This is an Owners/Technical Manual for the Mitsubishi Electric Automation, Inc. 2033C Series Uninterruptible Power Supply (UPS) system, Revision 2.2 dated April 2, 2001.
The manual provides comprehensive installation, operation, and maintenance guidance for 2033C Series UPS systems available in seven capacity ratings: 7.5, 10, 15, 20, 30, 40, and 50 kVA. All models operate at 208V three-phase, 60 Hz input and output, with internal batteries included for models up to 30 kVA and external batteries for 40-50 kVA models. Key specifications include 360 Vdc nominal battery voltage with 180 cells, battery ride-through times ranging from 5 to 11 minutes at full load depending on model, output voltage stability of ±1%, and frequency stability of ±0.01% in free-running mode. The UPS provides two power paths: normal operation through the inverter for clean, conditioned power, and static bypass operation for maintenance or emergency conditions. Installation requires user-supplied AC input circuit breakers (MCCB) with capacities ranging from 30A (7.5 kVA) to 200A (50 kVA), along with field-supplied output and DC input overcurrent protection. The manual specifies recommended cable sizes from 8 AWG to 2/0 AWG depending on capacity, all requiring 180 inch-pound torque at terminals. Operating procedures include start-up, shutdown, emergency power off (EPO), and maintenance bypass transfer protocols. The manual includes detailed fault code guidance with 50+ diagnostic codes covering battery, converter, inverter, bypass, control circuit, and overload conditions, with instructions to contact Mitsubishi Electric Automation at 1-800-887-7830 for service support.
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Revision 2.2: April 2, 2001
ALN-H0355
MITSUBISHI ELECTRIC AUTOMATION, INC.
UNINTERRUPTIBLE POWER SUPPLY SYSTEM
2033C SERIES
OWNERS / TECHNICAL MANUAL
MITSUBISHI
ELECTRIC
2033C SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
i
MITSUBISHI ELECTRIC 2033C SERIES UPS
Preface
2033C SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
ii
TABLE OF CONTENTS
LIST OF TABLES ................................................................................................ iii LIST OF FIGURES .............................................................................................. iv HOW TO USE THIS MANUAL ............................................................................ v
1.0 INTRODUCTION .......................................................................................... 1-1
1.1 GENERAL..................................................................................................... 1-3
1.2 DEFINITIONS ............................................................................................. 1-4
1.3 OVERVIEW ................................................................................................. 1-5
1.4 SPECIFICATIONS ...................................................................................... 1-12
2.0 OPERATION CONTROLS AND INDICATORS ..................... 2-1
2.1 LED DISPLAY AND KEYPAD .................................................................... 2-2
2.2 EXTERNAL SIGNAL TERMINAL BLOCK .................................................. 2-3
2.3 EXTERNAL COMMUNICATION CONNECTOR ...................................... 2-6
3.0 INSTALLATION AND OPERATION ............................... 3-1
3.1 TRANSPORTATION AND INSTALLATION .............................................. 3-1
3.2 HANDLING ................................................................................................. 3-1
3.3 INSTALLATION PROCEDURE .................................................................. 3-2
3.4 PROCEDURE FOR CABLE CONNECTIONS ........................................... 3-3
3.5 OPERATING PROCEDURES ................................................................... 3-9
3.6 MAINTENANCE BYPASS SET-UP PROCEDURES ................................ 3-10
4.0 RESPONSE TO UPS FAILURE .................................. 4-1
5.0 PARTS REPLACEMENT ........................................ 5-1
6.0 FAULT CODES ................................................ 6-1
2033C SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
iii
List of Tables
Table 1.1 Power Specifications .................................................................. 1-12 Table 1.2 UPS Module Information ............................................................. 1-12 Table 1.3 Detail of Specifications ............................................................... 1-13 Table 1.4 Rating of Conductor and Fuses .................................................. 1-14 Table 3.1 How to Transport and Install the System .................................... 3-1 Table 3.2 List of UPS Weights (lb.) ............................................................ 3-2 Table 3.3 Type and Number of Internal Battery ......................................... 3-2 Table 3.4 Recommended Cable Size and Torque Requirements ............. 3-4 Table 3.5 Crimp Type Compression Lug .................................................... 3-4
2033C SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
iv
List of Figures
Figure 1.1 Single Line Diagram- Normal Operation .................................... 1-5 Figure 1.2 Single Line Diagram- Bypass Operation .................................... 1-6 Figure 1.3 Single Line Diagram- Battery Operation ..................................... 1-7 Figure 1.4 Single Line Diagram- UPS on Maintenance Bypass Operation. . 1-7 Figure 1.5a UPS Parts Location (7.5-20kVA) ................................................ 1-9 Figure 1.5b UPS Parts Location (30kVA) ...................................................... 1-10 Figure 1.5c UPS Parts Location (40,50kVA) ................................................. 1-11 Figure 1.6 Display PCB DPAU-57/DPAU-58 ............................................... 1-11 Figure 1.7 External I/F PCB RYDR-O/RYDR-X ........................................... 1-11 Figure 1.8a Main Control PCB UPFR-Y ......................................................... 1-12 Figure 1.8b Main Control PCB UPFR-K ........................................................ 1-12 Figure 2.1 Operation/Display Panel ............................................................. 2-1 Figure 2.2 Normal operation on 7 Segment LED Display ........................... 2-2 Figure 2.3 External Signal Terminal Block .................................................. 2-3 Figure 2.4 Control Wiring for External Contacts .......................................... 2-4 Figure 2.5 Remote "Start" Contact Connections ......................................... 2-5 Figure 2.6 External communication connector ............................................ 2-6 Figure 3.1 Handling ...................................................................................... 3-1 Figure 3.2 UPS Terminal Designation ......................................................... 3-5 Figure 3.3 Input / Output Power Terminals (7.5-20kVA) ............................. 3-6 Figure 3.4 Input / Output Power Terminals (30kVA) .................................... 3-7 Figure 3.5 Input / Output Power Terminals (40,50kVA) ............................... 3-8 Figure 3.6 EPO Button ................................................................................. 3-9
2033C SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
v
How to use this Manual
This manual is designed for ease of use, giving the user easy and quick reference to information.
