Attachment_C_-_Drawings_Bldg_A-G_Commons.pdf
PDF 4 MB Posted
- Attached to
- Fire Alarm Installation
- Solicitation number
- EVT0010640
- Issued by
- Marion County, Levant CDP, Kansas
About this file
This is a fire alarm system installation drawing set prepared by Tech Electronics for the Larned Correctional Facility located at 1318 K-264 Highway, Larned, Kansas 67550. The drawings detail a complete new fire alarm system installation across seven buildings (Buildings A through G) comprising an Administration Building, two Commons Buildings, a Rotunda Building with two floors, four Housing Units, and a Power Plant Building. The system utilizes Notifier N16E intelligent fire alarm control panels with addressable signaling line circuits (SLC), multiple notification appliance circuits (NAC), and networked components connected via fiber optic cable. The installation includes 21 manual pull stations in Buildings A-C, 12 in Building D, 5 in Building E, and 6 in Building G; 61-98 intelligent photoelectric smoke detectors across various buildings; 25-98 addressable relay modules and mini monitor modules; and horn/strobe notification devices rated from 15 to 185 candlepower depending on location and application. The system incorporates duct detectors for HVAC monitoring, waterflow switches, tamper supervisory switches, and kitchen hood monitoring in applicable areas. Three independent fire alarm control units (Panels P1, P2, and P3) serve different building zones with secondary backup power provided by dual 12-volt 26-amp-hour batteries for each panel. The drawings were submitted for construction on May 21, 2024, reviewed for submittal on May 28, 2024, and are designed to conform to 2021 IBC, NFPA 72 (2019 edition), and NFPA 70 (2017 edition) standards under the authority having jurisdiction approval requirements.
The specification and installation documentation require strict adherence to all applicable federal, state, and local codes and regulations, with all wiring to be clear of shorts, opens, and grounds, and all fire alarm system components properly installed and commissioned per manufacturer specifications. The contract note indicates this is a one-for-one replacement of all existing fire alarm equipment with existing field wiring to be reused throughout the facility. The installing contractor is required to provide accurate as-built documentation showing all wiring types and routing, exact device quantities and placement, each device address, all modifications, circuit breaker information, and power supply details per NFPA 72 standards. All 120VAC power circuits must be dedicated 20-ampere circuits with locked circuit breakers. The system design accommodates the facility's operational requirements with multiple notification zones, addressable device monitoring across three independent control panels, and comprehensive fire detection and alarm signaling capabilities suitable for a correctional facility environment.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CABLE AND WIRE LEGEND
LABEL RESISTANCE
MFT AWG DESCRIPTION
2U 7.77 18 18 AWG, 1 PAIR, SOLID, TWISTED, OVERALL JACKET
(CONVENTIONAL INITIATING DEVICE)
A 7.77 18
18 AWG, 1 PAIR, SOLID, TWISTED, OVERALL JACKET (SLC -
INITIATION)
B 3.07 14
14 AWG, 1 PAIR, SOLID, OVERALL JACKET (NAC -
SIGNAL/STROBE)
F 0 0 MULTI MODE / SINGLE MODE FIBER
J 7.77 18
18 AWG, 1 PAIR, SOLID, TWISTED, SHIELDED (DATA -
ANNUNCIATOR OTHER THAN SLC)
L 3.07 14
14 AWG, 1 PAIR, SOLID, OVERALL JACKET (ANNUCIATOR
POWER)
U 7.77 18
18 AWG, 1 PAIR, SOLID, TWISTED, OVERALL JACKET
(CONVENTIONAL INITIATING DEVICE)
BUILDING D,E,F DEVICE LEGEND
SYMBOL QUANTITY MANUFACTURER PART NO DESCRIPTION MOUNTING
12 RSG SP1KO KEYED MANUAL PULL STATION
25 NOTIFIER DNR W/FSP-951R INTELLIGENT NON-RELAY PHOTOELECTRIC DUCT
DETECTOR/ FSP-951R. FLASHSCAN AND CLIP MODE.
MOUNTS ON AIR DUCT.
SEE MFR'S
RECOMMENDATIONS
FOR MOUNTING DETAILS
AND AIR VELOCITY
REQUIREMENTS. ANY
DEVIATIONS MUST BE
APPROVED BY THE
"AUTHORITY HAVING
JURISDICTION".
1 SYSTEM SENSOR SRLED STROBE, WALL, RED
4” SQUARE BOX 1-1/2”
DEEP. OR SURFACE
MOUNT TO SBBRL OR
SBBWL.
5 NOTIFIER NBG-12LX DUAL-ACTION ADDRESSABLE PULL STATION. INCLUDES KEY
LOCKING FEATURE.
4" SQUARE BOX WITH A
TWO GANG FRAME. IF
SURFACE MOUNTING IS
REQUIRED, USE SB-10
BOX.
1 NOTIFIER N16E
INTELLIGENT FIRE ALARM PANEL WITH ONE SLC LOOP, 10"
TOUCHSCREEN DISPLAY, 4 NACS, AND POWER SUPPLY IN A
BLACK ENCLOSURE.
SURFACE MOUNT 20.31”H
X 24”W X 5.5”D 120VAC
DEDICATED 20 AMPERE
CIRCUIT AND EARTH
GROUND IS REQUIRED.
USE EMERGENCY
POWER IF AVAILABLE
LOCATE AS SHOWN ON
THE PLANS.
25 SYSTEM SENSOR R-10 E/AHU RELAY, CONVENTIONAL RELAY IN A BOX
25 NOTIFIER FRM-1 ADDRESSABLE RELAY MODULE W/ FLASHSCAN, 2 FORM-C
DRY CONTACTS
4" SQUARE BOX 2-1/8"
DEEP WITH EXTENSION
RING. OVERALL MINIMUM
DEPTH 3 5/8". NO FRAME
REQUIRED.
6 SYSTEM SENSOR P2RLED 2-WIRE, HORN STROBE, RED
4” SQUARE BOX 1-1/2”
DEEP. OR SURFACE
MOUNT TO SBBRL OR
SBBWL.
25 NOTIFIER RTS151KEY REMOTE TEST STATION W/ SWITCH, ALARM & POWER LEDS,
KEY RESET
ONE GANG BOX 2-1/2"
DEEP.
10 STI STI-9705 HORN/STROBE/SPEAKER DAMAGE STOPPER® - WHITE INSTALL OVER FIELD
DEVICES
98 NOTIFIER FSP-951-SELFT W/B300-6 WHITE, LOW-PROFILE INTELLIGENT SELF-TESTING
PHOTOELECTRIC SENSOR, FLASHSCAN ONLY
4" OCTAGON BOX 2-1/8"
DEEP.
2 GENERIC VALVE TAMPER
SUPERVISORY SWITCH
3 GENERIC WATERFLOW SWITCH
17 NOTIFIER FMM-101 ADDRESSABLE MINI MONITOR MODULE
MOUNT IN SAME BOX AS
DEVICE BEING
MONITORED. MODULE
MEASURES
1-1/2"X3"X1-1/2. ENSURE
AMPLE SPACE IS
AVAILABLE OR INSTALL
MODULE IN A SEPARATE
BOX WITH A BLANK
COVER.
F
S
F
FACU
RL
AOM
R
WG
S
AIM
m
K
BUILDING A,B,C DEVICE LEGEND
SYMBOL QUANTITY MANUFACTURER PART NO DESCRIPTION MOUNTING
21 RSG SP1KO KEYED MANUAL PULL STATION
14 NOTIFIER DNR W/FSP-951R INTELLIGENT NON-RELAY PHOTOELECTRIC DUCT
DETECTOR/ FSP-951R. FLASHSCAN AND CLIP MODE.
MOUNTS ON AIR DUCT.
SEE MFR'S
RECOMMENDATIONS
FOR MOUNTING DETAILS
AND AIR VELOCITY
REQUIREMENTS. ANY
DEVIATIONS MUST BE
APPROVED BY THE
"AUTHORITY HAVING
JURISDICTION".
1 GENERIC AIR PRESSURE SWITCH
HIGH/LOW AIR PRESSURE SWITCH HIGH/LOW
PROVIDED BY
SPRINKLER
CONTRACTOR
61 SYSTEM SENSOR SRLED STROBE, WALL, RED
4” SQUARE BOX 1-1/2”
DEEP. OR SURFACE
MOUNT TO SBBRL OR
SBBWL.
1 GENERIC HOOD SYSTEM MONITOR
5 NOTIFIER NBG-12LX DUAL-ACTION ADDRESSABLE PULL STATION. INCLUDES KEY
LOCKING FEATURE.
4" SQUARE BOX WITH A
TWO GANG FRAME. IF
SURFACE MOUNTING IS
REQUIRED, USE SB-10
BOX.
1 NOTIFIER N16E
INTELLIGENT FIRE ALARM PANEL WITH ONE SLC LOOP, 10"
TOUCHSCREEN DISPLAY, 4 NACS, AND POWER SUPPLY IN A
BLACK ENCLOSURE.
SURFACE MOUNT 20.31”H
X 24”W X 5.5”D 120VAC
DEDICATED 20 AMPERE
CIRCUIT AND EARTH
GROUND IS REQUIRED.
USE EMERGENCY
POWER IF AVAILABLE
LOCATE AS SHOWN ON
THE PLANS.
14 SYSTEM SENSOR R-10 E/AHU RELAY, CONVENTIONAL RELAY IN A BOX
14 NOTIFIER FRM-1 ADDRESSABLE RELAY MODULE W/ FLASHSCAN, 2 FORM-C
DRY CONTACTS
4" SQUARE BOX 2-1/8"
DEEP WITH EXTENSION
RING. OVERALL MINIMUM
DEPTH 3 5/8". NO FRAME
REQUIRED.
74 SYSTEM SENSOR P2RLED 2-WIRE, HORN STROBE, RED
4” SQUARE BOX 1-1/2”
DEEP. OR SURFACE
MOUNT TO SBBRL OR
SBBWL.
14 NOTIFIER RTS151KEY REMOTE TEST STATION W/ SWITCH, ALARM & POWER LEDS,
KEY RESET
ONE GANG BOX 2-1/2"
DEEP.
26 NOTIFIER FSP-951-SELFT W/B300-6 WHITE, LOW-PROFILE INTELLIGENT SELF-TESTING
PHOTOELECTRIC SENSOR, FLASHSCAN ONLY
4" OCTAGON BOX 2-1/8"
DEEP.
3 GENERIC VALVE TAMPER
SUPERVISORY SWITCH
1 NOTIFIER NCD ASSEMBLY NETWORK CONTROL DISPLAY
3 GENERIC WATERFLOW SWITCH
29 NOTIFIER FMM-101 ADDRESSABLE MINI MONITOR MODULE
MOUNT IN SAME BOX AS
DEVICE BEING
MONITORED. MODULE
MEASURES
1-1/2"X3"X1-1/2. ENSURE
AMPLE SPACE IS
AVAILABLE OR INSTALL
MODULE IN A SEPARATE
BOX WITH A BLANK
COVER.
