This document outlines a federal contract opportunity for construction services. The Department of Veterans Affairs seeks to construct a 6,000 square foot addition to Building 20 housing administration, dialysis, and sleep lab spaces at its Martinez, California campus. It will also renovate 4,200 square feet of Building 20 for pharmacy, administration, and retail areas and add a 1,000 square foot coffee bar to Building 19. The work includes installing dialysis boxes in patient rooms and meeting level 4 infection control requirements. The solicitation will be issued as a total Service-Disabled Veteran-Owned Small Business set-aside with a NAICS code of 236220 and size standard of $36.5 million. The period of performance is approximately 760 calendar days from notice to proceed with questions due by July 24, 2020. The estimated value is over $10 million.
View the file
Other files for this federal contract opportunity
Show all 22
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A-1,3
GFCI
GFCI
GFCI
GFCI
J J
F
DUPLEX RECEPTACLE, NEMA 5-20R, GROUNDING
TYPE WITH GROUND FAULT INTERRUPTER (GFCI)
DUPLEX RECEPTACLE, NEMA 5-20R, GROUNDING
QUAD-RECEPTACLE (DOUBLE DUPLEX), NEMA
5-20R, GROUNDING TYPE WITH GROUND FAULT INTERRUPTER
CONDUIT OR WIRE RUN EXPOSED OR ABOVE THE CEILING
BRANCH CIRCUIT HOMERUN TO PANELBOARD; LETTER AND NUMBER NOTATION
OF PHASE, NEUTRAL AND GREEN GROUND WIRES
RECEPTACLE, NEMA 6-20R, 250V (GROUNDING TYPE)-EMERGENCY POWER
RECEPTACLE, NEMA 6-20R, 250V (GROUNDING TYPE), 20A, 1 PHASE, 2 POLE, 3
WIRE- GROUNDING, UNLESS OTHERWISE NOTED
TELECOMMUNICATION OUTLET, QUAD (1 VOICE, 3 DATA)
SWITCH, 20A, 1 POLE, 120/277 V, UNLESS OTHERWISE INDICATED
MOTOR, 1 PHASE NUMBER INDICATES HORSEPOWER
COMBINATION MOTOR STARTER
ELECTRIC PANELBOARD, SURFACE MOUNTED
ELECTRIC PANELBOARD, FLUSH MOUNTED
QUAD-RECEPTACLE (DOUBLE DUPLEX), NEMA
5-20R, GROUNDING TYPE WITH GROUND FAULT INTERRUPTER
QUAD-RECEPTACLE (DOUBLE DUPLEX), NEMA
DUPLEX RECEPTACLE, NEMA 5-20R, GROUNDING
TYPE WITH GROUND FAULT INTERRUPTER (GFCI) - EMERGENCY POWER
DUPLEX RECEPTACLE, NEMA 5-20R, GROUNDING
A, B, C INDICATES SEPARATE CONTROL OF CIRCUITS AS DESIGNATED
MOTOR STARTER OR CONTROLLER
IDENTIFIES PANEL AND CIRCUIT NUMBER(S). HASHMARKS INDICATES NUMBER
CIRCUIT BREAKER, ENCLOSED
CONDUIT/WIRE TURN DOWN
CONDUIT/WIRE TURN UP
CONTACTORCR
CB
SPEAKER/PUBLIC ADDRESS
DISCONNECT SWITCH, UNFUSED
3 3 WAY SWITCH
D DIMMER
DISCONNECT SWITCH, FUSED
SP
EXIT SIGN WITH INTREGAL BATTERY BACKUP
ELECTRICAL DISTRIBUTION PANEL
TEMPERATURE CONTROLLER
TEMPERATURE INDICATOR
SUFFIX OF:
T
TI
S
EP
TYPE - EMERGENCY POWER
EMERGENCY POWER
PHASE CONDUCTORGROUND
NEUTRAL
JUNCTION BOX
5-20R, GROUNDING TYPE
TYPE
LEGEND
ELECTRICAL ABBREVIATIONS:
LIGHT FIXTURE, SURFACE MOUNTED, ON NORMAL POWER (TYP) LETTER INDICATE
TYPE (SEE LIGHTING SCHEDULE FOR SPECIFIC FIXTURE IDENTIFICATION)
FIXTURE ON EMERGENCY POWER, LETTER INDICATE TYPE (TYP.) (SEE LIGHTING
SCHEDULE FOR SPECIFIC FIXTURE IDENTIFICATION)
RECEPTACLE SHALL BE MOUNTED 18" AFF AND SWITCH SHALL BE MOUNTED 48"
AFF, UNLESS OTHERWISE NOTED.
RECEPTACLE AND SWITCH SUFFIX OF:
-A MOUNTED ±6" ABOVE COUNTERTOP OR BACKSPLASH.
-B MOUNTED ±40" AFF OR ±6" ABOVE COUNTER TOP OF SINK
-C MOUNTED ON CEILING
-F MOUNTED ON FLOOR
-W MOUNTED 48" AFF
-H MOUNTED ±12" BELOW CEILING HEIGHT
-S SURFACE MOUNTED
GFCI GROUND FAULT CIRCUIT INTERRUPTER
SC SAFETY TYPE (TAMPER RESISTANCE)
WP WEATHER PROTECTED (NEMA 3R) ENCLOSURE
AMPERE
2.
SMOKE DETECTOR
1.
S
LEGEND (CONTINUATION)
WIRELESS ROUTER
NETWORK DEVICES / WI-FI
POWER STRIP
FLOOR MOUNTED POWER AND TELECOM UNIT
P F/A PULL STATION
CARD READERCRR
CONDUIT OR WIRE RUN UNDERGROUND OR BELOW ROOF
HATCH MARK INDICATE DEMOLITION WORK
BOLD INDICATES NEW WORK
OS
OS
TV COAXIAL CABLE OUTLET
V VIDEO UNIT
MOTION DETECTORMD
TELECOMMUNICATION TERMINAL OUTLET (2 DATA)
FAINT INDICATES EXISTING WORK
OCCUPANCY SWITCH
SUFFIX 'P' INDICATES ADDITIONAL AMBIENT LIGHT CONTROL FEATURE
OCCUPANCY SENSOR - CEILING MOUNTED
SUFFIX 'P' INDICATES ADDITIONAL AMBIENT LIGHT CONTROL FEATURE
VIDEO OUTLETv
PUSHBUTTON
QUAD RECEPTACLE (DOUBLE DUPLEX), NEMA 5-20R,
GROUNDING TYPE - EMERGENCY POWER
TELECOMMUNICATION OUTLET, QUADX
(1 VOICE, 2 DATA AND 1 ANALOG FOR FAX MACHINE)
PWR POWER
CURRENT TRANSFORMER
MISCELLANEOUS
NOT APPLICABLE
MTG
MTD
N/A
MOUNTED
MOUNTING
GND
JUNCTION BOX
KILOVOLT-AMPERE
KILO-AMPERES
GOVERNMENT
MAX
MECH'L
MIN
MISC
KVA
KV
LTG
LOC
LIGHT
MAXIMUM
MECHANICAL
MINIMUM
KILOWATT
KILOVOLT
LOCATION
HT
Hz
J.B.
KA
GOV
GRN
HEIGHT
HERTZ
GROUND
GREEN
ELECTRICAL METALLIC TUBING
FULL LOAD AMPS
DISTRIBUTION
GROUND FAULT PROTECTION
GROUND FAULT CIRCUIT-INTERRUPTER
EQUIP EQUIPMENT
FLR
GFCI
GALV
GFP
FLA
EXIST / (E)
FT
GALVANIZED
FLOOR
EXISTING
FOOT, FEET
DWG
ELEC'L
ELEV
EMT
ELECT
CU
CT
DISC
DIST
DRAWING
ELECTRICAL
ELECTRIC
ELEVATION
DISCONNECT
COPPER
VOLT AMPS
TRANSFORMER
WIRE TROUGH
WEATHERPROOF
FLOOR OR GRADE
MOUNTING HEIGHT ABOVE FINISHED
PHASE
+12"A.F.F.
WP
XFMR
WT
VA
V
W
VOLT
WIRE
RECEPTACLE
SCHEDULE
SWITCHBOARD
RIGID GALVANIZED STEEL
TELEVISION
TEMPORARY
TELECOM TELECOMMUNICATION
UNDERGROUND
UNIFORM BUILDING CODE
UNDERWRITERS LABORATORIES
UNLESS OTHERWISE NOTED
SHIELDED TWISTED WIRE PAIR
TELE/TEL.
UBC
UL
U/G
UON
TV
TERM
TEMP
TYP
STP
TERMINAL
TYPICAL
ST
SW
SWBD
SCHED
RM
RGS
RECEPT
STREET
SWITCH
ROOM
CONTRACTING OFFICER REPRESENTATIVE
ABOVE FINISHED FLOOR
AMERICAN WIRE GAUGE
BARE COPPER
AMPS INTERRUPTING CAPACITY
CIRCUIT BREAKER
COMMUNICATION
AMERICAN NATIONAL STANDARDS INSTITUTE
B.C.
CKT
COR
CLG
CONN
COMM
BLDG
C.B.
CAT
C
CONNECTED
CIRCUIT
CEILING
BUILDING
CONDUIT
CATALOG
A/AMP
AFF
ANSI
AIC
AWG
NON-FUSED
NATIONAL ELECTRICAL CODE
NOT TO SCALE
NATIONAL ELECTRICAL
OVERLOAD
POLYVINYL CHLORIDE
PUBLIC ADDRESS
MANUFACTURERS ASSOCIATION
NTS
PR
PH
PVC
PRI
PNL
O.L.
P
PA
PAIR
PHASE
PRIMARY
PANEL
POLE
NEC
NO.
NF
NEMA
NUMBER
F/A FIRE ALARM
NL NIGHT LIGHT
DUAL UNIT-D
SINGLE UNIT-S
VETERANS AFFAIR MEDICAL CENTERVAMC
FSD FIRE SMOKE DAMPER
HAND-HOLEHH
EF EXHAUST FAN
KW
1. PENETRATION OF CONDUITS, RACEWAYS AND WIRING THROUGH FIRE RATED WALLS, FLOORS AND
CEILINGS SHALL BE FIRE-STOPPED IN ACCORDANCE WITH SPECIFICATION SECTION 07 84 00. FIRE
STOPPING MATERIALS AND METHODS SHALL BE A U.L. LISTED ASSEMBLY.
2. METHODS AND MATERIALS SHALL BE IN ACCORDANCE WITH NEC. EQUIPMENT SHALL BE IN
ACCORDANCE WITH THE STANDARDS OF NEMA AND ANSI. EQUIPMENT SHALL BE NEW AND LISTED
BY U.L. AND INSTALLED IN ACCORDANCE WITH THE CONDITIONS STATED IN THAT LISTING.
3. BEFORE ENERGIZING, EQUIPMENT SHALL BE TESTED TO BE FREE OF GROUNDS AND SHORTS.
4. RECEPTACLES, OUTLETS AND JUNCTION BOXES (ABOVE AND BELOW CEILING) SHALL BE
PERMANENTLY MARKED AS TO INDICATE THE CIRCUIT NUMBER AND SOURCE PANELBOARD.
PERMANENT MARKING FOR BELOW THE CEILING DEVICES SHALL BE CLEAR 3/8" WIDE STICK-ON
LABEL WITH BLACK LETTERING. PERMANENT MARKING FOR ABOVE THE CEILING DEVICES MAY BE
HAND LABELED WITH PERMANENT MARKER.
