This document provides details for a federal contract solicitation. The solicitation number is 36C26323R0042 from the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 23 for preventative Legionella services. The solicitation seeks to address Phase 3 of project 618-18-108 to prevent Legionella bacteria at its facilities. The related file is an attachment containing drawings but no other information is provided.
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
KEY NOTES: GENERAL NOTES:
K L
DASHED LINES REPRESENT STEEL MEZZANINE -
SOME PIPING SHOWN IS EITHER ABOVE OR BELOW.
1ISOLATE EXISTING PRESSURE REDUCING STATION SERVING THIS
MECHANICAL ROOM AND OTHER AREAS IN NORTHEAST QUADRANT OF
BUILDING. REMOVE PIPING UP TO EXISTING TAKE-OFF TEE AND
INSTALL TRIPLE OFFSET BUTTERFLY VALVE WITH BLIND FLANGE CAP
TO SEAL FOR POTENTIAL FUTURE CONNECTION (SEE NEW PLANS FOR
LOCATION OF THIS ADDED VALVE). COORDINATE OUTAGE DURING
PREMIUM HOURS WITHIN MILD WEATHER SEASON TO MINIMIZE
DISRUPTION TO FACILITY. REPLACE ANY REMOVED OR DAMAGED
PIPING INSULATION ON COMPLETION.
REMOVE EXISTING 30 PSI STEAM PIPING TO WATER HEATERS
SCHEDULED FOR DEMOLITION. INCLUDE REMOVAL OF ALL
ASSOCIATED END OF MAIN STEAM TRAPS AND PIPING COMPONENTS.
REMOVE ALL SUPPORT HANGERS AS REQUIRED AND RESECURE ANY
IMPACTED PIPING ANCHORS THAT MAY HAVE BEEN IMPACTED BY
DEMOLITION. PERFORM ON OVERTIME DURING MILD WEATHER.
REMOVE EXISTING INSTANTANEOUS WATER HEATER ALONG WITH ALL
PIPING COMPONENTS, CONTROL SENSORS, AND WIRING. REMOVE
ANY INTEGRATION INTO BUILDING AUTOMATION TO BE REPLACED BY
NEW WATER HEATER INSTALLATION.
REMOVE EXISTING 30 PSI TAKE-OFF VALVE TO FUTURE WATER
HEATER THAT WAS NEVER INSTALLED.
PATCH ALL PIPING PENETRATIONS THROUGH ELEVATED PLATFORM
SERVING AS MEZZANINE FLOOR. WELD STEEL PATCHES AND/OR
GRATING AS REQUIRED AND PAINT ALL AFFECTED AREA TO RESIST
ANY CORROSION ON COMPLETION.
NOTE NOT USED.
CONTRACTOR TO ISOLATE HIGH PRESSURE STEAM MAIN AT HEADER
TAKE-OFF VALVE. NOTE THAT THIS STEAM RISER WILL AFFECT ENTIRE
QUADRANT OF BUILDING AND SHOULD BE SCHEDULED A MINIMUM OF
1-MONTH IN ADVANCE WHILE ON PREMIUM OVERTIME DURING MILD
WEATHER TO AVOID RISK TO HOSPITAL OPERATIONS.
DURING OUTAGE TAP INTO HIGH PRESSURE MAIN AT APPROXIMATE
LOCATION INDICATED AND INSTALL ISOLATION VALVE DETAIL IN KEY
NOTE #12 BELOW. FIELD VERIFY ACTUAL CONDITIONS FOR OFFSET
FROM MAIN REQUIRED TO AVOID EXISTING PIPING SERVICES AND
SUPPORT HANGERS IN THIS CONGESTED AREA.
PROVIDE 4" TRIPLE OFFSET BUTTERFLY VALVE WITH FLANGED
CONNECTIONS AND SPOOL PIECES FOR BYPASS ASSEMBLY. INSTALL
A 1.5" BYPASS AROUND VALVE WITH PISTON VALVE FOR EQUALIZING
LINE PRESSURE PRIOR TO CLOSING HIGH PRESSURE SERVICE.
ROUTE 3/4" HIGH PRESSURE CONDENSATE FROM REDUCING STATION
INLET DRIP LEG TO DISCHARGE INTO EXISTING FLASH TANK.
REFER TO PRESSURE REDUCING STATION DETAIL 7/PP500 FOR ALL
COMPONENTS REQUIRED IN THIS PREMANUFACTURED SKID
ASSEMBLY (CONTRACTOR WILL NOT BE ALLOWED TO FIELD
FABRICATE ON SITE). NOTE THAT ACCESS WILL BE FROM THE PLAN
WEST SIDE (UNDERNEATH MEZZANINE PLATFORM). FIELD VERIFY ALL
DIMENSIONS WITH FACTORY PRIOR TO SHOP DRAWING SUBMITTAL.
ROUTE 3/4" LOW PRESSURE CONDENSATE FROM 15 PSI OUTLET DRIP
LEG TO DISCHARGE DIRECTLY INTO CONDENSATE PUMP.
ROUTE 3" CONDENSATE FROM NEW WATER HEATER ASSEMBLY
ALONG FLOOR (DO NOT LIFT SO THAT GRAVITY DRAINAGE CAN BE
APPLIED WHEN NEEDED). CONNECT DIRECTLY INTO EXISTING
CONDENSATE PUMP WHERE INDICATED.
PROVIDE HEAVY DUTY 18" TALL GUARD RAILS AROUND PERIMETER OF
WATER HEATERS, MANUFACTURED BY HANDLE-IT, INC. VERIFY
INSTALLATION DOES NOT BLOCK ANY SERVICE ACCESSIBILITY.
POSITION WATER HEATERS FAR ENOUGH FROM COLUMN TO ALLOW
FOR FULL REMOVAL OF HEATING TUBE BUNDLES.
A.
B.
C.
D.
E.
MECHANICAL CONTRACTOR SHALL REFER TO THE VA MASTER
SPECIFICATION MANUAL ALONG WITH ANY APPLICABLE STANDARDS
WITHIN THE 2019 HVAC DESIGN GUIDE. ALL REQUIREMENTS OF THOSE
MANUALS SHALL BE MAINTAINED IN ADDITION TO ALL NOTES AND
DESCRIPTIONS INDICATED WITHIN THESE DRAWINGS. ANY CONFLICTS
BETWEEN THOSE DOCUMENTS SHOULD BE BROUGHT TO THE
ATTENTION OF THE ENGINEER FOR INTERPRETATION.
MECHANICAL CONTRACTOR WILL BE RESPONSIBLE TO REVIEW ALL
POTENTIAL OUTAGES RESULTING FROM TIE-INS SHOWN ON THESE
DRAWINGS TO DETERMINE APPROXIMATE AMOUNT OF OVERTIME
REQUIRED TO PERFORM ALL MECHANICAL WORK INDICATED. PROVIDE
THE VA COTR A MINIMUM OF 14 DAYS ADVANCE NOTICE OF ANY
OUTAGE FOR COORDINATION OF SCHEDULES WITH AFFECTED
DEPARTMENTS.
COORDINATE ALL NEW PIPE ROUTING WITH ALL OTHER TRADES TO
INSURE ADEQUATE CLEARANCES FOR PLUMBING, ELECTRICAL
CONDUIT, STRUCTURAL SUPPORTS, PIPING, ETC. ANY UNAVOIDABLE
CONFLICTS SHALL BE BROUGHT TO THE ATTENTION OF THE
ARCHITECT/ENGINEER OF RECORD. PROVIDE ALL OFFSETS AND
TRANSITIONS AS REQUIRED FOR A CLEAN INSTALLATION.
SUPPORT ALL PIPING DIRECTLY TO STRUCTURE. DO NOT SUPPORT ANY
PIPE FROM DUCTWORK, CONDUIT, OR OTHER PIPING ENCOUNTERED.
WHERE MECHANICAL SYSTEMS TO REMAIN ARE DAMAGED, OR
DISTURBED, DURING THE COURSE OF CONSTRUCTION THE
CONTRACTOR WILL BE RESPONSIBLE TO REMOVE DAMAGED PORTIONS
AND INSTALL NEW PRODUCTS OF EQUAL QUALITY AND FUNCTIONALITY.
ALL EXISTING PIPING THROUGH NEW FIRE RATED WALLS SHALL BE
ADEQUATELY FIRE SEALED AS REQUIRED. PIPING PENETRATIONS
THROUGH INTERSTITIAL FLOOR SHALL BE DRILLED, OR CUT, BY THE
CONTRACTOR AND FIRE SEALED AS REQUIRED.
" H
P S
4" HPS
" 1
R
8" 15# STM
3/4" 15#R
3/4" HPR
H J K L M
10" HPS10" HPS
4" HWR 4" HWR
" H
W R
DASHED LINES REPRESENT STEEL MEZZANINE -
SOME PIPING SHOWN IS EITHER ABOVE OR BELOW.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue DateCheckedDrawn
Drawing Title
Approved:
VA FORM 08 -6231
A
CONSTRUCTION
DOCUMENTS SUBMISSION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
2 145678910
Phase
ARCHITECT/ENGINEER OF RECORDSTAMP CONSULTANT
3 2 145678910
TRUE NORTH
PLAN NORTH
B
C :\R e v it P ro je c ts
\V A
B u ild in g
- P h a s e
- M e c h a n ic a l 2 ja s o n g o ttw a lt5
.rv t
/3 /2
:2
:0
A M
BASEMENT INTERSTITIAL - PHASE
4 - HYDRONIC PIPING PLAN
PREVENT LEGIONELLA,
PHASE III
MINNEAPOLIS
618-14-118
11/30/2022JGJG 618-14-118
1356-MP104.1
1/4" = 1'-0"
ENLARGED DEMOLITION MECHANICAL PLAN - PHASE 4.4
1/4" = 1'-0"
ENLARGED MECHANICAL PLAN - PHASE 4.4
41360 DATEREG. NO.
I HEREBY CERTIFY THAT THIS PLAN,
SPECIFICATION OR REPORT WAS PREPARED BY ME
OR UNDER MY DIRECT SUPERVISION AND THAT I
AM A DULY LICENSED PROFESSIONAL ENGINEER
UNDER THE LAWS OF THE STATE OF MINNESOTA.
JASON GOTTWALT, P.E.
11/30/2022
Revisions:Date:
KEY NOTES: GENERAL NOTES:
TS
TS
T S
TS
T S
T S
TS
T S
8" CW
E.B
E.A
E.C
8" CW
2 1/2" RHW
4" HW
8" CW
A.B
A.C
A.A
8" CW
TO BE
REPLACED
IN NEXT
PHASE
SWH
70-NE-02
REFER TO DRAWING PP100B FOR
INSTALLATION OF NEW RECIRC
WHILE SPLITTING EXISTING LOOP.