F
S
PS
HILO
KH
HOOD
F
FACU
RL
AOM
R
S
FAA
AIM
m
K
BUILDING G DEVICE LEGEND
SYMBOL QUANTITY MANUFACTURER PART NO DESCRIPTION MOUNTING
3 NOTIFIER DNR W/FSP-951R INTELLIGENT NON-RELAY PHOTOELECTRIC DUCT
DETECTOR/ FSP-951R. FLASHSCAN AND CLIP MODE.
MOUNTS ON AIR DUCT.
SEE MFR'S
RECOMMENDATIONS
FOR MOUNTING DETAILS
AND AIR VELOCITY
REQUIREMENTS. ANY
DEVIATIONS MUST BE
APPROVED BY THE
"AUTHORITY HAVING
JURISDICTION".
5 SYSTEM SENSOR SRLED STROBE, WALL, RED
4” SQUARE BOX 1-1/2”
DEEP. OR SURFACE
MOUNT TO SBBRL OR
SBBWL.
6 NOTIFIER NBG-12LX DUAL-ACTION ADDRESSABLE PULL STATION. INCLUDES KEY
LOCKING FEATURE.
4" SQUARE BOX WITH A
TWO GANG FRAME. IF
SURFACE MOUNTING IS
REQUIRED, USE SB-10
BOX.
1 NOTIFIER N16E
INTELLIGENT FIRE ALARM PANEL WITH ONE SLC LOOP, 10"
TOUCHSCREEN DISPLAY, 4 NACS, AND POWER SUPPLY IN A
BLACK ENCLOSURE.
SURFACE MOUNT 20.31”H
X 24”W X 5.5”D 120VAC
DEDICATED 20 AMPERE
CIRCUIT AND EARTH
GROUND IS REQUIRED.
USE EMERGENCY
POWER IF AVAILABLE
LOCATE AS SHOWN ON
THE PLANS.
3 SYSTEM SENSOR R-10 E/AHU RELAY, CONVENTIONAL RELAY IN A BOX
3 NOTIFIER FRM-1 ADDRESSABLE RELAY MODULE W/ FLASHSCAN, 2 FORM-C
DRY CONTACTS
4" SQUARE BOX 2-1/8"
DEEP WITH EXTENSION
RING. OVERALL MINIMUM
DEPTH 3 5/8". NO FRAME
REQUIRED.
9 SYSTEM SENSOR P2RLED 2-WIRE, HORN STROBE, RED
4” SQUARE BOX 1-1/2”
DEEP. OR SURFACE
MOUNT TO SBBRL OR
SBBWL.
3 NOTIFIER RTS151KEY REMOTE TEST STATION W/ SWITCH, ALARM & POWER LEDS,
KEY RESET
ONE GANG BOX 2-1/2"
DEEP.
2 NOTIFIER FSP-951-SELFT W/B300-6 WHITE, LOW-PROFILE INTELLIGENT SELF-TESTING
PHOTOELECTRIC SENSOR, FLASHSCAN ONLY
4" OCTAGON BOX 2-1/8"
DEEP.
2 GENERIC VALVE TAMPER
SUPERVISORY SWITCH
1 GENERIC WATERFLOW SWITCH
3 NOTIFIER FMM-101 ADDRESSABLE MINI MONITOR MODULE
MOUNT IN SAME BOX AS
DEVICE BEING
MONITORED. MODULE
MEASURES
1-1/2"X3"X1-1/2. ENSURE
AMPLE SPACE IS
AVAILABLE OR INSTALL
MODULE IN A SEPARATE
BOX WITH A BLANK
COVER.
S
F
FACU
RL
AOM
R
S
AIM
m
SHEET LEGEND
SHEET
NUMBER
SHEET REFERENCE
NUMBER DESCRIPTION
1 FA001 COVER SHEET, LEGENDS
2 FA101 ADMINISTRATION BUILDING "A" FIRE ALARM PLAN
3 FA102 COMMONS BUILDING "B' FIRE ALARM PLAN
4 FA103 COMMONS BUILDING "C" FIRE ALARM PLAN
5 FA104 ROTUNDA BUILDING "D" 1ST FLOOR FIRE ALARM PLAN
6 FA105 ROTUNDA BUILDING "D" 2ND FLOOR FIRE ALARM PLAN
7 FA106 HOUSING UNIT BUILDING "E" FIRE ALARM PLAN
8 FA107 HOUSING UNIT BUILDING "F" FIRE ALARM PLAN
9 FA108 HOUSING UNIT BUILDING "F2" FIRE ALARM PLAN
10 FA109 HOUSING UNIT BUILDING "F3" FIRE ALARM PLAN
11 FA110 HOUSING UNIT BUILDING "F4" FIRE ALARM PLAN
12 FA111 POWER PLANT BUILDING "G" FIRE ALARM PLAN
13 FA201 RISER DIAGRAMS & SEQUENCE OF OPERATIONS
14 FA301 BATTERY CALCULATIONS
15 FA501 CONNECTION DETAILS
CIRCUIT TYPE: SLC
NAC
SPK
AUX
P1:SLC1:D01
PANEL
DEVICE
ADDRESS ON SLC
LOOP
D - DETECTOR
M - MODULE
N O
D
AT
E:
RE
VI
SI
O
N D
ES
CR
IP
TI
O N
PR
O
JE
CT
N
AM
E
CU
ST
O
M
ER
L
O
CA
TI
O
N
SY
ST
EM
D
ES
CR
IP
TI
O N
DRAWING #:
DESIGNER:
PROJECT
JOB#:
DATE:
ISSUED
FOR:
St. Louis, Missouri | Columbia, Missouri | Springfield, Missouri Chicago, Illinois| Bloomington, Illinois | Indianapolis, Indiana
Denver, Colorado | Topeka, Kansas| Kansas City www.techelectronics.com
1.800.TECH.789
PROJECT MANAGER:
DRAFTER:
CONSTRUCTION
05/21/2024
PJ2404170004
MM SAS
BOJAN BALTIC
(816) 977-1228
NE
W
F
IR
E
AL
AR
M
S
YS
TE
M
LA
RN
ED
C
OR
RE
CT
IO
NA
L
FA
CI
LI
TY
K
HI
GH
W
AY
LA
RN
ED
, K S
SIGNATURE:
NICET # LEVEL:
DATE:
EXPIRATION:
THIS DRAWING HAS BEEN REVIEWED
FOR SUBMITTAL PURPOSES ONLY
05/28/2024
IV137416
Steven A. Sprague
12/01/2025
AHJ - AUTHORITY HAVING JURISDICTION
DD - DUCT DETECTOR
DH - DOOR HOLDER
DUA- DWELLING UNIT ALARM
E- PSD/HD W/ ELEV INTERFACE
ELEV1- PRIMARY ELEVATOR RECALL
ELEV2- ALTERNATE ELEVATOR RECALL
EST- ELEVATOR SHUNT TRIP
EXG - EXISTING
FH- ELEVATOR FIREHAT
FL - FIELD LOCATE
FM- FLUSH MOUNT
FGS- FIRE PLACE GAS SHUTOFF
FSD- FIRE/SMOKE DAMPER
KB- KNOX BOX
KH- KITCHEN HOOD
PIV- SPRINKLER POST INITIATOR VALVE
NT- NAC TRIGGER
RD- RETURN DUCT
RL- RELOCATE
RTU- ROOF TOP UNIT
SD- SUPPLY DUCT
TS - TAMPER SWITCH
VL - VERIFY LOCATION
WF - WATERFLOW
WP- WEATHER PROOF
ADDRESS LABEL CLARIFICATION
ABBREVIATIONS
DUCT DETECTOR MOUNTING
SAMPLING TUBE ENDCAP
DNR HOUSING
ARROW MUST FACE
INTO AIR FLOW
AIR FLOW
DIRECTION
Per NFPA sampling tubes over 3 feet long should be supported at the end opposite of the duct detector. In ducts wider than 8 feet, work must be performed inside the duct to couple the other section of the sampling tube to the section already installed using the ½ inch conduit fitting supplied. Make sure that the holes on both sections of the air inlet sampling tube are lined up and facing into the airflow.
SAMPLING TUBE ENDCAP
FA001
TECH ELECTRONICS
11/23/20
Note:
1. Contact Tech Electronics if you have questions concerning these instructions, discrepencies, or if your specific conditions require a solution not addressed by this document.
2. Refer to the proper device installation instructions for backbox mounting height
RECOMMENDED MOUNTING HEIGHTS PER CODES AND STANDARDS
Pull Station
Fire Fighters
Telephone
4" Min -
4" 3' Min
A/C Supply or Return DiffuserSmoke or Heat
Detector
Smoke or Heat Detector
Fi ni sh ed
W al l
Ceiling
Finished Floor (AFF - Above Finished Floor)
3"
5' Max
3"
46" AFF
Magnetic Door
Holder Height of Activating Handle
Door (Shown Open)
Door (Shown Closed)
Heights_and_Mounting.dwg:B
80" Min
AFF
96" Max
AFF
Top of Strobe Lens
Bottom of Strobe Lens
All strobes in a field of view shall be synchronized
FIRE
Visual Only Or Audible/Visual Signaling
Device
FACP
ANN
66" AFF 66" AFF
Heat Detectors Never Here
Note: NFPA 72 states 48" AFF maximum and 42" minimum for pull stations.
We recommend 46" AFF.
If this is not feasible stay within NFPA 72 code guidelines.
6" Min
Battery Box 6"
(For use on flat, smooth ceilings only)
12" Max
Audible Only Signaling Device
90" Min
AFF
6" Min
Smoke or Heat Detector
INSTALLING CONTRACTOR WILL NEED TO PROVIDE ACCURATE AS-BUILT INFORMATION TO TECH
ELECTRONICS. THIS SHALL INCLUDE ALL WIRING TYPE AND ROUTING INFORMATION FOR ALL
ADDRESSABLE LOOP (SLC), HORN, SPEAKER AND STROBE (NAC) AND ZONE (IDC) CIRCUITS. THE
AS-BUILT DRAWINGS SHALL SHOW THE EXACT QUANTITY AND PLACEMENT OF ALL DEVICES AND
EACH EXACT DEVICE ADDRESS INSTALLED, IF APPLICABLE. ALL DELETED, ADDED AND CHANGES
MUST BE SHOWN.
ALL 120VAC POWER SHALL BE NOTED WITH THE CIRCUIT BREAKER NUMBER, SIZE OF BREAKER
AND THE LOCATION OF THE CIRCUIT BREAKER PANEL. THE CIRCUIT BREAKER MUST BE LOCKED.
ALL ABOVE INFORMATION IS REQUIRED BY AND SHALL BE PROVIDED PER NFPA 72. SEE
CURRENTLY ENFORCED ORDINANCE IF NECESSARY.
