This drawing package provides control diagrams for the HVAC systems in several poultry rooms and related support spaces at the USDA Agricultural Research Service Beltsville Agricultural Research Center. The diagrams show control sequences for unit ventilators, exhaust fans, variable air volume boxes, and related equipment. Poultry rooms will have one to three exhaust fans, two to four circulation fans, and one unit heater each. Control panels will be provided for each poultry room and will operate independently from the direct digital control system. Interlocks are indicated to coordinate operation of fans and dampers.
View the file
Other files for this federal contract opportunity
Show all 18
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
M602
A.
B. SEE SPECIFICATION SECTION 15910 FOR SEQUENCE OF OPERATIONS.
FOR GENERAL NOTES, SYMBOLS, AND ABBREVIATIONS REFER TO SHEET M001 .
GENERAL NOTES:
SHEET NOTES:
M
M CD
N.C.
DS
DO
DIRECT DIGITAL CONTROL PANEL
DI
NTS
M602M602
A4
EXHAUST FAN
OUTDOOR
AIR
SUPPLY
AIR
CD
N.C.
M
DS
DO
SS CR
MOTOR
STARTER
DI
NTS
M602M602
B1
AI
TS
DIRECT DIGITAL CONTROL PANEL
CD
N.C.
M
DO
RELIEF
AIR
ATTIC
SPACE
OUTDOOR AIR FAN SF-2 CONTROL DIAGRAM
SF-2
EXHAUST FANS EF-7 & 9 CONTROL DIAGRAM
M
M CD
N.C.
DS
DO
DIRECT DIGITAL CONTROL PANEL
DI
NTS
M602M602
C1
M
M CD
N.C.
DS
DODI
M
M CD
N.C.
DS
DODI
EF-4 EF-5 EF-6
CD
N.C.
M
DO
CD
N.C.
M
DO
OUTDOOR
AIR
OUTDOOR
AIR
EXHAUST FANS EF-4, 5 & 6 CONTROL DIAGRAM
AI
TS
1 SW
DI
WINTER OPERATION
OVERRIDE SWITCH
FRCR
FRCRFRCRFRCR
2 ISOLATION DAMPER SHALL BE HARD WIRE INTERLOCKED WITH THE ASSOCIATED FAN MOTOR STARTER TO OPEN
WHEN THE FAN IS STARTED IN THE HAND OR AUTO POSITIONS. THE FAN SHALL BE HARD WIRE INTERLOCKED
WITH THE POSITION SWITCH ON THE ASSOCIATED ISOLATION DAMPER TO ENERGIZE ONCE THE ISOLATION
DAMPER HAS BEEN PROVEN OPEN.
ISOLATION DAMPER SHALL BE HARD WIRE INTERLOCKED WITH THE ASSOCIATED FAN DISCONNECT TO OPEN
WHEN THE FAN IS STARTED. THE FAN SHALL BE HARD WIRE INTERLOCKED WITH THE POSITION SWITCH ON
THE ASSOCIATED ISOLATION DAMPER TO ENERGIZE ONCE THE ISOLATION DAMPER HAS BEEN PROVEN OPEN.
FR M
BDD
M
M
N A
T
G A
S
AO
NTS
M602M602
A1
DO
FR
M
BDD
FR M
BDD
CI
DODO
FR
DO
GAS FIRED
UNIT HEATER
M
M M
M
CI
AO
VARIABLE SPEED
CONTROLLER
AI
TSPACE
THERMOSTAT
BDD
T
AI
M
M
N A
T
G A
S
GAS FIRED
UNIT HEATER
BDD
FR
DO
M
MAKE-UP
WATER
TO FLOAT SWITCH IN
EVAPORATIVE COOLER
WATER RESERVOIR
N.C.
N.C. N.C.T
POULTRY SPECIALTY CONTROL PANEL
TYPICAL POULTRY ROOM SPACE CONTROL DIAGRAM
EVAPORATIVE COOLER
SPACE
THERMOSTAT
SPACE
THERMOSTAT
COMBUSTION AIR
INTERLOCK
CIRCULATION FANS
STAGE 1 EXHAUST FAN
STAGE 2 EXHAUST FAN
STAGE 3 EXHAUST FAN
HALLWAY POULTRY ROOM
3 CIRCULATION FANS LOCATED IN THE HALLWAY OPERATE CONTINUALLY AND ARE NOT CONNECTED TO THE DDCS
OR THE POULTRY SPECIALTY CONTROLS.
