Attachment D - Drawing 19-181 Electrical .pdf

PDF 699 KB Posted

Attached to
Z2DZ--GI SPS Equipment Site Prep Federal contract opportunity
Solicitation number
36C24621R0087
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 6

About this file

This presolicitation notice announces a forthcoming solicitation for site preparation work at the Durham VA Medical Center's Gastrointestinal Sterile Processing Section. The project scope includes renovations to the GI SPS area located on the ground floor of Building 1. The construction value is estimated between $500,000 and $1,000,000. The solicitation is anticipated to be a total service-disabled veteran-owned small business set-aside with NAICS code 236220 and a size standard of $39.5 million. Interested vendors should monitor the website for issuance of the solicitation around June 1, 2021, which will include specifications, drawings and any amendments. Proposals will be due approximately 30 days after issuance. The notice provides contact information for site visits and directs any questions to the identified point of contact via email only.

View the file

Other files for this federal contract opportunity

Other files attached to Z2DZ--GI SPS Equipment Site Prep, newest first.
File Type Posted
36C24621R0087 0001.docx DOCX document
Attachment K - Past Performance Questionnaire.docx DOCX document
Attachment E - Drawing 19-181 Fire Suppression .pdf PDF
36C24621R0087_1.docx DOCX document
Attachment J - Corp Experience Form.docx DOCX document
Attachment I - Base Proposal Item Price Breakdown.xlsx XLSX spreadsheet
Attachment G - Drawing 19-181 Plumbing .pdf PDF
Attachment A - Combined Specs .pdf PDF
Attachment B - Drawing 19-181 General .pdf PDF
36C24621R0087_1.pdf PDF
Attachment H - Wage Determination NC20210028 01_01_2021.pdf PDF
Attachment F - Drawing 19-181 Mechanical .pdf PDF
Attachment C - Drawing 19-181 Architectural .pdf PDF
Show all 13

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

L L

ELECTRICAL ABBREVIATIONS LIST

SR SURFACE RACEWAY

SS STAINLESS STEEL

SSW SELECTOR SWITCH

STD STANDARD

SURF SURFACE MOUNTED

SW SWITCH

SWBD SWITCHBOARD

SYM SYMMETRICAL

SYS SYSTEM

TC TIMECLOCK

TEL TELEPHONE

TEL/DATA TELEPHONE/DATA

TERM TERMINAL

TP TWISTED PAIR

TPS TWISTED PAIR SHIELDED

TR TAMPER RESISTANT

T-STAT THERMOSTAT

TTB TELEPHONE TERMINAL BOARD

TTC TELEPHONE TERMINAL

CABINET

TV TELEVISION

TYP TYPICAL

UC UNDER COUNTER

UE UNDERGROUND ELECTRICAL

UG UNDERGROUND

UH UNIT HEATER

UL UNDERWRITER'S LABORATORY

UT UNDERGROUND TELEPHONE

UTP UNSHIELDED TWISTED PAIR

UTIL UTILITY

UV UNIT VENTILATOR OR

ULTRAVIOLET

V VOLT

VA VOLT-AMPERES

VERT VERTICAL

VFD VARIABLE FREQUENCY DRIVE

VOL VOLUME

W WATT

W/ WITH

WH WATER HEATER

W/O WITHOUT

WP WEATHERPROOF

XFMR TRANSFORMER

XFR TRANSFER

ANGLE

@ AT

DELTA

' FEET

" INCHES

# NUMBER

Φ PHASE

C CENTER LINE

P PLATE

MTR MOTOR, MOTORIZED

MTS MANUAL TRANSFER SWITCH

NA NOT APPLICABLE

NC NORMALLY CLOSED

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURER'S ASSOCIATION

NFDS NON-FUSED SAFETY DISCONNECT

SWITCH

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NO NORMALLY OPEN

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

OH OVERHEAD

OL OVERLOAD

PA PUBLIC ADDRESS

PB PULL BOX OR PUSHBUTTON

PBPU PREFABRICATED BEDSIDE PATIENT

UNIT

PCB POLYCHLORINATED BYPHENYL

PC PHOTOELECTRIC CELL

PED PEDESTAL

PEND PENDANT

PF POWER FACTOR

PH PHASE

PIV POST INDICATING VALVE

PNL PANEL

POE POWER-OVER-ETHERNET

PR PAIR

PRI PRIMARY

PROJ PROJECTION

PRV POWER ROOF VENTILATOR

PT POTENTIAL TRANSFORMER

PVC POLYVINYL CHLORIDE (CONDUIT)

PWR POWER

QTY QUANTITY

RCP REFLECTED CEILING PLAN

RCPT RECEPTACLE

REQD REQUIRED

RGS RIGID GALVANIZED STEEL

RM ROOM

RMS ROOT MEAN SQUARE

RTU ROOF TOP UNIT

SC SURFACE CONDUIT

SEC SECONDARY

SF SQUARE FEET/FOOT

SHT SHEET

SI INTERNATIONAL SYSTEM OF UNITS

SIM SIMILAR

S/N SOLID NEUTRAL

SPEC SPECIFICATION

SPKR SPEAKER

SP SPARE

1P 1 POLE (2P, 3P, 4P, ETC.)

1PH 1 PHASE

2/C TWO-CONDUCTOR (3/C, 4/C, ETC.)

W2 TWO-WIRE (3W, 4W, ETC.)

3PH 3 PHASE

A AMPERE

AAP ALARM ANNUNCIATOR PANEL

AC ABOVE COUNTER

AIR CONDITIONER

ALTERNATING CURRENT

ACC ACCESSIBLE

ACLG ABOVE CEILING

ADO AUTOMATIC DOOR OPENER

A/E ARCHITECT/ENGINEER

AF AMP FRAME

AFC AVAILABLE FAULT CURRENT (KILOAMPS)

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AFI ARC FAULT CIRCUIT INTERRUPTER

AHJ AUTHORITY HAVING JURISDICTION

AHU AIR HANDLING UNIT

AIC AMPERE INTERRUPTING CAPACITY

AL ALUMINUM

ALT ALTERNATE

AMP AMPERE

APPROX APPROXIMATELY

ARCH ARCHITECT, ARCHITECTURAL

AT AMP TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AUX AUXILIARY

AV AUDIO VISUAL

AWG AMERICAN WIRE GAUGE

BAS BUILDING AUTOMATION SYSTEM

BATT BATTERY

BC BARE COPPER

BD BOARD

BFF BELOW FINISHED FLOOR

BLDG BUILDING

BMS BUILDING MANAGEMENT SYSTEM

BOD BASIS OF DESIGN

BYP BYPASS

C CONDUIT

CAB CABINET

CALC CALCULATED

CAP CAPACITY

CAT CATALOG, CATEGORY

CATV COMMUNITY ANTENNA TELEVISION

CB CIRCUIT BREAKER

CCR CONTROL CONTACTOR

CCTV CLOSED CIRCUIT TELEVISION

cd CANDELA

CD CONSTRUCTION DOCUMENTS

CF CONTRACTOR-FURNISHED

CKT CIRCUIT

CLG CEILING

CO CONTRACTING OFFICER

COAX COAXIAL CABLE

COMM COMMUNICATION

CONN CONNECTION

CONST CONSTRUCTION

CONT CONTINUATION OR CONTINUOUS

CONTR CONTRACTOR

COORD COORDINATE

COR CONTRACTING OFFICER'S

REPRESENTATIVE

CPT CONTROL POWER TRANSFORMER

CRI COLOR RENDERING INDEX

CT CURRENT TRANSFORMER

CTV CABLE TELEVISION

CTR CENTER

CU COPPER

CU FT CUBIC FEET

dB DECIBEL

DB DIRECT BURIAL

DC DIRECT CURRENT

DEG C DEGREES CELSIUS

DEG F DEGREES FAHRENHEIT

DEMO DEMOLISH/DEMOLITION

DEPT DEPARTMENT

DIA DIAMETER

DISC DISCONNECT

DIST DISTRIBUTION

DN DOWN

DS SAFETY DISCONNECT SWITCH

DT DOUBLE THROW

DWG DRAWING

EC ELECTRICAL CONTRACTOR

EG EQUIPMENT GROUND

ELEC ELECTRIC, ELECTRICAL

ELEV ELEVATOR

EM EMERGENCY

EMI ELECTROMAGNETIC INTERFERENCE

EMS ENERGY MANAGEMENT SYSTEM

EMT ELECTRICAL METALLIC TUBING

EPO EMERGENCY POWER OFF

EQUIP EQUIPMENT

ESMT EASEMENT

ETR EXISTING TO REMAIN

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WALL HEATER

ELECTRIC WATER HEATER

EX EXISTING

EXP EXPLOSION PROOF

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

FC FOOTCANDLE

FCU FAN COIL UNIT

FIXT FIXTURE

FLR FLOOR

FLUOR FLUORESCENT

FU FUSE

FUDS FUSED SAFETY DISCONNECT SWITCH

FVR FULL VOLTAGE REVERSING

FVNR FULL VOLTAGE NON-REVERSING

GAL GALLON

GALV GALVANIZED

GC GENERAL CONTRACTOR

GEN GENERATOR

GFI GROUND FAULT CIRCUIT INTERRUPTER

GND GROUND

GRS GALVANIZED RIGID STEEL (CONDUIT)

GYP BDGYPSUM BOARD

HID HIGH-INTENSITY DISCHARGE

HOA HAND-OFF-AUTOMATIC

HP HORSEPOWER

HT HEIGHT

HTR HEATER

HV HIGH VOLTAGE

HVAC HEATING, VENTILATING AND AIR

CONDITIONING

IES ILLUMINATION ENGINEERING SOCIETY

IG ISOLATED GROUND

IMC INTERMEDIATE METAL CONDUIT

IR INFRARED

I/W INTERLOCK WITH

IWH INSTANTANEOUS WATER HEATER

J-BOX JUNCTION BOX

KV KILOVOLT

KVA KILOVOLT-AMPERE

KVAR KILOVOLT-AMPERE REACTIVE

KW KILOWATT

KWH KILOWATT HOUR

LED LIGHT-EMITTING DIODE

LF LINEAR FEET/FOOT

LM LUMEN

LRA LOCKED ROTOR AMPS

LT LIGHT

LTG LIGHTING

LTNG LIGHTNING

LV LOW VOLTAGE

MATV MASTER ANTENNA TELEVISION SYSTEM

MAX MAXIMUM

MC MECHANICAL CONTRACTOR

METAL-CLAD (CONDUIT)

MCA MINIMUM CIRCUIT AMPACITY

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDP MAIN DISTRIBUTION PANEL

MECH MECHANICAL

MFR MANUFACTURER

MFS MAIN FUSED DISCONNECT SWITCH

MH MANHOLE

MIC MICROPHONE

MIN MINIMUM

MISC MISCELLANEOUS

MLO MAIN LUGS ONLY

MOA MULTIOUTLET ASSEMBLY

MSBD MAIN SWITCHBOARD

MT MOUNT

A1 b

E1 c d

T1

'LPN'

ELECTRICAL SYMBOL NOTES

THE LIGHTING FIXTURE TYPE IS INDICATED BY AN UPPER CASE LETTER OR AN UPPER

CASE LETTER AND NUMBER.