GENERAL INSTALLATION NOTES:
1. INSTALLATION MUST COMPLY WITH ALL APPLICABLE FEDERAL, STATE, OR LOCAL
LAWS, REGULATIONS, CODES, AND SPECIFICATIONS. THIS SYSTEM SHALL BE IN
STRICT CONFORMANCE WITH THESE DRAWINGS; 2021 IBC ; NFPA 72 2019
EDITION; NFPA 70, 2017 EDITION; AND AHJ.
2. WHERE CONDUCTORS ARE RUN IN CONDUIT, USE ONLY APPROVED CABLE
WITHIN RACEWAYS, PIPES OR CONDUITS. ALL SHIELDED WIRE MUST BE
CONTINUOUS THROUGHOUT CIRCUIT, ALL SHIELDS SHALL BE ISOLATED FROM
GROUND, ALL SHIELDS SHALL TERMINATE AT THE FIRE ALARM CONTROL PANEL
(FACP) ONLY.
3. PER NFPA 72 2019, 17.7.1.11 - WHERE DETECTORS ARE INSTALLED FOR SIGNAL
INITIATION DURING CONSTRUCTION, THEY SHALL BE CLEANED AND VERIFIED TO
BE OPERATING IN ACCORDANCE WITH THE LISTED SENSITIVITY, OR THEY SHALL
BE REPLACED PRIOR TO THE FINAL COMMISSIONING OF THE SYSTEM. WHERE
DETECTORS ARE INSTALLED BUT NOT OPERATIONAL DURING CONSTRUCTION,
THEY SHALL BE PROTECTED FROM CONSTRUCTION DEBRIS, DUST, DIRT, AND
DAMAGE IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS
AND VERIFIED TO BE OPERATING IN ACCORDANCE WITH THE LISTED SENSITIVITY,
OR THEY SHALL BE REPLACED PRIOR TO THE FINAL COMMISSIONING OF THE
SYSTEM. WHERE DETECTION IS NOT REQUIRED DURING CONSTRUCTION,
DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER ALL OTHER CONSTRUCTION
TRADES HAVE COMPLETED CLEANUP.
4. ALL FIRE ALARM SYSTEM WIRING SHALL BE CLEAR FROM SHORTS, OPENS AND
GROUNDS.
5. NOTIFICATION CIRCUIT WIRE RUNS ARE CRITICAL. ANY INCREASE IN LENGTH OF
WIRE MAY AFFECT CIRCUIT CONFIGURATIONS.
Fire Alarm System Drawings
LARNED
CORRECTIONAL
1318 K264 HWY.
LARNED, KS 67550
NOTE - THIS IS A ONE FOR ONE REPLACEMENT OF
ALL FIRE ALARM EQUIPMENT. EXISTING FIELD
WIRING TO BE REUSED THROUGHOUT.
FACU
P1
F P1-L1-M001
FP1-L1-M002
F P1-L1-M003
F P1-L1-M004
F P1-L1-M005
S P1-L1-D010
S P1-L1-D009
S P1-L1-D008
S P1-L1-D002
S P1-L1-D001
S P1-L1-D003
S P1-L1-D004 S
P1-L1-D006 S
P1-L1-D007
S P1-L1-D005
FAA
P1-N1-25 15cd
P1-N1-29 30cd
P1-N1-28 15cd
P1-N1-30 15cd
P1-N1-23 15cd
P1-N1-20 75cd
P1-N1-17 75cd
P1-N1-31 75cd
P1-N1-02 15cd
P1-N1-12 15cd
P1-N1-14 15cd
P1-N1-09 30cd
P1-N1-08 110cd
P1-N1-07 75cd
P1-N1-04 15cd
P1-N1-26 30cd
P1-N1-32 15cd
P1-N1-27 15cd
P1-N1-24 15cd
P1-N1-22 30cd
P1-N1-21 75cd
P1-N1-19 15cd
P1-N1-18 15cd
P1-N1-16 30cd
P1-N1-15 30cd
P1-N1-13 15cd
P1-N1-03 15cd
P1-N1-11 15cd
P1-N1-06 15cd
P1-N1-05 15cd
P1-N1-01 15cd
S
P1-L1-D060
S P1-L1-D061
AOM
P1-L1-M060 R
AHU S.D.
AOM
P1-L1-M061 R
AHU S.D.
RL
RL
P1-N1-10 30cd
ADMINISTRATION BUILDING "A" FLOOR PLAN - FIRE ALARM
0 4' 8' 16'
N O
D
AT
E:
RE
VI
SI
O
N D
ES
CR
IP
TI
O N
PR
O
JE
CT
N
AM
E
CU
ST
O
M
ER
L
O
CA
TI
O
N
SY
ST
EM
D
ES
CR
IP
TI
O N
DRAWING #:
DESIGNER:
PROJECT
JOB#:
DATE:
ISSUED
FOR:
St. Louis, Missouri | Columbia, Missouri | Springfield, Missouri Chicago, Illinois| Bloomington, Illinois | Indianapolis, Indiana
Denver, Colorado | Topeka, Kansas| Kansas City www.techelectronics.com
1.800.TECH.789
PROJECT MANAGER:
DRAFTER:
CONSTRUCTION
05/21/2024
PJ2404170004
MM SAS
BOJAN BALTIC
(816) 977-1228
NE
W
F
IR
E
AL
AR
M
S
YS
TE
M
LA
RN
ED
C
OR
RE
CT
IO
NA
L
FA
CI
LI
TY
K
HI
GH
W
AY
LA
RN
ED
, K S
SIGNATURE:
NICET # LEVEL:
DATE:
EXPIRATION:
THIS DRAWING HAS BEEN REVIEWED
FOR SUBMITTAL PURPOSES ONLY
05/28/2024
IV137416
Steven A. Sprague
12/01/2025
FA101
AutoCAD SHX Text 1/8" = 1'-0"
S
P1-L1-D066
AOM
P1-L1-M066 R
AHU S.D.
S P1-L1-D067
AOM
P1-L1-M067 R
AHU S.D.
S
P1-L1-D063
AOM
P1-L1-M063 R
AHU S.D.
S P1-L1-D062
AOM
P1-L1-M062 R
AHU S.D.
S
P1-L1-D064
AOM
P1-L1-M064 R
AHU S.D.
S P1-L1-D065
AOM
P1-L1-M065 R
AHU S.D.
F EOL 47k
F
F EOL 47k
F EOL 47k
F EOL 47k
F EOL 47k
F EOL 47k
F EOL 47k
AIM
P1-L1-M009 m
AIM
P1-L1-M008 m
AIM
P1-L1-M007 m
AIM
P1-L1-M006 m
AIM
P1-L1-M016 m
AIM
P1-L1-M015 m
AIM P1-L1-M013
m
AIM
P1-L1-M012 m
F EOL 47k
S P1-L1-D022
S P1-L1-D023
S P1-L1-D011
S P1-L1-D013
S P1-L1-D012
S P1-L1-D018
S P1-L1-D019
S
P1-L1-D016
S P1-L1-D017
S P1-L1-D015
S P1-L1-D020
F EOL 47k
AIM
P1-L1-M010 m
F EOL 47k
AIM
P1-L1-M011 m
RL
RL
RL
RL
RL
RL
P1-N3-15 15cd
P1-N3-13 15cd
P1-N3-07 15cd
P1-N3-04 15cd
P1-N3-03 15cd
P1-N3-02 30cd
P1-N3-01 15cd
P1-N2-27 15cd
P1-N2-22 15cd
P1-N2-18 15cd
P1-N2-17 15cd
P1-N2-19 15cd
P1-N2-21 15cd
P1-N2-13 15cd
P1-N2-16 15cd
P1-N2-15 15cd
P1-N2-14 15cd
P1-N2-10 15cd
P1-N1-38 15cd
P1-N1-40 15cd
P1-N2-07 15cd
P1-N2-06 30cd
P1-N2-29 15cd
P1-N2-32 15cd
P1-N2-34 75cd
P1-N2-04 15cd
P1-N1-36 75cd
P1-N1-35 75cd
P1-N2-02 15cd
P1-N2-01 75cd
P1-N2-05 15cd
P1-N2-28 15cd
P1-N2-25 15cd
P1-N2-23 15cd
P1-N2-11 15cd
P1-N2-20 15cd
P1-N2-12 15cd
P1-N2-24 15cd
P1-N2-26 15cd
P1-N2-31 15cd
P1-N2-30 75cd
P1-N2-38 15cd
P1-N2-39 EOL 2.2k 15cd
P1-N3-05 15cd
P1-N3-06 75cd
P1-N3-12 30cd
P1-N2-35 15cd
P1-N2-36 15cd
P1-N2-37 15cd
P1-N2-33 15cd
P1-N2-03 15cd
P1-N1-34 15cd
P1-N1-33 15cd
P1-N1-37 15cd
P1-N1-39 15cd
P1-N1-41 EOL 2.2k 15cd
P1-N2-08 15cd
P1-N2-09 15cd
P1-N3-11 15cd
P1-N3-08 15cd
P1-N3-09 15cd
P1-N3-10 15cd
S P1-L1-D021
SP1-L1-D014
P1-N3-14 15cd
AIM
P1-L1-M014 m
K
K
K
K
K
KK
K
K
K
COMMONS BUILDING "B" FLOOR PLAN - FIRE ALARM
0 4' 8' 16'
N O
D
AT
E:
RE
VI
SI
O
N D
ES
CR
IP
TI
O N
PR
O
JE
CT
N
AM
E
CU
ST
O
M
ER
L
O
CA
TI
O
N
SY
ST
EM
D
ES
CR
IP
TI
O N
DRAWING #:
DESIGNER:
PROJECT
JOB#:
DATE:
ISSUED
FOR:
St. Louis, Missouri | Columbia, Missouri | Springfield, Missouri Chicago, Illinois| Bloomington, Illinois | Indianapolis, Indiana
Denver, Colorado | Topeka, Kansas| Kansas City www.techelectronics.com
1.800.TECH.789
PROJECT MANAGER:
DRAFTER:
CONSTRUCTION
05/21/2024
PJ2404170004
MM SAS
BOJAN BALTIC
(816) 977-1228
NE
W
F
IR
E
AL
AR
M
S
YS
TE
M
LA
RN
ED
C
OR
RE
CT
IO
NA
L
FA
CI
LI
TY
K
HI
GH
W
AY
LA
RN
ED
, K S
SIGNATURE:
NICET # LEVEL:
DATE:
EXPIRATION:
THIS DRAWING HAS BEEN REVIEWED
FOR SUBMITTAL PURPOSES ONLY
05/28/2024
IV137416
Steven A. Sprague
12/01/2025
FA102
FEOL 47k
FEOL 47k
F EOL 47k
F EOL 47k
FEOL 47k
F EOL 47k
AIM
P1-L1-M020 m
AIM
P1-L1-M021 m
AIM
P1-L1-M019 m
AIM P1-L1-M018
m
AIM P1-L1-M017
m
AIM
P1-L1-M023 m
AIM
P1-L1-M022 m
S P1-L1-D026
S P1-L1-D024
S P1-L1-D025
S
P1-L1-D070 AOM
P1-L1-M071 R
AHU S.D.
