This document is a Maintenance and Operations Facility Standards guide issued by the Central Arkansas Veterans Health Care System (CAVHS) in April 2020. It establishes minimum product specifications and installation requirements for contractors undertaking maintenance and operations projects at the facility located in North Little Rock, Arkansas.
The standards specify mandatory product selections across multiple categories to ensure facility standardization and staff familiarity. Building products include 2x2 Armstrong Cortega 770 ceiling tiles, Best Access Systems locks and hardware, Corbin Russwin door closers, solid material countertops without wood substrate, stainless steel corner guards, solid wood interior doors with Ceco metal grain doors for fire-rated applications, and minimum 6-mil vinyl roofing. Electrical requirements mandate Schneider Electric (SQ D) distribution equipment and breakers, Cummins transfer switches, copper conductors throughout, specific conduit color-coding by system type (blue for building management, red for fire alarm, purple for security, green for nurse call, white for paging, orange for communications), and detailed labeling protocols. Lighting specifications require LED fixtures from Lithonia Acuity with specific model compatibility, multi-voltage ballasts, and occupancy sensors. Plumbing mandates Sloan solar-powered fixtures and flushometers with Watts backflow preventers. HVAC requirements specify Trane equipment with direct-drive fans, ABB VFD drives, Siemens controls, and prohibit flex duct longer than three feet. Special systems include Edwards EST-3 compatible fire alarm equipment, Westcom Novis Connect nurse call systems, and Identiv Velocity access control compatible with current HSPD-12 requirements. The standards require contractors to submit all substitution requests for approval by the Contracting Officer and shop personnel, with contractors bearing all costs associated with approved substitutions including design, installation, training, and inventory replacement. Appendix A provides detailed preferred manufacturer specifications for electrical equipment, lighting, fixtures, and controls to ensure compatibility with existing facility systems.
View the file
Other files
Show all 28
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MAINTENANCE AND
OPERATIONS STANDARDS
April 2020
Central Arkansas Veterans Health Care System 2200 Fort Roots Drive, Bldg. #1
North Little Rock, AR 72114
CENTRAL ARKANSAS VETERANS HEALTH CARE SYSTEM
MAINTENANCE AND OPERATIONS FACILITY STANDARDS
MAINTENANCE AND OPERATIONS Page 1
Contents
PART 1: GENERAL
1.1 DESCRIPTION
PART 2: PRODUCTS
2.1 BUILDING Products
2.2 PLUMBING
2.3 HEATING, VENTILATION & AIR CONDITIONING
2.4 ELECTRICAL
2.5 SPECIAL SYSTEMS
2.6 COMMUNICATIONS AND DATA
2.7 SIGNS AND WAYFINDING
PART 3: EXECUTION
3.1 SPARES
Appendix A: Preferred Items
April 2020
MAINTENANCE AND OPERATIONS Page 2
PART 1: GENERAL
1.1 DESCRIPTION
A. This section specifies the engineering, furnishing and installation of equipment, utilities, appliances and any other related work requiring maintenance and upkeep by Maintenance and Operations (M&O) at the Central Arkansas Veterans Health Care System.
B. This is not a complete listing; however, listed items have been reoccurring issues that need to be corrected in future projects by Contractors. Items listed in the singular apply to entire facility except where noted.
C. Appendix A provides a list of facility preferred items. See 1.1.D for Substitution requirements.
D. Substitutions are subject to COR, and shop personnel approval. Substitutions and deviations must be specifically noted and addressed. Substitutions shall be based upon the cost to the item indicated in Appendix A or if not listed here accordingly per the basis of design. Substitution cost to the facility is much greater to the facility if a cheaper or alternate product is selected and total costs will require consideration if substitutions are to be considered, to include the potential for replacing any existing products throughout the facility to ensure standardization and familiarity for the facility is not compromised due to the substitution. Any costs associated with the substitution shall be the contractor’s responsibility to include all design, installation, training and replacement of existing spares and stock.
E. Items listed and detailed here are to be considered as in addition to the specifications. When this document is found to be in contradiction to the specification or drawings, the contractor shall be held to the strictest requirement and shall be required to clarify through the RFI process prior to proceeding.
PART 2: PRODUCTS
2.1 BUILDING Products
A. CEILING TILES – ALL PROJECTS WILL HAVE 2 X 2 ARMSTRONG CORTEGA 770
TILES (NO 2 X 4 TILES)
B. LOCKS AND HARDWARE – ALL LOCKS AND HARDWARE WILL BE BEST ACCESS
SYSTEMS (CAHVS CURRENTLY USES BAST THROUGHOUT THE FACILITY)
C. DOOR CLOSERS – CORBIN RUSSWIN DC 3200, 6210 SERIES HANDICAPPED
D. COUNTERTOPS – ALL COUNTERTOPS WILL BE SOLID MATERIAL WITH NO WOOD
SUBSTRATE OR FORMICA
E. CORNER GUARDS – ALL CORNER GUARDS WILL BE STAINLESS STEEL
F. INTERIOR DOORS – SOLID WOOD (ALL FIRE RATED DOORS WILL BE CECO METAL
GRAIN DOORS, CS5-PROVINCIAL)
April 2020
MAINTENANCE AND OPERATIONS Page 3
G. EXTERIOR DOORS – METAL GREY PRIMER FINISH (PAINT TO MATCH EXISTING
COLOR)
H. ROOFING – MINIMUM 6 MIL VINYL (NO BUILT-UP ROOFING)
I. BATHROOM PARTITIONS – ALL SOLID PLASTIC MATERIAL WITH FULL METAL
ATTACHMENT INSTALLED WITH MINIMUM ¼” TOGGLE BOLTS
J. FIRE CAULK – 3M CP 25WB+ FIRE BARRIER INTUMESCENT (RED)
K. NOTE: CONTRACTOR WILL BE REQUIRED TO SUBMIT FORM FOR FIRE WALL
PENETRATIONS PER THE SAFETY OFFICE
L. PAINT – ONLY SHERWIN WILLIAMS BASE WITH VA APPROVED COLORS
M. SHEETROCK – 5/8” BRAND “X” FIRE RATED
2.2 PLUMBING
A. For a list of preferred plumbing products, reference Appendix A: Preferred Items, section C.
2.3 HEATING, VENTILATION & AIR CONDITIONING
A. For a list of preferred items, reference Appendix A: Preferred Items, section D
2.4 ELECTRICAL
A. Cable Trays: Ladder style, Aluminum, 6” Deep, 12” wide, 6” spacing.
B. Conduit/Raceway Systems
Building Management Systems Blue Colored Conduits Fire Alarm Red Colored Conduits. All boxes and covers shall be red.