5. UNLESS OTHERWISE INDICATED, POWER AND LIGHTING CONDUCTORS SHALL BE TYPE THHN/THWN -2, 600 VOLT, SOLID OR STRANDED COPPER IN ACCORDANCE WITH SPECIFICATION SECTION 26 05 19
AND NOT SMALLER THAN #12 AWG FOR POWER AND LIGHTING CIRCUITS AND #14 AWG FOR
CONTROL CIRCUITS.
6. ALL EQUIPMENT SHALL BE PROPERLY GROUNDED IN STRICT ACCORDANCE WITH THE LATEST
EDITION OF THE NATIONAL ELECTRIC CODE (NEC). PROVIDE EQUIPMENT GROUNDING CONDUCTORS.
CONDUIT CANNOT BE USED AS THE ONLY MEANS OF GROUNDING.
7. FIXTURES AND EQUIPMENT SHALL BE SUPPORTED/MOUNTED TO COMPLY WITH THE SEISMIC
REQUIREMENTS OF THE IBC AND ASCE 7.
8. CONDUIT CONNECTIONS TO MOTORS SHALL BE MADE WITH FLEXIBLE, METAL OR LIQUID TIGHT FLEXIBLE METALLIC CONDUIT IN ACCORDANCE WITH SPECIFICATION SECTION 26 05 33. CONDUIT LENGTH SHALL NOT
BE MORE THAN 6 FEET LONG.
9. MECHANICAL ELECTRICALLY OPERATED EQUIPMENT SHALL BE PROVIDED WITH "WITHIN SIGHT"
PADLOCKABLE DISCONNECTING MEANS CONSISTING OF TOGGLE SWITCH, HORSEPOWER RATED SWITCH, SAFETY DISCONNECT SWITCH OR MOLDED CASE CIRCUIT BREAKER. OUT OF SIGHT LOCKABLE
DISCONNECTING DEVICES ARE NOT ACCEPTABLE TO MEET THIS REQUIREMENT.
10. CONTRACTOR SHALL COORDINATE ELECTRICAL WORK WITH OTHER TRADES.
11. LABEL AND IDENTIFY ALL PANEL SCHEDULES.
12. DEDICATED NEUTRAL SHALL BE PROVIDED FOR ALL NEW 120 AND 277 VOLT CIRCUITS.
13. ALL CONDUITS SHALL BE CONCEALED IN ACCORDANCE WITH SPECIFICATION 26 05 33, CONDUITS SHALL RUN ABOVE THE CEILING, BELOW FINISH FLOOR OR BEHIND THE FINISH WALL, UNLESS OTHERWISE
NOTED.
14. "PROVIDE" MEANS "FURNISH AND INSTALL".
15. ALL ELECTRICAL CONSTRUCTION WORK, METHODS AND MATERIALS SHALL BE IN COMPLIANCE WITH
THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE (NEC) AND APPLICABLE GOVERNMENT
AND VETERANS ADMINISTRATION RULES AND REGULATIONS.
16. ROUTE ALL TELECOMMUNICATION CIRCUITS 18" MINIMUM APART FROM ELECTRICAL CIRCUITS. IN
LOCATIONS WHERE MINIMUM SEPARATION CAN NOT BE OBTAINED, WRAP TELECOMMUNICATION
CIRCUITS WITH GROUNDED METALLIC SHEET TO REDUCE NOISE INTERFERENCE.
17. ALL TELECOMMUNICATION WIRES SHALL BE SUPPORTED BY HANGERS OR WIRE TRAYS. WIRES LAY
ON SUSPENDED CEILING IS PROHIBITED.
18. ALL ABOVE CEILING RACEWAYS, OUTLETS, J.B's AND PULL BOXES SHALL BE HUNG ON THE
CONCRETE SLAB. WALL MOUNTING IS NOT PERMITTED, UNLESS APPROVED BY VAMC
19. PROVIDE ADDITIONAL ACCESS PANEL PER NEC, AS REQUIRED, ON HARD CEILING FOR ELECTRICAL DEVICES, EQUIPMENT, J.B. ETC. ACCESS
GENERAL NOTES:
F/A STROBE
F/A SPEAKER
STROBE AND SPEAKER
M
M MOTOR, 3 PHASE NUMBER INDICATES HORSEPOWER
VARIABLE FREQUENCY DRIVE
TV
SECURE WI-FI CONNECTION
S
UNSECURE WI-FI CONNECTION
LIGHT FIXTURE RECESSED, ON NORMAL POWER (TYP) LETTER INDICATE TYPE (SEE LIGHTING
SCHEDULE FOR SPECIFIC FIXTURE IDENTIFICATION)
VARIABLE FREQUENCY DRIVEVFD
# NOTE REFERENCE
EP###
# DETAIL
DRAWING NUMBER ON WHICH DETAIL IS DRAWN
MECHANICAL EQUIPMENT TAG
XXX
XX
CABLE TRAY
AIR CONDITIONINGA/C
F/A
CAMERA
J T TELEPHONE JUNCTION BOX
SIMPLEX RECEPTACLE, NEMA 5-20R GROUNDING TYPE
SIMPLEX RECEPTACLE, NEMA 5-20R GROUNDING TYPE
WITH GROUND FAULT INTERRUPTER (GFCI)
SWITCHED SPLIT DUPLEX OUTLET, NEMA 5-20R, GROUNDING
TYPE TOP RECEPTACLE SWITCHED
-U UNDER COUNTER / MOUNTED ±18" AFF
NIGHT LIGHT, +/- 18" AFFNL
PENDANT-MTD STRIP LIGHT
TO BE DETERMINETBD
UNSHIELDED TWISTED WIRE PAIRUTP
(R) RELOCATE
S
GFCI
NEW(N)
RECEPTACLE, NEMA 6-20R, 250V (GROUNDING TYPE), 50A, 1 PHASE, 2 POLE, 3
WIRE, GROUNDING, UNLESS OTHERWISE NOTED
50A
VS VACANCY SENSOR - CEILING MOUNTED
E
EXIT SIGN WITHOUT INTREGAL BATTERY BACKUP
US
20. PROVIDE ALL THE EQUIPMENT REQUIRED LOW VOLTAGE CONDUITS AND WIRES.
S T
A
T E
O F C A L I F OR N
I A
EXP.________
E 17641 9-30-2019
R E
G
IS
TE
RED
PROFESS IONAL
ENG
IN
E E
RA
U
G
UST I NE K . LEU
N G
E
L E C T R I C A
L
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9 o n e e ig h t in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h ts i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t o n e i n c h o n e f o o t
VA FORM 08-6231
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Drawing Title: Project Title: Project Number:
Building Number:
Drawing Number:Location
Date Checked Drawn
Office of Construction and Facilities Management
Dwg. of
VA MARTINEZ CAMPUS , CA
19 & 20K. F. DAVIS ENGINEERING INC.
530 LA GONDA WAY, SUITE E
DANVILLE, CA 94526
WWW.KFDE.US
(925) 743-8884
02/25/2020
2/25/2020 10:25:35 AMC:\Users\ashrestha\Documents\CHRONIC DIALYSIS FINAL STAMPED SUBMITTAL - REV 2 - V2018_anil.shrestha9MD6R.rvt
CHRONIC DIALYSIS AND
SLEEP PROGRAM
I. VALDOV
E100
ELECTRICAL GENERAL NOTES,
LEGEND AND ABBREVIATIONS
A. LEUNG
612-502
I. VALDOV
1 FURNITURE PLAN 9/9/2019
2 CLIENT COMMENTS 1/28/2020
A A
AA
AA
A A A
AA
A A
A A
A A
A A
A
AA A A
A
A A
A
A A
A A
AAAA A
AAAA
A A A A
AAAA
A A
A A
AAAAA
SS
S S
S S
CCCC
S
S
S
OS
C
C
C
C
S S
S S
S
F
SS SS SS SS SS
S S
S S
SS
S
S
S
S 3 S 3 S 3
E
E E
E E
E
E E
E
E
E
B BB
BBB
BB
BB
BB
BB
B
B
B
B
B
B
B
B
A
A
S S
37.1 38 40 41 42 44 48 50 52 53 54 57 60 63 68 7040.8 48.2 74
B27
CHB-2
CHB-2
CHB-2
CHB-2
CHB-2
CHB-2
CHB-2
CLB-2
CHB-2
E E
E
CHB-2
CLB-2
CLB-2
CLB-2
CLB-2
CLB-2
7 3 4 5 1
CHB-2
B30
B31
B29
B28
SPSP
1. EQUIPMENT SHOWN ARE FOR REFERENCE ONLY AND DO NOT
REPRESENT THE TOTAL NUMBER OR EXACT LOCATION OF EXISTING
EQUIPMENT. CONTRACTOR SHALL FIELD INVESTIGATE THE EXACT
NUMBER AND LOCATION OF EXISTING EQUIPMENT IN THE REMODEL
AREA. CONTRACTOR IS TO DISCONNECT AND REMOVE ALL EXISTING
ELECTRICAL EQUIPMENT, ASSOCIATED WIRES, DEVICES, EXPOSED
AND ABOVE CEILING AND BELOW FLOOR CONDUITS,
OUTLET/JUNCTION BOXES, BACK TO THE SOURCE, UNLESS
OTHERWISE NOTED.
2. SOME OF THE EXISTING EQUIPMENT CIRCUITS FEED MULTIPLE
PIECES OF EXISTING EQUIPMENT THAT IS TO REMAIN OR OUTSIDE
OF THE REMODEL AREA CONTRACTOR SHALL FIELD VERIFY THESE
CIRCUITS AND USE CARE IN THE DISCONNECTION AND REMOVAL OF
THE EQUIPMENT CIRCUITS TO AVOID DISCONNECTING EQUIPMENT,
WHICH IS TO REMAIN, CONTRACTOR SHALL REROUTE CONDUIT AND
CABLES, AS REQUIRED, TO MAINTAIN CIRCUIT INTEGRITY OF THE
EQUIPMENT THAT IS TO REMAIN.
3. ON WALLS AND FLOORS THAT ARE TO REMAIN, REMOVE EXISTING
JUNCTION BOXES THAT ARE NO LONGER IN USE. CAP AND SEAL ALL
IN WALL CONDUITS THAT ARE NO LONGER IN USE AND LABEL AS
SPARE. CONTRACTOR SHALL REPAIR WALL AND FLOOR TO MATCH
EXISTING.
4. EQUIPMENT SOURCE CIRCUIT AND PANEL BOARD SHOWN ARE FOR
REFERENCE ONLY. CONTRACTOR SHALL FIELD VERIFY SOURCE
CIRCUIT AND PANEL BOARD ON EXISTING EQUIPMENT BEING
REMOVED PRIOR TO DEMOLITION.
5. WHETHER SHOWN OR NOT, REMOVE AND REINSTALL WIFI
ANTENNA IN THE SAME LOCATION, IF POSSIBLE, OR WITHIN 3 FEET
OF THE EXISTING LOCATION. COORDINATE WITH VAMC ON WIFI
ANTENNAS' FINAL LOCATIONS.
GENERAL NOTES
SHEET NOTES
1 ALL NORMAL POWER LIGHTS IN THE OFFICE AREA ARE FED FROM
NHB-1 (PNL NHB, CKT 1) UNLESS OTHERWISE NOTED.
CIRCUIT CHB-2 (PNL CHB, CKT 2) ALSO FEEDS EMERGENCY LTG OUTSIDE
OF THE REMODEL AREA.
