Attachment F - Mechanical Drawings & Plans.pdf
PDF 329 KB Posted
- Attached to
- One Waterfront Place Dry Coolers Replacement
- Solicitation number
- RFB202690000664
- Issued by
- Mingo County, West Virginia
About this file
These are mechanical design and engineering drawings for the Dry Coolers Replacement Project at West Virginia University's (WVU) One Waterfront Place facility, prepared by Stantec Architecture and Engineering LLC. The project involves replacing existing glycol cooling infrastructure, including two dry coolers (DC-1 and DC-2), associated piping, controls, and related mechanical systems. The drawings, marked as preliminary and not for construction, are dated July 24, 2025 for schematic design and August 15, 2025 for bid issuance. The project includes detailed mechanical plans for exterior dry coolers, glycol piping diagrams, mechanical details, schedules, and control network documentation.
The proposed work includes removing existing dry coolers, installing new 6-inch housekeeping pads, replacing piping, implementing new control systems, and maintaining continuous glycol system operation through a phased approach. The new dry coolers are Liebert DGHX120AA136A00 models, each with 1,448 MBH total heat rejection capacity, designed to operate with a 40% propylene glycol solution. The control strategy involves integrating with the existing Siemens building automation system, with specific sequences for dry cooler staging, temperature control, and maintaining system redundancy. The project also includes monitoring and controlling 9 Computer Room Air Conditioning (CRAC) units as an alternate scope item.
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A
EQUIPMENT MARK TYPE A, NUMBER 1
REFER TO SCHEDULES FOR EXPLANATION.
SECTION INDICATOR
(SECTION 1 ON DWG. M300)
KEY NOTE INDICATOR
(REFERS TO NOTES ON SAME SHEET)
1 REVISION INDICATOR
DIFFUSER/REGISTER/GRILLE MARK
(SEE SCHEDULE SHEET)
DENOTES CONNECT TO EXISTING
DENOTES LIMIT OF DEMOLITION
EXISTING
REMOVE
EX
RX
XA
22"x22"
M300
CHILLED WATER RETURNCHWR
CHILLED WATER SUPPLYCHWS
ANCHOR
AUTOMATIC AIR VENT
MANUAL AIR VENT
BALANCING VALVE
CHECK VALVE (GENERIC)
FLEXIBLE CONNECTOR
FLANGED CONNECTION
UNION CONNECTION
PRESSURE GAUGE
TEMPERATURE GAUGE
Y STRAINER (GENERIC)
TEMPERATURE AND PRESSURE TAP
GATE VALVE
GLOBE VALVE
BALL VALVE
BUTTERFLY VALVE
BACKFLOW PREVENTER (GENERIC)
PIPE CAP
PIPE BREAK
FLOW ARROW
PIPING ELBOW DOWN
PIPING ELBOW UP
PIPING TEE UP
PIPING TEE DOWN
PUMP (GENERIC)
ISOLATION VALVE (GENERIC)
FLOW LIMITING VALVE
VACUUM BREAKER
2-WAY CONTROL VALVE (GENERIC)
3-WAY CONTROL VALVE (GENERIC)
PIPE CROSS
BFP
2 1/2" PIPE SIZE
Y STRAINER (BLOWDOWN)
PRESSURE REGULATOR
PRESSURE RELIEF VALVE
M1
CHILLED WATER WITH GLYCOL RETURNCHWR(G)
CHILLER WATER WITH GLYCOL SUPPLYCHWS(G)
T TEMPERATURE SENSOR
1 2 3 4 5 6 7
A
B
C
D
E
The Contractor shall verify and be responsible for all dimensions.
DO NOT scale the drawing - any errors or omissions shall be reported to Stantec without delay.
The Copyrights to all designs and drawings are the property of
Stantec. Reproduction or use for any purpose other than that authorized by Stantec is forbidden.
Copyright Reserved
Client/Project
Drawing No.
Project No.
Title
ORIGINAL SHEET - ANSI D (22"x34")
Permit-Seal
Issued
Revision
By Appd YYYY.MM.DD
Revision
By Appd YYYY.MM.DD
PRELIMINARY
NOT FOR CONSTRUCTION
Not for permits, pricing or other official purposes.
This document has not been completed or checked and is for general information or comment only.
Consultants
Legend
Notes www.stantec.com
/1
/2
:3
:2
P
M A u to d e sk D o c s:
W
V U
O
W P
D ry C o o le rs
R e p la c e /s tn m e c h
W
V U
O
W P
D ry C o o le rs
R e p la c e
.r v t
Dry Coolers Replacement Project
WVU One Waterfront Place
MECHANICAL COVER SHEET
M001
218012186
1 Waterfront Place
Morgantown, WV 26501
SCHEMATIC DESIGN 2025.07.24
ISSUED FOR BID 2025.08.15
Stantec Architecture and Engineering LLC 101 East Diamond Street Suite 400 Butler, PA 16001-5975 Tel: (724) 285-4761 / Fax: (724) 285-6815
LEGEND OF SYMBOLS
(SOME SYMBOLS MAY NOT BE USED ON THIS PROJECT)
PROJECT GENERAL NOTES
LIST OF DRAWINGS
ABBREVIATIONS
(SOME ABBREVIATIONS MAY NOT BE USED ON THIS PROJECT)
M001 MECHANICAL COVER SHEET
M300 EXTERIOR DRY COOLERS MECHANICAL PLAN
M600 MECHANICAL GLYCOL PIPING DIAGRAM
M700 MECHANICAL DETAILS, SCHEDULES, AND CONTROLS
M800 MECHANICAL CONTROLS NETWORK DIAGRAM AND SYMBOL LEGEND
M801 MECHANICAL CONTROLS
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
INTENT OF THE DRAWINGS AND SPECIFICATIONS ARE TO PROVIDE A COMPLETE HEATING, VENTILATION AND AIR CONDITIONING SYSTEM FOR THE PROPOSED PROJECT. THE SYSTEMS PROVIDED SHALL CONFORM TO THE DETAILS STATED IN THE SPECIFICATIONS AND SHOWN ON THE DRAWINGS. ITEMS OR WORK NOT SHOWN OR SPECIFIED, BUT REQUIRED FOR A COMPLETE HEATING, VENTILATION AND AIR CONDITIONING SYSTEM, SHALL BE PROVIDED AND SHALL CONFORM WITH ACCEPTED TRADE PRACTICES, LOCAL CODES, AND GOVERNING AUTHORITIES.
THE DRAWINGS AND SPECIFICATIONS ARE PRESENTED TO DEFINE SPECIFIC SYSTEM REQUIREMENTS AND SERVE TO EXPAND ON THE PRIMARY CONTRACT REQUIREMENTS OF PROVIDING COMPLETE SYSTEMS. THE DRAWINGS ARE DIAGRAMMATIC AND INDICATE ONLY THE GENERAL ARRANGEMENT OF THE ITEMS COMPRISING THE SEVERAL SYSTEMS INCLUDED IN THE HEATING, VENTILATION AND AIR
CONDITIONING WORK.
