Attachment 8 - Drawing M602 HVAC Control Diagrams 21JUN2007.pdf

PDF 210 KB Posted

Attached to
Building 229 Roofing System Replacement Federal contract opportunity
Solicitation number
12305B23R0022
Issued by
Department of Agriculture Agricultural Research Service Field Research Implementation and Information Delivery Northeast Area

About this file

This drawing package provides control diagrams for the HVAC systems in several poultry rooms and related support spaces at the USDA Agricultural Research Service Beltsville Agricultural Research Center. The diagrams show control sequences for unit ventilators, exhaust fans, variable air volume boxes, and related equipment. Poultry rooms will have one to three exhaust fans, two to four circulation fans, and one unit heater each. Control panels will be provided for each poultry room and will operate independently from the direct digital control system. Interlocks are indicated to coordinate operation of fans and dampers.

View the file

Other files for this federal contract opportunity

Other files attached to Building 229 Roofing System Replacement, newest first.
File Type Posted
12305B23R00220001.pdf PDF
12305B23R0022.pdf PDF
Attachment 14 - USDA Forms - 02AUG2023.pdf PDF
Attachment 16 - WD Prince George s County MD Building MD20230044 04AUG2023.pdf PDF
SOW - B229 Roofing System Replacement - 16AUG2023.pdf PDF
Attachment 5 - Drawing A302 Building Elevations 21JUN2007.pdf PDF
Attachment 13 - Open Flame Policy and Permit - 16AUG2023.pdf PDF
Attachment 15 - Submittal Registry - B229 Roofing System Replacement - 16AUG2023.pdf PDF
Attachment 3 - Drawing A401 Building And Wall Sections 21JUN2007.pdf PDF
Attachment 4 - Drawing A301 Building Elevations 21JUN2007.pdf PDF
Attachment 6 - Drawing A203 Building Roof Plan 21JUN2007.pdf PDF
Attachment 9 - Drawing M701 HVAC Details 21JUN2007.pdf PDF
Attachment 10 - Drawing M801 Mechanical Equipment Schedules 21JUN2007.pdf PDF
Attachment 1 - Division 1 USDA General Requirements - B229 Roofing System Replacement - 16AUG2023.pdf PDF
Attachment 2 - Drawing A201 Breeder and Grow Out Wings Partial Floor Plan 21JUN2007.pdf PDF
Attachment 7 - Drawing A402 Building Sections 21JUN2007.pdf PDF
Attachment 11 - Drawing P204 Roof Plan 21JUN2007.pdf PDF
Attachment 12 - Drawing A202 Service Area Partial Floor Plan 21JUN2007.pdf PDF
Show all 18

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

M602

A.

B. SEE SPECIFICATION SECTION 15910 FOR SEQUENCE OF OPERATIONS.

FOR GENERAL NOTES, SYMBOLS, AND ABBREVIATIONS REFER TO SHEET M001 .

GENERAL NOTES:

SHEET NOTES:

M

M CD

N.C.

DS

DO

DIRECT DIGITAL CONTROL PANEL

DI

NTS

M602M602

A4

EXHAUST FAN

OUTDOOR

AIR

SUPPLY

AIR

CD

N.C.

M

DS

DO

SS CR

MOTOR

STARTER

DI

NTS

M602M602

B1

AI

TS

DIRECT DIGITAL CONTROL PANEL

CD

N.C.

M

DO

RELIEF

AIR

ATTIC

SPACE

OUTDOOR AIR FAN SF-2 CONTROL DIAGRAM

SF-2

EXHAUST FANS EF-7 & 9 CONTROL DIAGRAM

M

M CD

N.C.

DS

DO

DIRECT DIGITAL CONTROL PANEL

DI

NTS

M602M602

C1

M

M CD

N.C.

DS

DODI

M

M CD

N.C.

DS

DODI

EF-4 EF-5 EF-6

CD

N.C.

M

DO

CD

N.C.

M

DO

OUTDOOR

AIR

OUTDOOR

AIR

EXHAUST FANS EF-4, 5 & 6 CONTROL DIAGRAM

AI

TS

1 SW

DI

WINTER OPERATION

OVERRIDE SWITCH

FRCR

FRCRFRCRFRCR

2 ISOLATION DAMPER SHALL BE HARD WIRE INTERLOCKED WITH THE ASSOCIATED FAN MOTOR STARTER TO OPEN

WHEN THE FAN IS STARTED IN THE HAND OR AUTO POSITIONS. THE FAN SHALL BE HARD WIRE INTERLOCKED

WITH THE POSITION SWITCH ON THE ASSOCIATED ISOLATION DAMPER TO ENERGIZE ONCE THE ISOLATION

DAMPER HAS BEEN PROVEN OPEN.

ISOLATION DAMPER SHALL BE HARD WIRE INTERLOCKED WITH THE ASSOCIATED FAN DISCONNECT TO OPEN

WHEN THE FAN IS STARTED. THE FAN SHALL BE HARD WIRE INTERLOCKED WITH THE POSITION SWITCH ON

THE ASSOCIATED ISOLATION DAMPER TO ENERGIZE ONCE THE ISOLATION DAMPER HAS BEEN PROVEN OPEN.

FR M

BDD

M

M

N A

T

G A

S

AO

NTS

M602M602

A1

DO

FR

M

BDD

FR M

BDD

CI

DODO

FR

DO

GAS FIRED

UNIT HEATER

M

M M

M

CI

AO

VARIABLE SPEED

CONTROLLER

AI

TSPACE

THERMOSTAT

BDD

T

AI

M

M

N A

T

G A

S

GAS FIRED

UNIT HEATER

BDD

FR

DO

M

MAKE-UP

WATER

TO FLOAT SWITCH IN

EVAPORATIVE COOLER

WATER RESERVOIR

N.C.