Security Systems Purple Conduits (C-Cure, cameras, card readers, etc.)
Nurse Call/Code Blue Green Conduits Couplings or Bands every
10 Feet Paging White Conduits Couplings or Bands every
10 Feet Communications Orange Couplings or Bands every 10 Feet
(When required for protection and cable tray or J-Hooks deemed unfeasible) (Computers, VOIP, fiber, etc. for IT systems not related to other systems already noted)
Table 1: Conduit color codes.
1) All conduits to be a minimum of ¾” dia.
2) All conduits shall be bonded on both ends of the raceway when required to be bonded.
3) Conduit shall not be considered an adequate EGC.
April 2020
MAINTENANCE AND OPERATIONS Page 4
4) Contractor shall complete grounding on both sides of the raceway.
5) Electrical metallic tubing (EMT) with compression type couplings and fittings (up to 53mm
(2”)) shall be used generally for concealed applications, interior partition walls and above the 8foot demarcation as noted above.
6) In wall conduit for branch circuits shall be installed vertically and stubbed out above ceiling.
No horizontal conduit shall be installed in walls for branch circuits.
7) All rough in conduit to have plaster rings and pull cords (Telecom, Data, Nurse Call, etc.)
8) No MC or AC cable allowed.
9) No Multi-Branch Circuits Allowed.
10) Junction boxes shall be installed on pre-manufactured brackets that span the back of the box from stud to stud. Erico Telescoping Screw Gun Bracket or equal.
11) Conduits shall be supported per NFPA 70.
12) All flexible metal conduit shall be steel and 1/2” dia. Or larger.
13) Use of flexible metal conduit for connections to motors and vibrating equipment shall be limited to 24 inches.
C. Conduit Labeling
1) Provide cable and conduit identification tags, on all raceways, 30’ on center and within 24” of all terminations, bends, and penetrations.
2) Labels shall identify feeder source and load served (to and from), and voltage.
3) Letter size shall be as large as practical per raceway size.
4) Tags shall be permanent, self-adhesive with clear laminate
5) Essential System Power feeders or circuit labels shall be red with white letter.
6) Normal System Power feeders or circuit labels shall be blue with white letters
7) 1000V and above shall be painted orange in color and voltage marked every 30’ on center and within 24” of termination.
8) Self-Adhesive Identification Products: Clean surfaces before application, using materials and methods recommended by manufacturer of identification device.
D. Lighting
i. External Lighting: Reference Appendix A for standard requirements.
ii. Interior lighting shall be LED as base bid. Lithonia acuity BLTR, BLTBA, GLT or similar if applicable. Lighting designer to select and present option. Reference Appendix A for standard requirements.
iii. All lighting ballast/drivers shall be multi-voltage (120-277V).
iv. Emergency lighting battery packs shall be self-test and/or self-diagnostic.
v. Lighting Controls: Lithonia Acuity n-Light, or equal and shall be compatible/interchangeable to existing facility lighting controls. All lighting shall utilize occupancy sensors and controls per energy guidelines and NFPA.
vi. All hardwired interior luminaires shall contain a disconnecting means similar to the Sta-Kon Push-In Luminaire Disconnect for compliance with NFPA 70E.
E. Oil Filled Transformer –Shall be
i. Loop Feed Option, under oil 3- two position switches, Envirotemp FR3, FE.
ii. Shall be cooper windings.
iii. Shall be equipped with external flush or surface mounted enclosure containing oil sampling port, pressure gauge, pressure relieve valve and nitrogen fill valve.
iv. Shall be equipped with Primary and secondary door IR windows.
April 2020
MAINTENANCE AND OPERATIONS Page 5
v. Contractor shall install two 4-inch conduits and 1 set of matching spare conduits on both primary and secondary sides of the transformer. Spare conduits shall be capped and labeled appropriately. Provide coordination drawings indicating stub locations.
F. Oil Filled Transformer Labeling:
i. All new transformers shall have SCCR labeling, to include any calculations.
ii. Arc Flash and Shock Hazard: Install adhesive arc flash warning labels on all equipment as required by NFPA 70E. Label shall indicate the arc hazard boundary (inches), working distance (inches), arc flash incident energy at the working distance (calories/cm2), required PPE category and description including the glove rating, voltage rating of the equipment, limited approach distance (inches), restricted approach distance (inches), prohibited approach distance (inches), equipment/buss name, date prepared, and manufacturer name and address.
IEEE Std 1584a shall apply. Contractor shall complete study prior to ordering equipment.
Equipment shall not be permitted to be energized without a new or updated label.
G. Wiring Devices: See attachment A
1) 1) All receptacles shall be duplex type hospital grade. Tamper proof hospital grade outlets shall be required in public spaces such as waiting rooms, and hallways.
2) All receptacles shall be Hubbell HBL8300IU, or approved equal, 125-volt rated, 20-amp (minimum) as required.
a. Emergency Circuits - Red
b. Normal – Ivory
c. Isolated – Orange
3) A Normal outlet should always be located within 24” of every emergency outlet. Electrical, Mechanical, and IT rooms and closets should contain an equal amount of normal and emergency circuits. Contractors to notify COR of discrepancies to this rule.
4) All toggle switches shall be specification grade, silent acting, 125/277-volt rated, 20-amp, single-pole, 3-way, or 4-way as required.
H. Wiring Devices NLR building 170: See attachment A
2) All receptacles shall be duplex type hospital grade. Tamper proof hospital grade outlets shall be required in public spaces such as waiting rooms, and hallways.
3) All receptacles in wet or damp areas shall be GFCI with self-testing.
4) Corridors shall have a dedicated outlet every 50 ft. for use by EMS. This outlet shall utilize a special plug for floor cleaners, etc. Coordinate with the electric shop for details at this time.
5) Normal Power receptacles shall be duplex type ivory in color.
6) Normal power Wall plates shall be stainless steel. Circuit identification with self-adhesive label yellow with black lettering
7) Emergency Power receptacles shall be duplex type red in color.
8) Emergency power wall plates shall be stainless steel. Circuit identification with self-adhesive label red with black lettering
9) Provide coordination drawings to ensure locations and heights are acceptable.
10) Inspection Reports: Provide polarity test of receptacles in report (reference NFPA 99).
I. Wiring devices John L. McLellan (JLM) See attachment A
1) All receptacles shall be duplex type hospital grade. Tamper proof hospital grade outlets shall be required in public spaces such as waiting rooms, and hallways.
2) All receptacles in wet or damp areas shall be GFCI with self-testing.
3) Corridors shall have a dedicated outlet every 50 ft. for use by EMS. This outlet shall utilize a special plug for floor cleaners, etc. Coordinate with the electric shop for details at this time.
