About this file

This document outlines a federal contract opportunity for construction services. The Department of Veterans Affairs seeks to construct a 6,000 square foot addition to Building 20 housing administration, dialysis, and sleep lab spaces at its Martinez, California campus. It will also renovate 4,200 square feet of Building 20 for pharmacy, administration, and retail areas and add a 1,000 square foot coffee bar to Building 19. The work includes installing dialysis boxes in patient rooms and meeting level 4 infection control requirements. The solicitation will be issued as a total Service-Disabled Veteran-Owned Small Business set-aside with a NAICS code of 236220 and size standard of $36.5 million. The period of performance is approximately 760 calendar days from notice to proceed with questions due by July 24, 2020. The estimated value is over $10 million.

View the file

Other files for this federal contract opportunity

Other files attached to Y1DA--Construct Dialysis and Sleep Program Construct and Renovate Chronic Dialysis & Sleep Program Project #612 502 Minor Construction - Martinez, CA VISN 21, newest first.
File Type Posted
Amendment 0006 Attachment 2 - Deduct Alternative Update.pdf PDF
Amendment 0006 Attachment 1 - Amendment 0002 SF30.pdf PDF
Amendment 0006 36E77620R0039 - Proposal Extension and Clarifications - 20201008.pdf PDF
Amendment 0005 36E77620R0039 - Proposal Due Date Extension - 20200930.pdf PDF
Amendment 0004 Attachment 2 - AC101C-REV1.pdf PDF
Amendment 0004 Attachment 1 - Responses to Technical Questions Received.pdf PDF
Amendment 0004 36E77620R0039 - Responses to Technical Questions - 20200928.pdf PDF
Amendment 0003 36E77620R0039 - Proposal Due Date Extension - 20200921.pdf PDF
Amendment 0002 Attachment 1 Martinez Campus Parking 2020.pdf PDF
Amendment 0002 36E77620R0039 - Site Visit - 20200909.docx DOCX document
S06 - Amendment 0001 36E77620R0039 - 20200827.docx DOCX document
Attachment 4 Chronic Dialysis Sleep Program Drawings Part 1.pdf PDF
Attachment 11 - Past Performance Questionnaire 36E77620R0039.docx DOCX document
36E77620R0039_1.docx DOCX document
Attachment 8 Contractor Safety and Environmental Record Evaluation Form.docx DOCX document
Attachment 9 Wage Determination DBA - Martinez 20200721.pdf PDF
Attachment 7 Release of Claims.docx DOCX document
Attachment 1 Updated SOW Chronic Dialysis and Sleep Program.docx DOCX document
Attachment 2 Chronic Dialysis Sleep Program Specificiations Book.pdf PDF
Attachment 10 JA Brand Name Items Signed and Redacted.pdf PDF
Attachment 5 Chronic Dialysis Sleep Program Drawings Part 2.pdf PDF
Attachment 3 Chronic Dialysis Sleep Program Cover Page.pdf PDF
Show all 22

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

A-1,3

GFCI

GFCI

GFCI

GFCI

J J

F

DUPLEX RECEPTACLE, NEMA 5-20R, GROUNDING

TYPE WITH GROUND FAULT INTERRUPTER (GFCI)

DUPLEX RECEPTACLE, NEMA 5-20R, GROUNDING

QUAD-RECEPTACLE (DOUBLE DUPLEX), NEMA

5-20R, GROUNDING TYPE WITH GROUND FAULT INTERRUPTER

CONDUIT OR WIRE RUN EXPOSED OR ABOVE THE CEILING

BRANCH CIRCUIT HOMERUN TO PANELBOARD; LETTER AND NUMBER NOTATION

OF PHASE, NEUTRAL AND GREEN GROUND WIRES

RECEPTACLE, NEMA 6-20R, 250V (GROUNDING TYPE)-EMERGENCY POWER

RECEPTACLE, NEMA 6-20R, 250V (GROUNDING TYPE), 20A, 1 PHASE, 2 POLE, 3

WIRE- GROUNDING, UNLESS OTHERWISE NOTED

TELECOMMUNICATION OUTLET, QUAD (1 VOICE, 3 DATA)

SWITCH, 20A, 1 POLE, 120/277 V, UNLESS OTHERWISE INDICATED

MOTOR, 1 PHASE NUMBER INDICATES HORSEPOWER

COMBINATION MOTOR STARTER

ELECTRIC PANELBOARD, SURFACE MOUNTED

ELECTRIC PANELBOARD, FLUSH MOUNTED

QUAD-RECEPTACLE (DOUBLE DUPLEX), NEMA

5-20R, GROUNDING TYPE WITH GROUND FAULT INTERRUPTER

QUAD-RECEPTACLE (DOUBLE DUPLEX), NEMA

DUPLEX RECEPTACLE, NEMA 5-20R, GROUNDING

TYPE WITH GROUND FAULT INTERRUPTER (GFCI) - EMERGENCY POWER

DUPLEX RECEPTACLE, NEMA 5-20R, GROUNDING

A, B, C INDICATES SEPARATE CONTROL OF CIRCUITS AS DESIGNATED

MOTOR STARTER OR CONTROLLER

IDENTIFIES PANEL AND CIRCUIT NUMBER(S). HASHMARKS INDICATES NUMBER

CIRCUIT BREAKER, ENCLOSED

CONDUIT/WIRE TURN DOWN

CONDUIT/WIRE TURN UP

CONTACTORCR

CB

SPEAKER/PUBLIC ADDRESS

DISCONNECT SWITCH, UNFUSED

3 3 WAY SWITCH

D DIMMER

DISCONNECT SWITCH, FUSED

SP

EXIT SIGN WITH INTREGAL BATTERY BACKUP

ELECTRICAL DISTRIBUTION PANEL

TEMPERATURE CONTROLLER

TEMPERATURE INDICATOR

SUFFIX OF:

T

TI

S

EP

TYPE - EMERGENCY POWER

EMERGENCY POWER

PHASE CONDUCTORGROUND

NEUTRAL

JUNCTION BOX

5-20R, GROUNDING TYPE

TYPE

LEGEND

ELECTRICAL ABBREVIATIONS:

LIGHT FIXTURE, SURFACE MOUNTED, ON NORMAL POWER (TYP) LETTER INDICATE

TYPE (SEE LIGHTING SCHEDULE FOR SPECIFIC FIXTURE IDENTIFICATION)

FIXTURE ON EMERGENCY POWER, LETTER INDICATE TYPE (TYP.) (SEE LIGHTING

SCHEDULE FOR SPECIFIC FIXTURE IDENTIFICATION)

RECEPTACLE SHALL BE MOUNTED 18" AFF AND SWITCH SHALL BE MOUNTED 48"

AFF, UNLESS OTHERWISE NOTED.

RECEPTACLE AND SWITCH SUFFIX OF:

-A MOUNTED ±6" ABOVE COUNTERTOP OR BACKSPLASH.

-B MOUNTED ±40" AFF OR ±6" ABOVE COUNTER TOP OF SINK

-C MOUNTED ON CEILING

-F MOUNTED ON FLOOR

-W MOUNTED 48" AFF

-H MOUNTED ±12" BELOW CEILING HEIGHT

-S SURFACE MOUNTED

GFCI GROUND FAULT CIRCUIT INTERRUPTER

SC SAFETY TYPE (TAMPER RESISTANCE)

WP WEATHER PROTECTED (NEMA 3R) ENCLOSURE

AMPERE

2.

SMOKE DETECTOR

1.

S

LEGEND (CONTINUATION)

WIRELESS ROUTER

NETWORK DEVICES / WI-FI

POWER STRIP

FLOOR MOUNTED POWER AND TELECOM UNIT

P F/A PULL STATION

CARD READERCRR

CONDUIT OR WIRE RUN UNDERGROUND OR BELOW ROOF

HATCH MARK INDICATE DEMOLITION WORK

BOLD INDICATES NEW WORK

OS

OS

TV COAXIAL CABLE OUTLET

V VIDEO UNIT

MOTION DETECTORMD

TELECOMMUNICATION TERMINAL OUTLET (2 DATA)

FAINT INDICATES EXISTING WORK

OCCUPANCY SWITCH

SUFFIX 'P' INDICATES ADDITIONAL AMBIENT LIGHT CONTROL FEATURE

OCCUPANCY SENSOR - CEILING MOUNTED

SUFFIX 'P' INDICATES ADDITIONAL AMBIENT LIGHT CONTROL FEATURE

VIDEO OUTLETv

PUSHBUTTON

QUAD RECEPTACLE (DOUBLE DUPLEX), NEMA 5-20R,

GROUNDING TYPE - EMERGENCY POWER

TELECOMMUNICATION OUTLET, QUADX

(1 VOICE, 2 DATA AND 1 ANALOG FOR FAX MACHINE)

PWR POWER

CURRENT TRANSFORMER

MISCELLANEOUS

NOT APPLICABLE

MTG

MTD

N/A

MOUNTED

MOUNTING

GND

JUNCTION BOX

KILOVOLT-AMPERE

KILO-AMPERES

GOVERNMENT

MAX

MECH'L

MIN

MISC

KVA

KV

LTG

LOC

LIGHT

MAXIMUM

MECHANICAL

MINIMUM

KILOWATT

KILOVOLT

LOCATION

HT

Hz

J.B.

KA

GOV

GRN

HEIGHT

HERTZ

GROUND

GREEN

ELECTRICAL METALLIC TUBING

FULL LOAD AMPS

DISTRIBUTION

GROUND FAULT PROTECTION

GROUND FAULT CIRCUIT-INTERRUPTER

EQUIP EQUIPMENT

FLR

GFCI

GALV

GFP

FLA

EXIST / (E)

FT

GALVANIZED

FLOOR

EXISTING

FOOT, FEET

DWG

ELEC'L

ELEV

EMT

ELECT

CU

CT

DISC

DIST

DRAWING

ELECTRICAL

ELECTRIC

ELEVATION

DISCONNECT

COPPER

VOLT AMPS

TRANSFORMER

WIRE TROUGH

WEATHERPROOF

FLOOR OR GRADE

MOUNTING HEIGHT ABOVE FINISHED

PHASE

+12"A.F.F.

WP

XFMR

WT

VA

V

W

VOLT

WIRE

RECEPTACLE

SCHEDULE

SWITCHBOARD

RIGID GALVANIZED STEEL

TELEVISION

TEMPORARY

TELECOM TELECOMMUNICATION

UNDERGROUND

UNIFORM BUILDING CODE

UNDERWRITERS LABORATORIES

UNLESS OTHERWISE NOTED

SHIELDED TWISTED WIRE PAIR

TELE/TEL.

UBC

UL

U/G

UON

TV

TERM

TEMP

TYP

STP

TERMINAL

TYPICAL

ST

SW

SWBD

SCHED

RM

RGS

RECEPT

STREET

SWITCH

ROOM

CONTRACTING OFFICER REPRESENTATIVE

ABOVE FINISHED FLOOR

AMERICAN WIRE GAUGE

BARE COPPER

AMPS INTERRUPTING CAPACITY

CIRCUIT BREAKER

COMMUNICATION

AMERICAN NATIONAL STANDARDS INSTITUTE

B.C.

CKT

COR

CLG

CONN

COMM

BLDG

C.B.

CAT

C

CONNECTED

CIRCUIT

CEILING

BUILDING

CONDUIT

CATALOG

A/AMP

AFF

ANSI

AIC

AWG

NON-FUSED

NATIONAL ELECTRICAL CODE

NOT TO SCALE

NATIONAL ELECTRICAL

OVERLOAD

POLYVINYL CHLORIDE

PUBLIC ADDRESS

MANUFACTURERS ASSOCIATION

NTS

PR

PH

PVC

PRI

PNL

O.L.