THE SWITCH DESIGNATION (IF NEEDED) IS INDICATED BY A LOWER CASE LETTER.

EXAMPLE: LIGHTING FIXTURE TYPE 'A1' IS CONTROLLED BY SWITCH 'b'.

EXIT SIGNS: STEM INDICATES WALL MOUNTING. NO STEM INDICATES CEILING

MOUNTING. SHADED AREA INDICATES ILLUMINATED FACE(S). ARROW INDICATES

DIRECTIONAL ARROW ON ILLUMINATED FACE(S).

DEVICES: THE SWITCH DESIGNATION IS INDICATED BY A LOWER CASE LETTER.

THE CONTROL DEVICE DESIGNATION IS INDICATED BY A LOWER CASE LETTER.

TRANSFORMERS: THE TRANSFORMER TYPE IS INDICATED BY A NUMBER

FOLLOWING THE UPPER CASE LETTER 'T'. SEE THE TRANSFORMER SCHEDULE OR

THE SINGLE LINE DIAGRAM FOR THE TRANSFORMER DESCRIPTION AND

REQUIREMENTS.

PANELBOARDS: PANELBOARD DOORS MAY BE SHOWN TO INDICATE OPENING

SIDE OF RECESSED PANELBOARDS. SEE PANELBOARD IDENTIFICATION FOR

DESIGNATION CODES.

SHEET KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE NOTE

NUMBER INDICATED IN THE HEXAGON.

HOME RUN TO BRANCH CIRCUIT PANEL: THE PANEL DESIGNATION AND CIRCUIT

DESIGNATION ARE SHOWN ADJACENT TO THE HOME RUN ARROW.

CIRCUIT BREAKER SIZES (AMPS/NUMBER OF POLES) ARE SHOWN IN THE PANEL

SCHEDULE WITH THE CORRESPONDING PANEL AND CIRCUIT DESIGNATION.

SYMBOL NOTATIONS: UPPER CASE LETTERS ADJACENT TO SYMBOLS INDICATE

A UNIT TYPE. SEE APPROPRIATE SCHEDULE OR SPECIFICATIONS.

'LPN'-1,3,5

EXAMPLE 1: WALL MOUNTED EXIT SIGN TYPE 'E1' WITH SINGLE FACE

AND DIRECTIONAL ARROW.

EXAMPLE 2: CEILING MOUNTED EXIT SIGN TYPE 'E2' WITH DOUBLE

FACE AND DIRECTIONAL ARROWS.

E2

EXAMPLE: SPLIT DUPLEX RECEPTACLE; ONE RECEPTACLE OUTLET IS

CONTROLLED BY SWITCH 'c'.

EXAMPLE: SINGLE POLE SWITCH 'd' TO CONTROL LIGHTING FIXTURES INDICATED BY 'd'.

EXAMPLE: TRANSFORMER TYPE 'T1'.

EXAMPLE: HOME RUN TO PANELBOARD 'LPN'; CIRCUITS 1, 3, 5.

# DEMOLITION KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE

NOTE NUMBER INDICATED IN THE SQUARE.

GENERAL ELECTRICAL NOTES

1. ALL ELECTRICAL DEVICES, FIXTURES, EQUIPMENT AND FEEDERS SHALL BE INSTALLED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS, THE MANUFACTURER'S RECOMMENDED PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT AND WITH THE LATEST EDITION OF THE NATIONAL

ELECTRICAL CODE AND VA STANDARDS.

2. PROVIDE ADDITIONAL SUPPORT FOR DEVICES, FIXTURES, EQUIPMENT AND FEEDERS WHERE THE BUILDING

CONSTRUCTION IS NOT SUITABLE FOR DIRECT MOUNTING.

3. FIRESTOP, DRAFTSTOP, SMOKESTOP AND/OR PROTECT THE ANNULAR SPACE AROUND ALL PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILING, AND ROOFS IN ACCORDANCE WITH THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE, UL LISTING REQUIREMENT AND THE APPLICABLE BUILDING CODES.

4. VERIFY CEILING SYSTEMS AND PROVIDE MOUNTING ACCESSORIES, TRIMS AND ALL REQUIRED MOUNTING

HARDWARE TO SUIT THE PARTICULAR INSTALLATION.

5. BRANCH CIRCUIT CONDUCTORS SHALL BE 12 AWG COPPER MINIMUM.

6. COORDINATE ANY AND ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION SO AS TO AVOID CONFLICT

DURING CONSTRUCTION.

7. ALL PANELS SHALL HAVE TYPED, COMPLETED DIRECTORIES INDICATING EQUIPMENT SERVED AND ROOM NUMBER (AS INDICATED ON FINAL BUILDING ROOM SIGNAGE) OF EQUIPMENT LOCATION, OR SPARE, OR SPACE.

8. MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES, TO INDICATE A QUALITY STANDARD, AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR MANUFACTURER.

PRODUCTS DEEMED EQUAL AND APPROVED BY THE DESIGNER WILL BE ACCEPTED. ALL PRODUCTS MUST

COMPLY WITH "BUY AMERICAN ACT".

9. ALL FEEDERS AND CIRCUITRY SHALL BE TORQUED PER THE PANEL, BREAKER, AND/OR PARTICULAR EQUIPMENT

MANUFACTURER'S SPECIFICATIONS.

10. CIRCUITRY TO SWITCHES, RECEPTACLES, AND ALL OTHER DEVICES SHALL BE TERMINATED ON THE DEVICE'S

SCREW TERMINALS.

11. MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, OUTLET, FIXTURE, OR EQUIPMENT UNLESS NOTED

OTHERWISE.

12. ALL WIRE TERMINATIONS SHALL BE RATED FOR 75 DEGREES C.

13. ALL CONDUCTORS SHALL HAVE THHN/THWN INSULATION, UNLESS OTHERWISE NOTED.

14. ALL CONDUIT SHALL BE RGS OR EMT UNLESS OTHERWISE NOTED. FMC CONDUIT SHALL BE USED ON VIBRATING EQUIPMENT (MAXIMUM LENGTH OF 6 FEET). PVC SHALL BE USED FOR UNDERGROUND CONDUIT OR WHERE CONCRETE-ENCASED. WHERE VIBRATING EQUIPMENT IS LOCATED OUTSIDE, LFMC CONDUIT SHALL BE USED

(MAXIMUM SIX FEET) FOR FINAL CONNECTIONS.

15. ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT SHALL BE LABEL LISTED BY AN APPROVED

THIRD PARTY TESTING AGENCY.

16. IN CASE OF CONFLICTS OR DISCREPANCIES WITHIN OR AMONG THE CONTRACT DRAWINGS, THE BETTER QUALITY, MORE STRINGENT REQUIREMENTS OR GREATER QUANTITY OF WORK , AS DETERMINED BY THE

GOVERNMENT, SHALL BE PROVIDED.

17. COMPRESSION COUPLINGS SHALL BE USED. NO SET SCREW FITTINGS ARE ALLOWED.

18. MINIMUM CONDUIT SIZE TO BE USED IS 3/4".

ELECTRICAL SYMBOL LEGEND

120V DUPLEX RECEPTACLE

RECEPTACLE MODIFIERS:

AC: 3" ABOVE COUNTERTOP/BACKSPLASH

GFI: GROUND FAULT CURRENT INTERRUPTER

WP: WEATHERPROOF ENCLOSURE

DED: DEDICATED CIRCUIT

120V DUPLEX RECEPTACLE EMERGENCY OUTLET

AND COVER PLATE SHALL BE RED IN COLOR

120V QUADRUPLEX RECEPTACLE

120V QUADRUPLEX RECEPTACLE EMERGENCY

OUTLET AND COVER PLATE SHALL BE RED IN COLOR

JUNCTION BOX, WALL MOUNTED, PURPOSE AS NOTED

DISCONNECT SWITCH NON-FUSED

DISCONNECT SWITCH FUSED

SINGLE POLE WALL SWITCH: 48" AFF STANDARD UNO

SYMBOL HEIGHT DESCRIPTION

18"

18"

18"

18"

AS

NOTED

72" TOP

72" TOP

SWITCH MODIFIERS:

M: MOTOR-RATED

48"

ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.

TOP: HEIGHT TO TOP OF DEVICE

ANY HEIGHTS INDICATED IN PLANS SHALL SUPERCEDE THOSE LISTED HERE.

SPECIAL RECEPTACLE

EQUIPMENT CONNECTION

AS

NOTED

E

208V DUPLEX RECEPTACLE18"

18"

120V DUPLEX RECEPTACLE FLOOR BOX

120V DUPLEX RECEPTACLE EMERGENCY FLOOR BOX

OUTLET AND COVER PLATE SHALL BE RED IN COLOR

120V QUADUPLEX RECEPTACLE FLOOR BOX

120V QUADUPLEX RECEPTACLE EMERGENCY

FLOOR BOX OUTLET AND COVER PLATE SHALL BE

RED IN COLOR

CLNG

J

J

J

JUNCTION BOX, CEILING MOUNTED, PURPOSE AS

NOTED

JUNCTION BOX, FLOOR MOUNTED, PURPOSE AS

NOTED

LIGHTING SYMBOL LEGEND

2' X 2' RECESSED DIRECT/INDIRECT TROFFER

2' X 4' RECESSED DIRECT/INDIRECT TROFFER

SYMBOL HEIGHT

AFF *

DESCRIPTION

--- 2' X 4' RECESSED FLAT PRISMATIC LENS TROFFER

WALL SCONCE

6'-0"

CENTER

6" DIAMETER RECESSED DOWNLIGHT---

EXIT SIGN - WALL MOUNTED

EXIT SIGN - CEILING MOUNTED---

7'-5"

BOTTOM

SINGLE POLE WALL SWITCH

SWITCH MODIFIERS:

OS: OCCUPANCY SENSOR, DUAL TECHNOLOGY

VS: VACANCY SENSOR, DUAL TECHNOLOGY

LV: LOW VOLTAGE

LVD: LOW VOLTAGE DIMMER

D: LINE VOLTAGE DIMMER

T: DIGITAL TIMER

K: KEYED

3: 3 WAY

48"

CENTER

2' LINEAR - WALL MOUNTED

7'-0"

CENTER

EMERGENCY LIGHT BATTERY

OPERATED - WALL MOUNTED

7'-6"

CENTER

* - ANY HEIGHTS INDICATED IN PLANS SHALL SUPERCEDE THOSE

LISTED HERE.

4' LINEAR - WALL MOUNTED

7'-0"

CENTER

TECHNOLOGY SYMBOL LEGEND

DATA OUTLET - N-4 PR UTP

TELCO OUTLET - N-4 PR UTP

SYMBOL HEIGHT DESCRIPTION

18"

48"

ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.

ANY HEIGHTS INDICATED IN PLANS SHALL SUPERCEDE THOSE LISTED HERE.

SEE DRAWINGS FOR MORE INFORMATION.

NOTE: NOT ALL SYMBOLS ARE USED.

