Attachment C - Drawing 19-181 Architectural .pdf
PDF 2 MB Posted
- Attached to
- Z2DZ--GI SPS Equipment Site Prep Federal contract opportunity
- Solicitation number
- 36C24621R0087
About this file
This notice is for a federal contract opportunity for site preparation work at the Durham VA Medical Center in Durham, North Carolina. The contract is for renovations to the Gastrointestinal Sterile Processing Section in Building 1 of the medical center, with an estimated value between $500,000 and $1 million. The work includes renovation of existing spaces. The solicitation is anticipated to be a total service-disabled veteran-owned small business set-aside. The solicitation will be issued on or around June 1, 2021 and posted to the website listed. Proposals will be due approximately 30 days after issuance. A site visit date will be specified in the solicitation. Interested vendors should register on the website and monitor for any amendments to the solicitation. Registration in SAM and VetBiz is required for award eligibility. Questions must be submitted by email to the point of contact provided.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C24621R0087 0001.docx | DOCX document | |
| Attachment K - Past Performance Questionnaire.docx | DOCX document | |
| Attachment E - Drawing 19-181 Fire Suppression .pdf | ||
| Attachment D - Drawing 19-181 Electrical .pdf | ||
| 36C24621R0087_1.docx | DOCX document | |
| Attachment B - Drawing 19-181 General .pdf | ||
| 36C24621R0087_1.pdf | ||
| Attachment H - Wage Determination NC20210028 01_01_2021.pdf | ||
| Attachment F - Drawing 19-181 Mechanical .pdf | ||
| Attachment J - Corp Experience Form.docx | DOCX document | |
| Attachment I - Base Proposal Item Price Breakdown.xlsx | XLSX spreadsheet | |
| Attachment G - Drawing 19-181 Plumbing .pdf | ||
| Attachment A - Combined Specs .pdf |
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AFF ABOVE FINISHED FLOOR
ACP/APC ACOUSTIC CEILING PANEL/
ACOUSTIC PANEL CEILING
ACT ACOUSTIC(AL) TILE
ADJ ADJUSTABLE
ADT'L ADDITIONAL
AGG AGGREGATE
ALT ALTERNATE
AL ALUMINUM
APPROX APPROXIMATE(LY)
ASPH ASPHALT
AUTO AUTOMATIC
B/O BOTTOM OF
BD BOARD
BLDG BUILDING
BLKG BLOCKING
BOT BOTTOM
BRG BEARING
CENTERLINE
C/C CENTER TO CENTER
CJ CONTROL JOINT
CLL CONTRACT LIMIT LINE
CEM CEMENT(ITIOUS)
CMU CONCRETE MASONRY UNIT
CLG CEILING
CLR CLEAR
COL COLUMN
CONC CONCRETE
CONST CONSTRUCTION
CONT CONTINUOUS
CPT CARPET
CT CERAMIC TILE
CTR CENTER(ED)
DF DRINKING FOUNTAIN
DS DOWNSPOUT
DBL DOUBLE
DEG DEGREE
DEMO DEMOLITION
DET/DTL DETAIL
DIA DIAMETER
DIM DIMENSION
DN DOWN
DWG(S) DRAWING(S)
E EAST
EC ELECTRICAL CONTRACTOR
EHO ELECTRICAL HOLD OPEN
EJ EXPANSION JOINT
EW EACH WAY
EA EACH
EIFS EXTERIOR INSULATION
FINISH SYSTEM
EL ELEVATION
ELEC ELECTRIC(AL)
ELEV ELEVATOR
EMER EMERGENCY
EQ EQUAL
EQUIP EQUIPMENT
EXIST EXISTING
EXT EXTERIOR
EWC ELECTRIC WATER COOLER
FD FLOOR DRAIN
FE FIRE EXTINGUISHER
FFE FINISH FLOOR ELEVATION
FV FIELD VERIFY
FEC FIRE EXTINGUISHER CABINET
FDN FOUNDATION
FIN FINISH
FLSHG FLASHING
FLR FLOOR
FRMG FRAMING
FT FOOT/FEET
FTG FOOTING
GC GENERAL CONTRACTOR
GA GAUGE
GALV GALVANIZED
GEN GENERAL
GYP GYPSUM
HM HOLLOW METAL
HDWR HARDWARE
HOL HOLLOW
HOR HORIZONTAL
HT HEIGHT
HVAC HEATING/VENTILATION/AIR
CONDITIONING
IDPH ILLINOIS DEPARTMENT OF
PUBLIC HEALTH
ID INSIDE DIAMETER
IN INCH
INCL INCLUDING
INSUL INSULATION
INT INTERIOR
JAN JANITOR
JT JOINT
LAV LAVATORY
LB(S) POUND(S)
L/S LANDSCAPE
LT LIGHT
MO MASONRY OPENING
MAS MASONRY
MAT'L MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MTD MOUNTED
MTL METAL
N NORTH
NIC NOT IN CONTRACT
NTS NOT TO SCALE
NOM NOMINAL
OC ON CENTER
OD OUTSIDE DIAMETER
O TO O OUT TO OUT
OPNG OPENING
OPP OPPOSITE
OVHD OVERHEAD
PEB PRE-ENGINEERED BUILDING
PJF PREFORMED JOINT FILLER
PT PRESSURE TREATED
PERIM PERIMETER
PL PLATE
PLAM PLASTIC LAMINATE
PLBG PLUMBING
PLYWD PLYWOOD
PNT PAINT
PR PAIR
PTD PAINTED
PWR POWER
RB RUBBER BASE
RD ROOF DRAIN
RO ROUGH OPENING
RAD RADIUS
REC RECESSED
REINF REINFORCED
REQ'D REQUIRED
REV REVISED (REVISION)
RM ROOM
S SOUTH
SB SPLASH BLOCK
SF SQUARE FEET
SS STAINLESS STEEL
SIM SIMILAR
SPEC SPECIFICATIONS
SQ SQUARE
STD STANDARD
STL STEEL
STOR STORAGE
STRUCT STRUCTURAL
SUSP SUSPENDED
T&G TONGUE AND GROOVE
T/O TOP OF
TELE TELEPHONE
TRTD TREATED
TS TUBE STEEL
TYP TYPICAL
UNFIN UNFINISHED
UNO UNLESS NOTED OTHERWISE
VCT VINYL COMPOSITION TILE
VIF VERIFY IN FIELD
VERT VERTICAL
W WEST
W/ WITH
W/O WITHOUT
WC WATER CLOSET
WWF WELDED WIRE FABRIC
WD WOOD
WH WATER HEATER
WT WEIGHT
CL
DEMOLITION KEYNOTE WINDOW TYPE
ROOF PITCH SYMBOLDOOR NUMBER
TYPICAL KEYNOTE CEILING/ SOFFIT
HEIGHT
MATL
1'-0"
-1
# 1 PARTITION TYPE SYMBOL
GENERAL NOTES
1. INDICATIONS OF PROJECT LIMITS OR LINES OF DEMARCATION ARE SHOWN FOR GENERAL SCOPE DEFINITION AND REFLECT THE UNDERSTANDING OF THE DESIGNER AS TO THE LIMITATIONS OF THE WORK AREA IN AN OCCUPIED AREA. ACTUAL CONTRACT LIMITS ARE TO BE DETERMINED BY AGREEMENT BETWEEN THE COR AND CONTRACTOR BEFORE THE
START OF THE WORK.