REFER TO DRAWING PP100B, KEY NOTE
#71, FOR INSTALLATION OF INCOMING
WATER MONITORING STATION.
PROVIDE NEW DUAL RPZ
ASSEMBLY, SEE KEY NOTE
C W
C W
REFER TO DETAIL
2/1356-PP104
FOR VALVE LOCATION.
REFER TO DETAIL
2/1356-PP104
FOR VALVE LOCATION.
1356-PP104.1
1356-PP105.1
33 NOTE APPLIES TO ALL NEW
PIPING AND COMPONENTS
DWBP
70-NE-02
HJ
NOTE THAT THESE KEY NOTES ARE SPECIFIC TO THIS DRAWING (DO
NOT REFER TO MASTER KEY NOTES ON SHEET 1356-PP003). NOT ALL
KEY NOTES ARE UTILIZED AND MAY HAVE GAPS OF MISSING NOTE
NUMBERS TO KEEP 'GROUPS OF TEN NOTES' AVAILABLE PER PHASE.
SHUT-OFF VALVE E.C AND VALVE A.B TO ISOLATE SECTION OF PIPING
INDICATED FOR REMOVAL. REFER TO GENERAL NOTES FOR
PROVISIONS TO BE TAKEN TO VERIFY ANY EXISTING VALVE LEAKAGE.
ONCE ISOLATED, REMOVE SECTION OF 8" GALVANIZED PIPING LOOP.
CUT INTO SECTIONS SMALL ENOUGH TO TRANSPORT TO LOADING
DOCK AREA FOR REMOVAL. INCLUDE DEMOLITION OF EXISTING
SUPPORTS MOUNTED TO PIPING RACKS, NEW PIPING WILL BE
SUPPORTED ONTO EXISTING RACK STRUCTURE BUT SHOULD BE
PROVIDED WITH NEW PIPE CLAMPS.
CONTRACTOR TO COORDINATE ISOLATION OF 6" SECONDARY WATER
SERVICE TO BUILDING WITH UTILITIES REP. SCHEDULE TIMEFRAME
THAT VA BUILDING 70 WILL BE ON MAIN SERVICE ONLY, WITHOUT THIS
BACK-UP SOURCE, SO THAT AN INTERIM LIFE SAFETY REQUEST CAN BE
MADE BY VA COTR. TEMPORARILY CAP AT POINT OF DISCONNECT
UNTIL ALL NEW PIPING INSTALLATION IS COMPLETE.
REMOVE EXISTING RPZ ASSEMBLY AND ALL OTHER PIPING
COMPONENTS UP TO THE WALL PENETRATION. ALL PIPING AND
COMPONENTS TO BE REPLACED WITH NEW STAINLESS STEEL PER
PHASE 4.3 DRAWING.
EXISTING BOOSTER PUMP TO BE DEMOLISHED AND REPLACED WITH
NEW SYSTEM. COORDINATE SECONDARY SERVICE OUTAGE WITH VA
COTR PER KEY NOTE #12 ABOVE.
REMOVE EXISTING VFD FOR ADJACENT CHILLED WATER PUMPS.
REFER TO ELECTRICAL DRAWINGS FOR DISCONNECT/RECONNECT IN
ORDER TO RELOCATE AS REQUIRED TO PROVIDE CLEARANCE FOR
NEW RPZ ASSEMBLY INSTALLATION SHOWN IN PHASE 4.3.
SHUT OFF ISOLATION VALVES FOR HOT/COLD WATER TO EXISTING
WATER HEATER (INSTALLED DURING PREVIOUS PHASE). COORDINATE
INTERIM LIFE SAFETY REQUEST TO VA FOR SCHEDULE OF TIME WHERE
THIS SECONDARY WATER HEATER SHALL BE OFFLINE.
REMOVE EXISTING CIRCULATION PUMP. INSTALL ISOLATION VALVE
SHOWN ON INLINE PUMP PIPING DETAIL TO ISOLATE REMAINDER OF
SYSTEM WHILE PUMP RECONFIGURATION/UPDATE OCCURS.
REMOVE EXISTING STEAM-TO-WATER HEAT EXCHANGER ASSEMBLY
AND COMPONENTS. REFER TO DRAWING PP500 FOR REMOVAL OF
ASSOCIATED STEAM PIPING AND CONTROLS.
NOT USED.
INSTALL NEW SECTION OF 8" SCHEDULE 10 STAINLESS STEEL PIPING TO
REPLACE PREVIOUSLY REMOVED. INSTALL IN EXACT SAME LOCATION
AS REMOVED SECTION OF PIPING. PROVIDE NEW SUPPORT CLAMPS
ON EXISTING PIPING RACK AS REQUIRED.
PROVIDE TEMPORARY END CAPS AT EITHER SIDE OF NEW PIPING
SECTION. FIRST PERFORM A PRESSURE TEST ON PIPING SECTION PER
SPECIFICATION REQUIREMENTS, AND THEN STERILIZE PIPING USING
CHLORINE SOLUTION FOR AT LEASE 24 HOURS PRIOR TO FLUSHING.
INCLUDE DRAIN/FILL VALVES ON EITHER END TO ACCOMPLISH.
INSULATE ENTIRE LENGTH OF PIPING PER SPECIFICATION
REQUIREMENTS. INCLUDE CONTINUOUS PVC COVERING THROUGHOUT
AND PREPARE ENDS FOR EXTENSION TO NEXT SUB-PHASE PIPING
WHICH WILL INCLUDE INSULATING ALL VALVE BODIES.
NOT USED THROUGH KEY NOTE
SHUT-OFF VALVE E.C AND VALVE A.B (BOTH FURTHER OUT TO NEXT
ADJACENT RISER VALVES OUTSIDE THE EXTENTS OF THIS PHASE
DRAWING) TO ISOLATE THIS WATER SERVICE FOR VALVE AND PIPING
REPLACEMENT. REFER TO GENERAL NOTES FOR PROVISIONS TO BE
TAKEN TO VERIFY ANY EXISTING VALVE LEAKAGE AND AREAS THAT
WILL BE AFFECTED BY THIS MAJOR WATER OUTAGE.
RELOCATE VFD'S FOR EXISTING CHILLED WATER PUMPS TO
APPROXIMATE LOCATION INDICATED. FABRICATE UNISTRUT STANDS
AS REQUIRED, REFER TO ELECTRICAL DRAWINGS FOR POWER.
ALL PIPING, AND COMPONENTS, REPLACED FROM THE SECONDARY
WATER SERVICE SHALL BE 304 STAINLESS STEEL OR BETTER WITH
EITHER ROLL GROOVED OR WELDED FITTINGS. ANY EXCEPTIONS TO
THIS WILL REQUIRE APPROVAL FRO VA COTR.
ONCE VALVE INSTALLATION IS COMPLETED, INSULATE ALL AFFECTED
PIPING AND NEW VALVE BODIES COMPLETELY. COVER EVERYTHING
WITH PVC JACKET COVERS AND SEAL AS REQUIRED. INSULATION CAN
OCCUR DURING NORMAL HOURS AFTER OUTAGE COMPLETION, BUT
SHOULD NOT BE DELAYED FOR ANY MORE THAN 3 BUSINESS DAYS.
INSTALL ½” COLD WATER PIPE TAKE-OFF AND VALVE FROM INCOMING
WATER SERVICE. EXTEND THIS PIPING TO SAMPLING STATION AND
SENSORS NOTED AS ‘MS’ ON DRAWINGS. CONNECT TO PLASTIC
TUBING INLET OF WATER SAMPLING STATION MOUNTED TO WALL OR
UNISTRUT STAND. NOTE THAT SAMPLING CHAMBER WILL REQUIRE
PLASTIC DISCHARGE PIPING ROUTED TO NEARBY FLOOR DRAIN
ALONG WITH LOW VOLTAGE CABLING FROM INTERNAL SENSORS
EXTENDED TO CONTROLLER INDICATED WITHIN KEY NOTE #??.
PROVIDE A MASTER MONITORING STATION TO BE ADDED TO WATER
SERVICE ENTERING THE BUILDING. THIS WILL CONTINUALLY MONITOR:
THE TEMPERATURE, pH LEVEL, PRESSURE, TOTAL DISSOLVED SOLIDS
(TDS), AND FREE CHLORINE LEVEL. INTEGRATE ALL MONITORED
POINTS INTO CAMPUS AUTOMATION SYSTEM FOR REMOTE
MONITORING/ALARM. LOCATE FLOW CELL SAMPLING STATION NEXT
TO MASTER MONITORING STATION AND EXTEND SENSOR CABLES TO
SENSOR PORT ON PIPE. THE OPTIONAL EXTENDED LENGTH CABLING
WILL BE REQUIRED. USING PVC TUBING, PIPE DRAIN FROM FLOW
CELL AND OPEN SIGHT INTO NEARBY FLOOR DRAIN. REFER TO KEY
NOTE #71 ON DRAWING PP003 FOR MODEL NUMBER AND
SPECIFICATION REFERENCE.
PROVIDE TWO(2) 6" RPZ ASSEMBLIES IN PARALLEL CONSTRUCTED OF
304 STAINLESS STEEL OR BETTER. MOUNT EACH OF THE ASSEMBLIES
AT APPROXIMATELY 60" AND 30" ABOVE FLOOR LEVEL. ANGLE VALVE
STEMS ON EITHER SIDE AS REQUIRED FOR ACCESSIBILITY. REFER TO
OUTLINE SPECIFICATION BELOW.
DUAL RPZ VALVE SPECIFICATION - Each of the two assemblies shall consist of a pressure differential relief valve located in a zone between two positive seating check valves. The main valve body shall be manufactured from 300 Series stainless steel for corrosion resistance. The check valves shall be of thermoplastic construction with stain less steel hinge pins, cam arm, and cam bearing. The check valve shall utilize a single torsion spring design to minimize pressure drop through the assembly. The check valves shall be modular and shall seal to the main valve body by the use of an O-ring. There shall be no brass or bronze parts used with in the check assembly or relief valve. The use of seat screws to retain the check valve seat is prohibited. All internal parts shall be accessible through a single cover on the valve assembly securely held in place by a two bolt grooved coupling. The differential relief valve shall be of stain less steel con struction and shall utilize a rolling diaphragm and no sliding seals. The relief valve shall be bottom mounted and supplied with a steel reinforced sensing hose. The assembly shall include two resilient seated shutoff valves & four ball type test cocks. The assembly shall be a Watts Series 994, or equal coupled with either stainless steel body OS&Y valves or stainless triple offset butterfly valves.
