Attachment 6 - Drawings V5 of 5 - 56-24-115 - N Chicago Elevator Upgrades.pdf

PDF 5 MB Posted

Attached to
J035--Elevator Upgrade NRM Construction Project 556-24-115 James A. Lovell Federal Health Care Center, North Chicago, IL 60064
Solicitation number
36C77626R0048
Issued by

About this file

This document is a comprehensive mechanical design drawing set for an elevator upgrade project at the VA Lovell Federal Medical Center in North Chicago, Illinois. The project involves demolition and addition work to air, plumbing, and hydronic systems across multiple buildings (B04, B07, B66, B131, B133/133CA, and B195) at the facility.

The mechanical scope includes installation of split-system air conditioning units, unit heaters, fan coil units, sump pumps, and refrigerant piping in elevator machine rooms and related spaces. Contractor requirements mandate compliance with ANSI/ASHRAE/ASHE Standard 170 for air quality and pressurization, adherence to the facility's Infectious Control Risk Assessment (ICRA) requirements, and maintenance of existing air quality and utility requirements during construction. Key specifications require temporary air supply systems with minimum 90% efficiency (MERV 14) filters, proper air and water balance verification before and after work, fire protection sprinkler extensions per NFPA 13, and control of refrigerant and condensate drain piping to avoid routing above elevator equipment. Equipment schedules specify manufacturers including Daikin (split systems), Indeeco (unit heaters), Stancor (sump pumps), and Titus (diffusers/grilles). The project demands coordination across multiple mechanical, electrical, and plumbing contractors, with detailed schedules for equipment installation, insulation specifications, and pipe support requirements. All work must maintain continuous building operations with coordinated shutdowns scheduled minimum 14 days in advance and fire watch provisions where required.

View the file

Other files

File Type Posted
36C77626R0048 0005.docx DOCX document
FAR 52.222-90 - Addressing DEI Discrimination by Federal Contractors - APR 2026.docx DOCX document
RFI Responses - Elevator Upgrade N Chicago.pdf PDF
36C77626R0048 0004.docx DOCX document
36C77626R0048 0003.docx DOCX document
36C77626R0048 0002.docx DOCX document
Attachment 2 - Elevator Site Visit Sign In - 556-24-115.pdf PDF
Attachment 1 - Site Visit Agenda - 556-24-115.pdf PDF
Site Visit Instructions Rev 03272026.pdf PDF
36C77626R0048 0001.docx DOCX document
Attachment 3 - Drawings V2 of 5 - 56-24-115 - N Chicago Elevator Upgrades.pdf PDF
Attachment 9 - PCRA - 556-24-115.pdf PDF
Attachment 4 - Drawings V3 of 5 - 56-24-115 - N Chicago Elevator Upgrades.pdf PDF
Attachment 5 - Drawings V4 of 5 - 56-24-115 - N Chicago Elevator Upgrades.pdf PDF
36C77626R0048_1.docx DOCX document
Attachment 13 - Site Visit Instructions - 556-24-115.docx DOCX document
Attachment 7 - Statement of Work - 556-24-115.docx DOCX document
Attachment 10 - DBA WD IL20260009 01092026.pdf PDF
Attachment 12 - RFI Tracking Sheet - 36C77626R0048.docx DOCX document
Attachment 2 - Drawings V1 of 5 - 56-24-115 - N Chicago Elevator Upgrades.pdf PDF
Attachment 1 - Specifications - 556-24-115 - N Chicago Elevator Upgrades.pdf PDF
Attachment 8 - ICRA Combined Docs - 556-24-115.pdf PDF
Attachment 11 - Limitations on Subcontracting.docx DOCX document
Show all 23

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CONTRACTOR REQUIREMENTS FOR THE

DEMOLITION OF, OR ADDITION TO, ANY PORTION

OF AIR, PLUMBING OR HYDRONIC SYSTEMS.

COVER SHEET NOTES:

THE FOLLOWING SHALL APPLY TO ALL MECHANICAL SYSTEMS AFFECTED BY CONSTRUCTION ACTIVITIES. SYSTEMS INCLUDED BUT ARE NOT LIMITED TO HVAC, EXHAUST, EQUIPMENT, DUCTWORK, DUCTWORK ACCESSORIES, HYDRONICS, COILS, FILTERS, PLUMBING, TEMPERATURE CONTROLS, LIFE

SAFETY CONTROLS AND PRESSURIZATION CONTROLS.

1. AIR QUALITY, QUANTITY AND PRESSURE RELATIONSHIPS SHALL COMPLY WITH THE LATEST, ANSI/ASHRAE/ASHE STANDARD 170

REQUIREMENTS.

2. COMPLY WITH THE FACILITY'S INFECTIOUS CONTROL RISK ASSESSMENT (ICRA) REQUIREMENTS.

3. MAINTAIN EXISTING AIR QUALITY REQUIREMENTS, AIR PRESSURIZATION AND OTHER UTILITY REQUIREMENTS FOR OCCUPIED AREAS

DURING ANY RENOVATION OR CONSTRUCTION.

4. DETERMINE AND VERIFY THE AREAS SERVED BY THE AFFECTED SYSTEMS.

5. TAKE AIR AND OR/ WATER BALANCE READINGS OF THE SYSTEMS BEING AFFECTED.

6. IF THERE ARE SPACES BEING SERVED OUTSIDE OF THE DEMOLITION OR ADDITION AREA, THE FOLLOWING PROCEDURES MUST BE TAKEN:

a. TAKE AIR AND/OR WATER BALANCE READINGS AS NEEDED TO QUANTIFY THE AIR AND/OR WATER FLOWS DELIVERED TO THE

SYSTEMS OUTSIDE THE AFFECTED AREA.

b. DURING DEMOLITION, TAKE ALL NECESSARY MEASURES TO MAINTAIN THE CORRECT AIR AND/OR WATER FLOWS TO THE SYSTEMS

THAT ARE REMAINING.

c. AFTER THE COMPLETION OF DEMOLITION, VERIFY THAT AIR AND/OR WATER FLOWS ARE CORRECT.

d. AFTER COMPLETING ANY ADDITIONS TO THE SYSTEM, VERIFY THAT AIR AND/OR WATER FLOWS ARE CORRECT.

7. THE CONTRACTOR IS TO PROVIDE TEMPORARY AIR/AND OR WATER SYSTEMS AS NEEDED TO MAINTAIN PROPER TEMPERATURE AND

PRESSURE RELATIONSHIPS OF SPACES REQUIRED TO BE OCCUPIED DURING CONSTRUCTION.

8. ALL TEMPORARY AIR SUPPLY SYSTEMS MUST UTILIZE FINAL FILTERS THAT ARE A MINIMUM OF 90% EFFICIENT (MERV 14). FINAL FILTERS

MUST BE DOWNSTREAM OF ALL AIR SUPPLY COMPONENTS.

ABBREVIATION

GENERAL ABBREVIATIONS

DESCRIPTION ABBREVIATION DESCRIPTION

NOT ALL ABBREVIATIONS APPLY TO THIS SET OF DOCUMENTS

AD ACCESS DOOR/PANEL

AFF ABOVE FINISHED FLOOR

AMB AMBIENT

DIA DIAMETER

DN DOWN

E EXISTING

EC ELECTRICAL CONTRACTOR

EFF EFFICIENCY

GC GENERAL CONTRACTOR

FPM FEET PER MINUTE

FPS FEET PER SECOND

L LENGTH

LF LINEAR FEET

MAX MAXIMUM

MC MECHANICAL CONTRACTOR

MFR MANUFACTURER

MIN MINIMUM

NIC NOT IN CONTRACT

NTS NOT TO SCALE

PC PLUMBING CONTRACTOR

PSIG POUNDS PER SQUARE INCH GAUGE

RPM REVOLUTIONS PER MINUTE

SHT SHEET

TOB TOP OF BEAM

GPM GALLONS PER MINUTE

TOS TOP OF STEEL

BOB BOTTOM OF BEAM

VEL VELOCITY

VFD VARIABLE FREQUENCY DRIVE

UNION

Y STRAINER WITH BLOWDOWN

ELBOW UP

ELBOW DOWN

TEE UP

PIPING

- SOLID LINE INDICATES SYSTEM SUPPLY

-- DASHED LINE INDICATES SYSTEM RETURN

NUMBER INDICATES NOMINAL DIAMETER IN INCHES,

LETTER(S) INDICATES SYSTEM.

REFER TO ABBREVIATIONS FOR SYSTEM TYPE.

GENERAL MECHANICAL SYMBOLS

SYMBOL DESCRIPTION ADDITIONAL REMARKS

# SHEET NOTE

DENOTES SPECIFIC REQUIREMENT FOR THE SHEET ON WHICH THE NOTE APPEARS

AND IS USED TO DESCRIBE WORK THAT IS TOO LENGTHY TO PLACE ON PLAN.

DIAMETER

DENOTES CONNECTION OF NEW WORK TO

EXISTING SYSTEM

PROTECT EXISTING SYSTEM FROM ENTRANCE OF FOREIGN DEBRIS DURING WORK.

ARROW INDICATES DOWNWARD PIPE SLOPE

#/# INDICATES SLOPE IN INCHES PER FOOT

WHERE PIPING IS NOT MARKED, REFER TO SPECIFICATIONS FOR REQUIREMENTS

ARROW INDICATES DIRECTION OF FLOW IN PIPING

ISOLATION VALVE REFER TO SPECIFICATIONS FOR TYPE BASED ON SIZE AND SYSTEM

CHECK VALVE

ARROW INDICATES DIRECTION OF NORMAL FLOW

REFER TO SPECIFICATIONS FOR TYPE BASED ON SIZE AND SYSTEM

PIPE IN SLEEVE REFER TO SPECIFICATIONS FOR TYPE BASED ON SIZE AND SYSTEM

CIRCUIT SETTER, AUTOFLOW, ETC.