This manual uses notice icons to draw attention to the user important information regarding the safe operation and installation of the UPS. The notice icons used in this manual are explained below, and should be taken into account and adhered to whenever they appear in the text of this manual.
WARNING: A warning notice icon conveys information provided to protect the user and service personnel against hazards and/or possible equipment damage.
CAUTION: A caution notice icon conveys information provided to protect the user and service personnel against possible equipment damage.
NOTE: A Note notice icon indicates when the user should make a reference of information regarding the UPS operation, load status and display status.
Such information is essential if Mitsubishi field service group assistance and correspondence is required.
Safety Recommendations: If any problems are encountered while following this manual, Mitsubishi field service group assistance and correspondence is recommended.
ELECTRIC
2033C SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
1-1
1.0 INTRODUCTION
The Mitsubishi Uninterruptible Power Supply (UPS) is designed to provide many years of reliable power supply and protection from power failure, brown-outs, line noise and voltage transients. To ensure optimum performance of the equipment, follow the manufacturer's instructions accordingly.
This manual contains descriptions for the installation and operation procedures of the UPS. Please read this manual carefully and retain it for future reference.
This manual contains important instructions for the 2033C Series Uninterruptible Power Supply Systems that should be adhered to during installation, operation and maintenance of the UPS and batteries.
Lethal voltages exist within the equipment during operation.
Observe all warning and cautions in this manual.
Failure to comply may result in serious injury or death.
Obtain a qualified service for this equipment as per instructions.
IMPORTANT SAFETY INSTRUCTIONS
RETAIN THESE INSTRUCTIONS
WARNING 1
ELECTRIC
2033C SERIES UPS
OWNERS / TECHNICAL MANUAL
1-2
This UPS does not include an AC input circuit breaker (MCCB) to protect the bypass and main input circuit. The AC input circuit breaker (MCCB) is to be field supplied and installed. Circuit breaker (MCCB) specifications are as follows:
Capacity (kVA)
AC input Voltage (Vac)
AC input Rating (Aac)
Recommended Breaker (A)
7.5 208 23 30 10 208 30 35 15 208 45 60 20 208 61 75 30 208 91 125 40 208 121 150 50 208 151 200
AC output and DC input overcurrent protection and disconnection devices shall be field supplied and installed.
WARNING 2
ELECTRIC
2033C SERIES UPS
OWNERS / TECHNICAL MANUAL
1-3
1.1 General
The Mitsubishi 2033C Series UPS is designed to provide continuous and clean electrical power to a critical load. In the event of an input power failure, the UPS will supply power to the critical load for the specified battery time.
If the input power is not restored promptly, backup power from the UPS battery permits the orderly shutdown of equipment supported by the UPS. The UPS is simple to start up, operate and maintain.
The 2033C Series UPS is available in seven (7) kVA sizes: 7.5, 10, 15, 20, 30, 40 and 50kVA.
Specifications for each kVA model appear in Section 1.4. Models up to 30kVA have batteries included in the UPS module cabinet. 40kVA and 50kVA models have external batteries. The principles of operation described herein are applicable to all models.
This manual provides an overview of the 2033C Series components and their functions. The appearance and purpose of operator controls and indicators is described with procedures for operation, start-up, shutdown and basic maintenance included.
ELECTRIC
2033C SERIES UPS
OWNERS / TECHNICAL MANUAL
1-4
1.2 Definitions
UNINTERRUPTIBLE POWER SUPPLY SYSTEM (UPS) - All components within the UPS Module Cabinet and associated batteries which function as a system to provide continuous, conditioned AC power to a load. This is sometimes referred to as the "System".
UPS MODULE CABINET - The metal enclosure which contains the Converter / Charger, Inverter, Static Transfer Switch, Internal Bypass line, operator controls, batteries (up to 30kVA models only) and internal control systems required to provide specified AC power to a load.
UPS MODULE - The Converter / Charger and Inverter assemblies which, under the direction of the internal control system and operator controls, provide specified AC power to a load.
CONVERTER / CHARGER - The UPS components which contain the equipment and controls necessary to convert input AC power to regulated DC power required for battery charging and for supplying power to the Inverter.
INVERTER - The UPS components which contain the equipment and controls necessary to convert DC power from the Converter / Charger, or the battery, to AC power required by the critical load.
STATIC TRANSFER SWITCH - The device which connects the critical load to the bypass line when the Inverter cannot supply continuous power.
BYPASS LINE - The line which conducts electricity directly from the input power source to the critical load during Maintenance or whenever the UPS is not completely operational.
AC INPUT POWER - Power provided by the electrical utility company, or auxiliary generator, which is connected to the UPS for supplying the critical load and recharging the battery.
BATTERY - The rechargeable battery strings which supply DC power to the inverter to maintain continuous AC power to the load during AC input power failure conditions.
ELECTRIC
2033C SERIES UPS
OWNERS / TECHNICAL MANUAL
1-5
1.3 Overview
The UPS provides two power paths between the utility source and the critical load. Figure 1.1 shows the path for normal operation, with the load powered from the inverter. Figure 1.2 shows the path for bypass operation, with the load supplied through the static bypass line.
FIGURE 1.1 Single Line Diagram - Normal Operation. Load powered by inverter.
During normal operation, the path through the inverter is used to power the load.
Referring to Figure 1.1: Input AC power is converted to DC by the Converter. DC power is utilized to charge the UPS battery and to provide power to the Inverter. The Inverter converts the DC power to clean AC power to supply the critical load.
The conversion - inversion process eliminates any voltage transients or fluctuations existing in the input power before it reaches the critical load.
* The Input circuit breaker(MCCB) for protection of the UPS and cables are field supplied and field installed. (See WARNING 2 in section 1.0).
UPS Module
Static Transfer Switch
Power Flow
Not in Use
AC input
CB
FB
CB2
CB3
CONVERTER INVERTER
Output
52C CB1 FI FO
BATTERY
User supplied 52CS(7.5-20kVA)
52MB&52L(30-50kVA)
Maintenance Bypass Switch
40kVA, 50kVA:
External Battery
ELECTRIC
2033C SERIES UPS
OWNERS / TECHNICAL MANUAL
1-6
FIGURE 1.2 Single Line Diagram - Bypass Operation. Load fed through static bypass line.
