Attachment B Drawings~14.pdf
PDF 7 MB Posted
- Solicitation number
- S-63400-00011304
- Issued by
- Tillamook County, Moro City, Oregon
About this file
This document contains structural drawings and notes for the construction of Oregon Parks and Recreation Department (OPRD) cabins at Nehalem State Park. The project includes the structural design for 6 cabin buildings, including foundations, floors, walls, and roofs. The structural notes provide the design criteria, materials, and construction requirements. Special inspection and testing requirements are also outlined. The structural plans include a foundation plan, floor framing plan, roof framing plan, and various structural details. The project is located at 34600 Garey St, Nehalem, OR 97131.
The structural notes specify the design criteria, including live loads, snow loads, wind loads, and seismic design. The lumber species, grades, and sheathing requirements are provided. Connector and fastening details are also included. The structural plans provide the dimensions, framing members, and hold-down requirements for the foundations, floors, walls, and roofs of the cabins.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Attachment C Structural Calculations~2.pdf | ||
| ITB 10654 Nehalem Bay Staff Housing Cabins Building Project.docx | DOCX document | |
| Attachment A Technical Specifications~1.docx | DOCX document | |
| BID TABULATION~4.docx | DOCX document | |
| Addendum 2 to ITB 10654 Nehalem Bay Staff Housing Cabins Building Project.docx | DOCX document | |
| Attachment E Nehalem Bay Site Improvement Plans.pdf | ||
| RFP HVAC Aug 2024.doc | DOC document | |
| Pre-Bid sign-in sheet.docx | DOCX document | |
| Addendum 1 to ITB 10654 Nehalem Bay Staff Housing Cabins Building Project.docx | DOCX document | |
| Attachment D Tillamook County Dune Permit.pdf | ||
| Addendum 3 Attachment B Revised Drawing Sheets.pdf | ||
| Addendum 3 to ITB 10654 Nehalem Bay State Park Staff Cabin Project.docx | DOCX document | |
| Intent to Award~11.docx | DOCX document |
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STRUCTURAL NOTES
ORPD CABINS NEHALEM STATE PARK - VLMK JOB #20220299
DIVISION 1 - GENERAL
A. GENERAL
1. THESE DRAWINGS HAVE BEEN PREPARED SOLELY FOR USE IN THE CONSTRUCTION OF:
A. OREGON PARKS AND RECRETATION DEPARTMENT NEHALEM CABINS
B. 34600 GAREY ST, NEHALEM, OR 97131
C. POSSESSION OF THESE DRAWINGS DOES NOT GRANT A LICENSE TO CONSTRUCT OR
FABRICATE THE WHOLE, OR PARTS OF THIS PROJECT IN OTHER LOCATIONS.
2. THESE NOTES SET MINIMUM STANDARDS FOR CONSTRUCTION. THE DRAWINGS GOVERN OVER
THE GENERAL NOTES TO THE EXTENT SHOWN.
3. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS ON DRAWINGS AND IN FIELD.
COORDINATE LOCATIONS OF OPENINGS THROUGH FLOORS, ROOFS AND WALLS WITH
ARCHITECTURAL, MECHANICAL AND ELECTRICAL DRAWINGS. NOTIFY ENGINEER OF ANY
DISCREPANCIES OR IF ACTUAL CONDITIONS DIFFER FROM THOSE SHOWN OR NOTED.
4. CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR THE DESIGN AND INSTALLATION OF ALL
TEMPORARY BRACING, SHORING, ANCHORS, ETC., INCLUDING, BUT NOT LIMITED TO, WALL AND ROOF BRACING, LIFTING AND HANDLING INSERTS AND DEVICES, TRENCH SHORING, FORMS, ETC.
5. CONTRACTOR SHALL CONSIDER CONSTRUCTION LOADS WHENEVER SUCH LOADS ARE IN EXCESS OF NORMAL DESIGN LOADS. PARTICULAR ATTENTION SHOULD BE GIVEN TO CRANES, FORKLIFTS, WORKMAN, WHEEL LOADS, STORAGE OF MATERIALS, ETC. CONTRACTOR SHALL BE SOLELY
RESPONSIBLE FOR ALL SHORING, BRACING, CRIBBING, ETC. REQUIRED TO SUPPORT
CONSTRUCTION LOADS.
6. INSPECTION AND/OR JOB SUPERVISION IS NOT PROVIDED BY ENGINEER.
7. WHERE REFERENCE IS MADE TO ASTM, AISC, ACI, ASCE OR OTHER STANDARDS, THE LATEST
ISSUE SHALL APPLY.
8. ALL WORK SHALL BE IN STRICT COMPLIANCE WITH:
A. 2022 OREGON STRUCTURAL SPECIALTY CODE.
(BASED ON THE 2021 INTERNATIONAL BUILDING CODE)
B. ALL OTHER STATE AND LOCAL BUILDING REQUIREMENTS THAT APPLY.
9. DESIGN CRITERIA:
a. FLOOR LIVE LOADS (PER IBC 1603.1.1)
CABIN FLOOR 40 PSF
b. ROOF LIVE LOADS (PER IBC 1603.1.2)
MINIMUM 20 PSF
c. ROOF SNOW LOAD (PER IBC 1603.1.3)
FLAT-ROOF SNOW LOAD (Pf) 25 PSF SNOW DRIFT SURCHARGE AND WIDTH (Pd, W) SEE DWGS SNOW EXPOSURE FACTOR (Ce) 1.0 SNOW LOAD IMPORTANCE FACTOR (Is) 1.0 THERMAL FACTOR (Ct) 1.0
d. WIND LOAD (PER IBC 1603.1.4) ULTIMATE DESIGN WIND SPEED (Vult) 135 MPH NOMINAL DESIGN WIND SPEED (Vasd) 105 MPH
RISK CATEGORY II
WIND EXPOSURE C
INTERNAL PRESSURE COEFFICIENT (GCpi) ±0.18
e. EARTHQUAKE DESIGN DATA (PER IBC 1603.1.5) SEISMIC IMPORTANCE FACTOR (Ie) 1.0
RISK CATEGORY II
MAPPED SPECTRAL RESPONSE ACCELERATIONS Ss = 1.28 S1 = 0.67
SITE CLASS D
DESIGN SPECTRAL RESPONSE COEFFICIENTS Sds = 0.85 Sd1 = 0.76
SEISMIC DESIGN CATEGORY D
BASIC SEISMIC-FORCE-RESISTING SYSTEM LIGHT FRAME WOOD SHEAR WALLS
ANALYSIS PROCEDURE USED EQUIVALENT LATERAL FORCE
10. MECHANICAL EQUIPMENT, MECHANICAL AND SPRINKLER PIPING LARGER THAN 2 INCHES IN
DIAMETER OR ANY OTHER ITEMS PRODUCING A HANGER OR SUPPORT LOAD OF OVER 50
POUNDS SHALL BE HUNG BY A SYSTEM APPROVED BY ENGINEER. ANY HANGER OR SUPPORT
PRODUCING A LOAD OVER 200 POUNDS SHALL HAVE ADDITIONAL FRAMING INSTALLED TO
TRANSFER THESE LOADS TO THE MAIN STRUCTURAL BEAMS OR WALL UNLESS OTHERWISE
APPROVED.
11. WHERE REQUIRED, SEISMIC BRACING FOR MECHANICAL AND ELECTRICAL EQUIPMENT,
SPRINKLER PIPING OR OTHER NON-STRUCTURAL COMPONENTS SHALL BE PROVIDED BY THE
CONTRACTOR IN ACCORDANCE WITH CHAPTER 13 OF ASCE 7. STRUCTURAL CALCULATIONS AND
DETAILS STAMPED BY A LICENSED ENGINEER SHALL BE SUBMITTED TO ENGINEER FOR REVIEW.
12. PROVIDE SHOP DRAWINGS FOR ALL STRUCTURAL PRODUCTS DELIVERED TO THE PROJECT.
ENGINEER WILL REVIEW AND MARK-UP ELECTRONIC SUBMITTALS IN PDF FORMAT OR A MAXIMUM
OF THREE HARD COPIES OF SUBMITTALS. THE CONTRACTOR WILL BE RESPONSIBLE FOR
DUPLICATING MARK-UPS IF ADDITIONAL COPIES ARE REQUIRED. SUBMITTALS WILL BE REVIEWED
AND RETURNED TO THE GENERAL CONTRACTOR WITHIN TWO WEEKS. ALL SUBMITTALS SHALL BE
REVIEWED AND STAMPED BY THE CONTRACTOR PRIOR TO SUBMITTAL TO THE ENGINEER.
DIVISION 2 - SITE WORK (NOT USED)
DIVISION 4 - MASONRY - NOT USED
DIVISION 3 - CONCRETE AND REINFORCING (NOT USED)
DIVISION 5 - METAL
A. GENERAL
1. ALL STRUCTURAL MEMBERS TO BE DETAILED, FABRICATED AND ERECTED IN ACCORDANCE
WITH THE LATEST EDITION OF AISC STANDARDS.
B. MATERIALS
1. ANCHOR BOLTS AND WOOD CONNECTIONS TO BE A307. PROVIDE STANDARD PLATE WASHERS
UNDER ALL BOLT HEADS AND NUTS IN CONTACT WITH WOOD.
2. ANCHOR RODS TO BE ASTM F1554, GRADE 36 UNLESS OTHERWISE NOTED.
3. LAG BOLTS IN WOOD TO BE SAE J429 GRADE 1 WITH MINIMUM DIMENSIONS MEETING ANSI/ASME B.18.2.1.
C. POST-INSTALLED ANCHOR BOLTS:
1. UNLESS A SPECIFIC ANCHOR PRODUCT IS NOTED IN THE DRAWINGS, POST-INSTALLED
ANCHORS MAY USE ONE OF THE ANCHORS LISTED BELOW FOR THE REQUIRED TYPE AND BASE
MATERIAL. OTHER ANCHORS ARE ACCEPTABLE ONLY WITH PRIOR WRITTEN APPROVAL OF THE
ENGINEER.
2. INSTALL ALL ANCHORS PER MANUFACTURER'S INSTRUCTIONS AND PRODUCT EVALUATION
REPORTS.
3. EMBEDMENT SPECIFIED ON DRAWINGS FOR ADHESIVE ANCHORS ARE ‘EFFECTIVE’ EMBEDMENT.
‘NOMINAL’ EMBEDMENT IS SPECIFIED FOR EXPANSION AND SCREW ANCHORS, UNLESS
OTHERWISE NOTED. REFERENCE MANUFACTURER LITERATURE FOR MEASURING TOTAL
EMBEDMENT AND HOLE DEPTH REQUIREMENTS.
4. NOTE THAT ADHESIVE ANCHOR INSTALLATION TEMPERATURES AND CURE TIMES VARY BY
PRODUCT. CONSULT MANUFACTURER LITERATURE FOR SPECIFIC REQUIREMENTS.
5. ALL EXPANSION AND SCREW ANCHORS SPECIFIED AT EXTERIOR LOCATIONS OR EXPOSED TO
THE ELEMENTS SHALL BE THE STAINLESS STEEL VERSION PER EACH APPROVED
MANUFACTURER. EPOXY ANCHORS SPECIFIED AT EXTERIOR LOCATIONS OR EXPOSED TO THE
ELEMENTS SHALL USE STAINLESS STEEL OR HOT DIPPED GALVANIZED THREADED ROD.
6. SPECIAL INSPECTION OF ANCHOR INSTALLATION IS REQUIRED UNLESS SPECIFICALLY NOTED
OTHERWISE IN DRAWINGS. SEE SPECIAL INSPECTION AND MATERIALS TESTING PROGRAM AND
NOTES.
7. NO STEEL REINFORCEMENT SHALL BE CUT TO INSTALL ANCHORS WITHOUT THE PRIOR WRITTEN
APPROVAL OF THE ENGINEER.