REFER TO SPECIFICATIONS FOR TYPE BASED ON SIZE AND SYSTEM

REFER TO SPECIFICATIONS FOR TYPE AND ACCESSORIES

TEE DOWN

TEE HORIZONTAL

PIPE REDUCER

INDICATES POINT WHERE PIPING CHANGES FROM ONE SIZE TO ANOTHER.

SMALL POINT OF ARROW INDICATES SMALLER SIZE SIDE OF TRANSITION.

REQUIRED SERVICE CLEARANCE FOR EQUIPMENT

CONTINUATION

FIRST SYMBOL APPLIES TO ROUND DUCT AND PIPING.

SECOND SYMBOL APPLIES TO RECTANGULAR AND OVAL DUCT.

PLUMBING SYMBOLS

SYMBOL DESCRIPTION ADDITIONAL REMARKS

AIR VENT

AUTOMATIC FLOW CONTROL VALVE

# INDICATES FLOW TO BE BALANCED IN GPM

VALVE - SHUTOFF SERVICE

P/T PORT

PIPE CAP

PIPE CONTINUATION

Y STRAINER

CC CONTROLS CONTRACTOR

PIPING

- SINGLE DASH INDICATES DOMESTIC COLD WATER

- DOUBLE DASH INDICATES DOMESTIC HOT WATER

- TRIPLE DASH INDICATES HOT WATER

CIRCULATING

- SOLID INDICATES SANITARY ABOVE FLOOR

- CONTINUOUS DASHED INDICATES VENT

- LONG DASHED LINES INDICATE SANITARY BELOW

FLOOR

NUMBER INDICATES NOMINAL DIAMETER IN INCHES,

LETTER(S) INDICATES SYSTEM.

REFER TO ABBREVIATIONS FOR SYSTEM TYPE.

C.O.

C.O.

ROOF DRAIN

TAG INDICATES DRAIN SIZE IN INCHES AND AREA

OF ROOF DRAINED IN SQUARE FEET

REFER TO PLUMBING FIXTURE SCHEDULE FOR TYPE.

#"RD

# SF

WALL DISCHARGE (DOWNSPOUT NOZZLE)

TAG INDICATES DRAIN SIZE IN INCHES AND AREA

OF ROOF DRAINED IN SQUARE FEET

REFER TO PLUMBING FIXTURE SCHEDULE FOR TYPE.

#"DSN

# SF

FD-# FLOOR DRAIN REFER TO PLUMBING FIXTURE SCHEDULE FOR TYPE.

CLEANOUT

CIRCLE INDICATES UP TO FLOOR OR WALL CLEANOUT.

LINE INDICATES END OF PIPE CLEANOUT LOCATED ABOVE A CEILING.

DOUBLE GRADE CLEANOUT REFER TO DETAILS FOR ADDITIONAL REQUIREMENTS.

ABBREVIATION

PLUMBING ABBREVIATIONS

DESCRIPTION

CHEMICAL VENTCV

CHEMICAL WASTECW

BOTTLE/GLASS FILLERBF

ABBREVIATION DESCRIPTION

DOMESTIC HOT WATERDHW

DOMESTIC HOT WATER CIRCULATIONDHWC

LAVATORYL

NOT ALL ABBREVIATIONS APPLY TO THIS SET OF DOCUMENTS

BACK FLOW PREVENTERBFP

BATH TUBBT

COMPRESSED AIR (NON-MEDICAL)CA

PROPANELPG

LEAVING WATER TEMPERATURELWT

BTU (1000'S)MBH

CONDENSATE DRAINCD

CLEANOUTCO

CONDENSATE PUMPCP

MOP SINKMS

NORMALLY CLOSEDNC

NORMALLY OPENNO

CLINICAL SINKCS

DOMESTIC COLD WATERDCW

DRINKING FOUNTAINDF

NON-POTABLE WATERNPW

POST INDICATOR VALVEPIV

PRESSURE REDUCING VALVEPRVDOUBLE GRADE CLEANOUTDGCO

DEIONIZED WATERDI

DEIONIZED WATER CIRCULATINGDIC

ROOF DRAINRD

REVERSE OSMOSIS WATERRO

DEIONIZED HOT WATERDIH

RPZ

S

REDUCED PRESSURE ZONE (BACK FLOW PREVENTER)

SINK

DEIONIZED HOT WATER CIRCULATINGDIHC

DISTILLED WATERDIS

DISTILLED WATER CIRCULATINGDISC

SANITARY SEWERSAN

DOMESTIC SOFT COLD WATERSCW

DOMESTIC SOFT HOT WATERSHW

DIALYSIS WATER RETURNDR

DIALYSIS WATER SUPPLYDS

DRAIN TILEDT

DOMESTIC SOFT HOT WATER CIRCULATINGSHWC

SEWAGE EJECTORSE

SHOWERSH

EMERGENCY EYE WASHEEW

EMERGENCY SHOWERES

EMERGENCY SHOWER AND EYE WASH COMBOESEW

STORM OVERFLOWSO

SUMP PUMPSP

SERVICE SINKSS

EXPANSION TANKET

ELECTRIC WATER COOLEREWC

ENTERING WATER TEMPERATUREEWT

STORM SEWERST

TEMPERATURETEMP

URINALUR

FILTERF

FLOOR CLEANOUTFCO

FLOOR DRAINFD

VENTV

VENT THROUGH ROOFVTR

FLOOR SINKFS

WB

WC

WALL BOX

WATER CLOSET

NATURAL GASG

WALL CLEANOUTWCO

GRADE CLEANOUTGCO

HUB DRAINHD

WATER HEATERWH

WATER SOFTENERWS

HORSEPOWERHP

WPD

YCO

WATER PRESSURE DROP

YARD CLEANOUTGREASE VENTGV

HOSE BIBHB

GREASE WASTEGW

DOWN SPOUT NOZZLEDSN

SYMBOL

FIRE PROTECTION SYMBOLS

DESCRIPTION ADDITIONAL REMARKS

FLOW SWITCH COORDINATE INTERFACE WITH FIRE ALARM SYSTEM CONTRACTOR

FIRE DEPARTMENT CONNECTION MOUNT BETWEEN 18" AND 48" ABOVE FINISHED GRADE

REFER TO SPECIFICATIONS FOR TYPES AND FINISHES.

PENDANT REFERS TO FULL, SEMI-RECESSED AND RECESSED TYPES. LOCATIONS

FOR EACH ARE INDICATED IN THE SPECIFICATIONS OR ON THE PLANS.

SIDEWALL SPRINKLER -

EXISTING SIDEWALL SPRINKLER

SPRINKLER

EXISTING SPRINKLER

EXISTING SPRINKLER TO BE REMOVED

FIRE PIPEF

O.S. & Y. VALVE

SHUT-OFF VALVE WITH TAMPER SWITCHTS

F

ABBREVIATION

FIRE PROTECTION ABBREVIATIONS

DESCRIPTION

BACK FLOW PREVENTERBFP

FIRE PROTECTIONF

FIRE DEPARTMENT CONNECTIONFDC

ABBREVIATION DESCRIPTION

FLOW SWITCHFS

POST INDICATOR VALVEPIV

SPRINKLERSPR

NOT ALL ABBREVIATIONS APPLY TO THIS SET OF DOCUMENTS

RECTANGULAR DUCTWORK

W = DIMENSION IN VIEW (INCHES)

H = DIMENSION PERPENDICULAR TO VIEW (INCHES)

ROUND DUCTWORK

D = DUCT DIAMETER

TURNING VANES

WxH

D"Ø

HVAC SYMBOLS

SYMBOL DESCRIPTION ADDITIONAL REMARKS

W/H

FLAT OVAL DUCTWORK

W = DIMENSION IN VIEW (INCHES)

H = DIMENSION PERPENDICULAR TO VIEW (INCHES)

REFER TO DUCT CONSTRUCTION SCHEDULE AND SPECIFICATIONS FOR ADDITIONAL

INFORMATION AND REQUIREMENTS.

REFER TO DUCT CONSTRUCTION SCHEDULE AND SPECIFICATIONS FOR ADDITIONAL

INFORMATION AND REQUIREMENTS.

REFER TO DUCT CONSTRUCTION SCHEDULE AND SPECIFICATIONS FOR ADDITIONAL

INFORMATION AND REQUIREMENTS.

REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION AND REQUIREMENTS.

DUCT CROSS SECTION - SUPPLY

DUCT CROSS SECTION - RETURN

DUCT CROSS SECTION - EXHAUST

CROSS SECTION INDICATES DUCT EXTENDING PERPENDICULAR TO THE PAGE. IN

PLAN VIEW THIS INDICATES A DUCT RISE OR DROP TO ANOTHER LEVEL. SOLID

INTERIOR LINE INDICATES EXTENSION UP. DASHED INTERIOR LINE INDICATES

EXTENSION DOWN.

MANUAL BALANCE DAMPER

REFER TO SPECIFICATIONS FOR TYPE. LOCATE MANUAL BALANCE DAMPERS IN AN

ACCESSIBLE LOCATION AND AS CLOSE TO THE MAIN DUCT AS POSSIBLE.

CONTROL DAMPER

FIRE/SMOKE DAMPER

REFER TO SPECIFICATIONS FOR TYPE. LOCATE DAMPERS IN AN ACCESSIBLE

LOCATION AND PROVIDE ACCESS DOORS/PANELS IN DUCT AND CEILING/WALL.

D#

DIFFUSER TAG

D = TYPE # = TYPE NUMBER

### = AIRFLOW IN CFM

REFER TO DIFFUSER SCHEDULE FOR TYPE DESCRIPTIONS AND SIZING. BALANCE TO

AIRFLOW LISTED. WHEN TYPE IS NOT GIVEN AND ONLY CFM IS DESIGNATED, PROVIDE

D1 FOR SUPPLY OR G1 FOR RETURN/EXHAUST.

