This document is a comprehensive set of electrical construction drawings for elevator upgrades at the James A. Lovell Federal Health Care Center (FHCC) in North Chicago, Illinois, specifically addressing project 556-24-115. The drawings encompass multiple buildings (B04, B07, B66, B131, B133CA, and B195) and include detailed electrical plans, schematics, and specifications for the installation of new elevator systems and related electrical infrastructure. The work involves complete demolition and replacement of existing elevator equipment, with new installations requiring coordination with final elevator manufacturer specifications. Key electrical components include new shunt trip disconnects, elevator controllers, fire alarm integration systems, smoke detectors, heat detectors, sump pump control panels, and dedicated lighting circuits. All work must comply with NFPA 70 (NEC) Article 620 for elevator installations and NFPA 72 for fire alarm systems.
The drawings specify extensive coordination requirements with multiple trades, including mechanical contractors for HVAC systems, fire suppression contractors for sprinkler coordination, and telecommunications for data cable routing. Critical electrical requirements include Category 6 network data cables from server/communications rooms to elevator machine rooms, fire-rated wall penetration systems with UL-listed fire stopping, bonding to existing lightning protection systems, and arc flash hazard mitigation through selective coordination of protective devices. Special provisions address wet location wiring in elevator pits (within 48 inches of floor), emergency power systems for elevator cab lights, and automatic transfer switches where elevators connect to emergency generators. All panels and disconnects must achieve minimum 120 percent of available short circuit current ratings, with specific attention to proper grounding, neutral conductor isolation, and equipment ground specifications throughout the installation scope.
View the file
Other files
Show all 23
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ELECTRICAL ABBREVIATIONS
ABBREVIATION DESCRIPTION
REFER TO OTHER SCHEDULES AND NOTES FOR ADDITIONAL ABBREVIATIONS.
MOUNTING HEIGHT TO CENTERLINE (ABOVE FINISHED FLOOR)
AMPERE
AMPERE FRAME
ABOVE FINISHED FLOOR
ALUMINUM
AMPERE TRIP
CEILING
CIRCUIT BREAKER
CORRELATED COLOR TEMPERATURE
COPPER
DATA (WHEN APPLIED TO COMMUNICATIONS OUTLET)
DEMO (WHEN APPLIED TO EXISTING/DEMO ITEMS)
EXISTING
ELECTRICALLY OPERATED
ENERGY REDUCING MAINTENANCE SWITCH
FUSE
FULL LOAD AMPS
GROUND FAULT CIRCUIT INTERRUPTER
GROUND FAULT ALARM
GROUND FAULT PROTECTION
HORSEPOWER
KILOAMPERE INTERRUPTING CAPACITY
KILOVOLT AMPERE
KILOWATT
MAXIMUM
MINIMUM CIRCUIT AMPS
MAIN CIRCUIT BREAKER
MINIMUM
MAIN LUGS ONLY
MANUALLY OPERATED
NORMALLY CLOSED
NON-FUSED
NOT IN CONTRACT
NORMALLY OPEN
POLES
PARTIAL
RELOCATE
SHORT CIRCUIT CURRENT RATING
SURGE PROTECTIVE DEVICE
SHUNT TRIP
TYPICAL
UNLESS NOTED OTHERWISE
VOICE
WALL PHONE
WIRE
WEATHER RESISTANT
TRANSFORMER
ZONE SELECTIVE INTERLOCKING
A
AF
AFF
AL
AT
C
CB
CCT
CU
D
D
E
EO
ERMS
F
FLA
G, GFCI
GFA
GFP
HP
KAIC
KVA
KW
MAX
MCA
MCB
MIN
MLO
MO
NC
NF
NIC
NO
P
PART
R
SCCR
SPD
ST
TYP
UNO
V
W
W
WR
XFMR
ZSI
A. BRANCH CIRCUITS WITH A TOTAL LENGTH LONGER THAN 75' SHALL UTILIZE #10 AWG CONDUCTORS.
RECEPTACLE BRANCH CIRCUITS WITH A TOTAL LENGTH LONGER THAN 150' SHALL UTILIZE #8 AWG
CONDUCTORS. THIS SHALL APPLY TO 20A BRANCH CIRCUITS.
B. FOR ALL CONDUIT AND OTHER ITEMS PENETRATING A FIRE RATED WALL, PROVIDE UL LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL CONSTRUCTION ASSEMBLY AND COMPLIANT WITH ASTM E814. INSTALL SYSTEM IN STRICT COMPLIANCE WITH THE FIRE STOPPING MANUFACTURER’S U.L. APPROVED DETAIL. WHERE EXISTING WALLS ARE BEING UPGRADED TO FIRE RATED WALLS OR THE FIRE RATING IS BEING MODIFIED, PROVIDE U.L. LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM FOR ALL NEW AND EXISTING PENETRATIONS. REFER TO THE ARCHITECTURAL LIFE
SAFETY PLANS FOR LOCATIONS OF FIRE RATED WALLS.
C. NEW ROOF MOUNTED EQUIPMENT SHALL BE BONDED TO EXISTING BUILDING LIGHTNING PROTECTION SYSTEM IF ONE EXISTS. PROVIDE AIR TERMINALS ON TOP OF EQUIPMENT AND BOND TO EXISTING SYSTEM PER NFPA 780 AND UL 96A REQUIREMENTS. PROVIDE UL INSPECTION AND/OR LPI SYSTEM INSPECTION AS REQUIRED TO OBTAIN UL MASTER LABEL RECERTIFICATION, UL MASTER LABEL AND/OR LPI SYSTEM
CERTIFICATE.
D. ANY ITEMS DAMAGED BY THE CONTRACTOR SHALL BE REPLACED BY THE CONTRACTOR, AT NO ADDITIONAL
COST TO THE OWNER.
E. NEW WIRING DEVICES AND ASSOCIATED COVERPLATES SHALL MATCH EXISTING FINISH OF SIMILAR
INSTALLED DEVICES.
F. THE SELECTED EQUIPMENT AIC RATINGS ARE BASED ON THE IMPEDANCES FOR CONDUCTORS AND TRANSFORMERS USED IN THE CALCULATIONS. IF DIFFERENT EQUIPMENT OR DIFFERENT CONFIGURATIONS
ARE SELECTED FOR INSTALLATION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING
ADEQUATELY RATED EQUIPMENT THAT MEETS APPLICABLE SELECTIVE COORDINATION GOALS AND
PROVIDES SIMILAR INCIDENT ENERGY RISK OF ARC FLASH HAZARDS.
G. PROVIDE AN INSULATED CONTINUOUS COPPER CONDUCTOR, NOT SMALLER THAN #10, TO BOND ALL
NORMAL AND ESSENTIAL ELECTRICAL SYSTEM PANELBOARDS TOGETHER THAT SERVE THE SAME
INDIVIDUAL PATIENT VICINITY AS DEFINED IN NEC 517.14.
H. PROVIDE ADDITIONAL SUPPORTS AS REQUIRED TO INDEPENDENTLY SUPPORT ALL EXISTING TO REMAIN
CABLING.
(GENERAL NOTES SHALL APPLY TO ALL SHEETS)
ELECTRICAL GENERAL NOTES:
10360 Ellison Circle Omaha, NE 68134 Phone:
402.991.5520
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :
DESIGNER OF RECORDCONSULTANT
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project: 23.1019.05 10/03/2025
100% CONSTRUCTION DOCUMENTS 10/03/2025
/3
/2
:1
:4
P
M
A u to d e s k D o c s /2
.0
V A
L o v e ll E le v a to r
U p g ra d e /5
-5
.B u ild in g
.E
R
.r v t
E000
ELECTRICAL SYMBOLS AND ABBREVIATIONS Elevator Upgrade
3001 GREEN BAY RD, NORTH CHICAGO, IL 60064
556-24-115
B04
09/12/2025 KB RC
23022.012
ELECTRICAL FIXTURE
SYMBOLS
PLAN SYMBOL NAME
RECEPTACLE - DUPLEX - CONV
RECEPTACLE - DUPLEX - CONV -
GFCI
RECEPTACLE - DUPLEX -
EMERGENCY (RED) - CONV -
GFCI
FIRE ALARM SYMBOLS
PLAN SYMBOL NAME
DETECTOR - SYSTEM HEAT -
CEILING
DETECTOR - SYSTEM SMOKE -
CEILING
LIGHTING DEVICE SYMBOLS
PLAN SYMBOL NAME
LIGHT SWITCH
ELECTRICAL MISC SYMBOLS
PLAN SYMBOL NAME
BRANCH CIRCUIT CONCEALED IN
CEILING OR WALL
BRANCH CIRCUIT CONCEALED IN
FLOOR OR BELOW GRADE
CLEARANCE SPACE
CONDUIT BREAK
CONDUIT DOWN
CONDUIT STUB-OUT
CONDUIT UP
HOMERUN TO PANEL
G = GFCI CIRCUIT
(PART) = PARTIAL CIRCUIT
LIGHTING FIXTURE
SYMBOLS
PLAN SYMBOL NAME
EMERGENCY HATCH
INDUSTRIAL STRIP LIGHT
PORCELAIN SOCKET
WALL MOUNT - STRIPLIGHT
ONE LINE SYMBOLS
PLAN SYMBOL NAME
AUTOMATIC TRANSFER SWITCH
