Attachment_B_-_Fire_Alarm.pdf
PDF 9 MB Posted
- Attached to
- Fire Alarm Installation
- Solicitation number
- EVT0010640
- Issued by
- Marion County, Levant CDP, Kansas
About this file
This Invitation for Bid is issued by the State of Kansas Department of Administration, Office of Procurement and Contracts, on behalf of Larned State Correctional Facility in Marion County. The procurement requests complete removal of existing fire alarm systems and installation of a new Notifier Fire Alarm System at the Central and South buildings located at 1318 KS Highway 264, Larned, Kansas. Deliverables include removal of existing fire alarm infrastructure, installation of the new Notifier system, repair or replacement of equipment as necessary to ensure operational capability, and daily debris cleanup throughout the installation period. A mandatory pre-bid conference is scheduled for January 20, 2026, at 10:30 AM at the facility site, with attendance required for bid eligibility. Written questions must be submitted by February 3, 2026, at end of business, with bids due on February 3, 2026, at 2:00 PM CST. The contract period extends from the date of award through February 28, 2027, with project delivery completion required by February 8, 2026.
Pricing must be submitted as lump sum costs for system removal and installation, with all prices remaining firm for the contract period. No subcontracting is permitted; all work must be performed directly by the awarded qualified bidder. Award will be made to the lowest responsible bidder conforming to specifications and contract terms. Bidders must possess current workers' compensation insurance documentation for all employees and submit a Kansas Department of Revenue Tax Clearance Certificate at the time of bidding. Required bid submissions include an Immigration Reform and Control certification form, a Boycott of Israel compliance form, and a Sexual Harassment policy form. The project will be tax-exempt with a Project Tax Exemption Certificate issued at award. Bidders may claim Kansas Bidder Preference categories, including Disabled Veteran Owned Business or Certified Business preferences if supported by appropriate documentation. The State reserves the right to reject any or all bids, waive informalities, and terminate the contract for convenience with 30 days' notice or for cause if delivery or quality standards are not met. For additional information, bidders should contact Procurement Officer Ashley N. Evans at 785/296-8107 or ashley.n.evans@ks.gov.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Larned Correctional Facility KDOC- LCMHF Central Unit FA System Replacement
Address: 1318 K264 hwy.
Larned, KS 67550
Tech Job Number: PJ2404170004 Contractor:
WE ARE PLEASED TO SUBMIT THE ENCLOSED
DRAWINGS. AS REQUESTED, THESE SUBMITTALS ARE
FOR RECORD ONLY AND ALL MATERIAL WILL BE
ORDERED AS DESCRIBED HEREIN.
ESTIMATED DELIVERY IS 12 WEEKS AFTER RECEIPT
OF WRITTEN RELEASE AUTHORIZATION FROM .
FOR INFORMATION REGARDING THIS PROJECT PLEASE CALL:
Bojan Baltic Project Manager
Direct Phone: (785) 430-5824 Mobile Phone: (816) 977-1228 bojan.baltic@techelectronics.com
Tech Electronics of Kansas, LLC
6431 SE Bleckley St. Topeka, KS 66619 www.techelectronics.com
Offices & Representatives in Other Cities
5/29/2024
KDOC- LCMHF Central Unit FA System Replacement
Item Page Model Number & Description Recommended Rough-in
6431 SE Bleckley St. Topeka, KS 66619 . www.techelectronics.com I Tech Electronics of Kansas, LLC
N/E = NO EXHIBIT
Bldgs A,B & C-FA System Replacement
At: Building A 1318 K264 hwy.
Larned, KS 67550
1 1 N16E Intelligent Fire Alarm Panel, 1 SLC Loop Card, 318 DEVICES, 10" Touchscreen Display, 4 NAC'S And Power Supply With Enclosure
Surface Mount 20.31”H x 24”W x 5.5”D 120VAC dedicated 20 ampere circuit and earth ground is required.
Use Emergency Power if available locate as shown on the plans.
2 8 PS-12260F2
Battery; 12 Volt, 26AH
Mounts in Cabinet supplied by Tech Electronics.
3 10 NCM-F
Network Control Module - Fiber
Mounts in SBB-4X series cabinet.
4 12 NCD
Intuitive Color 10" Touch Screen Providing Color Coded Information of Detailed System Status; Compatible with Onyx Series Notes Such As NFS2-3030, NFS-320, and FNS2-640 Fire Alarm Control Panels
5 12 DP-GDIS1
Dress-Plate, First Row
6 14 BMP-1
Blank Module Panel
Mounts in SBB-4X backboxes or ABS and ABF series backboxes.
7 N/E CHS-M3
Mounting Chassis, 3030
Installs in FACP.
8 15 SBB-A4
Backbox; One Chassis - Black
Locate as shown on plans. Each cabinet is 29"H x 25"W x 6"D.
Reserve bottom 9" for batteries. Use only identified conduit entries. Allow 4" on each side for door to open.
9 15 DR-A4
Door; Lock & Keys. Accepts One Chassis - Black
Mounts on SBB-A4.
10 1 PMB-AUX-RTO
Auxiliary Power Supply, 6 Amps, Universal AC Input, on Chassis (to Mount on CAB-4).
No Loop Card, No Core Board
KDOC- LCMHF Central Unit FA System Replacement
Item Page Model Number & Description Recommended Rough-in
6431 SE Bleckley St. Topeka, KS 66619 . www.techelectronics.com II Tech Electronics of Kansas, LLC
N/E = NO EXHIBIT
11 21 BP2-4
Battery, Dress Plate, For NFS2-640 & NFS2-3030, Black
Installs on SBB series cabinet.
12 22 PS-12120
Battery; 12 Volt, 12 Amp Hour
Mounts in Cabinet supplied by Tech Electronics.
13 24 NBG-12LX
Addressable Pull Station
4" Square box with a two gang frame. If surface mounting is required, use SB-10 box.
14 N/E SP1KO
Pull Station, Manual
15 26 FMM-101
Addressable Mini Module
Mount in same box as device being monitored. Module measures 1-1/2"x3"x1-1/2. Ensure ample space is available or install module in a separate box with a blank cover.
16 30 FSP-951-SELFT
Self Test Intelligent Addressable Photo Detector
Mounts on B300-6 Base
17 33 B300-6 Intelligent Flanged Mounting Base, 6", White
4" Octagon box 2-1/8" deep.
18 36 DNR
Duct Smoke Detector Housing, Intelligent, Non-Relay, Photoelectric, Low Flow
Mounts on air duct. See Mfr's recommendations for mounting details and air velocity requirements.
Any deviations must be approved by the "Authority Having Jurisdiction".
19 38 FSP-951R
Remote Test Capable Photoelectric Detector With Flashscan, For Use With DNR(W) Duct Detector Housing, White
Mounts on DNR Duct Smoke Detector Housing
20 41 FRM-1
Addressable Relay Module
4" square box 2 1/8" deep with extension ring. Overall minimum depth 3 5/8". No frame required.
KDOC- LCMHF Central Unit FA System Replacement
Item Page Model Number & Description Recommended Rough-in
6431 SE Bleckley St. Topeka, KS 66619 . www.techelectronics.com III Tech Electronics of Kansas, LLC
N/E = NO EXHIBIT
21 43 DST5
Sampling Tube, Metal, Duct Widths Up To 4'-8' (1.2m-2.4m)
Must be sized by E.C. to completely span air duct. E.C. must specify correct length to Tech Electronics, Inc. BEFORE tubes will be ordered.
