Attachment 4 - Drawings V3 of 5 - 56-24-115 - N Chicago Elevator Upgrades.pdf

PDF 10 MB Posted

Attached to
J035--Elevator Upgrade NRM Construction Project 556-24-115 James A. Lovell Federal Health Care Center, North Chicago, IL 60064
Solicitation number
36C77626R0048
Issued by

About this file

This document is a comprehensive set of electrical construction drawings for elevator upgrades at the James A. Lovell Federal Health Care Center (FHCC) in North Chicago, Illinois, specifically addressing project 556-24-115. The drawings encompass multiple buildings (B04, B07, B66, B131, B133CA, and B195) and include detailed electrical plans, schematics, and specifications for the installation of new elevator systems and related electrical infrastructure. The work involves complete demolition and replacement of existing elevator equipment, with new installations requiring coordination with final elevator manufacturer specifications. Key electrical components include new shunt trip disconnects, elevator controllers, fire alarm integration systems, smoke detectors, heat detectors, sump pump control panels, and dedicated lighting circuits. All work must comply with NFPA 70 (NEC) Article 620 for elevator installations and NFPA 72 for fire alarm systems.

The drawings specify extensive coordination requirements with multiple trades, including mechanical contractors for HVAC systems, fire suppression contractors for sprinkler coordination, and telecommunications for data cable routing. Critical electrical requirements include Category 6 network data cables from server/communications rooms to elevator machine rooms, fire-rated wall penetration systems with UL-listed fire stopping, bonding to existing lightning protection systems, and arc flash hazard mitigation through selective coordination of protective devices. Special provisions address wet location wiring in elevator pits (within 48 inches of floor), emergency power systems for elevator cab lights, and automatic transfer switches where elevators connect to emergency generators. All panels and disconnects must achieve minimum 120 percent of available short circuit current ratings, with specific attention to proper grounding, neutral conductor isolation, and equipment ground specifications throughout the installation scope.

View the file

Other files

File Type Posted
36C77626R0048 0005.docx DOCX document
FAR 52.222-90 - Addressing DEI Discrimination by Federal Contractors - APR 2026.docx DOCX document
RFI Responses - Elevator Upgrade N Chicago.pdf PDF
36C77626R0048 0004.docx DOCX document
36C77626R0048 0003.docx DOCX document
36C77626R0048 0002.docx DOCX document
Attachment 2 - Elevator Site Visit Sign In - 556-24-115.pdf PDF
Attachment 1 - Site Visit Agenda - 556-24-115.pdf PDF
Site Visit Instructions Rev 03272026.pdf PDF
36C77626R0048 0001.docx DOCX document
Attachment 3 - Drawings V2 of 5 - 56-24-115 - N Chicago Elevator Upgrades.pdf PDF
Attachment 9 - PCRA - 556-24-115.pdf PDF
Attachment 5 - Drawings V4 of 5 - 56-24-115 - N Chicago Elevator Upgrades.pdf PDF
36C77626R0048_1.docx DOCX document
Attachment 13 - Site Visit Instructions - 556-24-115.docx DOCX document
Attachment 7 - Statement of Work - 556-24-115.docx DOCX document
Attachment 10 - DBA WD IL20260009 01092026.pdf PDF
Attachment 12 - RFI Tracking Sheet - 36C77626R0048.docx DOCX document
Attachment 2 - Drawings V1 of 5 - 56-24-115 - N Chicago Elevator Upgrades.pdf PDF
Attachment 1 - Specifications - 556-24-115 - N Chicago Elevator Upgrades.pdf PDF
Attachment 8 - ICRA Combined Docs - 556-24-115.pdf PDF
Attachment 6 - Drawings V5 of 5 - 56-24-115 - N Chicago Elevator Upgrades.pdf PDF
Attachment 11 - Limitations on Subcontracting.docx DOCX document
Show all 23

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ELECTRICAL ABBREVIATIONS

ABBREVIATION DESCRIPTION

REFER TO OTHER SCHEDULES AND NOTES FOR ADDITIONAL ABBREVIATIONS.

MOUNTING HEIGHT TO CENTERLINE (ABOVE FINISHED FLOOR)

AMPERE

AMPERE FRAME

ABOVE FINISHED FLOOR

ALUMINUM

AMPERE TRIP

CEILING

CIRCUIT BREAKER

CORRELATED COLOR TEMPERATURE

COPPER

DATA (WHEN APPLIED TO COMMUNICATIONS OUTLET)

DEMO (WHEN APPLIED TO EXISTING/DEMO ITEMS)

EXISTING

ELECTRICALLY OPERATED

ENERGY REDUCING MAINTENANCE SWITCH

FUSE

FULL LOAD AMPS

GROUND FAULT CIRCUIT INTERRUPTER

GROUND FAULT ALARM

GROUND FAULT PROTECTION

HORSEPOWER

KILOAMPERE INTERRUPTING CAPACITY

KILOVOLT AMPERE

KILOWATT

MAXIMUM

MINIMUM CIRCUIT AMPS

MAIN CIRCUIT BREAKER

MINIMUM

MAIN LUGS ONLY

MANUALLY OPERATED

NORMALLY CLOSED

NON-FUSED

NOT IN CONTRACT

NORMALLY OPEN

POLES

PARTIAL

RELOCATE

SHORT CIRCUIT CURRENT RATING

SURGE PROTECTIVE DEVICE

SHUNT TRIP

TYPICAL

UNLESS NOTED OTHERWISE

VOICE

WALL PHONE

WIRE

WEATHER RESISTANT

TRANSFORMER

ZONE SELECTIVE INTERLOCKING

A

AF

AFF

AL

AT

C

CB

CCT

CU

D

D

E

EO

ERMS

F

FLA

G, GFCI

GFA

GFP

HP

KAIC

KVA

KW

MAX

MCA

MCB

MIN

MLO

MO

NC

NF

NIC

NO

P

PART

R

SCCR

SPD

ST

TYP

UNO

V

W

W

WR

XFMR

ZSI

A. BRANCH CIRCUITS WITH A TOTAL LENGTH LONGER THAN 75' SHALL UTILIZE #10 AWG CONDUCTORS.

RECEPTACLE BRANCH CIRCUITS WITH A TOTAL LENGTH LONGER THAN 150' SHALL UTILIZE #8 AWG

CONDUCTORS. THIS SHALL APPLY TO 20A BRANCH CIRCUITS.

B. FOR ALL CONDUIT AND OTHER ITEMS PENETRATING A FIRE RATED WALL, PROVIDE UL LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL CONSTRUCTION ASSEMBLY AND COMPLIANT WITH ASTM E814. INSTALL SYSTEM IN STRICT COMPLIANCE WITH THE FIRE STOPPING MANUFACTURER’S U.L. APPROVED DETAIL. WHERE EXISTING WALLS ARE BEING UPGRADED TO FIRE RATED WALLS OR THE FIRE RATING IS BEING MODIFIED, PROVIDE U.L. LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM FOR ALL NEW AND EXISTING PENETRATIONS. REFER TO THE ARCHITECTURAL LIFE

SAFETY PLANS FOR LOCATIONS OF FIRE RATED WALLS.

C. NEW ROOF MOUNTED EQUIPMENT SHALL BE BONDED TO EXISTING BUILDING LIGHTNING PROTECTION SYSTEM IF ONE EXISTS. PROVIDE AIR TERMINALS ON TOP OF EQUIPMENT AND BOND TO EXISTING SYSTEM PER NFPA 780 AND UL 96A REQUIREMENTS. PROVIDE UL INSPECTION AND/OR LPI SYSTEM INSPECTION AS REQUIRED TO OBTAIN UL MASTER LABEL RECERTIFICATION, UL MASTER LABEL AND/OR LPI SYSTEM

CERTIFICATE.

D. ANY ITEMS DAMAGED BY THE CONTRACTOR SHALL BE REPLACED BY THE CONTRACTOR, AT NO ADDITIONAL

COST TO THE OWNER.

E. NEW WIRING DEVICES AND ASSOCIATED COVERPLATES SHALL MATCH EXISTING FINISH OF SIMILAR

INSTALLED DEVICES.

F. THE SELECTED EQUIPMENT AIC RATINGS ARE BASED ON THE IMPEDANCES FOR CONDUCTORS AND TRANSFORMERS USED IN THE CALCULATIONS. IF DIFFERENT EQUIPMENT OR DIFFERENT CONFIGURATIONS

ARE SELECTED FOR INSTALLATION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING

ADEQUATELY RATED EQUIPMENT THAT MEETS APPLICABLE SELECTIVE COORDINATION GOALS AND

PROVIDES SIMILAR INCIDENT ENERGY RISK OF ARC FLASH HAZARDS.

G. PROVIDE AN INSULATED CONTINUOUS COPPER CONDUCTOR, NOT SMALLER THAN #10, TO BOND ALL

NORMAL AND ESSENTIAL ELECTRICAL SYSTEM PANELBOARDS TOGETHER THAT SERVE THE SAME

INDIVIDUAL PATIENT VICINITY AS DEFINED IN NEC 517.14.

H. PROVIDE ADDITIONAL SUPPORTS AS REQUIRED TO INDEPENDENTLY SUPPORT ALL EXISTING TO REMAIN

CABLING.

