This document is an Electrical Connection Schedule for Building Management System (BMS) Panels that provides comprehensive specifications for electrical infrastructure across multiple buildings numbered 1 through 120. The schedule details BMS panel locations, normal power sources, emergency power sources, and mechanical reference drawings for facilities management purposes. The document contains two primary sections: the first is a panel names and location notes table identifying specific panel designations (B1.P0 through B120.P4) organized by building, with associated room numbers, circuit information, and functional notes; the second is a detailed electrical connection schedule correlating each BMS panel to its normal power source panel and circuit, emergency power source panel and circuit, panel locations, room numbers, and corresponding mechanical reference drawings.

The schedule encompasses multiple building types and systems including fan rooms, mechanical rooms, AHUs (Air Handling Units), boiler rooms, electrical rooms, and specialized facilities such as nuclear medicine, dental, and radiology areas. Key facilities referenced include the Allerton building complex, with panels supporting HVAC systems, pumps, and control functions across distributed locations. Normal power sources are identified through specific circuit designations (e.g., 2N1C, 2N7B, 2N20B) while emergency power sources reference corresponding panel locations and circuits. The mechanical reference drawings are standardized as format "##-M-###" (e.g., 01-M-401, 02-M-111). Notable system types include MBC (Modular Building Controller), MEC (Mechanical Equipment Controller), and PXC 36 (control panels with expansion capabilities), indicating a Siemens building automation infrastructure. This schedule serves as a critical reference document for electrical contractors, facilities engineers, and BMS technicians implementing or maintaining the automated building control systems across the facility complex.

View the file

Other files

Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PANEL SOURCE CIRCUIT#

PANELLOCATlb

N

RM#

PANEL

SOURCE

CIRCUIT#

PANEL LOCATION

RM#

PANEL NAMES AND LOCATION NOTES FROM UTILITIES SHOP

1 B1.PO G44A 2N1C 10 G29 2Ql 36 G30 01-M-401 ALLERTON 1 B1.P1 ATTIC 2LCIY 9 TBD Ql-4-lNA TBD ATTIC 01-M-401 B1.P1 FAN ROOM 5 NODE 1, AHU 1 &2 MEC W/EXPANSION 1 B1.P2 G44A 2N1C 10 G29 2Ql 36 G30 01-M-401 B1.P2 FAN ROOM 6 MBC BEHIND G44A NODE 2 NUCMED DENTAL 1 B1.P3 G29 TBD TBD TBD SPDl 2 G30 01-M-401 B1.P3 G30 NODE 32 MBC 1 B1.P4 4TH FLR 2N1FF TBD 406A 2Ql 40 G30 01-M-141 B1.P4 AHU2 :7172 BACKNET PXC 36 W/EXPANSION 4TH FLOOR FAN ROOM 2 1 B1.P5 4TH FLR 2N1FF TBD 406A 2Ql 42 G30 01-M-141 B1.P5 AHU1: 7171 BACKNET PXC36 W/EXPANSION 4TH FLOOR FAN ROOM 1 1 B1.P6 G44A 2N1C 10 G29 2Ql 36 G30 01-M-401 B1.P6 ALLERTON 1 B1.P7 G41 2N1C TBD G29 2Ql 38 G30 01-M-401 B1.P7 ALLERTON

2 B2.PO G25A TBD TBD G22 2Q2A 13 TBD 02-M-401 ALLERTON

2 B2.P1 G2SA TBD TBD G22 2Q2A 13 TBD 02-M-401 B2.P1 ALLERTON

2 B2.P2 FAN RM2 TBD TBD TBD 2Q2A 13 TBD 02-M-401 B2.P2 FAN ROOM (G25) NODE 4 MBC HAS POINTS FOR AL5, AHU 10, 11, 30, 33, 5W, E6, AL9 2 B2.P3 10 TBD TBD TBD 2Q2D 3S 102J 02-M-401 B2.P3 - 105J - MEDIA HALLWAY NODE 3 AHU10 POINTS 2 B2.P4 G24 TBD TBD G22 2Q2A TBD TBD 02-M-401 B2.P4 - 102J ELECTRICAL ROOM IN KITCHEN NODE 33 MEC W/EXPANSIONS AHU30

2 B2.P5 ROOF TBD TBD TBD 202D 37 102J 02-M-111 B2.P5 AHU - 08 NODE 34 MEC

2 B2.P6 ROOF TBD TBD TBD 2Q2D 39 102J 02-M-111 B2.P6 AHU - 09 NODE 39 PXC 36 W/EXPANSIONS AHU9

2 B2.P7 G21 TBD TBD G22 2Q2A TBD TBD 02-M-401 B2.P5 AHU - 09 NODE 36 MEC AHU 9T

3 B3.P0 BASEMEN TBD TBD TBD TBD TBD TBD 03-M-401

3 B3.P2 ATTIC TBD TBD TBD TBD TBD TBD 03-M-401 B3.P2 FAN ROOM 11 NORTH NODE 7 MEC W/2 EXPANSIONS AHU 16 3 B3.P3 ATTIC TBD TBD TBD TBD TBD TBD 03-M-401 B3.P3 FAN ROOM 11 NORTH NODE 8 MEC W/2 EXPANSIONS AHU 17 3 B3.P4 ATTIC TBD TBD TBD TBD TBD TBD 03-M-401 B3.P4 FAN ROOM 11 NORTH NODE 70 MEC W/EXPANSION ISO FANS

