Attachment A - Approved As Noted Const Drawings - 02.13.24.pdf
PDF 2 MB Posted
- Solicitation number
- 59722
- Issued by
- Fairfax County, Falls Church City, Virginia
About this file
This document contains construction drawings and specifications for the Piedmont and Tidewater Dormitories Roofing Replacement project at George Mason University in Fairfax, Virginia. The project scope includes the removal of the existing asphalt shingle roofing, underlayment, flashings and roof penetrations on the Piedmont and Tidewater dormitory buildings, and replacement with a new asphalt shingle roofing system. Additional insulation is to be installed in the attic spaces. The existing built-up roofing on the low roof connecting the Piedmont and Tidewater buildings shall be removed down to the existing deck and replaced with a fully-adhered EPDM roofing system. The buildings will remain occupied and operational throughout construction, and the contractor must protect occupants and pedestrians at all times.
The contract opportunity is designated as Project Number 247-221547. Sealed bids are being invited for the construction services. The contract includes unit pricing for the removal and replacement of damaged plywood sheathing. The project is subject to the Virginia Uniform Statewide Building Code, the Virginia State Fire Prevention Code, the Construction and Professional Services Manual, and the ADA Standards for Accessible Design. An asbestos inspection was not performed as all portions of the existing building were constructed after 1985, and a lead-based paint inspection was not conducted for the same reason.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EARTH
GRANULAR FILL
CONCRETE
BRICK
CMU
MARBLE
GROUT
STEEL
WOOD LUMBER
FINISH LUMBER
PLYWOOD
GYPSUM WALLBOARD
BATT INSULATION
RIGID INSULATION
SEALANT
SEALANT & BACKER ROD
SEALANT & COMPRESSIBLE
MATERIAL
ROOM NAME &
NUMBER
PARTITION TYPE
DOOR TYPE
# WINDOW TYPE
LEVEL MARKER
KEYNOTE
SECTION REFERENCE
SECTION NUMBER
SHEET NUMBER WHERE
DETAIL IS LOCATED
SHEET NUMBER WHERE
DETAIL IS REFERENCED
FROM
DETAIL REFERENCE
DETAIL NUMBER
SHEET NUMBER
WHERE SECTION IS
REFERENCED FROM
SHEET NUMBER WHERE
SECTION IS LOCATED
ELEVATION REFERENCE
ELEVATION NUMBER
SHEET NUMBER WHERE
ELEVATION IS REFERENCED
FROM SHEET NUMBER WHERE
ELEVATION IS LOCATED
INTERIOR ELEVATION
ELEVATION NUMBER
SHEET NUMBER WHERE
ELEVATION IS LOCATED
SECTION NUMBER
SHEET NUMBER WHERE
SECTION IS LOCATED
Name
NAME
PROJECT LOCATION
EXISTING TO REMAIN
EXISTING TO BE DEMOLISHED
NEW CONSTRUCTION
I-66
I-
LITTLE RIVER TURNPIKE
C H A
IN
B R
ID
G E R
D
BRADDOCK RD
ARLINGTON BLVD
PROJECT LOCATION
General
G0.01 Cover Sheet
Architectural
AD1.01 Demolition Roof Plan & Demolition Details
A1.01 Roof Plan
A5.01 Roof Details
A5.02 Roof Details
SHEET INDEX
Piedmont and Tidewater Dormitories
Roofing Replacement
4349 Chesapeake River Way C & D Fairfax, VA 22030
T
C
A
LAE
WN
O M
M O
OF
I
NI
G
RI
H V
I T EC T
HCRA
LOUIS M.
BARBIERI JR.
Lic. No. 16266
Consultants
Seal
Key Plan
Drawing
Date
Project No.
Sheet No.