PHASE 4.1 (DEMO - REFER TO DETAIL 1 AND 10-19 SERIES KEY NOTES):
THE EXISTING GALVANIZED 8" COLD WATER PIPING MAIN TO BE REMOVED
BETWEEN INTERIOR VALVES OF RISERS INDICATED IN KEY NOTES. REFER
TO WORK SEQUENCE DESCRIBED IN 'ISOLATION OF MAIN PIPING LOOP
SECTIONS' BELOW TO EITHER CONFIRM EXISTING VALVES DO NOT LEAK, OR
FOLLOW GUIDELINE PROVISIONS TO BE TAKEN IF THEY ARE FOUND
DEFECTIVE. NO OUTAGES WILL BE REQUIRED DURING THIS SUB-PHASE
WITH MAIN LOOP CONTINUALLY SERVING BOTH SIDES.
PHASE 4.2 (BUILD-BACK - REFER TO DETAIL 2 AND 20-29 SERIES KEY NOTES):
INSTALL NEW PIPING IN SAME LOCATION AS REMOVED SECTION OF 8" COLD
WATER MAIN. MAY REUTILIZE EXISTING PIPING RACK FOR PIPING
SUPPORTS. REFER TO KEY NOTES FOR ADDITIONAL INFORMATION RELATED
TO INSTALLATION.
PHASE 4.3 (WATER SERVICE REPLACEMENT - 30+ SERIES KEY NOTES):
AREA SHOWN IN EXPANDED 1/4" = 1'-0" PLAN VIEW ON DETAIL 3/PP104.1
SHALL BE UPGRADED WITH NEW DUAL RPZ BACKFLOW PREVENTION FROM
EXISTING 6" SERVICE INTO BUILDING. IN ADDITION THE EXISTING BOOSTER
PUMP ASSEMBLY SHALL BE FULLY REPLACED AS INDICATED ALONG WITH
ALL PIPING AND COMPONENTS TO NOW BE STAINLESS STEEL WITH EITHER
GROOVED OR WELDED FITTINGS. NOTE THIS WORK MAY OCCUR
SIMULTANEOUSLY WITH PHASE 4.2 EFFORT SHOWN.
PHASE 4.4 (WATER HEATER INSTALLATION / FINAL CONNECTIONS):
REFER TO DRAWING PP104.2 FOR DESCRIPTION OF THIS PROJECT PHASE.
ISOLATION OF MAIN PIPING LOOP SECTIONS:
PERFORM THE FOLLOWING PROCEDURE STEPS TO PROPERLY ISOLATE
EACH SECTION OF PIPING LOOP AS DESCRIBED IN PHASING SEQUENCES,
1) SHUT-OFF ISOLATION VALVES ON INTERIOR SIDE OF LOOP BEING
MODIFIED OR REMOVED TO MAINTAIN SERVICES TO ALL RISERS.
2) REMOVE SECTION OF PIPING, OR TAP TEMPORARY DRAIN CONNECTION
TO VERIFY VALVES ARE HOLDING FOR A MINIMUM PERIOD OF 24 HOURS.
3) IF NO VALVE LEAKAGE, OR MINIMAL AMOUNT, IS WITNESSED THAN
PROCEED TO PIPING MODIFICATION AND/OR DEMOLITION SCOPE OF WORK
IDENTIFIED.
4) IF MODERATE OR SIGNIFICANT VALVE LEAKAGE IS WITNESSED THAN
PROVIDE 1.5" VALVE TAP WITH THREADED CONNECTION TO HOSE TO
NEAREST MECHANICAL ROOM DRAIN DISCHARGE LOCATION. THIS
TEMPORARY DRAIN CONNECTION AND HOSE SHALL BE REMOVED ONCE
NEW RISER VALVE REPLACEMENTS ARE COMPLETED.
---CONTRACTOR WILL BE RESPONSIBLE TO KEEP ON SITE AT LEAST FOUR(4)
SETS OF 1.5" VALVES WITH THREADED CONNECTIONS AND TWO(2) 250' LONG
HOSES OF 1.5" DIAMETER IN SIZE.
CONTRACTOR ALLOWANCE FOR TEMP FIXTURES OR WATER SERVICES:
ASSUME THAT DURING THE COURSE OF THE 8 PHASE DOMESTIC WATER
LOOP REPLACEMENT THAT SPECIFIC AREAS WILL REQUIRE TEMPORARY
SINKS AND/OR EXTENSION OF TEMPORARY WATER SERVICES TO THEIR
DEPARTMENT. CONTRACTORS SHALL INCLUDE THE FOLLOWING
ALLOWANCES WITHIN THEIR BASE BID TO ACCOMMODATE THOSE
REQUESTS WHEN THEY ARISE DURING OUTAGE COORDINATION WITH VA
FACILITIES.
• INCLUDE UP TO TWELVE(12) TEMPORARY SINK FIXTURES TIED INTO AN
ADJACENT RISER SERVICE. EACH SINK WILL REQUIRE UP TO 50' OF
COPPER PIPE FOR WATER CONNECTIONS, OTHERWISE HOSE WILL BE
UTILIZED IF DISTANCE EXCEEDS THAT SPECIFIED AMOUNT OF PIPING.
• INCLUDE FOUR(4) TEMPORARY BACK-UP WATER CONNECTIONS FOR
COLD WATER SERVICE TO AN ENTIRE DEPARTMENT. TEMPORARY COLD
WATER MAIN SHALL BE ASSUMED AT 2" SIZE AND EXTEND A MAXIMUM OF
250' TO CONNECT INTO AN ADJACENT RISER SERVICE.
• NOTE THAT THE ABOVE IS FOR ENTIRE PROJECT, NOT PER PHASE.
23 29
G
1356-PP104.2
A.C
A.A
A.B
E.C
E.A E.B
1356-PP104.1
HJKL G
1356-PP103.1
1356-PP104.1
1356-PP104.2
E.C
E.A E.B
1356-PP104.1
HJKL
C W
C W
C W
G
8" CW
2 1/2" CHW
4" HW
H
2" SOFT
10" HPS
4" PC
5" CHWR
5" MPC
8" CHWS
8" CHWR
8" MPS
12" CHWR
12" CHWS
5" CHWS
5" CHWR
8" CHWS
8" CHWR
6" CW
5" HW
8" CW
2 1/2" CHW
12" CHWR
12" CHWS
6" PC
5" CHWR
2 1/2" V
2 1/2" HWS
5" CHWS
8" CHWS
6" CW
6" CW
6" CW
1/2" CW
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS SUBMISSION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
TRUE NORTH
PLAN NORTH
B
D
C R e v it P ro je c ts
\V A
B u ild in g
P h a s e
M e c h a n ic a l ja s o n g o tt w a lt
.r v t
/3 /2
:4
:5
A M
BASEMENT INTERSTITIAL - PHASE
4 - DOMESTIC WATER PLAN
PREVENT LEGIONELLA,
PHASE III
MINNEAPOLIS
618-14-118
11/30/2022 JG TM / JG618-14-118
1356-PP104.1
NO SCALE
PHASE 4 - ISOMETRIC VIEW
1/4" = 1'-0"
ENLARGED - PHASE 4.3
1/16" = 1'-0"
PHASE 4.1 - DEMO
1/16" = 1'-0"
PHASE 4.2 - NEW
NO SCALE
PHASE 4 ELEVATION - EAST TUNNEL
NO SCALE
PHASE 4 ELEVATION - WATER SERVICE
CONNECTION
TO PREVIOUS
PHASE.
41360DATE REG. NO.
I HEREBY CERTIFY THAT THIS PLAN,
SPECIFICATION OR REPORT WAS PREPARED BY ME
OR UNDER MY DIRECT SUPERVISION AND THAT I
AM A DULY LICENSED PROFESSIONAL ENGINEER
UNDER THE LAWS OF THE STATE OF MINNESOTA.
JASON GOTTWALT, P.E.
Revisions: Date:
T S
T S
T S
T S
T S
T S
KEY NOTES: GENERAL NOTES:KEY NOTES:
A.C
A.A
A.B
SWH
70-NE-02
2 1/2" RHW
5" HW
4" CW
5" HW
5" HW
4" CW
PRESSURE REDUCING
STATION, REFER TO
DETAIL 3/PP500 AND
HYDRONIC PIPING DWGS
DWP
70-NE-02
DWP
70-NE-01
HJKL
NOTE THAT DOUBLE DASHED LINES REPRESENT
A STRUCTURAL MEZZANINE PLATFORM. PIPING
SHOWN IS BOTH ABOVE AND BELOW.
/2
/2
A.C
A.A
A.B
11 10
HJKL
NOTE THAT THESE KEY NOTES ARE SPECIFIC TO THIS DRAWING (DO
NOT REFER TO MASTER KEY NOTES ON SHEET 1356-PP003). NOT ALL
KEY NOTES ARE UTILIZED AND MAY HAVE GAPS OF MISSING NOTE
NUMBERS TO KEEP GROUPS OF TEN NOTES AVAILABLE PER PHASE.
NOTE THAT PLUMBING KEY NOTES 20 THROUGH 29 BELOW ARE
ASSOCIATED WITH DETAIL 2/PP104.2 ON THIS DRAWING. CLOSELY
COORDINATE INSTALLATION SCHEDULE OF WATER HEATER WITH VA
FACILITIES TO CLOSELY MONITOR EXISTING SYSTEMS THAT WILL
TEMPORARILY SUPPORT THE ENTIRE BUILDING.
STEAM REDUCING STATION SHOWN ON THIS DRAWING FOR
REFERENCE ONLY. REFER TO DRAWING MP104.1 FOR ALL STEAM
PIPING INSTALLATION NOTES AND DETAILS.
INSTALL A FULL SIZE 4" STAINLESS STEEL TRIPLE OFFSET BUTTERFLY
VALVE TO ISOLATE HOT WATER SERVICE FROM NEW WATER HEATER
SYSTEM. NOTE TO PROVIDE THIS VALVE DURING WEEKEND OUTAGE
WHEN CROSS-OVER PIPING CONNECTION TO RISER 'A' IS INSTALLED.
DURING WEEKEND OUTAGE OF RISER 'A' (PLUS NORTHEAST QUADRANT
OF LOWER LEVEL) INSTALL SECTION OF 6" PIPING BETWEEN POINTS OF
DISCONNECT, ALONG WITH VALVE SHOWN IN KEY NOTE #21, TO
TEMPORARILY FEED THOSE AREAS FROM MAIN LOOP WHILE NEW
WATER HEATER SYSTEMS ARE BEING INSTALLED.