2. DETAILS FOR SPECIFIC PRODUCTS MAY CHANGE BEFORE THEY ARE ACTUALLY INCORPORATED INTO THE WORK, AND PRODUCTS BY OTHER MANUFACTURERS ARE ALSO ACCEPTABLE. THEREFORE, ACTUAL INSTALLATION DETAILS AND DIMENSIONS MAY DIFFER FROM THOSE SHOWN. CONTRACTOR SHALL VERIFY INSTALLATION REQUIREMENTS FOR ALL PRODUCTS TO BE INCORPORATED IN THE WORK (INCLUDING THICKNESS FOR RECESSED OR SEMI-RECESSED PRODUCTS) AND IS RESPONSIBLE FOR ACCOMMODATING AND COORDINATING CHANGES TO OTHER MATERIALS OR PRODUCTS THAT ARE NECESSARY BECAUSE OF THESE DIFFERENCES.
3. THE DRAWINGS AND SPECIFICATIONS ARE SEPARATED INTO DISCIPLINES FOR CONVENIENCE. THE SEPARATIONS USED ARE USED ONLY FOR THE PURPOSES OF CONVENIENCE AND REFERENCE AND IN NO WAY DO THEY DEFINE OR LIMIT THE SCOPE OR INTENT OF ANY PART OF THE DRAWINGS, OR OF THE DRAWINGS AND SPECIFICATIONS AS A WHOLE. THE
WORK IS TO BE CONSTRUCTED AS A COMPLETE, INTEGRATED AND UNIFIED WHOLE.
4. THE DRAWINGS AND SPECIFICATIONS, INCLUDING DRAWINGS PREPARED BY SPECIFIC ENGINEERING DISCIPLINES ARE COMPLEMENTARY; ITEMS SHOWN IN ANY ONE LOCATION IN THE DRAWINGS SHALL BE CONSIDERED TO BE REQUIREMENTS OF THE CONTRACT FOR CONSTRUCTION. IN THE EVENT OF AN INCONSISTENCY BETWEEN THE DRAWINGS AND SPECIFICATIONS, OR WITHIN EITHER DOCUMENT, THE CONTRACTOR SHALL SEEK CLARIFICATION OR INTERPRETATION FROM THE A/E AND C.O.R. PRIOR TO BIDDING. WHERE INCONSISTENCIES ARE NOT CLARIFIED PRIOR TO BIDDING, AND WHERE THE ACTUAL SOLUTION OR INTENT CANNOT BE REASONABLY INFERRED, THE CONTRACTOR SHALL PROVIDE
THE BETTER QUALITY OR GREATER QUANTITY OF WORK.
5. USE OF THE WORD "VERIFY" POINTS OUT A SITUATION WHICH MUST BE CONFIRMED PRIOR TO PROCEEDING WITH THE WORK, FABRICATION OF EQUIPMENT, OR ORDERING MATERIAL.
NOTIFY THE C.O.R OF ANY DISCREPANCY DISCOVERED.
6. THE CONTRACTOR SHALL NOTIFY THE COR IMMEDIATELY SHOULD DISCREPANCIES BE FOUND IN THE DRAWINGS AND SPECIFICATIONS.
7. THE CONTRACTOR IS RESPONSIBLE FOR CHECKING ALL FIELD CONDITIONS AND DIMENSIONS AS THEY RELATE TO THIS PROJECT. SHOULD DISCREPANCIES EXIST BETWEEN THE WORK INDICATED AND ACTUAL FIELD CONDITIONS NOTIFY THE COR PRIOR TO PROCEEDING WITH THE WORK.
8. COORDINATE WORK OF ALL TRADES PRIOR TO STARTING CONSTRUCTION.
9. THE CONTRACTOR AND SUBCONTRACTORS INVOLVED IN THIS PROJECT SHALL BE RESPONSIBLE FOR DESIGNING AND INSTALLING THEIR RESPECTIVE WORK AND SYSTEMS TO MEET ALL APPLICABLE FEDERAL, STATE, AND LOCAL CODES, LAWS, SAFETY REGULATIONS, HAZARDOUS WASTE LAWS, ETC. THE CONTRACTOR SHALL FURNISH ALL NECESSARY PERMITS.