OUBO SUBMISSION 12/20/23
703.684.5994
333 North Fairfax Street
Alexandria, Virginia 22314 coleanddenny.com
Revisions
Submission Set
PC No.: 247-221547
Permit Electronic Approval Stamp
12/20/23
20011.16
4349 Chesapeake River Way C & D Fairfax, VA 22030
G0.01
Cover Sheet
George Mason University Piedmont and Tidewater Dormitories Roofing Replacement
THE PROJECT INCLUDES THE REMOVAL OF THE EXISTING ASPHALT SHINGLE ROOFING, UNDERLAYMENT, FLASHINGS AND ROOF PENETRATIONS ON THE PIEDMONT AND TIDEWATER DORMITORY BUILDINGS, AND
REPLACEMENT WITH A NEW ASPHALT SHINGLE ROOFING SYSTEM. ADDITIONAL INSULATION IS TO BE INSTALLED
IN THE ATTIC SPACES. THE EXISTING BUILT-UP ROOFING ON THE LOW ROOF CONNECTING THE PIEDMONT AND
TIDEWATER BUILDINGS SHALL BE REMOVED DOWN TO THE EXISTING DECK AND REPLACED WITH A FULLY-
ADHERED EPDM ROOFING SYSTEM. THE GUTTERS AND DOWNSPOUTS ARE EXISTING TO REMAIN, HOWEVER THEY
SHALL BE INSPECTED, CLEANED AND RE-SET TO INSURE PROPER DRAINAGE. THE EXISTING LIGHTNING
PROTECTION SYSTEM SHALL BE REMOVED AND REINSTALLED AS NEEDED TO ACCOMPLISH THE WORK. AT THE
COMPLETION OF THE PROJECT, THE CONTRACTOR SHALL ENGAGE A CERTIFIED 3RD PARTY TESTING AGENCY FOR
UL 96A MASTER LABEL CERTIFICATE. THE CONTRACTOR SHALL RECTIFY ANY ISSUES TO ACHIEVE THE UL 96A
MASTER LABEL RELATED TO THE WORK AND SERVICES PERFORMED IN THIS CONTRACT. THE BUILDINGS WILL
REMAIN OCCUPIED AND OPERTIONAL THROUGHOUT CONSTRUCTION AND OCCUPANTS AND PEDESTRIANS SHALL
BE PROTECTED AT ALL TIMES.
DESCRIPTION OF WORK
AN ASBESTOS INSPECTION WAS NOT PERFORMED BECAUSE ALL PORTIONS OF THE EXISTING BUILDING THAT MAY
BE AFFECTED BY THE WORK WERE ORIGINALLY CONSTRUCTED AFTER JANUARY 1, 1985.
ASBESTOS DISCLOSURE STATEMENT
AN INSPECTION TO IDENTIFY LEAD CONTAINING OR COATED BUILDING COMPONENTS HAS NOT BEEN CONDUCTED
BECAUSE THE BUILDING WAS CONSTRUCTED AFTER JANUARY 1, 1985 AND THE OWNER HAS NO KNOWLEDGE OF
LEAD CONTAINING OR COATED BUILDING COMPONENTS IN THE BUILDING. IT IS THE CONTRACTOR’S
RESPONSIBILITY TO COMPLY WITH ALL VIRGINIA OCCUPATIONAL SAFETY AND HEALTH (VOSH) REGULATIONS AS
THEY PERTAIN TO EMPLOYEE EXPOSURES TO LEAD. ALL LEAD AND LEAD-COATED BUILDING COMPONENTS SHALL
BE RECYCLED TO THE EXTENT POSSIBLE.
LEAD-BASED PAINT DISCLOSURE STATEMENT
APPLICABLE CODES
THE BUILDING CODE AUTHORITY IS THE OFFICE OF THE UNIVERSITY BUILDING OFFICIAL
(OUBO) OF GEORGE MASON UNIVERSITY (GMU).
THE BUILDING CODE FOR THIS PROJECT IS THE VIRGINIA UNIFORM STATEWIDE BUILDING
CODE (VUSBC) 2018 EDITION. ALL WORK SHALL CONFORM TO THE BUILDING CODE.
THE PROJECT IS CLASSIFIED AS LEVEL 1 ALTERATION PER SECTION 601 OF THE VIRGINIA
EXISTING BUILDING CODE, 2018 EDITION.
THE FIRE CODES FOR THIS PROJECT ARE THE VIRGINIA STATE FIRE PREVENTION CODE,
2018 EDITION.
THE CONSTRUCTION AND PROFESSIONAL SERVICES MANUAL (CPSM) 2022 APPLIES TO
THIS PROJECT.
THE ACCESSIBILITY CODE FOR THIS PROJECT IS THE ADA STANDARDS FOR ACCESSIBLE
DESIGN (ASAD) 2010 EDITION. REFER TO SECTIONS 4.2.2 & 4.4 OF THE CPSM 2021
EDITION, REV 1 FOR EXCEPTIONS, AND FOR A COMPLETE LIST OF CODES AND
REGULATIONS WHICH MAY APPLY TO, OR TAKE PRECEDENCE OVER, CODES IDENTIFIED
HEREIN.
THE HIGHER EDUCATION CAPITAL OUTLAY (HECO) 2023 EDITION APPLIES TO THIS PROJECT.
