Attachment E - Electrical Drawings & Plans.pdf
PDF 320 KB Posted
- Attached to
- One Waterfront Place Dry Coolers Replacement
- Solicitation number
- RFB202690000664
- Issued by
- Mingo County, West Virginia
About this file
This document is an electrical design set for the Dry Coolers Replacement Project at WVU One Waterfront Place in Morgantown, West Virginia, prepared by Stantec Architecture and Engineering LLC. The project involves replacing existing dry coolers and associated electrical infrastructure, with electrical design drawings covering the ground floor electrical plan, enlarged electrical plans, and electrical schedules. The electrical design set includes comprehensive documentation for electrical equipment replacement, power distribution, and circuit modifications, with drawings issued for bid on August 15, 2025.
The electrical design set includes detailed specifications for electrical work, such as providing new 60A/3P disconnects with 50A fuses, rerouting existing conduits, and installing new electrical infrastructure for the dry coolers. The project involves working with existing electrical systems, including panelboards (PP-BEQM), and making precise electrical connections and modifications. The design accounts for temporary dry cooler installations, circuit redirections, and maintains the existing electrical infrastructure's overall integrity while facilitating the replacement of the cooling equipment.
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FIRE ALARM
H C#/F#
FIRE SERVICE PHONE STATION OUTLET
S
ID
IN DUCT
STROBE LIGHT, CEILING MOUNTED
H
RC#/F#
S E
ELEVATOR RECALL
S I
IONIZATION
S P
PHOTOELECTRIC
STROBE LIGHT, WALL MOUNTED
S SPEAKER, CEILING MOUNTED
SPEAKER, WALL MOUNTED
SPEAKER AND STROBE LIGHT, CEILING MOUNTED
SPEAKER AND STROBE LIGHT, WALL MOUNTED
HORN AND STROBE LIGHT, CEILING MOUNTED
HORN AND STROBE LIGHT, WALL MOUNTED
F HORN, CEILING MOUNTED
HORN, WALL MOUNTED
F CHIME, WALL MOUNTED
F PULL STATION
ARCR AREA OF REFUGE COMMUNICATION REMOTE UNIT
ARCM AREA OF REFUGE COMMUNICATION MASTER UNIT
BEAM DETECTOR RECEIVER
BEAM DETECTOR TRANSMITTER
ADDRESSABLE INPUT MODULEAIM
DOOR HOLDER
ELECTRICALLY OPERATED SMOKE OR FIRE/SMOKE
DAMPER CONNECTION
D
DH
FAT FIRE ALARM TRANSMITTER
FACP FIRE ALARM CONTROL PANEL
GAP GRAPHIC ANNUNCIATOR PANEL
FAA FIRE ALARM ANNUNCIATOR
FATC FIRE ALARM TERMINAL CABINET
S
BR
S
BT
CO
GAS DETECTOR, CARBON MONOXIDE
SMOKE/HEAT/CARBON MONOXIDE DETECTOR
S
CO
H
F S
REMOTE INDICATOR, CEILING MOUNTED
REMOTE INDICATOR, WALL MOUNTED
DOOR CLOSERDCL
VS VALVE SUPERVISORY TAMPER SWITCH
PS PRESSURE DETECTOR/SWITCH
WF FLOW DETECTOR/SWITCH
SMOKE/HEAT DETECTORS H
AOM ADDRESSABLE OUTPUT MODULE
S
AS
AIR SAMPLING
SS SMOKE DETECTOR, SINGLE STATION
FLAME DETECTOR
H R
RATE OF RISE
NAC FIRE ALARM NOTIFICATION APPLIANCE CIRCUIT PANEL
R INTERFACE RELAY
HEAT/SMOKE DETECTOR
TYPES
S SMOKE DETECTOR, CEILING MOUNTED
H HEAT DETECTOR
S SMOKE DETECTOR, WALL MOUNTED
FIXED TEMPERATURE, # INDICATES °C OR °F
COMBINED RATE OF RISE/FIXED TEMPERATURE
RACEWAYS
RACEWAY CONCEALED IN CEILING OR WALL. EXPOSED
RACEWAY IS ALLOWED ONLY WHERE NOTED.