10. THE CONTRACTOR SHALL REVIEW THE DRAWINGS AND UNDERSTAND THE SCOPE OF THE WORK TO BE THE FOLLOWING: THESE CONSTRUCTION DOCUMENTS (DRAWINGS, SPECIFICATIONS, ADDENDA, ETC.) INDICATE THE GENERAL SCOPE OF THE PROJECT IN TERMS OF ARCHITECTURAL DESIGN CONCEPTS, THE DIMENSIONS OF THE BUILDING, THE MAJOR ARCHITECTURAL ELEMENTS, AND THE MAJOR STRUCTURAL, MECHANICAL, ELECTRICAL, AND DATA SYSTEMS. THE DOCUMENTS DO NOT AND ARE NOT INTENDED TO INDICATE OR DESCRIBE IN DETAIL ALL THE NECESSARY WORK REQUIRED FOR FULL PERFORMANCE OF, AND COMPLETION OF THE REQUIREMENTS OF THE CONTRACT. ON THE BASIS OF THE GENERAL SCOPE INDICATED IN THESE DOCUMENTS, THE TRADE CONTRACTORS SHALL FURNISH ALL ITEMS REQUIRED FOR THE PROPER EXECUTION AND COMPLETION OF THEIR WORK. ALL WORK SHALL BE COMPLETE IN EVERY DETAIL AND THE CONTRACTORS SHALL PROVIDE A ONE YEAR WARRANTY FOR THEIR WORK UNLESS A LONGER WARRANTY
IS INDICATED IN THE SPECIFICATIONS.
11. CONTRACTORS SHALL FOLLOW AND OBEY ALL FEDERAL, STATE AND LOCAL CODES, LAWS, SAFETY REGULATIONS AND HAZARDOUS WASTE LAWS, ETC.
GENERAL DEMOLITION NOTES
1. KEY NOTES AND DRAWINGS ARE INTENDED TO GRAPHICALLY REPRESENT GENERAL WORK AND DO NOT PORTRAY FULL SCOPE OF THE PROJECT.
SEE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
2. REMOVE EXISTING CONSTRUCTION AS DESIGNATED HEREIN AND CLEAR AREA OF DEBRIS PRIOR TO PROCEEDING WITH NEW CONSTRUCTION.
3. EXISTING EQUIPMENT REMOVED SHALL BE PROPERLY DISPOSED OFF MEDICAL CENTER GROUNDS.
4. ANY PATCHED WALL OPENINGS SHALL MATCH THE INTEGRITY OF ADJACENT CONSTRUCTION UNLESS INDICATED OTHERWISE.
5. NOTIFY COR OF ANY DEMOLITION REQUIRED AND NOT INDICATED FOR INSTALLATION OF ELECTRICAL OR DATA ITEMS. AFTER SUCH DEMOLITION AND
INSTALLATION, PATCH OR REPLACE MATERIALS AND FINISHES TO MATCH EXISTING.
6. THE INFORMATION CONTAINED IN THESE DEMOLITION DOCUMENTS DEFINES GENERAL SCOPE ONLY AND DOES NOT RELIEVE THE CONTRACTOR OF THE RESPONSIBILITY OF PROVIDING ALL DEMOLITION REQUIRED FOR THE COMPLETION OF THE PROJECT.
7. REFER TO THE ELECTRICAL DRAWINGS FOR FURTHER INFORMATION REGARDING DEMOLITION OF ELECTRICAL SYSTEMS.
8. BEFORE THE START OF WORK, IDENTIFY ANY REQUIRED DEMOLITION BEYOND THE IDENTIFIED PROJECT SCOPE WHETHER ABOVE, BELOW OR OUTSIDE PROJECT AREA. NOTIFY AND COORDINATE WITH THE C.O.R., PROVIDE DEMOLITION OF THESE AREAS AND PATCH THE SAME AS A PART OF
THE SCOPE OF THE PROJECT.
9. ALL DEMOLITION WORK SHALL BE PERFORMED WITH DUE CARE AND DILIGENCE IN ORDER TO PREVENT ARBITRARY DAMAGE OR INTERRUPTION OF SERVICE OR CONCEALED UTILITIES INTENDED TO REMAIN IN SERVICE. DISCOVERY OF UTILITIES OR CONDITIONS LOCATED DIFFERENTLY FROM THAT
INDICATED OR THAT ARE NOT IDENTIFIED. SHALL BE REPORTED TO THE C.O.R.
WALL SECTION
SYMBOL
INTERIOR ELEVATION
SYMBOL
COLUMN GRID
ELEVATION SYMBOL
REVISION NOTE
ENLARGED DETAIL CALLOUT
ROOM DESIGNATION
SYMBOL
BREAK LINE
ROOF SLOPE
DIRECTION SYMBOL
TYPICAL GRAPHIC SCALE
DETAIL #
PAGE #
DETAIL #
PAGE #
TRUE NORTH ARROW
PROJECT NORTH ARROW
A8.1
EXTERIOR ELEVATION
SYMBOL
DETAIL #
PAGE #
A8.1
A8.1
A8.1
BUILDING SECTION
SYMBOL
DETAIL #
PAGE #
A8.1
A8.1
DETAIL SECTION
SYMBOL
DETAIL #
PAGE #
A8.1
WALL GRID
(REPRESENTS
FACE OF EXISTING
WALL)
XX.X
XX.X
ELEVATION
0'-0"
ROOM
NAME
101A
NORTH
PLAN
NORTH
TRUE
0 4 8 16
Engineers Architects
Revisions: Date
Drawing Title
Approved:
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
NOT FOR
CONSTRUCTIO
N
NOT FOR
CONSTRUCTIO
N
WALL RATING LEGEND
1 HR - FIRE BARRIER
2 HR - FIRE BARRIER
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
/2 /2
:3
:0
P M
A-001
ARCHITECTURAL SYMBOLS,
ABBREVIATIONS AND NOTES
1 3EJD
SPS GI EQUIPMENT INSTALL
DURHAM VA MEDICAL CENTER
508 FULTON ST.
DURHAM, NC 27705 OCTOBER 23, 2020
CONSTRUCTION DOCUMENTS
558-19-30219-181
WVS
ABBREVIATIONS
ARCHITECTURAL SYMBOL LEGEND
A. REFER TO LIFE SAFETY PLAN FOR RATED WALL
LOCATIONS.
