This document contains technical drawings and details for an HVAC system. It includes diagrams of ductwork, fans, dampers, piping, and other HVAC components with callouts and specifications. Relevant details shown are supply and return air main ducts, sound attenuators, motorized dampers, control damper locations, flexible duct connectors for constant volume air boxes, evaporative cooling systems, exhaust fans, unit heaters, and boiler venting. Product information given consists of fan types, damper actuators, piping materials and fittings. The drawings are dated June 21, 2007 and were produced for the USDA Agricultural Research Service as part of a project for designing a new poultry facility at the Beltsville Agricultural Research Center.
View the file
Other files for this federal contract opportunity
Show all 18
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
M701
HVAC DETAILS
D
2D
(TYPICAL OF 4)
STEEL HANGING ROD
A2
NO SCALE
M202 M701
SUPPLY AIR MAIN DUCT
NO MEDIA SOUND ATTENUATOR
SEALANT ALL AROUND
GALVANIZED PLATE SLEEVE
CONTINUOUS WELD AT SEAM
FAN WITH FRAME
FAN GUARD
BOLTS AT 12" OC
3/8" DIA (MIN)
COORDINATE FAN MOUNTING
TO ALLOW FULL UNOBSTRUCTED
OPERATION OF THE DAMPER
REFER TO ARCH
TWO POSITION
MOTORIZED
DAMPER
NOTE: DIRECT DRIVE FAN IS SHOWN. INSTALLATION
FOR BELT DRIVE FAN IS SIMILAR.
NO SCALE
C5
M202 M701
TYPICAL CAV BOX
CAV
BOX
FLEXIBLE DUCT CONNECTOR FOR CAV
C1
NO SCALE
M201 M701
EVAPORATIVE COOLING SYSTEM TYPICAL DETAIL
381mm SLIP
CAP
381mm PIPE
38mm SUPPLY LINE
381mm TEE
FLOAT VALVE
90 OVERFLOW
ELBOW
FLOAT VALVE
BRACKET
381mm PIPE
19mm FLEX
SUPPLY LINE
381mm SLIP
CAP
203mm PIPE
203mm X 22.5 ELBOW PIPE SUPPORT
BRACKET (TYP)
203mm PIPE 203mm RUBBER CAP
WITH CLAMP FOR END
OF PIPE RESERVOIR
FLARED END OF
DISTRIBUTOR PIPE
38mm SLIP UNION
38mm X 38mm X 25mm
SLIP TEE
25mm SLIP
BALL VALVE
25mm X 127mm
PIPE NIPPLE
(2) 38mm MALE
ADAPTERS
38mm INLINE
STRAINER
38mm SUPPLY LINE
38mm SLIP ELBOW
(2) 38mm X 254mm
PIPE NIPPLES
38mm SLIP
BALL VALVE
TYPICAL INLINE FAN DETAIL
STEEL ROD
SRING HANGING
ISOLATOR (TYP)
MOUNTING BRACKET
(TYP)
MOTOR
DUCTWORK
DUCTWORK
FLEXIBLE CONNECTION
(TYP)
ADJUSTABLE SHEAVE
PULLEY
FAN
NOTE:
ONLY TO SHOW THE GENERAL SIZE, CONFIGURATION, LOCATION, CONNECTIONS, AND/OR SUPPORT
FOR EQUIPMENT OR SYSTEMS SPECIFIED WITH RELATION TO OTHER BUILDING SYSTEMS.
32 or 38mm
MALE ADAPTER
SUBMERSIBLE
PUMP
19mm RIGID
PIPE
SHUT-OFF
VALVE
RAINPROOF LOUVER WITH
REMOVABLE INSECT SCREEN
A3
NO SCALE
M202 M701
A4
NO SCALE
M202 M701
3mm THICK BENT
51mm
25mm CLEAR
NO SCALE
C4
INSULATION
SHEET METAL DUCT
M202 M701
CONCRETE PAD
ALUMINUM JACKET
FASTEN DUCT TO ANGLE IRON
WITH CADMIUM OR STAINLESS
STEEL METAL SCREWS MIN
3 PER SIDE
DUCT GROUND SUPPORT DETAIL
ANGLE IRON
50mm X 50m x 6mm
ANGLE RIENFORCED AND
WELDED TO 6mm SQUARE
PLATE. FASTEN TO CONCRETE
PAD WITH FOUR FASTENERS
NOTE:
SIMILAR CONSTRUCTION FOR SINGLE DUCT SUPPORT.