April 2020
MAINTENANCE AND OPERATIONS Page 6
4) Normal Power receptacles shall be duplex type Ivory in color.
5) Normal power Wall plates shall be stainless steel. Circuit identification with self-adhesive label yellow with black lettering
6) Emergency Power receptacles shall be duplex type red in color.
7) Emergency power wall plates shall be stainless steel. Circuit identification with self-adhesive label red with black lettering
8) All toogle switches shall be specification grade, silent acting, 125/277-volt rated, 20-amp, single-pole, 3-way, or 4-way as required.
J. Power Monitoring System: Schneider Electric PME monitoring system, or compatible to existing PME monitoring system.
K. Metering: Switchgear, Switchboards and Panel boards: Schneider Electric Meters, or compatible to existing PME monitoring system. All programming, cabling, and appurtenances to be included.
L. Switchgear: Schneider Electric (SQ D), or equal, Low Voltage Switchgear fully compatible to match existing and parts inventory, copper fully rated bussing
M. Switchboards: Schneider Electric (SQ D) I-LINE or equal fully compatible to match existing and parts inventory, copper fully rated bussing
N. Panelboards: Schneider Electric (SQ D), NQ, NF, I-LINE or equal fully compatible to match existing and parts inventory, copper fully rated bussing with door in door hinged cover
i. Submit all panel schedules, including updated panel schedules in pdf and Microsoft Excel format. Coordinate with COR for existing files if available.
O. Automatic Transfer Switches: Cummins, match existing controls. Contractor shall ensure programming and installation is done in accordance with all applicable regulations and requirements, to include Joint Commission requirements.
P. Breakers: See Attachment A
1) Electronic breakers shall be expected to achieve coordination.
2) Breakers shall be Schneider Electric (SQ D) QOB, EDB, I-LINE, MTZ or equal. When replacing breakers in existing equipment, breakers shall be of the same manufacture of the existing equipment.
3) Switchgear and Switchboard breakers shall have the ability to show status open/closed/trip.
4) Low-Voltage Switchgear shall utilize Schneider Electric MTZ breakers, or equal.
5) Distribution Switchboards shall utilize Schneider Electric I-line breakers, or equal, unless otherwise specified in the drawings.
Q. Power Systems Study:
1) Study shall be required to be completed prior to approval of electrical equipment submittals.
2) Coordination shall be per most current NFPA 70.
3) Contractor shall provide coordination study in SKS, pdf and hard copy report formats.
4) Contractor shall include an index of all curves.
5) Load study shall be required for existing panel upgrades.
April 2020
MAINTENANCE AND OPERATIONS Page 7
R. Conductors:
1) All new feeders and branch circuit wiring shall be copper.
2) Branch circuit conductors serving general-purpose 120-volt receptacles and miscellaneous equipment circuits in finished areas shall be 12 AWG and 3/4" conduit, minimum.
3) Conductors serving 120-volt, 20-amp, branch circuits exceeding 100’-0” from source to furthest electrical outlet or device shall be minimum 10 AWG copper.
4) Conductor insulation shall be code grade type THHN/XHHW-2/THWN-2, rated 90 degrees
Celsius.
5) Copper shall be utilized for all electrical components including but not limited to transformers, panelboards, switchgear, switchboards, buss duct, etc
6) MV conductors 2/0 shall be copper single conductor 15KV MV105/133% EPR/PVC copper tape shield OKINITE CAT# 115-23-3117 or equivalent
7) MV conductors 500 shall be copper single conductor 15KV MV105/133% EPR/PVC copper tape shield OKINITE CAT# 115-23-3131 or equivalent
S. Conductor/circuit identification:
1) MV conductors in each manhole, pull box and termination point, install permanent identification tags on each circuit's cables to clearly designate the circuit identification and voltage. The tags shall be the embossed red phenolic with white lettering, 6in. x 2in. Attach tags with plastic ties. Position the tags so they will be easy to read after the fireproofing tape is installed.
T. Electrical equipment/enclosure: See Attachment A
1) All equipment specified shall be Underwriters Laboratories (UL) labeled and listed when available.
2) Copper shall be utilized for all electrical components including but not limited to transformers, panelboards, switchgear, switchboards, buss duct, etc.
3) New fusible safety switches shall be Schneider Electric (SQ D) heavy duty and shall be provided at the new HVAC unit locations to provide motor disconnecting means as well as motor overload protection.
4) Fuses in new fusible safety switches shall be dual element, time-delay
5) External enclosures shall be rated for the environment that they are subjected to. External enclosures shall be protected against windblown dust, and rain at a minimum and shall utilize NEMA 3 enclosures vs. NEMA 3R. Enclosure type subject to review during submittal process.
U. CAVHS Motor lead connections
1) Motor lead connections #8awg and larger shall be connected with mechanical split bolt type connectors. (no aluminum products shall be used)
2) Aluminum motor leads to copper shall be coated with a anti oxidizer (noalox or similar product). Remove excess anti oxidizer.
3) Verify connection is tight (no loose or damaged conductors)
4) Shall apply 2 half lap layers of 3M 2510 cambric tape .5-inch past connection.
5) Shall apply 4 half lap layers of 3M 130C rubber mastic tape .5-inch past cambric.
6) Shall apply 4 half lap layers of 3M super 33+ tape shall .5-inch past rubber mastic.
April 2020
MAINTENANCE AND OPERATIONS Page 8
V. All work described herein shall conform to the current editions of the National Electrical Code (NEC), the International Building Code, NFPA 99, NFPA 101, NFPA 70E and VA Design Guidelines.
2.5 SPECIAL SYSTEMS
A. All special systems shall be installed in minimum ¾” conduit. See 2.5 D for labeling requirement.
B. Special systems wire labeling shall be per section 2.7.
C. Wiring shall be in accordance with all national standards and installation quality shall be monitored by the contractor.
D. Fire alarm system equipment is to be Edwards EST-3 compatible and new Fire Alarm Control
Panels shall be fully networked. Coordination with CAVHS Electronics Shop is crucial during the installation or modification of the Fire Alarm System.
1) Fire Alarm wiring shall follow the below:
a. Data: Red (+)/Black(-) 18 AWG
b. Audio: Green (+)/Brown (-)
c. Visual: Yellow (+)/Orange (-)
2) Contractor shall provide all required information for Fire Alarm System programming and FireWorks updates to the Electronics Shop. CAVHS Electronics Shop will perform all program and FireWorks updates.
E. Nurse call to be used is Westcom Novis Connect Nurse Call, or equal, (which is in the process of being networked to incorporate the code blue system).
1) Nurse call shall be included at all nurses’ stations, all exam rooms, all patient bed locations and all restrooms.