Referring to Figure 1.2, the Internal Static Bypass line is a Hard wired line through CB3 which supplies the critical load with unconditioned input power. The purpose of this line is to route power to the critical load while the UPS module is de-energized (converter and inverter), and during Start-up before the system is fully operational.
The internal control system determines the operation of the two paths, with the load powered from the inverter being the normal operation.
Referring to Figure 1.3, if the input power is interrupted, the battery will immediately supply the DC power required by the Inverter to maintain continuous AC power to the load. A fully charged battery will provide power for the specified time at the rated load, or longer at reduced load.
When power is restored after a low battery shutdown, the Converter automatically restarts operation, recharges the batteries and the Inverter is automatically restarted without operator intervention. The load is assumed by the inverter automatically without operator intervention.
In the event of a power failure, the Converter will de-energize and the batteries will discharge into the
Inverter and maintain power to the critical load until a) the battery capacity expires and the inverter turns off, or b) input power is restored after which the converter will power the inverter and
UPS Module
Power Flow
Not in Use
AC input
CB
FB
CB2
CB3
CONVERTER INVERTER
Output
52C CB1 FI FO
BATTERY
User supplied 52CS(7.5-20kVA)
52MB&52L(30-50kVA)
Maintenance Bypass Switch
40kVA, 50kVA:
External Battery
Static Transfer Switch
ELECTRIC
2033C SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
1-7 simultaneously recharge the batteries. Figure 1.3 illustrates the flow diagram during battery operation.
FIGURE 1.3 Single Line Diagram - Battery Operation
The UPS is equipped with an internal rotary type Maintenance Bypass Switch (MBS) that can be used to divert utility power to the load during maintenance sessions. Figure 1.4 illustrates the power path when the MBS is in the BYPASS mode.
FIGURE 1.4 Single Line Diagram - UPS on Maintenance Bypass Operation.
UPS Module
FB
BATTERY
CB2
CB3
Static Transfer Switch
Power Flow
Not in Use
Output
52C CB1 FI FO
AC input
CB
User supplied
CONVERTER INVERTER
Maintenance Bypass Switch
40kVA, 50kVA:
External Battery
52CS(7.5-20kVA) 52MB&52L(30-50kVA)
UPS Module
FB
BATTERY
CB2
CB3
Static Transfer Switch
Power Flow
Not in Use
52C FO
CONVERTER INVERTER
Output AC input
CB
User supplied
Maintenance Bypass Switch
CB1 FI
40kVA, 50kVA:
External Battery
52CS(7.5-20kVA) 52MB&52L(30-50kVA)
ELECTRIC
2033C SERIES UPS
OWNERS / TECHNICAL MANUAL
1-8
(7.5/10/15/20kVA)
The rotary maintenance bypass switch is shown as 52CS in Figure 1.4. 52CS is a two position three point make-before-break transfer switch.
(30/40/50kVA)
Two contactors (52MB, 52L) are used instead of the 52CS. A rotary switch(SWM) is used for control of the two contactors.
The two positions are identified as NORMAL and BYPASS. In the NORMAL position the load is fed by the UPS - either through the inverter or through the static bypass line. In the BYPASS position the load is powered by an external source such as the utility or a generator. This transfer operation must be made while the UPS is in the static bypass mode.
The transfer procedure to place the UPS in maintenance bypass mode, or from bypass mode to normal operation mode is outlined below:
A) Transfer of load from inverter to maintenance bypass
1. On the front panel, press the "STOP" button. The “BYP.OP.” LED illuminates within 3 seconds.
2. After confirming that the “BYP.OP.” LED is illuminated, Rotate MBS(52CS/SWM) clockwise to the
“TRANSFER” position (Do not rotate 52CS/SWM if the “BYP.OP.” LED is NOT illuminated).
3. After 3 seconds, rotate 52CS/SWM clockwise to the “BYPASS” position.
4. Transfer complete. Load is now powered from the external source. UPS can be shutdown.
B) Transfer of load from maintenance bypass to inverter
1. Rotate 52CS/SWM counterclockwise from the “BYPASS” position to the “TRANSFER” position, wait 5 seconds.
2. On the UPS, confirm the “BYP.OP.” LED is illuminated. If not, press the “STOP” button.
3. Rotate 52CS/SWM counterclockwise to the “NORMAL” position.
4. On the UPS, press the “START” button. The “INV.OP.” LED should illuminate.
5. Transfer complete. Load now powered by the inverter.
ELECTRIC
2033C SERIES UPS
OWNERS / TECHNICAL MANUAL
1-9
FIGURE 1.5a UPS Parts Location(7.5-20kVA)
3.Main PCB
UPER-Y/UPFR-K
2.Relay PCB
RYDR-O/RYDR-X
UPS module
FRONT VIEW
Converter & Inverter Unit
6.Maintenance bypass transfer switch
52CS
Battery
4.AC input, AC output terminal
Cooling fan
1.Display PCB
DPAU-57/DPAU-58
5.Grounding bar
ELECTRIC
2033C SERIES UPS
OWNERS / TECHNICAL MANUAL
1-10
FIGURE 1.5b UPS Parts Location(30kVA)
3.Main PCB
UPFR-K
2.Relay PCB
RYDR-X
UPS module
FRONT VIEW
Converter & Inverter Unit
6.Maintenance bypass transfer switch
SWM
Battery
4.AC input, AC output terminal
Cooling fan
1.Display PCB
DPAU-58
5.Grounding bar
ELECTRIC
2033C SERIES UPS
OWNERS / TECHNICAL MANUAL
1-11
FIGURE 1.5c UPS Parts Location(40,50kVA)
FIGURE 1.6 Display PCB DPAU-57/DPAU-58
FIGURE 1.7 External I/F PCB RYDR-O/ RYDR-X
DPAU-57
DPAU-57/58
7.SW5
TEST switch
3.Main PCB
UPFR-K
UPS module
FRONT VIEW
Converter & Inverter Unit
6.Maintenance bypass transfer switch
SWM
4.AC input, AC output terminal
Cooling fan
1.Display PCB
DPAU-58
5.Grounding bar 2.Relay PCB
RYDR-X
RYDR-O/
RYDR-X
9.CN62 RS232C
D-sub Connector
8.External contact signal terminal block
(for RYDR-X only)
10.CN64 RS232C
D-sub Connector (for RYDR-X only)
ELECTRIC
2033C SERIES UPS
OWNERS / TECHNICAL MANUAL
1-12
FIGURE 1.8a Main control PCB UPER-Y
FIGURE 1.8b Main control PCB UPFR-K
MCBR-T
UPER-Y
11.SW3
BOOT switch
12.SW1
RESET switch
7.SW2
TEST switch
UPFR-K
11.SW13
BOOT switch
12.SW14
RESET switch
7.SW11
TEST switch
ELECTRIC
2033C SERIES UPS
OWNERS / TECHNICAL MANUAL
1-13
Description of UPS parts, referred to in Figure 1.5:
1. Display PCB DPAU-57/DPAU-58
Switches on DPAU-57/DPAU-58 board : FOR SERVICE PERSONNEL ONLY (Figure 1.6):
- (7) SW5 (TEST switch)
2. Relay PCB RYDR-O/RYDR-X board
Signal I/F on RYDR-O/RYDR-X board : (Figure 1.7):
- (8) External contact signal terminal block
- (9) CN62 (RS232C communication connector)
- (10) CN64 (RS232C communication connector)
3. Main PCB UPFR-Y/UPFR-K
Switches on UPFR-Y/UPFR-K board : FOR SERVICE PERSONNEL ONLY (Figure 1.8):
- (7) SW2(UPFR-Y)/SW11(UPER-K) (TEST switch)
- (11) SW3(UPFR-Y)/SW13(UPER-K) (BOOT switch).