B. UL WALL DESIGNATIONS TO BE USED TO DEFINE NEW
RATED WALL ASSEMBLIES. IN CASE OF EXISTING
RATED WALLS, CONFIRM DESIGN IMPROVEMENTS TO
EXISTING ASSEMBLY MEETS UL STANDARDS FOR
RATED WALL ASSEMBLIES.
C. REFER TO FLOOR PLANS SHEET FOR FIRE RATED AND
SMOKE PARTITION LOCATIONS. ALL FIRE AND SMOKE
PARTITIONS SHALL EXTEND FROM FLOOR SLAB TO
THE UNDERSIDE OF STRUCTURE - DECK ABOVE. ALL
PENETRATIONS SHALL BE SEALED AND PROTECTED
WITH FIRE RATED SEALANT TO MAINTAIN THE
INTEGRITY OF THE PARTITION.
D. PARTITION INSTALLATION SHALL CONFORM TO
APPLICABLE CODE REQUIREMENTS.
E. WHERE PARTITIONS OF DIFFERENT FIRE RATING
INTERSECT, PARTITION WITH THE HIGHEST FIRE
RATING SHALL BE CONTINUOUS PER FOLLOWING
PRIORITY LIST:
PRIORITY 1: TWO HOUR FIRE AND SMOKE WALL
PRIORITY 2: TWO HOUR FIRE OR SHAFT WALL
PRIORITY 3: ONE HOUR FIRE AND SMOKE WALL
PRIORITY 4: ONE HOUR FIRE WALL
PRIORITY 5: NON-RATED WALL
PROVIDE IDENTIFICATION OF ALL FIRE RATED AND/OR
SMOKE PARTITIONS AT NOT MORE THAN 10'-0" ON
CENTER ABOVE CEILINGS WITH 3" HIGH STENCILED
BLOCK LETTERING AS FOLLOWS: "1 HOUR FIRE", "1
HOUR FIRE/SMOKE", "2 HOUR FIRE", "2 HOUR
FIRE/SMOKE", "2 HOUR SHAFT", ETC.
F. EXTEND FIRE RATED WALL CONSTRUCTION BEHIND
RECESSED OR BUILT-IN EQUIPMENT SUCH AS FIRE
EXTINGUISHER CABINETS (FEC), ELECTRICAL WATER
COOLERS (EWC), ELECTRICAL PANELS, ETC.
G. STAGGER GYPSUM BOARD JOINTS VERTICALLY AND
HORIZONTALLY A MINIMUM OF 16" EACH SIDE OF
PARTITION AT ALL PARTITIONS.
H. WHERE HVAC OR OTHER MECHANICAL , ELECTRICAL
AND PLUMBING ITEMS PENETRATE PARTITIONS,
STUDS SHALL BE BRACED AND FRAMED TO
STRUCTURE AS REQUIRED TO PROVIDE ADEQUATE
SUPPORT. ALL PENETRATIONS THROUGH RATED
WALLS SHALL BE SEALED TO PROVIDE FIRE, SMOKE,
AND/OR ACOUSTICAL ISOLATION OF SPACES,WITH
APPROPRIATE FIRE STOP MATERIAL.
I. COORDINATE METAL STUD GAUGE WITH PRE-
APPROVED EQUIPMENT ANCHORAGE. WHERE
DISCREPANCY OCCURS, THE MORE STRINGENT
REQUIREMENT SHALL GOVERN.
J. PROVIDE FIRE SAFE INSULATION AS REQUIRED TO
MAINTAIN THE INTEGRITY OF FIRE RATED PARTITIONS.
K. PROVIDE REQUIRED FRAMES AND BRACING AROUND
WALL PENETRATIONS.
L. PROVIDE CONTINUOUS ACOUSTICAL SEALANT AT
BOTTOM OF ALL PARTITIONS.
M. THERE SHALL BE NO BACK-TO-BACK ELECTRICAL,
TELEPHONE, OR OTHER OUTLETS, EXCEPT WHERE
SPECIFICALLY SHOWN.
GENERAL SYMBOL LEGEND
N
KEY PLAN
SCALE: NO SCALE
AREA OF WORK
GROUND FLOOR
TOILET
FG314
PROCEDURE
FG313
PROCEDURE
FG315
CLEAN
SUPPLIES
FG221
STAFF T
FG220 WAITING
FG222A
WAITING
FG222B
STAFF
LOCKERS
FG403
GAS
FG189
PROCEDURE
FG165
OFFICE
FG172
NEW
EXIT
PASSAGEWAY
FG400C
PRIMARY AREA OF WORK
1 1 1
SCOPES
CLEAN
FG318
SCOPES SOIL
FG319
STORAGE
FG317 OFFICE
FG316
2'-0"
F.V.