CONTINUATION
ENCLOSED CIRCUIT BREAKER
GROUND BAR
GROUNDING ELECTRODE
MOTOR STARTER
NON-FUSED DISCONNECT
PANEL BOARD
SWITCHBOARD/SWITCHGEAR
TRANSFORMER
ELECTRICAL EQUIPMENT
SYMBOLS
PLAN SYMBOL NAME
ENCLOSED DISCONNECT
SWITCH - FUSED
ENCLOSED DISCONNECT
SWITCH - NON-FUSED
LOW VOLTAGE PANEL
PANELBOARD - SURFACE
TRANSFORMER - DRY TYPE
FHCC CONDUIT COLOR SCHEME
RED - FIRE ALARM
BLUE - CONTROLS, HVAC, BAS
ORANGE - FIBER OPTIC, COMMUNICATIONS
GREEN - NORMAL POWER
YELLOW - EMERGENCY POWER, CRITICAL POWER
BLACK - SECURITY
PURPLE - MEDICAL SYSTEMS, NURSE CALL
Revisions: Date:
B04-E400
STAIR 4
ST4
Room
Room
Room
Room
Room
Room
Room
Room
STAIR 5
ST5
Room
JANITOR
Room
STAIR 1
ST1WOMEN'S RESTROOM
OFFICE
OFFICE
CONFERENCE ROOM
OFFICE
OFFICE
OFFICE
CONFERENCE ROOM
STORAGE
TMS LAB
OFFICE
163D
OFFICE
163C
OFFICE
163B
OFFICE
163A
STORAGE
166A
COMP RM
ELECTRICAL RM
OFFICE
OFFICE
OFFICE
OFFICE
MEN'S RESTROOM
JANITOR
WOMEN'S RESTROOM
VIRTUAL RECREATION SPACE
Room
209XXXX
SUPPORT RM
139A
DEBBRIEFING
OFFICE
STORAGE
DENTAL LAB
DEBBRIEFING
SKILLS LAB
OR/SURGICAL SIM
MILITARY SIM
CONTROL ROOM
EMT SIM
SHOWER
119A
SHOWER
118A
FEMALE LOCKER RM
Room
MALE LOCKER RM
STAIR 2
ST2
ER SIM
DEPARTMENT HEAD
SIMULATION MANAGER
STAFF SUPPORT
ICU/MED SURGE
COAT RM
CONTROL ROOM
Room
Room
209IIIIIII
ELECTRICAL RM
SERVER RM
STORAGE
116A
Room
114B
EQUIPMENT STORAGE
JANITOR
STORAGE
MEN'S RESTROOM
WOMEN'S RESTROOM
RESOURCE OFFICE
CLASSROOM
MAIN ENTRY
Room
RECEPTION
LOW FIDELITY SKILLS LAB
COFFEE SHOP
CLASSROOM
138B
CLASSROOM
138A
HALLWAY
C106
HALLWAY
C104
HALLWAY
C105
CORRIDOR
C103 Room
114A
CORRIDOR
C102
VENDING RM
SEATING AREA
Room
BREAK-OUT RM
104B
BREAK-OUT RM
104A
CORRIDOR
C100
CAFE SEATING
RESOURCE RM
COPY ROOM
WORK RM
CORRIDOR
C111
CORRIDOR
C110
CORRIDOR-1
C101-1
CORRIDOR-2
C101-2
CORRIDOR
C108
BREAK ROOM
CORRIDOR
C107
THEATER MEZZ
105A
THEATER
MEN'S RESTROOM
Space
ELEVATOR
1-EL-P23
10360 Ellison Circle Omaha, NE 68134 Phone:
402.991.5520
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :
DESIGNER OF RECORDCONSULTANT
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project: 23.1019.05
E
A CB
D FE
G IH
KEYPLAN
10/03/2025
100% CONSTRUCTION DOCUMENTS 10/03/2025
/3
/2
:1
:5
P
M
A u to d e s k D o c s /2
.0
V A
L o v e ll E le v a to r
U p g ra d e /5
-5
.B u ild in g
.E
R
.r v t
B04-ED100
FIRST LEVEL FLOOR
PLAN-OVERALL-ELECTRICAL-DEMOLITION
Elevator Upgrade
3001 GREEN BAY RD, NORTH CHICAGO, IL 60064
556-24-115
B04
09/12/2025 KB RC
23022.012
1/16" = 1'-0"
FIRST LEVEL FLOOR PLAN - OVERALL - ELECTRICAL - DEMOLITION
N
5 5 10 15 20 25 30 35 40 45
1/16" = 1'-0"
FEETSCALE
4-DP-001-211
E
10360 Ellison Circle Omaha, NE 68134 Phone:
402.991.5520
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :
DESIGNER OF RECORDCONSULTANT
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project: 23.1019.05
E
A CB
D FE
G IH
KEYPLAN
10/03/2025
100% CONSTRUCTION DOCUMENTS 10/03/2025
/3
/2
:1
:0
P
M
A u to d e s k D o c s /2
.0
V A
L o v e ll E le v a to r
U p g ra d e /5
-5
.B u ild in g
.E
R
.r v t
B04-ED101
SECOND LEVEL FLOOR
PLAN-OVERALL-ELECTRICAL-DEMOLITION
Elevator Upgrade
3001 GREEN BAY RD, NORTH CHICAGO, IL 60064
556-24-115
B04
09/12/2025 KB RC
23022.012
1/16" = 1'-0"
SECOND LEVEL FLOOR PLAN - OVERALL - ELECTRICAL - DEMOLITION
N
5 5 10 15 20 25 30 35 40 45
1/16" = 1'-0"
10360 Ellison Circle Omaha, NE 68134 Phone:
402.991.5520
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :
DESIGNER OF RECORDCONSULTANT
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project: 23.1019.05
E
A CB
D FE
G IH
KEYPLAN
10/03/2025
100% CONSTRUCTION DOCUMENTS 10/03/2025
/3
/2
:1
:0
P
M
A u to d e s k D o c s /2
.0
V A
L o v e ll E le v a to r
U p g ra d e /5
-5
.B u ild in g
.E
R
.r v t
B04-ED102
PENTHOUSE
PLAN-OVERALL-ELECTRICAL-DEMOLITION
Elevator Upgrade
3001 GREEN BAY RD, NORTH CHICAGO, IL 60064
556-24-115
B04
09/12/2025 KB RC
23022.012
1/16" = 1'-0"
PENTHOUSE PLAN - OVERALL - ELECTRICAL - DEMOLITION
N
5 5 10 15 20 25 30 35 40 45
1/16" = 1'-0"
STAIR 4
ST4
Room
Room
Room
Room
Room
Room
Room
Room
STAIR 5
ST5
Room
JANITOR
Room
STAIR 1
ST1
WOMEN'S RESTROOM
OFFICE
OFFICE
CONFERENCE ROOM
OFFICE
OFFICE
OFFICE
CONFERENCE ROOM
STORAGE
TMS LAB
OFFICE
163D
OFFICE
163C
OFFICE
163B
OFFICE
163A
STORAGE
166A
COMP RM
ELECTRICAL RM
OFFICE
OFFICE
OFFICE
OFFICE
MEN'S RESTROOM
JANITOR
WOMEN'S RESTROOM
VIRTUAL RECREATION SPACE
Room
209XXXX
SUPPORT RM
139A
DEBBRIEFING
OFFICE
STORAGE
DENTAL LAB
DEBBRIEFING
SKILLS LAB
OR/SURGICAL SIM
MILITARY SIM
CONTROL ROOM
EMT SIM
SHOWER
119A
SHOWER
118A
FEMALE LOCKER RM
Room
MALE LOCKER RM
STAIR 2
ST2
ER SIM
DEPARTMENT HEAD
SIMULATION MANAGER
STAFF SUPPORT
ICU/MED SURGE
COAT RM
CONTROL ROOM
Room
Room
209IIIIIII
ELECTRICAL RM
SERVER RM
STORAGE
116A
Room
114B
EQUIPMENT STORAGE
JANITOR
STORAGE
MEN'S RESTROOM
WOMEN'S RESTROOM
RESOURCE OFFICE
CLASSROOM
MAIN ENTRY
Room
RECEPTION
LOW FIDELITY SKILLS LAB
COFFEE SHOP
CLASSROOM
138B
CLASSROOM
138A
HALLWAY
C106
HALLWAY
C104
HALLWAY
C105
CORRIDOR
C103 Room
114A
CORRIDOR
C102
VENDING RM
SEATING AREA
Room
BREAK-OUT RM
104B
BREAK-OUT RM
104A
CORRIDOR
C100
CAFE SEATING
RESOURCE RM
COPY ROOM
WORK RM
CORRIDOR
C111
CORRIDOR
C110
CORRIDOR-1
C101-1
CORRIDOR-2
C101-2
CORRIDOR
C108
BREAK ROOM
CORRIDOR
C107
THEATER MEZZ
105A
THEATER
MEN'S RESTROOM
Space
ELEVATOR
1-EL-P23
B04-E400
G-LP1
G-LP-N3
G-LP-N2
G-LP-N1
G-FCU-N
FACP
4-PNL-001-109
4-EPNL-001-109
4-PNL-002-109
4-PNL-003-109
4-PNL-004-109
4-PNL-005-105
4-DP-001-109
(E) TYP.
(E) TYP.
4-DP-001-CO-1-107
10360 Ellison Circle Omaha, NE 68134 Phone:
402.991.5520
INSTALL GREEN INSULATED
GROUND WIRE WITH
LIGHTING, RECEPTACLE AND
EQUIPMENT BRANCH CIRCUITS.
INSTALL INDIVIDUAL (DEDICATED)
NEUTRAL CONDUCTORS FOR
EACH 120V OR 277V PHASE
CONDUCTOR SERVED FROM A
SINGLE POLE CIRCUIT BREAKER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :
DESIGNER OF RECORDCONSULTANT
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project: 23.1019.05
E
A CB
D FE
G IH
KEYPLAN
10/03/2025
100% CONSTRUCTION DOCUMENTS 10/03/2025
/3
/2
:1
:0
P
M
A u to d e s k D o c s /2
.0
V A
L o v e ll E le v a to r
U p g ra d e /5
-5
.B u ild in g
.E
R
.r v t
B04-E100
FIRST LEVEL FLOOR
PLAN-OVERALL-ELECTRICAL
Elevator Upgrade
3001 GREEN BAY RD, NORTH CHICAGO, IL 60064
556-24-115
B04
09/12/2025 KB RC
23022.012
1/16" = 1'-0"
FIRST LEVEL FLOOR PLAN - OVERALL - ELECTRICAL
N
5 5 10 15 20 25 30 35 40 45
1/16" = 1'-0"
FEETSCALE
SHEET NOTES:
1. ELECTRICAL ROOM WITH PANEL THAT FEEDS ELEVATOR AND EMERGENCY PANEL FOR CAB LIGHTS.
2. PROVIDE (6) CAT 6 CABLES FROM SERVER ROOM TO ELEVATOR EQUIPMENT ROOM. CONTRACTOR SHALL COORDINATE STARTING POINT IN
SERVER ROOM WITH VA IT AND THEN FINAL LOCATION IN ELEVATOR EQUIPMENT ROOM WITH ELEVATOR MANUFACTURER.