See specification sheet included with this submittal for tube length.
22 44 RTS151KEY
Remote Test Station With Switch, Alarm & Power LED's, Key Reset
One gang box 2-1/2" deep.
23 48 R-10E Relay, SPDT, Multivolt, Track Mount, Metal Enclosure
Comes with its own EnclosureSize:
5.1" L x 3.75" W x 2.5" H
24 52 P2RLED
Horn/Strobe, LED, 2W Red Wall 2X4
4” SQUARE BOX 1-1/2” DEEP.
SURFACE MOUNT TO SBBRL OR
SBBWL.
25 52 SRLED
Strobe LED Red Wall 4X4
4” SQUARE BOX 1-1/2” DEEP.
SURFACE MOUNT TO SBBRL OR
SBBWL.
KDOC- LCMHF Central Unit FA System Replacement
Item Page Model Number & Description Recommended Rough-in
6431 SE Bleckley St. Topeka, KS 66619 . www.techelectronics.com IV Tech Electronics of Kansas, LLC
N/E = NO EXHIBIT
Bldgs D, E & F- FA System Replacement
At: Commons Bldg.
1318 K264 hwy.
Larned, KS 67550
26 1 N16E Intelligent Fire Alarm Panel, 1 SLC Loop Card, 318 DEVICES, 10" Touchscreen Display, 4 NAC'S And Power Supply With Enclosure
Surface Mount 20.31”H x 24”W x 5.5”D 120VAC dedicated 20 ampere circuit and earth ground is required.
Use Emergency Power if available locate as shown on the plans.
27 8 PS-12260F2
Battery; 12 Volt, 26AH
Mounts in Cabinet supplied by Tech Electronics.
28 10 NCM-F
Network Control Module - Fiber
Mounts in SBB-4X series cabinet.
29 56 SLM-318
Signaling Loop Card, Flashscan
30 24 NBG-12LX
Addressable Pull Station
4" Square box with a two gang frame. If surface mounting is required, use SB-10 box.
31 N/E SP1KO
Pull Station, Manual
32 26 FMM-101
Addressable Mini Module
Mount in same box as device being monitored. Module measures 1-1/2"x3"x1-1/2. Ensure ample space is available or install module in a separate box with a blank cover.
33 30 FSP-951-SELFT
Self Test Intelligent Addressable Photo Detector
Mounts on B300-6 Base
34 33 B300-6 Intelligent Flanged Mounting Base, 6", White
4" Octagon box 2-1/8" deep.
35 58 STI-9705
Strobe Wire Guard, Flush Mount, White
Mounts to flat surface over protected device, KDOC- LCMHF Central Unit FA System Replacement
Item Page Model Number & Description Recommended Rough-in
6431 SE Bleckley St. Topeka, KS 66619 . www.techelectronics.com V Tech Electronics of Kansas, LLC
N/E = NO EXHIBIT
36 36 DNR
Duct Smoke Detector Housing, Intelligent, Non-Relay, Photoelectric, Low Flow
Mounts on air duct. See Mfr's recommendations for mounting details and air velocity requirements.
Any deviations must be approved by the "Authority Having Jurisdiction".
37 38 FSP-951R
Remote Test Capable Photoelectric Detector With Flashscan, For Use With DNR(W) Duct Detector Housing, White
Mounts on DNR Duct Smoke Detector Housing
38 41 FRM-1
Addressable Relay Module
4" square box 2 1/8" deep with extension ring. Overall minimum depth 3 5/8". No frame required.
39 43 DST5
Sampling Tube, Metal, Duct Widths Up To 4'-8' (1.2m-2.4m)
Must be sized by E.C. to completely span air duct. E.C. must specify correct length to Tech Electronics, Inc. BEFORE tubes will be ordered.
See specification sheet included with this submittal for tube length.
40 44 RTS151KEY
Remote Test Station With Switch, Alarm & Power LED's, Key Reset
One gang box 2-1/2" deep.
41 48 R-10E Relay, SPDT, Multivolt, Track Mount, Metal Enclosure
Comes with its own EnclosureSize:
5.1" L x 3.75" W x 2.5" H
42 52 P2RLED
Horn/Strobe, LED, 2W Red Wall 2X4
4” SQUARE BOX 1-1/2” DEEP.
SURFACE MOUNT TO SBBRL OR
SBBWL.
43 52 SRLED
Strobe LED Red Wall 4X4
4” SQUARE BOX 1-1/2” DEEP.
KDOC- LCMHF Central Unit FA System Replacement
Item Page Model Number & Description Recommended Rough-in
6431 SE Bleckley St. Topeka, KS 66619 . www.techelectronics.com VI Tech Electronics of Kansas, LLC
N/E = NO EXHIBIT
Bldgs G- Power Plant- FA System Replacement
At: Building G Maintenance Shop 1318 K264 hwy.
Larned, KS 67550
44 1 N16E Intelligent Fire Alarm Panel, 1 SLC Loop Card, 318 DEVICES, 10" Touchscreen Display, 4 NAC'S And Power Supply With Enclosure
Surface Mount 20.31”H x 24”W x 5.5”D 120VAC dedicated 20 ampere circuit and earth ground is required.
Use Emergency Power if available locate as shown on the plans.
45 8 PS-12260F2
Battery; 12 Volt, 26AH
Mounts in Cabinet supplied by Tech Electronics.
46 10 NCM-F
Network Control Module - Fiber
Mounts in SBB-4X series cabinet.
47 24 NBG-12LX
Addressable Pull Station
4" Square box with a two gang frame. If surface mounting is required, use SB-10 box.
48 26 FMM-101
Addressable Mini Module
Mount in same box as device being monitored. Module measures 1-1/2"x3"x1-1/2. Ensure ample space is available or install module in a separate box with a blank cover.
49 30 FSP-951-SELFT
Self Test Intelligent Addressable Photo Detector
Mounts on B300-6 Base
50 33 B300-6 Intelligent Flanged Mounting Base, 6", White
4" Octagon box 2-1/8" deep.
51 36 DNR
Duct Smoke Detector Housing, Intelligent, Non-Relay, Photoelectric, Low Flow
Mounts on air duct. See Mfr's recommendations for mounting details and air velocity requirements.
Any deviations must be approved by the "Authority Having Jurisdiction".
52 38 FSP-951R
Remote Test Capable Photoelectric Detector With Flashscan, For Use With DNR(W) Duct Detector Housing, White
Mounts on DNR Duct Smoke Detector Housing
KDOC- LCMHF Central Unit FA System Replacement
Item Page Model Number & Description Recommended Rough-in
6431 SE Bleckley St. Topeka, KS 66619 . www.techelectronics.com VII Tech Electronics of Kansas, LLC
N/E = NO EXHIBIT
53 41 FRM-1
Addressable Relay Module
4" square box 2 1/8" deep with extension ring. Overall minimum depth 3 5/8". No frame required.
54 43 DST5
Sampling Tube, Metal, Duct Widths Up To 4'-8' (1.2m-2.4m)
Must be sized by E.C. to completely span air duct. E.C. must specify correct length to Tech Electronics, Inc. BEFORE tubes will be ordered.
