PM8000.pdf
PDF 8 MB Posted
- Solicitation number
- 36C25626R0023
About this file
This is a technical datasheet for the PowerLogic™ PM8000 Series, a line of compact, cost-effective multifunction power meters manufactured by Schneider Electric. The PM8000 series is designed for low to high voltage applications across industrial facilities, data centers, infrastructure, healthcare buildings, and other critical power environments to measure, monitor, and analyze power quality and energy consumption.
The PM8000 series comprises three feature tiers: Essential (PM81XX), Standard (PM82XX), and Advanced (PM83XX). Key specifications include Class 0.2S active energy accuracy per IEC 62053-22, current and voltage accuracy of 0.1% reading, frequency measurement to Class 0.02, and reactive energy accuracy to Class 0.5S. The meters support multiple voltage ranges (57-400V line-to-neutral, 100-690V line-to-line), current measurement from 50 mA to 10 A, and operate across 42-69 Hz frequencies. Standard models feature 256 samples per cycle sampling, while Advanced models provide 512 samples per cycle. All models include dual 10/100BASE-TX Ethernet ports, RS-485 serial connectivity, and support for multiple protocols including Modbus, IEC 61850, DNP3, BACnet/IP, and MQTT. The meters offer extensive power quality compliance reporting per EN 50160, IEC 61000-4-30 Class A/S, and IEEE 519 standards; harmonic analysis up to the 63rd harmonic; disturbance direction detection; and waveform capture with COMTRADE format output. Available mounting options include 96×96 panel mount, DIN rail mount, and remote display configurations. Optional modules expand functionality with 4-wire RS-485 serial ports, fiber-optic Ethernet isolation, digital I/O modules (6 inputs, 2 relay outputs), and analog I/O modules (4 inputs, 2 outputs). The datasheet includes complete technical specifications, dimensions, component diagrams, and commercial reference numbers for all model variants and accessories.
View the file
Other files
Show all 28
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
The PowerLogic™ PM8000 series meters are compact, cost-effective multifunction power meters that will help you ensure reliability and efficiency of your power-critical facility.
Reveal and understand complex power quality conditions. Measure, understand and act on insightful data gathered from your entire power system. Designed for key metering points throughout your energy infrastructure, the PowerLogic™ PM8000 series meter has the versatility to perform nearly any job you need a meter to do, wherever you need it!
Applications
Ideal for low to high voltage applications in industrial facilities, data centers, infrastructure and other critical power environments.
PowerLogic™ PM8000 Series Technical Datasheet
P B
METSEPM8240
ADVANCED METERING� FUNCTIONS AND CHARACTERISTICS
1Version: 1.0 - 12/03/2026
PLSED310058EN
https://www.se.com/ww/en/product/METSEPM8240
The solution for
Markets that can benefit from a solution that includes PowerLogic™ PM8000 series meters:
• Industry
• Data centers
• Infrastructure
• Healthcare
• Buildings
Power management solutions
Schneider Electric provides innovative power management solutions to increase your energy efficiency and cost savings, maximize electrical network reliability and availability, and optimise electrical asset performance.
Competitive advantages
• Modular, flexible patented ION technology architecture enables a simple building block approach.
• Disturbance Direction Detection, modularity and compliance with latest power quality standards.
• Color screen.
• Multiple communication options.
• Excellent accuracy.
Benefits
• Makes understanding power quality simple to help operations personnel avoid downtime and helps ensure increased productivity and equipment life.
• Makes energy and power quality immediately relevant and actionable to support your operational and sustainability goals.