- (12) SW1(UPFR-Y)/SW14(UPER-K) (RESET switch)
4. AC input, AC output terminal Refer to Figure 3.3 for details
5. Grounding bar (E)
6. Maintenance Bypass Switch (52CS/SWM) (FOR SERVICE PERSONNEL ONLY) This switch is used to transfer the load from inverter power to external power for maintenance purposes. Do not operate it under normal operation.
7. "Test mode" switch (FOR SERVICE PERSONNEL ONLY) This switch changes system operation to the test-mode. This switch is mounted on Display PCB and Main PCB. (This switch should not be operated by personnel other than an Authorized Service Engineer).
8. External contact signal terminal block Terminal block to connect contact signal input/output lines to and from external dry contacts. Refer to FIGURE 2.3 for details.
9. RS232C connector (CN62)
Refer to Figure 2.6 for detail.
10. RS232C connector (CN64)
11. "BOOT" switch (FOR SERVICE PERSONNEL ONLY) This switch boots the processor on the main control circuit board following alarm conditions. (Do not operate this switch while inverter and converter are in operation).
12. "Reset" switch (FOR SERVICE PERSONNEL ONLY) This switch resets errors resulting from alarm conditions. (Do not operate this switch while inverter and converter are in operation).
ELECTRIC
2033C SERIES UPS
OWNERS / TECHNICAL MANUAL
1-14
1.4 Specifications
The UPS name plate displays the rated kVA as well as nominal voltages and currents.
The name plate is located on the interior side of the UPS front door.
TABLE 1.1 Power Specifications
Rated output
Power
Input voltage
3 ∅ / 4 wire
Output voltage
3 ∅ /3 or 4 wire
7.5kVA/6kW
10kVA/8kW
15kVA/12kW
20kVA/16kW
30kVA/24kW
40kVA/32kW
50kVA/40kW
TABLE 1.2 UPS Module Information
UPS
(kVA)
CABLE
ENTRY
WIDTH
(in/mm)
DEPTH
(in/mm)
HEIGHT
(in/mm)
WEIGHT
(lb./kg)
HEAT LOSS
@ 208V
(kBTU/h)
7.5 BOTTOM 17.7 / 450 31.5 / 800 43.3 / 1100 562 / 255* 3.2
10 BOTTOM 17.7 / 450 31.5 / 800 43.3 / 1100 562 / 255* 3.9
15 BOTTOM 17.7 / 450 31.5 / 800 43.3 / 1100 816 / 370* 5.1
20 BOTTOM 17.7 / 450 31.5 / 800 43.3 / 1100 816 / 370* 6.5
30 BOTTOM 23.6 / 600 31.5 / 800 59.0 / 1500 1235 / 560* 8.8
40 BOTTOM 27.6 / 700 31.5 / 800 59.0 / 1500 1082 / 490 11.9
50 BOTTOM 27.6 / 700 31.5 / 800 59.0 / 1500 1082 / 490 14.6
*:7.5-30kVA Including batteries
ELECTRIC
2033C SERIES UPS
OWNERS / TECHNICAL MANUAL
1-15
TABLE 1.3 Detail of Specifications
Rated Output kVA 7.5 10 15 20 30 40 50 Rated Output kW 6 8 12 16 24 32 40
AC INPUT CHARACTERISTICS
Configuration 3 phase, 4 wire Voltage 120/208 V +15% ~ -25% Frequency 60 Hz ± 5% Reflected Current THD 4% typ. at 100% load; 7% typ. at 50% load
BATTERY
Type VRLA Ride Through 8min.
at 100% load
5min.
at 100% load
11min.