ELECTRONIC LOCKING MECHANISM

DOOR CONTACT

REQUEST FOR EXIT SENSOR

CARD READER

(K - KEYPAD)

48"CR

ES

DC

RX

48" PUSH PAD FOR DOOR OPERATOR

WIRELESS ACCESS POINT - N-4 PR UTP

WALL PHONEW

IC

INTERCOM WITH CAMERA

IC

INTERCOM MASTER WITH PUSH TO RELEASE DOORM

N

TV OUTLET WALL MOUNTED

48"

54"

DESK

CCTV DOME CAMERA FIXED

CCTV DOME CAMERA PAN/TILT/ZOOM

FOUR POST OIT EQUIPMENT RACK

OIT EQUIPMENT CABINET

MATV EQUIPMENT CABINET

CCTV EQUIPMENT CABINET

MATV

CCTV

LADDER CABLE TRAY

N

N

FLOOR BOX FOR DATA

AS NOTED

DOOR

DOOR

ABOVE

DOOR

6' TO TOP

FLOOR

PHYSICAL ACCESS CONTROL SYSTEMPACS 6' TO TOP

ELECTRONIC PANIC HARDWAREEP

DO DOOR OPERATOR

HANDWAVE

L

KP PATIENT ROAM ALERT ACCESS CONTROL KEYPAD48"

PATIENT ROAM ALERT ANTENNACEILING

GROUND BUS

CEILING

DOOR

DOOR

48"

FLOOR

FLOOR

FLOOR

ABOVE

CEILING

18"

4'x8'x3/4" FIRE RATED TTB8"

FLOOR TWO POST OIT EQUIPMENT RACK

CEILING MOUNTED SPEAKERSCEILING

WALL MOUNTED SPEAKERS96"

S

S

SECURE WIRELESS ACCESS POINT - N-4 PR UTP

N

CEILING

S

(N - QUANTITY)

(N - QUANTITY)

(N - QUANTITY)

(N - QUANTITY)

CEILING

CEILING

S

NURSE CALL/INTERCOM STATION48"

GENERAL TECHNOLOGY NOTES

1. PROVIDE COMMUNICATIONS DEVICES AND EQUIPMENT IN ACCORDANCE WITH THE CONTRACT DOCUMENTS, MANUFACTURER'S RECOMMENDED PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT, LATEST EDITION OF THE NATIONAL ELECTRICAL CODE, BICSI STANDARDS, AND VA STANDARDS.

2. PROVIDE ADDITIONAL SUPPORT FOR DEVICES AND EQUIPMENT WHERE BUILDING CONSTRUCTION IS NOT SUITABLE

FOR DIRECT MOUNTING.

3. FIRESTOP, DRAFTSTOP, SMOKESTOP OR PROTECT ANNULAR SPACE AROUND PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILINGS, AND ROOF IN ACCORDANCE WITH REQUIREMENTS OF NFPA 70, UL LISTING

REQUIREMENT AND APPLICABLE BUILDING CODES.

4. PROVIDE CABLING THAT COMPLIES WITH THE LATEST EDITION OF TELECOMMUNICATIONS DISTRIBUTION METHOD

MANUAL AND ANSI/TIA/EIA PUBLICATIONS.

5. COMPLY WITH THE LATEST ANSI/TIA/EIA 758 AND 607B OR 607A - GROUNDING AND BONDING REQUIREMENTS FOR

TELECOMMUNICATIONS IN COMMERCIAL BUILDING.

6. COMPLY WITH THE LATEST ANSI/TIA/EIA 568B - COMMERCIAL BUILDING TELECOMMUNICATIONS WIRING STANDARD.

7. COMPLY WITH THE LATEST ANSI/TIA/EIA 569B - COMMERCIAL BUILDING STANDARD FOR TELECOMMUNICATIONS

PATHWAYS AND SPACES.

8. COMPLY WITH THE LATEST NFPA 70 NATIONAL ELECTRICAL CODE.

9. COMPLY WITH THE LATEST NFPA 99 HEALTHCARE FACILITIES CODE.

10. COMPLY WITH THE LATEST NFPA 101 LIFE SAFETY CODE.

11. COORDINATE WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION.

12. MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES, TO INDICATE A QUALITY STANDARD, AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR MANUFACTURER. PRODUCTS DEEMED EQUAL AND APPROVED BY THE COR WILL BE ACCEPTABLE. COMPLY WITH "BUY AMERICAN ACT".

13. MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, BOXES, OUTLET, OR EQUIPMENT UNLESS NOTED

OTHERWISE.

14. PROVIDE RGS OR EMT CONDUIT UNLESS OTHERWISE NOTED.

15. PROVIDE MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT LABEL LISTED BY APPROVED THIRD PARTY TESTING

AGENCY.

16. NOTIFY COR REGARDING DISCREPANCY BETWEEN PLANS AND SPECIFICATIONS FOR CLARIFICATION. THE MORE

STRINGENT OF THE THEM SHALL TAKE PRECEDENCE.

17. PROVIDE TIA/EIA CAT 6 COPPER OUTLETS AND CONNECTORS.

18. ALL WORK AREA OUTLETS SHALL BE 8 PIN, CAT 6 KEYSTONE JACK WIRED PER T568A OR T568B AS DIRECTED BY THE

VA COR.

19. LABEL DEVICES IN ACCORDANCE WITH LATEST ANSI/TIA 606A OR 606B EDITION AS WELL AS THE STANDARDS SET

FORTH BY THE VA HOSPITAL OIT.

20. PROVIDE A MINIMUM OF 12" CLEARANCE ABOVE THE CABLE TRAY PER TIA/EIA 569.B PARAGRAPH 4.5.6.2.

21. ALL CABLING INSTALLED ABOVE CEILING SHALL BE PLENUM RATED.

22. MINIMUM CONDUIT SIZE TO BE USED IS 3/4".

LUMINAIRE SCHEDULE

A. CONTRACTOR RESPONSIBLE FOR REMOVING, PROTECTING, AND REINSTALLING EXISTING LIGHTING FIXTURES. IF LIGHTING FIXTURE IS DAMAGED DURING COURSE OF WORK. CONTRACTOR SHALL BE RESPONSIBLE FOR REPLACING FIXTURE. CONTRACTOR SHALL CLEAN

FIXTURES PRIOR TO REINSTALLATION.

B. MANUFACTURER AND CATALOG NUMBERS SHOWN ARE FOR BASIS OF DESIGN, DESCRIPTIVE AND QUALITY STANDARDS ONLY, NOT TO BE USED FOR ORDERING WITHOUT VERIFICATION AND APPROVAL. CONTRACTOR TO PROVIDE PRODUCT OR EQUAL FOR APPROVAL BY OWNER, ARCHITECT AND ENGINEER. ENGINEER SHALL NOT BE RESPONSIBLE FOR MISMATCHED OR INACCURATE PART NUMBERS.

C. VERIFY ALL LIGHT FIXTURE MOUNTING TYPES AND COLORS WITH ARCHITECT.

D. LIGHTING CONTROLS, INCLUDING CONTROL SCHEMATICS, DEVICES, SWITCHES, SENSORS AND GRAPHIC DISPLAYS/CONTROLLERS. THIS INFORMATION MUST BE SUBMITTED WITH THE LIGHT FIXTURE SHOP DRAWINGS, FOR A COMPLETE REVIEW.

GENERAL NOTES:

FIRE ALARM SYMBOL LEGEND

SYMBOL HEIGHT DESCRIPTION

ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.

TOP: HEIGHT TO TOP OF DEVICE

ANY HEIGHTS INDICATED IN PLANS SHALL SUPERCEDE THOSE LISTED HERE.

F FIRE ALARM STROBE

FIRE ALARM SPEAKER AND STROBE

90"

90"

XX - CANDELA

XX - CANDELA

XX - WATTAGEF

S

FIRE ALARM SPEAKER90"F

S

FIRE ALARM DUCT SMOKE DETECTOR

FIRE ALARM SMOKE DETECTORSD

FIRE ALARM RELAY MODULE

DD

FAR

1. PROVIDE FIRE ALARM SYSTEM AND COMPONENTS COMPLYING WITH THE LATEST:

A. NFPA 70 NATIONAL ELECTRICAL CODE.

B. NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE.

C. NFPA 101 LIFE SAFETY CODE.

D. VA FIRE PROTECTION DESIGN MANUAL.

E. ANSI S3.41 AUDIBLE EMERGENCY EVACUATION SIGNAL.

2. FIRE ALARM SYSTEM SHALL COMPLY WITH FACTORY MUTUAL RESEARCH CORPORATION (FM).

3. PROVIDE FIRE ALARM WIRING IN CONDUIT, FACTORY PAINTED RED.

4. BEFORE STARTING WORK, TEST EXISTING FIRE ALARM SYSTEM IN WORK AREA AND ADJACENT AREAS.

5. NOTIFY COR REGARDING DEFICIENCIES AND NON-OPERATING COMPONENTS. VA WILL MAKE REPAIRS.

6. WHEN WORK IS COMPLETE, TEST EXISTING FIRE ALARM SYSTEM IN WORK AREA AND ADJACENT AREAS.

7. MAKE REPAIRS TO RESOLVE INCORRECT SYSTEM OPERATIONS AT NO ADDITIONAL COST.

8. THE FIRE ALARM SYSTEM VENDOR/CONTRACTOR SHALL TERMINATE, TEST AND PROGRAM ALL NEW FIRE ALARM

DEVICES. COORDINATE WITH COR.

9. CONNECT SPRINKLER SYSTEM SUPERVISORY DEVICES TO THE FIRE ALARM SYSTEM. COORDINATE LOCATION WITH

THE SPRINKLER CONTRACTOR.

GENERAL FIRE ALARM NOTES

FIRE ALARM RISER NOTES:

A. FIRE ALARM SYSTEM SHALL BE INTERCONNECTED WITH

ACCESS CONTROL SYSTEM TO ALLOW EGRESS DURING

ALARM CONDITIONS. COORDINATE BETWEEN ACCESS

CONTROL SYSTEM AND FIRE ALARM SYSTEM

MANUFACTURERS.

B. ALL FIRE ALARM WIRING SHALL BE IN FACTORY PAINTED

"RED" EMT CONDUIT.

C. ALL WIRING SHALL BE AS RECOMMENDED BY

MANUFACTURER.

D. PROVIDE POWER SUPPLY AND/OR NAC (NOTIFICATION

APPLIANCE CIRCUIT) PANEL AS REQUIRED FOR ADDITIONAL

DEVICES.

E. THE NEW FIRE ALARM SYSTEM SHALL MATCH THE EXISTING

SIMPLEX

FIRE ALARM SYSTEM.

TO EXISTING

CORRIDOR

INDICATING

APPLIANCES

F F F

GENERAL ELECTRICAL DEMOLITION NOTES

A. RETURN REMOVED MATERIAL DEEMED SALVAGEABLE BY OWNER'S REPRESENTATIVE. MATERIALS DEEMED NOT SALVAGEABLE SHALL BE REMOVED FROM THE PREMISES.