Conformity of standards
• EN 50160
• EN 50470
• IEC 61000-4-30
• IEC 61010-1
• IEC 61326-1
• IEC 61557-12
• IEC 62052-11
• IEC 62053-11
• IEC 62053-22
• IEC 62053-23
• IEC 62053-24
• IEC 62586-2
• IEEE 519
• UL 61010-1
PM8000 series
PowerLogic™ PM8000 series meter - rear view PowerLogic™ PM8000 DIN rail mounted meter
P B
P B
P B
PowerLogic™ PM8000 DIN rail meter- underside
ADVANCED METERING� FUNCTIONS AND CHARACTERISTICS
Version: 1.0 - 12/03/2026
Main characteristics
| • | Precision metering: |
| – IEC 61557-12 PMD/SD/K70/0.2 and PMD/SS/K70/0.2 3000m (performance |
measuring and monitoring functions).
– Class 0.2S accuracy IEC 62053-22, ANSI C12.20 Class 0.2 (active energy).
– Industry leading Class 0.5S accuracy for reactive energy (IEC 62053-24).
– Cycle-by-cycle RMS measurements updated every ½ cycle.
– Full ‘multi-utility’ WAGES metering support.
– Net metering.
– Anti-tamper protection seals and hardware metrology lock.
| • | PQ compliance reporting and basic PQ analysis: |
| – Monitors and logs parameters in support of international PQ standards, |
– IEC 61000-4-30 Class A/S (test methods as per IEC 62586-2).
– Generates onboard PQ compliance reports accessible via onboard web pages:
– Basic event summary and pass/fail reports, for EN 50160 for power frequency, supply voltage indication, supply voltage dips, short and long interruptions, temporary over voltages, voltage unbalance and harmonic voltage.
– ITIC (CBEMA) and SEMI curves, with alarm categorization to support further analyses.
– NEMA Motor Derating curve.
– Pass/fail report for IEEE 519 for voltage and current harmonic limits.
– Harmonic analysis:
– THD on voltage and current, per phase, min/max, custom alarming.
– Individual harmonic magnitudes and angles on voltage and current, up to the 63rd harmonic.
– High resolution waveform capture: triggered manually or by alarm, captured waveforms available directly from the meter via SFTP in a COMTRADE format.
– Disturbance detection and capture: sag/swell on any current and voltage channel, alarm on disturbance event, waveform capture with pre-event information.
– Patented Disturbance Direction Detection: provides indication of the captured disturbance occurring upstream or downstream of the meter; timestamped results provided in the event log, with degree of certainty of disturbance direction.
• Used with Schneider Electric’s sophisticated software tools, provides detailed PQ reporting across entire network:
– EN 50160 report.
– IEC 61000-4-30 report.
– IEEE 519 harmonic compliance report.
– PQ compliance summary.
– Display of waveforms and PQ data from all connected meters.
– Onboard web-based waveform viewer.
– Energy reports for consumption analysis and cost management.
– WAGES dashboards and reports.
– EcoStruxure™ Power Events Analysis, including alarm management, sequence of events, and root cause analysis.
| • | Cybersecurity: |
| – Security events logging with Syslog protocol support. |
– HTTPS secure protocol.
– Ability to enable or disable any communication port and any protocol per port.
– Anti-tamper protection seals and hardware metrology lock.
– User accounts with strong passwords.
| • | Data and event logging: |
| – Onboard data and event logging. |
– 512 MB storage.
PowerLogic™ PM8000 series meter
P B
PM8000 series
PowerLogic™ PM8000 series waveform web page sample
P B
PowerLogic™ PM8000 series CBEMA web page sample
P B
PowerLogic™ PM8000 series PQ harmonics web page sample
P B
Feature selection
Commercial reference number
PM8000 meters
PM81XX Essential Feature Set
PM82XX Standard Feature Set
PM83XX Advanced Feature Set
ADVANCED METERING� FUNCTIONS AND CHARACTERISTICS
3Version: 1.0 - 12/03/2026
– No data gaps due to network outages or server downtime.
– Min/Max log for standard values.
– Up to 64 user definable data logs, recording up to 50 parameters on a cycle-by-cycle or other user definable interval.
– Continuous logging or ‘snapshot’ triggered by setpoint and stopped after defined duration.