2) Paging system shall be RComm PT2025 radio paging system, or equal, PT2025 has sole propriety software and newly installed hardware must meet the system requirements.
F. Access Control equipment will be compatible with the current version of Identiv Velocity Access
Control Management software. Identiv, or compatible, card readers or keypad readers shall be used and with firmware to support current HSPD-12 Identification requirements. Doors hardware will include an active motion detector and a manual exit button in accordance with NFPA 101.
When Magnetic Locks are used it will be mounted to the secure side of the door. When Electronic Strike Locks are used it will be configured in fail secure mode. Coordination with CAVHS Electronics Shop is crucial during the installation or modification of the Access Control System.
G. All TV drops shall be included as a part of the contract. To include cabling as required.
Coordinate with Electronics shop to identify locations of television distribution drops. Upgrades to the system to accommodate additional TV’s and drops shall be included. Televisions will be hospital grade and shall be Nurse Call compatible.
2.6 COMMUNICATIONS AND DATA
A. SEE NEWEST ISTS 4.0: Miscellaneous Criteria - Office of Construction & Facilities Management (va.gov) https://www.cfm.va.gov/til/spclRqmts.asp#TelecomInfraStds https://www.cfm.va.gov/til/spclRqmts.asp#TelecomInfraStds
April 2020
MAINTENANCE AND OPERATIONS Page 9
2.7 SIGNS AND WAYFINDING
A. Follow the TIL and match existing design.
PART 3: EXECUTION
3.1 SPARES
A. Typical NTC specified extra stock quantity is approximately 5-10% of material quantity used on project. This includes the following work categories:
Specification Description 08 80 00 Glazing 09 30 13 Ceramic/Porcelain Tiling 09 51 00 Acoustical Ceilings 09 54 23 Linear Metal Ceilings 09 65 13 Resilient Base and Accessories 09 65 16 Resilient Sheet Flooring 09 65 19 Resilient Tile Flooring 09 68 00 Carpeting 09 72 16 Vinyl-Coated Fabric Wall Coverings 09 72 31 Polypropylene Fabric Wall Covering 09 84 33 Sound-Absorbing Wall Units 09 91 00 Painting 09 94 19 Multicolor Interior Finishing 10 21 23 Cubicle Curtain Tracks
Table 2: NTC stock work categories.
April 2020
MAINTENANCE AND OPERATIONS Page 10
Appendix A: Preferred Items
A. Electrical:
a. Electrical distribution equipment shall be Schneider Electric (SQ D) with the exception of transfer switches, medium voltage transformers and specialty systems. All breakers shall be Schneider Electric (SQ D). Existing legacy equipment not compatible with Schneider (SQ D) breakers shall be replaced with Schneider Electric (SQ D).
b. Medium Voltage transformers shall be FE type Copper with FR3. Loop Feed Option, under oil 3- two position switches
c. Transfer switches and associated equipment shall be CUMMINS.
B. External Lighting: Distribution and pole heights will vary. Contractor must use these listed items or equal.
Table 6: Electric Equipment Interior Lighting:
Lithonia acuity BLTR or compatible equivalent Retro fit kit 120/277V
Lithonia acuity BLTBA or compatible equivalent W/housing
120/277V
Lithonia acuity GLT or compatible equivalent 120/277V Lithonia acuity FIELD ADJUSTABLE
OUTPUT (FAO)
Lighting Controls:
Lithonia Acuity n-Light n-Light or compatible equivalent shall be interchangeable with existing facility lighting control shall be compatible/interchangeable with existing facility lighting control
Exit & emergency lighting Exit Lighting: Lithonia/acuity LQM SW 3R MVOLT EL N
SD M6
120/277V shall be self-test and/or self-diagnostic
Emergency battery back up;
Lithonia/Acuity
ELM6L UVOLT LTP EHO
SDRT
120/277V shall be self-test and/or self-diagnostic
Exit/emergency combo battery back up: Lithonia/acuity
LHQM LED R HO SD M6 120/277V shall be self-test and/or self-diagnostic
Exterior Lighting:
Wall Packs Lithonia TWH LED ALO 50K
MVOLT
shall be compatible/interchangeable with existing
Other specialty lights to be reviewed based on application
MAINTENANCE AND OPERATIONS Page 11
Electrical Devices:
Wiring devices: receptacles Normal power Receptacles Hospital grade
IVORY
Hubbell HBL8300I or equivalent ivory, Duplex, Hospital Grade, 2-Pole 3-Wire Grounding, 20A 125V, 5-20R
Receptacles Hospital grade Tamper Resistant IVORY
Hubbell 8300IVTRA Ivory, Tamper Resistant, Hospital Grade, Self-Test, 20A 125V, 2-Pole 3-Wire Grounding, 5-20R
GFCI receptacles Hospital grade IVORY:
Hubbell GFTWRST83I or equivalent
Ivory, GFCI, Tamper and Weather Resistant, Hospital Grade, Self-Test, 20A 125V, 2-Pole 3-Wire Grounding, 5- 20R
Emergency power Receptacles Hospital grade
RED
Hubbell HBL8300RED or equivalent red, Duplex, Hospital Grade, 2-Pole 3-Wire Grounding, 20A 125V, 5-20R
Tamper Resistant RED
Hubbell 8300REDTRA RED, Tamper Resistant, Hospital Grade, Self-Test, 20A 125V, 2-Pole 3-Wire Grounding, 5-20R
GFCI receptacles Hospital grade RED
Hubbell GFTWRST83R 5-20R, or equivalent red, GFCI, Tamper and Weather Resistant, Hospital Grade, Self-Test, 20A 125V, 2- Pole 3-Wire Grounding
Wiring devices: Switches Single pole: Hubbell HBL1221I or equivalent Extra Heavy Duty Industrial Grade, Toggle Switches, General Purpose AC, Single Pole, 20A 120/277V AC, Back and Side Wired, Three way: Hubbell HBL1223I or equivalent
Extra Heavy Duty Industrial Grade, Toggle Switches, General Purpose AC, three way, 20A 120/277V AC, Back and Side Wired, Four way: Hubbell HBL1224I or equivalent
Extra Heavy Duty Industrial Grade, Toggle Switches, General Purpose AC, four
April 2020
MAINTENANCE AND OPERATIONS Page 12 way, 20A 120/277V AC, Back and Side Wired, MV Protective Relays Sweitzer SEI-351 or newer Sweitzer SEI-551 or newer
Power Monitoring System: Schneider Electric PME monitoring system, or compatible to existing PME monitoring system.