P

PA

PAIR

PHASE

PRIMARY

PANEL

POLE

NEC

NO.

NF

NEMA

NUMBER

F/A FIRE ALARM

NL NIGHT LIGHT

DUAL UNIT-D

SINGLE UNIT-S

VETERANS AFFAIR MEDICAL CENTERVAMC

FSD FIRE SMOKE DAMPER

HAND-HOLEHH

EF EXHAUST FAN

KW

1. PENETRATION OF CONDUITS, RACEWAYS AND WIRING THROUGH FIRE RATED WALLS, FLOORS AND

CEILINGS SHALL BE FIRE-STOPPED IN ACCORDANCE WITH SPECIFICATION SECTION 07 84 00. FIRE

STOPPING MATERIALS AND METHODS SHALL BE A U.L. LISTED ASSEMBLY.

2. METHODS AND MATERIALS SHALL BE IN ACCORDANCE WITH NEC. EQUIPMENT SHALL BE IN

ACCORDANCE WITH THE STANDARDS OF NEMA AND ANSI. EQUIPMENT SHALL BE NEW AND LISTED

BY U.L. AND INSTALLED IN ACCORDANCE WITH THE CONDITIONS STATED IN THAT LISTING.

3. BEFORE ENERGIZING, EQUIPMENT SHALL BE TESTED TO BE FREE OF GROUNDS AND SHORTS.

4. RECEPTACLES, OUTLETS AND JUNCTION BOXES (ABOVE AND BELOW CEILING) SHALL BE

PERMANENTLY MARKED AS TO INDICATE THE CIRCUIT NUMBER AND SOURCE PANELBOARD.

PERMANENT MARKING FOR BELOW THE CEILING DEVICES SHALL BE CLEAR 3/8" WIDE STICK-ON

LABEL WITH BLACK LETTERING. PERMANENT MARKING FOR ABOVE THE CEILING DEVICES MAY BE

HAND LABELED WITH PERMANENT MARKER.

5. UNLESS OTHERWISE INDICATED, POWER AND LIGHTING CONDUCTORS SHALL BE TYPE THHN/THWN -2, 600 VOLT, SOLID OR STRANDED COPPER IN ACCORDANCE WITH SPECIFICATION SECTION 26 05 19

AND NOT SMALLER THAN #12 AWG FOR POWER AND LIGHTING CIRCUITS AND #14 AWG FOR

CONTROL CIRCUITS.

6. ALL EQUIPMENT SHALL BE PROPERLY GROUNDED IN STRICT ACCORDANCE WITH THE LATEST

EDITION OF THE NATIONAL ELECTRIC CODE (NEC). PROVIDE EQUIPMENT GROUNDING CONDUCTORS.

CONDUIT CANNOT BE USED AS THE ONLY MEANS OF GROUNDING.

7. FIXTURES AND EQUIPMENT SHALL BE SUPPORTED/MOUNTED TO COMPLY WITH THE SEISMIC

REQUIREMENTS OF THE IBC AND ASCE 7.

8. CONDUIT CONNECTIONS TO MOTORS SHALL BE MADE WITH FLEXIBLE, METAL OR LIQUID TIGHT FLEXIBLE METALLIC CONDUIT IN ACCORDANCE WITH SPECIFICATION SECTION 26 05 33. CONDUIT LENGTH SHALL NOT

BE MORE THAN 6 FEET LONG.

9. MECHANICAL ELECTRICALLY OPERATED EQUIPMENT SHALL BE PROVIDED WITH "WITHIN SIGHT"

PADLOCKABLE DISCONNECTING MEANS CONSISTING OF TOGGLE SWITCH, HORSEPOWER RATED SWITCH, SAFETY DISCONNECT SWITCH OR MOLDED CASE CIRCUIT BREAKER. OUT OF SIGHT LOCKABLE

DISCONNECTING DEVICES ARE NOT ACCEPTABLE TO MEET THIS REQUIREMENT.

10. CONTRACTOR SHALL COORDINATE ELECTRICAL WORK WITH OTHER TRADES.

11. LABEL AND IDENTIFY ALL PANEL SCHEDULES.

12. DEDICATED NEUTRAL SHALL BE PROVIDED FOR ALL NEW 120 AND 277 VOLT CIRCUITS.

13. ALL CONDUITS SHALL BE CONCEALED IN ACCORDANCE WITH SPECIFICATION 26 05 33, CONDUITS SHALL RUN ABOVE THE CEILING, BELOW FINISH FLOOR OR BEHIND THE FINISH WALL, UNLESS OTHERWISE

NOTED.

14. "PROVIDE" MEANS "FURNISH AND INSTALL".

15. ALL ELECTRICAL CONSTRUCTION WORK, METHODS AND MATERIALS SHALL BE IN COMPLIANCE WITH

THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE (NEC) AND APPLICABLE GOVERNMENT

AND VETERANS ADMINISTRATION RULES AND REGULATIONS.

16. ROUTE ALL TELECOMMUNICATION CIRCUITS 18" MINIMUM APART FROM ELECTRICAL CIRCUITS. IN

LOCATIONS WHERE MINIMUM SEPARATION CAN NOT BE OBTAINED, WRAP TELECOMMUNICATION

CIRCUITS WITH GROUNDED METALLIC SHEET TO REDUCE NOISE INTERFERENCE.

17. ALL TELECOMMUNICATION WIRES SHALL BE SUPPORTED BY HANGERS OR WIRE TRAYS. WIRES LAY

ON SUSPENDED CEILING IS PROHIBITED.

18. ALL ABOVE CEILING RACEWAYS, OUTLETS, J.B's AND PULL BOXES SHALL BE HUNG ON THE

CONCRETE SLAB. WALL MOUNTING IS NOT PERMITTED, UNLESS APPROVED BY VAMC

19. PROVIDE ADDITIONAL ACCESS PANEL PER NEC, AS REQUIRED, ON HARD CEILING FOR ELECTRICAL DEVICES, EQUIPMENT, J.B. ETC. ACCESS

GENERAL NOTES:

F/A STROBE

F/A SPEAKER

STROBE AND SPEAKER

M

M MOTOR, 3 PHASE NUMBER INDICATES HORSEPOWER

VARIABLE FREQUENCY DRIVE

TV

SECURE WI-FI CONNECTION

S

UNSECURE WI-FI CONNECTION

LIGHT FIXTURE RECESSED, ON NORMAL POWER (TYP) LETTER INDICATE TYPE (SEE LIGHTING

SCHEDULE FOR SPECIFIC FIXTURE IDENTIFICATION)

VARIABLE FREQUENCY DRIVEVFD

# NOTE REFERENCE

EP###

# DETAIL

DRAWING NUMBER ON WHICH DETAIL IS DRAWN

MECHANICAL EQUIPMENT TAG

XXX

XX

CABLE TRAY

AIR CONDITIONINGA/C

F/A

CAMERA

J T TELEPHONE JUNCTION BOX

SIMPLEX RECEPTACLE, NEMA 5-20R GROUNDING TYPE

SIMPLEX RECEPTACLE, NEMA 5-20R GROUNDING TYPE

WITH GROUND FAULT INTERRUPTER (GFCI)

SWITCHED SPLIT DUPLEX OUTLET, NEMA 5-20R, GROUNDING

TYPE TOP RECEPTACLE SWITCHED

-U UNDER COUNTER / MOUNTED ±18" AFF

NIGHT LIGHT, +/- 18" AFFNL

PENDANT-MTD STRIP LIGHT

TO BE DETERMINETBD

UNSHIELDED TWISTED WIRE PAIRUTP

(R) RELOCATE

S

GFCI

NEW(N)

RECEPTACLE, NEMA 6-20R, 250V (GROUNDING TYPE), 50A, 1 PHASE, 2 POLE, 3

WIRE, GROUNDING, UNLESS OTHERWISE NOTED

50A

VS VACANCY SENSOR - CEILING MOUNTED

E

EXIT SIGN WITHOUT INTREGAL BATTERY BACKUP

US

20. PROVIDE ALL THE EQUIPMENT REQUIRED LOW VOLTAGE CONDUITS AND WIRES.

S T

A

T E

O F C A L I F OR N

I A

EXP.________

E 17641 9-30-2019

R E

G

IS

TE

RED

PROFESS IONAL

ENG

IN

E E

RA

U

G

UST I NE K . LEU

N G

E

L E C T R I C A

L

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 o n e e ig h t in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h ts i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t o n e i n c h o n e f o o t

VA FORM 08-6231

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS:

Drawing Title: Project Title: Project Number:

Building Number:

Drawing Number:Location

Date Checked Drawn

Office of Construction and Facilities Management

Dwg. of

VA MARTINEZ CAMPUS , CA

19 & 20K. F. DAVIS ENGINEERING INC.

530 LA GONDA WAY, SUITE E

DANVILLE, CA 94526

WWW.KFDE.US

(925) 743-8884

02/25/2020

2/25/2020 10:25:35 AMC:\Users\ashrestha\Documents\CHRONIC DIALYSIS FINAL STAMPED SUBMITTAL - REV 2 - V2018_anil.shrestha9MD6R.rvt

CHRONIC DIALYSIS AND

SLEEP PROGRAM

I. VALDOV

E100

ELECTRICAL GENERAL NOTES,

LEGEND AND ABBREVIATIONS

A. LEUNG

612-502

I. VALDOV

1 FURNITURE PLAN 9/9/2019

2 CLIENT COMMENTS 1/28/2020

A A

AA

AA

A A A

AA

A A

A A

A A

A A

A

AA A A

A

A A

A

A A

A A

AAAA A

AAAA

A A A A

AAAA

A A

A A

AAAAA

SS

S S

S S

CCCC

S

S

S

OS

C

C

C

C

S S

S S

S

F

SS SS SS SS SS

S S

S S

SS

S

S

S

S 3 S 3 S 3

E

E E

E E

E

E E

E

E

E

B BB

BBB

BB

BB

BB

BB

B

B

B

B

B

B

B

B

A

A

S S

37.1 38 40 41 42 44 48 50 52 53 54 57 60 63 68 7040.8 48.2 74

B27

CHB-2

CHB-2

CHB-2

CHB-2

CHB-2

CHB-2

CHB-2

CLB-2

CHB-2

E E

E

CHB-2

CLB-2

CLB-2

CLB-2

CLB-2

CLB-2

7 3 4 5 1

CHB-2

B30

B31

B29

B28

SPSP

1. EQUIPMENT SHOWN ARE FOR REFERENCE ONLY AND DO NOT

REPRESENT THE TOTAL NUMBER OR EXACT LOCATION OF EXISTING

EQUIPMENT. CONTRACTOR SHALL FIELD INVESTIGATE THE EXACT

NUMBER AND LOCATION OF EXISTING EQUIPMENT IN THE REMODEL

AREA. CONTRACTOR IS TO DISCONNECT AND REMOVE ALL EXISTING

ELECTRICAL EQUIPMENT, ASSOCIATED WIRES, DEVICES, EXPOSED

AND ABOVE CEILING AND BELOW FLOOR CONDUITS,

OUTLET/JUNCTION BOXES, BACK TO THE SOURCE, UNLESS

OTHERWISE NOTED.

2. SOME OF THE EXISTING EQUIPMENT CIRCUITS FEED MULTIPLE

PIECES OF EXISTING EQUIPMENT THAT IS TO REMAIN OR OUTSIDE

OF THE REMODEL AREA CONTRACTOR SHALL FIELD VERIFY THESE

CIRCUITS AND USE CARE IN THE DISCONNECTION AND REMOVAL OF

THE EQUIPMENT CIRCUITS TO AVOID DISCONNECTING EQUIPMENT,

WHICH IS TO REMAIN, CONTRACTOR SHALL REROUTE CONDUIT AND

CABLES, AS REQUIRED, TO MAINTAIN CIRCUIT INTEGRITY OF THE

EQUIPMENT THAT IS TO REMAIN.

