Attachment E - Electrical Drawings & Plans.pdf

PDF 320 KB Posted

Attached to
One Waterfront Place Dry Coolers Replacement
Solicitation number
RFB202690000664
Issued by
Mingo County, West Virginia

About this file

This document is an electrical design set for the Dry Coolers Replacement Project at WVU One Waterfront Place in Morgantown, West Virginia, prepared by Stantec Architecture and Engineering LLC. The project involves replacing existing dry coolers and associated electrical infrastructure, with electrical design drawings covering the ground floor electrical plan, enlarged electrical plans, and electrical schedules. The electrical design set includes comprehensive documentation for electrical equipment replacement, power distribution, and circuit modifications, with drawings issued for bid on August 15, 2025.

The electrical design set includes detailed specifications for electrical work, such as providing new 60A/3P disconnects with 50A fuses, rerouting existing conduits, and installing new electrical infrastructure for the dry coolers. The project involves working with existing electrical systems, including panelboards (PP-BEQM), and making precise electrical connections and modifications. The design accounts for temporary dry cooler installations, circuit redirections, and maintains the existing electrical infrastructure's overall integrity while facilitating the replacement of the cooling equipment.

View the file

Other files

Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FIRE ALARM

H C#/F#

FIRE SERVICE PHONE STATION OUTLET

S

ID

IN DUCT

STROBE LIGHT, CEILING MOUNTED

H

RC#/F#

S E

ELEVATOR RECALL

S I

IONIZATION

S P

PHOTOELECTRIC

STROBE LIGHT, WALL MOUNTED

S SPEAKER, CEILING MOUNTED

SPEAKER, WALL MOUNTED

SPEAKER AND STROBE LIGHT, CEILING MOUNTED

SPEAKER AND STROBE LIGHT, WALL MOUNTED

HORN AND STROBE LIGHT, CEILING MOUNTED

HORN AND STROBE LIGHT, WALL MOUNTED

F HORN, CEILING MOUNTED

HORN, WALL MOUNTED

F CHIME, WALL MOUNTED

F PULL STATION

ARCR AREA OF REFUGE COMMUNICATION REMOTE UNIT

ARCM AREA OF REFUGE COMMUNICATION MASTER UNIT

BEAM DETECTOR RECEIVER

BEAM DETECTOR TRANSMITTER

ADDRESSABLE INPUT MODULEAIM

DOOR HOLDER

ELECTRICALLY OPERATED SMOKE OR FIRE/SMOKE

DAMPER CONNECTION

D

DH

FAT FIRE ALARM TRANSMITTER

FACP FIRE ALARM CONTROL PANEL

GAP GRAPHIC ANNUNCIATOR PANEL

FAA FIRE ALARM ANNUNCIATOR

FATC FIRE ALARM TERMINAL CABINET

S

BR

S

BT

CO

GAS DETECTOR, CARBON MONOXIDE

SMOKE/HEAT/CARBON MONOXIDE DETECTOR

S

CO

H

F S

REMOTE INDICATOR, CEILING MOUNTED

REMOTE INDICATOR, WALL MOUNTED

DOOR CLOSERDCL

VS VALVE SUPERVISORY TAMPER SWITCH

PS PRESSURE DETECTOR/SWITCH

WF FLOW DETECTOR/SWITCH

SMOKE/HEAT DETECTORS H

AOM ADDRESSABLE OUTPUT MODULE

S

AS

AIR SAMPLING

SS SMOKE DETECTOR, SINGLE STATION

FLAME DETECTOR

H R

RATE OF RISE

NAC FIRE ALARM NOTIFICATION APPLIANCE CIRCUIT PANEL

R INTERFACE RELAY

HEAT/SMOKE DETECTOR

TYPES

S SMOKE DETECTOR, CEILING MOUNTED

H HEAT DETECTOR

S SMOKE DETECTOR, WALL MOUNTED

FIXED TEMPERATURE, # INDICATES °C OR °F

COMBINED RATE OF RISE/FIXED TEMPERATURE

RACEWAYS

RACEWAY CONCEALED IN CEILING OR WALL. EXPOSED

RACEWAY IS ALLOWED ONLY WHERE NOTED.