MATERIALSDRAWING SYMBOLS
CODE SUMMARY
ORIGINAL CODE BUILT UNDER:
USE & OCCUPANCY CLASSIFICATION:
CONSTRUCTION TYPE:
SPRINKLERED:
EXISTING BUILDING AREA:
EXISTING BUILDING HEIGHT:
PROJECT AREA:
VUSBC 2000
R-1, R-2
A-3, M, B
1B
YES
128,578 SF
5/6 STORIES
30,079 SF
VICINITY PLAN
ABBREVIATIONS
PHASING
# NUMBER
& AND
@ AT
ACP ACOUSTICAL CEILING PANEL
AFF ABOVE FINISH FLOOR
ALT ALTERNATIVE
ALUM ALUMINUM
ASTM AMERICAN SOCIETY OF TESTING &
MATERIALS
BD BUILDING
BOT BOTTOM
CJ CONTROL JOINT
CLG CEILING
CLOS CLOSET
CMU CONCRETE MASONRY UNIT
CONC CONCRETE
CONT CONTINUOUS
CPT CARPET
CT CERAMIC TILE
DEMO DEMOLITION
DF DRINKING FOUNTAIN
DIA DIAMETER
DN DOWN
DS DOWNSPOUT
EF EXHAUST FAN
EIFS EXTERIOR INSULATION FINISHING SYSTEM
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRICAL
ELEV ELEVATOR
EQ EQUAL
EQUIP EQUIPMENT
ETR EXISTING TO REMAIN
EXIST EXISTING
EXT EXTERIOR
FE FIRE EXTINGUISHER
FRT FIRE RETARDANT TREATED
FT FEET/FOOT
GA GAUGE
GALV GALVANIZED
GWB GYPSUM WALL BOARD
HDWR HARDWARE
HM HOLLOW METAL
HR HOUR
IN INCH
INSUL INSULATION
INT INTERIOR
JAN JANITOR'S CLOSET
JT JOINT
MAX MAXIMUM
MECH MECHANICAL
MFR MANUFACTURER
MIN MINIMUM
MO MASONRY OPENING
MTL METAL
N NORTH
NIC NOT IN CONTRACT
NO NUMBER
OC ON CENTER
PLAM PLASTIC LAMINATE
PLUMB PLUMBING
PLYWD PLYWOOD
PT PRESSURE TREATED
PTD PAINTED
PVC POLYVINYL CHLORIDE
RB RESILIENT BASE
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
RM ROOM
SCW SOLID CORE WOOD
SF SQUARE FOOT/FEET
SIM SIMILAR
SST STAINLESS STEEL
STOR STORAGE
STRUCT STRUCTURAL
THRU THROUGH
TOS TOP OF STEEL
TYP TYPICAL
UL UNDERWRITER'S LABORATORIES
UNO UNLESS NOTED OTHERWISE
VCT VINYL COMPOSITE TILE
VEST VESTIBULE
VIF VERIFY IN FIELD
VWC VINYL WALL COVERING
W/ WITH
WD WOOD
HIGH PERFORMANCE BUILDINGS ACT
COMPLIANCE STATEMENT
VIRGINIA ENERGY CONSERVATION CODE
COMPLIANCE STATEMENT
IN ACCORD WITH THE HIGH PERFORMANCE BUILDINGS ACT, THE BUILDING IS EXEMPT FROM COMPLIANCE
BECAUSE THE COST OF THE RENOVATIONS DOES NOT EXCEED 50% OF THE VALUE OF THE BUILDING.
1. IN ACCORD WITH THE VIRGINIA ENERGY CONSERVATION CODE (VECC), THE BUILDING SHALL COMPLY
WITH VECC SECTIONS C402 THROUGH C405 AND C408.
PER TABLE C402.1.3, R-38 ATTIC INSULATION IS ACHIEVED AS FOLLOWS.
ASPHALT SHINGLE ROOFING AREAS:
EXISTING: R-30 LOOSE FILL INSULATION IN ATTIC
NEW: R-8 LOOSE FILL INSULATION IN ATTIC
TOTAL: R-38 LOOSE FILL INSULATION IN ATTIC.
EPDM ROOFING AREAS:
NEW AVERAGE R-30 CONTINUIOUS TAPERED INSULATION ABOVE ROOF DECK
Project Number: 247-221547
LOCATION MAP
George Mason University
UNIT PRICES
1. UNIT PRICE SHALL BE BASED ON AN ESTIMATED QUANITY OF 800 SQUARE FEET
FOR THE REMOVAL OF ROTTED OR OTHERWISE DAMAGED PLYWOOD SHEATHING,
AND REPLACEMENT WITH 3/4" CDX FIRE RATED PLYWOOD SHEATHING FOR THE
PURPOSES OF THE UNIT PRICE. THE CONTRACTOR SHALL ASSUME THAT THE
REMOVAL AND REPLACEMENT WILL BE A MINIMUM OF 32 SQUARE FEET AND WILL
OCCUR AT MULTIPLE LOCATIONS. FINAL AMOUNTS WILL BE ADJUSTED UP OR DOWN
BASED UPON ACTUAL QUANTITY AUTHORIZED.