(GENERAL NOTES SHALL APPLY TO ALL SHEETS)

ELECTRICAL GENERAL NOTES:

10360 Ellison Circle Omaha, NE 68134 Phone:

402.991.5520

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :

DESIGNER OF RECORDCONSULTANT

1221 N. Pennsylvania St.

Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com

GD Project: 23.1019.05 10/03/2025

100% CONSTRUCTION DOCUMENTS 10/03/2025

/3

/2

:1

:4

P

M

A u to d e s k D o c s /2

.0

V A

L o v e ll E le v a to r

U p g ra d e /5

-5

.B u ild in g

.E

R

.r v t

E000

ELECTRICAL SYMBOLS AND ABBREVIATIONS Elevator Upgrade

3001 GREEN BAY RD, NORTH CHICAGO, IL 60064

556-24-115

B04

09/12/2025 KB RC

23022.012

ELECTRICAL FIXTURE

SYMBOLS

PLAN SYMBOL NAME

RECEPTACLE - DUPLEX - CONV

RECEPTACLE - DUPLEX - CONV -

GFCI

RECEPTACLE - DUPLEX -

EMERGENCY (RED) - CONV -

GFCI

FIRE ALARM SYMBOLS

PLAN SYMBOL NAME

DETECTOR - SYSTEM HEAT -

CEILING

DETECTOR - SYSTEM SMOKE -

CEILING

LIGHTING DEVICE SYMBOLS

PLAN SYMBOL NAME

LIGHT SWITCH

ELECTRICAL MISC SYMBOLS

PLAN SYMBOL NAME

BRANCH CIRCUIT CONCEALED IN

CEILING OR WALL

BRANCH CIRCUIT CONCEALED IN

FLOOR OR BELOW GRADE

CLEARANCE SPACE

CONDUIT BREAK

CONDUIT DOWN

CONDUIT STUB-OUT

CONDUIT UP

HOMERUN TO PANEL

G = GFCI CIRCUIT

(PART) = PARTIAL CIRCUIT

LIGHTING FIXTURE

SYMBOLS

PLAN SYMBOL NAME

EMERGENCY HATCH

INDUSTRIAL STRIP LIGHT

PORCELAIN SOCKET

WALL MOUNT - STRIPLIGHT

ONE LINE SYMBOLS

PLAN SYMBOL NAME

AUTOMATIC TRANSFER SWITCH

CONTINUATION

ENCLOSED CIRCUIT BREAKER

GROUND BAR

GROUNDING ELECTRODE

MOTOR STARTER

NON-FUSED DISCONNECT

PANEL BOARD

SWITCHBOARD/SWITCHGEAR

TRANSFORMER

ELECTRICAL EQUIPMENT

SYMBOLS

PLAN SYMBOL NAME

ENCLOSED DISCONNECT

SWITCH - FUSED

ENCLOSED DISCONNECT

SWITCH - NON-FUSED

LOW VOLTAGE PANEL

PANELBOARD - SURFACE

TRANSFORMER - DRY TYPE

FHCC CONDUIT COLOR SCHEME

RED - FIRE ALARM

BLUE - CONTROLS, HVAC, BAS

ORANGE - FIBER OPTIC, COMMUNICATIONS

GREEN - NORMAL POWER

YELLOW - EMERGENCY POWER, CRITICAL POWER

BLACK - SECURITY

PURPLE - MEDICAL SYSTEMS, NURSE CALL

Revisions: Date:

B04-E400

STAIR 4

ST4

Room

Room

Room

Room

Room

Room

Room

Room

STAIR 5

ST5

Room

JANITOR

Room

STAIR 1

ST1WOMEN'S RESTROOM

OFFICE

OFFICE

CONFERENCE ROOM

OFFICE

OFFICE

OFFICE

CONFERENCE ROOM

STORAGE

TMS LAB

OFFICE

163D

OFFICE

163C

OFFICE

163B

OFFICE

163A

STORAGE

166A

COMP RM

ELECTRICAL RM

OFFICE

OFFICE

OFFICE

OFFICE

MEN'S RESTROOM

JANITOR

WOMEN'S RESTROOM

VIRTUAL RECREATION SPACE

Room

209XXXX

SUPPORT RM

139A

DEBBRIEFING

OFFICE

STORAGE

DENTAL LAB

DEBBRIEFING

SKILLS LAB

OR/SURGICAL SIM

MILITARY SIM

CONTROL ROOM

EMT SIM

SHOWER

119A

SHOWER

118A

FEMALE LOCKER RM

Room

MALE LOCKER RM

STAIR 2

ST2

ER SIM

DEPARTMENT HEAD

SIMULATION MANAGER

STAFF SUPPORT

ICU/MED SURGE

COAT RM

CONTROL ROOM

Room

Room

209IIIIIII

ELECTRICAL RM

SERVER RM

STORAGE

116A

Room

114B

EQUIPMENT STORAGE

JANITOR

STORAGE

MEN'S RESTROOM

WOMEN'S RESTROOM

RESOURCE OFFICE

CLASSROOM

MAIN ENTRY

Room

RECEPTION

LOW FIDELITY SKILLS LAB

COFFEE SHOP

CLASSROOM

138B

CLASSROOM

138A

HALLWAY

C106

HALLWAY

C104

HALLWAY

C105

CORRIDOR

C103 Room

114A

CORRIDOR

C102

VENDING RM

SEATING AREA

Room

BREAK-OUT RM

104B

BREAK-OUT RM

104A

CORRIDOR

C100

CAFE SEATING

RESOURCE RM

COPY ROOM

WORK RM

CORRIDOR

C111

CORRIDOR

C110

CORRIDOR-1

C101-1

CORRIDOR-2

C101-2

CORRIDOR

C108

BREAK ROOM

CORRIDOR

C107

THEATER MEZZ

105A

THEATER

MEN'S RESTROOM

Space

ELEVATOR

1-EL-P23

10360 Ellison Circle Omaha, NE 68134 Phone:

402.991.5520

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :

DESIGNER OF RECORDCONSULTANT

1221 N. Pennsylvania St.

Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com

GD Project: 23.1019.05

E

A CB

D FE

G IH

KEYPLAN

10/03/2025

100% CONSTRUCTION DOCUMENTS 10/03/2025

/3

/2

:1

:5

P

M

A u to d e s k D o c s /2

.0

V A

L o v e ll E le v a to r

U p g ra d e /5

-5

.B u ild in g

.E

R

.r v t

B04-ED100

FIRST LEVEL FLOOR

PLAN-OVERALL-ELECTRICAL-DEMOLITION

Elevator Upgrade

3001 GREEN BAY RD, NORTH CHICAGO, IL 60064

556-24-115

B04

09/12/2025 KB RC

23022.012

1/16" = 1'-0"

FIRST LEVEL FLOOR PLAN - OVERALL - ELECTRICAL - DEMOLITION

N

5 5 10 15 20 25 30 35 40 45

1/16" = 1'-0"

FEETSCALE

4-DP-001-211

E

10360 Ellison Circle Omaha, NE 68134 Phone:

402.991.5520

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :

DESIGNER OF RECORDCONSULTANT

1221 N. Pennsylvania St.

Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com

GD Project: 23.1019.05

E

A CB

D FE

G IH

KEYPLAN

10/03/2025

100% CONSTRUCTION DOCUMENTS 10/03/2025

/3

/2

:1

:0

P

M

A u to d e s k D o c s /2

.0

V A

L o v e ll E le v a to r

U p g ra d e /5

-5

.B u ild in g

.E

R

.r v t

B04-ED101

SECOND LEVEL FLOOR

PLAN-OVERALL-ELECTRICAL-DEMOLITION

Elevator Upgrade

3001 GREEN BAY RD, NORTH CHICAGO, IL 60064

556-24-115

B04

09/12/2025 KB RC

23022.012

1/16" = 1'-0"

SECOND LEVEL FLOOR PLAN - OVERALL - ELECTRICAL - DEMOLITION

N

5 5 10 15 20 25 30 35 40 45

1/16" = 1'-0"

10360 Ellison Circle Omaha, NE 68134 Phone:

402.991.5520

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :

DESIGNER OF RECORDCONSULTANT

1221 N. Pennsylvania St.

Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com

GD Project: 23.1019.05

E

A CB

D FE

G IH

KEYPLAN

10/03/2025

100% CONSTRUCTION DOCUMENTS 10/03/2025

/3

/2

:1

:0

P

M

A u to d e s k D o c s /2

.0

V A

L o v e ll E le v a to r

U p g ra d e /5

-5

.B u ild in g

.E

R

.r v t

B04-ED102

PENTHOUSE

PLAN-OVERALL-ELECTRICAL-DEMOLITION

Elevator Upgrade

3001 GREEN BAY RD, NORTH CHICAGO, IL 60064

556-24-115

B04

09/12/2025 KB RC

23022.012

1/16" = 1'-0"

PENTHOUSE PLAN - OVERALL - ELECTRICAL - DEMOLITION

N

5 5 10 15 20 25 30 35 40 45

1/16" = 1'-0"

STAIR 4

ST4

Room

Room

Room

Room

Room

Room

Room

Room

STAIR 5

ST5

Room

JANITOR

Room

STAIR 1

ST1

WOMEN'S RESTROOM

OFFICE

OFFICE

CONFERENCE ROOM

OFFICE

OFFICE

OFFICE

CONFERENCE ROOM

STORAGE

TMS LAB

OFFICE

163D

OFFICE

163C

OFFICE

163B

OFFICE

163A

STORAGE

166A

COMP RM

ELECTRICAL RM

OFFICE

OFFICE

OFFICE

OFFICE

MEN'S RESTROOM

JANITOR

WOMEN'S RESTROOM

VIRTUAL RECREATION SPACE

Room

209XXXX

SUPPORT RM

139A

DEBBRIEFING

OFFICE

STORAGE

DENTAL LAB

DEBBRIEFING

SKILLS LAB

OR/SURGICAL SIM

MILITARY SIM

CONTROL ROOM

EMT SIM

SHOWER

119A

SHOWER

118A

FEMALE LOCKER RM

Room

MALE LOCKER RM

STAIR 2

ST2

ER SIM

DEPARTMENT HEAD

SIMULATION MANAGER

STAFF SUPPORT

ICU/MED SURGE

COAT RM

CONTROL ROOM

Room

Room

209IIIIIII

ELECTRICAL RM

SERVER RM

STORAGE

116A

Room

114B

EQUIPMENT STORAGE

JANITOR

STORAGE

MEN'S RESTROOM

WOMEN'S RESTROOM

RESOURCE OFFICE

CLASSROOM

MAIN ENTRY

Room

RECEPTION

LOW FIDELITY SKILLS LAB

COFFEE SHOP

CLASSROOM

138B

CLASSROOM

138A

HALLWAY

C106

HALLWAY

C104

HALLWAY

C105

CORRIDOR

C103 Room

114A

CORRIDOR

C102

VENDING RM

SEATING AREA

Room

BREAK-OUT RM

104B

BREAK-OUT RM

104A

CORRIDOR

C100

CAFE SEATING

RESOURCE RM

COPY ROOM

WORK RM

CORRIDOR

C111

CORRIDOR

C110

CORRIDOR-1

C101-1

CORRIDOR-2

C101-2

CORRIDOR

C108

BREAK ROOM

CORRIDOR

C107

THEATER MEZZ

105A

THEATER

MEN'S RESTROOM

Space

ELEVATOR

1-EL-P23

B04-E400

G-LP1

G-LP-N3

G-LP-N2

G-LP-N1

G-FCU-N

FACP

4-PNL-001-109

4-EPNL-001-109

4-PNL-002-109

4-PNL-003-109

4-PNL-004-109

4-PNL-005-105

4-DP-001-109

(E) TYP.

(E) TYP.

4-DP-001-CO-1-107

10360 Ellison Circle Omaha, NE 68134 Phone:

402.991.5520

INSTALL GREEN INSULATED

GROUND WIRE WITH

LIGHTING, RECEPTACLE AND

EQUIPMENT BRANCH CIRCUITS.

