Attachment F - Vol_3_BOF HEC Original Documents Submittal Specifications 29 October 2021.pdf
PDF 5 MB Posted
- Attached to
- SOF BATTALION OPERATIONS FACILITY, HEC, ALEXANDRIA, VIRGINIA Federal contract opportunity
- Solicitation number
- W912DR22R0030
About this file
This federal contract opportunity announcement solicits construction services for the SOF Battalion Operations Facility at the Humphreys Engineer Center in Alexandria, Virginia. The U.S. Army Corps of Engineers, Baltimore District has been tasked to award a firm-fixed-price, design-bid-build construction contract utilizing the Best Value Tradeoff Process. The proposed project involves building a new SOF Battalion Operations Facility. Interested contractors should review the attached solicitation and attachments for full details of the requirement.
View the file
Other files for this federal contract opportunity
Show all 18
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Battalion Operations Facility Humphreys Engineer Center, Alexandria, Virginia
Project Number 91018
Specifications
29 October 2021
W912HD19D2000
Delivery Order W912DR20F0205
- Volume III of IV
ARCHITECTURAL
ELECTRICAL MECHANICAL
STRUCTURAL CIVIL
FIRE PROTECTION
TELECOMMUNICATIONS
C O
M
MONWEALTH OF VIRGINIA
P
R O
FESSIONAL ENGIN
EE
R
PETER Q. LOMAX
Lic. No. 0402062554
10/29/2021
10/29/202110/29/2021
Battalion Operations Facility Solicitation No: TBD Humphreys Engineer Center, Alexandria, Virginia Project Number: 91018
PROJECT TABLE OF CONTENTS Page | 1
PROJECT TABLE OF CONTENTS
DIVISION 01 - GENERAL REQUIREMENTS
01 11 00 SUMMARY OF WORK
01 14 00 WORK RESTRICTIONS
01 30 00 ADMINISTRATIVE REQUIREMENTS
01 32 01.00 10 PROJECT SCHEDULE
01 33 00 SUBMITTAL PROCEDURES
ATTACHMENT – SUBMITTAL REGISTER
ATTACHMENT B – ENG FORM 2025, MAY 2017
01 33 29 SUSTAINABILITY REPORTING
01 35 26 GOVERNMENT SAFETY REQUIREMENTS
01 42 00 SOURCES FOR REFERENCE PUBLICATIONS
01 45 00.00 10 QUALITY CONTROL
01 45 00.15 10 RESIDENT MANAGEMENT SYSTEM CONTRACTOR MODE (RMS CM)
01 45 35 SPECIAL INSPECTIONS
01 50 00 TEMPORARY CONSTRUCTION FACILITIES AND CONTROLS
01 57 19 TEMPORARY ENVIRONMENTAL CONTROLS
ATTACHMENT A – CGP NOTICE OF TERMINATION
ATTACHMENT B – REGISTRATION OF STATEMENT 2019
01 58 00 PROJECT IDENTIFICATION
01 74 19 CONSTRUCTION WASTE MANAGEMENT AND DISPOSAL
01 78 00 CLOSEOUT SUBMITTALS
01 78 23 OPERATION AND MAINTENANCE DATA
01 91 00.15 10 TOTAL BUILDING COMMISSIONING
APPENDIX A – OWNER’S PROJECT REQUIREMENT DOCUMENT
APPENDIX B – BASIS OF DESIGN
APPENDIX C – DESIGN PHASE COMMISSIONING PLAN
DIVISION 02 - EXISTING CONDITIONS
02 41 00 DEMOLITION
DIVISION 03 – CONCRETE
03 30 00 CAST-IN-PLACE CONCRETE
03 45 00 PRECAST ARCHITECTURAL CONTCRETE
DIVISION 04 – MASONRY
04 20 00 MASONRY
DIVISION 05 - METALS
05 12 00 STRUCTURAL STEEL
05 21 00 STEEL JOIST FRAMING
05 30 00 STEEL DECKS
05 40 00 COLD-FORMED METAL FRAMING
05 50 13 MISCELLANEOUS METAL FABRICATIONS
05 51 00 METAL STAIRS
05 51 33 METAL LADDERS
05 52 00 METAL RAILINGS
DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES
06 20 00 FINISH CARPENTRY
06 41 16.00 10 PLASTIC-LAMINATE-CLAD ARCHITECTURAL CABINETS
PROJECT TABLE OF CONTENTS Page | 4
26 29 23 VARIABLE FREQUENCY DRIVE SYSTEMS UNDER 600 VOLTS
26 32 15.00 10 DIESEL-GENERATOR SET STATIONARY 100-2500 KW, WITH
AUXILIARIES
26 33 53 STATIC UNINTERRUPTIBLE POWER SUPPLY (UPS)
26 41 00 LIGHTNING PROTECTION SYSTEM
26 51 00 INTERIOR LIGHTING
26 56 00 EXTERIOR LIGHTING
DIVISION 27 – COMMUNICATIONS
27 05 10 COMMON WORK RESULTS FOR AUDIO-VIDEO SYSTEMS
27 05 14.00 10 CABLE TELEVISION PREMISES DISTRIBUTION SYSTEM
27 05 28.33 CONDUITS AND BACKBOXES FOR AUDIO-VIDEO (AV) SYSTEMS
27 10 00 BUILDING TELECOMMUNICATIONS CABLING SYSTEM
27 41 16 AUDIO-VIDEO SYSTEMS BASIC MATERIALS AND METHODS
27 41 16.20 AUDIO-VIDEO SYSTEMS NARRATIVE
DIVISION 28 - ELECTRONIC SAFETY AND SECURITY
28 08 10 ELECTRONIC SECURITY SYSTEM ACCEPTANCE TESTING
28 10 05 ELECTRONIC SECURITY SYSTEMS (ESS)
28 31 76 INTERIOR FIRE ALARM AND MASS NOTIFICATION SYSTEM
DIVISION 31 - EARTHWORK
31 00 00 EARTHWORK
31 11 00 CLEARING AND GRUBBING
31 61 00 AGGREGATE PIERS
DIVISION 32 - EXTERIOR IMPROVEMENTS
32 05 33 LANDSCAPE ESTABLISHMENT
32 11 10 PAVEMENT DRAINAGE LAYER (RDM)
32 11 23 DENSE GRADED AGGREGATE (DGA) BASE COURSE
32 12 17.05 BITUMINOUS PAVING - VIRGINIA (SUPERPAVE)
32 16 19 CONCRETE CURBS, GUTTERS AND SIDEWALKS
32 31 13 CHAIN LINK FENCES AND GATES
32 31 13.53 HIGH SECURITY FENCES
32 92 19 SEEDING
32 92 23 SODDING
32 93 00 EXTERIOR PLANTS
DIVISION 33 – UTILITIES
33 11 00 WATER UTILITY DISTRIBUTION PIPING