5'-2"
4'-10" 1'-10 1/2"
/2
2'-9" 13'-2"
/2
PRIMARY AREA OF WORK
TOILET
FG314
OFFICE
FG316
ANTE RM
FG317
OFFICE
FG172 NEW
EXIT
PASSAGEWAY
FG400C
STAFF
LOCKERS
FG403
CIRCULATION
FG300B
STAFF T
FG220
CLEAN
SUPPLIES
FG221
WAITING
FG222A
WAITING
FG222B
PROCEDURE
FG165
GAS
FG189
PROCEDURE
FG315
PROCEDURE
FG313
12 1212
SCOPES
STAGING
FG319
SCOPES
DECON.
FG318
4'-5"
6'-0 1/2"
D317
21'-0" 5'-0"
A-101
D
D
21 1222
NOTES:
1. PROVIDE FIRE-RATED GLASS AT FIRE RATED CONDITIONS
2. ALL GLASS MUST BE TEMPERED
TYPE A
2" 2"
SCHEDULE
SEE
S E
E S
C H
E D
U L E
TYPE 1
10"6"
BASIS OF DESIGN:
PT-1 SHERWIN WILLIAMS
COLOR TO BE SELECTED BY VA, EGGSHELL
PT-2 SHERWIN WILLIAMS
COLOR TO BE SELECTED BY VA, EGGSHELL,
DOOR FRAMES ONLY
RES-1 MATCH EXISTING POURED RESINIOUS BASE
FLOORING WITH INTEGRAL BASE. COLOR AND
TEXTURE TO MATCH AS POSSIBLE. SAMPLES
REQUIRED IN SUBMITTAL
ACT-1 ARMSTRONG 2x2, ULTIMA HEALTH ZONE, WHITE ON 15/16" xl PRELUDE GRID, OR
APPROVED EQUAL
GYP-1 ARMSTRONG DRYWALL FLAT CEILING
SUSPENSION SYSTEM. CEILING GYP. BOARD
TO BE 5/8" THICK, LEVEL 4 FINISH, PAINT PT-1.
REMARKS:
1. EXISTING HM DOOR FRAME TO REMAIN IN PLACE. FRAME TO BE MODIFIED TO REVERSE
DOOR SWING TO LH.
2. EXISTING HM DOOR AND FRAME, COMPLETE WITH HARDWARE TO BE RELOCATED. SEE
DEMOLITION KEYNOTE 10 AND DOOR TAG FG318
3. NEW SOLID CORE WOOD VENEER DOOR TO MATCH EXISTING ADJACENT DOOR TYPE
AND FINISH SUBMITTAL AND SAMPLE REQUIRED. NEW FRAME AND DOOR TO
ACCOMODATE DOOR SWING CHANGE. ALL HARDWARE FROM EXISTING DOOR TO BE
RE-USED INCLUDING CLOSER, LATCH SET, KICKPLATES, ETC.
M A
T C
H E
X
IS
T
IN
G T
H
IC
K N
E S
S
NEW RESINIOUS
FLOORING TO
MATCH EXISTING
COLOR AND STYLE
SUBSTRATE
R =1
MATCH EXISTING THICKNESS
RESINOUS
FLOORING
SS EDGING
OCCUR UNDER
1 3/4" DOOR
RESILIENT
FLOORING
GRIND SLAB
FOR RESINOUS
FLOORING
TRANSITION
DOOR
VERIFY EQUIPMENT TYPE AND
REQUIREMENTS PRIOR TO ROUGH-IN
SEALANT
SS CLOSURE ANGLE AT ALL SIDES OF
EQUIPMENT - ANCHOR TO WALL AND
SEAL ALL EDGES AIRTIGHT
THIS DETAIL IS INTENDED TO ILLUSTRATE
GENERAL SCOPE FOR REPROCESSOR
INSTALLATION. CONTRACTOR SHALL VERIFY
DIMENSIONS WITH MANUFACTURER'S
INSTALLATION INSTRUCTIONS
5/8" GYP BD
4" METAL STUDS
V E
R
IF
Y W
M
F R
COLD FORM HEADER BY
METAL STUD SUPPLIER
(SPAN APPROX. 9'-0")
CEILING
STEEL STUDS
(4") (UNO) @
16" OC
GYP WALL BD (5/8")
FLOOR SLAB
SEALANT
*SEAL ALL
PENETRATIONS
WITH SEALANT
TYPE 1
SCALE: 1-1/2"=1'-0"
SOUND
ATTENUATION
INSULATION
BASE AS
SCHEDULED
EXTEND STUDS TO
STRUCTURE AND
SECURE W/ SLIP TRACK
UNDERSIDE OF
FLOOR OR ROOF
ASSEMBLY
STC-49
I
FLOOR SLAB
FIRE SEALANT
STEEL STUDS
(4") (UNO) @
16" OC
TYPE "X" GYP
WALL BD (5/8")
CEILING
*FIRESTOP ALL
PENETRATIONS
TYPE 2 (1-HR)
SCALE: 1-1/2"=1'-0"
STC-49 SA870717
UL-U419 1 HOUR
/8
GLASS FIBER OR
MINERAL WOOL
INSULATION
M A
X
/4
FIRE SEALANT
D E
C K
D E
P T
H
TYPE "X" GYP BD (5/8") CUT
TO DECK PROFILE
UNDERSIDE OF FLOOR
OR ROOF ASSEMBLY
PER U.L. DESIGN
NUMBER
BASE AS SCHEDULED
EXTEND STUDS TO
STRUCTURE AND
SECURE W/ SLIP
TRACK
Engineers Architects
## KEY NOTES:
# KEY NOTES:
Revisions: Date
Drawing Title
Approved:
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
NOT FOR
CONSTRUCTIO
N
NOT FOR
CONSTRUCTIO
N
WALL RATING LEGEND
1 HR - FIRE BARRIER
2 HR - FIRE BARRIER
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
/2 /2
:3
:1
P M
A-100
PARTIAL GROUND FLOOR PLAN DEMO
+ NEW WORK
2 3EJD
SPS GI EQUIPMENT INSTALL
DURHAM VA MEDICAL CENTER
508 FULTON ST.
DURHAM, NC 27705 OCTOBER 23, 2020
CONSTRUCTION DOCUMENTS
558-19-30219-181
WVS
0 2 4 8
NORTH
PLAN
1 PPE STORAGE FOR SPS STAFF
2 NEW SEAMLESS FLOORING TO MATCH EXISTING
3 NEW COMBO EYEWASH/HANDSINK UNIT SINK SHOWN
ON THIS PLAN IS SYMBOLIC. SEE PLUBING DRAWINGS
AND SPECS FOR ACTUAL MODEL NUMBER AND SIZE
AND TYPE.