at 100% load
7min. at 100% load
5min. at 100% load
Nominal Voltage 360 Vdc Minimum Voltage 300 Vdc Number of Cells 180
AC OUTPUT
Configuration 3 phase, 3 or 4 wire Voltage 120/208 V Voltage Stability ±1% Frequency 60 Hz Frequency Stability ±0.01% in free running mode Power Factor 0.8 nominal Power Factor range 0.8 ~ 1.0 lagging (within output kW rating) Voltage THD 2% typical THD at 100% Linear Load
4% typical THD at 100% non-linear load Transient Response ±3% typical at 100% load step
±1% typical at loss/return of AC power ±3% typical at load transfer to/from static bypass
Transient Recovery 16.7 ms Voltage Unbalance 2% typical at 100% unbalanced load Phase Displacement 1deg. typical at 100% load Inverter Overload 150% for 1 minute System Overload 150% for 1 minute, 1000% for 1 cycle (with bypass available) Bypass Overload 150% for 1 minute, 1000% for 1 cycle Crest Factor Capabilities 3:1
ENVIRONMENTAL
Cooling Forced Air Operating Temperature 2° F ~ 104° F (0° C ~ 40° C). Recommended 59° F ~ 77° F (15° C ~
25° C) Relative Humidity 5% ~ 95% Non Condensing Altitude 0 ~ 5000 feet No Derating Location Temperature-controlled, indoor area free of conductive contaminants
ELECTRIC
2033C SERIES UPS
OWNERS / TECHNICAL MANUAL
1-16
TABLE 1.4 Rating of Contactors and Fuses
Component(s) Description Component Rating @ 208V,3 phase, 60 Hz UPS Rating (kVA) 7.5 10 15 20 30 40 50
CB1 AC Input Contactor 60A 100A 150A 150A
CB2 DC Input Contactor 60A 100A 150A 150A
CB3
Static Bypass Input
Contactor 60A 100A 150A 150A
52C AC Output Contactor 60A 100A 150A 150A
FIU,FIV,FIW AC Input Fuse 140A/660V 180A/ 600V
280A/ 660V
280A/ 660V
FBP,FBN Battery Input Fuse 140A/660V 180A/ 600V
280A/ 660V
280A/ 660V
FOU,FOV,FOW AC Output Fuse 140A/660V 180A/ 600V
280A/ 660V
280A/ 660V
F1,F2,F3 UPER-Y/UPFR-K 6.3A/250V 6.3A/
250V
6.3A/ 250V
6.3A/ 250V
F1 CABR-JA 12A/600V
ELECTRIC
2033C SERIES UPS
OWNERS / TECHNICAL MANUAL
2-1
2.0 OPERATOR CONTROLS AND INDICATORS
The 2033C Series operator controls and indicators are located as follows:
Maintenance bypass switch and contactors : Inside the module UPS status indicators : Door exterior
FIGURE 2.1 Operation/Display Panel (Front panel)
2033C SERIES UPS
INV OP. BYP OP.
FAILURE BAT OP.
START STOP SILENCE CLEAR
EPO 1
6 7 8 9 10
MBP
ELECTRIC
2033C SERIES UPS
OWNERS / TECHNICAL MANUAL
2-2
2.1 LED Display and keypad
1) 7 SEGMENT LED DISPLAY (red) The 7 segment LED Indicates the status of the UPS and error codes.
(Refer to failure code list in section 6.)
During normal operation, LED indication is shown in figure 2.2.
FIGURE 2.2 7 segment LED display for normal operation
2) Load on inverter [INV OP.] (green)
Illuminated when power is supplied from inverter to the critical load.
3) Battery operation [BAT OP.] (yellow)
Illuminated when the battery is operating following an AC power failure.
4) Load on bypass [BYP OP.] (yellow)
Illuminated when power is supplied to load devices by static bypass.
5) UPS failure [FAILURE] (red)
Illuminated when UPS is in fault mode.
6) Inverter start [START] (green)
Inverter start button.
When pressed, the load will transfer from the static bypass line to the inverter.
7) Inverter stop [STOP] (gray) Inverter stop button. When pressed, the inverter can be stopped.
The load will transfer from the inverter to the static bypass line.
8) Alarm Silence [SILENCE] (gray) Audible alarm is silenced when this button is pressed.
9) Clear [CLEAR] (gray) Clears errors in UPS system.
10) Emergency Power Off [EPO] (red) Shuts down UPS when pressed. Load is dropped.
11)Load on maintenance bypass [MBP] (red) Illuminated when power is supplied to load devices by maintenance bypass.
ELECTRIC
2033C SERIES UPS
OWNERS / TECHNICAL MANUAL
2-3
2.2 External Signal Terminal Block
The UPS is equipped with a series of input/output terminals for the external annunciation of alarms and the remote access of certain UPS functions. Layout of terminals is shown in Figure 2.3, with a functional description of the input/output port presented:
FIGURE 2.3 External Signal Terminal Block (NEC Class2)
TB
BATTERY TEMP. HIGH (Optional)
- For external battery cabinet.
EMERGENCY STOP (Optional)
SUMMARY ALARM
LOAD ON INVERTER
LOAD ON BYPASS
BATTERY OPERATION
CONVERTER OPERATION
BATTERY LOW VOLTAGE
OVERLOAD
(User supplied dry contact)
(User supplied sensor and dry contact)
UPS
ELECTRIC
2033C SERIES UPS
OWNERS / TECHNICAL MANUAL
2-4
A) Output Contacts (for external alarm annunciation)
Output contacts consist of form “A” dry type contacts. The rated capacity of all output contacts is 120Vac/0.5Aac or 30Vdc/1Adc. All dry contacts must be operated at their rated values or lower. Figure 2.4 illustrates a typical installation. The external relay can also be a lamp, LED, or computer, etc.
FIGURE 2.4 Control Wiring for External Contacts
Terminal
UPS Cabinet External to UPS Cabinet
Relay
Coil
Power Source
Relay Contact Terminal
Details of output alarm contacts :
Terminals 5 to 6 “Summary Alarm” contact Activated when a fault alarm occurs.
Terminals 7 to 8 “Load on Inverter” contact Activated when the power is supplied by the inverter.
Terminals 9 to 10 “Load on Bypass” contact Activated when the power is supplied by the static bypass input.
Terminals 11 to 12 “Battery Operation” contact Activated when the battery is operating following an AC power failure.
Terminals 13 to 14 “Converter Operation” contact Activated when the converter is operating.
Terminals 15 to 16 “Battery Low Voltage” contact Activated when battery voltage drops below discharge end voltage level during inverter operation (i.e. During AC failure conditions).
Terminals 17 to 18 “Overload” contact Activated when a system overload occurs.
User supplied
ELECTRIC
2033C SERIES UPS
OWNERS / TECHNICAL MANUAL
2-5
B) Input Contacts (for remote access of UPS)
External contacts are provided by the user of the UPS system. The terminal voltage at the UPS is 24Vdc. External dry contacts are to be provided accordingly.
WARNING: Do not apply voltages to remote access input terminals.
Damage to UPS may result.
Refer to Figure 2.5 for a typical wiring configuration. Although this figure shows the emergency stop configuration, the same wiring arrangement is used for battery temperature high. See below for terminal connection details.
FIGURE 2.5 Remote "Stop" Contact Connections
1
Relay Coil current : 8.3mA Use Momentary Switches
UPS Cabinet External to UPS Cabinet
Relay
Coil
24 VDC
Emergency Stop
Details of input contacts for remote access :
Terminals 1 to 2 “Emergency Stop” contact input
Used to perform a remote UPS emergency power off (EPO).