DO NOT SCALE THE DRAWINGS. BECAUSE OF THE SCALE OF THE DRAWINGS, IT IS NOT POSSIBLE TO INDICATE ALL OFFSETS, FITTINGS, VALVES, OR SIMILAR ITEMS WHICH MAY BE REQUIRED TO MAKE A COMPLETE OPERATING SYSTEM. CAREFULLY INVESTIGATE CONDITIONS AFFECTING WORK AND INSTALL WORK IN SUCH A MANNER THAT INTERFERENCES BETWEEN PIPES, CONDUIT, DUCTS, EQUIPMENT, ARCHITECTURAL AND STRUCTURAL FEATURES SHALL BE AVOIDED. PROVIDE ITEMS THAT MAY BE REQUIRED TO MEET THE CONDITIONS AT THE BUILDING.
CONTRACTORS SHALL HAVE SUFFICIENT EXPERTISE IN THIS TYPE OF CONSTRUCTION TO REALIZE THE EXTENT OF THE WORK REQUIRED. THEREFORE, IT SHOULD BE OBVIOUS TO ANY PRUDENT FIRM WITH EXPERIENCE IN THIS FIELD THAT THESE DOCUMENTS MAY NOT EXPLICITLY DISCLOSE FINAL DETAILS; HOWEVER, CONTRACTORS SHALL HAVE THE EXPERTISE NECESSARY TO INCLUDE NECESSARY
APPOINTMENTS.
PROTECT FLOORING FROM DAMAGE DURING THE CONSTRUCTION PERIOD. PROVIDE PLYWOOD OR SIMILAR MATERIAL UNDER EQUIPMENT OR MATERIALS STORED ON FLOORS, AND IN AREA WHERE CONSTRUCTION MAY DAMAGE THE FLOOR SURFACES. FLOOR SURFACES (INCLUDING SEALER) DAMAGED DURING THE CONSTRUCTION SHALL BE REPLACED AT THE COST OF THE CONTRACTOR AT FAULT.
COORDINATE ALL WORK WITH WORK SHOWN ON DRAWINGS FOR OTHER TRADES. COORDINATE EXACT LOCATION OF DIFFUSERS, REGISTERS AND GRILLES WITH THE ARCHITECTS REFLECTED CEILING
PLANS.
PROVIDE MAINTENANCE AREAS AROUND ALL EQUIPMENT AS REQUIRED BY CODES AND RECOMMENDED BY THE EQUIPMENT MANUFACTURER. PAY PARTICULAR ATTENTION TO COIL ACCESS AND
REMOVAL.
INDICATED PIPING RUNS ARE DIAGRAMMATIC. CONTRACTOR SHALL DETERMINE ALL REQUIRED OFFSETS AND DIRECTION CHANGES BEFORE FABRICATION AND INSTALLATION TO AVOID INTERFERENCE
WITH OTHER TRADES.
UNLESS OTHERWISE NOTED, PIPING IS OVERHEAD, TIGHT TO UNDERSIDE OF SLAB/STEEL, WITH SPACE FOR INSULATION IF REQUIRED.
ALL PIPING IN FINISHED ROOMS OR SPACES SHALL BE INSTALLED CONCEALED IN A FURRED CHASE OR ABOVE THE CEILING.
INSTALL PIPING SO THAT ALL VALVES ARE ACCESSIBLE.
NO PIPING SHALL BE LOCATED IN ELECTRICAL ROOMS, ELECTRICAL CLOSETS OR TELECOMMUNICATIONS ROOMS UNLESS THOSE PIPES OR DUCTS SERVE ONLY THAT SPACE AND ARE INDICATED ON THE
DRAWINGS.
FLOOR PLANS SHOW GENERAL PIPE ROUTING. REFER TO PIPING DIAGRAMS AND DETAILS FOR LOCATIONS OF VALVES AT EQUIPMENT.
INSTALL ALL DRAIN PIPING WITH 2% MINIMUM GRADE UNLESS OTHERWISE NOTED.
PROVIDE DRAIN VALVES AT THE BASE OF ALL RISERS AND AT ALL PIPING LOW POINTS ON HOT WATER, GLYCOL WATER AND CHILLED WATER PIPING SYSTEMS VALVES SHALL BE COMPLETE WITH HOSE
CONNECTIONS AND SCREW-ON CAPS.
PROVIDE MANUAL AIR VENTS AT ALL HIGH POINTS FOR VENTING.
PROVIDE SHUT-OFF VALVES AT EQUIPMENT REQUIRING CONNECTION, REGARDLESS OF WHETHER SHOWN ON DRAWINGS.
PROVIDE SHUT-OFF VALVES IN UTILITY SHAFTS ON EACH FLOOR FOR ALL PIPING SERVING THE FLOOR.
PIPING, EXCEPT IN MECHANICAL ROOMS AND ROOMS WITHOUT CEILINGS, SHALL BE LOCATED CONCEALED IN CHASES OR ABOVE THE CEILING UNLESS OTHERWISE NOTED.
UNLESS OTHERWISE NOTED, MINIMUM SIZE FOR ALL PIPING SHALL BE 3/4".
PROVIDE SLEEVES IN STRUCTURE FOR ALL PIPING PENETRATING WALLS OR FLOORS.
PROVIDE APPROVED FIRESAFING AT OPENINGS IN FLOORS, WALLS, ETC.
PAINT ALL PIPING, SUPPORTS, ETC. THAT WILL BE EXPOSED TO WEATHER.
ABOVE ABV.
ABOVE FINISHED FLOOR AFF
ALTERNATE ALT.
ALUMINUM ALUM.
AMBIENT AMB.
ARCHITECTURAL ARCH.
AUTOMATIC TEMPERATURE CONTROL ATC
BRAKE HORSEPOWER BHP
BUILDING BLDG.
BOTTOM BTM.
BRITISH THERMAL UNITS/HOUR BTUH
CAPACITY CAP.
COOLING COIL CC
CUBIC FEET/MINUTE CFM
CABINET HEATER CH
CEILING CLG.
COOLER CLR.
CLEANOUT CO.
COLUMN COL.
COMBINATION COMB.
CONCRETE CONC.
CONDENSATE COND.
CONDENSER CONDR.
CONNECTION CONN.
CONSTRUCTION CONST.
CONTINUOUS CONT.
CITY WATER CW
DRYBULB TEMPERATURE (DEG. F) DB
DECIBEL dB
DIRECT DIGITAL CONTROL DDC
DETAIL DET.
DIAMETER DIA.
DIMENSION DIM.
DISCHARGE DISCH.
DOWN DN.
DRAWING DWG.
ENTERING AIR TEMPERATURE (DEG. F) EAT
ELECTRICAL ELEC.
ELECTRICAL CONTRACTOR E.C.
EMERGENCY GENERATOR EM. GEN.
EQUIPMENT EQUIP.
EXTERNAL STATIC PRESSURE ESP
EVAPORATOR EVAP.
ENTERING WATER TEMPERATURE (DEG. F) EWT
EXISTING EXIST.
FAHRENHEIT F
FLOOR DRAIN FD
FINISH FIN.
FIXTURE FIXT.
FLEXIBLE FLEX.
FLOOR FLR.
FOUNDATION FND.
FIRE PROTECTION FP
FEET PER MINUTE FPM
FEET OF WATER GAUGE FT. W.G.
FOOT (FEET) FT.
GAUGE GA.
GALLONS GAL.
GALVANIZED GALV.
GALLONS PER HOUR GPH
GALLONS PER MINUTE GPM
HEIGHT HGT.
HAND-OFF-AUTOMATIC HOA
HORIZONTAL HORIZ.
HORSEPOWER HP
HIGH POINT HP
HUMIDISTAT H-STAT
HEATING HTG.