B. THE CONTRACTOR WILL BE HELD TO HAVE EXAMINED THE PREMISES AND SATISFIED HIMSELF AS TO EXISTING CONDITIONS UNDER WHICH HE WILL BE OBLIGED TO PERFORM HIS WORK. THE DRAWINGS ARE GENERALLY DIAGRAMMATIC AND THE CONTRACTOR SHALL HARMONIZE HIS WORK SO THAT EACH PIECE OF EQUIPMENT WILL BE INSTALLED AS TO FUNCTION PROPERLY. THE

CONTRACTOR SHALL COOPERATE WITH OTHER TRADES.

C. REMOVE ALL EXISTING WIRING DEVICES, LIGHT FIXTURES, WIRE, CONDUIT, ETC., AS NOTED OR INDICATED WITHIN DEMOLITION AREA. (ALL ITEMS MAY NOT BE SHOWN). REWORK AS

NECESSARY CIRCUITING WHICH REQUIRES CONTINUATION THROUGH THE AREA.

D. ELECTRICAL CONTRACTOR TO PROVIDE ALL NECESSARY LABOR, CONDUIT, WIRE, CONNECTIONS, ETC., FOR DEVICES, FIXTURES, ETC., NOTED AS "EXISTING TO REMAIN" SUCH THAT EXISTING

CIRCUIT CONTINUITY IS MAINTAINED.

E. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WORK REQUIRED TO REMOVE/RELOCATE ANY EXISTING ELECTRICAL EQUIPMENT SUCH THAT ELECTRIC SHOCK HAZARDS TO

WORKMEN ARE ELIMINATED DURING DEMOLITION AND NEW CONSTRUCTION.

F. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WORK IN REMOVING AND REPLACING "EXISTING TO REMAIN" FIXTURES, DEVICES, ETC., AS REQUIRED SO THAT THESE DEVICES ARE NOT DAMAGED DURING DEMOLITION. RELOCATED TO NEAREST APPROPRIATE LOCATION TO AVOID CONFLICTS WITH OTHER TRADES' WORK. REPLACE WITH NEW ANY "EXISTING TO REMAIN"

FIXTURE, DEVICE, ETC., NOT DEEMED SALVAGEABLE BY OWNER'S REPRESENTATIVE.

G. REMOVED OR DAMAGED CONDUIT, WIRE, AND FITTINGS SHALL NOT BE REUSED FOR RELOCATED OR NEW DEVICES.

H. MAKE AS-BUILTS WITH NEW TYPED DIRECTORIES FOR ALL PANELBOARDS, INDICATING CIRCUIT DESCRIPTION (USED OR SPARE), CIRCUIT BREAKERS AND CIRCUIT LOAD.

I. WORK REQUIRED FOR EXISTING EQUIPMENT NOTED AS "EXISTING TO BE REMOVED" SHALL INCLUDE:

A. REMOVAL OF FEEDER FROM EQUIPMENT TO POINT OF FEED.

B. REMOVAL OR RE-CIRCUITING OF ALL BRANCH CIRCUITING.

C. REMOVAL OF ALL FITTINGS, SUPPORTS, BRACKETS, ETC.

D. PATCHING OF WALLS, FLOORS AND CEILINGS PER ARCHITECT'S INSTRUCTIONS.

E. CAPPING OF FEEDER CONDUIT AT 6" ABOVE OR BELOW FLOOR/CEILING AS REQUIRED AND MARKING LOCATION OF POINT OF FEED WITH AN ENGRAVED BRASS TAG.

F. REMOVAL OF FEEDER CONDUIT IF FOUND TO BE UNSALVAGEABLE BY ARCHITECT, ENGINEER OR OWNER'S REPRESENTATIVE.

J. EXISTING EQUIPMENT NOT IMPLICITLY SHOWN ON THE DRAWINGS IS INTENDED TO BE "EXISTING TO REMAIN UNCHANGED", UNLESS NOTED OTHERWISE.

GENERAL ELECTRICAL REMODELING NOTES

A. PRIOR TO SUBMITTING PROPOSAL, BIDDER SHALL EXAMINE ALL GENERAL CONSTRUCTION DRAWINGS. BIDDER SHALL BE FAMILIAR WITH THE EXISTING CONDITIONS UNDER WHICH BIDDER WILL HAVE TO OPERATE AND WHICH WILL IN ANY WAY AFFECT THE WORK UNDER THIS CONTRACT. NO SUBSEQUENT ALLOWANCE WILL BE MADE IN THIS CONNECTION IN BEHALF OF THE

CONTRACTOR FOR ANY ERROR OR NEGLIGENCE ON HIS PART.

B. CERTAIN REMODELING OF ELECTRICAL FACILITIES WILL BE REQUIRED IN THE EXISTING BUILDING. EXISTING CONDUIT RUNS ARE GENERALLY NOT SHOWN. ALTHOUGH A FULL ATTEMPT HAS BEEN MADE TO SHOW SOME EXISTING CONDITIONS, OF WHICH INFORMATION HAS BEEN TAKEN FROM EXISTING RECORD DRAWINGS OF THIS PROJECT. THE DRAWINGS SHOWING LOCATION OF EXISTING EQUIPMENT, OUTLETS, FIXTURES, ETC., IN EXISTING AREAS ARE APPROXIMATE ONLY (FIELD VERIFY).

C. BRANCH CIRCUITS SHALL BE REUSED WHERE PRACTICAL AND SHALL, IN ADDITION, BE REMODELED AS REQUIRED. THE CONTRACTOR SHALL CONCEAL ALL WORK WHERE POSSIBLE.

D. EXISTING ELECTRICAL WIRING WHICH WILL NOT BE MADE OBSOLETE AND WHICH WILL BE DISTURBED DUE TO CONSTRUCTION CHANGES REQUIRED BY THIS CONTRACT SHALL BE RESTORED TO OPERATING CONDITION, AS REQUIRED AND/OR DIRECTED. WHERE REQUIRED, SHOWN AND/OR DIRECTED, OUTLETS AND CONDUIT RUNS SHALL BE RELOCATED. IN SOME CASES IT MAY BE NECESSARY TO EXTEND CONDUITS AND PULL IN NEW WIRING OR INSTALL JUNCTION BOXES AND SPLICE IN NEW WIRING OR REPLACE OLD WIRING WITH NEW.

E. OUTLETS FROM WHICH FIXTURES, SWITCHES, RECEPTACLES, AND/OR OTHER ELECTRICAL DEVICES ARE MOVED AND WHICH ARE NOT REPLACED OR REUSED SHALL BE REMOVED OR, IF IT IS NOT POSSIBLE TO REMOVE, PLACE A BLANK COVER ON THE OUTLET BOX. WHERE OUTLETS, BOXES, ETC., ARE COMPLETELY REMOVED, THE CONTRACTOR SHALL CUT OFF CONDUITS AND

REMOVE WIRING.

F. WHERE EXISTING LIGHT FIXTURES ARE TO BE REUSED, THE ELECTRICAL CONTRACTOR SHALL CLEAN AND REPLACE LAMPS, REPAIR OR REPLACE DEFECTIVE PARTS, LENS, BALLAST, ETC. AS

REQUIRED.

G. WHERE CONDUITS EXTENDING THROUGH FLOORS ARE TO BE ABANDONED, THE CONTRACTOR SHALL CUT AND CAP OR PLUG CONDUIT, THAT IT WILL NOT PROTRUDE ABOVE THE FLOOR.

H. WHERE EXISTING CONDUIT IS TO BE ABANDONED, THE CONDUIT SHALL BE REMOVED IF IT IS EXPOSED, IN A CRAWL SPACE OR IN AN ACCESSIBLE CEILING. WHERE IT IS IMPOSSIBLE TO

REMOVE THE CONDUIT, IT SHALL BE CUT OFF AND CAPPED OR PLUGGED.

I. THE CONTRACTOR SHALL BE HELD FULLY RESPONSIBLE FOR THE PROPER RESTORATION OF ALL EXISTING SURFACES REQUIRED PATCHING, PLASTERING, PAINTING AND/OR OTHER REPAIR DUE TO THE INSTALLATION OF ELECTRICAL WORK UNDER THE TERMS OF THIS SPECIFICATION. CLOSE ALL OPENINGS, REPAIR ALL SURFACES, ETC., AS REQUIRED. THE CONTRACTOR SHALL EMPLOY QUALIFIED AND EXPERIENCED WORKMEN FOR THIS WORK. ALL RESTORATION WORK SHALL BE SUBJECT TO THE APPROVAL OF THE ARCHITECT AND/OR THE OWNER.

J. ALL TEMPORARY AND REMODELING WORK SHALL BE CONSIDERED A PART OF THIS CONTRACT AND NO EXTRA CHARGES WILL BE ALLOWED. THIS SHALL INCLUDE MINOR ITEMS OF MATERIAL

OR EQUIPMENT NECESSARY TO MEET THE REQUIREMENTS AND INTENT OF THE PROJECT.

K. EXAMINE ARCHITECTURAL, STRUCTURAL, AND MECHANICAL DRAWINGS AND SPECIFICATIONS TO DETERMINE THE SEQUENCE OF CONSTRUCTION THROUGHOUT THE PROJECT, INCLUDING

EXISTING, TEMPORARY, REMODELED AND NEW AREAS.

L. ALL ELECTRICAL CONNECTIONS REQUIRING AN OUTAGE SHALL BE MADE DURING AN APPROVED TIME LIMIT. CHANGEOVERS SHALL BE AS SHORT A DURATION AS POSSIBLE AND SHALL NOT INTERFERE WITH NORMAL OPERATION OF THE OWNER'S FACILITIES. NOTICE SHALL BE REQUIRED IN ADVANCE OF A SHUTDOWN OF ANY ELECTRICAL CIRCUIT FOR CHANGEOVER, AND SUCH A CHANGEOVER SHALL BE DONE DURING HOURS AS DIRECTED BY OWNER. WORK SHALL BE SCHEDULED SO THAT AT NO TIME WILL ANY EMERGENCY FEEDER, CIRCUIT, OR FIRE ALARM ZONE BE OUT OF SERVICE. PROVIDE NECESSARY TEMPORARY FEEDERS TO ACCOMPLISH THIS REQUIREMENT.

M. EXISTING LOW VOLTAGE WIRING WHICH WILL NOT BE MADE OBSOLETE AND WHICH WILL BE DISTURBED DUE TO CONSTRUCTION CHANGES REQUIRED BY THIS CONTRACT SHALL BE RESTORED TO CONDITION, OR POSITION, AS REQUIRED. PROPERLY RE-SECURE CABLE IN CHASES, CRAWL SPACES, TUNNELS, AND CEILING SPACES AS REQUIRED BY NEC. IN SOME CASES IT

MAY BE NECESSARY TO ADD SUPPORTING HARDWARE TO ACCOMPLISH THIS REQUIREMENT.

N. IF POSSIBLE, ALL NEWLY INSTALLED RECEPTACLES SHALL BE INSTALLED IN SEPARATE OR ADJACENT STUD SPACES, TO AVOID SOUND TRANSMISSION AND WALL INTEGRITY ISSUES. ALL NEWLY INSTALLED RECEPTACLES LOCATED IN COMMON STUD SPACES OF FIRE-RESISTANT WALLS SHALL BE EQUIPPED WITH FIRE-RESISTANT PUTTY PADS AT THE BACK OF EACH BOX IN

ACCORDANCE WITH NEC 300.21.