4 NEW MANUAL PASS THRU WINDOW @ 48" A.F.F. MOBILE
CART WITH LEAK TESTER TO FIT UNDER
5 EXISTING VA ENDRODRY CABNET
6 3 COMPARTMENT DECONTAMINATION SINKS. SEE
PLUMBING DWGS
7 RELOCATED EXISTING 8 L.F. WALL HUNG STORAGE
CABINETS
8 NEW WALL MOUNT BRACKET FOR EXISTING
WORKSTATION. REMOVE DRYWALL AND INSTALL
SUFFICIENT BLOCKING TO SUPPORT BRACKET. INSTALL
NEW DRYWALL, PATCH AND FINISH TO MATCH
ADJACENT TEXTURE AND FINISH.
9 NEW PASS THRU SCOPE REPROCESSORS - (3) UNITS 6
BOWLS TOTAL - 23MIN AVG. CYCLE TIME
10 NEW HM FRAME AND WOOD DOOR - SEE DOOR
SCHEDULE
11 RELOCATED EXISTING DOOR AND FRAME
12 RELOCATED EXISTING SCOPE STORAGE CABINETS
13 EXISTING FLOOR TO REMAIN
14 FILTRATION SYSTEM TO BE RELOCATED SEE MECH
DWGS
15 SCOPE STORAGE TO HAVE GYPSUM BOARD CEILING
16 CONSTRUCTION ACCESS FROM CORRIDOR
17 NEW PASS THRU FOR RME
18 NEW FLOOR FINISH TO EXISTING FLOOR FINISH SEAM
TO OCCUR UNDER THE DOOR. BASIS OF DESIGN,
SCHLUTER SCHIENE, ALUM.
19 PATCH AND REPAIR TO LIKE NEW CONDITION. PAINT
WALL TO MATCH ADJACENT.
20 EXTENT (69 S.F.) OF NEW RESINOUS FLOORING TO
MATCH EXISTING
21 NEW WALL MOUNTED SHELF FOR BACK UP LEAK
TESTER AND SCOPE BUDDY
22 EXISTING CONCRETE COLUMN
23 EXISTING 30" X 30" FLOOR ACCESS DOOR TO REMAIN.
INSTALL NEW FLOOR FINISH SAME AS ROOM, SEE
ROOM FINISH SCHEDULE.
24 EXISTING RECESSED FIRE EXTINGUISHER
25 BRACE EXISTING WALL WITH 16 GA STUDS ON EITHER
SIDE OF PASS THRU CHAMBER FLOOR TO UNDERSIDE
OF STRUCTURE ABOVE
N
KEY PLAN
SCALE: NO SCALE
AREA OF WORK
GROUND FLOOR
0 2 4 8
NORTH
PLAN
Scale: 1/4" = 1'-0"
PARTIAL GROUND FLOOR PLAN - DEMOLITION
Scale: 1/4" = 1'-0"
PARTIAL GROUND FLOOR PLAN - NEW WORK
A. FLOOR TO FLOOR HEIGHT FROM GROUND FLOOR
PLAN TO FIRST LEVEL 12'-0" (FIELD VERIFY)
B. CONTRACTOR SHALL MAKE PROVISIONS TO ENSURE
CONSTRUCTION NOISE DOES NOT EXCEED VA
DETERMINED THRESHOLD IN OCCUPIED AREAS
ADJACENT TO CONSTRUCTION.
C. VA TO REMOVE ALL NON FIXED EQUIPMENT PRIOR TO
START OF CONSTRUCTION. SCOPE DRYING CABINETS,
EXISTING MEDIVATORS, MOVEABLE CARTS, ETC.
D. SEE THIS SHEET FOR PARTITION TYPES 1 AND 2
E. CONTRACTOR RESPONSIBLE FOR FLOOR PATCHING
AROUND NEW FLOOR DRAINS, COLOR, TYPE, AND
STYLE OF FLOOR TO MATCH EXISTING.
F. CONTRACTOR SHALL CONDUCT HIGH NOISE
ACTIVITIES IN A WAY TO ALLOW THE FACILITY TO
OPERATE DURING CONSTRUCTION. ACTIONS THAT
THE CONTRACTOR TAKE TO MINIMIZE THE IMPACT
INCLUDE:
a. NOTIFYING THE COR TWO DAYS PRIOR TO THE
TIME OF HIGH NOISE ACTIVITIES TO ALLOW THE
COR TO COMMUNICATE THIS TO THE EMPLOYEES
AND PATIENTS.
b. SCHEDULING HIGH NOISE ACTIVITIES DURING THE
TIMES OF MINIMAL IMPACT.
1 DRYING CABINET TO BE RELOCATED, PATCH AND
REPAIR FLOOR AND WALLS
2 REMOVE HM FRAME, WOOD DOOR, AND DOOR
OPERATOR. PATCH AND REPAIR WALL.