SUSPENDED FIXTURES AND WALL SCONES IN THE CANTEEN AREA ARE
FED FROM NLB-37 (PNL NLB, CKT 37) UNLESS OTHERWISE NOTED.
2 X 4 FIXTURES IN THE CANTEEN AREA ARE FED FROM NHB-3 (PNL NHB,
CKT 3) UNLESS OTHERWISE NOTED.
DOWNLIGHT IN THE CANTEEN ARE FED FROM NLB-39 (PNL NLB, CKT 39)
UNLESS OTHERWISE NOTED
CIRCUIT CLB-2 (PNL CLB, CKT 2) ALSO FEEDS EMERGENCY LTGS
OUTSIDE OF THE REMODEL AREA
CEILING FIXTURES IN THE PHARMACY AREA ARE FED FROM CHB-2
(PNL CHB, CKT 2) UNLESS OTHERWISE NOTED.
LEGEND
2x2 CEILING RECESSED FIXTURE
CEILING RECESSES DOWNLIGHT
WALL-MTD SCONE
CEILING SUSPENDED FIXTURE
2x4 CEILING RECESSED FIXTURE
WALL-MTD VANITY LIGHT
PLUG-CONNECTED, WALL-MTD BUG LIGHT
CEILING SPEAKER
A
B
A
F
S
E
C
SP
S T A T E
O F C A L I F OR N
I A
EXP.________
E 17641 9-30-2019
RE
G
IS
TE
RED PROFESS IONAL
ENG
INEERA
UG
UST I NE K . LEUNG
E
L E C T R I C A L
PROJECT
NORTH
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9 on e ei gh t i nc h on e fo ot on e qu ar te r i nc h on e fo ot th re e ei gh ts in ch o ne fo ot on e ha lf in ch o ne fo ot th re e qu ar te rs in ch o ne fo ot on e in ch o ne fo ot on e an d on e ha lf in ch o ne fo ot on e in ch o ne fo ot
VA FORM 08-6231
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Drawing Title: Project Title: Project Number:
Building Number:
Drawing Number:Location
Date Checked Drawn
Office of Construction and Facilities Management
Dwg. of
VA MARTINEZ CAMPUS , CA
19 & 20K. F. DAVIS ENGINEERING INC.
530 LA GONDA WAY, SUITE E
DANVILLE, CA 94526
WWW.KFDE.US
(925) 743-8884
KEY PLAN
C BUILDING 19
BUILDING 20
02/25/2020
2/25/2020 8:08:55 AMC:\Users\ashrestha\Documents\CHRONIC DIALYSIS FINAL STAMPED SUBMITTAL - REV 2 - V2018_anil.shrestha9MD6R.rvt
CHRONIC DIALYSIS AND
SLEEP PROGRAM
I. VALDOV
ED101C
ELECTRICAL LIGHTING DEMOLITION
PLAN - RENOVATION C
A. LEUNG
612-502
I. VALDOV
1/4" = 1'-0"ED101C
1 ELECTRICAL LIGHTING DEMOLITION PLAN - RENOVATION C
JW
J
J
J
CAN-26 CAN-26
C A
N -2
-H
PNL CAN
M O
TO
R
IZ
E
D
S C
R E
E N
IN
C
LG
P R
O
JE
C
TO
R C
E
IL
IN
G
M O
U N
T E
D
A/C 1
WIRE WAY TO
MODULAR
FURNITURE (TYP)
J T
PRINTER
OUTLET
WIREMOLD
TV
37.1 38 40 41 42 44 48 50 52 53 54 57 60 63 68 7040.8 48.2 74
B27
5CLB-16
CLB-16
NLB-1
T-CAN
T
B30
B31
B29
B28
B26
4.33
VAV
4.34
VAV
4.35
VAV
4.36
VAV
1.
2.
3.
4.
5.
GENERAL NOTES
EQUIPMENT SHOWN ARE FOR REFERENCE ONLY AND DO NOT
REPRESENT THE TOTAL NUMBER OR EXACT LOCATION OF EXISTING
EQUIPMENT. CONTRACTOR SHALL FIELD INVESTIGATE THE EXACT
NUMBER AND LOCATION OF EXISTING EQUIPMENT IN THE REMODEL
AREA. CONTRACTOR IS TO DISCONNECT AND REMOVE ALL EXISTING
ELECTRICAL EQUIPMENT, ASSOCIATED WIRES, DEVICES, EXPOSED
AND ABOVE CEILING AND BELOW FLOOR CONDUITS,
OUTLET/JUNCTION BOXES BACK TO THE SOURCE, UNLESS
OTHERWISE NOTED.
SOME OF THE EXISTING EQUIPMENT CIRCUITS FEED MULTIPLE
PIECES OF EXISTING EQUIPMENT THAT IS TO REMAIN OR OUTSIDE OF
THE REMODEL AREA. CONTRACTOR SHALL FIELD VERIFY THESE
CIRCUITS AND USE CARE IN THE DISCONNECTION AND REMOVAL OF
THE EQUIPMENT CIRCUITS TO AVOID DISCONNECTING EQUIPMENT,
WHICH IS TO REMAIN, CONTRACTOR SHALL REROUTE CONDUIT AND
CABLES, AS REQUIRED, TO MAINTAIN CIRCUIT INTEGRITY OF THE
EQUIPMENT THAT IS TO REMAIN.
ON WALLS AND FLOORS THAT ARE TO REMAIN, REMOVE EXISTING
JUNCTION BOXES THAT ARE NO LONGER IN USE. CAP AND SEAL ALL
CONDUITS THAT ARE NO LONGER IN USE AND LABEL AS SPARE.
CONTRACTOR SHALL REPAIR WALL AND FLOOR TO MATCH EXISTING.
EQUIPMENT SOURCE CIRCUIT AND PANELBOARD SHOWN ARE FOR
REFERENCE ONLY. CONTRACTOR SHALL FIELD VERIFY SOURCE
CIRCUIT AND PANELBOARD ON EXISTING EQUIPMENT BEING
REMOVED PRIOR TO DEMOLITION.
SEE MECHANICAL DRAWING ON MECHANICAL EQUIPMENT
DEMOLITION REQUIREMENTS.
SHEET NOTES
1 REMOVE A/C UNIT CONDUIT WIRES AND ASSOCIATED DEVICES.
REMOVE CAMERA.
RECEPT IN THE OFFICE AREA ARE FED FROM NLB-3, 5, 7, 9, 11, 13,
15, 17, 19, 21, AND 23, UON.
CKT NLB-7 ALSO FED RECEPT OUTSIDE OF THE REMODEL AREA.
CKT CLB-16 (PNL CLB, CKT 16) ALSO FED EQUIP OUTSIDE OF THE
REMODEL AREA.
EQUIPMENT IN CANTEEN KITCHEN AND STORAGE AREA ARE FED
FROM PNL CAN, UON.
RECEPT IN CANTEEN SEATING AREA ARE FED FROM NLB-1 & 2 (PNL
NLB, CKT 1 & 2), UON.
CKT NLB-2 ALSO FED RECEPT OUTSIDE OF THE REMODEL AREA.
EQUIPMENT IN PHARMACY AREA ARE FED FROM NLK-37, 39, 41 (PNL
NLK, CKT 37, 39, 41), UON.
REMOVE ALL CONDUITS, WIRES AND DEVICES ASSOCIATED WITH
VAV.
VAV POWER CIRCUIT IS TO REMAIN FOR EXTENSION TO FEED NEW
VAV. SEE DRAWING EP122C
REMOVE ALL OTHER CONDUITS, WIRES AND DEVICES ASSOCIATED
WITH THE VAV.
S T A T E
O F C A L I F OR N
I A
EXP.________
E 17641 9-30-2019
RE
G
IS
TE
RED PROFESS IONAL
ENG
INEERA
UG
UST I NE K . LEUNG
E
L E C T R I C A L
PROJECT
NORTH
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9 on e ei gh t i nc h on e fo ot on e qu ar te r i nc h on e fo ot th re e ei gh ts in ch o ne fo ot on e ha lf in ch o ne fo ot th re e qu ar te rs in ch o ne fo ot on e in ch o ne fo ot on e an d on e ha lf in ch o ne fo ot on e in ch o ne fo ot
VA FORM 08-6231
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Drawing Title: Project Title: Project Number:
Building Number:
Drawing Number:Location
Date Checked Drawn
Office of Construction and Facilities Management
Dwg. of
VA MARTINEZ CAMPUS , CA
19 & 20K. F. DAVIS ENGINEERING INC.
530 LA GONDA WAY, SUITE E
DANVILLE, CA 94526
WWW.KFDE.US
(925) 743-8884
KEY PLAN
C BUILDING 19
BUILDING 20
02/25/2020
2/25/2020 8:08:58 AMC:\Users\ashrestha\Documents\CHRONIC DIALYSIS FINAL STAMPED SUBMITTAL - REV 2 - V2018_anil.shrestha9MD6R.rvt
CHRONIC DIALYSIS AND
SLEEP PROGRAM
I. VALDOV
ED102C
ELECTRICAL POWER DEMOLITION
PLAN - RENOVATION C
A. LEUNG
612-502
I. VALDOV
1/4" = 1'-0"ED102C
1 ELECTRICAL POWER DEMOLITION PLAN - RENOVATION C
F .E
.C .C
GCG
CG
CG
CG
CG
JK
12.9
HL
O S
O S
D
D D ccc
A 24 A
A
T1
A
A
A
T1
B
B
B
B
B
B
C
C
C
C
C
C
T1
K
F F
J
J
G
H
A
A
A
A
A
J SP
J SP2
4 5
PNL HAA1, CKT 24
J
J
J
E
E
SP
SP
S
US
GENERAL NOTES
1.
2.
3.
4.
5.
6.
7.
8.
FOR SIMPLICITY AND CLARITY BRANCH FEEDER CONDUIT AND WIRES
ARE NOT SHOWN ON THE DRAWING. ONLY CIRCUIT NUMBER TO THE
EQUIPMENT AND HOMERUNS ARE SHOWN. CONTRACTOR SHALL
PROVIDE AND INSTALL BRANCH FEEDER CONDUITS, OUTLET BOXES,
WIRE AND JUNCTION BOXES FOR NEW WIRING INSTALLATION. ALL
HOMERUN CIRCUITS ARE 2 #10 AND 1 #10 GND (GRN) IN A 3/4"
CONDUIT, UNLESS OTHERWISE NOTED.
LIGHT SWITCHES MOUNTED 48" A.F.F., UNLESS OTHERWISE
INDICATED.
ALL CONDUITS SHALL BE CONCEALED IN ACCORDANCE WITH
SPECIFICATION SECTION 26 05 33. CONDUIT SHALL RUN ABOVE
CEILING OR WITHIN FINISHED WALLS.
CORE DRILL WALL AND FLOOR FOR CONDUITS PENETRATION, AS
REQUIRED.
LIGHT CIRCUIT IS FROM PANEL HAA1, CKT 24.
PROVIDE ADDITIONAL ACCESS PANELS, AS REQUIRED PER NEC, ON
HARD CEILING FOR ELECTRICAL J.B., DEVICES, EQUIPMENT, ETC.
OCCUPANCY SENSORS SHALL BE SUITABLE FOR LED LIGHT FIXTURE
AND IT SHALL PROVIDE COMPLETE COVERAGE OF THE ASSOCIATED
AREA WHERE THE OCCUPANCY SENSOR IS INSTALLED.