B5.P0 BASEMEN TBD TBD TBD TBD TBD TBD O5-M-401

5 B5.P1 ATTIC TBD TBD TBD 2Q5 7 TBD O5-M-401 B5.P1 NODE 10 FAN ROOM 15 MEC W/EXPANSION - SVC ROOM FUNCTIONS 5 B5.P2 BASEMEN TBD TBD TBD 2Q55R 2 BASEMENT 05-M-401 B5.P2 NODE 11 FAN ROOM 14 PXC 36 W/CONTROL FRONT AHU 19 + AHU 15 HUMIDITY FUNCTION 5 B5.P4 ATTIC TBD TBD TBD 2Q5 7 TBD 05-M-401 B5.P4 NODE 71 FAN ROOM 14 MEC MONITORS LIBERT , COMPUTER ROOMS, AND EX FANS 7 B7.PO G2S TBD TBD TBD TBD TBD TBD 07-M-401 ALLERTON? THERE IS NO 4TH PANEL FOR SIEMENS LISTED IN BLDG 7 7 B7.P1 GSO 2N7B TBD GSOB 2Q7B TBD GSOB 07-M-401 B7.P1 NODE 16 MBC G50 AHU 7C+AHU 7D+PUMPS 7 B7.P2 G51 2N7A TBD GSlB 2Q7A TBD G51B 07-M-401 B7.P2 NODE 17 MBC G51 AHU 7A+7B 7 B7.P3 G25 TBD TBD TBD TBD TBD TBD 07-M-401 B7.P3 NODE 18 MEC G25 BLDG 7 HW SYSTEM 8 B8.PO G2S TBD TBD TBD TBD TBD TBD 08-M-401 THERE IS NO 4TH PANEL FOR SIEMENS LISTED IN BLDG 8 8 B8.P1 G33 TBD TBD G33A TBD TBD G33A 08-M-401 B8.P1 NODE 19 MBC G33 AHU 8C+AHU 8D+PUMPS

8 B8.P2 G34 2N8A 1 G34B 2LBA 8 G34B 08-M-401 B8.P2 NODE 20 MBC G34 AHU 8A+AHU 8B

8 B8.P3 G13 TBD TBD TBD TBD TBD TBD O8-M-401 B8.P3 NODE 21 MEC PUMPS FOR DOMESTIC HOT WATER SYSTEM EXCHANGER

9 B9.P0 BASEMEN TBD TBD TBD TBD TBD TBD O9-M-401

9 B9.P1 ATTIC TBD TBD TBD TBD TBD TBD O9-M-401 B9.P1 NODE 23 MEC FAN ROOM 21 SVC FUNCTIONS 9 B9.P2 ATTIC TBD TBD TBD TBD TBD TBD O9-M-401 B9.P2 NODE 25 MEC FAN ROOM 20 AHU 25+AHU 26 9 B9.P4 ATTIC TBD TBD TBD TBD TBD TBD O9-M-401 B9.P4 NODE 67 MEC FAN ROOM 20 EXAHUST FANS

10 B10.P0 G15 TBD TBD TBD TBD TBD TBD 10-M-101

10 B10.P1 G15 TBD TBD TBD TBD TBD TBD 10-M-101 B10.P1 NODE 26 MEC FAN ROOM 22

11 B11.P0 G04 TBD TBD TBD TBD TBD TBD 11-M-101

11 B11.P1 G04 TBD TBD TBD TBD TBD TBD 11-M-101 B11.P1 NODE 27 MEC FAN ROOM 24

16 B16.PO CTRL RM TBD TBD TBD TBD TBD TBD 16-M-101 B16.P1 BOILER MAU 1&2 NODE 22 B16.P2 BOILER PUMPS NODE 24

116 B116.P1 A114A A3 5 A114A EA 2S A114A 116-M-401 B116.P1 NODE 78 MEC G114C SVC ROOM FUNCTIONS 116 B116.P2 A114C A3 5 A114A EA 25 A114A 116-M-401 B116.P2 NODE 79 MBC A114C AHU 40

117 B117.PO 100 TBD TBD TBD TBD TBD TBD 117-M-401 ALLERTON?

117 B117.P1 FAN RM8 TBD TBD TBD 2Q7E 27 FAN RMB 117-M-401 B117.P1 NODE 76 MBC FAN FOOM 9 W/EXPANSION BUS AHU 13+AHU 14 117 B117.P2 FAN RM9 N?G TBD FAN RM9 2Q7G 2S FAN RM9 117-M-401 B117.P2 NODE 77 MBC FAN ROOM 9 ISO FANS AL1 + AL2 120 B120.P1 FAN RM 10 2N20B 31 FAN RM 10 2Q20B 19 FAN RM 10 120-M-401 B120.P2 NODE 81 FAN ROOM 10 PXC

120 B120.P2 FAN RM 10 2N20B 31 FAN RM 10 2Q20B TBD FAN RM 10 120-M-401

120 B120.P3 FAN RM 10 2N20B 31 FAN RM 10 2Q20B TBD FAN RM 10 120-M-401

120 B120.P4 FAN RM 10 2N20B 31 FAN RM 10 2Q20B 19 FAN RM 10 120-M-401 B120.P4 NODE 84 MEC RADIOLOGY

ELECTRICAL CONNECTION SCHEDULE FOR BMS PANELS

BUILD

ING

BMS

PANEL

NAME

BMS

PANEL

ROOM#

NORMAL POWER SOURCE EMERGENCY POWER SOURCE MECHANICAL

REFERENCE

DRAWING#