INSTALL INDIVIDUAL (DEDICATED)

NEUTRAL CONDUCTORS FOR

EACH 120V OR 277V PHASE

CONDUCTOR SERVED FROM A

SINGLE POLE CIRCUIT BREAKER

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :

DESIGNER OF RECORDCONSULTANT

1221 N. Pennsylvania St.

Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com

GD Project: 23.1019.05

E

A CB

D FE

G IH

KEYPLAN

10/03/2025

100% CONSTRUCTION DOCUMENTS 10/03/2025

/3

/2

:1

:0

P

M

A u to d e s k D o c s /2

.0

V A

L o v e ll E le v a to r

U p g ra d e /5

-5

.B u ild in g

.E

R

.r v t

B04-E100

FIRST LEVEL FLOOR

PLAN-OVERALL-ELECTRICAL

Elevator Upgrade

3001 GREEN BAY RD, NORTH CHICAGO, IL 60064

556-24-115

B04

09/12/2025 KB RC

23022.012

1/16" = 1'-0"

FIRST LEVEL FLOOR PLAN - OVERALL - ELECTRICAL

N

5 5 10 15 20 25 30 35 40 45

1/16" = 1'-0"

FEETSCALE

SHEET NOTES:

1. ELECTRICAL ROOM WITH PANEL THAT FEEDS ELEVATOR AND EMERGENCY PANEL FOR CAB LIGHTS.

2. PROVIDE (6) CAT 6 CABLES FROM SERVER ROOM TO ELEVATOR EQUIPMENT ROOM. CONTRACTOR SHALL COORDINATE STARTING POINT IN

SERVER ROOM WITH VA IT AND THEN FINAL LOCATION IN ELEVATOR EQUIPMENT ROOM WITH ELEVATOR MANUFACTURER.

Room

Room

200A

STAIR 5

ST5

Room

209OOOOOOOOO

SERVER RM

Room

Room

Room

Room

Room

Room

CORRIDOR

C100

Room

MAIN ENTRY-2

100-2

Room

STAIR 1

ST1

MEN'S RESTROOM

Room

BREAK-OUT RM

104A

Room

Room

207A

Room

Room

Room

208Room

Room

205B

Room

PROJECTOR RM

205E

FE CLOSET

Room

Room

Room

205A Room

205C

STORAGE RM

205D

MECH RM

CORRIDOR

C202

Room

Room

Room

Room

Room

227A

CORRIDOR

C201

CORRIDOR

C200

Room

LARGE ROOM

Room

Room

Room

CORRIDOR

C203

STAIR 2

ST2

MECH RM

THEATER-2

105-2

Room

Room

4-DP-001-211

10360 Ellison Circle Omaha, NE 68134 Phone:

402.991.5520

INSTALL GREEN INSULATED

GROUND WIRE WITH

LIGHTING, RECEPTACLE AND

EQUIPMENT BRANCH CIRCUITS.

INSTALL INDIVIDUAL (DEDICATED)

NEUTRAL CONDUCTORS FOR

EACH 120V OR 277V PHASE

CONDUCTOR SERVED FROM A

SINGLE POLE CIRCUIT BREAKER

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :

DESIGNER OF RECORDCONSULTANT

1221 N. Pennsylvania St.

Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com

GD Project: 23.1019.05

E

A CB

D FE

G IH

KEYPLAN

10/03/2025

100% CONSTRUCTION DOCUMENTS 10/03/2025

/3

/2

:1

:0

P

M

A u to d e s k D o c s /2

.0

V A

L o v e ll E le v a to r

U p g ra d e /5

-5

.B u ild in g

.E

R

.r v t

B04-E101

SECOND LEVEL FLOOR

PLAN-OVERALL-ELECTRICAL

Elevator Upgrade

3001 GREEN BAY RD, NORTH CHICAGO, IL 60064

556-24-115

B04

09/12/2025 KB RC

23022.012

1/16" = 1'-0"

SECOND LEVEL FLOOR PLAN - OVERALL - ELECTRICAL

N

5 5 10 15 20 25 30 35 40 45

1/16" = 1'-0"

FEETSCALE

SHEET NOTES:

1. SMOKE DETECTOR TO BE PROVIDED AT THE TOP OF HOISTWAY.

10360 Ellison Circle Omaha, NE 68134 Phone:

402.991.5520

INSTALL GREEN INSULATED

GROUND WIRE WITH

LIGHTING, RECEPTACLE AND

EQUIPMENT BRANCH CIRCUITS.

INSTALL INDIVIDUAL (DEDICATED)

NEUTRAL CONDUCTORS FOR

EACH 120V OR 277V PHASE

CONDUCTOR SERVED FROM A

SINGLE POLE CIRCUIT BREAKER

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :

DESIGNER OF RECORDCONSULTANT

1221 N. Pennsylvania St.

Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com

GD Project: 23.1019.05

E

A CB

D FE

G IH

KEYPLAN

10/03/2025

100% CONSTRUCTION DOCUMENTS 10/03/2025

/3

/2

:1

:0

P

M

A u to d e s k D o c s /2

.0

V A

L o v e ll E le v a to r

U p g ra d e /5

-5

.B u ild in g

.E

R

.r v t

B04-E102

PENTHOUSE PLAN-OVERALL-ELECTRICAL Elevator Upgrade

3001 GREEN BAY RD, NORTH CHICAGO, IL 60064

556-24-115

B04

09/12/2025 KB RC

23022.012

1/16" = 1'-0"

PENTHOUSE PLAN - OVERALL - ELECTRICAL

5 5 10 15 20 25 30 35 40 45

1/16" = 1'-0"

FEETSCALE

N

ELEVATOR

1-EL-P23

DD

D

D

ELEV DISCONNECT (D)

E

E

D

ELEV CONTROLLER (D)

TRANSFORMER (E)

E

E

ELEV CONTROLLER

ELEV DISCONNECT

TRANSFORMER (E)

K1

K1

K1

K1

UH-04-300

SS-04-CU

SS-04-300

48"48"

48"

ELEVATOR

1-EL-P23

7 7

SP-04-300

A. ELECTRICAL DEVICE MOUNTING HEIGHTS ARE NOT INDICATED ON ELECTRICAL FLOOR

PLANS. CONTRACTOR SHALL COORDINATE EXACT DEVICE LOCATIONS AND MOUNTING

HEIGHTS.

B. ROUTE ALL ELECTRICAL BRANCH CIRCUITS AND CONDUITS SPECIFIED, TO COORDINATE

WITH OTHER TRADES AND TO ALLOW FOR SERVICE AND MAINTENANCE AND TO MINIMIZE

THE USE OF ACCESS PANELS. WHERE ACCESS PANELS CANNOT BE AVOIDED, ARRANGE

WORK TO INSTALL PANELS IN LOCATIONS ACCEPTABLE TO ARCHITECT.

C. REFER TO SPECIFIC ELEVATOR DETAIL ON SHEET B04-E400.

D. REFER TO DETAILS, SCHEDULES, AND SYMBOL LEGENDS FOR ADDITIONAL

REQUIREMENTS.

(POWER GENERAL NOTES SHALL APPLY TO ALL SHEETS)

ELEVATOR GENERAL NOTES:

ELEVATOR

MACHINE ROOM

ELEVATOR LOBBY

ELEVATOR PIT

ST

MM CM CM

FIRE ALARM CONTROL MODULE (TYP)

HOISTWAY PIT LIGHT - REFER TO PLANS

FOR FINAL COUNT

SUMP PUMP CONTROL/POWER JUNCTION BOX

EXISTING MACHINE ROOM SMOKE DETECTOR

NEW MACHINE ROOM LIGHT

DEDICATED CAR LIGHT CIRCUIT DISCONNECT SWITCH

ELEVATOR LOBBY

SMOKE DETECTOR

(TYP ALL FLOORS)

ELEVATOR

CONTROLLER

CM CM

PROVIDE WET LOCATION WIRING

METHODS IN PIT WITHIN 48" OF

THE FLOOR. MOUNT ALL FIRE

ALARM DEVICES, JUNCTION

BOXES, AND RECEPTACLES

ABOVE 48" AFF.

HOISTWAY SMOKE DETECTOR

1. ELEVATOR POWER SHUNT TRIP. CONNECT TO FIRE SAFETY INTERFACE IN ELEVATOR MAIN POWER SWITCH.

COORDINATE

2. ELEVATOR RECALL INITIATED BY FIRE ALARM SYSTEM VIA CONTROL MODULES. COORDINATE WITH

UPDATED SYSTEM.

3. SMOKE DETECTOR ALARM SIGNAL TO FIRE ALARM SYSTEM INITIATES ELEVATOR RECALL. COORDINATE

WITH UPDATED SYSTEM.

4. HEAT DETECTOR ALARM SIGNAL TO FIRE ALARM SYSTEM INITIATES ELEVATOR SHUNT TRIP. COORDINATE

WITH UPDATED SYSTEM.

5. DEDICATED CAR LIGHT CIRCUIT WITH LOCKABLE FUSED SWITCH PER NFPA 70, ARTICLE 620. SERVE FROM

LIFE SAFETY BRANCH SOURCE INDICATED. PROVIDE 2-#12, #12 GROUND IN 3/4" CONDUIT.

6. DEDICATED ELEVATOR HOISTWAY PIT BRANCH CIRCUITS PER NFPA 70, ARTICLE 620. SERVE FROM EXISTING CIRCUIT. SHOULD BOTH LIGHTINGS AND RECEPTACLES BE FOUND TO BE ON THE SAME CIRCUIT THE CONTRACTOR SHALL PROVIDE AN ADDITIONAL CIRCUIT TO ALLOW FOR SEPARATION OF RECEPTACLES AND

LIGHTING.

7. ELEVATOR CAB VISUAL INDICATOR CONTROL. (FIREFIGHTERS HAT LIGHT)

8. TELEPHONE OUTLET AND CONDUIT PER FINAL ELEVATOR MANUFACTURER. PROVIDE CONNECTION TO

ELEVATOR CONTROLLER PER MANUFACTURERS INSTRUCTIONS.

9. SHUNT TRIP POWER SOURCE MONITORING MODULE.

10. PROVIDE BUSSMANN POWER MODULE SWITCH, LITTELFUSE LPS SERIES, MERSEN ES SERIES OR

EQUIVALENT SHUNT TRIP DISCONNECT SWITCH WITH AMPACITY TO MEET OR EXCEED OVERCURRENT DEVICE SERVING ELEVATOR. PROVIDE WITH CONTROL POWER TRANSFORMER, FIRE SAFETY INTERFACE

RELAY, AND AUXILIARY CONTACTS (1 SET). PROVIDE CLASS J FUSES SIZED PER ELEVATOR

MANUFACTURER'S RECOMMENDATIONS. THE AVAILABLE SHORT CIRCUIT CURRENT (SCC) AT THE

ELEVATOR MAIN POWER SWITCH SHALL MATCH EXISTING, REFER TO CURRENT POWER SYSTEM STUDY UNDER DESIGN. RATING SHALL BE ADJUSTED IF REQUIRED BASED ON FINAL SCC CALCULATION. PROVIDE NEW FEEDERS PER ONE-LINE DIAGRAM, UTILIZE EXISTING CONDUIT. CONFIRM FINAL FEEDER AND CIRCUIT

BREAKER SIZE WITH FINAL EQUIPMENT SELECTION.