S
P1-L1-D069
AOM
P1-L1-M070 R
AHU S.D.
S
P1-L1-D068
AOM
P1-L1-M069 R
AHU S.D.S
P1-L1-D071
AOM
P1-L1-M068 R
AHU S.D.
AIM
P1-L1-M034 m
AIM
P1-L1-M024 m
AIM
P1-L1-M025 m
AIM
P1-L1-M026 m
AIM
P1-L1-M027 m
AIM
P1-L1-M028 m
AIM
P1-L1-M029 m
AIM
P1-L1-M030 m
KH EOL 47k
HOOD
EOL 47k
EOL 47k
EOL 47k
EOL 47k
EOL 47k
EOL 47k
PS EOL 47k
HILO
RL
RL RL
RL
P1-N3-26 15cd
P1-N3-19 15cd
P1-N3-17 75cd
P1-N3-18 75cd
P1-N3-16 30cd
P1-N3-20 15cd
P1-N3-25 75cd
P1-N4-08 15cd
P1-N4-07 30cd
P1-N4-15 30cd
P1-N4-16 15cd
P1-N4-04 15cd
P1-N4-05 110cd
P1-N4-02 15cd
P1-N4-06 75cd
P1-N4-01 15cd
P1-N4-18 30cd
P1-N4-19 15cd
P1-N4-23 15cd
P1-N4-24 EOL 2.2k 110cd
P1-N4-13 15cd
P1-N3-24 15cd
P1-N3-31 EOL 2.2k 15cd
P1-N3-30 15cd P1-N3-29
15cd
P1-N3-28 15cd P1-N3-27
15cd
P1-N4-10 15cd
P1-N4-09 15cd
P1-N3-21 15cd
P1-N3-22 15cd
P1-N3-23 15cd
P1-N4-03 15cd
P1-N4-17 15cd
P1-N4-11 15cd
P1-N4-12 15cd
P1-N4-20 15cd
P1-N4-21 15cd
P1-N4-22 15cd
P1-N4-14 15cd
S
P1-L1-D072
AOM
P1-L1-M072 R
AHU S.D.
RL
S P1-L1-D073
AOM
P1-L1-M073 R
AHU S.D.RL
F EOL 47k
F EOL 47k
F EOL 47k
AIM
P1-L1-M032 m
AIM
P1-L1-M031 m
AIM
P1-L1-M033 m
K
K
K
K
K
K
K
K
K
COMMONS BUILDING "C" FLOOR PLAN - FIRE ALARM
0 4' 8' 16'
N O
D
AT
E:
RE
VI
SI
O
N D
ES
CR
IP
TI
O N
PR
O
JE
CT
N
AM
E
CU
ST
O
M
ER
L
O
CA
TI
O
N
SY
ST
EM
D
ES
CR
IP
TI
O N
DRAWING #:
DESIGNER:
PROJECT
JOB#:
DATE:
ISSUED
FOR:
St. Louis, Missouri | Columbia, Missouri | Springfield, Missouri Chicago, Illinois| Bloomington, Illinois | Indianapolis, Indiana
Denver, Colorado | Topeka, Kansas| Kansas City www.techelectronics.com
1.800.TECH.789
PROJECT MANAGER:
DRAFTER:
CONSTRUCTION
05/21/2024
PJ2404170004
MM SAS
BOJAN BALTIC
(816) 977-1228
NE
W
F
IR
E
AL
AR
M
S
YS
TE
M
LA
RN
ED
C
OR
RE
CT
IO
NA
L
FA
CI
LI
TY
K
HI
GH
W
AY
LA
RN
ED
, K S
SIGNATURE:
NICET # LEVEL:
DATE:
EXPIRATION:
THIS DRAWING HAS BEEN REVIEWED
FOR SUBMITTAL PURPOSES ONLY
05/28/2024
IV137416
Steven A. Sprague
12/01/2025
FA103
FACU
P2
F P2-L1-M002
F P2-L1-M001
F P2-L1-M011
F EOL 47k
F EOL 47k
AIM
P2-L1-M012 m
AIM
P2-L1-M013 m
S P2-L1-D001
S P2-L1-D004
S P2-L1-D002
S P2-L1-D003
S P2-L1-D005
S P2-L1-D006
S P2-L1-D014
S P2-L1-D013
S P2-L1-D012
S P2-L1-D011
S P2-L1-D010
S P2-L1-D009
S P2-L1-D008
S P2-L1-D007
S P2-L1-D019
S P2-L1-D020
S
P2-L1-D022
S P2-L1-D024
S P2-L1-D025
S P2-L1-D026
S P2-L1-D030
S P2-L1-D027
S P2-L1-D029
S P2-L1-D028
S P2-L1-D035
S P2-L1-D036
S P2-L1-D037
S P2-L1-D039
S P2-L1-D038
S P2-L1-D047
S P2-L1-D040
S P2-L1-D041
S P2-L1-D043
S P2-L1-D044
S
P2-L1-D046
S P2-L1-D045
S P2-L1-D052 S
P2-L1-D053
S P2-L1-D042
S P2-L1-D077
S P2-L1-D078
S P2-L1-D081
S P2-L1-D080
S P2-L1-D079
S P2-L1-D059
S P2-L1-D060
S P2-L1-D058
S P2-L1-D057
S P2-L1-D056
S P2-L1-D064
S P2-L1-D055
S P2-L1-D054
S P2-L1-D069
S P2-L1-D070S
P2-L1-D062
S P2-L1-D063
S P2-L1-D061
S P2-L1-D071
S P2-L1-D073
SP2-L1-D074
S P2-L1-D072
S P2-L1-D087
S P2-L1-D086
S P2-L1-D092
S P2-L1-D093
S P2-L1-D085
S P2-L1-D084
S P2-L1-D075
S P2-L1-D083
S P2-L1-D082
S P2-L1-D076
S P2-L1-D023
P2-N1-01 75cd
P2-N1-02 EOL 2.2k 15cd
WG
WG
WG
WG
WG
WG
WG
WG
WG
WG
S P2-L1-D021
KK
ROTUNDA BUILDING "D" 1ST FLOOR PLAN - FIRE ALARM
0 4' 8' 16'
N O
D
AT
E:
RE
VI
SI
O
N D
ES
CR
IP
TI
O N
PR
O
JE
CT
N
AM
E
CU
ST
O
M
ER
L
O
CA
TI
O
N
SY
ST
EM
D
ES
CR
IP
TI
O N
DRAWING #:
DESIGNER:
PROJECT
JOB#:
DATE:
ISSUED
FOR:
St. Louis, Missouri | Columbia, Missouri | Springfield, Missouri Chicago, Illinois| Bloomington, Illinois | Indianapolis, Indiana
Denver, Colorado | Topeka, Kansas| Kansas City www.techelectronics.com
1.800.TECH.789
PROJECT MANAGER:
DRAFTER:
CONSTRUCTION
05/21/2024
PJ2404170004
MM SAS
BOJAN BALTIC
(816) 977-1228
NE
W
F
IR
E
AL
AR
M
S
YS
TE
M
LA
RN
ED
C
OR
RE
CT
IO
NA
L
FA
CI
LI
TY
K
HI
GH
W
AY
LA
RN
ED
, K S
SIGNATURE:
NICET # LEVEL:
DATE:
EXPIRATION:
THIS DRAWING HAS BEEN REVIEWED
FOR SUBMITTAL PURPOSES ONLY
05/28/2024
IV137416
Steven A. Sprague
12/01/2025
FA104
F P2-L1-M016
F P2-L1-M022
AIM
P2-L1-M021 m
AIM
P2-L1-M020 m
AIM
P2-L1-M019 m
AIM
P2-L1-M018 m
AIM
P2-L1-M017 m
EOL 47k
EOL 47k
EOL 47k
EOL 47k
EOL 47k
S P2-L1-D094
S P2-L1-D095
S P2-L1-D096
S P2-L1-D097
S P2-L1-D098
S P2-L1-D101
S
P2-L1-D102
S
P2-L1-D103
S P2-L1-D104
S P2-L1-D105
S P2-L1-D106
SP2-L1-D110
S P2-L1-D109
S P2-L1-D108
S P2-L1-D107
S P2-L1-D112
S P2-L1-D113
S P2-L1-D114
S P2-L1-D115
S
P2-L1-D111
S
P2-L1-D120
S P2-L1-D119
S P2-L1-D118
S P2-L1-D117
S P2-L1-D116
S
P2-L1-D121
S
P2-L1-D122
S
P2-L1-D123
S
P2-L1-D124
S P2-L1-D125
AOM
P2-L1-M101 R
AHU S.D.
AOM
P2-L1-M102 R
AHU S.D.
AOM
P2-L1-M103 R
AHU S.D.
AOM
P2-L1-M104 R
AHU S.D.
AOM
P2-L1-M105 R
AHU S.D.
AOM
P2-L1-M106 R
AHU S.D.
AOM
P2-L1-M107 R
AHU S.D.
AOM
P2-L1-M108 R
AHU S.D.
AOM
P2-L1-M109 R
AHU S.D.
AOM
P2-L1-M110 R
AHU S.D.
AOM
P2-L1-M111 R
AHU S.D.
AOM
P2-L1-M115 R
AHU S.D.
AOM
P2-L1-M114 R
AHU S.D.
AOM
P2-L1-M113 R
AHU S.D.
AOM
P2-L1-M112 R
AHU S.D.
AOM
P2-L1-M117 R
AHU S.D.
AOM
P2-L1-M118 R
AHU S.D.
AOM P2-L1-M119
R
AHU S.D.
AOM
P2-L1-M120 R
AHU S.D.
AOM
P2-L1-M116 R
AHU S.D.
AOM
P2-L1-M121 R
AHU S.D.
AOM
P2-L1-M122 R
AHU S.D.
AOM
P2-L1-M123 R
AHU S.D.
AOM
P2-L1-M124 R
AHU S.D.
AOM
P2-L1-M125 R
AHU S.D.