3. ON WALLS AND FLOORS THAT ARE TO REMAIN, REMOVE EXISTING

JUNCTION BOXES THAT ARE NO LONGER IN USE. CAP AND SEAL ALL

IN WALL CONDUITS THAT ARE NO LONGER IN USE AND LABEL AS

SPARE. CONTRACTOR SHALL REPAIR WALL AND FLOOR TO MATCH

EXISTING.

4. EQUIPMENT SOURCE CIRCUIT AND PANEL BOARD SHOWN ARE FOR

REFERENCE ONLY. CONTRACTOR SHALL FIELD VERIFY SOURCE

CIRCUIT AND PANEL BOARD ON EXISTING EQUIPMENT BEING

REMOVED PRIOR TO DEMOLITION.

5. WHETHER SHOWN OR NOT, REMOVE AND REINSTALL WIFI

ANTENNA IN THE SAME LOCATION, IF POSSIBLE, OR WITHIN 3 FEET

OF THE EXISTING LOCATION. COORDINATE WITH VAMC ON WIFI

ANTENNAS' FINAL LOCATIONS.

GENERAL NOTES

SHEET NOTES

1 ALL NORMAL POWER LIGHTS IN THE OFFICE AREA ARE FED FROM

NHB-1 (PNL NHB, CKT 1) UNLESS OTHERWISE NOTED.

CIRCUIT CHB-2 (PNL CHB, CKT 2) ALSO FEEDS EMERGENCY LTG OUTSIDE

OF THE REMODEL AREA.

SUSPENDED FIXTURES AND WALL SCONES IN THE CANTEEN AREA ARE

FED FROM NLB-37 (PNL NLB, CKT 37) UNLESS OTHERWISE NOTED.

2 X 4 FIXTURES IN THE CANTEEN AREA ARE FED FROM NHB-3 (PNL NHB,

CKT 3) UNLESS OTHERWISE NOTED.

DOWNLIGHT IN THE CANTEEN ARE FED FROM NLB-39 (PNL NLB, CKT 39)

UNLESS OTHERWISE NOTED

CIRCUIT CLB-2 (PNL CLB, CKT 2) ALSO FEEDS EMERGENCY LTGS

OUTSIDE OF THE REMODEL AREA

CEILING FIXTURES IN THE PHARMACY AREA ARE FED FROM CHB-2

(PNL CHB, CKT 2) UNLESS OTHERWISE NOTED.

LEGEND

2x2 CEILING RECESSED FIXTURE

CEILING RECESSES DOWNLIGHT

WALL-MTD SCONE

CEILING SUSPENDED FIXTURE

2x4 CEILING RECESSED FIXTURE

WALL-MTD VANITY LIGHT

PLUG-CONNECTED, WALL-MTD BUG LIGHT

CEILING SPEAKER

A

B

A

F

S

E

C

SP

S T A T E

O F C A L I F OR N

I A

EXP.________

E 17641 9-30-2019

RE

G

IS

TE

RED PROFESS IONAL

ENG

INEERA

UG

UST I NE K . LEUNG

E

L E C T R I C A L

PROJECT

NORTH

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 on e ei gh t i nc h on e fo ot on e qu ar te r i nc h on e fo ot th re e ei gh ts in ch o ne fo ot on e ha lf in ch o ne fo ot th re e qu ar te rs in ch o ne fo ot on e in ch o ne fo ot on e an d on e ha lf in ch o ne fo ot on e in ch o ne fo ot

VA FORM 08-6231

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Drawing Title: Project Title: Project Number:

Building Number:

Drawing Number:Location

Date Checked Drawn

Office of Construction and Facilities Management

Dwg. of

VA MARTINEZ CAMPUS , CA

19 & 20K. F. DAVIS ENGINEERING INC.

530 LA GONDA WAY, SUITE E

DANVILLE, CA 94526

WWW.KFDE.US

(925) 743-8884

KEY PLAN

C BUILDING 19

BUILDING 20

02/25/2020

2/25/2020 8:08:55 AMC:\Users\ashrestha\Documents\CHRONIC DIALYSIS FINAL STAMPED SUBMITTAL - REV 2 - V2018_anil.shrestha9MD6R.rvt

CHRONIC DIALYSIS AND

SLEEP PROGRAM

I. VALDOV

ED101C

ELECTRICAL LIGHTING DEMOLITION

PLAN - RENOVATION C

A. LEUNG

612-502

I. VALDOV

1/4" = 1'-0"ED101C

1 ELECTRICAL LIGHTING DEMOLITION PLAN - RENOVATION C

JW

J

J

J

CAN-26 CAN-26

C A

N -2

-H

PNL CAN

M O

TO

R

IZ

E

D

S C

R E

E N

IN

C

LG

P R

O

JE

C

TO

R C

E

IL

IN

G

M O

U N

T E

D

A/C 1

WIRE WAY TO

MODULAR

FURNITURE (TYP)

J T

PRINTER

OUTLET

WIREMOLD

TV

37.1 38 40 41 42 44 48 50 52 53 54 57 60 63 68 7040.8 48.2 74

B27

5CLB-16

CLB-16

NLB-1

T-CAN

T

B30

B31

B29

B28

B26

4.33

VAV

4.34

VAV

4.35

VAV

4.36

VAV

1.

2.

3.

4.

5.

GENERAL NOTES

EQUIPMENT SHOWN ARE FOR REFERENCE ONLY AND DO NOT

REPRESENT THE TOTAL NUMBER OR EXACT LOCATION OF EXISTING

EQUIPMENT. CONTRACTOR SHALL FIELD INVESTIGATE THE EXACT

NUMBER AND LOCATION OF EXISTING EQUIPMENT IN THE REMODEL

AREA. CONTRACTOR IS TO DISCONNECT AND REMOVE ALL EXISTING

ELECTRICAL EQUIPMENT, ASSOCIATED WIRES, DEVICES, EXPOSED

AND ABOVE CEILING AND BELOW FLOOR CONDUITS,

OUTLET/JUNCTION BOXES BACK TO THE SOURCE, UNLESS

OTHERWISE NOTED.

SOME OF THE EXISTING EQUIPMENT CIRCUITS FEED MULTIPLE

PIECES OF EXISTING EQUIPMENT THAT IS TO REMAIN OR OUTSIDE OF

THE REMODEL AREA. CONTRACTOR SHALL FIELD VERIFY THESE

CIRCUITS AND USE CARE IN THE DISCONNECTION AND REMOVAL OF

THE EQUIPMENT CIRCUITS TO AVOID DISCONNECTING EQUIPMENT,

WHICH IS TO REMAIN, CONTRACTOR SHALL REROUTE CONDUIT AND

CABLES, AS REQUIRED, TO MAINTAIN CIRCUIT INTEGRITY OF THE

EQUIPMENT THAT IS TO REMAIN.

ON WALLS AND FLOORS THAT ARE TO REMAIN, REMOVE EXISTING

JUNCTION BOXES THAT ARE NO LONGER IN USE. CAP AND SEAL ALL

CONDUITS THAT ARE NO LONGER IN USE AND LABEL AS SPARE.

CONTRACTOR SHALL REPAIR WALL AND FLOOR TO MATCH EXISTING.

EQUIPMENT SOURCE CIRCUIT AND PANELBOARD SHOWN ARE FOR

REFERENCE ONLY. CONTRACTOR SHALL FIELD VERIFY SOURCE

CIRCUIT AND PANELBOARD ON EXISTING EQUIPMENT BEING

REMOVED PRIOR TO DEMOLITION.

SEE MECHANICAL DRAWING ON MECHANICAL EQUIPMENT

DEMOLITION REQUIREMENTS.

SHEET NOTES

1 REMOVE A/C UNIT CONDUIT WIRES AND ASSOCIATED DEVICES.

REMOVE CAMERA.

RECEPT IN THE OFFICE AREA ARE FED FROM NLB-3, 5, 7, 9, 11, 13,

15, 17, 19, 21, AND 23, UON.

CKT NLB-7 ALSO FED RECEPT OUTSIDE OF THE REMODEL AREA.

CKT CLB-16 (PNL CLB, CKT 16) ALSO FED EQUIP OUTSIDE OF THE

REMODEL AREA.

EQUIPMENT IN CANTEEN KITCHEN AND STORAGE AREA ARE FED

FROM PNL CAN, UON.

RECEPT IN CANTEEN SEATING AREA ARE FED FROM NLB-1 & 2 (PNL

NLB, CKT 1 & 2), UON.

CKT NLB-2 ALSO FED RECEPT OUTSIDE OF THE REMODEL AREA.

EQUIPMENT IN PHARMACY AREA ARE FED FROM NLK-37, 39, 41 (PNL

NLK, CKT 37, 39, 41), UON.

REMOVE ALL CONDUITS, WIRES AND DEVICES ASSOCIATED WITH

VAV.

VAV POWER CIRCUIT IS TO REMAIN FOR EXTENSION TO FEED NEW

VAV. SEE DRAWING EP122C

REMOVE ALL OTHER CONDUITS, WIRES AND DEVICES ASSOCIATED

WITH THE VAV.

S T A T E

O F C A L I F OR N

I A

EXP.________

E 17641 9-30-2019

RE

G

IS

TE

RED PROFESS IONAL

ENG

INEERA

UG

UST I NE K . LEUNG

E

L E C T R I C A L

PROJECT

NORTH

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 on e ei gh t i nc h on e fo ot on e qu ar te r i nc h on e fo ot th re e ei gh ts in ch o ne fo ot on e ha lf in ch o ne fo ot th re e qu ar te rs in ch o ne fo ot on e in ch o ne fo ot on e an d on e ha lf in ch o ne fo ot on e in ch o ne fo ot

VA FORM 08-6231

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Drawing Title: Project Title: Project Number:

Building Number:

Drawing Number:Location

Date Checked Drawn

Office of Construction and Facilities Management

Dwg. of

VA MARTINEZ CAMPUS , CA

19 & 20K. F. DAVIS ENGINEERING INC.

530 LA GONDA WAY, SUITE E

DANVILLE, CA 94526

WWW.KFDE.US

(925) 743-8884

KEY PLAN

C BUILDING 19

BUILDING 20

02/25/2020

2/25/2020 8:08:58 AMC:\Users\ashrestha\Documents\CHRONIC DIALYSIS FINAL STAMPED SUBMITTAL - REV 2 - V2018_anil.shrestha9MD6R.rvt

CHRONIC DIALYSIS AND

SLEEP PROGRAM

I. VALDOV

ED102C

ELECTRICAL POWER DEMOLITION

PLAN - RENOVATION C

A. LEUNG

612-502

I. VALDOV

1/4" = 1'-0"ED102C

1 ELECTRICAL POWER DEMOLITION PLAN - RENOVATION C

F .E

.C .C

GCG

CG

CG

CG

CG

JK

12.9

HL

O S

O S

D

D D ccc

A 24 A

A

T1

A

A

A

T1

B

B

B

B

B

B

C

C

C

C

C

C

T1

K

F F

J

J

G

H

A

A

A

A

A

J SP

J SP2

4 5

PNL HAA1, CKT 24

J

J

J

E

E

SP

SP

S

US

GENERAL NOTES

1.

2.

3.

4.

5.

6.

7.

8.

FOR SIMPLICITY AND CLARITY BRANCH FEEDER CONDUIT AND WIRES

ARE NOT SHOWN ON THE DRAWING. ONLY CIRCUIT NUMBER TO THE

EQUIPMENT AND HOMERUNS ARE SHOWN. CONTRACTOR SHALL

PROVIDE AND INSTALL BRANCH FEEDER CONDUITS, OUTLET BOXES,

WIRE AND JUNCTION BOXES FOR NEW WIRING INSTALLATION. ALL

HOMERUN CIRCUITS ARE 2 #10 AND 1 #10 GND (GRN) IN A 3/4"

CONDUIT, UNLESS OTHERWISE NOTED.