Room
Room
200A
STAIR 5
ST5
Room
209OOOOOOOOO
SERVER RM
Room
Room
Room
Room
Room
Room
CORRIDOR
C100
Room
MAIN ENTRY-2
100-2
Room
STAIR 1
ST1
MEN'S RESTROOM
Room
BREAK-OUT RM
104A
Room
Room
207A
Room
Room
Room
208Room
Room
205B
Room
PROJECTOR RM
205E
FE CLOSET
Room
Room
Room
205A Room
205C
STORAGE RM
205D
MECH RM
CORRIDOR
C202
Room
Room
Room
Room
Room
227A
CORRIDOR
C201
CORRIDOR
C200
Room
LARGE ROOM
Room
Room
Room
CORRIDOR
C203
STAIR 2
ST2
MECH RM
THEATER-2
105-2
Room
Room
4-DP-001-211
10360 Ellison Circle Omaha, NE 68134 Phone:
402.991.5520
INSTALL GREEN INSULATED
GROUND WIRE WITH
LIGHTING, RECEPTACLE AND
EQUIPMENT BRANCH CIRCUITS.
INSTALL INDIVIDUAL (DEDICATED)
NEUTRAL CONDUCTORS FOR
EACH 120V OR 277V PHASE
CONDUCTOR SERVED FROM A
SINGLE POLE CIRCUIT BREAKER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :
DESIGNER OF RECORDCONSULTANT
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project: 23.1019.05
E
A CB
D FE
G IH
KEYPLAN
10/03/2025
100% CONSTRUCTION DOCUMENTS 10/03/2025
/3
/2
:1
:0
P
M
A u to d e s k D o c s /2
.0
V A
L o v e ll E le v a to r
U p g ra d e /5
-5
.B u ild in g
.E
R
.r v t
B04-E101
SECOND LEVEL FLOOR
PLAN-OVERALL-ELECTRICAL
Elevator Upgrade
3001 GREEN BAY RD, NORTH CHICAGO, IL 60064
556-24-115
B04
09/12/2025 KB RC
23022.012
1/16" = 1'-0"
SECOND LEVEL FLOOR PLAN - OVERALL - ELECTRICAL
N
5 5 10 15 20 25 30 35 40 45
1/16" = 1'-0"
FEETSCALE
SHEET NOTES:
1. SMOKE DETECTOR TO BE PROVIDED AT THE TOP OF HOISTWAY.
10360 Ellison Circle Omaha, NE 68134 Phone:
402.991.5520
INSTALL GREEN INSULATED
GROUND WIRE WITH
LIGHTING, RECEPTACLE AND
EQUIPMENT BRANCH CIRCUITS.
INSTALL INDIVIDUAL (DEDICATED)
NEUTRAL CONDUCTORS FOR
EACH 120V OR 277V PHASE
CONDUCTOR SERVED FROM A
SINGLE POLE CIRCUIT BREAKER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :
DESIGNER OF RECORDCONSULTANT
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project: 23.1019.05
E
A CB
D FE
G IH
KEYPLAN
10/03/2025
100% CONSTRUCTION DOCUMENTS 10/03/2025
/3
/2
:1
:0
P
M
A u to d e s k D o c s /2
.0
V A
L o v e ll E le v a to r
U p g ra d e /5
-5
.B u ild in g
.E
R
.r v t
B04-E102
PENTHOUSE PLAN-OVERALL-ELECTRICAL Elevator Upgrade
3001 GREEN BAY RD, NORTH CHICAGO, IL 60064
556-24-115
B04
09/12/2025 KB RC
23022.012
1/16" = 1'-0"
PENTHOUSE PLAN - OVERALL - ELECTRICAL
5 5 10 15 20 25 30 35 40 45
1/16" = 1'-0"
FEETSCALE
N
ELEVATOR
1-EL-P23
DD
D
D
ELEV DISCONNECT (D)
E
E
D
ELEV CONTROLLER (D)
TRANSFORMER (E)
E
E
ELEV CONTROLLER
ELEV DISCONNECT
TRANSFORMER (E)
K1
K1
K1
K1
UH-04-300
SS-04-CU
SS-04-300
48"48"
48"
ELEVATOR
1-EL-P23
7 7
SP-04-300
A. ELECTRICAL DEVICE MOUNTING HEIGHTS ARE NOT INDICATED ON ELECTRICAL FLOOR
PLANS. CONTRACTOR SHALL COORDINATE EXACT DEVICE LOCATIONS AND MOUNTING
HEIGHTS.
B. ROUTE ALL ELECTRICAL BRANCH CIRCUITS AND CONDUITS SPECIFIED, TO COORDINATE
WITH OTHER TRADES AND TO ALLOW FOR SERVICE AND MAINTENANCE AND TO MINIMIZE
THE USE OF ACCESS PANELS. WHERE ACCESS PANELS CANNOT BE AVOIDED, ARRANGE
WORK TO INSTALL PANELS IN LOCATIONS ACCEPTABLE TO ARCHITECT.
C. REFER TO SPECIFIC ELEVATOR DETAIL ON SHEET B04-E400.
D. REFER TO DETAILS, SCHEDULES, AND SYMBOL LEGENDS FOR ADDITIONAL
REQUIREMENTS.
(POWER GENERAL NOTES SHALL APPLY TO ALL SHEETS)
ELEVATOR GENERAL NOTES:
ELEVATOR
MACHINE ROOM
ELEVATOR LOBBY
ELEVATOR PIT
ST
MM CM CM
FIRE ALARM CONTROL MODULE (TYP)
HOISTWAY PIT LIGHT - REFER TO PLANS
FOR FINAL COUNT
SUMP PUMP CONTROL/POWER JUNCTION BOX
EXISTING MACHINE ROOM SMOKE DETECTOR
NEW MACHINE ROOM LIGHT
DEDICATED CAR LIGHT CIRCUIT DISCONNECT SWITCH
ELEVATOR LOBBY
SMOKE DETECTOR
(TYP ALL FLOORS)
ELEVATOR
CONTROLLER
CM CM
PROVIDE WET LOCATION WIRING
METHODS IN PIT WITHIN 48" OF
THE FLOOR. MOUNT ALL FIRE
ALARM DEVICES, JUNCTION
BOXES, AND RECEPTACLES
ABOVE 48" AFF.
HOISTWAY SMOKE DETECTOR
1. ELEVATOR POWER SHUNT TRIP. CONNECT TO FIRE SAFETY INTERFACE IN ELEVATOR MAIN POWER SWITCH.
COORDINATE
2. ELEVATOR RECALL INITIATED BY FIRE ALARM SYSTEM VIA CONTROL MODULES. COORDINATE WITH
UPDATED SYSTEM.
3. SMOKE DETECTOR ALARM SIGNAL TO FIRE ALARM SYSTEM INITIATES ELEVATOR RECALL. COORDINATE
WITH UPDATED SYSTEM.
4. HEAT DETECTOR ALARM SIGNAL TO FIRE ALARM SYSTEM INITIATES ELEVATOR SHUNT TRIP. COORDINATE
WITH UPDATED SYSTEM.
5. DEDICATED CAR LIGHT CIRCUIT WITH LOCKABLE FUSED SWITCH PER NFPA 70, ARTICLE 620. SERVE FROM
LIFE SAFETY BRANCH SOURCE INDICATED. PROVIDE 2-#12, #12 GROUND IN 3/4" CONDUIT.
6. DEDICATED ELEVATOR HOISTWAY PIT BRANCH CIRCUITS PER NFPA 70, ARTICLE 620. SERVE FROM EXISTING CIRCUIT. SHOULD BOTH LIGHTINGS AND RECEPTACLES BE FOUND TO BE ON THE SAME CIRCUIT THE CONTRACTOR SHALL PROVIDE AN ADDITIONAL CIRCUIT TO ALLOW FOR SEPARATION OF RECEPTACLES AND
LIGHTING.
7. ELEVATOR CAB VISUAL INDICATOR CONTROL. (FIREFIGHTERS HAT LIGHT)
8. TELEPHONE OUTLET AND CONDUIT PER FINAL ELEVATOR MANUFACTURER. PROVIDE CONNECTION TO
ELEVATOR CONTROLLER PER MANUFACTURERS INSTRUCTIONS.
9. SHUNT TRIP POWER SOURCE MONITORING MODULE.
10. PROVIDE BUSSMANN POWER MODULE SWITCH, LITTELFUSE LPS SERIES, MERSEN ES SERIES OR
EQUIVALENT SHUNT TRIP DISCONNECT SWITCH WITH AMPACITY TO MEET OR EXCEED OVERCURRENT DEVICE SERVING ELEVATOR. PROVIDE WITH CONTROL POWER TRANSFORMER, FIRE SAFETY INTERFACE
RELAY, AND AUXILIARY CONTACTS (1 SET). PROVIDE CLASS J FUSES SIZED PER ELEVATOR
MANUFACTURER'S RECOMMENDATIONS. THE AVAILABLE SHORT CIRCUIT CURRENT (SCC) AT THE
ELEVATOR MAIN POWER SWITCH SHALL MATCH EXISTING, REFER TO CURRENT POWER SYSTEM STUDY UNDER DESIGN. RATING SHALL BE ADJUSTED IF REQUIRED BASED ON FINAL SCC CALCULATION. PROVIDE NEW FEEDERS PER ONE-LINE DIAGRAM, UTILIZE EXISTING CONDUIT. CONFIRM FINAL FEEDER AND CIRCUIT
BREAKER SIZE WITH FINAL EQUIPMENT SELECTION.
11. ELEVATOR HOISTWAY PIT LIGHTS. PROVIDE LIGHT FIXTURESAS INDICATED ON FLOOR PLANS. COORDINATE EXACT FIXTURE LOCATIONS AND REQUIREMENTS PRIOR TO ROUGH-IN. PROVIDE LITHONIA CATALOG # FEM- L48-6000LM-LPAFL-WD-MVOLT-GZ10-40K-80CRI OR PRIOR APPROVED EQUIVALENT. REFER TO FLOORPLANS
FOR LOCATIONS.
12. DEDICATED MACHINE ROOM BRANCH CIRCUITS PER NFPA 70, ARTICLE 620. SERVE FROM NEW NORMAL
BRANCH SOURCE AS SHOWN ON FLOORPLANS.