RL
RL RL
RL
RL
RL
RL
RL
RL
RL
RL
RL
RL
RL
RL
RL
RL
RL
RL
RL
RL
RL RL
RL
P2-N2-05 EOL 2.2k 185cd
P2-N2-04 185cd
P2-N2-03 185cd
P2-N2-02 185cd
P2-N2-01 185cd
ROTUNDA BUILDING "D" 2ND FLOOR PLAN - FIRE ALARM
0 4' 8' 16'
N O
D
AT
E:
RE
VI
SI
O
N D
ES
CR
IP
TI
O N
PR
O
JE
CT
N
AM
E
CU
ST
O
M
ER
L
O
CA
TI
O
N
SY
ST
EM
D
ES
CR
IP
TI
O N
DRAWING #:
DESIGNER:
PROJECT
JOB#:
DATE:
ISSUED
FOR:
St. Louis, Missouri | Columbia, Missouri | Springfield, Missouri Chicago, Illinois| Bloomington, Illinois | Indianapolis, Indiana
Denver, Colorado | Topeka, Kansas| Kansas City www.techelectronics.com
1.800.TECH.789
PROJECT MANAGER:
DRAFTER:
CONSTRUCTION
05/21/2024
PJ2404170004
MM SAS
BOJAN BALTIC
(816) 977-1228
NE
W
F
IR
E
AL
AR
M
S
YS
TE
M
LA
RN
ED
C
OR
RE
CT
IO
NA
L
FA
CI
LI
TY
K
HI
GH
W
AY
LA
RN
ED
, K S
SIGNATURE:
NICET # LEVEL:
DATE:
EXPIRATION:
THIS DRAWING HAS BEEN REVIEWED
FOR SUBMITTAL PURPOSES ONLY
05/28/2024
IV137416
Steven A. Sprague
12/01/2025
FA105
F EOL 47k
EOL 47k
AIM
P2-L1-M004 m
AIM
P2-L1-M003 m
S P2-L1-D015
S P2-L1-D017
S P2-L1-D018
S P2-L1-D016
K
K
HOUSING UNIT "E" FLOOR PLAN - FIRE ALARM
0 4' 8' 16'
N O
D
AT
E:
RE
VI
SI
O
N D
ES
CR
IP
TI
O N
PR
O
JE
CT
N
AM
E
CU
ST
O
M
ER
L
O
CA
TI
O
N
SY
ST
EM
D
ES
CR
IP
TI
O N
DRAWING #:
DESIGNER:
PROJECT
JOB#:
DATE:
ISSUED
FOR:
St. Louis, Missouri | Columbia, Missouri | Springfield, Missouri Chicago, Illinois| Bloomington, Illinois | Indianapolis, Indiana
Denver, Colorado | Topeka, Kansas| Kansas City www.techelectronics.com
1.800.TECH.789
PROJECT MANAGER:
DRAFTER:
CONSTRUCTION
05/21/2024
PJ2404170004
MM SAS
BOJAN BALTIC
(816) 977-1228
NE
W
F
IR
E
AL
AR
M
S
YS
TE
M
LA
RN
ED
C
OR
RE
CT
IO
NA
L
FA
CI
LI
TY
K
HI
GH
W
AY
LA
RN
ED
, K S
SIGNATURE:
NICET # LEVEL:
DATE:
EXPIRATION:
THIS DRAWING HAS BEEN REVIEWED
FOR SUBMITTAL PURPOSES ONLY
05/28/2024
IV137416
Steven A. Sprague
12/01/2025
FA106
EOL 47k
F EOL 47kAIM
P2-L1-M006 m
AIM
P2-L1-M005 m
S P2-L1-D031
S P2-L1-D032
S P2-L1-D033
S P2-L1-D034
K
K
HOUSING UNIT BUILDING "F" FLOOR PLAN - FIRE ALARM
0 4' 8' 16'
N O
D
AT
E:
RE
VI
SI
O
N D
ES
CR
IP
TI
O N
PR
O
JE
CT
N
AM
E
CU
ST
O
M
ER
L
O
CA
TI
O
N
SY
ST
EM
D
ES
CR
IP
TI
O N
DRAWING #:
DESIGNER:
PROJECT
JOB#:
DATE:
ISSUED
FOR:
St. Louis, Missouri | Columbia, Missouri | Springfield, Missouri Chicago, Illinois| Bloomington, Illinois | Indianapolis, Indiana
Denver, Colorado | Topeka, Kansas| Kansas City www.techelectronics.com
1.800.TECH.789
PROJECT MANAGER:
DRAFTER:
CONSTRUCTION
05/21/2024
PJ2404170004
MM SAS
BOJAN BALTIC
(816) 977-1228
NE
W
F
IR
E
AL
AR
M
S
YS
TE
M
LA
RN
ED
C
OR
RE
CT
IO
NA
L
FA
CI
LI
TY
K
HI
GH
W
AY
LA
RN
ED
, K S
SIGNATURE:
NICET # LEVEL:
DATE:
EXPIRATION:
THIS DRAWING HAS BEEN REVIEWED
FOR SUBMITTAL PURPOSES ONLY
05/28/2024
IV137416
Steven A. Sprague
12/01/2025
FA107
EOL 47k
FEOL 47k
AIM P2-L1-M008
m
AIM
P2-L1-M007 m
S P2-L1-D048
S P2-L1-D049
S P2-L1-D050
S P2-L1-D051
K
K
HOUSING UNIT BUILDING "F2" FLOOR PLAN - FIRE ALARM
0 4' 8' 16'
N O
D
AT
E:
RE
VI
SI
O
N D
ES
CR
IP
TI
O N
PR
O
JE
CT
N
AM
E
CU
ST
O
M
ER
L
O
CA
TI
O
N
SY
ST
EM
D
ES
CR
IP
TI
O N
DRAWING #:
DESIGNER:
PROJECT
JOB#:
DATE:
ISSUED
FOR:
St. Louis, Missouri | Columbia, Missouri | Springfield, Missouri Chicago, Illinois| Bloomington, Illinois | Indianapolis, Indiana
Denver, Colorado | Topeka, Kansas| Kansas City www.techelectronics.com
1.800.TECH.789
PROJECT MANAGER:
DRAFTER:
CONSTRUCTION
05/21/2024
PJ2404170004
MM SAS
BOJAN BALTIC
(816) 977-1228
NE
W
F
IR
E
AL
AR
M
S
YS
TE
M
LA
RN
ED
C
OR
RE
CT
IO
NA
L
FA
CI
LI
TY
K
HI
GH
W
AY
LA
RN
ED
, K S
SIGNATURE:
NICET # LEVEL:
DATE:
EXPIRATION:
THIS DRAWING HAS BEEN REVIEWED
FOR SUBMITTAL PURPOSES ONLY
05/28/2024
IV137416
Steven A. Sprague
12/01/2025
FA108
EOL 47k
AIM
P2-L1-M010 m
AIM
P2-L1-M009 m
S P2-L1-D065
S P2-L1-D066
S P2-L1-D067
S P2-L1-D068
K
K
HOUSING UNIT BUILDING "F3" FLOOR PLAN - FIRE ALARM
0 4' 8' 16'
N O
D
AT
E:
RE
VI
SI
O
N D
ES
CR
IP
TI
O N
PR
O
JE
CT
N
AM
E
CU
ST
O
M
ER
L
O
CA
TI
O
N
SY
ST
EM
D
ES
CR
IP
TI
O N
DRAWING #:
DESIGNER:
PROJECT
JOB#:
DATE:
ISSUED
FOR:
St. Louis, Missouri | Columbia, Missouri | Springfield, Missouri Chicago, Illinois| Bloomington, Illinois | Indianapolis, Indiana
Denver, Colorado | Topeka, Kansas| Kansas City www.techelectronics.com
1.800.TECH.789
PROJECT MANAGER:
DRAFTER:
CONSTRUCTION
05/21/2024
PJ2404170004
MM SAS
BOJAN BALTIC
(816) 977-1228
NE
W
F
IR
E
AL
AR
M
S
YS
TE
M
LA
RN
ED
C
OR
RE
CT
IO
NA
L
FA
CI
LI
TY
K
HI
GH
W
AY
LA
RN
ED
, K S
SIGNATURE:
NICET # LEVEL:
DATE:
EXPIRATION:
THIS DRAWING HAS BEEN REVIEWED
FOR SUBMITTAL PURPOSES ONLY
05/28/2024
IV137416
Steven A. Sprague
12/01/2025
FA109
F EOL 47k
EOL 47k
AIM
P2-L1-M014 m
AIM P2-L1-M015
m
S P2-L1-D088
S P2-L1-D089
S P2-L1-D090
S P2-L1-D091
K
K
HOUSING UNIT BUILDING "F4" FLOOR PLAN - FIRE ALARM
0 4' 8' 16'
N O
D
AT
E:
RE
VI
SI
O
N D
ES
CR
IP
TI
O N
PR
O
JE
CT
N
AM
E
CU
ST
O
M
ER
L
O
CA
TI
O
N
SY
ST
EM
D
ES
CR
IP
TI
O N
DRAWING #:
DESIGNER:
PROJECT
JOB#:
DATE:
ISSUED
FOR:
St. Louis, Missouri | Columbia, Missouri | Springfield, Missouri Chicago, Illinois| Bloomington, Illinois | Indianapolis, Indiana
Denver, Colorado | Topeka, Kansas| Kansas City www.techelectronics.com
1.800.TECH.789
PROJECT MANAGER:
DRAFTER:
CONSTRUCTION
05/21/2024
PJ2404170004
MM SAS
BOJAN BALTIC
(816) 977-1228
NE
W
F
IR
E
AL
AR
M
S
YS
TE
M
LA
RN
ED
C
OR
RE
CT
IO
NA
L
FA
CI
LI
TY
K
HI
GH
W
AY
LA
RN
ED
, K S
SIGNATURE:
NICET # LEVEL:
DATE:
EXPIRATION:
THIS DRAWING HAS BEEN REVIEWED
FOR SUBMITTAL PURPOSES ONLY
05/28/2024
IV137416
Steven A. Sprague
12/01/2025
FA110
FACU P3
FP3-L1-M009
F P3-L1-M008
FP3-L1-M007F P3-L1-M006F P3-L1-M005F P3-L1-M001
AIM
P3-L1-M002 m
AIM
P3-L1-M003 m
AIM
P3-L1-M004 m
EOL 47k
EOL 47k
EOL 47k
S P3-L1-D001
S P3-L1-D002
S P3-L1-D021
AOM
P3-L1-M021 R
AHU S.D.
RL
S P3-L1-D022
AOM
P3-L1-M022 R
AHU S.D.
RL
S P3-L1-D023
AOM
P3-L1-M023 R
AHU S.D.