FLOW ARROW ARROW INDICATES DIRECTION OF AIRFLOW FROM DIFFUSERS WITH ADJUSTABLE

THROWS.

WALL REGISTER / GRILLE

SMOKE DAMPER

REFER TO SPECIFICATIONS FOR TYPE. LOCATE DAMPERS IN AN ACCESSIBLE

LOCATION AND PROVIDE ACCESS DOORS/PANELS IN DUCT AND CEILING/WALL.

ABBREVIATION

HVAC ABBREVIATIONS

DESCRIPTION

NOT ALL ABBREVIATIONS APPLY TO THIS SET OF DOCUMENTS

CONDENSATE DRAINCD

CONDENSING UNITCU

DIRECT EXPANSIONDX

PRESSURE/TEMPERATURE TEST PORT

TEMPERATURE CONTROL SYMBOLS

SYMBOL DESCRIPTION ADDITIONAL REMARKS

WALL MOUNTED CONTROL DEVICE

# INDICATES TYPE

REFER TO MOUNTING HEIGHTS DETAIL FOR MOUNTING ELEVATION.

T = THERMOSTAT H = HUMIDISTAT S = SENSOR (CARBON MONOXIDE, ETC.)

OCCUPANCY SENSOR

REFER TO ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION. WHEN SENSOR IS

NOT SHOWN ON ELECTRICAL DRAWINGS IT SHALL BE PROVIDED AND INSTALLED BY

THE TEMPERATURE CONTROLS CONTRACTOR.

DUCT, PIPE, OR CEILING MOUNTED CONTROL

SENSOR

REFER TO SPECIFICATIONS FOR TYPE. REFER TO SEQUENCES AND SCHEMATICS FOR

ADDITIONAL INFORMATION AND REQUIREMENTS.

T = THERMOSTAT H = HUMIDISTAT S = SENSOR (CARBON DIOXIDE, ETC.)

CONTROL VALVE (3-WAY)

CONTROL VALVE (2-WAY)

REFER TO SPECIFICATIONS FOR TYPE. REFER TO SEQUENCES AND SCHEMATICS FOR

ADDITIONAL INFORMATION AND REQUIREMENTS.

F/S FLOW MEASURING STATION REFER TO SPECIFICATIONS FOR TYPE. REFER TO SEQUENCES AND SCHEMATICS FOR

ADDITIONAL INFORMATION AND REQUIREMENTS.

FIRE DAMPER

REFER TO SPECIFICATIONS FOR TYPE. LOCATE DAMPERS IN AN ACCESSIBLE

LOCATION AND PROVIDE ACCESS DOORS/PANELS IN DUCT AND CEILING/WALL.

CD

FD

SD

FS

DAMPER SHALL BE SAME SIZE AS DUCT UNLESS NOTED OTHERWISE. REFER TO

SEQUENCES, SCHEMATICS AND SPECIFICATIONS FOR ADDITIONAL INFORMATION AND

REQUIREMENTS.

REFER TO SPECIFICATIONS FOR TYPE. REFER TO SEQUENCES AND SCHEMATICS FOR

ADDITIONAL INFORMATION AND REQUIREMENTS.

FLOW SWITCHF

ABBREVIATION DESCRIPTION

PUMPP

REFRIGERANT DX LIQUIDREFL

REFRIGERANT DX SUCTION GASREFS

WET BULB TEMPERATUREWB

WATER COLUMNWC

MECHANICAL GENERAL NOTES:

A. THESE NOTES APPLY TO ALL SHEETS CONTAINING HVAC, PIPING, PLUMBING, TEMPERATURE CONTROLS, AND FIRE PROTECTION WORK. REFER TO PROJECT SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. WHERE A DISCREPANCY EXISTS BETWEEN THESE PLANS AND THE PROJECT SPECIFICATIONS, THE SPECIFICATION REQUIREMENTS SHALL TAKE PRECEDENCE OVER THE DRAWINGS.

B. VERIFY THE EXISTING CONDITIONS AT THE PROJECT SITE BEFORE SUBMITTING COST PROPOSAL. BE ADVISED THAT LOCATIONS SHOWN ARE APPROXIMATE. AN ATTEMPT HAS BEEN MADE TO SHOW ALL PIPING, FIXTURES, DUCTWORK, AND OUTLETS. CONTRACTOR SHALL VISIT THE SITE TO VERIFY COMPONENTS, LOCATIONS AND SIZES SHOWN OR NOT SHOWN. ALL COMPONENTS NEED TO BE REMOVED IN THE DEMOLITION AREA UNLESS NOTED ON THE DRAWINGS. IF DEVIATION BETWEEN EXISTING CONDITIONS AND NEW WORK IS FOUND, CONTRACTOR SHALL NOTIFY

ENGINEER.

C. IT IS MANDATORY THAT THE EXISTING BUILDING REMAIN IN CONTINUOUS AND NON-INTERRUPTED OPERATION DURING THE CONSTRUCTION OF THE ADDITIONS AND REMODELING/ALTERATION OF THE EXISTING BUILDING. SERVICES TO THE EXISTING BUILDING SHALL BE KEPT ON CONTINUOUS OPERATION EXCEPT DURING SCHEDULED SHUTDOWNS FOR EXTENSION OR MODIFICATION. PLAN TO COMPLETE SHUTDOWNS DURING OFF HOURS TO MINIMIZE IMPACT TO THE OWNER. COORDINATE SHUTDOWNS WITH THE OWNER A MINIMUM OF 14 DAYS PRIOR TO WORK. PROVIDE TEMPORARY SERVICES WHERE NECESSARY TO ACCOMPLISH ANY SHUTDOWN. THIS INCLUDES BUT IS NOT LIMITED TO STAFFING AND EQUIPMENT FOR FIRE WATCHES, PROVISIONS FOR BOTTLED WATER, AND TEMPORARY HEATING OR COOLING EQUIPMENT.

TEMPORARY MEASURES SHALL NOT BE REMOVED UNTIL THE PERMANENT SYSTEMS ARE OPERATIONAL AND HAVE PASSED ALL REQUIRED

TESTING.

D. CONTRACTOR SHALL BE RESPONSIBLE FOR THEIR OWN DEMOLITION, REMOVAL, CAPPING, STORING, ABANDONING, DISCONNECTING, RELOCATING AND RECONNECTION OF EXISTING EQUIPMENT AND MATERIAL. ALL CUTTING, PATCHING, REPAIRING, REPLACEMENT AND

REFINISHING SHALL MATCH THE EXISTING CONSTRUCTION AS NEARLY AS POSSIBLE.

E. EXCEPT WHERE OTHERWISE SHOWN OR NOTED ON THE DRAWINGS AS "TO BE RETAINED, RELOCATED", ALL EXISTING EQUIPMENT AND MATERIAL IN AREAS TO BE REMODELED/ALTERED SHALL BE REMOVED WHERE THEY INTERFERE WITH PROPOSED NEW CONSTRUCTION AND/OR

WITH PROPOSED USAGE OF SPACE BY OWNER AS FOLLOWS:

a. REMOVE ANY PIPING PROTRUDING ABOVE FINISHED FLOOR OR THROUGH WALL AND CAP WITHIN 3 PIPE DIAMETERS OF NEAREST ACTIVE

MAIN WITH MATERIAL TO MATCH EXISTING.

b. REMOVE ALL FIXTURES, CARRIERS, SUPPLY AND WASTE AND VENT PIPING, STEAM, HEATING HOT WATER, HVAC SUPPLY, RETURN AND EXHAUST AS NOTED. CAP WITHIN 3 PIPE DIAMETERS OF NEAREST ACTIVE MAIN. SUPPLY AND RETURN MAINS ON PIPING SYSTEMS

CONVEYING WATER OR GASES SHALL BE VALVED AND CAPPED

c. IN REMODELED/ALTERED AREAS, ANY PIPING OR DUCTWORK PASSING THROUGH THE REMODELED AREAS TO SERVE (OR BEING SERVED FROM EXISTING ADJACENT, REMOTE, OR SURROUNDING AREAS THAT ARE TO REMAIN) SHALL BE RETAINED AND KEPT OPERATIONAL AND SHALL BE REROUTED IN ALL CASES WHERE THEY INTERFERE WITH ANY NEW WORK OR USAGE TO BE ACCOMPLISHED IN THE

REMODELED AREA.

d. REMOVE UNUSED OR ABANDONED HANGERS AND PATCH ABANDONED PENETRATIONS TO MATCH EXISTING.

e. PENETRATIONS THROUGH EXISTING WALLS AND FLOORS FORMERLY OCCUPIED BY REMOVED PIPING OR DUCTWORK SHALL BE PATCHED

TO MATCH EXISTING CONSTRUCTION.

f. RE-SUPPORT ANY PIPING AND DUCTWORK THAT WAS SUPPORTED FROM BUILDING ELEMENTS REMOVED AS PART OF THE WORK.

g. MAINTAIN CONTROL WIRING OR PNEUMATIC TUBING REQUIRED FOR THE CONTINUED PROPER OPERATION OF THE BUILDING

AUTOMATION SYSTEM.

F. ALL EXISTING EQUIPMENT BEING REMOVED WILL BE HANDED OVER TO OWNER FOR FIRST RIGHT OF SALVAGE. IF OWNER REFUSES SALVAGE

ITEMS, REMOVING CONTRACTOR SHALL BE RESPONSIBLE FOR DISPOSAL.

G. CONTRACTOR SHALL REFER TO THE DRAWINGS OF ALL TRADES TO FAMILIARIZE THEMSELVES WITH EXTENT OF WORK INCLUDING BUT NOT

LIMITED TO WHERE NEW PARTITIONING IS BEING INSTALLED, WHERE EXISTING PARTITIONING IS BEING REMOVED, WHERE CEILINGS ARE BEING

REMOVED AND/OR REPLACED, ETC.