The load will be dropped.
Terminals 3 to 4 “Battery Temp. High” contact input Input fed by a thermocouple that monitors battery temperature.
The converter float voltage level is reduced for battery over-temperature conditions. The external thermocouple will be user supplied
NOTE: In all cases, a switch having a protective cover is recommended in order to reduce possibility of accidental operation.
User supplied
ELECTRIC
2033C SERIES UPS
OWNERS / TECHNICAL MANUAL
2-6
2.3 External communication connector
This is an RS232C port for “DiamondLink”* monitoring software. The layout of the connector is shown in Figure 2.6.
FIGURE 2.6 External communication connector (NEC Class2)
Pin 1. : Not used Pin 2. RXD : Receive data Pin 3. TXD : Transmit data Pin 4. DTR : Always high level Pin 5. GND : Signal ground Pin 6. : Not used Pin 7. RTS : Always high level Pin 8. : Not used Pin 9. : Not used
* Consult MITSUBISHI ELECTRIC AUTOMATION, INC. for detail on “Diamond Link” monitoring software and its capabilities.
CN62
D-SUB 9Pin (male)
RYDR-O/ RYDR-X
2033C SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
3-1
3.0 INSTALLATION AND OPERATION
3.1 Transportation and Installation
TABLE 3.1 How to transport and install the system Transportation Installation
Transport unit with forklift. Pull out the UPS cabinet as shown in Figure 3.1 Fix the UPS unit in place using the four (4) leveling feet.
NOTE: Do not transport in a horizontal position. Cabinets should be maintained upright within +/- 15° of the vertical during handling.
3.2 Handling
The UPS is shipped in export packaging. Remove the UPS from the package only when it is ready for installation. Refer to Figure 3.1 for handling.
FIGURE 3.1 Handling
RAMP
Roof of the package during shipping
Leveling feet
2033C SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
3-2
3.3 Installation Procedure
A) Note the load tolerance of the floor Refer to Table 3.2 for list of UPS weights:
TABLE 3.2 List of UPS weights
UPS Capacity (kVA) 7.5 10 15 20 30 40 50
Weight (lb.) 562 562 816 816 1235 1082 1082
NOTE: 40kVA and 50kVA UPS have batteries external to module cabinet.
Please refer to the remote battery supply installation manual.
B) Minimum clearance required for ventilation Right side 1.0" (25 mm) (not required when sidecars are used) Left side 1.0" (25 mm) (not required when sidecars are used) Back side 7.8" (200 mm) Top side 39.4" (1000 mm)
C) Space requirement for routine maintenance Allow for the following space at the time of installation.
Front 39.4" (1000 mm) Sides 1.0" (25 mm) Rear 7.8" (200 mm)
D) Battery Please refer to the following when installing and maintaining batteries:
1. Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries.
2. When installing or replacing batteries, install or replace with the same number and type per Table 3.3
2033C SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
3-3
TABLE 3.3 Type and number of battery
Type Manufacturer Number
7.5kVA, 10kVA PM12-7.2
NP7-12
Power Battery Inc.
Yuasa Corp.
15kVA, 20kVA PM12-18
NP18-12B
Power Battery Inc.
Yuasa Corp.
30kVA PM12-18
NP18-12B
NP18-12BFR
Power Battery Inc.
Yuasa Corp.
Yuasa Corp.
40kVA, 50kVA
NOTE: 40kVA and 50kVA UPS batteries are external to module cabinet.
Please refer to the remote battery supply installation manual.
CAUTION - Do not dispose of battery or batteries in a fire. The battery may explode.
CAUTION - Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin and eyes and may be toxic.
CAUTION - A battery can present a risk of electrical shock and high short circuit current. The following precautions should be observed when working on batteries:
! Remove watches, rings, or other metal objects.
! Use tools with insulated handles.
! Wear rubber gloves and boots.
! Do not lay tools or metal parts on top of batteries.
! Disconnect charging source prior to connecting or disconnecting battery terminals.
3.4 Procedure for Cable Connections (Refer to Table 3.4 for cable sizes.)
I. Confirm the capacity of the UPS being installed. Identify the input/output power terminal blocks as shown in the appropriate Figure 3.2 or Figure 3.3-Figure 3.5.
II. Connect the grounding conductor from the input service entrance to the UPS ground bar.
III. Confirm that an external input circuit breaker sized to protect both the converter input and the bypass lines is installed. Consult equipment nameplate for current ratings. Connect the AC power source cables from the input service entrance to the UPS’ INPUT power
2033C SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
3-4
MITSUBISHI ELECTRIC 2033C SERIES UPS
terminals identified as A, B, C and N in Figure 3.3-Figure 3.5. Input cables must be sized for an ampere rating larger than the maximum current capacity of the UPS.
IV. Refer to Table 3.4 for recommended cable sizes. Referring to Figure 3.3-Figure 3.5, connect UPS’ OUTPUT load terminals A, B, C and N to load distribution panel.
V. Connect external signal terminal block as needed. Refer to section 2.2 and Figure 2.3 for functional description. 12 AWG, or less, shielded conductor is recommended.
NOTES: 1. Confirm that all UPS internal contactors (breakers) "CB1", "CB2", and "CB3" are open before energizing UPS.
2. UPS power terminals are supplied with stud type fittings. It is recommended that compression lugs be used to fasten all input/output power cables. Refer to Table 3.5 for recommended compression lugs and appropriate crimping tool
Table 3.4 Recommended Cable Size and Torque Requirements
UPS Capacity Input Side
* 1
Output Side
* 1
(kVA)
Cable *2 Size
Torque
(in. lbs)
Cable *2 Size
Torque
in. lbs
7.5kVA (208V)
8 AWG
or larger
in. lbs
8 AWG
or larger
in. lbs
10kVA (208V)
8 AWG
or larger
in. lbs
8 AWG
or larger
in. lbs
15kVA (208V)
8 AWG
or larger
in. lbs
8 AWG
or larger
in. lbs
20kVA (208V)
6 AWG
or larger
in. lbs
6 AWG
or larger
in. lbs
30kVA (208V)
2 AWG
or larger
in. lbs
2 AWG
or larger
in. lbs
40kVA (208V)
2/0 AWG
or larger
in. lbs
2/0 AWG
or larger
in. lbs
50kVA (208V)
2/0 AWG
or larger
in. lbs
2/0 AWG
or larger
in. lbs
*1 - Voltage drop across power cables not to exceed 3% of nominal source voltage.