– Trend energy, demand and other measured parameters.
– Forecasting via web pages: average, minimum and maximum for the next four hours and next four days.
– Advanced time-of-use capability.
– Security / event log: alarm conditions, metering configuration changes, power outages, firmware download, and user login/logout all timestamped to ±1 millisecond.
| • | Alarming and control: |
| – 50+ definable alarms to log critical event data, trigger waveform recording, |
or perform control function.
– Trigger on any condition, with 1/2-cycle and 1-second response time.
– Combine alarms using Boolean logic and to create alarm levels.
– Alarm notification via email.
– In conjunction with Schneider Electric’s EcoStruxure™ software, alarms, software alarms, and alarm frequency are categorized and trended enabling sequence of events and root cause analyses.
Usability
• Easy installation and setup:
– Panel and DIN rail mounting options, remote display option.
– Pluggable connectors.
– Free setup application simplifies meter configuration.
– Auto-discovery using DPWS (Device Profile Web Services).
– DHCP for automatic IP address configuration.
| • | Front panel: |
| – Easy to read color graphic display. |
– Simple, intuitive menu navigation with multi-language (8) support.
| • | Flexible remote communications: |
| – Multiple simultaneously operating communication ports and protocols |
allow interfacing with other automation systems; (e.g. waveforms, alarms, billing data, etc.) can be uploaded for viewing/analysis while other systems access real-time information.
– Supports Modbus, ION, DNP3, IEC 61850, BACnet/IP.
– Supports MQTT Protocol for sharing up-to 30 customizable parameters of gap-less, high-speed power monitoring data.
– Dual port Ethernet: 10/100BASE-TX; supports IPV4 and IPV6; daisy-chaining capability removes need for additional switches.
– Secure web interface with HTTPS and TLS 1.2 with support for user-provided certificates to access real-time power monitoring data, PQ compliance data, and customizable webpages.
– Create redundant network loop using Rapid Spanning Tree Protocol (RSTP) and managed Ethernet switches.
– Customize TCP/IP port numbers and enable/disable individual ports.
– RS-485 2-wire connection, up to 115,200 baud, Modbus RTU, ION and DNP3 protocols.
– Ethernet to serial gateway with Modbus Master functionality, connecting to 31 downstream serial Modbus devices. Also supports Modbus Mastering over TCP/IP (Ethernet) network.
Main characteristics (contd.)PM8000 series
PowerLogic™ PM8000 series meter with option modules
P B
PowerLogic™ PM8000 series with RS-485 4-Wire module
PowerLogic™ PM8000 series with Fiber-Ethernet Module
P B
P B
PowerLogic™ PM8000 series meter with remote display
P B
ADVANCED METERING� FUNCTIONS AND CHARACTERISTICS
Version: 1.0 - 12/03/2026
PowerLogic™ I/O module
4-Wire RS-485 Option Module Fiber-Ethernet Option Module
P B
P B
P B
| • | Time synchronization via: |
| – GPS clock (RS-485) or IRIG-B (digital input) to ±1 millisecond. | |
| – Network Time Protocol (NTP/SNTP). | |
| – Precision Time Protocol (PTP - IEEE 1588 / IEC 61588). | |
| – Time set function from Schneider Electric software server. |
Adaptability
– ION™ frameworks are customizable, scalable applications with object-oriented programming that compartmentalizes functions, and increases flexibility and adaptability.
– Applications include: accessing and aggregating data from downstream Modbus devices over serial or across the network (Modbus TCP/IP), logging and/or processing data through totalization, unit conversion or other calculations, applying complex logic for alarming or control operations, and visualization via webpages.
Standard meter I/O
| • | 3 digital status/counter inputs. |
| • | 1 KY (form A) energy pulse output for interfacing with other systems. |
Advanced Metering Option Modules
| • | Expanding meter’s flexibility with communication and I/O option modules |
| • | Powered from meter base |
I/O Expansion Option Modules
Option modules include:
| • | Digital module: |
| – 6 digital status/counter inputs. |
| – 2 Form C relay outputs, 250 V, 8 A. | |
| • | Analog module: |
– 4 analog inputs (4...20 mA; 0...20 mA; 0...30 V).