H. THESE DRAWINGS ARE NECESSARILY DIAGRAMMATIC IN NATURE. NOT ALL FITTINGS, OFFSETS, VENTS OR DRAINS ARE SHOWN. THE CONTRACTOR SHALL INCLUDE ALL FITTINGS, OFFSETS, VENTS, DRAINS, AND DEVICES REQUIRED TO PROVIDE A COMPLETE AND FUNCTIONING

SYSTEM.

I. PROVIDE ACCESS DOORS IN DUCTWORK AND/OR ARCHITECTURAL ELEMENTS WHERE REQUIRED TO ACCESS ALL EQUIPMENT REQUIRING MAINTENANCE AND ADJUSTMENT. THIS EQUIPMENT INCLUDES BUT IS NOT LIMITED TO SENSORS, DAMPERS, ACTUATORS, CONTROL DEVICES, VALVES, ETC. ACCESS DOORS SHALL BE SIZED TO PROVIDE APPROPRIATE ACCESS BASED ON HEIGHT OF ACCESS REQUIRED AND ACTIVITY.

INSTALL SUCH THAT ACCESS DOOR IS FULLY OPERABLE WITHOUT THE REMOVAL OF ARCHITECTURAL ELEMENTS SUCH AS CEILING RUNNERS, SUPPORTS, ETC. INSTALL IN A LOCATION SUCH THAT STEPPING OR LEANING OVER PERMANENT EQUIPMENT OR FURNITURE IS NOT REQUIRED.

WHERE ACCESS DOORS ARE REQUIRED IN ARCHITECTURAL ELEMENTS THAT PROVIDE A FIRE AND/OR SMOKE RATING, ACCESS DOOR SHALL

MAINTAIN THE REQUIRED RATING.

J. SEAL ALL WALL PENETRATIONS (DUCTWORK, PIPING, CONTROLS, CONDUITS, ETC.) WITH NON-COMBUSTIBLE MATERIAL. SEAL PENETRATIONS INTO ROOMS THAT REQUIRE PRESSURE CONTROL OR SOUND ISOLATION. WITH NON-COMBUSTIBLE MATERIAL AND CAULK.

K. PIPING AND DUCTWORK SHALL NOT BE ROUTED OVER ELECTRICAL AND TELECOM ROOMS. WHERE ROUTING OVER SUCH ROOMS IS UNAVOIDABLE, CONTRACTOR SHALL COORDINATE WITH OWNER, DESIGN TEAM, AHJ, AND OTHER TRADES REGARDING LOCATION OF PANELS AND UTILITY ROUTING AND SHALL PROVIDE DRIP PANS UNDER ALL UTILITIES WITH MOISTURE SENSORS OR DRAIN PIPING AS REQUIRED BY THE

SPECIFICATIONS.

L. REMOVAL AND REINSTALLATION OF CEILINGS REQUIRED FOR THE COMPLETION OF WORK IS THE RESPONSIBILITY OF THE CONTRACTOR.

CONTRACTOR SHALL REPAIR OR REPLACE ALL DAMAGED CEILING COMPONENTS TO MATCH EXISTING. WHERE AN IDENTICAL MATCH IS NO LONGER AVAILABLE, CONTRACTOR SHALL PROVIDE A SIMILAR REPLACEMENT UPON APPROVAL FROM THE OWNER.

M. SUPPORT ALL DUCTWORK, PIPING AND EQUIPMENT FROM BUILDING STRUCTURE MEMBERS. ROUTE DUCT MAINS TIGHT TO STRUCTURE UNLESS NOTED OTHERWISE. HOLD PIPING TIGHT TO BOTTOM OF STRUCTURAL MEMBERS OR RUN THROUGH JOIST WEBS IF POSSIBLE. DO NOT USE WIRE OR PERFORATED METAL TO SUPPORT PIPING. DO NOT SUPPORT PIPING FROM OTHER PIPING, DUCTWORK, AND/OR ELECTRICAL CONDUITS. DO NOT SUPPORT FROM WOOD TONGUE AND GROOVE ROOF DECK. SUPPORT FROM BOTTOM CHORD OF BAR JOISTS ONLY AT PANEL POINTS. ALL COMPONENTS REQUIRING MAINTENANCE SHALL BE SUPPORTED IN SUCH A MANNER AS TO BE READILY ACCESSIBLE WITHOUT REMOVAL OF THE CEILING SYSTEM AND TO ALLOW FOR REMOVAL FROM THE SYSTEM WHEN SUCH REMOVAL IS REQUIRED FOR

MAINTENANCE.

N. PROVIDE CONSTRUCTION FILTERS ON AIR MOVING EQUIPMENT SERVING THE CONSTRUCTION AREA AS WELL AS ALL RETURN/EXHAUST DUCT PENETRATIONS COMING FROM THE CONSTRUCTION AREA. AT THE COMPLETION OF WORK, REMOVE ALL TEMPORARY AND CONSTRUCTION

FILTERS AND PROVIDE NEW FILTERS FOR ALL AIR MOVING EQUIPMENT.

O. AT THE COMPLETION OF WORK, CLEAN ALL STRAINERS PROVIDED AS A PART OF THE WORK AS WELL AS PRIMARY SYSTEM STRAINERS LOCATED AT PUMPS WHERE SYSTEMS WERE EXTENDED. ON EXISTING EQUIPMENT, COORDINATE WORK WITH OWNER.

P. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL PIPING, EQUIPMENT AND DUCTWORK

INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.

Q. REFER TO SCHEDULES FOR SIZES OF FINAL RUNOUTS TO EQUIPMENT, FIXTURES, DIFFUSERS, GRILLES, AND TERMINAL DEVICES. FINAL RUNOUT SIZES LISTED SHALL BE USED TO WITHIN 10 EQUIVALENT DIAMETERS OF FINAL CONNECTION POINT. FINAL PIPING CONNECTION TO EQUIPMENT SHALL MATCH EQUIPMENT CONNECTION SIZE, PROVIDE TRANSITIONS AS REQUIRED. REFER TO DETAILS, DIAGRAMS AND SCHEMATICS FOR

ADDITIONAL FINAL CONNECTION REQUIREMENTS.

R. FOR ALL PIPING, CONDUIT, AND OTHER ITEMS PENETRATING A FIRE RATED WALL, PROVIDE U.L. LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL CONSTRUCTION ASSEMBLY AND COMPLIANT WITH ASTM E814. INSTALL SYSTEM IN STRICT COMPLIANCE WITH THE FIRE STOPPING MANUFACTURER'S U.L. APPROVED DETAIL. WHERE EXISTING WALLS ARE BEING UPGRADED TO FIRE RATED WALLS OR THE FIRE RATING IS BEING MODIFIED, PROVIDE U.L. LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM FOR ALL NEW AND EXISTING PENETRATIONS. REFER TO THE ARCHITECTURAL LIFE SAFETY PLANS FOR LOCATIONS OF FIRE RATED WALLS.

FIRE PROTECTION GENERAL NOTES:

A. FIRE PROTECTION WORK SHALL INCLUDE, BUT NOT LIMITED TO, THE FOLLOWING: EXTEND FIRE PROTECTION SPRINKLER PIPING WITH NEW SPRINKLER HEADS INTO ELEVATOR SHAFT AND ELEVATOR EQUIPMENT ROOM PER NFPA 13 REQUIREMENTS.

B. ALL AREAS OF THE BUILDING INDICATED SHALL BE SPRINKLERED ACCORDING TO THE CURRENTLY ADOPTED EDITION OF NFPA STANDARD 13 AND OTHER NFPA STANDARDS AS REQUIRED. ENTIRE SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF THE STATE FIRE MARSHAL OFFICE, OWNER'S INSURANCE COMPANY AND AUTHORITIES HAVING JURISDICTION.

C. FIRE SPRINKLER DESIGN SHALL BE BASED ON HYDRAULIC CALCULATIONS ACCORDING NFPA 13, WITH SHOP DRAWINGS PREPARED ACCORDING TO THE REQUIREMENTS OF THE STATE FIRE MARSHAL AND AUTHORITIES HAVING JURISDICTION.

D. SPRINKLER CONTRACTOR SHALL OBTAIN STATIC AND RESIDUAL WATER PRESSURE AND FLOW PRIOR TO SYSTEM DESIGN AND SHALL SUBMIT

RECENT HYDRANT FLOW TEST DATA WITH SHOP DRAWING SUBMITTALS.

E. DRAWINGS ARE SCHEMATIC IN NATURE, INTENDED TO CONVEY THE SCOPE OF WORK AND GENERAL ARRANGEMENT OF THE SYSTEM.

SPRINKLER SYSTEM INSTALLING CONTRACTOR SHALL COORDINATE SYSTEM ARRANGEMENT WITH ARCHITECTURAL, STRUCTURAL, MECHANICAL AND ELECTRICAL COMPONENTS. SPRINKLER PIPING SHALL NOT BE INSTALLED BELOW MECHANICAL EQUIPMENT OR WITHIN CLEARANCE SPACES FOR MECHANICAL EQUIPMENT. PROVIDE SPRINKLER PROTECTION BELOW ALL DUCTS GREATER THAN 48 INCHES IN WIDTH. INSTALLING CONTRACTOR SHALL BE RESPONSIBLE FOR ANY MODIFICATIONS TO THE SYSTEM REQUIRED TO AVOID CONFLICTS.

F. COORDINATE PIPING AND SPRINKLERS IN EXPOSED AREAS TO MINIMIZE APPEARANCE. INSTALL SPRINKLERS A MINIMUM OF SIX INCHES FROM DIFFUSERS, GRILLES AND LIGHT FIXTURES. INSTALL SPRINKLERS IN LAY-IN CEILINGS WITHIN THREE INCHES OF THE CENTER OF CEILING TILE.

