Attachment D - Drawing 19-181 Electrical .pdf
PDF 699 KB Posted
- Attached to
- Z2DZ--GI SPS Equipment Site Prep Federal contract opportunity
- Solicitation number
- 36C24621R0087
About this file
This presolicitation notice announces a forthcoming solicitation for site preparation work at the Durham VA Medical Center's Gastrointestinal Sterile Processing Section. The project scope includes renovations to the GI SPS area located on the ground floor of Building 1. The construction value is estimated between $500,000 and $1,000,000. The solicitation is anticipated to be a total service-disabled veteran-owned small business set-aside with NAICS code 236220 and a size standard of $39.5 million. Interested vendors should monitor the website for issuance of the solicitation around June 1, 2021, which will include specifications, drawings and any amendments. Proposals will be due approximately 30 days after issuance. The notice provides contact information for site visits and directs any questions to the identified point of contact via email only.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C24621R0087 0001.docx | DOCX document | |
| Attachment K - Past Performance Questionnaire.docx | DOCX document | |
| Attachment E - Drawing 19-181 Fire Suppression .pdf | ||
| 36C24621R0087_1.docx | DOCX document | |
| Attachment J - Corp Experience Form.docx | DOCX document | |
| Attachment I - Base Proposal Item Price Breakdown.xlsx | XLSX spreadsheet | |
| Attachment G - Drawing 19-181 Plumbing .pdf | ||
| Attachment A - Combined Specs .pdf | ||
| Attachment B - Drawing 19-181 General .pdf | ||
| 36C24621R0087_1.pdf | ||
| Attachment H - Wage Determination NC20210028 01_01_2021.pdf | ||
| Attachment F - Drawing 19-181 Mechanical .pdf | ||
| Attachment C - Drawing 19-181 Architectural .pdf |
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
L L
ELECTRICAL ABBREVIATIONS LIST
SR SURFACE RACEWAY
SS STAINLESS STEEL
SSW SELECTOR SWITCH
STD STANDARD
SURF SURFACE MOUNTED
SW SWITCH
SWBD SWITCHBOARD
SYM SYMMETRICAL
SYS SYSTEM
TC TIMECLOCK
TEL TELEPHONE
TEL/DATA TELEPHONE/DATA
TERM TERMINAL
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TR TAMPER RESISTANT
T-STAT THERMOSTAT
TTB TELEPHONE TERMINAL BOARD
TTC TELEPHONE TERMINAL
CABINET
TV TELEVISION
TYP TYPICAL
UC UNDER COUNTER
UE UNDERGROUND ELECTRICAL
UG UNDERGROUND
UH UNIT HEATER
UL UNDERWRITER'S LABORATORY
UT UNDERGROUND TELEPHONE
UTP UNSHIELDED TWISTED PAIR
UTIL UTILITY
UV UNIT VENTILATOR OR
ULTRAVIOLET
V VOLT
VA VOLT-AMPERES
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VOL VOLUME
W WATT
W/ WITH
WH WATER HEATER
W/O WITHOUT
WP WEATHERPROOF
XFMR TRANSFORMER
XFR TRANSFER
ANGLE
@ AT
DELTA
' FEET
" INCHES
# NUMBER
Φ PHASE
C CENTER LINE
P PLATE
MTR MOTOR, MOTORIZED
MTS MANUAL TRANSFER SWITCH
NA NOT APPLICABLE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURER'S ASSOCIATION
NFDS NON-FUSED SAFETY DISCONNECT
SWITCH
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OH OVERHEAD
OL OVERLOAD
PA PUBLIC ADDRESS
PB PULL BOX OR PUSHBUTTON
PBPU PREFABRICATED BEDSIDE PATIENT
UNIT
PCB POLYCHLORINATED BYPHENYL
PC PHOTOELECTRIC CELL
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PIV POST INDICATING VALVE
PNL PANEL
POE POWER-OVER-ETHERNET
PR PAIR
PRI PRIMARY
PROJ PROJECTION
PRV POWER ROOF VENTILATOR
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE (CONDUIT)
PWR POWER
QTY QUANTITY
RCP REFLECTED CEILING PLAN
RCPT RECEPTACLE
REQD REQUIRED
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT MEAN SQUARE
RTU ROOF TOP UNIT
SC SURFACE CONDUIT
SEC SECONDARY
SF SQUARE FEET/FOOT
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SIM SIMILAR
S/N SOLID NEUTRAL
SPEC SPECIFICATION
SPKR SPEAKER
SP SPARE
1P 1 POLE (2P, 3P, 4P, ETC.)
1PH 1 PHASE
2/C TWO-CONDUCTOR (3/C, 4/C, ETC.)
W2 TWO-WIRE (3W, 4W, ETC.)
3PH 3 PHASE
A AMPERE
AAP ALARM ANNUNCIATOR PANEL
AC ABOVE COUNTER
AIR CONDITIONER
ALTERNATING CURRENT
ACC ACCESSIBLE
ACLG ABOVE CEILING
ADO AUTOMATIC DOOR OPENER
A/E ARCHITECT/ENGINEER
AF AMP FRAME
AFC AVAILABLE FAULT CURRENT (KILOAMPS)
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFI ARC FAULT CIRCUIT INTERRUPTER
AHJ AUTHORITY HAVING JURISDICTION
AHU AIR HANDLING UNIT
AIC AMPERE INTERRUPTING CAPACITY
AL ALUMINUM
ALT ALTERNATE
AMP AMPERE
APPROX APPROXIMATELY
ARCH ARCHITECT, ARCHITECTURAL
AT AMP TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AV AUDIO VISUAL
AWG AMERICAN WIRE GAUGE
BAS BUILDING AUTOMATION SYSTEM
BATT BATTERY
BC BARE COPPER
BD BOARD
BFF BELOW FINISHED FLOOR
BLDG BUILDING
BMS BUILDING MANAGEMENT SYSTEM
BOD BASIS OF DESIGN
BYP BYPASS
C CONDUIT
CAB CABINET
CALC CALCULATED
CAP CAPACITY
CAT CATALOG, CATEGORY
CATV COMMUNITY ANTENNA TELEVISION
CB CIRCUIT BREAKER
CCR CONTROL CONTACTOR
CCTV CLOSED CIRCUIT TELEVISION
cd CANDELA
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR-FURNISHED
CKT CIRCUIT
CLG CEILING
CO CONTRACTING OFFICER
COAX COAXIAL CABLE
COMM COMMUNICATION
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUATION OR CONTINUOUS
CONTR CONTRACTOR
COORD COORDINATE
COR CONTRACTING OFFICER'S
REPRESENTATIVE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CTR CENTER
CU COPPER
CU FT CUBIC FEET
dB DECIBEL
DB DIRECT BURIAL
DC DIRECT CURRENT
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLISH/DEMOLITION
DEPT DEPARTMENT
DIA DIAMETER
DISC DISCONNECT
DIST DISTRIBUTION
DN DOWN
DS SAFETY DISCONNECT SWITCH
DT DOUBLE THROW
DWG DRAWING
EC ELECTRICAL CONTRACTOR
EG EQUIPMENT GROUND
ELEC ELECTRIC, ELECTRICAL
ELEV ELEVATOR
EM EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMS ENERGY MANAGEMENT SYSTEM
EMT ELECTRICAL METALLIC TUBING
EPO EMERGENCY POWER OFF
EQUIP EQUIPMENT
ESMT EASEMENT
ETR EXISTING TO REMAIN
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WALL HEATER
ELECTRIC WATER HEATER
EX EXISTING
EXP EXPLOSION PROOF
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FCU FAN COIL UNIT
FIXT FIXTURE
FLR FLOOR
FLUOR FLUORESCENT
FU FUSE
FUDS FUSED SAFETY DISCONNECT SWITCH
FVR FULL VOLTAGE REVERSING
FVNR FULL VOLTAGE NON-REVERSING
GAL GALLON
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERATOR
GFI GROUND FAULT CIRCUIT INTERRUPTER
GND GROUND
GRS GALVANIZED RIGID STEEL (CONDUIT)
GYP BDGYPSUM BOARD
HID HIGH-INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HTR HEATER
HV HIGH VOLTAGE
HVAC HEATING, VENTILATING AND AIR
CONDITIONING
IES ILLUMINATION ENGINEERING SOCIETY
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
IR INFRARED
I/W INTERLOCK WITH
IWH INSTANTANEOUS WATER HEATER
J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT-AMPERE
KVAR KILOVOLT-AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
LED LIGHT-EMITTING DIODE
LF LINEAR FEET/FOOT
LM LUMEN
LRA LOCKED ROTOR AMPS
LT LIGHT
LTG LIGHTING
LTNG LIGHTNING
LV LOW VOLTAGE
MATV MASTER ANTENNA TELEVISION SYSTEM
MAX MAXIMUM
MC MECHANICAL CONTRACTOR
METAL-CLAD (CONDUIT)
MCA MINIMUM CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MFR MANUFACTURER
MFS MAIN FUSED DISCONNECT SWITCH
MH MANHOLE
MIC MICROPHONE
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MOA MULTIOUTLET ASSEMBLY
MSBD MAIN SWITCHBOARD
MT MOUNT
A1 b
E1 c d
T1
'LPN'
ELECTRICAL SYMBOL NOTES
THE LIGHTING FIXTURE TYPE IS INDICATED BY AN UPPER CASE LETTER OR AN UPPER
CASE LETTER AND NUMBER.
THE SWITCH DESIGNATION (IF NEEDED) IS INDICATED BY A LOWER CASE LETTER.
EXAMPLE: LIGHTING FIXTURE TYPE 'A1' IS CONTROLLED BY SWITCH 'b'.
EXIT SIGNS: STEM INDICATES WALL MOUNTING. NO STEM INDICATES CEILING
MOUNTING. SHADED AREA INDICATES ILLUMINATED FACE(S). ARROW INDICATES
DIRECTIONAL ARROW ON ILLUMINATED FACE(S).
DEVICES: THE SWITCH DESIGNATION IS INDICATED BY A LOWER CASE LETTER.
THE CONTROL DEVICE DESIGNATION IS INDICATED BY A LOWER CASE LETTER.
TRANSFORMERS: THE TRANSFORMER TYPE IS INDICATED BY A NUMBER
FOLLOWING THE UPPER CASE LETTER 'T'. SEE THE TRANSFORMER SCHEDULE OR
THE SINGLE LINE DIAGRAM FOR THE TRANSFORMER DESCRIPTION AND
REQUIREMENTS.
PANELBOARDS: PANELBOARD DOORS MAY BE SHOWN TO INDICATE OPENING
SIDE OF RECESSED PANELBOARDS. SEE PANELBOARD IDENTIFICATION FOR
DESIGNATION CODES.
SHEET KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE NOTE
NUMBER INDICATED IN THE HEXAGON.