LIGHT SWITCHES MOUNTED 48" A.F.F., UNLESS OTHERWISE

INDICATED.

ALL CONDUITS SHALL BE CONCEALED IN ACCORDANCE WITH

SPECIFICATION SECTION 26 05 33. CONDUIT SHALL RUN ABOVE

CEILING OR WITHIN FINISHED WALLS.

CORE DRILL WALL AND FLOOR FOR CONDUITS PENETRATION, AS

REQUIRED.

LIGHT CIRCUIT IS FROM PANEL HAA1, CKT 24.

PROVIDE ADDITIONAL ACCESS PANELS, AS REQUIRED PER NEC, ON

HARD CEILING FOR ELECTRICAL J.B., DEVICES, EQUIPMENT, ETC.

OCCUPANCY SENSORS SHALL BE SUITABLE FOR LED LIGHT FIXTURE

AND IT SHALL PROVIDE COMPLETE COVERAGE OF THE ASSOCIATED

AREA WHERE THE OCCUPANCY SENSOR IS INSTALLED.

CONTRACTOR SHALL PROVIDE SPEAKERS FOR PUBLIC ADDRESS

SYSTEM TO MATCH EXISTING FACILITY SPEAKERS. TIE IN THE NEW

SPEAKERS TO THE EXISTING PUBLIC ADDRESS SYSTEM. PROVIDE A

SUFFICIENT NUMBER OF SPEAKERS AS NECESSARY TO ACHIEVE

ADEQUATE SOUND COVERAGE THROUGHOUT THE REMODEL AREA.

COORDINATE WITH VAMC ON EXISTING SYSTEM TYPE,

REQUIREMENTS AND POINT OF CONNECTION.

SHEET NOTES

PROVIDE AN UNSWITCHED HOT WIRE CONNECTION TO

EMERGENCY DRIVER.

4" X 4" J.B. FOR SECURED WI-FI. RUN WIRES TO ROOM D101.

COORDINATE WITH VAMC ON J.B. EXACT LOCATION.

4" X 4" J.B. FOR PUBLIC WI-FI. RUN WIRES TO ROOM D101.

COORDINATE WITH VAMC ON J.B. EXACT LOCATION.

COORDINATE WITH VMAC ON WI-FI WIRING REQUIREMENTS AND

POINT OF TERMINATION.

COORDINATE WITH COR ON PUBLIC ADDRESS SPEAKER

REQUIREMENTS AND POINT OF TERMINATION.

PROVIDE SPEAKERS MATCHING EXISTING SPEAKERS AND SYSTEM

IN BLDG 19.

MARK "LTG-COFFEE BAR" ON PANELBOARD SCHEDULE.

PROVIDE LABEL ON SWITCH "EMERGENCY LIGHT MAINTENANCE

DISCONNECT".

S T

A

T E

O F C A L I F OR N

I A

EXP.________

E 17641 9-30-2019

R E

G

IS

TE

RED

PROFESS IONAL

ENG

IN

E E

RA

U

G

UST I NE K . LEU

N G

E

L E C T R I C A

L

PROJECT

NORTH

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 o n e e ig h t in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h ts i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t o n e i n c h o n e f o o t

VA FORM 08-6231

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS:

Drawing Title: Project Title: Project Number:

Building Number:

Drawing Number:Location

Date Checked Drawn

Office of Construction and Facilities Management

Dwg. of

VA MARTINEZ CAMPUS , CA

19 & 20K. F. DAVIS ENGINEERING INC.

530 LA GONDA WAY, SUITE E

DANVILLE, CA 94526

WWW.KFDE.US

(925) 743-8884

KEY PLAN

A

BUILDING 19

BUILDING 20

02/25/2020

2/25/2020 9:54:52 AMC:\Users\ashrestha\Documents\CHRONIC DIALYSIS FINAL STAMPED SUBMITTAL - REV 2 - V2018_anil.shrestha9MD6R.rvt

CHRONIC DIALYSIS AND

SLEEP PROGRAM

I. VALDOV

EL110A

ELECTRICAL LIGHTING, PUBLIC

ADDRESS AND WI-FI PLAN -

ADDITION A

A. LEUNG

612-502

I. VALDOV

PROJECT

NORTH

1/4" = 1'-0"EL110A

1 ELECTRICAL LIGHTING PLAN - ADDITION A

F.E.C. F.E.C.

D D

3D

D

3D

3D

DD

3D

D D D

3D3D

3D

3D

3D 3D

3D

3D

3D

3D

DD

D

3D 3D

3D 3D

GENERAL NOTES

1.

2.

3.

4.

5.

6.

7.

8.

9.

FOR SIMPLICITY AND CLARITY BRANCH FEEDER CONDUIT AND WIRES

ARE NOT SHOWN ON THE DRAWING. ONLY CIRCUIT NUMBER TO THE

EQUIPMENT AND HOMERUNS ARE SHOWN. CONTRACTOR SHALL

PROVIDE AND INSTALL BRANCH FEEDER CONDUITS, OUTLET BOXES,

WIRE AND JUNCTION BOXES FOR NEW WIRING INSTALLATION. ALL

HOMERUN CIRCUITS ARE 2 #10 AND 1 #10 GND (GRN) IN A 3/4"

CONDUIT, UNLESS OTHERWISE NOTED.

LIGHT SWITCHES MOUNTED 48" A.F.F., UNLESS OTHERWISE

INDICATED.

ALL CONDUITS SHALL BE CONCEALED IN ACCORDANCE WITH

SPECIFICATION SECTION 26 05 33. CONDUIT SHALL RUN ABOVE

CEILING OR WITHIN FINISHED WALLS.

CORE DRILL WALL AND FLOOR FOR CONDUITS PENETRATION, AS

REQUIRED.

OCCUPANCY SENSOR LOCATION AND AMOUNT SHOWN IS FOR

REFERENCE ONLY. CONTRACTOR IS TO PROVIDE SUFFICIENT

NUMBER OF OCCUPANCY SENSORS, INSTALL AT LOCATIONS WHICH

COMPLETELY COVERS THE AREA WHERE THE OCCUPANCY SENSORS

ARE INSTALLED

PROVIDE ADDITIONAL ACCESS PANEL, AS REQUIRED PER NEC, ON

HARD CEILING FOR ELECTRICAL J.B., DEVICES, EQUIPMENT, ETC.

ACCESSIBLE.

OCCUPANCY SENSOR SHALL BE SUITABLE FOR LED LIGHT FIXTURE

AND IT SHALL PROVIDE COMPLETE COVERAGE OF THE ASSOCIATED

AREA WHERE THE OCCUPANCY SENSOR IS INSTALLED.

CONTRACTOR SHALL PROVIDE SPEAKERS FOR PUBLIC ADDRESS

SYSTEM TO MATCH EXISTING FACILITY SPEAKERS. TIE IN THE NEW

SPEAKERS TO THE EXISTING PUBLIC ADDRESS SYSTEM. PROVIDE A

SUFFICIENT NUMBER OF SPEAKERS AS NECESSARY TO ACHIEVE

ADEQUATE SOUND COVERAGE THROUGHOUT THE REMODEL AREA.

COORDINATE WITH COR ON EXISTING SYSTEM TYPE, REQUIREMENTS

AND POINT OF CONNECTION.

CIRCUIT NUMBERS WITHOUT ANY PANEL IDENTIFICATION ARE LIGHT

CIRCUITS FROM PANEL NHG, OTHERS ARE PRECEEDED BY PANEL

DESIGNATION.

6 7

C

E

F

G

CONFERENCE

G109

NEPHRO - LOGIST

G110

STERILE

EQUIPMENT

G111 TOILET 1

G112

SLEEP ROOM 1

G113 ba a a b

TOILET 3

G115A

TOILET 1

G113A

CONTROL ROOM

G114

PRINT/COPY

C410A

SLEEP ROOM 3

G115

SLEEP ROOM 4

G116

SLEEP ROOM 2

G117

TOILET 2

G118

DIALYSIS

EQUIPMENT

G119

CORRIDOR 2

C409

CORRIDOR 4

C410

TOILET 4

G116A

TOILET 2

G117A b a b

OS

OS

OS

OS

a

B

A

6.3 6.4

B.8

C.8

D

F.8

CORRIDOR 3

C408

OS

OS

8.1 9 10

E2 b a a a

O S

O S

E2

E2E2 aa a a aa a a aa a a b bb

B1

B1

B1

B1B1B1

B1B1B1

B1

B1B1 K

K

D1

D1

D1

D1

D2

D2

E2

E2

E

F

E

F

D1 D1

O S

D1

D1D1

O S

O S

D

8 8.5

B1

D1

B1

F

B1

B1

T1

SP

F

FF

F

F

F F

F

F F

F F

FF

FF

F

FF

F

F

F F

F

T1 K

OS

SP

SPOSSP

T1

OS

OS

SP

T1

SP

SP

T1

T1

DEMO EXISTING LIGHT

CHG-4

CHG-44

CHG-4

4 4

CHG-2

4 CHG-2

CHG-2

CHG-4

CHG-2

CHG-2

4 4

4 4

4 4

4 4

CHG-2

4 4

4 4

CHG-2

CHG-2

CHG-2

CHG-2

CHG-2

CHG-2

CHG-2

CHG-2

CHG-2

CHG-2

CHG-2

1 CHG-2 (TYP)

2 CHG-4 (TYP)

3 (TYP)

2 (TYP)

CHG-2

PNL NHG, CKT4

CHG-2

CHG-2

CHG-2

CHG-2

CHG-2

CHG-2

CHG-2

CHG-2

PNL CHG, CKT2

CHG-4

T1

SP

T1

PNL CHG, CKT4

CHG-4

OS

CHG-2

OS

T1

CHG-4

3 (TYP)

SEE EL 110.1B FOR

CONTINUATION

SEE EL 110.1B FOR

CONTINUATION

ALL EMERGENCY LITE CIRCUIT IS FROM PANEL CHG CIRCUIT #2

ALL EXIT LITE CIRCUIT IS FROM PANEL CHG CIRCUIT #4

LIGHT CIRCUIT IS FROM PANEL NHG CIRCUIT #4

SHEET NOTES:

S T A T E

O F C A L I F OR N

I A

EXP.________

E 17641 9-30-2019

RE

G

IS

TE

RED PROFESS IONAL

ENG

INEERA

UG

UST I NE K . LEUNG

E

L E C T R I C A L

PROJECT

NORTH

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 on e ei gh t i nc h on e fo ot on e qu ar te r i nc h on e fo ot th re e ei gh ts in ch o ne fo ot on e ha lf in ch o ne fo ot th re e qu ar te rs in ch o ne fo ot on e in ch o ne fo ot on e an d on e ha lf in ch o ne fo ot on e in ch o ne fo ot

VA FORM 08-6231

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Drawing Title: Project Title: Project Number:

Building Number:

Drawing Number:Location

Date Checked Drawn

Office of Construction and Facilities Management

Dwg. of

VA MARTINEZ CAMPUS , CA

19 & 20K. F. DAVIS ENGINEERING INC.