CONTRACTOR SHALL PROVIDE SPEAKERS FOR PUBLIC ADDRESS
SYSTEM TO MATCH EXISTING FACILITY SPEAKERS. TIE IN THE NEW
SPEAKERS TO THE EXISTING PUBLIC ADDRESS SYSTEM. PROVIDE A
SUFFICIENT NUMBER OF SPEAKERS AS NECESSARY TO ACHIEVE
ADEQUATE SOUND COVERAGE THROUGHOUT THE REMODEL AREA.
COORDINATE WITH VAMC ON EXISTING SYSTEM TYPE,
REQUIREMENTS AND POINT OF CONNECTION.
SHEET NOTES
PROVIDE AN UNSWITCHED HOT WIRE CONNECTION TO
EMERGENCY DRIVER.
4" X 4" J.B. FOR SECURED WI-FI. RUN WIRES TO ROOM D101.
COORDINATE WITH VAMC ON J.B. EXACT LOCATION.
4" X 4" J.B. FOR PUBLIC WI-FI. RUN WIRES TO ROOM D101.
COORDINATE WITH VAMC ON J.B. EXACT LOCATION.
COORDINATE WITH VMAC ON WI-FI WIRING REQUIREMENTS AND
POINT OF TERMINATION.
COORDINATE WITH COR ON PUBLIC ADDRESS SPEAKER
REQUIREMENTS AND POINT OF TERMINATION.
PROVIDE SPEAKERS MATCHING EXISTING SPEAKERS AND SYSTEM
IN BLDG 19.
MARK "LTG-COFFEE BAR" ON PANELBOARD SCHEDULE.
PROVIDE LABEL ON SWITCH "EMERGENCY LIGHT MAINTENANCE
DISCONNECT".
S T
A
T E
O F C A L I F OR N
I A
EXP.________
E 17641 9-30-2019
R E
G
IS
TE
RED
PROFESS IONAL
ENG
IN
E E
RA
U
G
UST I NE K . LEU
N G
E
L E C T R I C A
L
PROJECT
NORTH
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9 o n e e ig h t in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h ts i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t o n e i n c h o n e f o o t
VA FORM 08-6231
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Drawing Title: Project Title: Project Number:
Building Number:
Drawing Number:Location
Date Checked Drawn
Office of Construction and Facilities Management
Dwg. of
VA MARTINEZ CAMPUS , CA
19 & 20K. F. DAVIS ENGINEERING INC.
530 LA GONDA WAY, SUITE E
DANVILLE, CA 94526
WWW.KFDE.US
(925) 743-8884
KEY PLAN
A
BUILDING 19
BUILDING 20
02/25/2020
2/25/2020 9:54:52 AMC:\Users\ashrestha\Documents\CHRONIC DIALYSIS FINAL STAMPED SUBMITTAL - REV 2 - V2018_anil.shrestha9MD6R.rvt
CHRONIC DIALYSIS AND
SLEEP PROGRAM
I. VALDOV
EL110A
ELECTRICAL LIGHTING, PUBLIC
ADDRESS AND WI-FI PLAN -
ADDITION A
A. LEUNG
612-502
I. VALDOV
PROJECT
NORTH
1/4" = 1'-0"EL110A
1 ELECTRICAL LIGHTING PLAN - ADDITION A
F.E.C. F.E.C.
D D
3D
D
3D
3D
DD
3D
D D D
3D3D
3D
3D
3D 3D
3D
3D
3D
3D
DD
D
3D 3D
3D 3D
GENERAL NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
FOR SIMPLICITY AND CLARITY BRANCH FEEDER CONDUIT AND WIRES
ARE NOT SHOWN ON THE DRAWING. ONLY CIRCUIT NUMBER TO THE
EQUIPMENT AND HOMERUNS ARE SHOWN. CONTRACTOR SHALL
PROVIDE AND INSTALL BRANCH FEEDER CONDUITS, OUTLET BOXES,
WIRE AND JUNCTION BOXES FOR NEW WIRING INSTALLATION. ALL
HOMERUN CIRCUITS ARE 2 #10 AND 1 #10 GND (GRN) IN A 3/4"
CONDUIT, UNLESS OTHERWISE NOTED.
LIGHT SWITCHES MOUNTED 48" A.F.F., UNLESS OTHERWISE
INDICATED.
ALL CONDUITS SHALL BE CONCEALED IN ACCORDANCE WITH
SPECIFICATION SECTION 26 05 33. CONDUIT SHALL RUN ABOVE
CEILING OR WITHIN FINISHED WALLS.
CORE DRILL WALL AND FLOOR FOR CONDUITS PENETRATION, AS
REQUIRED.
OCCUPANCY SENSOR LOCATION AND AMOUNT SHOWN IS FOR
REFERENCE ONLY. CONTRACTOR IS TO PROVIDE SUFFICIENT
NUMBER OF OCCUPANCY SENSORS, INSTALL AT LOCATIONS WHICH
COMPLETELY COVERS THE AREA WHERE THE OCCUPANCY SENSORS
ARE INSTALLED
PROVIDE ADDITIONAL ACCESS PANEL, AS REQUIRED PER NEC, ON
HARD CEILING FOR ELECTRICAL J.B., DEVICES, EQUIPMENT, ETC.
ACCESSIBLE.
OCCUPANCY SENSOR SHALL BE SUITABLE FOR LED LIGHT FIXTURE
AND IT SHALL PROVIDE COMPLETE COVERAGE OF THE ASSOCIATED
AREA WHERE THE OCCUPANCY SENSOR IS INSTALLED.
CONTRACTOR SHALL PROVIDE SPEAKERS FOR PUBLIC ADDRESS
SYSTEM TO MATCH EXISTING FACILITY SPEAKERS. TIE IN THE NEW
SPEAKERS TO THE EXISTING PUBLIC ADDRESS SYSTEM. PROVIDE A
SUFFICIENT NUMBER OF SPEAKERS AS NECESSARY TO ACHIEVE
ADEQUATE SOUND COVERAGE THROUGHOUT THE REMODEL AREA.
COORDINATE WITH COR ON EXISTING SYSTEM TYPE, REQUIREMENTS
AND POINT OF CONNECTION.
CIRCUIT NUMBERS WITHOUT ANY PANEL IDENTIFICATION ARE LIGHT
CIRCUITS FROM PANEL NHG, OTHERS ARE PRECEEDED BY PANEL
DESIGNATION.
6 7
C
E
F
G
CONFERENCE
G109
NEPHRO - LOGIST
G110
STERILE
EQUIPMENT
G111 TOILET 1
G112
SLEEP ROOM 1
G113 ba a a b
TOILET 3
G115A
TOILET 1
G113A
CONTROL ROOM
G114
PRINT/COPY
C410A
SLEEP ROOM 3
G115
SLEEP ROOM 4
G116
SLEEP ROOM 2
G117
TOILET 2
G118
DIALYSIS
EQUIPMENT
G119
CORRIDOR 2
C409
CORRIDOR 4
C410
TOILET 4
G116A
TOILET 2
G117A b a b
OS
OS
OS
OS
a
B
A
6.3 6.4
B.8
C.8
D
F.8
CORRIDOR 3
C408
OS
OS
8.1 9 10
E2 b a a a
O S
O S
E2
E2E2 aa a a aa a a aa a a b bb
B1
B1
B1
B1B1B1
B1B1B1
B1
B1B1 K
K
D1
D1
D1
D1
D2
D2
E2
E2
E
F
E
F
D1 D1
O S
D1
D1D1
O S
O S
D
8 8.5
B1
D1
B1
F
B1
B1
T1
SP
F
FF
F
F
F F
F
F F
F F
FF
FF
F
FF
F
F
F F
F
T1 K
OS
SP
SPOSSP
T1
OS
OS
SP
T1
SP
SP
T1
T1
DEMO EXISTING LIGHT
CHG-4
CHG-44
CHG-4
4 4
CHG-2
4 CHG-2
CHG-2
CHG-4
CHG-2
CHG-2
4 4
4 4
4 4
4 4
CHG-2
4 4
4 4
CHG-2
CHG-2
CHG-2
CHG-2
CHG-2
CHG-2
CHG-2
CHG-2
CHG-2
CHG-2
CHG-2
1 CHG-2 (TYP)
2 CHG-4 (TYP)
3 (TYP)
2 (TYP)
CHG-2
PNL NHG, CKT4
CHG-2
CHG-2
CHG-2
CHG-2
CHG-2
CHG-2
CHG-2
CHG-2
PNL CHG, CKT2
CHG-4
T1
SP
T1
PNL CHG, CKT4
CHG-4
OS
CHG-2
OS
T1
CHG-4
3 (TYP)
SEE EL 110.1B FOR
CONTINUATION
SEE EL 110.1B FOR
CONTINUATION
ALL EMERGENCY LITE CIRCUIT IS FROM PANEL CHG CIRCUIT #2
ALL EXIT LITE CIRCUIT IS FROM PANEL CHG CIRCUIT #4
LIGHT CIRCUIT IS FROM PANEL NHG CIRCUIT #4
SHEET NOTES:
S T A T E
O F C A L I F OR N
I A
EXP.________
E 17641 9-30-2019
RE
G
IS
TE
RED PROFESS IONAL
ENG
INEERA
UG
UST I NE K . LEUNG
E
L E C T R I C A L
PROJECT
NORTH
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9 on e ei gh t i nc h on e fo ot on e qu ar te r i nc h on e fo ot th re e ei gh ts in ch o ne fo ot on e ha lf in ch o ne fo ot th re e qu ar te rs in ch o ne fo ot on e in ch o ne fo ot on e an d on e ha lf in ch o ne fo ot on e in ch o ne fo ot
VA FORM 08-6231
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Drawing Title: Project Title: Project Number:
Building Number:
Drawing Number:Location
Date Checked Drawn
Office of Construction and Facilities Management
Dwg. of
VA MARTINEZ CAMPUS , CA
19 & 20K. F. DAVIS ENGINEERING INC.
530 LA GONDA WAY, SUITE E
DANVILLE, CA 94526
WWW.KFDE.US
(925) 743-8884
KEY PLAN
B
BUILDING 19
BUILDING 20
02/25/2020
2/25/2020 8:09:03 AMC:\Users\ashrestha\Documents\CHRONIC DIALYSIS FINAL STAMPED SUBMITTAL - REV 2 - V2018_anil.shrestha9MD6R.rvt
CHRONIC DIALYSIS AND
SLEEP PROGRAM
I. VALDOV
EL110.1B
ELECTRICAL LIGHTING PLAN EAST -
ADDITION B
A. LEUNG
612-502
I. VALDOV
PROJECT
NORTH
1/4" = 1'-0"EL110.1B
1 ELECTRICAL LIGHTING PLAN EAST - ADDITION B
.C
DDDD
D D
3D
3D
3D
3D
D
3D
3D
3D
3D
3D
3D
3D 3D
3D 3D
1 2 3 4 6
C
E
F
G
CHIEF
G106 CONSULT
G107
ELECTRICAL
ROOM
G108
OPEN OFFICE
G100
OS
TELECOM
G105
SUPV
G104
SUPV
G103
SUPV
G102
CONFERENCE
G109
CORRIDOR 1
C411
2.9
B
A
3.5
B.8
C.8
D
F.8
4.7
CORRIDOR 3
C408
OS
OS
B1
D1
D1
D2
D2
D1
K B1B1
E1
E1 E2 E1
E1E2 E2
E2
E2
E2 D1
D1
D2 D2 D2 D2
D2 D2 D2 D2
C1 C1 C1 C1
D1 D1 D1
D1 D1 D1
OS
OS
OS
C1C1K
F
D1
OS
SP
T1
SP
SP
T1
T1
T1
SP
SPSP
SPSP
SP
T1
D
D
D
DEMO EXISTING LIGHT
CHG-4
CHG-2
CHG-2
CHG-2
CHG-2
CHG-2
2 (TYP)
2CHG-4
CHG-2
CHG-2
CHG-2
CHG-2
CHG-2
CHG-2
CHG-2
CHG-2
3 CHG-2
1 (TYP)
CHG-4
OS
CHG-2
OS
T1
CHG-4
CHG-4
SEE EL 110.1B FOR
CONTINUATION
SEE EL 110.1B FOR
CONTINUATION
PNL NHG
CKT 2.