33 30 00 SANITARY SEWERAGE
33 40 00 STORM DRAINAGE UTILITIES
33 46 16 SUBDRAINAGE SYSTEM
33 71 02 UNDERGROUND ELECTRICAL DISTRIBUTION
33 82 00 TELECOMMUNICATIONS OUTSIDE PLANT (OSP)
-- End of Project Table of Contents –
PROJECT TABLE OF CONTENTS Page | 2
DIVISION 07 - THERMAL AND MOISTURE PROTECTION
07 05 23 PRESSURE TESTING AN AIR BARRIER SYSTEM FOR AIR TIGHTNESS
07 19 00 WATER REPELLENTS
07 21 13 BOARD INSULATION
07 21 16 MINERAL FIBER BLANKET INSULATION
07 22 00 ROOF AND DECK INSULATION
07 27 10.00 10 BUILDING AIR BARRIER SYSTEM
07 27 19.01 SELF-ADHERING AIR BARRIERS
07 27 26 FLUID-APPLIED MEMBRANE AIR BARRIERS
07 42 63 FABRICATED WALL PANEL ASSEMBLIES
07 53 23 ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING
07 60 00 FLASHING AND SHEET METAL
07 84 00 FIRESTOPPING
07 92 00 JOINT SEALANTS
DIVISION 08 – OPENINGS
08 11 13 STEEL DOORS AND FRAMES
08 14 00 WOOD DOORS
08 33 23 OVERHEAD COILING DOORS
08 41 13 ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS
08 44 00 CURTAIN WALL AND GLAZED ASSEMBLIES
08 71 00 DOOR HARDWARE
08 81 00 GLAZING
08 91 00 METAL WALL LOUVERS
DIVISION 09 – FINISHES
09 22 00 SUPPORTS FOR GYPSUM BOARD
09 29 00 GYPSUM BOARD
09 30 10 CERAMIC TILING
09 51 00 ACOUSTICAL CEILINGS
09 62 38 STATIC-CONTROL FLOORING
09 65 00 RESILIENT FLOORING
09 68 00 CARPETING
09 69 13 RIGID GRID ACCESS FLOORING
09 90 00 PAINTS AND COATINGS
DIVISION 10 – SPECIALTIES
10 11 00 VISUAL DISPLAY UNITS
10 14 00.10 EXTERIOR SIGNAGE
10 21 13 TOILET COMPARTMENTS
10 22 13 WIRE MESH PARTITIONS
10 26 00 WALL AND DOOR PROTECTION
10 28 13 TOILET ACCESSORIES
10 44 16 FIRE EXTINGUISHERS
DIVISION 11 – EQUIPMENT
11 31 13 ELECTRIC KITCHEN EQUIPMENT
DIVISION 12 - FURNISHINGS
12 24 13 ROLLER WINDOW SHADES
12 32 00 MANUFACTURED METAL CASEWORK
12 36 00 COUNTERTOPS
PROJECT TABLE OF CONTENTS Page | 3
12 48 13 ENTRANCE FLOOR MATS
12 50 00.13 00 FURNITURE AND FURNITURE INSTALLATION
DIVISION 14 -CONVEYING EQUIPMENT
14 21 23 MACHINE-ROOM-LESS ELECTRIC TRACTION PASSENGER ELEVATORS
DIVISION 21 – FIRE SUPPRESSION
21 13 13.10 WET PIPE SPRINKLER SYSTEMS
DIVISION 22 – PLUMBING
22 00 00 PLUMBING, GENERAL PURPOSE
22 07 19.00 40 PLUMBING PIPING INSULATION
22 14 29.00 40 SUMP PUMPS
DIVISION 23 - HEATING, VENTILATING, AND AIR CONDITIONING (HVAC)
23 00 00 AIR SUPPLY, DISTRIBUTION, VENTILATION, AND EXHAUST SYSTEMS
23 05 15 COMMON PIPING FOR HVAC
23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC
23 07 00 THERMAL INSULATION FOR MECHANICAL SYSTEMS
23 09 00 INSTRUMENTATION AND CONTROL FOR HVAC
23 09 13 INSTRUMENTATION AND CONTROL DEVICES FOR HVAC
23 09 23.02 BACNET DIRECT DIGITAL CONTROL FOR HVAC AND OTHER BUILDING
CONTROL SYSTEMS
23 11 25 FACILITY GAS PIPING
23 52 00 HEATING BOILERS
23 64 26 CHILLED, CHILLED-HOT, AND CONDENSER WATER PIPING SYSTEMS
23 65 00 COOLING TOWERS AND REMOTE EVAPORATIVELY-COOLED CONDENSERS
23 81 00 DECENTRALIZED UNITARY HVAC EQUIPMENT
DIVISION 25 - INTEGRATED AUTOMATION
25 05 11.01 CYBERSECURITY FOR FACILITY-RELATED CONTROL SYSTEMS (HVAC)
ATTACHMENT – HVAC SYSTEM
25 05 11.02 CYBERSECURITY FOR FACILITY-RELATED CONTROL SYSTEMS (ELEC
GENERATOR)
ATTACHMENT – GEN SYSTEM
25 05 11.03 CYBERSECURITY FOR FACILITY-RELATED CONTROL SYSTEMS (ELEC
UPS)
ATTACHMENT – UPS SYSTEM
25 05 11.04 CYBERSECURITY FOR FACILITY-RELATED CONTROL SYSTEMS (ELEC
SWITCHBOARD)
SWBD SYSTEM
25 05 11.05 CYBERSECURITY FOR FACILITY-RELATED CONTROL SYSTEMS (ESS)
ESS SYSTEM
25 05 11.07 CYBERSECURITY FOR FACILITY-RELATED CONTROL SYSTEMS (FA/MNS)
25 10 10 UTILITY MONITORING AND CONTROL SYSTEM (UMCS) FRONT END AND
INTEGRATION
DIVISION 26 – ELECTRICAL
26 00 00.00 20 BASIC ELECTRICAL MATERIALS AND METHODS
26 08 00 APPARATUS INSPECTION AND TESTING
26 20 00 INTERIOR DISTRIBUTION SYSTEM
26 24 13 SWITCHBOARDS
26 28 01.00 10 COORDINATED POWER SYSTEM PROTECTION
SECTION TABLE OF CONTENTS
DIVISION 25 - INTEGRATED AUTOMATION
SECTION 25 05 11.01
CYBERSECURITY FOR FACILITY-RELATED CONTROL SYSTEMS (HVAC)
11/17
PART 1 GENERAL
1.1 CONTROL SYSTEM APPLICABILITY
1.2 RELATED REQUIREMENTS
1.3 REFERENCES
1.4 DEFINITIONS
1.4.1 Computer
1.4.2 Network Connected
1.4.3 User Account Support Levels
1.4.3.1 FULLY Supported
1.4.3.2 MINIMALLY Supported
1.4.3.3 NOT Supported
1.4.4 User Interface
1.4.4.1 Limited Local User Interface
1.4.4.2 Full Local User Interface
1.4.4.3 Remote User Interface
1.5 ADMINISTRATIVE REQUIREMENTS
1.5.1 Coordination
1.6 SUBMITTALS
1.7 QUALITY CONTROL
1.7.1 Certifications and Qualifications
1.8 CYBERSECURITY DOCUMENTATION
1.8.1 Cybersecurity Interconnection Schedule
1.8.2 Network Communication Report