HIGH VOLTAGE HV
HEAT EXCHANGER HX
HYDRAULIC HYD.
INSIDE DIAMETER ID
INCHES OF WATER GAUGE IN. W.G.
INSULATION INSUL.
JOINT JT.
KILOWATT KW
KILOWATT HOUR KWh
LEAVING AIR TEMPERATURE LAT
LINEAL FOOT LF
LIGHTING LTG.
LOW VOLTAGE LV
LEAVING WATER TEMPERATURE LWT
THOUSANDS OF BTUs/HOUR MBH
MECHANICAL CONTRACTOR M.C.
MECHANICAL MECH.
MECHANICAL EQUIPMENT ROOM MER
MANUFACTURER MFR.
MAXIMUM OVER CURRENT PROTECTION MOCP
MOUNTED MTD.
MOUNTING MTG.
METAL MTL.
NOT APPLICABLE N/A
NORMALLY CLOSED N.C.
NOT IN CONTRACT NIC
NORMALLY OPEN N.O.
NOMINAL NOM.
NOT TO SCALE NTS
OUTDOOR AIR TEMPERATURE OAT
OUTSIDE DIAMETER OD
OVERHEAD OH
OPENING OPNG.
OPEN END RETURN OER
PRESSURE DIFFERENTIAL PD
PLUMBING PLBG.
PRESSURE PRESS.
POUNDS PER SQUARE INCH PSI
POUNDS PER SQUARE INCH ABSOLUTE PSIA
POUNDS PER SQUARE INCH GAUGE PSIG
RETURN AIR RA
RETURN AIR TEMPERATURE RAT
REVISION REV.
RELATIVE HUMIDITY RH
ROOM RM.
REVOLUTIONS PER MINUTE RPM
SOUND ATTENUATOR SA
SUPPLY AIR SA
SUPPLY AIR TEMPERATURE SAT
SHORT CIRCUIT CURRENT RATING SCCR
SCHEDULE SCHED.
SECTION SECT.
SQUARE FOOT SF
SHEET METAL SM
SPECIFICATION SPEC.
STEEL STL.
STRAINER STR.
STRUCTURAL STRUCT.
SUSPENDED SUSP.
SWITCH SW.
TEMPERATURE DIFFERENTIAL TD
TOTAL HEAT REJECTION THR
TEMPERATURE TEMP.
THICK THK.
TAMPERPROOF SWITCH TS
TOTAL STATIC PRESSURE TSP
THERMOSTAT T-STAT
VERTICAL VERT.
VIBRATION ISOLATOR VI
VOLUME VOL.
WIDE FLANGE WF
WEIGHT WT.
Key Value Keynote Text
M1 EXISTING CHWS/R (G) PIPING BELOW GRADE.
M2 REMOVE EXISTING DRY COOLER, PIPING, CONTROLS VALVES, CONTROL WIRING, AND APPURTENANCES.
M3 REMOVE EXISTING 4" HOUSEKEEPING PAD.
M4 PROVIDE NEW 6" THICK HOUSEKEEPING PAD. PAD SHALL EXTEND 6" MIN BEYOND DRY COOLER BASE RAILS ON ALL
SIDES.
M5 PIPING SUPPORT STANDS.
M6 BALANCE TO INDICATED GPM.
MECHANICAL KEY NOTE LEGEND
PHASING
1.
2.
3.
4.
5.
6.
7.
8.
9.
THE GLYCOL PIPING MAIN DOWNSTREAM OF THE CHILLED WATER/GLYCOL HEAT EXCHANGER SHALL BE MODIFIED TO INSTALL THE TEMPORARY DRY COOLER CONNECTIONS WITH PHASING VALVES AND A NEW MAIN SHUTOFF VALVE TO ALLOW THE PLANT TO BE ISOLATED WITH THE SYSTEM STILL IN OPERATION WITH THE 1200 MBH TEMPORARY DRY COOLER.
INSTALL THE NEW MINIMUM FLOW BYPASS VALVE AT THE TOP OF THE RISER ON LEVEL 6 AND ASSOCIATED CONTROLS FOR THE
BYPASS VALVE (INCLUDING RELOCATION OF THE EXISTING D/P SENSOR).
PROVIDE PIPING FOR THE TEMPORARY DRY COOLER. NEW 4” BLACK STEEL LINES SHALL BE INSTALLED FROM THE TIE-IN POINT TO THE RISER/MAIN TO THE EXTERIOR WALL SPACE BELOW THE ROLL-UP DOOR. PROVIDE INSULATED PLYWOOD BLANK-OFF AROUND THE PIPING AND BELOW THE OPEN PORTION OF THE DOOR. PROVIDE A MEANS OF LOCKING THE ROLL-UP DOOR FOR SECURITY. THE TEMPORARY DRY COOLER SHALL BE LOCATED ON GRADE OUTSIDE THE ROLL-UP DOOR. TEMPORARY PIPING SHALL BE EXTENDED FROM THE VICINITY OF THE DOOR TO THE DRY COOLER. FROM THIS POINT THE MFR MAY USE STANDARD PIPING MATERIAL FOR CONNECTION. THE INTENT IS FOR THE PIPING TO RUN ALONG THE GROUND WITH PLYWOOD COVERS OVER THE PIPING TO PROTECT THE PIPING FROM DAMAGE. THE PIPING AND DRY COOLER SHALL BE LOCATED IN SUCH A WAY TO NOT BLOCK FACILITY ACCESS AND OPERATION (COORDINATE FINAL LOCATION WITH OWNER). FILL TEMPORARY PIPING AND DRY COOLER WITH A 40% PROPYLENE
GLYCOL SOLUTION.
UTILIZE THE EXISTING SHUTOFF VALVES IN THE DRY COOLER PIPING WHERE IT FIRST ENTERS THE BUILDING TO ISOLATE THE MAINS
TO THE EXISTING DRY COOLERS. DRAIN THE EXISTING PIPING BACK TO THE DRY COOLERS.
SHUT DOWN THE EXISTING DRY COOLERS AND RUN OFF OF THE HEAT EXCHANGER/TEMPORARY DRY COOLER FOR N+1 REDUNDANCY.
PROCEED WITH INSTALLING THE NEW DRY COOLERS AND REMAINING SCOPE OF WORK INDICATED.
WHEN INSTALLATION IS COMPLETE, TRANSFER THE LOAD OFF OF THE TEMPORARY DRY COOLER AND BACK TO THE NEW DRY COOLER SYSTEM. ONCE THE NEW PLANT OPERATION IS CONFIRMED, REMOVE THE TEMPORARY DRY COOLER AND ALL OF THE
TEMPORARY PIPING/ELECTRICAL ETC.
THE GLYCOL SYSTEM IS A CRITICAL SYSTEM AND CANNOT BE SHUT DOWN.
THE PROJECT SHALL END WITH THE GLYCOL SYSTEM RETURNING TO THE NEW DRY COOLERS PROVIDING HEAT REJECTION WITH
CHILLED WATER HX BACKUP.
ALTERNATE(S)
M1 PROVIDE START/STOP/STATUS MONITORING OF 9 COMPUTER ROOM AIR CONDITIONING (CRAC) UNITS. SEE DRAWING M801.
Attachment F
GENERAL NOTES
GENERAL NOTES APPLY TO ALL SHEETS IN THE SERIES THAT THEY ARE ON.