RACEWAY BELOW SLAB OR UNDERGROUND

RACEWAY UP

RACEWAY DOWN

RACEWAY STUB-OUT WITH BUSHING

RACEWAY CONTINUATION

JUNCTION BOX, CEILING OR ABOVE CEILING MOUNTED

PULL BOX

JUNCTION BOX, WALL MOUNTED

J

PB

J

JUNCTION BOX, IN-GROUNDJ

SURFACE RACEWAY (HORIZONTAL/VERTICAL)

WORK DEFINITION

EXISTING

REMOVE EXISTING

NEW WORK

FUTURE

TEMPORARY, AS NOTED

REMOVE EXISTING ELECTRICAL EQUIPMENT

KEY NOTE?:##

EQUIPMENT IDENTIFICATION

RECEPTACLESCIRCUITS

EMERGENCY NORMAL

SINGLE RECEPTACLE, 120V

N/A

DUPLEX RECEPTACLE, 120V

DOUBLE DUPLEX RECEPTACLE, 120V

RECEPTACLE, NEMA #

COMBINATION RECEPTACLE, NEMA # AND 120V

INDICATES TWIST LOCK

CLOCK RECEPTACLE, 120V

CORD DROP, 120V

MULTI-SERVICE FLOOR BOX (RECEPTACLES AS

INDICATED)

MULTI-SERVICE POKE THRU (RECEPTACLES AS

INDICATED)

MULTI-SERVICE POWER POLE (RECEPTACLES AS

INDICATED)

MULTI-SERVICE ASSEMBLY (RECEPTACLES AS

INDICATED)

SINGLE RECEPTACLE, 120V, CEILING MOUNTED

DUPLEX RECEPTACLE, 120V, CEILING MOUNTED

DOUBLE DUPLEX RECEPTACLE, 120V, CEILING

MOUNTED

N/A

N/A

N/A

N/A

N/A

INDICATES 15AN/A

RECEPTACLE TYPES

DEDICATED CIRCUITD

GROUND FAULT CIRCUIT INTERRUPTERG

GROUND FAULT CIRCUIT INTERRUPTER AND TAMPER

RESISTANT

GT

ISOLATED GROUNDIG

TAMPER RESISTANTT

INTEGRAL USB PORT(S)U

WEATHER RESISTANT COVERWP

SURGE PROTECTORS

INDICATES FULLY CONTROLLEDN/A

FURNITURE SYSTEMS RECEPTACLE, 120V

N/A

ARC FAULT CIRCUIT INTERRUPTERA

ARC FAULT CIRCUIT INTERRUPTER AND TAMPER

RESISTANT

AT

RECEPTACLE, NEMA #, CEILING MOUNTED##

CEILING CORD DROP, 120V

SPLIT WIRED RECEPTACLE, 120V, TOP CONTROLLED,

BOTTOM CONSTANTLY ENERGIZED

PLUG STRIP (HORIZONTAL/VERTICAL)N/A

MULTI-SERVICE FURNITURE BOX (RECEPTACLES AS

INDICATED)

N/A

INDICATES MOUNTED ABOVE COUNTER BACKSPLASH

MULTI-SERVICE CEILING BOX (RECEPTACLES AS

INDICATED)

N/A

MULTI-SERVICE WALL BOX (RECEPTACLES AS

INDICATED)

N/A

ELECTRICAL EQUIPMENT

EQUIPMENT CABINET OR PANEL

EQUIPMENT CONNECTION, FILL INDICATES

EMERGENCY CIRCUIT

GROUND BAR

MOTOR CONNECTION, 1Ø

MOTOR CONNECTION, 3Ø

BUS DUCT

BUS DUCT PLUGB

SURGE PROTECTIVE DEVICE

TRANSFORMER, NOT TO SCALE

TRANSFORMER, DRAWN TO SCALE

SPD

T

T

480V OR 600V POWER PANELBOARD

208V OR 240V POWER PANELBOARD

AUTOMATIC TRANSFER SWITCHATS

CONTROLS

FUSED SAFETY SWITCH, FUSE RATING INDICATED

NON-FUSED SAFETY SWITCH

COMBINATION MOTOR STARTER AND FUSED SAFETY

SWITCH, FUSE RATING INDICATED

MOTOR STARTER

MANUAL MOTOR STARTER

ENCLOSED CIRCUIT BREAKER

ENCLOSED CONTACTOR

AUTOMATIC DOOR PUSHPLATE

EMERGENCY SHUTDOWN

DEAD FRONT GFCI

DIRECT DIGITAL CONTROL PANEL

RELAY

THERMOSTAT

TIME CLOCK

VARIABLE FREQUENCY DRIVE

PUSH BUTTON CONTROL STATION

DDC

R

TC

VFD

TOGGLE SWITCH, MOTOR RATEDM

T

TOUCHLESS AUTOMATIC DOOR OPENER

1 2 3 4 5 6 7

A

B

C

D

E

The Contractor shall verify and be responsible for all dimensions.

DO NOT scale the drawing - any errors or omissions shall be reported to Stantec without delay.

The Copyrights to all designs and drawings are the property of

Stantec. Reproduction or use for any purpose other than that authorized by Stantec is forbidden.

Copyright Reserved

Client/Project

Drawing No.

Project No.

Title

ORIGINAL SHEET - ANSI D (22"x34")

Permit-Seal

Issued

Revision

By Appd YYYY.MM.DD

Revision

Scale

By Appd YYYY.MM.DD

PRELIMINARY

NOT FOR CONSTRUCTION

Not for permits, pricing or other official purposes.