*2 - Allowable ampere ratings based on 90 °C insulation at an ambient temperature of 30 °C. No more than 3 conductors in a raceway without de-rating. Copper conductors assumed.
2033C SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
3-5
TABLE 3.5 Crimp Type Compression Lug
WIRE
SIZE
WIRE
STRAND
RECOMMENDATION CRIMP TOOL REQUIRED
BURNDY TYPE Y35 OR Y46
(CODE) CLASS VENDOR CAT. NO. COLOR KEY DIE INDEX
8 B
BURNDY YA8C-L2 RED 49
6 B
BURNDY YA6C-L3 BLUE 7 / 374
4 B
BURNDY YA4C-L3 GRAY 8 / 346
2 B
BURNDY YA2C-L BROWN 10
2/0 B
BURNDY YA26-L3 BLACK 13
NOTE: When using crimp type lugs, the lugs should be crimped to the specifications given in the manufacturer's instructions for both crimp tool and lug.
Fig.3.2 UPS Terminal Designation
Terminals:
INPUT
A,B,C,N
Terminals:
OUTPUT
A,B,C,N
Output AC input
BATTERY
CB3
Static Transfer Switch
52C CB1 FO FI
CONVERTER INVERTER
UPS Module
CB2
FB
52CS
40kVA, 50kVA:
External Battery
52CS(7.5-20kVA) 52MB&52L(30-50kVA)
2033C SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
3-6
FIGURE 3.3 Input/Output Power Terminals (7.5kvA - 20kVA)
Control printed circuit boards
Fan
Inverter and Converter
52CS
Input/Output Power Terminal Designation
ALL POWER TERMINALS USE 1/4” (6 MM) DIAMETER
BOLTS
A B C N A B C N
(INPUT) (OUTPUT)
Battery Battery
Battery Battery
RYDR-O/RYDR-X
NORMAL
TRANSFER
BYPASS
2033C SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
3-7
FIGURE 3.4 Input/Output Power Terminals (30kVA)
Converter & Inverter Unit
Cooling fan
A B C N A B C N
Battery
Battery
Battery
Battery
RYDR-X
N P
(INPUT) (OUTPUT)
TRANSFER
NORMAL BYPASS
MBS
(DC INPUT)
Control printed circuit boards
Grounding bar AC Input/Output Power Terminal Designation
HOLE DIAMETER: 0.36” (9 MM)
DC Input Power Terminal
HOLE DIAMETER: 0.28” (7 MM)
2033C SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
3-8
FIGURE 3.5 Input/Output Power Terminals (40kvA - 50kVA)
Control printed circuit boards
Converter & Inverter Unit
Cooling fan
A B C N A B C N N P
(AC INPUT) (AC OUTPUT) (DC INPUT)
Grounding bar
MBS
BYPASS
TRANSFER
NORMAL
RYDR-X
Input/Output Power Terminal Designation
HOLE DIAMETER: 0.47” (12 MM)
2033C SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
3-9
3.5 Operating Procedures
A) UPS Start-up Procedure
1. Close External Input Circuit Breaker (User supplied. Refer to warning 2).
2. The “BYP.OP.” illuminates and power is supplied to the critical load from the static bypass line automatically.
3. Within ten (10) seconds, the “INV.OP.” LED flashes and the Inverter starts. The UPS will automatically transfer the load from the static bypass line to the inverter and the “INV.OP.”
light illuminates.
NOTE: If LED Display indicates code “81”, please check position of EPO button. If EPO button is in the ON position, press the button to clear EPO as shown in figure 3.6. Press the “CLEAR” button. If LED Display indicate code “99”, press the “CLEAR” button again.
FIGURE 3.6 EPO button
EPO position Normal position
B) UPS Shutdown Procedure
1. If a total UPS module (inverter and converter) shutdown is required, press the "STOP" button on the front panel. Within 3 seconds the “BYP.OP.” LED will illuminate and the UPS will transfer the load to the static bypass line.
WARNING: Verify the load is OFF if the next step is to be performed .
NOTE: Power to the critical load is supplied through the static bypass line.
Power to the critical load will be lost after execution of the next step.
The load will drop.
2. If turning off all power to the critical load is desired, open the AC Input Circuit Breaker (User supplied.).
2033C SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
3-10
CAUTION : In bypass mode, all UPS power terminals are still live. Lethal voltages are present. De-energize all external sources of AC and DC power before handling UPS.
C) EPO (Emergency Power Off) Procedure
If an all power supply shutdown is required in an emergency situation, press the "EPO" button on the front panel. The UPS will be shutdown and no power is supplied to the load.
WARNING : With EPO operation, although all output power from the UPS is shutdown, it is necessary to manually open the input circuit breaker (user supplied), to remove the input power to the UPS.
3.6 Maintenance bypass set-up procedures
The transfer procedure to place the UPS in maintenance bypass mode, or from bypass mode to normal operation mode is outlined below:
A) Transfer of load from inverter to maintenance bypass
1. On the front panel, press the "STOP" button. The “BYP.OP.” LED illuminates within 3 seconds.
2. After confirming that the “BYP.OP.” LED is illuminated, Rotate the MBS(52CS/SWM) clockwise to the “TRANSFER” position (Do not rotate 52CS/SWM if the “BYP.OP.” LED is NOT illuminated).
3. After 3 seconds, rotate 52CS/SWM clockwise to the “BYPASS” position.
4. Transfer complete. Load is now powered from the external source. UPS can be shutdown.
B) Transfer of load from maintenance bypass to inverter
1. Rotate 52CS/SWM counterclockwise from the “BYPASS” position to the “TRANSFER” position, wait 5 seconds.
2. On the UPS, confirm the “BYP.OP.” LED is illuminated. If not, press the “STOP” button.
3. Rotate 52CS/SWM counterclockwise to the “NORMAL” position.
4. On the UPS, press the “START” button. The “INV.OP.” LED should illuminate.
5. Transfer complete. Load now powered by the inverter.
2033C SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
4-1
4.0 RESPONSE TO UPS FAILURE
Depress “SILENCE” button on the front panel.