EACH SERIES OF SHEETS WILL START OVER AT NOTE 1.
KEY NOTES
KEY NOTES ARE NUMBERED SEQUENTIALLY FROM M1 TO THE LAST KEY NOTE.
THEY ARE PROJECT SPECIFIC. ONLY THE KEY NOTES USED ON A SPECIFIC SHEET
WILL BE LISTED ON THAT SHEET.
1.
2.
3.
4.
5.
EXISTING CONDITIONS ARE BASED ON FIELD SURVEYS AND OWNER
RECORD DRAWINGS. FIELD VERIFY EXISTING CONDITIONS PRIOR TO
START OF DEMOLITION / CONSTRUCTION.
REFER TO SHEET M001 FOR ADDITIONAL GENERAL NOTES, SYMBOLS,
AND ABBREVIATIONS.
DO NOT SCALE DRAWINGS.
COORDINATE SHUTDOWN OF EXISTING BUILDING SYSTEMS FOR WORK
INVOLVED WITH BUILDING OWNER.
REFER TO M600 RISER DIAGRAM DRAWING FOR ADDITIONAL
INFORMATION.
RX 4"ø CHWS(G)
RX 6"ø CHWR(G)
M1
TO/FROM BUILDING
RX 6"ø CHWR(G) RX 6"ø CHWS(G)
RX 6"ø CHWS(G)
EX COOLING TOWERS
RX 4"ø CHWR(G)
RX 4"ø CHWS(G)
RX 4"ø CHWR(G)
RX 6"ø CHWS(G)
M2 (TYP OF 2)
M3 (TYP OF 2)
M1
TO/FROM BUILDING
EX COOLING TOWERS
DC
DC
6"ø CHWR(G)
6"ø CHWS(G)
4"ø CHWS(G) 4"ø CHWR(G)
4"ø CHWS(G) 4"ø CHWR(G)
4"ø CHWS(G) 4"ø CHWR(G)
4"ø CHWS(G) 4"ø CHWR(G)
M4 (TYP OF 2)
6"ø CHWS(G)
6"ø CHWR(G)
M5(TYP)
TRUE
NORTH
1 2 3 4 5 6 7
A
B
C
D
E
The Contractor shall verify and be responsible for all dimensions.
DO NOT scale the drawing - any errors or omissions shall be reported to Stantec without delay.
The Copyrights to all designs and drawings are the property of
Stantec. Reproduction or use for any purpose other than that authorized by Stantec is forbidden.
Copyright Reserved
Client/Project
Drawing No.
Project No.
Title
ORIGINAL SHEET - ANSI D (22"x34")
Permit-Seal
Issued
Revision
By Appd YYYY.MM.DD
Revision
Scale
By Appd YYYY.MM.DD
PRELIMINARY
NOT FOR CONSTRUCTION
Not for permits, pricing or other official purposes.
This document has not been completed or checked and is for general information or comment only.
Consultants
Legend
Notes www.stantec.com
/1
/2
:3
:2
P
M A u to d e sk D o c s:
W
V U
O
W P
D ry C o o le rs
R e p la c e /s tn m e c h
W
V U
O
W P
D ry C o o le rs
R e p la c e
.r v t
As indicated
Dry Coolers Replacement Project
WVU One Waterfront Place
EXTERIOR DRY COOLERS MECHANICAL
PLAN
M300
218012186
1 Waterfront Place
Morgantown, WV 26501
SCHEMATIC DESIGN 2025.07.24
ISSUED FOR BID 2025.08.15
Stantec Architecture and Engineering LLC 101 East Diamond Street Suite 400 Butler, PA 16001-5975 Tel: (724) 285-4761 / Fax: (724) 285-6815
M1 EXISTING CHWS/R (G) PIPING BELOW GRADE.
M2 REMOVE EXISTING DRY COOLER, PIPING, CONTROLS VALVES,
CONTROL WIRING, AND APPURTENANCES.
M3 REMOVE EXISTING 4" HOUSEKEEPING PAD.
M4 PROVIDE NEW 6" THICK HOUSEKEEPING PAD. PAD SHALL
EXTEND 6" MIN BEYOND DRY COOLER BASE RAILS ON ALL
SIDES.
M5 PIPING SUPPORT STANDS.
1/4" = 1'-0"M300
1 EXTERIOR DRY COOLERS MECHANICAL DEMOLITION PLAN
1/4" = 1'-0"M300
2 EXTERIOR DRY COOLERS MECHANICAL NEW WORK PLAN
LEVEL 2
LEVEL 4
LEVEL 5
LEVEL 1
LEVEL 6
LEVEL 2
LEVEL 4
LEVEL 5
LEVEL 1
LEVEL 6
GENERAL NOTES
GENERAL NOTES APPLY TO ALL SHEETS IN THE SERIES THAT THEY ARE ON.
EACH SERIES OF SHEETS WILL START OVER AT NOTE 1.
KEY NOTES
KEY NOTES ARE NUMBERED SEQUENTIALLY FROM M1 TO THE LAST KEY NOTE.
THEY ARE PROJECT SPECIFIC. ONLY THE KEY NOTES USED ON A SPECIFIC SHEET
WILL BE LISTED ON THAT SHEET.
1.
2.
3.
4.
5.
6.
EXISTING CONDITIONS ARE BASED ON FIELD SURVEYS AND OWNER
RECORD DRAWINGS. FIELD VERIFY EXISTING CONDITIONS PRIOR TO
START OF DEMOLITION / CONSTRUCTION.
REFER TO SHEET M001 FOR ADDITIONAL GENERAL NOTES, SYMBOLS,
AND ABBREVIATIONS.
DO NOT SCALE DRAWINGS.
COORDINATE SHUTDOWN OF EXISTING BUILDING SYSTEMS FOR WORK
INVOLVED WITH BUILDING OWNER.
DRAIN AND DISPOSE OF 40% PROPYLENE GLYCOL MIXTURE.
PROVIDE PROPYLENE GLYCOL, MIX, AND FILL WITH WATER TO BE 40%
SOLUTION.
LEVEL 3
OUTDOOR GLYCOL
COOLERS
BUILDING
EX 6"
CHWR(G)
EX 6"
CHWS(G)
EX 3" CHWR(G)
EX 3" CHWS(G)
EX 6" CHWR(G)
EX 6" CHWS(G)
EX 6" CHWR(G)
EX 6" CHWS(G)
EX CRU-10
EX 6" CHWR(G)
EX 6" CHWS(G)
EX CRU-9
EX CRU-2EX CRU-4EX CRU-3EX CRU-1
EX CRU-8EX CRU-6
EX CRU-7
EX BLIND FLANGE
N.C.N.O.
EX INLINE PUMPS
EX PLATE AND
FRAME HEAT
EXCHANGER
EX 4" CHWS(G)
EX 6" CHWS(G)
EX 6" CHWR(G)
EX 4" CHWS
EX 4" CHWR
EX 6" CHWR(G)
EX 6" CHWR(G)
EX 6" CHWR(G)
EX 6" CHWS
EX 6" CHWR
EX EXPANSION
TANK
EX CHEMICAL
CLOSED SYSTEM
FEEDER.