11. ELEVATOR HOISTWAY PIT LIGHTS. PROVIDE LIGHT FIXTURESAS INDICATED ON FLOOR PLANS. COORDINATE EXACT FIXTURE LOCATIONS AND REQUIREMENTS PRIOR TO ROUGH-IN. PROVIDE LITHONIA CATALOG # FEM- L48-6000LM-LPAFL-WD-MVOLT-GZ10-40K-80CRI OR PRIOR APPROVED EQUIVALENT. REFER TO FLOORPLANS

FOR LOCATIONS.

12. DEDICATED MACHINE ROOM BRANCH CIRCUITS PER NFPA 70, ARTICLE 620. SERVE FROM NEW NORMAL

BRANCH SOURCE AS SHOWN ON FLOORPLANS.

13. SUMP PUMP CONTROL PANEL (PROVIDED BY SUMP PUMP MANUFACTURER), MOUNTED PER MECHANICAL PLANS. REFER TO FLOORPLANS FOR EXACT LOCATION. POWER SOURCE FOR ASSOCIATED SUMP PUMP

SHALL ROUTE THROUGH CONTROL PANEL AND PROVIDE POWER TO CONTROL PANEL. COORDINATE

LOCATION OF CONTROL PANEL TO ACCOMMODATE ALL RELEVANT CODES AND AVAILABLE LENGTHS OF CONTROL CABLE. PROVIDE PUMP ALARM SIGNAL TO FIRE ALARM CONTROL PANEL AS A SUPERVISORY ALARM. COORDINATE ALL REQUIREMENTS OF SUMP PUMP SYSTEMS SPECIFIED AND MAKE PROVISIONS FOR MOUNTING, CONFIGURATION, AND CONNECTION AS DIRECTED BY VENDOR / MANUFACTURER.

14. PROVIDE TWO (2) 1" CONDUITS FROM CONTROL PANEL INTO ELEVATOR PIT FOR CONTROL CABLE ROUTING BY SUMP PUMP MANUFACTURER. COORDINATE SIZE AND QUANTITY OF CONDUITS TO ACCOMMODATE CONTROL CABLES (FLOATS, PROBES, SENSORS, ETC.) AS RECOMMENDED BY MANUFACTURER. ROUTE

CONDUIT TO CONNECTION JUNCTION BOX AND PROVIDE CONNECTIONS PER MANUFACTURER'S

INSTRUCTIONS. COORDINATE ROUTING OF CONTROL CABLE CONDUIT TO DETERMINE LENGTH

REQUIREMENTS OF CONTROL CABLES.

15. SURFACE MOUNT MANUFACTURER FURNISHED SUMP PUMP CONTROL JUNCTION BOX WITHIN ELEVATOR PIT. MOUNT WITH BOTTOM OF JUNCTION BOX 50" ABOVE ELEVATOR PIT FLOOR. COORDINATE LOCATION OF

JUNCTION BOX WITH LOCATION OF SUMP PUMP AND CONTROL CABLE LENGTHS. PROVIDE FINAL

CONNECTIONS OF CONTROL CABLES AT SUMP PUMP. COORDINATE ALL REQUIREMENTS OF SUMP PUMP

SYSTEMS SPECIFIED AND MAKE PROVISIONS FOR MOUNTING AND CONNECTION AS DIRECTED BY

VENDOR/MANUFACTURER.

16. PROVIDE SIMPLEX NEMA RECEPTACLE, HARD-WIRED FROM SUMP PUMP CONTROL PANEL, MOUNTED WITH BOTTOM OF BACK BOX AT 50" ABOVE ELEVATOR PIT FLOOR. SERVE FROM SUMP PUMP CONTROL PANEL SOURCE. PROVIDE SUMP PUMP WITH CORD AND PLUG TO MATCH NEMA CONFIGURATION OF SIMPLEX NEMA RECEPTACLE. REFER TO EQUIPMENT CONNECTION SCHEDULE SUMP PUMP SP-04-P23 FOR NEMA

CONFIGURATION, FEEDER, AND OVERCURRENT PROTECTION REQUIREMENTS.

17. IF ELEVATOR IS PROVIDED WITH AUTOMATIC BATTERY LOWERING FEATURE, PROVIDE CONNECTION FROM ELEVATOR CONTROLLER DISCONNECT SWITCH AUXILIARY CONTACTS TO AUTOMATIC BATTERY LOWERING

FEATURE FOR SAFETY INTERLOCK TO PREVENT AUTOMATIC LOWERING OF ELEVATOR DURING

MAINTENANCE.

18. DEDICATED TWO-WAY VIDEO COMMUNICATION DEVICE CONNECTION PER ASME A17.1. PROVIDE NETWORK

DATA CONNECTION FROM ASSOCIATED COMMUNICATIONS ROOM.

19. PROVIDE REMOTE SAMPLING SMOKE DETECTOR TO ALLOW FOR ACCESSIBILITY. LOCATE ACCESSIBLE UNIT

IN ELEVATOR LOBBY.

ELEVATOR CONNECTION SCHEMATIC KEYED NOTES:

MOUNT ADJACENT TO PIT ACCESS / LADDER ENTRY LEVEL

NEW MACHINE ROOM HEAT DETECTOR

ELEVATOR MAIN POWER SWITCH

J

SUMP PIT

EXISTING

CIRCUIT

FIRE ALARM MONITORING MODULE (TYP)

MM

A. COMPLY WITH NFPA 70, ARTICLE 620.

B. SMOKE DETECTORS SHALL BE INSTALLED AT EACH ELEVATOR LOBBY AT EACH LANDING, AND ASSOCIATED

ELEVATOR MACHINE ROOM, AND WITHIN ELEVATOR HOISTWAY. PROVIDE QUANTITY OF SMOKE

DETECTORS REQUIRED BASED ON FINAL CEILING HEIGHT, BEAM POCKET DEPTH, ETC. TO MEET NFPA 72, CHAPTER 17 REQUIREMENTS. ACTIVATION OF ANY OF THESE SMOKE DETECTORS SHALL INITIATE

ELEVATOR RECALL.

C. ACTIVATION OF SMOKE DETECTOR(S) ON A DESIGNATED LEVEL SHALL CAUSE THE ELEVATOR TO RETURN TO AN ALTERNATE LEVEL. DESIGNATED AND ALTERNATE LEVELS TO BE DETERMINED BY THE ELEVATOR

INSPECTOR AND FIRE MARSHAL.

D. HEAT DETECTORS USED FOR ELEVATOR POWER SHUT DOWN SHALL BE LOCATED WITHIN 24" OF SPRINKLER HEADS WITHIN ELEVATOR MACHINE ROOM. COORDINATE EXACT LOCATION(S) AND QUANTITY WITH FIRE SPRINKLER CONTRACTOR. ACTIVATION OF HEAT DETECTOR WITHIN ELEVATOR MACHINE ROOM

SHALL SHUT DOWN POWER TO ELEVATOR CONTROLLER.

E. FIRE ALARM CONNECTIONS INDICATED ARE BASED ON AN ADDRESSABLE FIRE ALARM SYSTEM. WHERE A NON-ADDRESSABLE FIRE ALARM SYSTEM IS SPECIFIED PROVIDE RELAYS AND CONNECTIONS TO CONTROL

PANEL AS REQUIRED.

F. VERIFY ALL EQUIPMENT LOCATIONS WITH ELEVATOR MANUFACTURER'S SHOP DRAWINGS PRIOR TO

INSTALLATION OF EQUIPMENT.

ELEVATOR CONNECTION SCHEMATIC GENERAL NOTES:

ELEVATOR LOBBY

EXISTING

CIRCUIT

4-EPNL-001-109 - 31

ELEVATOR LOBBY

SMOKE DETECTOR

(TYP ALL FLOORS)

4-EPNL-001-109 - 33

10360 Ellison Circle Omaha, NE 68134 Phone:

402.991.5520

INSTALL GREEN INSULATED

GROUND WIRE WITH

LIGHTING, RECEPTACLE AND

EQUIPMENT BRANCH CIRCUITS.

INSTALL INDIVIDUAL (DEDICATED)

NEUTRAL CONDUCTORS FOR

EACH 120V OR 277V PHASE

CONDUCTOR SERVED FROM A

SINGLE POLE CIRCUIT BREAKER

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :

DESIGNER OF RECORDCONSULTANT

1221 N. Pennsylvania St.

Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com

GD Project: 23.1019.05

E

A CB

D FE

G IH

KEYPLAN

10/03/2025

100% CONSTRUCTION DOCUMENTS 10/03/2025

/3

/2

:1

:0

P

M

A u to d e s k D o c s /2

.0

V A

L o v e ll E le v a to r

U p g ra d e /5

-5

.B u ild in g

.E

R

.r v t

B04-E400

ENLARGED FLOOR PLANS-ELECTRICAL Elevator Upgrade

3001 GREEN BAY RD, NORTH CHICAGO, IL 60064

556-24-115

B04

09/12/2025 KB RC

23022.012

1/4" = 1'-0"

B04 ENLARGED ROOM 1-EL-P23 - DEMOLITION ELEVATOR PIT ELECTRICAL

N 2 2 4 6 8 10

1/4" = 1'-0"

FEETSCALE

1/4" = 1'-0"

B04 ENLARGED ROOM 300 - DEMOLITION ELEVATOR MACHINE ROOM

SHEET NOTES:

1. EXISTING SMOKE DETECTOR TO BE TESTED FOR FULL FUNCTIONALITY AND COMPLIANCE.

SHOULD SMOKE DETECTOR NOT BE FUNCTIONAL THE CONTRACTOR SHALL REPLACE WITH

NEW. THE EXISTING SMOKE DETECTOR SHALL BE REMOVED AND MAINTENANCE PERFORMED.

CONTRACTOR TO PLACE BACK AT CEILING HEIGHT.

2. EXISTING ELEVATOR EQUIPMENT TO BE REMOVED AND REPLACED. EXISTING CONDUIT

SERVING EQUIPMENT SHALL REMAIN. THE CONTRACTOR SHALL REMOVE CONDUCTORS FROM

CONDUIT AND PROVIDE PULLSTRING FOR NEW WORK.

3. EXISTING LIGHT FIXTURE TO BE REMOVED. REMOVE BACK TO POINT OF ORIGIN AND MARK

SPARE SHOULD NO OTHER ELECTRICAL COMPONENTS BE ON THE CIRCUIT. REFER TO NEW

WORK PLAN FOR MORE INFORMATION.