HOME RUN TO BRANCH CIRCUIT PANEL: THE PANEL DESIGNATION AND CIRCUIT
DESIGNATION ARE SHOWN ADJACENT TO THE HOME RUN ARROW.
CIRCUIT BREAKER SIZES (AMPS/NUMBER OF POLES) ARE SHOWN IN THE PANEL
SCHEDULE WITH THE CORRESPONDING PANEL AND CIRCUIT DESIGNATION.
SYMBOL NOTATIONS: UPPER CASE LETTERS ADJACENT TO SYMBOLS INDICATE
A UNIT TYPE. SEE APPROPRIATE SCHEDULE OR SPECIFICATIONS.
'LPN'-1,3,5
EXAMPLE 1: WALL MOUNTED EXIT SIGN TYPE 'E1' WITH SINGLE FACE
AND DIRECTIONAL ARROW.
EXAMPLE 2: CEILING MOUNTED EXIT SIGN TYPE 'E2' WITH DOUBLE
FACE AND DIRECTIONAL ARROWS.
E2
EXAMPLE: SPLIT DUPLEX RECEPTACLE; ONE RECEPTACLE OUTLET IS
CONTROLLED BY SWITCH 'c'.
EXAMPLE: SINGLE POLE SWITCH 'd' TO CONTROL LIGHTING FIXTURES INDICATED BY 'd'.
EXAMPLE: TRANSFORMER TYPE 'T1'.
EXAMPLE: HOME RUN TO PANELBOARD 'LPN'; CIRCUITS 1, 3, 5.
# DEMOLITION KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE
NOTE NUMBER INDICATED IN THE SQUARE.
GENERAL ELECTRICAL NOTES
1. ALL ELECTRICAL DEVICES, FIXTURES, EQUIPMENT AND FEEDERS SHALL BE INSTALLED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS, THE MANUFACTURER'S RECOMMENDED PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT AND WITH THE LATEST EDITION OF THE NATIONAL
ELECTRICAL CODE AND VA STANDARDS.
2. PROVIDE ADDITIONAL SUPPORT FOR DEVICES, FIXTURES, EQUIPMENT AND FEEDERS WHERE THE BUILDING
CONSTRUCTION IS NOT SUITABLE FOR DIRECT MOUNTING.
3. FIRESTOP, DRAFTSTOP, SMOKESTOP AND/OR PROTECT THE ANNULAR SPACE AROUND ALL PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILING, AND ROOFS IN ACCORDANCE WITH THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE, UL LISTING REQUIREMENT AND THE APPLICABLE BUILDING CODES.
4. VERIFY CEILING SYSTEMS AND PROVIDE MOUNTING ACCESSORIES, TRIMS AND ALL REQUIRED MOUNTING
HARDWARE TO SUIT THE PARTICULAR INSTALLATION.
5. BRANCH CIRCUIT CONDUCTORS SHALL BE 12 AWG COPPER MINIMUM.
6. COORDINATE ANY AND ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION SO AS TO AVOID CONFLICT
DURING CONSTRUCTION.
7. ALL PANELS SHALL HAVE TYPED, COMPLETED DIRECTORIES INDICATING EQUIPMENT SERVED AND ROOM NUMBER (AS INDICATED ON FINAL BUILDING ROOM SIGNAGE) OF EQUIPMENT LOCATION, OR SPARE, OR SPACE.
8. MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES, TO INDICATE A QUALITY STANDARD, AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR MANUFACTURER.
PRODUCTS DEEMED EQUAL AND APPROVED BY THE DESIGNER WILL BE ACCEPTED. ALL PRODUCTS MUST
COMPLY WITH "BUY AMERICAN ACT".
9. ALL FEEDERS AND CIRCUITRY SHALL BE TORQUED PER THE PANEL, BREAKER, AND/OR PARTICULAR EQUIPMENT
MANUFACTURER'S SPECIFICATIONS.
10. CIRCUITRY TO SWITCHES, RECEPTACLES, AND ALL OTHER DEVICES SHALL BE TERMINATED ON THE DEVICE'S
SCREW TERMINALS.
11. MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, OUTLET, FIXTURE, OR EQUIPMENT UNLESS NOTED
OTHERWISE.
12. ALL WIRE TERMINATIONS SHALL BE RATED FOR 75 DEGREES C.
13. ALL CONDUCTORS SHALL HAVE THHN/THWN INSULATION, UNLESS OTHERWISE NOTED.
14. ALL CONDUIT SHALL BE RGS OR EMT UNLESS OTHERWISE NOTED. FMC CONDUIT SHALL BE USED ON VIBRATING EQUIPMENT (MAXIMUM LENGTH OF 6 FEET). PVC SHALL BE USED FOR UNDERGROUND CONDUIT OR WHERE CONCRETE-ENCASED. WHERE VIBRATING EQUIPMENT IS LOCATED OUTSIDE, LFMC CONDUIT SHALL BE USED
(MAXIMUM SIX FEET) FOR FINAL CONNECTIONS.
15. ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT SHALL BE LABEL LISTED BY AN APPROVED
THIRD PARTY TESTING AGENCY.
16. IN CASE OF CONFLICTS OR DISCREPANCIES WITHIN OR AMONG THE CONTRACT DRAWINGS, THE BETTER QUALITY, MORE STRINGENT REQUIREMENTS OR GREATER QUANTITY OF WORK , AS DETERMINED BY THE
GOVERNMENT, SHALL BE PROVIDED.
17. COMPRESSION COUPLINGS SHALL BE USED. NO SET SCREW FITTINGS ARE ALLOWED.
18. MINIMUM CONDUIT SIZE TO BE USED IS 3/4".
ELECTRICAL SYMBOL LEGEND
120V DUPLEX RECEPTACLE
RECEPTACLE MODIFIERS:
AC: 3" ABOVE COUNTERTOP/BACKSPLASH
GFI: GROUND FAULT CURRENT INTERRUPTER
WP: WEATHERPROOF ENCLOSURE
DED: DEDICATED CIRCUIT
120V DUPLEX RECEPTACLE EMERGENCY OUTLET
AND COVER PLATE SHALL BE RED IN COLOR
120V QUADRUPLEX RECEPTACLE
120V QUADRUPLEX RECEPTACLE EMERGENCY
OUTLET AND COVER PLATE SHALL BE RED IN COLOR
JUNCTION BOX, WALL MOUNTED, PURPOSE AS NOTED
DISCONNECT SWITCH NON-FUSED
DISCONNECT SWITCH FUSED
SINGLE POLE WALL SWITCH: 48" AFF STANDARD UNO
SYMBOL HEIGHT DESCRIPTION
18"
18"
18"
18"
AS
NOTED
72" TOP
72" TOP
SWITCH MODIFIERS:
M: MOTOR-RATED
48"
ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.
TOP: HEIGHT TO TOP OF DEVICE
ANY HEIGHTS INDICATED IN PLANS SHALL SUPERCEDE THOSE LISTED HERE.
SPECIAL RECEPTACLE
EQUIPMENT CONNECTION
AS
NOTED
E
208V DUPLEX RECEPTACLE18"
18"
120V DUPLEX RECEPTACLE FLOOR BOX
120V DUPLEX RECEPTACLE EMERGENCY FLOOR BOX
OUTLET AND COVER PLATE SHALL BE RED IN COLOR
120V QUADUPLEX RECEPTACLE FLOOR BOX
120V QUADUPLEX RECEPTACLE EMERGENCY
FLOOR BOX OUTLET AND COVER PLATE SHALL BE
RED IN COLOR
CLNG
J
J
J
JUNCTION BOX, CEILING MOUNTED, PURPOSE AS
NOTED
JUNCTION BOX, FLOOR MOUNTED, PURPOSE AS
NOTED
LIGHTING SYMBOL LEGEND
2' X 2' RECESSED DIRECT/INDIRECT TROFFER
2' X 4' RECESSED DIRECT/INDIRECT TROFFER
SYMBOL HEIGHT
AFF *
DESCRIPTION
--- 2' X 4' RECESSED FLAT PRISMATIC LENS TROFFER
WALL SCONCE
6'-0"
CENTER
6" DIAMETER RECESSED DOWNLIGHT---
EXIT SIGN - WALL MOUNTED
EXIT SIGN - CEILING MOUNTED---
7'-5"
BOTTOM
SINGLE POLE WALL SWITCH
SWITCH MODIFIERS:
OS: OCCUPANCY SENSOR, DUAL TECHNOLOGY
VS: VACANCY SENSOR, DUAL TECHNOLOGY
LV: LOW VOLTAGE
LVD: LOW VOLTAGE DIMMER
D: LINE VOLTAGE DIMMER
T: DIGITAL TIMER
K: KEYED
3: 3 WAY
48"
CENTER
2' LINEAR - WALL MOUNTED
7'-0"
CENTER
EMERGENCY LIGHT BATTERY
OPERATED - WALL MOUNTED
7'-6"
CENTER
* - ANY HEIGHTS INDICATED IN PLANS SHALL SUPERCEDE THOSE
LISTED HERE.
4' LINEAR - WALL MOUNTED
7'-0"
CENTER
TECHNOLOGY SYMBOL LEGEND
DATA OUTLET - N-4 PR UTP
TELCO OUTLET - N-4 PR UTP
SYMBOL HEIGHT DESCRIPTION
18"
48"
ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.
ANY HEIGHTS INDICATED IN PLANS SHALL SUPERCEDE THOSE LISTED HERE.
SEE DRAWINGS FOR MORE INFORMATION.
NOTE: NOT ALL SYMBOLS ARE USED.
ELECTRONIC LOCKING MECHANISM
DOOR CONTACT
REQUEST FOR EXIT SENSOR
CARD READER
(K - KEYPAD)
48"CR
ES
DC
RX
48" PUSH PAD FOR DOOR OPERATOR
WIRELESS ACCESS POINT - N-4 PR UTP
WALL PHONEW
IC
INTERCOM WITH CAMERA
IC
INTERCOM MASTER WITH PUSH TO RELEASE DOORM
N
TV OUTLET WALL MOUNTED
48"
54"
DESK
CCTV DOME CAMERA FIXED
CCTV DOME CAMERA PAN/TILT/ZOOM
FOUR POST OIT EQUIPMENT RACK
OIT EQUIPMENT CABINET
MATV EQUIPMENT CABINET
CCTV EQUIPMENT CABINET
MATV
CCTV
LADDER CABLE TRAY
N
N
FLOOR BOX FOR DATA
AS NOTED
DOOR
DOOR
ABOVE
DOOR
6' TO TOP
FLOOR
PHYSICAL ACCESS CONTROL SYSTEMPACS 6' TO TOP
ELECTRONIC PANIC HARDWAREEP
DO DOOR OPERATOR
HANDWAVE
L
KP PATIENT ROAM ALERT ACCESS CONTROL KEYPAD48"
PATIENT ROAM ALERT ANTENNACEILING
GROUND BUS
CEILING
DOOR
DOOR
48"
FLOOR
FLOOR
FLOOR
ABOVE
CEILING
18"
4'x8'x3/4" FIRE RATED TTB8"
FLOOR TWO POST OIT EQUIPMENT RACK
CEILING MOUNTED SPEAKERSCEILING
WALL MOUNTED SPEAKERS96"
S
S
SECURE WIRELESS ACCESS POINT - N-4 PR UTP
N
CEILING
S
(N - QUANTITY)
(N - QUANTITY)
(N - QUANTITY)
(N - QUANTITY)
CEILING
CEILING
S
NURSE CALL/INTERCOM STATION48"
GENERAL TECHNOLOGY NOTES
1. PROVIDE COMMUNICATIONS DEVICES AND EQUIPMENT IN ACCORDANCE WITH THE CONTRACT DOCUMENTS, MANUFACTURER'S RECOMMENDED PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT, LATEST EDITION OF THE NATIONAL ELECTRICAL CODE, BICSI STANDARDS, AND VA STANDARDS.