DO NOT APPLY
TO SMALL
POULTRY ROOMS
DOES NOT APPLY
TO SMALL
POULTRY ROOMS
6 PROVIDE ONE POULTRY SPECIALTY CONTROL PANEL AND ONE VARIABLE SPEED CONTROLLER PER POULTRY
ROOM. POULTRY SPECIALTY CONTROL PANEL MUST BE LOCATED IN THE HALLWAY OUTSIDE OF THE ROOM SERVED
BY THE PANEL. THE VARIABLE SPEED CONTROLLER SHALL BE LOCATED IN THE POULTRY ROOM SERVED. SEE
SHEET M201 FOR PANEL LOCATIONS.
ALARM
OUTPUT
TO DDCS
AX
PROVIDE COVERAGE OF 3300 MM OF ACTIVE ELEMENT PER SQUARE METER OF COIL. HARD WIRE INTERLOCK
FREEZESTAT WITH FAN TO STOP FAN WHEN FREEZESTAT IS ACTIVATED.
TS
SPACE TEMPERATURE
SENSOR TO DDCS
DI
OUTDOOR
AIR
SUPPLY
AIR
CD
N.C.
M
DS
PDI
DP
F
DO
SS CR
MOTOR
STARTER
DI
NTS
M602M602
B1
M
M CD
N.C.
EF-8
SS
MOTOR
STARTER
CR
DS
AI DO
TS
DI
OUTDOOR AIR FAN SF-1 AND EF-8 CONTROL DIAGRAM
DIRECT DIGITAL CONTROL PANEL
SF-1
ROOMS
125 & 126
SW
DI
TYPICAL OF TWO
LIGHT SWITCHES
(ONE PER ROOM)
(PROVIDED BY DIV. 16)
DO
SS CR
DI
SSCR
DODI
HWS
HWR
M
CV
N.O.
C
H
AO
FZ
DI
DO DI
FR CR
SET AT
2^C.
SEE DETAIL B4/M601 FOR CONTINUATION9
EXPLOSION
PROOF
HVAC CONTROL
DIAGRAMS
A. PELLEGRINO
A. PELLEGRINO
R. WARD
THERE ARE SEVEN LARGE POULTRY ROOMS WHICH CONTAIN THREE EXHAUST FANS, FOUR CIRCULATION FANS AND
ONE UNIT HEATER. THERE ARE THREE SMALL POULTRY ROOMS WHICH CONTAIN ONLY TWO EXHAUST FANS, TWO
CIRCULATION FANS AND ONE UNIT HEATER. ALL ROOMS ARE CONFIGURED IN THE MANNER AS SHOWN IN THIS
DETAIL. FOR SMALL POULTRY ROOMS DISREGUARD THIRD STAGE EXHAUST FAN AND TWO OF THE CIRCULATION
FANS.
HARD WIRE INTERLOCK UNIT HEATER LOCATED IN HALLWAY AND UNIT HEATER LOCATED IN THE POULTRY ROOM
WITH THE FIRST STAGE EXHAUST FAN SUCH THAT THE UNITS HEATERS WILL NOT BE ABLE TO START IF THE
FIRST STAGE EXHAUST FAN IS NOT OPERATING. UNIT HEATER LOCATED IN HALLWAY SHALL BE INTERLOCKED
WITH CLOSEST FIRST STAGE EXHAUST FAN. SEE SHEET M201 FOR LOCATIONS AND QUANTITIES OF UNIT
HEATERS.
POULTRY SPECIALTY CONTROL PANEL AND VARIABLE SPEED CONTROLLER ARE NOT PART OF THE DIRECT
DIGITAL CONTROL SYSTEM (DDCS). THESE CONTROLS OPERATE INDEPENDENTLY OF THE DDCS. SEE
SPECIFICATION SECTION 15725 FOR FURTHER DETAILS. SEE SPECIFICATION SECTION 15910 FOR
ASSOCIATED SEQUENCES OF OPERATION.
Drawing No.:
Drawing Title:
Date:
Issues:
F5W51104
A
B
C
D
1 2 3 4 5
1 2 3 4 5
Jacobs Project No.:
Designed By:
Drawn By:
Checked By:
Project No:
02-21-03
EPM:
RPM:
Safety & Health:
Real Property:
JFI
FINAL TURNOVER
B. Runser
C. Joyner
DR. McMurty
06-21-07 FINAL RECORD DRAWING
FACILITIES INC.
R
1100 NORTH GLEBE ROAD, SUITE 500, ARLINGTON, VIRGINIA 22201
JUNE 6, 2007
USDA-ARS
C. Harris Proj. Manager:
D e s ig n o f A
N e w
P o u lt ry F a c il it y
B e lt s v il le
A g ri c u lt u ra l
R e s e a rc h C e n te r
US
DA
AR
S
JACOBS
File details come from the government source that posted it. Updated .