8. ADHESIVE ANCHORS:
BASE MATERIAL PRODUCT REPORT#
CONCRETE SIMPSON SET-XP EPOXY ADHESIVE ANCHOR ICC ESR-2508
CONCRETE SIMPSON AT-XP ADHESIVE ANCHOR APMO ER-263
CONCRETE HILTI HIT-HY 200 ADHESIVE ANCHOR ICC ESR-3187
9. EXPANSION ANCHORS:
BASE MATERIAL PRODUCT REPORT#
CONCRETE SIMPSON STRONG-BOLT 2 WEDGE ANCHOR ICC ESR-3037
CONCRETE HILTI KWIK BOLT TZ ANCHOR ICC ESR-1917
10. SCREW ANCHORS:
BASE MATERIAL PRODUCT REPORT#
CONCRETE SIMPSON TITEN HD SCREW ANCHOR ICC ESR-2713
CONCRETE HILTI KWIK HUS-EZ SCREW ANCHOR ICC ESR-3027
2. PROVIDE FIRE BLOCKING AS REQUIRED AND BLOCKING FOR ALL SPECIFIED WALL-MOUNTED ITEMS
INCLUDING CABINETS, DOORSTOPS, ETC.
3. CONNECTORS:
a. TIE STRAPS, FRAMING ANCHORS, HANGERS, STIRRUPS, COLUMN CAPS, COLUMN BASES, ETC., TO BE SIMPSON AS DETAILED, OR AS APPROVED.
b. FULLY FASTEN ACCORDING TO MANUFACTURER'S SCHEDULE USING LARGEST SIZE SHOWN.
c. ALL BEAMS AND JOISTS NOT BEARING ON ANOTHER MEMBER TO CONNECT WITH 'U' TYPE
HANGERS UNLESS OTHERWISE NOTED ON DRAWINGS.
d. NAILING: ALL NAILS SPECIFIED IN THE DRAWINGS TO BE "COMMON" NAILS UNLESS OTHERWISE
NOTED. ALL NAILING SHALL COMPLY WITH IBC FASTENING SCHEDULE PER CHAPTER 23.
OBTAIN ENGINEERS APPROVAL OF ALL PROPRIETARY NAILING SYSTEMS.
e. NAILS AT ROOF, FLOOR, AND WALL DIAPHRAGMS TO BE DRIVEN SO THAT THEIR HEAD OR
CROWN IS FLUSH WITH THE SURFACE OF THE SHEATHING. CHECK AND RESINK IF NEEDED,
IMMEDIATELY BEFORE ROOFING.
f. BOLTS - SEE DIVISION 5, METAL.
g. CORROSION PROTECTION:
1. CONFIRM REQUIRED CORROSION PROTECTION FOR HARDWARE AND FASTENERS WITH
SPECIFIC RECOMMENDATIONS FROM PRESSURE TREATING MANUFACTURER OR HANGER
MANUFACTURER (USE MOST CONSERVATIVE) FOR SPECIFIC WOOD TREATMENTS USED.
2. MINIMUM CORROSION PROTECTION ON METAL CONNECTORS EXPOSED TO THE
ENVIRONMENT OR PRESSURE TREATED LUMBER TO BE PER ASTM A653 CLASS 185
(SIMPSON ZMAX) OR ASTM A123.
3. FASTENERS FOR PRESSURE TREATED LUMBER MUST BE MINIMUM HOT-DIP GALVANIZED,
STAINLESS STEEL, SILICON BRONZE OR COPPER.
4. HOT-DIP GALVANIZED HARDWARE AND FASTENERS MUST COMPLY WITH ASTM A153,
STAINLESS STEEL FASTENERS TO BE TYPE 304 OR TYPE 316.
5. HARDWARE AND FASTENERS USED TOGETHER MUST BE THE SAME TYPE (E.G. HOT-DIP
GALVANIZED NAILS WITH HOT-DIP GALVANIZED HANGERS).
4. DELIVERY AND STORAGE: ALL LUMBER AND SHEATHING DELIVERED TO THE SITE, SHALL BE
STACKED OR STORED OFF THE GROUND AND PROPERLY PROTECTED AGAINST WEATHER.
5. CUTTING AND NOTCHING OF JOISTS NOT ALLOWED. A 1 INCH DIAMETER HOLE MAY BE DRILLED IN
THE CENTER 1/3 OF THE MEMBER DEPTH. ALL OTHER HOLES TO BE APPROVED BY ENGINEER.
6. STUDS MAY BE NOTCHED IN THE LOWER 1/5 OF THE HEIGHT OF THE STUD FOR ELECTRIC AND PLUMBING PIPES, BUT NO PART OF THE NOTCH IS TO BE DEEPER THAN 25 PERCENT OF THE WIDTH OF THE STUD. HOLES OF DIAMETERS UP TO 1/3 OF WIDTH OF STUD MAY BE DRILLED IN THE STUD.
DIVISION 6 - WOOD
A. ROUGH CARPENTRY
1. LUMBER SPECIES AND GRADES TO BE AS FOLLOWS UNLESS OTHERWISE SHOWN ON DRAWINGS:
JOISTS, BEAMS & STRINGERS: DOUGLAS FIR #2
6 INCH NOMINAL AND GREATER: DOUGLAS FIR #1
BUCKS, BLOCKING, BRIDGING AND MISCELLANEOUS: DOUGLAS FIR OR HEM FIR #3
2x STUDS: DOUGLAS FIR #2
SILLS, LEDGERS, STRIPPING, ETC. IN CONTACT PRESSURE TREATED HEM FIR #2
WITH CONCRETE, AND WOOD CURBS:
PLATES AND HEADERS: KILN DRIED DOUGLAS FIR #2
POSTS, COLUMNS (SAWN): DOUGLAS FIR #1
ROOF, FLOOR AND WALL SHEATHING:
APA RATED SHEATHING, EXPOSURE 1, CONFORMING TO APA PERFORMANCE STANDARD PS
1-95 AND EXCERPT NER-108. SEE DRAWINGS FOR REQUIRED THICKNESS OF SHEATHING
AND/OR SPAN RATING. INSTALL ROOF AND FLOOR SHEATHING WITH LONG DIMENSION
PERPENDICULAR TO SUPPORTS UNLESS OTHERWISE NOTED. USE SPACERS TO PROVIDE 1/8
INCH END AND EDGE JOINTS WHENEVER SHEATHING IS EXPOSED TO WET WEATHER. FILL ANY
JOINT SPACING OVER 3/8 INCH UNLESS OTHERWISE APPROVED BY ENGINEER. INSTALL 2x4
OR THICKER BLOCKING AT UNSUPPORTED JOINTS IN WALL SHEATHING. BLOCK ROOF AND
FLOOR SHEATHING WHERE NOTED ON DRAWINGS.
GLULAM BEAMS:
• Fb = 2,400 PSI, E = 1,800,000 PSI PER ANSI A190.1 SPECIFICATION.
• SIMPLE SPANS COMBINATION: 24F-V4
• CANTILEVER SPANS COMBINATION: 24F-V8
• SUBMIT CERTIFICATE OF CONFORMANCE INDICATING MEMBERS MEET THE REQUIREMENTS
OF ANSI A190.1
.2
.2
A d d e n d u m
10116
36857
S T
A F
F H
O U
S
IN
G P
R O
J E
C T
C A
B
IN
B U
IL
D
IN
G
P L
A N
S N
E H
A L
E M
B A
Y S
T A
T E
P A
R K
B J P
P A R K
SO
N
E G
O R S T A T E
O R E G O N
P A R K S
A N D
R E C R E A
TI
O N
D E P A R
TM
E N T
D E S
IG
N E D
B Y
A P P R O V E D
B Y
C H E C K E D
B Y
D R A W N
B Y
D A T E
R E V
IS
IO
N
D A T E
B Y
SHEET:
OPRIS#: CONTRACT #:
.1
.2
A d d e n d u m
C
A B
IN
V
E B
J P
.2
.2
A d d e n d u m
O
P R
D C
O M
M E
N T
S B
J P
.3
.2
A d d e n d u m
O
P R
D C
O M
M E
N T
S R
J S
B J P
J J E
B J P
J J E
/3
/2
S0.0
S T
R U
C T
R U
A L
N O
T E
S
EXP. 12/31/2025
CODE REQUIRED SPECIAL INSPECTION AND MATERIALS TESTING PROGRAM
WOOD:
ROOF-DIAPHRAGM SHEATHING AND NAIL SPACING
PRE-FABRICATED WOOD SHEAR PANEL CONNECTIONS
AND HOLDOWNS
SHEARWALL SHEATHING, NAIL SPACING AND HOLDOWNS
PRE-FABRICATED STRUCTURAL ELEMENTS
ARCHITECTURAL:
CEILING CLIPS
COMMENTS DURATION INSPECTION AGENCY
P
P
P
P
P
TESTING LAB
TESTING LAB
TESTING LAB
TESTING LAB
TESTING LAB
PER ICC EVALUATION REPORT
1. DURATION REFERS TO TIME AND FREQUENCY OF INSPECTION FOR THE PORTIONS OF WORK INDICATED.
C = CONTINUOUS INSPECTION IN WHICH THE SPECIAL INSPECTOR IS ON SITE AT ALL TIMES, OBSERVING THE WORK
REQUIRING SPECIAL INSPECTION.
P = PERIODIC INSPECTION IN WHICH THE SPECIAL INSPECTOR IS ON SITE AT TIME INTERVALS NECESSARY TO CONFIRM
THAT THE WORK REQUIRING SPECIAL INSPECTION IS IN CONFORMANCE WITH APPROVED PERMIT DRAWINGS AND
SPECIFICATIONS.
2. THE INSPECTION AGENCIES ARE AS FOLLOWS:
TESTING LAB: TO BE DETERMINED
TESTING LAB SHALL PERFORM INSPECTIONS OF ALL PORTIONS OF WORK DESIGNATED IN THE PROGRAM. THE SELECTED INSPECTION AGENCY SHALL BE AN ACCREDITED, APPROVED SPECIAL INSPECTION AGENCY EMPLOYED BY THE PROJECT
MANAGER, NOT THE CONTRACTOR OR SUB CONTRACTOR, PER IBC SECTION 1704.2.
3. PRIOR TO THE BEGINNING OF CONSTRUCTION, THE ARCHITECT (OR ENGINEER) SHALL CALL A PRE-CONSTRUCTION MEETING WITH THE ARCHITECT, ENGINEER, BUILDING OFFICIAL, CONTRACTOR, AND SPECIAL INSPECTORS TO REVIEW THE SPECIAL INSPECTION REQUIREMENTS. THE STRUCTURAL OBSERVATION REQUIREMENTS SHALL ALSO BE DISCUSSED DURING THIS
MEETING.
4. DUTIES OF THE CONTRACTOR INCLUDE, BUT ARE NOT LIMITED TO:
A. NOTIFY THE SPECIAL INSPECTOR THAT THE WORK IS READY FOR INSPECTION AT LEAST 24 HOURS BEFORE SUCH
INSPECTION.
B. ALL WORK REQUIRING SPECIAL INSPECTION SHALL REMAIN ACCESSIBLE AND EXPOSED UNTIL IT HAS BEEN OBSERVED
AND INDICATED TO BE IN CONFORMANCE BY THE SPECIAL INSPECTOR AND APPROVED BY THE BUILDING OFFICIAL.
C. PROVIDE THE SPECIAL INSPECTOR WITH ACCESS TO APPROVED PERMIT DRAWINGS AND SPECIFICATIONS AT THE JOB
SITE.