– 2 analog outputs (4...20 mA; 0...20 mA; 0...10 V) for interfacing with building management sensors and systems.
Communication Option Modules
Option modules include:
• 4-Wire RS-485 Module (+1):
– Adds 4-wire support to the meter i.e. eliminating the cost and efforts of rewiring while replacing/retrofitting legacy 4-Wire RS-485 systems
– Pluggable screw terminal connector
| • | Fiber-Ethernet Module (+2): |
| – Provides isolated data transmission through fiber optics up to 2000 m |
length
– Supports multi-mode 100Base-FX type
– SC duplex connector
PM8000 series
(+1) Onboard 2-Wire RS-485 port is disabled with the optional module.
(+2) Connected to the meter base using Ethernet patch cable (included with the module)
Maximum of 4 optional modules in total (Fiber-Ethernet, 4-Wires RS-485, I/O modules) can be connected to the meter. Only 1 Fiber-Ethernet and 1 4-Wire RS- 485 option module is supported per meter.
Please refer to the option module Installation Guides for more details.
P B
PowerLogic™ PM8000 connection with Fiber-Ethernet module
ADVANCED METERING� FUNCTIONS AND CHARACTERISTICS
5Version: 1.0 - 12/03/2026
PM8000 series Feature guide
PM8000
Essential
PM8000
Standard
PM8000
Advanced
General
Use on LV, MV, and HV systems b b b
Current accuracy 0.1 % reading 0.1 % reading 0.1 % reading
Voltage accuracy 0.1 % reading 0.1 % reading 0.1 % reading
Active energy accuracy 0.2 Class 0.2 Class 0.2 Class
Number of samples/cycle or sample frequency 256 (+3) 256 512
ION programability b b b
Instantaneous rms values
Current, voltage, frequency b b b
Active, reactive, apparent power Total and per phase b b b
Power factor Total and per phase b b b
Current measurement range (autoranging) 0.05...10 A 0.05...10 A 0.05...10 A
Energy values
Active, reactive, apparent energy b b b
Settable accumulation modes b b b
Demand values
Current Present and max.values b b b
Active, reactive, apparent power Present and max.values b b b
Predicted active, reactive, apparent power b b b
Synchronization of the measurement window b b b
Setting of calculation mode Block, sliding b b b
Power quality measurements
Harmonic distortion Current and voltage b b b
Individual harmonics Via front panel and web page 31 63 63
Via EcoStruxure™ software - 127 127
Waveform capture b (+3) b b
Detection of voltage swells and sags b b b
Fast acquisition 1/2 cycle data b b b
IEC 61000-4-30 Class A/S - S A
EN 50160 Interharmonic - - b
IEC 61000-4-15 - - b
EN 50160 compliance checking - b b
IEEE 519 compliance checking - b b
Disturbance Direction Detection - b b
Rapid Voltage Change - b b
Customizable data outputs (using logic and math functions) b b b
Data recording
Min/max of instantaneous values b b b
Event logs b b b
Trending/forecasting - b b
SER (Sequence of event recording) b b b
Time stamping b b b
GPS synchronization (±1 ms) b b b
Data Recorder 10 50 64
Memory Channels 500 2500 3200
Storage (in Mbytes) 64 512 512
(+3) Waveform capture is limited to 128 Samples/cycle recording.
