Attachment 6 - Technical Compliance Crosswalk_C2PL2550 Amendment 0005.xlsx
XLSX spreadsheet 18 KB Posted
- Solicitation number
- 70Z04425RC2PL2550
About this file
The file is a Technical Compliance Crosswalk for a United States Coast Guard (USCG) solicitation for Uninterruptible Power Supplies (UPS) for shipboard systems. The technical specifications require a UPS with 3.0kVA/2.25kW capacity, 120V nominal input voltage, and specific dimensional constraints (maximum height of 10.50 inches/6U, width of 19 inches, depth of 18 inches). Additional requirements include a NEMA L5-30P input connection, four NEMA 5-30R output connections, rack mounting, minimum 30-minute runtime at full load, RS-232 connection for monitoring, and a receptacle locking cover.
The solicitation (Number 70Z04425RC2PL2550) is issued by the Department of Homeland Security's US Coast Guard Command Control, Communications, Computers, Cyber and Intelligence Service Center (C5ISC). The UPS will serve the Shipboard Alarm & Announcing System (A&AS) and Electronic Chart Display and Information System (ECDIS). Warranty terms mandate a minimum 3-year standard commercial warranty with a product return policy, and any Original Equipment Manufacturer (OEM) warranties must be directly available to the USCG.
View the file
Other files
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet1
| Solicitation 70Z04425RC2PL2550 |
| Attachment 7 - Technical Compliance Crosswalk |
| Contractor's Name: |
| SAM Unique Entity Identifier (UEI): |
Manufacturer Name, Model/Part Number:
| The Uniterupptible Power Supply (UPS) shall meet all of the following Threshold (minimum) requirements/specifications. | Specify below if your proposed solution meets or does not meet each requirement/specification in the left hand column. Please provide additonal information if your proposed solution does not meet a specific requirement. You may provide datasheets to supplement this form. |
| Desired replacement for the existing 1.5kVA/1.8kVA UPS/3.0kVA UPS/3.1kVA UPS shall meet/exceed the following specifications: | |
| System Capacity: 3.0kVA / 2.25kW (2.1kW acceptable) | |
| Nominal Input Voltage: 120V | |
| Dimensions: | |
| Height – No taller than 10.50 inches / 6U | |
| Width – No wider than 19 inches due to standard rack width | |
| Depth – No deeper than 18 inches due to standard rack depth and space for cabling. The depth includes the locking cover. | |
| Input Connection: NEMA L5-30P | |
| Output Connection: (4) NEMA 5-30R | |
| Mounting: Rack Mount | |
| Minimum Runtime Requirement: 30 Minutes at Full Load | |
| Provide RS-232 connection (DB-25 preferred) for monitoring status of UPS at remote (on board) location through cable connection. | |
| Provide receptacle locking/cover for NEMA 5-30R output connections, so that unauthorized equipment will not be connected to UPS. | |
| Warranty: | |
| The contractor shall provide a standard commercial warranty for a minimum of 3 years after delivery of equipment to the USCG. Product warranties shall include a product return policy. Any Original Equipment Manufacturer (OEM) warranties associated with products delivered under this contract/task order shall be available directly to the USCG. |
File details come from the government source that posted it. Updated .