Engineers Architects

Revisions: Date

Drawing Title

Approved:

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

NOT FOR

CONSTRUCTIO

N

NOT FOR

CONSTRUCTIO

N

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

/2 /2

:4

:1

P M

E-001

ELECTRICAL GENERAL NOTES,

SYMBOL LEGENDS, AND

ABBREVIATIONS

1 5JDM

SPS EQUIPMENT

INSTALLATION

DURHAM VA MEDICAL CENTER

508 FULTON ST.

DURHAM, NC 27705 OCTOBER 23, 2020

CONSTRUCTION DOCUMENTS

558-19-30219-181

JAV

TYPE DESCRIPTION MOUNTING LAMP VOLTAGE MANUFACTURER MODEL NUMBER

A EXISTING 2' X 4'

LENSED FLUORESCENT

TROFFER;

RECESSED

GRID

3-LAMP 277.00 V - WHERE NOTED (F), THE ELECTRICAL CONTRACTOR SHALL PROVIDE

DRYWALL FLANGE KIT COMPATIBLE WITH EXISTING GRID-MOUNTED

LUMINAIRE. BASIS OF DESIGN: LSI FK-24, FIXTURE CONVERSION KIT.

B EXISTING 2' X 4'

LENSED FLUORESCENT

TROFFER;

RECESSED

GRID

2-LAMP 277.00 V - -

Scale: N.T.S.

FIRE ALARM RISER

48"

GFI

" A

C G

FI

S

AC

GFI

30"30"30"

30"

GFI

30"

GFI

A C

G

FI

30"

G

FI

AC

GFI

F

S

FS

40"

S

4 A

C DO

DO

48"

GFI

48"

GFI

S

F

S

D D

48"

GFI

48"

GFI

48"

GFI

48"

GFI

48"

GFI

GFI

48"

GFI

48"

GFI

48"

GFI

48"

GFI

J

J

F

S

FS

S

48"

48"

48"

48"

48" 48"

GFI

48"

48"

48"

48"

48"

48"

48"

48"

48"

GFI

48"

GFI

GFI

F

15 cd

F

15 cd

F15 cdW

S

F

S

S

D D

TOILET

FG314

STORAGE

FG312

ASSIST

FG311

CLERIC AL

FG309

NOURISH

FG331

PROCEDURE 3

FG313

PROCEDURE 2

FG315

SUPPLIES

FG310

PROCEDURE 4

FG308

OFFICE

FG316

PROCEDURE

FG165

GAS

FG189

OFFICE

FG172

NEW EXIT PASSAGEWAY

FG400C

CIRCULATION

FG300B

J

J

EXISTING

PANEL 'GN2'

EXISTING

PANEL 'GCR2'

EXISTING

PANEL 'GCR2A'

('GN2A'-37)

('GCR2'-16)

('GN2A'-37)

('GN2A'-35) ('GN2A'-35)

('GN2A'-35)

('GCR2'-16)('GCR2'-16) ('GN2A'-35) ('GCR2'-16)

('GCR2'-16)

('GCR2'-16)

('GCR2'-16)

('GCR2'-18)

('GCR2'-18)

('GCR2'-18) ('GCR2'-18)

('GN2A'-33)

('GCR2'-18)

('GN2A'-33)

('GN2A'-33)

TB-2.18

TB-2.17

TB-2.19

SCOPE CLEAN

FG318

SCOPES SOIL

FG319

SOIL

FG317

('GN2A'-33)

TB-2.11

TB-2.12

FAR

TOILET

FG314

STORAGE

FG312

ASSIST

FG311

CLERIC AL

FG309

NOURISH

FG331

PROCEDURE 3

FG313

PROCEDURE 2

FG315

SUPPLIES

FG310

PROCEDURE 4

FG308

OFFICE

FG316

ANTE RM

FG317

PROCEDURE

FG165

GAS

FG189

OFFICE

FG172

NEW EXIT PASSAGEWAY

FG400C

CIRCULATION

FG300B

SCOPES DECON.

FG318

SCOPES STAGING

FG319

2'GCR2'-18

'GN2A'-33

'GCR2'-16

'GCR2'-30

'GCR2'-32

'GN1A'-33

'GN2A'-37

'GN2A'-35

EXISTING

PANEL 'GN2'

EXISTING

PANEL 'GCR2'

EXISTING

PANEL 'GCR2A'

TB-2.18

TB-2.11

TB-2.12

TB-2.19

TB-2.17

FAR

Engineers Architects

## KEY NOTES:

# KEY NOTES:

Revisions: Date

Drawing Title

Approved:

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

NOT FOR

CONSTRUCTIO

N

NOT FOR

CONSTRUCTIO

N

WALL RATING LEGEND

1 HR - FIRE BARRIER

2 HR - FIRE BARRIER

SMOKE RESISTIVE HAZARDOUS AREA

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

S S S S

/2 /2

:4

:1

P M

E-101

PARTIAL GROUND FLOOR ELECTRICAL

PLANS

2 5JDM

SPS EQUIPMENT

INSTALLATION

DURHAM VA MEDICAL CENTER

508 FULTON ST.

DURHAM, NC 27705 OCTOBER 23, 2020

CONSTRUCTION DOCUMENTS

558-19-30219-181

JAV

N

KEY PLAN

SCALE: NO SCALE

AREA OF WORK

GROUND FLOOR

Scale: 1/4" = 1'-0"

GROUND FLOOR ELECTRICAL DEMOLITION PLAN

Scale: 1/4" = 1'-0"

PARTIAL GROUND FLOOR POWER PLAN 0 2 4 8

NORTH

PLAN

0 2 4 8

NORTH

PLAN

1 SEE DEMOLITION PLANS FOR EXISTING

CIRCUITS TO BE REUSED. PROVIDE

ADDITIONAL CIRCUITS FROM RESPECTIVE

PANELS AS REQUIRED.

2 (TYP) COORDINATE CONNECTIONS FOR

MEDIVATORS WITH EQUIPMENT INSTALLERS.

3 (TYP) NEW FIRE ALARM STROBE. CONNECT

TO EXISTING FIRE ALARM CIRCUIT COVERING

CORRIDOR.

4 (TYP) CONNECT NEW HEPA FILTER UNITS TO

EXISTING TERMINAL UNIT CIRCUIT 'GN2'-18.

A. ALL BRANCH CIRCUIT CONDUCTORS SHALL BE

2-12 AWG, 1-12 AWG EG IN 3/4" CONDUIT

UNLESS NOTED OTHERWISE.

B. FOR MORE INFORMATION REGARDING DATA

JACK INSTALLATION SEE DETAILS 1 & 2 ON

SHEET E-501. LABEL TECHNOLOGY JACKS PER

DETAIL 3 SHEET E-501.

C. DEMOLISH ALL EXISTING ELECTRICAL

DEVICES AS SHOWN ON DEMOLITION PLAN

UNLESS NOTED OTHERWISE.

D. CONTRACTOR SHALL BE RESPONSIBLE FOR

TRACING AND IDENTIFYING ALL CIRCUITS AND

CONDUIT THAT ORIGINATE, PASS THROUGH,

OR TERMINATE IN THE AREA OF WORK.

DEMOLISH ALL CIRCUITS THAT ARE NO

LONGER IN USE. MAINTAIN CIRCUIT

CONTINUITY TO ALL CIRCUITS WHICH ARE NOT

COMPLETELY REMOVED.

E. INSTALL ALL DEVICES AS INDICATED ON NEW

WORK PLAN. COORDINATE ALL WORK WITH

COR AND OTHER TRADES.

F. DEMOLITION SHALL INCLUDE BUT NOT BE

LIMITED TO THE DEVICES AND/OR SYSTEMS

SHOWN. COORDINATE WITH ARCHITECTURAL,

MECHANICAL, AND PLUMBING DEMOLITION

PLANS.

G. REFER TO SHEET E-102 FOR LOCATION OF

EXISTING PANELS GN2A AND GN1A.

1 PROVIDE AND INSTALL NEW JUNCTION BOXES.

DEMO CIRCUITS BACK TO JUNCTION BOXES.

RETAIN AND REUSE TO FEED NEW DEVICES.

2 (TYP.) VERIFY CIRCUITING IN FIELD.

3 (TYP.) PROTECT EXISTING CIRCUIT 'GN2'-18

FEEDING EXISTING TERMINAL UNITS.

4 THE ELECTRICAL CONTRACTOR SHALL

PROTECT THE EXISTING FIRE ALARM

NOTIFICATION DEICE DURING WALL

DEMOLITION. THE DEVICE SHALL REMAIN IN

SERVICE. SUPPORT AND SECURE THE DEVICE

UNTIL IT IS REINSTALLED.

FG234

FG231 FG232 FG233

FG201 FG400B

WAITING

OFFICE

RECEPTION

NEW EXIT

PASSAGEWAY

FG172

FG168

FG169

FG187

FG185A

FG186

FG170

FG185

G185A

G185C

G185B

G186A

FG404

FG219

FG200A

FG234

FG402

FG401

FG220

FG221

FG218

FG202FG203FG205FG207

FG215

FG217

FG216

FG214 FG208 FG204 FG230

FG223 FG227 FG229

FG224 FG226 FG228

FG231 FG232 FG233

FG206

FG225

FG213

FG200C

F G D

FG222A FG222B

F G B

FG210

FG211

FG212

FG201FG209

FG405

FG403

FG165

FG321

FG318

FG322

FG345

FG317 FG316

FG340

FG341

FG342

FG344

FG320

FG308 FG306 FG304 FG302FG315 FG313

FG332

FG323

FG312

FG319

FG324 FG325 FG326 FG327 FG328 FG329 FG334FG330 FG335 FG336 FG337 FG338

FG301FG303FG305FG307FG309FG311

FG339

FG333

FG300B

FG314

FG189

FG310

FG331

FG300D

FG300A

FG300CL

FG343A

FG343

FG400C

FG218A

FG166

FG164

FG173

FG174

FG167

FG171

FG175

SEDATION

STORAGE

TELECOM

EQUIP

CONTROL RM

WAITING

OFFICE

DATA RM

HSK

CIRCULATION

WAITING

PUBLIC TOILETS (M)

PUBLIC TOILETS(W)