PLAN VIEW
DUCT SUPPORT
STRAP
ANCHORS
GALVANIZED STEEL
FASTENER
GALVANIZED STEEL
ANCHORS
MECH
DUCTWORK
CMU WALL
PIPE CAP
END PANEL
NO SCALE
C3
M202 M701
DUCT WALL SUPPORT DETAIL
NOTE:
PROVIDE DUCT SUPPORT IN ACCORDANCE WITH SMACNA HVAC INDUSTRIAL
DUCT CONSTRUCTION STANDARDS.
50mm
50mm WIDE GALVANIZED STEEL STRAP W/ EXP. SHIELDS AND 6mm
DIA. SHEET METAL SCREWS
AT 150mm VERTICALLY ATTACHED
TO BRICK
B1
NO SCALE
M202 M701
ROOF MOUNTED EXHAUST FAN DETAIL
ROOF EXHAUST FAN
MOTOR HOUSING WITH
BIRD SCREEN BY FAN
MANUFACTURER
ROOF CURB
(SEE ARCH DWGS.
FOR DETAIL)
DUCT SIZE TO MATCH FAN
INLET OPENING UNLESS
OTHERWISE NOTED
B2
NO SCALE
M201 M701
CIRCULATION FAN DETAIL
CIRCULATION FAN
INLET GUARD
HIGH EFFICIENCY
VARIABLE SPEED MOTOR
OUTLET
GUARD
B4
NO SCALE
M201 M701
BREEDER/GROWOUT WING EXHAUST FAN DETAIL
REFER TO ARCH.
DWGS. FOR WALL
OPENING SIZE
CMU WALL
DISCHARGE
CONE
OUTLET
GUARD
38mm FLANGE
PROVIDE HANGER
PER MANUFACTURER’S
RECOMMENDATIONS
(TYP)
25mm DRAIN LINE & VALVE
900mm
B3
NO SCALE
M202 M701
COMBUSTION VENTING DETAIL
203mm DIA.
254mm DIA
THE DETAIL SHOWN IS INTENDED
ATTACH TO WALL WITH
LAG SCREWS PER
MANUFACTURER’S
RECOMMENDATIONS
INLET SHUTTER
SHEET METAL
BOOT AND
LIGHT TRAP
B5
NO SCALE
M201 M701
ECP DAMPER DETAIL
COOLING PAD
ASSEMBLY
CMU WALL
SHEET
METAL
BAROMETRIC
DAMPER 203mm o
W
L
NOTE
VOLUME DAMPER
NOTE
A1
NO SCALE
M202 M701
DAMPERS SHOULD NOT BE INSTALLED CLOSER THAN
TWO DUCT WIDTHS TO ELBOWS OR INTERSECTIONS
L= W/4 (100mm MIN.)
TYPICAL BRANCH DUCT TAKE-OFF WITH VOLUME DAMPER
SERVICE AREA SIDEWALL PROPELLER FAN DETAIL
SERVICE AREA UNIT HEATER DETAIL
NOTE: MAINTAIN CLEARANCE TO ALL COMBUSTIBLE
MATERIALS PER MANUFACTURER’S RECOMMENDATIONS.
HWS
HWR
BALANCING VALVE
DRAIN VALVE
A
IR
F
LO
W
WITH CAPPED
HOSE CONNECTION
MANUAL AIR VENT
STRAINER
M702 M702
S.S. DOUBLE WALL
FLUE GAS EXHAUST
152mm 127mm
3-WAY CONTROL VALVE
ISOLATION VALVE
HOT WATER
REHEAT COIL
FOR ROOF CONSTRUCTION
AND FLASHING DETAILS
SEE ARCH. DRAWINGS
M
B-1 GWH-1 GWH-1
T. LINN
T. LINN
K. MCCABE
FOR CHIMNEY ROOF CURB
INSTALLATION SEE
D3/A402 DETAIL.
Drawing No.:
Drawing Title:
Date:
Issues:
F5W51104
A
B
C
D
1 2 3 4 5
1 2 3 4 5
Jacobs Project No.:
Designed By:
Drawn By:
Checked By:
Project No:
02-21-03
EPM:
RPM:
Safety & Health:
Real Property:
JFI
FINAL TURNOVER
B. Runser
C. Joyner
DR. McMurty
06-21-07 FINAL RECORD DRAWING
FACILITIES INC.
R
1100 NORTH GLEBE ROAD, SUITE 500, ARLINGTON, VIRGINIA 22201
JUNE 6, 2007
USDA-ARS
C. Harris Proj. Manager:
D e s ig n o f A
N e w
P o u lt ry F a c il it y
B e lt s v il le
A g ri c u lt u ra l
R e s e a rc h C e n te r
US
DA
AR
S
JACOBS
File details come from the government source that posted it. Updated .