RACEWAY BELOW SLAB OR UNDERGROUND
RACEWAY UP
RACEWAY DOWN
RACEWAY STUB-OUT WITH BUSHING
RACEWAY CONTINUATION
JUNCTION BOX, CEILING OR ABOVE CEILING MOUNTED
PULL BOX
JUNCTION BOX, WALL MOUNTED
J
PB
J
JUNCTION BOX, IN-GROUNDJ
SURFACE RACEWAY (HORIZONTAL/VERTICAL)
WORK DEFINITION
EXISTING
REMOVE EXISTING
NEW WORK
FUTURE
TEMPORARY, AS NOTED
REMOVE EXISTING ELECTRICAL EQUIPMENT
KEY NOTE?:##
EQUIPMENT IDENTIFICATION
RECEPTACLESCIRCUITS
EMERGENCY NORMAL
SINGLE RECEPTACLE, 120V
N/A
DUPLEX RECEPTACLE, 120V
DOUBLE DUPLEX RECEPTACLE, 120V
RECEPTACLE, NEMA #
COMBINATION RECEPTACLE, NEMA # AND 120V
INDICATES TWIST LOCK
CLOCK RECEPTACLE, 120V
CORD DROP, 120V
MULTI-SERVICE FLOOR BOX (RECEPTACLES AS
INDICATED)
MULTI-SERVICE POKE THRU (RECEPTACLES AS
INDICATED)
MULTI-SERVICE POWER POLE (RECEPTACLES AS
INDICATED)
MULTI-SERVICE ASSEMBLY (RECEPTACLES AS
INDICATED)
SINGLE RECEPTACLE, 120V, CEILING MOUNTED
DUPLEX RECEPTACLE, 120V, CEILING MOUNTED
DOUBLE DUPLEX RECEPTACLE, 120V, CEILING
MOUNTED
N/A
N/A
N/A
N/A
N/A
INDICATES 15AN/A
RECEPTACLE TYPES
DEDICATED CIRCUITD
GROUND FAULT CIRCUIT INTERRUPTERG
GROUND FAULT CIRCUIT INTERRUPTER AND TAMPER
RESISTANT
GT
ISOLATED GROUNDIG
TAMPER RESISTANTT
INTEGRAL USB PORT(S)U
WEATHER RESISTANT COVERWP
SURGE PROTECTORS
INDICATES FULLY CONTROLLEDN/A
FURNITURE SYSTEMS RECEPTACLE, 120V
N/A
ARC FAULT CIRCUIT INTERRUPTERA
ARC FAULT CIRCUIT INTERRUPTER AND TAMPER
RESISTANT
AT
RECEPTACLE, NEMA #, CEILING MOUNTED##
CEILING CORD DROP, 120V
SPLIT WIRED RECEPTACLE, 120V, TOP CONTROLLED,
BOTTOM CONSTANTLY ENERGIZED
PLUG STRIP (HORIZONTAL/VERTICAL)N/A
MULTI-SERVICE FURNITURE BOX (RECEPTACLES AS
INDICATED)
N/A
INDICATES MOUNTED ABOVE COUNTER BACKSPLASH
MULTI-SERVICE CEILING BOX (RECEPTACLES AS
INDICATED)
N/A
MULTI-SERVICE WALL BOX (RECEPTACLES AS
INDICATED)
N/A
ELECTRICAL EQUIPMENT
EQUIPMENT CABINET OR PANEL
EQUIPMENT CONNECTION, FILL INDICATES
EMERGENCY CIRCUIT
GROUND BAR
MOTOR CONNECTION, 1Ø
MOTOR CONNECTION, 3Ø
BUS DUCT
BUS DUCT PLUGB
SURGE PROTECTIVE DEVICE
TRANSFORMER, NOT TO SCALE
TRANSFORMER, DRAWN TO SCALE
SPD
T
T
480V OR 600V POWER PANELBOARD
208V OR 240V POWER PANELBOARD
AUTOMATIC TRANSFER SWITCHATS
CONTROLS
FUSED SAFETY SWITCH, FUSE RATING INDICATED
NON-FUSED SAFETY SWITCH
COMBINATION MOTOR STARTER AND FUSED SAFETY
SWITCH, FUSE RATING INDICATED
MOTOR STARTER
MANUAL MOTOR STARTER
ENCLOSED CIRCUIT BREAKER
ENCLOSED CONTACTOR
AUTOMATIC DOOR PUSHPLATE
EMERGENCY SHUTDOWN
DEAD FRONT GFCI
DIRECT DIGITAL CONTROL PANEL
RELAY
THERMOSTAT
TIME CLOCK
VARIABLE FREQUENCY DRIVE
PUSH BUTTON CONTROL STATION
DDC
R
TC
VFD
TOGGLE SWITCH, MOTOR RATEDM
T
TOUCHLESS AUTOMATIC DOOR OPENER
1 2 3 4 5 6 7
A
B
C
D
E
The Contractor shall verify and be responsible for all dimensions.
DO NOT scale the drawing - any errors or omissions shall be reported to Stantec without delay.
The Copyrights to all designs and drawings are the property of
Stantec. Reproduction or use for any purpose other than that authorized by Stantec is forbidden.
Copyright Reserved
Client/Project
Drawing No.
Project No.