N.C. N.C.T

POULTRY SPECIALTY CONTROL PANEL

TYPICAL POULTRY ROOM SPACE CONTROL DIAGRAM

EVAPORATIVE COOLER

SPACE

THERMOSTAT

SPACE

THERMOSTAT

COMBUSTION AIR

INTERLOCK

CIRCULATION FANS

STAGE 1 EXHAUST FAN

STAGE 2 EXHAUST FAN

STAGE 3 EXHAUST FAN

HALLWAY POULTRY ROOM

3 CIRCULATION FANS LOCATED IN THE HALLWAY OPERATE CONTINUALLY AND ARE NOT CONNECTED TO THE DDCS

OR THE POULTRY SPECIALTY CONTROLS.

DO NOT APPLY

TO SMALL

POULTRY ROOMS

DOES NOT APPLY

TO SMALL

POULTRY ROOMS

6 PROVIDE ONE POULTRY SPECIALTY CONTROL PANEL AND ONE VARIABLE SPEED CONTROLLER PER POULTRY

ROOM. POULTRY SPECIALTY CONTROL PANEL MUST BE LOCATED IN THE HALLWAY OUTSIDE OF THE ROOM SERVED

BY THE PANEL. THE VARIABLE SPEED CONTROLLER SHALL BE LOCATED IN THE POULTRY ROOM SERVED. SEE

SHEET M201 FOR PANEL LOCATIONS.

ALARM

OUTPUT

TO DDCS

AX

PROVIDE COVERAGE OF 3300 MM OF ACTIVE ELEMENT PER SQUARE METER OF COIL. HARD WIRE INTERLOCK

FREEZESTAT WITH FAN TO STOP FAN WHEN FREEZESTAT IS ACTIVATED.

TS

SPACE TEMPERATURE

SENSOR TO DDCS

DI

OUTDOOR

AIR

SUPPLY

AIR

CD

N.C.

M

DS

PDI

DP

F

DO

SS CR

MOTOR

STARTER

DI

NTS

M602M602

B1

M

M CD

N.C.

EF-8

SS

MOTOR

STARTER

CR

DS

AI DO

TS

DI

OUTDOOR AIR FAN SF-1 AND EF-8 CONTROL DIAGRAM

DIRECT DIGITAL CONTROL PANEL

SF-1

ROOMS

125 & 126

SW

DI

TYPICAL OF TWO

LIGHT SWITCHES

(ONE PER ROOM)

(PROVIDED BY DIV. 16)

DO

SS CR

DI

SSCR

DODI

HWS

HWR

M

CV

N.O.

C

H

AO

FZ

DI

DO DI

FR CR

SET AT

2^C.

SEE DETAIL B4/M601 FOR CONTINUATION9

EXPLOSION

PROOF

HVAC CONTROL

DIAGRAMS

A. PELLEGRINO

A. PELLEGRINO

R. WARD

THERE ARE SEVEN LARGE POULTRY ROOMS WHICH CONTAIN THREE EXHAUST FANS, FOUR CIRCULATION FANS AND

ONE UNIT HEATER. THERE ARE THREE SMALL POULTRY ROOMS WHICH CONTAIN ONLY TWO EXHAUST FANS, TWO

CIRCULATION FANS AND ONE UNIT HEATER. ALL ROOMS ARE CONFIGURED IN THE MANNER AS SHOWN IN THIS

DETAIL. FOR SMALL POULTRY ROOMS DISREGUARD THIRD STAGE EXHAUST FAN AND TWO OF THE CIRCULATION

FANS.

HARD WIRE INTERLOCK UNIT HEATER LOCATED IN HALLWAY AND UNIT HEATER LOCATED IN THE POULTRY ROOM

WITH THE FIRST STAGE EXHAUST FAN SUCH THAT THE UNITS HEATERS WILL NOT BE ABLE TO START IF THE

FIRST STAGE EXHAUST FAN IS NOT OPERATING. UNIT HEATER LOCATED IN HALLWAY SHALL BE INTERLOCKED

WITH CLOSEST FIRST STAGE EXHAUST FAN. SEE SHEET M201 FOR LOCATIONS AND QUANTITIES OF UNIT

HEATERS.

POULTRY SPECIALTY CONTROL PANEL AND VARIABLE SPEED CONTROLLER ARE NOT PART OF THE DIRECT

DIGITAL CONTROL SYSTEM (DDCS). THESE CONTROLS OPERATE INDEPENDENTLY OF THE DDCS. SEE

SPECIFICATION SECTION 15725 FOR FURTHER DETAILS. SEE SPECIFICATION SECTION 15910 FOR

ASSOCIATED SEQUENCES OF OPERATION.

Drawing No.:

Drawing Title:

Date:

Issues:

F5W51104

A

B

C

D

1 2 3 4 5

1 2 3 4 5

Jacobs Project No.:

Designed By:

Drawn By:

Checked By:

Project No:

02-21-03

EPM:

RPM:

Safety & Health:

Real Property:

JFI

FINAL TURNOVER

B. Runser

C. Joyner

DR. McMurty

06-21-07 FINAL RECORD DRAWING

FACILITIES INC.

R

1100 NORTH GLEBE ROAD, SUITE 500, ARLINGTON, VIRGINIA 22201

JUNE 6, 2007

USDA-ARS

C. Harris Proj. Manager:

D e s ig n o f A

N e w

P o u lt ry F a c il it y

B e lt s v il le

A g ri c u lt u ra l

R e s e a rc h C e n te r

US

DA

AR

S

JACOBS