See specification sheet included with this submittal for tube length.
55 44 RTS151KEY
Remote Test Station With Switch, Alarm & Power LED's, Key Reset
One gang box 2-1/2" deep.
56 48 R-10E Relay, SPDT, Multivolt, Track Mount, Metal Enclosure
Comes with its own EnclosureSize:
5.1" L x 3.75" W x 2.5" H
57 52 P2RLED
Horn/Strobe, LED, 2W Red Wall 2X4
4” SQUARE BOX 1-1/2” DEEP.
SURFACE MOUNT TO SBBRL OR
SBBWL.
58 52 SRLED
Strobe LED Red Wall 4X4
4” SQUARE BOX 1-1/2” DEEP.
Design Installation Service
Tech Electronics is Your Source for CABLE on these Electronic Systems.
For information, Availability, & Pricing of CABLE Please Call:
Inside Sales
(314) 951-1718 or
(855) 262-8318
For All Other Information on This Project, Please Call:
Bojan Baltic
(785) 430-5824
Tech Electronics of Kansas, LLC
6431 SE Bleckley St. Topeka, KS 66619 www.techelectronics.com
Offices & Representatives in Other Cities
DN-62116:A • 02/19/2021 — Page 1 of 7
N16e
N16e/x Fire Alarm Control Panel
EFFICIENT, SCALABLE, CONNECTED
General The NOTIFIER INSPIRE™ Series Fire Alarm Control Panels (FACPs) bring the latest technology to life safety. Fire emergency detection and evacuation are extremely critical to life safety. With the N16e and N16x panels, NOTIFIER INSPIRE Series offers a scalable platform to meet any size application.
NOTIFIER INSPIRE Series FACPs feature an intuitive 10" color touchscreen display. This display is color coded with system and sta-tus information. Users are presented with vital information that is easy to read and navigate.
Offered in a standard preconfigured enclosure, the N16e comes with one Signaling Line Module to support 318 intelligent addressable devices. Up two additional Signaling Line Modules (SLM-318) can be added, expanding capacity to 954 intelligent addressable devices on three Signaling Line Circuit (SLC) loops. The panel ships with power supply PMB-AUX to support four NACs and two auxiliary out-puts. Panels can be configured with just a few devices for small building applications or networked with many devices to protect a large campus or a high-rise office block. Simply add additional peripheral equipment to suit the application.
The N16x features a modular design. Order CPU-N16LND, CPU- N16LD, or CPU-16-RTO to meet project requirements. Panels can be configured for stand-alone or network systems. The N16x can support one to 10 SLM-318 modules, for a capacity of up to 3,180 intelligent addressable devices on 10 SLC loops. Optional enclosure sizes are available to support additional peripheral equipment. A host of other options are available, including single or multichannel integrated voice; firefighter's telephone and many additional options.
The NOTIFIER INSPIRE Series integrates with the Connected Life Safety Services (CLSS) platform through the CLSS Gateway, provid-ing connectivity to central station, cloud, and mobile applications.
(See HON-62034.) This cloud-based functionality provides reliable protection and remote monitoring of the system, reduced manual data entry, and reporting. Use CLSS to access licensable panel fea-tures, VeriFire® Tools, workstation licenses, and more.
Features
• 10" high definition touchscreen display with customizable buttons
• 6.0 A power supply with customizable outputs (see DN-62116)
– Two auxiliary Class A/B outputs configurable for resettable or non-resettable operation
– Four Class A/B power outputs that can be configured as Class A/B Notification Appliance Circuits (NACs), power circuit, door holder circuit, or Universal Zone Coding circuit (UZC license-able option)
– NACs support selectable System Sensor, Wheelock, and Gentex strobe synchronization
– NACs support up to 3 patterns of output to allow dynamic sig-naling based on system events: Temp-3 (Fire), Temp-4 (CO), two-stage evacuation, selective silence
• Easy expansion of isolated intelligent Signaling Line Circuit (SLC) capacity
– One expandable to three on N16e (three cards in the cabinet)
– One expandable to ten on N16x
• Easy expansion of N16x power capacity (one expandable to three PMB-AUX power supplies)
• Wireless fire protection using SWIFT® Smart Wireless Integrated Fire Technology (see DN-60820)
• Up to 159 detectors and 159 modules per SLC; 318 devices per loop/3,180 per FACP or network node
– Self-Test detector technology
– Detectors can be any mix of photo, thermal, or multi-sensor;
wireless detectors are available for use with the SWIFT Wire-less Gateway (FWSG)
– Modules include addressable pull stations, normally open con-tact devices, two-wire smoke detectors, notification, or relay;
wireless modules are available for use with the FWSG
• Network options:
– High-speed network for up to 200 nodes (NFS2-3030, NFS2-
640, NFS-320(C), NFS-320SYS, NCD, NCA-2, DVC-EM,
ONYXWorks®)
– Standard network for up to 103 nodes (NFS2-3030, NFS2-640, NFS-320(C), NFS-320SYS, NCD, NCA-2, DVC-EM, ONYXWorks). Up to 54 nodes when DVC-EM is used in net-work paging
• Network Display Mode (licenseable feature) allows the panel to act as a network display node, making the NCD optional
• Emergency voice options available (integrated digital voice or sidecar audio)
• Weekly Occupancy Schedules allow changing sensitivity by time of day and day of week
• History Buffer (10,000 events, 3000 displayed)
• Advanced history filters allow sorting by event, time, date, or address
• Alarm Verification selection per point, with automatic counter
• Color coded icon-based event notification
• Event filtering to quickly view event groups
• Optional cloud connectivity for remote off site monitoring through
CLSS (see HON-62034)
• Monitor multiple buildings through one off-campus central station, and report through the CLSS Gateway
• Silence Inhibit and Auto Silence timer options
Page 2 of 7 — DN-62116:A • 02/19/2021
• Field programmable with VeriFire Tools
• Optional remote programing through CLSS
• Non-alarm points for lower priority functions
• Up to 2000 powerful Boolean logic equations
• Supplemental EIA-232 printer port
• Internal and external connectors for AIO Bus devices
LICENSABLE PANEL FEATURES THROUGH CLSS
• Expanded general zones (250 zones included, expandable up to
2000 zones in increments of 250)
• Expanded logic zones (250 zones included, expandable up to 2000 zones in increments of 250)
• Universal Zone Coding (UZC)
• Network display mode enables N16 to emulate the NCD’s full net-work display capabilities
• Expanded custom action buttons (8 buttons included, expandable up to 32 buttons, in increments of 8)
• CLIP mode
SWIFT WIRELESS
• Self-healing mesh wireless protocol
• Each SWIFT Gateway supports up to 49 devices
• Up to 4 wireless gateways can be installed with overlapping net-work coverage
VOICE AND TELEPHONE FEATURES
• Up to eight channels of digital audio
• 35 watt, 50 watt, 75 watt, and 100/125 watt digital amplifiers
(DAA2/DAX series and DS series)
• Solid state message generation
• Hard-wired voice control module options
• Firefighter telephone option
• 30- to 120-watt analog amplifiers (AA Series)
• Backup tone generator and amplifier option
FLASHSCAN® INTELLIGENT FEATURES
• Polls up to 318 devices on each loop in less than two seconds
• Activates up to 159 outputs in less than five seconds
• Fully digital, high-precision protocol (U.S. Patent 5,539,389)
• Manual sensitivity adjustment — up to nine levels
• Pre-alarm intelligent sensing — up to nine levels
• Sensitivity levels:
– Photo: 0.5 to 2.35%/foot obscuration
– High-Sensitivity Photoelectric (VIEW®): Open Air Protection (0.5% - 2.0%/ft. obscuration), Special Applications (0.02%- 0.5%/ft. obscuration)
– Multi-Criteria Detector: Open Air Protection (2.52-3.89%/ft.