This document has not been completed or checked and is for general information or comment only.

Consultants

Legend

Notes www.stantec.com

/1

/2

:0

:5

A

M A u to d e sk D o c s:

W

V U

O

W P

D ry C o o le rs

R e p la c e /s tn m e c h

W

V U

O

W P

D ry C o o le rs

R e p la c e

.r v t

12" = 1'-0"

Dry Coolers Replacement Project

WVU One Waterfront Place

ELECTRICAL COVER SHEET

E001

218012186

1 Waterfront Place

Morgantown, WV 26501

ISSUED FOR BID 2025.08.15

Stantec Architecture and Engineering LLC 101 East Diamond Street Suite 400 Butler, PA 16001-5975 Tel: (724) 285-4761 / Fax: (724) 285-6815

ABBREVIATIONS

#/C MULTI-CONDUCTOR, # INDICTATES

QUANTITY

(D) DEMOLISH

(E) EXISTING

(N) NEW

(R) EXISTING TO BE RELOCATED

1/C SINGLE CONDUCTOR

A AMPS

A/C AIR CONDITIONING UNIT

AC ALTERNATING CURRENT

ACH ABOVE COUNTER HEIGHT

ACT ACOUSTICAL CEILING TILE

ADA AMERICANS WITH DISABILITIES ACT

ADJ ADJUSTABLE

AF AMP FRAME

AFC ABOVE FINISHED CEILING

AFCI ARC FAULT CIRCUIT INTERRUPTER

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AHJ AUTHORITY HAVING JURISDICTION

