Attachment 7 - Drawing A402 Building Sections 21JUN2007.pdf
PDF 417 KB Posted
- Attached to
- Building 229 Roofing System Replacement Federal contract opportunity
- Solicitation number
- 12305B23R0022
About this file
This drawing package contains construction drawings for a new poultry facility at the USDA Agricultural Research Center in Beltsville, Maryland. Key details include specifications for reinforced concrete masonry unit walls, metal roofing system, HVAC ductwork, equipment curbs and exhaust fans, control joints, insulation, flashing and sealant details. The drawings also include sections and details for items like equipment pads, equipment screens, louvered vents, windows, doors, gutters and downspouts. Relevant information is provided for structural supports, foundations, slabs and paving. Dimensioned wall sections, elevations and other construction details are depicted.
The related federal contract opportunity is a solicitation to replace an existing roofing system at Building 229 for the USDA Agricultural Research Service Field Research Implementation and Information Delivery Northeast Area. The solicitation number and opportunity type are provided.
View the file
Other files for this federal contract opportunity
Show all 18
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Drawing No.:
Drawing Title:
Date:
Issues:
F5W51104
A
B
C
D
1 2 3 4 5
1 2 3 4 5
Jacobs Project No.:
Designed By:
Drawn By:
Checked By:
Project No:
02-21-03
EPM:
RPM:
Safety & Health:
Real Property:
JFI
FINAL TURNOVER
B. Runser
C. Joyner
DR. McMurty
06-21-07 FINAL RECORD DRAWING
FACILITIES INC.
R
1100 NORTH GLEBE ROAD, SUITE 500, ARLINGTON, VIRGINIA 22201
JUNE 6, 2007
USDA-ARS
C. Harris Proj. Manager:
D e s ig n o f A
N e w
P o u lt ry F a c il it y
B e lt s v il le
A g ri c u lt u ra l
R e s e a rc h C e n te r
US
DA
AR
S
JACOBS
A402
BUILDING SECTIONS
A402
A1
A401
SCALE 1:20
WALL SECTION
METAL TRUSS ANCHORS
GALVANIZED METAL
CLOSURE PANEL W/
METAL BLOCKING AS
REQUIRED
METAL TRUSS
TOP OF SLAB
203 TH REINFORCED CMU WALL
CONCRETE FOOTING
A402
A2
A401
SCALE 1:20
WALL SECTION
A402
A3
A401
SCALE 1:20
WALL SECTION
GRAVITY DAMPER
A F
F
CONC. APRON
A402
C1
A202
SCALE 1:20
WALL SECTION AT ENTRANCE
CONTINUOUS
BOND BEAM
METAL SADDLE
12 4
GENERAL NOTES:
B O
T T
O M
O F
B O
N D
B E
A M
TYP. HOLLOW METAL
DOOR AND FRAME
TYP. ROOF ASSEMBLY
COOLING PAD TYP.
REFER TO MECHANICAL
REINFORCED/INSULATED CMU
DELETE INSULATION WHERE CELLS
FILLED SOLID FOR REINFORCING.
TYP. GRADE
REFER TO CIVIL
TYP. CONC. APRON
REFER TO CIVIL
PAVING
REFER TO CIVIL
TYP. CONC. SLAB ON GRADE
CONTINUOUS BOND BEAM TYP.
SUSPENDED CEILING
SEE FINISH SCHEDULE
CONCRETE FOOTING -
REFER TO STRUCTURAL
52 TH RIGID INSULATION - EXTEND TO TOP OF
CONC. FOOTING AND MINIMUM 610 HORIZONTALLY
BOTTOM OF LINTEL @ ROLL-UP DOOR
PRE FINISHED
METAL DOWNSPOUT
BEYOND
A402
C2
A201
SCALE 1:20
BOLLARD SECTION
203 203 BITUMINOUS PAVING
CONCRETE FOUNDATION
A402
D2
A201
SCALE 1:10
SEALANT AND BACKER ROD
EACH SIDE10
PREFORMED CONTROL
JOINT GASKET
CONCRETE SASH BLOCK
H/2
H
NOTES:
1. CONTRACTOR TO SUBMIT FOR APPROVAL A SET OF CMU CONTROL
JOINT LOCATION LAYOUT PLANS.
2.
3.
A402
C6
A402 N.T.S.
CONTROL JOINT LOCATIONS, TYP
T Y
P
A402
C3
A202
SCALE 1:20
SCREEN WALL SECTION
CONC. FOOTING
CONTINUOUS SEALANT
EACH SIDE
CONTINUOUS FLASHING
CONTINUOUS SEALANT
EACH SIDE
CONTINUOUS SEALANT
WITH JOINT FILLER
SLOPE
A402
A4
A202
SCALE 1:20
WALL SECTION
CONCRETE SPLASH BLOCK - TYP
CONCRETE FOOTING - REFER TO
STRUCTURAL DWGS.