PROVIDE TWO(2) RECIRCULATION PUMPS VERTICALLY STACKED IN A
PARALLEL PIPING CONFIGURATION WITH DUAL ISOLATION VALVES ON
EITHER SIDE AND FULL SIZED STRAINERS WITH BLOW-DOWN VALVES.
INCLUDE PRESSURE AND TEMPERATURE GAUGES ON BOTH SIDES OF
DUAL RECIRCULATION PUMP ASSEMBLIES.
PROVIDE A 1.5" CIRCUIT SETTER FOR BALANCING LARGE
RECIRCULATION TAKE-OFF TO RISER 'A' AND NE PORTION OF LOWER
LEVEL. INCLUDE PRESSURE AND TEMPERATURE GAUGES TO ASSIST IN
BALANCING ALONG WITH FULL SIZED ISOLATION VALVES ON EITHER
SIDE FOR SERVICING WHEN REQUIRED.
POINT OF CONNECTION FOR COLD WATER MAKE-UP TO NEW WATER
HEATERS FROM ISOLATION VALVE INSTALLED DURING PHASE 3 (SEE
DRAWING PP103). CONTRACTOR TO TEST, STERILIZE, AND
THOROUGHLY FLUSH NEW PIPING AND WATER HEATER SYSTEM PRIOR
TO ENGAGING INTO SERVICE.
VERIFY ADEQUATE SPACE FROM COLUMN FOR PULLING TUBE BUNDLES
OUT HORIZONTALLY. COORDINATE ALL OTHER SERVICE ACCESS WITH
VA FACILITIES REPRESENTATIVES.
PHASE 4.1 (DEMO - REFER TO DETAIL 1 AND 10-19 SERIES KEY NOTES):
REFER TO DRAWING PP104 DRAWINGS FOR DESCRIPTIVE NOTES AND
DETAILS OF THIS PHASE THAT IS DEFINED ON THAT DRAWING.
PHASE 4.2 (BUILD-BACK - REFER TO DETAIL 2 AND 20-29 SERIES KEY NOTES):
REFER TO DRAWING PP104 DRAWINGS FOR DESCRIPTIVE NOTES AND
DETAILS OF THIS PHASE THAT IS DEFINED ON THAT DRAWING.
PHASE 4.3 (WATER SERVICE REPLACEMENT - 30+ SERIES KEY NOTES):
REFER TO DRAWING PP104 DRAWINGS FOR DESCRIPTIVE NOTES AND
DETAILS OF THIS PHASE THAT IS DEFINED ON THAT DRAWING.
PHASE 4.4 (WATER HEATER INSTALLATION / FINAL CONNECTIONS):
MECHANICAL CONTRACTOR MAY SCHEDULE AND PERFORM
PREINSTALLATION OF EQUIPMENT AND PIPING DURING PHASES 1 THROUGH
4 AND MAKE ALL FINAL CONNECTIONS DURING PHASE 3.4 SERVICE OUTAGE.
ALL CONTROLS AND PIPING COMPONENTS SHALL BE FULLY TESTED AND
COMMISSIONED DURING PHASE 4 AND READY TO BE SHIFTED ONLINE PRIOR
TO ENTERING PHASE 5.1 DEMOLITION.
ISOLATION OF MAIN PIPING LOOP SECTIONS:
PERFORM THE FOLLOWING PROCEDURE STEPS TO PROPERLY ISOLATE
EACH SECTION OF PIPING LOOP AS DESCRIBED IN PHASING SEQUENCES,
1) SHUT-OFF ISOLATION VALVES ON INTERIOR SIDE OF LOOP BEING
MODIFIED OR REMOVED TO MAINTAIN SERVICES TO ALL RISERS.
2) REMOVE SECTION OF PIPING, OR TAP TEMPORARY DRAIN CONNECTION
TO VERIFY VALVES ARE HOLDING FOR A MINIMUM PERIOD OF 24 HOURS.
3) IF NO VALVE LEAKAGE, OR MINIMAL AMOUNT, IS WITNESSED THAN
PROCEED TO PIPING MODIFICATION AND/OR DEMOLITION SCOPE OF WORK
IDENTIFIED.
4) IF MODERATE OR SIGNIFICANT VALVE LEAKAGE IS WITNESSED THAN
PROVIDE 1.5" VALVE TAP WITH THREADED CONNECTION TO HOSE TO
NEAREST MECHANICAL ROOM DRAIN DISCHARGE LOCATION. THIS
TEMPORARY DRAIN CONNECTION AND HOSE SHALL BE REMOVED ONCE
NEW RISER VALVE REPLACEMENTS ARE COMPLETED.
---CONTRACTOR WILL BE RESPONSIBLE TO KEEP ON SITE AT LEAST FOUR(4)
SETS OF 1.5" VALVES WITH THREADED CONNECTIONS AND TWO(2) 250' LONG
HOSES OF 1.5" DIAMETER IN SIZE.
CONTRACTOR ALLOWANCE FOR TEMP FIXTURES OR WATER SERVICES:
ASSUME THAT DURING THE COURSE OF THE 8 PHASE DOMESTIC WATER
LOOP REPLACEMENT THAT SPECIFIC AREAS WILL REQUIRE TEMPORARY
SINKS AND/OR EXTENSION OF TEMPORARY WATER SERVICES TO THEIR
DEPARTMENT. CONTRACTORS SHALL INCLUDE THE FOLLOWING
ALLOWANCES WITHIN THEIR BASE BID TO ACCOMMODATE THOSE
REQUESTS WHEN THEY ARISE DURING OUTAGE COORDINATION WITH VA
FACILITIES.
• INCLUDE UP TO TWELVE(12) TEMPORARY SINK FIXTURES TIED INTO AN
ADJACENT RISER SERVICE. EACH SINK WILL REQUIRE UP TO 50' OF
COPPER PIPE FOR WATER CONNECTIONS, OTHERWISE HOSE WILL BE
UTILIZED IF DISTANCE EXCEEDS THAT SPECIFIED AMOUNT OF PIPING.
• INCLUDE FOUR(4) TEMPORARY BACK-UP WATER CONNECTIONS FOR
COLD WATER SERVICE TO AN ENTIRE DEPARTMENT. TEMPORARY COLD
WATER MAIN SHALL BE ASSUMED AT 2" SIZE AND EXTEND A MAXIMUM OF
250' TO CONNECT INTO AN ADJACENT RISER SERVICE.
• NOTE THAT THE ABOVE IS FOR ENTIRE PROJECT, NOT PER PHASE.
NOTE THAT THESE KEY NOTES ARE SPECIFIC TO THIS DRAWING (DO
NOT REFER TO MASTER KEY NOTES ON SHEET 1356-PP003). NOT ALL
KEY NOTES ARE UTILIZED AND MAY HAVE GAPS OF MISSING NOTE
NUMBERS TO KEEP GROUPS OF TEN NOTES AVAILABLE PER PHASE.
NOTE THAT DEMOLITION NOTES 10 THROUGH 19 BELOW ARE
ASSOCIATED WITH DETAIL 1/PP104.2 ON THIS DRAWING. DO NO
PERFORM ANY DEMOLITION UNTIL ISOLATION IS COORDINATED.
REMOVE EXISTING SECTIONS OF COLD WATER, HOT WATER, AND
RECIRC PIPING INDICATED ON DRAWING IN PREPARATION FOR NEW
WATER HEATER INSTALLATION. REFER TO PHASE 3 PLANS FOR
INSTALLATION OF ISOLATION VALVES NEEDED IN ORDER TO ALLOW
FOR PIPING DEMOLITION.
SECTION OF HOT WATER PIPING INDICATED FOR REMOVAL WILL NEED
TO REMAIN IN PLACE AS LONG AS POSSIBLE TO KEEP RISER 'A ' AND
NORTHEAST SECTION OF BASEMENT LEVEL IN SERVICE. HAVE PIPING
PREPARED TO ALONG FOR QUICK SWITCHOVER TO NEW WATER
HEATER SYSTEM DURING SCHEDULED WEEKEND OUTAGE.
REMOVE EXISTING HOT WATER HEAT EXCHANGERS AND
CONTROLLERS. ALL ASSOCIATED VALVES AND COMPONENTS SHALL
BE FULLY REMOVED AND DISPOSED OF BY CONTRACTOR. CLEAN UP
MEZZANINE AREA AND PATCH AREAS OF FLOOR GRATING CAUSED BY
DEMOLITION (VISIT SITE TO CONFIRM CONDITIONS PRIOR TO BID).
REMOVE EXISTING RECIRCULATION PUMP AND STAND. NOTE THAT
AFTER DISCONNECTION OF THIS RECIRCULATION SYSTEM THAT ENTIRE
BUILDING MAY SIGNIFICANTLY TREND OUT OF BALANCE. INTENT
WOULD BE FOR CONTRACTOR TO HAVE ALL TEMPERATURE SENSORS
FOR EACH RECIRCULATION LOOP APPROPRIATELY VERIFIED AND
ADDRESSED WITHIN BAS SYSTEM (SEE KEY NOTE #21 ON DRAWING
PP03). CONTRACTOR SHALL UTILIZE THESE TEMPERATURE SENSORS
TO MAKE ADJUSTMENTS ON SYSTEM TO COMPENSATE FOR PERIOD OF
TIME WITH REDUCED RECIRCULATION FLOW ORIGINATING ONLY FROM
SOUTHWEST PUMP.
TEMPORARILY DISCONNECT SET OF RPZ BACKFLOW ASSEMBLIES
FROM DOMESTIC WATER MAIN. CHECK EXISTING VALVE SEAL AND
TEMPORARILY CAP UNTIL RECONNECTION INTO WATER HEATER MAKE-
UP, AND RECONNECTION INTO RPZ VALVE ASSEMBLIES TO REMAIN.
REMOVE SET OF THREE(3) VALVES AT THIS LOCATION. CONFIRM IF VA
WOULD LIKE TO SALVAGE THESE VALVES BEFORE DISPOSAL.
14 25
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS SUBMISSION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
TRUE NORTH
PLAN NORTH
B
C R e v it P ro je c ts
\V A
B u ild in g
P h a s e
M e c h a n ic a l ja s o n g o tt w a lt
.r v t
/3 /2
:4
:0
A M
BASEMENT INTERSTITIAL - PHASE
4.4 - DOMESTIC WATER PLAN
PREVENT LEGIONELLA,
PHASE III
MINNEAPOLIS
618-14-118
11/30/2022 JG TM / JG618-14-118
1356-PP104.2
1/4" = 1'-0"
ENLARGED - PHASE 4.4
1/4" = 1'-0"
ENLARGED DEMOLITION - PHASE 4.4
41360DATE REG. NO.