ADVANCED METERING� FUNCTIONS AND CHARACTERISTICS
Version: 1.0 - 12/03/2026
Commercial references
Essential Standard Advanced Description
METSEPM8140 METSEPM8240 METSEPM8340 96 x 96 panel mount meter, AC/DC power
METSEPM8110 METSEPM8210 METSEPM8310 96 x 96 panel mount meter, LVdc power
METSEPM8143 METSEPM8243 METSEPM8343 DIN rail mount meter, AC/DC power
METSEPM8113 METSEPM8213 METSEPM8313 DIN rail mount meter, LVdc power
METSEPM8144 METSEPM8244 METSEPM8344 DIN rail mount meter with remote display, AC/DC power
METSEPM8114 METSEPM8214 METSEPM8314 DIN rail mount meter with remote display, LVdc power
METSEPM81401 METSEPM82401 METSEPM83401 MID approved panel mount meter (+4)
- METSEPM82403 - RMICAN approved panel mount meter (+5)
METSEPM81404 METSEPM82404 METSEPM83404 RMICAN sealed panel mount meter (+5)
Accessories Description
METSEPM89RD96
Remote display, 3 metre cable, mounting hardware for 30 mm hole (nut & centering pin), mounting hardware for DIN96 cutout (92 x 92 mm) adapter plate
METSEPM89M2600 Digital I/O module (6 digital inputs & 2 relay outputs)
METSEPM89M0024 Analog I/O module (4 analog inputs & 2 analog outputs)
METSECAB10 Display Cable, 10 m
METSEPM8HWK Replacement hardware kit (connectors, screws, retainer clips, mounting template)
METSEPMRS4854W 4-Wire RS 485 option module
METSEPMFIBER Fiber-Ethernet option module
METSEPM8000SK Sealing kit
Feature guide (Contd.)
PM8000
Essential
PM8000
Standard
PM8000
Advanced
Display and I/O
Front panel display b b b
Wiring self-test b b b
Pulse output 1 1 1
Digital or analog inputs (max) 27 digital 16 analog
27 digital 16 analog
27 digital 16 analog
Digital or analog outputs (max, including pulse output) 1 digital 8 relay
8 analog
1 digital 8 relay
8 analog
1 digital 8 relay
8 analog
Communication
2-Wire RS-485 port 1 1 1
Ethernet port 2 2 2
Serial port (Modbus, ION, DNP3) b b b
Ethernet port (Modbus/TCP, ION TCP, DNP3 TCP, DHCP, DNS, IPv4, IPv6, IEC 61850, MQTT, and BACnet/IP ) b b b
Ethernet gateway b b b
Alarm notification via email b b b
HTTP/HTTPs web server with waveform viewer b b b
SNMP with custom MIB and traps for alarms b b b
SMTP email b b b
PTP and NTP time synchronization b b b
FTP file transfer b b b
Option module with 4-Wire RS-485 port b b b
Option module with Fiber-Ethernet port b b b
(+4) For UK + EU only.
(+5) For Canada only.
ADVANCED METERING� FUNCTIONS AND CHARACTERISTICS
7Version: 1.0 - 12/03/2026
PLSED310058EN
https://www.se.com/ww/en/product/METSEPM8240/powerlogic-pm8000-pm8240-panel-mount-meter-intermediate-metering/ https://www.se.com/ww/en/product/METSEPM8210/powerlogic-pm8000-pm8210-lv-dc-panel-mount-meter-intermediate-metering/ https://www.se.com/ww/en/product/METSEPM8243/powerlogic-pm8000-pm8243-din-rail-mount-meter-intermediate-metering/ https://www.se.com/ww/en/product/METSEPM8213/powerlogic-pm8000-pm8213-lv-dc-din-rail-mount-meter-intermediate-metering/ https://www.se.com/ww/en/product/METSEPM8244/powerlogic-pm8000-pm8244-din-rail-mount-meter-+-remote-display-int-metering/ https://www.se.com/ww/en/product/METSEPM8214/powerlogic-pm8000-pm8214-lv-dc-din-rail-mount-meter-+-remote-display-int-/ https://www.se.com/ww/en/product/METSEPM82401/powerlogic-pm8000-pm8240-panel-meter-intermediate-metering-mid-certification/ https://www.se.com/ww/en/product/METSEPM89RD96/powerlogic-pm8000-89rd-remote-display-96x96mm-with-3m-cable-+-mount-acc/ https://www.se.com/ww/en/product/METSEPM89M2600/powerlogic-pm8000-i-o-module-digital-6-inputs-+-2-relays-outputs/ https://www.se.com/ww/en/product/METSEPM89M0024/powerlogic-pm8000-i-o-module-analogue-4-inputs-+-2-outputs/ https://www.se.com/ww/en/product/METSECAB10/powerlogic-pm8000-cable-for-remote-display-rd96-10m/ https://www.se.com/ww/en/product/METSEPM8HWK/powerlogic-series-input-connector-ct-screws-and-panel-mounting-hardware-pm8000/ https://www.se.com/ww/en/product/METSEPMRS4854W/powerlogic-pm8000-communication-module-rs485-4wire-module/ https://www.se.com/ww/en/product/METSEPMFIBER/powerlogic-pm8000-communication-module-fiberethernet-module/ https://www.se.com/ww/en/product/METSEPM8000SK/powerlogic-series-terminal-covers-and-sealing-instructions-for-pm8000/
Technical Specifications Electrical characteristics
Type of measurement True rms to 512 samples per cycle
Measurement accuracy
Current & voltage Class 0.2 as per IEC 61557-12
Active Power Class 0.2 as per IEC 61557-12
Power factor Class 0.5 as per IEC 61557-12
Frequency Class 0.02 as per IEC 61557-12
Active energy Class 0.2S IEC 62053-22 Class 0.2 IEC 61557-12, ANSI C12.20 Class 0.2
Reactive Energy Class 0.5S IEC 62053-24*
MID Directive EN 50470-1, EN 50470-1, AnnexB & AnnexD (optional model)
Display refresh rate 1/2 cycle or 1 second
Input-voltage characteristics
Specified accuracy voltage 57...400 V L-N / 100... 690 V L-L
Impedance 5 MW per phase
Specified accuracy frequency - Frequency
42 to 69 Hz (50/60 Hz nominal)
Limit range of operation - frequency 20...450 Hz
Input-current characteristics
Rated nominal current 1 A (0.2S), 5 A (0.2S) , 10 A (0.2 ANSI)
Specified accuracy current range
Starting Current: 5 mA Accurate Range: 50 mA ...10 A
Permissible overload 200 A rms for 0.5 s, non-recurring
Impedance 0.0003 W per phase
Burden 0.01 VA max at 5 A
Power supply
AC/DC
AC 90...415 Vac ±10 % (50/60 Hz ±10 %) 90...120 Vac +/- 10% (400 Hz)
DC 110...415 Vdc ±15 % (20...60 Vdc ±10 % for PM8210
Ride-through time 100 ms (6 cycles at 60 Hz) min., any condition 200 ms (12 cycles at 60 Hz) typ., 120 Vac 500 ms (30 cycles at 60 Hz) typ., 415 Vac
Burden Typical: 7.7 W / 16 VA at 230 V (50/60 Hz) Fully optioned: max. 18 W / 40 VA at 415 V (50/60 Hz)
Power supply LVdc
DC 20...60 Vdc ±10 %
Burden Fully optioned: max. 18 W at 18...60 Vdc
Input/outputs
Meter Base Only 3 digital inputs (30 Vac/60 Vdc) 1 form A (KY) solid state digital output (30 Vac/60 Vdc, 75 mA)
Optional Digital - 6 digital inputs (30/60 Vdc) wetted + 2 form C relay outputs (250 Vac, 8 A)
Analog - 4 analog inputs (4...20 mA, 0...30 V DC) + 2 analog outputs (4...20 mA, 0...10 Vdc)
Mechanical characteristics
Weight
Integrated Display Model 0.581 kg DIN rail mounted Model 0.528 kg IO modules 0.140 kg Remote display 0.300 kg
IP degree of protection IP 54, UL type 12: Panel mount and Remote display, front IP 30: Panel mount rear, DIN rail mount, I/O modules
Excellent quality ISO 9001 and ISO 14000 certified manufacturing
Dimensions
Panel mount model 96 x 96 x 77.5 mm
DIN model 90.5 x 90.5 x 90.8 mm
Remote display 96 x 96 x 27 mm
IO modules 90.5 x 90.5 x 22 mm
Environmental conditions
Operating temperature -25...70 ºC