G. COORDINATE INSTALLATION OF SPRINKLERS AND PIPING SYSTEMS TO AVOID FREEZING CONDITIONS. NOTIFY ENGINEER OF AREAS FOR WHERE SYSTEM MAY BE EXPOSED TO FREEZING. INSTALL DRY SIDEWALL SPRINKLERS IN ROOMS INDICATED WHERE ROOMS MAY BE UNCONDITIONED

OR EXPOSED TO FREEZING CONDITIONS. PROVIDE AUXILIARY DRAINS WHERE REQUIRED.

H. EXPOSED SPRINKLER PIPING, EXCEPT IN MECHANICAL AND STORAGE ROOMS, SHALL BE CLEANED, PRIMED AND PREPARED FOR PAINTING.

I. AVOID ROUTING SPRINKLER PIPING ABOVE ELECTRICAL, DATA, IT AND COMMUNICATION PANELS.

10360 Ellison Circle Omaha, NE 68134 Phone:

402.991.5520

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :

DESIGNER OF RECORDCONSULTANT

1221 N. Pennsylvania St.

Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com

GD Project: 23.1019.05 10/03/2025

100% CONSTRUCTION DOCUMENTS 10/03/2025

/3

/2

:1

:0

P

M

A u to d e s k D o c s /2

.0

V A

L o v e ll E le v a to r

U p g ra d e /5

-5

.B u ild in g

.E

R

.r v t

M000

MECHANICAL SYMBOLS AND ABBREVIATIONS Elevator Upgrade

3001 GREEN BAY RD, NORTH CHICAGO, IL 60064

556-24-115

B04

09/12/2025 JMM LJT

23022.012

B04, 07,66, 131, 133/133CA, 195

Revisions: Date:

B04-M400

10360 Ellison Circle Omaha, NE 68134 Phone:

402.991.5520

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :

DESIGNER OF RECORDCONSULTANT

1221 N. Pennsylvania St.

Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com

GD Project: 23.1019.05

E

A CB

D FE

G IH

KEYPLAN

10/03/2025

100% CONSTRUCTION DOCUMENTS 10/03/2025

/3

/2

:1

:0

P

M

A u to d e s k D o c s /2

.0

V A

L o v e ll E le v a to r

U p g ra d e /5

-5

.B u ild in g

.E

R

.r v t

B04-MD102

PENTHOUSE

PLAN-OVERALL-MECHANICAL-DEMOLITION

Elevator Upgrade

3001 GREEN BAY RD, NORTH CHICAGO, IL 60064

556-24-115

B04

09/12/2025 JMM LJT

23022.012

N

5 5 10 15 20 25 30 35 40 45

1/16" = 1'-0"

FEETSCALE

GENERAL NOTES:

1. MECHANICAL SYMBOLS AND ABBREVIATIONS SHEET GENERAL NOTES APPLY TO ALL SHEETS.

2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR DASHED, EXISTING MECHANICAL

SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE

WEIGHTS.

3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL PIPING, EQUIPMENT AND DUCTWORK

INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.

4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO PERFORM THIS WORK.

5. COORDINATE ROUTING OF REFRIGERANT AND CONDENSATE DRAIN PIPING TO NOT RUN ABOVE ELEVATOR EQUIPMENT AND ELEVATOR

CONTROLS.

1/16" = 1'-0"

PENTHOUSE PLAN - OVERALL - MECHANICAL - DEMOLITION

STAIR 4

ST4

Room

Room

Room

Room

Room

Room

Room

Room

STAIR 5

ST5

Room

JANITOR

Room

STAIR 1

ST1

WOMEN'S RESTROOM

OFFICE

OFFICE

CONFERENCE ROOM

OFFICE

OFFICE

OFFICE

CONFERENCE ROOM

STORAGE

TMS LAB

OFFICE

163D

OFFICE

163C

OFFICE

163B

OFFICE

163A

STORAGE

166A

COMP RM

ELECTRICAL RM

OFFICE

OFFICE

OFFICE

OFFICE

MEN'S RESTROOM

JANITOR

WOMEN'S RESTROOM

VIRTUAL RECREATION SPACE

Room

209XXXX

SUPPORT RM

139A

DEBBRIEFING

OFFICE

STORAGE

DENTAL LAB

DEBBRIEFING

SKILLS LAB

OR/SURGICAL SIM

MILITARY SIM

CONTROL ROOM

EMT SIM

SHOWER

119A

SHOWER

118A

FEMALE LOCKER RM

Room

MALE LOCKER RM

STAIR 2

ST2

ER SIM

DEPARTMENT HEAD

SIMULATION MANAGER

STAFF SUPPORT

ICU/MED SURGE

COAT RM

CONTROL ROOM

Room

Room

209IIIIIII

ELECTRICAL RM

SERVER RM

STORAGE

116A

Room

114B

EQUIPMENT STORAGE

JANITOR

STORAGE

MEN'S RESTROOM

WOMEN'S RESTROOM

RESOURCE OFFICE

CLASSROOM

MAIN ENTRY

Room

RECEPTION

LOW FIDELITY SKILLS LAB

COFFEE SHOP

CLASSROOM

138B

CLASSROOM

138A

HALLWAY

C106

HALLWAY

C104

HALLWAY

C105

CORRIDOR

C103 Room

114A

CORRIDOR

C102

VENDING RM

SEATING AREA

Room

BREAK-OUT RM

104B

BREAK-OUT RM

104A

CORRIDOR

C100

CAFE SEATING

RESOURCE RM

COPY ROOM

WORK RM

CORRIDOR

C111

CORRIDOR

C110

CORRIDOR-1

C101-1

CORRIDOR-2

C101-2

CORRIDOR

C108

BREAK ROOM

CORRIDOR

C107

THEATER MEZZ

105A

THEATER

MEN'S RESTROOM

B04-M400

2"

B04-M400

10360 Ellison Circle Omaha, NE 68134 Phone:

402.991.5520

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :

DESIGNER OF RECORDCONSULTANT

1221 N. Pennsylvania St.

Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com

GD Project: 23.1019.05

E

A CB

D FE

G IH

KEYPLAN

10/03/2025

100% CONSTRUCTION DOCUMENTS 10/03/2025

/3

/2

:1

:0

P

M

A u to d e s k D o c s /2

.0

V A

L o v e ll E le v a to r

U p g ra d e /5

-5

.B u ild in g

.E

R

.r v t

B04-M100

FIRST LEVEL FLOOR

PLAN-OVERALL-MECHANICAL

Elevator Upgrade

3001 GREEN BAY RD, NORTH CHICAGO, IL 60064

556-24-115

B04

09/12/2025 JMM LJT

23022.012

1/16" = 1'-0"

FIRST LEVEL FLOOR PLAN - OVERALL - MECHANICAL

N

5 5 10 15 20 25 30 35 40 45

1/16" = 1'-0"

FEETSCALE

GENERAL NOTES:

1. MECHANICAL SYMBOLS AND ABBREVIATIONS SHEET GENERAL NOTES APPLY TO ALL SHEETS.

2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR DASHED, EXISTING MECHANICAL

SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE

WEIGHTS.

3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL PIPING, EQUIPMENT AND DUCTWORK

INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.

4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO PERFORM THIS WORK.

5. COORDINATE ROUTING OF SUMP PUMP DISCHARGE PIPING TO NOT RUN ABOVE ELEVATOR EQUIPMENT AND ELEVATOR CONTROLS.

T

B04-M400

SS-04-CU

10360 Ellison Circle Omaha, NE 68134 Phone:

402.991.5520

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :

DESIGNER OF RECORDCONSULTANT

1221 N. Pennsylvania St.

Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com

GD Project: 23.1019.05

E

A CB

D FE

G IH

KEYPLAN

10/03/2025

100% CONSTRUCTION DOCUMENTS 10/03/2025

/3

/2

:1

:0

P

M

A u to d e s k D o c s /2

.0

V A

L o v e ll E le v a to r

U p g ra d e /5

-5

.B u ild in g

.E

R

.r v t

B04-M102

PENTHOUSE PLAN-OVERALL-MECHANICAL Elevator Upgrade

3001 GREEN BAY RD, NORTH CHICAGO, IL 60064

556-24-115

B04

09/12/2025 JMM LJT

23022.012

1/16" = 1'-0"

PENTHOUSE PLAN - OVERALL - MECHANICAL

N

5 5 10 15 20 25 30 35 40 45

1/16" = 1'-0"

FEETSCALE

GENERAL NOTES:

1. MECHANICAL SYMBOLS AND ABBREVIATIONS SHEET GENERAL NOTES APPLY TO ALL SHEETS.

2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR DASHED, EXISTING MECHANICAL

SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE

WEIGHTS.

3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL PIPING, EQUIPMENT AND DUCTWORK

INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.

4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO PERFORM THIS WORK.

5. COORDINATE ROUTING OF REFRIGERANT AND CONDENSATE DRAIN PIPING TO NOT RUN ABOVE ELEVATOR EQUIPMENT AND ELEVATOR

CONTROLS.

SHEET NOTES:

1. MAINTAIN MANUFACTURERS RECOMMENDED CLEARANCES FOR CONDENSING UNIT.

SP-04-300

SS-04-300

REFL

REFS

UH-04-300

ST DN

ST UP

3/4" CD

SS-04-CU

(E)RD

ST UP

ST DN

(E)RD

MSFD

2" V UP

4" SAN

2" V

2"

10360 Ellison Circle Omaha, NE 68134 Phone:

402.991.5520

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :

DESIGNER OF RECORDCONSULTANT

1221 N. Pennsylvania St.

Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com

GD Project: 23.1019.05

E

A CB

D FE

G IH

KEYPLAN

10/03/2025

100% CONSTRUCTION DOCUMENTS 10/03/2025

/3

/2

:1

:0

P

M

A u to d e s k D o c s /2

.0

V A

L o v e ll E le v a to r

U p g ra d e /5

-5

.B u ild in g

.E

R

.r v t

B04-M400

ENLARGED FLOOR PLANS-MECHANICAL Elevator Upgrade

3001 GREEN BAY RD, NORTH CHICAGO, IL 60064

556-24-115

B04

09/12/2025 JMM LJT

23022.012

1/4" = 1'-0"

B04 ENLARGED ROOM 1-EL-P23 - MECHANICAL

SHEET NOTES:

1. REMOVE DECOMMISSIONED UNIT HEATER.

2. DEMOLISH EXISTING GRILLE AND ASSOCIATED DUCTWORK BACK TO MAIN AND CAP. FILL EXISTING DUCTWORK PENETRATION TO MAINTAIN

FLOOR RATING.

