Attachment 6 - Technical Compliance Crosswalk_C2PL2550.xlsx

XLSX spreadsheet 16 KB Posted

Attached to
Uninterruptible Power Supply for Shipboard Alarm and Announcing System and Electronic Chart Display and Information System
Solicitation number
70Z04425RC2PL2550
Issued by

About this file

This document is a Technical Compliance Crosswalk for a United States Coast Guard solicitation for Uninterruptible Power Supplies (UPS) for shipboard systems. The solicitation requires two specific UPS models: a 1.5kVA/980W unit and a 3.0kVA/2.25kW unit, both with rack-mount configurations. Key technical specifications include 120V nominal input voltage, specific dimensional constraints (2U and 4-6U heights), NEMA input/output connections, 30-minute runtime at full load, RS-232 monitoring capabilities, and receptacle locking mechanisms.

The contract mandates a minimum 3-year standard commercial warranty with product return policy, and requires the UPS to support the Shipboard Alarm & Announcing System (A&AS) and Electronic Chart Display and Information System (ECDIS). The solicitation is issued by the Department of Homeland Security's US Coast Guard Command Control, Communications, Computers, Cyber and Intelligence Service Center (C5ISC), with the specific solicitation number 70Z04425RC2PL2550. Vendors must complete the technical compliance crosswalk, indicating how their proposed UPS solutions meet each specified requirement.

View the file

Other files

Show all 21

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet1

Solicitation 70Z04425RC2PL2550
Attachment 7 - Technical Compliance Crosswalk
Contractor's Name:
SAM Unique Entity Identifier (UEI):

Manufacturer Name, Model/Part Number:

The Uniterupptible Power Supply (UPS) shall meet all of the following Threshold (minimum) requirements/specifications.Specify below if your proposed solution meets or does not meet each requirement/specification in the left hand column. Please provide additonal information if your proposed solution does not meet a specific requirement. You may provide datasheets to supplement this form.
Desired replacement for the existing 850VA UPS/1.15kVA UPS/1.5kVA UPS shall meet/exceed the following specifications:
System Capacity: 1.5kVA / 980W
Nominal Input Voltage: 120V
Dimensions:
Height – No taller than 3.50 inches / 2U
Width – No wider than 19 inches due to standard rack width
Depth – No deeper than 18 inches due to standard rack depth and space for cabling.
Input Connection: NEMA L5-30P
Output Connection: (4) NEMA 5-30R
Mounting: Rack Mount (2U)
Minimum Runtime Requirement: 30 Minutes at Full Load
Provide RS-232 connection (DB-25 preferred) for monitoring status of UPS at remote (on board) location through cable connection.
Provide receptacle locking/cover for NEMA 5-30R output connections, so that unauthorized equipment will not be connected to UPS.
Desired replacement for the existing 1.8kVA UPS/3.0kVA UPS/3.1kVA UPS shall meet/exceed the following specifications:
System Capacity: 3.0kVA / 2.25kW
Nominal Input Voltage: 120V
Dimensions:
Height – No taller than 10.50 inches / 6U but no smaller than 7.00 inches (4U)
Width – No wider than 19 inches due to standard rack width
Depth – No deeper than 18 inches due to standard rack depth and space for cabling.
Input Connection: NEMA L5-30P
Output Connection: (4) NEMA 5-30R
Mounting: Rack Mount (4U or 6U)
Minimum Runtime Requirement: 30 Minutes at Full Load
Provide RS-232 connection (DB-25 preferred) for monitoring status of UPS at remote (on board) location through cable connection.
Provide receptacle locking/cover for NEMA 5-30R output connections, so that unauthorized equipment will not be connected to UPS.
Provide (1) rack for rack mounted UPS that will serve the Shipboard Alarm & Announcing System (A&AS).
Warranty:
The contractor shall provide a standard commercial warranty for a minimum of 3 years after delivery of equipment to the USCG. Product warranties shall include a product return policy. Any Original Equipment Manufacturer (OEM) warranties associated with products delivered under this contract/task order shall be available directly to the USCG.

File details come from the government source that posted it. Updated .