Remote Display Unit -25... 60 ºC
Storage temperature -40...85 ºC
Humidity rating 5 ...95 % non-condensing
Installation category III
Operating altitude (maximum) 3000 m above sea-level
Electromagnetic compatibility
EMC standards IEC 62052-11 and IEC 61326-1
Immunity to electrostatic discharge IEC 61000-4-2
Immunity to radiated fields IEC 61000-4-3
Immunity to fast transients IEC 61000-4-4
Immunity to surges IEC 61000-4-5
Immunity to conducted disturbances IEC 61000-4-6
Immunity to power frequency magnetic fields IEC 61000-4-8
Immunity to conducted disturbances, 2-150kHz CLC/TR 50579
Immunity to voltage dips & interruptions IEC 61000-4-11
Immunity to ring waves IEC 61000-4-12
Conducted and radiated emissions EN 55022, EN 55011, FCC part 15 Class B, EN55011, EN55022 Class B, ICES-003 Class B
Surge withstand Capability (SWC) IEEE / ANSI C37.90.1
PM8000 series
ADVANCED METERING� FUNCTIONS AND CHARACTERISTICS
Version: 1.0 - 12/03/2026
Technical Specifications(Contd.)
Safety
Safety Construction IEC/EN 61010-1 ed.3, CAT III, 400 V L-N / 690 V L-L UL 61010-1 ed.3 and CSA-C22.2 No. 61010-1 ed.3, CAT III, 347 V L-N / 600 V L-L IEC/EN 62052-11, protective class II
Communication
Ethernet to serial line gateway Communicates directly with up to 31 unit load devices
Web server Customisable pages, new page creation capabilities, HTML/XML compatible
Serial port RS-485 Baud rates of 2400 to 115200, pluggable screw terminal connector
Ethernet port(s) 2x 10/100BASE-TX, RJ45 connector (UTP)
Protocol BACnet/IP, Modbus, ION, MQTT, DNP3, IEC 61850, HTTPS, FTP, SNMP, SMTP, DPWS, RSTP, NTP, PTP, NTP/SNTP, GPS, IPv4 /IPv6, DHCP and Syslog protocols
Communication Option Modules
Optional 4-Wire RS-485 serial port
Baud rates of 2400 to 115200, pluggable screw terminal connector
Optional Fiber-Ethernet port Ethernet patch cable from base meter, multi-mode 100Base-FX, SC duplex connector
Firmware characteristics
High-speed data recording Down to 1/2 cycle interval burst recording, stores detailed characteristics of disturbances or outages. Trigger recording by a user-defined setpoint, or from external equipment
Harmonic distortion Up to 63rd harmonic (127th via Schneider Electric software) for all voltage and current inputs
Sag/swell detection Analyse severity/potential impact of sags and swells: magnitude and duration data suitable for plotting on voltage tolerance curves per phase triggers for waveform recording, control
Disturbance direction detection Determine the location of a disturbance more quickly and accurately by determining the direction of the disturbance relative to the meter. Analysis results are captured in the event log, along with a timestamp and confidence level indicating level of certainty
Instantaneous High accuracy of standard speed (1s) and high-speed (1/2 cycle) measurements, including true rms per phase and total for: voltage, current, active power (kW),reactive power (kvar), apparent power (kVA), power factor, frequency, voltage and current unbalance, phase reversal
Load profiling Channel assignments (Up to 3200 Channels via 64 data recorders) configurable for any measurable parameter, including historical trend recording of energy, demand, voltage, current, power quality, or any measured parameter.