AHU AIR HANDLING UNIT

AIC AMPERE INTERRUPTING CAPACITY

AL ALUMINUM

ALD ASSISTED LISTENING DEVICE

ALT ALTERNATE

ARCH ARCHITECTURAL

AS AMP SWITCH

AT AMP TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AV AUDIO VISUAL

AVG AVERAGE

AWG AMERICAN WIRE GAUGE

BC BONDING CONDUCTOR

BCU BARE COPPER

BFC BELOW FINISHED CEILING

BFG BELOW FINISHED GRADE

BKR BREAKER

BLDG BUILDING

BOF BOTTOM OF FIXTURE

BOH BACK OF HOUSE

BTM BOTTOM

C CONDUIT

C/W COMPLETE WITH

CAP CAPACITY

CATV COMMUNITY ANTENNA TELEVISION

CB CIRCUIT BREAKER

CCTV CLOSED CIRCUIT TELEVISION

CEC CANADIAN ELECTRIC CODE

CFOI CONTRACTOR FURNISHED, OWNER

INSTALLED

CIRC CIRCULATING

CKT CIRCUIT

CL CENTERLINE

CLG CEILING

CM CEILING MOUNTED

CMU CONCRETE MASONRY UNIT

CO CONDUIT ONLY

COMM COMMUNICATIONS

CONC CONCRETE

CONN CONNECTION

CONST CONSTRUCTION

CONT CONTINUOUS

CONTR CONTRACTOR

CPT CONTROL POWER TRANSFORMER

CPU CENTRAL PROCESSING UNIT

CR CRITICAL BRANCH

CT CURRENT TRANSFORMERS

CTR CENTER

CU COPPER

CUH CABINET UNIT HEATER

D DEDICATED

DALI DIGITAL ADDRESSABLE LIGHTING

INTERFACE

DC DIRECT CURRENT

DET DETAIL

DIA DIAMETER

DIM DIMENSION

DISC DISCONNECT

DIV DIVISION

DL DAMP LOCATION

DMX DIGITAL MULTIPLEX

DMX-RDM DIGITAL MULTIPLEX REMOTE

DEVICE MANAGEMENT

DN DOWN

DP DISTRIBUTION PANEL

DPDT DOUBLE POLE, DOUBLE THROW

DPR DAMPER

DPST DOUBLE POLE, SINGLE THROW

DWG DRAWING

DWH DOMESTIC WATER HEATER

EA EACH

EC ELECTRICAL CONTRACTOR

EF EXHAUST FAN

ELEC ELECTRICAL

ELEV ELEVATOR

EM EMERGENCY

EM GEN EMERGENCY GENERATOR

EMT ELECTRICAL METALLIC TUBING

ENCL ENCLOSURE

EP ELECTRIC-PNEUMATIC

EPO EMERGENCY POWER OFF

EQ EQUIPMENT BRANCH

EQUIP EQUIPMENT

ABBREVIATIONS

ETD EMERGENCY TRANSFER DEVICE

EWC ELECTRIC WATER COOLER

EXH EXHAUST

EXP EXPLOSION PROOF

EXTER EXTERIOR

F&I FURNISHED AND INSTALLED

FA FIRE ALARM

FAA FIRE ALARM ANNUNCIATOR

FACP FIRE ALARM CONTROL PANEL

FB FLOOR BOX

FCU FAN COIL UNIT

FLR FLOOR

FLUOR FLUORESCENT

FO FIBER (FIBRE) OPTIC

FOH FRONT OF HOUSE

FP FIRE PROTECTION

FPC FORWARD PHASE CONTROL

FS FUSIBLE SWITCH

FSCS FIRE FIGHTER SMOKE CONTROL

STATION

FU FUSE

FVNR FULL VOLTAGE NON REVERSING

FVR FULL VOLTAGE REVERSING

G, GND GROUND

G/Y GREEN YELLOW

GA GAUGE

GAL GALLONS

GC GENERAL CONTRACTOR

GEN GENERATOR

GFI, GFCI GROUND FAULT (CIRCUIT)

INTERRUPTER

H HOT CONDUCTOR

HC HORIZONTAL CROSS CONNECT

HD HAND DRYER

HFF HANDS FREE FIXTURE

HH HANDHOLE

HID HIGH INTENSITY DISCHARGE

HK HOUSE KEEPING PAD

HM HORIZONTALLY MOUNTED

HOA HAND-OFF-AUTO

HOR HORIZONTAL

HP HORSEPOWER

HT HEIGHT

HTG HEATING

HV HIGH VOLTAGE

HVCB HIGH VOLTAGE CIRCUIT BREAKER

HW HOT WATER

HZ HERTZ

IC INTERMEDIATE CROSS CONNECT

ID INSIDE DIAMETER

IDF INTERMEDIATE DISTRIBUTION

FRAME

IG ISOLATED GROUND

IMC INTERMEDIATE METAL CONDUIT

INST INSTANTANEOUS

IP INTERNET PROTOCOL

JB JUNCTION BOX

K KIRK KEY INTERLOCK

KAIC KILO-AMPS INTERRUPTING

CAPACITY

KV KILOVOLT

KVA KILOVOLT-AMPERES

KW KILOWATT

LED LIGHT EMITTING DIODE

LR LEGALLY REQUIRED

LS LIFE SAFETY BRANCH

LSIG LONG TIME, SHORT TIME,

INSTANTANEOUS, GROUND FAULT

LTG LIGHTING

LV LOW VOLTAGE

MAU MAKE UP AIR UNIT

MAX MAXIMUM

MC METAL CLAD CABLE

MCA MINIMUM CIRCUIT AMPS

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MCCB MOLDED CASE CIRCUIT BREAKER