Refer to the list of fault codes for a description of the error. See section 6. For fault codes
Take necessary action per the list of fault codes in section 6 of this manual.
When faults occur, contact the Authorized Mitsubishi Service Representative or call Mitsubishi at 1-800-887-7830.
Note The error code indicated on the 7 Segment LED Display at the time of UPS alarm condition is very important. In order to minimize repair time, please include this information along with the operation status and load status, on all correspondence with Mitsubishi’s field service group.
UPS FAULT
Annunciator Silence
Recording of Fault
Primary Action
Information to Service Center
ELECTRIC
2033C SERIES UPS
OWNERS / TECHNICAL MANUAL
5-1
5.0 PARTS REPLACEMENT
Contact Mitsubishi or its Authorized Service Center on all issues regarding the replacement of parts.
A)A)A)A) Battery Battery lifetime may vary according to the frequency of use and the average ambient operating temperature. Battery end of life is defined as the state of charge resulting in an ampere-hour capacity less than, or equal to, 80% of nominal capacity. Replace battery if capacity is within this percentage.
B)B)B)B) UPS Component Parts Contact Mitsubishi or its Authorized Service Center for a complete parts replacement schedule.
Recommended replacement time interval varies with operating environment. Contact Mitsubishi or its Authorized Service Center for specific application recommendations.
2033C SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
6-1
6.0 FAULT CODES
This section covers the fault codes, their description and required action.
At time of error :
A) Verify and record the occurrence of the alarm. Note fault code on the 7-segment LED Display .
Contact Mitsubishi Electric Automation, Inc. at 1-800-887-7830.
B) If the External AC Input Circuit Breaker (MCCB) is in the trip state, depress the toggle to reset the breaker before re-closing.
20033C SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
6-2
Failure Code List Note 1 Note 2 Note 3
7seg. LED Code Status Guidance Buzzer External send-out contact Failure LED
00 Test mode (Pulse check) - [1] - -
01 Maintenance mode - [1] - -
10 Battery circuit abnormal Call service engineer [1] Minor Flicker
11 Battery test - - - -
12 Battery circuit abnormal Call service engineer [1] Minor Flicker
13 Battery depleted warning - [1] Alarm Flicker
14 Battery depleted - [2] Alarm Lit up
15 Battery temperature abnormal Check battery [1] Alarm Flicker
16 Battery temperature abnormal Check battery [1] Minor Flicker
17 Battery charge voltage abnormal Call service engineer [1] Alarm Flicker
18 DC voltage abnormal Call service engineer [1] Minor Flicker
19 Battery depleted (Converter overload) Check AC input voltage [2] Major Lit up
21 AC input voltage out of range Check AC input voltage [1] Alarm -
22 AC input phase rotation error Check AC input voltage [1] Minor Flicker
23 Converter overload Call service engineer [1] Alarm Flicker
24 Converter over current Call service engineer [1] Minor Flicker
25 Converter abnormal (DCOV) Call service engineer [2] Major Lit up
26 Converter abnormal (DCUV) Call service engineer [2] Major Lit up
27 Converter abnormal Call service engineer [2] Major Lit up
28 Converter abnormal at pre-charge Call service engineer [2] Major Lit up
31 Inverter voltage abnormal Call service engineer [1] Minor Flicker
32 Inverter abnormal (VLOV) Call service engineer [2] Major Lit up
33 Inverter abnormal (VLUV) Call service engineer [2] Major Lit up
34 Inverter abnormal (OC) Call service engineer [2] Major Lit up
35 Inverter abnormal Call service engineer [2] Major Lit up
36 52C abnormal Call service engineer [1] Minor Flicker
37 52C abnormal Call service engineer [1] Minor Flicker
41 Bypass voltage out of range Check bypass input - Alarm Flicker
42 Bypass frequency out of range Check bypass input - Alarm Flicker
43 Interrupted transfer - [1] Alarm Flicker
44 Transfer warning - - Alarm -
46 Overload interrupt transfer Press clear button [1] Alarm Flicker
47 Overload interrupt transfer Press clear button [1] Alarm Flicker
51 Synchronous control abnormal Call service engineer [1] Minor Flicker
52 Transfer circuit abnormal Call service engineer [1] Minor Flicker
20033C SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
6-3
Note 1 Note 2 Note 3 7seg. LED Code Status Guidance Buzzer External send-out contact Failure LED
53 Transfer circuit abnormal Call service engineer [1] Minor Flicker
54 Control circuit error Call service engineer [2] Major Lit up
55 Control circuit error Call service engineer [2] Major Lit up
56 Control circuit error Call service engineer [2] Major Lit up
57 Control circuit error Call service engineer [2] Major Lit up
58 Control circuit error Call service engineer [1] Minor Flicker
59 Control circuit error Call service engineer [2] Major Lit up
71 Overload Reduce load [1] Alarm Flicker
72 kW overload Reduce load [1] Alarm Flicker
73 Instantaneous overload Reduce load [1] Alarm Flicker
74 Load abnormal Check load [1] Alarm Flicker
76 Overload Reduce load [1] Alarm Flicker
81 Emergency stop activated - [1] Alarm Flicker
82 Fin temperature abnormal Call service engineer [2] Major Lit up
96 Control circuit error Call service engineer [2] Major Lit up
97 Restart after battery depleted - - Alarm -
98 Control circuit error Call service engineer [2] Major Lit up
99 Start up Press Clear button - Alarm -
ELECTRIC
2033C SERIES UPS
OWNERS / TECHNICAL MANUAL
6-4
(Note 1)
Audible annunciator: [1] intermittent sound, [2] continuous sound.
(Note 2)
• "Major" is defined as a major failure. Load transferred from inverter to the static bypass line;
• "Minor" is defined as a minor failure. UPS continues to operate normally, but cause of alarm must be identified;
• “Over" is defined as an overload condition. Load will transfer from inverter to the static bypass line and may or may not return to the inverter. Return to inverter will occur only if overload corrects itself and output load is within rating of UPS. (Note: Inverter may need to be restarted manually subsequent to an output bolted fault.)
(Note 3)
Indicates one of two possible LED illumination patterns - continuously on (lit) or intermittent (flicker).