RL
P3-N1-03 110cd P3-N1-04
110cd
P3-N1-08 75cd
P3-N1-09 75cd
P3-N1-10 75cd
P3-N1-11 15cd
P3-N1-12 110cd
P3-N1-13 185cd
P3-N1-14 EOL 2.2k 110cd
P3-N1-01 30cd
P3-N1-02 30cd
P3-N1-05 15cd
P3-N1-06 15cd
P3-N1-07 110cd
POWER PLANT BUILDING "G" FLOOR PLAN - FIRE ALARM
0 4' 8' 16'
N O
D
AT
E:
RE
VI
SI
O
N D
ES
CR
IP
TI
O N
PR
O
JE
CT
N
AM
E
CU
ST
O
M
ER
L
O
CA
TI
O
N
SY
ST
EM
D
ES
CR
IP
TI
O N
DRAWING #:
DESIGNER:
PROJECT
JOB#:
DATE:
ISSUED
FOR:
St. Louis, Missouri | Columbia, Missouri | Springfield, Missouri Chicago, Illinois| Bloomington, Illinois | Indianapolis, Indiana
Denver, Colorado | Topeka, Kansas| Kansas City www.techelectronics.com
1.800.TECH.789
PROJECT MANAGER:
DRAFTER:
CONSTRUCTION
05/21/2024
PJ2404170004
MM SAS
BOJAN BALTIC
(816) 977-1228
NE
W
F
IR
E
AL
AR
M
S
YS
TE
M
LA
RN
ED
C
OR
RE
CT
IO
NA
L
FA
CI
LI
TY
K
HI
GH
W
AY
LA
RN
ED
, K S
SIGNATURE:
NICET # LEVEL:
DATE:
EXPIRATION:
THIS DRAWING HAS BEEN REVIEWED
FOR SUBMITTAL PURPOSES ONLY
05/28/2024
IV137416
Steven A. Sprague
12/01/2025
FA111
RISER DIAGRAM - BUILDING A,B,C
P3-N1 (x9) P3-N1 (x5)
DEDICATED 120V
20 AMP CIRCUIT
H N G
FIRE ALARM
CONTROL UNIT
P3-L1 (x1)
S P3-L1 (x2)
F P3-L1 (x6)
AIM
m P3-L1 (x1)
P2-N2 (x5)
P2-N1 (x1) P2-N1 (x1)
DEDICATED 120V
20 AMP CIRCUIT
H N G
FIRE ALARM
CONTROL UNIT
P2
F P2-L1 (x5)
S P2-L1 (x98)
AIM
m P2-L1 (x12)
AOM
R P2-L1 (x25)
S
P2-L1 (x25)
KH
HOOD
(x1)
PS
HILO
(x1)(x3)(x3)
F (x21) (x14)P1-N4 (x9) P1-N4 (x15)
P1-N3 (x15) P1-N3 (x16)
P1-N2 (x15) P1-N2 (x24)
P1-N1 (x19) P1-N1 (x22)
S P1-L1 (x26)
S
P1-L1 (x14)
AOM
R P1-L1 (x14)
F P1-L1 (x5)
AIM
m P1-L1 (x21)
DEDICATED 120V
20 AMP CIRCUIT
H N G
FIRE ALARM
CONTROL UNIT
P1
ANN
1B
1B
1A 1A 1A 1A
1B 1B
1A 1A 1A 1A 1A
2U
1B
1B
1B
1B
1B
1B
1B
1B
1A
1A
1A 1A 1A 1A
1U
AIM
m P1-L1 (x1)
1A
1U
AIM
m P1-L1 (x3)
1A
1U
AIM
m P1-L1 (x3)
1A
1U
AIM
m P1-L1 (x1)
1A
1U
1J
1L
1B
(x25)
2U
AIM
m P2-L1 (x3)
1A AIM
m P2-L1 (x2)
1A
(x2)(x3)
F (x12)
1U 1U 1U
1B
1B
RISER DIAGRAM - BUILDING D,E,F
AOM
R P2-L1 (x3)
S
P2-L1 (x3)
1A
(x3)
2U
1A AIM
m P2-L1 (x2)
1A
(x2)(x1)
1U 1U
RISER DIAGRAM - BUILDING G
N O
D
AT
E:
RE
VI
SI
O
N D
ES
CR
IP
TI
O N
PR
O
JE
CT
N
AM
E
CU
ST
O
M
ER
L
O
CA
TI
O
N
SY
ST
EM
D
ES
CR
IP
TI
O N
DRAWING #:
DESIGNER:
PROJECT
JOB#:
DATE:
ISSUED
FOR:
St. Louis, Missouri | Columbia, Missouri | Springfield, Missouri Chicago, Illinois| Bloomington, Illinois | Indianapolis, Indiana
Denver, Colorado | Topeka, Kansas| Kansas City www.techelectronics.com
1.800.TECH.789
PROJECT MANAGER:
DRAFTER:
CONSTRUCTION
05/21/2024
PJ2404170004
MM SAS
BOJAN BALTIC
(816) 977-1228
NE
W
F
IR
E
AL
AR
M
S
YS
TE
M
LA
RN
ED
C
OR
RE
CT
IO
NA
L
FA
CI
LI
TY
K
HI
GH
W
AY
LA
RN
ED
, K S
SIGNATURE:
NICET # LEVEL:
DATE:
EXPIRATION:
THIS DRAWING HAS BEEN REVIEWED
FOR SUBMITTAL PURPOSES ONLY
05/28/2024
IV137416
Steven A. Sprague
12/01/2025
FA201
N O
D
AT
E:
RE
VI
SI
O
N D
ES
CR
IP
TI
O N
PR
O
JE
CT
N
AM
E
CU
ST
O
M
ER
L
O
CA
TI
O
N
SY
ST
EM
D
ES
CR
IP
TI
O N
DRAWING #:
DESIGNER:
PROJECT
JOB#:
DATE:
ISSUED
FOR:
St. Louis, Missouri | Columbia, Missouri | Springfield, Missouri Chicago, Illinois| Bloomington, Illinois | Indianapolis, Indiana
Denver, Colorado | Topeka, Kansas| Kansas City www.techelectronics.com
1.800.TECH.789
PROJECT MANAGER:
DRAFTER:
CONSTRUCTION
05/21/2024
PJ2404170004
MM SAS
BOJAN BALTIC
(816) 977-1228
NE
W
F
IR
E
AL
AR
M
S
YS
TE
M
LA
RN
ED
C
OR
RE
CT
IO
NA
L
FA
CI
LI
TY
K
HI
GH
W
AY
LA
RN
ED
, K S
SIGNATURE:
NICET # LEVEL:
DATE:
EXPIRATION:
THIS DRAWING HAS BEEN REVIEWED
FOR SUBMITTAL PURPOSES ONLY
05/28/2024
IV137416
Steven A. Sprague
12/01/2025
FA301
PANEL P3 (N16E) BATTERY CALCULATION
(SECONDARY POWER SOURCE REQUIREMENTS)
PANEL POWER SUPPLY MAX CURRENT = 6A TOTAL USED CAPACITY (IN ALARM) = 1.8098A (30.16 %)
STANDBY CURRENT (AMPS) SECONDARY ALARM CURRENT (AMPS)
PANEL COMPONENTS
QTY PART NO. DESCRIPTION CURRENT DRAW (A) TOTAL (A) CURRENT DRAW (A) TOTAL
1 CPU-N16LD
N16x with display. Intelligent fire alarm with one SLC loop, 10" touchscreen display, 4 NACs, and power supply; chassis mounted for use in a CAB-5 Series cabinet. 0.269 0.269 0.279 0.279
1 NCM-F Network Communication Module, Fiber 0.11 0.11 0.11 0.11 1 PMB-AUX Addressable Power Supply/Battery Charger 0.096 0.096 0.11 0.11
1 SLM-318
Signaling Line Module provides a Signaling Line Circuit of 159 addressable points. Add SLM-318 units to expand SLC capability. See DN-62115. 0.159 0.159 0.21 0.21
CIRCUIT SYMBOL QTY PART NO DESCRIPTION CURRENT DRAW (A) TOTAL (A) CURRENT DRAW (A) TOTAL (A)
P3-L1
3 DNR w/FSP-951R Intelligent Non-Relay Photoelectric Duct Detector/ FSP-951R. FlashScan and CLIP mode. 0.0002 0.0006 0.0045 0.0135
3 FMM-101 Addressable Mini Monitor Module 0.00035 0.00105 0.0006 0.0018
3 FRM-1 Addressable Relay Module W/ FlashScan, 2 Form-C Dry Contacts 0.000255 0.000765 0.0065 0.0195
2 FSP-951-SELFT w/B300-6 White, low-profile intelligent self-testing photoelectric sensor, FlashScan only 0.0002 0.0004 0.0045 0.009
6 NBG-12LX Dual-action addressable pull station. Includes key locking feature. 0.000375 0.00225 0.005 0.03
P3-N1
1 P2RLED 2-Wire, Horn Strobe, Red 15cd 0 0 0.035 0.035
3 P2RLED 2-Wire, Horn Strobe, Red 75cd 0 0 0.087 0.261
4 P2RLED 2-Wire, Horn Strobe, Red 110cd 0 0 0.094 0.376
1 P2RLED 2-Wire, Horn Strobe, Red 185cd 0 0 0.19 0.19
2 SRLED Strobe, Wall, Red 15cd 0 0 0.018 0.036
2 SRLED Strobe, Wall, Red 30cd 0 0 0.022 0.044
1 SRLED Strobe, Wall, Red 110cd 0 0 0.085 0.085
TOTAL STANDBY (A) 0.639065 TOTAL ALARM (A) 1.8098
REQUIRED STANDBY TIME = 24 HOURS
REQUIRED ALARM TIME = 5 MINUTES
SECONDARY STANDBY LOAD (A) 0.639065 24 15.34
SECONDARY ALARM LOAD (A) 1.8098 0.08 0.15
STANDBY AND ALARM SUBTOTAL (AMP HOURS) 15.49
DERATING FACTOR 1.25
SECONDARY LOAD REQUIREMENTS (AMP HOURS) 19.36
PROVIDE (2) 12V 26AH BATTERIES
*BATTERY BOX SIZE CAPACITY NOT SPECIFIED. REFER TO MANUFACTURER DOCUMENTATION.