MCP MOTOR CIRCUIT PROTECTOR

MCT MAIN CROSS CONNECT

MDF MAIN DISTRIBUTION FRAME

MDP MAIN DISTRIBUTION PANEL

MECH MECHANICAL

MET MAIN EARTHING TERMINAL

MFR MANUFACTURER

MH MANHOLE

MIN MINIMUM

MISC MISCELLANEOUS

MLO MAIN LUG ONLY

MM MULTIMODE FIBER (FIBRE) OPTIC

STRAND

MSB MAIN SWITCHBOARD

MTD MOUNTED

MTG MOUNTING

MTS MAIN TERMINAL SPACE

MV MEDIUM VOLTAGE

MVCB MEDIUM VOLTAGE CIRCUIT

BREAKER

MW MICROWAVE OVEN

N NEUTRAL

NAC NOTIFICATION APPLIANCE CIRCUIT

NC NORMALLY CLOSED

NEC NATIONAL ELECTRIC CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURERS ASSOCIATION

ABBREVIATIONS

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NO NORMALLY OPEN

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

OFCI OWNER FURNISHED, CONTRACTOR

INSTALLED

OFE OWNER FURNISHED EQUIPMENT

OH OVERHEAD

OL OVERLOAD

OS OCCUPANCY SENSOR, OPTIONAL

STANDBY

OSP OUTSIDE PLANT

P POLE

PA PUBLIC ADDRESS

PB PULL BOX

PD PUNCHDOWN

PF POWER FACTOR

PNL PANEL

POE POINT OF ENTRANCE

POS POINT OF SERVICE

PR PAIR

PT POTENTIAL TRANSFORMERS

PTS PNEUMATIC TUBE STATION

PTZ PAN/TILT/ZOOM

PV PHOTOVOLTAIC

PVC POLYVINYL CHLORIDE

PWR POWER

RA RETURN AIR

REC RECESSED

RECP RECEPTACLE

REQD REQUIRED

REX REQUEST TO EXIT

RM ROOM

RNC RIGID NON-METALLIC CONDUIT

RO RACEWAY ONLY

RPC REVERSE PHASE CUT

RSC, RGS RIGID STEEL CONDUIT

SCCR SHORT CIRCUIT CURRENT RATING

SEC SECURITY

SECT SECTION

SIM SIMILAR

SM SINGLE MODE FIBER OPTIC STRAND

SMR SURFACE MOUNTED RACEWAY

SPD SURGE PROTECTED DEVICE

SPDT SINGLE POLE DOUBLE THROW

SPECS SPECIFICATIONS

SPST SINGLE POLE SINGLE THROW

SS STAINLESS STEEL

ST SHUNT TRIP

STD STANDARD

SW SWITCH

SWBD SWITCHBOARD

SWGR SWITCHGEAR

SYS SYSTEM

TBB TELECOMMUNICATIONS BACKBONE

TC TEMPERATURE CONTROL OR

TERMINAL CABINET

TE TELECOMMUNICATIONS

ENCLOSURE

TELE TELEPHONE

TELECOM TELECOMMUNICATIONS

TEMP TEMPERATURE

TERM TERMINAL

TGB TELECOMMUNICATIONS GROUND

BAR

TMGB TELECOMMUNICATIONS MAIN

GROUND BAR

TOF TOP OF FIXTURE

TP TAMPER RESISTANT

TR TELECOMMUNICATIONS ROOM

TSP TWISTED SHIELDED PAIR

TSTAT THERMOSTAT

TTB TELECOM TERMINAL BOARD

TV TELEVISION

TYP TYPICAL

UG UNDERGROUND

UH UNIT HEATER

UNO UNLESS NOTED OTHERWISE

UNV UNIVERSAL VOLTAGE

UPS UNINTERRUPTIBLE POWER SUPPLY

USB UNIVERSAL SERIAL BUS

UTP UNSHIELDED TWISTED PAIR

UV UNIT VENTILATOR

V VOLTS

VA VOLT-AMPS

VAV VARIABLE AIR VOLUME

VC VOLUME CONTROL

VDT VISUAL DISPLAY TERMINAL

VERT VERTICAL

VFD VARIABLE FREQUENCY DRIVE

VIF VERIFY IN FIELD

VOL VOLUME

VT VAPOR TIGHT

W WIRE, WATT

WAP WIRELESS ACCESS POINT

WG WIREGUARD

WL WET LOCATION

WP WEATHERPROOF

WT WATERTIGHT

XFMR TRANSFORMER

Ø, PH PHASE

- Drawing List - Electrical

E001 ELECTRICAL COVER SHEET

E200 GROUND FLOOR ELECTRICAL PLAN

E500 ENLARGED GROUND FLOOR ELECTRICAL PLAN

E510 ENLARGED GROUND FLOOR ELECTRICAL PLAN - SITE

E700 ELECTRICAL SCHEDULES

Attachment E

E200 E500

E200 E510

DC

DC

PP-BEQM

EXISTING

PANELBOARD

LOCATION

RP-BEQ

EXISTING

PANELBOARD

LOCATION

PROVIDE 60A FUSIBLE NEMA 3R

DISCONNECT WITH 50A FUSES

FED FROM CIRCUIT SHOWN FOR

TEMPORARY DRY COOLER.

COORDINATE EXACT LOCATION

PRIOR TO ROUGH IN.

(3) #6 & (1) #10G - 3/4" C

PP-BEQM-62,64,66

GENERAL NOTES

GENERAL NOTES APPLY TO ALL SHEETS IN THE SERIES THAT THEY ARE ON.

EACH SERIES OF SHEETS WILL START OVER AT NOTE 1.

KEY NOTES

KEY NOTES ARE NUMBERED SEQUENTIALLY FROM E1 TO THE LAST KEY NOTE.

THEY ARE PROJECT SPECIFIC. ONLY THE KEY NOTES USED ON A SPECIFIC SHEET

WILL BE LISTED ON THAT SHEET.

1. REFER TO DRAWING E700 FOR PANEL SCHEDULES AND COPPER

FEEDER SCHEDULES.

TRUE

NORTH

1 2 3 4 5 6 7

A

B

C

D

E

The Contractor shall verify and be responsible for all dimensions.

DO NOT scale the drawing - any errors or omissions shall be reported to Stantec without delay.

The Copyrights to all designs and drawings are the property of

Stantec. Reproduction or use for any purpose other than that authorized by Stantec is forbidden.

Copyright Reserved

Client/Project

Drawing No.

Project No.

Title

ORIGINAL SHEET - ANSI D (22"x34")

Permit-Seal

Issued

Revision

By Appd YYYY.MM.DD

Revision

Scale

By Appd YYYY.MM.DD

PRELIMINARY

NOT FOR CONSTRUCTION

Not for permits, pricing or other official purposes.

This document has not been completed or checked and is for general information or comment only.