3. SEAL AROUND STORM PIPE PENETRATION THROUGH FLOOR TO MAINTAIN RATING.

4. PROVIDE REFRIGERANT PIPING SIZED AND INSTALLED PRE MANUFACTURER'S RECOMMENDATIONS.

5. ROUTE CONDENSATE DRAIN DISCHARGE WITHIN 5'-0" OF NEARBY ROOF DRAIN.

6. EXTEND FIRE PROTECTION SPRINKLER PIPING FROM EXISTING SYSTEM TO ELEVATOR MACHINE ROOM. PROVIDE FULL SPRINKLER COVERAGE

PER NFPA 13 REQUIREMENTS.

7. PROVIDE OIL MINDER CONTROL PANEL AND CONNECT TO ELEVATOR SUMP PUMP. COORDINATE EXACT LOCATION WITH OWNER AND AHJ.

8. INSTALL SUMP PUMP ON EXISTING PIT FLOOR. THERE SHALL BE A MINIMUM OF 24" CLEARANCE BETWEEN BOTTOM OF ELEVATOR CAR AND

TOP OF PUMP WHEN ELEVATOR CAR IS FULLY RESTED ON BUMPERS. IF CLEARANCE IS NOT MAINTAINED, PROVIDE REDUCED CLEARANCE

IDENTIFICATION IN ACCORDANCE WITH ASME 17.1.

9. EXTEND FIRE PROTECTION SPRINKLER PIPING FROM EXISTING SYSTEM TO ELEVATOR HOISTWAY. INSTALL SIDEWALL SPRINKLERS AT BOTTOM OF HOISTWAY NO MORE THAN 24" ABOVE FLOOR THAT PROVIDE FULL COVERAGE OF PIT FLOOR. REFER TO DETAIL 4/B04-M400 FOR

FURTHER REQUIREMENTS.

10. EXISTING UNDERFLOOR PIPING IS SHOWN FOR REFERENCE ONLY. CONTRACTOR SHALL SCOPE EXISTING SANITARY SYSTEM WITHIN ROOM PRIOR TO CUTTING FLOOR. PROVIDE 8"ØX36" STANDPIPE OFF THE EXISTING 4" SANITARY LINE AND TERMINATE SUMP PUMP DISCHARGE IN

STANDPIPE WITH AIR GAP.

1/4" = 1'-0"

B04 ENLARGED ROOM 300 - MECHANICAL

1/4" = 1'-0"

B04 ENLARGED ROOM 300 - MECHANICAL DEMOLITION

N 2 2 4 6 8 10

1/4" = 1'-0"

FEETSCALE

GENERAL NOTES:

1. MECHANICAL SYMBOLS AND ABBREVIATIONS SHEET GENERAL NOTES APPLY TO ALL SHEETS.

2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR DASHED, EXISTING MECHANICAL

SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE

WEIGHTS.

3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL PIPING, EQUIPMENT AND DUCTWORK

INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.

4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO PERFORM THIS WORK.

5. COORDINATE ROUTING OF REFRIGERANT AND CONDENSATE DRAIN PIPING TO NOT RUN ABOVE ELEVATOR EQUIPMENT AND ELEVATOR

CONTROLS.

1/4" = 1'-0"

B04 ENLARGED ROOM 1-JAN-174 - MECHANICAL

ABBREVIATIONS: MF = MINERAL FIBER/FIBERGLASS, E = ELASTOMERIC, CG = CELLULAR GLASS

REMARKS:

1. PLATE NUMBER REFERENCED ARE PROVIDED TO CLARIFY THE SCOPE OF INSTALLATION. INSTALL INSULATION AND ACCESSORY COMPONENTS PER APPLICABLE MICA AND MANUFACTURERS RECOMMENDATIONS.

2. MICA REFERENCE PLATES FOR PIPING ARE 1-100 FOR FIBERGLASS AND CELLULAR GLASS PIPE INSULATION, 1-200 FOR ELASTOMERIC AND 1-900 FIBERGLASS WITH HEAT TRACE.

REMARKS:

1. IF NO CC IN CONTRACT, MC TO WIRE CONTROLS AND EC TO PIPE CONDUIT.

2. ALL LOW VOLTAGE WIRING OF PANELS TO BE COVERED IN MC BID, WIRING CONTRACTOR TO BE SUBCONTRACTOR TO MC.

3. INSTALLING CONTRACTOR IS RESPONSIBLE FOR FIELD ALIGNMENT SERVICES WHEN REQUIRED BY COMMON MOTOR REQUIREMENTS

SPECIFICATION OR BY INDIVIDUAL EQUIPMENT SPECIFICATIONS.

4. ALL HARDWARE, SOFTWARE, EQUIPMENT, ACCESSORIES, WIRING (POWER AND SENSOR), PIPING, RELAYS, SENSORS, POWER

SUPPLIES, TRANSFORMERS, AND INSTRUMENTATION REQUIRED FOR A COMPLETE AND OPERATIONAL DDC SYSTEM, BUT NOT SHOWN

ON THE ELECTRICAL DRAWINGS, ARE THE RESPONSIBILITY OF THE CC.

CONDENSING UNIT

FAN GUARD

REFRIGERANT

GAUGE

CONNECTION

REFRIGERANT

SUCTION LINE

CONDUIT - POWER

AND CONTROL

REFRIGERANT LIQUID LINE

FILTER-DRYER AND SIGHT

GLASS INSTALLED PER

MANUFACTURER SPEC

CONDENSER

COIL

CURB RAILS

FLOOR

STRUT CLAMP HANGERS VERTICAL PIPE SUPPORTCLEVIS HANGER ROLLER SUPPORTTRAPEZE HANGER

OVERSIZE HANGER TO

ALLOW LONGITUDINAL

PIPE EXPANSION AND

PIPE INSULATION TO

PASS THROUGH

UNBROKEN (TYP)

STEEL PIPE

SADDLE, TACK

WELDED TO PIPE,

FILL SADDLE

WITH INSULATION

INSULATION AND

NEOPRENE MOUNTS

RISER CLAMP

INSULATION

LUG, COUPLING, OR HUB

THREADED ROD

CLEVIS HANGER

INSULATION

HIGH DENSITY

INSULATION

INSERT

INSULATION SHIELD

INSULATION

PIPE INSULATION (TYP)

THREADED ROD (TYP)

HIGH DENSITY INSULATION INSERT

UNI-STRUT OR

EQUIVALENT

INSULATION SHIELD (TYP)

INSTALL CLAMP ON ALL

PIPES LESS THAN 4"Ø

F

SPR

2' -0

FLOW SWITCH

CORRIDOR

ELEV

SHAFT

FIRE SPRINKLER

PIPING ROUTED TO

MAINTAIN ELEVATOR

CLEARANCES

REFER TO PLANS FOR

ROUTING DISCHARGE PIPE

SHUTOFF VALVE

CHECK VALVE

UNION

FLANGED COUPLING OR UNION

PUMP

ON/OFF INTEGRAL OR

PIGGY-BACK FLOAT SWITCH

ALARM WHEN WATER LEVEL

IS 3" BELOW INVERT OF

LOWEST INLET

OIL SENSOR

CONTROL PANEL WITH HIGH

WATER AND OIL PRESENT

ALARMS

NOTES:

1. INSTALL CONTROL PANEL PER MANUFACTURER INSTRUCTIONS. COMPONENTS

AND WIRING ARRANGEMENT MAY DIFFER FROM THAT SHOWN.

EXISTING ELEVATOR PIT FLOOR

THE DISTANCE FROM ROOF

SURFACE TO THE BOTTOM

OF THE EQUIPMENT

MOUNTED ON THE CURB

MUST BE A MINIMUM OF 18 IN

INSULATION

CONFIL & STONEPITCH

GALVANIZED STEEL FLASHING

WOOD NAILER

EQUIPMENT

CHANNEL

VIBRATION ISOLATORS

REFER TO SCHEDULE

LAG SCREW ISOLATOR

INTO WOOD NAILER

SEAL PENETRATIONS

BUILT-IN RAISED CANT

10360 Ellison Circle Omaha, NE 68134 Phone:

402.991.5520

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :

DESIGNER OF RECORDCONSULTANT

1221 N. Pennsylvania St.

Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com

GD Project: 23.1019.05 10/03/2025

100% CONSTRUCTION DOCUMENTS 10/03/2025

/3

/2

:1

:0

P

M

A u to d e s k D o c s /2

.0

V A

L o v e ll E le v a to r

U p g ra d e /5

-5

.B u ild in g

.E

R

.r v t

B04-M500

MECHANICAL SCHEDULES AND DETAILS Elevator Upgrade

3001 GREEN BAY RD, NORTH CHICAGO, IL 60064

556-24-115

B04

09/12/2025 JMM LJT

23022.012

NO SCALE

AIR-COOLED CONDENSING UNIT - ROOF MOUNTED

NO SCALE

PIPE SUPPORT - TYPICAL FOR ALL PIPING

NO SCALE

ELEVATOR SPRINKLER

NO SCALE

ELEVATOR SUMP PUMP

NO SCALE

EQUIPMENT MOUNTING RAILS

SPLIT SYSTEM SCHEDULE

MARK SERVES

NOMINAL

CAPACITY

[TONS]

TOTAL

COOLING

CAPACITY

[MBH]

SENSIBLE

COOLING

CAPACITY

[MBH]