D. MAINTAIN AT THE JOB SITE, COPIES OF ALL REPORTS SUBMITTED BY THE SPECIAL INSPECTOR.
5. IN ADDITION TO THE INSPECTION AND TESTING REQUIREMENTS INDICATED IN THE IBC, THE FOLLOWING SHALL ALSO APPLY:
A. MOISTURE TESTS PRIOR TO INSULATION
SPECIAL INSPECTION PROGRAM NOTES:
APPROVED FABRICATORS:
CERTIFICATE OF COMPLIANCE MUST BE SUBMITTED TO THE
ARCHITECT OR ENGINEER OF RECORD FOR ALL OFF-SITE
FABRICATION SUCH AS STRUCTURAL STEEL, OPEN-WEB STEEL
JOISTS AND GIRDERS, GLU-LAMS AND PRE-CAST CONCRETE
P TESTING LAB
.2
.2
A d d e n d u m
10116
36857
S T
A F
F H
O U
S
IN
G P
R O
J E
C T
C A
B
IN
B U
IL
D
IN
G
P L
A N
S N
E H
A L
E M
B A
Y S
T A
T E
P A
R K
B J P
P A R K
SO
N
E G
O R S T A T E
O R E G O N
P A R K S
A N D
R E C R E A
TI
O N
D E P A R
TM
E N T
D E S
IG
N E D
B Y
A P P R O V E D
B Y
C H E C K E D
B Y
D R A W N
B Y
D A T E
R E V
IS
IO
N
D A T E
B Y
SHEET:
OPRIS#: CONTRACT #:
.1
.2
A d d e n d u m
C
A B
IN
V
E B
J P
.2
.2
A d d e n d u m
O
P R
D C
O M
M E
N T
S B
J P
.3
.2
A d d e n d u m
O
P R
D C
O M
M E
N T
S R
J S
B J P
J J E
B J P
J J E
/3
/2
S0.1
S P
E C
IA
L
I N
S P
E C
T
IO
N
11' - 5 1/2" 12' - 0" 6' - 11 1/2"
33 3
NOTE:
ALL DIMENSIONS TO CENTERLINE OF BEAMS ABOVE
H D U
H D U
H D
U
H D
U
S3.1
TYP
S3.1
S3.1
S3.1
S3.1
AT
CABIN 3
ONLY
AT
CABIN 3
ONLY
CONCRETE FOOTING PER SCHEDULE THIS SHEET
FOUNDATION LEGEND:
H D
U X
SIMPSON HOLDOWN PER PLAN
6x6 POST
1. CONTRACTOR TO VERIFY ALL DIMENSIONS AND ELEVATIONS WITH
ARCHITECTURAL DRAWINGS.
2. CONTRACTOR TO VERIFY ALL FOOTING ELEVATIONS WITH THE
FOLLOWING CRITERIA: TOP OF FOOTING TO BE MINIMUM 12"
BELOW FINISH GRADE AND FINISH FLOOR. BOTTOM OF FOOTING
TO BE A MINIMUM OF 18" BELOW FINISH GRADE.
3. SEE GEOTECHNICAL REPORT FOR SUBGRADE PREPARATION AND
COMPACTION TO SUPPORT FOUNDATIONS AND CONCRETE SLAB
ON GRADE.
FOUNDATION NOTES:
6x12 6x12 6x10
6x106x126x12 x x
6x12 6x12
6x10
2x10 AT 24" O.C.
(TYPICAL U.O.N.)
x x x x x
A
A
A
B
B
(3) 2x6
JA
M
B S
TU
D S
(3) 2x6
JA
M
B S
TU
D S
(3 ) 2 x6
JA
M B
S
TU
D S
(3) 2x6
JA
M
B S
TU
D S
H D U
H D U
H D
U
H D
U
4x
S3.1
S3.1
S3.1
S3.1
2x6 DOUG FIR #2 STUDS AT 16" O.C. TYPICAL U.O.N.
ON PLAN. ALIGN JOISTS WITH STUDS
FOOTING BELOW PER FOUNDATION PLAN
FLOOR FRAMING LEGEND:
WOOD POST PER FOUNDATION PLAN
X
SHEAR WALL TYPE PER SCHEDULE THIS SHEET. ALL
EXTERIOR WALLS TO BE TYPE 'A' SHEAR WALLS
UNLESS OTHERWISE NOTED
TYPICAL HEADER TO BE PER FLOOR FRAMING NOTESHDR
FLOOR FRAMING NOTES:
1. CONTRACTOR TO VERIFY ALL DIMENSIONS AND ELEVATIONS
WITH ARCHITECTURAL DRAWINGS.
2. FLOOR DESIGN CRITERIA:
DEAD LOAD = 15 PSF
LIVE LOAD = 40 PSF
DEFLECTION = SMALLER OF LL/360, TL/240
3. FLOOR SHEATHING TO BE T&G APA RATED STURD-I-FLOOR
SHEATHING WITH A MINIMUM SPAN RATING OF 24oc AND
MINIMUM THICKNESS OF 3/4". GLUE WITH CONTINUOUS WAVY
3/8" BEAD AT ALL SUPPORTS AND NAIL AS INDICATED BELOW.
ORIENT STRONG AXIS OF SHEATHING PERPENDICULAR TO
SUPPORTS.
4. FLOOR NAILING TO BE 10d RING OR SCREW SHANK NAILS WITH A
MINIMUM 1 5/8" PENETRATION. NAIL AT 6" O.C. AT ALL
SUPPORTED EDGES AND AT 12" O.C. AT INTERMEDIATE
SUPPORTS. BLOCKING IS NOT REQUIRED.
5. SPLICE DOUBLE TOP PLATE AT ALL EXTERIOR WALLS AND
SHEARWALLS BY LAPPING 6'-0" MINIMUM AND NAILING WITH 16d
AT 4" O.C. STAGGERED.
6. TYPICAL HEADERS (HDR) TO BE PER , U.O.N.
7. AT BEAM TO POST CONNECTIONS USE SIMPSON 'AC' OR 'ACE'
POST CAP TYPICAL, U.O.N.
8. ALL SOLID SAWN HEADERS, PLATES (OTHER THAN P.T.) AND
HORIZONTAL MEMBERS TO BE KILN DRIED (K.D.) LUMBER.
9. ALL EXTERIOR WALLS TO BE SHEATHED PER SHEAR WALL TYPE
'A'. SEE SCHEDULE FOR REQUIREMENTS.
10. PROVIDE DOUBLE JOIST BELOW INTERIOR NON-BEARING WALLS
RUNNING PARALLEL WITH JOISTS.
11. SOLID BLOCK AT RIM LOCATIONS WHERE POSTS OR BUILT-UP
STUDS ARE BEARING.
(3/ S3.0)
D
TT2Z
D
TT2Z
S1.0
D
TT2Z
D
TT2Z
11' - 5 1/2" 12' - 0"
11' - 5 1/2" 12' - 0" 6' - 11 1/2"
3 3 3
TYP
NOTE:
ALL DIMENSIONS TO CENTERINE OF BEAMS ABOVE
.2
.2
A d d e n d u m
10116
36857
S T
A F
F H
O U
S
IN
G P
R O
J E
C T
C A
B
IN
B U
IL
D
IN
G
P L
A N
S N
E H
A L
E M
B A
Y S
T A
T E
P A
R K
B J P
P A R K
SO
N
E G
O R S T A T E
O R E G O N
P A R K S
A N D
R E C R E A
TI
O N
D E P A R
TM
E N T
D E S
IG
N E D
B Y
A P P R O V E D
B Y
C H E C K E D
B Y
D R A W N
B Y
D A T E
R E V
IS
IO
N
D A T E
B Y
SHEET:
OPRIS#: CONTRACT #:
.1
.2
A d d e n d u m
C
A B
IN
V
E B
J P
.2
.2
A d d e n d u m
O
P R
D C
O M
M E
N T
S B
J P
.3
.2
A d d e n d u m
O
P R
D C
O M
M E
N T
S R
J S
B J P
J J E
B J P
J J E
/0
/2
S1.0
S T
A F
F C
A B
IN
F
O U
N D
A T
IO
N
P L
A N
S1.0 1/4" = 1'-0"
A FOUNDATION PLAN CABINS 1-3
STRUCTURAL FOUNDATION SCHEDULE
Footing Label Column/Wall Type Reinforcing Pier Size Notes
1 BEAM PER
PLAN
2'-0"x2'-0"x12"DEEP (3) #4 EACH WAY
BOTTOM
16" DIA. SEE DETAIL 2/S2.1
2 BEAM PER
PLAN
2'-6"x2'-6"x12"DEEP (4) #4 EACH WAY
BOTTOM
16" DIA. SEE DETAIL 1/S2.1
3 BEAM PER
PLAN
3'-0"x3'-0"x12"DEEP (4) #4 EACH WAY
BOTTOM
16" DIA. SEE DETAIL 1/S2.1
4 BEAM PER
PLAN
3'-6"x3'-6"x12"DEEP 2 (5) #4 EACH WAY
BOTTOM
16" DIA. SEE DETAIL 1/S2.1
5 CONCRETE
WALL 8"
1'-6" WIDE x 12" DEEP x CONT (2) #4 CONT. TOP
& BOTTOM
N/A SEE DETAIL
S1.0 1/4" = 1'-0"
C FLOOR FRAMING PLAN
S1.0 1/4" = 1'-0"
B FOUNDATION PLAN CABINS 4-6
FOUNDATION PLAN PROVIDED FOR INFORMATION ONLY.
WORK WAS PREVIOUSLY COMPLETED BY OTHERS.
FOUNDATION PLAN PROVIDED FOR INFORMATION ONLY.
WORK WAS PREVIOUSLY COMPLETED BY OTHERS.
5 1/8x13 1/2 GLB (RIDGE BEAM) 5 1/8x13 1/2 GLB (RIDGE BEAM) 5 1/8x13 1/2 GLB (RIDGE BEAM) x
6x10 x x x H
D R x H
D R
2x10 AT 24" O.C.
(TYPICAL U.O.N.)
2x10 AT 24" O.C.
(TYPICAL U.O.N.)
6x10
S3.2
S3.2
S3.2
6x6A
BO
VE
6x6A B O
VE
H D R
6x6A B O
VE
H D R
S3.2
S3.2
OPP
S3.2
1. CONTRACTOR TO VERIFY ALL DIMENSIONS AND ELEVATIONS
WITH ARCHITECTURAL DRAWINGS.
2. ROOF DESIGN CRITERIA:
DEAD LOAD = 15 PSF
SNOW LOAD = 75 PSF + DRIFT
DEFLECTION = SMALLER OF LL/360, TL/240
3. ROOF SHEATHING TO BE APA RATED EXPOSURE I SHEATHING
WITH MINIMUM SPAN RATING OF 40/20 AND A MINIMIM
THICKNESS OF 19/32".
4. ROOF NAILING TO BE 10d COMMON OR GALVANIZED BOX
NAILS. NAIL AT 6" O.C. AT ALL SUPPORTED PANEL EDGES AND
AT 12" O.C. INTERMEDIATE SUPPORTS. BLOCKING IS NOT
REQUIRED.
5. SPLICE DOUBLE TOP PLATE AT ALL EXTERIOR WALLS AND
SHEARWALLS BY LAPPING 6'-0" MINIMUM AND NAILING WITH 16d
AT 4" O.C. STAGGERED.
6. TYPICAL HEADERS (HDR) TO BE PER , U.O.N.
7. AT BEAM TO POST CONNECTIONS USE SIMPSON 'AC' OR 'ACE'
POST CAP TYPICAL, U.O.N.
8. ALL SOLID SAWN HEADERS, PLATES (OTHER THAN P.T.) AND
HORIZONTAL MEMBERS TO BE KILN DRIED (K.D.) LUMBER.
9. ALL EXTERIOR WALLS TO BE SHEATHED PER SHEAR WALL
TYPE 'A'. SEE SCHEDULE FOR REQUIREMENTS.
10. INTERIOR BEARING WALLS WITHOUT A SCHEDULED SHEAR
ASSEMBLY TO BE PER DRAWINGS.
11. SOLID BLOCK AT RIM LOCATIONS WHERE POSTS OR BUILT-UP
STUDS ARE BEARING.
ROOF FRAMING NOTES:
(3/ S3.0)
STRUCTURAL BEARING WALL BELOW
ROOF FRAMING LEGEND:
WOOD POST PER FOUNDATION PLAN
TYPICAL HEADER TO BE PER FLOOR FRAMING NOTESHDR
4x8 4x8
2x6 AT 16" O.C.
S3.2
S3.2
S3.2
S3.2
2x6 DOUG FIR #2 STUDS AT 16" O.C. TYPICAL U.O.N.
ON PLAN. ALIGN JOISTS WITH STUDS
CEILING/SOFFIT FRAMING LEGEND:
WOOD POST PER FOUNDATION PLAN
LEDGER PER DETAIL
S3.2
1. CONTRACTOR TO VERIFY ALL DIMENSIONS AND ELEVATIONS
WITH ARCHITECTURAL DRAWINGS.
2. ROOF DESIGN CRITERIA:
DEAD LOAD = 10 PSF
LIVE LOAD = 10 PSF
DEFLECTION = SMALLER OF LL/240, TL/180
3. SOFFIT SHEATHING PER ARCH
4. SOFFIT NAILING TO BE 10d COMMON OR GALVANIZED BOX
NAILS. NAIL AT 6" O.C. AT ALL SUPPORTED PANEL EDGES AND
AT 12" O.C. INTERMEDIATE SUPPORTS. BLOCKING IS NOT
REQUIRED.