4. PROVIDE NEW ELEVATOR SHUNT TRIP DISCONNECT AND ELEVATOR CONTROLLER.

COORDINATE WITH FINAL ELEVATOR MANUFACTURER SELECTED. CONTRACTOR TO PROVIDE

NEW FEEDERS WITHIN THE EXISTING CONDUIT. REFER TO ONE-LINE DIAGRAM FOR MORE

INFORMATION. SHOULD EXISTING CONDUIT NOT MEET THE REQUIREMENTS OF THE NEW

ELEVATOR CONTRACTOR SHALL PROVIDE NEW.

5. CONNECT NEW LIGHT FIXTURES TO NEW EMERGENCY BRANCH CIRCUIT FROM NEAREST

EMERGENCY BRANCH 208/120V PANEL. CONNECT TO 120V 20A/1P BREAKER.

6. REMOVE EXISTING RECEPTACLE. REMOVE BACK TO POINT OF ORIGIN AND MARK SPARE

SHOULD NO OTHER ELECTRICAL COMPONENTS BE ON THE CIRCUIT. REFER TO NEW WORK

PLAN FOR MORE INFORMATION.

7. REFER TO ELEVATOR DETAIL FOR LIGHT FIXTURE TYPE.

8. CONNECT TO EXISTING RECEPTACLE CIRCUIT MAINTAINED DURING CONSTRUCTION.

9. CONNECT TO NEW NORMAL BRANCH CIRCUIT FROM NEAREST SPARE 20A/1P BREAKER ON THE

NORMAL BRANCH OF THE ELECTRICAL SYSTEM.

10. PROVIDE ADDITIONAL DETECTOR FOR ROOM COVERAGE DUE TO DEPTH OF EXISTING

STRUCTURAL BEAM.

11. LIGHT SWITCH TO BE LOCATED AT LADDER. CONTRACTOR TO ENSURE SWITCH IS AT CORRECT

HEIGHT.

12. EXISTING CAB DISCONNECT TO REMAIN. CONTRACTOR TO CONFIRM LOCATION AND

COORDINATION WITH FINAL ELEVATOR MANUFACTURER CHANGES.

1/4" = 1'-0"

B04 ENLARGED ROOM 300 - NEW WORK ELEVATOR MACHINE ROOM

1/4" = 1'-0"

B04 ENLARGED ROOM 1-EL-P23 - NEW WORK ELEVATOR PIT ELECTRICAL

NO SCALE

ELEVATOR CONNECTION SCHEMATIC

175A D

17N

ELEVATOR

D

2000A E

200A E

200A E

1000A E

1200A E

4-DT-SS-SB

208/120V 2000A 3/4W E

4-ATS-001-SB

200A E

B-LP-1

208/120V

200A 3/4W E

TRANSFORMER

E

TO BUILDING 156

GENERATOR

E

B-EDLP-1

208/120V

200A 3/4W E

EM-G

208/120V

100A 3/4W E

4-DP-001-109

208/120V

1000A 3/4W E1000A

E

1200A E

100A E

200A E

200A E

200A E

200A E

300A E

50A E

70A E

GI

208/120V

100A 3/4W E

G1S 208/120V 70A 3/4W

E

G-FCU-N

208/120V

100A 3/4W E

G-LP-N1

208/120V

200A 3/4W E

G-LP-N2

208/120V

200A 3/4W E

G-SP-1

208/120V

200A 3/4W E

G-LP-1

208/120V

200A 3/4W E

1L 208/120V 70A 3/4W

E

MP

208/120V

500A 3/4W E

FR-LP-2

208/120V

200A 3/4W E

1M 208/120V

100A 3/4W E

100A E

70A E

100A E

200A E

200A E

200A E

200A E

70A E

SERVICE RM #7

E

4-TDT-DT-SS-SB

750KVA

4-DP-001-CO-1-107

208/120V

1200A 3/4W E

2000A E

200A E

200A E

1000A E

1200A E

4-DT-SS-SB

208/120V 2000A 3/4W E

4-ATS-001-SB

200A

NEC 700 - EMERGENCY BRANCH

E

B-LP-1

208/120V

200A 3/4W E

TRANSFORMER

E

TO BUILDING 156

GENERATOR

E

4-PNL-B-EDLP-1-SB

208/120V 200A 3/4W E

4-EPNL-001-109

208/120V 100A 3/4W E

4-DP-001-109

208/120V

1000A 3/4W E

4-DP-001-CO-1-107

208/120V

1200A 3/4W E1000A

E

1200A E

100A E

200A E

200A E

200A E

200A E

300A E

50A E

70A E

GI

208/120V

100A 3/4W E

G1S 208/120V 70A 3/4W

E

G-FCU-N

208/120V

100A 3/4W E

G-LP-N1

208/120V

200A 3/4W E

G-LP-N2

208/120V

200A 3/4W E

G-SP-1

208/120V

200A 3/4W E

G-LP-1

208/120V

200A 3/4W E

1L 208/120V 70A 3/4W

E

MP

208/120V

500A 3/4W E

FR-LP-1

208/120V

200A 3/4W E

FR-LP-2

208/120V

200A 3/4W E

1M 208/120V

100A 3/4W E

100A E

70A E

100A E

500A E

200A E

175A 200A E

200A E

200A E

200A E

200A E

200A E

70A E

SERVICE RM #7

E

17N

SHUNT

175A

ELEVATOR

ELEVATOR

CONTROLLER

4-TDT-DT-SS-SB

750KVA

10360 Ellison Circle Omaha, NE 68134 Phone:

402.991.5520

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :

DESIGNER OF RECORDCONSULTANT

1221 N. Pennsylvania St.

Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com

GD Project: 23.1019.05 10/03/2025

100% CONSTRUCTION DOCUMENTS 10/03/2025

/3

/2

:1

:0

P

M

A u to d e s k D o c s /2

.0

V A

L o v e ll E le v a to r

U p g ra d e /5

-5

.B u ild in g

.E

R

.r v t

B04-E500

ONE-LINE DIAGRAM Elevator Upgrade

3001 GREEN BAY RD, NORTH CHICAGO, IL 60064

556-24-115

B04

09/12/2025 KB RC

23022.012

NO SCALE

ELECTRICAL ONE-LINE - SWBD BLDG 4 DEMO

FEEDER SCHEDULE - COPPER

FEEDER NOMINAL SIZE WIRE AND CONDUIT

17N 175 A 4-#3/0 CU, #6 CU GND - 2-1/2" C.

NO SCALE

NEW ELECTRICAL ONE-LINE - SWBD BLDG 4

SHEET NOTES:

1. REMOVE EXISTING BREAKER AND PROVIDE NEW BREAKER AS REQUIRED FOR UPDATED MOTOR. NEW BREAKER TO BE COMPATIBLE WITH EXISTING PANEL MANUFACTURER. FINAL SELECTION TO BE BASED ON FINAL ELEVATOR EQUIPMENT.

2. REMOVE EXISTING SOURCE CONDUCTORS SERVING THE ELEVATOR AND RETAIN EXISTING CONDUIT FOR REUSE. PROVIDE NEW CONDUCTORS AS SCHEDULED. THE CONDUCTOR SIZE/CONFIGURATION IS PRELIMINARY AND FOR BIDDING PUPOSES ONLY. PRIOR TO ORDERING MATERIAL ASSOCIATED WITH THE NEW CONDUCTOR INSTALLATION, CONTRACTOR SHALL SEEK VERIFICATION OF THE FINAL CONDUCTOR SIZE/CONFIGURATION FROM THE ENGINEER TO ACCOMMODATE THE FINAL SELECTED ELEVATOR MANUFACTURER AND EQUIPMENT.

REMARKS: (EQUIPMENT CONNECTION SCHEDULE)

1. CONTROLS BETWEEN INDOOR AND OUTDOOR UNITS - INCLUDE CONTROL WIRING IN CONDUIT BETWEEN INDOOR AND OUTDOOR UNIT PER MANUFACTURER'S REQUIREMENTS.

2. WALK-IN COOLER CONNECTIONS - PROVIDE CONNECTION TO COOLER ACCESSORIES (EVAPORATOR, LIGHTS, LIGHT CONTROLS, AND DOOR FRAME HEATER) WITH BRANCH CIRCUITS INDICATED ON PLANS.

ACCESSORIES FURNISHED WITH EQUIPMENT.

3. KITCHEN HOOD FIRE SUPPRESSION CONNECTIONS - INTERLOCK HOOD FIRE SUPPRESSION WITH FIRE ALARM MONITORING, SHUNT TRIP CIRCUIT BREAKERS SERVING EQUIPMENT BELOW HOOD, AND GAS SUPPLY

SOLENOID VALVES/RESETS SERVING EQUIPMENT BELOW HOOD. ACTIVATION OF HOOD FIRE SUPPRESSION SHALL TRIP SHUNT CIRCUIT BREAKERS TO THEIR OFF POSITION. SHALL CLOSE GAS SUPPLY SOLENOID VALVES AND SHALL PROVIDE INDICATION TO THE FIRE ALARM SYSTEM. 120V BRANCH CIRCUIT SHALL SERVE HOOD LIGHTS, HOOD CONTROLS, AND FIRE SUPPRESSION INTERLOCKS. HOOD FIRE SUPPRESSION SYSTEM IS SHIPPED LOOSE, COORDINATE MOUNTING LOCATION IN FIELD. SEE FOOD SERVICE EXHAUST HOOD DRAWING FOR CLARIFICATION AND ADDITIONAL REQUIREMENTS.

4. KITCHEN HOOD CONTROL CONNECTIONS - INTERLOCK HOOD CONTROL PANEL WITH FAN SWITCH AT HOOD, LIGHT SWITCH AND LIGHTING AT HOOD, HOOD FIRE SUPPRESSION SYSTEM, ASSOCIATED EXHAUST FAN STARTERS, AND ASSOCIATED MAKE-UP AIR/ROOFTOP UNITS. HOOD CONTROL PANEL IS SHIPPED LOOSE, COORDINATE MOUNTING LOCATION IN FIELD. SEE FOOD SERVICE EXHAUST HOOD DRAWING FOR

CLARIFICATION AND ADDITIONAL REQUIREMENTS.

GENERAL NOTES: (EQUIPMENT CONNECTION SCHEDULE)

A. EQUIPMENT LISTED MAY NOT BE UNIQUE, VERIFY QUANTITY WITH FLOOR PLANS. WHERE LOCATIONS ARE NOT INDICATED ON ELECTRICAL FLOOR PLANS, REFER TO MECHANICAL SHEETS. REFER TO DEFINITIONS

BELOW FOR CLARIFICATIONS OF CONNECTION REQUIREMENTS.