EX N.O. CONTROL
ISOLATION VALVE
EX N.C. CONTROL
ISOLATION VALVE
EX 6" CHWR(G)
EX 6" CHWR(G)
EX 6" CHWS(G)
MINIMUM FLOW
BYPASS VALVE
DC
DC
PROVIDE NEW MANUAL
AIR VENTS AT SYSTEM
HIGH POINT
NEW LOCATION
OF EXISTING DP
PUMP
CONTROLLER
M6 M6 M6
M6 M6 M6 M6
M6
M6
32 GPM
12 GPM 17 GPM
52 GPM 52 GPM 9 GPM 52 GPM
28 GPM
9 GPM
T
EX TEMPERATURE
SENSOR
NEW TEMPERATURE
SENSOR FOR
SYSTEM CONTROL
T T
PROVIDE TEMPORARY
DRY COOLER
CONNECTIONS
LEVEL 3
RX OUTDOOR
GLYCOL COOLERS
BUILDING
EX 6"
CHWR(G)
EX 6"
CHWS(G)
EX 3" CHWR(G)
EX 3" CHWS(G)
EX 6" CHWR(G)
EX 6" CHWS(G)
EX 6" CHWR(G)
EX 6" CHWS(G)
EX CRU-10
EX 6" CHWR(G)
EX 6" CHWS(G)
EX CRU-9
EX CRU-2EX CRU-4EX CRU-3EX CRU-1
CRU-5EX CRU-8EX CRU-6
EX CRU-7
EX BLIND FLANGE
PREVIOUSLY
REMOVED PER CLIENT
AND SITE SURVEY
N.C.N.O.
EX INLINE PUMPS
EX PLATE AND
FRAME HEAT
EXCHANGER
EX 4" CHWS(G)
EX 6" CHWS(G)
EX 6" CHWR(G)
EX 4" CHWS
EX 4" CHWR
EX 6" CHWR(G)
EX 6" CHWR(G)
EX 6" CHWR(G)
EX 6" CHWS
EX 6" CHWR
EX EXPANSION
TANK
EX CHEMICAL
CLOSED SYSTEM
FEEDER.
EX N.O. CONTROL
ISOLATION VALVE
EX N.C. CONTROL
ISOLATION VALVE
EX 6" CHWR(G)
EX 6" CHWR(G)
EX 6" CHWS(G)
EXISTING DIFFERENTIAL
PRESSURE SENSOR
INSTALLED UNDER
CHILLER UPGRADES
(RELOCATE TO NEW
LOCATION INDICATED)
T
RX TEMPERATURE
SENSOR FOR SYSTEM
CONTROL
RX 6" CHWR(G)
RX 6" CHWS(G)
RX PRESSURE
CONTROL VALVE
RX ORIGINAL DP
CONTROLLER
T
T
EX TEMPERATURE
SENSOR
RX 4" CHWS(G)
1 2 3 4 5 6 7
A
B
C
D
E
The Contractor shall verify and be responsible for all dimensions.
DO NOT scale the drawing - any errors or omissions shall be reported to Stantec without delay.
The Copyrights to all designs and drawings are the property of
Stantec. Reproduction or use for any purpose other than that authorized by Stantec is forbidden.
Copyright Reserved
Client/Project
Drawing No.
Project No.
Title
ORIGINAL SHEET - ANSI D (22"x34")
Permit-Seal
Issued
Revision
By Appd YYYY.MM.DD
Revision
By Appd YYYY.MM.DD
PRELIMINARY
NOT FOR CONSTRUCTION
Not for permits, pricing or other official purposes.
This document has not been completed or checked and is for general information or comment only.
Consultants
Legend
Notes www.stantec.com
/1
/2
:3
:2
P
M A u to d e sk D o c s:
W
V U
O
W P
D ry C o o le rs
R e p la c e /s tn m e c h
W
V U
O
W P
D ry C o o le rs
R e p la c e
.r v t
Dry Coolers Replacement Project
WVU One Waterfront Place
MECHANICAL GLYCOL PIPING
DIAGRAM
M600
218012186
1 Waterfront Place
Morgantown, WV 26501
SCHEMATIC DESIGN 2025.07.24
ISSUED FOR BID 2025.08.15
Stantec Architecture and Engineering LLC 101 East Diamond Street Suite 400 Butler, PA 16001-5975 Tel: (724) 285-4761 / Fax: (724) 285-6815
Not to ScaleM600
2 MECHANICAL GLYCOL PIPING DIAGRAM NEW WORK
Not to ScaleM600
1 MECHANICAL GLYCOL PIPING DIAGRAM DEMOLITION
M6 BALANCE TO INDICATED GPM.
PAD THICKNESS
HOUSEKEEPING PAD REINFORCEMENT SCHEDULE
T = 4"
4" < T <= 6"
6" < T <= 8"
8" < T <= 12"
12" < T <= 16"
WWR 4x4-W2.9xW2.9 OR #3@12" EACH WAY
WWR 4x4-W4xW4 OR #4@18" EACH WAY
WWR 4x4-W6xW6 OR #4@12" EACH WAY
#4@18" EACH WAY
#4@12" EACH WAY
TOP
REINFORCEMENT
BOTTOM REINFORCEMENT
NONE
NONE
NONE
#4@18" EACH WAY
#4@12" EACH WAY
NOTES:
1. REFER TO MECHANICAL DRAWINGS FOR HOUSEKEEPING PAD PLAN DIMENSIONS AND THICKNESS (4" MINIMUM
THICKNESS).
2. CONTRACTOR SHALL COORDINATE DIMENSIONS AND OTHER SPECIAL REQUIREMENTS WITH EQUIPMENT MANUFACTURERS AND PROVIDE WHERE REQUIRED WHETHER SHOWN ON STRUCTURAL DRAWINGS OR NOT.
COORDINATE WITH
MECHANICAL DRAWINGS.
SINGLE POUR WITH SLAB OR
SEPARATE POUR WITH
BONDING AGENT (LEAVE SLAB
ROUGH)
3/4" CHAMFER
BOTTOM REINFORCEMENT,
WHERE SCHEDULED
TOP REINFORCEMENT,
REFER TO SCHEDULE
REFER TO NOTE 1
1-#4 CONTINUOUS AT
PERIMETER WITH 1-#4x4'-0"
AT EXTERIOR CORNERS AND
1-#4x4'-0" DIAGONAL AT
RE-ENTRANT CORNERS
4'- 0"2'-0"
2' -0
EXTERIOR
CORNERS
RE-ENTRANT
CORNERS
2"
CHWS(G)
UNION
DRY COOLER
6" HOUSEKEEPING PAD
NOTES:
1. LOCATE PIPING TO FACILITATE THE REQUIRED ACCESS AND REMOVAL OF DRY COOLER COMPONENTS.
2. SHUT OFF VALVES AND ACCESSORIES SHALL BE THE SAME SIZE AS THE SYSTEM PIPING. TRANSITION TO THE DRY
COOLER INLET/OUTLET SIZES AT THE DRY COOLER.
3. ISOLATION VALVES ARE SHOWN AS BUTTERFLY VALVES, REFER TO THE SPECIFICATIONS FOR THE SPECIFIC VALVE TYPE
BASED ON THE PIPE SIZE AND APPLICATION.
DRAIN WITH HOSE
END CONNECTION
CHWR(G)
ISOLATION
VALVE
PRESSURE
RELIEF VALVE MANUAL AIR
VENT
PROVIDE NEOPRENE ISOLATION
PADS BETWEEN DRY COOLER
BASE RAIL AND HOUSEKEEPING
PAD.