1.8.3 Control System Inventory Report
1.8.4 Software Recovery and Reconstitution Images
1.8.5 Cybersecurity Riser Diagram
1.8.6 Control System Cybersecurity Documentation
1.8.6.1 Software Applications
1.8.6.2 For HVAC Control System Devices
1.8.6.2.1 HVAC Control System Devices FULLY Supporting User
Accounts
1.8.6.2.2 All Other HVAC Control System Devices
1.8.6.3 Default Requirements for Control System Devices
1.9 SOFTWARE UPDATE LICENSING
1.10 CYBERSECURITY DURING CONSTRUCTION
1.10.1 Contractor Computer Equipment
1.10.1.1 Operating System
1.10.1.2 Anti-Malware Software
1.10.1.3 Passwords and Passphrases
1.10.1.4 Contractor Computer Cybersecurity Compliance Statements
1.10.2 Temporary IP Networks
1.10.2.1 Network Boundaries and Connections
1.10.3 Government Access to Network
1.10.4 Temporary Wireless IP Networks
1.10.5 Passwords and Passphrases
SECTION 25 05 11.01 Page 1
1.10.6 Contractor Temporary Network Cybersecurity Compliance
Statements
1.11 CYBERSECURITY DURING WARRANTY PERIOD
PART 2 PRODUCTS
PART 3 EXECUTION
3.1 ACCESS CONTROL REQUIREMENTS
3.1.1 User Accounts
3.1.1.1 For HVAC Control System Devices
3.1.1.2 Default Requirements for Control System Devices
3.1.2 Unsuccessful Logon Attempts
3.1.2.1 Devices MINIMALLY Supporting Accounts
3.1.2.2 Devices FULLY Supporting Accounts
3.1.2.3 High Availability Interfaces Exempt from Unsuccessful
Logon Attempts Requirements
3.1.3 System Use Notification
3.1.3.1 User Interface Banner Schedule
3.1.4 Permitted Actions Without Identification or Authentication
3.1.5 Wireless Access
3.1.5.1 Wireless IP Communications
3.1.5.2 Non-IP Wireless Communication
3.2 CYBERSECURITY AUDITING
3.2.1 Audit Events, Content of Audit Records, and Audit Generation
3.2.1.1 HVAC Control System Devices
3.2.1.1.1 HVAC Control System Devices FULLY Supporting User
Accounts
3.2.1.1.2 Other HVAC Control System Devices
3.2.1.2 Default Requirements for Control System Devices
3.2.1.2.1 Devices Which FULLY Support Accounts
3.2.1.2.1.1 Audited Events
3.2.1.2.1.2 Audit Event Information To Record
3.2.1.2.2 Devices Which Do Not FULLY Support Accounts
3.2.2 Audit Storage Capacity and Audit Upload
3.2.2.1 Device Audit Record Upload Software
3.2.3 Response to Audit Processing Failures
3.2.4 Time Stamps
3.2.4.1 For HVAC Control System Devices
3.2.4.2 Default Requirements for Control System Devices
3.3 REQUIREMENTS FOR LEAST FUNCTIONALITY
3.3.1 Non-IP Control Networks
3.3.2 IP Control Networks
3.4 SAFE MODE AND FAIL SAFE OPERATION
3.5 IDENTIFICATION AND AUTHENTICATION
3.5.1 User Identification and Authentication
3.5.1.1 HVAC Control Systems Devices
3.5.1.2 Default Requirements for Control System Devices
3.5.2 Authenticator Management
3.5.2.1 Authentication Type
3.5.2.1.1 For HVAC Control System Devices
3.5.2.1.2 Default Requirements for Control System Devices
3.5.2.2 Password-Based Authentication Requirements
3.5.2.2.1 Passwords for Non-Computer Devices FULLY Supporting
Accounts
3.5.2.2.2 Passwords for Web Interfaces
3.5.2.2.3 Passwords for Devices Minimally Supporting Accounts
3.5.2.2.4 Password Configuration and Reporting
SECTION 25 05 11.01 Page 2
3.5.2.3 Hardware Token-Based Authentication Requirements
3.5.3 Authenticator Feedback
3.5.4 Device Identification and Authentication
3.5.4.1 For HVAC Control System Devices
3.5.4.2 Default Requirements for Control System Devices
3.6 EMERGENCY POWER
3.7 DURABILITY TO VULNERABILITY SCANNING
3.7.1 HVAC Control System Devices Other Than Computers
3.7.2 Default Requirements for Control System Devices
3.8 FIPS 201-2 REQUIREMENT
3.9 DEVICES WITH CONNECTION TO MULTIPLE IP NETWORKS
3.10 SYSTEM AND COMMUNICATION PROTECTION
3.10.1 Denial of Service Protection, Process Isolation and Boundary
Protection
3.10.2 Cryptographic Protection
3.11 SYSTEM AND INTEGRATION INTEGRITY
3.11.1 Malicious Code Protection
3.11.2 Information System Monitoring
3.11.3 Software, Firmware, And Information Integrity
3.12 FIELD QUALITY CONTROL
3.12.1 Tests
-- End of Section Table of Contents --
SECTION 25 05 11.01 Page 3
SECTION 25 05 11.01
CYBERSECURITY FOR FACILITY-RELATED CONTROL SYSTEMS (HVAC)
11/17
PART 1 GENERAL
Many subparts in this Section contain text in curly braces ("{" and "}") indicating which cybersecurity control and control correlation identifier (CCI) the requirements of the subpart relate to. The text inside these curly braces is for Government reference only, and enables coordination of the requirements of this Section with the RMF process throughout the design and construction process. Text in curly braces are not contractor requirements.