No. Revision Date
1 OUBO PERMIT RESUBMISSION #1 1/19/2024
1-19-2023
OUBO Review Stamp
Date = 02/13/2024
APPROVED AS NOTED
FOR CONSTRUCTION
Ethan Scholl Reviewer Questions OUBO recommends the PM, A/E, and Contractor review the "OUBO Roofing System Permitting and Inspection Procedure" as well as Appendix G of the 2023 GMU HECO Manual prior to commencement of work.
DS DS
DS
DS
DS
DS
DS
DS
DS
DS
DS
DS
DS
DS
DS
DS
DS
D-1
D-1D-1
D-1
D-1
D-1
D-1
D-1
D-1
D-1
D-2
D-2
DS
D-3
D-3
D-3
D-4
D-4
DS DS
DS
DS
DS
DS
DS
DS
DS
DS
DS
DS
DS
DS DS
D-1
D-1
D-1
D-1
D-1
D-1
D-1
D-1
D-2
D-2
D-3
D-3 D-3
D-1
D-1
D-1
D-4
D-5
DS
DS
DS
DS
D-1
AD1.01AD1.01
AD1.01AD1.01
AD1.01AD1.01
AD1.01AD1.01
AD1.01AD1.01
AD1.01AD1.01
AD1.01AD1.01
AD1.01AD1.01
AD1.01AD1.01
AD1.01AD1.01
EXIST CANOPY
FACE OF EXTERIOR WALL - TYP
EXISTING GUTTER AND
DOWNSPOUTS TO REMAIN - TYP
AD1.01AD1.01
D-6
D-6
D-6
D-6
D-6
D-6
D-6
D-6
D-6 D-6
D-6
D-6
D-6
D-6
D-6
D-6
D-6
AD1.01AD1.01
AD1.01AD1.01
REMOVE ASPHALT SHINGLES
EXIST 3/4" FRT PLYWOOD
SHEATHING
EXIST STEEL ROOF DECK
REMOVE ROOFING UNDERLAYMENT
EXIST ALUM GUTTER
REMOVE METAL
DRIP
REMOVE INSULATION
REMOVE BUILT UP ROOF
REMOVE FLASHING
REMOVE OVERFLOW GUARD
REMOVE SCUPPER
CAST STONE COPING
METAL FLASHING
BRICK VENEER
CONC ROOF
DECK
REMOVE ASPHALT SHINGLES
EXIST 3/4" FIRE RETARDANT
PLYWOOD SHEATHING TO REMAIN
EXIST STEEL ROOF
DECK TO REMAIN
REMOVE ROOFING UNDERLAYMENT
REMOVE METAL COUNTER FLASHING
METAL FLASHING
METAL FASCIA
REMOVE ASPHALT SHINGLES
AND UNDERLAYMENT
REMOVE BUILT-UP ROOF
EXIST CONCRETE
ROOF SLAB
REMOVE INSULATION
REMOVE CONTINUOUS
SILICONE TOP SEAL
REMOVE GRAVEL
REMOVE WD BLOCKING
REMOVE BASE FLASHING
COUNTER FLASHING
BEYOND
CAST STONE COPING BEYOND
THRU WALL FLASHING
MTL ALUM COUNTER WALL
FLASHING
REMOVE ROOF BASE
FLASHING
REMOVE BUILT-UP ROOF
REMOVE INSULATION
REMOVE GRAVEL
REMOVE WD BLOCKING
CAST STONE COPING
REMOVE GRAVEL
REMOVE BUILT UP ROOFING
REMOVE INSULATION
REMOVE FLASHING
REMOVE METAL
FLASHING
REMOVE
CONDUCTOR HEAD
CAST STONE COPING
METAL FLASHING
BRICK VENEER
CONC ROOF DECK
MTL FLASHING
REMOVE BASE FLASHING
REMOVE GRAVEL
REMOVE BUILT UP ROOFING
REMOVE INSULATION
REMOVE WD BLOCKING
CAST STONE COPING
REMOVE ASPHALT SHINGLES
EXIST 3/4" FRT PLYWOOD
SHEATHING TO REMAIN
EXIST STEEL ROOF
DECK TO REMAIN
REMOVE ROOFING UNDERLAYMENT
REMOVE PIPE VENT FLASHING
PIPE VENT
REMOVE ASPHALT SHINGLES
REMOVE ROOFING UNDERLAYMENT
EXIST 3/4" FRT PLYWOOD
SHEATHING TO REMAIN
EXIST STEEL ROOF DECK
TO REMAIN
REMOVE RIDGE VENT
REMOVE ASPHALT SHINGLES
REMOVE ROOFING UNDERLAYMENT
EXIST 3/4" FRT PLYWOOD
SHEATHING TO REMAIN
EXIST STEEL ROOF STRUCTURE
REMOVE AIR TERMINAL,
SALVAGE FOR REINSTALLATION
REMOVE SEALANT
REMOVE ADAPTER
REMOVE WASHER
EXIST LIGHTNING PROTECTION
SYSTEM TO REMAIN
EXIST 3/4" FRT PLYWOOD
SHEATHING TO REMAIN
EXIST STEEL ROOF
DECK TO REMAIN
REMOVE ASPHALT
SHINGLES &
UNDERLAYMENT
REMOVE ASPHALT SHINGLES
& UNDERLAYMENT
T
C
A
LAE
WN
O M
M O
OF
I
NI
G
RI
H V
I T EC T
HCRA
LOUIS M.