B. ITEMS NOTED AS "NA" ARE NOT APPLICABLE TO THE CONNECTION.

C. "CONTROL TYPE" - PROVIDE CONTROL AND CONNECTIONS:

• "INT" = CONTROLS ARE MANUFACTURED INTEGRAL TO THE EQUIPMENT (SELF-CONTAINED).

• "CONT" = EQUIPMENT OPERATES CONTINUOUSLY (NO CONTROLS). FOR MOTORS WITHOUT INTERNAL OVERLOAD PROTECTION, PROVIDE SEPARATE OVERLOAD PROTECTION. OVERLOAD PROTECTION MAY BE

PROVIDED AS PART OF A MANUAL MOTOR STARTER.

• "DDC" = CONTROL SIGNAL FROM TEMPERATURE CONTROL SYSTEM PROVIDED BY MECHANICAL CONTRACTOR OR TEMPERATURE CONTROLS CONTRACTOR.

• "TIME SW" = CONTROL SIGNAL FROM TIME SWITCH PROVIDED BY ELECTRICAL CONTRACTOR.

• TIME SWITCH SHALL BE 7-DAY DIGITAL TYPE WITH AUTOMATIC DAYLIGHT SAVINGS ADJUSTMENTS AND BATTERY BACKUP. LOCATE TIMESWITCH IN NEAREST MECHANICAL OR ELECTRICAL UTILITY ROOM.

LABEL TIME SWITCH. COORDINATE TIME SCHEDULE WITH OWNER AND MECHANICAL ENGINEER.

• "WALL SW" = CONTROL SIGNAL FROM WALL SWITCH PROVIDED BY ELECTRICAL CONTRACTOR.

• COORDINATE LOCATION OF WALL SWITCH WITH OWNER. LABEL WALL SWITCH.

• "FA STOP" = FANS WITH CFM OF 2000 OR GREATER AND FANS SERVING DUCTS CONTAINING SMOKE DAMPERS.

• PROVIDE FIRE ALARM SYSTEM DUCT SMOKE DETECTORS AT RETURN-SIDE AND SUPPLY-SIDE OF FAN/UNIT. PROVIDE MULTIPLE DETECTORS IF REQUIRED TO ACCOMMODATE MAIN DUCT TAKE-OFFS WHERE A

SINGLE DETECTOR CANNOT BE INSTALLED TO CAPTURE ALL AIRFLOW. FIRE ALARM SYSTEM SHALL SHUTDOWN FAN UPON DETECTION OF SMOKE IN DUCT OR ROOMS SERVED FROM THIS EQUIPMENT.

PROVIDE WITH INDIVIDUAL FIRE ALARM SYSTEM ADDRESSABLE CONTROL MODULE AT MOTOR CONTROLLER/STARTER AND CONNECT TO SHUTDOWN FAN.

• "WF STOP" = HIGH VOLUME LOW SPEED (HVLS) FANS SHUT DOWN HVLS FAN UPON WATERFLOW ALARM. PROVIDE WITH INDIVIDUAL FIRE ALARM SYSTEM ADDRESSABLE CONTROL MODULE AT MOTOR AND

CONNECT TO SHUT DOWN FAN.

• "FA START" = FANS USED FOR SMOKE EVACUATION OR PRESSURIZATION.

• FIRE ALARM SYSTEM SHALL START FAN UPON DETECTION OF SMOKE IN DUCT OR ROOMS SERVED FROM THIS EQUIPMENT. PROVIDE WITH INDIVIDUAL FIRE ALARM SYSTEM ADDRESSABLE CONTROL MODULE

AT MOTOR CONTROLLER/STARTER AND CONNECT TO START FAN.

• "DATA" = PROVIDE WITH DATA CONNECTION FROM NEAREST DATA NETWORK COMMUNICATIONS ROOM.

• "CONDUIT" = PROVIDE EMPTY 3/4" CONTROLS CONDUIT BETWEEN INDOOR AND OUTDOOR UNIT TO ACCOMMODATE CONTROL CABLING BY MECHANICAL OR TEMPERATURE CONTROLS CONTRACTOR.

D. "DISCONNECT BY" :

• "MECHANICAL" = DISCONNECT IS FURNISHED BY MECHANICAL CONTRACTOR OR PROVIDED WITH MECHANICAL EQUIPMENT.

• ELECTRICAL CONTRACTOR SHALL PROVIDE MOUNTING AND ADDITIONAL CONNECTIONS REQUIRED FOR LOOSE DISCONNECTS FURNISHED BY THE MECHANICAL CONTRACTOR.

• "ELECTRICAL" = DISCONNECT IS FURNISHED BY ELECTRICAL CONTRACTOR. COORDINATE EXACT REQUIREMENTS WITH EQUIPMENT FURNISHED BY MECHANICAL CONTRACTOR.

• "MANUFACTURER" = DISCONNECT IS FURNISHED BY EQUIPMENT MANUFACTURER. ELECTRICAL CONTRACTOR SHALL PROVIDE MOUNTING AND ADDITIONAL CONNECTIONS REQUIRED FOR LOOSE DISCONNECTS

FURNISHED BY EQUIPMENT MANUFACTURER.

E. "DISCONNECT TYPE" - PROVIDE DISCONNECT/RECEPTACLE AT EQUIPMENT LOCATION AND ASSOCIATED CONNECTION TO EQUIPMENT AND BRANCH CIRCUIT:

• "NEMA-___" = DUPLEX (TYP) RECEPTACLE TO ACCOMMODATE CORD AND PLUG CONNECTION (CORD AND PLUG FURNISHED WITH EQUIPMENT UNLESS NOTED OTHERWISE)

• "REC/SW" = PROVIDE 20A 120V RECEPTACLE OR 20A TOGGLE SWITCH DISCONNECT.

• COORDINATE REQUIRED SELECTION WITH EQUIPMENT.

• "NF" = NON-FUSED DISCONNECT. SIZE AND POLE QUANTITY AS INDICATED. 20/1 AND SMALLER SHALL BE TOGGLE SWITCH DISCONNECT.

• "F" = FUSED DISCONNECT. SIZE AND POLE QUANTITY AS INDICATED.

• FUSE PER MANUFACTURER'S RECOMMENDATIONS.

• "FUSTAT" = SWITCH AND FUSTAT. FUSE SIZE PER EQUIPMENT MANUFACTURER.

• LOCATE SWITCH IN CONCEALED ACCESSIBLE LOCATION.

• "ENCL CB" = ENCLOSED CIRCUIT BREAKER DISCONNECT.

• SIZE, POLE QUANTITY, AND FLUSH/SURFACE MOUNTING AS INDICATED.

• "ENCL MCSW" = ENCLOSED MOLDED CASE SWITCH DISCONNECT.

• SIZE, POLE QUANTITY, AND FLUSH/SURFACE MOUNTING AS INDICATED.

• "SHUNT ENCL CB" = SHUNT TRIP ENCLOSED CIRCUIT BREAKER DISCONNECT.

• SIZE, POLE QUANTITY, AND FLUSH/SURFACE MOUNTING AS INDICATED. PROVIDE WITH INTEGRAL 120V CONTROL TRANSFORMER SERVED FROM LINE SOURCE WITH PRIMARY AND SECONDARY FUSING.

COORDINATE ENCLOSURE AND COVER SIZE TO ACCOMMODATE TRANSFORMER. PROVIDE WITH EQUIPMENT GROUND BAR AND SEPARATE INSULATED ISOLATED GROUND BAR. WHERE NEUTRAL CONDUCTOR IS UTILIZED. PROVIDE SOLID NEUTRAL BAR. CONNECT SHUNT TRIP VOLTAGE SOURCE AND ACTUATOR TO ASSOCIATED EMERGENCY POWER (EPO) SWITCHES. PROVIDE EPO AND COORDINATE

LOCATION.

• "LOCK CB" = CIRCUIT BREAKER CAPABLE OF BEING LOCKED IN THE OPEN POSITION, LOCATED IN THE SOURCE ELECTRICAL PANEL. THE PROVISIONS FOR LOCKING MUST REMAIN IN PLACE WITH OR WITHOUT THE

LOCK INSTALLED.

• "MAG" = COMBINATION MAGNETIC MOTOR STARTER WITH DISCONNECT (COORDINATE COIL VOLTAGE WITH CONTROL SOURCE). LOCATE COMBINATION MAGNETIC MOTOR STARTER TO SERVE AS THE MOTOR DISCONNECT. WHERE STARTER SERVES OUTDOOR EQUIPMENT, LOCATE STARTER IN THE SOURCE ELECTRICAL ROOM.

• "MAN" = COMBINATION MANUAL MOTOR STARTER WITH DISCONNECT. LOCATE COMBINATION MANUAL MOTOR STARTER TO SERVE AS THE MOTOR DISCONNECT. WHERE STARTER SERVES OUTDOOR

EQUIPMENT, LOCATE STARTER IN THE SOURCE ELECTRICAL ROOM.

• "VFD" = VARIABLE FREQUENCY DRIVE CONTROLLER. LOCATE VARIABLE FREQUENCY DRIVE CONTROL TO SERVE AS THE MOTOR DISCONNECT.

• "INT" = DISCONNECT IS MANUFACTURED INTEGRAL TO THE EQUIPMENT.

• "HW" = HARDWIRE. DISCONNECT NOT REQUIRED.

• LOCATE DISCONNECT ADJACENT TO EQUIPMENT PER NEC - PROVIDE WITH STRUT MOUNTING AS REQUIRED.

• LOCATE RECEPTACLE OR JUNCTION BOX TO DIRECTLY SERVE EQUIPMENT.

• COORDINATE EXACT LOCATION WITH ARCHITECT, ARCHITECTURAL DETAILS, AND EQUIPMENT MANUFACTURER'S REQUIREMENTS.

• WHERE DISCONNECT SERVES OUTDOOR EQUIPMENT, PROVIDE AS NEMA-3R.

• PROVIDE DISCONNECT WITH EQUIPMENT GROUND KIT.

• WHERE FEEDER INDICATED UTILIZES A NEUTRAL, PROVIDE DISCONNECT WITH SOLID NEUTRAL KIT.

• WHERE FEEDER INDICATED UTILIZES AN ISOLATED GROUND, PROVIDE DISCONNECT WITH ADDITIONAL INSULATED GROUND KIT.

• DISCONNECTS NOT SHOWN AS "F" OR "NF" SHALL BE NON-FUSED.

• DISCONNECTS OF MOTORS SERVED FROM A VFD SHALL CONTAIN AUXILIARY CONTACTS CONNECTED TO THE VFD TO DISABLE VFD UPON DISCONNECTION.

• WHERE STARTERS OR VFD'S CONTAIN INTEGRAL DISCONNECTS AND ARE LOCATED PER NEC TO SATISFY AS THE EQUIPMENT DISCONNECT, AN ADDITIONAL EQUIPMENT DISCONNECT IS NOT REQUIRED.