STAFF T

CLEAN SUPPLIES

CLEAN UTILITY

PHOTOEXAMEXAMEXAM

LASER

EXAM

WAITING

PROCEDURES EXAM EXAM EXAM

EXAM EXAM EXAM

EXAM EXAM EXAM

FIELD PRETEST/FIT

EXAM

EXAM

LASER

CIRCULATION

C

IR

C U

LA

TI

O N

WAITING WAITING

C

IR

C U

LA

TI

O N

OFFICE

CONFERENCE

OFFICE

RECEPTIONEXAM

ELEC. RM

STAFF LOCKERS

PRESCREEN

HSK

SCOPES CLEAN

EQUIP

MECHANICAL

SOIL CLEAN

RESIDENTS

EXAMS

EXAMS

WAITING

PROCEDURE 4 PROCEDURE 5 PROCEDURE 6 PROCEDURE 7PROCEDURE 3

NURSE STATION

TOILET

STORAGE

SCOPES SOIL

RECOVERY HOLDING HOLDING HOLDING HOLDING HOLDING

P.A.PHYSICIANCHIEFCLERICALASSIST

TOILET

TOILET

CIRCULATION

TOILET

GAS

SUPPLIES

Nourish

CIRCULATION

CIRCULATION

ELEC CLOSET

LOCKER ROOM

RECEPTION

NEW EXIT PASSAGWAY

PHYSICIAN

PROCEDURE 2

PROCEDURE 1

RECOVERY RECOVERY RECOVERY RECOVERY RECOVERY RECOVERY

SOILED UTILITY

DRSG RM

EXAM RM

TOILET

WAITING

WAITING

TOILET

DRSG RM

DRSG RM

TOILET

RECEPTION

CORRIDOR

DRSG RM

E-101

EXISTING

PANEL 'GN2A'

EXISTING

PANEL 'GN1'

EXISTING

PANEL 'GN1A'

EXISTING

PANEL 'GCR1'

EXISTING

PANEL 'GEQ1'EXISTING

PANEL 'GCR1A'

EXISTING SONITROL

(SECURITY) PANEL

Engineers Architects

## KEY NOTES:

Revisions: Date

Drawing Title

Approved:

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

NOT FOR

CONSTRUCTIO

N

NOT FOR

CONSTRUCTIO

N

WALL RATING LEGEND

1 HR - FIRE BARRIER

2 HR - FIRE BARRIER

SMOKE RESISTIVE HAZARDOUS AREA

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

S S S S

/2 /2

:4

:1

P M

E-102

GROUND FLOOR OVERALL

ELECTRICAL PLAN

3 5JDM

SPS EQUIPMENT

INSTALLATION

DURHAM VA MEDICAL CENTER

508 FULTON ST.

DURHAM, NC 27705 OCTOBER 23, 2020

CONSTRUCTION DOCUMENTS

558-19-30219-181

JAV

N

KEY PLAN

SCALE: NO SCALE

AREA OF WORK

GROUND FLOOR

Scale: 1/8" = 1'-0"

GROUND FLOOR OVERALL ELECTRICAL PLAN 0 4 8 16

NORTH

PLAN

1 ELECTRICAL CLOSET FEEDING AREA OF

WORK. EXISTING PANELS AS NOTED. SEE

ENLARGEMENT THIS SHEET.

2 EXISTING TELECOM CLOSET. PULL NEW

FEEDS AS REQUIRED FROM THIS CLOSET.

OS

A

TOILET

FG314

STORAGE

FG312

ASSIST

FG311

CLERIC AL

FG309

NOURISH

FG331

PROCEDURE 3

FG313

PROCEDURE 2

FG315

SUPPLIES

FG310

PROCEDURE 4

FG308

OFFICE

FG316

PROCEDURE

FG165

GAS

FG189

OFFICE

FG172

NEW EXIT PASSAGEWAY

FG400C

CIRCULATION

FG300B

EXISTING

PANEL 'GN2'

EXISTING

PANEL 'GCR2'

EXISTING

PANEL 'GCR2A'3

('GN2'-6)

('GCR2'-5)

('GN2'-6)

('GCR2'-5)

A

SCOPE CLEAN

FG318

SCOPES SOIL

FG319

SOIL

FG317

('GCR2'-5)

B

(TYP)

A

('GN2'-6)

('GCR2'-5)

A

(TYP)

A

(TYP)

('GN2'-6)

('GCR2'-5)

('GN2'-6)

('GCR2'-5)

A A

A

TOILET

FG314

STORAGE

FG312

ASSIST

FG311

CLERIC AL

FG309

NOURISH

FG331

PROCEDURE 3

FG313

PROCEDURE 2

FG315

SUPPLIES

FG310

PROCEDURE 4

FG308

OFFICE

FG316

ANTE RM

FG317

PROCEDURE

FG165

GAS

FG189

OFFICE

FG172

NEW EXIT PASSAGEWAY

FG400C

CIRCULATION

FG300B

1 1

B

AA

SCOPES DECON.

FG318

SCOPES STAGING

FG319

EXISTING

PANEL 'GN2'

EXISTING

PANEL 'GCR2'

EXISTING

PANEL 'GCR2A'

A

A(F)

A(F) A(F)

('GCR2'-5)

('GCR2'-5)('GCR2'-5)

('GCR2'-5)('GCR2'-5)

G

C R

Engineers Architects

## KEY NOTES:

# KEY NOTES:

Revisions: Date

Drawing Title

Approved:

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

NOT FOR

CONSTRUCTIO

N

NOT FOR

CONSTRUCTIO

N

WALL RATING LEGEND

1 HR - FIRE BARRIER

2 HR - FIRE BARRIER

SMOKE RESISTIVE HAZARDOUS AREA

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

S S S S

/2 /2

:4

:2

P M

EL101

PARTIAL GROUND FLOOR LIGHTING

PLAN

4 5JDM

SPS EQUIPMENT

INSTALLATION

DURHAM VA MEDICAL CENTER

508 FULTON ST.

DURHAM, NC 27705 OCTOBER 23, 2020

CONSTRUCTION DOCUMENTS

558-19-30219-181

JAV

N

KEY PLAN

SCALE: NO SCALE

AREA OF WORK

GROUND FLOOR

0 2 4 8

NORTH

PLAN

0 2 4 8

NORTH

PLAN

Scale: 1/4" = 1'-0"

GROUND FLOOR LIGHTING DEMOLITION PLAN

Scale: 1/4" = 1'-0"

PARTIAL GROUND FLOOR LIGHTING PLAN

1 REINSTALL EXISTING LUMINAIRE.

RECONNECT TO CIRCUIT RETAINED DURING

DEMOLITION.

2 PROVIDE LINE-VOLTAGE, PASSIVE INFRARED

WALL SWITCH OCCUPANCY SENSOR. BOD:

LUTRON MAESTRO.

A. ALL BRANCH CIRCUIT CONDUCTORS SHALL BE

2-12 AWG, 1-12 AWG EG IN 3/4" CONDUIT

UNLESS NOTED OTHERWISE.

B. COORDINATE ALL TIME DELAY, AUTO DIM,

PRESET DIMMING LEVELS, SENSOR

SENSITIVITY AND CONFIGURATIONS WITH THE

VA.

C. DEMOLISH ALL EXISTING ELECTRICAL

DEVICES AS SHOWN ON DEMOLITION PLAN

UNLESS NOTED OTHERWISE.

D. CONTRACTOR SHALL BE RESPONSIBLE FOR

TRACING AND IDENTIFYING ALL CIRCUITS AND

CONDUIT THAT ORIGINATE, PASS THROUGH,

OR TERMINATE IN THE AREA OF WORK.

DEMOLISH ALL CIRCUITS THAT ARE NO

LONGER IN USE. MAINTAIN CIRCUIT

CONTINUITY TO ALL CIRCUITS WHICH ARE NOT

COMPLETELY REMOVED.

E. COORDINATE ALL WORK IMPACTING AREAS

OUTSIDE AREA OF WORK WITH COR.

F. REFERENCE LUMINAIRE SCHEDULE ON E-001

FOR MORE INFO.

G. DEMOLITION SHALL INCLUDE BUT NOT BE

LIMITED TO THE DEVICES AND/OR SYSTEMS

SHOWN. COORDINATE WITH ARCHITECTURAL,

MECHANICAL, AND PLUMBING DEMOLITION

PLANS.

1 THE ELECTRICAL CONTRACTOR SHALL REMOVE

EXISTING LUMINAIRES FOR REUSE. CRITICAL

BRANCH CIRCUIT WIRING SHALL BE RETAINED.

NORMAL BRANCH CIRCUIT WIRING SHALL BE

REMOVED BACK TO LAST OPERABLE DEVICE,

FIXTURE OR PANELBOARD.

2 DISCONNECT AND REMOVE LIGHT SWITCH.

RETAIN WIRING, DEVICE BOX AND CONDUIT

FOR REUSE.

3 DEMO 3-WAY SWITCHES. DISCONNECT AND

REMOVE DEVICES, WIRING AND CONDUIT BACK

TO EXISTING JUNCTION BOX ABOVE CEILING.

4 CIRCULATION FG300B LIGHTING IS EXISTING TO

REMAIN, NOT IN CONTRACT.

(1) 4 PR UTP

TELEPHONE

CABLE/JACK

SINGLE GANG S.S.

COVER PLATE.

LOCATIONS AS SHOWN

ON PLANS.

WALL PHONE (TYP.) ( W)

DETAIL NOTES:

A. ALL EQUIPMENT AND INSTALLATION SHALL BE APPROVED BY VAMC IT DEPARTMENT.

(1) 4 PR UTP

DATA

CABLE/JACK

(1) 4 PR UTP

TELEPHONE

CABLE/JACK

1/2" HIGH BLACK LETTERS

ON CLEAR BACKGROUND,

PANDUIT OR EQUAL ON

PERMANENT LABEL,

TYPICAL.

XXX

XXX

B B

T T

BLANK

SINGLE GANG COVER

PLATE WITH 6 OUTLETS

(TYPICAL). LOCATIONS

AS SHOWN ON PLANS

TELE/DATA (TYP.) ( 4)

(1) 4 PR UTP

TELEPHONE

CABLE/JACK

C C

(1) 4 PR UTP

DATA CABLE/JACK

BLANK

(1) 4 PR UTP

DATA

CABLE/JACK

(1) 4 PR UTP

TELEPHONE

CABLE/JACK

1/2" HIGH BLACK LETTERS

ON CLEAR BACKGROUND,

PANDUIT OR EQUAL ON

PERMANENT LABEL,

TYPICAL.

XXX

XXX

B B

T B

BLANK

SINGLE GANG COVER

PLATE WITH 6 OUTLETS

(TYPICAL). LOCATIONS

AS SHOWN ON PLANS

TELE/DATA (TYP.) ( 2)

BLANK

C B

BLANK

BLANK

T

FINISHED FLOOR

MOUNTING HEIGHT AS

SHOWN IN DRAWINGS

4-11/16" SQ. BY 2-1/2"

DEEP BOX WITH SINGLE

GANG 5/8" TILE RING.

1-1/4" CONDUIT WITH

COMMUNICATIONS WIRING

WALL

CORRIDORROOM

6" MIN NYLON BUSHING

COORDINATE WITH DUCTWORK

EXTEND CONDUIT TO ABOVE

FINISHED ACCESSABLE

CEILING IN CORRIDOR TO

CABLE TRAY UNLESS NOTED

OTHERWISE.