Trigger recorders based on time interval, calendar schedule, alarm/event condition, or manually
Trend curves Historical trends and future forecasts to better manage demand, circuit loading, and other parameters. Provides average, min, max and standard deviation every hour for last 24 hours, every day for last month, every week for last 8 weeks and every month for last 12 months
Waveform captures Simultaneous capture of all voltage and current channels, sub-cycle disturbance capture, ability to record from 320 cycles at 512 sample per cycle to over 2880 cycles at 16 points per cycle with user selectable sampling speed as well as pre- and post-trigger length
Alarms Threshold alarms: adjustable pickup and dropout setpoints and time delays, numerous activation levels possible for a given type of alarm, user-defined or automatic alarm threshold settings, user-defined priority levels (optional automatic alarm setting)
Advanced Time of Use (TOU) 6 seasons; 3 different day types: weekend, weekday, and holiday; up to 8 tariffs per day type
Advanced security Up to 50 users with unique access rights. Perform resets, time sync, or meter configurations based on user privileges
Storage 512 MB
Firmware update Update via the communication ports
Display characteristics
Integrated or Remote display 320 x 240 (1/4 VGA) Color LCD, configurable screens, 5 buttons and 2 LED indicators (alarm and meter status)
Languages English, French, Spanish, Russian, Portugese, German, Italian, Chinese
Notations IEC, IEEE
The HMI menu includes
Alarms Active alarms, historic alarms (50+ alarms)
Basic Reading Voltage, current, frequency, power summary
Power Power summary, demand, power factor
Energy Energy total, delivered, received
Events Timestamped verbose event log
Power Quality EN 50160, IEEE 519, harmonics, phasor diagrams
Inputs/Outputs Digital inputs, digital outputs, analog inputs, analog outputs
Nameplate Model, serial and FW version
Custom Screens Build your own metrics
Setup Menu Meter setup, communications setup, display setup, date/time/clock setup, alarm setup, language setup, time of use setup, resets, password setup
PM8000 series
ADVANCED METERING� FUNCTIONS AND CHARACTERISTICS
9Version: 1.0 - 12/03/2026
PM8000 panel mount meter dimensions
PM8000 DIN rail mount meter dimensions
PM8000 with I/O modules dimensions
Please see the appropriate Installation Guide for accurate and complete information on the installation of this product.
P B
P B
P B
P B
P B
PM8000 series P
B
PM8000 remote display dimensions
PM8000 with communication option modules
P B
P B
ADVANCED METERING� DIMENSIONS AND CONNECTION
Version: 1.0 - 12/03/2026
PM8000 series parts
P B
P B
Alarm icon
Display
Navigation icons
Up
Down
Select
Cancel
Edit
More
Navigation buttons
Home button
Alarm LED (red)
Bar graph
R
V
S
T
P
Q
U
Voltage inputs
Control power
Digital inputs
Revenue lock LED (green)
Status LED (green/red)
Revenue lock switch
Digital output
Sealing gasket
Infrared energy pulsing LED
Energy pulsing LED
RS-485
Current inputs
Ethernet (2)
Date/time
Revenue lock iconO
L
M
N
K
A
B
C
D
E
F
G
H
I
J
ADVANCED METERING� DIMENSIONS AND CONNECTION
Version: 1.0 - 12/03/2026
Schneider Electric Industries SAS
35, Rue Joseph Monier
CS 30323
92506 Rueil Malmaison Cedex
France
RCS Nanterre 954 503 439
Capital social 928 298 512 € www.se.com
March 2026
PowerLogic™ PM8000 Series
PLSED310058EN
© 2026 - Schneider Electric. All rights reserved.
All trademarks are owned by Schneider Electric
Industries SAS or its affiliated companies.
As standards, specifications and designs develop from time to time, please ask for confirmation of the information given in this document.