2. PROVIDE ADDITIONAL SUPPORT FOR DEVICES AND EQUIPMENT WHERE BUILDING CONSTRUCTION IS NOT SUITABLE
FOR DIRECT MOUNTING.
3. FIRESTOP, DRAFTSTOP, SMOKESTOP OR PROTECT ANNULAR SPACE AROUND PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILINGS, AND ROOF IN ACCORDANCE WITH REQUIREMENTS OF NFPA 70, UL LISTING
REQUIREMENT AND APPLICABLE BUILDING CODES.
4. PROVIDE CABLING THAT COMPLIES WITH THE LATEST EDITION OF TELECOMMUNICATIONS DISTRIBUTION METHOD
MANUAL AND ANSI/TIA/EIA PUBLICATIONS.
5. COMPLY WITH THE LATEST ANSI/TIA/EIA 758 AND 607B OR 607A - GROUNDING AND BONDING REQUIREMENTS FOR
TELECOMMUNICATIONS IN COMMERCIAL BUILDING.
6. COMPLY WITH THE LATEST ANSI/TIA/EIA 568B - COMMERCIAL BUILDING TELECOMMUNICATIONS WIRING STANDARD.
7. COMPLY WITH THE LATEST ANSI/TIA/EIA 569B - COMMERCIAL BUILDING STANDARD FOR TELECOMMUNICATIONS
PATHWAYS AND SPACES.
8. COMPLY WITH THE LATEST NFPA 70 NATIONAL ELECTRICAL CODE.
9. COMPLY WITH THE LATEST NFPA 99 HEALTHCARE FACILITIES CODE.
10. COMPLY WITH THE LATEST NFPA 101 LIFE SAFETY CODE.
11. COORDINATE WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION.
12. MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES, TO INDICATE A QUALITY STANDARD, AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR MANUFACTURER. PRODUCTS DEEMED EQUAL AND APPROVED BY THE COR WILL BE ACCEPTABLE. COMPLY WITH "BUY AMERICAN ACT".
13. MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, BOXES, OUTLET, OR EQUIPMENT UNLESS NOTED
OTHERWISE.
14. PROVIDE RGS OR EMT CONDUIT UNLESS OTHERWISE NOTED.
15. PROVIDE MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT LABEL LISTED BY APPROVED THIRD PARTY TESTING
AGENCY.
16. NOTIFY COR REGARDING DISCREPANCY BETWEEN PLANS AND SPECIFICATIONS FOR CLARIFICATION. THE MORE
STRINGENT OF THE THEM SHALL TAKE PRECEDENCE.
17. PROVIDE TIA/EIA CAT 6 COPPER OUTLETS AND CONNECTORS.
18. ALL WORK AREA OUTLETS SHALL BE 8 PIN, CAT 6 KEYSTONE JACK WIRED PER T568A OR T568B AS DIRECTED BY THE
VA COR.
19. LABEL DEVICES IN ACCORDANCE WITH LATEST ANSI/TIA 606A OR 606B EDITION AS WELL AS THE STANDARDS SET
FORTH BY THE VA HOSPITAL OIT.
20. PROVIDE A MINIMUM OF 12" CLEARANCE ABOVE THE CABLE TRAY PER TIA/EIA 569.B PARAGRAPH 4.5.6.2.
21. ALL CABLING INSTALLED ABOVE CEILING SHALL BE PLENUM RATED.
22. MINIMUM CONDUIT SIZE TO BE USED IS 3/4".
LUMINAIRE SCHEDULE
A. CONTRACTOR RESPONSIBLE FOR REMOVING, PROTECTING, AND REINSTALLING EXISTING LIGHTING FIXTURES. IF LIGHTING FIXTURE IS DAMAGED DURING COURSE OF WORK. CONTRACTOR SHALL BE RESPONSIBLE FOR REPLACING FIXTURE. CONTRACTOR SHALL CLEAN
FIXTURES PRIOR TO REINSTALLATION.
B. MANUFACTURER AND CATALOG NUMBERS SHOWN ARE FOR BASIS OF DESIGN, DESCRIPTIVE AND QUALITY STANDARDS ONLY, NOT TO BE USED FOR ORDERING WITHOUT VERIFICATION AND APPROVAL. CONTRACTOR TO PROVIDE PRODUCT OR EQUAL FOR APPROVAL BY OWNER, ARCHITECT AND ENGINEER. ENGINEER SHALL NOT BE RESPONSIBLE FOR MISMATCHED OR INACCURATE PART NUMBERS.
C. VERIFY ALL LIGHT FIXTURE MOUNTING TYPES AND COLORS WITH ARCHITECT.
D. LIGHTING CONTROLS, INCLUDING CONTROL SCHEMATICS, DEVICES, SWITCHES, SENSORS AND GRAPHIC DISPLAYS/CONTROLLERS. THIS INFORMATION MUST BE SUBMITTED WITH THE LIGHT FIXTURE SHOP DRAWINGS, FOR A COMPLETE REVIEW.
GENERAL NOTES:
FIRE ALARM SYMBOL LEGEND
SYMBOL HEIGHT DESCRIPTION
ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.
TOP: HEIGHT TO TOP OF DEVICE
ANY HEIGHTS INDICATED IN PLANS SHALL SUPERCEDE THOSE LISTED HERE.
F FIRE ALARM STROBE
FIRE ALARM SPEAKER AND STROBE
90"
90"
XX - CANDELA
XX - CANDELA
XX - WATTAGEF
S
FIRE ALARM SPEAKER90"F
S
FIRE ALARM DUCT SMOKE DETECTOR
FIRE ALARM SMOKE DETECTORSD
FIRE ALARM RELAY MODULE
DD
FAR
1. PROVIDE FIRE ALARM SYSTEM AND COMPONENTS COMPLYING WITH THE LATEST:
A. NFPA 70 NATIONAL ELECTRICAL CODE.
B. NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE.
C. NFPA 101 LIFE SAFETY CODE.
D. VA FIRE PROTECTION DESIGN MANUAL.
E. ANSI S3.41 AUDIBLE EMERGENCY EVACUATION SIGNAL.
2. FIRE ALARM SYSTEM SHALL COMPLY WITH FACTORY MUTUAL RESEARCH CORPORATION (FM).
3. PROVIDE FIRE ALARM WIRING IN CONDUIT, FACTORY PAINTED RED.
4. BEFORE STARTING WORK, TEST EXISTING FIRE ALARM SYSTEM IN WORK AREA AND ADJACENT AREAS.
5. NOTIFY COR REGARDING DEFICIENCIES AND NON-OPERATING COMPONENTS. VA WILL MAKE REPAIRS.
6. WHEN WORK IS COMPLETE, TEST EXISTING FIRE ALARM SYSTEM IN WORK AREA AND ADJACENT AREAS.
7. MAKE REPAIRS TO RESOLVE INCORRECT SYSTEM OPERATIONS AT NO ADDITIONAL COST.
8. THE FIRE ALARM SYSTEM VENDOR/CONTRACTOR SHALL TERMINATE, TEST AND PROGRAM ALL NEW FIRE ALARM
DEVICES. COORDINATE WITH COR.
9. CONNECT SPRINKLER SYSTEM SUPERVISORY DEVICES TO THE FIRE ALARM SYSTEM. COORDINATE LOCATION WITH
THE SPRINKLER CONTRACTOR.
GENERAL FIRE ALARM NOTES
FIRE ALARM RISER NOTES:
A. FIRE ALARM SYSTEM SHALL BE INTERCONNECTED WITH
ACCESS CONTROL SYSTEM TO ALLOW EGRESS DURING
ALARM CONDITIONS. COORDINATE BETWEEN ACCESS
CONTROL SYSTEM AND FIRE ALARM SYSTEM
MANUFACTURERS.
B. ALL FIRE ALARM WIRING SHALL BE IN FACTORY PAINTED
"RED" EMT CONDUIT.
C. ALL WIRING SHALL BE AS RECOMMENDED BY
MANUFACTURER.
D. PROVIDE POWER SUPPLY AND/OR NAC (NOTIFICATION
APPLIANCE CIRCUIT) PANEL AS REQUIRED FOR ADDITIONAL
DEVICES.
E. THE NEW FIRE ALARM SYSTEM SHALL MATCH THE EXISTING
SIMPLEX
FIRE ALARM SYSTEM.
TO EXISTING
CORRIDOR
INDICATING
APPLIANCES
F F F
GENERAL ELECTRICAL DEMOLITION NOTES
A. RETURN REMOVED MATERIAL DEEMED SALVAGEABLE BY OWNER'S REPRESENTATIVE. MATERIALS DEEMED NOT SALVAGEABLE SHALL BE REMOVED FROM THE PREMISES.
B. THE CONTRACTOR WILL BE HELD TO HAVE EXAMINED THE PREMISES AND SATISFIED HIMSELF AS TO EXISTING CONDITIONS UNDER WHICH HE WILL BE OBLIGED TO PERFORM HIS WORK. THE DRAWINGS ARE GENERALLY DIAGRAMMATIC AND THE CONTRACTOR SHALL HARMONIZE HIS WORK SO THAT EACH PIECE OF EQUIPMENT WILL BE INSTALLED AS TO FUNCTION PROPERLY. THE
CONTRACTOR SHALL COOPERATE WITH OTHER TRADES.
C. REMOVE ALL EXISTING WIRING DEVICES, LIGHT FIXTURES, WIRE, CONDUIT, ETC., AS NOTED OR INDICATED WITHIN DEMOLITION AREA. (ALL ITEMS MAY NOT BE SHOWN). REWORK AS
NECESSARY CIRCUITING WHICH REQUIRES CONTINUATION THROUGH THE AREA.
D. ELECTRICAL CONTRACTOR TO PROVIDE ALL NECESSARY LABOR, CONDUIT, WIRE, CONNECTIONS, ETC., FOR DEVICES, FIXTURES, ETC., NOTED AS "EXISTING TO REMAIN" SUCH THAT EXISTING
CIRCUIT CONTINUITY IS MAINTAINED.
E. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WORK REQUIRED TO REMOVE/RELOCATE ANY EXISTING ELECTRICAL EQUIPMENT SUCH THAT ELECTRIC SHOCK HAZARDS TO
WORKMEN ARE ELIMINATED DURING DEMOLITION AND NEW CONSTRUCTION.
F. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WORK IN REMOVING AND REPLACING "EXISTING TO REMAIN" FIXTURES, DEVICES, ETC., AS REQUIRED SO THAT THESE DEVICES ARE NOT DAMAGED DURING DEMOLITION. RELOCATED TO NEAREST APPROPRIATE LOCATION TO AVOID CONFLICTS WITH OTHER TRADES' WORK. REPLACE WITH NEW ANY "EXISTING TO REMAIN"
FIXTURE, DEVICE, ETC., NOT DEEMED SALVAGEABLE BY OWNER'S REPRESENTATIVE.
G. REMOVED OR DAMAGED CONDUIT, WIRE, AND FITTINGS SHALL NOT BE REUSED FOR RELOCATED OR NEW DEVICES.
H. MAKE AS-BUILTS WITH NEW TYPED DIRECTORIES FOR ALL PANELBOARDS, INDICATING CIRCUIT DESCRIPTION (USED OR SPARE), CIRCUIT BREAKERS AND CIRCUIT LOAD.
I. WORK REQUIRED FOR EXISTING EQUIPMENT NOTED AS "EXISTING TO BE REMOVED" SHALL INCLUDE:
A. REMOVAL OF FEEDER FROM EQUIPMENT TO POINT OF FEED.
B. REMOVAL OR RE-CIRCUITING OF ALL BRANCH CIRCUITING.
C. REMOVAL OF ALL FITTINGS, SUPPORTS, BRACKETS, ETC.
D. PATCHING OF WALLS, FLOORS AND CEILINGS PER ARCHITECT'S INSTRUCTIONS.
E. CAPPING OF FEEDER CONDUIT AT 6" ABOVE OR BELOW FLOOR/CEILING AS REQUIRED AND MARKING LOCATION OF POINT OF FEED WITH AN ENGRAVED BRASS TAG.
F. REMOVAL OF FEEDER CONDUIT IF FOUND TO BE UNSALVAGEABLE BY ARCHITECT, ENGINEER OR OWNER'S REPRESENTATIVE.
J. EXISTING EQUIPMENT NOT IMPLICITLY SHOWN ON THE DRAWINGS IS INTENDED TO BE "EXISTING TO REMAIN UNCHANGED", UNLESS NOTED OTHERWISE.
GENERAL ELECTRICAL REMODELING NOTES
A. PRIOR TO SUBMITTING PROPOSAL, BIDDER SHALL EXAMINE ALL GENERAL CONSTRUCTION DRAWINGS. BIDDER SHALL BE FAMILIAR WITH THE EXISTING CONDITIONS UNDER WHICH BIDDER WILL HAVE TO OPERATE AND WHICH WILL IN ANY WAY AFFECT THE WORK UNDER THIS CONTRACT. NO SUBSEQUENT ALLOWANCE WILL BE MADE IN THIS CONNECTION IN BEHALF OF THE
CONTRACTOR FOR ANY ERROR OR NEGLIGENCE ON HIS PART.
B. CERTAIN REMODELING OF ELECTRICAL FACILITIES WILL BE REQUIRED IN THE EXISTING BUILDING. EXISTING CONDUIT RUNS ARE GENERALLY NOT SHOWN. ALTHOUGH A FULL ATTEMPT HAS BEEN MADE TO SHOW SOME EXISTING CONDITIONS, OF WHICH INFORMATION HAS BEEN TAKEN FROM EXISTING RECORD DRAWINGS OF THIS PROJECT. THE DRAWINGS SHOWING LOCATION OF EXISTING EQUIPMENT, OUTLETS, FIXTURES, ETC., IN EXISTING AREAS ARE APPROXIMATE ONLY (FIELD VERIFY).
C. BRANCH CIRCUITS SHALL BE REUSED WHERE PRACTICAL AND SHALL, IN ADDITION, BE REMODELED AS REQUIRED. THE CONTRACTOR SHALL CONCEAL ALL WORK WHERE POSSIBLE.
D. EXISTING ELECTRICAL WIRING WHICH WILL NOT BE MADE OBSOLETE AND WHICH WILL BE DISTURBED DUE TO CONSTRUCTION CHANGES REQUIRED BY THIS CONTRACT SHALL BE RESTORED TO OPERATING CONDITION, AS REQUIRED AND/OR DIRECTED. WHERE REQUIRED, SHOWN AND/OR DIRECTED, OUTLETS AND CONDUIT RUNS SHALL BE RELOCATED. IN SOME CASES IT MAY BE NECESSARY TO EXTEND CONDUITS AND PULL IN NEW WIRING OR INSTALL JUNCTION BOXES AND SPLICE IN NEW WIRING OR REPLACE OLD WIRING WITH NEW.
E. OUTLETS FROM WHICH FIXTURES, SWITCHES, RECEPTACLES, AND/OR OTHER ELECTRICAL DEVICES ARE MOVED AND WHICH ARE NOT REPLACED OR REUSED SHALL BE REMOVED OR, IF IT IS NOT POSSIBLE TO REMOVE, PLACE A BLANK COVER ON THE OUTLET BOX. WHERE OUTLETS, BOXES, ETC., ARE COMPLETELY REMOVED, THE CONTRACTOR SHALL CUT OFF CONDUITS AND
REMOVE WIRING.
F. WHERE EXISTING LIGHT FIXTURES ARE TO BE REUSED, THE ELECTRICAL CONTRACTOR SHALL CLEAN AND REPLACE LAMPS, REPAIR OR REPLACE DEFECTIVE PARTS, LENS, BALLAST, ETC. AS
REQUIRED.
G. WHERE CONDUITS EXTENDING THROUGH FLOORS ARE TO BE ABANDONED, THE CONTRACTOR SHALL CUT AND CAP OR PLUG CONDUIT, THAT IT WILL NOT PROTRUDE ABOVE THE FLOOR.
H. WHERE EXISTING CONDUIT IS TO BE ABANDONED, THE CONDUIT SHALL BE REMOVED IF IT IS EXPOSED, IN A CRAWL SPACE OR IN AN ACCESSIBLE CEILING. WHERE IT IS IMPOSSIBLE TO
REMOVE THE CONDUIT, IT SHALL BE CUT OFF AND CAPPED OR PLUGGED.
I. THE CONTRACTOR SHALL BE HELD FULLY RESPONSIBLE FOR THE PROPER RESTORATION OF ALL EXISTING SURFACES REQUIRED PATCHING, PLASTERING, PAINTING AND/OR OTHER REPAIR DUE TO THE INSTALLATION OF ELECTRICAL WORK UNDER THE TERMS OF THIS SPECIFICATION. CLOSE ALL OPENINGS, REPAIR ALL SURFACES, ETC., AS REQUIRED. THE CONTRACTOR SHALL EMPLOY QUALIFIED AND EXPERIENCED WORKMEN FOR THIS WORK. ALL RESTORATION WORK SHALL BE SUBJECT TO THE APPROVAL OF THE ARCHITECT AND/OR THE OWNER.
J. ALL TEMPORARY AND REMODELING WORK SHALL BE CONSIDERED A PART OF THIS CONTRACT AND NO EXTRA CHARGES WILL BE ALLOWED. THIS SHALL INCLUDE MINOR ITEMS OF MATERIAL
OR EQUIPMENT NECESSARY TO MEET THE REQUIREMENTS AND INTENT OF THE PROJECT.
K. EXAMINE ARCHITECTURAL, STRUCTURAL, AND MECHANICAL DRAWINGS AND SPECIFICATIONS TO DETERMINE THE SEQUENCE OF CONSTRUCTION THROUGHOUT THE PROJECT, INCLUDING
EXISTING, TEMPORARY, REMODELED AND NEW AREAS.
L. ALL ELECTRICAL CONNECTIONS REQUIRING AN OUTAGE SHALL BE MADE DURING AN APPROVED TIME LIMIT. CHANGEOVERS SHALL BE AS SHORT A DURATION AS POSSIBLE AND SHALL NOT INTERFERE WITH NORMAL OPERATION OF THE OWNER'S FACILITIES. NOTICE SHALL BE REQUIRED IN ADVANCE OF A SHUTDOWN OF ANY ELECTRICAL CIRCUIT FOR CHANGEOVER, AND SUCH A CHANGEOVER SHALL BE DONE DURING HOURS AS DIRECTED BY OWNER. WORK SHALL BE SCHEDULED SO THAT AT NO TIME WILL ANY EMERGENCY FEEDER, CIRCUIT, OR FIRE ALARM ZONE BE OUT OF SERVICE. PROVIDE NECESSARY TEMPORARY FEEDERS TO ACCOMPLISH THIS REQUIREMENT.
M. EXISTING LOW VOLTAGE WIRING WHICH WILL NOT BE MADE OBSOLETE AND WHICH WILL BE DISTURBED DUE TO CONSTRUCTION CHANGES REQUIRED BY THIS CONTRACT SHALL BE RESTORED TO CONDITION, OR POSITION, AS REQUIRED. PROPERLY RE-SECURE CABLE IN CHASES, CRAWL SPACES, TUNNELS, AND CEILING SPACES AS REQUIRED BY NEC. IN SOME CASES IT
MAY BE NECESSARY TO ADD SUPPORTING HARDWARE TO ACCOMPLISH THIS REQUIREMENT.
N. IF POSSIBLE, ALL NEWLY INSTALLED RECEPTACLES SHALL BE INSTALLED IN SEPARATE OR ADJACENT STUD SPACES, TO AVOID SOUND TRANSMISSION AND WALL INTEGRITY ISSUES. ALL NEWLY INSTALLED RECEPTACLES LOCATED IN COMMON STUD SPACES OF FIRE-RESISTANT WALLS SHALL BE EQUIPPED WITH FIRE-RESISTANT PUTTY PADS AT THE BACK OF EACH BOX IN
ACCORDANCE WITH NEC 300.21.
Engineers Architects
Revisions: Date
Drawing Title
Approved:
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
NOT FOR
CONSTRUCTIO
N
NOT FOR
CONSTRUCTIO
N
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/2 /2
:4
:1
P M
E-001
ELECTRICAL GENERAL NOTES,
SYMBOL LEGENDS, AND
ABBREVIATIONS
1 5JDM
SPS EQUIPMENT
INSTALLATION
DURHAM VA MEDICAL CENTER
508 FULTON ST.
DURHAM, NC 27705 OCTOBER 23, 2020
CONSTRUCTION DOCUMENTS
558-19-30219-181
JAV
TYPE DESCRIPTION MOUNTING LAMP VOLTAGE MANUFACTURER MODEL NUMBER
A EXISTING 2' X 4'
LENSED FLUORESCENT
TROFFER;
RECESSED
GRID
3-LAMP 277.00 V - WHERE NOTED (F), THE ELECTRICAL CONTRACTOR SHALL PROVIDE
DRYWALL FLANGE KIT COMPATIBLE WITH EXISTING GRID-MOUNTED
LUMINAIRE. BASIS OF DESIGN: LSI FK-24, FIXTURE CONVERSION KIT.