BARBIERI JR.
Lic. No. 16266
Consultants
Seal
Key Plan
Drawing
Date
Project No.
Sheet No.
OUBO SUBMISSION 12/20/23
703.684.5994
333 North Fairfax Street
Alexandria, Virginia 22314 coleanddenny.com
Revisions
Submission Set
PC No.: 247-221547
Permit Electronic Approval Stamp
12/20/23
20011.16
4349 Chesapeake River Way C & D Fairfax, VA 22030
AD1.01
Demolition Roof Plan & Demolition Details
George Mason University Piedmont and Tidewater Dormitories Roofing Replacement
0' 10' 20' 30'
SCALE: 1/16" = 1'-0"
GENERAL DEMOLITION NOTES
1. ALL EXISTING DIMENSIONS AND CONDITIONS SHALL BE FIELD VERIFIED.
2. REQUIRED DEMOLITION SHALL NOT BE LIMITED TO THAT PORTION ON THE PLANS, BUT SHALL
INCLUDE ALL NECESSARY WORK (OR INCIDENTAL THERE TO) TO COMPLETE THE WORK IN
ACCORDANCE WITH THE CONTRACT DOCUMENTS.
3. REMOVE MATERIALS AND CONSTRUCTION AS INDICATED.
4. PREPARE REMAINING SURFACES TO RECEIVE NEW CONSTRUCTION. REMOVE EXISTING ASPHALTIC
MATERIALS AS REQUIRED BY THE MANUFACTURER TO PREPARE FOR ROOFING SYSTEM.
5. PATCH EXISTING SURFACES AS REQUIRED TO ACCOMMODATE NEW WORK. ALL NEW WORK SHALL
BE CONCEALED UNLESS NOTED OTHERWISE.
D-1 REMOVE ASPHALT SHINGLES AND UNDERLAYMENT DOWN TO PLYWOOD SHEATHING
D-2 REMOVE PIPE VENT FLASHING - PIPE VENT SHALL REMAIN
D-3 REMOVE VALLEY FLASHING
D-4 REMOVE RIDGE VENT AND FLASHING
D-5 REMOVE EXISTING BUILT UP ROOFING DOWN TO METAL DECK
D-6 REMOVE EXISTING LIGHTNING CONDUCTOR AERIAL AND SALVAGE FOR REINSTALLATION
KEYED DEMO NOTES
1/16" = 1'-0"AD1.01
1 DEMOLITION ROOF PLAN N
1 1/2" = 1'-0"AD1.01 AD1.01
2 DEMOLITION EAVE DETAIL
1 1/2" = 1'-0"AD1.01 AD1.01
3 DEMOLITION OVERFLOW DETAIL
1 1/2" = 1'-0"AD1.01 AD1.01
4 DEMOLITION LOUVER FLASHING DETAIL
1 1/2" = 1'-0"AD1.01 AD1.01
5 DEMOLITION EXPANSION JOINT DETAIL
1 1/2" = 1'-0"AD1.01 AD1.01
6 DEMOLITION PARAPET DETAIL
1 1/2" = 1'-0"AD1.01 AD1.01
11 DEMOLITION SCUPPER DETAIL
1 1/2" = 1'-0"AD1.01 AD1.01
12 DEMOLITION FLASHING DETAIL
1 1/2" = 1'-0"AD1.01 AD1.01
7 DEMOLITION PIPE VENT DETAIL
1 1/2" = 1'-0"AD1.01 AD1.01
9 DEMOLITION RIDGE VENT DETAIL
1 1/2" = 1'-0"AD1.01 AD1.01
10 DEMOLITION VALLEY DETAIL
0' 1' 2'6"
SCALE: 1 1/2" = 1'-0"
1 1/2" = 1'-0"AD1.01 AD1.01
8 DEMOLITION LIGHTNING CONDUCTOR DETAIL
No. Revision Date