13. SUMP PUMP CONTROL PANEL (PROVIDED BY SUMP PUMP MANUFACTURER), MOUNTED PER MECHANICAL PLANS. REFER TO FLOORPLANS FOR EXACT LOCATION. POWER SOURCE FOR ASSOCIATED SUMP PUMP
SHALL ROUTE THROUGH CONTROL PANEL AND PROVIDE POWER TO CONTROL PANEL. COORDINATE
LOCATION OF CONTROL PANEL TO ACCOMMODATE ALL RELEVANT CODES AND AVAILABLE LENGTHS OF CONTROL CABLE. PROVIDE PUMP ALARM SIGNAL TO FIRE ALARM CONTROL PANEL AS A SUPERVISORY ALARM. COORDINATE ALL REQUIREMENTS OF SUMP PUMP SYSTEMS SPECIFIED AND MAKE PROVISIONS FOR MOUNTING, CONFIGURATION, AND CONNECTION AS DIRECTED BY VENDOR / MANUFACTURER.
14. PROVIDE TWO (2) 1" CONDUITS FROM CONTROL PANEL INTO ELEVATOR PIT FOR CONTROL CABLE ROUTING BY SUMP PUMP MANUFACTURER. COORDINATE SIZE AND QUANTITY OF CONDUITS TO ACCOMMODATE CONTROL CABLES (FLOATS, PROBES, SENSORS, ETC.) AS RECOMMENDED BY MANUFACTURER. ROUTE
CONDUIT TO CONNECTION JUNCTION BOX AND PROVIDE CONNECTIONS PER MANUFACTURER'S
INSTRUCTIONS. COORDINATE ROUTING OF CONTROL CABLE CONDUIT TO DETERMINE LENGTH
REQUIREMENTS OF CONTROL CABLES.
15. SURFACE MOUNT MANUFACTURER FURNISHED SUMP PUMP CONTROL JUNCTION BOX WITHIN ELEVATOR PIT. MOUNT WITH BOTTOM OF JUNCTION BOX 50" ABOVE ELEVATOR PIT FLOOR. COORDINATE LOCATION OF
JUNCTION BOX WITH LOCATION OF SUMP PUMP AND CONTROL CABLE LENGTHS. PROVIDE FINAL
CONNECTIONS OF CONTROL CABLES AT SUMP PUMP. COORDINATE ALL REQUIREMENTS OF SUMP PUMP
SYSTEMS SPECIFIED AND MAKE PROVISIONS FOR MOUNTING AND CONNECTION AS DIRECTED BY
VENDOR/MANUFACTURER.
16. PROVIDE SIMPLEX NEMA RECEPTACLE, HARD-WIRED FROM SUMP PUMP CONTROL PANEL, MOUNTED WITH BOTTOM OF BACK BOX AT 50" ABOVE ELEVATOR PIT FLOOR. SERVE FROM SUMP PUMP CONTROL PANEL SOURCE. PROVIDE SUMP PUMP WITH CORD AND PLUG TO MATCH NEMA CONFIGURATION OF SIMPLEX NEMA RECEPTACLE. REFER TO EQUIPMENT CONNECTION SCHEDULE SUMP PUMP SP-04-P23 FOR NEMA
CONFIGURATION, FEEDER, AND OVERCURRENT PROTECTION REQUIREMENTS.
17. IF ELEVATOR IS PROVIDED WITH AUTOMATIC BATTERY LOWERING FEATURE, PROVIDE CONNECTION FROM ELEVATOR CONTROLLER DISCONNECT SWITCH AUXILIARY CONTACTS TO AUTOMATIC BATTERY LOWERING
FEATURE FOR SAFETY INTERLOCK TO PREVENT AUTOMATIC LOWERING OF ELEVATOR DURING
MAINTENANCE.
18. DEDICATED TWO-WAY VIDEO COMMUNICATION DEVICE CONNECTION PER ASME A17.1. PROVIDE NETWORK
DATA CONNECTION FROM ASSOCIATED COMMUNICATIONS ROOM.
19. PROVIDE REMOTE SAMPLING SMOKE DETECTOR TO ALLOW FOR ACCESSIBILITY. LOCATE ACCESSIBLE UNIT
IN ELEVATOR LOBBY.
ELEVATOR CONNECTION SCHEMATIC KEYED NOTES:
MOUNT ADJACENT TO PIT ACCESS / LADDER ENTRY LEVEL
NEW MACHINE ROOM HEAT DETECTOR
ELEVATOR MAIN POWER SWITCH
J
SUMP PIT
EXISTING
CIRCUIT
FIRE ALARM MONITORING MODULE (TYP)
MM
A. COMPLY WITH NFPA 70, ARTICLE 620.
B. SMOKE DETECTORS SHALL BE INSTALLED AT EACH ELEVATOR LOBBY AT EACH LANDING, AND ASSOCIATED
ELEVATOR MACHINE ROOM, AND WITHIN ELEVATOR HOISTWAY. PROVIDE QUANTITY OF SMOKE
DETECTORS REQUIRED BASED ON FINAL CEILING HEIGHT, BEAM POCKET DEPTH, ETC. TO MEET NFPA 72, CHAPTER 17 REQUIREMENTS. ACTIVATION OF ANY OF THESE SMOKE DETECTORS SHALL INITIATE
ELEVATOR RECALL.
C. ACTIVATION OF SMOKE DETECTOR(S) ON A DESIGNATED LEVEL SHALL CAUSE THE ELEVATOR TO RETURN TO AN ALTERNATE LEVEL. DESIGNATED AND ALTERNATE LEVELS TO BE DETERMINED BY THE ELEVATOR
INSPECTOR AND FIRE MARSHAL.
D. HEAT DETECTORS USED FOR ELEVATOR POWER SHUT DOWN SHALL BE LOCATED WITHIN 24" OF SPRINKLER HEADS WITHIN ELEVATOR MACHINE ROOM. COORDINATE EXACT LOCATION(S) AND QUANTITY WITH FIRE SPRINKLER CONTRACTOR. ACTIVATION OF HEAT DETECTOR WITHIN ELEVATOR MACHINE ROOM
SHALL SHUT DOWN POWER TO ELEVATOR CONTROLLER.
E. FIRE ALARM CONNECTIONS INDICATED ARE BASED ON AN ADDRESSABLE FIRE ALARM SYSTEM. WHERE A NON-ADDRESSABLE FIRE ALARM SYSTEM IS SPECIFIED PROVIDE RELAYS AND CONNECTIONS TO CONTROL
PANEL AS REQUIRED.
F. VERIFY ALL EQUIPMENT LOCATIONS WITH ELEVATOR MANUFACTURER'S SHOP DRAWINGS PRIOR TO
INSTALLATION OF EQUIPMENT.
ELEVATOR CONNECTION SCHEMATIC GENERAL NOTES:
ELEVATOR LOBBY
EXISTING
CIRCUIT
4-EPNL-001-109 - 31
ELEVATOR LOBBY
SMOKE DETECTOR
(TYP ALL FLOORS)
4-EPNL-001-109 - 33
10360 Ellison Circle Omaha, NE 68134 Phone:
402.991.5520
INSTALL GREEN INSULATED
GROUND WIRE WITH
LIGHTING, RECEPTACLE AND
EQUIPMENT BRANCH CIRCUITS.
INSTALL INDIVIDUAL (DEDICATED)
NEUTRAL CONDUCTORS FOR
EACH 120V OR 277V PHASE
CONDUCTOR SERVED FROM A
SINGLE POLE CIRCUIT BREAKER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :
DESIGNER OF RECORDCONSULTANT
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project: 23.1019.05
E
A CB
D FE
G IH
KEYPLAN
10/03/2025
100% CONSTRUCTION DOCUMENTS 10/03/2025
/3
/2
:1
:0
P
M
A u to d e s k D o c s /2
.0
V A
L o v e ll E le v a to r
U p g ra d e /5
-5
.B u ild in g
.E
R
.r v t
B04-E400
ENLARGED FLOOR PLANS-ELECTRICAL Elevator Upgrade
3001 GREEN BAY RD, NORTH CHICAGO, IL 60064
556-24-115
B04
09/12/2025 KB RC
23022.012
1/4" = 1'-0"
B04 ENLARGED ROOM 1-EL-P23 - DEMOLITION ELEVATOR PIT ELECTRICAL
N 2 2 4 6 8 10
1/4" = 1'-0"
FEETSCALE
1/4" = 1'-0"
B04 ENLARGED ROOM 300 - DEMOLITION ELEVATOR MACHINE ROOM
SHEET NOTES:
1. EXISTING SMOKE DETECTOR TO BE TESTED FOR FULL FUNCTIONALITY AND COMPLIANCE.
SHOULD SMOKE DETECTOR NOT BE FUNCTIONAL THE CONTRACTOR SHALL REPLACE WITH
NEW. THE EXISTING SMOKE DETECTOR SHALL BE REMOVED AND MAINTENANCE PERFORMED.
CONTRACTOR TO PLACE BACK AT CEILING HEIGHT.
2. EXISTING ELEVATOR EQUIPMENT TO BE REMOVED AND REPLACED. EXISTING CONDUIT
SERVING EQUIPMENT SHALL REMAIN. THE CONTRACTOR SHALL REMOVE CONDUCTORS FROM
CONDUIT AND PROVIDE PULLSTRING FOR NEW WORK.
3. EXISTING LIGHT FIXTURE TO BE REMOVED. REMOVE BACK TO POINT OF ORIGIN AND MARK
SPARE SHOULD NO OTHER ELECTRICAL COMPONENTS BE ON THE CIRCUIT. REFER TO NEW
WORK PLAN FOR MORE INFORMATION.
4. PROVIDE NEW ELEVATOR SHUNT TRIP DISCONNECT AND ELEVATOR CONTROLLER.
COORDINATE WITH FINAL ELEVATOR MANUFACTURER SELECTED. CONTRACTOR TO PROVIDE
NEW FEEDERS WITHIN THE EXISTING CONDUIT. REFER TO ONE-LINE DIAGRAM FOR MORE
INFORMATION. SHOULD EXISTING CONDUIT NOT MEET THE REQUIREMENTS OF THE NEW
ELEVATOR CONTRACTOR SHALL PROVIDE NEW.
5. CONNECT NEW LIGHT FIXTURES TO NEW EMERGENCY BRANCH CIRCUIT FROM NEAREST
EMERGENCY BRANCH 208/120V PANEL. CONNECT TO 120V 20A/1P BREAKER.
6. REMOVE EXISTING RECEPTACLE. REMOVE BACK TO POINT OF ORIGIN AND MARK SPARE
SHOULD NO OTHER ELECTRICAL COMPONENTS BE ON THE CIRCUIT. REFER TO NEW WORK
PLAN FOR MORE INFORMATION.