530 LA GONDA WAY, SUITE E

DANVILLE, CA 94526

WWW.KFDE.US

(925) 743-8884

KEY PLAN

B

BUILDING 19

BUILDING 20

02/25/2020

2/25/2020 8:09:03 AMC:\Users\ashrestha\Documents\CHRONIC DIALYSIS FINAL STAMPED SUBMITTAL - REV 2 - V2018_anil.shrestha9MD6R.rvt

CHRONIC DIALYSIS AND

SLEEP PROGRAM

I. VALDOV

EL110.1B

ELECTRICAL LIGHTING PLAN EAST -

ADDITION B

A. LEUNG

612-502

I. VALDOV

PROJECT

NORTH

1/4" = 1'-0"EL110.1B

1 ELECTRICAL LIGHTING PLAN EAST - ADDITION B

.C

DDDD

D D

3D

3D

3D

3D

D

3D

3D

3D

3D

3D

3D

3D 3D

3D 3D

1 2 3 4 6

C

E

F

G

CHIEF

G106 CONSULT

G107

ELECTRICAL

ROOM

G108

OPEN OFFICE

G100

OS

TELECOM

G105

SUPV

G104

SUPV

G103

SUPV

G102

CONFERENCE

G109

CORRIDOR 1

C411

2.9

B

A

3.5

B.8

C.8

D

F.8

4.7

CORRIDOR 3

C408

OS

OS

B1

D1

D1

D2

D2

D1

K B1B1

E1

E1 E2 E1

E1E2 E2

E2

E2

E2 D1

D1

D2 D2 D2 D2

D2 D2 D2 D2

C1 C1 C1 C1

D1 D1 D1

D1 D1 D1

OS

OS

OS

C1C1K

F

D1

OS

SP

T1

SP

SP

T1

T1

T1

SP

SPSP

SPSP

SP

T1

D

D

D

DEMO EXISTING LIGHT

CHG-4

CHG-2

CHG-2

CHG-2

CHG-2

CHG-2

2 (TYP)

2CHG-4

CHG-2

CHG-2

CHG-2

CHG-2

CHG-2

CHG-2

CHG-2

CHG-2

3 CHG-2

1 (TYP)

CHG-4

OS

CHG-2

OS

T1

CHG-4

CHG-4

SEE EL 110.1B FOR

CONTINUATION

SEE EL 110.1B FOR

CONTINUATION

PNL NHG

CKT 2.

(TYP)

GENERAL NOTES

1.

2.

3.

4.

5.

6.

7.

8.

9.

FOR SIMPLICITY AND CLARITY BRANCH FEEDER CONDUIT AND

WIRES ARE NOT SHOWN ON THE DRAWING. ONLY CIRCUIT

NUMBER TO THE EQUIPMENT AND HOMERUNS ARE SHOWN.

CONTRACTOR SHALL PROVIDE AND INSTALL BRANCH FEEDER

CONDUITS, OUTLET BOXES, WIRE AND JUNCTION BOXES FOR NEW

WIRING INSTALLATION. ALL HOMERUN CIRCUITS ARE 2 #10 AND 1 #

10 GND (GRN) IN A 3/4" CONDUIT, UNLESS OTHERWISE NOTED.

LIGHT SWITCHES MOUNTED 48" A.F.F., UNLESS OTHERWISE

INDICATED.

ALL CONDUITS SHALL BE CONCEALED IN ACCORDANCE WITH

SPECIFICATION SECTION 26 05 33. CONDUIT SHALL RUN ABOVE

CEILING OR WITHIN FINISHED WALLS.

CORE DRILL WALL AND FLOOR FOR CONDUITS PENETRATION, AS

REQUIRED.

OCCUPANCY SENSOR LOCATION AND AMOUNT SHOWN IS FOR

REFERENCE ONLY. CONTRACTOR IS TO PROVIDE SUFFICIENT

NUMBER OF OCCUPANCY SENSORS, INSTALL AT LOCATIONS

WHICH COMPLETELY COVERS THE AREA WHERE THE OCCUPANCY

SENSORS ARE INSTALLED

CIRCUIT NUMBERS WITHOUT ANY PANEL IDENTIFICATION ARE

LIGHT CIRCUITS FROM PANEL NHG; OTHERS ARE PROCEEDED BY

PANEL IDENTIFICATION.

PROVIDE ADDITIONAL ACCESS PANEL, AS REQUIRED PER NEC, ON

HARD CEILING FOR ELECTRICAL J.B., DEVICES, EQUIPMENT, ETC.

ACCESSIBLE.

OCCUPANCY SENSORS SHALL BE SUITABLE FOR LED LIGHT

FIXTURE AND IT SHALL PROVIDE COMPLETE COVERAGE OF THE

ASSOCIATED AREA WHERE THE OCCUPANCY SENSOR IS

INSTALLED.

CONTRACTOR SHALL PROVIDE SPEAKERS FOR PUBLIC ADDRESS

SYSTEM TO MATCH EXISTING FACILITY SPEAKERS. TIE IN THE NEW

SPEAKERS TO THE EXISTING PUBLIC ADDRESS SYSTEM. PROVIDE

A SUFFICIENT NUMBER OF SPEAKERS AS NECESSARY TO

ACHIEVE ADEQUATE SOUND COVERAGE THROUGHOUT THE

REMODEL AREA. COORDINATE WITH COR ON EXISTING SYSTEM

TYPE, REQUIREMENTS AND POINT OF CONNECTION.

ALL EMERGENCY LITE CIRCUIT IS FROM PANEL CHG CIRCUIT #2

ALL EXIT LITE CIRCUIT IS FROM PANEL CHG CIRCUIT #4

LIGHT CIRCUIT IS FROM PANEL NHG CIRCUIT #2

SHEET NOTES:

S T A T E

O F C A L I F OR N

I A

EXP.________

E 17641 9-30-2019

RE

G

IS

TE

RED PROFESS IONAL

ENG

INEERA

UG

UST I NE K . LEUNG

E

L E C T R I C A L

PROJECT

NORTH

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 on e ei gh t i nc h on e fo ot on e qu ar te r i nc h on e fo ot th re e ei gh ts in ch o ne fo ot on e ha lf in ch o ne fo ot th re e qu ar te rs in ch o ne fo ot on e in ch o ne fo ot on e an d on e ha lf in ch o ne fo ot on e in ch o ne fo ot

VA FORM 08-6231

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Drawing Title: Project Title: Project Number:

Building Number:

Drawing Number:Location

Date Checked Drawn

Office of Construction and Facilities Management

Dwg. of

VA MARTINEZ CAMPUS , CA

19 & 20K. F. DAVIS ENGINEERING INC.

530 LA GONDA WAY, SUITE E

DANVILLE, CA 94526

WWW.KFDE.US

(925) 743-8884

KEY PLAN

B

BUILDING 19

BUILDING 20

02/25/2020

2/25/2020 8:09:12 AMC:\Users\ashrestha\Documents\CHRONIC DIALYSIS FINAL STAMPED SUBMITTAL - REV 2 - V2018_anil.shrestha9MD6R.rvt

CHRONIC DIALYSIS AND

SLEEP PROGRAM

I. VALDOV

EL110.2B

ELECTRICAL LIGHTING PLAN WEST -

ADDITION B

A. LEUNG

612-502

I. VALDOV

1/4" = 1'-0"EL110.2B

1 ELECTRICAL LIGHTING PLAN WEST - ADDITION B PROJECT

NORTH

D D

D DD

D D

D D

D D

DD

3D3D

DD

BREAKROOM

56 SF

VAULT

H301

PREP AND

PACKAGING

b b aa a a aaa a a a

D D D D

B

B B

B B

B B

A

A

A

A

AA A

aa a a a a a a b b a aa

A b

A b

A a

A a

A a

A b

A a

A

A

A c

A c a b

A d

A A

A

A c

A c

D2 D2D2 d

A c

A c d c e

DD

D

D

D

D

D

A d

A c

A c

A cD D D D

D D D D

D1D1 D1D1

B1

D1D1

B1 ab B1B1 b b

D1D1D1

D1

D1 D1

D1 D2 D2

D2D2

37.1 38 40 41 42 44 48 50 52 53 54 57 60 63 68 7040.8 48.2 74

B27

I1I1 I1

I2

I2

I2

I2

I1I1 I1

I2

I2

I2

I2

I1I1 I1

I2

I2

I2

I2

I1 I1

I2

I2

I2

I2

T1

T1

A

T1

SP SP

SPSP

SP

SPSP

SP

SP

SP

SP

T1

SP

SP

T1

T1 b a

SP

T1

SP

A c

A c d A

B30

B31

PNL CHB

#6 37

PNL CHB

#6

PNL CHB

#6

PNL CHB

#6

PNL CHB

#6

PNL CHB

#6

PNL CHB

#6

PNL CHB

#6

37 37

PNL CHB

#6

PNL CHB

#6

PNL CHB

#6

37 37 37

PNL CHB

#6

373737

PNL CHB

#6

37 37 37

PNL CHB

#6

37 37

PNL CHB

#6

PNL CHB

#6

37 37

37 37 37 37

PNL CHB

#6 37

PNL CHB

#6

PNL CHB

#6

PNL CHB

#6

PNL CHB

#6

PNL CHB

#6

PNL CHB

#6

PNL CHB

#6

37 37

PNL CHB

#6 e e e e cdc d c c cdc d c

3737 37

PNL CHB

#6

37 37

PNL CHB

#6

PNL CHB

#6

CHB #4

CHB #4

(TYP)

CHB#4

(TYP)

CHB#2

(TYP)

NHB#37

B29

B28

PNL CHB

#6

CHB #4

CHB#4

CHB #4

CHB #4

c

CONFERENCE

CONSULT FOOD PREP

ELECTRICAL

ROOM

RECEIVING STOR

RETAIL SPACE

RETAIL SPACE

DINING

DINING

A c

(TYP)

PNL CHB, CKT 4 PNL NHB, CKT 37

PNL CHB, CKT 6

FOR SIMPLICITY AND CLARITY BRANCH FEEDER CONDUIT AND WIRES IS

NOT SHOWN ON THE DRAWING. ONLY CIRCUIT NUMBER TO THE

EQUIPMENT AND HOMERUNS ARE SHOWN. CONTRACTOR SHALL

PROVIDE AND INSTALL BRANCH FEEDER CONDUITS, OUTLET BOXES,

WIRE AND JUNCTION BOXES FOR NEW WIRING INSTALLATION. ALL

HOMERUN CIRCUITS ARE 2#10 AND 1#10 GND (GRN) IN A 3/4" CONDUIT

UNLESS OTHERWISE NOTED.

LIGHT SWITCHES MOUNTED 48", AFF UNLESS OTHERWISE INDICATED.

ALL CONDUITS SHALL BE CONCEALED IN ACCORDANCE WITH

SPECIFICATION SECTION 26 05 33 CONDUIT SHALL RUN ABOVE CEILING

OR WITHIN FINISHED WALLS.

CORE DRILL WALL AND FLOOR FOR CONDUITS PENETRATION, AS

REQUIRED.

OCCUPANCY SENSOR LOCATION AND AMOUNT SHOWN IS FOR

REFERENCE ONLY. CONTRACTOR IS TO PROVIDE SUFFICIENT NUMBER

OF OCCUPANCY SENSORS, INSTALL AT LOCATIONS WHICH COMPLETELY

COVERS THE AREA WHERE THE OCCUPANCY SENSORS ARE INSTALLED.

PROVIDE ADDITIONAL ACCESS PANEL, AS REQUIRED PER NEC, ON HARD

CEILING FOR ELECTRICAL J.B., DEVICES, EQUIPMENT, ETC. ACCESSIBLE.

OCCUPANCY SENSOR SHALL BE SUITABLE FOR LED LIGHT FIXTURE.

CONTRACTOR SHALL PROVIDE SPEAKERS FOR PUBLIC ADDRESS

SYSTEM TO MATCH EXISTING FACILITY SPEAKERS. TIE IN THE NEW

SPEAKERS TO THE EXISTING PUBLIC ADDRESS SYSTEM. PROVIDE A

SUFFICIENT NUMBER OF SPEAKERS AS NECESSARY TO ACHIEVE

ADEQUATE SOUND COVERAGE THROUGHOUT THE REMODEL AREA.