1 OUBO PERMIT RESUBMISSION #1 1/19/2024
1-19-2023
OUBO Review Stamp
Date = 02/13/2024
APPROVED FOR
CONSTRUCTION
DS DS
DS
DS
DS
DS
DS
DS
DS
DS
DS
DS
DS
DS
DS
DS
DS
R-1
R-1
R-1
R-1
R-1
R-1
R-1
R-1
R-2
R-2
DS
R-3
R-3
R-3
R-4
R-4
R-5
DS
DS
DS DS
DS
DS
DS
DS
DS
DS
DS
DS
DS
DS
DS
DS DS
R-1
R-1
R-1
R-1
R-1
R-1
R-1
R-1
R-2
R-2
R-3
R-3
R-3
R-1
R-1
R-1
R-4
DS
DS
R-1
DS
A5.02A1.01
A5.01A1.01
A5.01A1.01
A5.01A1.01
A5.02A1.01
A5.01A1.01
A5.02A1.01
A5.01A1.01
A5.01A1.01
A5.01A1.01
FACE OF EXTERIOR
WALL - TYP
EXISTING GUTTER AND
DOWNSPOUTS TO
REMAIN - TYP
EXIST CANOPY (NIC)
'-2
62'-0" 24'-0"
'-2
/4
'-1
/4
43'-5"24'-0" 18'-7"
'-7
/4
'-3
/4
55'-0"
1/4"/FT
+1-0 1/2"
62'-0" 35'-8" 10'-0"
'-2
'-1
'-3
/4
35'-8" 10'-0 1/8"43'-3 7/8"18'-8"
'-4
/4
'-7
/4
'-7
'-1
/4
1/2"/FT 1/2"/FT 1/2"/FT 1/2"/FT
+4 1/2"+4 1/2"
+5 7/8" +9 1/2"
A5.01A1.01
A5.02A1.01
A5.01A1.01
TYP
APPROXIMATE
LOCATION OF ATTIC
ACCESS ON 6TH
FLOOR BELOW
APPROXIMATE
LOCATION OF ATTIC
ACCESS ON 5TH
FLOOR BELOW
A5.02A1.01
TYP
R-6
R-6
R-6
R-6
R-6
R-6
R-6
R-6 R-6
R-6
R-6
R-6
R-6
R-6
R-6
R-6 R-6
R-1
R-1
A5.01A1.01
TYP
TYP
TYP.
P.C. SPLASH BLOCK
ON PROTECTION
MEMBRANE LAYER
P.C. SPLASH BLOCK
ON PROTECTION
MEMBRANE LAYER
TAPERED INSULATION
THICKNESS AT A
SPECIFIC POINT
ROOF SLOPE DIRECTION
+ 4 1/2"
T
C
A
LAE
WN
O M
M O
OF
I
NI
G
RI
H V
I T EC T
HCRA
LOUIS M.
BARBIERI JR.
Lic. No. 16266
Consultants
Seal
Key Plan
Drawing
Date
Project No.
Sheet No.
OUBO SUBMISSION 12/20/23
703.684.5994
333 North Fairfax Street
Alexandria, Virginia 22314 coleanddenny.com
Revisions
Submission Set
PC No.: 247-221547
Permit Electronic Approval Stamp
12/20/23
20011.16
4349 Chesapeake River Way C & D Fairfax, VA 22030
A1.01
Roof Plan
George Mason University Piedmont and Tidewater Dormitories Roofing Replacement
N
5'0' 10' 20'
SCALE: 1/8" = 1'-0"
GENERAL NEW WORK NOTES
1. DIMENSIONS ARE TO FINISH FACE OF CONSTRUCTION UNLESS OTHERWISE INDICATED.
2. CONTRACTOR IS RESPONSIBLE FOR CONFIRMING ALL EXISTING DIMENSIONS AND CONDITIONS IN THE FIELD.
3. REINSTALL AS NEEDED TO ACCOMPLISH THE WORK. AT THE COMPLETION OF THE PROJECT. THE
CONTRACTOR SHALL RECTIFY ANY ISSUES TO ACHIEVE THE UL 96A MASTER LABEL RELATED TO THE WORK
AND SERVICES PERFORMED IN THIS CONTRACT.