obscuration), Special Applications (1.13-2.52%/ft. obscuration)
– Acclimate® Plus: 0.5 to 4.0%/foot obscuration
• Drift compensation (U.S. Patent 5,764,142)
• Multi-detector algorithm involves nearby detectors in alarm deci-sion (U.S. Patent 5,627,515)
• Automatic detector sensitivity testing (NFPA-72 compliant)
• Maintenance alert (two levels)
• Self-optimizing pre-alarm
• Programmable activation of sounder/relay bases during alarm or pre-alarm
FSV-951 SERIES VIEW® (VERY INTELLIGENT EARLY WARNING)
HIGH-SENSITIVITY SMOKE DETECTOR
• Advanced intelligent sensing algorithms differentiate between smoke and non-smoke signals
• Addressable operation pinpoints the fire location
• Ivory models (-IV) support CLIP mode as well as FlashScan
• Retrofit models (-R) available, backwards compatible for use with older panels
FCO-951(A)/-IV ADVANCED MULTI-CRITERIA FIRE/CO DETECTOR
• Detects all four major elements of a fire (smoke, heat, CO, and flame)
• 135°F (57.2°C) fixed-temperature heat detector
• Transmits an alarm signal due to heat
• Separate signal for life-safety CO detection
• Optional addressable sounder base for Temp-3 (fire) or Temp-4
(CO) tone
• Automatic drift compensation of smoke sensor and CO cell
• High nuisance-alarm immunity
FPTI-951 INTELLIGENT MULTI-CRITERIA DETECTOR
• Combined Photoelectric Thermal and Infrared Sensor
• UL 268 7th Edition and UL 521 Listed
• Microprocessor-based technology; combination photo, thermal, and infrared technology
FPC-951(A) PHOTOELECTRIC/CO SENSOR
• Combined photoelectric and carbon monoxide sensor
FSCO-951(A) INTELLIGENT CO SENSOR
• Carbon monoxide sensor
FS-OSI-RI(A) ADDRESSABLE INTELLIGENT SINGLE-ENDED BEAM
SMOKE DETECTOR
• Intelligent addressable reflector-type linear optical beam smoke detector
• Fast, easy, and intuitive beam alignment indicated by directional LED arrows
• Long range coverage of 16-328 ft (5-100 m) is standard; no sepa-rate long-range kit required
INTELLIGENT VESDA® DETECTORS
• Intelligent aspiration smoke detectors connect directly to the panel’s SLC loop:
– VEA-040-A00-NTF, VEA-040-A10-NTF
– VEP-A00-P-NTF, VEP-A10-P-NTF, VEP-A00-1P-NTF
– VEU-A00-NTF, VEU-A10-NTF
• Models offer LED display, LCD display, or both
• Coverage options for spaces up to 69,965 square feet
SELF-TEST SERIES DETECTORS
• Intelligent addressable detectors able to perform maintenance tests of smoke and heat detection without using canned smoke or heat guns
– FSP-951-SELFT
– FSP-951T-SELFT
– FST-951-SELFT
• First self-testing detectors approved by UL
• Simultaneously test multiple loops and panels for photo, heat, and photo/heat detection
FlashScan® Exclusive World-Leading Detector Protocol At the heart of the NOTIFIER INSPIRE™ N16e/x panel series is a set of detection devices and device protocol — FlashScan (U.S. Pat-ent 5,539,389). FlashScan is an all-digital protocol that gives superior precision and high noise immunity.
This protocol enables quick identification of an active input device, as well as activation of many output devices in a fraction of the time required by competitive protocols. The high speed also gives N16
DN-62116:A • 02/19/2021 — Page 3 of 7 the largest device per loop capacity in the industry – 318 points – yet every input and output device is sampled in less than two seconds.
The microprocessor-based FlashScan detectors have bicolor LEDs that can be coded to provide diagnostic information.
NOTIFIER INSPIRE Intelligent Sensing N16e/x has a set of software algorithms that provide industry-lead-ing smoke detection capability. These complex algorithms process many calculations on each reading of each detector, and are made possible by the high-speed microcomputer used by the N16e/x.
Drift Compensation and Smoothing. Drift compensation allows the detector to retain its original ability to detect actual smoke, and resist false alarms, even as dirt accumulates. It reduces mainte-nance requirements by allowing the system to automatically perform the periodic sensitivity measurements required by NFPA 72.
Smoothing filters are also provided by software to remove transient noise signals, usually caused by electrical interference.
Maintenance Warnings. When the drift compensation performed for a detector reaches a certain level, the performance of the detec-tor may be compromised, and special warnings are given. There are three warning levels: (1) Low Chamber value; (2) Maintenance Alert, indicative of dust accumulation that is near but below the allowed limit; (3) Maintenance Urgent, indicative of dust accumulation above the allowed limit.
Sensitivity Adjust. Nine sensitivity levels are provided for alarm detection. These levels can be set manually, or can change automat-ically between day and night. Nine levels of pre-alarm sensitivity can also be selected, based on predetermined levels of alarm. Pre-alarm operation can be latching or self-restoring, and can be used to acti-vate special control functions.
Self-Optimizing Pre-Alarm. Each detector may be set for “Self- Optimizing” pre-alarm. In this special mode, the detector “learns” its normal environment, measuring the peak analog readings over a long period of time, and setting the pre-alarm level just above these normal peaks.
Cooperating Multi-Detector Sensing. A patented feature of NOTIFIER INSPIRE Intelligent Sensing is the ability of a smoke sen-sor to consider readings from nearby sensors in making alarm or pre-alarm decisions. Without statistical sacrifice in the ability to resist false alarms, it allows a sensor to increase its sensitivity to actual smoke by a factor of almost two to one.
Field Programming Options Autoprogram is a timesaving feature. The FACP “learns” what devices are physically connected and automatically loads them in the program with default values for all parameters. Requiring less than one minute to run, this routine allows the user to have almost immediate fire protection in a new installation, even if only a portion of the detectors are installed.
VeriFire® Tools is an offline programming and test utility that can greatly reduce installation programming time, and increase confi-dence in the site-specific software. It is Windows® based and provides technologically advanced capabilities to aid the installer.
The installer may create the entire program for the N16 in the com-fort of the office, test it, store a backup file, then bring it to the site and download from a laptop into the panel (Version 11.2 and higher).
Product Line Information
• “Configuration Guidelines” on page 3
• “Main System Components” on page 3
• “Networking Options” on page 3
• “Auxiliary Power Supplies And Batteries” on page 4
• “Audio Options” on page 4
• “Compatible Devices, EIA-232 Ports” on page 4
• “Compatible Intelligent Devices” on page 4
• “Enclosures, Chassis, And Dress Plates” on page 5
• “Backboxes” on page 5
• “CLSS Gateway and Licenseable Features” on page 6
CONFIGURATION GUIDELINES
Stand-alone and network systems require a main display. The main display must be either NCD, ONYXWorks or one panel in the net-work with Network Display mode enabled.