B EXISTING 2' X 4'
LENSED FLUORESCENT
TROFFER;
RECESSED
GRID
2-LAMP 277.00 V - -
Scale: N.T.S.
FIRE ALARM RISER
48"
GFI
" A
C G
FI
S
AC
GFI
30"30"30"
30"
GFI
30"
GFI
A C
G
FI
30"
G
FI
AC
GFI
F
S
FS
40"
S
4 A
C DO
DO
48"
GFI
48"
GFI
S
F
S
D D
48"
GFI
48"
GFI
48"
GFI
48"
GFI
48"
GFI
GFI
48"
GFI
48"
GFI
48"
GFI
48"
GFI
J
J
F
S
FS
S
48"
48"
48"
48"
48" 48"
GFI
48"
48"
48"
48"
48"
48"
48"
48"
48"
GFI
48"
GFI
GFI
F
15 cd
F
15 cd
F15 cdW
S
F
S
S
D D
TOILET
FG314
STORAGE
FG312
ASSIST
FG311
CLERIC AL
FG309
NOURISH
FG331
PROCEDURE 3
FG313
PROCEDURE 2
FG315
SUPPLIES
FG310
PROCEDURE 4
FG308
OFFICE
FG316
PROCEDURE
FG165
GAS
FG189
OFFICE
FG172
NEW EXIT PASSAGEWAY
FG400C
CIRCULATION
FG300B
J
J
EXISTING
PANEL 'GN2'
EXISTING
PANEL 'GCR2'
EXISTING
PANEL 'GCR2A'
('GN2A'-37)
('GCR2'-16)
('GN2A'-37)
('GN2A'-35) ('GN2A'-35)
('GN2A'-35)
('GCR2'-16)('GCR2'-16) ('GN2A'-35) ('GCR2'-16)
('GCR2'-16)
('GCR2'-16)
('GCR2'-16)
('GCR2'-18)
('GCR2'-18)
('GCR2'-18) ('GCR2'-18)
('GN2A'-33)
('GCR2'-18)
('GN2A'-33)
('GN2A'-33)
TB-2.18
TB-2.17
TB-2.19
SCOPE CLEAN
FG318
SCOPES SOIL
FG319
SOIL
FG317
('GN2A'-33)
TB-2.11
TB-2.12
FAR
TOILET
FG314
STORAGE
FG312
ASSIST
FG311
CLERIC AL
FG309
NOURISH
FG331
PROCEDURE 3
FG313
PROCEDURE 2
FG315
SUPPLIES
FG310
PROCEDURE 4
FG308
OFFICE
FG316
ANTE RM
FG317
PROCEDURE
FG165
GAS
FG189
OFFICE
FG172
NEW EXIT PASSAGEWAY
FG400C
CIRCULATION
FG300B
SCOPES DECON.
FG318
SCOPES STAGING
FG319
2'GCR2'-18
'GN2A'-33
'GCR2'-16
'GCR2'-30
'GCR2'-32
'GN1A'-33
'GN2A'-37
'GN2A'-35
EXISTING
PANEL 'GN2'
EXISTING
PANEL 'GCR2'
EXISTING
PANEL 'GCR2A'
TB-2.18
TB-2.11
TB-2.12
TB-2.19
TB-2.17
FAR
Engineers Architects
## KEY NOTES:
# KEY NOTES:
Revisions: Date
Drawing Title
Approved:
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
NOT FOR
CONSTRUCTIO
N
NOT FOR
CONSTRUCTIO
N
WALL RATING LEGEND
1 HR - FIRE BARRIER
2 HR - FIRE BARRIER
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
/2 /2
:4
:1
P M
E-101
PARTIAL GROUND FLOOR ELECTRICAL
PLANS
2 5JDM
SPS EQUIPMENT
INSTALLATION
DURHAM VA MEDICAL CENTER
508 FULTON ST.
DURHAM, NC 27705 OCTOBER 23, 2020
CONSTRUCTION DOCUMENTS
558-19-30219-181
JAV
N
KEY PLAN
SCALE: NO SCALE
AREA OF WORK
GROUND FLOOR
Scale: 1/4" = 1'-0"
GROUND FLOOR ELECTRICAL DEMOLITION PLAN
Scale: 1/4" = 1'-0"
PARTIAL GROUND FLOOR POWER PLAN 0 2 4 8
NORTH
PLAN
0 2 4 8
NORTH
PLAN
1 SEE DEMOLITION PLANS FOR EXISTING
CIRCUITS TO BE REUSED. PROVIDE
ADDITIONAL CIRCUITS FROM RESPECTIVE
PANELS AS REQUIRED.
2 (TYP) COORDINATE CONNECTIONS FOR
MEDIVATORS WITH EQUIPMENT INSTALLERS.
3 (TYP) NEW FIRE ALARM STROBE. CONNECT
TO EXISTING FIRE ALARM CIRCUIT COVERING
CORRIDOR.
4 (TYP) CONNECT NEW HEPA FILTER UNITS TO
EXISTING TERMINAL UNIT CIRCUIT 'GN2'-18.
A. ALL BRANCH CIRCUIT CONDUCTORS SHALL BE
2-12 AWG, 1-12 AWG EG IN 3/4" CONDUIT
UNLESS NOTED OTHERWISE.
B. FOR MORE INFORMATION REGARDING DATA
JACK INSTALLATION SEE DETAILS 1 & 2 ON
SHEET E-501. LABEL TECHNOLOGY JACKS PER
DETAIL 3 SHEET E-501.
C. DEMOLISH ALL EXISTING ELECTRICAL
DEVICES AS SHOWN ON DEMOLITION PLAN
UNLESS NOTED OTHERWISE.
D. CONTRACTOR SHALL BE RESPONSIBLE FOR
TRACING AND IDENTIFYING ALL CIRCUITS AND
CONDUIT THAT ORIGINATE, PASS THROUGH,
OR TERMINATE IN THE AREA OF WORK.
DEMOLISH ALL CIRCUITS THAT ARE NO
LONGER IN USE. MAINTAIN CIRCUIT
CONTINUITY TO ALL CIRCUITS WHICH ARE NOT
COMPLETELY REMOVED.
E. INSTALL ALL DEVICES AS INDICATED ON NEW
WORK PLAN. COORDINATE ALL WORK WITH
COR AND OTHER TRADES.
F. DEMOLITION SHALL INCLUDE BUT NOT BE
LIMITED TO THE DEVICES AND/OR SYSTEMS
SHOWN. COORDINATE WITH ARCHITECTURAL,
MECHANICAL, AND PLUMBING DEMOLITION
PLANS.
G. REFER TO SHEET E-102 FOR LOCATION OF
EXISTING PANELS GN2A AND GN1A.
1 PROVIDE AND INSTALL NEW JUNCTION BOXES.
DEMO CIRCUITS BACK TO JUNCTION BOXES.
RETAIN AND REUSE TO FEED NEW DEVICES.
2 (TYP.) VERIFY CIRCUITING IN FIELD.
3 (TYP.) PROTECT EXISTING CIRCUIT 'GN2'-18
FEEDING EXISTING TERMINAL UNITS.
4 THE ELECTRICAL CONTRACTOR SHALL
PROTECT THE EXISTING FIRE ALARM
NOTIFICATION DEICE DURING WALL
DEMOLITION. THE DEVICE SHALL REMAIN IN
SERVICE. SUPPORT AND SECURE THE DEVICE
UNTIL IT IS REINSTALLED.
FG234
FG231 FG232 FG233
FG201 FG400B
WAITING
OFFICE
RECEPTION
NEW EXIT
PASSAGEWAY
FG172
FG168
FG169
FG187
FG185A
FG186
FG170
FG185
G185A
G185C
G185B
G186A
FG404
FG219
FG200A
FG234
FG402
FG401
FG220
FG221
FG218
FG202FG203FG205FG207
FG215
FG217
FG216
FG214 FG208 FG204 FG230
FG223 FG227 FG229
FG224 FG226 FG228
FG231 FG232 FG233
FG206
FG225
FG213
FG200C
F G D
FG222A FG222B
F G B
FG210
FG211
FG212
FG201FG209
FG405
FG403
FG165
FG321
FG318
FG322
FG345
FG317 FG316
FG340
FG341
FG342
FG344
FG320
FG308 FG306 FG304 FG302FG315 FG313
FG332
FG323
FG312
FG319
FG324 FG325 FG326 FG327 FG328 FG329 FG334FG330 FG335 FG336 FG337 FG338
FG301FG303FG305FG307FG309FG311
FG339
FG333
FG300B
FG314
FG189
FG310
FG331
FG300D
FG300A
FG300CL
FG343A
FG343
FG400C
FG218A
FG166
FG164
FG173
FG174
FG167
FG171
FG175
SEDATION
STORAGE
TELECOM
EQUIP
CONTROL RM
WAITING
OFFICE
DATA RM
HSK
CIRCULATION
WAITING
PUBLIC TOILETS (M)
PUBLIC TOILETS(W)
STAFF T
CLEAN SUPPLIES
CLEAN UTILITY
PHOTOEXAMEXAMEXAM
LASER
EXAM
WAITING
PROCEDURES EXAM EXAM EXAM
EXAM EXAM EXAM
EXAM EXAM EXAM
FIELD PRETEST/FIT
EXAM
EXAM
LASER
CIRCULATION
C
IR
C U
LA
TI
O N
WAITING WAITING
C
IR
C U
LA
TI
O N
OFFICE
CONFERENCE
OFFICE
RECEPTIONEXAM
ELEC. RM
STAFF LOCKERS
PRESCREEN
HSK
SCOPES CLEAN
EQUIP
MECHANICAL
SOIL CLEAN
RESIDENTS
EXAMS
EXAMS
WAITING
PROCEDURE 4 PROCEDURE 5 PROCEDURE 6 PROCEDURE 7PROCEDURE 3
NURSE STATION
TOILET
STORAGE
SCOPES SOIL
RECOVERY HOLDING HOLDING HOLDING HOLDING HOLDING
P.A.PHYSICIANCHIEFCLERICALASSIST
TOILET
TOILET
CIRCULATION
TOILET
GAS
SUPPLIES
Nourish
CIRCULATION
CIRCULATION
ELEC CLOSET
LOCKER ROOM
RECEPTION
NEW EXIT PASSAGWAY
PHYSICIAN
PROCEDURE 2
PROCEDURE 1
RECOVERY RECOVERY RECOVERY RECOVERY RECOVERY RECOVERY
SOILED UTILITY
DRSG RM
EXAM RM
TOILET
WAITING
WAITING
TOILET
DRSG RM
DRSG RM
TOILET
RECEPTION
CORRIDOR
DRSG RM
E-101
EXISTING
PANEL 'GN2A'
EXISTING
PANEL 'GN1'
EXISTING
PANEL 'GN1A'
EXISTING
PANEL 'GCR1'
EXISTING
PANEL 'GEQ1'EXISTING
PANEL 'GCR1A'
EXISTING SONITROL
(SECURITY) PANEL
Engineers Architects
## KEY NOTES:
Revisions: Date
Drawing Title
Approved:
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
NOT FOR
CONSTRUCTIO
N
NOT FOR
CONSTRUCTIO
N
WALL RATING LEGEND
1 HR - FIRE BARRIER
2 HR - FIRE BARRIER
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
/2 /2
:4
:1
P M
E-102
GROUND FLOOR OVERALL
ELECTRICAL PLAN
3 5JDM
SPS EQUIPMENT
INSTALLATION
DURHAM VA MEDICAL CENTER
508 FULTON ST.
DURHAM, NC 27705 OCTOBER 23, 2020
CONSTRUCTION DOCUMENTS
558-19-30219-181
JAV
N
KEY PLAN
SCALE: NO SCALE
AREA OF WORK
GROUND FLOOR
Scale: 1/8" = 1'-0"
GROUND FLOOR OVERALL ELECTRICAL PLAN 0 4 8 16
NORTH
PLAN
1 ELECTRICAL CLOSET FEEDING AREA OF
WORK. EXISTING PANELS AS NOTED. SEE
ENLARGEMENT THIS SHEET.
2 EXISTING TELECOM CLOSET. PULL NEW
FEEDS AS REQUIRED FROM THIS CLOSET.
OS
A
TOILET
FG314
STORAGE
FG312
ASSIST
FG311
CLERIC AL
FG309
NOURISH
FG331
PROCEDURE 3
FG313
PROCEDURE 2
FG315
SUPPLIES
FG310
PROCEDURE 4
FG308
OFFICE
FG316
PROCEDURE
FG165
GAS
FG189
OFFICE
FG172
NEW EXIT PASSAGEWAY
FG400C
CIRCULATION
FG300B
EXISTING
PANEL 'GN2'
EXISTING
PANEL 'GCR2'
EXISTING
PANEL 'GCR2A'3
('GN2'-6)
('GCR2'-5)
('GN2'-6)
('GCR2'-5)
A
SCOPE CLEAN
FG318
SCOPES SOIL
FG319
SOIL
FG317
('GCR2'-5)
B
(TYP)
A
('GN2'-6)
('GCR2'-5)
A
(TYP)
A
(TYP)
('GN2'-6)
('GCR2'-5)
('GN2'-6)
('GCR2'-5)
A A
A
TOILET
FG314
STORAGE
FG312
ASSIST
FG311
CLERIC AL
FG309
NOURISH
FG331
PROCEDURE 3
FG313
PROCEDURE 2
FG315
SUPPLIES
FG310
PROCEDURE 4
FG308
OFFICE
FG316
ANTE RM
FG317
PROCEDURE
FG165
GAS
FG189
OFFICE
FG172
NEW EXIT PASSAGEWAY
FG400C
CIRCULATION
FG300B
1 1
B
AA
SCOPES DECON.
FG318
SCOPES STAGING
FG319
EXISTING
PANEL 'GN2'
EXISTING
PANEL 'GCR2'
EXISTING
PANEL 'GCR2A'
A
A(F)
A(F) A(F)
('GCR2'-5)
('GCR2'-5)('GCR2'-5)
('GCR2'-5)('GCR2'-5)
G
C R
Engineers Architects
## KEY NOTES:
# KEY NOTES:
Revisions: Date
Drawing Title
Approved:
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
NOT FOR
CONSTRUCTIO
N
NOT FOR
CONSTRUCTIO
N
WALL RATING LEGEND
1 HR - FIRE BARRIER
2 HR - FIRE BARRIER
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
/2 /2
:4
:2
P M
EL101
PARTIAL GROUND FLOOR LIGHTING
PLAN
4 5JDM
SPS EQUIPMENT
INSTALLATION
DURHAM VA MEDICAL CENTER
508 FULTON ST.
DURHAM, NC 27705 OCTOBER 23, 2020
CONSTRUCTION DOCUMENTS
558-19-30219-181
JAV
N
KEY PLAN
SCALE: NO SCALE
AREA OF WORK
GROUND FLOOR
0 2 4 8
NORTH
PLAN
0 2 4 8
NORTH
PLAN
Scale: 1/4" = 1'-0"
GROUND FLOOR LIGHTING DEMOLITION PLAN
Scale: 1/4" = 1'-0"
PARTIAL GROUND FLOOR LIGHTING PLAN
1 REINSTALL EXISTING LUMINAIRE.
RECONNECT TO CIRCUIT RETAINED DURING
DEMOLITION.
2 PROVIDE LINE-VOLTAGE, PASSIVE INFRARED
WALL SWITCH OCCUPANCY SENSOR. BOD:
LUTRON MAESTRO.
A. ALL BRANCH CIRCUIT CONDUCTORS SHALL BE
2-12 AWG, 1-12 AWG EG IN 3/4" CONDUIT
UNLESS NOTED OTHERWISE.
B. COORDINATE ALL TIME DELAY, AUTO DIM,
PRESET DIMMING LEVELS, SENSOR
SENSITIVITY AND CONFIGURATIONS WITH THE
VA.
C. DEMOLISH ALL EXISTING ELECTRICAL
DEVICES AS SHOWN ON DEMOLITION PLAN
UNLESS NOTED OTHERWISE.
D. CONTRACTOR SHALL BE RESPONSIBLE FOR
TRACING AND IDENTIFYING ALL CIRCUITS AND
CONDUIT THAT ORIGINATE, PASS THROUGH,
OR TERMINATE IN THE AREA OF WORK.
DEMOLISH ALL CIRCUITS THAT ARE NO
LONGER IN USE. MAINTAIN CIRCUIT
CONTINUITY TO ALL CIRCUITS WHICH ARE NOT
COMPLETELY REMOVED.
E. COORDINATE ALL WORK IMPACTING AREAS
OUTSIDE AREA OF WORK WITH COR.
F. REFERENCE LUMINAIRE SCHEDULE ON E-001
FOR MORE INFO.
G. DEMOLITION SHALL INCLUDE BUT NOT BE
LIMITED TO THE DEVICES AND/OR SYSTEMS
SHOWN. COORDINATE WITH ARCHITECTURAL,
MECHANICAL, AND PLUMBING DEMOLITION
PLANS.
1 THE ELECTRICAL CONTRACTOR SHALL REMOVE
EXISTING LUMINAIRES FOR REUSE. CRITICAL
BRANCH CIRCUIT WIRING SHALL BE RETAINED.
NORMAL BRANCH CIRCUIT WIRING SHALL BE
REMOVED BACK TO LAST OPERABLE DEVICE,
FIXTURE OR PANELBOARD.
2 DISCONNECT AND REMOVE LIGHT SWITCH.
RETAIN WIRING, DEVICE BOX AND CONDUIT
FOR REUSE.
3 DEMO 3-WAY SWITCHES. DISCONNECT AND
REMOVE DEVICES, WIRING AND CONDUIT BACK
TO EXISTING JUNCTION BOX ABOVE CEILING.
4 CIRCULATION FG300B LIGHTING IS EXISTING TO
REMAIN, NOT IN CONTRACT.
(1) 4 PR UTP
TELEPHONE
CABLE/JACK
SINGLE GANG S.S.
COVER PLATE.
LOCATIONS AS SHOWN
ON PLANS.
WALL PHONE (TYP.) ( W)
DETAIL NOTES:
A. ALL EQUIPMENT AND INSTALLATION SHALL BE APPROVED BY VAMC IT DEPARTMENT.
(1) 4 PR UTP
DATA
CABLE/JACK
(1) 4 PR UTP
TELEPHONE
CABLE/JACK
1/2" HIGH BLACK LETTERS
ON CLEAR BACKGROUND,
PANDUIT OR EQUAL ON
PERMANENT LABEL,
TYPICAL.
XXX
XXX
B B
T T
BLANK
SINGLE GANG COVER
PLATE WITH 6 OUTLETS
(TYPICAL). LOCATIONS
AS SHOWN ON PLANS
TELE/DATA (TYP.) ( 4)
(1) 4 PR UTP
TELEPHONE
CABLE/JACK
C C
(1) 4 PR UTP
DATA CABLE/JACK
BLANK
(1) 4 PR UTP
DATA
CABLE/JACK
(1) 4 PR UTP
TELEPHONE
CABLE/JACK
1/2" HIGH BLACK LETTERS
ON CLEAR BACKGROUND,
PANDUIT OR EQUAL ON
PERMANENT LABEL,
TYPICAL.
XXX
XXX
B B
T B
BLANK
SINGLE GANG COVER
PLATE WITH 6 OUTLETS
(TYPICAL). LOCATIONS
AS SHOWN ON PLANS
TELE/DATA (TYP.) ( 2)
BLANK
C B
BLANK
BLANK
T
FINISHED FLOOR
MOUNTING HEIGHT AS
SHOWN IN DRAWINGS
4-11/16" SQ. BY 2-1/2"
DEEP BOX WITH SINGLE
GANG 5/8" TILE RING.
1-1/4" CONDUIT WITH
COMMUNICATIONS WIRING
WALL
CORRIDORROOM
6" MIN NYLON BUSHING
COORDINATE WITH DUCTWORK
EXTEND CONDUIT TO ABOVE
FINISHED ACCESSABLE
CEILING IN CORRIDOR TO
CABLE TRAY UNLESS NOTED
OTHERWISE.