3 EXISTING SINK TO BE REMOVED. SEE PLUMBING DWGS.
ASSOCIATED EQUIPMENT TO REMAIN (SCOPE BUDDY,
VACUUM, AIR, DRAIN ETC...)
4 NOT USED
5 EXISTING WALL HUNG STORAGE CABINETS TO BE
REMOVED AND RELOCATED TO SCOPES DECON. NEW
CONSTRUCTION LOCATION.
6 NOT USED
7 REMOVE BASE CABINETS. PATCH AND REPAIR WALLS.
8 CONTRACTOR TO CUT NEW 3'-0"X 7'-0" OPENING IN
EXISTING WALLS FOR ACCESS TO AREA OF WORK.
9 DEMOLISH WALL IN ITS ENTIRETY.
10 HM DOOR AND FRAME TO BE RELOCATED
11 EXISTING SINK TO BE REMOVED. SEE PLUMBING DWGS.
PATCH AND RAPAIR WALLS. FINISH TO MATCH
ADJACENT
12 EXISTING DOOR TO REMAIN.
13 DEMOLISH EXISTING CASEWORK, SINK AND UPPER
CABINETS.
14 CUT PORTION OF LOWER WALL FOR NEW
REPROCESSOR AND DEMOLISH, VERIFY VERTICAL AND
HORIZ. DIMENSIONS. INSTALL NEW COLD FIRM HEADER.
SEE DETAIL 7/A-100 (SIMILAR), PATCH AND REPAIR OR
INSTALL NEW GYP.BD. AS REQ'D.
15 REMOVE EXISTING DOOR, HM FRAME AND DOOR
OPERATOR.
16 EXISTING 30" x 30" FLOOR ACCESS DOOR TO REMAIN.
REMOVE EXISTING FLOOR FINISH.
DOOR SCHEDULE
DOOR DOOR FRAME THRESH
DETAIL NO. LBL
HDWR
SET REMARKSNO. WIDTH HEIGHT THICK MAT'L FINISH ELEV MAT'L FINISH ELEV
D317 3' - 0" 7' - 0" 1 3/4" EXIST WD EXIST EXIST EXIST EXIST EXIST 6 45 MIN. EXIST NOTE 1
D318 3' - 0" 7' - 0" 1 3/4" EXIST HM EXIST EXIST EXIST PT EXIST 45 MIN. EXIST NOTE 2
D319 3' - 0" 7' - 0" 1 3/4" SCW PF TYPE A HM PT EXIST 45 MIN. NOTE 3
Scale: 1/4" = 1'-0"
DOOR AND FRAME ELEVATIONS
ROOM FINISH SCHEDULE
ROOM NO. NAME FLOOR BASE
WALLS CEILING
REMARKS
EAST NORTH SOUTH WEST
FIN HEIGHTMAT'L FIN MAT'L FIN MAT'L FIN MAT'L FIN
FG317 ANTE RM RES-1 RES-1 GYP BD PT-1 GYP BD PT-1 GYP BD PT-1 GYP BD PT-1 ACT-1 8' - 0"
FG318 SCOPES DECON. RES-1 RES-1 GYP BD PT-1 GYP BD PT-1 GYP BD PT-1 GYP BD PT-1 ACT-1 8' - 0"
FG319 SCOPES STAGING RES-1 RES-1 GYP BD PT-1 GYP BD PT-1 GYP BD PT-1 GYP BD PT-1 GYP-1 8' - 0"
EXIST= EXISTING
HM= HOLLOW METAL
PF= PREFINISHED
PT= PAINT
SCW= SOLID CORE WOOD
WD= WOOD
Scale: 3" = 1'-0"
INTEGRAL BASE DETAIL
Scale: 6" = 1'-0"
TRANSITION FLOORING DETAIL
Scale: 3/4" = 1'-0"
EQUIP DETAIL - SCOPE REPROCESSOR
Scale: 1 1/2" = 1'-0"
PARTITION TYPES 1 AND 2
8'-11"
REFLECTED CEILING PLAN
LEGEND
SUPPLY DIFFUSER
RETURN GRILL
DOWN LIGHT
FIXTURE
EXIT SIGN (SHADED
AREA INDICATES
DIRECTION OF
EGRESS)
DENOTES GWB
SOFFIT/CEILING
E Q
B
EQ. A
SPRINKLER HEAD
2'x4' LAY-IN LED
MAT
8'-0"
CEILING HEIGHT
DESIGNATION
(WHEN HEIGHT
VARIES FROM
TYPICAL)
CEILING CONTRACTOR TO MEASURE EACH CEILING
AREA AND ESTABLISH A CEILING LAYOUT TO BALANCE
BORDER WIDTHS AT OPPOSITE EDGES OF EACH
ROOM. AVOID USE OF LESS-THAN 6" TILES.
EXHAUST GRILL
EQ. A
E Q
B
ACCESS PANEL
PRIMARY AREA OF WORK
TOILET
FG314
STAFF T
FG220
CLEAN
SUPPLIES
FG221
STORAGE
FG317
SCOPES
CLEAN
FG318
SCOPES SOIL
FG319
OFFICE
FG316
OFFICE
FG172
PROCEDURE
FG165
GAS
FG189
PROCEDURE
FG315
PROCEDURE
FG313
NEW
EXIT
PASSAGEWAY
FG400C
STAFF
LOCKERS
FG403
WAITING
FG222A
WAITING
FG222B
PRIMARY AREA OF WORK
TOILET
FG314
STAFF
LOCKERS
FG403
STAFF T
FG220
CLEAN
SUPPLIES
FG221
WAITING
FG222A
WAITING
FG222B
OFFICE
FG316
ANTE RM
FG317
SCOPES
DECON.