Consultants

Legend

Notes www.stantec.com

/1

/2

:0

:5

A

M A u to d e sk D o c s:

W

V U

O

W P

D ry C o o le rs

R e p la c e /s tn m e c h

W

V U

O

W P

D ry C o o le rs

R e p la c e

.r v t

As indicated

Dry Coolers Replacement Project

WVU One Waterfront Place

GROUND FLOOR ELECTRICAL PLAN

E200

218012186

1 Waterfront Place

Morgantown, WV 26501

ISSUED FOR BID 2025.08.15

Stantec Architecture and Engineering LLC 101 East Diamond Street Suite 400 Butler, PA 16001-5975 Tel: (724) 285-4761 / Fax: (724) 285-6815

1/16" = 1'-0"E200

1 GROUND FLOOR ELECTRICAL PLAN

T

T

T

ATS-EQ

ATS-E

LP-BE RP-BE

PP-B

LP-B

RP-B

RP-BEQ

MSB-SC

PP-BEQ PP-BEQM

MCC-BEQ

RP-MCC-BT-112

T-30

T-30

EXISTING

PANELBOARD

PROVIDE 120V NORMAL/EMERGENCY CIRCUIT FROM

PANELBOARD 'RP-BEQ' FOR DRY COOLER CONTROLS PANEL.

COORDINATE EXACT LOCATION OF CONTROLS PANEL WITH

MECHANICAL AND CONTROLS CONTRACTORS.

GENERAL NOTES

GENERAL NOTES APPLY TO ALL SHEETS IN THE SERIES THAT THEY ARE ON.

EACH SERIES OF SHEETS WILL START OVER AT NOTE 1.

KEY NOTES

KEY NOTES ARE NUMBERED SEQUENTIALLY FROM E1 TO THE LAST KEY NOTE.

THEY ARE PROJECT SPECIFIC. ONLY THE KEY NOTES USED ON A SPECIFIC SHEET

WILL BE LISTED ON THAT SHEET.

1. REFER TO DRAWING E700 FOR PANEL SCHEDULES AND COPPER

FEEDER SCHEDULES.

TRUE

NORTH

1 2 3 4 5 6 7

A

B

C

D

E

The Contractor shall verify and be responsible for all dimensions.

DO NOT scale the drawing - any errors or omissions shall be reported to Stantec without delay.

The Copyrights to all designs and drawings are the property of

Stantec. Reproduction or use for any purpose other than that authorized by Stantec is forbidden.

Copyright Reserved

Client/Project

Drawing No.

Project No.

Title

ORIGINAL SHEET - ANSI D (22"x34")

Permit-Seal

Issued

Revision

By Appd YYYY.MM.DD

Revision

Scale

By Appd YYYY.MM.DD

PRELIMINARY

NOT FOR CONSTRUCTION

Not for permits, pricing or other official purposes.

This document has not been completed or checked and is for general information or comment only.

Consultants

Legend

Notes www.stantec.com

/1

/2

:0

:5

A

M A u to d e sk D o c s:

W

V U

O

W P

D ry C o o le rs

R e p la c e /s tn m e c h

W

V U

O

W P

D ry C o o le rs

R e p la c e

.r v t

As indicated

Dry Coolers Replacement Project

WVU One Waterfront Place

ENLARGED GROUND FLOOR

ELECTRICAL PLAN

E500

218012186

1 Waterfront Place

Morgantown, WV 26501

ISSUED FOR BID 2025.08.15

Stantec Architecture and Engineering LLC 101 East Diamond Street Suite 400 Butler, PA 16001-5975 Tel: (724) 285-4761 / Fax: (724) 285-6815

1/8" = 1'-0"E500

1 ENLARGED GROUND FLOOR ELECTRICAL PLAN - POWER

J

J

GENERAL NOTES

GENERAL NOTES APPLY TO ALL SHEETS IN THE SERIES THAT THEY ARE ON.

EACH SERIES OF SHEETS WILL START OVER AT NOTE 1.

KEY NOTES

KEY NOTES ARE NUMBERED SEQUENTIALLY FROM E1 TO THE LAST KEY NOTE.

THEY ARE PROJECT SPECIFIC. ONLY THE KEY NOTES USED ON A SPECIFIC SHEET

WILL BE LISTED ON THAT SHEET.

1. REFER TO DRAWING E700 FOR PANEL SCHEDULES AND COPPER

FEEDER SCHEDULES.

EXISTING COOLING TOWERS EXISTING GLYCOL COOLER

GLYCOL PUMP

GLYCOL PUMP

EXISTING GLYCOL COOLER

EXISTING DRY COOLERS TO BE REMOVED BY

THE M.C.. E.C. TO REMOVE EXISTING BRANCH

CIRCUIT CONDUCTORS, DISCONNECT

SWITCHES, ETC, AND WIRING BACK TO

SOURCE. RETAIN EXISTING CONDUIT FOR

REUSE IN NEW WORK

EXISTING COOLING TOWERS

DC

DC

PP-BEQM- 56,58,60

PROVIDE 60A FUSIBLE NEMA3R

DISCONNECT WITH 50A FUSES FED

FROM CIRCUIT SHOWN

TO DISCONNECT

TO DISCONNECT

TRUE

NORTH

1 2 3 4 5 6 7

A

B

C

D

E

The Contractor shall verify and be responsible for all dimensions.

