This document is a Questions and Responses file for a U.S. Coast Guard solicitation (70Z04425RC2PL2550) for Uninterruptible Power Supplies (UPS) for shipboard systems. The document contains 13 technical specification questions and corresponding government responses addressing critical details such as power input configurations, TEMPEST requirements, battery specifications, and system capacities. Key clarifications include confirming a BLACK TEMPEST application, accepting L5-20/15P input configurations, allowing NEMA L5-15R outputs, and verifying a 30-minute runtime as a threshold requirement. NAVSEA is identified as the approving authority for lithium batteries in shipboard applications, and the U.S. Coast Guard will be responsible for first article testing. The UPS must meet specific dimensional constraints, with a maximum depth of 18 inches, and have a system capacity of 3.0kVA/2.25kW, with potential flexibility to adjust to 3.0kVA/2.1kW if necessary.
View the file
Other files
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Question Original Document Page /
Section Issue Question
Answers
Technical
Specifications
Will the Government Accept one L5-30R (locking) for
PDU's to distribute more 120V receptacles
No, UPS must have several output locking receptacles for simplicity of equipment integration and lessening failure points.
Technical
Specifications the requested 30 AMP 120V input to provide 1.5kVA is not doable. At minimum, off of a L5-30P, it will be at 3000VA.
Will the Government accept L5-20P/5-20P (or even a standard 5-15P), then we can likely size down appropriately
Lowering the AMP for a suitable UPS (1.5KVA having L5-
20/15P) is acceptable.
Technical
Specifications 1.3.1
U.S. Coast Guard TEMPEST Program, COMDTINST
M2241.6 – we are unable to locate this document, please provide the locating data.
Provided as "Attachment 9" with this Amendment.
Technical
Specifications 1.3.1
MIL-STD-1680C, TEMPEST Requirements – This reference requires that RED and BLACK power be identified. The Technical Specifications do not specify if this is a RED or BLACK Application. Please identify the TEMPEST application.
Attachment 1 - Technical Specifications, Section 2.1 has been revised to state, "All Uninterruptible Power Supplies will be a BLACK application when it comes to the
TEMPEST requirements. BLACK power is the requirement due to non-cyber sensitive interactions with supported equipment. Solution must follow the applicable bonding
(Class B Bonding) requirements in accordance with MIL-
STD-1310." [MIL-STD-1310 provided as "Attachment 8" with this Amendment]
Technical
Specifications 1.3.1
TS-313 Technical Standard 313 Batteries – we are unable to locate this document, please provide the locating data.
Provided as "Attachment 7" with this Amendment.
Technical
Specifications 2.1.1.3
Dimensions: Does the does the desired volume include the batteries or may the batteries be provided separately?
Attachment 1 - Technical Specifications, Section 2.1.1.3 has been revised to state, "Dimensions (Desired volume of UPS upon installation will include batteries installed
Technical
Specifications
2.1.1.3.3 Depth: Is the depth inclusive of the locking cover?
Attachment 1 - Technical Specifications, Section 2.1.1.3.3 has been revised to state, "Depth – No deeper than 18 inches due to standard rack depth and space for cabling.
The depth includes the locking cover."
Technical
Specifications 2.1.1.5
Output Connection: (4) NEMA 5-30R – the maximum current is 8.2Amps Are NEMA 5-15R Outputs acceptable?
Yes, NEMA L5-15R outputs are acceptable.
Technical
Specifications 2.1.2.1
System Capacity: 3.0kVA / 2.25kW: The system capacity is outside of the allowed value for
Reference i. MIL-DTL-24765B which has a maximum capacity of 3.0kVA / 2.1kW.
Please clarify the correct capacity.
The Government reviewed MIL-DTL-24765B and could not find the noted requirement for maximum capacity of
3.0kVA/2.1kW. It is acceptable to move forward with maximum capacity of 3.0kVA / 2.1kW, if necessary.
Questions & Responses_70Z04425RC2PL2550
10 Technical 2.1.2.3.3 Depth: Is the depth inclusive of the locking cover? See response provided for Questions 7.
11 MIL-DTL-24765B
Specifies the use of Lead Acid Batteries or NAVSEA approval for the use of Lithium Batteries.
Is NAVSEA the approving authority for Lithium
Batteries?
Yes, NAVSEA is the approving authority for Lithium batteries in a shipboard application in accordance with
NAVSEA Technical Publication S9310-AQ-SAF-010 and TS-
313 Technical Standard 313 Batteries.
12 MIL-DTL-24765B
For the 1.5KVA UPS the minimum volume for lead acid batteries to achieve a run time of 30 minutes at
980W is 609 cubic inches. The maximum available volume for the UPS is 1025 cubic inches. There is insufficient volume for the UPS electronics and the batteries.
Is 30 minutes a threshold or objective value?
30 mintues is the threshold.
13 MIL-DTL-24765B
Who is responsible for first article testing? USCG or
Contractor?
USCG will be responsible for the First Artcile Testing.