R-1 INSTALL UNDERLAYMENT AND ASPHALT SHINGLE ROOFING SYSTEM. INSTALL R-8 LOOSE
FILL INSULATION IN ATTIC OVER EXISTING R-30 LOOSE FILL INSULATION. EXTEND RAFTER
BAFFLES AT EAVE 6" ABOVE THE TOP OF THE NEW INSULATION TO ENSURE VENTILATION IS
MAINTAINED.
R-2 INSTALL PIPE VENT FLASHING.
R-3 INSTALL VALLEY FLASHING.
R-4 INSTALL RIDGE VENT.
R-5 INSTALL FULLY ADHERED EPDM ROOFING SYSTEM WITH TAPERED INSULATION.
R-6 REINSTALL LIGHTNING CONDUCTOR AERIAL.
KEYED REPAIR NOTES
1/8" = 1'-0"A1.01
1 ROOF PLAN
LEGEND
No. Revision Date
1 OUBO PERMIT RESUBMISSION #1 1/19/2024
1-19-2023
UNIT PRICES
1. UNIT PRICE SHALL BE BASED ON AN ESTIMATED QUANITY OF 800 SQUARE FEET
FOR THE REMOVAL OF ROTTED OR OTHERWISE DAMAGED PLYWOOD SHEATHING,
AND REPLACEMENT WITH 3/4" CDX FIRE RATED PLYWOOD SHEATHING FOR THE
PURPOSES OF THE UNIT PRICE. THE CONTRACTOR SHALL ASSUME THAT THE
REMOVAL AND REPLACEMENT WILL BE A MINIMUM OF 32 SQUARE FEET AND WILL
OCCUR AT MULTIPLE LOCATIONS. FINAL AMOUNTS WILL BE ADJUSTED UP OR DOWN
BASED UPON ACTUAL QUANTITY AUTHORIZED.
OUBO Review Stamp
Date = 02/13/2024
ASPHALT SHINGLES
EXIST FRT PLYWOOD
SHEATHING
ROOFING UNDERLAYMENT
PIPE VENT BOOT
SEALANT
CLAMP RING
ASPHALT SHINGLES
ROOFING UNDERLAYMENT
EXIST FRT PLYWOOD
SHEATHING
RIDGE VENT
ASPHALT SHINGLES (SECONDARY SLOPE)
ROOFING UNDERLAYMENT
ASPHALT SHINGLES (PRIMARY SLOPE)
EXIST STEEL ROOF STRUCTURE
6" MIN
EXIST CONCRETE
ROOF SLAB
ROOFING MEMBRANE
TAPERED INSULATION
MEMBRANE FLASHING
MEMBRANE SUPPORT
BATT INSULATION
MANUF EXPAN JT COVER
2x PT WD BLOCKING
TERMINATION BAR & SEALANT
EXIST THRU WALL FLASHING
CAST STONE COPING BEYOND
'-6
/2
WIND CLIP @ 16" O.C MAX
FASTENER W/ NEOPRENE WASHER
SET IN SEALANT @ 16" O.C.
EXIST MTL
COUNTER
FLASHING
MEMBRANE FLASHING
/2
PT WD BLOCKING
ROOFING MEMBRANE
MEMBRANE FLASHING
1/2" PLYWOOD
CAST STONE COPING
SEALANT TOP & SIDES
METAL OVERFLOW
SCUPPER FABRICATED
FACE. OPENING SIZE TO
MATCH EXISTING
TERMINATION BAR
& SEALANT
FASTENER W/
NEOPRENE
WASHER SET
IN SEALANT @
16" O.C.
EXIST CONCRETE
ROOF SLAB
ROOFING MEMBRANE
TAPERED INSULATION
MEMBRANE FLASHING
2x PT WD BLOCKING TYP
SLOPE TOP 1/2"/FT
CAST STONE COPING BEYOND
WIND CLIP @ 16" O.C MAX
TERMINATION BAR & SEALANT
EXIST THRU WALL FLASHING
FASTNER W/ NEOPRENE WASHER
SET IN SEALANT @ 16" O.C.