DO NOT scale the drawing - any errors or omissions shall be reported to Stantec without delay.

The Copyrights to all designs and drawings are the property of

Stantec. Reproduction or use for any purpose other than that authorized by Stantec is forbidden.

Copyright Reserved

Client/Project

Drawing No.

Project No.

Title

ORIGINAL SHEET - ANSI D (22"x34")

Permit-Seal

Issued

Revision

By Appd YYYY.MM.DD

Revision

Scale

By Appd YYYY.MM.DD

PRELIMINARY

NOT FOR CONSTRUCTION

Not for permits, pricing or other official purposes.

This document has not been completed or checked and is for general information or comment only.

Consultants

Legend

Notes www.stantec.com

/1

/2

:0

:5

A

M A u to d e sk D o c s:

W

V U

O

W P

D ry C o o le rs

R e p la c e /s tn m e c h

W

V U

O

W P

D ry C o o le rs

R e p la c e

.r v t

As indicated

Dry Coolers Replacement Project

WVU One Waterfront Place

ENLARGED GROUND FLOOR

ELECTRICAL PLAN - SITE

E510

218012186

1 Waterfront Place

Morgantown, WV 26501

ISSUED FOR BID 2025.08.15

Stantec Architecture and Engineering LLC 101 East Diamond Street Suite 400 Butler, PA 16001-5975 Tel: (724) 285-4761 / Fax: (724) 285-6815

1/4" = 1'-0"E510

1 EXTERIOR DRY COOLERS ELECTRICAL DEMOLITION PLAN

1/4" = 1'-0"E510

2 EXTERIOR DRY COOLERS ELECTRICAL NEW WORK PLAN

PROVIDE NEMA3R WIREWAY

TO SPLIT CIRCUIT.

LOCATION TO BE DETERMINED IN FIELD.

PROVIDE NECESSARY SUPPORTS AS REQUIRED

NEW 60A/3P DISCONNECT

WITH 50A FUSESNEW 60A/3P DISCONNECT

WITH 50A FUSES

C50 3W C50 3W

C70 3W

INTERCEPT EXISTING CONDUIT &

REDIRECT AS REQUIRED

PP-BEQM

TO DRY COOLER

CONTROL PANEL

TO DRY COOLER

CONTROL PANEL

C50 3W C50 3W

1 2 3 4 5 6 7

A

B

C

D

E

The Contractor shall verify and be responsible for all dimensions.

DO NOT scale the drawing - any errors or omissions shall be reported to Stantec without delay.

The Copyrights to all designs and drawings are the property of

Stantec. Reproduction or use for any purpose other than that authorized by Stantec is forbidden.

Copyright Reserved

Client/Project

Drawing No.

Project No.

Title

ORIGINAL SHEET - ANSI D (22"x34")

Permit-Seal

Issued

Revision

By Appd YYYY.MM.DD

Revision

Scale

By Appd YYYY.MM.DD

PRELIMINARY

NOT FOR CONSTRUCTION

Not for permits, pricing or other official purposes.

This document has not been completed or checked and is for general information or comment only.

Consultants

Legend

Notes www.stantec.com

/1

/2

:0

:5

A

M A u to d e sk D o c s:

W

V U

O

W P

D ry C o o le rs

R e p la c e /s tn m e c h

W

V U

O

W P

D ry C o o le rs

R e p la c e

.r v t

12" = 1'-0"

Dry Coolers Replacement Project

WVU One Waterfront Place

ELECTRICAL SCHEDULES

E700

218012186

1 Waterfront Place

Morgantown, WV 26501

ISSUED FOR BID 2025.08.15

Stantec Architecture and Engineering LLC 101 East Diamond Street Suite 400 Butler, PA 16001-5975 Tel: (724) 285-4761 / Fax: (724) 285-6815

COPPER FEEDERS

ID

NOMINAL

CIRCUIT

RATING SETS CONDUCTORS GROUND

CONDUIT W/

N (4W)

CONDUIT

W/O N (3W)

C20 20 1 #12 #12 3/4" 3/4"

C30 30 1 #10 #10 3/4" 3/4"

C40 40 1 #8 #10 3/4" 3/4"

C50 50 1 #6 #10 1" 3/4"

C60 60 1 #4 #10 1 1/4" 1"

C70 70 1 #4 #8 1 1/4" 1 1/4"

C80 80 1 #3 #8 1 1/4" 1 1/4"