I HEREBY CERTIFY THAT THIS PLAN,
SPECIFICATION OR REPORT WAS PREPARED BY ME
OR UNDER MY DIRECT SUPERVISION AND THAT I
AM A DULY LICENSED PROFESSIONAL ENGINEER
UNDER THE LAWS OF THE STATE OF MINNESOTA.
JASON GOTTWALT, P.E.
T S
TS
T S
T S
KEY NOTES:
GENERAL NOTES:
TS T
S
T S
T S
T S
TU
2.C' 2.B'
2.A'
REFER TO DETAIL
1/1356-PP105.1
FOR VALVE LOCATION.
REFER TO DETAIL
1/1356-PP106.1
FOR VALVE
LOCATION.
DRAIN
1356-PP105.1
8"
4" HW
8" CW
2 1/2" CHW
/4
C H
W
Z
BW.A
BW.BBW.C
REFER TO DETAIL
1/1356-PP106.1 FOR
VALVE LOCATION.
REFER TO DETAIL
1/1356-PP105.1 FOR
VALVE LOCATION.
1 1/2" CW
DRAIN
2.5" TAKE-OFF VALVE
8" CW 8" CW
2 1/2" CHW
4" HW
A.B
A.C
8" CW
8" CW
2 1/2" RHW
8" CW
4" HW
2.B'
2.C'
2.A'
BW.B
BW.C
BW.A
TO BE
REPLACED
IN NEXT
PHASE
8" CW
NOTE THAT THESE KEY NOTES ARE SPECIFIC TO THIS DRAWING (DO
NOT REFER TO MASTER KEY NOTES ON SHEET 1356-PP003). NOT ALL
KEY NOTES ARE UTILIZED AND MAY HAVE GAPS OF MISSING NOTE
NUMBERS TO KEEP GROUPS OF TEN NOTES AVAILABLE PER PHASE.
INSTALL 8" SCHEDULE 10 STAINLESS STEEL PIPING MAIN ALONG NORTH
WALL OF SERVICE TUNNEL (WITHIN OPEN AREA OF EXISTING PIPE
RACK). CONTRACTOR SHALL PROVIDE ADDITIONAL SUPPORT BRACES
ON EXISTING PIPING RACK TO SUPPORT NEW PIPE CLAMPS. ALL PIPE
RACK MODIFICATIONS TO BE REVIEWED BY STRUCTURAL ENGINEER.
NOTE THAT NEW RISER VALVES SHALL BE PRE-INSTALLED DURING THIS
PHASE WHEN POSSIBLE. REFER TO ENLARGED PLANS FOR VALVE
REPLACEMENT INFORMATION.
PROVIDE TEMPORARY END CAPS AT EITHER SIDE OF NEW PIPING
SECTION. FIRST PERFORM A PRESSURE TEST ON PIPING SECTION PER
SPECIFICATION REQUIREMENTS, AND THEN STERILIZE PIPING USING
CHLORINE SOLUTION FOR AT LEASE 24 HOURS PRIOR TO FLUSHING.
INCLUDE DRAIN/FILL VALVES ON EITHER END TO ACCOMPLISH.
INSULATE ENTIRE LENGTH OF PIPING PER SPECIFICATION
REQUIREMENTS. INCLUDE CONTINUOUS PVC COVERING THROUGHOUT
AND PREPARE ENDS FOR EXTENSION TO NEXT SUB-PHASE PIPING
WHICH WILL INCLUDE INSULATING ALL VALVE BODIES.
EXISTING VALVE TO REMAIN UNTIL COMPLETION OF PHASE 5.2.
ROUTING OF NEW 8" COLD WATER MAIN THROUGH THIS AREA WILL BE
EXTREMELY CONSTRICTED BY EXISTING PIPING SERVICES ENTERING
TUNNEL. CONTRACTOR MAY NEED TO TEMPORARILY DISCONNECT AND
RECONNECT SOME SERVICE TO GET PROPER ACCESS ALONG WALL TO
ROUTE NEW PIPING MAIN THROUGH, AND/OR DEMOLISH EXISTING
PIPING MAIN ON COMPLETION. FIELD VERIFY SITE CONDITIONS.
NOT USED THROUGH KEY NOTE
PROVIDE TWO(2) 8" VALVES ON EITHER SIDE OF COLD WATER RISER
TAKE-OFF VALVE WITH NEW STAINLESS 8" TRIPLE OFFSET BUTTERFLY
VALVES AND ALSO REPLACE THE THIRD EXISTING TAKE OFF VALVE
(refer to plans for size info) WITH THE SAME MODEL VALVE AS MAIN LOOP.
INCLUDE A 1.5" STAINLESS STEEL BALL VALVE FOR DRAINING RISER IN
SECTION OF PIPING BETWEEN THESE THREE VALVES. NOTE THAT THIS
PHASE WILL BE HAPPENING CONCURRENTLY WITH RISER
REPLACEMENT CONNECTIONS. REFER TO THOSE NOTES FOR
STERILIZING AND FLUSHING ALL NEW PIPING AND VALVES PRIOR TO
CONNECTION INTO MAIN SYSTEM.
WHEN ALL PREINSTALLATION OF VALVES AND PIPING IS COMPLETED,
COORDINATE SERVICE OUTAGE PER GENERAL NOTE DESCRIPTION.
PERFORM RECONNECTION TO EXISTING PIPING AS REQUIRED.
DURING OUTAGE, INSTALL THERMOWELLS ON BOTH HOT AND COLD
WATER MAINS TO ACCEPT AN INSERTION TYPE TEMPERATURE SENSOR
TO BE INTEGRATED INTO BUILDING AUTOMATION SYSTEM FOR
INFORMATION MONITORING AND TRENDING.
INSTALL STRAP ON TEMPERATURE SENSORS INDICATED ON
RECIRCULATION PIPING. REPAIR ANY DAMAGED OR REMOVED
INSULATION ON COMPLETION.
ONCE VALVE INSTALLATION IS COMPLETED, INSULATE ALL AFFECTED
PIPING AND NEW VALVE BODIES COMPLETELY. COVER EVERYTHING
WITH PVC JACKET COVERS AND SEAL AS REQUIRED. INSULATION CAN
OCCUR DURING NORMAL HOURS AFTER OUTAGE COMPLETION, BUT
SHOULD NOT BE DELAYED FOR ANY MORE THAN 3 BUSINESS DAYS.
SHUT-OFF VALVE A.C AND VALVE M.B (BOTH FURTHER OUT TO NEXT
ADJACENT RISER VALVES OUTSIDE THE EXTENTS OF THIS PHASE
DRAWING) TO ISOLATE THIS SECTION OF PIPING FOR VALVE
REPLACEMENT. REFER TO GENERAL NOTES FOR PROVISIONS TO BE
TAKEN TO VERIFY ANY EXISTING VALVE LEAKAGE AND AREAS THAT
WILL BE AFFECTED BY THIS MAJOR WATER OUTAGE.
NOT USED THROUGH KEY NOTE
ONCE ISOLATED, REMOVE SECTION OF 8" GALVANIZED PIPING LOOP.
CUT INTO SECTIONS SMALL ENOUGH TO TRANSPORT TO LOADING
DOCK AREA FOR REMOVAL. INCLUDE DEMOLITION OF EXISTING
SUPPORTS MOUNTED TO PIPING RACKS, NEW PIPING WILL BE
SUPPORTED ONTO EXISTING RACK STRUCTURE BUT SHOULD BE
PROVIDED WITH NEW PIPE CLAMPS.
PHASE 5.1 (PREINSTALLATION) - DETAIL 1 AND 10-19 SERIES KEY NOTES):
APPROACH WITHIN THIS PHASE WILL BE SLIGHTLY DIFFERENT THAN
PREVIOUS PHASES 1-3 IN THAT THE NEW STAINLESS STEEL PIPING MAINS
WILL BE PREINSTALLED AND TESTED PRIOR TO DEMOLITION OF EXISTING
MAINS. REFER TO DETAIL 1 ON THIS DRAWING FOR LOCATION OF NEW
SECTION OF PIPING LOOP ON OPPOSITE NORTH WALL WITHIN AVAILABLE
SPACE OF EXISTING PIPING RACK ON THAT SIDE.
PHASE 5.2 (RECONNECT TO EXISTING RISERS - DETAILS 3 & 4 PLUS NOTES):
ALL NEW ISOLATION VALVES WILL BE PREINSTALLED, SANITIZED, FLUSHED,
AND TESTED PRIOR TO CONNECTION INTO EXISTING LOOP AND RISERS.
THIS SUB-PHASE WILL CAUSE A LARGE DOMESTIC WATER OUTAGE FOR
AREAS OF FACILITY THAT MAY BE CRITICAL, CONTRACTOR SHALL REFER TO
'ALLOWANCE FOR TEMP FIXTURES OR WATER SERVICES' BELOW FOR
ACCOMMODATIONS NEEDED FOR THOSE AREAS. OUTAGE WILL AFFECT THE
FOLLOWING DEPARTMENTS AND SHOULD BE CAREFULLY COORDINATED
WITH VA FACILITIES;
• BASEMENT LEVEL: SAFETY - DIRECTOR'S OFFICE, CANTEEN STORAGE,
NUCLEAR MEDICINE - PET SUITE, RADIOLOGY-MRI
• FIRST FLOOR: VOLUNTARY SERVICE, LIBRARY, MAS, EDUCATION,
PHARMACY OUTPATIENT, SECURITY ADMIN, FISCAL, VETERANS
ASSISTANCE/SERVICE ORGANIZATIONS, NUTRITION/FOOD SERVICE
• SECOND FLOOR: AUDIOLOGY, ACS (SPECIALTY) - EYE, IRM SERVICE,
SURGERY - AMBULATORY
• THIRD FLOOR: PHARMACY OUTPATIENT, REHABILITATION MEDICAL
SERVICE, EDUCATION, ACS (SPECIALTY) - GI CLINIC, ACS (PRIMARY) -
HYPERTENSION/RENAL CLINIC, OUT LEASED - VISN
• FOURTH FLOOR: ECR - GRECC, EDUCATION, DIRECTOR'S SUITE, MEDICAL
MEDIA, MEDICAL RESEARCH - BRAIN SCIENCE.
PHASE 5.3 (DEMO - REFER TO DETAIL 2 AND 30+ SERIES KEY NOTES):
AFTER ALL NEW PIPING HAS BEEN INSTALLED AND RECONNECTED INTO
MAIN LOOP, THEN THE EXISTING GALVANIZED 8" COLD WATER PIPING MAIN
MAY REMOVED. SINCE ALL OUTAGES WERE PERFORMED IN PREVIOUS
PHASE THERE WILL BE NO RESTRICTIONS OR OUTAGE COORDINATION
NECESSARY DURING THIS SUB-PHASE.
