROVIDE THRUST BLOCK. SEE CIVIL DRAWINGS FOR

DETAIL.

7. PROVIDE 4" STORZ FIRE DEPARTMENT CONNECTION

WITH CHECK VALVE AND AUTOMATIC BALL DRIP.

8. PROVIDE 6"X (3) 2½" BACKFLOW TEST HEADER WITH

AUTOMATIC BALL DRIP.

9. PROVIDE NEW 4"…