Title
ORIGINAL SHEET - ANSI D (22"x34")
Permit-Seal
Issued
Revision
By Appd YYYY.MM.DD
Revision
Scale
By Appd YYYY.MM.DD
PRELIMINARY
NOT FOR CONSTRUCTION
Not for permits, pricing or other official purposes.
This document has not been completed or checked and is for general information or comment only.
Consultants
Legend
Notes www.stantec.com
/1
/2
:0
:5
A
M A u to d e sk D o c s:
W
V U
O
W P
D ry C o o le rs
R e p la c e /s tn m e c h
W
V U
O
W P
D ry C o o le rs
R e p la c e
.r v t
12" = 1'-0"
Dry Coolers Replacement Project
WVU One Waterfront Place
ELECTRICAL COVER SHEET
E001
218012186
1 Waterfront Place
Morgantown, WV 26501
ISSUED FOR BID 2025.08.15
Stantec Architecture and Engineering LLC 101 East Diamond Street Suite 400 Butler, PA 16001-5975 Tel: (724) 285-4761 / Fax: (724) 285-6815
ABBREVIATIONS
#/C MULTI-CONDUCTOR, # INDICTATES
QUANTITY
(D) DEMOLISH
(E) EXISTING
(N) NEW
(R) EXISTING TO BE RELOCATED
1/C SINGLE CONDUCTOR
A AMPS
A/C AIR CONDITIONING UNIT
AC ALTERNATING CURRENT
ACH ABOVE COUNTER HEIGHT
ACT ACOUSTICAL CEILING TILE
ADA AMERICANS WITH DISABILITIES ACT
ADJ ADJUSTABLE
AF AMP FRAME
AFC ABOVE FINISHED CEILING
AFCI ARC FAULT CIRCUIT INTERRUPTER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHJ AUTHORITY HAVING JURISDICTION
AHU AIR HANDLING UNIT
AIC AMPERE INTERRUPTING CAPACITY
AL ALUMINUM
ALD ASSISTED LISTENING DEVICE
ALT ALTERNATE
ARCH ARCHITECTURAL
AS AMP SWITCH
AT AMP TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AV AUDIO VISUAL
AVG AVERAGE
AWG AMERICAN WIRE GAUGE
BC BONDING CONDUCTOR
BCU BARE COPPER
BFC BELOW FINISHED CEILING
BFG BELOW FINISHED GRADE
BKR BREAKER
BLDG BUILDING
BOF BOTTOM OF FIXTURE
BOH BACK OF HOUSE
BTM BOTTOM
C CONDUIT
C/W COMPLETE WITH
CAP CAPACITY
CATV COMMUNITY ANTENNA TELEVISION
CB CIRCUIT BREAKER
CCTV CLOSED CIRCUIT TELEVISION
CEC CANADIAN ELECTRIC CODE
CFOI CONTRACTOR FURNISHED, OWNER
INSTALLED
CIRC CIRCULATING
CKT CIRCUIT
CL CENTERLINE
CLG CEILING
CM CEILING MOUNTED
CMU CONCRETE MASONRY UNIT
CO CONDUIT ONLY
COMM COMMUNICATIONS
CONC CONCRETE
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUOUS
CONTR CONTRACTOR
CPT CONTROL POWER TRANSFORMER
CPU CENTRAL PROCESSING UNIT
CR CRITICAL BRANCH
CT CURRENT TRANSFORMERS
CTR CENTER
CU COPPER
CUH CABINET UNIT HEATER
D DEDICATED
DALI DIGITAL ADDRESSABLE LIGHTING
INTERFACE
DC DIRECT CURRENT
DET DETAIL
DIA DIAMETER
DIM DIMENSION
DISC DISCONNECT
DIV DIVISION
DL DAMP LOCATION
DMX DIGITAL MULTIPLEX
DMX-RDM DIGITAL MULTIPLEX REMOTE
DEVICE MANAGEMENT
DN DOWN
DP DISTRIBUTION PANEL
DPDT DOUBLE POLE, DOUBLE THROW
DPR DAMPER
DPST DOUBLE POLE, SINGLE THROW
DWG DRAWING
DWH DOMESTIC WATER HEATER
EA EACH
EC ELECTRICAL CONTRACTOR
EF EXHAUST FAN
ELEC ELECTRICAL
ELEV ELEVATOR
EM EMERGENCY
EM GEN EMERGENCY GENERATOR
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
EP ELECTRIC-PNEUMATIC
EPO EMERGENCY POWER OFF