S
AIM
m
AOM
R
S
F
PANEL P1 (N16E) BATTERY CALCULATION
(SECONDARY POWER SOURCE REQUIREMENTS)
PANEL POWER SUPPLY MAX CURRENT = 6A TOTAL USED CAPACITY (IN ALARM) = 5.8254A (97.09 %)
STANDBY CURRENT (AMPS) SECONDARY ALARM CURRENT (AMPS)
PANEL COMPONENTS
QTY PART NO. DESCRIPTION CURRENT DRAW (A) TOTAL (A) CURRENT DRAW (A) TOTAL
1 CPU-N16LD
N16x with display. Intelligent fire alarm with one SLC loop, 10" touchscreen display, 4 NACs, and power supply; chassis mounted for use in a CAB-5 Series cabinet. 0.269 0.269 0.279 0.279
2 NCM-F Network Communication Module, Fiber 0.11 0.22 0.11 0.22 1 PMB-AUX Addressable Power Supply/Battery Charger 0.096 0.096 0.11 0.11
1 SLM-318
Signaling Line Module provides a Signaling Line Circuit of 159 addressable points. Add SLM-318 units to expand SLC capability. See DN-62115. 0.159 0.159 0.21 0.21
CIRCUIT SYMBOL QTY PART NO DESCRIPTION CURRENT DRAW (A) TOTAL (A) CURRENT DRAW (A) TOTAL (A)
P1-AUX1 1 NCD Assembly Network Control Display 0 0 0 0
P1-FIBER1 2 N16e Intelligent fire alarm panel with one SLC loop, 10" touchscreen display, 4 NACs, and power supply in a black enclosure. 0 0 0 0
P1-L1
14 DNR w/FSP-951R Intelligent Non-Relay Photoelectric Duct Detector/ FSP-951R. FlashScan and CLIP mode. 0.0002 0.0028 0.0045 0.063
29 FMM-101 Addressable Mini Monitor Module 0.00035 0.01015 0.0006 0.0174
14 FRM-1 Addressable Relay Module W/ FlashScan, 2 Form-C Dry Contacts 0.000255 0.00357 0.0065 0.091
26 FSP-951-SELFT w/B300-6 White, low-profile intelligent self-testing photoelectric sensor, FlashScan only 0.0002 0.0052 0.0045 0.117
5 NBG-12LX Dual-action addressable pull station. Includes key locking feature. 0.000375 0.001875 0.005 0.025
P1-N1
10 P2RLED 2-Wire, Horn Strobe, Red 15cd 0 0 0.035 0.35
2 P2RLED 2-Wire, Horn Strobe, Red 30cd 0 0 0.038 0.076
6 P2RLED 2-Wire, Horn Strobe, Red 75cd 0 0 0.087 0.522
1 P2RLED 2-Wire, Horn Strobe, Red 110cd 0 0 0.094 0.094
16 SRLED Strobe, Wall, Red 15cd 0 0 0.018 0.288
5 SRLED Strobe, Wall, Red 30cd 0 0 0.022 0.11
1 SRLED Strobe, Wall, Red 75cd 0 0 0.07 0.07
P1-N2
21 P2RLED 2-Wire, Horn Strobe, Red 15cd 0 0 0.035 0.735
1 P2RLED 2-Wire, Horn Strobe, Red 30cd 0 0 0.038 0.038
2 P2RLED 2-Wire, Horn Strobe, Red 75cd 0 0 0.087 0.174
14 SRLED Strobe, Wall, Red 15cd 0 0 0.018 0.252
1 SRLED Strobe, Wall, Red 75cd 0 0 0.07 0.07
P1-N3
11 P2RLED 2-Wire, Horn Strobe, Red 15cd 0 0 0.035 0.385
2 P2RLED 2-Wire, Horn Strobe, Red 30cd 0 0 0.038 0.076
3 P2RLED 2-Wire, Horn Strobe, Red 75cd 0 0 0.087 0.261
13 SRLED Strobe, Wall, Red 15cd 0 0 0.018 0.234
1 SRLED Strobe, Wall, Red 30cd 0 0 0.022 0.022
1 SRLED Strobe, Wall, Red 75cd 0 0 0.07 0.07
P1-N4
9 P2RLED 2-Wire, Horn Strobe, Red 15cd 0 0 0.035 0.315
3 P2RLED 2-Wire, Horn Strobe, Red 30cd 0 0 0.038 0.114
1 P2RLED 2-Wire, Horn Strobe, Red 75cd 0 0 0.087 0.087
2 P2RLED 2-Wire, Horn Strobe, Red 110cd 0 0 0.094 0.188
9 SRLED Strobe, Wall, Red 15cd 0 0 0.018 0.162
TOTAL STANDBY (A) 0.767595 TOTAL ALARM (A) 5.8254
REQUIRED STANDBY TIME = 24 HOURS
REQUIRED ALARM TIME = 5 MINUTES
SECONDARY STANDBY LOAD (A) 0.767595 24 18.42
SECONDARY ALARM LOAD (A) 5.8254 0.08 0.49
STANDBY AND ALARM SUBTOTAL (AMP HOURS) 18.91
DERATING FACTOR 1.25
SECONDARY LOAD REQUIREMENTS (AMP HOURS) 23.63
PROVIDE (2) 12V 26AH BATTERIES
*BATTERY BOX SIZE CAPACITY NOT SPECIFIED. REFER TO MANUFACTURER DOCUMENTATION.
FAA
FACU
S
AIM
m
AOM
R
S
F
PANEL P2 (N16E) BATTERY CALCULATION
(SECONDARY POWER SOURCE REQUIREMENTS)
PANEL POWER SUPPLY MAX CURRENT = 6A TOTAL USED CAPACITY (IN ALARM) = 2.5152A (41.92 %)
STANDBY CURRENT (AMPS) SECONDARY ALARM CURRENT (AMPS)
PANEL COMPONENTS
QTY PART NO. DESCRIPTION CURRENT DRAW (A) TOTAL (A) CURRENT DRAW (A) TOTAL
1 CPU-N16LD
N16x with display. Intelligent fire alarm with one SLC loop, 10" touchscreen display, 4 NACs, and power supply; chassis mounted for use in a CAB-5 Series cabinet. 0.269 0.269 0.279 0.279
1 NCM-F Network Communication Module, Fiber 0.11 0.11 0.11 0.11 1 PMB-AUX Addressable Power Supply/Battery Charger 0.096 0.096 0.11 0.11
1 SLM-318
Signaling Line Module provides a Signaling Line Circuit of 159 addressable points. Add SLM-318 units to expand SLC capability. See DN-62115. 0.159 0.159 0.21 0.21
CIRCUIT SYMBOL QTY PART NO DESCRIPTION CURRENT DRAW (A) TOTAL (A) CURRENT DRAW (A) TOTAL (A)
P2-L1
25 DNR w/FSP-951R Intelligent Non-Relay Photoelectric Duct Detector/ FSP-951R. FlashScan and CLIP mode. 0.0002 0.005 0.0045 0.1125
17 FMM-101 Addressable Mini Monitor Module 0.00035 0.00595 0.0006 0.0102
25 FRM-1 Addressable Relay Module W/ FlashScan, 2 Form-C Dry Contacts 0.000255 0.006375 0.0065 0.1625
98 FSP-951-SELFT w/B300-6 White, low-profile intelligent self-testing photoelectric sensor, FlashScan only 0.0002 0.0196 0.0045 0.441
5 NBG-12LX Dual-action addressable pull station. Includes key locking feature. 0.000375 0.001875 0.005 0.025
P2-N1
1 P2RLED 2-Wire, Horn Strobe, Red 75cd 0 0 0.087 0.087
1 SRLED Strobe, Wall, Red 15cd 0 0 0.018 0.018
P2-N2 5 P2RLED 2-Wire, Horn Strobe, Red 185cd 0 0 0.19 0.95
TOTAL STANDBY (A) 0.6728 TOTAL ALARM (A) 2.5152
REQUIRED STANDBY TIME = 24 HOURS
REQUIRED ALARM TIME = 5 MINUTES
SECONDARY STANDBY LOAD (A) 0.6728 24 16.15
SECONDARY ALARM LOAD (A) 2.5152 0.08 0.21
STANDBY AND ALARM SUBTOTAL (AMP HOURS) 16.36
DERATING FACTOR 1.25
SECONDARY LOAD REQUIREMENTS (AMP HOURS) 20.45
PROVIDE (2) 12V 26AH BATTERIES
*BATTERY BOX SIZE CAPACITY NOT SPECIFIED. REFER TO MANUFACTURER DOCUMENTATION.
S
AIM
m
AOM
R
S
N O
D
AT
E:
RE
VI
SI
O
N D
ES
CR
IP
TI
O N
PR
O
JE
CT
N
AM
E
CU
ST
O
M
ER
L
O
CA
TI
O
N
SY
ST
EM
D
ES
CR
IP
TI
O N
DRAWING #:
DESIGNER:
PROJECT
JOB#:
DATE:
ISSUED
FOR:
St. Louis, Missouri | Columbia, Missouri | Springfield, Missouri Chicago, Illinois| Bloomington, Illinois | Indianapolis, Indiana
Denver, Colorado | Topeka, Kansas| Kansas City www.techelectronics.com
1.800.TECH.789
PROJECT MANAGER:
DRAFTER:
CONSTRUCTION
05/21/2024
PJ2404170004
MM SAS
BOJAN BALTIC
(816) 977-1228
NE
W
F
IR
E
AL
AR
M
S
YS
TE
M
LA
RN
ED
C
OR
RE
CT
IO
NA
L
FA
CI
LI
TY
K
HI
GH
W
AY
LA
RN
ED
, K S
SIGNATURE:
NICET # LEVEL:
DATE:
EXPIRATION:
THIS DRAWING HAS BEEN REVIEWED
FOR SUBMITTAL PURPOSES ONLY
05/28/2024
IV137416
Steven A. Sprague
12/01/2025
FA501
24.00"
(2) PS-12260F2
N16E
20.31"
TO 120VAC
DEDICATED
CIRCUIT
No Print:
· To Use as the Primary Display for NFS2-640 or NFS-320 - NUP together - This is not
Networkable.
· Can be mounted on the left with a DP-GDIS1 dress panel (CAB-4 Row A) DP-T2A
(CAB-5) or DP-GDIS2 (Row B-D CAB-4)
· NBB-2 Backbox, black, Surface - can mount a single HS-NCM or 2 NCM
TB1
Alt. 24v Pwr
IN OUT
NUP
J10 Trouble
Relay
N/O N/C
COM
TX
RX
CTS
REFPrinter
External AIO Bus
Internal AIO Bus
A+ A- B+ B-
485+ 485-
SYS Sync Tamper Trouble
J9 J8 J7
J13J1
SW1
AIO A Side Term
SW2
AIO B Side Term
SW16
Piezo Enable/Disable
Enable Disable
J6
J3
USB A
USB B Micro J12
J11
TB2
TB3
TB4
TB5
\\techadnet.local\techdata\vdi\employees\KF\t2z\vmartinez\My Documents\Sandbox\01_CAD Related\PDF Images\Pages from LS10210-051NF-E - Copyd0537373.png \\techadnet.local\techdata\vdi\employees\KF\t2z\vmartinez\My Documents\Sandbox\01_CAD Related\PDF Images\Pages from LS10210-051NF-E - Copyb938f9a3.png\\techadnet.local\techdata\vdi\employees\KF\t2z\vmartinez\My Documents\Sandbox\01_CAD Related\PDF Images\Pages from LS10210-051NF-E - Copy7c73580b.png
\\techadnet.local\techdata\vdi\employees\KF\t2z\vmartinez\My Documents\Sandbox\01_CAD Related\PDF Images\Pages from LS10210-051NF-E - Copybb86bdb5.png
\\techadnet.local\techdata\vdi\employees\KF\t2z\vmartinez\My Documents\Sandbox\01_CAD Related\PDF Images\Pages from LS10210-051NF-E - Copy96896215.png
\\techadnet.local\techdata\vdi\employees\KF\t2z\vmartinez\My Documents\Sandbox\01_CAD Related\PDF Images\Pages from LS10210-051NF-E - Copy5b9c8786.png
\\techadnet.local\techdata\vdi\employees\KF\t2z\vmartinez\My Documents\Sandbox\01_CAD Related\PDF Images\Pages from LS10210-051NF-E - Copy79fbaf89.png
\\techadnet.local\techdata\vdi\employees\KF\t2z\vmartinez\My Documents\Sandbox\01_CAD Related\PDF Images\Pages from LS10210-051NF-E - Copy63129307.png
\\techadnet.local\techdata\vdi\employees\KF\t2z\vmartinez\My Documents\Sandbox\01_CAD Related\PDF Images\Pages from LS10210-051NF-E - Copydbaadbd9.png
CO ALARM
OTHER
DISABLE
TROUBLE
SUPERVISORY
SIGNALS
SILENCED
FIRE ALARM
System Normal Ack Silence Reset
Tue 01/01/23
02:38:06PM
Master
From Non Restable Power Supply
To Next Device Requiring Power
L L
To Printer
NUP to Network CardNUP to FACU
From FACU
To Other Device or
FACU
J
J
SBB-A4 - CABINET
24.00" Backbox 24.13" Overall
20.13" Overall
(2) BMP-1
BP2-4
DP-GDIS1
RXB TXB RXA TXA
NU
P1
NU
P2
J3
PORT
NUP
J2
SW2SW1
ST Style Fiber Connection
Fr om
P re vi ou s No de
NC
M -F
(C ha nn el
A
N
To N ex t N od e
NC
M
-F (C ha nn el B
N
7555675556 To FACP or NCA-2
J1 NUP Connection
WIC (F.B.O.)