This Section refers to Security Requirements Guide (SRGs) and Security Technical Implementation Guide (STIGs). STIGs and SRGs are are available online at the Information Assurance Support Environment (IASE) website at http://iase.disa.mil/stigs/Pages/index.aspx . Not all control system components have applicable STIGs or SRGs.
1.1 CONTROL SYSTEM APPLICABILITY
There are multiple versions of this Section associated with this project.
Different versions have requirements applicable to different control systems. This specific Section applies only to the following control systems: HVAC Controls .
1.2 RELATED REQUIREMENTS
All Sections containing facility-related control systems or control system components are related to the requirements of this Section. Review all specification sections to determine related requirements.
1.3 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN SOCIETY OF HEATING, REFRIGERATING AND AIR-CONDITIONING
ENGINEERS (ASHRAE)
ASHRAE 135 (2016) BACnet—A Data Communication Protocol for Building Automation and Control Networks
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE 802.1x (2010) Local and Metropolitan Area Networks - Port Based Network Access Control
NATIONAL INSTITUTE OF STANDARDS AND TECHNOLOGY (NIST)
NIST FIPS 201-2 (2013) Personal Identity Verification
SECTION 25 05 11.01 Page 4
(PIV) of Federal Employees and Contractors
U.S. DEPARTMENT OF DEFENSE (DOD)
DODI 8551.01 (2014) Ports, Protocols, and Services Management (PPSM)
DTM 08-060 (2008) Policy on Use of Department of Defense (DoD) Information Systems - Standard Consent Banner and User Agreement
1.4 DEFINITIONS
1.4.1 Computer
As used in this Section, a computer is one of the following:
a. a device running a non-embedded desktop or server version of Microsoft Windows
b. a device running a non-embedded version of MacOS
c. a device running a non-embedded version of Linux
d. a device running a version or derivative of the Android OS, where Android is considered separate from Linux
e. a device running a version of Apple iOS
1.4.2 Network Connected
A component is network connected (or "connected to a network") only when the device has a network transceiver which is directly connected to the network and implements the network protocol. A device lacking a network transceiver (and accompanying protocol implementation) can never be considered network connected. Note that a device connected to a non-IP network is still considered network connected (an IP connection or IP address is not required for a device to be network connected).
Any device that supports wireless communication is network connected, regardless of whether the device is communicating using wireless .
1.4.3 User Account Support Levels
The support for user accounts is categorized in this Section as one of three levels:
1.4.3.1 FULLY Supported
Device supports configurable individual accounts. Accounts can be created, deleted, modified, etc. Privileges can be assigned to accounts.
1.4.3.2 MINIMALLY Supported
Device supports a small, fixed number of accounts (perhaps only one).
Accounts cannot be modified. A device with only a "User" and an "Administrator" account would fit this category. Similarly, a device with two PINs for logon - one for restricted and one for unrestricted rights would fit here (in other words, the accounts do not have to be the
SECTION 25 05 11.01 Page 5 traditional "user name and password" structure).
1.4.3.3 NOT Supported
Device does not support any Access Enforcement therefore the whole concept of "account" is meaningless.
1.4.4 User Interface
Generally, a user interface is hardware on a device allowing user interaction with that device via input (buttons, switches, sliders, keyboard, touch screen, etc.) and a screen. There are three types of user interfaces defined in this Section: Limited Local User Interface, Full Local User Interface and Remote User Interface. In this Section, when the term "User Interface" is used without specifying which type, it refers only to Full Local User Interface and Remote User Interface (NOT to Limited Local User Interface).
1.4.4.1 Limited Local User Interface
A Limited Local User Interface is a user interface where the interaction is limited, fixed at the factory, and cannot be modified in the field.
The user must be physically at the device to interact with it.
Examples of Limited Local User Interface include thermostats (Space Sensor Modules as defined in Section 23 09 13 INSTRUMENTATION AND CONTROL DEVICES
FOR HVAC).
1.4.4.2 Full Local User Interface
A Full Local User Interface is a user interface where the interaction and displays are field-configurable.
Examples of a Full Local User Interface include local applications on a computer and user interfaces to Variable Speed Drives .
1.4.4.3 Remote User Interface
A Remote User Interface is a user interface on a Client device allowing user interaction with a different Server device. The user need not be physically at the Server device to interact with it.
Examples of Remote User Interfaces include web browsers and Local Display Panels as defined in Section 23 09 00 INSTRUMENTATION AND CONTROL FOR HVAC.
1.5 ADMINISTRATIVE REQUIREMENTS
1.5.1 Coordination
Coordinate the execution of this Section with the execution of all other Sections related to control systems as indicated in the paragraph RELATED REQUIREMENTS. Items that must be considered when coordinating project efforts include but are not limited to:
a. If requesting permission for wireless communication, the Wireless Communication Request submittal must be approved prior to control system device selection and integration.
b. If requesting permission for alternate account lock permissions, the
SECTION 25 05 11.01 Page 6
Device Account Lock Exception Request must be approved prior to control system device selection and integration.
c. If requesting permission for the use of a device with multiple IP connections, the Multiple IP Connection Device Request must be approved prior to control system device selection and integration.
d. If the Device Audit Record Upload Software is to be installed on a computer not being provided as part of the control system, coordination is required to identify the computer on which to install the software.
e. Cybersecurity Interconnection Schedule must be coordinated with other work that will be interconnected to, and interconnections must be approved by the Government before relying on them for system functionality.
f . Cybersecurity testing support must be coordinated across control systems and with the Government cybersecurity testing schedule.
g. Passwords must be coordinated with the indicated contact for the project site.
h. If applicable, HTTP web server certificates must be obtained from the indicated contact for the project site.
i . Contractor Computer Cybersecurity Compliance Statements for each contractor using contractor owned computers.
1.6 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor Quality Control approval. Submittals with an "S" are for inclusion in the Sustainability eNotebook, in conformance with Section 01 33 29 SUSTAINABILITY REPORTING.