EQ EQUIPMENT BRANCH
EQUIP EQUIPMENT
ABBREVIATIONS
ETD EMERGENCY TRANSFER DEVICE
EWC ELECTRIC WATER COOLER
EXH EXHAUST
EXP EXPLOSION PROOF
EXTER EXTERIOR
F&I FURNISHED AND INSTALLED
FA FIRE ALARM
FAA FIRE ALARM ANNUNCIATOR
FACP FIRE ALARM CONTROL PANEL
FB FLOOR BOX
FCU FAN COIL UNIT
FLR FLOOR
FLUOR FLUORESCENT
FO FIBER (FIBRE) OPTIC
FOH FRONT OF HOUSE
FP FIRE PROTECTION
FPC FORWARD PHASE CONTROL
FS FUSIBLE SWITCH
FSCS FIRE FIGHTER SMOKE CONTROL
STATION
FU FUSE
FVNR FULL VOLTAGE NON REVERSING
FVR FULL VOLTAGE REVERSING
G, GND GROUND
G/Y GREEN YELLOW
GA GAUGE
GAL GALLONS
GC GENERAL CONTRACTOR
GEN GENERATOR
GFI, GFCI GROUND FAULT (CIRCUIT)
INTERRUPTER
H HOT CONDUCTOR
HC HORIZONTAL CROSS CONNECT
HD HAND DRYER
HFF HANDS FREE FIXTURE
HH HANDHOLE
HID HIGH INTENSITY DISCHARGE
HK HOUSE KEEPING PAD
HM HORIZONTALLY MOUNTED
HOA HAND-OFF-AUTO
HOR HORIZONTAL
HP HORSEPOWER
HT HEIGHT
HTG HEATING
HV HIGH VOLTAGE
HVCB HIGH VOLTAGE CIRCUIT BREAKER
HW HOT WATER
HZ HERTZ
IC INTERMEDIATE CROSS CONNECT
ID INSIDE DIAMETER
IDF INTERMEDIATE DISTRIBUTION
FRAME
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
INST INSTANTANEOUS
IP INTERNET PROTOCOL
JB JUNCTION BOX
K KIRK KEY INTERLOCK
KAIC KILO-AMPS INTERRUPTING
CAPACITY
KV KILOVOLT
KVA KILOVOLT-AMPERES
KW KILOWATT
LED LIGHT EMITTING DIODE
LR LEGALLY REQUIRED
LS LIFE SAFETY BRANCH
LSIG LONG TIME, SHORT TIME,
INSTANTANEOUS, GROUND FAULT
LTG LIGHTING
LV LOW VOLTAGE
MAU MAKE UP AIR UNIT
MAX MAXIMUM
MC METAL CLAD CABLE
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MCCB MOLDED CASE CIRCUIT BREAKER
MCP MOTOR CIRCUIT PROTECTOR
MCT MAIN CROSS CONNECT
MDF MAIN DISTRIBUTION FRAME
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MET MAIN EARTHING TERMINAL
MFR MANUFACTURER
MH MANHOLE
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUG ONLY
MM MULTIMODE FIBER (FIBRE) OPTIC
STRAND
MSB MAIN SWITCHBOARD
MTD MOUNTED
MTG MOUNTING
MTS MAIN TERMINAL SPACE
MV MEDIUM VOLTAGE
MVCB MEDIUM VOLTAGE CIRCUIT
BREAKER
MW MICROWAVE OVEN
N NEUTRAL
NAC NOTIFICATION APPLIANCE CIRCUIT
NC NORMALLY CLOSED
NEC NATIONAL ELECTRIC CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS ASSOCIATION
ABBREVIATIONS
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OFCI OWNER FURNISHED, CONTRACTOR
INSTALLED
OFE OWNER FURNISHED EQUIPMENT
OH OVERHEAD
OL OVERLOAD
OS OCCUPANCY SENSOR, OPTIONAL
STANDBY
OSP OUTSIDE PLANT
P POLE
PA PUBLIC ADDRESS
PB PULL BOX
PD PUNCHDOWN
PF POWER FACTOR
PNL PANEL
POE POINT OF ENTRANCE
POS POINT OF SERVICE
PR PAIR
PT POTENTIAL TRANSFORMERS
PTS PNEUMATIC TUBE STATION
PTZ PAN/TILT/ZOOM
PV PHOTOVOLTAIC
PVC POLYVINYL CHLORIDE
PWR POWER
RA RETURN AIR
REC RECESSED
RECP RECEPTACLE
REQD REQUIRED
REX REQUEST TO EXIT
RM ROOM
RNC RIGID NON-METALLIC CONDUIT
RO RACEWAY ONLY
RPC REVERSE PHASE CUT
RSC, RGS RIGID STEEL CONDUIT
SCCR SHORT CIRCUIT CURRENT RATING
SEC SECURITY