INDOOR UNIT OUTDOOR UNIT

OPERATING

WEIGHT

[LBS]

ELECTRICAL DATA

MANUFACTURER REMARKS

DIMENSIONS [IN] EAT

(DB / WB)

[°F]

AIRFLOW

[CFM] MODEL

DIMENSIONS [IN] SUMMER

AMBIENT AIR

[°F]

WINTER AMBIENT

AIR

[°F] MODEL VOLTAGE PHASE DISCONNECT BY

SCCR

(REMARK 4)LENGTH WIDTH HEIGHT LENGTH WIDTH HEIGHT

SS-04-300 ROOM 300 2 22.4 16.4 40" 11" 12" 80/67 750 FTKF24 - 31 208 V 1 MANUFACTURER 0 DAIKIN (2)(3)

SS-04-CU SS-04-300 2 22.4 16.4 80/67 - 37" 16" 27 1/2" 95 -4 RKF24 101 208 V 1 MANUFACTURER 0 DAIKIN (1)(2)(3)

UNIT HEATER SCHEDULE

MARK

MAX SIZE

CAPACITY

[MBH]

AIRFLOW

[CFM]

ELECTRIC HEAT

MANUFACTURER MODEL REMARKSLENGTH WIDTH HEIGHT VOLTAGE PHASE DISCONNECT BY

SCCR

(REMARK 3)

UH-04-300 8" 17" 24" 34.1 650 208 V 3 MANUFACTURER 0 INDEECO UHIR (1)(2)(3)

PUMP SCHEDULE

MARK

FLOW

[GPM]

TOTAL

HEAD

[FT]

SHUT-OFF

HEAD

[FT]

DIMENSIONS

(LxWxH) [IN.]

TYPE OF

FLUID

DISCHARGE

SIZE

[IN]

ELECTRICAL DATA

MANUFACTURER MODEL REMARKSVOLTAGE PHASE DISCONNECT BY

SCCR

(REMARK 3)

SP-04-300 50 20 33 9x6x16.2 WATER 2" 120 V 1 MANUFACTURER 0 STANCOR SV-50 (1)(2)(3)

HVAC PIPING INSULATION SCHEDULE

PIPING SYSTEM FLUID

TEMP.

RANGE DEG.

F.

THICKNESS IN INCHES FOR PIPE SIZES THROUGH SIZE LISTED

TYPE

JACKET

TYPE

MICA PLATE

NUMBER (1) REMARKS<1 1 - 1.25 1.5 - 3 4 - 6 >/= 8

REFRIGERANT ANY 0.5 1 1 1 NA E 1-200 (5)

INDOOR CONDENSATE AND EQUIPMENT DRAINS BELOW 60 0.5 0.5 0.5 0.5 0.5 MF, E ASJ-SSL 1-100, 1-200 (6)

COORDINATION OF WORK SCHEDULE

ITEM SUPPLIER INSTALLER POWER CONTROL (4)

EQUIPMENT MOUNTED ELECTRICAL COMPONENTS MC MC EC CC

LOOSE MOUNTED ELECTRICAL COMPONENTS EC EC EC CC

CONTROL RELAYS, TRANSFORMERS, POWER MC EC EC (4) CC

TEMPERATURE CONTROL SENSORS MC MC CC CC

ELECTRIC HEATERS MC MC EC EC

DX CONDENSING UNITS AND CONDENSERS MC MC EC CC (1)

REMARKS:

1. PROVIDE CURB RAILS AND ROOF SUPPORTS FOR OUTDOOR UNIT.

2. PROVIDE THE FOLLOWING ACCESSORIES: HAIL GUARDS, EC MOTOR ON INDOOR UNIT, LOW AMBIENT KIT, THERMOSTAT, AND WIND BAFFLES.

3. PROVIDE WITH SINGLE POINT POWER CONNECTION SO INDOOR UNIT IS POWERED BY OUTDOOR UNIT.

4. "SCCR" - VALUE INDICATED IS AVAILABLE SHORT CIRCUIT CURRENT (SCC) IN KILOAMPS AT THE EQUIPMENT BASED ON PRELIMINARY DESIGN PHASE CALCULATIONS. EQUIPMENT SCCR SHALL BE MINIMUM 120% OF THE AVAILABLE SCC. RATING SHALL BE ADJUSTED IF REQUIRED BASED ON FINAL SCC CALCULATION. EQUIPMENT INDICATED WITH 5 KA MAY BE PROVIDED WITH 5 KA SCCR. REVIEW SCCR WITH ELECTRICAL CONTRACTOR

PRIOR TO ORDERING EQUIPMENT.

REMARKS:

1. PROVIDE WITH 2-STAGE CONTROL, BUILT-IN THERMOTAT, AND DISCONNECT.

2. MAINTAIN REQUIRED CLEARANCES IN ACCORDANCE WITH MANUFACTURER RECOMMENDATIONS AND NEC REQUIREMENTS. DO NOT INSTALL NEAR HEAT DETECTORS.

3. "SCCR" - VALUE INDICATED IS AVAILABLE SHORT CIRCUIT CURRENT (SCC) IN KILOAMPS AT THE EQUIPMENT BASED ON PRELIMINARY DESIGN PHASE CALCULATIONS. EQUIPMENT SCCR SHALL BE MINIMUM 120% OF THE AVAILABLE SCC.

RATING SHALL BE ADJUSTED IF REQUIRED BASED ON FINAL SCC CALCULATION. EQUIPMENT INDICATED WITH 5 KA MAY BE PROVIDED WITH 5 KA SCCR. REVIEW SCCR WITH ELECTRICAL CONTRACTOR PRIOR TO ORDERING EQUIPMENT.

REMARKS:

1. PERFORMANCE BASED ON FLUID AND CONDITIONS INDICATED IN THIS SCHEDULE.

2. PROVIDE WITH THE FOLLOWING ACCESSORIES: CHECK VALVE, UNION AND AUTOMATIC FLOAT CONTROL.

3. "SCCR" - VALUE INDICATED IS AVAILABLE SHORT CIRCUIT CURRENT (SCC) IN KILOAMPS AT THE EQUIPMENT BASED ON PRELIMINARY DESIGN PHASE CALCULATIONS. EQUIPMENT SCCR SHALL BE MINIMUM 120% OF THE AVAILABLE SCC. RATING

SHALL BE ADJUSTED IF REQUIRED BASED ON FINAL SCC CALCULATION. EQUIPMENT INDICATED WITH 5 KA MAY BE PROVIDED WITH 5 KA SCCR. REVIEW SCCR WITH ELECTRICAL CONTRACTOR PRIOR TO ORDERING EQUIPMENT.

B07-M400

(E)FD

FIRE ALARM PANEL

ELEVATOR

P-22

SPRINKLER ROOM

CORRIDOR

CO-B-01A

STAIR

STORAGE

CORRIDOR

CO-B-01

LAUNDRY

STORAGE

STORAGE

STORAGE

HEAT DUCT SHAFT

CORRIDOR

CO-B-18

STORAGE

STORAGE

CORRIDOR

CO-B-17

CORRIDOR

CO-B-18A

STORAGE

009A

TLT

CORRIDOR

CO-B-09

STORAGE

TLT

STORAGE

STORAGE

STORAGE

10360 Ellison Circle Omaha, NE 68134 Phone:

402.991.5520

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :

DESIGNER OF RECORDCONSULTANT100% CONSTRUCTION DOCUMENTS 10/03/2025

1221 N. Pennsylvania St.

Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com

GD Project: 23.1019.05

E

A CB

D FE

G IH

KEYPLAN

100% CONSTRUCTION

DOCUMENTS

10/03/2025

/3

/2

:2

:0

P

M

A u to d e s k D o c s /2

.0

V A

L o v e ll E le v a to r

U p g ra d e /5

-5

.B u ild in g

.E

R

.r v t

B07-MD100

BASEMENT LEVEL FLOOR PLAN - OVERALL -

MECHANICAL DEMOLITION

Elevator Upgrade

3001 N GREEN BAY RD, NORTH CHICAGO, IL 60064

556-24-115

B07

10/03/2025 JMM LJT

23022.012

1. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.

2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR DASHED, EXISTING MECHANICAL

SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE

WEIGHTS.

3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL PIPING, EQUIPMENT AND DUCTWORK

INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.

4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO PERFORM THIS WORK.

GENERAL NOTES:

3/32" = 1'-0"

BASEMENT LEVEL FLOOR PLAN - OVERALL - MECHANICAL - DEMOLITION

5 5 10 15 20 25 30

3/32" = 1'-0"

FEETSCALE

N

LAUNDRY

CORRIDOR

CO-B-18

HEAT DUCT SHAFT

STORAGE

STO

014A

STO

012A

STORAGE

STORAGE

TLT

STORAGE

TLT

STAIR

STORAGE

STORAGE

STORAGE

CORRIDOR

CO-B-01

STORAGE

009A

CORRIDOR

CO-B-09

FIRE ALARM PANEL

CORRIDOR

CO-B-01A

ELEVATOR

P-22

STORAGE

SPRINKLER ROOM

STORAGE

CORRIDOR

CO-B-18A

CORRIDOR

CO-B-17

STORAGE

B07-M400

SS-07-CU

10360 Ellison Circle Omaha, NE 68134 Phone:

402.991.5520

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :

DESIGNER OF RECORDCONSULTANT100% CONSTRUCTION DOCUMENTS 10/03/2025

1221 N. Pennsylvania St.

Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com

GD Project: 23.1019.05

E

A CB

D FE

G IH

KEYPLAN

100% CONSTRUCTION

DOCUMENTS

10/03/2025

/3

/2

:2

:0

P

M

A u to d e s k D o c s /2

.0

V A

L o v e ll E le v a to r

U p g ra d e /5

-5

.B u ild in g

.E

R

.r v t

B07-M100

BASEMENT LEVEL FLOOR PLAN - OVERALL -

MECHANICAL

Elevator Upgrade

3001 N GREEN BAY RD, NORTH CHICAGO, IL 60064

556-24-115

B07

10/03/2025 JMM LJT

23022.012

3/32" = 1'-0"

BASEMENT LEVEL FLOOR PLAN - OVERALL - MECHANICAL

5 5 10 15 20 25 30

3/32" = 1'-0"

FEETSCALE

N

1. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.