shall be
Metering: Schneider Electric Meters
PM5300, or compatible to existing PME monitoring system. All programming, cabling, and appurtenances to be included shall be
Switchgear Schneider Electric (SQ D), or equal, Low Voltage Switchgear fully compatible to match existing and parts inventory, copper fully rated bussing shall be
Switchboards Schneider Electric (SQ D), or
Switchgear fully compatible to match existing and parts inventory, copper fully rated bussing shall be
Panel Boards Schneider Electric (SQ D), NQ, NF, I-LINE or equal fully compatible to match existing and parts inventory, copper fully rated bussing with door in door hinged cover shall be 22K AIC or higher
Breakers 120/208V molded case Shall be 22K AIC rating or higher Safety Switches (disconnects) Schneider Electric (SQ D) heavy duty (fused or non-fused per NFPS 70) shall be
MV CABLE
April 2020
MAINTENANCE AND OPERATIONS Page 13
Distribution (feeders)
2/0 Type MV105/133% Insulation Cat# 115-23- 3117 or equivalent
Incoming utility 500 Type MV105/133% Insulation Cat# 115-23-3131
MV TERMINATIONS
200A Load-Break Elbow-
Elastimold Brand 2/0 Cat#
166LRR-GAB-250
(Transformer Terminations) or
200A Straight Plug- Elastimold Brand 2/0 Cat# K151SP-B0240 (Manhole Terminations) or
200A Straight Receptacle-
Elastimold Brand Cat# KI51SR- B0240 (Manhole Terminations) or equivalent
200A Tee Splice- Elastimold Brand Cat# K150T (Man-Hole
Grounding Device (Shield Adapter) Elastimold Brand Cat# 20MA-G (required For All Elbow, Plug & Receptacle
200A SURGE ARRESTER
Elastimold 167ESA-18 (transformer) or equivalent
April 2020
MAINTENANCE AND OPERATIONS Page 14
Appendix B: Preferred Items
C. Hardware: The following table dictates the type of hardware Central Arkansas Veterans Health Care System will accept installed in the facility. Contractor must use these listed items or equal.
PART/ EQUIPMENT MANUFACTURER REMARKS
Intrusion System (Card Readers)
EST Synergy
Table 3: Product.
D. Building Products: The following table dictates the manufactured products that are allowed to be installed in the facility. Contractor must use these listed items or equal.
REMARKS
ALL PROJECTS WILL HAVE 2 X 2
ARMSTRONG CORTEGA 770 TILES (NO
2 X 4 TILES)
ALL LOCKS AND HARDWARE WILL BE
BEST ACCESS SYSTEMS
(CAHVS CURRENTLY USES BAST
THROUGHOUT THE FACILITY)
ALL COUNTERTOPS WILL BE SOLID
MATERIAL WITH NO WOOD
SUBSTRATE OR FORMICA
ALL CORNER GUARDS WILL BE
STAINLESS STEEL
SOLID WOOD
ALL FIRE RATED DOORS WILL BE
CECO METAL GRAIN DOORS, CS5-
PROVINCIAL
METAL GREY PRIMER FINISH
(PAINT TO MATCH EXISTING COLOR)
MINIMUM 6 MIL VINYL
(NO BUILT-UP ROOFING)
ALL SOLID PLASTIC MATERIAL WITH
FULL METAL ATTACHMENT
INSTALLED WITH MINIMUM ¼”
TOGGLE BOLTS
3M CP 25WB+ FIRE BARRIER
INTUMESCENT (RED)
NOTE: CONTRACTOR WILL BE
REQUIRED TO SUBMIT FORM FOR
April 2020
MAINTENANCE AND OPERATIONS Page 15
FIRE WALL PENETRATIONS PER THE
SAFETY OFFICE
ONLY SHERWIN WILLIAMS BASE
WITH VA APPROVED COLORS
5/8” BRAND “X” FIRE RATED
Table 4: Building products.
E. Plumbing Fixtures: The following table dictates the manufactured products that are allowed to be installed in the facility. Contractor must use these listed items or equal.
PART/ EQUIPMENT MANUFACTURER
Lav Faucets Sloan EFX-275 Solar-Powered Deck-Mounted Mid Body Faucet, Integrated Side Mixer 0.5 gpm, Multi- Laminar Spray, Infrared Sensor Sloan® Solis® EAF-275-ISM Solar Powered Faucet
Bar Sink Faucets Sloan EFX-175.002.0200 BASYS Sensor Faucet, High, Solar Powered, 1.5 GPM Aerator, 8 Inch Trim Plate
Flushometers Sloan SOLIS 8111-1.6 Water Closet Flushometer, Exposed, Solar Powered, Sensor Activated, Low Consumption, 1.6 GPF Sloan SOLIS 8186-0.5-OR Urinal Flushometer, Exposed, Solar Powered, Sensor Activated, Electrical Override, 0.5 GPF, Polished Chrome, Less Batteries
Watts Backflow Preventers
Table 5: Plumbing products.
F. HVAC Controls: Contractor must use these listed items or equal.
a. ALL FLEX DUCT NEEDS TO BE REPLACED.
b. NO FLEX DUCT LONGER THAN 3 FEET
c. All AHU equipment will be Trane
d. All fans will be direct drive
e. All AHU will have two or more fans for supply and return fans
f. ALL WATER FOUNTAINS WILL BE REMOVED AND REPLACED WITH ELKAY M#
LZSDWSSK L/ REFRIGERATION.
g. ALL SUPPLY GRILLES WILL BE REPLACED WITH HART AND COOLY P# FPD R6
h. ALL RETURN GRILLES WILL BE REPLACED WITH HART AND COOLY P# 94AT
i. ALL VFD’S WILL BE ABB
j. ALL room pressure monitors will be Siemens 547-103A
k. All controls will be the latest vision of siemens or Trane Ensemble
l. All control wiring will be labeled on both ends
m. All thermostats will be labeled
n. All grilles will be labeled the same as the thermostat serving that grille
April 2020
MAINTENANCE AND OPERATIONS Page 16
o. All return grilles will be labeled the same as the t stat serving that grille if the return grill is on a VAV box.
p. All label should be clear with black lettering
q. All filed installed UV lights will come from Arkansas filter and Steril Aire
r. Contractor will provide one electronic and one hard copy of all parts, equipment, maintenance, owner manual TAB report and warranty paperwork.
s. A ONE YEAR LABOR AND PARTS WARRANTY WILL BE ON ALL PARTS AND
EQUIPMENT FROM THE DATE THAT THE VA EXCEPTS THE PROJECT AS A
WHOLE.
G. Electrical:
transfer switches, medium voltage transformers and specialty systems. All breakers shall be Schneider Eletric (SQ D). Existing legacy equipment not compatible with Schneider (SQ D) breakers shall be replaced with Schneider Electric (SQ D).
b. Medium Voltage transformers shall be FE type Cooper with FR3.
c. Transfer switches and associated equipment shall be CUMMINS.