SECT SECTION
SIM SIMILAR
SM SINGLE MODE FIBER OPTIC STRAND
SMR SURFACE MOUNTED RACEWAY
SPD SURGE PROTECTED DEVICE
SPDT SINGLE POLE DOUBLE THROW
SPECS SPECIFICATIONS
SPST SINGLE POLE SINGLE THROW
SS STAINLESS STEEL
ST SHUNT TRIP
STD STANDARD
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
SYS SYSTEM
TBB TELECOMMUNICATIONS BACKBONE
TC TEMPERATURE CONTROL OR
TERMINAL CABINET
TE TELECOMMUNICATIONS
ENCLOSURE
TELE TELEPHONE
TELECOM TELECOMMUNICATIONS
TEMP TEMPERATURE
TERM TERMINAL
TGB TELECOMMUNICATIONS GROUND
BAR
TMGB TELECOMMUNICATIONS MAIN
GROUND BAR
TOF TOP OF FIXTURE
TP TAMPER RESISTANT
TR TELECOMMUNICATIONS ROOM
TSP TWISTED SHIELDED PAIR
TSTAT THERMOSTAT
TTB TELECOM TERMINAL BOARD
TV TELEVISION
TYP TYPICAL
UG UNDERGROUND
UH UNIT HEATER
UNO UNLESS NOTED OTHERWISE
UNV UNIVERSAL VOLTAGE
UPS UNINTERRUPTIBLE POWER SUPPLY
USB UNIVERSAL SERIAL BUS
UTP UNSHIELDED TWISTED PAIR
UV UNIT VENTILATOR
V VOLTS
VA VOLT-AMPS
VAV VARIABLE AIR VOLUME
VC VOLUME CONTROL
VDT VISUAL DISPLAY TERMINAL
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VIF VERIFY IN FIELD
VOL VOLUME
VT VAPOR TIGHT
W WIRE, WATT
WAP WIRELESS ACCESS POINT
WG WIREGUARD
WL WET LOCATION
WP WEATHERPROOF
WT WATERTIGHT
XFMR TRANSFORMER
Ø, PH PHASE
- Drawing List - Electrical
E001 ELECTRICAL COVER SHEET
E200 GROUND FLOOR ELECTRICAL PLAN
E500 ENLARGED GROUND FLOOR ELECTRICAL PLAN
E510 ENLARGED GROUND FLOOR ELECTRICAL PLAN - SITE
E700 ELECTRICAL SCHEDULES
Attachment E
E200 E500
E200 E510
DC
DC
PP-BEQM
EXISTING
PANELBOARD
LOCATION
RP-BEQ
EXISTING
PANELBOARD
LOCATION
PROVIDE 60A FUSIBLE NEMA 3R
DISCONNECT WITH 50A FUSES
FED FROM CIRCUIT SHOWN FOR
TEMPORARY DRY COOLER.
COORDINATE EXACT LOCATION
PRIOR TO ROUGH IN.
(3) #6 & (1) #10G - 3/4" C
PP-BEQM-62,64,66
GENERAL NOTES
GENERAL NOTES APPLY TO ALL SHEETS IN THE SERIES THAT THEY ARE ON.
EACH SERIES OF SHEETS WILL START OVER AT NOTE 1.
KEY NOTES
KEY NOTES ARE NUMBERED SEQUENTIALLY FROM E1 TO THE LAST KEY NOTE.
THEY ARE PROJECT SPECIFIC. ONLY THE KEY NOTES USED ON A SPECIFIC SHEET
WILL BE LISTED ON THAT SHEET.
1. REFER TO DRAWING E700 FOR PANEL SCHEDULES AND COPPER
FEEDER SCHEDULES.
TRUE
NORTH
1 2 3 4 5 6 7
A
B
C
D
E
The Contractor shall verify and be responsible for all dimensions.
DO NOT scale the drawing - any errors or omissions shall be reported to Stantec without delay.
The Copyrights to all designs and drawings are the property of
Stantec. Reproduction or use for any purpose other than that authorized by Stantec is forbidden.
Copyright Reserved
Client/Project
Drawing No.
Project No.
Title
ORIGINAL SHEET - ANSI D (22"x34")
Permit-Seal
Issued
Revision
By Appd YYYY.MM.DD
Revision
Scale
By Appd YYYY.MM.DD
PRELIMINARY
NOT FOR CONSTRUCTION
Not for permits, pricing or other official purposes.
This document has not been completed or checked and is for general information or comment only.