CEILING/SOFFIT FRAMING NOTES:
.2
.2
A d d e n d u m
10116
36857
S T
A F
F H
O U
S
IN
G P
R O
J E
C T
C A
B
IN
B U
IL
D
IN
G
P L
A N
S N
E H
A L
E M
B A
Y S
T A
T E
P A
R K
B J P
P A R K
SO
N
E G
O R S T A T E
O R E G O N
P A R K S
A N D
R E C R E A
TI
O N
D E P A R
TM
E N T
D E S
IG
N E D
B Y
A P P R O V E D
B Y
C H E C K E D
B Y
D R A W N
B Y
D A T E
R E V
IS
IO
N
D A T E
B Y
SHEET:
OPRIS#: CONTRACT #:
.1
.2
A d d e n d u m
C
A B
IN
V
E B
J P
.2
.2
A d d e n d u m
O
P R
D C
O M
M E
N T
S B
J P
.3
.2
A d d e n d u m
O
P R
D C
O M
M E
N T
S R
J S
B J P
J J E
B J P
J J E
/3
/2
S2.0
S T
A F
F C
A B
IN
F
R A
M
IN
G P
L A
N S
S2.0 1/4" = 1'-0"
B ROOF FRAMING PLAN
S2.0 1/4" = 1'-0"
A CEILING FRAMING PLAN
WOOD STUD SHEARWALL SCHEDULE - 10d NAILS
MARK SHEATHING AND NAILING SILL PLATE AND ANCHORAGE CAPACITY NOTES
UPPER WALL: 2x SOLE PLATE WITH 16d NAILS
AT 6" O.C. STAGGERED
FOUNDATION: 2x P.T. SILL PLATE WITH 5/8" DIA
LAG BOLTS AT 18" O.C.
435 PLF
(WIND)
310 PLF
(SEISMIC)
TYPICAL
EXTERIOR
WALLS
U.O.N.
UPPER WALL: 3x SOLE PLATE WITH SIMPSON SDS 1/4" x 6" AT 8" O.C.
FOUNDATION: 3x P.T. SILL PLATE WITH 5/8" DIA
LAG BOLTS AT 12" O.C.
WOOD STUD SHEARWALL SCHEDULE NOTES
A
B
15/32" APA RATED, EXPOSURE 1 SHEATHING,
ONE SIDE, ALL EDGES BLOCKED, WITH 10d
COMMON WIRE NAILS AT 6" O.C. ALL PANEL
EDGES AND 12" O.C. IN-FIELD
15/32" APA RATED, EXPOSURE 1 SHEATHING,
ONE SIDE, ALL EDGES BLOCKED, WITH 10d
COMMON WIRE NAILS AT 3" O.C. ALL PANEL
EDGES AND 12" O.C. IN-FIELD
1. INSTALL SHEATHING HORIZONTAL OR VERTICAL. NO PIECE SMALLER THAN 2'-0" x 2'-0".
2. ALL INTERIOR WALLS WITHOUT A SCHEDULE SHEAR ASSEMBLY TO BE SHEATHED PER ARCHITECTURAL DRAWINGS.
3. APPLY GYPSUM BOARD OVER SHEATHING AS REQUIRED BY ARCHITECTURAL DRAWINGS.
4. AT POSTS EMBEDDED IN SHEAR WALLS, ATTACH SHEATHING PER THE EDGE NAILING REQUIREMENTS FOR THAT SHEAR WALL.
5. ALL SHEAR WALL NAILS TO BE COMMON WIRE (10d = 0.148") OR GALVANIZED BOX NAILS (10d DIA = 0.128"). MINIMUM PENETRATION TO BE 1 3/8" FOR 8d NAILS. STAPLES ARE NOT AN ACCEPTABLE SUBSTITUTION.
6. ANCHOR BOLTS TO BE STANDARD LAG BOLTS WITH 5" MINIMUM EMBED AND 1 1/2" MINIMUM EDGE DISTANCE. PROVIDE A
MINIMUM OF (2) LAG BOLTS PER WALL SECTION.
7. PROVIDE PLATE WASHERS - MINIMUM OF 1/4" x 3" x 3" IN SIZE, AT ALL SILL PLATE ANCHOR BOLTS.
8. DO NOT USE NAILS FOR ANCHORAGE OF 3x SILL/SOLE PLATES. PROVIDE SIMPSON 'SDS' SCREWS AS SPECIFIED.
9. WHERE SHEAR WALL CAPACITY IS GREATER THAN 350 PLF, PANEL EDGE FRAMING RECEIVING EDGE NAILING FROM ABUTTING PANELS TO BE 3x NOMINAL FRAMING. PLYWOOD JOINT AND SILL PLATE NAILING TO BE STAGGERED IN ALL CASES.
840 PLF
(WIND)
600 PLF
(SEISMIC)
HOLDOWN NOTES:
SIMPSON SPECIFIED
FASTENERS
WOOD POST PER PLAN
SIMPSON HOLDOWN
PER SCHEDULE
P.T. SILL PLATE
PER SHEARWALL
SCHEDULE
PT EDGE BEAM PER
PLAN
LAG SCREW PER
SCHEDULE
POST THICKNESS
PER SCHEDULE
1. HOLDOWNS, MANUFACTURED BY SIMPSON STRONG TIE, INC. INSTALL PER SIMPSON RECOMMENDATIONS.
2. SHEARWALL SHEATHING TO BE ATTACHED TO VERTICAL MEMBER WITH EDGE NAILING REQUIREMENTS PER
SHEARWALL SCHEDULE.
3. MULTIPLE STUDS TO BE ATTACHED TOGETHER WITH 16d NAILS AT 8" O.C. STAGGERED. ANY POST WITH
THICKNESS 5 1/2" AND GREATER TO BE A SOLID MEMBER.
LAG SCREWHOLDOWN
MINIMUM
POST THICKNESS
SIMPSON HOLDOWN SCHEDULE
3"SIMPSON 'HDU2-SDS2.5' 5/8" DIA x REQ'D LEGTH
2, 3
EXISTING CONCRETE
PIER BY OTHERS
M
IN
V E
R
IF
Y
F
IE
L D
O P
E N
IN
G
H E
IG
H
T
V E
R
IF
Y
F
IE
L D
HEADER PER PLAN
SIMPSON 'CS20' x REQ'D
COILED STRAP, TYPICAL
TOP AND BOTTOM OF
OPENING
POST PER FLOOR
FRAMING NOTES,
TYPICAL
2x6 DF#2 EACH END OF HDR WITH (4) 16d NAILS INTO HDR
END, SISTER STUDS TOGETHER
PER DETAIL
2x BLOCKING
AS REQ'D END LENGTH
1' - 0"
OPENING WIDTH
A
C
B C
B E
A D
1' - 4" TYP.
1' - 0" MAX
1. 2x6 EXTERIOR STUDS: #2 & BTR AT 16" O.C.
2. 2x4 INTERIOR STUDS: #2 & BTR AT 16" O.C.
3. R-21 WALL INSULATION
4. DOUBLE TOP PLATE THROUGHOUT
5. 7/16" OSB WALL SHEATHING PER SHEARWALL
SCHEDULE
6. HARDI-PLANK LAP SIDING, ACCENT SIDING AT
GABLE ENDS PER ELEVATIONS
7. 2x8 PRE-PRIMED SPRUCED FASCIA
WALL FRAMING NOTES
A. HEADER PER SCHEDULE
B. TRIMMERS PER SCHEDULE
C. KING STUDS PER SCHEDULE
D. (2) A35 AT MULTIPLE KING STUDS
E. BLOCKING AT 7'-0" O.C. AND PER
SHEARWALL SCHEDULE
F. BLOCK SOLID AT MULTIPLE STUDS AND
CONTINUE MULTIPLE STUD GROUPS TO
FOUNDATION, UNO
KEYNOTE LEGEND#
2x4 BEARING WALL OPENING SCHEDULE
OPENING SIZE
UP TO 4'-0"
4'-0" TO 6'-0"
6'-0" TO 8'-0"
8'-0" TO 10'-0"
BEAM SIZE (A)
4x4 4x6 4x8 4x10
TRIMMERS (B)
(1)2x4 (1)2x4 (1)2x4 (2)2x4
KING STUDS (C)
(1)2x4 (1)2x4 (1)2x4 (2)2x4
2x6 BEARING WALL OPENING SCHEDULE
OPENING SIZE
UP TO 4'-0"
4'-0" TO 6'-0"
6'-0" TO 8'-0"
8'-0" TO 10'-0"
BEAM SIZE (A)
4x4 4x6 4x8 4x10
TRIMMERS (B)
(1)2x6 (1)2x6 (1)2x6 (2)2x6
KING STUDS (C)
(1)2x6 (1)2x6 (1)2x6 (2)2x6
.2
.2
A d d e n d u m
10116
36857
S T
A F
F H
O U
S
IN
G P
R O
J E
C T
C A
B
IN
B U
IL
D
IN
G
P L
A N
S N
E H
A L
E M
B A
Y S
T A
T E
P A
R K
B J P
P A R K
SO
N
E G
O R S T A T E
O R E G O N
P A R K S
A N D
R E C R E A
TI
O N
D E P A R
TM
E N T
D E S
IG
N E D
B Y
A P P R O V E D
B Y
C H E C K E D
B Y
D R A W N
B Y
D A T E
R E V
IS
IO
N
D A T E
B Y
SHEET:
OPRIS#: CONTRACT #:
.1
.2
A d d e n d u m
C
A B
IN
V
E B
J P
.2
.2
A d d e n d u m
O
P R
D C
O M
M E
N T
S B
J P
.3
.2
A d d e n d u m
O
P R
D C
O M
M E
N T
S R
J S
B J P
J J E
B J P
J J E
/3
/2
S3.0
S H
E A
R W
A L
L S
C H
E D
U L
E A
N D
D E
T A
IL
S
S3.0 1" = 1'-0"
2 SHEARWALL HOLDOWN SCHEDULE
S3.0 1/2" = 1'-0"
1 TYPICAL SHEARWALL ELEVATION
S3.0 1/4" = 1'-0"
3 TYPICAL WALL FRAMING
FLOOR SHEATHING PER
PLAN
JOISTS PER PLAN
BEAM PER PLAN
STUD WALL PER
PLAN
SIMPSON 'LB210' TOP
FLANGE HANGER EACH END
OFFSET BEAM TO
FLUSH WITH
EXTERIOR FINISH
P E
N E
T R
A T
IO
N
M
IN
S C
R E
W
LAG SCREW PER
SHEARWALL
SCHEDULE
FLOOR SHEATHING PER
PLAN
BLOCKING AT 4'-0" O.C.
IN FIRST JOIST BAY
BEAM PER PLAN
STUD WALL PER
PLAN
SIMPSON 'HUS' FACE
MOUNT HANGER EACH END
OFFSET BEAM TO
FLUSH WITH
EXTERIOR FINISH
JOIST PER PLAN
P E
N E
T R
A T
IO
N
M
IN
S C
R E
W
LAG SCREW PER
SHEARWALL
SCHEDULE
0'-0"
GRADE
-1'-0"
T.O.F.
SIMPSON COLUMN CAP PER
16" DIA CONCRETE PIER
WITH (4) #5 VERTICAL
BARS WITH 4" HOOK
3" CLR
3" CLR
FOOTING SIZE AND
REINFORCING PER
SCHEDULE
ROUGHEN SURFACE
OR POUR MONOLITHIC
(3) #3 TIES AT TOP
BALANCE AT 12" O.C.
C L R
A S
R E
Q 'D
PLAN VIEWS (AS OCCURS PER FOUNDATION PLANS)
A A
PROVIDE SIMPSON
'CCQM' POST CAP
PROVIDE SIMPSON
'ECCLQM' POST CAP
PROVIDE SIMPSON
'CCTQM' POST CAP
PROVIDE SIMPSON
'CCCQM' POST CAP
3" COMPACTED CRUSHED
ROCK BELOW FOOTING
0'-0"
GRADE
-1'-0"
T.O.F.
STUD WALL PER PLAN
BEAM PER PLAN
BEAM PER PLAN
2x DECKING
BLOCKING AS REQUIRED
AT STUD WALL
EXISTING CONCRETE
STEM WALL AND
FOOTING BY OTHERS
STUD WALL PER PLAN
2x DECKING
BEAM PER PLAN
2x10 LEDGER WITH (2)
SIMPSON 'SDS' SCREWS
AT 12" O.C.