(TYP)
GENERAL NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
FOR SIMPLICITY AND CLARITY BRANCH FEEDER CONDUIT AND
WIRES ARE NOT SHOWN ON THE DRAWING. ONLY CIRCUIT
NUMBER TO THE EQUIPMENT AND HOMERUNS ARE SHOWN.
CONTRACTOR SHALL PROVIDE AND INSTALL BRANCH FEEDER
CONDUITS, OUTLET BOXES, WIRE AND JUNCTION BOXES FOR NEW
WIRING INSTALLATION. ALL HOMERUN CIRCUITS ARE 2 #10 AND 1 #
10 GND (GRN) IN A 3/4" CONDUIT, UNLESS OTHERWISE NOTED.
LIGHT SWITCHES MOUNTED 48" A.F.F., UNLESS OTHERWISE
INDICATED.
ALL CONDUITS SHALL BE CONCEALED IN ACCORDANCE WITH
SPECIFICATION SECTION 26 05 33. CONDUIT SHALL RUN ABOVE
CEILING OR WITHIN FINISHED WALLS.
CORE DRILL WALL AND FLOOR FOR CONDUITS PENETRATION, AS
REQUIRED.
OCCUPANCY SENSOR LOCATION AND AMOUNT SHOWN IS FOR
REFERENCE ONLY. CONTRACTOR IS TO PROVIDE SUFFICIENT
NUMBER OF OCCUPANCY SENSORS, INSTALL AT LOCATIONS
WHICH COMPLETELY COVERS THE AREA WHERE THE OCCUPANCY
SENSORS ARE INSTALLED
CIRCUIT NUMBERS WITHOUT ANY PANEL IDENTIFICATION ARE
LIGHT CIRCUITS FROM PANEL NHG; OTHERS ARE PROCEEDED BY
PANEL IDENTIFICATION.
PROVIDE ADDITIONAL ACCESS PANEL, AS REQUIRED PER NEC, ON
HARD CEILING FOR ELECTRICAL J.B., DEVICES, EQUIPMENT, ETC.
ACCESSIBLE.
OCCUPANCY SENSORS SHALL BE SUITABLE FOR LED LIGHT
FIXTURE AND IT SHALL PROVIDE COMPLETE COVERAGE OF THE
ASSOCIATED AREA WHERE THE OCCUPANCY SENSOR IS
INSTALLED.
CONTRACTOR SHALL PROVIDE SPEAKERS FOR PUBLIC ADDRESS
SYSTEM TO MATCH EXISTING FACILITY SPEAKERS. TIE IN THE NEW
SPEAKERS TO THE EXISTING PUBLIC ADDRESS SYSTEM. PROVIDE
A SUFFICIENT NUMBER OF SPEAKERS AS NECESSARY TO
ACHIEVE ADEQUATE SOUND COVERAGE THROUGHOUT THE
REMODEL AREA. COORDINATE WITH COR ON EXISTING SYSTEM
TYPE, REQUIREMENTS AND POINT OF CONNECTION.
ALL EMERGENCY LITE CIRCUIT IS FROM PANEL CHG CIRCUIT #2
ALL EXIT LITE CIRCUIT IS FROM PANEL CHG CIRCUIT #4
LIGHT CIRCUIT IS FROM PANEL NHG CIRCUIT #2
SHEET NOTES:
S T A T E
O F C A L I F OR N
I A
EXP.________
E 17641 9-30-2019
RE
G
IS
TE
RED PROFESS IONAL
ENG
INEERA
UG
UST I NE K . LEUNG
E
L E C T R I C A L
PROJECT
NORTH
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9 on e ei gh t i nc h on e fo ot on e qu ar te r i nc h on e fo ot th re e ei gh ts in ch o ne fo ot on e ha lf in ch o ne fo ot th re e qu ar te rs in ch o ne fo ot on e in ch o ne fo ot on e an d on e ha lf in ch o ne fo ot on e in ch o ne fo ot
VA FORM 08-6231
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Drawing Title: Project Title: Project Number:
Building Number:
Drawing Number:Location
Date Checked Drawn
Office of Construction and Facilities Management
Dwg. of
VA MARTINEZ CAMPUS , CA
19 & 20K. F. DAVIS ENGINEERING INC.
530 LA GONDA WAY, SUITE E
DANVILLE, CA 94526
WWW.KFDE.US
(925) 743-8884
KEY PLAN
B
BUILDING 19
BUILDING 20
02/25/2020
2/25/2020 8:09:12 AMC:\Users\ashrestha\Documents\CHRONIC DIALYSIS FINAL STAMPED SUBMITTAL - REV 2 - V2018_anil.shrestha9MD6R.rvt
CHRONIC DIALYSIS AND
SLEEP PROGRAM
I. VALDOV
EL110.2B
ELECTRICAL LIGHTING PLAN WEST -
ADDITION B
A. LEUNG
612-502
I. VALDOV
1/4" = 1'-0"EL110.2B
1 ELECTRICAL LIGHTING PLAN WEST - ADDITION B PROJECT
NORTH
D D
D DD
D D
D D
D D
DD
3D3D
DD
BREAKROOM
56 SF
VAULT
H301
PREP AND
PACKAGING
b b aa a a aaa a a a
D D D D
B
B B
B B
B B
A
A
A
A
AA A
aa a a a a a a b b a aa
A b
A b
A a
A a
A a
A b
A a
A
A
A c
A c a b
A d
A A
A
A c
A c
D2 D2D2 d
A c
A c d c e
DD
D
D
D
D
D
A d
A c
A c
A cD D D D
D D D D
D1D1 D1D1
B1
D1D1
B1 ab B1B1 b b
D1D1D1
D1
D1 D1
D1 D2 D2
D2D2
37.1 38 40 41 42 44 48 50 52 53 54 57 60 63 68 7040.8 48.2 74
B27
I1I1 I1
I2
I2
I2
I2
I1I1 I1
I2
I2
I2
I2
I1I1 I1
I2
I2
I2
I2
I1 I1
I2
I2
I2
I2
T1
T1
A
T1
SP SP
SPSP
SP
SPSP
SP
SP
SP
SP
T1
SP
SP
T1
T1 b a
SP
T1
SP
A c
A c d A
B30
B31
PNL CHB
#6 37
PNL CHB
#6
PNL CHB
#6
PNL CHB
#6
PNL CHB
#6
PNL CHB
#6
PNL CHB
#6
PNL CHB
#6
37 37
PNL CHB
#6
PNL CHB
#6
PNL CHB
#6
37 37 37
PNL CHB
#6
373737
PNL CHB
#6
37 37 37
PNL CHB
#6
37 37
PNL CHB
#6
PNL CHB
#6
37 37
37 37 37 37
PNL CHB
#6 37
PNL CHB
#6
PNL CHB
#6
PNL CHB
#6
PNL CHB
#6
PNL CHB
#6
PNL CHB
#6
PNL CHB
#6
37 37
PNL CHB
#6 e e e e cdc d c c cdc d c
3737 37
PNL CHB
#6
37 37
PNL CHB
#6
PNL CHB
#6
CHB #4
CHB #4
(TYP)
CHB#4
(TYP)
CHB#2
(TYP)
NHB#37
B29
B28
PNL CHB
#6
CHB #4
CHB#4
CHB #4
CHB #4
c
CONFERENCE
CONSULT FOOD PREP
ELECTRICAL
ROOM
RECEIVING STOR
RETAIL SPACE
RETAIL SPACE
DINING
DINING
A c
(TYP)
PNL CHB, CKT 4 PNL NHB, CKT 37
PNL CHB, CKT 6
FOR SIMPLICITY AND CLARITY BRANCH FEEDER CONDUIT AND WIRES IS
NOT SHOWN ON THE DRAWING. ONLY CIRCUIT NUMBER TO THE
EQUIPMENT AND HOMERUNS ARE SHOWN. CONTRACTOR SHALL
PROVIDE AND INSTALL BRANCH FEEDER CONDUITS, OUTLET BOXES,
WIRE AND JUNCTION BOXES FOR NEW WIRING INSTALLATION. ALL
HOMERUN CIRCUITS ARE 2#10 AND 1#10 GND (GRN) IN A 3/4" CONDUIT
UNLESS OTHERWISE NOTED.
LIGHT SWITCHES MOUNTED 48", AFF UNLESS OTHERWISE INDICATED.
ALL CONDUITS SHALL BE CONCEALED IN ACCORDANCE WITH
SPECIFICATION SECTION 26 05 33 CONDUIT SHALL RUN ABOVE CEILING
OR WITHIN FINISHED WALLS.
CORE DRILL WALL AND FLOOR FOR CONDUITS PENETRATION, AS
REQUIRED.
OCCUPANCY SENSOR LOCATION AND AMOUNT SHOWN IS FOR
REFERENCE ONLY. CONTRACTOR IS TO PROVIDE SUFFICIENT NUMBER
OF OCCUPANCY SENSORS, INSTALL AT LOCATIONS WHICH COMPLETELY
COVERS THE AREA WHERE THE OCCUPANCY SENSORS ARE INSTALLED.
PROVIDE ADDITIONAL ACCESS PANEL, AS REQUIRED PER NEC, ON HARD
CEILING FOR ELECTRICAL J.B., DEVICES, EQUIPMENT, ETC. ACCESSIBLE.
OCCUPANCY SENSOR SHALL BE SUITABLE FOR LED LIGHT FIXTURE.
CONTRACTOR SHALL PROVIDE SPEAKERS FOR PUBLIC ADDRESS
SYSTEM TO MATCH EXISTING FACILITY SPEAKERS. TIE IN THE NEW
SPEAKERS TO THE EXISTING PUBLIC ADDRESS SYSTEM. PROVIDE A
SUFFICIENT NUMBER OF SPEAKERS AS NECESSARY TO ACHIEVE
ADEQUATE SOUND COVERAGE THROUGHOUT THE REMODEL AREA.
COORDINATE WITH COR ON EXISTING SYSTEM TYPE, REQUIREMENTS
AND POINT OF CONNECTION.
GENERAL NOTES
1.
2.
3.
4.
5.
6.
7.
8.
SHEET NOTES
ALL EMERGENCY LIGHTS IN PANEL CHB CIRCUIT #6.
ALL EXIT LIGHT ON PANEL CHB CIRCUIT #4.
ALL LIGHTING NOT MARKED OTHERWISE OR NOT MARKED FOR
EMERGENCY LIGHTS IS FED FROM PANEL NHB CIRCUIT #37.
FIXTURE I2 GLOBAL POWER TRACK.