TYP REINFORCED CMU
WITH EPS - DELETE EPS
INSERTS AT
REINFORCED CELLS
305 TYP
FINISH CEILING
AS SCHEDULED
TYP CMU LINTEL
TYP CONTROL JOINT DETAIL
FINISH GRADE VARIES -
REFER TO CIVIL DWGS
102 TH PRECAST CONC. CAP
W/DOWELS ANCHORED
@ 609 OC TO CMU WALL
R-19 INSULATION - TYP
THRU WALL FLASHING - TYP.
ABOVE STEM WALL WITH
WEEPS AT 813 O.C.
ASPHALT/ FIBERGLASS SHINGLES
ON 30LB ROOFING FELT ON 16 CDX
PLYWOOD ON METAL DECK ON
PRE-FAB METAL TRUSSES - TYP.
ROOF ASSEMBLY
CONTINUOUS CMU BOND BEAM
AT TOP COURSE
PREFINISHED METAL
GUTTER AND
DOWN SPOUT - TYP.
CONTINUOUS SEALANT
ALL AROUND
TOP MASONRY
TOP MASONRY
CIRCULATION FAN
HEATER BEYOND
SHEET METAL
BOOT
LIGHT TRAP
A402
D3
A402
SCALE 1:10
EXHAUST FAN CURB DETAIL
A402
D4
A402
SCALE 1:10
EQUIPMENT CURB
BY MANUFACTURER
METAL COUNTER FLASHING
M
IN
REFER TO MECHANICAL
DWGS FOR EQUIPMENT
VENT DETAIL
SEAL WITH SEALANT WATERTIGHT
CLAMP
VENT PIPE
FASTENERS
TYP. ROOF STRUCTURE
PIPE BOOT
SEAL WITH SEALANT WATERTIGHT
PREFINISHED METAL
GUTTER AND DOWNSPOUT
FACE OF EXTERIOR
WALL BEOYND
203 CMU - REFER
TO STRUCTURAL DWGS.
FOR DETAILS
CONTROL JOINT
AT CORNERS, TYP
( H=HEIGHT OF
MAS. WALLS)
EXTERIOR CMU WALL CONTROL JOINTS
BASED ON THESE CMU CONTROL JOINT LOCATION REQUIREMENTS
PRIOR TO CMU INSTALLATION.
4. SEE DETAIL D2/A402 THIS SHEET FOR TYP CONTROL JOINT DETAIL.
MASONRY CONTROL JOINT MAXIMUM SPACING 7 620.
TRUSS BEARING
CONTINUOUS SEALANT
EXHAUST FAN
AND ENCLOSURE -
REFER MECHANICAL
CONTINUOUS
BOND BEAM
TYP LINTEL
ELEV. 45 000
51 TH RIGID PERIMETER
INSULATION - EXTEND 610
HORIZONTAL AND DOWN TO
FOOTING - TYP
305 PRE FINISHED METAL DOWNSPOUT
BEYOND TYP.
PRE FINISHED
METAL GUTTER
WITH DOWNSPOUTS
R-19 INSULATION - TYP
REINFORCED CONC. SLAB
ON 6 MIL POLY ON GRAVEL
- TYP. CONC. SLAB ON GRADE
CONTROL JOINT AT WALL
INTERSECTIONS AND OFFSETS - TYP
PROVIDE METAL GUTTER SUPPORTS
AT 915 O.C.
THROUGH WALL FLASHING
WITH WEEPS AT 813 O.C.
TYP. LINTEL
ANODIZED ALUMINIUM
INSULATED GLASS -
FIXED WINDOW
A402
C4
A202
SCALE 1:20
A402
C5
A202
SCALE 1:20
ELEVATION DETAIL
AT DUCT PENETRATION
SECTION DETAIL
AT DUCT PENETRATION
BOND BEAM
CONTINUOUS FLASHING
CONTINUOUS SEALANT
EACH SIDE
DUCT- REFER TO
MECHANICAL DWGS
FOR SIZE
MIN.
CONTINUOUS SEALANT
SIZE OPENING
FOR HVAC DUCT
AT 48 251
PRESSURE TREATED
WOOD BLOCKING
EACH SIDE
BEARING 48 251 AFF
BEARING 48 251 AFF
M
IN
CONTINUOUS SEALANT
OVER 13TH
PREMOLDED JOINT
FILLER - TYP
C
O U
R S
E S
C
O U
R S
E S
C
O U
R S
E S
BOND BEAM TYP AT
COOLING PAD LOCATIONS -
REFER TO STRUCTURAL
SHEET METAL
BAROMETRIC
DAMPER
48 148 AFF
TOP CMU AT
INTER. PARTIT.