HANGER ROD
INSULATION
WELD
SADDLE
NOTES:
1. FOLLOW REQUIREMENTS FOR VIBRATION ISOLATION AND SEISMIC AS NOTED IN THE CONTRACT
DOCUMENTS.
2. ALL STEEL MEMBERS SHALL BE HOT DIP GALVANIZED.
ROLLER SUPPORT 6"x6" FISH PLATE
BOLTED/ANCHORED TO
EXISTING CONCRETE (TYP.)
DC
DC
TEMPORARY DRY COOLER LOCATION
1 2 3 4 5 6 7
A
B
C
D
E
The Contractor shall verify and be responsible for all dimensions.
DO NOT scale the drawing - any errors or omissions shall be reported to Stantec without delay.
The Copyrights to all designs and drawings are the property of
Stantec. Reproduction or use for any purpose other than that authorized by Stantec is forbidden.
Copyright Reserved
Client/Project
Drawing No.
Project No.
Title
ORIGINAL SHEET - ANSI D (22"x34")
Permit-Seal
Issued
Revision
By Appd YYYY.MM.DD
Revision
By Appd YYYY.MM.DD
PRELIMINARY
NOT FOR CONSTRUCTION
Not for permits, pricing or other official purposes.
This document has not been completed or checked and is for general information or comment only.
Consultants
Legend
Notes www.stantec.com
/1
/2
:3
:3
P
M A u to d e sk D o c s:
W
V U
O
W P
D ry C o o le rs
R e p la c e /s tn m e c h
W
V U
O
W P
D ry C o o le rs
R e p la c e
.r v t
Dry Coolers Replacement Project
WVU One Waterfront Place
MECHANICAL DETAILS, SCHEDULES,
AND CONTROLS
M700
218012186
1 Waterfront Place
Morgantown, WV 26501
SCHEMATIC DESIGN 2025.07.24
ISSUED FOR BID 2025.08.15
Stantec Architecture and Engineering LLC 101 East Diamond Street Suite 400 Butler, PA 16001-5975 Tel: (724) 285-4761 / Fax: (724) 285-6815
8 5000 SCCR RATING.
7 FANS ARE TEMPERATURE STAGE CONTROLLED.
6 MANUFACTURER AND MODEL ARE BASIS OF DESIGN.
5 DRY COOLERS ARE 40% PROPYLENE GLYCOL SOLUTION.
4 INSTALL PER MANUFACTURER'S REQUIREMENTS.
2 UNIT MOUNTED ON GRADE ON 6" HOUSEKEEPING PAD.
1 PROVIDE NEMA 3R EXTERNAL FUSED DISCONNECT.
NOTES:
DC-2 CRAC UNITS LEVEL 1 OUTDOOR 1448 120 108 263 16.1 10 74160 95 480/3 27 480/3 2.7 1 LIEBERT DGHX120AA136A00 1, 2, 3, 4, 5, 6, 7, 8
DC-1 CRAC UNITS LEVEL 1 OUTDOOR 1448 120 108 263 16.1 10 74160 95 480/3 27 480/3 2.7 1 LIEBERT DGHX120AA136A00 1, 2, 3, 4, 5, 6, 7,8
EWT (°F) LWT (°F)
FLOW RATE
(GPM)
PRESSURE
DROP (FT)
NO. OF
FANS
FLOW
(CFM)
AMB. TEMP
(°F)
VOLTAGE/
PHASE
FLA
VOLTAGE/
PHASE
FLA HP
TAG SERVICE LOCATION
THR
(MBH)
FLUID SIDE AIR SIDE ELECTRICAL (DRY COOLERS) ELECTRICAL (PER FAN)
MANUFACTURER AND MODEL REMARKS
DRY COOLER SCHEDULE
Not to Scale
TYPICAL HOUSEKEEPING PAD OVER SLAB-ON-GRADE
NOT TO SCALE
DRY COOLER PIPING DETAIL
Not to Scale
PIPING SUPPORT STAND DETAIL
Not to Scale
TEMPORARY DRY COOLER LOCATION
FM
D/P
P
ES
T M
H
L
MAO
FS
D/P
CO2
H
D/P
H
C
H L
C
C
CONTROLS GENERAL NOTES
1.
2.
3.
4.
5.
6.
7.
THE DESIGN INTENT IS FOR THE BUILDING AUTOMATION SYSTEM (BAS) TO BE AN EXTENSION OF THE EXISTING SIEMENS
SYSTEM WHICH WAS RECENTLY UPGRADED AS PART OF SIEMENS CONTRACT WITH WVU
UTILIZE EXISTING CONTROLLER FOR THE GLYCOL SYSTEM. ALL SENSORS SHALL BE NEW.
ALL ACTUATORS SHALL BE ELECTRIC ACTUATORS UNLESS NOTED OTHERWISE.
THE CONTROLS CONTRACTOR IS RESPONSIBLE FOR POWERING ALL CONTROL PANELS AND SENSORS / END DEVICES. REFER TO THE ELECTRICAL DRAWINGS FOR THE DESIGNATED ELECTRICAL CIRCUITS THAT SHOULD BE USED BY THE CONTROLS CONTRACTOR. THE CONTROLS CONTRACTOR WILL BE RESPONSIBLE FOR ALL STEP DOWN TRANSFORMERS AND THE 120V
WIRING AS REQUIRED. ALL POWER SHALL COME FROM STANDBY CIRCUITS.
ALL CONTROL POINTS REQUIRED FOR THE SEQUENCES TO BE EXECUTED SHALL BE HARD WIRED TO THE CORRESPONDING CONTROLLER SO THAT THE SEQUENCES CAN STILL OPERATE WITH THE BUILDING CONTROLS LOCATE AREA NETWORK NOT
WORKING.
ALL SAFETIES SHALL BE HARD WIRED.
ALL CONTROL SEQUENCES SHALL UTILIZE DEAD BANDS TO ALLOW FOR STABLE CONTROL.
CONTROLS LEGEND AND SYMBOLS
DI
DO
AI
AO
DIGITAL INPUT
DIGITAL OUTPUT
ANALOG INPUT
ANALOG OUTPUT
LIQUID / STEAM FLOW METER
SMOKE DETECTOR
DIFFERENTIAL PRESSURE TRANSMITTER
AHU CONTROL VALVE
PRESSURE GAUGE
PRESSURE GAUGE W/ ISOLATION VALVE
PRESSURE TRANSMITTER
PARALLEL BLADE DAMPER
AIR FLOW STATION
OPPOSED BLADE DAMPER
STARTER
TEMPERATURE SENSOR
NETWORK INTERFACE PANEL
UNITARY CONTROL PANEL
REGULATOR
BALL VALVE
LINE SIZE BUTTERFLY VALVE
PIPING UNION
ACTUATOR WITH END SWITCH
DUCT STATIC PRESSURE SENSOR
CONTROLLER
FAN
VARIABLE FREQUENCY DRIVE
NIP
UCP
NOTE:
THESE SYMBOL DEFINITIONS SHALL BE USED UNLESS OTHERWISE NOTED ON THE CONTROL DRAWINGS. REFER TO
MECHANICAL LEGEND AND CONTROL SPECIFICATIONS FOR ADDITIONAL DEFINITIONS.
TEMPERATURE SENSOR
2D CONTROL VALVE
REHEAT, UH, CUH, FCU, AND MISC.