SUSPENDED LAY-IN

CEILING

CABLE TRAY

Example: B01 F2 IT102 B A 02

BLDG # (IF APPLICABLE)

FLOOR # (IF APPLICABLE)

IT CLOSET #

IT CLOSET LOCATION (UNIT B)

PATCH PANEL #

PORT #

EXISTING PANEL

'GCR2'

120/208V

3PH, 4W

225A MLO

CRITICAL

EXISTING PANEL

'GN1A'

120/208V

3PH, 4W

225A MLO

NORMAL

EXISTING PANEL

'GN2A'

120/208V

3PH, 4W

225A MLO

NORMAL

EXISTING PANEL

'GN1'

120/208V

3PH, 4W

400A MCB

NORMAL

EXISTING PANEL

'GN2'

120/208V

3PH, 4W

225A MLO

NORMAL

EXISTING PANEL

'GCR2A'

120/208V

3PH, 4W

225A MLO

CRITICAL

EXISTING PANEL

'GCR1'

120/208V

3PH, 4W

225A MCB

CRITICAL

3-3 AWG, 1-3 AWG

NEUTRAL, 1-8 AWG

EGC IN 1 1/4" C. (EX)

3-3 AWG, 1-3 AWG

NEUTRAL, 1-8 AWG

EGC IN 1 1/4" C. (EX)

3-1/0 AWG, 1-1/0 AWG

NEUTRAL, 1-6 AWG

EGC IN 2" C. (EX)

150A

150A

100A

225A

100A 100A

400A

Engineers Architects

Revisions: Date

Drawing Title

Approved:

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

NOT FOR

CONSTRUCTIO

N

NOT FOR

CONSTRUCTIO

N

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

/2 /2

:4

:1

P M

E-501

ELECTRICAL DETAILS

5 5JDM

SPS EQUIPMENT

INSTALLATION

DURHAM VA MEDICAL CENTER

508 FULTON ST.

DURHAM, NC 27705 OCTOBER 23, 2020

CONSTRUCTION DOCUMENTS

558-19-30219-181

JAV

Scale: N.T.S.

TELECOMMUNICATIONS FACEPLATES

Scale: N.T.S.

TELECOMMUNICATIONS OUTLET INSTALLATION

Scale: N.T.S.

JACK LABELING SCHEME

EX (GCR2)

(TOTAL KVA) X 1000 = TOTAL AMPS

VOLTS X 1.732 71

PANEL / FEEDER (TOTAL KVA) 25.54

TOTAL DEMAND AMPERES PER PHASE 72 74 67

TOTAL KVA PER PHASE 9.72 10.67 10.17 8.67 8.84 8.03

SIGN 0.00 0.00 0.00 125% 0.00 0.00 0.00

DEDICATED 4.68 4.14 3.78 65% 3.04 2.69 2.46

NEUTRAL RATING 100% FIX. ELEC. SPACE HEAT 0.00 0.00 0.00 100% 0.00 0.00 0.00

BUS RATING 225A WATER HEATERS 0.08 0.00 0.00 125% 0.10 0.00 0.00

MCB RATING MLO ALL OTHERS 0.08 1.69 1.77 65% 0.05 1.10 1.15

MINIMUM AIC (K AMPS) 22 MOTORS AND

EQUIPMENT

LARGEST 0.00 0.00 0.00 125% 0.00 0.00 0.00

SERVICE ENTR. RATED YES X NO >10KVA@50% -0.13 0.11 0.35

MAIN CIRCUIT BREAKER YES X NO GENERAL USE

RECEPT

3.06 3.56 4.02

<=10 KVA@100% 3.33 3.33 3.33

ISOLATED GROUND BUS YES X NO GENERAL LIGHTING 1.82 1.28 0.60 125% 2.28 1.60 0.75

MOUNTING SURFACE A B C A B C

C/B TEMP. 75 C. RATING 120 208 V 3 PH 4 WIRE

LOAD TYPE

CONNECTED KVA NEC DEM

FACTOR

DEMAND KVA

10.84 10.67 11.37 TOTAL

SUB TOTAL 8.30 6.86 6.18 2.54 3.81 5.19 SUB TOTAL

--- --- 3.78 41 42 --- --- 1.69

(EX) GCR2A --- 4.14 --- 3P-100 39 40

2P-25

--- 1.69 --- CU-2

4.68 --- --- 37 38 0.08 --- ---

(EX)RECEPT --- --- 0.18 1P-20 35 36

2P-15

--- --- 0.08 DSU-2

(EX)RECEPT --- 0.18 --- 1P-20 33 34 1P-20 --- 0.00 --- SPARE

(EX)RECEPT 0.54 --- --- 1P-20 31 32 1P-20 1.20 --- --- MEDIVATOR FG318

(EX)RECEPT --- --- 0.36 1P-20 29 30 1P-20 --- --- 1.20 MEDIVATOR FG318

(EX)RECEPT --- 0.18 --- 1P-20 27 28 1P-20 --- 0.50 --- (EX) NURSE CALL SYST

(EX)RECEPT 0.18 --- --- 1P-20 25 26 1P-20 0.18 --- --- (EX)RECEPT

(EX)RECEPT --- --- 0.18 1P-20 23 24 1P-20 --- --- 0.72 (EX)RECEPT

(EX)RECEPT --- 0.18 --- 1P-20 21 22 1P-20 --- 0.72 --- (EX)RECEPT

(EX)RECEPT 0.18 --- --- 1P-20 19 20 1P-20 0.18 --- --- (EX)RECEPT

(EX)RECEPT --- --- 0.18 1P-20 17 18 1P-20 --- --- 0.60 RECEPT GI SCOPE FG319

(EX)RECEPT --- 0.18 --- 1P-20 15 16 1P-20 --- 0.54 --- RECEPT GI SCOPE FG318

(EX)RECEPT 0.90 --- --- 1P-20 13 14 1P-20 0.54 --- --- (EX)RECEPT

(EX)RECEPT --- --- 0.90 1P-20 11 12 1P-20 --- --- 0.72 (EX)RECEPT

(EX)RECEPT --- 0.72 --- 1P-20 9 10 1P-20 --- 0.18 --- (EX)RECEPT

(EX) LTG 0.38 --- --- 1P-20 7 8 1P-20 0.18 --- --- (EX)RECEPT

LTG FG317, FG318, FG319 --- --- 0.60 1P-20 5 6 1P-20 --- --- 0.18 (EX)RECEPT

(EX) LTG --- 1.28 --- 1P-20 3 4 1P-20 --- 0.18 --- (EX)RECEPT

(EX) LTG 1.44 --- --- 1P-20 1 2 1P-20 0.18 --- --- (EX)RECEPT

A B C A B C

LOAD SERVED

KVA / Phase

CKT

BRKR

CKT

NO

NEUTRAL

A B C

CKT

NO

CKT

BRKR

KVA / Phase

LOAD SERVED

EX (GN1A)

(TOTAL KVA) X 1000 = TOTAL AMPS

VOLTS X 1.732 53

PANEL / FEEDER (TOTAL KVA) 19.00

TOTAL DEMAND AMPERES PER PHASE 61 50 47

TOTAL KVA PER PHASE 8.26 7.00 6.38 7.37 6.01 5.62

SIGN 0.00 0.00 0.00 125% 0.00 0.00 0.00

DEDICATED 0.00 0.00 0.00 65% 0.00 0.00 0.00

NEUTRAL RATING 100% FIX. ELEC. SPACE HEAT 0.00 0.00 0.00 100% 0.00 0.00 0.00

BUS RATING 225A WATER HEATERS 0.00 0.00 0.00 125% 0.00 0.00 0.00

MCB RATING MLO ALL OTHERS 1.50 2.00 1.50 65% 0.98 1.30 0.98

MINIMUM AIC (K AMPS) 22 MOTORS AND

EQUIPMENT

LARGEST 0.00 0.00 0.00 125% 0.00 0.00 0.00

SERVICE ENTR. RATED YES X NO >10KVA@50% 0.82 0.48 0.42

MAIN CIRCUIT BREAKER YES X NO GENERAL USE

RECEPT

4.96 4.28 4.16

<=10 KVA@100% 3.33 3.33 3.33

ISOLATED GROUND BUS YES X NO GENERAL LIGHTING 1.80 0.72 0.72 125% 2.25 0.90 0.90

MOUNTING SURFACE A B C A B C

C/B TEMP. 75 C. RATING 120 208 V 3 PH 4 WIRE

LOAD TYPE

CONNECTED KVA NEC DEM

FACTOR

DEMAND KVA

7.06 7.48 5.66 TOTAL

SUB TOTAL 3.96 4.76 2.88 3.10 2.72 2.78 SUB TOTAL

SPARE --- --- 0.00 1P-20 41 42 1P-20 --- --- 0.00 SPARE

SPARE --- 0.00 --- 1P-20 39 40 1P-20 --- 0.00 --- SPARE

SPARE 0.00 --- --- 1P-20 37 38 1P-20 0.00 --- --- SPARE

SPARE --- --- 0.00 1P-20 35 36 1P-20 --- --- 0.00 SPARE

MEDIVATOR --- 1.20 --- 1P-20 33 34 1P-20 --- 0.00 --- SPARE

SPARE 0.00 --- --- 1P-20 31 32 1P-20 0.00 --- --- SPARE

SPARE --- --- 0.00 1P-20 29 30 1P-20 --- --- 0.00 SPARE

(EX)MAG LOCKS --- 0.50 --- 1P-20 27 28 1P-20 --- 0.50 --- (EX)AUTO DOORS

(EX)RECEPT 0.72 --- --- 1P-20 25 26 1P-20 0.50 --- --- AUTO DOORS

(EX)RECEPT --- --- 0.72 1P-20 23 24 1P-20 --- --- 0.50 AUTO DOORS

(EX)RECEPT --- 0.90 --- 1P-20 21 22 1P-20 --- 0.50 --- (EX)AUTO DOORS

(EX)RECEPT 0.72 --- --- 1P-20 19 20 1P-20 0.50 --- --- (EX)AUTO DOORS

(EX)RECEPT --- --- 0.72 1P-20 17 18 1P-20 --- --- 0.50 (EX)AUTO DOORS

(EX)RECEPT --- 0.72 --- 1P-20 15 16 1P-20 --- 0.50 --- (EX)AUTO DOORS

(EX)RECEPT 0.72 --- --- 1P-20 13 14 1P-20 0.50 --- --- (EX)AUTO DOORS

(EX)RECEPT --- --- 0.72 1P-20 11 12 1P-20 --- --- 0.50 (EX)AUTO DOORS

(EX)RECEPT --- 0.72 --- 1P-20 9 10 1P-20 --- 0.50 --- (EX)AUTO DOORS

(EX)RECEPT 0.72 --- --- 1P-20 7 8 1P-20 1.00 --- --- (EX)DOOR HOLDERS

(EX)RECEPT --- --- 0.72 1P-20 5 6 1P-20 --- --- 1.28 (EX)RECEPT

(EX)RECEPT --- 0.72 --- 1P-20 3 4 1P-20 --- 0.72 --- (EX)RECEPT

(EX)RECEPT 1.08 --- --- 1P-20 1 2 1P-20 0.60 --- --- (EX)VAV BOXES

A B C A B C

LOAD SERVED

KVA / Phase

CKT

BRKR

CKT

NO

NEUTRAL

A B C

CKT

NO

CKT

BRKR

KVA / Phase

LOAD SERVED

EX (GN2A)