COORDINATE WITH COR ON EXISTING SYSTEM TYPE, REQUIREMENTS

AND POINT OF CONNECTION.

GENERAL NOTES

1.

2.

3.

4.

5.

6.

7.

8.

SHEET NOTES

ALL EMERGENCY LIGHTS IN PANEL CHB CIRCUIT #6.

ALL EXIT LIGHT ON PANEL CHB CIRCUIT #4.

ALL LIGHTING NOT MARKED OTHERWISE OR NOT MARKED FOR

EMERGENCY LIGHTS IS FED FROM PANEL NHB CIRCUIT #37.

FIXTURE I2 GLOBAL POWER TRACK.

S T A T E

O F C A L I F OR N

I A

EXP.________

E 17641 9-30-2019

RE

G

IS

TE

RED PROFESS IONAL

ENG

INEERA

UG

UST I NE K . LEUNG

E

L E C T R I C A L

PROJECT

NORTH

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 on e ei gh t i nc h on e fo ot on e qu ar te r i nc h on e fo ot th re e ei gh ts in ch o ne fo ot on e ha lf in ch o ne fo ot th re e qu ar te rs in ch o ne fo ot on e in ch o ne fo ot on e an d on e ha lf in ch o ne fo ot on e in ch o ne fo ot

VA FORM 08-6231

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Drawing Title: Project Title: Project Number:

Building Number:

Drawing Number:Location

Date Checked Drawn

Office of Construction and Facilities Management

Dwg. of

VA MARTINEZ CAMPUS , CA

19 & 20K. F. DAVIS ENGINEERING INC.

530 LA GONDA WAY, SUITE E

DANVILLE, CA 94526

WWW.KFDE.US

(925) 743-8884

KEY PLAN

C BUILDING 19

BUILDING 20

02/25/2020

2/25/2020 8:09:21 AMC:\Users\ashrestha\Documents\CHRONIC DIALYSIS FINAL STAMPED SUBMITTAL - REV 2 - V2018_anil.shrestha9MD6R.rvt

CHRONIC DIALYSIS AND

SLEEP PROGRAM

I. VALDOV

EL110C

ELECTRICAL LIGHTING PLAN -

RENOVATION C

A. LEUNG

612-502

I. VALDOV

1/4" = 1'-0"EL110C

1 ELECTRICAL LIGHTING PLAN - RENOVATION C

PROJECT

NORTH

LIGHTING FIXTURE SCHEDULE

DESCRIPTION AND MANUFACTURER

SYMBOL

FIXTURE

LAMP REMARKS

FIXTURE

MOUNTING

INPUT WATT W/

DRIVER LOCATION

FIXTURE

TYPE

FIXTURE

A

B

E

LED

CEILING

RECESSED

CEILING

SURFACE

LED, 900 LUMENS MINIMUM, 2" ROUND PINHOLE SURFACE MOUNTED DOWNLIGHT WITH 4" LED MODULE, 40º FLOOD OPTIC, WHITE

HOUSING LED ELECTRONIC DRIVER, 3500ºK, CRI ≥ 90, UNIVERSAL VOLTAGE

EATON COOPER LIGHTING, HALO BRAND, CAT. NO. ML4D09NFL935E-TIR50FL40-TL4IR-454R OR APPROVED EQUAL

LED 11.9W

(EST)

F

LED

WALL

SURFACE

LED

COFFEE BAR

COFFEE BAR PREP AREA

COFFEE BAR TOILET

G

LED, 2900 LUMENS MINIMUM, 2' X 2' RECESSED TROFFER, LINEAR LENS LIGHT GUIDE, CURVED REFLECTOR, LED

ELECTRONIC DIMMING DRIVER, 3500ºK, CRI ≥ 85, UNIVERSAL VOLTAGE

EATON COOPER LIGHTING, METALUX BRAND, SKYRIDGE SERIES, CAT.NO. 22SR-LD2-29-C-UNV-L835-CD1 OR APPROVED

EQUAL

LED COFFEE BAR TOILET

LED, 14" DIAMETER CIRCULAR FLUSH MOUNTED, 2300 LUMENS MINIMUM ELECTRONIC DRIVER, 3000ºK, CRI ≥ 90, 277 VOLT, DAMP LOCATION RATED

WAC LIGHTING, SLICE SERIES, CAT. NO.FM-4115F-30-BN OR APPROVED EQUAL

D LED UNDER DECK

SURFACE

DE

LED, 2700 LUMENS MINIMUM, REFLECTOR STRIPLIGHT, 4 FT, ELECTRONIC DIMMER DRIVER, 3500ºK, CRI ≥ 85, UNIVERSAL

VOLTAGE

EATON COOPER LIGHTING, METALUX BRAND, REFLECTOR LED STRIPLIGHT, CAT. NO. 4SLED-LD5-25SL-RW-UNV-L835-CD1 OR

APPROVED EQUAL

2 FEET LED VANITY WALL SCONCE, 1735 LUMENS, LED ELECTRONIC DRIVER, 3500ºK, CRI ≥ 90, UNIVERSAL VOLTAGE, DAMP LOCATION RATED

WAC LIGHTING, LEVEL SERIES, CAT. NO. WS-85624-AL OR APPROVED EQUAL

COFFEE BAR CORRIDOR ABOVE SKYLIGHT

LED, 2000 LUMENS MINIMUM, WALL BRACKET, 4 FT, ELECTRONIC DIMMING DRIVER, 3500ºK, CRI ≥ 85, UNIVERSAL VOLTAGE EATON COOPER LIGHTING, METALUX BRAND, CAT.NO. 4BCLED-LD4-20SL-F-UNV-L835-CD1 OR APPROVED EQUAL

LED WALL

SURFACE

COFFEE BAR SUPPLY ROOM

A

CEILING

SURFACE

G

H

CEILING

SURFACE

LED

J 23W

(EST)

LED

J

COFFEE BAR

WALL

SURFACE

LED COFFEE BAR OUTDOOR

B

LED, 900 LUMENS MINIMUM, 2" ROUND OPEN PINHOLE RECESSED DOWNLIGHT WITH 4" RECESSED LED MODULE, 40º FLOOD OPTIC, WHITE FLANGE, LED ELECTRONIC DRIVER, 3500ºK, CRI ≥ 90, UNIVERSAL VOLTAGE

EATON COOPER LIGHTING, HALO BRAND, CAT. NO. ML4D09NFL935E-TIR50FL40-TL4IR-454MW OR APPROVED EQUAL

11.9W

(EST)

COFFEE BAR 1

C

C

1. PROVIDE EL14W EMERGENCY

BATTERY PACK IN EMERGENCY

FIXTURE

D

D LED, 2700 LUMENS MINIMUM, REFLECTOR STRIPLIGHT, 4 FT, ELECTRONIC DIMMER DRIVER, 3500ºK, CRI ≥ 85, UNIVERSAL

VOLTAGE, EMERGENCY BATTERY PACK

EATON COOPER LIGHTING, METALUX BRAND, REFLECTOR LED STRIPLIGHT, CAT. NO. 4SLED-LD5-25SL-RW-UNV-L835-ELI4W-CD1

OR APPROVED EQUAL

19.3W

(EST)

23.4W

(EST)

MOUNT ±8" FROM EDGE OF

SKYLIGHT,ON UNDERSIDE OF

ABOVE DECK

LED UNDER DECK

SURFACE

COFFEE BAR CORRIDOR ABOVE SKYLIGHT

19.3W

(EST)

1. MOUNT LIGHT OVER CENTER OF

SKYLIGHT ON THE UNDERSIDE OF

ABOVE DECK

2. PROVIDE EMERGENCY

BATTERY PACK

E 20.5W

(EST)

F 25W

(EST)

22W

(EST)

MOUNT ±7-6" AFF

H LED, 2800 LUMENS MINIMUM, WRAP AROUND, 4 FT, ELECTRONIC DIMMING DRIVER, 3500ºK, CRI ≥ 85, UNIVERSAL VOLTAGE EATON COOPER LIGHTING, METALUX BRAND, CAT.NO. 4WSNLED-LD4-28SL-F-UNV-L835-CD1 OR APPROVED EQUAL 44W

(EST)

COFFEE BAR SUPPLY ROOM

LED, EMERGENCY LIGHT WITH NICKEL CADMIUM BATTERY, UL924 LISTED, DUAL VOLTAGE

EATON COOPER LIGHTING, CU2-LED SERIES, CU2-LED OR APPROVED EQUAL

1. CONTRACTOR IS TO FIELD

DETERMINE A SUITABLE

MOUNTING HEIGHT. COORDINATE

WITH VAMC

K

LED, 2,200LUMENS MINIMUM, QUARTER SPHERE, WALL MOUNTED, OUTDOOR LIGHT FIXTURE, TYPE 3 DISTRIBUTION, LED ELECTRONIC

DRIVER, 4000ºK, CRI ≥ 70, 277 VOLT

EATON COOPER LIGHTING, McGRAW-EDISON BRAND, CAT. NO. ISS-F01-LED-E1-BL3-BZ-P-TR-BBB-CWB-277 OR APPROVED EQUAL

K 26W

(EST)

1. PROVIDE PHOTOCELL

2. MOUNTED ±8'-0" AFF UNLESS

OTHERWISE NOTED

3. PROVIDE EMERGENCY

BATTERY PACK

4. PROVIDE TAMPER RESISTANT

HARDWARE

5. PROVIDE BACK BOX, AS

REQUIRED

L RED LED HIGH IMPACT ACRYLIC PANEL EDGE-LIT EXIT SIGN, 120/277V, WITH INTEGRAL SEALED MAINTENACE FREE BATTERY AND

SOLID STATE CHARGING SYSTEM

X DESIGNATES MOUNTING POSITION

E= END MOUNTED

T= TOP MOUNTED

B= BACK MOUNTED

ST= STEM MOUNTED

R= RECESSED

N DESIGNATES FACE ARRANGEMENT

1= SINGLE FACE

2= DOUBLE FACE

EATON, COOPER LIGHTING, SURE-LITE BRAND CAT. NO. EUS70R OR APPROVED EQUAL

LED

2 3

CEILING

RECESSED

WALL

SURFACE

CEILING

SURFACE

4.5W

(EST)

VARIOUS

C

XN

GENERAL NOTES

SHEET NOTES

1.

2.

3.

1 PROVIDE FIXTURE MOUNTING MATCHING CEILING TYPE.

REFER TO LIGHTING PLAN FOR SIGNAGE MOUNTING AND NUMBER

OF FACES.

FILL IN DIRECTION INDICATOR POINTING DIRECTION.

MOUNTED BOTTOM OF FIXTURE ±3" ABOVE MIRROR

WHERE CEILINGS ARE INSULATED, PROVIDE IC RATED LIGHTING

FIXTURE WHETHER OR NOT IC RATING IS CALLED OUT ON FIXTURE

SCHEDULE OR DRAWINGS. IC RATED FIXTURE TYPE AND

APPEARANCE SHALL MATCH NON-RATED FIXTURE TYPE AS SHOWN

ON FIXTURE SCHEDULE. SUBMIT NEW IC RATED FIXTURE TYPE TO

COTR OR VAMC REPRESENTATIVE FOR APPROVAL.

LED LAMP SHALL HAVE A MINIMUM COLOR TEMPERATURE OF 3500°K

AND CRI OF 85, UNLESS OTHERWISE NOTED.

PROVIDE T-BAR SAFETY EARTHQUAKE CLIP ON LIGHT FIXTURES.

WHEN AVAILABLE.