MAIN SYSTEM COMPONENTS
CPU-N16LD: N16x with display. Intelligent fire alarm with one SLC loop, 10" touchscreen display, 4 NACs, and power supply; chassis mounted for use in a CAB-5 Series cabinet.
CPU-N16LND: N16x without display, for use as network node. Intel-ligent fire alarm with one SLC loop, 4 NACs, and power supply;
chassis mounted for use in a CAB-5 Series cabinet.
CPU-16-RTO: N16x with display for use in retrofit cabinets. Intelli-gent fire alarm with one SLC loop, 10" touchscreen display, 4 NACs, and power supply; chassis mounted for use in a CAB-4 Series cabinet.
N16E: Intelligent fire alarm panel with one SLC loop, 10" touch-screen display, 4 NACs, and power supply in a black enclosure.
N16E-R: Intelligent fire alarm panel with one SLC loop, 10" touch-screen display, 4 NACs, and power supply in a red enclosure.
SLM-318: Signaling Line Module provides a Signaling Line Circuit of 159 addressable points. Add SLM-318 units to expand SLC capabil-ity. See DN-62115.
NETWORKING OPTIONS
NCD: Network Control Display. On network systems (two or more networked fire panel nodes), one network display is required for every system (either NCD, ONYXWorks, or N16 with Network Dis-play mode enabled). On network systems, the NCD connects (and requires) a standard Network Communication module or High- Speed Network Communication Module. See DN-60974.
NCM-W, NCM-F: Standard Network Communications Modules. Wire and multi-mode fiber versions available. See DN-6861.
HS-NCM-W(-2), HS-NCM-MF, HS-NCM-SF, HS-NCM-WMF(-2),
HS-NCM-WSF(-2), HS-NCM-MFSF: High-speed Network Commu-nications Modules that can connect to two nodes. Wire, single-mode fiber, multi-mode fiber, and media conversion models are available.
See DN-60454.
RPT-W, RPT-F, RPT-WF: Standard-network repeater board with wire connection (RPT-W), multi-mode fiber connection (RPT-F), or allow-ing a change in media type between wire and fiber (RPT-WF). Not used with high-speed networks. See DN-6971.
ONYXWorks: UL-listed graphics PC workstation, ONYXWorks GUI software, and computer hardware. See DN-7048 for specific part numbers.
NFN-GW-EM-3: NFN Gateway, embedded. (Replaces NFN-GW- EM.) See DN-60499.
CAP-GW: Common Alerting Protocol Gateway. See DN-60756.
VESDA-HLI-GW: VESDAnet high-level interface gateway. See DN- 60753.
Mikemeier arrow
Page 4 of 7 — DN-62116:A • 02/19/2021
LEDSIGN-GW: UL-listed sign gateway. Interfaces with classic and high-speed NOTI•FIRE•NET networks through the NFN Gateway.
See DN-60679.
OAX2-24V: UL-listed LED sign, used with LEDSIGN-GW. See DN- 60679.
AUXILIARY POWER SUPPLIES AND BATTERIES
PMB-AUX: Auxiliary power supply, 6 amps, universal AC input, 4 NACs and 2 Auxiliary outputs, chassis-mounted for use in a CAB-5 Series cabinet. Charges 7-100AH batteries. See DN-62116.
PMB-AUX-RTO: Auxiliary power supply, 6 amps, universal AC input, 4 NACs and 2 Auxiliary outputs, chassis-mounted for use in a CAB-4 Series cabinet. Charges 7-100AH batteries. See DN-62116.
PSE-6/10: PowerStrike™ Remote 6A/10A power supply with battery charger. See DN-61092.
BAT Series: Sealed lead-acid batteries listed for fire-protective ser-vice. (Required.) See DN-6933.
AUDIO OPTIONS
NOTE: See “Enclosures, Chassis, And Dress Plates” on page 5 for mounting hardware.
DVC-EM: Digital Voice Command, digital audio processor with mes-sage storage for up to 32 minutes of standard quality (4 minutes at high quality) digital audio. See DN-7045.
DVC-RPU: Digital Voice Command Remote Paging Unit for use with DVC-EM. Includes the keypad/display. See DN-60726.
DS-DB: Digital Series Distribution Board, provides bulk amplification capabilities to the DVC-EM while retaining digital audio distribution capabilities. Can be configured with up to four DS-AMPs, supplying high-level risers spread throughout an installation. See DN-60565.
DVC-KD: DVC-EM keypad for local annunciation and controls; sta-tus LEDs and 24 user-programmable buttons. See DN-7045.
DS-AMP/E: 125W, 25 VRMS, or 100W, 70VRMS. 70VRMS requires DS-XF70V step-up transformer. Digital Series Amplifier, part of the DS-DB system. See DN-60663.
DS-RFM, DS-FM, DS-SFM: Fiber conversion modules for DVC-EM, DS-DB distribution board, and DAA2/DAX Series amplifiers. See
DN-60633.
DAA2-5025(E): 50W, 25 Vrms Digital Audio Amplifier assembly with power supply; includes chassis. See DN-60556.
DAA2-5070(E): 50W, 70.7 Vrms Digital Audio Amplifier assembly with power supply; includes chassis. See DN-60556.
DAA2-7525(E): 75W, 25 Vrms digital audio amplifier assembly with power supply; includes chassis. See DN-60556.
DAX-3525(E): 35W, 25 Vrms Digital Audio Amplifier assembly with power supply, includes chassis. See DN-60561.
DAX-3570(E): 35W, 70.7 Vrms Digital Audio Amplifier assembly with power supply, includes chassis. See DN-60561.
DAX-5025(E): 50W, 25 Vrms Digital Audio Amplifier assembly with power supply, includes chassis. See DN-60561.
DAX-5070(E): 50W, 70.7 Vrms Digital Audio Amplifier assembly with power supply, includes chassis. See DN-60561.
TELH-1: Firefighter’s Telephone Handset for use with the DVC-EM when mounted in the CA-2 chassis. See DN-7045.
CMIC-1: Microphone used with DVC/DVC-EM. Included with CA-2 chassis assembly. See DN-7045.
RM-1/RM-1SA: Remote microphone assemblies, mount on ADP-4 (RM-1) dress panel or CAB-RM/-RMR (RM-1SA) stand-alone cabi-nets. See DN-6728.
DAA Series Digital Audio Amplifiers: Legacy DAA Series amplifi-ers are compatible with DVC systems running SR4.0. For specific information on DAA-50 series amplifiers, refer to DN-7046. For infor-mation on DAA-7525 Series, refer to DN-60257.
DAX-3525(E): 35W, 25 Vrms Digital Audio Amplifier assembly with power supply, includes chassis. See DN-60561.
DAX-3570(E): 35W, 70.7 Vrms Digital Audio Amplifier assembly with power supply, includes chassis. See DN-60561.
DAX-5025(E): 50W, 25 Vrms Digital Audio Amplifier assembly with power supply, includes chassis. See DN-60561.