JOISTS PER PLAN
AS REQ'D
PER ARCH
2x6 TOP RAIL. ROUTER
EXPOSED EDGES 1/2" AND
SAND SMOOTH
2x4 HORIZONTAL RAILS
WITH SIMPSON 'APLH24'
HANGERS EACH END
SIMPSON 'A34' EACH END
OF TOP AND BOTTOM RAIL
POSTS PER PLAN
PAINT AND FINISH RAILING
PER ARCH
2x6 BOTTOM RAIL
P E
R A
R C
H
2x2 VERTICAL PICKETS AT 5" O.C.
WITH 2 1/2" STAINLESS STEEL
WOOD SCREW INTO TOP AND
BOTTOM RAIL
PER CIVIL
T.O.PAVING
AS REQ'D
T.O.F.
FOOTING SIZE AND
REINFORCING PER
SCHEDULE
POST PER PLAN
PROVIDE SIMPSON 'APW66Z'
WITH 1/2" DIA x 3" EMBED
SCREW ANCHORWOOD DECKING
ASPHALT PAVING
BLOCKING PER
S3.1
M
IN
2x10 PT LEDGER WITH 1/2" DIA x 3" EMBED AT
24" O.C. STAGGERED
(2) #4 HORIZONTAL AT TOP
EXISTING CONCRETE
STEM WALL AND
FOOTING BY OTHERS
PER CIVIL
T.O.PAVING
AS REQ'D
T.O.F.
POST PER PLAN
PROVIDE SIMPSON 'APW66Z'
WITH 1/2" DIA x 3" EMBED
SCREW ANCHOR
WOOD DECKING
ASPHALT PAVING
BEAM PER PLAN
M
IN
SIMPSON
'MBHU5.50/9.25' BEAM
HANGER
EXISTING CONCRETE
STEM WALL AND
FOOTING BY OTHERS
EXISTING FOOTING AND
STEM WALL BY OTHERS
WOOD DECKING, NOTCH
AROUND POST AS REQUIRED
P.T. 4x6 SILL PLATE, RIP AS REQUIRED, WITH 1/2" DIA x 4" EMBED
EPOXY ANCHORS AT 32" O.C.
2x10 RIM JOIST, RIP AS REQUIRED
BEAM PER PLAN,
NOTCH AT SILL
PLATE AS REQUIRED
POST PER PLAN
PROVIDE SIMPSON 'BC60' POST
BASE WITH 1/2" DIA x 4" LAG SCREW
SIMPSON 'A34' CLIP,
EACH SIDE OF BEAM
EXISTING FOOTING AND
STEM WALL BY OTHERS
WOOD DECKING
P.T. 4x6 SILL PLATE, RIP AS
REQUIRED, WITH
1/2" DIA x 4" EMBED EPOXY
ANCHORS AT 32" O.C.
2x10 RIM JOIST, RIP AS REQUIREDJOIST PER PLAN
.2
.2
A d d e n d u m
10116
36857
S T
A F
F H
O U
S
IN
G P
R O
J E
C T
C A
B
IN
B U
IL
D
IN
G
P L
A N
S N
E H
A L
E M
B A
Y S
T A
T E
P A
R K
B J P
P A R K
SO
N
E G
O R S T A T E
O R E G O N
P A R K S
A N D
R E C R E A
TI
O N
D E P A R
TM
E N T
D E S
IG
N E D
B Y
A P P R O V E D
B Y
C H E C K E D
B Y
D R A W N
B Y
D A T E
R E V
IS
IO
N
D A T E
B Y
SHEET:
OPRIS#: CONTRACT #:
.1
.2
A d d e n d u m
C
A B
IN
V
E B
J P
.2
.2
A d d e n d u m
O
P R
D C
O M
M E
N T
S B
J P
.3
.2
A d d e n d u m
O
P R
D C
O M
M E
N T
S R
J S
B J P
J J E
B J P
J J E
/3
/2
S3.1
D E
T A
IL
S
S3.1 1" = 1'-0"
4 FLOOR FRAMING DETAIL
S3.1 1" = 1'-0"
5 FLOOR FRAMING DETAIL
S3.1 1" = 1'-0"
1 PIER FOOTING AT BEAM
S3.1 1" = 1'-0"
6 FLOOR FRAMING DETAIL
S3.1 1" = 1'-0"
7 FLOOR FRAMING DETAIL
S3.1 1 1/2" = 1'-0"
8 WOOD RAILING DETAIL
S3.1 1" = 1'-0"
2 RETAINING WALL SECTION
S3.1 1" = 1'-0"
3 RETAINING WALL SECTION
S3.1 1" = 1'-0"
10 RETAINING WALL SECTION
S3.1 1" = 1'-0"
9 RETAINING WALL SECTION
PIER FOOTING DETAIL PROVIDED FOR INFORMATION ONLY.
WORK WAS PREVIOUSLY COMPLETED BY OTHERS.
NOTE:
COORDINATE VENTING
REQUIREMENTS WITH
ARCHITECT
SAWN JOIST PER PLAN PROVIDE
'BIRDS MOUTH' CUT AT BEARING
PLATE DO NOT OVERCUT
SIMPSON 'H3' AT EACH
TRUSS, TYPICAL
ROOF SHEATHING
PER PLAN
SIMPSON 'RBC' AT 48" O.C.
WHERE SHEAR WALLS OCCUR
SPACE AT 24" O.C.
2x SHEAR BLOCKING
WITH BOUNDARY NAILING
COORDINATE EAVE
EXTENSION AND FRAMING
WITH ARCHITECT
SHEARWALL SHEATHING
PER PLAN, EXTEND FULL
HEIGHT
STUD WALL PER PLAN
ROOF FRAMING
PER PLAN, TYPICAL
ROOF SHEATHING
PER PLAN, TYPICAL
RIPPED BLOCKING
WITH EDGE NAILING
SIMPSON 'LSSJ210'
FACE MOUNT
HANGER, TYPICAL
BEAM PER PLAN
FINISHES PER
ARCHITECT, TYPICAL
SOFFIT JOIST PER
PLAN WITH SIMPSON
'LUS26' HANGER
STUD WALL
PER PLAN
2x LEDGER WITH (2) 10d NAILS AT EACH
STUD
FINISHES PER ARCH
2x BLOCKING AT 4'-0"
O.C. WITH 'LUS26'
HANGER EACH END
STUD WALL
PER PLAN
2x LEDGER WITH (2) 10d NAILS AT EACH
STUD
FINISHES PER ARCH
BEAM PER PLAN
BEAM PER PLAN
POST PER PLAN
WITH SIMPSON
'APVT6' STRAP
EACH SIDE
POST PER PLAN WITH
SIMPSON 'APVT6' STRAP
EACH SIDE
JOIST PER DETAIL
S3.2
BEAM PER PLAN WITH
SIMPSON 'APHH610' HANGER
POST PER PLAN
BEAM PER PLAN
SIMPSON 'APVL6'
EACH SIDE
SIMPSON 'APVT6'
JOIST PER DETAIL
S3.2
.2
.2
A d d e n d u m
10116
36857
S T
A F
F H
O U
S
IN
G P
R O
J E
C T
C A
B
IN
B U
IL
D
IN
G
P L
A N
S N
E H
A L
E M
B A
Y S
T A
T E
P A
R K
B J P
P A R K
SO
N
E G
O R S T A T E
O R E G O N
P A R K S
A N D
R E C R E A
TI
O N
D E P A R
TM
E N T
D E S
IG
N E D
B Y
A P P R O V E D
B Y
C H E C K E D
B Y
D R A W N
B Y
D A T E
R E V
IS
IO
N
D A T E
B Y
SHEET:
OPRIS#: CONTRACT #:
.1
.2
A d d e n d u m
C
A B
IN
V
E B
J P
.2
.2
A d d e n d u m
O
P R
D C
O M
M E
N T
S B
J P
.3
.2
A d d e n d u m
O
P R
D C
O M
M E
N T
S R
J S
B J P
J J E
B J P
J J E
/3
/2
S3.2
D E
T A
IL
S
S3.2 1" = 1'-0"
3 ROOF FRAMING DETAIL
S3.2 1" = 1'-0"
4 ROOF FRAMING DETAIL
S3.2 1" = 1'-0"
1 CEILING/SOFFIT JOIST PERPENDICULAR
S3.2 1" = 1'-0"
2 CEILING/SOFFIT JOIST PARALLEL
S3.2 1" = 1'-0"
M353
EXTERIOR POST ELEVATION
S3.2 1" = 1'-0"
M353
EXTERIOR POST ELEVATION
MISC. VALVES & COCKS
SHUTOFF VALVE
GLOBE VALVE
GATE VALVE OS&Y
BALL VALVE
BUTTERFLY VALVE
CHECK VALVE
WYE STRAINER
WYE STRAINER WITH BLOWDOWN
DRAIN VALVE
BALANCING VALVE
PRESSURE REDUCING VALVE
RELIEF VALVE
TWO-WAY CONTROL VALVE
DOUBLE CHECK VALVE ASSEMBLY (DCVA)
REDUCED PRESSURE BACKFLOW PREVENTER (RPBP)
THERMOMETER
PRESSURE GAUGE
PRESSURE-TEMPERATURE TEST PLUG
MANUAL AIR VENT
AUTOMATIC AIR VENT
FLOW SWITCH
TEMPERATURE SENSOR
SHOCK ARRESTOR
VACUUM BREAKER
SHUTOFF VALVE WITH TAMPER SWITCH
THRUST BLOCK
SOLENOID VALVE
S
S
S
V
T
F
AAV
MAV
CLEANOUT
FLOOR CLEANOUT
CLEANOUT TO GRADE
WALL CLEANOUT
AREA DRAIN
CATCH BASIN
FLOOR DRAIN
OVERFLOW ROOF DRAIN
ROOF DRAIN
TRENCH SHOWER DRAIN
TRENCH DRAIN
HOSE BIBB
GROUND HYDRANT
WALL BOX HYDRANT
FLOOR SINK
PLUMBING SPECIALITIES
SYMBOLS
A
E
B
X
K
R
F
ACCESS PANEL
POINT OF CONNECTION
EXISTING TO REMAIN
BELOW GRADE / FLOOR
REVISION NUMBER
NUMBERED NOTE
REMOVE EXISTING
CAP EXISTING / CAP FOR FUTURE
RELOCATE EXISTING
FUTURE
EQUIPMENT
XXX
TAG NUMBER
XX-XXX
XXX
EQUIPMENT PROVIDED
FIXTURE NUMBER
FIXTURE UNITS
FIXTURE TYPE
FIXTURES DETAIL CALLOUT
X
XX.XX
X
XX
RISER TAG
DETAIL NUMBER
SHEET NUMBER
SYSTEM TYPE
RISER NUMBER
MISC. FITTINGS & SYMBOLS
DIRECTION OF FLOW
DIRECTION OF SLOPE
PIPE SLEEVE
REDUCER
ANCHOR
ELBOW (90 DEGREE)
PIPING CONNECTIONS
TEE
JOINT OR COUPLING POINT
PIPE CONTINUATION
HEAT TRACE
FLEXIBLE HOSE CONNECTOR
TEE DOWN
TEE UP
ELBOW DOWN
ELBOW UP
RISER
PLUG OR BLIND FLANGE
CAP
FLANGED CONNECTION
UNION
ELBOW (45 DEGREE)
MC
MECHANICAL COUPLING
PLUMBING PIPING
G
W WASTE ABOVE GRADE
W WASTE BELOW GRADE
STORM DRAIN ABOVE GRADE
STORM DRAIN BELOW GRADE
DRAIN (CONDENSATE/INDIRECT)
VENT
COLD WATER
HOT WATER
RECIRCULATING HOT WATER
IRRIGATION
NON-POTABLE WATER
SD
SD
D
V
CW
HW
RHW
IRR
NPW
BY OTHERS
GENERAL NOTES:
A. THIS IS A STANDARD LEGEND SHEET, THEREFORE, SOME SYMBOLS MAY APPEAR ON THIS SHEET
THAT DO NOT APPEAR ON THE DRAWINGS.