7. REFER TO ELEVATOR DETAIL FOR LIGHT FIXTURE TYPE.
8. CONNECT TO EXISTING RECEPTACLE CIRCUIT MAINTAINED DURING CONSTRUCTION.
9. CONNECT TO NEW NORMAL BRANCH CIRCUIT FROM NEAREST SPARE 20A/1P BREAKER ON THE
NORMAL BRANCH OF THE ELECTRICAL SYSTEM.
10. PROVIDE ADDITIONAL DETECTOR FOR ROOM COVERAGE DUE TO DEPTH OF EXISTING
STRUCTURAL BEAM.
11. LIGHT SWITCH TO BE LOCATED AT LADDER. CONTRACTOR TO ENSURE SWITCH IS AT CORRECT
HEIGHT.
12. EXISTING CAB DISCONNECT TO REMAIN. CONTRACTOR TO CONFIRM LOCATION AND
COORDINATION WITH FINAL ELEVATOR MANUFACTURER CHANGES.
1/4" = 1'-0"
B04 ENLARGED ROOM 300 - NEW WORK ELEVATOR MACHINE ROOM
1/4" = 1'-0"
B04 ENLARGED ROOM 1-EL-P23 - NEW WORK ELEVATOR PIT ELECTRICAL
NO SCALE
ELEVATOR CONNECTION SCHEMATIC
175A D
17N
ELEVATOR
D
2000A E
200A E
200A E
1000A E
1200A E
4-DT-SS-SB
208/120V 2000A 3/4W E
4-ATS-001-SB
200A E
B-LP-1
208/120V
200A 3/4W E
TRANSFORMER
E
TO BUILDING 156
GENERATOR
E
B-EDLP-1
208/120V
200A 3/4W E
EM-G
208/120V
100A 3/4W E
4-DP-001-109
208/120V
1000A 3/4W E1000A
E
1200A E
100A E
200A E
200A E
200A E
200A E
300A E
50A E
70A E
GI
208/120V
100A 3/4W E
G1S 208/120V 70A 3/4W
E
G-FCU-N
208/120V
100A 3/4W E
G-LP-N1
208/120V
200A 3/4W E
G-LP-N2
208/120V
200A 3/4W E
G-SP-1
208/120V
200A 3/4W E
G-LP-1
208/120V
200A 3/4W E
1L 208/120V 70A 3/4W
E
MP
208/120V
500A 3/4W E
FR-LP-2
208/120V
200A 3/4W E
1M 208/120V
100A 3/4W E
100A E
70A E
100A E
200A E
200A E
200A E
200A E
70A E
SERVICE RM #7
E
4-TDT-DT-SS-SB
750KVA
4-DP-001-CO-1-107
208/120V
1200A 3/4W E
2000A E
200A E
200A E
1000A E
1200A E
4-DT-SS-SB
208/120V 2000A 3/4W E
4-ATS-001-SB
200A
NEC 700 - EMERGENCY BRANCH
E
B-LP-1
208/120V
200A 3/4W E
TRANSFORMER
E
TO BUILDING 156
GENERATOR
E
4-PNL-B-EDLP-1-SB
208/120V 200A 3/4W E
4-EPNL-001-109
208/120V 100A 3/4W E
4-DP-001-109
208/120V
1000A 3/4W E
4-DP-001-CO-1-107
208/120V
1200A 3/4W E1000A
E
1200A E
100A E
200A E
200A E
200A E
200A E
300A E
50A E
70A E
GI
208/120V
100A 3/4W E
G1S 208/120V 70A 3/4W
E
G-FCU-N
208/120V
100A 3/4W E
G-LP-N1
208/120V
200A 3/4W E
G-LP-N2
208/120V
200A 3/4W E
G-SP-1
208/120V
200A 3/4W E
G-LP-1
208/120V
200A 3/4W E
1L 208/120V 70A 3/4W
E
MP
208/120V
500A 3/4W E
FR-LP-1
208/120V
200A 3/4W E
FR-LP-2
208/120V
200A 3/4W E
1M 208/120V
100A 3/4W E
100A E
70A E
100A E
500A E
200A E
175A 200A E
200A E
200A E
200A E
200A E
200A E
70A E
SERVICE RM #7
E
17N
SHUNT
175A
ELEVATOR
ELEVATOR
CONTROLLER
4-TDT-DT-SS-SB
750KVA
10360 Ellison Circle Omaha, NE 68134 Phone:
402.991.5520
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :
DESIGNER OF RECORDCONSULTANT
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project: 23.1019.05 10/03/2025
100% CONSTRUCTION DOCUMENTS 10/03/2025
/3
/2
:1
:0
P
M
A u to d e s k D o c s /2
.0
V A
L o v e ll E le v a to r
U p g ra d e /5
-5
.B u ild in g
.E
R
.r v t
B04-E500
ONE-LINE DIAGRAM Elevator Upgrade
3001 GREEN BAY RD, NORTH CHICAGO, IL 60064
556-24-115
B04
09/12/2025 KB RC
23022.012
NO SCALE
ELECTRICAL ONE-LINE - SWBD BLDG 4 DEMO
FEEDER SCHEDULE - COPPER
FEEDER NOMINAL SIZE WIRE AND CONDUIT
17N 175 A 4-#3/0 CU, #6 CU GND - 2-1/2" C.
NO SCALE
NEW ELECTRICAL ONE-LINE - SWBD BLDG 4
SHEET NOTES:
1. REMOVE EXISTING BREAKER AND PROVIDE NEW BREAKER AS REQUIRED FOR UPDATED MOTOR. NEW BREAKER TO BE COMPATIBLE WITH EXISTING PANEL MANUFACTURER. FINAL SELECTION TO BE BASED ON FINAL ELEVATOR EQUIPMENT.
2. REMOVE EXISTING SOURCE CONDUCTORS SERVING THE ELEVATOR AND RETAIN EXISTING CONDUIT FOR REUSE. PROVIDE NEW CONDUCTORS AS SCHEDULED. THE CONDUCTOR SIZE/CONFIGURATION IS PRELIMINARY AND FOR BIDDING PUPOSES ONLY. PRIOR TO ORDERING MATERIAL ASSOCIATED WITH THE NEW CONDUCTOR INSTALLATION, CONTRACTOR SHALL SEEK VERIFICATION OF THE FINAL CONDUCTOR SIZE/CONFIGURATION FROM THE ENGINEER TO ACCOMMODATE THE FINAL SELECTED ELEVATOR MANUFACTURER AND EQUIPMENT.
REMARKS: (EQUIPMENT CONNECTION SCHEDULE)
1. CONTROLS BETWEEN INDOOR AND OUTDOOR UNITS - INCLUDE CONTROL WIRING IN CONDUIT BETWEEN INDOOR AND OUTDOOR UNIT PER MANUFACTURER'S REQUIREMENTS.
2. WALK-IN COOLER CONNECTIONS - PROVIDE CONNECTION TO COOLER ACCESSORIES (EVAPORATOR, LIGHTS, LIGHT CONTROLS, AND DOOR FRAME HEATER) WITH BRANCH CIRCUITS INDICATED ON PLANS.
ACCESSORIES FURNISHED WITH EQUIPMENT.
3. KITCHEN HOOD FIRE SUPPRESSION CONNECTIONS - INTERLOCK HOOD FIRE SUPPRESSION WITH FIRE ALARM MONITORING, SHUNT TRIP CIRCUIT BREAKERS SERVING EQUIPMENT BELOW HOOD, AND GAS SUPPLY
SOLENOID VALVES/RESETS SERVING EQUIPMENT BELOW HOOD. ACTIVATION OF HOOD FIRE SUPPRESSION SHALL TRIP SHUNT CIRCUIT BREAKERS TO THEIR OFF POSITION. SHALL CLOSE GAS SUPPLY SOLENOID VALVES AND SHALL PROVIDE INDICATION TO THE FIRE ALARM SYSTEM. 120V BRANCH CIRCUIT SHALL SERVE HOOD LIGHTS, HOOD CONTROLS, AND FIRE SUPPRESSION INTERLOCKS. HOOD FIRE SUPPRESSION SYSTEM IS SHIPPED LOOSE, COORDINATE MOUNTING LOCATION IN FIELD. SEE FOOD SERVICE EXHAUST HOOD DRAWING FOR CLARIFICATION AND ADDITIONAL REQUIREMENTS.
4. KITCHEN HOOD CONTROL CONNECTIONS - INTERLOCK HOOD CONTROL PANEL WITH FAN SWITCH AT HOOD, LIGHT SWITCH AND LIGHTING AT HOOD, HOOD FIRE SUPPRESSION SYSTEM, ASSOCIATED EXHAUST FAN STARTERS, AND ASSOCIATED MAKE-UP AIR/ROOFTOP UNITS. HOOD CONTROL PANEL IS SHIPPED LOOSE, COORDINATE MOUNTING LOCATION IN FIELD. SEE FOOD SERVICE EXHAUST HOOD DRAWING FOR
CLARIFICATION AND ADDITIONAL REQUIREMENTS.
GENERAL NOTES: (EQUIPMENT CONNECTION SCHEDULE)
A. EQUIPMENT LISTED MAY NOT BE UNIQUE, VERIFY QUANTITY WITH FLOOR PLANS. WHERE LOCATIONS ARE NOT INDICATED ON ELECTRICAL FLOOR PLANS, REFER TO MECHANICAL SHEETS. REFER TO DEFINITIONS
BELOW FOR CLARIFICATIONS OF CONNECTION REQUIREMENTS.
B. ITEMS NOTED AS "NA" ARE NOT APPLICABLE TO THE CONNECTION.
C. "CONTROL TYPE" - PROVIDE CONTROL AND CONNECTIONS:
• "INT" = CONTROLS ARE MANUFACTURED INTEGRAL TO THE EQUIPMENT (SELF-CONTAINED).
• "CONT" = EQUIPMENT OPERATES CONTINUOUSLY (NO CONTROLS). FOR MOTORS WITHOUT INTERNAL OVERLOAD PROTECTION, PROVIDE SEPARATE OVERLOAD PROTECTION. OVERLOAD PROTECTION MAY BE
PROVIDED AS PART OF A MANUAL MOTOR STARTER.
• "DDC" = CONTROL SIGNAL FROM TEMPERATURE CONTROL SYSTEM PROVIDED BY MECHANICAL CONTRACTOR OR TEMPERATURE CONTROLS CONTRACTOR.