S T A T E
O F C A L I F OR N
I A
EXP.________
E 17641 9-30-2019
RE
G
IS
TE
RED PROFESS IONAL
ENG
INEERA
UG
UST I NE K . LEUNG
E
L E C T R I C A L
PROJECT
NORTH
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9 on e ei gh t i nc h on e fo ot on e qu ar te r i nc h on e fo ot th re e ei gh ts in ch o ne fo ot on e ha lf in ch o ne fo ot th re e qu ar te rs in ch o ne fo ot on e in ch o ne fo ot on e an d on e ha lf in ch o ne fo ot on e in ch o ne fo ot
VA FORM 08-6231
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Drawing Title: Project Title: Project Number:
Building Number:
Drawing Number:Location
Date Checked Drawn
Office of Construction and Facilities Management
Dwg. of
VA MARTINEZ CAMPUS , CA
19 & 20K. F. DAVIS ENGINEERING INC.
530 LA GONDA WAY, SUITE E
DANVILLE, CA 94526
WWW.KFDE.US
(925) 743-8884
KEY PLAN
C BUILDING 19
BUILDING 20
02/25/2020
2/25/2020 8:09:21 AMC:\Users\ashrestha\Documents\CHRONIC DIALYSIS FINAL STAMPED SUBMITTAL - REV 2 - V2018_anil.shrestha9MD6R.rvt
CHRONIC DIALYSIS AND
SLEEP PROGRAM
I. VALDOV
EL110C
ELECTRICAL LIGHTING PLAN -
RENOVATION C
A. LEUNG
612-502
I. VALDOV
1/4" = 1'-0"EL110C
1 ELECTRICAL LIGHTING PLAN - RENOVATION C
PROJECT
NORTH
LIGHTING FIXTURE SCHEDULE
DESCRIPTION AND MANUFACTURER
SYMBOL
FIXTURE
LAMP REMARKS
FIXTURE
MOUNTING
INPUT WATT W/
DRIVER LOCATION
FIXTURE
TYPE
FIXTURE
A
B
E
LED
CEILING
RECESSED
CEILING
SURFACE
LED, 900 LUMENS MINIMUM, 2" ROUND PINHOLE SURFACE MOUNTED DOWNLIGHT WITH 4" LED MODULE, 40º FLOOD OPTIC, WHITE
HOUSING LED ELECTRONIC DRIVER, 3500ºK, CRI ≥ 90, UNIVERSAL VOLTAGE
EATON COOPER LIGHTING, HALO BRAND, CAT. NO. ML4D09NFL935E-TIR50FL40-TL4IR-454R OR APPROVED EQUAL
LED 11.9W
(EST)
F
LED
WALL
SURFACE
LED
COFFEE BAR
COFFEE BAR PREP AREA
COFFEE BAR TOILET
G
LED, 2900 LUMENS MINIMUM, 2' X 2' RECESSED TROFFER, LINEAR LENS LIGHT GUIDE, CURVED REFLECTOR, LED
ELECTRONIC DIMMING DRIVER, 3500ºK, CRI ≥ 85, UNIVERSAL VOLTAGE
EATON COOPER LIGHTING, METALUX BRAND, SKYRIDGE SERIES, CAT.NO. 22SR-LD2-29-C-UNV-L835-CD1 OR APPROVED
EQUAL
LED COFFEE BAR TOILET
LED, 14" DIAMETER CIRCULAR FLUSH MOUNTED, 2300 LUMENS MINIMUM ELECTRONIC DRIVER, 3000ºK, CRI ≥ 90, 277 VOLT, DAMP LOCATION RATED
WAC LIGHTING, SLICE SERIES, CAT. NO.FM-4115F-30-BN OR APPROVED EQUAL
D LED UNDER DECK
SURFACE
DE
LED, 2700 LUMENS MINIMUM, REFLECTOR STRIPLIGHT, 4 FT, ELECTRONIC DIMMER DRIVER, 3500ºK, CRI ≥ 85, UNIVERSAL
VOLTAGE
EATON COOPER LIGHTING, METALUX BRAND, REFLECTOR LED STRIPLIGHT, CAT. NO. 4SLED-LD5-25SL-RW-UNV-L835-CD1 OR
APPROVED EQUAL
2 FEET LED VANITY WALL SCONCE, 1735 LUMENS, LED ELECTRONIC DRIVER, 3500ºK, CRI ≥ 90, UNIVERSAL VOLTAGE, DAMP LOCATION RATED
WAC LIGHTING, LEVEL SERIES, CAT. NO. WS-85624-AL OR APPROVED EQUAL
COFFEE BAR CORRIDOR ABOVE SKYLIGHT
LED, 2000 LUMENS MINIMUM, WALL BRACKET, 4 FT, ELECTRONIC DIMMING DRIVER, 3500ºK, CRI ≥ 85, UNIVERSAL VOLTAGE EATON COOPER LIGHTING, METALUX BRAND, CAT.NO. 4BCLED-LD4-20SL-F-UNV-L835-CD1 OR APPROVED EQUAL
LED WALL
SURFACE
COFFEE BAR SUPPLY ROOM
A
CEILING
SURFACE
G
H
CEILING
SURFACE
LED
J 23W
(EST)
LED
J
COFFEE BAR
WALL
SURFACE
LED COFFEE BAR OUTDOOR
B
LED, 900 LUMENS MINIMUM, 2" ROUND OPEN PINHOLE RECESSED DOWNLIGHT WITH 4" RECESSED LED MODULE, 40º FLOOD OPTIC, WHITE FLANGE, LED ELECTRONIC DRIVER, 3500ºK, CRI ≥ 90, UNIVERSAL VOLTAGE
EATON COOPER LIGHTING, HALO BRAND, CAT. NO. ML4D09NFL935E-TIR50FL40-TL4IR-454MW OR APPROVED EQUAL
11.9W
(EST)
COFFEE BAR 1
C
C
1. PROVIDE EL14W EMERGENCY
BATTERY PACK IN EMERGENCY
FIXTURE
D
D LED, 2700 LUMENS MINIMUM, REFLECTOR STRIPLIGHT, 4 FT, ELECTRONIC DIMMER DRIVER, 3500ºK, CRI ≥ 85, UNIVERSAL
VOLTAGE, EMERGENCY BATTERY PACK
EATON COOPER LIGHTING, METALUX BRAND, REFLECTOR LED STRIPLIGHT, CAT. NO. 4SLED-LD5-25SL-RW-UNV-L835-ELI4W-CD1
OR APPROVED EQUAL
19.3W
(EST)
23.4W
(EST)
MOUNT ±8" FROM EDGE OF
SKYLIGHT,ON UNDERSIDE OF
ABOVE DECK
LED UNDER DECK
SURFACE
COFFEE BAR CORRIDOR ABOVE SKYLIGHT
19.3W
(EST)
1. MOUNT LIGHT OVER CENTER OF
SKYLIGHT ON THE UNDERSIDE OF
ABOVE DECK
2. PROVIDE EMERGENCY
BATTERY PACK
E 20.5W
(EST)
F 25W
(EST)
22W
(EST)
MOUNT ±7-6" AFF
H LED, 2800 LUMENS MINIMUM, WRAP AROUND, 4 FT, ELECTRONIC DIMMING DRIVER, 3500ºK, CRI ≥ 85, UNIVERSAL VOLTAGE EATON COOPER LIGHTING, METALUX BRAND, CAT.NO. 4WSNLED-LD4-28SL-F-UNV-L835-CD1 OR APPROVED EQUAL 44W
(EST)
COFFEE BAR SUPPLY ROOM
LED, EMERGENCY LIGHT WITH NICKEL CADMIUM BATTERY, UL924 LISTED, DUAL VOLTAGE
EATON COOPER LIGHTING, CU2-LED SERIES, CU2-LED OR APPROVED EQUAL
1. CONTRACTOR IS TO FIELD
DETERMINE A SUITABLE
MOUNTING HEIGHT. COORDINATE
WITH VAMC
K
LED, 2,200LUMENS MINIMUM, QUARTER SPHERE, WALL MOUNTED, OUTDOOR LIGHT FIXTURE, TYPE 3 DISTRIBUTION, LED ELECTRONIC
DRIVER, 4000ºK, CRI ≥ 70, 277 VOLT
EATON COOPER LIGHTING, McGRAW-EDISON BRAND, CAT. NO. ISS-F01-LED-E1-BL3-BZ-P-TR-BBB-CWB-277 OR APPROVED EQUAL
K 26W
(EST)
1. PROVIDE PHOTOCELL
2. MOUNTED ±8'-0" AFF UNLESS
OTHERWISE NOTED
3. PROVIDE EMERGENCY
BATTERY PACK
4. PROVIDE TAMPER RESISTANT
HARDWARE
5. PROVIDE BACK BOX, AS
REQUIRED
L RED LED HIGH IMPACT ACRYLIC PANEL EDGE-LIT EXIT SIGN, 120/277V, WITH INTEGRAL SEALED MAINTENACE FREE BATTERY AND
SOLID STATE CHARGING SYSTEM
X DESIGNATES MOUNTING POSITION
E= END MOUNTED
T= TOP MOUNTED
B= BACK MOUNTED
ST= STEM MOUNTED
R= RECESSED
N DESIGNATES FACE ARRANGEMENT
1= SINGLE FACE
2= DOUBLE FACE
EATON, COOPER LIGHTING, SURE-LITE BRAND CAT. NO. EUS70R OR APPROVED EQUAL
LED
2 3
CEILING
RECESSED
WALL
SURFACE
CEILING
SURFACE
4.5W
(EST)
VARIOUS
C
XN
GENERAL NOTES
SHEET NOTES
1.
2.
3.
1 PROVIDE FIXTURE MOUNTING MATCHING CEILING TYPE.
REFER TO LIGHTING PLAN FOR SIGNAGE MOUNTING AND NUMBER
OF FACES.
FILL IN DIRECTION INDICATOR POINTING DIRECTION.
MOUNTED BOTTOM OF FIXTURE ±3" ABOVE MIRROR
WHERE CEILINGS ARE INSULATED, PROVIDE IC RATED LIGHTING
FIXTURE WHETHER OR NOT IC RATING IS CALLED OUT ON FIXTURE
SCHEDULE OR DRAWINGS. IC RATED FIXTURE TYPE AND
APPEARANCE SHALL MATCH NON-RATED FIXTURE TYPE AS SHOWN
ON FIXTURE SCHEDULE. SUBMIT NEW IC RATED FIXTURE TYPE TO
COTR OR VAMC REPRESENTATIVE FOR APPROVAL.
LED LAMP SHALL HAVE A MINIMUM COLOR TEMPERATURE OF 3500°K
AND CRI OF 85, UNLESS OTHERWISE NOTED.
PROVIDE T-BAR SAFETY EARTHQUAKE CLIP ON LIGHT FIXTURES.
WHEN AVAILABLE.
S T
A
T E
O F C A L I F OR N
I A
EXP.________
E 17641 9-30-2019
R E
G
IS
TE
RED
PROFESS IONAL
ENG
IN
E E
RA
U
G
UST I NE K . LEU
N G
E
L E C T R I C A
L
PROJECT
NORTH
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9 o n e e ig h t in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h ts i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t o n e i n c h o n e f o o t
VA FORM 08-6231
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Drawing Title: Project Title: Project Number:
Building Number:
Drawing Number:Location
Date Checked Drawn
Office of Construction and Facilities Management
Dwg. of
VA MARTINEZ CAMPUS , CA
19 & 20K. F. DAVIS ENGINEERING INC.