ISOLATION OF MAIN PIPING LOOP SECTIONS:
PERFORM THE FOLLOWING PROCEDURE STEPS TO PROPERLY ISOLATE
EACH SECTION OF PIPING LOOP AS DESCRIBED IN PHASING SEQUENCES,
1) SHUT-OFF ISOLATION VALVES ON INTERIOR SIDE OF LOOP BEING
MODIFIED OR REMOVED TO MAINTAIN SERVICES TO ALL RISERS.
2) REMOVE SECTION OF PIPING, OR TAP TEMPORARY DRAIN CONNECTION
TO VERIFY VALVES ARE HOLDING FOR A MINIMUM PERIOD OF 24 HOURS.
3) IF NO VALVE LEAKAGE, OR MINIMAL AMOUNT, IS WITNESSED THAN
PROCEED TO PIPING MODIFICATION AND/OR DEMOLITION SCOPE OF WORK
IDENTIFIED.
4) IF MODERATE OR SIGNIFICANT VALVE LEAKAGE IS WITNESSED THAN
PROVIDE 1.5" VALVE TAP WITH THREADED CONNECTION TO HOSE TO
NEAREST MECHANICAL ROOM DRAIN DISCHARGE LOCATION. THIS
TEMPORARY DRAIN CONNECTION AND HOSE SHALL BE REMOVED ONCE
NEW RISER VALVE REPLACEMENTS ARE COMPLETED.
---CONTRACTOR WILL BE RESPONSIBLE TO KEEP ON SITE AT LEAST FOUR(4)
SETS OF 1.5" VALVES WITH THREADED CONNECTIONS AND TWO(2) 250' LONG
HOSES OF 1.5" DIAMETER IN SIZE.
CONTRACTOR ALLOWANCE FOR TEMP FIXTURES OR WATER SERVICES:
ASSUME THAT DURING THE COURSE OF THE 8 PHASE DOMESTIC WATER
LOOP REPLACEMENT THAT SPECIFIC AREAS WILL REQUIRE TEMPORARY
SINKS AND/OR EXTENSION OF TEMPORARY WATER SERVICES TO THEIR
DEPARTMENT. CONTRACTORS SHALL INCLUDE THE FOLLOWING
ALLOWANCES WITHIN THEIR BASE BID TO ACCOMMODATE THOSE
REQUESTS WHEN THEY ARISE DURING OUTAGE COORDINATION WITH VA
FACILITIES.
• INCLUDE UP TO TWELVE(12) TEMPORARY SINK FIXTURES TIED INTO AN
ADJACENT RISER SERVICE. EACH SINK WILL REQUIRE UP TO 50' OF
COPPER PIPE FOR WATER CONNECTIONS, OTHERWISE HOSE WILL BE
UTILIZED IF DISTANCE EXCEEDS THAT SPECIFIED AMOUNT OF PIPING.
• INCLUDE FOUR(4) TEMPORARY BACK-UP WATER CONNECTIONS FOR
COLD WATER SERVICE TO AN ENTIRE DEPARTMENT. TEMPORARY COLD
WATER MAIN SHALL BE ASSUMED AT 2" SIZE AND EXTEND A MAXIMUM OF
250' TO CONNECT INTO AN ADJACENT RISER SERVICE.
• NOTE THAT THE ABOVE IS FOR ENTIRE PROJECT, NOT PER PHASE.
NPQRSTUVWXYZ
1356-PP105.1
1356-PP105.1
A.B
A.C
2.C'
2.A'
2.B'
BW.A'
BW.A
BW.C BW.B
BW.B'BW.C'
10 12 13 10 12 13 10 12 13
CONTRACTOR NOTE: NEED TO CAREFULLY
SITE SURVEY THIS AREA FOR ROUTING AND
DISPLACEMENT OF EXISTING SERVICES
1356-PP105.1
1356-PP105.1
JKLM
8" CW8" CW8" CW8" CW8" CW
NPQRSTUVWXYZ
BW.C
BW.C'
BW.A'
BW.A
BW.B'
BW.B
2.C'
2.A'
2.B'
A.C
A.B
30 30 30
JKLM
8" CW 2 1/2" RHW
4" HW
8" CW
J
3/4" CW
10" HPS
12" HPS
10" HPS
8" CHWS
8" CHWR
6" PC
20" CHWS
20" CHWR
12" CHWR12" CHWS
4" HW
8" CW
4" CW
8" CW
2 1/2" RHW
8" CHWR
8" CHWS
10" HPS
2" MPS
2" MPC
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS SUBMISSION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
TRUE NORTH
PLAN NORTH
A B
C R e v it P ro je c ts
\V A
B u ild in g
P h a s e
M e c h a n ic a l ja s o n g o tt w a lt
.r v t
/3 /2
:4
:0
A M
BASEMENT INTERSTITIAL - PHASE
5 - DOMESTIC WATER PLAN
PREVENT LEGIONELLA,
PHASE III
MINNEAPOLIS
618-14-118
11/30/2022 JG TM / JG618-14-118
1356-PP105.1
1/4" = 1'-0"
ENLARGED - PHASE 5.2.1
1/4" = 1'-0"
ENLARGED - PHASE 5.2.2
NO SCALE
PHASE 5 - ISOMETRIC VIEW
1/16" = 1'-0"
PHASE 5.1 - NEW
1/16" = 1'-0"
PHASE 5.3 DEMO
NO SCALE
PHASE 5 ELEVATION - EAST TUNNEL
NO SCALE
PHASE 5 ELEVATION - NORTH TUNNEL
CONNECTION
TO PREVIOUS
PHASE.
41360DATE REG. NO.
I HEREBY CERTIFY THAT THIS PLAN,
SPECIFICATION OR REPORT WAS PREPARED BY ME
OR UNDER MY DIRECT SUPERVISION AND THAT I
AM A DULY LICENSED PROFESSIONAL ENGINEER
UNDER THE LAWS OF THE STATE OF MINNESOTA.
JASON GOTTWALT, P.E.
TS
S
TS
T S
T S
T S
T S
T S
KEY NOTES: GENERAL NOTES:
T S
T S
UV
4" CW
4" CW
UV
SHAFT 2
SHAFT 3
4" CW
3" CW
3" CW UP
2 1/2" HW UP
3" CW UP
1" RHW UP
UVWXYZAABBCCDDEEFFGGHH
1 1 1
TO VALVE M.C, SEE
1/1356-PP106.1
TO VALVE BP.B,
SEE 1/1356-PP107.1
SHAFT 2
SHAFT 3
3.B
3.A
3.C
4" CW
C W
C W
8" CW
C W
C W
H W
/4
R H
W
C W
/2
H W
R H
W
C W
3/4" CW
2 1/2" CW
3" CW UP
1" RHW UP 2 1/2" HW UP
3" CW UP
WARNING: CONGESTED
AREA OF INTERSTITIAL
SURROUNDING SHAFT #2
4" CW
4" CW
1 BEFORE OUTAGE: REMOVE ABANDONED 4" COPPER PIPING AND
REPLACE WITH NEW PIPING TO SERVE SHAFT 2 AND SHAFT 3. EXTEND
TAKEOFF PIPING TO SHAFT 2, SHAFT 3 AND BRANCHES SERVING
BASEMENT LEVEL AS INDICATED ON PLAN. CONTRACTOR TO VERIFY
PIPE SIZING AND OUTAGE AREAS PRIOR TO CONSTRUCTION.
DURING OUTAGE: CLOSE VALVES M.C (1/1356-PP106.1) AND BP.B
(1/1356-PP107.1) TO MAKE TEMPORARY CONNCTION INTO EXISTING
MAIN. NEW RISER VALVE ASSEMBLY TO BE INSTALLED IN PHASE 7.
MAKE FINAL CONNECTIONS TO SHAFT 2, SHAFT 3, SHAFT 3
ASSOCIATED TAKEOFFS ON ALL LEVELS (1356-PP105.3), AND BRANCH
TAKEOFFS SERVING BASMENT LEVEL.
AFTER OUTAGE: REFER TO ASSOCIATED LEVEL DEMOLITION VIEWS
AND KEY NOTE 2.
AFTER OUTAGE: REMOVE ABANDONED COLD WATER RISER PIPING.
DEADLEG OR ABANDONED PIPING SHALL NOT REMAIN.
NOTE TO CONTRACTOR: THERE IS A REASON WHY NEW COLD
WATER MAIN ROUTING DOES NOT FOLLOW THIS EXISTING PATH.
AREA IS EXTREMELY CONGESTED WITH 'CHALLENGING
ACCESSIBILITY'. DEMOLISHED PIPING MAY NEED TO BE CUT INTO
SMALL SECTIONS FOR REMOVAL. FIELD VERIFY SITE CONDITIONS
PRIOR TO BID.
LABEL COLD WATER MAIN "NEW VALVE ASSEMBLY SERVING SHAFT 2
AND SHAFT 3 LOCATED SOUTH OF COLUMN 25/GG." REFER TO KEY
NOTE #7 BELOW.
SIGNIFICANT DUCTWORK CONGESTION IN THIS AREA. CONTRACTOR
WILL BE REQUIRED TO OFFSET PIPING AROUND DUCT
OBSTRUCTIONS AND FOLLOW APPROXIMATE PATH INDICATE AROUND
MOST CONSTRICTIVE AREAS. CONTRACTOR MAY BE REQUIRED TO
DISCONNECT AND RECONNECT SOME DUCT MAINS FOR ACCESS AND
CONSTRUCTABILITY, COORDINATE SCHEDULE OF ASSOCIATED HVAC
OUTAGES WITH VA REPRESENTATIVES. FIELD VERIFY SITE
CONDITIONS.
REFER TO DRAWING 1356-PP105.3 FOR CONTINUATION AND
REPLACEMENT OF EXISTING GALVANIZED RISER WITHIN SHAFT #3
ABOVE. CORE DRILL NEW PIPE PENTRATION FOR PARALLED RISER
TO BE INSTALLED PRIOR TO DEMOLITION OF EXISTING.
DISCONNECT AND RECONNECT SHAFT #2 AT BASE OF RISER DURING
SCHEDULED OUTAGE.
CLEARLY LABEL RISER TAKE-OFF VALVE TO SERVE BOTH SHAFT #2
AND SHAFT #3 RISERS. ALSO INDICATE THAT CORRESPONDING HOT
WATER AND RECIRC VALVE ARE LOCATED IN SERVICE TUNNEL NEAR
GRIDLINES 32/U. REFER TO KEY NOTE #3 ABOVE.