Consultants
Legend
Notes www.stantec.com
/1
/2
:0
:5
A
M A u to d e sk D o c s:
W
V U
O
W P
D ry C o o le rs
R e p la c e /s tn m e c h
W
V U
O
W P
D ry C o o le rs
R e p la c e
.r v t
As indicated
Dry Coolers Replacement Project
WVU One Waterfront Place
GROUND FLOOR ELECTRICAL PLAN
E200
218012186
1 Waterfront Place
Morgantown, WV 26501
ISSUED FOR BID 2025.08.15
Stantec Architecture and Engineering LLC 101 East Diamond Street Suite 400 Butler, PA 16001-5975 Tel: (724) 285-4761 / Fax: (724) 285-6815
1/16" = 1'-0"E200
1 GROUND FLOOR ELECTRICAL PLAN
T
T
T
ATS-EQ
ATS-E
LP-BE RP-BE
PP-B
LP-B
RP-B
RP-BEQ
MSB-SC
PP-BEQ PP-BEQM
MCC-BEQ
RP-MCC-BT-112
T-30
T-30
EXISTING
PANELBOARD
PROVIDE 120V NORMAL/EMERGENCY CIRCUIT FROM
PANELBOARD 'RP-BEQ' FOR DRY COOLER CONTROLS PANEL.
COORDINATE EXACT LOCATION OF CONTROLS PANEL WITH
MECHANICAL AND CONTROLS CONTRACTORS.
GENERAL NOTES
GENERAL NOTES APPLY TO ALL SHEETS IN THE SERIES THAT THEY ARE ON.
EACH SERIES OF SHEETS WILL START OVER AT NOTE 1.
KEY NOTES
KEY NOTES ARE NUMBERED SEQUENTIALLY FROM E1 TO THE LAST KEY NOTE.
THEY ARE PROJECT SPECIFIC. ONLY THE KEY NOTES USED ON A SPECIFIC SHEET
WILL BE LISTED ON THAT SHEET.
1. REFER TO DRAWING E700 FOR PANEL SCHEDULES AND COPPER
FEEDER SCHEDULES.
TRUE
NORTH
1 2 3 4 5 6 7
A
B
C
D
E
The Contractor shall verify and be responsible for all dimensions.
DO NOT scale the drawing - any errors or omissions shall be reported to Stantec without delay.
The Copyrights to all designs and drawings are the property of
Stantec. Reproduction or use for any purpose other than that authorized by Stantec is forbidden.
Copyright Reserved
Client/Project
Drawing No.
Project No.
Title
ORIGINAL SHEET - ANSI D (22"x34")
Permit-Seal
Issued
Revision
By Appd YYYY.MM.DD
Revision
Scale
By Appd YYYY.MM.DD
PRELIMINARY
NOT FOR CONSTRUCTION
Not for permits, pricing or other official purposes.
This document has not been completed or checked and is for general information or comment only.
Consultants
Legend
Notes www.stantec.com
/1
/2
:0
:5
A
M A u to d e sk D o c s:
W
V U
O
W P
D ry C o o le rs
R e p la c e /s tn m e c h
W
V U
O
W P
D ry C o o le rs
R e p la c e
.r v t
As indicated
Dry Coolers Replacement Project
WVU One Waterfront Place
ENLARGED GROUND FLOOR
ELECTRICAL PLAN
E500
218012186
1 Waterfront Place
Morgantown, WV 26501
ISSUED FOR BID 2025.08.15
Stantec Architecture and Engineering LLC 101 East Diamond Street Suite 400 Butler, PA 16001-5975 Tel: (724) 285-4761 / Fax: (724) 285-6815
1/8" = 1'-0"E500
1 ENLARGED GROUND FLOOR ELECTRICAL PLAN - POWER
J
J
GENERAL NOTES
GENERAL NOTES APPLY TO ALL SHEETS IN THE SERIES THAT THEY ARE ON.
EACH SERIES OF SHEETS WILL START OVER AT NOTE 1.
KEY NOTES
KEY NOTES ARE NUMBERED SEQUENTIALLY FROM E1 TO THE LAST KEY NOTE.
THEY ARE PROJECT SPECIFIC. ONLY THE KEY NOTES USED ON A SPECIFIC SHEET
WILL BE LISTED ON THAT SHEET.
1. REFER TO DRAWING E700 FOR PANEL SCHEDULES AND COPPER
FEEDER SCHEDULES.
EXISTING COOLING TOWERS EXISTING GLYCOL COOLER
GLYCOL PUMP
GLYCOL PUMP
EXISTING GLYCOL COOLER
EXISTING DRY COOLERS TO BE REMOVED BY
THE M.C.. E.C. TO REMOVE EXISTING BRANCH
CIRCUIT CONDUCTORS, DISCONNECT
SWITCHES, ETC, AND WIRING BACK TO
SOURCE. RETAIN EXISTING CONDUIT FOR
REUSE IN NEW WORK
EXISTING COOLING TOWERS
DC
DC
PP-BEQM- 56,58,60
PROVIDE 60A FUSIBLE NEMA3R
DISCONNECT WITH 50A FUSES FED
FROM CIRCUIT SHOWN
TO DISCONNECT
TO DISCONNECT
TRUE
NORTH
1 2 3 4 5 6 7
A
B
C
D
E
The Contractor shall verify and be responsible for all dimensions.