H. External Lighting: Distribution and pole heights will vary. Contractor must use these listed items
Wall Packs Lithonia TWH LED 20C 50K
Table 6: External lighting.
I. Data Receptacles: Contractor must use Panduit items listed or equal. Wall face plates and patch panels shall conform to the following model numbers:
Black D2 Jack NK688MBL Ivory Voice Jack NK688EIY Orange D1 Jack NK688MOR Black D2 Jack NK688MBL Spare NKBMEI-X 4 Port Face Plate NK4FEIY 48 Port, CAT6, Patch Panel DP48688TGY
4 PR CLIPS 110C-4
110 Punch Down Block w/ Clips P110KB1004Y
Table 7: Wall face plates and patch panels.
J. Ice Machine: Follet Corporation Model No. Contractor must use these listed items or equal.
Manufacturer Model No. Additional Information Ice & Water Dispenser Manitowoc 300lb. capacity Freestanding, SensorSAFE dispense, ice machine in base, April 2020
MAINTENANCE AND OPERATIONS Page 17
Table 8: Ice Machine automatic load, nugget style, air-cooled condenser, 400 lb.
production/24 hours, 90 lb.
storage capacity, stainless steel exterior with plastic trim, 6” adjustable legs
Ice & Water Dispenser Water Filter System
Water filter system (one per ice machine) for ice and water dispensers, 3,000 gallons capacity. Contractor to provide 10 filters per machine installed.
CAVHS M&O Electrical Standards into 2.4 ELECTRICAL
A. Cable Trays: Ladder style, Aluminum, 6” Deep, 12” wide, 6” spacing.
B. Conduit/Raceway Systems
Building Management Systems Blue Colored Conduits Fire Alarm Red Colored Conduits. All boxes and covers shall be red.
Security Systems Purple Conduits (C-Cure, cameras, card readers, etc.)
Nurse Call/Code Blue Green Conduits Couplings or Bands every
10 Feet Paging White Conduits Couplings or Bands every
10 Feet Communications Orange Couplings or Bands every 10 Feet
(When required for protection and cable tray or J-Hooks deemed unfeasible) (Computers, VOIP, fiber, etc. for IT systems not related to other systems already noted)
Table 1: Conduit color codes.
1) All conduits to be a minimum of ¾” dia.
2) All conduits shall be bonded on both ends of the raceway when required to be bonded.
3) Conduit shall not be considered an adequate EGC.
4) Contractor shall complete grounding on both sides of the raceway.
5) Electrical metallic tubing (EMT) with compression type couplings and fittings (up to 53mm
(2”)) shall be used generally for concealed applications, interior partition walls and above the 8foot demarcation as noted above.
6) In wall conduit for branch circuits shall be installed vertically and stubbed out above ceiling.
No horizontal conduit shall be installed in walls for branch circuits.
7) All rough in conduit to have plaster rings and pull cords (Telecom, Data, Nurse Call, etc.)
8) No MC or AC cable allowed.
9) No Multi-Branch Circuits Allowed.
10) Junction boxes shall be installed on pre-manufactured brackets that span the back of the box from stud to stud. Erico Telescoping Screw Gun Bracket or equal.
11) Conduits shall be supported per NFPA 70.
12) All flexible metal conduit shall be steel and 1/2” dia. Or larger.
13) Use of flexible metal conduit for connections to motors and vibrating equipment shall be limited to 24 inches.
C. Conduit Labeling
1) Provide cable and conduit identification tags, on all raceways, 30’ on center and within 24” of all terminations, bends, and penetrations.
2) Labels shall identify feeder source and load served (to and from), and voltage.
3) Letter size shall be as large as practical per raceway size.
4) Tags shall be permanent, self-adhesive with clear laminate
5) Essential System Power feeders or circuit labels shall be red with white letter.
6) Normal System Power feeders or circuit labels shall be blue with white letters
7) 1000V and above shall be painted orange in color and voltage marked every 30’ on center and within 24” of termination.
8) Self-Adhesive Identification Products: Clean surfaces before application, using materials and methods recommended by manufacturer of identification device.
D. Lighting
1) External Lighting: Reference Appendix A for standard requirements.
2) Interior lighting shall be LED as base bid. Lithonia acuity BLTR, BLTBA, GLT or similar if applicable. Lighting designer to select and present option. Reference Appendix A for standard requirements.
3) All lighting ballast/drivers shall be multi-voltage (120-277V).
4) Emergency lighting battery packs shall be self-test and/or self-diagnostic.
5) Lighting Controls: Lithonia Acuity n-Light, or equal and shall be compatible/interchangeable to existing facility lighting controls. All lighting shall utilize occupancy sensors and controls per energy guidelines and NFPA.
6) All hardwired interior luminaires shall contain a disconnecting means similar to the Sta-Kon Push-In Luminaire Disconnect for compliance with NFPA 70E.
E. Oil Filled Transformer –Shall be
1) Loop Feed Option, under oil 3- two position switches, Envirotemp FR3, FE.
2) Shall be cooper windings.
3) Shall be equipped with external flush or surface mounted enclosure containing oil sampling port, pressure gauge, pressure relieve valve and nitrogen fill valve.
4) Shall be equipped with Primary and secondary door IR windows.
5) Contractor shall install two 4-inch conduits and 1 set of matching spare conduits on both primary and secondary sides of the transformer. Spare conduits shall be capped and labeled appropriately. Provide coordination drawings indicating stub locations.
F. Oil Filled Transformer Labeling:
1) All new transformers shall have SCCR labeling, to include any calculations.
2) Arc Flash and Shock Hazard: Install adhesive arc flash warning labels on all equipment as required by NFPA 70E. Label shall indicate the arc hazard boundary (inches), working distance (inches), arc flash incident energy at the working distance (calories/cm2), required PPE category and description including the glove rating, voltage rating of the equipment, limited approach distance (inches), restricted approach distance (inches), prohibited approach distance (inches), equipment/buss name, date prepared, and manufacturer name and address.
IEEE Std 1584a shall apply. Contractor shall complete study prior to ordering equipment.
Equipment shall not be permitted to be energized without a new or updated label.
G. Wiring Devices: See attachment A
1) 1) All receptacles shall be duplex type hospital grade. Tamper proof hospital grade outlets shall be required in public spaces such as waiting rooms, and hallways.
2) All receptacles shall be Hubbell HBL8300IU, or approved equal, 125-volt rated, 20-amp (minimum) as required.
a. Emergency Circuits - Red
b. Normal – Ivory
c. Isolated – Orange
3) A Normal outlet should always be located within 24” of every emergency outlet. Electrical, Mechanical, and IT rooms and closets should contain an equal amount of normal and emergency circuits. Contractors to notify COR of discrepancies to this rule.