COIL/EQUIPMENT CONTROL VALVE
FAN
GROUND
AQUA STAT
PUMP
FLOW SWITCH
DIFFUSER
OCCUPANCY SENSOR
SPACE PRESSURE SENSOR
SPACE TEMPERATURE SENSOR
CHECK VALVE
GLOBE VALVE
DIGITAL CONTROL PANEL WHICH IS A
PROGRAMMABLE LOGIC CONTROLLER
DCP
ELECTRIC ACTUATOR
OCCUPANCY SENSOR
LOW LIMIT TEMPERATURE SENSOR
PRESSURE GAUGE
CO2 SENSOR
SPACE HUMIDITY SENSOR
DIFFERENTIAL PRESSURE SENSOR
OCCUPANCY SENSOR
HEATING COIL
FILTER
LOW LEVEL SENSOR
LINE VOLTAGE THERMOSTAT
DIFFERENTIAL PRESSURE SWITCH
BTU METER
COOLING COIL
TEMPERATURE TRANSMITTER DETAIL
N.T.S.
DIFFERENTIAL PRESSURE DETAIL
N.T.S.
DIFFERENTIAL PRESSURE
TRANSMITTER
PORTS
3-WAY MANIFOLD
1/2" TUBING
BALL VALVE
3/4" WELD-O-LET
RETURN SUPPLY
AI
D/P
L H
AI
INSULATION
TEMP TRANSMITTER
LOGGING WELL
304 STAINLESS STEEL
3/4" WELD-O-LET
1 2 3 4 5 6 7
A
B
C
D
E
The Contractor shall verify and be responsible for all dimensions.
DO NOT scale the drawing - any errors or omissions shall be reported to Stantec without delay.
The Copyrights to all designs and drawings are the property of
Stantec. Reproduction or use for any purpose other than that authorized by Stantec is forbidden.
Copyright Reserved
Client/Project
Drawing No.
Project No.
Title
ORIGINAL SHEET - ANSI D (22"x34")
Permit-Seal
Issued
Revision
By Appd YYYY.MM.DD
Revision
By Appd YYYY.MM.DD
PRELIMINARY
NOT FOR CONSTRUCTION
Not for permits, pricing or other official purposes.
This document has not been completed or checked and is for general information or comment only.
Consultants
Legend
Notes www.stantec.com
/1
/2
:3
:3
P
M A u to d e sk D o c s:
W
V U
O
W P
D ry C o o le rs
R e p la c e /s tn m e c h
W
V U
O
W P
D ry C o o le rs
R e p la c e
.r v t
Dry Coolers Replacement Project
WVU One Waterfront Place
MECHANICAL CONTROLS NETWORK
DIAGRAM AND SYMBOL LEGEND
M800
218012186
1 Waterfront Place
Morgantown, WV 26501
SCHEMATIC DESIGN 2025.07.24
ISSUED FOR BID 2025.08.15
Stantec Architecture and Engineering LLC 101 East Diamond Street Suite 400 Butler, PA 16001-5975 Tel: (724) 285-4761 / Fax: (724) 285-6815
VFD
TO BAS
DO - START/STOP
DI - STATUS
AO- SPEED ADJUST
DI - BYPASS (STARTER)
D/P
VFD
TO BAS
DO - START/STOP
DI - STATUS
AO- SPEED ADJUST
DI - BYPASS (STARTER)
DO
T
AI
AO
DO
T
AI
AO
A O
A O
T
A I
C H
W R
(G
ALL CONTROL FUNCTIONS, SET POINT ADJUSTMENTS, AND SEQUENCES SHALL BE PROVIDED
THROUGH THE BAS SYSTEM.
ALL TEMPERATURES AND PRESSURES SHALL BE MONITORED THROUGH THE BAS SYSTEM.
ALL SEQUENCES SHALL HAVE TIME CONSTRAINT WHERE APPLICABLE TO ALLOW THE SYSTEM TO
REACH STEADY STATE CONDITIONS. SETPOINTS SHALL BE USER ADJUSTABLE AND BE REFINED
DURING THE CX PROCESS.
1.
2.
3.
EXISTING GLYCOL PUMPS
AT ALL TIMES A MINIMUM OF 1 PUMP SHALL RUN.
THE CHILLED WATER PUMP SPEED SHALL BE VARIED FROM THE MIN SPEED (20 HZ) TO THE MAX SPEED
(60 HZ) TO MAINTAIN THE D/P SET POINT.
THE PUMPS SHALL BE IN A 1 DUTY CONFIGURATION WITH A BACK-UP. THE PUMPS SHALL BE STAGED TO EQUALIZE RUN TIME. THE PUMP COMING ON SHALL START AND RUN TO 20HZ PRIOR TO THE OLD DUTY PUMP SHUTTING OFF SO THAT THE MIN D/P IS MAINTAINED AT ALL TIME. THE PUMP ROTATION SHOULD
BE DONE ONE A MONTH ON A WEEKDAY AT 7AM.
IF THE DUTY PUMP WOULD FAIL, THE DUTY PUMP SHALL BE TAKEN OUT OF ROTATION AND THE PUMP THAT WAS THE STANDBY PUMP SHALL NOW BE THE DUTY PUMP. WHEN THE FAILED PUMP IS REPAIRED AND THE ALARM CLEARED, THE FORMERLY FAILED PUMP SHALL REMAIN OFF UNTIL AT LEAST THE NEXT
TIME TO ROTATE PUMPS.
SETPOINT VALUE
SUPPLY GLYCOL TEMP SP 108
REMOTE DIFFERENTIAL PRESSURE TAB
GENERAL
EX GP-2
AI
CHWR(G)
CHWS(G)
RELOCATED REMOTE DIFFERENTIAL PRESSURE
SENSOR ON LV6
GLYCOL
WATER
RISER
EX GP-1
DRY COOLER DRY COOLER
EX
FREE
COOLING HX
EXISTING MODE SWITCHING - DRY COOLER / FREE COOLING HX
THERE SHALL BE A MODE SELECTOR TO DETERMINE ON THE GRAPHICS.
THERE ARE (2) 2-WAY VALVES TO DETERMINE THE DIRECTION OF FLOW. NORMALLY THE
FLOW WILL GO TO THE DRY COOLERS. THIS SHALL BE THE DEFAULT MODE. THE OTHER
MODE IS CHILLED WATER BACKUP. IN THIS MODE THE CHILLED WATER GOES TO THE HX.
WHEN SWITCHING BETWEEN MODES, THE ISOLATION VALVE THAT IS CLOSED SHALL FULLY
OPEN BEFORE THE OPEN VALVE BEGINS TO CLOSE. AT ALL TIMES THERE SHALL BE A
MINIMUM OF 1 FULLY OPEN VALVE.
IF THE TEMPERATURE COMING FROM THE DRY COOLERS IS NOT AT SET POINT FOR A
PERIOD OF 15 MINUTES, AN ALARM SHALL BE GENERATED. IF THE TEMPERATURE EXCEEDS
THE HIGH LIMIT BY MORE THAN 5 DEGREES AT ANY TIME THERE SHALL BE AN ALARM AND
THE MODE SHALL BE SWITCHED TO CHILLED WATER MODE.