DO NOT scale the drawing - any errors or omissions shall be reported to Stantec without delay.
The Copyrights to all designs and drawings are the property of
Stantec. Reproduction or use for any purpose other than that authorized by Stantec is forbidden.
Copyright Reserved
Client/Project
Drawing No.
Project No.
Title
ORIGINAL SHEET - ANSI D (22"x34")
Permit-Seal
Issued
Revision
By Appd YYYY.MM.DD
Revision
Scale
By Appd YYYY.MM.DD
PRELIMINARY
NOT FOR CONSTRUCTION
Not for permits, pricing or other official purposes.
This document has not been completed or checked and is for general information or comment only.
Consultants
Legend
Notes www.stantec.com
/1
/2
:0
:5
A
M A u to d e sk D o c s:
W
V U
O
W P
D ry C o o le rs
R e p la c e /s tn m e c h
W
V U
O
W P
D ry C o o le rs
R e p la c e
.r v t
As indicated
Dry Coolers Replacement Project
WVU One Waterfront Place
ENLARGED GROUND FLOOR
ELECTRICAL PLAN - SITE
E510
218012186
1 Waterfront Place
Morgantown, WV 26501
ISSUED FOR BID 2025.08.15
Stantec Architecture and Engineering LLC 101 East Diamond Street Suite 400 Butler, PA 16001-5975 Tel: (724) 285-4761 / Fax: (724) 285-6815
1/4" = 1'-0"E510
1 EXTERIOR DRY COOLERS ELECTRICAL DEMOLITION PLAN
1/4" = 1'-0"E510
2 EXTERIOR DRY COOLERS ELECTRICAL NEW WORK PLAN
PROVIDE NEMA3R WIREWAY
TO SPLIT CIRCUIT.
LOCATION TO BE DETERMINED IN FIELD.
PROVIDE NECESSARY SUPPORTS AS REQUIRED
NEW 60A/3P DISCONNECT
WITH 50A FUSESNEW 60A/3P DISCONNECT
WITH 50A FUSES
C50 3W C50 3W
C70 3W
INTERCEPT EXISTING CONDUIT &
REDIRECT AS REQUIRED
PP-BEQM
TO DRY COOLER
CONTROL PANEL
TO DRY COOLER
CONTROL PANEL
C50 3W C50 3W
1 2 3 4 5 6 7
A
B
C
D
E
The Contractor shall verify and be responsible for all dimensions.
DO NOT scale the drawing - any errors or omissions shall be reported to Stantec without delay.
The Copyrights to all designs and drawings are the property of
Stantec. Reproduction or use for any purpose other than that authorized by Stantec is forbidden.
Copyright Reserved
Client/Project
Drawing No.
Project No.
Title
ORIGINAL SHEET - ANSI D (22"x34")
Permit-Seal
Issued
Revision
By Appd YYYY.MM.DD
Revision
Scale
By Appd YYYY.MM.DD
PRELIMINARY
NOT FOR CONSTRUCTION
Not for permits, pricing or other official purposes.
This document has not been completed or checked and is for general information or comment only.
Consultants
Legend
Notes www.stantec.com
/1
/2
:0
:5
A
M A u to d e sk D o c s:
W
V U
O
W P
D ry C o o le rs
R e p la c e /s tn m e c h
W
V U
O
W P
D ry C o o le rs
R e p la c e
.r v t
12" = 1'-0"
Dry Coolers Replacement Project
WVU One Waterfront Place
ELECTRICAL SCHEDULES
E700
218012186
1 Waterfront Place
Morgantown, WV 26501
ISSUED FOR BID 2025.08.15
Stantec Architecture and Engineering LLC 101 East Diamond Street Suite 400 Butler, PA 16001-5975 Tel: (724) 285-4761 / Fax: (724) 285-6815
COPPER FEEDERS
ID
NOMINAL
CIRCUIT
RATING SETS CONDUCTORS GROUND