S T

A

T E

O F C A L I F OR N

I A

EXP.________

E 17641 9-30-2019

R E

G

IS

TE

RED

PROFESS IONAL

ENG

IN

E E

RA

U

G

UST I NE K . LEU

N G

E

L E C T R I C A

L

PROJECT

NORTH

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 o n e e ig h t in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h ts i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t o n e i n c h o n e f o o t

VA FORM 08-6231

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS:

Drawing Title: Project Title: Project Number:

Building Number:

Drawing Number:Location

Date Checked Drawn

Office of Construction and Facilities Management

Dwg. of

VA MARTINEZ CAMPUS , CA

19 & 20K. F. DAVIS ENGINEERING INC.

530 LA GONDA WAY, SUITE E

DANVILLE, CA 94526

WWW.KFDE.US

(925) 743-8884

KEY PLAN

A

BUILDING 19

BUILDING 20

02/25/2020

2/25/2020 9:54:18 AMC:\Users\ashrestha\Documents\CHRONIC DIALYSIS FINAL STAMPED SUBMITTAL - REV 2 - V2018_anil.shrestha9MD6R.rvt

CHRONIC DIALYSIS AND

SLEEP PROGRAM

I. VALDOV

EL610A

ELECTRICAL LIGHTING FIXTURE

SCHEDULE - ADDITION A

A. LEUNG

612-502

I. VALDOV

SYMBOL

FIXTURE

LAMP REMARKS

FIXTURE

MOUNTING

INPUT WATT W/

DRIVER LOCATION

FIXTURE

TYPE

FIXTURE

F

LED STAFF TOILET 1,2, TOILET 1,2,3,4, SLEEP ROOM 1,2,3,4

LED, 14" DIAMETER CIRCULAR FLUSH MOUNTED, 2300 LUMENS MINIMUM ELECTRONIC DRIVER, 3000ºK, CRI ≥ 90, UNIVERSAL VOLTAGE, DAMP LOCATION RATED

WAC LIGHTING, SLICE SERIES, CAT. NO.FM-4115F-30-BN OR APPROVED EQUAL

CEILING

SURFACE

WALL

SURFACE

LED

F 25W

(EST)

K LED, 2,200 LUMENS MINIMUM, QUARTER SPHERE, WALL MOUNTED, OUTDOOR LIGHT FIXTURE, TYPE 3 DISTRIBUTION, LED ELECTRONIC

DRIVER, 4000ºK, CRI ≥ 70, UNIVERSAL VOLTAGE

EATON COOPER LIGHTING, McGRAW-EDISON BRAND, CAT. NO. ISS-AF-350-LED-E1-SL3-BZ-P-TR OR APPROVED EQUAL

K 20.3W

(EST)

1. PROVIDE PHOTOCELL

2. MOUNTED ±1'-0" ABOVE DOOR

UNLESS OTHERWISE NOTED

3. PROVIDE TAMPER RESISTANT

HARDWARE

4. PROVIDE BACK BOX, AS

REQUIRED

L

RED LED HIGH IMPACT ACRYLIC PANEL EDGE-LIT EXIT SIGN, 120/277V / AC ONLY.

X DESIGNATES MOUNTING POSITION

E= END MOUNTED

T= TOP MOUNTED

B= BACK MOUNTED

ST= STEM MOUNTED

R= RECESSED

N DESIGNATES FACE ARRANGEMENT

1= SINGLE FACE

2= DOUBLE FACE

EATON, COOPER LIGHTING, SURE-LITE BRAND CAT. NO. EUS60R OR APPROVED EQUAL

LED 2 3

B1 LED, 2900 LUMENS MINIMUM, 2'-0" x 2'-0" RECESSED TROFFER, LINEAR LENS LIGHT GUIDE, CURVED REFLECTOR, LED ELECTRONICS

DIMMING DRIVER, 3500°K, CRI ≥ 85, UNIVERSAL VOLTAGE.

EATON'S COOPER LIGHTING, METALUX BRAND, SKYRIDGE SERIES, CAT. NO. 22SR-LD2-29-C-UNV-L835-CD1, OR APPROVED EQUAL.

LED 23.4 W

(EST.)

B1

CEILING

RECESSED

C1 LED, 3400 LUMENS MINIMUM, 2'-0" x 4'-0" RECESSED TROFFER, LINEAR LENS LIGHT GUIDE, CURVED REFLECTOR, LED ELECTRONICS

DIMMING DRIVER, 3500°K, CRI ≥ 85, UNIVERSAL VOLTAGE.

EATON'S COOPER LIGHTING, METALUX BRAND, SKYRIDGE SERIES, CAT. NO. 24SR-LD2-34-C-UNV-L835-CD1, OR APPROVED EQUAL.

LED 27.2 W

(EST.)

C1

CEILING

RECESSED

E1 LED, 6400 LUMENS MINIMUM, 2'-0" x 4'-0" RECESSED TROFFER, LINEAR LENS LIGHT GUIDE, CURVED REFLECTOR, LED ELECTRONICS

DIMMING DRIVER, 3500°K, CRI ≥ 85, UNIVERSAL VOLTAGE.

EATON'S COOPER LIGHTING, METALUX BRAND, SKYRIDGE SERIES, CAT. NO. 24SR-LD2-64-C-UNV-L835-CD1, OR APPROVED EQUAL.

LED 55.5 W

(EST.)

E1 CEILING

RECESSED

E2 LED, 6400 LUMENS MINIMUM, 2'-0" x 4'-0" RECESSED TROFFER, LINEAR LENS LIGHT GUIDE, CURVED REFLECTOR, LED ELECTRONICS DIMMING DRIVER, 3500°K, CRI ≥ 85, UNIVERSAL VOLTAGE. INTERATED DIMMING DAYLIGHT HARVESTING SENSOR.

EATON'S COOPER LIGHTING, METALUX BRAND, SKYRIDGE SERIES, CAT. NO. 24SR-LD2-64-C-UNV-L835-CD1,SVD1, OR APPROVED EQUAL.

LED 55.5 W

(EST.)

E2

CEILING

RECESSED

D1

LED, 4800 LUMENS MINIMUM, 2'-0" x 4'-0" RECESSED TROFFER, LINEAR LENS LIGHT GUIDE, CURVED REFLECTOR, LED ELECTRONICS

DIMMING DRIVER, 3500°K, CRI ≥ 85, UNIVERSAL VOLTAGE.

EATON'S COOPER LIGHTING, METALUX BRAND, SKYRIDGE SERIES, CAT. NO. 24SR-LD2-48-C-UNV-L835-CD1, OR APPROVED EQUAL.

LED 38.2 W

(EST.)D1

CEILING

RECESSED

D2 LED, 4800 LUMENS MINIMUM, 2'-0" x 4'-0" RECESSED TROFFER, LINEAR LENS LIGHT GUIDE, CURVED REFLECTOR, LED ELECTRONICS DIMMING DRIVER, 3500°K, CRI ≥ 85, UNIVERSAL VOLTAGE. INTERATED DIMMING DAYLIGHT HARVESTING SENSOR.

EATON'S COOPER LIGHTING, METALUX BRAND, SKYRIDGE SERIES, CAT. NO. 24SR-LD2-48-C-UNV-L835-CD1,SVD1, OR APPROVED EQUAL.

LED 38.2 W

(EST.)

CEILING

RECESSED

NEPHROLOGIST, SUPV

CHIEF, TELECOM, SUPV

CONFERENCE, SLEEP ROOMS 1,2,3,4

CONFERENCE, DIALYSIS EQUIPMENT, STERILE EQUIPMENT,

CONTROL ROOM, CONSULT, OFFICE SUPPLY, OPEN OFFICE

CORRIDOR 1

CORRIDORS 2,3,4

D LED UNDER DECK

SURFACE

LED, 2700 LUMENS MINIMUM, REFLECTOR STRIPLIGHT, 4 FT, ELECTRONIC DIMMER DRIVER, 3500ºK, CRI ≥ 85, UNIVERSAL

VOLTAGE

EATON COOPER LIGHTING, METALUX BRAND, REFLECTOR LED STRIPLIGHT, CAT. NO. 4SLED-LD5-25SL-RW-UNV-L835-CD1 OR

APPROVED EQUAL

EXTERNAL ELECTRICAL ROOM

19.3W

(EST)

STAFF TOILET 1,2

E WALL

SURFACE

LED2 FEET LED VANITY WALL SCONCE, 1735 LUMENS, LED ELECTRONIC DRIVER, 3500ºK, CRI ≥ 90, UNIVERSAL VOLTAGE, DAMP LOCATION RATED

WAC LIGHTING, LEVEL SERIES, CAT. NO. WS-85624-AL OR APPROVED EQUAL

E 20.5W

(EST)

D

D

D2

B1

C1

D1

D2

E2

F

XN

GENERAL NOTES

SHEET NOTES

1.

2.

3.

1 NO BATTERY BACKUP.

REFER TO LIGHTING PLAN FOR SIGNAGE MOUNTING AND NUMBER

OF FACES.

FILL IN DIRECTION INDICATOR POINTING DIRECTION.

MOUNTED BOTTOM OF FIXTURE ±3" ABOVE MIRROR

WHERE CEILINGS ARE INSULATED, PROVIDE IC RATED LIGHTING

FIXTURE WHETHER OR NOT IC RATING IS CALLED OUT ON FIXTURE

SCHEDULE OR DRAWINGS. IC RATED FIXTURE TYPE AND

APPEARANCE SHALL MATCH NON-RATED FIXTURE TYPE AS SHOWN

ON FIXTURE SCHEDULE. SUBMIT NEW IC RATED FIXTURE TYPE TO

COTR OR VAMC REPRESENTATIVE FOR APPROVAL.

LED LAMP SHALL HAVE A MINIMUM COLOR TEMPERATURE OF 3500°K

AND CRI OF 85, UNLESS OTHERWISE NOTED.

PROVIDE T-BAR SAFETY EARTHQUAKE CLIP ON LIGHT FIXTURES.

WHEN AVAILABLE.

S T A T E

O F C A L I F OR N

I A

EXP.________

E 17641 9-30-2019

RE

G

IS

TE

RED PROFESS IONAL

ENG

INEERA

UG

UST I NE K . LEUNG

E

L E C T R I C A L

PROJECT

NORTH

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 on e ei gh t i nc h on e fo ot on e qu ar te r i nc h on e fo ot th re e ei gh ts in ch o ne fo ot on e ha lf in ch o ne fo ot th re e qu ar te rs in ch o ne fo ot on e in ch o ne fo ot on e an d on e ha lf in ch o ne fo ot on e in ch o ne fo ot

VA FORM 08-6231

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Drawing Title: Project Title: Project Number:

Building Number:

Drawing Number:Location

Date Checked Drawn

Office of Construction and Facilities Management

Dwg. of

VA MARTINEZ CAMPUS , CA

19 & 20K. F. DAVIS ENGINEERING INC.