DAX-5070(E): 50W, 70.7 Vrms Digital Audio Amplifier assembly with power supply, includes chassis. See DN-60561.
COMPATIBLE DEVICES, EIA-232 PORTS
PRN-7: 80-column printer. See DN-60897
VS4095/5: Printer, 40-column, 24 V. Order from Keltron, Inc. See
DN-3260.
COMPATIBLE DEVICES, AIO BUS
ACM-30: Fully-customizable annunciator; Independently-configured buttons with up to 60 points of annunciation. LEDs can be pro-grammed to activate in red, green, yellow, white, amber, blue, cyan or purple. Up to 40 annunciators per FACP. See DN-62114.
COMPATIBLE INTELLIGENT DEVICES
FSP-951-SELFT: White, low-profile intelligent self-testing photoelec-tric sensor, FlashScan only. See DN-62046.
FSP-951T-SELFT: White, same as FSP-951 but includes a built-in 135°F (57°C) fixed-temperature thermal device, FlashScan only.
See DN-62046.
FST-951-SELFT: White, low-profile intelligent self-testing 135°F fixed thermal sensor, FlashScan only. See DN-62046
FCO-951/-IV FlashScan, Addressable intelligent multi-criteria smoke sensors, photo, carbon monoxide, fixed temperature heat detector, and infra-red (IR). See DN-61097.
FPC-951. FlashScan, Combined photoelectric and carbon monoxide sensor. See DN-62023.
FWSG Wireless SWIFT Gateway: Addressable gateway supports wireless SLC devices. See DN-60820
FSCO-951. FlashScan, Addressable carbon monoxide sensor. See
DN-62018.
FPTI-951, FPTI-951-IV: Addressable intelligent multi-criteria photo-electric, thermal, and IR sensors. See DN-62004.
FS-OSI-RI: Addressable intelligent single-ended beam smoke detector. See DN-61042.
FSP-951: White, low-profile intelligent photoelectric sensor, FlashScan only. See DN-60977.
FSP-951-IV: Ivory, low-profile intelligent photoelectric sensor.
FSP-951T: White, same as FSP-951 but includes a built-in 135°F (57°C) fixed-temperature thermal device. FlashScan only. See DN- 60977.
FSP-951T-IV: Ivory, same as FSP-951T but includes a built-in 135°F (57°C) fixed-temperature thermal device.
FSP-951R: White, low-profile intelligent photoelectric sensor, remote test capable. For use with DNR/DNRW. FlashScan only. See DN- 60977.
FSP-951R-IV: Ivory, low-profile intelligent photoelectric sensor, remote test capable. FlashScan only.
FST-951: White, low-profile intelligent 135°F fixed thermal sensor, FlashScan only. Must be mounted to one of the bases listed below.
See DN-60975.
FST-951-IV: Ivory, low-profile intelligent 135°F fixed thermal sensor, FlashScan and CLIP. Must be mounted to one of the bases listed below.
FST-951R: White, low-profile intelligent rate-of-rise thermal sensor, FlashScan only. Must be mounted to one of the bases listed below.
FSP-951R-IV: Ivory, low-profile intelligent photoelectric sensor, remote test capable. FlashScan only.
DN-62116:A • 02/19/2021 — Page 5 of 7
FST-951H: White, low-profile intelligent 190°F fixed thermal sensor, FlashScan only. Must be mounted to one of the bases listed below.
FST-951H-IV: Ivory, low-profile intelligent 190°F thermal sensor, FlashScan and CLIP. Must be mounted to one of the bases listed below.
FSV-951, FSV-951R: White, intelligent high-sensitivity photoelectric smoke detector. See DN-61053.
FSV-951-IV, FSV-951R-IV: Ivory, intelligent high-sensitivity photo-electric smoke detector.
VEP-A00-P-NTF: Intelligent aspiration smoke detector with LED dis-play, 4 pipes, covers up to 21,520 square feet. See DN-61029.
VEP-A10-P-NTF: Intelligent aspiration smoke detector with LED and LCD display, 4 pipes, covers up to 21,520 square feet. See DN- 61029.
VEP-A00-1P-NTF: Intelligent aspiration smoke detector with LED display, single pipe, covers up to 10,760 square feet. See DN-61029.
VEU-A00-NTF: Intelligent aspiration smoke detector with LED dis-play, 4 pipes, covers up to 69,965 square feet. See DN-61034.
VEU-A10-NTF: Intelligent aspiration smoke detector with LED and LCD display, 4 pipes, covers up to 69,965 square feet. See DN- 61034.
VEA-040-A00-NTF: Intelligent aspiration with LED display, 40 point-addressable detection points. Covers 36,000 square feet. See DN- 61036.
VEA-040-A10-NTF: Intelligent aspiration with LED and LCD display, 40 point-addressable detection points. Covers 36,000 square feet.
See DN-61036.
DNR: InnovairFlex low-flow non-relay duct-detector housing. (Order FSP-951R separately.) See DN-60429.
DNRW: Same as above with NEMA-4 rating, watertight. See DN- 60429.
B224RB-WH: White, low-profile relay base. See DN-60054.
B224RB-IV: Ivory, plug-in System Sensor relay base.
B224BI-WH: White, isolator base for low-profile detectors. See DN- 60054.
B224BI-IV: Ivory isolator detector base.
B300-6: White, standard flanged low-profile mounting base. (For 10-pack order B300-6-BP.)
B300-6-IV: Ivory, standard flanged low-profile mounting base.
B501-WHITE: European-style, 4" (10.16 cm) base. (For 10-pack order B501-WHITE-BP.) See DN-60054.
B501-BL: Black, 4” standard European flangeless mounting base.
B501-IV: Ivory color, 4” standard European flangeless mounting base.
B200S-WH: White, intelligent programmable sounder base, capable of producing a variety of tone patterns including ANSI Temporal 3.
Compatible with synchronization protocol. See DN-60054.
B200S-IV: Ivory intelligent, programmable sounder base.
B200S-LF-WH: White, low-frequency version of B200S. See DN- 60054.
B200S-LF-IV: Ivory, low-frequency version of B200S.
B200SR-WH: White intelligent programmable sounder base, Tem-poral 3 or Continuous tone. For retrofit installations replacing B501BH series bases. See DN-60054.
B200SR-IV: Ivory intelligent programmable sounder base, Temporal 3 or Continuous tone. For retrofit installations replacing B501BH series bases.
B200SR-LF-WH: White, low-frequency version of B200SR. See DN- 60054.
B200SR-LF-IV: Ivory, low-frequency version of B200SR.
FMM-1: FlashScan monitor module. See DN-6720.
FDM-1: FlashScan dual monitor module. See DN-6720.
FZM-1: FlashScan two-wire detector monitor module. See DN-6720.
FMM-101: FlashScan miniature monitor module. See DN-6720.
FTM-1: Firephone Telephone Module connects a remote firefighter telephone to a centralized telephone console. Reports status to panel. Wiring to jacks and handsets is supervised. See DN-6989.
FCM-1: FlashScan control module. See DN-6724.
FCM-1-REL: FlashScan releasing control module. See DN-60390.
FRM-1: FlashScan relay module. See DN-6724.
FDRM-1: FlashScan dual monitor/dual relay module. See DN-60709.
NBG-12LX: Manual pull station, addressable. See DN-6726.