• "TIME SW" = CONTROL SIGNAL FROM TIME SWITCH PROVIDED BY ELECTRICAL CONTRACTOR.
• TIME SWITCH SHALL BE 7-DAY DIGITAL TYPE WITH AUTOMATIC DAYLIGHT SAVINGS ADJUSTMENTS AND BATTERY BACKUP. LOCATE TIMESWITCH IN NEAREST MECHANICAL OR ELECTRICAL UTILITY ROOM.
LABEL TIME SWITCH. COORDINATE TIME SCHEDULE WITH OWNER AND MECHANICAL ENGINEER.
• "WALL SW" = CONTROL SIGNAL FROM WALL SWITCH PROVIDED BY ELECTRICAL CONTRACTOR.
• COORDINATE LOCATION OF WALL SWITCH WITH OWNER. LABEL WALL SWITCH.
• "FA STOP" = FANS WITH CFM OF 2000 OR GREATER AND FANS SERVING DUCTS CONTAINING SMOKE DAMPERS.
• PROVIDE FIRE ALARM SYSTEM DUCT SMOKE DETECTORS AT RETURN-SIDE AND SUPPLY-SIDE OF FAN/UNIT. PROVIDE MULTIPLE DETECTORS IF REQUIRED TO ACCOMMODATE MAIN DUCT TAKE-OFFS WHERE A
SINGLE DETECTOR CANNOT BE INSTALLED TO CAPTURE ALL AIRFLOW. FIRE ALARM SYSTEM SHALL SHUTDOWN FAN UPON DETECTION OF SMOKE IN DUCT OR ROOMS SERVED FROM THIS EQUIPMENT.
PROVIDE WITH INDIVIDUAL FIRE ALARM SYSTEM ADDRESSABLE CONTROL MODULE AT MOTOR CONTROLLER/STARTER AND CONNECT TO SHUTDOWN FAN.
• "WF STOP" = HIGH VOLUME LOW SPEED (HVLS) FANS SHUT DOWN HVLS FAN UPON WATERFLOW ALARM. PROVIDE WITH INDIVIDUAL FIRE ALARM SYSTEM ADDRESSABLE CONTROL MODULE AT MOTOR AND
CONNECT TO SHUT DOWN FAN.
• "FA START" = FANS USED FOR SMOKE EVACUATION OR PRESSURIZATION.
• FIRE ALARM SYSTEM SHALL START FAN UPON DETECTION OF SMOKE IN DUCT OR ROOMS SERVED FROM THIS EQUIPMENT. PROVIDE WITH INDIVIDUAL FIRE ALARM SYSTEM ADDRESSABLE CONTROL MODULE
AT MOTOR CONTROLLER/STARTER AND CONNECT TO START FAN.
• "DATA" = PROVIDE WITH DATA CONNECTION FROM NEAREST DATA NETWORK COMMUNICATIONS ROOM.
• "CONDUIT" = PROVIDE EMPTY 3/4" CONTROLS CONDUIT BETWEEN INDOOR AND OUTDOOR UNIT TO ACCOMMODATE CONTROL CABLING BY MECHANICAL OR TEMPERATURE CONTROLS CONTRACTOR.
D. "DISCONNECT BY" :
• "MECHANICAL" = DISCONNECT IS FURNISHED BY MECHANICAL CONTRACTOR OR PROVIDED WITH MECHANICAL EQUIPMENT.
• ELECTRICAL CONTRACTOR SHALL PROVIDE MOUNTING AND ADDITIONAL CONNECTIONS REQUIRED FOR LOOSE DISCONNECTS FURNISHED BY THE MECHANICAL CONTRACTOR.
• "ELECTRICAL" = DISCONNECT IS FURNISHED BY ELECTRICAL CONTRACTOR. COORDINATE EXACT REQUIREMENTS WITH EQUIPMENT FURNISHED BY MECHANICAL CONTRACTOR.
• "MANUFACTURER" = DISCONNECT IS FURNISHED BY EQUIPMENT MANUFACTURER. ELECTRICAL CONTRACTOR SHALL PROVIDE MOUNTING AND ADDITIONAL CONNECTIONS REQUIRED FOR LOOSE DISCONNECTS
FURNISHED BY EQUIPMENT MANUFACTURER.
E. "DISCONNECT TYPE" - PROVIDE DISCONNECT/RECEPTACLE AT EQUIPMENT LOCATION AND ASSOCIATED CONNECTION TO EQUIPMENT AND BRANCH CIRCUIT:
• "NEMA-___" = DUPLEX (TYP) RECEPTACLE TO ACCOMMODATE CORD AND PLUG CONNECTION (CORD AND PLUG FURNISHED WITH EQUIPMENT UNLESS NOTED OTHERWISE)
• "REC/SW" = PROVIDE 20A 120V RECEPTACLE OR 20A TOGGLE SWITCH DISCONNECT.
• COORDINATE REQUIRED SELECTION WITH EQUIPMENT.
• "NF" = NON-FUSED DISCONNECT. SIZE AND POLE QUANTITY AS INDICATED. 20/1 AND SMALLER SHALL BE TOGGLE SWITCH DISCONNECT.
• "F" = FUSED DISCONNECT. SIZE AND POLE QUANTITY AS INDICATED.
• FUSE PER MANUFACTURER'S RECOMMENDATIONS.
• "FUSTAT" = SWITCH AND FUSTAT. FUSE SIZE PER EQUIPMENT MANUFACTURER.
• LOCATE SWITCH IN CONCEALED ACCESSIBLE LOCATION.
• "ENCL CB" = ENCLOSED CIRCUIT BREAKER DISCONNECT.
• SIZE, POLE QUANTITY, AND FLUSH/SURFACE MOUNTING AS INDICATED.
• "ENCL MCSW" = ENCLOSED MOLDED CASE SWITCH DISCONNECT.
• SIZE, POLE QUANTITY, AND FLUSH/SURFACE MOUNTING AS INDICATED.
• "SHUNT ENCL CB" = SHUNT TRIP ENCLOSED CIRCUIT BREAKER DISCONNECT.
• SIZE, POLE QUANTITY, AND FLUSH/SURFACE MOUNTING AS INDICATED. PROVIDE WITH INTEGRAL 120V CONTROL TRANSFORMER SERVED FROM LINE SOURCE WITH PRIMARY AND SECONDARY FUSING.
COORDINATE ENCLOSURE AND COVER SIZE TO ACCOMMODATE TRANSFORMER. PROVIDE WITH EQUIPMENT GROUND BAR AND SEPARATE INSULATED ISOLATED GROUND BAR. WHERE NEUTRAL CONDUCTOR IS UTILIZED. PROVIDE SOLID NEUTRAL BAR. CONNECT SHUNT TRIP VOLTAGE SOURCE AND ACTUATOR TO ASSOCIATED EMERGENCY POWER (EPO) SWITCHES. PROVIDE EPO AND COORDINATE
LOCATION.
• "LOCK CB" = CIRCUIT BREAKER CAPABLE OF BEING LOCKED IN THE OPEN POSITION, LOCATED IN THE SOURCE ELECTRICAL PANEL. THE PROVISIONS FOR LOCKING MUST REMAIN IN PLACE WITH OR WITHOUT THE
LOCK INSTALLED.
• "MAG" = COMBINATION MAGNETIC MOTOR STARTER WITH DISCONNECT (COORDINATE COIL VOLTAGE WITH CONTROL SOURCE). LOCATE COMBINATION MAGNETIC MOTOR STARTER TO SERVE AS THE MOTOR DISCONNECT. WHERE STARTER SERVES OUTDOOR EQUIPMENT, LOCATE STARTER IN THE SOURCE ELECTRICAL ROOM.
• "MAN" = COMBINATION MANUAL MOTOR STARTER WITH DISCONNECT. LOCATE COMBINATION MANUAL MOTOR STARTER TO SERVE AS THE MOTOR DISCONNECT. WHERE STARTER SERVES OUTDOOR
EQUIPMENT, LOCATE STARTER IN THE SOURCE ELECTRICAL ROOM.
• "VFD" = VARIABLE FREQUENCY DRIVE CONTROLLER. LOCATE VARIABLE FREQUENCY DRIVE CONTROL TO SERVE AS THE MOTOR DISCONNECT.
• "INT" = DISCONNECT IS MANUFACTURED INTEGRAL TO THE EQUIPMENT.
• "HW" = HARDWIRE. DISCONNECT NOT REQUIRED.
• LOCATE DISCONNECT ADJACENT TO EQUIPMENT PER NEC - PROVIDE WITH STRUT MOUNTING AS REQUIRED.
• LOCATE RECEPTACLE OR JUNCTION BOX TO DIRECTLY SERVE EQUIPMENT.
• COORDINATE EXACT LOCATION WITH ARCHITECT, ARCHITECTURAL DETAILS, AND EQUIPMENT MANUFACTURER'S REQUIREMENTS.
• WHERE DISCONNECT SERVES OUTDOOR EQUIPMENT, PROVIDE AS NEMA-3R.
• PROVIDE DISCONNECT WITH EQUIPMENT GROUND KIT.
• WHERE FEEDER INDICATED UTILIZES A NEUTRAL, PROVIDE DISCONNECT WITH SOLID NEUTRAL KIT.
• WHERE FEEDER INDICATED UTILIZES AN ISOLATED GROUND, PROVIDE DISCONNECT WITH ADDITIONAL INSULATED GROUND KIT.
• DISCONNECTS NOT SHOWN AS "F" OR "NF" SHALL BE NON-FUSED.
• DISCONNECTS OF MOTORS SERVED FROM A VFD SHALL CONTAIN AUXILIARY CONTACTS CONNECTED TO THE VFD TO DISABLE VFD UPON DISCONNECTION.
• WHERE STARTERS OR VFD'S CONTAIN INTEGRAL DISCONNECTS AND ARE LOCATED PER NEC TO SATISFY AS THE EQUIPMENT DISCONNECT, AN ADDITIONAL EQUIPMENT DISCONNECT IS NOT REQUIRED.
F. "GEN" - EQUIPMENT IS SERVED FROM A SOURCE PANEL PROVIDED WITH GENERATOR BACK-UP.
G. "SCCR" - VALUE INDICATED IS AVAILABLE SHORT CIRCUIT CURRENT (SCC) IN KILOAMPS AT THE EQUIPMENT BASED ON PRELIMINARY DESIGN PHASE CALCULATIONS. EQUIPMENT SCCR SHALL BE MINIMUM 120% OF
THE AVAILABLE SCC. RATING SHALL BE ADJUSTED IF REQUIRED BASED ON FINAL SCC CALCULATION. EQUIPMENT INDICATED WITH 5 KA MAY BE PROVIDED WITH 5 KA SCCR.