530 LA GONDA WAY, SUITE E
DANVILLE, CA 94526
WWW.KFDE.US
(925) 743-8884
KEY PLAN
A
BUILDING 19
BUILDING 20
02/25/2020
2/25/2020 9:54:18 AMC:\Users\ashrestha\Documents\CHRONIC DIALYSIS FINAL STAMPED SUBMITTAL - REV 2 - V2018_anil.shrestha9MD6R.rvt
CHRONIC DIALYSIS AND
SLEEP PROGRAM
I. VALDOV
EL610A
ELECTRICAL LIGHTING FIXTURE
SCHEDULE - ADDITION A
A. LEUNG
612-502
I. VALDOV
SYMBOL
FIXTURE
LAMP REMARKS
FIXTURE
MOUNTING
INPUT WATT W/
DRIVER LOCATION
FIXTURE
TYPE
FIXTURE
F
LED STAFF TOILET 1,2, TOILET 1,2,3,4, SLEEP ROOM 1,2,3,4
LED, 14" DIAMETER CIRCULAR FLUSH MOUNTED, 2300 LUMENS MINIMUM ELECTRONIC DRIVER, 3000ºK, CRI ≥ 90, UNIVERSAL VOLTAGE, DAMP LOCATION RATED
WAC LIGHTING, SLICE SERIES, CAT. NO.FM-4115F-30-BN OR APPROVED EQUAL
CEILING
SURFACE
WALL
SURFACE
LED
F 25W
(EST)
K LED, 2,200 LUMENS MINIMUM, QUARTER SPHERE, WALL MOUNTED, OUTDOOR LIGHT FIXTURE, TYPE 3 DISTRIBUTION, LED ELECTRONIC
DRIVER, 4000ºK, CRI ≥ 70, UNIVERSAL VOLTAGE
EATON COOPER LIGHTING, McGRAW-EDISON BRAND, CAT. NO. ISS-AF-350-LED-E1-SL3-BZ-P-TR OR APPROVED EQUAL
K 20.3W
(EST)
1. PROVIDE PHOTOCELL
2. MOUNTED ±1'-0" ABOVE DOOR
UNLESS OTHERWISE NOTED
3. PROVIDE TAMPER RESISTANT
HARDWARE
4. PROVIDE BACK BOX, AS
REQUIRED
L
RED LED HIGH IMPACT ACRYLIC PANEL EDGE-LIT EXIT SIGN, 120/277V / AC ONLY.
X DESIGNATES MOUNTING POSITION
E= END MOUNTED
T= TOP MOUNTED
B= BACK MOUNTED
ST= STEM MOUNTED
R= RECESSED
N DESIGNATES FACE ARRANGEMENT
1= SINGLE FACE
2= DOUBLE FACE
EATON, COOPER LIGHTING, SURE-LITE BRAND CAT. NO. EUS60R OR APPROVED EQUAL
LED 2 3
B1 LED, 2900 LUMENS MINIMUM, 2'-0" x 2'-0" RECESSED TROFFER, LINEAR LENS LIGHT GUIDE, CURVED REFLECTOR, LED ELECTRONICS
DIMMING DRIVER, 3500°K, CRI ≥ 85, UNIVERSAL VOLTAGE.
EATON'S COOPER LIGHTING, METALUX BRAND, SKYRIDGE SERIES, CAT. NO. 22SR-LD2-29-C-UNV-L835-CD1, OR APPROVED EQUAL.
LED 23.4 W
(EST.)
B1
CEILING
RECESSED
C1 LED, 3400 LUMENS MINIMUM, 2'-0" x 4'-0" RECESSED TROFFER, LINEAR LENS LIGHT GUIDE, CURVED REFLECTOR, LED ELECTRONICS
DIMMING DRIVER, 3500°K, CRI ≥ 85, UNIVERSAL VOLTAGE.
EATON'S COOPER LIGHTING, METALUX BRAND, SKYRIDGE SERIES, CAT. NO. 24SR-LD2-34-C-UNV-L835-CD1, OR APPROVED EQUAL.
LED 27.2 W
(EST.)
C1
CEILING
RECESSED
E1 LED, 6400 LUMENS MINIMUM, 2'-0" x 4'-0" RECESSED TROFFER, LINEAR LENS LIGHT GUIDE, CURVED REFLECTOR, LED ELECTRONICS
DIMMING DRIVER, 3500°K, CRI ≥ 85, UNIVERSAL VOLTAGE.
EATON'S COOPER LIGHTING, METALUX BRAND, SKYRIDGE SERIES, CAT. NO. 24SR-LD2-64-C-UNV-L835-CD1, OR APPROVED EQUAL.
LED 55.5 W
(EST.)
E1 CEILING
RECESSED
E2 LED, 6400 LUMENS MINIMUM, 2'-0" x 4'-0" RECESSED TROFFER, LINEAR LENS LIGHT GUIDE, CURVED REFLECTOR, LED ELECTRONICS DIMMING DRIVER, 3500°K, CRI ≥ 85, UNIVERSAL VOLTAGE. INTERATED DIMMING DAYLIGHT HARVESTING SENSOR.
EATON'S COOPER LIGHTING, METALUX BRAND, SKYRIDGE SERIES, CAT. NO. 24SR-LD2-64-C-UNV-L835-CD1,SVD1, OR APPROVED EQUAL.
LED 55.5 W
(EST.)
E2
CEILING
RECESSED
D1
LED, 4800 LUMENS MINIMUM, 2'-0" x 4'-0" RECESSED TROFFER, LINEAR LENS LIGHT GUIDE, CURVED REFLECTOR, LED ELECTRONICS
DIMMING DRIVER, 3500°K, CRI ≥ 85, UNIVERSAL VOLTAGE.
EATON'S COOPER LIGHTING, METALUX BRAND, SKYRIDGE SERIES, CAT. NO. 24SR-LD2-48-C-UNV-L835-CD1, OR APPROVED EQUAL.
LED 38.2 W
(EST.)D1
CEILING
RECESSED
D2 LED, 4800 LUMENS MINIMUM, 2'-0" x 4'-0" RECESSED TROFFER, LINEAR LENS LIGHT GUIDE, CURVED REFLECTOR, LED ELECTRONICS DIMMING DRIVER, 3500°K, CRI ≥ 85, UNIVERSAL VOLTAGE. INTERATED DIMMING DAYLIGHT HARVESTING SENSOR.
EATON'S COOPER LIGHTING, METALUX BRAND, SKYRIDGE SERIES, CAT. NO. 24SR-LD2-48-C-UNV-L835-CD1,SVD1, OR APPROVED EQUAL.
LED 38.2 W
(EST.)
CEILING
RECESSED
NEPHROLOGIST, SUPV
CHIEF, TELECOM, SUPV
CONFERENCE, SLEEP ROOMS 1,2,3,4
CONFERENCE, DIALYSIS EQUIPMENT, STERILE EQUIPMENT,
CONTROL ROOM, CONSULT, OFFICE SUPPLY, OPEN OFFICE
CORRIDOR 1
CORRIDORS 2,3,4
D LED UNDER DECK
SURFACE
LED, 2700 LUMENS MINIMUM, REFLECTOR STRIPLIGHT, 4 FT, ELECTRONIC DIMMER DRIVER, 3500ºK, CRI ≥ 85, UNIVERSAL
VOLTAGE
EATON COOPER LIGHTING, METALUX BRAND, REFLECTOR LED STRIPLIGHT, CAT. NO. 4SLED-LD5-25SL-RW-UNV-L835-CD1 OR
APPROVED EQUAL
EXTERNAL ELECTRICAL ROOM
19.3W
(EST)
STAFF TOILET 1,2
E WALL
SURFACE
LED2 FEET LED VANITY WALL SCONCE, 1735 LUMENS, LED ELECTRONIC DRIVER, 3500ºK, CRI ≥ 90, UNIVERSAL VOLTAGE, DAMP LOCATION RATED
WAC LIGHTING, LEVEL SERIES, CAT. NO. WS-85624-AL OR APPROVED EQUAL
E 20.5W
(EST)
D
D
D2
B1
C1
D1
D2
E2
F
XN
GENERAL NOTES
SHEET NOTES
1.
2.
3.
1 NO BATTERY BACKUP.
REFER TO LIGHTING PLAN FOR SIGNAGE MOUNTING AND NUMBER
OF FACES.
FILL IN DIRECTION INDICATOR POINTING DIRECTION.
MOUNTED BOTTOM OF FIXTURE ±3" ABOVE MIRROR
WHERE CEILINGS ARE INSULATED, PROVIDE IC RATED LIGHTING
FIXTURE WHETHER OR NOT IC RATING IS CALLED OUT ON FIXTURE
SCHEDULE OR DRAWINGS. IC RATED FIXTURE TYPE AND
APPEARANCE SHALL MATCH NON-RATED FIXTURE TYPE AS SHOWN
ON FIXTURE SCHEDULE. SUBMIT NEW IC RATED FIXTURE TYPE TO
COTR OR VAMC REPRESENTATIVE FOR APPROVAL.
LED LAMP SHALL HAVE A MINIMUM COLOR TEMPERATURE OF 3500°K
AND CRI OF 85, UNLESS OTHERWISE NOTED.
PROVIDE T-BAR SAFETY EARTHQUAKE CLIP ON LIGHT FIXTURES.
WHEN AVAILABLE.
S T A T E
O F C A L I F OR N
I A
EXP.________
E 17641 9-30-2019
RE
G
IS
TE
RED PROFESS IONAL
ENG
INEERA
UG
UST I NE K . LEUNG
E
L E C T R I C A L
PROJECT
NORTH
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9 on e ei gh t i nc h on e fo ot on e qu ar te r i nc h on e fo ot th re e ei gh ts in ch o ne fo ot on e ha lf in ch o ne fo ot th re e qu ar te rs in ch o ne fo ot on e in ch o ne fo ot on e an d on e ha lf in ch o ne fo ot on e in ch o ne fo ot
VA FORM 08-6231
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Drawing Title: Project Title: Project Number:
Building Number:
Drawing Number:Location
Date Checked Drawn
Office of Construction and Facilities Management
Dwg. of
VA MARTINEZ CAMPUS , CA
19 & 20K. F. DAVIS ENGINEERING INC.
530 LA GONDA WAY, SUITE E
DANVILLE, CA 94526
WWW.KFDE.US
(925) 743-8884
KEY PLAN
B
BUILDING 19
BUILDING 20
02/25/2020
2/25/2020 8:09:26 AMC:\Users\ashrestha\Documents\CHRONIC DIALYSIS FINAL STAMPED SUBMITTAL - REV 2 - V2018_anil.shrestha9MD6R.rvt
CHRONIC DIALYSIS AND
SLEEP PROGRAM
L. HARRIS
EL610B
ELECTRICAL LIGHTING FIXTURE
SCHEDULE - ADDITION B
A. LEUNG
612-502
L. HARRIS
SYMBOL
FIXTURE
LAMP REMARKS
FIXTURE
MOUNTING
INPUT WATT W/
DRIVER LOCATION
FIXTURE
TYPE
FIXTURE
A CEILING
SURFACE
LED, 900 LUMENS MINIMUM, 2" ROUND PINHOLE SURFACE MOUNTED DOWNLIGHT WITH 4" LED MODULE, 40º FLOOD OPTIC, WHITE
HOUSING LED ELECTRONIC DRIVER, 3500ºK, CRI ≥ 90, UNIVERSAL VOLTAGE
EATON COOPER LIGHTING, HALO BRAND, CAT. NO. ML4D09NFL935E-TIR50FL40-TL4IR-454R OR APPROVED EQUAL
LED 11.9W
(EST)A
B LEDB
LED, 900 LUMENS MINIMUM, 2" ROUND OPEN PINHOLE RECESSED DOWNLIGHT WITH 4" RECESSED LED MODULE, 40º FLOOD OPTIC, WHITE FLANGE, LED ELECTRONIC DRIVER, 3500ºK, CRI ≥ 90, UNIVERSAL VOLTAGE
EATON COOPER LIGHTING, HALO BRAND, CAT. NO. ML4D09NFL935E-TIR50FL40-TL4IR-454MW OR APPROVED EQUAL
11.9W
(EST)
CEILING
RECESSE
D
B1 LED, 2900 LUMENS MINIMUM, 2'-0" x 2'-0" RECESSED TROFFER, LINEAR LENS LIGHT GUIDE, CURVED REFLECTOR, LED ELECTRONICS
DIMMING DRIVER, 3500°K, CRI ≥ 85, UNIVERSAL VOLTAGE.