SUSPENDED LAY-IN
CEILING
CABLE TRAY
Example: B01 F2 IT102 B A 02
BLDG # (IF APPLICABLE)
FLOOR # (IF APPLICABLE)
IT CLOSET #
IT CLOSET LOCATION (UNIT B)
PATCH PANEL #
PORT #
EXISTING PANEL
'GCR2'
120/208V
3PH, 4W
225A MLO
CRITICAL
EXISTING PANEL
'GN1A'
120/208V
3PH, 4W
225A MLO
NORMAL
EXISTING PANEL
'GN2A'
120/208V
3PH, 4W
225A MLO
NORMAL
EXISTING PANEL
'GN1'
120/208V
3PH, 4W
400A MCB
NORMAL
EXISTING PANEL
'GN2'
120/208V
3PH, 4W
225A MLO
NORMAL
EXISTING PANEL
'GCR2A'
120/208V
3PH, 4W
225A MLO
CRITICAL
EXISTING PANEL
'GCR1'
120/208V
3PH, 4W
225A MCB
CRITICAL
3-3 AWG, 1-3 AWG
NEUTRAL, 1-8 AWG
EGC IN 1 1/4" C. (EX)
3-3 AWG, 1-3 AWG
NEUTRAL, 1-8 AWG
EGC IN 1 1/4" C. (EX)
3-1/0 AWG, 1-1/0 AWG
NEUTRAL, 1-6 AWG
EGC IN 2" C. (EX)
150A
150A
100A
225A
100A 100A
400A
Engineers Architects
Revisions: Date
Drawing Title
Approved:
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
NOT FOR
CONSTRUCTIO
N
NOT FOR
CONSTRUCTIO
N
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/2 /2
:4
:1
P M
E-501
ELECTRICAL DETAILS
5 5JDM
SPS EQUIPMENT
INSTALLATION
DURHAM VA MEDICAL CENTER
508 FULTON ST.
DURHAM, NC 27705 OCTOBER 23, 2020
CONSTRUCTION DOCUMENTS
558-19-30219-181
JAV
Scale: N.T.S.
TELECOMMUNICATIONS FACEPLATES
Scale: N.T.S.
TELECOMMUNICATIONS OUTLET INSTALLATION
Scale: N.T.S.
JACK LABELING SCHEME
EX (GCR2)
(TOTAL KVA) X 1000 = TOTAL AMPS
VOLTS X 1.732 71
PANEL / FEEDER (TOTAL KVA) 25.54
TOTAL DEMAND AMPERES PER PHASE 72 74 67
TOTAL KVA PER PHASE 9.72 10.67 10.17 8.67 8.84 8.03
SIGN 0.00 0.00 0.00 125% 0.00 0.00 0.00
DEDICATED 4.68 4.14 3.78 65% 3.04 2.69 2.46
NEUTRAL RATING 100% FIX. ELEC. SPACE HEAT 0.00 0.00 0.00 100% 0.00 0.00 0.00
BUS RATING 225A WATER HEATERS 0.08 0.00 0.00 125% 0.10 0.00 0.00
MCB RATING MLO ALL OTHERS 0.08 1.69 1.77 65% 0.05 1.10 1.15
MINIMUM AIC (K AMPS) 22 MOTORS AND
EQUIPMENT
LARGEST 0.00 0.00 0.00 125% 0.00 0.00 0.00
SERVICE ENTR. RATED YES X NO >10KVA@50% -0.13 0.11 0.35
MAIN CIRCUIT BREAKER YES X NO GENERAL USE
RECEPT
3.06 3.56 4.02
<=10 KVA@100% 3.33 3.33 3.33
ISOLATED GROUND BUS YES X NO GENERAL LIGHTING 1.82 1.28 0.60 125% 2.28 1.60 0.75
MOUNTING SURFACE A B C A B C
C/B TEMP. 75 C. RATING 120 208 V 3 PH 4 WIRE
LOAD TYPE
CONNECTED KVA NEC DEM
FACTOR
DEMAND KVA
10.84 10.67 11.37 TOTAL
SUB TOTAL 8.30 6.86 6.18 2.54 3.81 5.19 SUB TOTAL
--- --- 3.78 41 42 --- --- 1.69
(EX) GCR2A --- 4.14 --- 3P-100 39 40
2P-25
--- 1.69 --- CU-2
4.68 --- --- 37 38 0.08 --- ---
(EX)RECEPT --- --- 0.18 1P-20 35 36
2P-15
--- --- 0.08 DSU-2
(EX)RECEPT --- 0.18 --- 1P-20 33 34 1P-20 --- 0.00 --- SPARE
(EX)RECEPT 0.54 --- --- 1P-20 31 32 1P-20 1.20 --- --- MEDIVATOR FG318
(EX)RECEPT --- --- 0.36 1P-20 29 30 1P-20 --- --- 1.20 MEDIVATOR FG318
(EX)RECEPT --- 0.18 --- 1P-20 27 28 1P-20 --- 0.50 --- (EX) NURSE CALL SYST
(EX)RECEPT 0.18 --- --- 1P-20 25 26 1P-20 0.18 --- --- (EX)RECEPT
(EX)RECEPT --- --- 0.18 1P-20 23 24 1P-20 --- --- 0.72 (EX)RECEPT
(EX)RECEPT --- 0.18 --- 1P-20 21 22 1P-20 --- 0.72 --- (EX)RECEPT
(EX)RECEPT 0.18 --- --- 1P-20 19 20 1P-20 0.18 --- --- (EX)RECEPT
(EX)RECEPT --- --- 0.18 1P-20 17 18 1P-20 --- --- 0.60 RECEPT GI SCOPE FG319
(EX)RECEPT --- 0.18 --- 1P-20 15 16 1P-20 --- 0.54 --- RECEPT GI SCOPE FG318
(EX)RECEPT 0.90 --- --- 1P-20 13 14 1P-20 0.54 --- --- (EX)RECEPT
(EX)RECEPT --- --- 0.90 1P-20 11 12 1P-20 --- --- 0.72 (EX)RECEPT
(EX)RECEPT --- 0.72 --- 1P-20 9 10 1P-20 --- 0.18 --- (EX)RECEPT
(EX) LTG 0.38 --- --- 1P-20 7 8 1P-20 0.18 --- --- (EX)RECEPT
LTG FG317, FG318, FG319 --- --- 0.60 1P-20 5 6 1P-20 --- --- 0.18 (EX)RECEPT
(EX) LTG --- 1.28 --- 1P-20 3 4 1P-20 --- 0.18 --- (EX)RECEPT
(EX) LTG 1.44 --- --- 1P-20 1 2 1P-20 0.18 --- --- (EX)RECEPT
A B C A B C
LOAD SERVED
KVA / Phase
CKT
BRKR
CKT
NO
NEUTRAL
A B C
CKT
NO
CKT
BRKR
KVA / Phase
LOAD SERVED
EX (GN1A)
(TOTAL KVA) X 1000 = TOTAL AMPS
VOLTS X 1.732 53
PANEL / FEEDER (TOTAL KVA) 19.00
TOTAL DEMAND AMPERES PER PHASE 61 50 47
TOTAL KVA PER PHASE 8.26 7.00 6.38 7.37 6.01 5.62
SIGN 0.00 0.00 0.00 125% 0.00 0.00 0.00
DEDICATED 0.00 0.00 0.00 65% 0.00 0.00 0.00
NEUTRAL RATING 100% FIX. ELEC. SPACE HEAT 0.00 0.00 0.00 100% 0.00 0.00 0.00
BUS RATING 225A WATER HEATERS 0.00 0.00 0.00 125% 0.00 0.00 0.00
MCB RATING MLO ALL OTHERS 1.50 2.00 1.50 65% 0.98 1.30 0.98
MINIMUM AIC (K AMPS) 22 MOTORS AND
EQUIPMENT
LARGEST 0.00 0.00 0.00 125% 0.00 0.00 0.00
SERVICE ENTR. RATED YES X NO >10KVA@50% 0.82 0.48 0.42
MAIN CIRCUIT BREAKER YES X NO GENERAL USE
RECEPT
4.96 4.28 4.16
<=10 KVA@100% 3.33 3.33 3.33
ISOLATED GROUND BUS YES X NO GENERAL LIGHTING 1.80 0.72 0.72 125% 2.25 0.90 0.90
MOUNTING SURFACE A B C A B C
C/B TEMP. 75 C. RATING 120 208 V 3 PH 4 WIRE
LOAD TYPE
CONNECTED KVA NEC DEM
FACTOR
DEMAND KVA
7.06 7.48 5.66 TOTAL
SUB TOTAL 3.96 4.76 2.88 3.10 2.72 2.78 SUB TOTAL
SPARE --- --- 0.00 1P-20 41 42 1P-20 --- --- 0.00 SPARE
SPARE --- 0.00 --- 1P-20 39 40 1P-20 --- 0.00 --- SPARE
SPARE 0.00 --- --- 1P-20 37 38 1P-20 0.00 --- --- SPARE
SPARE --- --- 0.00 1P-20 35 36 1P-20 --- --- 0.00 SPARE
MEDIVATOR --- 1.20 --- 1P-20 33 34 1P-20 --- 0.00 --- SPARE
SPARE 0.00 --- --- 1P-20 31 32 1P-20 0.00 --- --- SPARE
SPARE --- --- 0.00 1P-20 29 30 1P-20 --- --- 0.00 SPARE
(EX)MAG LOCKS --- 0.50 --- 1P-20 27 28 1P-20 --- 0.50 --- (EX)AUTO DOORS
(EX)RECEPT 0.72 --- --- 1P-20 25 26 1P-20 0.50 --- --- AUTO DOORS
(EX)RECEPT --- --- 0.72 1P-20 23 24 1P-20 --- --- 0.50 AUTO DOORS
(EX)RECEPT --- 0.90 --- 1P-20 21 22 1P-20 --- 0.50 --- (EX)AUTO DOORS
(EX)RECEPT 0.72 --- --- 1P-20 19 20 1P-20 0.50 --- --- (EX)AUTO DOORS
(EX)RECEPT --- --- 0.72 1P-20 17 18 1P-20 --- --- 0.50 (EX)AUTO DOORS
(EX)RECEPT --- 0.72 --- 1P-20 15 16 1P-20 --- 0.50 --- (EX)AUTO DOORS
(EX)RECEPT 0.72 --- --- 1P-20 13 14 1P-20 0.50 --- --- (EX)AUTO DOORS
(EX)RECEPT --- --- 0.72 1P-20 11 12 1P-20 --- --- 0.50 (EX)AUTO DOORS
(EX)RECEPT --- 0.72 --- 1P-20 9 10 1P-20 --- 0.50 --- (EX)AUTO DOORS
(EX)RECEPT 0.72 --- --- 1P-20 7 8 1P-20 1.00 --- --- (EX)DOOR HOLDERS
(EX)RECEPT --- --- 0.72 1P-20 5 6 1P-20 --- --- 1.28 (EX)RECEPT
(EX)RECEPT --- 0.72 --- 1P-20 3 4 1P-20 --- 0.72 --- (EX)RECEPT
(EX)RECEPT 1.08 --- --- 1P-20 1 2 1P-20 0.60 --- --- (EX)VAV BOXES