4) All toggle switches shall be specification grade, silent acting, 125/277-volt rated, 20-amp, single-pole, 3-way, or 4-way as required.
H. Wiring Devices NLR building 170: See attachment A
2) All receptacles shall be duplex type hospital grade. Tamper proof hospital grade outlets shall be required in public spaces such as waiting rooms, and hallways.
3) All receptacles in wet or damp areas shall be GFCI with self-testing.
4) Corridors shall have a dedicated outlet every 50 ft. for use by EMS. This outlet shall utilize a special plug for floor cleaners, etc. Coordinate with the electric shop for details at this time.
5) Normal Power receptacles shall be duplex type ivory in color.
6) Normal power Wall plates shall be stainless steel. Circuit identification with self-adhesive label yellow with black lettering
7) Emergency Power receptacles shall be duplex type red in color.
8) Emergency power wall plates shall be stainless steel. Circuit identification with self-adhesive label red with black lettering
I. Wiring devices John L. McLellan (JLM) See attachment A
1) All receptacles shall be duplex type hospital grade. Tamper proof hospital grade outlets shall be required in public spaces such as waiting rooms, and hallways.
2) All receptacles in wet or damp areas shall be GFCI with self-testing.
3) Corridors shall have a dedicated outlet every 50 ft. for use by EMS. This outlet shall utilize a special plug for floor cleaners, etc. Coordinate with the electric shop for details at this time.
4) Normal Power receptacles shall be duplex type Ivory in color.
5) Normal power Wall plates shall be stainless steel. Circuit identification with self-adhesive label yellow with black lettering
6) Emergency Power receptacles shall be duplex type red in color.
7) Emergency power wall plates shall be stainless steel. Circuit identification with self-adhesive label red with black lettering
8) All toogle switches shall be specification grade, silent acting, 125/277-volt rated, 20-amp, single-pole, 3-way, or 4-way as required.
J. Power Monitoring System: Schneider Electric PME monitoring system, or compatible to existing PME monitoring system.
K. Metering: Switchgear, Switchboards and Panel boards: Schneider Electric Meters, or compatible to existing PME monitoring system. All programming, cabling, and appurtenances to be included.
L. Switchgear: Schneider Electric (SQ D), or equal, Low Voltage Switchgear fully compatible to match existing and parts inventory, copper fully rated bussing
M. Switchboards: Schneider Electric (SQ D) I-LINE or equal fully compatible to match existing and parts inventory, copper fully rated bussing
N. Panelboards: Schneider Electric (SQ D), NQ, NF, I-LINE or equal fully compatible to match existing and parts inventory, copper fully rated bussing with door in door hinged cover
1) Submit all panel schedules, including updated panel schedules in pdf and Microsoft Excel format. Coordinate with COR for existing files if available.
O. Automatic Transfer Switches: Cummins, match existing controls. Contractor shall ensure programming and installation is done in accordance with all applicable regulations and requirements, to include Joint Commission requirements.
P. Breakers: See Attachment A
1) Electronic breakers shall be expected to achieve coordination.
2) Breakers shall be Schneider Electric (SQ D) QOB, EDB, I-LINE, MTZ or equal. When replacing breakers in existing equipment, breakers shall be of the same manufacture of the existing equipment.
3) Switchgear and Switchboard breakers shall have the ability to show status open/closed/trip.
4) Low-Voltage Switchgear shall utilize Schneider Electric MTZ breakers, or equal.
5) Distribution Switchboards shall utilize Schneider Electric I-line breakers, or equal, unless otherwise specified in the drawings.
Q. Power Systems Study:
1) Study shall be required to be completed prior to approval of electrical equipment submittals.
2) Coordination shall be per most current NFPA 70.
3) Contractor shall provide coordination study in SKS, pdf and hard copy report formats.
4) Contractor shall include an index of all curves.
5) Load study shall be required for existing panel upgrades.
R. Conductors:
1) All new feeders and branch circuit wiring shall be copper.
2) Branch circuit conductors serving general-purpose 120-volt receptacles and miscellaneous equipment circuits in finished areas shall be 12 AWG and 3/4" conduit, minimum.
3) Conductors serving 120-volt, 20-amp, branch circuits exceeding 100’-0” from source to furthest electrical outlet or device shall be minimum 10 AWG copper.
4) Conductor insulation shall be code grade type THHN/XHHW-2/THWN-2, rated 90 degrees
Celsius.
5) Copper shall be utilized for all electrical components including but not limited to transformers, panelboards, switchgear, switchboards, buss duct, etc
6) MV conductors 2/0 shall be copper single conductor 15KV MV105/133% EPR/PVC copper tape shield OKINITE CAT# 115-23-3117 or equivalent
7) MV conductors 500 shall be copper single conductor 15KV MV105/133% EPR/PVC copper tape shield OKINITE CAT# 115-23-3131 or equivalent
S. Conductor/circuit identification:
1) MV conductors in each manhole, pull box and termination point, install permanent identification tags on each circuit's cables to clearly designate the circuit identification and voltage. The tags shall be the embossed red phenolic with white lettering, 6in. x 2in. Attach tags with plastic ties. Position the tags so they will be easy to read after the fireproofing tape is installed.
T. Electrical equipment/enclosure: See Attachment A
1) All equipment specified shall be Underwriters Laboratories (UL) labeled and listed when available.
2) Copper shall be utilized for all electrical components including but not limited to transformers, panelboards, switchgear, switchboards, buss duct, etc.
3) New fusible safety switches shall be Schneider Electric (SQ D) heavy duty and shall be provided at the new HVAC unit locations to provide motor disconnecting means as well as motor overload protection.
4) Fuses in new fusible safety switches shall be dual element, time-delay
5) External enclosures shall be rated for the environment that they are subjected to. External enclosures shall be protected against windblown dust, and rain at a minimum and shall utilize NEMA 3 enclosures vs. NEMA 3R. Enclosure type subject to review during submittal process.
U. CAVHS Motor lead connections
1) Motor lead connections #8awg and larger shall be connected with mechanical split bolt type connectors. (no aluminum products shall be used)
2) Aluminum motor leads to copper shall be coated with a anti oxidizer (noalox or similar product). Remove excess anti oxidizer.
3) Verify connection is tight (no loose or damaged conductors)
4) Shall apply 2 half lap layers of 3M 2510 cambric tape .5-inch past connection.
5) Shall apply 4 half lap layers of 3M 130C rubber mastic tape .5-inch past cambric.