REMARKS: (LIGHTING FIXTURE SCHEDULE)
1. PENDANT/SUSPENSION MOUNTING - COORDINATE EXACT LOCATION, MOUNTING ELEVATION, AND REQUIRED
PENDANT/SUSPENSION LENGTH WITH ARCHITECT AND ARCHITECTURAL DETAILS.
GENERAL NOTES: (LIGHTING FIXTURE SCHEDULE)
A. CATALOG NUMBER VERIFICATION - CONTRACTOR SHALL VERIFY LIGHTING FIXTURE INSTALLATION REQUIREMENTS
AND CATALOG NUMBER PRIOR TO ORDERING.
B. SUBSTITUTIONS - WHERE INDICATED WITH 'N' (NO), NO SUBSTITUTIONS WILL BE ACCEPTED. WHERE INDICATED WITH
'P' (PRIOR APPROVAL), SUBSTITUTIONS MUST BE APPROVED PRIOR TO BID WITH ACCEPTANCE ISSUED BY ADDENDUM.
WHERE INDICATED WITH 'Y' (YES), THE FOLLOWING MANUFACTURER'S ARE CONSIDERED ACCEPTABLE EQUIVALENT MANUFACTURER'S, PROVIDED THE EQUIVALENT FIXTURE IS OF THE SAME QUALITY, EFFICIENCY, PERFORMANCE AND
CHARACTERISTICS AS THAT SCHEDULED:
1. ACUITY BRANDS
2. EATON/COOPER BRANDS
3. HUBBELL
4. WILLIAMS
5. PHILLIPS/SIGNIFY BRANDS
C. FIXTURE FINISH - WHERE CATALOG NUMBER LISTED INDICATES '**' IN LIEU OF MANUFACTURER'S FINISH OPTION, COORDINATE WITH ARCHITECT FOR EXACT FINISH PRIOR TO ORDERING.
10360 Ellison Circle Omaha, NE 68134 Phone:
402.991.5520
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :
DESIGNER OF RECORDCONSULTANT
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project: 23.1019.05 10/03/2025
100% CONSTRUCTION DOCUMENTS 10/03/2025
/3
/2
:1
:0
P
M
A u to d e s k D o c s /2
.0
V A
L o v e ll E le v a to r
U p g ra d e /5
-5
.B u ild in g
.E
R
.r v t
B04-E700
ELECTRICAL SCHEDULES Elevator Upgrade
3001 GREEN BAY RD, NORTH CHICAGO, IL 60064
556-24-115
B04
09/12/2025 KB RC
23022.012
EQUIPMENT CONNECTION SCHEDULE
MARK DESCRIPTION ROOM NAME ROOM # HP KW FLA MCA MOCP VOLTS PHASE POLES
LOAD
[VA]
CONTROL
TYPE
DISCONNECT
BY
DISCONNECT
TYPE FEEDER PANEL
CIRCUIT
NUMBER SCCR GEN REMARKS
SP-04-300 SUMP PUMP ELEVATOR 1-EL-P23 0.5 0 8 0 20 120 1 1 960 INT ELECTRICAL NF 30/1 (1M1) (1/6 - 1 HP 120V) 2-#12 CU, #12 CU GND - 3/4"C. 4-DP-001-211 38 0 No
SS-04-300 DUCT FREE SPLIT SYSTEM - INDOOR 0 0 0 0 0 0 0 1 0 DDC MECHANICAL NF 30/2 0 No
SS-04-CU DUCT FREE SPLIT SYSTEM -
OUTDOOR
0 0 0 14.2 20 208 1 2 2960 DDC ELECTRICAL NF 30/2 (2X) (20A) 2-#12 CU, #12 CU GND - 3/4"C. 4-DP-001-211 40,42 0 No
UH-04-300 UNIT HEATER 0 10 28.5 0 35 208 3 3 10000 DDC ELECTRICAL NF 60/3 (4) (40A) 3-#8 CU, #10 CU GND - 3/4"C. 4-DP-001-211 25,27,29 0 No
LIGHTING FIXTURE SCHEDULE
MARK DESCRIPTION SUBS MANUFACTURER CATALOG # (NOTE A)
LAMP /
NOMINAL
LUMENS CCT
MINIMUM
CRI VOLTAGE
INPUT
WATTS MOUNTING REMARKS
K1 INDUSTRIAL STRIP - 4'-0" Y LITHONIA CLX-L48-3000LM-SEF-RDL-MVOLT-GZ10-35
K-80CRI-WH
3000 3500 80 120 V 22 SUSPENDED 1
A. PANEL AIC (INTERRUPTING) RATING SHALL BE MINIMUM 120% OF THE AVAILABLE SCC (SHORT CIRCUIT CURRENT).
GENERAL REMARKS:
CIRCUIT BREAKER OPTIONS SUFFIX: 'S' OR 'ST' - PROVIDE SHUNT TRIP CIRCUIT BREAKER / 'G' OR 'GFCI' - PROVIDE GFCI CIRCUIT BREAKER / 'GFP' - PROVIDE GFP CIRCUIT BREAKER / 'ERMS' - ENERGY REDUCING MAINTENANCE SWITCH / 'ZSI' - ZONE SELECTIVE INTERLOCKING / 'L' - PROVIDE CIRCUIT BREAKER WITH LOCKING PROVISIONS / 'R'
- PROVIDE CIRCUIT BREAKER WITH RED MARKING
OPTIONS:
1 A
SPARE CAPACITY:
100 %
FEEDER AVAILABLE:
EQUIPMENT AMPS: 1 A
CONSIDER 125% DEMAND: 0 A
DEMAND CURRENT: 0 A
DEMAND LOAD: 0 VA
CONNECTED CURRENT: 0 A
CONNECTED LOAD: 0 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
TOTAL AMPS: 0 A 0 A 0 A
TOTAL LOAD: 0 VA 0 VA 0 VA
41 SPACE -- -- 1 -- -- 1 -- -- SPACE 42
39 SPACE -- -- 1 -- -- 1 -- -- SPACE 40
37 SPACE -- -- 1 -- -- 1 -- -- SPACE 38
35 SPACE -- -- 1 -- -- 1 -- -- SPACE 36
33 SPACE -- -- 1 -- -- 1 -- -- SPACE 34
31 SPACE -- -- 1 -- -- 1 -- -- SPACE 32
29 0 VA 0 VA 1 20 A -- FIRE ALARM 30
ELECTRIC HTR -- 20 A 2
0 VA 0 VA 1 20 A -- FIRE ALARM 28
25 0 VA 0 VA 1 20 A -- AUTO DOOR 26
ELECTRIC HTR -- 20 A 2
0 VA 0 VA 1 20 A -- LTG TRAMWAY 24
21 0 VA 0 VA 1 20 A -- LGT TRAMWAY 22
ELECTRIC HTR -- 20 A 2
0 VA 0 VA 1 20 A -- LTG TRAMWAY 20
17 DATA CLOSET LTG -- 20 A 1 0 VA 0 VA 1 20 A -- EM LTG 1ST FLR 18
15 DATA CLOSET OUTLET -- 20 A 1 0 VA 0 VA 1 20 A -- EM LTG 1ST FLR 16
13 0 VA 1 20 A -- EM LTG 1ST FLR 14
11 0 VA 1 20 A -- EM LTG 1ST FLR 12
9 STAIR LTG -- 20 A 1 0 VA 0 VA 1 20 A -- EM LTG 1ST FLR 10
7 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- EM LTG 1ST FLR 8
5 EMERGENCY LTG SECOND FLR -- 20 A 1 0 VA 0 VA 1 20 A -- EM LTG 1ST FLR 6
3 EMERGENCY LTG SECOND FLR -- 20 A 1 0 VA 0 VA 1 20 A -- EM LTG 1ST FLR 4
1 EMERGENCY LTG -- 20 A 1 0 VA 0 VA 1 20 A -- EM LTG 1ST FLR 2
CKT CIRCUIT DESCRIPTION OPT RATING POLES A B C POLES RATING OPT CIRCUIT DESCRIPTION CKT
NEMA ENCLOSURE:
MOUNTING: SURFACE AVAILABLE SCC (kA): PANEL POLES: 42
SERVICE RATED: INTEGRAL SPD: SECTIONS: 1
BRANCH: EEMRGENCY WIRES: 4 MCB OPTIONS:
SUPPLY FROM: PHASES: 3 MCB/MLO RATING: 1 A
LOCATION: ELECTRICAL RM 109 VOLTS: 208/120 WYE MAINS TYPE: MCB
LIGHTING PANEL: 4-EPNL-001-109
A. PANEL AIC (INTERRUPTING) RATING SHALL BE MINIMUM 120% OF THE AVAILABLE SCC (SHORT CIRCUIT CURRENT).
GENERAL REMARKS:
CIRCUIT BREAKER OPTIONS SUFFIX: 'S' OR 'ST' - PROVIDE SHUNT TRIP CIRCUIT BREAKER / 'G' OR 'GFCI' - PROVIDE GFCI CIRCUIT BREAKER / 'GFP' - PROVIDE GFP CIRCUIT BREAKER / 'ERMS' - ENERGY REDUCING MAINTENANCE SWITCH / 'ZSI' - ZONE SELECTIVE INTERLOCKING / 'L' - PROVIDE CIRCUIT BREAKER WITH LOCKING PROVISIONS / 'R'
- PROVIDE CIRCUIT BREAKER WITH RED MARKING
OPTIONS:
252 A
SPARE CAPACITY:
83 %
FEEDER AVAILABLE:
EQUIPMENT AMPS: 300 A
CONSIDER 125% DEMAND: 21750 A
DEMAND CURRENT: 48 A
DEMAND LOAD: 17400 VA
CONNECTED CURRENT: 39 A
MEQ-C 13920 VA 125.00% 17400 VA CONNECTED LOAD: 13920 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
TOTAL AMPS: 36 A 41 A 41 A
TOTAL LOAD: 4293 VA 4813 VA 4813 VA
41 SPACE -- -- 1 -- 1480 VA 42
39 SPACE -- -- 1 -- 1480 VA
2 20 A SS-04-CU
37 SPACE -- -- 1 -- 960 VA 1 20 A SP-04-300 38
35 SPACE -- -- 1 -- 0 VA 1 20 A -- EXISTING 36
33 SPACE -- -- 1 -- 0 VA 1 20 A -- DAMPER 34
31 SPACE -- -- 1 -- -- 1 -- -- SPACE 32
29 3333 VA 0 VA 30
27 3333 VA 0 VA 28
UH-04-300 35 A 3
3333 VA 0 VA
3 15 A -- EF
23 0 VA 0 VA 1 20 A -- EXISTING 24
21 0 VA 0 VA 1 20 A -- EXISTING 22
4-EF-5 -- 30 A 3
0 VA 0 VA 1 20 A -- LTG 20
17 0 VA 0 VA 1 20 A -- REC 18
15 0 VA 0 VA 1 20 A -- REC 16
4-RAH-2 -- 15 A 3
0 VA 0 VA 1 20 A -- LTG 14
11 0 VA 0 VA 12
9 0 VA 0 VA 10
4-SF-5 -- 20 A 3
0 VA 0 VA
3 50 A -- 4-ACCU-3
5 0 VA 0 VA 6
3 0 VA 0 VA 4
4-EF-2 -- 90 A 3
0 VA 0 VA
3 80 A -- 4-SF-2
CKT CIRCUIT DESCRIPTION OPT RATING POLES A B C POLES RATING OPT CIRCUIT DESCRIPTION CKT
NEMA ENCLOSURE: 1
MOUNTING: SURFACE AVAILABLE SCC (kA): EXISTING PANEL POLES: 42
SERVICE RATED: No INTEGRAL SPD: No SECTIONS: 1
BRANCH: NORMAL WIRES: 4 MCB OPTIONS: -
SUPPLY FROM: PHASES: 3 MCB/MLO RATING: 300 A
LOCATION: MECH RM 211 VOLTS: 208/120 WYE MAINS TYPE: MCB
LIGHTING PANEL: 4-DP-001-211
B07-E400
MDP
E EM PANEL
E
LAUNDRY
CORRIDOR
CO-B-18
HEAT DUCT SHAFT
STORAGE
STO
014A
STO
012A
STORAGE
STORAGE
TLT
STORAGE
TLT
STAIR
STORAGE
STORAGE
STORAGE
CORRIDOR
CO-B-01
STORAGE
009A
CORRIDOR
CO-B-09
FIRE ALARM PANEL
CORRIDOR
CO-B-01A
ELEVATOR
P-22
STORAGE
SPRINKLER ROOM
STORAGE
CORRIDOR
CO-B-18A
CORRIDOR
CO-B-17
STORAGE
10360 Ellison Circle Omaha, NE 68134 Phone:
402.991.5520
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :
DESIGNER OF RECORDCONSULTANT100% CONSTRUCTION DOCUMENTS 10/03/2025
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project: 23.1019.05
E
A CB
D FE
G IH
KEYPLAN
100% CONSTRUCTION
DOCUMENTS
10/03/2025
/3
/2
:2
:5
P
M
A u to d e s k D o c s /2
.0
V A
L o v e ll E le v a to r
U p g ra d e /5
-5
.B u ild in g
.E
R
.r v t
B07-ED100
BASEMENT LEVEL FLOOR PLAN - OVERALL -
ELECTRICAL - DEMOLITION
Elevator Upgrade
3001 N GREEN BAY RD, NORTH CHICAGO, IL 60064
556-24-115
B07
10/03/2025 KB RC
23022.012
3/32" = 1'-0"
BASEMENT LEVEL FLOOR PLAN - OVERALL - ELECTRICAL - DEMOLITION
5 5 10 15 20 25 30
3/32" = 1'-0"
FEETSCALE
CHASE
CO-1-8B
OFFICE
OFFICE
OFFICE
CORRIDOR
CO-01-06
OFFICE
OFFICE
OFFICE
CHASE
CO-1-5B
STORAGE
138A
BREAK/LOCKER
JAN
MEDICINE
MEDICINE
JAN
131A
OFFICE
OFFICE
SUPPLY
DUCT SHAFT
OFFICE
OFFICE
STORAGE
130A
STORAGE
130B
CORRIDOR
CORRIDOR
CO-1-02
STAIR
CONFERENCE
OFFICE
OFFICE
DUCT SHAFT
OFFICE
130 TEL/DATA
CO-1-5A
GROUP THERAPY
BREAK ROOM
OFFICE
OFFICE
130C
ELEVATOR
P-22
SUPPLY
TOILET
TEL/DATA
CO-1-8A
CORRIDOR
CO-1-08
JAN
PORCH
CO-2-09
PORCH
CO-2-10
STAIR
NAVY MESS
OFFICE
OFFICE
OFFICE
CORRIDOR
CO-1-09
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
CORRIDOR
CO-1-04
OFFICE
OFFICE
OFFICE
SHOWER
113A
CONFERENCE
TOILET
141A
BATH/SHOWER
TOILET
CORRIDOR
TRAMWAY
STAIR
10360 Ellison Circle Omaha, NE 68134 Phone:
402.991.5520
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :
DESIGNER OF RECORDCONSULTANT100% CONSTRUCTION DOCUMENTS 10/03/2025
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project: 23.1019.05
E
A CB
D FE
G IH
KEYPLAN
100% CONSTRUCTION
DOCUMENTS
10/03/2025
/3
/2
:2
:5
P
M
A u to d e s k D o c s /2
.0
V A
L o v e ll E le v a to r
U p g ra d e /5
-5
.B u ild in g
.E
R
.r v t
B07-ED101
FIRST LEVEL FLOOR PLAN - OVERALL -
ELECTRICAL - DEMOLITION
Elevator Upgrade
3001 N GREEN BAY RD, NORTH CHICAGO, IL 60064
556-24-115
B07
10/03/2025 KB RC
23022.012
3/32" = 1'-0"
FIRST LEVEL FLOOR PLAN - OVERALL - ELECTRICAL - DEMOLITION
5 5 10 15 20 25 30
3/32" = 1'-0"
FEETSCALE
1-BED PATIENT
CHASE
234A
DAY ROOM
DAY ROOM
CHASE
214A
CONFERENCE
OFFICE
OFFICE
OFFICE
KITCHEN
215A
WEIGHT ROOM
2-BED PATIENT
HEAT DUCT
CO-2-03
1-BED PATIENT
1-BED PATIENT
1-BED PATIENT
1-BED PATIENT
1-BED PATIENT
2-BED PATIENT
JAN
SHOWER
212A
1-BED PATIENT
STO
233A
ELEC
233B
1-BED PATIENT
OFFICE
OFFICE
OFFICE
1-BED PATIENT
OFFICE
OFFICE
OFFICE
CORRIDOR
2-BED PATIENT
STAIR
1-BED PATIENT
STAIR
SHOWER
236A
CORRIDOR
CO-2-06
LINEN
CORRIDOR
CO-2-07
ELEVATOR
P-2-22
OFFICE
CORRIDOR-1
CO-2-01-1
PORCH
CO-2-08
PORCH
CO-2-11
JAN
LAUNDRY
TOILET
LAUNDRY
TOILET
OFFICE
BREAK ROOM
TOILET
MALE TOILET
STORAGE
1-BED PATIENT
1-BED PATIENT
CONFERENCE
TEL / DATA
CORRIDOR
CO-2-04
TEL/DATA
STAIR
CORRIDOR-2
CO-2-01-2
1-BED PATIENT
207 CORRIDOR
CO-2-02
CORRIDOR-3
CO-2-01-3
10360 Ellison Circle Omaha, NE 68134 Phone:
402.991.5520
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :
DESIGNER OF RECORDCONSULTANT100% CONSTRUCTION DOCUMENTS 10/03/2025
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project: 23.1019.05
E
A CB
D FE
G IH
KEYPLAN
100% CONSTRUCTION
DOCUMENTS
10/03/2025
/3
/2
:2
:5
P
M
A u to d e s k D o c s /2
.0
V A
L o v e ll E le v a to r
U p g ra d e /5
-5
.B u ild in g
.E
R
.r v t
B07-ED102
SECOND LEVEL FLOOR PLAN - OVERALL -
ELECTRICAL - DEMOLITION
Elevator Upgrade
3001 N GREEN BAY RD, NORTH CHICAGO, IL 60064
556-24-115
B07
10/03/2025 KB RC
23022.012
3/32" = 1'-0"
SECOND LEVEL FLOOR PLAN - OVERALL - ELECTRICAL - DEMOLITION
5 5 10 15 20 25 30
3/32" = 1'-0"
FEETSCALE
10360 Ellison Circle Omaha, NE 68134 Phone:
402.991.5520
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :
DESIGNER OF RECORDCONSULTANT100% CONSTRUCTION DOCUMENTS 10/03/2025
1221 N. Pennsylvania St.
Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com
GD Project: 23.1019.05
E
A CB
D FE
G IH
KEYPLAN
100% CONSTRUCTION
DOCUMENTS
10/03/2025
/3
/2
:2
:5
P
M
A u to d e s k D o c s /2
.0
V A
L o v e ll E le v a to r
U p g ra d e /5
-5
.B u ild in g
.E
R
.r v t
B07-ED103
PENTHOUSE LEVEL FLOOR PLAN - OVERALL -
ELECTRICAL - DEMOLITION
Elevator Upgrade
3001 N GREEN BAY RD, NORTH CHICAGO, IL 60064
556-24-115
B07
10/03/2025 KB RC
23022.012
3/32" = 1'-0"
PENTHOUSE PLAN - OVERALL - ELECTRICAL - DEMOLITION
5 5 10 15 20 25 30
3/32" = 1'-0"
FEETSCALE
LAUNDRY
CORRIDOR
CO-B-18
HEAT DUCT SHAFT
STORAGE
STO
014A
STO
012A
STORAGE
STORAGE
TLT
STORAGE
TLT
STAIR
STORAGE
STORAGE
STORAGE
CORRIDOR
CO-B-01
STORAGE
009A
CORRIDOR
CO-B-09
FIRE ALARM PANEL
CORRIDOR
CO-B-01A
ELEVATOR
P-22
STORAGE
SPRINKLER ROOM
STORAGE
CORRIDOR
CO-B-18A
CORRIDOR
CO-B-17
STORAGE
B07-E400
B07-E400
MDP
EM PANEL
7-PNL-001-24
10360…