Submit the following in accordance with Section 01 33 00 SUBMITTAL
PROCEDURES:
SD-01 Preconstruction Submittals
Device Account Lock Exception Request ; G, AE
Multiple IP Connection Device Request ; G, AE
Contractor Computer Cybersecurity Compliance Statements ; G, AE
Contractor Temporary Network Cybersecurity Compliance Statements ; G, AE
SD-02 Shop Drawings
User Interface Banner Schedule ; G, AE
Network Communication Report ; G, AE
Cybersecurity Riser Diagram ; G, AE
Control System Inventory Report ; G, AE
SECTION 25 05 11.01 Page 7
Cybersecurity Interconnection Schedule ; GSD-03 Product Data
Control System Cybersecurity Documentation ; G, AE
SD-07 Certificates
Software Licenses ; G, AE
SD-11 Closeout Submittals
Password Summary Report ; G, AE
Software Recovery And Reconstitution Images ; G, AE
Device Audit Record Upload Software ; G, AE
1.7 QUALITY CONTROL
1.7.1 Certifications and Qualifications For the HVAC control system:
CYBERSECURITY SERVICES
Obtain the services of a Cybersecurity professional to implement the requirements of this Specification. The Cybersecurity professional must interpret and apply the requirements to the indicated control system,advise the control system subcontractor on the implementation of the requirements, verify the implementation of the requirements, compile and submit the required documentation to the Government, coordinate the requirements with the Government, and perform other duties as required to implement the requirements.
The Cybersecurity professional must have one of the following certificates:
-Global Industrial Cyber Security Professional (GICSP) or Certified -Information Systems Security Professional (CISSP)
1.8 CYBERSECURITY DOCUMENTATION
1.8.1 Cybersecurity Interconnection Schedule
{For Reference Only: This subpart (and its subparts) relates to CA-3(b), CCI-00 0258}
Provide a completed Cybersecurity Interconnection Schedule documenting connections between the installed system and other systems. Provide the following information for each device communicating between systems:
Device Identifier, Device Description, Transport layer Protocol, Network Address, Port (if applicable), MAC (Layer 2) address (if applicable), Media, Application Protocol, Service (if applicable), Descriptive Purpose of communication. For communication with other authorized systems also provide the Foreign Destination and POC for Destination. If other control system Sections used on this project include submittals documenting this information, provide copies of those submittals to meet this requirement.
The HVAC facility control system will connect to a separately authorized system (i.e. the basewide LAN) through a Level 3 FPOC hand-off. That IP transition will be facilitated by the network staff or by the control system contractor with oversight by the network staff.
In addition to the requirements of Section 01 33 00 SUBMITTAL PROCEDURES, SECTION 25 05 11.01 Page 8 provide the Cybersecurity Interconnection Schedule as an editable Microsoft Excel file (a template Cybersecurity Interconnection Schedule in Excel format is available at http://www.wbdg.org/ffc/dod/unified-facilities-guide-specifications-ufgs/forms-graphics-tables
1.8.2 Network Communication Report
{For Reference Only: This subpart (and its subparts) relates to CA-9;
CCI-002102, CCI-002103, CCI-002104, CCI-002105 and also the submittal requirements associated with CM-6, CM-7 and SC-41 }
Provide a network communication report. For each networked controller, document the communication characteristics of the controller including communication protocols, services used, and a general description of what information is communicated over the network. For each controller using IP, document all TCP and UDP ports used. If other control system Sections used on this project include submittals documenting this information, provide copies of those submittals to meet this requirement.
In addition to the requirements of Section 01 33 00 SUBMITTAL PROCEDURES, provide the Network Communication Report as an editable Microsoft Excel file.
1.8.3 Control System Inventory Report
{For Reference Only: This subpart (and its subparts) relates to CM-8(a), CP-12, SI-17, IA-3; CCI-000389, CCI-000392, CCI-000398, CCI-002855, CCI-002856, CCI-002857, CCI-002773, CCI-002774, CCI-002775, CCI-000777, CCI-000778, CCI-001958}
Provide a Control System Inventory report using the Inventory Spreadsheet listed under this Section at http://www.wbdg.org/ffc/dod/unified-facilities-guide-specifications-ufgs/forms-graphics-tables documenting all devices, including networked devices, network infrastructure devices, non-networked devices, input devices (e.g.
sensors) and output devices (e.g. actuators). For each device provide all applicable information for which there is a field on the spreadsheet in accordance with the instructions on the spreadsheet.
In addition to the requirements of Section 01 33 00 SUBMITTAL PROCEDURES, provide the Control System Inventory Report as an editable Microsoft Excel file.
1.8.4 Software Recovery and Reconstitution Images
{For Reference Only: This subpart (and its subparts) relates to CP-10;
CCI-000550, CCI-000551, CCI-000552 , CM-2, CCI-000293 }
For each computer and control system device on which software is installed under this project, provide a recovery image of the final as-built computer and control system device . This image must allow for bare-metal restore such that restoration of the image is sufficient to restore system operation to the imaged state without the need for re-installation of software.
If additional user permissions are required to meet this requirement, coordinate the creation of the image with the government .
SECTION 25 05 11.01 Page 9
1.8.5 Cybersecurity Riser Diagram
{For Reference Only: This subpart (and its subparts) relates to PL-2(a);
CCI-003051, CCI-003053}
Provide a cybersecurity riser diagram of the complete control system including all network and controller hardware. If the control system specifications require a riser diagram submittal, provide a copy of that submittal as the cybersecurity riser diagram. Otherwise, provide a riser diagram in one-line format overlayed on a facility schematic.
1.8.6 Control System Cybersecurity Documentation
This subpart (and its subparts) relates to SA-5 (a),(b),(c); CCIs:
CCI-003124, CCI-003125, CCI-003126, CCI-003127, CCI-003128, CCI-003129,
CCI-003130, CCI-003131 , AC-4; CCIs: CCI-001368, CCI-001414, CCI-001548, CCI-001550,CCI-001551. }
Provide a Control System Cybersecurity Documentation submittal containing the indicated information for each device and software application.