6) Shall apply 4 half lap layers of 3M super 33+ tape shall .5-inch past rubber mastic.
V. All work described herein shall conform to the current editions of the National Electrical Code
(NEC), the International Building Code, NFPA 99, NFPA 101, NFPA 70E and VA Design Guidelines.
Appendix A: Preferred Items
A. Electrical:
transfer switches, medium voltage transformers and specialty systems. All breakers shall be Schneider Electric (SQ D). Existing legacy equipment not compatible with Schneider (SQ D) breakers shall be replaced with Schneider Electric (SQ D).
b. Medium Voltage transformers shall be FE type Copper with FR3. Loop Feed Option, under oil 3- two position switches
c. Transfer switches and associated equipment shall be CUMMINS.
B. External Lighting: Distribution and pole heights will vary. Contractor must use these listed items
Table 6: Electric Equipment Interior Lighting:
Lithonia acuity BLTR or compatible equivalent Retro fit kit 120/277V
Lithonia acuity BLTBA or compatible equivalent W/housing
120/277V
Lithonia acuity GLT or compatible equivalent 120/277V
Lithonia acuity FIELD ADJUSTABLE
OUTPUT (FAO)
Lighting Controls:
Lithonia Acuity n-Light n-Light or compatible equivalent shall be interchangeable with existing facility lighting control shall be compatible/interchangeable with existing facility lighting control
Exit & emergency lighting Exit Lighting: Lithonia/acuity LQM SW 3R MVOLT EL N
SD M6
120/277V shall be self-test and/or self-diagnostic
Emergency battery back up;
Lithonia/Acuity
ELM6L UVOLT LTP EHO
SDRT
120/277V shall be self-test and/or self-diagnostic
Exit/emergency combo battery back up: Lithonia/acuity
LHQM LED R HO SD M6 120/277V shall be self-test and/or self-diagnostic
Exterior Lighting:
Wall Packs Lithonia TWH LED ALO 50K
MVOLT
shall be
Electrical Devices:
Wiring devices: receptacles Normal power Receptacles Hospital grade
IVORY
Hubbell HBL8300I or equivalent ivory, Duplex, Hospital Grade, 2-Pole 3-Wire Grounding, 20A 125V, 5-20R
Receptacles Hospital grade Tamper Resistant IVORY
Hubbell 8300IVTRA Ivory, Tamper Resistant, Hospital Grade, Self-Test, 20A 125V, 2-Pole 3-Wire Grounding, 5-20R
GFCI receptacles Hospital grade IVORY:
Hubbell GFTWRST83I or equivalent
Ivory, GFCI, Tamper and Weather Resistant, Hospital Grade, Self-Test, 20A 125V, 2-Pole 3-Wire Grounding, 5- 20R
Emergency power
RED
Hubbell HBL8300RED or red, Duplex, Hospital Grade, 2-Pole 3-Wire Grounding, 20A 125V, 5-20R
Tamper Resistant RED
Hubbell 8300REDTRA RED, Tamper Resistant, Hospital Grade, Self-Test, 20A 125V, 2-Pole 3-Wire Grounding, 5-20R
GFCI receptacles Hospital grade RED
Hubbell GFTWRST83R 5-20R, red, GFCI, Tamper and Weather Resistant, Hospital Grade, Self-Test, 20A 125V, 2- Pole 3-Wire Grounding
Wiring devices: Switches Single pole: Hubbell HBL1221I or equivalent Extra Heavy Duty Industrial Grade, Toggle Switches, General Purpose AC, Single Pole, 20A 120/277V AC, Back and Side Wired, Three way: Hubbell HBL1223I or equivalent
Extra Heavy Duty Industrial Grade, Toggle Switches, General Purpose AC, three way, 20A 120/277V AC, Back and Side Wired, Four way: Hubbell HBL1224I or equivalent
Extra Heavy Duty Industrial Grade, Toggle Switches, General Purpose AC, four way, 20A 120/277V AC, Back and Side Wired, MV Protective Relays Sweitzer SEI-351 or newer Sweitzer SEI-551 or newer
Power Monitoring System: Schneider Electric PME monitoring system, or compatible to existing PME monitoring system.
shall be
Metering: Schneider Electric Meters
PM5300, or compatible to existing PME monitoring system. All programming, cabling, and appurtenances to be included shall be
Switchgear Schneider Electric (SQ D), or
Switchgear fully compatible to match existing and parts inventory, copper fully rated bussing shall be
Switchboards Schneider Electric (SQ D), or
Switchgear fully compatible to match existing and parts inventory, copper fully rated bussing shall be
Panel Boards Schneider Electric (SQ D), NQ, NF, I-LINE or equal fully compatible to match existing and parts inventory, copper fully rated bussing with door in door hinged cover shall be 22K AIC or higher
Breakers 120/208V molded case Shall be 22K AIC rating or higher Safety Switches (disconnects) Schneider Electric (SQ D) heavy duty (fused or non-fused per NFPS 70) shall be
MV CABLE
Distribution (feeders)
2/0 Type MV105/133% Insulation Cat# 115-23- 3117 or equivalent
Incoming utility 500 Type MV105/133% Insulation Cat# 115-23-3131
200A Load-Break Elbow-
Elastimold Brand 2/0 Cat#
166LRR-GAB-250
(Transformer Terminations) or
200A Straight Plug- Elastimold Brand 2/0 Cat# K151SP-B0240 (Manhole Terminations) or
200A Straight Receptacle-
Elastimold Brand Cat# KI51SR- B0240 (Manhole
200A Tee Splice- Elastimold Brand Cat# K150T (Man-Hole
Grounding Device (Shield Adapter) Elastimold Brand Cat# 20MA-G (required For All Elbow, Plug & Receptacle
200A SURGE ARRESTER
Elastimold 167ESA-18 (transformer) or equivalent
| 1 - MASTER - CAVHS M&O Standard |
| PART 1: GENERAL |
| 1.1 DESCRIPTION |
| PART 2: PRODUCTS |
| 2.1 BUILDING Products |
| 2.2 PLUMBING |
| 2.3 HEATING, VENTILATION & AIR CONDITIONING |
| 2.4 ELECTRICAL |
| 2.5 SPECIAL SYSTEMS |
| 2.6 COMMUNICATIONS AND DATA |
| 2.7 SIGNS AND WAYFINDING |
| PART 3: EXECUTION |
| 3.1 SPARES |
| Appendix A: Preferred Items |
Appendix B: Preferred Items
| 2 - CAVHS M&O ELECTRICAL STANDARDS DB 6-11-25 |
| CAVHS M&O Electrical Standards into 2.4 ELECTRICAL |
| Appendix A: Preferred Items |
File details come from the government source that posted it. Updated .