EATON'S COOPER LIGHTING, METALUX BRAND, SKYRIDGE SERIES, CAT. NO. 22SR-LD2-29-C-UNV-L835-CD1, OR APPROVED EQUAL.
LED 23.4 W
(EST.) CEILING
RECESSED
D LED UNDER DECK
SURFACE
LED, 2700 LUMENS MINIMUM, REFLECTOR STRIPLIGHT, 4 FT, ELECTRONIC DIMMER DRIVER, 3500ºK, CRI ≥ 85, UNIVERSAL VOLTAGE EATON COOPER LIGHTING, METALUX BRAND, REFLECTOR LED STRIPLIGHT, CAT. NO. 4SLED-LD5-25SL-RW-UNV-L835-
CD1 OR APPROVED EQUAL
19.3W
(EST)
KITCHEN SERVING, BEVERAGE BAR, DINING
RETAIL
DINING
PREP AND PACKAGING
CONFERENCE, KITCHEN
B1
L
RED LED HIGH IMPACT ACRYLIC PANEL EDGE-LIT EXIT SIGN, 120/277V AC ONLY
X DESIGNATES MOUNTING POSITION
E= END MOUNTED
T= TOP MOUNTED
B= BACK MOUNTED
ST= STEM MOUNTED
R= RECESSED
N DESIGNATES FACE ARRANGEMENT
1= SINGLE FACE
2= DOUBLE FACE
EATON, COOPER LIGHTING, SURE-LITE BRAND CAT. NO. EUS60R OR APPROVED EQUAL
LED 2 3
D1
LED, 4800 LUMENS MINIMUM, 2'-0" x 4'-0" RECESSED TROFFER, LINEAR LENS LIGHT GUIDE, CURVED REFLECTOR, LED ELECTRONICS
DIMMING DRIVER, 3500°K, CRI ≥ 85, UNIVERSAL VOLTAGE.
EATON'S COOPER LIGHTING, METALUX BRAND, SKYRIDGE SERIES, CAT. NO. 24SR-LD2-48-C-UNV-L835-CD1, OR APPROVED EQUAL.
LED 38.2 W
(EST.)
D1 CEILING
RECESSED
D2 LED, 4800 LUMENS MINIMUM, 2'-0" x 4'-0" RECESSED TROFFER, LINEAR LENS LIGHT GUIDE, CURVED REFLECTOR, LED ELECTRONICS DIMMING DRIVER, 3500°K, CRI ≥ 85, UNIVERSAL VOLTAGE. INTERATED DIMMING DAYLIGHT HARVESTING SENSOR.
EATON'S COOPER LIGHTING, METALUX BRAND, SKYRIDGE SERIES, CAT. NO. 24SR-LD2-48-C-UNV-L835-CD1,SVD1, OR APPROVED EQUAL.
LED 38.2 W
(EST.)D2 CEILING
RECESSED
I1
CEILING
SURFACE
LEDI1 LED, 2000 LUMENS MINIMUM, 4'X2 3/8", SURFACE MOUNTED, SUPPORT BY STRUCTURE ABOVE CEILING, LED ELECTRONICS DIMMING DRIVER, 3500°K, CRI>, 90, UNIVRSAL VOLTAGE. 33W
(EST)
I2
CEILING
SURFACE
LED
I2
21W
(EST)
LUMENWERX, VIA2PD, LED BRAND, VIA2PD-HLO-LED-90-500-35-4FT-UNV-DI1-B OR APPROVED EQUAL
LED, 1500 LUMENS MINIMUN, TRACK LIGHT, SURFACE MOUNTED, SUPPORT TRACK BY STRUCTURE ABOVE CEILING & ATTACH TO CEILING, FIXTURE EXTENDS NO MORE THAN 9" BELOW TRACK, APPROX 4" DIAMETER, 3500°K, CRI >, 90, 277V, NON-DIMMING.
AMERLUX, SPEQ-M MEDIUM CYLINDER TRACK HEAD, SPEQ-M-A17-21-BT277-359-ND OR APPROVED EQUAL
PREP AND PACKAGING, VAULT, BREAKROOM,
CONSULT
PREP AND PACKAGING, VAULT, BREAKROOM,
CONSULT
RETAIL
RETAIL
D
D
D1
D2
I1
XN
GENERAL NOTES
SHEET NOTES
1.
2.
3.
1 PROVIDE FIXTURE MOUNTING MATCHING CEILING TYPE.
REFER TO LIGHTING PLAN FOR SIGNAGE MOUNTING AND NUMBER
OF FACES.
FILL IN DIRECTION INDICATOR POINTING DIRECTION.
NO BATTERY BACK UP.
PROVIDE 277V GLOBAL POWER TRACK. BLACK IN COLOR.
WHERE CEILINGS ARE INSULATED, PROVIDE IC RATED LIGHTING
FIXTURE WHETHER OR NOT IC RATING IS CALLED OUT ON FIXTURE
SCHEDULE OR DRAWINGS. IC RATED FIXTURE TYPE AND
APPEARANCE SHALL MATCH NON-RATED FIXTURE TYPE AS SHOWN
ON FIXTURE SCHEDULE. SUBMIT NEW IC RATED FIXTURE TYPE TO
COTR OR VAMC REPRESENTATIVE FOR APPROVAL.
LED LAMP SHALL HAVE A MINIMUM COLOR TEMPERATURE OF 3500°K
AND CRI OF 85, UNLESS OTHERWISE NOTED.
PROVIDE T-BAR SAFETY EARTHQUAKE CLIP ON LIGHT FIXTURES.
WHEN AVAILABLE.
S T A T E
O F C A L I F OR N
I A
EXP.________
E 17641 9-30-2019
RE
G
IS
TE
RED PROFESS IONAL
ENG
INEERA
UG
UST I NE K . LEUNG
E
L E C T R I C A L
PROJECT
NORTH
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9 on e ei gh t i nc h on e fo ot on e qu ar te r i nc h on e fo ot th re e ei gh ts in ch o ne fo ot on e ha lf in ch o ne fo ot th re e qu ar te rs in ch o ne fo ot on e in ch o ne fo ot on e an d on e ha lf in ch o ne fo ot on e in ch o ne fo ot
VA FORM 08-6231
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Drawing Title: Project Title: Project Number:
Building Number:
Drawing Number:Location
Date Checked Drawn
Office of Construction and Facilities Management
Dwg. of
VA MARTINEZ CAMPUS , CA
19 & 20K. F. DAVIS ENGINEERING INC.
530 LA GONDA WAY, SUITE E
DANVILLE, CA 94526
WWW.KFDE.US
(925) 743-8884
KEY PLAN
C BUILDING 19
BUILDING 20
02/25/2020
2/25/2020 8:09:28 AMC:\Users\ashrestha\Documents\CHRONIC DIALYSIS FINAL STAMPED SUBMITTAL - REV 2 - V2018_anil.shrestha9MD6R.rvt
CHRONIC DIALYSIS AND
SLEEP PROGRAM
I. VALDOV
EL610C
ELECTRICAL LIGHTING FIXTURE
SCHEDULE - RENOVATION C
A. LEUNG
612-502
I. VALDOV
.C
F .E
.C
C
GCG
CG
CG
CG
CG
T
GFCI
GFCI
GFCI
G
FC
I G
FC
I
JK
12.9
HL
TOILET 1
19A101 TOILET 2
19A102
SUPPLY
19A100B
PREP
19A100ASEATING
19A100
CORRIDOR
C19A
WP
SP
-H-H
-A
C
25 25
25 25
GFCI
GFCI
A
A2,4 2
A -
A
PNL LBD1,
CKT 1,3,5
PNL LBD1,
CKT 2,4
2 #12 & 1 #12
GND, 3/4"C
PNL LBD1,
CKT 21,25,31
21 31TV
SP-C
-C
-B 23
-B
PNL LBD1, CKT 23
2 #12 & 1 #12 GND
3/4"C
-A
GFCI
11 3
PNL LBD1, CKT 11,37
4 #10 & 1 #10 GND,
3/4"C
PNL LBD1, CKT 18
2 #12 & 1 #12
GND, 3/4"C
GFCI
-A
PNL LBD1,
CKT 15,17,19
PNL LBD1, CKT 8,13
4 #10 & 1 #10 GND,
3/4"C
9GFCI
-A
7GFCI
-A
13GFCI
19GFCI
-A
GFCI
-A
PNL LBD1, CKT 6,7,9
-A
10,12
PNL LBD1, CKT 10,12
2 #8 & 1 #10 GND,
3/4"C
GFCI
-A
17GFCI
-A
GENERAL NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
FOR SIMPLICITY AND CLARITY BRANCH FEEDER CONDUIT AND
WIRES IS NOT SHOWN ON THE DRAWING. ONLY CIRCUIT NUMBER
TO THE EQUIPMENT AND HOMERUNS ARE SHOWN. CONTRACTOR
SHALL PROVIDE AND INSTALL BRANCH FEEDER CONDUITS,
OUTLET BOXES, WIRE AND JUNCTION BOXES FOR NEW WIRING
INSTALLATION. ALL HOMERUN CIRCUITS ARE 6#10 AND 1#10 GND
(GRN) IN A 3/4" CONDUIT, UNLESS OTHERWISE NOTED.
ALL CONDUITS SHALL BE CONCEALED. CONDUITS SHALL RUN
ABOVE THE CEILING OR WITHIN FINISHED WALLS.
TELECOMMUNICATION OUTLET AND POWER RECEPTACLE SHALL
BE A MINIMUM OF 6" APART.
PROVIDE CAT 6 TELECOMMUNICATION RECEPTACLE (DATA
OUTLETS), WIRES, J.B. (4"x4" BOX) COVER PLATE, 1" CONDUIT
WITH BUSHINGS. CONDUIT SHALL BE TERMINATED 6" ABOVE
CEILING.
CONTRACTOR SHALL PROVIDE A COMPLETE FULLY OPERATIONAL
AND CERTIFIED TELECOMMUNICATION SYSTEM AT THE MINIMUM
MEETING INDUSTRY STANDARD ANSI/TIA/EIA-S-68,B,2 AND ANSI /
TIA-568,C FOR CATEGORY 6 CABLING SYSTEM. THE SYSTEM SHALL
BE CABLE TO CO-EXIT WITH THE EXISTING VAMC
TELECOMMUNICATION SYSTEM.
PROVIDE CONDUIT AND WIRING…