1.8.6.1 Software Applications
For all software applications running on computers provide:
a. administrator documentation that describes secure configuration of the software {relates to CCI-003124}
b. administrator documentation that describes secure installation of the software {relates to CCI-003125}
c. administrator documentation that describes secure operation of the software {relates to CCI-003124}
d. administrator documentation that describes effective use and maintenance of security functions or mechanisms for the software {relates to CCI-003127}
e. administrator documentation that describes known vulnerabilities regarding configuration and use of administrative (i.e. privileged) functions for the software {relates to CCI-003128}
f. user documentation that describes user-accessible security functions or mechanisms in the software and how to effectively use those security functions or mechanisms {relates to CCI-003129}
g. user documentation that describes methods for user interaction which enables individuals to use the software in a more secure manner {relates to CCI-003130}
h. user documentation that describes user responsibilities in maintaining the security of the software {relates to CCI-003131}
1.8.6.2 For HVAC Control System Devices
1.8.6.2.1 HVAC Control System Devices FULLY Supporting User Accounts
For all HVAC Control System Devices which FULLY support user accounts, provide:
SECTION 25 05 11.01 Page 10
a. Documentation that describes secure configuration of the device {for reference only: relates to CCI-003124}
b. Documentation that describes secure operation of the device {for reference only: relates to CCI-003124}
c. Documentation that describes effective use and maintenance of security functions or mechanisms for the device {for reference only: relates to
CCI-003127}
d. Documentation that describes known vulnerabilities regarding configuration and use of administrative (i.e. privileged) functions for the device {for reference only: relates to CCI-003128}
e. Documentation that describes user-accessible security functions or mechanisms in the device and how to effectively use those security functions or mechanisms; or a specific indication that there are no user-accessible security functions or mechanisms in the device {for reference only: relates to CCI-003129}
f. Documentation that describes methods for user interaction which enables individuals to use the device in a more secure manner {for reference only: relates to CCI-003130}
1.8.6.2.2 All Other HVAC Control System Devices
For all HVAC Control System Devices which do not FULLY support user accounts, provide:
a. Documentation that describes secure configuration of the device; or a specific indication that there are no secure configuration steps that apply {for reference only: relates to CCI-003124}
b. Documentation that describes effective use and maintenance of security functions or mechanisms for the device; or a specific indication that there are no security functions or mechanisms in the device {for reference only: relates to CCI-003127}
c. For devices which include a user interface, documentation that describes methods for user interaction which enables individuals to use the device in a more secure manner {for reference only: relates to
CCI-003130}
1.8.6.3 Default Requirements for Control System Devices
For control system devices where Control System Cybersecurity Documentation requirements are not otherwise indicated in this Section, provide:
a. Documentation that describes secure configuration of the device {for reference only: relates to CCI-003124}
b. Documentation that describes secure installation of the device {for reference only: relates to CCI-003125}
c. Documentation that describes secure operation of the device {for reference only: relates to CCI-003124}
d. Documentation that describes effective use and maintenance of security
SECTION 25 05 11.01 Page 11 functions or mechanisms for the device {for reference only: relates to
CCI-003127}
e. Documentation that describes known vulnerabilities regarding configuration and use of administrative (i.e. privileged) functions for the device {for reference only: relates to CCI-003128}
f. Documentation that describes user-accessible security functions or mechanisms in the device and how to effectively use those security functions or mechanisms {for reference only: relates to CCI-003129}
g. Documentation that describes methods for user interaction which enables individuals to use the device in a more secure manner {for reference only: relates to CCI-003130}
h. Documentation that describes user responsibilities in maintaining the security of the device {for reference only: relates to CCI-003131}
1.9 SOFTWARE UPDATE LICENSING
{For Reference Only: This subpart (and its subparts) relates to SI-2 (a),(c); CCI-001227, CCI-002605}
In addition to all other licensing requirements, all software licensing must include licensing of the following software updates for a period of no less than 5 years:
a. Security and bug-fix patches issued by the software manufacturer.
b. Security patches to address any vulnerability identified in the National Vulnerability Database at http://nvd.nist.gov with a Common Vulnerability Scoring System (CVSS) severity rating of MEDIUM or higher.
Provide a single Software Licenses submittal with documentation of the software licenses for all software provided
1.10 CYBERSECURITY DURING CONSTRUCTION
{For Reference Only: This subpart (and its subparts) relates to AC-18, SA-3, CCI-0 00258 , CCI-001438, CCI-002323, CCI-001439, CCI-001441, CCI-001443, CCI-001444 }
In addition to the control system cybersecurity requirements indicated in this section, meet following requirement throughout the construction process.
1.10.1 Contractor Computer Equipment
Contractor owned computers may be used for construction. When used, contractor computers must meet the following requirements:
1.10.1.1 Operating System
The operating system must be an operating system currently supported by the manufacturer of the operating system. The operating system must be current on security patches and operating system manufacturer required updates.
SECTION 25 05 11.01 Page 12
1.10.1.2 Anti-Malware Software
The computer must run anti-malware software from a reputable software manufacturer. Anti-malware software must be a version currently supported by the software manufacturer, must be current on all patches and updates, and must use the latest definitions file. All computers used on this project must be scanned using the installed software at least once per day.
1.10.1.3 Passwords and Passphrases
The passwords and passphrases for all computers must be changed from their default values. Passwords must be a minimum of eight characters with a minimum of one uppercase letter, one lowercase letter, one number and one special character.
1.10.1.4 Contractor Computer Cybersecurity Compliance Statements
Provide a single submittal containing completed Contractor Computer Cybersecurity Compliance Statements for each company using contractor owned computers. Contractor Computer Cybersecurity Compliance Statements must use the template published at http://www.wbdg.org/ffc/dod/unified-facilities-guide-specifications-ufgs/forms-graphics-tables Each Statement must be signed by a cybersecurity representative for the relevant company.
1.10.2 Temporary IP Networks
Temporary contractor-installed IP networks may be used during construction. When used, temporary contractor-installed IP networks must meet the following requirements:
1.10.2.1 Network Boundaries and Connections
The network must not extend outside the project site and must not connect to any IP network other than IP networks provided under this project or Government furnished IP networks provided for this purpose. Any and all network access from outside the project site is prohibited.
1.10.3 Government Access to Network
Government personnel must be allowed to have complete and immediate access to the network at any time in order to verify compliance with this specification
1.10.4 Temporary Wireless IP Networks
In addition to the other requirements on temporary IP networks, temporary wireless IP (WiFi) networks must not interfere with existing wireless network and must use WPA2 security. Network names (SSID) for wireless networks must be changed from their default values.
1.10.5 Passwords and Passphrases
The passwords and passphrases for all network devices and network access must be changed from their default values. Passwords must be a minimum 8 characters with a minimum of one uppercase letter, one lowercase letter, one number and one special character.
SECTION 25 05 11.01 Page 13
1.10.6 Contractor Temporary Network Cybersecurity Compliance Statements
Provide a single submittal containing completed Contractor Temporary Network Cybersecurity Compliance Statements for each company implementing a temporary IP network. Contractor Temporary Network Cybersecurity Compliance Statements must use the template published at http://www.wbdg.org/ffc/dod/unified-facilities-guide-specifications-ufgs/forms-graphics-tables Each Statement must be signed by a cybersecurity representative for the relevant company. If no temporary IP networks will be used, provide a single copy of the Statement indicating this.
1.11 CYBERSECURITY DURING WARRANTY PERIOD
All work performed on the control system after acceptance must be performed using Government Furnished Equipment or equipment specifically and individually approved by the Government.