ISO-X: Isolator module. See DN-2243.
ISO-6: Six fault isolator module. See DN-60844.
XP6-C: FlashScan six-circuit supervised control module. See DN- 6924.
XP6-MA: FlashScan six-zone interface module; connects intelligent alarm system to two-wire conventional detection zone. See DN- 6925.
XP6-R: FlashScan six-relay (Form-C) control module. See DN-6926.
XP10-M: FlashScan ten-input monitor module. See DN-6923.
ENCLOSURES, CHASSIS, AND DRESS PLATES
CAB-5 Series Enclosure: CPU-N16LD and CPU-N16LND mount in a standard CAB-5 Series enclosure (available in 5 sizes, “A” through “E”). Backbox and door ordered separately; requires BP-5 battery plate. See DN-62113.
CA-2: Chassis for FACP control panel when DVC-EM is used with firefighter's telephone. Mounts in the top two rows of a CAB-4 series enclosure.
DP-T2A: Dress panel for CAB-5 Series, mounts 10" display and two ACM-30 annunciators.
DP-T2A-CB4: Dress panel for CAB-4 Series, mounts 10" display and two ACM-30 annunciators.
DP-4A: Dress panel for CAB-5 Series, mounts four ACM-30 annunciators.
DP-BLN: Blank dress panel. Provides dead-front panel for unused tiers in a CAB-5 Series enclosure.
BP-5: Battery plate, required.
NFS-LBB: Battery Box. The NFS-LBB is used to mount up to two 55 AH batteries. Dimensions: Box: 24" (610 mm) wide x 14" (356 mm) high x 7.75" (197 mm) deep. Door: 24.125" (613 mm) wide x 14.25" (362 mm) high; door adds 0.0625" (approx. 1.6 mm) to depth.
CHS-CGW: Chassis for mounting the CGW-MBB in a CAB-4 or CAB-5 Series enclosure.
CHS-ADP: Adapter plate for mounting a CAB-4 chassis in a CAB-5 Series enclosure.
BACKBOXES
BB-100: Backbox for batteries and power supplies. The BB-100 mounts up to two 100 AH batteries and power supply, if needed. 30" (76.20 cm) wide x 25" (63.50 cm) high x 7.5" (19.05 cm) deep; depth includes door.
BB-200: Backbox for batteries and power supplies. Holds up to four 100 AH batteries (200 AH capacity) and power supply. 30" (76.20
cm) wide x 36" (91.44 cm) high x 7.5" (19.05 cm) deep; depth includes door.
ABB-1: Backbox for ACM-30 annunciator, 1 position.
ABB-2: Backbox for ACM-30 annunciator, 2 position.
NBB-2: Annunciator backbox, 2 position.
Page 6 of 7 — DN-62116:A • 02/19/2021
CLSS GATEWAY AND LICENSEABLE FEATURES
CGW-MBB: CLSS Gateway for Internet/cloud-based communication between the FACP and peripheral devices. See HON-62034.
HON-CGW-MBB: CLSS Gateway, pre-installed in a cabinet. See
HON-62034.
Licenseable features: Individually purchased and downloaded to a specific panel.
• N16-CAC: Custom Action Button expansion. Adds 8 custom action buttons to an N16 panel (maximum 32 buttons).
• N16-CLIP: Enables CLIP mode on an N16 panel.
• N16-GZN: General Zone expansion. Adds 250 general zones to an N16 panel (maximum 2000 zones).
• N16-LGZ: Logic Zone expansion. Adds 250 logic zones to an
N16 panel (maximum 2000 zones).
• N16-NWD: Enables Network Display Mode on an N16 panel to emulate NCD’s network display capabilities.
• N16-UZC: Universal Zone Coding, enables UZC for an N16 panel.
NOTE: For other options including compatibility with retrofit equipment, refer to the panel's installation manual, the SLC manual, and the Device Compatibility Document.
NOTIFIRE INSPIRE™ and NOTI•FIRE•NET™ are trademarks; and
Acclimate®, FlashScan®, NOTIFIER®, ONYX®, ONYXWorks®, SWIFT®, VeriFire® Tools, VESDA®, and VIEW® are all registered trademarks of
Honeywell International Inc.
©2021 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
Country of Origin: USA
NOTIFIER
12 Clintonville Road
Northford, CT 06472
203.484.7161 www.notifier.com
SPECIFICATIONS
SYSTEM CAPACITY
• Intelligent Signaling Line Circuits
– N16e ..............................................................1 expandable to 3
– N16x ............................................................1 expandable to 10
• Intelligent detectors ................................................. 159 per loop
• Addressable monitor/control modules ...................... 159 per loop
• Programmable software zones.................................... over 2000
• AIO Annunciators per N16
• Network nodes............................................up to 200 per network
ELECTRICAL SPECIFICATIONS
Primary Input Power:
PMB-AUX(-RTO): 120VAC 50/60 Hz 2.5A, 240VAC 50/60 Hz, 1.25A
24VDC aux outputs: Power-limited (Class 2) 24V @ 1.5A each, Special Applications Aux Power, Aux 1 Class A/B, Aux 2 Class B only.
Current draw (Standby/Alarm):
– TB1 SLC Connection 24VDC
– Alarm 210mA
– Class B/A/X
– Standby 159mA
– Power Limited
– Supervised
– 50 ohms Maximum
Battery charger range: 7 AH – 100 AH. Use separate cabinet for batteries over 26 AH.
Charging current: 1A, 2A, and 4.25A
Float Rate: 27.6 V.
PHYSICAL SPECIFICATIONS
N16e Shipping Weight: 35 lb
N16e Backbox dimensions: 20.31" H x 24.00" W x 5.5" D (51.6 cm H x 61 cm D x 14cm D)
Temperature and Humidity Ranges: This system meets NFPA requirements for operation at 0 – 49°C/32 – 120°F and at a relative humidity 93% ± 2% RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 – 27°C/60 – 80°F.
AGENCY LISTINGS AND APPROVALS
These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process.
Consult NOTIFIER for latest listing status.
• UL Listed: S635.
STANDARDS
The N16 Series complies with the following UL Standards and NFPA 72 Fire Alarm Systems requirements:
• UL 864, 10th edition (Fire).
• UL 1076 (Burglary).
• UL 2017 (General-Purpose Signaling Devices and Systems).
• NFPA 72 Local (Automatic, Manual, Waterflow, and Sprinkler
Supervisory).
• NFPA 72 Central Station (Automatic, Manual, Waterflow, and
Sprinkler Supervisory, requires CGW-MBB or HON-CGW-MBB.)
• NFPA 72 Remote Station (Automatic, Manual, Waterflow, and
Sprinkler Supervisory) (requires UL 10th edition listed DACT).
• NFPA 72 Proprietary (Automatic, Manual, Waterflow, and Sprin-kler Supervisory).
• NFPA 72 Emergency Voice/Alarm (requires DVC/DAA/DAA-2)
• NFPA 72 PB (Performance Based Technologies) (Requires CGW-MBB or HON-CGW-MBB).
NOTE: Install in accordance with the UL and NFPA standards specified in panel documentation.