WIC CAN NOT BE MOUNTED
INSIDE OF FIRE ALARM
CABINETS
NCM-F
0 12
678910
14 15 Address
Loop
Normal
Activated
NBG-12LX
0 12
Loop Address
Write address number (1-159) here Write loop number (1-10) here
Splice and Tape up Shield Completely or Cut and Tape up if last device on run
Notifier NBG-12LX Manual Pull Station Wiring Connections
To Next Addressable
Device or FACP (If Applicable)
Style 6 (Class A):
Style 6 wiring requires that all devices be looped in and out. "T" Tapping is NOT permissible for the SLC Style 4 (Class B):
"T" Tapping is permissible for the SLC
STRIP GAUGE
A
A
From FACP or Previous
Addressable Device
- Connection F.B.O. - Furnished by Other
E.O.L. - End of Line- No Connection
TECH ELECTRONONICS
TE_DC_NBG-12LX.dwg:A
04/28/14
Notifier B300-6 or B300-6-IV Low Profile Detector Base for use with: FSP-951, FSP-951-IV, FSP-951T, FSP-951T-IV, FST-951, FSP-951-IV, Series Detectors
Style 6 (Class A):
Style 6 wiring requires that all devices be looped in and out. "T" Tapping is NOT permissible for the SLC Style 4 (Class B):
"T" Tapping is permissible for the
SLC
- Connection F.B.O. - Furnished by Other
E.O.L. - End of Line- No Connection
From FACP or Previous
Addressable Device
To Next Addressable Device or FACP (If Applicable)
Splice and Tape up Shield Completely or Cut and Tape up if last device on run
RA
AA
TECH ELECTRONONICS
B300-6.dwg:A
11/28/18
TECH ELECTRONICS
02/21/12
- Connection F.B.O. - Furnished by Other
E.O.L. - End of Line- No Connection
Yellow Violet
From FACP or Previous
Addressable Device
To Next Addressable Device or FACP (If Applicable)
BlackRed
FMM-101 Device Connection Drawing for a Single Normally Open Switch
TE_DC_FMM-101.dwg:A
0 12
5678910
14 15 Address
Loop
0 12
56789 Tens Ones
(+) (-) (+) (-) Splice and Tape up Shield Completely or Cut and Tape up if last device on run
FMM-101
A
A
Cut and Tape up Shield Completely
Any Normally Open Switch Examples:
1. Fire Pump - Power Loss - F.B.O.
2. Fire Pump - Phase Reversal - F.B.O.
3. Fire Pump - Running - F.B.O.
4. Fire Pump - Emergency Power - F.B.O.
5. Water Flow Switch - F.B.O.
6. Tamper Switch - F.B.O.
7. PIV Tamper Switch - F.B.O.
8. Low Pressure Switch - F.B.O.
9. Kitchen Hood Alarm Contact - F.B.O.
10. Crosstie to existing FACP - Alarm Relay
11. Crosstie to existing FACP - Trouble Relay
12. Crosstie to existing FACP - Supervisory Relay
13. Fire Suppression - Alarm
14. Fire Suppression - Trouble
15. Fire Suppression - Supervisory
16. Generator Running - F.B.O.
17. Generator Alarm - F.B.O.
47K
U
FSP-951R
RTS+
COM -
TEST COIL+
TEST COIL -
COM+
RA+
RA/RTS -
OUT+
DNR
From FACP or Previous Addressable Device
To Next Addressable Device or FACP (If Applicable)
Style 6 (Class A):
Style 6 wiring requires that all devices be looped in and out. "T" Tapping is NOT permissible for the SLC Style 4 (Class B):
"T" Tapping is permissible for the
SLC
Splice and Tape up Shield Completely or Cut and Tape up if last device on run
4 5 6
1 2 3
RTS451KEY/RTS151KEY
Cut and Tape up Shield Completely
System Sensor DNR Duct Detector with a RTS451KEY or RTS151KEY Remote Test Station
U
A
A
UU
TECH ELECTRONONICS
TE_DC_DNR.dwg:E
11/28/18
From FACP or Previous
Addressable Device
To Next Addressable
Device or FACP (If Applicable)
The Installing Contractor shall locate this device within 3-feet of device to be controlled.
Contacts shown in Non-Alarm state.
The Installing Contractor shall determine if the control circuit requires a normally open or normally closed operation.
Notifier FRM-1 Device Connection Drawing
Use this drawing for the following Functions
1. AHU Shutdown
2. Damper Control
3. Exhaust Fan
4. Stair Pressurization
5. Kitchen Hood
6. Lock Control Device
7. Door Holders
SLC (+)
* Use a "C" Cable if the controller is Low Voltage. If the Controller is 120VAC use
THHN (F.B.O.)
If the load exceeds the Relay Contact rating, Install an interposing Relay
Splice and Tape up Shield Completely or Cut and Tape up if last device on run
Style 6 (Class A):
Style 6 wiring requires that all devices be looped in and out. "T" Tapping is NOT permissible for the SLC Style 4 (Class B):
"T" Tapping is permissible for the
SLC
Note: The FRM-1, FZM-1, FCM-1 FDM-1, FTM-1 and the FMM-1 are similar in physical appearance but different in application. Verify the correct module that is being installed.
Failure to do so could cause damage to the device or the Fire
Alarm Control Panel.
TECH ELECTRONICS
09/05/08
- Connection F.B.O. - Furnished by Other
E.O.L. - End of Line- No Connection
TE_DC_FRM_1_New.dwg:A
Load Type Max.
Voltage Current Rating
Resistive Resistive Inductive
30VDC
125VAC
125VAC
3.0A 0.9A 0.3A
FRM-1 Table
A
A
SLC (-)
SLC (+)
67 8910
AddressLoop
567 8 9
OnesTens
T9 T8 T7 T6
T1 N.C. 2 N.O. 2
COMM 1
N.C. 1
T2T10
COMM 2
FRM-1
T11
N.O. 1
From Previous Devices or Power
Supply
Note: "T" Tapping is not allowed
S- S+ S+
S- S+ S+
B B
Horn Tone Audio Select
1 High Temporal Horn
2 Low Temporal Horn
3 High Non-Temporal Horn
4 Low Non-Temporal Horn
5 High 3.1KHz Temporal Horn
6 Low 3.1KHz Temporal Horn
The Horns Have to be Set to a Temporal Horn Only Use
Setting 1, 2, 5, or 6
Note: The default setting for the
Audio Select is 1.
Change this to 2.
Unless otherwise noted.
7 High 3.1KHz Non-Temporal Horn
8 Low 3.1KHz Non-Temporal Horn
Chime Tone Audio Select
1 High 1 Second
2 Low 1 Second
3 High 14 Second
4 Low 14 Second
5 High Temporal
6 Low Temporal
The Chimes Have to be Set to a Temporal Chime Only Use
Setting 5 or 6
7 High 5 Second Whoop
8 Low 5 Second Whoop
Verify EOLR Value Based on the associated Signal Circuit Control Panel
EOLR
For use with the following models: P2RLED, P2RLED-B, P2WLED, P2WLED-B, P2RLED-P, P2WLED-P, P2RLED-SP, P2WLED-SP, P2GRLED, P2RGLED-B, P2GWLED, P2GWLED-B, SRLED, SRLED-B, SWLED, SWLED-B, SRLED-P, SWLED-P, SRLED-P, SRLED-SP, SWLED-CLR-ALERT, SWLED-ALERT, SGRLED, SGRLED-B, SGRLED-P, SGWLED, SGWLED-P, SGWLED-B, PC2RLED, PC2RLED-B, PC2WLED, PC2WLED-B, SCRLED, SCWLED, SCWLED-CLR-ALERT, SCRLED-P, SCWLED-P, SCRLED-B, SCWLED-B
Candela Range
110^
135^
177*
Note: Refer to Floorplans for candela ratings
115*
150*
185^
*Ceiling Mount Devices Only ^Wall Mount Devices Only
TECH ELECTRONICS
TE_DC_SS_NAC_L_SERIES_LED.dwg:A
11/15/2023
Connection Drawing for System Sensor "L" Series Horn, Chime, Horn/Strobe with LED, Chime/Strobe with LED, and Strobe with LED
Audio Selector Candela Selector
N16E PANEL DETAIL NCD ASSEMBLY DETAIL
| Sheets and Views |
| PJ2404170004 Bldg A_G Commons New FA-FA001 |
| PJ2404170004 Bldg A_G Commons New FA-FA101 |
| PJ2404170004 Bldg A_G Commons New FA-FA102 |
| PJ2404170004 Bldg A_G Commons New FA-FA103 |
| PJ2404170004 Bldg A_G Commons New FA-FA104 |
| PJ2404170004 Bldg A_G Commons New FA-FA105 |
| PJ2404170004 Bldg A_G Commons New FA-FA106 |
| PJ2404170004 Bldg A_G Commons New FA-FA107 |
| PJ2404170004 Bldg A_G Commons New FA-FA108 |
| PJ2404170004 Bldg A_G Commons New FA-FA109 |
| PJ2404170004 Bldg A_G Commons New FA-FA110 |
| PJ2404170004 Bldg A_G Commons New FA-FA111 |
| PJ2404170004 Bldg A_G Commons New FA-FA201 |
| PJ2404170004 Bldg A_G Commons New FA-FA301 |
| PJ2404170004 Bldg A_G Commons New FA-FA501 |
File details come from the government source that posted it. Updated .