530 LA GONDA WAY, SUITE E

DANVILLE, CA 94526

WWW.KFDE.US

(925) 743-8884

KEY PLAN

B

BUILDING 19

BUILDING 20

02/25/2020

2/25/2020 8:09:26 AMC:\Users\ashrestha\Documents\CHRONIC DIALYSIS FINAL STAMPED SUBMITTAL - REV 2 - V2018_anil.shrestha9MD6R.rvt

CHRONIC DIALYSIS AND

SLEEP PROGRAM

L. HARRIS

EL610B

ELECTRICAL LIGHTING FIXTURE

SCHEDULE - ADDITION B

A. LEUNG

612-502

L. HARRIS

SYMBOL

FIXTURE

LAMP REMARKS

FIXTURE

MOUNTING

INPUT WATT W/

DRIVER LOCATION

FIXTURE

TYPE

FIXTURE

A CEILING

SURFACE

LED, 900 LUMENS MINIMUM, 2" ROUND PINHOLE SURFACE MOUNTED DOWNLIGHT WITH 4" LED MODULE, 40º FLOOD OPTIC, WHITE

HOUSING LED ELECTRONIC DRIVER, 3500ºK, CRI ≥ 90, UNIVERSAL VOLTAGE

EATON COOPER LIGHTING, HALO BRAND, CAT. NO. ML4D09NFL935E-TIR50FL40-TL4IR-454R OR APPROVED EQUAL

LED 11.9W

(EST)A

B LEDB

LED, 900 LUMENS MINIMUM, 2" ROUND OPEN PINHOLE RECESSED DOWNLIGHT WITH 4" RECESSED LED MODULE, 40º FLOOD OPTIC, WHITE FLANGE, LED ELECTRONIC DRIVER, 3500ºK, CRI ≥ 90, UNIVERSAL VOLTAGE

EATON COOPER LIGHTING, HALO BRAND, CAT. NO. ML4D09NFL935E-TIR50FL40-TL4IR-454MW OR APPROVED EQUAL

11.9W

(EST)

CEILING

RECESSE

D

B1 LED, 2900 LUMENS MINIMUM, 2'-0" x 2'-0" RECESSED TROFFER, LINEAR LENS LIGHT GUIDE, CURVED REFLECTOR, LED ELECTRONICS

DIMMING DRIVER, 3500°K, CRI ≥ 85, UNIVERSAL VOLTAGE.

EATON'S COOPER LIGHTING, METALUX BRAND, SKYRIDGE SERIES, CAT. NO. 22SR-LD2-29-C-UNV-L835-CD1, OR APPROVED EQUAL.

LED 23.4 W

(EST.) CEILING

RECESSED

D LED UNDER DECK

SURFACE

LED, 2700 LUMENS MINIMUM, REFLECTOR STRIPLIGHT, 4 FT, ELECTRONIC DIMMER DRIVER, 3500ºK, CRI ≥ 85, UNIVERSAL VOLTAGE EATON COOPER LIGHTING, METALUX BRAND, REFLECTOR LED STRIPLIGHT, CAT. NO. 4SLED-LD5-25SL-RW-UNV-L835-

CD1 OR APPROVED EQUAL

19.3W

(EST)

KITCHEN SERVING, BEVERAGE BAR, DINING

RETAIL

DINING

PREP AND PACKAGING

CONFERENCE, KITCHEN

B1

L

RED LED HIGH IMPACT ACRYLIC PANEL EDGE-LIT EXIT SIGN, 120/277V AC ONLY

X DESIGNATES MOUNTING POSITION

E= END MOUNTED

T= TOP MOUNTED

B= BACK MOUNTED

ST= STEM MOUNTED

R= RECESSED

N DESIGNATES FACE ARRANGEMENT

1= SINGLE FACE

2= DOUBLE FACE

EATON, COOPER LIGHTING, SURE-LITE BRAND CAT. NO. EUS60R OR APPROVED EQUAL

LED 2 3

D1

LED, 4800 LUMENS MINIMUM, 2'-0" x 4'-0" RECESSED TROFFER, LINEAR LENS LIGHT GUIDE, CURVED REFLECTOR, LED ELECTRONICS

DIMMING DRIVER, 3500°K, CRI ≥ 85, UNIVERSAL VOLTAGE.

EATON'S COOPER LIGHTING, METALUX BRAND, SKYRIDGE SERIES, CAT. NO. 24SR-LD2-48-C-UNV-L835-CD1, OR APPROVED EQUAL.

LED 38.2 W

(EST.)

D1 CEILING

RECESSED

D2 LED, 4800 LUMENS MINIMUM, 2'-0" x 4'-0" RECESSED TROFFER, LINEAR LENS LIGHT GUIDE, CURVED REFLECTOR, LED ELECTRONICS DIMMING DRIVER, 3500°K, CRI ≥ 85, UNIVERSAL VOLTAGE. INTERATED DIMMING DAYLIGHT HARVESTING SENSOR.

EATON'S COOPER LIGHTING, METALUX BRAND, SKYRIDGE SERIES, CAT. NO. 24SR-LD2-48-C-UNV-L835-CD1,SVD1, OR APPROVED EQUAL.

LED 38.2 W

(EST.)D2 CEILING

RECESSED

I1

CEILING

SURFACE

LEDI1 LED, 2000 LUMENS MINIMUM, 4'X2 3/8", SURFACE MOUNTED, SUPPORT BY STRUCTURE ABOVE CEILING, LED ELECTRONICS DIMMING DRIVER, 3500°K, CRI>, 90, UNIVRSAL VOLTAGE. 33W

(EST)

I2

CEILING

SURFACE

LED

I2

21W

(EST)

LUMENWERX, VIA2PD, LED BRAND, VIA2PD-HLO-LED-90-500-35-4FT-UNV-DI1-B OR APPROVED EQUAL

LED, 1500 LUMENS MINIMUN, TRACK LIGHT, SURFACE MOUNTED, SUPPORT TRACK BY STRUCTURE ABOVE CEILING & ATTACH TO CEILING, FIXTURE EXTENDS NO MORE THAN 9" BELOW TRACK, APPROX 4" DIAMETER, 3500°K, CRI >, 90, 277V, NON-DIMMING.

AMERLUX, SPEQ-M MEDIUM CYLINDER TRACK HEAD, SPEQ-M-A17-21-BT277-359-ND OR APPROVED EQUAL

PREP AND PACKAGING, VAULT, BREAKROOM,

CONSULT

PREP AND PACKAGING, VAULT, BREAKROOM,

CONSULT

RETAIL

RETAIL

D

D

D1

D2

I1

XN

GENERAL NOTES

SHEET NOTES

1.

2.

3.

1 PROVIDE FIXTURE MOUNTING MATCHING CEILING TYPE.

REFER TO LIGHTING PLAN FOR SIGNAGE MOUNTING AND NUMBER

OF FACES.

FILL IN DIRECTION INDICATOR POINTING DIRECTION.

NO BATTERY BACK UP.

PROVIDE 277V GLOBAL POWER TRACK. BLACK IN COLOR.

WHERE CEILINGS ARE INSULATED, PROVIDE IC RATED LIGHTING

FIXTURE WHETHER OR NOT IC RATING IS CALLED OUT ON FIXTURE

SCHEDULE OR DRAWINGS. IC RATED FIXTURE TYPE AND

APPEARANCE SHALL MATCH NON-RATED FIXTURE TYPE AS SHOWN

ON FIXTURE SCHEDULE. SUBMIT NEW IC RATED FIXTURE TYPE TO

COTR OR VAMC REPRESENTATIVE FOR APPROVAL.

LED LAMP SHALL HAVE A MINIMUM COLOR TEMPERATURE OF 3500°K

AND CRI OF 85, UNLESS OTHERWISE NOTED.

PROVIDE T-BAR SAFETY EARTHQUAKE CLIP ON LIGHT FIXTURES.

WHEN AVAILABLE.

S T A T E

O F C A L I F OR N

I A

EXP.________

E 17641 9-30-2019

RE

G

IS

TE

RED PROFESS IONAL

ENG

INEERA

UG

UST I NE K . LEUNG

E

L E C T R I C A L

PROJECT

NORTH

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 on e ei gh t i nc h on e fo ot on e qu ar te r i nc h on e fo ot th re e ei gh ts in ch o ne fo ot on e ha lf in ch o ne fo ot th re e qu ar te rs in ch o ne fo ot on e in ch o ne fo ot on e an d on e ha lf in ch o ne fo ot on e in ch o ne fo ot

VA FORM 08-6231

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Drawing Title: Project Title: Project Number:

Building Number:

Drawing Number:Location

Date Checked Drawn

Office of Construction and Facilities Management

Dwg. of

VA MARTINEZ CAMPUS , CA

19 & 20K. F. DAVIS ENGINEERING INC.

530 LA GONDA WAY, SUITE E

DANVILLE, CA 94526

WWW.KFDE.US

(925) 743-8884

KEY PLAN

C BUILDING 19

BUILDING 20

02/25/2020

2/25/2020 8:09:28 AMC:\Users\ashrestha\Documents\CHRONIC DIALYSIS FINAL STAMPED SUBMITTAL - REV 2 - V2018_anil.shrestha9MD6R.rvt

CHRONIC DIALYSIS AND

SLEEP PROGRAM

I. VALDOV

EL610C

ELECTRICAL LIGHTING FIXTURE

SCHEDULE - RENOVATION C

A. LEUNG

612-502

I. VALDOV

.C

F .E

.C

C

GCG

CG

CG

CG

CG

T

GFCI

GFCI

GFCI

G

FC

I G

FC

I

JK

12.9

HL

TOILET 1

19A101 TOILET 2

19A102

SUPPLY

19A100B

PREP

19A100ASEATING

19A100

CORRIDOR

C19A

WP

SP

-H-H

-A

C

25 25

25 25

GFCI

GFCI

A

A2,4 2

A -

A

PNL LBD1,

CKT 1,3,5

PNL LBD1,

CKT 2,4

2 #12 & 1 #12

GND, 3/4"C

PNL LBD1,

CKT 21,25,31

21 31TV

SP-C

-C

-B 23

-B

PNL LBD1, CKT 23

2 #12 & 1 #12 GND

3/4"C

-A

GFCI

11 3

PNL LBD1, CKT 11,37

4 #10 & 1 #10 GND,

3/4"C

PNL LBD1, CKT 18

2 #12 & 1 #12

GND, 3/4"C

GFCI

-A

PNL LBD1,

CKT 15,17,19

PNL LBD1, CKT 8,13

4 #10 & 1 #10 GND,

3/4"C

9GFCI

-A

7GFCI

-A

13GFCI

19GFCI

-A

GFCI

-A

PNL LBD1, CKT 6,7,9

-A

10,12

PNL LBD1, CKT 10,12

2 #8 & 1 #10 GND,

3/4"C

GFCI

-A

17GFCI

-A

GENERAL NOTES

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

FOR SIMPLICITY AND CLARITY BRANCH FEEDER CONDUIT AND

WIRES IS NOT SHOWN ON THE DRAWING. ONLY CIRCUIT NUMBER

TO THE EQUIPMENT AND HOMERUNS ARE SHOWN. CONTRACTOR

SHALL PROVIDE AND INSTALL BRANCH FEEDER CONDUITS,

OUTLET BOXES, WIRE AND JUNCTION BOXES FOR NEW WIRING

INSTALLATION. ALL HOMERUN CIRCUITS ARE 6#10 AND 1#10 GND

(GRN) IN A 3/4" CONDUIT, UNLESS OTHERWISE NOTED.

ALL CONDUITS SHALL BE CONCEALED. CONDUITS SHALL RUN

ABOVE THE CEILING OR WITHIN FINISHED WALLS.

TELECOMMUNICATION OUTLET AND POWER RECEPTACLE SHALL

BE A MINIMUM OF 6" APART.

PROVIDE CAT 6 TELECOMMUNICATION RECEPTACLE (DATA

OUTLETS), WIRES, J.B. (4"x4" BOX) COVER PLATE, 1" CONDUIT

WITH BUSHINGS. CONDUIT SHALL BE TERMINATED 6" ABOVE

CEILING.

CONTRACTOR SHALL PROVIDE A COMPLETE FULLY OPERATIONAL

AND CERTIFIED TELECOMMUNICATION SYSTEM AT THE MINIMUM

MEETING INDUSTRY STANDARD ANSI/TIA/EIA-S-68,B,2 AND ANSI /

TIA-568,C FOR CATEGORY 6 CABLING SYSTEM. THE SYSTEM SHALL

BE CABLE TO CO-EXIT WITH THE EXISTING VAMC

TELECOMMUNICATION SYSTEM.

PROVIDE CONDUIT AND WIRING…