UNIT NUMBER
FLOOR UNIT IS
LOCATED ON
EQUIPMENT TYPE
XX-XXX XXXX-XX-XXXXX
UNIT NUMBER
FLOOR UNIT IS
LOCATED ON
EQUIPMENT TYPE
STANDARD ABBREVIATIONS
AREA DRAINAD
AMERICANS WITH DISABILITIES ACTADA
ABOVE FINISHED FLOORAFF
ALTERNATIVEALT
APPROXIMATELYAPPROX
ARCHITECT, ARCHITECTURALARCH
ACCESS PANELAP
BELOW FINISHED FLOORBFF
BUILDINGBLDG
BOTTOM OF PIPEBOP
BOTTOM OF STRUCTUREBOS
BRITISH THERMAL UNITBTU
BRITISH THERMAL UNITS PER HOURBTUH
BUTTERFLY VALVEBTV
BALANCING VALVEBV
CATCH BASINCB
CUBIC FEET PER HOURCFH
CUBIC FEET PER MINUTECFM
CUBIC FEET PER SECONDCFS
CALCULATIONCALC
CENTERLINECL
CLEANOUTCO
CONNECT, CONNECTIONCONN
CONTINUED, CONTINUATIONCONT
CIRCULATING PUMPCP
CLEANOUT TO GRADECTG
CONCRETECONC
CHECK VALVECV
DRAINAGE FIXTURE UNITDFU
DIAMETERDIA
DRINKING FOUNTAINDF
DOWN (PENETRATES FLOOR)DN
DRAINDR
DRAIN VALVEDV
DRAWINGDWG
EXISTING(E), EXIST
ELECTRONICALLY COMMUTATED MOTORECM
EMERGENCY EYE WASHEEW
ELECTRIC, ELECTRICALELEC
ELEVATIONELEV
ENGINEERENGR
EFFICIENCYEFF
EQUALEQ
EQUIPMENTEQUIP
EMERGENCY SHOWERES
ELECTRIC WATER COOLEREWC
ELECTRIC WATER HEATEREWH
ENTERING WATER TEMPERATUREEWT
EXPANSION TANKET
EXTRACTOREX
EXPANSIONEXP
EXHAUST OR EXHAUST AIREXH
DEGREES FAHRENHEITF
FLOOR CLEANOUTFCO
FLOOR DRAIN (PLUMBING)FD
FIRE DEPARTMENT CONNECTIONFDC
FINISHED FLOOR ELEVATIONFFE
FIGUREFIG
FLOORFL
FULL LOAD AMPACITYFLA
FIRE PUMPFP
FEET PER MINUTEFPM
FEET PER SECONDFPS
FLEXIBLEFLEX
FLOOR SINKFS
FEET/FOOTFT
FIXTURE UNITFU
FLUSH VALVEFV
FUTURE(F)
GRADEG
FLUSH TANKFLT
GAGE/GAUGEGA
GALLONGAL
GALVANIZEDGALV
GLYCOLGLY
GALLONS PER HOURGPH
GALLONS PER MINUTEGPM
GATE VALVEGV
HEIGHTH
GROUND HYDRANTGH
HOSE BIBBHB
HUB DRAINHD
HORIZONTALHORIZ
HORSEPOWERHP
HEAT TRACEHT
HOURHR
INSIDE DIAMETER, INSIDE DIMENSIONID
MAXIMUMMAX
THOUSAND BTU PER HOURMBH
MINIMUM CIRCUIT AMPACITYMCA
MECHANICALMECH
MINIMUM EFFICIENCY REPORTING VALUEMERV
MANUFACTURERMFR
MISCELLANEOUSMISC
MAXIMUM OVERCURRENT PROTECTIONMOCP
MOP SINKMS
MOUNTEDMTD
MINIMUMMIN
NORMALLY CLOSEDNC
NOT IN CONTRACTNIC
NORMALLY OPENNO
NOMINAL PIPE SIZENPS
NOT TO SCALENTS
OVERFLOW DRAINOD
OUTSIDE SCREW & YOKE GATE VALVEOS&Y
PHASEPH
POST INDICATING VALVEPIV
POLYPROPYLENEPP
PRESSURE REDUCING VALVEPRV
PRESSURE GAUGEPG
PRESSURE SWITCHPS
POUNDS PER SQUARE INCHPSI
POUNDS PER SQUARE INCH (GAUGE)PSIG
POLYVINYL CHLORIDEPVC
RADIUSR, RAD
ROOF DRAINRD
REVISIONREV
REVOLUTIONS PER MINUTERPM
SINKS
STANDARD CUBIC FEET PER MINUTESCFM
SHOWER DRAIN (PLUMBING)SD
SMOKE DAMPER (MECHANICAL)SD
SEWAGE EJECTORSE
SQUARE FOOT, SQUARE FEETSF
SHOWERSH
SIMILARSIM
SECTIONSECT
SHUTOFF VALVESOV
SPECIFICATIONSPEC
SQUARESQ
STAINLESS STEEL (ALL)SS
SQUARE INCH, SQUARE INCHESSQ IN
TRENCH DRAINTD
TOTAL DEVELOPED LENGTHTDL
TEMPERATURETEMP
THERMOSTATIC MIXING VALVETMV
TOP OF PIPETOP
TOTAL DISCHARGE HEADTDH
TRAP PRIMER VALVETP
TAMPER SWITCHTS
TOTAL STATIC PRESSURETSP
TYPICALTYP
UNDERGROUNDUG
UP (PENETRATES FLOOR SLAB)UP
VOLTSV
URINALU
VACUUM BREAKERVB
VOLUME DAMPERVD
VELOCITYVEL
VERTICALVERT
VENT THROUGH ROOFVTR
WIDTHW
WATER CLOSETWC
VARIABLE FREQUENCY DRIVEVFD
WALL CLEANOUTWCO
WATER FIXTURE UNITSWFU
WATER GAUGEWG
WALL HYDRANTWH
WITHW/
WATER HAMMER ARRESTORWHA
WITHOUTW/O
LAVATORYLAV
POUNDLB
LINEAR FEETLF
KILOWATTKW
KILOWATT HOURKWH
ISOMETRICISO
LENGTHL
IRON PIPE SIZEIPS
INSULATIONINSUL
INVERT ELEVATIONIE
INCH, INCHESIN
P A R K
SO
N
E G
O R S T A T E
O R E G O N
P A R K S
A N D
R E C R E A
TI
O N
D E P A R
TM
E N T
D E S
IG
N E D
B Y
A P P R O V E D
B Y
C H E C K E D
B Y
D R A W N
B Y
D A T E
R E V
IS
IO
N
D A T E
B Y
SHEET:
OPRIS#: CONTRACT #:
1065436857
P0.01
P A
E
P A
E
P A
E
P A
E
/1
/2
S T
A F
F H
O U
S
IN
G P
R O
J E
C T
C A
B
IN
B U
IL
D
IN
G
P L
A N
S N
E H
A L
E M
S T
A T
E P
A R
K
S Y
M B
O L
S A
N D
L E
G E
N D
S
P L
U M
B
IN
G
12/8/23
P
R K
SO
N
E G
O R S T A T E
O R E G O N
P A R K S
A N D
R E C R E A
TI
O N
D E P A R
TM
E N T
D E S
IG
N E D
B Y
A P P R O V E D
B Y
C H E C K E D
B Y
D R A W N
B Y
D A T E
R E V
IS
IO
N
D A T E
B Y
SHEET:
OPRIS#: CONTRACT #:
1065436857
P0.02
P A
E
P A
E
P A
E
P A
E
/1
/2
S T
A F
F H
O U
S
IN
G P
R O
J E
C T
C A
B
IN
B U
IL
D
IN
G
P L
A N
S N
E H
A L
E M
S T
A T
E P
A R
K
S C
H E
D U
L E
S
P L
U M
B
IN
G
JACKET UV RESISTANT POLYMER ASTM E84. ANSI LC1/CSA 6.26.
ABOVE GRADE
CORRUGATED STAINLESS STEEL TUBING (CSST), ASTM A240 TYPE 304 STAINLESS STEEL WITH PROTECTIVEPRPOPANE
BELOW GRADE POLYETHYLENE, MEDIUM DENISTY: ASTM D2513.
SANITARY WASTE AND VENT SCHEDULE 40 SOLID WALL PVC: ASTM D2665-85a, ASTM D3311-82.
COPPER MANIFOLDS WITH INTEGRAL VALVES. PEX-A COLD EXPANSION TYPE FITTINGS, ASTM F1960.
NON-HEAT TRACE
CROSS-LINKED POLYETHYLENE (PEX): PEX-A OR PEROXIDE METHOD, ASTM F876, ASTM F877, CAN/CDA-B137.5.
ANSI B16.22 SOLDERED JOINTS.
DOMESTIC WATER
UNDER HEAT TRACE
COPPER: ASTM B88 HARD DRAWN COPPER TUBING, TYPE L, WROUGHT COPPER FITTINGS (150 PSI SERVICE), SERVICE MATERIAL
PIPE SCHEDULE
FOR UNDILUTED PROPANE.
BASIS OF DESIGN: 2019 OREGON MECHANICAL SPECIALTY CODE, APPENDIX C, 'FUEL GAS', SECTION C402, 'PIPE SIZING'
PROPANE SYSTEM:
ALL WASTE PIPING SIZED AT 1/4"/FT. SLOPE UNLESS OTHERWISE NOTED.
BASIS OF DESIGN: 2021 OREGON PLUMBING SPECIALTY CODE, CHAPTER 7, 'SANITARY DRAINAGE'.
WASTE AND VENT PIPING SYSTEM:
AND NOT TO EXCEED 5 FT./SEC. (HOT WATER).
WATER SUPPLY SYSTEM'. PIPING SIZED ON 3 PSI/100 FT. DROP, VELOCITIES NOT TO EXCEED 8 FT./SEC. (COLD WATER)
BASIS OF DESIGN: 2021 OREGON PLUMBING SPECIALTY CODE, APPENDIX A 'RECOMMENDED RULES FOR SIZING THE
DOMESTIC WATER PIPING SYSTEM:
PLUMBING DESIGN CRITERIA (OREGON)
B. PROVIDE CONDENSATE NEUTRALIZER ON FLUE DRAIN.
A. COORDINATE POWER SUPPLY WITH DIVISION 26
GENERAL NOTES:
PWH-101 PROPANE WATER HEATER CLOSET DOMESTIC HOT WATER PROPANE INSTANTANEOUS - 3.9 0.4 PROPANE 15,000 199,000 120/1 RINNAI - CU199iP
NUMBER DESCRIPTION LOCATION SERVICE TYPE (GAL) (GPM) (GPM) TYPE (BTU) (BTU) PHASE & MODEL NOTES
TAG CAPACITY @ 100F RISE ACTIVATION MIN MAX VOLT/ MANUFACTURER
STORAGE FLOW RATE MIN FLOW
FUEL ELEC
WATER HEATER SCHEDULE
WB-1 WALL BOX HYDRANT - - 3/4 - - - FREEZE PROOF, BOX/FLUSH TYPE w/LOCKING COVER, INTEGRAL VACUUM BREAKER
SH-1 SHOWER 2 1-1/2 1/2 1/2 - 1.5 VALVE AND SHOWERHEAD ONLY, TILED ENCLOSURE
S-1 SINK 2 1-1/2 1/2 1/2 - 1.5 COUNTERTOP, STAINLESS STEEL, MANUAL SINGLE LEVER FAUCET
L-1 LAVATORY 2 1-1/2 1/2 1/2 - 0.5 WALL HUNG, MANUAL FAUCET, ADA
WC-1 WATER CLOSET 4 2 3/4 - - 1.28 FLOOR MOUNTED, TANK TYPE, ADA
NUMBER FIXTURE TYPE W V CW HW TW GPM/GPF DESCRIPTION NOTES
TAG ROUGH-IN SIZE (INCHES)
PLUMBING FIXTURE SCHEDULE
1 2 3
C
B
UP 4 RISERS @ 5.5"
3 TREADS @ 12"
WC-1
SH-1
L-1 S-1
PWH-101
PEX DISTRIBUTION
MANIFOLDS
P5.01
3/4" CW DN
2" W DN
3" VTR
2" W DN
2" V DN
3" VTR
1 1/2" V DN
WB-1
1/2" G DN
SLEEPING
LIVING/DINING
BATHROOM
9 FD-1
P A R K
SO
N
E G
O R S T A T E
O R E G O N
P A R K S
A N D
R E C R E A
TI
O N
D E P A R
TM
E N T
D E S
IG
N E D
B Y
A P P R O V E D
B Y
C H E C K E D
B Y
D R A W N
B Y
D A T E
R E V
IS
IO
N
D A T E
B Y
SHEET:
OPRIS#: CONTRACT #:
1065436857
P2.11B
P A
E
P A
E
P A
E
P A
E
/1
/2
S T
A F
F H
O U
S
IN
G P
R O
J E
C T
C A
B
IN
B U
IL
D
IN
G
P L
A N
S N
E H
A L
E M
S T
A T
E P
A R
K
S T
A F
F F
L O
O R
P L
P L
U M
B
IN
G
1/2" = 1'-0"
STAFF - PLUMBING
NORTH
A. RUN PIPING CONCEALED, UNLESS SPECIFIED
OTHERWISE, AND CLEAR OF CEILING
INSERTS. ALL PIPING SHALL BE INSTALLED AS
CLOSE AS POSSIBLE TO WALL AND
UNDERSIDE OF BEAMS AND JOISTS.