A.
B.
C.
D.
E.
F.
THE OUTLINE OF 'MEANS-AND-METHODS' NOTES BELOW FOR VERTICAL
COLD WATER RISER REPLACEMENTS INDICATED WITHIN THESE
DRAWINGS IS NOT INTENDED TO BE ALL-INCLUSIVE OF EFFORT
REQUIRED BY CONTRACTOR. NOR ARE THESE NOTES AND/OR
SUGGESTIONS MEANT TO LIMIT CONTRACTORS FROM DEVELOPING
THEIR OWN APPROACH THAT MAY BE CONSIDERED MORE COST
EFFECTIVE OR SAFE. THESE NOTES ARE MAINLY MEANT TO QUALIFY
EXISTING CONDITIONS AND DEFINE MINIMUM LEVEL OF PLANNING
REQUIRED BY VA FOR EACH OF THESE TIME SENSITIVE OUTAGES.
NO MAJOR WATER OUTAGE SHALL LAST MORE THAN 12 HOURS IN
DURATION. PLUMBING CONTRACTOR TO DETERMINE ADEQUATE
NUMBER OF PLUMBER CREWS REQUIRED TO PERFORM MULTIPLE
TASKS SIMULTANEOUSLY DURING OUTAGES. ALL OUTAGES SHALL BE
ASSUMED TO BE PERFORMED DURING WEEKEND OR NIGHT OVERTIME
HOURS WHEN BIDDING THIS PROJECT.
VERTICAL RISER REPLACEMENT (TYPE 1 - WITHIN MECHANICAL ROOM)
• FOR RISERS WITHIN MECHANICAL ROOMS, CONTRACTOR SHALL
CORE DRILL HOLES THROUGH FLOOR ADJACENT TO EXISTING
PLUMBING RISER FOR NEW INSTALLATION. EXISTING FLOOR
PENETRATIONS AND/OR SLEEVE SHALL BE PATCHED FLUSH TO
EXISTING FLOOR AS REQUIRE UPON DEMOLITION OF THOSE RISERS.
• EXISTINGT TAKE-OFF VALVES MAY REQUIRE RELOCATION FOR
CONNECTION INTO NEW RISER. VERIFY ADEQUATE ACCESS TO ALL
TAKE-OFF VALVES AND PROVIDE WITH NEW LAMINATE SIGNAGE.
ANY VALVES FOUND AT INACCESSIBLE LOCATIONS SHALL BE
RELOCATED BY CONTRACTOR.
• REFER TO CLIN 3001 FOR REPLACEMENT OF ALL ICRCUIT SETTER
VALVES WITHIN ENTIRE BUILDING. PLUMBING CONTRACTOR MAY
OPT TO HAVE DEDICATED CREWS ASSIGNED TO THIS TASK DURING
RISER OUTAGE TO LIMIT NUMBER OF SECONDARY OUTAGES
REQUIRED. HOWEVER, IF ENOUGH PLUMBERS ARE AVAILABLE TO
ACHIEVE THIS DURING LIMITED OUTAGE TIMEFRAME, THAN REFER
TO GENERAL NOTES ON DRAWING PP002 FOR 'LARGE OUTAGES' TO
PERFORM PRIOR TO THE MAJOR RISER OUTAGE.
VERTICAL RISER REPLACEMENT (TYPE 2 - WITHIN ENCLOSED SHAFT)
• IN GENERAL, MAJOR RATED SHAFTS SHOWN IN THESE DRAWINGS
HAVE EXISTING FULL SIZED ACCESS DOOR FROM BASE OF SHAFT
ON FIRST FLOOR LEVEL. HOWEVER, THAT IS TYPICALLY THE ONLY
ACCESS INTO THESE SHAFTS THAT ARE FULLY OPEN (NO
INTERMEDIATE FLOOR STRUCTURES) UP THROUGH PENTHOUSE
LEVEL WHERE RATED WALLS ARE BUILT-UP WITH LID (TYPICALLY
12'+) WITHIN ENCLOSED PENTHOUSE LEVEL.
• IN ORDER TO GAIN ACCESS TO TOP OF SHAFT, CONTRACTOR WILL
BE REQUIRED TO FURNSIH AND INSTALL FIRE RATED DOOR
ASSEMBLIES FROM PENTHOUSE LEVEL. THESE DOORS MAY BE
USED IN CONJUCTION OF RIGGING FOR BOSUN CHAIRS FROM TOP
OF SHAFT IF CONTRACTOR DEEMS THAT AS SAFE AFTER REVIEW
WITH THEIR INTERNAL SAFETY OFFICIAL.
• IN ADDITION TO ACCESS ON TOP LEVEL OF SHAFT, CONTRACTOR
WILL HAVE OPPORTUNITIES TO INSTALL 24"X24" OR 48"X24" FIRE
RATED ACCESS PANELS ON ANY OTHER LEVEL REQUIRED (BUT
ONLY FROM INTERSTITIAL SPACE, INSTALLATION OF ACCESS
PANELS FROM PATIENT CARE AREAS WILL NOT BE PERMITTED).
• CONTRACTOR WILL BE REQUIRED TO PROVIDE THEIR OWN
SCAFFOLDING REQUIRED AT EACH LEVEL TO INSTALL NEW COLD
WATER RISERS ADJACENT TO EXISTING PRIOR TO SIOWTCHOVER
OUTAGE. SCAFFOLDS SHOULD BE STRATEGICALLY PLACE TO
ALLOW ACCESS FOR RECONNECTION TO FLOOR TAKE-OFF PIPING
INSIDE OF EACH SHAFT.
• EXISTING CONDITION PDF SKETCHES ARE PROVIDED ON DRAWINGS
WHERE WORK INSIDE CONFINED AREAS OF RATED SHAFTS IS
REQUIRED. THESE SKETCHES ARE FOR CONTRACTOR REFERENCE
ONLY AND MAY NOT FULLY INDICATE ALL SERVICES WITHIN SHAFT
ENCLOSURES. CONTRACTOR WILL BE REQUIRED TO FIELD VERIFY
ACTUAL SITE CONDITIONS OF EACH SHAFT WHILE DEVELOPING
ACCESS AND SAFETY PLANNING.
NOTE THAT SOME AREAS HAVE EXISTING COPPER MAINS INTENDED TO
REPLACE GALVANIZED RISERS. HOWEVER THESE MAINS WERE
INSTALLED UP TO 15-25 YEARS AGO AND THEIR INTEGRITY IS
QUESTIONABLE. CONTRACTOR MAY UTILIZE THE EXISTING ROUTE, AND
CORRESPONDING SUPPORT HANGERS, BUT MUST FULLY REMOVE ALL
ABANDONED/UNUSED COPPER PIPING MAINS. ONCE OFF SITE THE
CONTRACTOR MAY TAKE OWNERSHIP OF PIPING FOR RECYLCING OR
REPURPOSING, BUT IT SHALL NOT BE UTILIZED WITHIN THIS PROJECT.
NO EXISTING PIPING WILL BE ALLOWED TO BE LEFT ABANDONED. SOME
AREAS HAVE RESTRICITVE ACCESS DUE TO SURROUNDING PIPES
AND/OR STRUCTURE AND MAY REQUIRE TEMPORARY REMOVAL OF
PIPING OR DUCTWORK TO GAIN ACCESS FOR DEMOLITION.
CONTRACTOR TO ASSUME SOME LEVEL OF DISCONNECT/RECONNECT
OF EXISTING SERVICES TO GAIN ACCCESS FOR COMPLETE DEMOLITION
OF EXISTING PIPING, OR INSTALLATION OF NEW PIPE IN CONGESTED
AREAS. REFER TO DRAWING NOTES FOR ADDITIONAL INFORMATION.
U
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS SUBMISSION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
TRUE NORTH
PLAN NORTH
B
C D
C R e v it P ro je c ts
\V A
B u ild in g
P h a s e
M e c h a n ic a l ja s o n g o tt w a lt
.r v t
/3 /2
:4
:2
A M
BASEMENT - PHASE 5 - ENLARGED
SHAFT 3 COLD WATER
REPLACEMENT PLANS
PREVENT LEGIONELLA,
PHASE III
MINNEAPOLIS
618-14-118
11/30/2022 JG TM / JG618-14-118
1356-PP105.2
1/8" = 1'-0"
BASEMENT - SHAFT 3 REPLACEMENT DEMO (1/2)
1/8" = 1'-0"
BASEMENT - SHAFT 3 REPLACEMENT DEMO (2/2)
1/8" = 1'-0"
BASEMENT - SHAFT 3 REPLACEMENT NEW (1/2)
NO SCALE
SHAFT 2 - BASEMENT DETAIL
NO SCALE
SHAFT 3 - BASEMENT DETAIL
1/8" = 1'-0"
BASEMENT - SHAFT 3 REPLACEMENT NEW (2/2)
41360DATE REG. NO.
I HEREBY CERTIFY THAT THIS PLAN,
SPECIFICATION OR REPORT WAS PREPARED BY ME
OR UNDER MY DIRECT SUPERVISION AND THAT I
AM A DULY LICENSED PROFESSIONAL ENGINEER
UNDER THE LAWS OF THE STATE OF MINNESOTA.
JASON GOTTWALT, P.E.
T S
KEY NOTES:
GENERAL NOTES:
U
3" CW UP & DN
1" RHW UP & DN
2 1/2" HW UP & DN
3" CW UP & DN
U
3" CW UP & DN
1" RHW UP & DN
2 1/2" HW UP & DN
3" CW UP & DN
2 1/2" CW
U
23" CW UP & DN
1" RHW DN
3/4" RHW UP
2 1/2" HW UP & DN
3" CW UP & DN
U
3" CW UP & DN
1" RHW DN
3/4" RHW UP
2 1/2" HW UP & DN
3" CW UP & DN
2" CW
U
3" CW DN
2 1/2" CW UP
3/4" RHW DN
1/2" RHW UP
2 1/2" HW DN
3/4" HW UP
2 1/2" CW UP
3" CW DN
U
3" CW DN
2 1/2" CW UP
3/4" RHW DN
1/2" RHW UP
2 1/2" HW DN
3/4" HW UP
3" CW UP
2 1/2" CW UP
U
2 1/2" CW DN
1/2" RHW DN
3/4" HW DN
2 1/2" CW DN
U
2 1/2" CW DN
1/2" RHW DN
3/4" HW DN
2 1/2" CW DN
1 BEFORE OUTAGE: ROUTE NEW SHAFT 3 PIPING PARALLEL TO
EXISTING PIPING TO LEVEL ABOVE. EXTEND NEW TAKEOFFS TO
EXISTING BRANCH TAKEOFFS AND PREPARE FOR NEW CONNECTION.