IN CHILLED WATER MODE, THE HX SHALL BE THE PRIORITY. NON CRITICAL AHU LOADS
SHALL BE SHED TEMPORARILY AS REQUIRED TO MAINTAIN SET POINT USING THE HX. THE
AHUS ON LV 3 SHOULD BE SHED FIRST (TOGGLES TO CHANGE THE LEVEL OF AHUS TO BE
SHUT OFF FROM CHILLED WATER).
TEMPERATURE CONTROL
IN DRY COOLER MODE, THE DRY COOLERS SHALL BE CONTROLLED (FAN STAGING) TO
MAINTAIN THE TEMPERATURE SET POINT 108oF (ADJ). THE DESIGN INTENT IS ONE DRY
COOLER WILL SATISFY THE BUILDING LOAD REQUIREMENTS UNDER NORMAL CONDITIONS.
IF THE GLYCOL LOOP SUPPLY TEMPERATURE RISES ABOVE 110oF (ADJ), THE LAG DRY
COOLER SHALL BE ENERGIZED AND THE ASSOCIATED ISOLATION VALVE MODULATED
OPEN TO MAINTAIN LOOP SUPPLY TEMPERATURE SET POINT. WHEN THE LOOP SUPPLY
TEMPERATURE DROPS BELOW 108oF (ADJ), THE LAG DRY COOLER SHALL BE DE-
ENERGIZED AND THE ASSOCIATED ISOLATION VALVE CLOSED.
IN HX MODE, THE CHILLED WATER CONTROL VALVE SHALL MODULATE TO MAINTAIN THE
TEMPERATURE SET POINT AT THE TEMPERATURE SENSOR LEAVING THE HX. WHEN NOT IN
HX MODE, ONCE A MONTH THE CONTROL VALVE ON THE CHILLED WATER LINE SHALL
MODULE SLOWING FROM 0% OPEN TO 100% OPEN AND THEN BACK TO 0% OPEN. THE
CHILLER STAGING / PUMP STATING SHALL BE LOCKED OFF AT THIS TIME TO PREVENT ANY
ADDITIONAL CHILLERS OR PUMPS TO TURN ON DURING THIS SHORT FLOW INCREASE. THIS
SHOULD BE DONE AT 1AM ON A WEEKDAY.
EXISTING
EXISTING
MIN FLOW BYPASS
VALVE ON LV6
DRY COOLER STAGING
THE BAS SHALL ENABLE THE DRY COOLERS WHEN THE PLANT IS ENABLED. THE DRY COOLER
CONTROLLER SHALL OPERATE TO MAINTAIN THE SUPPLY CHILLED WATER WITH GLYCOL
TEMPERATURE SET POINT.
THE BAS SHALL ISOLATE A DRY COOLER WHEN THE DRY COOLER IS NOT RUNNING. AT A MINIMUM, ONE ISOLATION VALVE SHALL ALWAYS BE OPEN. THE VALVES ARE SHOWN AS MODULATING VALVES
SO THE TRANSITION CAN SLOW ENOUGH TO ALLOW TIME FOR THE SYSTEM TO REACT. THE
MINIMUM FLOW IN THE SYSTEM SHOULD BE RESET PRIOR TO TURNING ON A SECOND DRY COOLER
SO THAT THE FLOW STAYS ABOVE THE MINIMUM FLOW DURING THE TRANSITION.
DRY COOLER STAGING SHALL BE USED TO EQUALIZE DRY COOLER RUN TIME. THE LEAD DRY
COOLER SHALL ROTATE AT 6AM IN THE MORNING ON A WEEKDAY TO ROTATE THE DRY COOLER
POSITION. THE DRY COOLER WITH THE SHORTEST RUN TIME SHALL BE THE LEAD.
BYPASS CONTROL
THE BYPASS VALVE SHALL BE USED AS PART OF THE D/P CONTROL. WHEN THE PUMPS
REACH MIN SPEED, THE BYPASS VALVE SHALL MODULATE TO MAINTAIN THE D/P SET POINT.
EX
EX
EX
EX
CHWS
CHWR
CRAC SYSTEM SEQUENCE
THE CRAC UNIT TO CONTINUE TO OPERATE ON EXISTING PACKAGED CONTROL.
PROVIDE DRY CONTACT INTEGRAL OF EXISTING UNIT TO PROVIDE REMOTE START/STOP FUNCTION AND MONITOR UNIT STATUS.
PROVIDE NEW THERMOSTAT TO MONITOR/ALARM ZONE TEMPERATURE.
CONTROLS CONTRACTOR TO PROVIDE BACNET CONNECTION TO BMS.
ALARMS
HIGH SPACE TEMP: IF THE ZONE TEMPERATURE IS GREATER THAN COOLING SETPOINT BY 10oF (ADJ.) FOR A PERIOD OF 5 MINUTES
(ADJ.).
COMPUTER ROOM
AC UNIT
EXISTING ROOM
TEMPERATURE
SENSOR
DDC
INTERFACE
24V DRY CONTACT
INTERFACE TO EXISTING
UNIT CONTROL PANEL
ZONE
MONITORING
SENSOR
1 2 3 4 5 6 7
A
B
C
D
E
The Contractor shall verify and be responsible for all dimensions.
DO NOT scale the drawing - any errors or omissions shall be reported to Stantec without delay.
The Copyrights to all designs and drawings are the property of
Stantec. Reproduction or use for any purpose other than that authorized by Stantec is forbidden.
Copyright Reserved
Client/Project
Drawing No.
Project No.
Title
ORIGINAL SHEET - ANSI D (22"x34")
Permit-Seal
Issued
Revision
By Appd YYYY.MM.DD
Revision
By Appd YYYY.MM.DD
PRELIMINARY
NOT FOR CONSTRUCTION
Not for permits, pricing or other official purposes.
This document has not been completed or checked and is for general information or comment only.
Consultants
Legend
Notes www.stantec.com
/1
/2
:3
:3
P
M A u to d e sk D o c s:
W
V U
O
W P
D ry C o o le rs
R e p la c e /s tn m e c h
W
V U
O
W P
D ry C o o le rs
R e p la c e
.r v t
Dry Coolers Replacement Project
WVU One Waterfront Place
MECHANICAL CONTROLS
M801
218012186
1 Waterfront Place
Morgantown, WV 26501
SCHEMATIC DESIGN 2025.07.24
ISSUED FOR BID 2025.08.15
Stantec Architecture and Engineering LLC 101 East Diamond Street Suite 400 Butler, PA 16001-5975 Tel: (724) 285-4761 / Fax: (724) 285-6815
Not to Scale
GLYCOL PLANT
Not to Scale
CRAC SYSTEM MONITOR CONTROL DIAGRAM
HIGH ZONE TEMPERATURE X X
STATUS X X X
START/STOP X X X
ZONE TEMPERATURE X X X
AI DI AO DO AV DV SCHEDULE TREND ALARM
DESCRIPTION
HARDWARE POINTS SOFTWARE POINTS
GRAPHICS
ALTERNATE M1
| Sheets |
| M001 - MECHANICAL COVER SHEET |
| M300 - EXTERIOR DRY COOLERS MECHANICAL PLAN |
| M600 - MECHANICAL GLYCOL PIPING DIAGRAM |
| M700 - MECHANICAL DETAILS, SCHEDULES, AND CONTROLS |
| M800 - MECHANICAL CONTROLS NETWORK DIAGRAM AND SYMBOL LEGEND |
| M801 - MECHANICAL CONTROLS |
File details come from the government source that posted it. Updated .