C90 90 1 #2 #8 1 1/2" 1 1/4"

C100 100 1 #1 #8 1 1/2" 1 1/2"

C125 125 1 #1 #6 1 1/2" 1 1/2"

C150 150 1 #1/0 #6 2" 1 1/2"

C175 175 1 #2/0 #6 2" 2"

C200 200 1 #3/0 #6 2" 2"

C225 225 1 #4/0 #4 2 1/2" 2"

C250 250 1 250 kcmil #4 3" 2 1/2"

C300 300 1 350 kcmil #4 3" 2 1/2"

C350 350 1 500 kcmil #3 3 1/2" 3"

C400 400 1 500 kcmil #3 3 1/2" 3"

C450 450 2 #4/0 #2 2 1/2" 2"

C500 500 2 250 kcmil #2 3" 2 1/2"

C600 600 2 350 kcmil #1 3" 2 1/2"

C800 800 2 500 kcmil #1/0 3 1/2" 3"

C900 900 3 350 kcmil #2/0 3" 3"

C100

1000 3 500 kcmil #2/0 3 1/2" 3"

C120

1200 4 350 kcmil #3/0 3" 3"

C160

1600 5 500 kcmil #4/0 3 1/2" 3"

C200

2000 6 500 kcmil 250 kcmil 3 1/2" 3"

C250

2500 7 500 kcmil 350 kcmil 3 1/2" 3 1/2"

C300

3000 8 500 kcmil 500 kcmil 4" 3 1/2"

C400

4000 11 500 kcmil 500 kcmil 4" 3 1/2"

Notes:

Total Est. Demand Current: 81 A

Total Conn. Current: 81 A

Total Est. Demand: 67339 VA

Total Conn. Load: 67339 VA

HVAC 67339 VA 100.00% 67339 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 81 A 81 A 81 A

Total Load: 22446 VA 22446 VA 22446 VA

65 0 VA 7482... 66

63 0 VA 7482... 64

AHU-5-1 (EXISTING) 60 A 3

0 VA 7482...

3 50 A TEMPORARY DRY COOLER

59 0 VA 1496... 60

57 0 VA 1496... 58

AHU-4-2 (EXISTING) 80 A 3

0 VA 1496...

3 70 A DC-1, DC-2

53 0 VA 0 VA 54

51 0 VA 0 VA 52

AHU-4-1 (EXISTING) 60 A 3

0 VA 0 VA

3 20 A EXISTING

47 0 VA 0 VA 48

45 0 VA 0 VA 46

AHU-3-2 (EXISTING) 80 A 3

0 VA 0 VA

3 20 A EXISTING

41 0 VA 0 VA 42

39 0 VA 0 VA 40

AHU-3-1 (EXISTING) 60 A 3

0 VA 0 VA

3 20 A SPF-2 (EXISTING)

35 0 VA 0 VA 36

33 0 VA 0 VA 34

AHU-2-2 (EXISTING) 80 A 3

0 VA 0 VA

3 20 A SPF-1 (EXISTING)

29 0 VA 0 VA 30

27 0 VA 0 VA 28

AHU-2-1 (EXISTING) 60 A 3

0 VA 0 VA

3 60 A AHU-7-2 (EXISTING)

23 0 VA 0 VA 24

21 0 VA 0 VA 22

AHU-1-2 (EXISTING) 80 A 3

0 VA 0 VA

3 60 A AHU-7-1 (EXISTING)

17 0 VA 0 VA 18

15 0 VA 0 VA 16

AHU-1-1 (EXISTING) 60 A 3

0 VA 0 VA

3 80 A AHU-6-2 (EXISTING)

11 0 VA 0 VA 12

9 0 VA 0 VA 10

MAIN (CONT.) 0 A 3

0 VA 0 VA

3 60 A AHU-6-1 (EXISTING)

5 0 VA 0 VA 6

3 0 VA 0 VA 4

MAIN 800 A 3

0 VA 0 VA

3 80 A AHU-5-2 (EXISTING)

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

1. PANELBOARD IS EXISTING.

Notes:

Enclosure: Type 1 MCB Rating: 800 A

Mounting: Surface Wires: 4 Mains Rating: 800 A

Supply From: Phases: 3 Mains Type: MLO

Location: MAIN ELECTRICAL G103 Volts: 480/277 Wye A.I.C. Rating:

Branch Panel: PP-BEQM

Not to Scale

RISER DIAGRAM

Sheets
E001 - ELECTRICAL COVER SHEET
E200 - GROUND FLOOR ELECTRICAL PLAN
E500 - ENLARGED GROUND FLOOR ELECTRICAL PLAN
E510 - ENLARGED GROUND FLOOR ELECTRICAL PLAN - SITE
E700 - ELECTRICAL SCHEDULES

File details come from the government source that posted it. Updated .