PART 2 PRODUCTS
(NOT USED)
PART 3 EXECUTION
3.1 ACCESS CONTROL REQUIREMENTS
3.1.1 User Accounts
{For Reference Only: This subpart (and its subparts) relate to AC-2(a)and
AC-3; CCI-002110, CCI-000213 , AC-6(1); CCI-001558, CCI-002221, CCI-002222,
CCI-002223, AC-6(2); CCI-000039, CCI-001419, AC-6(10); CCI-002235, AC-11;
CCI-000058, CCI-000059, CCI-000056 AC-11(1); CCI-000060 .}
Any device supporting user accounts (either FULLY or MINIMALLY) must limit access to the device according to specified limitations for each account.
Install and configure any device having a STIG or SRG in accordance with that STIG or SRG.
3.1.1.1 For HVAC Control System Devices
Devices with web interfaces must either FULLY support user accounts or have their web interface disabled. Field devices with full local user interfaces allowing modification of data must at least MINIMALLY support user accounts.
3.1.1.2 Default Requirements for Control System Devices
{For Reference Only: This subpart (and its subparts) relates to AC-12, CCI-002361}
For control system devices where User Account requirements are not otherwise indicated in this Section:
a. Devices with web interfaces must either FULLY support user accounts or have their web interface disabled.
b. Field devices with full local user interfaces allowing modification of data must FULLY support user accounts.
c. Field devices with read-only full local user interfaces must at least
SECTION 25 05 11.01 Page 14
MINIMALLY support user accounts.
d. All devices must at least MINIMALLY support user accounts.
3.1.2 Unsuccessful Logon Attempts
{For Reference Only: This subpart (and its subparts) relate AC-7 (a), AC-7 (b); CCI-000043, CCI-000044, CCI-001423, CCI-002236, CCI-002237, CCI-002238}
Except for high availability user interfaces indicated as exempt, devices must meet the indicated requirements for handling unsuccessful logon attempts.
3.1.2.1 Devices MINIMALLY Supporting Accounts
Devices which MINIMALLY support accounts are not required to lock based on unsuccessful logon attempts.
3.1.2.2 Devices FULLY Supporting Accounts
Devices which FULLY support accounts must meet the following requirements. If a device cannot meet these requirements, document device capabilities to protect from subsequent unsuccessful logon attempts and propose alternate protections in a Device Account Lock Exception Request submittal. Do not implement alternate protection measures without explicit permission from the Government.
a. It must lock the user account when three unsuccessful logon attempts occur within a 15 minute interval.
b. Once an account is locked, the account must stay locked until unlocked by an administrator.
c. Once the indicated number of unsuccessful logon attempts occurs, delay further logon prompts by 5 seconds.
3.1.2.3 High Availability Interfaces Exempt from Unsuccessful Logon Attempts Requirements
There are no high availability interfaces which are exempt from unsuccessful logon attempts requirements.
3.1.3 System Use Notification
{For Reference Only: This subpart (and its subparts) relates to AC-8;
CCI-000048, CCI-002247, CCI-002243, CCI-002244, CCI-002245, CCI-002246,
CCI-000050, CCI-002248}
Web interfaces must display a warning banner meeting the requirements of
DTM 08-060 .
Devices which are connected to a network and have a user interface must display a warning banner meeting the requirements of DTM 08-060 if capable of doing so. Devices which are connected to a network and have a user interface but are not capable of displaying a banner must have a permanently affixed label displaying an approved banner from DTM 08-060 .Labels must be machine printed or engraved, plastic or metal, designed for permanent installation, must use a font no smaller than 14 point, and must
SECTION 25 05 11.01 Page 15 provide a high contract between font and background colors.
3.1.3.1 User Interface Banner Schedule
Provide a User Interface Schedule using the format indicated showing each user interface provided and how the information banner requirement has been implemented for each user interface.
User I nt er f ace Schedul e For mat ( wi t h sampl e ent r i es)
User I nt er f ace Description
User I nt er f ace Location
Type of User Interface
Banner I mpl ement at i on
Sample 1 Room 1 Remote DTM 08-060 Banner "A" Displayed at Logon
Sample 2 Room 2 Limited Local DTM 08-060 Banner "B" on Affixed Label
Sample 3 Room 3 Full Local DTM 08-060 Banner "B" Displayed on Screen
3.1.4 Permitted Actions Without Identification or Authentication
{For Reference Only: This subpart (and its subparts) relates to AC-14;
CCI-000061, CCI-000232}
The control system must require identification and authentication before allowing any actions by a user acting from a user interface which MINIMALLY or FULLY supports accounts.
3.1.5 Wireless Access
{For Reference Only: This subpart (and its subparts) relates to AC-18;
CCI-001438, CCI-001439, CCI-002323, CCI-001441 , AC-18 (1); CCI-001443,
CCI-001444. }
Unless explicitly authorized by the Government, do not use any wireless communication. Any device with wireless communication capability is considered to be using wireless communication, regardless of whether or not the device is actively communicating wirelessly, except when wireless communication has been physically permanently disabled (such as through the removal of the wireless transceiver).
3.1.5.1 Wireless IP Communications
Do not install wireless IP networks, including: do not install a wireless access point; do not install or configure an ad-hoc wireless network; do not install or configure a WiFi Direct communication.
When explicitly authorized by the Government, wireless IP communication may be used to communicate with an existing wireless network.
3.1.5.2 Non-IP Wireless Communication
When non-IP wireless communication is explicitly authorized by the
SECTION 25 05 11.01 Page 16
Government, use the maximum level of encryption supported by the specific protocol employed and select signal strength and radiated power to the minimum necessary for reliable communication.
3.2 CYBERSECURITY AUDITING
3.2.1 Audit Events, Content of Audit Records, and Audit Generation
{For Reference Only: This subpart (and its subparts) relates to AU-2(a),(c),(d), AU-3, AU-12; CCI-000123, CCI-001571, CCI-000125, CCI-001485, CCI-000130, CCI-000131, CCI-000132, CCI- 000133, CCI-000134, CCI-000135, CCI-001487, CCI-001488, CCI-000169, CCI-001459, CCI-000171, CCI-000172, CCI-001910}
For devices that have STIG/SRGs related to audit events, content of audit records or audit generation, comply with the requirements of those STIG/SRGs.