A B C A B C
LOAD SERVED
KVA / Phase
CKT
BRKR
CKT
NO
NEUTRAL
A B C
CKT
NO
CKT
BRKR
KVA / Phase
LOAD SERVED
EX (GN2A)
(TOTAL KVA) X 1000 = TOTAL AMPS
VOLTS X 1.732 47
PANEL / FEEDER (TOTAL KVA) 16.78
TOTAL DEMAND AMPERES PER PHASE 51 38 52
TOTAL KVA PER PHASE 8.44 5.66 9.00 6.07 4.52 6.19
SIGN 0.00 0.00 0.00 125% 0.00 0.00 0.00
DEDICATED 1.20 0.18 0.18 65% 0.78 0.12 0.12
NEUTRAL RATING 100% FIX. ELEC. SPACE HEAT 0.00 0.00 0.00 100% 0.00 0.00 0.00
BUS RATING 225A WATER HEATERS 0.00 0.00 0.00 125% 0.00 0.00 0.00
MCB RATING MLO ALL OTHERS 0.00 0.00 0.00 65% 0.00 0.00 0.00
MINIMUM AIC (K AMPS) 22 MOTORS AND
EQUIPMENT
LARGEST 0.00 0.00 0.00 125% 0.00 0.00 0.00
SERVICE ENTR. RATED YES X NO >10KVA@50% 1.96 1.08 2.75
MAIN CIRCUIT BREAKER YES X NO GENERAL USE
RECEPT
7.24 5.48 8.82
<=10 KVA@100% 3.33 3.33 3.33
ISOLATED GROUND BUS YES X NO GENERAL LIGHTING 0.00 0.00 0.00 125% 0.00 0.00 0.00
MOUNTING SURFACE A B C A B C
C/B TEMP. 75 C. RATING 120 208 V 3 PH 4 WIRE
LOAD TYPE
CONNECTED KVA NEC DEM
FACTOR
DEMAND KVA
7.24 5.48 8.82 TOTAL
SUB TOTAL 3.18 1.88 4.22 4.06 3.60 4.60 SUB TOTAL
(EX)CONTROLS --- --- 0.18 1P-20 41 42 1P-20 --- --- 1.00 (EX)MAG LOCKS
(EX)CONTROLS --- 0.18 --- 1P-20 39 40 1P-20 --- 0.54 --- (EX)RECEPT
RECEPT FG317, FG316, FG314 1.20 --- --- 1P-20 37 38 1P-20 0.54 --- --- (EX)RECEPT
RECEPT FG318 --- --- 1.70 1P-20 35 36 1P-20 --- --- 0.54 (EX)RECEPT
RECEPT FG319 --- 0.80 --- 1P-20 33 34 1P-20 --- 0.54 --- (EX)RECEPT
(EX)RECEPT 0.72 --- --- 1P-20 31 32 1P-20 0.54 --- --- (EX)RECEPT
(EX)RECEPT --- --- 1.26 1P-20 29 30 1P-20 --- --- 0.54 (EX)RECEPT
(EX)RECEPT --- 0.18 --- 1P-20 27 28 1P-20 --- 0.54 --- (EX)RECEPT
(EX)RECEPT 0.18 --- --- 1P-20 25 26 1P-20 0.54 --- --- (EX)RECEPT
(EX)RECEPT --- --- 0.18 1P-20 23 24 1P-20 --- --- 0.54 (EX)RECEPT
(EX)RECEPT --- 0.18 --- 1P-20 21 22 1P-20 --- 0.54 --- (EX)RECEPT
(EX)RECEPT 0.18 --- --- 1P-20 19 20 1P-20 1.00 --- --- (EX)RECEPT
(EX)RECEPT --- --- 0.18 1P-20 17 18 1P-20 --- --- 0.54 (EX)RECEPT
(EX)RECEPT --- 0.18 --- 1P-20 15 16 1P-20 --- 0.54 --- (EX)RECEPT
(EX)RECEPT 0.54 --- --- 1P-20 13 14 1P-20 0.54 --- --- (EX)RECEPT
(EX)RECEPT --- --- 0.54 1P-20 11 12 1P-20 --- --- 0.72 (EX)RECEPT
(EX)RECEPT --- 0.18 --- 1P-20 9 10 1P-20 --- 0.54 --- (EX)RECEPT
(EX)RECEPT 0.18 --- --- 1P-20 7 8 1P-20 0.54 --- --- (EX)RECEPT
(EX)RECEPT --- --- 0.18 1P-20 5 6 1P-20 --- --- 0.72 (EX)RECEPT
(EX)RECEPT --- 0.18 --- 1P-20 3 4 1P-20 --- 0.36 --- (EX)RECEPT
(EX)RECEPT 0.18 --- --- 1P-20 1 2 1P-20 0.36 --- --- (EX)RECEPT
A B C A B C
LOAD SERVED
KVA / Phase
CKT
BRKR
CKT
NO
NEUTRAL
A B C
CKT
NO
CKT
BRKR
KVA / Phase
LOAD SERVED
Scale: No Scale
PARTIAL SINGLE LINE DIAGRAM
EX (GN2)
(TOTAL KVA) X 1000 = TOTAL AMPS
VOLTS X 1.732 118
PANEL / FEEDER (TOTAL KVA) 42.50
TOTAL DEMAND AMPERES PER PHASE 122 106 126
TOTAL KVA PER PHASE 24.04 20.77 25.16 14.59 12.73 15.17
SIGN 0.00 0.00 0.00 125% 0.00 0.00 0.00
DEDICATED 6.07 4.52 6.19 65% 3.94 2.94 4.02
NEUTRAL RATING 100% FIX. ELEC. SPACE HEAT 0.00 0.00 0.00 100% 0.00 0.00 0.00
BUS RATING 225A WATER HEATERS 0.00 0.00 0.00 125% 0.00 0.00 0.00
MCB RATING MLO ALL OTHERS 0.00 0.00 0.00 65% 0.00 0.00 0.00
MINIMUM AIC (K AMPS) 22 MOTORS AND
EQUIPMENT
LARGEST 0.00 0.00 0.00 125% 0.00 0.00 0.00
SERVICE ENTR. RATED YES X NO >10KVA@50% 7.32 6.46 7.82
MAIN CIRCUIT BREAKER YES X NO GENERAL USE
RECEPT
17.97 16.25 18.96
<=10 KVA@100% 3.33 3.33 3.33
ISOLATED GROUND BUS YES X NO GENERAL LIGHTING 0.00 0.00 0.00 125% 0.00 0.00 0.00
MOUNTING SURFACE A B C A B C
C/B TEMP. 75 C. RATING 120 208 V 3 PH 4 WIRE
LOAD TYPE
CONNECTED KVA NEC DEM
FACTOR
DEMAND KVA
17.97 16.25 18.96 TOTAL
SUB TOTAL 10.49 9.30 10.47 7.49 6.95 8.49 SUB TOTAL
--- --- 6.19 41 42 1P-20 --- --- 1.44 (EX)RECEPT
--- 4.52 --- 39 40 1P-20 --- 1.44 --- (EX)RECEPTPANEL "GN2A"
6.07 --- ---
3P-100
37 38 1P-20 1.44 --- --- (EX)RECEPT
(EX)RECEPT --- --- 0.54 1P-20 35 36 1P-20 --- --- 1.08 (EX)RECEPT
(EX)MAGLOCKS --- 1.00 --- 1P-20 33 34 1P-20 --- 0.90 --- (EX)RECEPT
SPARE 0.00 --- --- 1P-20 31 32 1P-20 0.72 --- --- (EX)RECEPT
SPARE --- --- 0.00 1P-20 29 30 1P-20 --- --- 1.44 (EX)RECEPT
SPARE --- 0.00 --- 1P-20 27 28 1P-20 --- 1.44 --- (EX)RECEPT
SPARE 0.00 --- --- 1P-20 25 26 1P-20 1.44 --- --- (EX)RECEPT
(EX)MAGLOCKS --- --- 0.50 1P-20 23 24 1P-20 --- --- 0.80 (EX)VAV BOXES
(EX)RECEPT --- 0.36 --- 1P-20 21 22 1P-20 --- 0.80 --- (EX)VAV BOXES
(EX)DOOR HOLDERS 1.00 --- --- 1P-20 19 20 1P-20 0.80 --- --- (EX)VAV BOXES
(EX)RECEPT --- --- 0.90 1P-20 17 18 1P-20 --- --- 0.80 (EX)VAV BOXES
(EX)RECEPT --- 1.62 --- 1P-20 15 16 1P-20 --- 0.80 --- (EX)VAV BOXES
(EX)RECEPT 1.44 --- --- 1P-20 13 14 1P-20 0.36 --- --- (EX)ROOFTOP RECEPT
(EX)RECEPT --- --- 1.08 1P-20 11 12 1P-20 --- --- 1.40 (EX)EF-1, EF-3
(EX)RECEPT --- 0.90 --- 1P-20 9 10 1P-20 --- 1.57 --- (EX)LIGHTS
(EX)RECEPT 1.08 --- --- 1P-20 7 8 1P-20 1.34 --- --- (EX)LIGHTS
(EX)RECEPT --- --- 1.26 1P-20 5 6 1P-20 --- --- 1.54 (EX)LIGHTS
(EX)RECEPT --- 0.90 --- 1P-20 3 4 1P-20 --- 1,41 --- (EX)LIGHTS
(EX)RECEPT 0.90 --- --- 1P-20 1 2 1P-20 1.39 --- --- (EX)LIGHTS
A B C A B C
LOAD SERVED
KVA / Phase
CKT
BRKR
CKT
NO
NEUTRAL
A B C
CKT
NO
CKT
BRKR
KVA / Phase
LOAD SERVED
EX (GCR1)
(TOTAL KVA) X 1000 = TOTAL AMPS
VOLTS X 1.732 178
PANEL / FEEDER (TOTAL KVA) 64.10
TOTAL DEMAND AMPERES PER PHASE 259 130 145
TOTAL KVA PER PHASE 34.87 21.74 24.70 31.02 15.66 17.42
SIGN 0.00 0.00 0.00 125% 0.00 0.00 0.00
DEDICATED 9.64 10.67 10.81 65% 6.27 6.94 7.03
NEUTRAL RATING 100% FIX. ELEC. SPACE HEAT 0.00 0.00 0.00 100% 0.00 0.00 0.00
BUS RATING 225A WATER HEATERS 10.56 0.00 0.00 125% 13.20 0.00 0.00
MCB RATING 225A ALL OTHERS 10.56 7.72 10.92 65% 6.86 5.02 7.10
MINIMUM AIC (K AMPS) 22 MOTORS AND
EQUIPMENT
LARGEST 0.00 0.00 0.00 125% 0.00 0.00 0.00
SERVICE ENTR. RATED YES X NO >10KVA@50% 0.00 0.00 0.00
MAIN CIRCUIT BREAKER X YES NO GENERAL USE
RECEPT
1.77 1.90 1.69
<=10 KVA@100% 1.77 1.90 1.69
ISOLATED GROUND BUS YES X NO GENERAL LIGHTING 2.34 1.44 1.28 125% 2.92 1.80 1.60
MOUNTING SURFACE A B C A B C
C/B TEMP. 75 C. RATING 120 208 V 3 PH 4 WIRE
LOAD TYPE
CONNECTED KVA NEC DEM
FACT…