CONDUIT W/
N (4W)
CONDUIT
W/O N (3W)
C20 20 1 #12 #12 3/4" 3/4"
C30 30 1 #10 #10 3/4" 3/4"
C40 40 1 #8 #10 3/4" 3/4"
C50 50 1 #6 #10 1" 3/4"
C60 60 1 #4 #10 1 1/4" 1"
C70 70 1 #4 #8 1 1/4" 1 1/4"
C80 80 1 #3 #8 1 1/4" 1 1/4"
C90 90 1 #2 #8 1 1/2" 1 1/4"
C100 100 1 #1 #8 1 1/2" 1 1/2"
C125 125 1 #1 #6 1 1/2" 1 1/2"
C150 150 1 #1/0 #6 2" 1 1/2"
C175 175 1 #2/0 #6 2" 2"
C200 200 1 #3/0 #6 2" 2"
C225 225 1 #4/0 #4 2 1/2" 2"
C250 250 1 250 kcmil #4 3" 2 1/2"
C300 300 1 350 kcmil #4 3" 2 1/2"
C350 350 1 500 kcmil #3 3 1/2" 3"
C400 400 1 500 kcmil #3 3 1/2" 3"
C450 450 2 #4/0 #2 2 1/2" 2"
C500 500 2 250 kcmil #2 3" 2 1/2"
C600 600 2 350 kcmil #1 3" 2 1/2"
C800 800 2 500 kcmil #1/0 3 1/2" 3"
C900 900 3 350 kcmil #2/0 3" 3"
C100
1000 3 500 kcmil #2/0 3 1/2" 3"
C120
1200 4 350 kcmil #3/0 3" 3"
C160
1600 5 500 kcmil #4/0 3 1/2" 3"
C200
2000 6 500 kcmil 250 kcmil 3 1/2" 3"
C250
2500 7 500 kcmil 350 kcmil 3 1/2" 3 1/2"
C300
3000 8 500 kcmil 500 kcmil 4" 3 1/2"
C400
4000 11 500 kcmil 500 kcmil 4" 3 1/2"
Notes:
Total Est. Demand Current: 81 A
Total Conn. Current: 81 A
Total Est. Demand: 67339 VA
Total Conn. Load: 67339 VA
HVAC 67339 VA 100.00% 67339 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 81 A 81 A 81 A
Total Load: 22446 VA 22446 VA 22446 VA
65 0 VA 7482... 66
63 0 VA 7482... 64
AHU-5-1 (EXISTING) 60 A 3
0 VA 7482...
3 50 A TEMPORARY DRY COOLER
59 0 VA 1496... 60
57 0 VA 1496... 58
AHU-4-2 (EXISTING) 80 A 3
0 VA 1496...
3 70 A DC-1, DC-2
53 0 VA 0 VA 54
51 0 VA 0 VA 52
AHU-4-1 (EXISTING) 60 A 3
0 VA 0 VA
3 20 A EXISTING
47 0 VA 0 VA 48
45 0 VA 0 VA 46
AHU-3-2 (EXISTING) 80 A 3
0 VA 0 VA
3 20 A EXISTING
41 0 VA 0 VA 42
39 0 VA 0 VA 40
AHU-3-1 (EXISTING) 60 A 3
0 VA 0 VA
3 20 A SPF-2 (EXISTING)
35 0 VA 0 VA 36
33 0 VA 0 VA 34
AHU-2-2 (EXISTING) 80 A 3
0 VA 0 VA
3 20 A SPF-1 (EXISTING)
29 0 VA 0 VA 30
27 0 VA 0 VA 28
AHU-2-1 (EXISTING) 60 A 3
0 VA 0 VA
3 60 A AHU-7-2 (EXISTING)
23 0 VA 0 VA 24
21 0 VA 0 VA 22
AHU-1-2 (EXISTING) 80 A 3
0 VA 0 VA
3 60 A AHU-7-1 (EXISTING)
17 0 VA 0 VA 18
15 0 VA 0 VA 16
AHU-1-1 (EXISTING) 60 A 3
0 VA 0 VA
3 80 A AHU-6-2 (EXISTING)
11 0 VA 0 VA 12
9 0 VA 0 VA 10
MAIN (CONT.) 0 A 3
0 VA 0 VA
3 60 A AHU-6-1 (EXISTING)
5 0 VA 0 VA 6
3 0 VA 0 VA 4
MAIN 800 A 3
0 VA 0 VA
3 80 A AHU-5-2 (EXISTING)
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
1. PANELBOARD IS EXISTING.
Notes:
Enclosure: Type 1 MCB Rating: 800 A
Mounting: Surface Wires: 4 Mains Rating: 800 A
Supply From: Phases: 3 Mains Type: MLO
Location: MAIN ELECTRICAL G103 Volts: 480/277 Wye A.I.C. Rating:
Branch Panel: PP-BEQM
Not to Scale
RISER DIAGRAM
| Sheets |
| E001 - ELECTRICAL COVER SHEET |
| E200 - GROUND FLOOR ELECTRICAL PLAN |
| E500 - ENLARGED GROUND FLOOR ELECTRICAL PLAN |
| E510 - ENLARGED GROUND FLOOR ELECTRICAL PLAN - SITE |
| E700 - ELECTRICAL SCHEDULES |
File details come from the government source that posted it. Updated .