3.2.1.1 HVAC Control System Devices
3.2.1.1.1 HVAC Control System Devices FULLY Supporting User Accounts
For devices FULLY supporting accounts, provide the capability to select audited events, and the contents of audit logs. Configure devices to audit the following events:
a. Successful and unsuccessful logon attempts to the device
b. Starting and ending time for user access to the device
c. All account creations, modifications, disabling, and terminations
d. All device shutdown and startup
Configure the device to record for each event the following information (as applicable): the type of event, when the event occurred and the identity of any individuals or subjects associated with the event
3.2.1.1.2 Other HVAC Control System Devices
There are no requirements to perform auditing at HVAC field devices that do not FULLY support accounts.
3.2.1.2 Default Requirements for Control System Devices
For control system devices where Audit Events, Content of Audit Records, and Audit Generation are not otherwise indicated in this Section:
3.2.1.2.1 Devices Which FULLY Support Accounts
For each device which FULLY supports accounts, provide the capability to select audited events and the content of audit logs. Configure devices to audit the indicated events, and to record the indicated information for each auditable event
3.2.1.2.1.1 Audited Events
Configure each device to audit the following events:
SECTION 25 05 11.01 Page 17
a. Successful and unsuccessful attempts to access, modify, or delete privileges, security objects, security levels, or categories of information (e.g. classification levels)
a. Successful and unsuccessful logon attempts
b. Privileged activities or other system level access
c. Starting and ending time for user access to the system
d. Concurrent logons from different workstations
e. All account creations, modifications, disabling, and terminations
f. All kernel module load, unload, and restart
3.2.1.2.1.2 Audit Event Information To Record
Configure each computer to record, for each auditable event, the following information (where applicable to the event):
a. what type of event occurred
b. when the event occurred
c. where the event occurred
d. the source of the event
e. the outcome of the event
f. the identity of any individuals or subjects associated with the event
3.2.1.2.2 Devices Which Do Not FULLY Support Accounts
For each Device which does not FULLY support accounts configure the device to audit all device shutdown and startup events and to record for each event the type of event and when the event occurred.
3.2.2 Audit Storage Capacity and Audit Upload
{For Reference Only: This subpart (and its subparts) relates to AU-4;
CCI-001848, CCI-001849}
a. For devices that have STIG/SRGs related to audit storage capacity (CCI-001848 or CCI-001849) comply with the requirements of those STIG/SRGs.
b. For non-computer control system devices capable of generating audit records, provide 60 days worth of secure local storage, assuming 1 000 auditable events per day.
3.2.2.1 Device Audit Record Upload Software
For each non-computer device required to audit events, provide, and license to the Government, software implementing a secure mechanism of uploading audit records from the device to a computer and of exporting the uploaded audit records as a Microsoft Excel file or comma separated value text file. Where different devices use different software, provide
SECTION 25 05 11.01 Page 18 software of each type required to upload audit logs from all devices.
Install device audit record upload software on the furnished front end computer. Submit copies of device audit record upload software. If there are no non-computer devices requiring auditing, provide a document stating this in lieu of this submittal.
3.2.3 Response to Audit Processing Failures
{For Reference Only: This subpart (and its subparts) relates to AU-5;
CCI-000139, CCI-000140, CCI-001490}.
Front end computers associated with auditing must, in the case of a failure in the auditing system, notify the Information Systems Security Manager (ISSM) or Information Systems Security Officer (ISSO) via e-mail.
In case of an audit failure, if possible, continue to collect audit records by overwriting existing audit records.
3.2.4 Time Stamps
{For Reference Only: This subpart (and its subparts) relates to AU-8;
CCI-000159, CCI-001888, CCI-001889, CCI-001890 , AU-8 (1); CCI-001891,
CCI-001892, CCI-002046. }
3.2.4.1 For HVAC Control System Devices
Time stamp requirements for HVAC Control Systems are as indicated in the HVAC Control System specifications.Devices generating audit records must have internal clocks capable of providing time with a resolution of 1 second. Clocks cannot drift more than 10 seconds per day. Configure the system so that each device generating audit records maintains accurate time to within 1 second.
3.2.4.2 Default Requirements for Control System Devices
For control system devices where Time Stamps requirements are not otherwise indicated in this Section: Devices generating audit records must have internal clocks capable of providing time with a resolution of 1 second. Clocks must not drift more than 10 seconds per day. Configure the system so that each device generating audit records maintains accurate time to within 1 second.
3.3 REQUIREMENTS FOR LEAST FUNCTIONALITY
{For Reference Only: This subpart (and its subparts), along with the network communication report submittal specified elsewhere in this section, relates to CM-6 (a), (c), CM-7, CM-7 (1)(b), CM-7 (2), CM-7 (5)(a) (b) SC-41; CCI-000363, CCI-000364, CCI-000365, CCI-001588, CCI-001755, CCI-000381, CCI-000380, CCI-0 00382, CCI-001761, CCI-001762, CCI-002544, CCI-002545, CCI-002546 , CCI-001764, CCI-001772, CCI-001773, CCI-001774 .}
For devices that have a STIG or SRG related to Requirements for Least Functionality (such as configuration settings and port and device I/O access for least functionality), install and configure the device in accordance with that STIG or SRGs.
For HVAC Control Systems: Do not provide devices with user interfaces where one was not required. Do not use a networked sensor or actuator
SECTION 25 05 11.01 Page 19 where a non-networked sensor or actuator would suffice.
For Other Control Systems: Do not provide devices with user interfaces where one was not required. Do not use a networked sensor or actuator where a non-networked sensor or actuator would suffice.
3.3.1 Non-IP Control Networks
When control system specifications require particular communication protocols, use only those communication protocols and only as specified.
Do not implement any other communication protocol, or use any protocol on ports other than those specified.
When control system specifications do not indicate requirements for communication protocols, use only those protocols required for operation of the system as specified.
3.3.2 IP Control Networks
Do not use nonsecure functions, ports, protocols and services as defined in DODI 8551.01 unless those ports, protocols and services are specifically required by the control system specifications or otherwise specifically authorized by the Government. Do not use ports, protocols and services that are not specified in the control system specifications or required for operation of the control system.
3.4 SAFE MODE AND FAIL SAFE OPERATION
{For Reference Only: This subpart (and its subparts) relates to CP-12, SI-17; CCI-002855, CCI-002856, CCI-002857, CCI-002773, CCI-002774, CCI-002775}
For all control system components with an applicable STIG or SRG, configure the component in accordance with all applicable STIGs and SRGs.
3.5 IDENTIFICATION AND AUTHENTICATION
3.5.1 User Identification and Authentication
{For Reference Only: This subpart (and its subparts) relates to
IA-2,(1),(12); CCI-000764, CCI-000765, CCI-001953, CCI-001954}
a. Devices that FULLY support accounts must uniquely identify and authenticate…