1/2" PLY WD, TYP
'-6
/2
7 1/4"
REINSTALL AIR TERMINAL
SEALANT
REINSTALL ADAPTER
REINSTALL WASHER
EXIST LIGHTNING
PROTECTION SYSTEM
ASPHALT SHINGLES
ROOFING UNDERLAYMENT
EXIST FRT PLYWOOD SHEATHING
EXIST DOWNSPOUT
METAL
SCUPPER TO
MATCH EXIST
1/2" PLYWOOD
PT WD BLOCKING
ROOFING MEMBRANE
MEMBRANE FLASHING
MEMBRANE FLASHING
MTL COUNTER FLASHING
CAST STONE COPING
TERMINATION BAR & SEALANT
SEALANT TOP &
SIDES
FASTENER W/ NEOPRENE
WASHER SET IN SEALANT
@ 16" O.C.
METAL TRIM
TOP & SIDES
T
C
A
LAE
WN
O M
M O
OF
I
NI
G
RI
H V
I T EC T
HCRA
LOUIS M.
BARBIERI JR.
Lic. No. 16266
Consultants
Seal
Key Plan
Drawing
Date
Project No.
Sheet No.
OUBO SUBMISSION 12/20/23
703.684.5994
333 North Fairfax Street
Alexandria, Virginia 22314 coleanddenny.com
Revisions
Submission Set
PC No.: 247-221547
Permit Electronic Approval Stamp
12/20/23
20011.16
4349 Chesapeake River Way C & D Fairfax, VA 22030
A5.01
Roof Details
George Mason University Piedmont and Tidewater Dormitories Roofing Replacement
0' 6" 1'4"2"
SCALE: 3" = 1'-0"
3" = 1'-0"A1.01 A5.01
1 PIPE VENT DETAIL
3" = 1'-0"A1.01 A5.01
2 RIDGE VENT DETAIL
3" = 1'-0"A1.01 A5.01
3 TYPICAL VALLEY DETAIL
3" = 1'-0"A1.01 A5.01
8 EXPANSION JOINT DETAIL
3" = 1'-0"A1.01 A5.01
6 OVERFLOW DETAIL
3" = 1'-0"A1.01 A5.01
7 ROOF FLASHING DETAIL
3" = 1'-0"A1.01 A5.01
4 LIGHTNING CONDUCTOR AERIAL DETAIL
3" = 1'-0"A1.01 A5.01
5 SCUPPER DETAIL
No. Revision Date
1 OUBO PERMIT RESUBMISSION #1 1/19/2024
1-19-2023
OUBO Review Stamp
Date = 02/13/2024
EXISTING FRT PLY WD SHEATHING
ROOFING UNDERLAYMENT
ASPHALT SHINGLES
METAL DRIP
1/2" PT PLY WD
MEMBRNE FLASHING
MEMBRANE ROOFING
TAPERED INSULATION
MTL COUNTER FLASHING
WIND CLIP @ 16" O.C MAX
TERMINATION BAR & SEALANT
ASPHALT SHINGLES
EXISTING FRT ROOF SHEATHING
ROOFING UNDERLAYMENT
ASPHALT SHINGLE
ROOF UNDERLAYMENT
EXISTING FRT ROOF SHEATING
EXISTING METAL FLASHING
FASTENER W/ NEOPRENE
WASHER SET IN SEALANT
@ 16" OC
EXISTING MTL FLASHING
EXISTING LOUVER
METAL FLASHING SET
IN SEALANT
8" 1
T
C
A
LAE
WN
O M
M O
OF
I
NI
G
RI
H V
I T EC T
HCRA
LOUIS M.
BARBIERI JR.
Lic. No. 16266
Consultants
Seal
Key Plan
Drawing
Date
Project No.
Sheet No.
OUBO SUBMISSION 12/20/23
703.684.5994
333 North Fairfax Street
Alexandria, Virginia 22314 coleanddenny.com
Revisions
Submission Set
PC No.: 247-221547
Permit Electronic Approval Stamp
12/20/23
20011.16
4349 Chesapeake River Way C & D Fairfax, VA 22030
A5.02
Roof Details
George Mason University Piedmont and Tidewater Dormitories Roofing Replacement
0' 6" 1'4"2"
SCALE: 3" = 1'-0"
3" = 1'-0"A1.01 A5.02
1 EAVE DETAIL
3" = 1'-0"A1.01 A5.02
2 PARAPET DETAIL
3" = 1'-0"A1.01 A5.02
3 LOUVER DETAIL
No. Revision Date
1 OUBO PERMIT RESUBMISSION #1 1/19/2024
1-19-2023
OUBO Review Stamp
Date = 02/13/2024
| Sheets |
| A1.01 - Roof Plan |
| A5.01 - Roof Details |
| A5.02 - Roof Details |
| AD1.01 - Demolition Roof Plan & Demolition Details |
| G0.01 - Cover Sheet |
File details come from the government source that posted it. Updated .