B. ALL WORK SHALL BE COORDINATED WITH ALL
TRADES INVOLVED. OFFETS IN PIPING AND
TRANSITIONS AROUND OBSTRUCTIONS SHALL
BE PROVIDED AT NO ADDITIONAL COST TO
THE OWNER.
C. VERIFY ALL EQUIPMENT CONNECTIONS WITH
MANUFACTURER'S CERTIFIED DRAWINGS.
FIELD VERIFY AND COORDINATE ALL
DIMENSIONS BEFORE FABRICATION.
D. PROVIDE FINAL CONNECTION TO ALL
PLUMBING FIXTURES.
E. COORDINATE ACCESS PANEL LOCATIONS
WITH ARCHITECT.
F. COORDINATE ALL UNDERGROUND PIPE
ROUTINGS WITH AVOID STRUCTURAL
FOOTING LOCATIONS AND DEPTHS TO AVOID
CONFLICTS.
GENERAL NOTES:
1. CABIN COLD WATER SUPPLY FROM SITE
WATER DISTRIBUTION SYSTEM SHOWN FOR
REFERENCE. DIRECTION OF SITE WATER
SUPPLY WILL VARY BY CABIN LOCATION.
2. CABIN SANITARY WASTE CONNECTION TO
SITE SEWER SYSTEM SHOWN FOR
REFERENCE. DIRECTION OF SITE SEWER
CONNECTION WILL VARY BY CABIN
LOCATION.
3. WASTE PIPING ROUTED UNDERFLOOR
TIGHT TO STRUCTURE INSIDE INSULATION
LAYER.
4. WASTE PIPE CLEANOUT UNDER FLOOR
ACCESSIBLE TO MAINTENANCE STAFF.
5. WASTE MAIN TO DROP OUT OF INSULATION
LAYER TO BELOW GRADE. PROVIDE CAST
IRON SLEEVE AROUND PLASTIC WASTE
PIPING TO PREVENT RODENT DAMAGE.
6. CLEANOUT TO GRADE OUTSIDE CABIN
FOOTPRINT. COORDINATE FINAL LOCATION
WITH SITE CONDITIONS.
7. CABIN PROPANE SUPPLY FROM SITE
DISTRIBUTION SYSTEM SHOWN FOR
REFERENCE. DIRECTION OF SITE PROPANE
SUPPLY WILL VARY BY CABIN LOCATION.
8. PROPANE GAS REGULATOR ON CABIN
EXTERIOR. GAS PIPE TO PENETRATE CABIN
ABOVE GRADE.
9. FLOOR DRAIN MOUNTED UNDER WATER
HEATER FOR T&P RELIEF VALVE
DISCHARGE AND FOR FLUE CONDENSATE.
PROVIDE WITH TRAP PRIMER.
NOTES:
RELIEF VALVE
THERMOMETER
CABIN FLOOR
PROPANE
WATER
HEATER
1. 3/4" COLD WATER SUPPLY FROM SITE DISTRIBUTION.
2. WATER HEATER T&P RELIEF SPILLS INTO DRAIN PAN.
3. WATER SUPPLY SHUT OFF VALVE BOX. REFER TO VALVE
BOX DETAIL.
4. PROPANE SUPPLY FROM SITE DISTRIBUTION.
5. CAST IRON PIPE SLEEVE THROUGH CRAWL SPACE TO
PROTECT UTILITY PIPING FOR RODENT DAMAGE
6. SEAL PIPE SLEEVE AT CABIN FLOOR.
7. HEAT TRACE ANY EXPOSED WATER PIPING BETWEEN
GRADE LEVEL AND CABIN FLOOR FOR FREEZE
PROTECTION. ROUTE WATER PIPE IN COPPER FOR THE
SECTION THAT HAS HEAT TRACE.
NOTES:
PEX MANIFOLDS
PEX TUBING (TYP)
PEX TRANSITION (TYP)
CONNECTIONS TO MANIFOLD
3/4"
PWH-101
SH-1
L-1
S-1
WC-1
SH-1
L-1
S-1
WB-1
REFERENCE
MECHANICAL FOR
FLUE ROUTING
GRADE CRAWLSPACE
8. CABIN PRESSURE REGULATOR FOR SITE DISTRIBUTION SET
AT 2 PSI. CONTRACTOR TO VERIFY SITE PROPANE
DISTRIBUTION SYSTEM HAS PRESSURE AND CAPACITY FOR
CABIN SUPPLY.
9. APPLIANCE REGULATOR SET FOR WATER HEATER INPUT
BASED ON MANUFACTURER INSTRUCTIONS.
10. CONNECTIONS TO WATER HEATER BASED ON
MANUFACTURER'S INSTRUCTIONS.
11. PRESSURE ACTIVATED TRAP PRIMER.
DRAIN VALVE, TYP
1/2"
FLOOR DRAIN
MAX. 24"
SHUTOFF
VALVE
DRAIN
VALVE
1. PLASTIC COVER COVER AND FRAME.
2. CROWN TO SHED WATER.
3. 36" LENGTH OF 12" DIAMETER VALVE BOX AND RISER.
4. WATER SUPPLY TO CABIN.
5. 3/4" MINUS GRAVEL FILL.
6. WATER SUPPLY AT DEPTH TO PROTECT FROM FREEZING.
NOTES:
1 2
5 6
P A R K
SO
N
E G
O R S T A T E
O R E G O N
P A R K S
A N D
R E C R E A
TI
O N
D E P A R
TM
E N T
D E S
IG
N E D
B Y
A P P R O V E D
B Y
C H E C K E D
B Y
D R A W N
B Y
D A T E
R E V
IS
IO
N
D A T E
B Y
SHEET:
OPRIS#: CONTRACT #:
1065436857
P5.01
P A
E
P A
E
P A
E
P A
E
/1
/2
S T
A F
F H
O U
S
IN
G P
R O
J E
C T
C A
B
IN
B U
IL
D
IN
G
P L
A N
S N
E H
A L
E M
S T
A T
E P
A R
K
D E
T A
IL
S
P
L U
M B
IN
G
NONE
1 WATER SYSTEM DETAIL
NONE
2 VALVE BOX DETAIL
HVAC PIPING
REFRIGERANT LIQUID
REFRIGERANT SUCTION
RL
RS
STANDARD ABBREVIATIONS GENERAL NOTES:
A. THIS IS A STANDARD LEGEND SHEET, THEREFORE, SOME SYMBOLS MAY APPEAR ON THIS SHEET
THAT DO NOT APPEAR ON THE DRAWINGS.
AIR PRSSURE DROPAPD
BACKDRAFT DAMPERBDD
BREAK HORESPOWERBHP
BRITISH THERMAL UNITBTU
BRITISH THERMAL UNITS PER HOURBTUH
CUBIC FEET PER MINUTECFM
ENTERING AIR TEMPERATUREEAT
FEET PER MINUTEFPM
FEET PER SECONDFPS
FEET/FOOTFT
OUTSIDE AIROSA
RELIEF AIRRA
SUPPLY AIRSA
VARIABLE FREQUENCY DRIVEVFD
LEAVING AIR TEMPLAT
UNIT NUMBER
EQUIPMENT TYPE
XX-XXX
EQUIPMENT
XXXX-XX-XXXXX
UNIT NUMBER
FLOOR UNIT IS
LOCATED ON
EQUIPMENT TYPE EQUIPMENT PROVIDED
BY OTHERS
XXX
TAG NUMBER
TU-X-XXX
DETAIL CALLOUT
X
XX.XX
DETAIL NUMBER
SHEET NUMBER
SYMBOLS
A
E
B
X
K
R
F
ACCESS PANEL
POINT OF CONNECTION
EXISTING TO REMAIN
BELOW GRADE / FLOOR
REVISION NUMBER
NUMBERED NOTE
REMOVE EXISTING
CAP EXISTING / CAP FOR FUTURE
RELOCATE EXISTING
FUTURE
WALL-MOUNTED
PENDENT-MOUNTED
TEMPERATURE
HUMIDITY
DIFFERENTIAL
PRESSURE SWITCH
T
H
DP
T
H
DP
WALL-MOUNTED
PENDENT-MOUNTED
CARBON MONOXIDE
CARBON DIOXIDE
NITROGEN OXIDE
CO
CO2
NOX
CO
CO2
NOX
SENSORS
TERMINAL UNIT NUMBER
TERMINAL UNIT
FLOOR UNIT IS LOCATED ON
AIR HANDLER NUMBER
TERMINAL UNITS
24x16
R
R=1-1/2W
RADIUS ELBOW
W
MITER ELBOWS & TEES
TURNING VANES IN ALL
ELBOWS AND TEES FLEX
CONNECTION ACOUSTICAL LINER
SIZE SHOWN IS CLEAR
AIR PASSAGE
DUCT OFFSETS
R=1-1/2W W
LESS THAN 15° 15° TO 30° GREATER THAN 30°
30° MAX 30° MAX
TRANSITIONS
RECTANGULAR TO ROUND
45°
W
4" MIN OR
1/4W OR
12" MAX
RECTANGULAR DUCT FITTING
SPIN-IN
FITTING
CONICAL SPIN-IN
FITTING
RECTANGULAR TO ROUND FITTING
FS
D
CFM
TYPE
RETURN EXHAUST SUPPLY
FLOW DIRECTION
(NONE SHOWN
IF 4-WAY)
CFM
SIZE TYPE
TYPE REFERENCE
H = 6" BELOW CEILING
L = 6" ABOVE FLOOR
F = FLOOR
S = SLOT DIFFUSER
C = CEILING
T = DOOR TRANSFER
NECK SIZE (SIDEWALL & FLOOR GRILLE)
PLENUM INLET SIZE (SLOT DIFFUSER)
CEILING DIFFUSERS & GRILLES SIDEWALL, SLOT & FLOOR GRILLES
SUPPLY
AIR
RETURN
AIR
EXHAUST
AIR
OUTSIDE
AIR
DUCT SECTIONS
COMBINATION
FIRE/SMOKE FIRE
SMOKE
VOLUME
AUTOMATIC
RETURN OR EXHAUST AIR FLOW
SUPPLY OR OUTSIDE AIR FLOW
UNDERCUT DOORUC 1/2"
SECTION
R=2D FOR FLEX
PLAN
R=1-1/2D FOR ROUNDD
R
RETURN OR EXHAUST GRILLE CONNECTION
SECTION
D
R
R=2D FOR FLEX
PLAN
R=1-1/2D FOR ROUNDD
R
SUPPLY DIFFUSER CONNECTION
SECTION PLAN
SECTION PLAN
SECTION PLAN
SUPPLY DIFFUSER SIDE FLEX CONNECTION
SECTION PLAN
RETURN OR EXHAUST GRILLE
FLEX DUCT ROUND DUCT
FLEX DUCT ROUND DUCT
RECTANGULAR DUCT SQUARE NECK
SPIN-IN
FITTING
D
R
LINED PLENUM
FLEX DUCT
SEE SPEC FOR TYPE
SEE SCHEDULE FOR SIZE
DAMPERS
SECTION PLAN SECTION PLAN
SUPPLY DIFFUSER HARD CONNECTION SIDEWALL SUPPLY GRILLE CONNECTION
DUCT LEGEND
LOW PRESSURE DUCTWORK
DUCT DETAILS (LOW VELOCITY)
FD S
D
INCH, INCHESIN
P A R K
SO
N
E G
O R S T A T E
O R E G O N
P A R K S
A N D
R E C R E A
TI
O N
D E P A R
TM
E N T
D E S
IG
N E D
B Y
A P P R O V E D
B Y
C H E C K E D
B Y
D R A W N
B Y
D A T E
R E V
IS
IO
N
D A T E
B Y
SHEET:
OPRIS#: CONTRACT #:
1065436857
M0.01B
P A
E
P A
E
P A
E
P A
E
/1
/2
S T
A F
F H
O U
S
IN
G P
R O
J E
C T
C A
B
IN
B U
IL
D
IN
G
P L
A N
S N
E H
A L
E M
S T
A T
E P
A R
K
L E
G E
N D
S A
N D
S C
H E
D U
L E
S
M E
C H
A N
IC
A
L
A. OUTDOOR CONDITIONS BASED ON ASHRAE FUNDAMENTALS 2021 99.6% AND 0.4% DATA.
GENERAL NOTES:
INDOOR 70˚ F ± 2˚ F DB 75˚ F ± 2˚ F DB
OUTDOOR 5˚ F DB 94˚ F DB / 61˚ F MCWB
TEMPERATURE TEMPERATURE
SPACE WINTER SUMMER
DESIGN CONDITIONS - BASED ON BEND/REDMOND, OR
C. PROVIDE UNIT WITH SINGLE POINT POWER CONNECTION AND FUSED DISCONNECT.
B. HEAT RECOVERY SECTION EFFECTIVENESS IS BASED ON AHRI 1060.
A. UNIT HUNG FROM STRUCTURE WITH VIBRATION ISOLATION PER SPECIFICATIONS AND PER MANUFACTURER'S INSTRUCTIONS.
GENERAL NOTES:
ERV-01 LARGE/DELUXE/STAFF CABINS 13 180 0.4 ECM 6 180 0.4 ECM ENTHALPY CORE 73 1.9 120/1 200 60 VENT-US ERV 150 EC
TAG SERVICE (MERV) (CFM) (IN WG) CONTROL (MERV) (CFM) (IN WG) CONTROL TYPE (%) (SONES) PHASE (WATTS) (LBS) & MODEL NOTES
FILTER AIRFLOW MAX ESP SPEED FILTER AIRFLOW MAX ESP SPEED SENSIBLE EFF VOLT/ POWER WEIGHT MANUFACTURER
SUPPLY FAN EXHAUST FAN ENERGY RECOVERY SOUND ELECTRICAL
ENERGY RECOVERY VENTILATOR SCHEDULE
C. ROUTE CONDENSATE DRAIN TO EXTERIOR.
B. PROVIDE WASHABLE ELECTROSTATIC FILTER.
A. PROVIDE WALL MOUNTED PROGRAMMABLE CONTROLLER/THERMOSTAT FOR EACH INDOOR UNIT.
GENERAL NOTES:
FCU-02 BEDROOM WALL MOUNTED 9.0 9.6 208/230, 1 1.00 40 MITSUBISHI NTXWPH09
FCU-01 LIVING ROOM WALL MOUNTED 9.0 9.6 208/230, 1 1.00 40 MITSUBISHI NTXWPH09
TAG LOCATION TYPE (MBH) (MBH) PHASE (A) (LBS) & MODEL NOTES
TOTAL TOTAL VOLT, MCA WEIGHT MANUFACTURER
COOLING HEATING ELECTRICAL APPROX.
FAN COIL UNIT SCHEDULE
D. MOUNT ON HOUSEKEEPING PAD ON GRADE WITH VIBRATION ISOLATION PER SPECIFICATIONS AND PER MANUFACTURER'S INSTRUCTIONS.
C. PROVIDE 100% HEATING CAPACITY DOWN TO -5°F OAT.
B. COOLING EFFICIENCY RATED AT 95°F OAT. HEATING EFFICIENCY RATED AT 47°F OAT.
A. COOLING CAPACITY RATED AT 95°F OAT. HEATING CAPACITY RATED AT 5°F OAT.
GENERAL NOTES:
ODU-01 ON GRADE FCU-1-1,FCU-1-2 18 22 17.1/14.3 4.37 R410A 208/230, 1 30 200 MITSUBISHI NTXMPH20
TAG LOCATION SERVICE (MBH) (MBH) SEER/EER COP TYPE PHASE (A) (LBS) & MODEL NOTES
COOLING HEATING COOLING HEATING VOLT, MCA WEIGHT MANUFACTURER
CAPACITY MIN EFFICIENCY REFRIGERANT ELECTRICAL APPROX.
OUTDOOR UNIT SCHEDULE
B. PROVIDE INTEGRAL THERMOSTAT CONTROL.
A. UNIT MOUNTED HIGH ON WALL.
GENERAL NOTES:
EH-01 DELUXE/STAFF CABIN BATHROOM ELECTRIC COVE 34 420 120/1 10 KING KCV1204
TAG SERVICE TYPE (IN) (WATTS) PHASE (LBS) & MODEL NOTES
LENGTH CAPACITY VOLT/ WEIGHT MANUFACTURER
ELECTRIC HEATER SCHEDULE
12/11/23
C
B
UP 4 RISERS @ 5.5"
3 TREADS @ 12"
FCU-01
ODU-01
C-2
ERV-016"ø EA
6"ø EA
6"ø OA
H-1
(TYP 2)
6"ø EA
EXHAUST HOOD
RL/RS
32EH-01
FCU-02
5T
4T
4T
RL/RS
6"ø SA
SLEEPING
LIVING/DINING
BATHROOM
A. RUN DUCTS AND PIPING CONCEALED, UNLESS
SPECIFIED OTHERWISE, AND CLEAR OF
CEILING INSERTS. ALL DUCTWORK SHALL BE
INSTALLED AS CLOSE AS POSSIBLE TO WALL
AND UNDERSIDE OF BEAMS AND JOISTS.
B. ALL WORK SHALL BE COORDINATED WITH ALL
TRADES INVOLVED. OFFETS IN PIPING AND
DUCTS (INCLUDING DIVIDED DUCTS) AND
TRANSITIONS AROUND OBSTRUCTIONS SHALL
BE PROVIDED AT NO ADDITIONAL COST TO
THE OWNER.
C. VERIFY ALL EQUIPMENT CONNECTIONS WITH
MANUFACTURER'S CERTIFIED DRAWINGS.
VERIFY AND PROVIDE DUCT TRANSITIONS TO
FURNISHED EQUIPMENT. FIELD VERIFY AND
COORDINATE ALL DIMENSIONS BEFORE
FABRICATION.
D. REFER TO ARCHITECTURAL REFLECTED
CEILING PLANS, ELEVATIONS, AND FLOOR
PLANS FOR ACTUAL LOCATIONS OF ALL
CEILING, WALL, AND FLOOR MOUNTED
DEVICES AND EQUIPMENT.
E. COORDINATE ACCESS PANEL LOCATIONS
WITH ARCHITECT.
GENERAL NOTES:
P A R K
SO
N
E G
O R S T A T E
O R E G O N
P A R K S
A N D
R E C R E A
TI
O N
D E P A R
TM
E N T
D E S
IG
N E D
B Y
A P P R O V E D
B Y
C H E C K E D
B Y
D R A W N
B Y
D A T E
R E V
IS
IO
N
D A T E
B Y
SHEET:
OPRIS#: CONTRACT #:
1065436857
M2.11B
P A
E
P A
E
P A
E
P A
E
/1
/2
S T
A F
F H
O U
S
IN
G P
R O
J E
C T
C A
B
IN
B U
IL
D
IN
G
P L
A N
S N
E H
A L
E M
S T
A T
E P
A R
K
S T
A F
F F
L O
O R
P L
M E
C H
1/2" = 1'-0"
STAFF - MECHANICAL
NORTH
1. PROVIDE HOUSEKEEPING PAD AND MOUNT
ON GRADE.
2. PROVIDE 2-FT BY 2-FT ACCESS PANEL IN
CLEARANCE ZONE.
3. PROVIDE MINIMUM 0.5-SF FREE AREA
LOUVER (APPROXIMATELY 1-SF GROSS
AREA).
4. PROVIDE PROGRAMMABLE WALL MOUNTED
THERMOSTAT CONTROLLER FOR FCU.
BASED ON MITSUBISHI MODEL TAR.
5. PROVIDE INTERGRAL THERMOSTAT TO
COVE HEATER. BASED ON KING MODEL
KCVT.
6. ROUTE CONDENSATE THROUGH EXTERIOR
WALL TO DRAIN AT GRADE. COORDINATE
PENETRATION THROUGH EXTERIOR WALL
WITH ARCHITECT AND SEAL AIR TIGHT.
7. 2-IN EXHAUST VENT AND INTAKE TO
PROPANE WATER HEATER. BASED ON
RINNAI FLEX ROLL FOR CONDENSING
APPLIANCES. TERMINATE IN APPROVED
VENT CAP FOR VERTICAL WALL.
8. PROVIDE CLEARANCE AROUND ALL SIDES
OF UNIT PER MANUFACTURER
INSTALLATION REQUIREMENTS. PROVIDE
36-INCH CLEARANCE IN FRONT OF
ELECTRICAL DISCONNECT.
NOTES:
NEW, POINT OF CONNECTION
EQUIPMENT DESIGNATOR SEE SCHEDULE.
TRANSFORMERXFMR
WEATHERPROOFWP
WATTSW
VOLT-AMPEREVA
VOLTAGEV
UNDERGROUNDUG
TYPICALTYP
TELEVISIONTV
TAMPERPROOFTP
TIME DELAYTD
SWITCHSW
SOLENOID VALVESV
STARTERSTR
POWERPWR
POLYVINYL CHLORIDEPVC
PANELBOARDPNL
PHOTOELECTRIC CELLPE
NOT IN CONTRACTNIC
MANUAL TRANSFER SWITCHMTS
MEDIUM VOLTAGEMV
MAIN LUGS ONLYMLO
MECHANICALMECH
MAIN CIRCUIT BREAKERMCB
MINIMUM CIRCUIT AMPACITYMCA
LOW VOLTAGELV
LIGHTINGLTG
KILOVOLT-AMPEREKVA
KILOVOLTKV
KILOWATT HOURKWH
KILOWATTKW
JUNCTION BOXJB
HERTZHZ
HIGH VOLTAGEHV
HORSEPOWERHP
GROUNDGND
GALVANIZED RIGID CONDUITGRC
GROUND FAULT CIRCUIT INTERRUPTERGFCI
INSTALLED BY OWNER
FURNISHED BY OWNERFOIO
INSTALLED BY CONTRACTOR
FURNISHED BY OWNERFOIC
INSTALLED BY CONTRACTOR
FURNISHED BY CONTRACTORFCIC
FLUORESCENTFLUOR
FULL LOAD AMPSFLA
FIRE ALARMFA
ELECTRICAL METALLIC TUBINGEMT
EMERGENCYEM
DOWNDN
COPPERCU
CURRENT TRANSFORMERCT
CEILINGCLG
CIRCUITCKT
CONDUITC
CIRCUIT BREAKERCB
ARCHITECT / ARCHITECTURALARCH
ALUMINUMAL
AMPERE (AMP)A
AMERICANS DISABILITIES ACTADA
NOTE
EXISTING TO BE RELOCATED, FUTURE
EXISTING TO REMAIN, EXISTING TO BE REMOVED
AMERICAN WIRE GAUGEAWG
J
WALL RECEPTACLE: DUPLEX, QUADPLEX
JUNCTION BOX
CONNECTION TO EQUIPMENT PROVIDED BY OTHERS
42. DENOTES CIRCUIT NUMBER.
REFER TO SHEET GENERAL NOTES FOR PANELBOARD.
PANELBOARD: SURFACE, RECESSED
DENOTES GFCI
SPECIAL PURPOSE RECEPTACLE.
DENOTES RECEPTACLE ABOVE COUNTER
DENOTES GFCI AND
WEATHER PROOF
G SINGLE WALL RECEPTACLE, FACELESS GFCI REMOTE TEST BUTTON
G G
WW
ABOVE FINISHED FLOORAFF LIGHT EMITTING DIODELED
MAXIMUM…
This is the start of the file's text. The full file is on GovTribe.