FG318
SCOPES
STAGING
FG319
NEW
EXIT
PASSAGEWAY
FG400C
OFFICE
FG172
GAS
FG189
PROCEDURE
FG165
PROCEDURE
FG315
PROCEDURE
FG313
8' - 0"
ACT
2x2
8' - 0"
ACT
2x2
A-101
8' - 0"
GYP-1
10 10
11 7
A-101
4 10
12 5
A-101
EXISTING RELOCATED
CABINETS SEE INTERIOR
ELEVATIONS
PROVIDE 2x BLOCKING IN
WALL CAVITY FOR
CABINET MOUNTING, TOP
& BOTTOM
REMOVE GYPSUM BOARD AS
NECESSARY TO INSTALL
ADEQUATE BLOCKING FOR
RELOCATED CABINETRY. SEE
INTERIOR ELEVATIONS. PATCH
AND REPAIR INCLUDING VISIBLE
JOINTS. MATCH FINISH AND
TEXTURE OF ADJACENT
SURFACES.
5/8" GYPSUM BOARD
METAL STUDS
Engineers Architects
## KEY NOTES:
# KEY NOTES:
Revisions: Date
Drawing Title
Approved:
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
NOT FOR
CONSTRUCTIO
N
NOT FOR
CONSTRUCTIO
N
WALL RATING LEGEND
1 HR - FIRE BARRIER
2 HR - FIRE BARRIER
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
/2 /2
:3
:1
P M
A-101
PARTIAL GROUND FLOOR DEMOLITION
REFLECTED CEILING PLAN + NEW
WORK REFLECTED CEILING PLAN
3 3EJD
SPS GI EQUIPMENT INSTALL
DURHAM VA MEDICAL CENTER
508 FULTON ST.
DURHAM, NC 27705 OCTOBER 23, 2020
CONSTRUCTION DOCUMENTS
558-19-30219-181
WVS
1 NEW ACT CEILING - GRID AND PADS
2 NEW GYP CEILING.
3 NEW PASS THRU SCOPE REPROCESSORS, BY VA
4 COMPUTER WORKSTATION, EXISTING
WORKSTATION RELOCATED NEW WALL MOUNT
BRACKETS SUPPLIED BY VA. DEMO GYPSUM
BOARD BEHIND WALL BRACKET TO ADEQUATELY
PROVIDE BLOCKING FOR SUPPORT OF WALL
BRACKET TYPE. COORDINATE WITH C.O.R.
5 NEW COMBO EYEWASH/HANDSINK UNIT
6 NEW MANUAL PASS THRU WINDOW WITH NO
FINISHED SIDES @ 48" A.F.F. MOBILE CART WITH
LEAK TESTER TO FIT UNDER
7 EXISTING RELOCATED VACUUM
8 3 COMPARTMENT DECONTAMINATION SINKS. SEE
PLUMBING DWGS
9 RELOCATED EXISTING WALL HUNG STORAGE
CABINETS. DEMO GYPSUM BOARD BEHIND
CABINETS AS NECESSARY TO ADEQUATELY
PROVIDE BLOCKING FOR SUPPORT OF
RELOCATED CABINETS
10 EXISTING CONCRETE COLUMN
11 NEW WALL MOUNTED SHELF FOR BACK UP LEAK
TESTER AND SCOPE BUDDY
12 ELECTRICAL RECEPTACLES AS NECESSARY,
TYPICAL ALL LOCATIONS
13 EXISTING FLOOR TO REMAIN
14 NEW PASS THRU WINDOW FOR RME
15 FILTRATION SYSTEM TO BE RELOCATED. REMOVE
DRYWALL AND INSTALL SUFFICIENT BLOCKING TO
SUPPPORT FILTERS. INSTALL NEW DRYWALL,
PATCH AND FINSH TO MATCH ADJACENT TEXTURE
AND FINISH. SEE MECH DWGS
16 NEW FLUSH ACCESS PANEL. BASIS OF DESIGN:
LARSEN'S MANUFACTURING, 24"x24" MODEL L-DW24x24 OR EQUAL.
N
KEY PLAN
SCALE: NO SCALE
AREA OF WORK
GROUND FLOOR
0 2 4 8
NORTH
PLAN
Scale: 1/4" = 1'-0"
PARTIAL REFLECTED CEILING PLAN - DEMOLITION
Scale: 1/4" = 1'-0"
PARTIAL REFLECTED CEILING PLAN - NEW WORK
0 2 4 8
NORTH
PLAN
A. SEE ELECTRICAL AND MECHANICAL DWG'S FOR
CEILING-MOUNTED ELECTRICAL AND MECHANICAL
DEVICES.
B. SEE FIRE PROTECTION DWGS FOR SPRINKLER
LOCATIONS AND TYPES.
1 REMOVE CEILING MOUNTED DEVICES AND EXISTING
SUSPENDED ACOUSTICAL CEILING GRID AND
BOARD. COORDINATE WITH MECHANICAL,
ELECTRICAL AND PLUMBING CONTRACTORS FOR
INSTALLATION THEIR RESPECTIVE NEW WORK.
Scale: 1/2" = 1'-0"
INTERIOR ELEVATION
Scale: 1/2" = 1'-0"
INTERIOR ELEVATION
Scale: 1 1/2" = 1'-0"
CABINET BLOCKING DETAIL
Scale: 1/2" = 1'-0"
INTERIOR ELEVATION
| Sheets |
| A-001 - ARCHITECTURAL SYMBOLS, ABBREVIATIONS AND NOTES |
| A-100 - PARTIAL GROUND FLOOR PLAN DEMO + NEW WORK |
| A-101 - PARTIAL GROUND FLOOR DEMOLITION REFLECTED CEILING PLAN + NEW WORK REFLECTED CEILING PLAN |
File details come from the government source that posted it. Updated .