F. "GEN" - EQUIPMENT IS SERVED FROM A SOURCE PANEL PROVIDED WITH GENERATOR BACK-UP.

G. "SCCR" - VALUE INDICATED IS AVAILABLE SHORT CIRCUIT CURRENT (SCC) IN KILOAMPS AT THE EQUIPMENT BASED ON PRELIMINARY DESIGN PHASE CALCULATIONS. EQUIPMENT SCCR SHALL BE MINIMUM 120% OF

THE AVAILABLE SCC. RATING SHALL BE ADJUSTED IF REQUIRED BASED ON FINAL SCC CALCULATION. EQUIPMENT INDICATED WITH 5 KA MAY BE PROVIDED WITH 5 KA SCCR.

REMARKS: (LIGHTING FIXTURE SCHEDULE)

1. PENDANT/SUSPENSION MOUNTING - COORDINATE EXACT LOCATION, MOUNTING ELEVATION, AND REQUIRED

PENDANT/SUSPENSION LENGTH WITH ARCHITECT AND ARCHITECTURAL DETAILS.

GENERAL NOTES: (LIGHTING FIXTURE SCHEDULE)

A. CATALOG NUMBER VERIFICATION - CONTRACTOR SHALL VERIFY LIGHTING FIXTURE INSTALLATION REQUIREMENTS

AND CATALOG NUMBER PRIOR TO ORDERING.

B. SUBSTITUTIONS - WHERE INDICATED WITH 'N' (NO), NO SUBSTITUTIONS WILL BE ACCEPTED. WHERE INDICATED WITH

'P' (PRIOR APPROVAL), SUBSTITUTIONS MUST BE APPROVED PRIOR TO BID WITH ACCEPTANCE ISSUED BY ADDENDUM.

WHERE INDICATED WITH 'Y' (YES), THE FOLLOWING MANUFACTURER'S ARE CONSIDERED ACCEPTABLE EQUIVALENT MANUFACTURER'S, PROVIDED THE EQUIVALENT FIXTURE IS OF THE SAME QUALITY, EFFICIENCY, PERFORMANCE AND

CHARACTERISTICS AS THAT SCHEDULED:

1. ACUITY BRANDS

2. EATON/COOPER BRANDS

3. HUBBELL

4. WILLIAMS

5. PHILLIPS/SIGNIFY BRANDS

C. FIXTURE FINISH - WHERE CATALOG NUMBER LISTED INDICATES '**' IN LIEU OF MANUFACTURER'S FINISH OPTION, COORDINATE WITH ARCHITECT FOR EXACT FINISH PRIOR TO ORDERING.

10360 Ellison Circle Omaha, NE 68134 Phone:

402.991.5520

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :

DESIGNER OF RECORDCONSULTANT

1221 N. Pennsylvania St.

Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com

GD Project: 23.1019.05 10/03/2025

100% CONSTRUCTION DOCUMENTS 10/03/2025

/3

/2

:1

:0

P

M

A u to d e s k D o c s /2

.0

V A

L o v e ll E le v a to r

U p g ra d e /5

-5

.B u ild in g

.E

R

.r v t

B04-E700

ELECTRICAL SCHEDULES Elevator Upgrade

3001 GREEN BAY RD, NORTH CHICAGO, IL 60064

556-24-115

B04

09/12/2025 KB RC

23022.012

EQUIPMENT CONNECTION SCHEDULE

MARK DESCRIPTION ROOM NAME ROOM # HP KW FLA MCA MOCP VOLTS PHASE POLES

LOAD

[VA]

CONTROL

TYPE

DISCONNECT

BY

DISCONNECT

TYPE FEEDER PANEL

CIRCUIT

NUMBER SCCR GEN REMARKS

SP-04-300 SUMP PUMP ELEVATOR 1-EL-P23 0.5 0 8 0 20 120 1 1 960 INT ELECTRICAL NF 30/1 (1M1) (1/6 - 1 HP 120V) 2-#12 CU, #12 CU GND - 3/4"C. 4-DP-001-211 38 0 No

SS-04-300 DUCT FREE SPLIT SYSTEM - INDOOR 0 0 0 0 0 0 0 1 0 DDC MECHANICAL NF 30/2 0 No

SS-04-CU DUCT FREE SPLIT SYSTEM -

OUTDOOR

0 0 0 14.2 20 208 1 2 2960 DDC ELECTRICAL NF 30/2 (2X) (20A) 2-#12 CU, #12 CU GND - 3/4"C. 4-DP-001-211 40,42 0 No

UH-04-300 UNIT HEATER 0 10 28.5 0 35 208 3 3 10000 DDC ELECTRICAL NF 60/3 (4) (40A) 3-#8 CU, #10 CU GND - 3/4"C. 4-DP-001-211 25,27,29 0 No

LIGHTING FIXTURE SCHEDULE

MARK DESCRIPTION SUBS MANUFACTURER CATALOG # (NOTE A)

LAMP /

NOMINAL

LUMENS CCT

MINIMUM

CRI VOLTAGE

INPUT

WATTS MOUNTING REMARKS

K1 INDUSTRIAL STRIP - 4'-0" Y LITHONIA CLX-L48-3000LM-SEF-RDL-MVOLT-GZ10-35

K-80CRI-WH

3000 3500 80 120 V 22 SUSPENDED 1

A. PANEL AIC (INTERRUPTING) RATING SHALL BE MINIMUM 120% OF THE AVAILABLE SCC (SHORT CIRCUIT CURRENT).

GENERAL REMARKS:

CIRCUIT BREAKER OPTIONS SUFFIX: 'S' OR 'ST' - PROVIDE SHUNT TRIP CIRCUIT BREAKER / 'G' OR 'GFCI' - PROVIDE GFCI CIRCUIT BREAKER / 'GFP' - PROVIDE GFP CIRCUIT BREAKER / 'ERMS' - ENERGY REDUCING MAINTENANCE SWITCH / 'ZSI' - ZONE SELECTIVE INTERLOCKING / 'L' - PROVIDE CIRCUIT BREAKER WITH LOCKING PROVISIONS / 'R'

- PROVIDE CIRCUIT BREAKER WITH RED MARKING

OPTIONS:

1 A

SPARE CAPACITY:

100 %

FEEDER AVAILABLE:

EQUIPMENT AMPS: 1 A

CONSIDER 125% DEMAND: 0 A

DEMAND CURRENT: 0 A

DEMAND LOAD: 0 VA

CONNECTED CURRENT: 0 A

CONNECTED LOAD: 0 VA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS

TOTAL AMPS: 0 A 0 A 0 A

TOTAL LOAD: 0 VA 0 VA 0 VA

41 SPACE -- -- 1 -- -- 1 -- -- SPACE 42

39 SPACE -- -- 1 -- -- 1 -- -- SPACE 40

37 SPACE -- -- 1 -- -- 1 -- -- SPACE 38

35 SPACE -- -- 1 -- -- 1 -- -- SPACE 36

33 SPACE -- -- 1 -- -- 1 -- -- SPACE 34

31 SPACE -- -- 1 -- -- 1 -- -- SPACE 32

29 0 VA 0 VA 1 20 A -- FIRE ALARM 30

ELECTRIC HTR -- 20 A 2

0 VA 0 VA 1 20 A -- FIRE ALARM 28

25 0 VA 0 VA 1 20 A -- AUTO DOOR 26

ELECTRIC HTR -- 20 A 2

0 VA 0 VA 1 20 A -- LTG TRAMWAY 24

21 0 VA 0 VA 1 20 A -- LGT TRAMWAY 22

ELECTRIC HTR -- 20 A 2

0 VA 0 VA 1 20 A -- LTG TRAMWAY 20

17 DATA CLOSET LTG -- 20 A 1 0 VA 0 VA 1 20 A -- EM LTG 1ST FLR 18

15 DATA CLOSET OUTLET -- 20 A 1 0 VA 0 VA 1 20 A -- EM LTG 1ST FLR 16

13 0 VA 1 20 A -- EM LTG 1ST FLR 14

11 0 VA 1 20 A -- EM LTG 1ST FLR 12

9 STAIR LTG -- 20 A 1 0 VA 0 VA 1 20 A -- EM LTG 1ST FLR 10

7 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- EM LTG 1ST FLR 8

5 EMERGENCY LTG SECOND FLR -- 20 A 1 0 VA 0 VA 1 20 A -- EM LTG 1ST FLR 6

3 EMERGENCY LTG SECOND FLR -- 20 A 1 0 VA 0 VA 1 20 A -- EM LTG 1ST FLR 4

1 EMERGENCY LTG -- 20 A 1 0 VA 0 VA 1 20 A -- EM LTG 1ST FLR 2

CKT CIRCUIT DESCRIPTION OPT RATING POLES A B C POLES RATING OPT CIRCUIT DESCRIPTION CKT

NEMA ENCLOSURE:

MOUNTING: SURFACE AVAILABLE SCC (kA): PANEL POLES: 42

SERVICE RATED: INTEGRAL SPD: SECTIONS: 1

BRANCH: EEMRGENCY WIRES: 4 MCB OPTIONS:

SUPPLY FROM: PHASES: 3 MCB/MLO RATING: 1 A

LOCATION: ELECTRICAL RM 109 VOLTS: 208/120 WYE MAINS TYPE: MCB

LIGHTING PANEL: 4-EPNL-001-109

A. PANEL AIC (INTERRUPTING) RATING SHALL BE MINIMUM 120% OF THE AVAILABLE SCC (SHORT CIRCUIT CURRENT).

GENERAL REMARKS:

CIRCUIT BREAKER OPTIONS SUFFIX: 'S' OR 'ST' - PROVIDE SHUNT TRIP CIRCUIT BREAKER / 'G' OR 'GFCI' - PROVIDE GFCI CIRCUIT BREAKER / 'GFP' - PROVIDE GFP CIRCUIT BREAKER / 'ERMS' - ENERGY REDUCING MAINTENANCE SWITCH / 'ZSI' - ZONE SELECTIVE INTERLOCKING / 'L' - PROVIDE CIRCUIT BREAKER WITH LOCKING PROVISIONS / 'R'

- PROVIDE CIRCUIT BREAKER WITH RED MARKING

OPTIONS:

252 A

SPARE CAPACITY:

83 %

FEEDER AVAILABLE:

EQUIPMENT AMPS: 300 A

CONSIDER 125% DEMAND: 21750 A

DEMAND CURRENT: 48 A

DEMAND LOAD: 17400 VA

CONNECTED CURRENT: 39 A

MEQ-C 13920 VA 125.00% 17400 VA CONNECTED LOAD: 13920 VA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS

TOTAL AMPS: 36 A 41 A 41 A

TOTAL LOAD: 4293 VA 4813 VA 4813 VA

41 SPACE -- -- 1 -- 1480 VA 42

39 SPACE -- -- 1 -- 1480 VA

2 20 A SS-04-CU

37 SPACE -- -- 1 -- 960 VA 1 20 A SP-04-300 38

35 SPACE -- -- 1 -- 0 VA 1 20 A -- EXISTING 36

33 SPACE -- -- 1 -- 0 VA 1 20 A -- DAMPER 34

31 SPACE -- -- 1 -- -- 1 -- -- SPACE 32

29 3333 VA 0 VA 30

27 3333 VA 0 VA 28

UH-04-300 35 A 3

3333 VA 0 VA

3 15 A -- EF

23 0 VA 0 VA 1 20 A -- EXISTING 24

21 0 VA 0 VA 1 20 A -- EXISTING 22

4-EF-5 -- 30 A 3

0 VA 0 VA 1 20 A -- LTG 20

17 0 VA 0 VA 1 20 A -- REC 18

15 0 VA 0 VA 1 20 A -- REC 16

4-RAH-2 -- 15 A 3

0 VA 0 VA 1 20 A -- LTG 14

11 0 VA 0 VA 12

9 0 VA 0 VA 10

4-SF-5 -- 20 A 3

0 VA 0 VA

3 50 A -- 4-ACCU-3

5 0 VA 0 VA 6

3 0 VA 0 VA 4

4-EF-2 -- 90 A 3

0 VA 0 VA

3 80 A -- 4-SF-2

CKT CIRCUIT DESCRIPTION OPT RATING POLES A B C POLES RATING OPT CIRCUIT DESCRIPTION CKT

NEMA ENCLOSURE: 1

MOUNTING: SURFACE AVAILABLE SCC (kA): EXISTING PANEL POLES: 42

SERVICE RATED: No INTEGRAL SPD: No SECTIONS: 1

BRANCH: NORMAL WIRES: 4 MCB OPTIONS: -

SUPPLY FROM: PHASES: 3 MCB/MLO RATING: 300 A

LOCATION: MECH RM 211 VOLTS: 208/120 WYE MAINS TYPE: MCB

LIGHTING PANEL: 4-DP-001-211

B07-E400

MDP

E EM PANEL

E

LAUNDRY

CORRIDOR

CO-B-18

HEAT DUCT SHAFT

STORAGE

STO

014A

STO

012A

STORAGE

STORAGE

TLT

STORAGE

TLT

STAIR

STORAGE

STORAGE

STORAGE

CORRIDOR

CO-B-01

STORAGE

009A

CORRIDOR

CO-B-09

FIRE ALARM PANEL

CORRIDOR

CO-B-01A

ELEVATOR

P-22

STORAGE

SPRINKLER ROOM

STORAGE

CORRIDOR

CO-B-18A

CORRIDOR

CO-B-17

STORAGE

10360 Ellison Circle Omaha, NE 68134 Phone:

402.991.5520

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :

DESIGNER OF RECORDCONSULTANT100% CONSTRUCTION DOCUMENTS 10/03/2025

1221 N. Pennsylvania St.

Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com

GD Project: 23.1019.05

E

A CB

D FE

G IH

KEYPLAN

100% CONSTRUCTION

DOCUMENTS

10/03/2025

/3

/2

:2

:5

P

M

A u to d e s k D o c s /2

.0

V A

L o v e ll E le v a to r

U p g ra d e /5

-5

.B u ild in g

.E

R

.r v t

B07-ED100

BASEMENT LEVEL FLOOR PLAN - OVERALL -

ELECTRICAL - DEMOLITION

Elevator Upgrade

3001 N GREEN BAY RD, NORTH CHICAGO, IL 60064

556-24-115

B07

10/03/2025 KB RC

23022.012

3/32" = 1'-0"

BASEMENT LEVEL FLOOR PLAN - OVERALL - ELECTRICAL - DEMOLITION

5 5 10 15 20 25 30

3/32" = 1'-0"

FEETSCALE

CHASE

CO-1-8B

OFFICE

OFFICE

OFFICE

CORRIDOR

CO-01-06

OFFICE

OFFICE

OFFICE

CHASE

CO-1-5B

STORAGE

138A

BREAK/LOCKER

JAN

MEDICINE

MEDICINE

JAN

131A

OFFICE

OFFICE

SUPPLY

DUCT SHAFT

OFFICE

OFFICE

STORAGE

130A

STORAGE

130B

CORRIDOR

CORRIDOR

CO-1-02

STAIR

CONFERENCE

OFFICE

OFFICE

DUCT SHAFT

OFFICE

130 TEL/DATA

CO-1-5A

GROUP THERAPY

BREAK ROOM

OFFICE

OFFICE

130C

ELEVATOR

P-22

SUPPLY

TOILET

TEL/DATA

CO-1-8A

CORRIDOR

CO-1-08

JAN

PORCH

CO-2-09

PORCH

CO-2-10

STAIR

NAVY MESS

OFFICE

OFFICE

OFFICE

CORRIDOR

CO-1-09

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

CORRIDOR

CO-1-04

OFFICE

OFFICE

OFFICE

SHOWER

113A

CONFERENCE

TOILET

141A

BATH/SHOWER

TOILET

CORRIDOR

TRAMWAY

STAIR

10360 Ellison Circle Omaha, NE 68134 Phone:

402.991.5520

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :

DESIGNER OF RECORDCONSULTANT100% CONSTRUCTION DOCUMENTS 10/03/2025

1221 N. Pennsylvania St.

Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com

GD Project: 23.1019.05

E

A CB

D FE

G IH

KEYPLAN

100% CONSTRUCTION

DOCUMENTS

10/03/2025

/3

/2

:2

:5

P

M

A u to d e s k D o c s /2

.0

V A

L o v e ll E le v a to r

U p g ra d e /5

-5

.B u ild in g

.E

R

.r v t

B07-ED101

FIRST LEVEL FLOOR PLAN - OVERALL -

ELECTRICAL - DEMOLITION

Elevator Upgrade

3001 N GREEN BAY RD, NORTH CHICAGO, IL 60064

556-24-115

B07

10/03/2025 KB RC

23022.012

3/32" = 1'-0"

FIRST LEVEL FLOOR PLAN - OVERALL - ELECTRICAL - DEMOLITION

5 5 10 15 20 25 30

3/32" = 1'-0"

FEETSCALE

1-BED PATIENT

CHASE

234A

DAY ROOM

DAY ROOM

CHASE

214A

CONFERENCE

OFFICE

OFFICE

OFFICE

KITCHEN

215A

WEIGHT ROOM

2-BED PATIENT

HEAT DUCT

CO-2-03

1-BED PATIENT

1-BED PATIENT

1-BED PATIENT

1-BED PATIENT

1-BED PATIENT

2-BED PATIENT

JAN

SHOWER

212A

1-BED PATIENT

STO

233A

ELEC

233B

1-BED PATIENT

OFFICE

OFFICE

OFFICE

1-BED PATIENT

OFFICE

OFFICE

OFFICE

CORRIDOR

2-BED PATIENT

STAIR

1-BED PATIENT

STAIR

SHOWER

236A

CORRIDOR

CO-2-06

LINEN

CORRIDOR

CO-2-07

ELEVATOR

P-2-22

OFFICE

CORRIDOR-1

CO-2-01-1

PORCH

CO-2-08

PORCH

CO-2-11

JAN

LAUNDRY

TOILET

LAUNDRY

TOILET

OFFICE

BREAK ROOM

TOILET

MALE TOILET

STORAGE

1-BED PATIENT

1-BED PATIENT

CONFERENCE

TEL / DATA

CORRIDOR

CO-2-04

TEL/DATA

STAIR

CORRIDOR-2

CO-2-01-2

1-BED PATIENT

207 CORRIDOR

CO-2-02

CORRIDOR-3

CO-2-01-3

10360 Ellison Circle Omaha, NE 68134 Phone:

402.991.5520

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :

DESIGNER OF RECORDCONSULTANT100% CONSTRUCTION DOCUMENTS 10/03/2025

1221 N. Pennsylvania St.

Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com

GD Project: 23.1019.05

E

A CB

D FE

G IH

KEYPLAN

100% CONSTRUCTION

DOCUMENTS

10/03/2025

/3

/2

:2

:5

P

M

A u to d e s k D o c s /2

.0

V A

L o v e ll E le v a to r

U p g ra d e /5

-5

.B u ild in g

.E

R

.r v t

B07-ED102

SECOND LEVEL FLOOR PLAN - OVERALL -

ELECTRICAL - DEMOLITION

Elevator Upgrade

3001 N GREEN BAY RD, NORTH CHICAGO, IL 60064

556-24-115

B07

10/03/2025 KB RC

23022.012

3/32" = 1'-0"

SECOND LEVEL FLOOR PLAN - OVERALL - ELECTRICAL - DEMOLITION

5 5 10 15 20 25 30

3/32" = 1'-0"

FEETSCALE

10360 Ellison Circle Omaha, NE 68134 Phone:

402.991.5520

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10 www.specializedeng.com SES Project :

DESIGNER OF RECORDCONSULTANT100% CONSTRUCTION DOCUMENTS 10/03/2025

1221 N. Pennsylvania St.

Indianapolis, IN 46202 Phone: 317.800.6388 www.guidondesign.com

GD Project: 23.1019.05

E

A CB

D FE

G IH

KEYPLAN

100% CONSTRUCTION

DOCUMENTS

10/03/2025

/3

/2

:2

:5

P

M

A u to d e s k D o c s /2

.0

V A

L o v e ll E le v a to r

U p g ra d e /5

-5

.B u ild in g

.E

R

.r v t

B07-ED103

PENTHOUSE LEVEL FLOOR PLAN - OVERALL -

ELECTRICAL - DEMOLITION

Elevator Upgrade

3001 N GREEN BAY RD, NORTH CHICAGO, IL 60064

556-24-115

B07

10/03/2025 KB RC

23022.012

3/32" = 1'-0"

PENTHOUSE PLAN - OVERALL - ELECTRICAL - DEMOLITION

5 5 10 15 20 25 30

3/32" = 1'-0"

FEETSCALE

LAUNDRY

CORRIDOR

CO-B-18

HEAT DUCT SHAFT

STORAGE

STO

014A

STO

012A

STORAGE

STORAGE

TLT

STORAGE

TLT

STAIR

STORAGE

STORAGE

STORAGE

CORRIDOR

CO-B-01

STORAGE

009A

CORRIDOR

CO-B-09

FIRE ALARM PANEL

CORRIDOR

CO-B-01A

ELEVATOR

P-22

STORAGE

SPRINKLER ROOM

STORAGE

CORRIDOR

CO-B-18A

CORRIDOR

CO-B-17

STORAGE

B07-E400

B07-E400

MDP

EM PANEL

7-PNL-001-24

10360…