(TOTAL KVA) X 1000 = TOTAL AMPS

VOLTS X 1.732 47

PANEL / FEEDER (TOTAL KVA) 16.78

TOTAL DEMAND AMPERES PER PHASE 51 38 52

TOTAL KVA PER PHASE 8.44 5.66 9.00 6.07 4.52 6.19

SIGN 0.00 0.00 0.00 125% 0.00 0.00 0.00

DEDICATED 1.20 0.18 0.18 65% 0.78 0.12 0.12

NEUTRAL RATING 100% FIX. ELEC. SPACE HEAT 0.00 0.00 0.00 100% 0.00 0.00 0.00

BUS RATING 225A WATER HEATERS 0.00 0.00 0.00 125% 0.00 0.00 0.00

MCB RATING MLO ALL OTHERS 0.00 0.00 0.00 65% 0.00 0.00 0.00

MINIMUM AIC (K AMPS) 22 MOTORS AND

EQUIPMENT

LARGEST 0.00 0.00 0.00 125% 0.00 0.00 0.00

SERVICE ENTR. RATED YES X NO >10KVA@50% 1.96 1.08 2.75

MAIN CIRCUIT BREAKER YES X NO GENERAL USE

RECEPT

7.24 5.48 8.82

<=10 KVA@100% 3.33 3.33 3.33

ISOLATED GROUND BUS YES X NO GENERAL LIGHTING 0.00 0.00 0.00 125% 0.00 0.00 0.00

MOUNTING SURFACE A B C A B C

C/B TEMP. 75 C. RATING 120 208 V 3 PH 4 WIRE

LOAD TYPE

CONNECTED KVA NEC DEM

FACTOR

DEMAND KVA

7.24 5.48 8.82 TOTAL

SUB TOTAL 3.18 1.88 4.22 4.06 3.60 4.60 SUB TOTAL

(EX)CONTROLS --- --- 0.18 1P-20 41 42 1P-20 --- --- 1.00 (EX)MAG LOCKS

(EX)CONTROLS --- 0.18 --- 1P-20 39 40 1P-20 --- 0.54 --- (EX)RECEPT

RECEPT FG317, FG316, FG314 1.20 --- --- 1P-20 37 38 1P-20 0.54 --- --- (EX)RECEPT

RECEPT FG318 --- --- 1.70 1P-20 35 36 1P-20 --- --- 0.54 (EX)RECEPT

RECEPT FG319 --- 0.80 --- 1P-20 33 34 1P-20 --- 0.54 --- (EX)RECEPT

(EX)RECEPT 0.72 --- --- 1P-20 31 32 1P-20 0.54 --- --- (EX)RECEPT

(EX)RECEPT --- --- 1.26 1P-20 29 30 1P-20 --- --- 0.54 (EX)RECEPT

(EX)RECEPT --- 0.18 --- 1P-20 27 28 1P-20 --- 0.54 --- (EX)RECEPT

(EX)RECEPT 0.18 --- --- 1P-20 25 26 1P-20 0.54 --- --- (EX)RECEPT

(EX)RECEPT --- --- 0.18 1P-20 23 24 1P-20 --- --- 0.54 (EX)RECEPT

(EX)RECEPT --- 0.18 --- 1P-20 21 22 1P-20 --- 0.54 --- (EX)RECEPT

(EX)RECEPT 0.18 --- --- 1P-20 19 20 1P-20 1.00 --- --- (EX)RECEPT

(EX)RECEPT --- --- 0.18 1P-20 17 18 1P-20 --- --- 0.54 (EX)RECEPT

(EX)RECEPT --- 0.18 --- 1P-20 15 16 1P-20 --- 0.54 --- (EX)RECEPT

(EX)RECEPT 0.54 --- --- 1P-20 13 14 1P-20 0.54 --- --- (EX)RECEPT

(EX)RECEPT --- --- 0.54 1P-20 11 12 1P-20 --- --- 0.72 (EX)RECEPT

(EX)RECEPT --- 0.18 --- 1P-20 9 10 1P-20 --- 0.54 --- (EX)RECEPT

(EX)RECEPT 0.18 --- --- 1P-20 7 8 1P-20 0.54 --- --- (EX)RECEPT

(EX)RECEPT --- --- 0.18 1P-20 5 6 1P-20 --- --- 0.72 (EX)RECEPT

(EX)RECEPT --- 0.18 --- 1P-20 3 4 1P-20 --- 0.36 --- (EX)RECEPT

(EX)RECEPT 0.18 --- --- 1P-20 1 2 1P-20 0.36 --- --- (EX)RECEPT

A B C A B C

LOAD SERVED

KVA / Phase

CKT

BRKR

CKT

NO

NEUTRAL

A B C

CKT

NO

CKT

BRKR

KVA / Phase

LOAD SERVED

Scale: No Scale

PARTIAL SINGLE LINE DIAGRAM

EX (GN2)

(TOTAL KVA) X 1000 = TOTAL AMPS

VOLTS X 1.732 118

PANEL / FEEDER (TOTAL KVA) 42.50

TOTAL DEMAND AMPERES PER PHASE 122 106 126

TOTAL KVA PER PHASE 24.04 20.77 25.16 14.59 12.73 15.17

SIGN 0.00 0.00 0.00 125% 0.00 0.00 0.00

DEDICATED 6.07 4.52 6.19 65% 3.94 2.94 4.02

NEUTRAL RATING 100% FIX. ELEC. SPACE HEAT 0.00 0.00 0.00 100% 0.00 0.00 0.00

BUS RATING 225A WATER HEATERS 0.00 0.00 0.00 125% 0.00 0.00 0.00

MCB RATING MLO ALL OTHERS 0.00 0.00 0.00 65% 0.00 0.00 0.00

MINIMUM AIC (K AMPS) 22 MOTORS AND

EQUIPMENT

LARGEST 0.00 0.00 0.00 125% 0.00 0.00 0.00

SERVICE ENTR. RATED YES X NO >10KVA@50% 7.32 6.46 7.82

MAIN CIRCUIT BREAKER YES X NO GENERAL USE

RECEPT

17.97 16.25 18.96

<=10 KVA@100% 3.33 3.33 3.33

ISOLATED GROUND BUS YES X NO GENERAL LIGHTING 0.00 0.00 0.00 125% 0.00 0.00 0.00

MOUNTING SURFACE A B C A B C

C/B TEMP. 75 C. RATING 120 208 V 3 PH 4 WIRE

LOAD TYPE

CONNECTED KVA NEC DEM

FACTOR

DEMAND KVA

17.97 16.25 18.96 TOTAL

SUB TOTAL 10.49 9.30 10.47 7.49 6.95 8.49 SUB TOTAL

--- --- 6.19 41 42 1P-20 --- --- 1.44 (EX)RECEPT

--- 4.52 --- 39 40 1P-20 --- 1.44 --- (EX)RECEPTPANEL "GN2A"

6.07 --- ---

3P-100

37 38 1P-20 1.44 --- --- (EX)RECEPT

(EX)RECEPT --- --- 0.54 1P-20 35 36 1P-20 --- --- 1.08 (EX)RECEPT

(EX)MAGLOCKS --- 1.00 --- 1P-20 33 34 1P-20 --- 0.90 --- (EX)RECEPT

SPARE 0.00 --- --- 1P-20 31 32 1P-20 0.72 --- --- (EX)RECEPT

SPARE --- --- 0.00 1P-20 29 30 1P-20 --- --- 1.44 (EX)RECEPT

SPARE --- 0.00 --- 1P-20 27 28 1P-20 --- 1.44 --- (EX)RECEPT

SPARE 0.00 --- --- 1P-20 25 26 1P-20 1.44 --- --- (EX)RECEPT

(EX)MAGLOCKS --- --- 0.50 1P-20 23 24 1P-20 --- --- 0.80 (EX)VAV BOXES

(EX)RECEPT --- 0.36 --- 1P-20 21 22 1P-20 --- 0.80 --- (EX)VAV BOXES

(EX)DOOR HOLDERS 1.00 --- --- 1P-20 19 20 1P-20 0.80 --- --- (EX)VAV BOXES

(EX)RECEPT --- --- 0.90 1P-20 17 18 1P-20 --- --- 0.80 (EX)VAV BOXES

(EX)RECEPT --- 1.62 --- 1P-20 15 16 1P-20 --- 0.80 --- (EX)VAV BOXES

(EX)RECEPT 1.44 --- --- 1P-20 13 14 1P-20 0.36 --- --- (EX)ROOFTOP RECEPT

(EX)RECEPT --- --- 1.08 1P-20 11 12 1P-20 --- --- 1.40 (EX)EF-1, EF-3

(EX)RECEPT --- 0.90 --- 1P-20 9 10 1P-20 --- 1.57 --- (EX)LIGHTS

(EX)RECEPT 1.08 --- --- 1P-20 7 8 1P-20 1.34 --- --- (EX)LIGHTS

(EX)RECEPT --- --- 1.26 1P-20 5 6 1P-20 --- --- 1.54 (EX)LIGHTS

(EX)RECEPT --- 0.90 --- 1P-20 3 4 1P-20 --- 1,41 --- (EX)LIGHTS

(EX)RECEPT 0.90 --- --- 1P-20 1 2 1P-20 1.39 --- --- (EX)LIGHTS

A B C A B C

LOAD SERVED

KVA / Phase

CKT

BRKR

CKT

NO

NEUTRAL

A B C

CKT

NO

CKT

BRKR

KVA / Phase

LOAD SERVED

EX (GCR1)

(TOTAL KVA) X 1000 = TOTAL AMPS

VOLTS X 1.732 178

PANEL / FEEDER (TOTAL KVA) 64.10

TOTAL DEMAND AMPERES PER PHASE 259 130 145

TOTAL KVA PER PHASE 34.87 21.74 24.70 31.02 15.66 17.42

SIGN 0.00 0.00 0.00 125% 0.00 0.00 0.00

DEDICATED 9.64 10.67 10.81 65% 6.27 6.94 7.03

NEUTRAL RATING 100% FIX. ELEC. SPACE HEAT 0.00 0.00 0.00 100% 0.00 0.00 0.00

BUS RATING 225A WATER HEATERS 10.56 0.00 0.00 125% 13.20 0.00 0.00

MCB RATING 225A ALL OTHERS 10.56 7.72 10.92 65% 6.86 5.02 7.10

MINIMUM AIC (K AMPS) 22 MOTORS AND

EQUIPMENT

LARGEST 0.00 0.00 0.00 125% 0.00 0.00 0.00

SERVICE ENTR. RATED YES X NO >10KVA@50% 0.00 0.00 0.00

MAIN CIRCUIT BREAKER X YES NO GENERAL USE

RECEPT

1.77 1.90 1.69

<=10 KVA@100% 1.77 1.90 1.69

ISOLATED GROUND BUS YES X NO GENERAL LIGHTING 2.34 1.44 1.28 125% 2.92 1.80 1.60

MOUNTING SURFACE A B C A B C

C/B TEMP. 75 C. RATING 120 208 V 3 PH 4 WIRE

LOAD TYPE

CONNECTED KVA NEC DEM

FACT…