CONTRACTOR TO VERIFY PIPE SIZING AND OUTAGE AREAS PRIOR TO
CONSTRUCTION.
DURING OUTAGE: DISCONNECT EXISTING BRANCH TAKEOFFS AND
REMOVE TAKEOFF PIPING. MAKE TAKEOFF FINAL CONNECTIONS.
ABANDON EXISTING COLD WATER RISER PIPING TO BE DEMOLISHED
AFTER ALL SHAFT 3 FINAL CONNECTIONS ARE MADE AND OUTAGE IS
COMPLETE.
AFTER OUTAGE: REFER TO ASSOCIATED LEVEL DEMOLITION VIEW
AND KEY NOTE 2.
AFTER OUTAGE: REMOVE ABANDONED COLD WATER RISER PIPING.
DEADLEG OR ABANDONED PIPING SHALL NOT REMAIN.
A.
B.
C.
D.
E.
F.
THE OUTLINE OF 'MEANS-AND-METHODS' NOTES BELOW FOR VERTICAL
COLD WATER RISER REPLACEMENTS INDICATED WITHIN THESE
DRAWINGS IS NOT INTENDED TO BE ALL-INCLUSIVE OF EFFORT
REQUIRED BY CONTRACTOR. NOR ARE THESE NOTES AND/OR
SUGGESTIONS MEANT TO LIMIT CONTRACTORS FROM DEVELOPING
THEIR OWN APPROACH THAT MAY BE CONSIDERED MORE COST
EFFECTIVE OR SAFE. THESE NOTES ARE MAINLY MEANT TO QUALIFY
EXISTING CONDITIONS AND DEFINE MINIMUM LEVEL OF PLANNING
REQUIRED BY VA FOR EACH OF THESE TIME SENSITIVE OUTAGES.
NO MAJOR WATER OUTAGE SHALL LAST MORE THAN 12 HOURS IN
DURATION. PLUMBING CONTRACTOR TO DETERMINE ADEQUATE
NUMBER OF PLUMBER CREWS REQUIRED TO PERFORM MULTIPLE
TASKS SIMULTANEOUSLY DURING OUTAGES. ALL OUTAGES SHALL BE
ASSUMED TO BE PERFORMED DURING WEEKEND OR NIGHT OVERTIME
HOURS WHEN BIDDING THIS PROJECT.
VERTICAL RISER REPLACEMENT (TYPE 1 - WITHIN MECHANICAL ROOM)
• FOR RISERS WITHIN MECHANICAL ROOMS, CONTRACTOR SHALL
CORE DRILL HOLES THROUGH FLOOR ADJACENT TO EXISTING
PLUMBING RISER FOR NEW INSTALLATION. EXISTING FLOOR
PENETRATIONS AND/OR SLEEVE SHALL BE PATCHED FLUSH TO
EXISTING FLOOR AS REQUIRE UPON DEMOLITION OF THOSE RISERS.
• EXISTINGT TAKE-OFF VALVES MAY REQUIRE RELOCATION FOR
CONNECTION INTO NEW RISER. VERIFY ADEQUATE ACCESS TO ALL
TAKE-OFF VALVES AND PROVIDE WITH NEW LAMINATE SIGNAGE.
ANY VALVES FOUND AT INACCESSIBLE LOCATIONS SHALL BE
RELOCATED BY CONTRACTOR.
• REFER TO CLIN 3001 FOR REPLACEMENT OF ALL ICRCUIT SETTER
VALVES WITHIN ENTIRE BUILDING. PLUMBING CONTRACTOR MAY
OPT TO HAVE DEDICATED CREWS ASSIGNED TO THIS TASK DURING
RISER OUTAGE TO LIMIT NUMBER OF SECONDARY OUTAGES
REQUIRED. HOWEVER, IF ENOUGH PLUMBERS ARE AVAILABLE TO
ACHIEVE THIS DURING LIMITED OUTAGE TIMEFRAME, THAN REFER
TO GENERAL NOTES ON DRAWING PP002 FOR 'LARGE OUTAGES' TO
PERFORM PRIOR TO THE MAJOR RISER OUTAGE.
VERTICAL RISER REPLACEMENT (TYPE 2 - WITHIN ENCLOSED SHAFT)
• IN GENERAL, MAJOR RATED SHAFTS SHOWN IN THESE DRAWINGS
HAVE EXISTING FULL SIZED ACCESS DOOR FROM BASE OF SHAFT
ON FIRST FLOOR LEVEL. HOWEVER, THAT IS TYPICALLY THE ONLY
ACCESS INTO THESE SHAFTS THAT ARE FULLY OPEN (NO
INTERMEDIATE FLOOR STRUCTURES) UP THROUGH PENTHOUSE
LEVEL WHERE RATED WALLS ARE BUILT-UP WITH LID (TYPICALLY
12'+) WITHIN ENCLOSED PENTHOUSE LEVEL.
• IN ORDER TO GAIN ACCESS TO TOP OF SHAFT, CONTRACTOR WILL
BE REQUIRED TO FURNSIH AND INSTALL FIRE RATED DOOR
ASSEMBLIES FROM PENTHOUSE LEVEL. THESE DOORS MAY BE
USED IN CONJUCTION OF RIGGING FOR BOSUN CHAIRS FROM TOP
OF SHAFT IF CONTRACTOR DEEMS THAT AS SAFE AFTER REVIEW
WITH THEIR INTERNAL SAFETY OFFICIAL.
• IN ADDITION TO ACCESS ON TOP LEVEL OF SHAFT, CONTRACTOR
WILL HAVE OPPORTUNITIES TO INSTALL 24"X24" OR 48"X24" FIRE
RATED ACCESS PANELS ON ANY OTHER LEVEL REQUIRED (BUT
ONLY FROM INTERSTITIAL SPACE, INSTALLATION OF ACCESS
PANELS FROM PATIENT CARE AREAS WILL NOT BE PERMITTED).
• CONTRACTOR WILL BE REQUIRED TO PROVIDE THEIR OWN
SCAFFOLDING REQUIRED AT EACH LEVEL TO INSTALL NEW COLD
WATER RISERS ADJACENT TO EXISTING PRIOR TO SIOWTCHOVER
OUTAGE. SCAFFOLDS SHOULD BE STRATEGICALLY PLACE TO
ALLOW ACCESS FOR RECONNECTION TO FLOOR TAKE-OFF PIPING
INSIDE OF EACH SHAFT.
• EXISTING CONDITION PDF SKETCHES ARE PROVIDED ON DRAWINGS
WHERE WORK INSIDE CONFINED AREAS OF RATED SHAFTS IS
REQUIRED. THESE SKETCHES ARE FOR CONTRACTOR REFERENCE
ONLY AND MAY NOT FULLY INDICATE ALL SERVICES WITHIN SHAFT
ENCLOSURES. CONTRACTOR WILL BE REQUIRED TO FIELD VERIFY
ACTUAL SITE CONDITIONS OF EACH SHAFT WHILE DEVELOPING
ACCESS AND SAFETY PLANNING.
NOTE THAT SOME AREAS HAVE EXISTING COPPER MAINS INTENDED TO
REPLACE GALVANIZED RISERS. HOWEVER THESE MAINS WERE
INSTALLED UP TO 15-25 YEARS AGO AND THEIR INTEGRITY IS
QUESTIONABLE. CONTRACTOR MAY UTILIZE THE EXISTING ROUTE, AND
CORRESPONDING SUPPORT HANGERS, BUT MUST FULLY REMOVE ALL
ABANDONED/UNUSED COPPER PIPING MAINS. ONCE OFF SITE THE
CONTRACTOR MAY TAKE OWNERSHIP OF PIPING FOR RECYLCING OR
REPURPOSING, BUT IT SHALL NOT BE UTILIZED WITHIN THIS PROJECT.
NO EXISTING PIPING WILL BE ALLOWED TO BE LEFT ABANDONED. SOME
AREAS HAVE RESTRICITVE ACCESS DUE TO SURROUNDING PIPES
AND/OR STRUCTURE AND MAY REQUIRE TEMPORARY REMOVAL OF
PIPING OR DUCTWORK TO GAIN ACCESS FOR DEMOLITION.
CONTRACTOR TO ASSUME SOME LEVEL OF DISCONNECT/RECONNECT
OF EXISTING SERVICES TO GAIN ACCCESS FOR COMPLETE DEMOLITION
OF EXISTING PIPING, OR INSTALLATION OF NEW PIPE IN CONGESTED
AREAS. REFER TO DRAWING NOTES FOR ADDITIONAL INFORMATION.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS SUBMISSION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
TRUE NORTH
PLAN NORTH
D
C R e v it P ro je c ts
\V A
B u ild in g
P h a s e
M e c h a n ic a l ja s o n g o tt w a lt
.r v t
/3 /2
:4
:2
A M
LEVELS 1-4 - PHASE 5 - ENLARGED
SHAFT 3 COLD WATER
REPLACEMENT PLANS
PREVENT LEGIONELLA,
PHASE III
MINNEAPOLIS
618-14-118
11/30/2022 JG TM / JG618-14-118
1356-PP105.3
NO SCALE
SHAFT 3 - FIRST LEVEL DETAIL
NO SCALE
SHAFT 3 - SECOND LEVEL DETAIL
NO SCALE
SHAFT 3 - THIRD LEVEL DETAIL
NO SCALE
SHAFT 3 - FOURTH LEVEL DETAIL
1/8" = 1'-0"
FIRST LEVEL - SHAFT 3 REPLACEMENT DEMO
1/8" = 1'-0"
FIRST LEVEL - SHAFT 3 REPLACEMENT NEW
1/8" = 1'-0"
SECOND LEVEL - SHAFT 3 REPLACEMENT DEMO
1/8" = 1'-0"
SECOND LEVEL - SHAFT 3 REPLACEMENT NEW
1/8" = 1'-0"
THIRD LEVEL - SHAFT 3 REPLACEMENT DEMO
1/8" = 1'-0"
THIRD LEVEL - SHAFT 3 REPLACEMENT NEW
1/8" = 1'-0"
FOUTH LEVEL - SHAFT 3 REPLACEMENT DEMO
1/8" = 1'-0"
FOURTH LEVEL - SHAFT 3 REPLACEMENT NEW
41360DATE REG. NO.
I HEREBY CERTIFY THAT THIS PLAN,
SPECIFICATION OR REPORT WAS PREPARED BY ME
OR UNDER MY DIRECT SUPERVISION AND THAT I
AM A DULY…