CONTINUOUS SEALANT
WITH 13 PREMOLDED
JOINT FILLER
CONTROL JOINT AT BOTH SIDES
OF OPENING OVER 1 830 WIDE, TYP
CONTROL JOINT AT ONE SIDE OF
OPENINGS LESS THAN 1 830 WIDE, TYP
CMU BOND BEAM
LINTEL GROUT CMU
SOLID AT JAMBS
B5
A202
A402
D5
A402
SCALE 1:10
RIDGE VENT DETAIL
STEEL ANCHOR PLATE -
REFER TO STRUCT
REFERENCE EL.
45 000
CONTINUOUS SEALANT AND
13 PREMOLDED JOINT
FILLER - TYP AT CONC APPRON
TYP CONC APRON
A402
REINFORCED
CMU BOND BEAM
LINTEL
CONTINUOUS
SEALANT
CORRIDORBIRD ROOM
C S
E S
C
S E
S
�C S
E S
TOP OF CONC.
STEM WALL
C
G E
S C
G E
S C
G E
S
BITUMINDUS
PAVING
LINE OF CONCRETE
PAD FOR FEED BINS
BEY - REFER TO CIVIL
PROVIDE AT 203 CMU EXTERIOR WALL PREFORMED
EXTRUDED POLYSTYRENE INSULATION INSERTS. DELETE INSULATION
WHERE CELLS ARE FILLED SOLID FOR REINFORCING - TYP
203 H X 254 W CONC.
CURB TYP. AT
PERIMETER
254 TH CONCRETE STEM WALL
DOWNSPOUT DOWN TO
BOOT TO BELOW GRADE
STORM PIPING
METAL FURRING
AT 610 O.C.
TYP. ASPHALT/ FIBERGALSS ROOFING
ASPHALT/ FIBERGLASS SHINGLES
ON 30LB ROOFING FELT ON 16
CDX PLYWOOD ON METAL DECK -
TYP. ROOF ASSEMBLYPRE FINISHED METAL GUTTER
CONC. SLAB ON VAPOR
BARRIER TURN DOWN
TO CONC. FOOTING
- REFER TO STRUCTURAL
CONTINOUS SEALANT
OVER 13 TH
PREMOLDED JOINT
FILLER - TYP
CONC. SPLASH BLOCK BEYOND -
TYP. AT EXTERIOR AREAS
5/4" X 12" PTD WOOD
FASCIA, TYP.
15O DIAMETER
PAINTED
STEEL PIPE
FILLED WITH
CONCRETE
1.
METAL RIDGE
VENT CAP
LIGHT GAGE METAL
ROOF TRUSSES
METAL ROOF DECK
30# ASPHALT ROOFING FELT
FOAM AND METAL CLOSURE,
SEAL TOP AND BOTTOM
W/CONT MASTIC
RIDGE VENT 6-PLY
CORRUGATED
POLYETHYLENE VENTS.
1 220 LENGTH, TYP
RIDGE VENT BAFFLE
16 TH EXTERIOR GRADE
PLYWOOD SHEATHING
LIGHT TRAP
REFER MECH
PRECAST CONCRETE SILL
W/ ANCHOR BOLTS
TOP OF SILL
AFF
PREFINISHED ROLL UP
COILING DOOR -
CONTRACTOR PROVIDE
ADEQUATE SUPPORT AT
BOND BEAM
STEEL ANGLE BEYOND BOLT
TO CMU WALL - TYP AT JAMB
C5
A402 A402
C3
A802A402
THROUTH WALL FLASHING
WITH WEEPS AT 610 O.C.
NOTE; FASTEN EQUIPMENT CURBS THROUGH
PLYWOOD INTO METAL DECK
CONTINUOUS SEALANT
EACH SIDE
M .O
CONTINUOUS SEALANT
TYP.
M .O
M .O
M .O
EXTEND FLASHING MIN. 101
AT SIDE AND BOTTOM
OVER ROOFING
EXTEND FLASHING MIN. 101
AT BELOW ROOFING
EXTEND FLASHING MIN. 101
AT BELOW ROOFING
EXTEND FLASHING MIN. 101
AT SIDE AND BOTTOM
OVER ROOFING
METAL ROOFING SYSTEM
PREFINISHED METAL
DRIP EDGE - TYP.
PREFINISHED PERFORATED METAL SOFFIT
PREFINISHED
METAL DRIP EDGE
- TYP.
WOOD FASCIA - ALUM CLAD
ALUM. CLAD
5/4" X 12"
WOOD FASCIA, TYP
PREFINISHED
PERFORATED METAL
SOFFIT- TYP.
PREFINISHED METAL
DRIP EDGE - TYP.
CONTINUOUS SEALANT EACH SIDE - TYP.