2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR DASHED, EXISTING MECHANICAL

SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE

WEIGHTS.

3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL PIPING, EQUIPMENT AND DUCTWORK

INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.

4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO PERFORM THIS WORK.

GENERAL NOTES:

SHEET NOTES:

1. LOCATE CONDENSING UNIT OUTSIDE ON GRADE AND PROVIDE A CONCRETE PAD FOR MOUNTING.

2. PROVIDE CONTROL PANEL WITHIN MECHANICAL ROOM AND CONNECT TO ELEVATOR SUMP PUMP. COORDINATE EXACT LOCATION WITH OWNER

AND AHJ.

B07-M400

MACHINE ROOM

CO-2-05

10360 Ellison Circle Omaha, NE 68134 Phone:

402.991.5520

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :

DESIGNER OF RECORDCONSULTANT100% CONSTRUCTION DOCUMENTS 10/03/2025

1221 N. Pennsylvania St.

Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com

GD Project: 23.1019.05

E

A CB

D FE

G IH

KEYPLAN

100% CONSTRUCTION

DOCUMENTS

10/03/2025

/3

/2

:2

:0

P

M

A u to d e s k D o c s /2

.0

V A

L o v e ll E le v a to r

U p g ra d e /5

-5

.B u ild in g

.E

R

.r v t

B07-M103

PENTHOUSE LEVEL FLOOR PLAN - OVERALL -

MECHANICAL

Elevator Upgrade

3001 N GREEN BAY RD, NORTH CHICAGO, IL 60064

556-24-115

B07

10/03/2025 JMM LJT

23022.012

3/32" = 1'-0"

PENTHOUSE PLAN - OVERALL - MECHANICAL

5 5 10 15 20 25 30

3/32" = 1'-0"

FEETSCALE

N

1. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.

2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR DASHED, EXISTING MECHANICAL

SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE

WEIGHTS.

3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL PIPING, EQUIPMENT AND DUCTWORK

INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.

4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO PERFORM THIS WORK.

GENERAL NOTES:

ELEVATOR

P-22

SP-07-P22

REFS UP

REFL UP

2"

4" SAN UP/DN

(E)MS

V UP

2" V

FIRE ALARM PANEL

SS-07-302

UH-07-302

3/4" CD

REFL DN

REFS DN

MACHINE ROOM

CO-2-05

ELEVATOR

P-22

1 (E)SP

4" SAN UP/DN

1 1/2"

FIRE ALARM PANEL

(E)AC

MACHINE ROOM

CO-2-05

10360 Ellison Circle Omaha, NE 68134 Phone:

402.991.5520

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :

DESIGNER OF RECORDCONSULTANT100% CONSTRUCTION DOCUMENTS 10/03/2025

1221 N. Pennsylvania St.

Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com

GD Project: 23.1019.05

E

A CB

D FE

G IH

KEYPLAN

100% CONSTRUCTION

DOCUMENTS

10/03/2025

/3

/2

:2

:0

P

M

A u to d e s k D o c s /2

.0

V A

L o v e ll E le v a to r

U p g ra d e /5

-5

.B u ild in g

.E

R

.r v t

B07-M400

ENLARGED FLOOR PLANS - MECHANICAL Elevator Upgrade

3001 N GREEN BAY RD, NORTH CHICAGO, IL 60064

556-24-115

B07

10/03/2025 JMM LJT

23022.012

1/4" = 1'-0"

B07 ENLARGED ROOM P-22 ELEVATOR - NEW WORK MECHANICAL

SHEET NOTES:

1. DEMOLISH EXISTING SUMP PUMP AND ASSOCIATED COMPONENTS IN THEIR ENTIRETY. CAP SUMP PUMP DISCHARGE CONNECTION TO EXISTING

SANITARY RISER.

2. CUT PIT FLOOR TO EXTEND SUMP OPENING TO 13" IN DIAMETER TO ACCOMMODATE NEW SUMP PUMP INSTALLATION. REFER TO ELEVATOR SUMP PUMP DETAIL FOR FURTHER REQUIREMENTS. PROVIDE COVERING FOR SUMP PIT PER ASME 17.1 REQUIREMENTS.

3. PROVIDE REFRIGERANT PIPING SIZED AND INSTALLED PER MANUFACTURER'S RECOMMENDATIONS.

4. ROUTE CONDENSATE DRAIN OUTSIDE AND TERMINATE ONTO GUTTERED ROOF.

5. CONTRACTOR SHALL SCOPE EXISTING SANITARY SYSTEM WITHIN ROOM TO VALIDATE EXACT LOCATION PRIOR TO CUTTING FLOOR. PROVIDE

8"ØX36" STANDPIPE OFF THE EXISTING 4" SANITARY LINE AND TERMINATE SUMP PUMP DISCHARGE IN STANDPIPE WITH AIR GAP.

2 2 4 6 8 10

1/4" = 1'-0"

FEETSCALE

1/4" = 1'-0"

B07 ENLARGED ROOM 302 NEW WORK MECHANICAL

1/4" = 1'-0"

B07 ENLARGED ROOM P-22 ELEVATOR - DEMOLITION MECHANICAL

1/4" = 1'-0"

B07 ENLARGED ROOM 302 DEMOLITION MECHANICAL

GENERAL NOTES:

1. MECHANICAL SYMBOLS AND ABBREVIATIONS SHEET GENERAL NOTES APPLY TO ALL SHEETS.

2. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR DASHED, EXISTING MECHANICAL

SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE

WEIGHTS.

3. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL PIPING, EQUIPMENT AND DUCTWORK

INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.

4. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO PERFORM THIS WORK.

5. COORDINATE ROUTING OF REFRIGERANT AND CONDENSATE DRAIN PIPING TO NOT RUN ABOVE ELEVATOR EQUIPMENT AND ELEVATOR

CONTROLS.

FLOOR

STRUT CLAMP HANGERS VERTICAL PIPE SUPPORTCLEVIS HANGER ROLLER SUPPORTTRAPEZE HANGER

OVERSIZE HANGER TO

ALLOW LONGITUDINAL

PIPE EXPANSION AND

PIPE INSULATION TO

PASS THROUGH

UNBROKEN (TYP)

STEEL PIPE

SADDLE, TACK

WELDED TO PIPE,

FILL SADDLE

WITH INSULATION

INSULATION AND

NEOPRENE MOUNTS

RISER CLAMP

INSULATION

LUG, COUPLING, OR HUB

THREADED ROD

CLEVIS HANGER

INSULATION

HIGH DENSITY

INSULATION

INSERT

INSULATION SHIELD

INSULATION

PIPE INSULATION (TYP)

THREADED ROD (TYP)

HIGH DENSITY INSULATION INSERT

UNI-STRUT OR

EQUIVALENT

INSULATION SHIELD (TYP)

INSTALL CLAMP ON ALL

PIPES LESS THAN 4"Ø

DISCHARGE PIPE

ROUTE TO CODE APPROVED

LOCATION

SHUTOFF VALVE

CHECK VALVE

UNION

FLANGED COUPLING OR UNION

PUMP

BASIN WITH GASKETED

COVER PLATE

ON/OFF INTEGRAL OR

PIGGY-BACK FLOAT SWITCH

ALARM WHEN WATER LEVEL

IS 3" BELOW INVERT OF

LOWEST INLET

CONTROL PANEL WITH HIGH

WATER ALARM

NOTES:

1. INSTALL CONTROL PANEL PER MANUFACTURER INSTRUCTIONS. COMPONENTS

AND WIRING ARRANGEMENT MAY DIFFER FROM THAT SHOWN.

2. SUMP PUMPS THAT DISCHARGE TO STORM SHALL BE INSTALLED WITH THE TOP

OF THE SUMP BASIN 2" ABOVE FLOOR LEVEL. A 2" HIGH X 4" WIDE CONCRETE

CURB AROUND THE PERIMETER OF THE BASIN LID MAY BE USED IN LIEU OF

RAISING THE ENTIRE SUMP BASIN.

ABBREVIATIONS: MF = MINERAL FIBER/FIBERGLASS, E = ELASTOMERIC, CG = CELLULAR GLASS

REMARKS:

1. PLATE NUMBER REFERENCED ARE PROVIDED TO CLARIFY THE SCOPE OF INSTALLATION. INSTALL INSULATION AND ACCESSORY COMPONENTS PER APPLICABLE MICA AND MANUFACTURERS RECOMMENDATIONS.

2. MICA REFERENCE PLATES FOR PIPING ARE 1-100 FOR FIBERGLASS AND CELLULAR GLASS PIPE INSULATION, 1-200 FOR ELASTOMERIC AND 1-900 FIBERGLASS WITH HEAT TRACE.

REMARKS:

1. IF NO CC IN CONTRACT, MC TO WIRE CONTROLS AND EC TO PIPE CONDUIT.

2. ALL LOW VOLTAGE WIRING OF PANELS TO BE COVERED IN MC BID, WIRING CONTRACTOR TO BE SUBCONTRACTOR TO MC.

3. INSTALLING CONTRACTOR IS RESPONSIBLE FOR FIELD ALIGNMENT SERVICES WHEN REQUIRED BY COMMON MOTOR REQUIREMENTS

SPECIFICATION OR BY INDIVIDUAL EQUIPMENT SPECIFICATIONS.

4. ALL HARDWARE, SOFTWARE, EQUIPMENT, ACCESSORIES, WIRING (POWER AND SENSOR), PIPING, RELAYS, SENSORS, POWER

SUPPLIES, TRANSFORMERS, AND…