�F2 - Quick disconnect tabs, 0.250” x 0.032”
- Mate with AMP. INC FASTON “250” series �NB2: Tin plated brass post with 5mm nut & bolt connectors �T12 - Threaded insert with 5mm stud
Sealed Rechargeable
MODEL PS-12260 NB
12 Volt 26.0 Amp. Hr.
Battery www.power-sonic.com
BA
TT
E
RY
MUST BE REC
YC
LED
Pb
NONSPILLABLE
MH20845
L
HT H
W
4.5
7.95
6.35
3.4
0.8
12mm
F2
T12
NB
6mm
M5
Tolerances are +/- 0.04 in. (+/- 1mm) and +/- 0.08 in. (+/- 2mm) for height dimensions. All data subject to change without notice.
Physical Dimensions: in (mm)
Features
� �Absorbent Glass Mat (AGM) technology for superior performance
� �Valve regulated, spill proof construction allows safe operation in any position
� �Power/volume ratio yielding unrivaled energy density
Rugged impact resistant ABS case and cover (UL94-HB)
� �Approved for transport by air. D.O.T., I.A.T.A., F.A.A. and C.A.B. certified
U.L. recognized under file number MH 20845
Performance Specifications
Nominal Voltage......................................................................... 12 volts (6 cells)
Nominal Capacity
20-hr. (1.3A to 10.50 volts) ............................................................. 26.0 AH
10-hr. (2.4A to 10.50 volts) .............................................................. 24.0 AH
5-hr. (4.4A to 10.20 volts) ............................................................. 22.0 AH
1-hr. (16.1A to 9.00 volts) .............................................................. 16.1 AH
15-min. (51A to 9.00 volts).................................................................. 12.8 AH
Approximate Weight ........................................................... 17.00 lbs. (7.71 kg)
Energy Density (20-hr. rate) ................................. 1.39 W-h/in3 (84.64 W-h/l)
Specific Energy (20-hr. rate) .............................. 18.35 W-h/lb (40.46 W-h/kg)
Internal Resistance (approx.) ....................................................... 14 milliohms
Max Discharge Current (7 Min.) ................................................ 78.0 amperes
Max Short-Duration Discharge Current (10 Sec.)................. 260.0 amperes
Shelf Life (% of nominal capacity at 68°F (20°C))
1 Month ...................................................................................................... 97%
3 Months...................................................................................................... 91%
6 Months ..................................................................................................... 83%
Operating Temperature Range
Charge... ........................................................... -4°F (-20°C) to 122°F (50°C)
Discharge........................................................ -40°F (-40°C) to 140°F (60°C)
Case....................................................................................................... ABS Plastic
Power-Sonic Chargers.....PSC-122000A, 124000A, 122000A-C, 124000A-C
PS-12260
www.power-sonic.comTo ensure safe and efficient operation always refer to the latest edition of our Technical Manual, as published on our website.
All data subject to change without notice.
Terminals (mm)
12 Volt 26.0 AH
L: 6.56 (167) W: 6.97 (177) H: 4.92 (125) HT: 4.92 (125)
Charging Cycle Applications: Limit initial current to 7.8A. Charge until battery voltage (under charge) reaches 14.4 to 14.7 volts at 68°F (20°C). Hold at 14.4 to 14.7 volts until current drops to under 260mA. Battery is fully charged under these conditions, and charger should be disconnected or switched to “float” voltage.
“Float” or “Stand-By” Service: Hold battery across constant voltage source of
13.5 to 13.8 volts continuously. When held at this voltage, the battery will seek its own current level and maintain itself in a fully charged condition.
Note: Due to the self-discharge characteristics of this type of battery, it is imperative that they be charged within 6 months of storage, otherwise permanent loss of capacity might occur as a result of sulfation.
Chargers Power-Sonic offers a wide range of chargers suitable for batteries up to 100AH.
Please refer to the Charger Selection Guide in our specification sheets for “C-Series Switch Mode Chargers” and “Transformer Type A and F Series”. Please contact our Technical department for advice if you have difficulty in locating suitable models.
C ap ac ity
R et en tio n R at io
Standing Period (Months)
0 2 4 6 8 10 12 14 16 18 20
40oC (104oF)
30oC (86oF)
20oC (68oF)
5oC (41oF)
Charging is not necessary unless 100% of capacity is required.
Charging before use is necessary to help recover full capacity.
Charge may fail to restore full capacity. Do not let batteries reach this state.
0 1 2 3 4
Ambient Temperature 20˚C (68˚F)
Float Charging Voltage
2.25 - 2.30 V/Cell
R et en tio n C ap ac ity
Years
0 200 400 600 800 1000 1200
Number of Cycles
1. Discharge Current 0.2C (Final Voltage 1.7V/Cell)
2. Charge Current: 0.1C
3. Ambient Temperature: 20oC to 25oC (68oF to 77oF)R et en tio n
C ap ac ity
Discharge Depth 30%
Discharge Depth 100%
Discharge Depth 50%
Discharge Characteristics
Discharge Time vs. Discharge Current
Shelf Life & Storage
Life Characteristics in Stand-By Use
Life Characteristics in Cyclic Use
PS-12260 12 Volt 26.0 AH
Further Information Please refer to our website www.power-sonic.com for a complete range of useful downloads, such as product catalogs, material safety data sheets (MSDS), ISO certification, etc..
13.0
12.0
11.0
10.0
9.0
8.0
14.0
Te rm in al
V ol ta ge
(V
Ambient Temperature 20oC (68oF)
1.2 2.4 6 12 24 36 48 1 2 4 6 8 10 20 4 0
Discharge Time
Final Voltage min h
1.302.6 5.2
1.30 2.6 5.2 13 26 52 Discharge Current (A)
D is ch ar ge T im e
40oC (104oF) 20oC (68oF) 0oC (32oF) m in h
10.2V
9.6V
9.0V
8.1V
Final Voltage 10.5V
CORPORATE OFFICE • 7550 Panasonic Way • San Diego, CA 92154 • USA • Tel: +1-619-661-2020 • Fax: +1-619-661-3650
CUSTOMER SERVICE
Tel: +1-619-661-2030 Fax: +1-619-661-3648 customer-service@power-sonic.com
INTERNATIONAL SALES
Tel: +1-650-364-5001 Fax: +1-650-366-3662 international-sales@power-sonic.com
DOMESTIC SALES
Tel: +1-619-661-2020 Fax: +1-619-661-3650 national-sales@power-sonic.com
TECHNICAL SUPPORT
Tel: +1-619-661-2020 Fax: +1-619-661-3648 support@power-sonic.com
Contact Information www.power-sonic.com
0812 1M
© 2012. Power-Sonic Corporation. All rights reserved. All trademarks are the property of their respective owners. 9
DN-6861:C • 10/04/2010 — Page 1 of 2
NCM-W, NCM-F
ONYX® Series Network Communications Modules
Network Systems
DN-6861:C • A0-260
General The Network Communications Module (NCM) provides NOTIFIER Intelligent Fire Alarm Control Panels, and NCA and NCA-2 Network Control Annunciators with a means to connect to NOTI•FIRE•NET™. Two types of NCM are available:
NCM-W for connecting nodes with twisted-pair wire, and NCM-F for connecting nodes with fiber-optic cable.
NOTE: Do not mix NCM and High Speed (HS) NCM on the same system.
NCM-W Features
• Supports twisted-pair wire medium.
• NFPA Style 4 (Class B)…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .