This solicitation is for a construction project to construct an infill of Building 26 for dental clinics, a new police office, and renovate specialty care services at the Wichita VA Medical Center in Wichita, Kansas. The solicitation seeks to construct an infill space for dental clinics, a new police office, and renovate existing space for specialty care services including gastrointestinal, rheumatology, and neurology clinics. The work includes construction drawings, fire protection, fire alarms, and fire suppression. The period of performance is 720 calendar days. The Department of Veterans Affairs Technology Acquisition Center Austin issued the solicitation.
View the file
Other files
Show all 30
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GENERAL:
1. THE CONTRACTOR SHALL CAREFULLY REVIEW ALL APPLICABLE DESIGN CRITERIA,
THESE DRAWINGS, AND THE PROJECT SPECIFICATIONS FOR IMPORTANT
QUALIFICATION, DEFINITION, SUBMITTAL, PRODUCT, INSTALLATION, AND TESTING
REQUIREMENTS.
2. ALL SUBMITTALS, INSTALLATION, AND TESTING SHALL BE COMPLETED IN A NEAT,
WORKMAN-LIKE MANNER.
3. PRODUCT, DESIGN, INSTALLATION, AND TESTING ALTERNATE APPROACHES AND/OR
SUBSTITUTIONS WILL BE CONSIDERED BY THE ENGINEER IF THE CONTRACTOR
PROVIDES WRITTEN, WELL-DOCUMENTED, ENGINEERING-BASED SUBSTANTIATION
FOR PROPOSED ALTERNATIVE.
4. BEFORE WORK BEGINS, THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE
AVAILABLE CAPACITY OF THE EXISTING FIRE ALARM PANEL. IF AVAILABLE CAPACITY
IS NOT ADEQUATE FOR THE EXPECTED NEW NOTIFICATION APPLIANCES AND
INITIATING DEVICES THE CONTRACTOR SHALL ALERT THE COR FOR FURTHER
DIRECTION.
APPLICABLE CODES AND STANDARDS:
1. VA FIRE PROTECTION DESIGN MANUAL EIGHTH EDITION - JUNE 2021
2. NFPA 70 NATIONAL ELECTRIC CODE (2020)
3. NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE (2022)
4. NFPA 101 (2021)
5. INTERNATIONAL BUILDING CODE (2021)
AUDIBILITY DESIGN:
1. BECAUSE OF UNPREDICTABLE BACKGROUND NOISES AND PROJECT CONDITIONS,
THE AUDIBILITY DESIGN GOALS SHALL BE CONFIRMED BY MEASUREMENT WITH
CALIBRATED TEST EQUIPMENT. IF RESULTS INDICATE THAT ADDITIONAL
NOTIFICATION APPLIANCES ARE REQUIRED, THE CONTRACTOR SHALL ADD THEM AT
NO ADDITIONAL COST.
2. SPEAKERS MAY BE FIELD-LOCATED WITHIN 6 FT OF THE LOCATION INDICATED ON THE
APPROVED DESIGN WITHOUT CONSULTING THE ENGINEER.
3. DENTAL TREATMENT ROOMS WILL BE DESIGNED AROUND PRIVATE MODE
NOTIFICATION IN ACCORDANCE WITH NFPA 72. PRIVATE-MODE SIGNALING WILL BE
PROVIDED TO NURSE STATIONS TO ENSURE EMERGENCY ACTION IS CONDUCTED IN
THE EVENT OF A FIRE ALARM.
VISUAL NOTIFICATION DESIGN:
1. CLEAR STROBES SHALL BE PROVIDED WHERE INDICATED ON THE APPROVED
DESIGN.
2. STROBES MAY BE FIELD-LOCATED WITHIN 3 FT OF THE LOCATION INDICATED ON THE
APPROVED DESIGN WITHOUT CONSULTING THE ENGINEER. CONSULT WITH
ENGINEER PRIOR TO RELOCATING STROBES MORE THAN 3 FT.
INITIATING DEVICES:
1. INITIATING DEVICES MAY BE FIELD-LOCATED WITHIN 3 FT OF THE LOCATION
INDICATED ON THE APPROVED DESIGN WITHOUT CONSULTING THE ENGINEER.
CONSULT WITH ENGINEER PRIOR TO RELOCATING INITIATING DEVICES MORE THAN 3
FT.
CIRCUITS AND CONDUIT:
1. ALL CIRCUITS SHALL BE PROVIDED IN CONDUIT IN ACCORDANCE WITH NFPA 70 AND
THE CONDUIT LISTING.
2. NEW SIGNALING LINE CIRCUITS AND NOTIFICATION APPLIANCE CIRCUITS SHALL BE
ARRANGED SO THAT A SINGLE FAULT DOES NOT CAUSE THE LOSS OF ADDRESSABLE
DEVICES ON MORE THAN ONE SMOKE COMPARTMENT.
3. WIRING SHALL BE INSTALLED IN METAL RACEWAY. PER VA DESIGN MANUAL THIS IN
COMBINATION WITH BUILDINGS PROTECTED THROUGHOUT BY SPRINKLERS SHALL BE
CONSIDERED TO MEET THE REQUIREMENTS FOR PATHWAY SURVIVABILITY LEVEL 2 IN
ACCORDANCE WITH NFPA 72 AND VA AUTHORITY HAVING JURISDICTION.
4. SPEAKERS AND STROBES SHALL BE ARRANGED TO OPERATE ON SEPARATE
CIRCUITS.
INSTALLATION:
1. ALL EQUIPMENT SHALL BE INSTALLED TIGHT TO THE BUILDING STRUCTURE AND
SHALL BE INSTALLED PARALLEL OR PERPENDICULAR TO THE BUILDING STRUCTURE
UNLESS NOTED OTHERWISE.
2. THE CONTRACTOR SHALL NOT APPRECIABLY DEVIATE FROM THE APPROVED DESIGN
WITHOUT WRITTEN APPROVAL FROM THE ENGINEER.
TESTING:
1. UNLESS SPECIFICALLY NOTED OTHERWISE, THE CONTRACTOR SHALL PERFORM ALL
ACCEPTANCE TESTING IN ACCORDANCE WITH THE APPLICABLE DESIGN CRITERIA
AND THE EQUIPMENT MANUFACTURER'S INSTRUCTIONS.
2. UNLESS SPECIFICALLY NOTED OTHERWISE, THE CONTRACTOR SHALL PERFORM
TESTING AND PROVIDE DOCUMENTATION PRIOR TO REQUESTING ENGINEER'S
PRESENCE TO WITNESS TESTING.
FIRE ALARM GENERAL NOTES
FACU
SPD
GROUND FLOOR
NOTES:
1. TO DEDICATED 120VAC BRANCH CIRCUIT
2. EXISTING FIRE ALARM CONTROL PANEL. THE AVAILABLE CAPACITY IS ASSUMED TO BE ADEQUATE FOR
THE PROPOSED NEW WORK, CONTRACTOR IS RESPONSIBLE FOR DETERMINING ACTUAL AVAILABLE
CAPACITY.
3. THIS RISER DIAGRAM IS INTENDED ONLY TO CAPTURE THE SYSTEM DESIGN INTENT, PANEL CONNECTIONS, AND GENERAL CIRCUIT ROUTING REQUIREMENTS. EXACT QUANTITIES AND TYPES OF DEVICES NECESSARY TO ACCOMPLISH THE DESIGN GOALS ARE NOT INDICATED. THE INTENT OF THIS
RISER DIAGRAM IS TO INDICATE THE GENERAL SYSTEM CONFIGURATION AFTER SUCCESSFUL
COMPLETION OF THE PROJECT.
FIRST FLOOR
SS
WF VS
AIM AIMs F s
SS
AOM AOM AOM
FES
A L A
R M
T R
O U
B L E
S U
P E
R V
IS
O
R Y
SECOND FLOOR PENTHOUSE
SECOND FLOOR ROOF
s s
-A
H U
-5 A
-A
H U
-5 B s
-A
H U
-5 C
AOM
AHU
AOM
AHU
AOM
AHU
FACU
F
WF
FIRE ALARM CONTROL UNIT
FIRE ALARM LEGEND
SPD SURGE PROTECTIVE DEVICE
FIRE ALARM PULL STATION
AIM ADDRESSABLE INPUT MODULE
AOM ADDRESSABLE OUTPUT MODULE
WATERFLOW SWITCH
VS VALVE SUPERVISORY SWITCH
s SMOKE DETECTOR - SPOT TYPE
S SPEAKER
SPEAKER STROBE
STROBE - WALL MOUNT
STROBE - CEILING MOUNT
SYMBOL MODIFIERS
C ncd nW
WP
CEILING MOUNTED
CANDELA RATING
WATT TAP
WEATHER PROOF
AHU AIR HANDLING UNIT CONTROLLER
FES KITCHEN HOOD SYSTEM
s SMOKE DETECTOR - DUCT TYPE
4 WATERFLOW/PRESSURE SWITCH X X X X X X 4
5 CONTROL VALVE SUPERVISORY SWITCH X X X X 5
14 ANY OTHER SYSTEM TROUBLE X X X X 14
SUPERVISORY CONDITIONS A B C D E F G H I K L
A B C D E F G H I K L
X PERFORM OPERATION/REPORT DEVICE STATUS
6 SMOKE DETECTOR - DUCT TYPE X X X X 6
7 KITCHEN HOOD SUPPRESSION SYSTEM COMMON SUPERVISORY X X X X 7
SYSTEM OUTPUTS
SYSTEM INPUTS
F A
C U
A N
N U
N C
IA
T
IO
N
A C
T
IV
A T
E C
O M
M O
N A
L A
R M
S
IG
N A
L I
N D
IC
A
T O
R
A C
T
IV
A T
E A
U D
IB
L E
A L A
R M
S
IG
N A
L
A C
T
IV
A T
E C
O M
M O
N S
U P
E R
V
IS
O R
Y S
IG
N
A L I
N D
IC
A
T O
R
A C
T
IV
A T
E A
U D
IB
L E
S U
P E
R V
IS
O
R Y
S
IG
N A
L
A C
T
IV
A T
E C
O M
M O
N T
R O
U B
L E
S
IG
N A
L I
N D
IC
A
T O
R
A C
T
IV
A T
E A
U D
IB
L E
T R
O U
B L E
S
IG
N A
L
D
IS
P L A
Y /P
R
IN
T C
H A
N G
E O
F S
T A
T U
S
N O
T
IF
IC
A
T
IO
N
A C
T
IV
A T
E T
E M
P O
R A
L
A L E
R T
T O
N E
A N
D P
R E
-R E
C O
R D
E D
F
IR
E
E V
A C
U A
T
IO
N M
E S
S A
G E
T H
R O
U G
H O
U T
B U
IL
D
IN
G
A C
T
IV
A T
E S
T R
O B
E S
T H
R O
U G
H O
U T
B U
IL
D
IN
G
T R
A N
S M
IT
S
IG
N
A L T
O S
U P
E R
V
IS
IN
G
S T
A T
IO
N
A U
X
IL
IA
R
Y F
U N
C T
IO
N
S
S H
U T
D O
W N
A S
S O
C
IA
T E
D A
IR
H
A N
D L
IN
G U
N
IT
ALARM CONDITIONS A B C D E F G H I K L
1 MANUAL ALARM PULL STATION X X X X X X 1
2 SMOKE DETECTOR - SPOT TYPE X X X X X X 2
TROUBLE CONDITIONS A B C D E F G H I K L
8 AC POWER FAILURE X X X X 8
9 LOW BATTERY X X X X 9
10 OPEN CIRCUIT X X X X 10
11 GROUND FAULT X X X X 11
12 NOTIFICATION APPLIANCE CIRCUIT SHORT X X X X 12
13 REMOTE POWER SUPPLY COMMON TROUBLE X X X X 13
NOTE: THIS MATRIX PERTAINS TO SCOPE OF WORK AREA. ALL
EXISTING PROGRAMMING FOR BUILDING NOT TO BE MODIFIED
UNLESS REQUIRED BY SOW FOR THIS PROJECT.
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
KS ARCH REG. NO. A-930, EXP. 12/31/2023
KS ENGR REG. NO. E-2586, EXP. 12/31/2023
STRUCTURAL / CIVIL ENGINEER
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB / TECH ENGR
SPUR DESIGN
25219 MADISON AVENUE, SUITE 100
KANSAS CITY, MO 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT HEALTH & SAFETY
1139 OLIVE STREET,
ST. LOUIS, MO 63101
(314) 436-9492
HEALTHCARE PLANNER
INNOVA GROUP
3196 N. SWAN ROAD
TUCSON, AZ 85712
(520) 886-8650
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH ROAD, STE 1415
PANAMA CITY, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:SPUR #: 2016
/1
/2
:2 :5
P
M
FA001
FIRE ALARM GENERAL NOTES, LEGEND,
AND RISER DIAGRAM
SAB
88 OF 190BLS
100% BID SET
CONSTRUCT INFILL OF
BUILDING 26 AND RENOVATE
SPECIALTY CARE CLINICS
12/21/2022
589-704
5500 EAST KELLOGG AVENUE
WICHITA, KANSAS 67218
NOT TO SCALE
FIRE ALARM RISER DIAGRAM2
NOT TO SCALE
FACU INPUT/OUTPUT MATRIX1
NO. REVISION DESCRIPTION DATE
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
KEY PLAN
BLDG 26
BLDG 3 BLDG 1
BLDG 2BLDG 19
BLDG 61
BLDG 62
BLDG 29
N
A B C D E F G H J K L M
DINING AREA
VENDOR
DINING AREA
037A
RETAIL STORE
RETAIL
STORAGE
CORRIDOR
KITCHEN
041A
DISH WASH
041A
SERVING LINE
037B
SAFE
038C
VCS CHIEF
OFFICE
038B
VCS OFFICE
038A
COOLER
044A
FREEZER
044B
FOOD STG
FOOD STG
WORKSTATIONS
GUEST
SERVICES
IT ROOM
HAC
ELEC
STORAGE
DENTAL
MECH
045 042
CLEAN
SUPPLY
SOILED
UTILITY
044 043
TRAY
STORAGE
STERILE
INSTRUMENTS
041 038
MOBILE
EQUIPMENT
MED
040 039
PAT TLT
X-RAY
STF TLT
WAITING
034A
CHECK-IN
KIOSK
034A 034B
WC ALC.
034B
C3
CORRIDOR
C3 035A
RECEPTION
035A
035F
COPY /
SUPPLY
035F
035B
CHIEF
035B
WORKSTATIONS
DTR-8
059058
DTR-7
058057
DTR-6
057056
DTR-5
056055
DTR-4
055054
DTR-3
054053
DTR-2
053052
DTR-1
LAB
A008
CAD/CAM
CART
A008 A007
EQUIP
A007 A006
LIFT
A006 A005
EQUIP
A005 A004
WC
A004 A003
EQUIP
A003 A002
EQUIP
A002 A001
CRASH
CART
A001
035D
LOUNGE
035D
035E
DRESSING
035E
035C
LOCKER
035C
SECURITY
REQUIRED AUDIBILITY LEGEND
54dB AMBIENT SPL 69dB EXPECTED SPL
60dB AMBIENT SPL 75dB EXPECTED SPL
30dB AMBIENT SPL 45dB EXPECTED SPL
(STORAGE OCCUPANCIES)
(BUSINESS OCCUPANCIES)
(ASSEMBLY OCCUPANCIES)
OUT OF SCOPE AREA
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
KS ARCH REG. NO. A-930, EXP. 12/31/2023
KS ENGR REG. NO. E-2586, EXP. 12/31/2023
STRUCTURAL / CIVIL ENGINEER
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB / TECH ENGR
SPUR DESIGN
25219 MADISON AVENUE, SUITE 100
KANSAS CITY, MO 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT HEALTH & SAFETY
1139 OLIVE STREET,
ST. LOUIS, MO 63101
(314) 436-9492
HEALTHCARE PLANNER
INNOVA GROUP
3196 N. SWAN ROAD
TUCSON, AZ 85712
(520) 886-8650
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH ROAD, STE 1415
PANAMA CITY, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:SPUR #: 2016
/1
/2
:2 :0
P
M
FA101
FIRE ALARM AUDIBILITY PLAN -
GROUND FLOOR
SAB
89 OF 190BLS
100% BID SET
CONSTRUCT INFILL OF
BUILDING 26 AND RENOVATE
SPECIALTY CARE CLINICS
12/21/2022
589-704
5500 EAST KELLOGG AVENUE
WICHITA, KANSAS 67218
N
1/8" = 1'-0"
FIRE ALARM AUDIBILITY PLAN - GROUND FLOOR1
NO. REVISION DESCRIPTION DATE
The information on this document is preliminary or incomplete, not for
BLDG 3 BLDG 1
BLDG 2BLDG 19
BLDG 61
BLDG 62
BLDG 29
N
A B C D E F G H J K L M
LOUNGE /
LOCKER
GI EXAM
GI EXAM
110 108
GI /
RHEUM
108 106
GI /
RHEUM
106 104
NEURO
104 102
NEURO
CORRIDOR
117 115
CORRIDOR
STF TLT
GI /
RHEUM
113 111
GI EXAM
111 107
NEURO
107 105
PAT TLT
CORRIDOR
CLEAN
UTILITY
A100
SCALE
A100
100A
SHARED
WAITING
100A
TEAM
SPACE 1
109 100B
RECEPTION
100B
A101
ALCOVE
A101
A102
CRASH
CART
A102
ELEC
IT ROOM
PROC TLT
123B
MED EQUIP
STORAGE
CORR.
TEAM SPACE
122A VESTIBULE
122B
PAT. TLT
CPAP STG
IT ROOM
STAFF TLT
MEDICATION
PROCEDURE
ROOM
123A
PFT
126A
PFT TLT
126A
SOILED UTILITY
HAC
O2, EMPTY
129A
O2, FULL
129B
EXAM SP-16
CLEAN UTILITY
STG
141B STG
143B
EXAM SP-17
EXAM SP-16
EXAM SP-16
EXAM SP-16
EXAM SP-16
EXAM SP-16
EXAM SP-16
EXAM SP-16
EXAM SP-16
EXAM SP-16
EXAM SP-16
EXAM SP-16
RECEPTION
100C
REQUIRED AUDIBILITY LEGEND
54dB AMBIENT SPL 69dB EXPECTED SPL
60dB AMBIENT SPL 75dB EXPECTED SPL
30dB AMBIENT SPL 45dB EXPECTED SPL
(STORAGE OCCUPANCIES)
(BUSINESS OCCUPANCIES)
(ASSEMBLY OCCUPANCIES)
OUT OF SCOPE AREA
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
KS ARCH REG. NO. A-930, EXP. 12/31/2023
KS ENGR REG. NO. E-2586, EXP. 12/31/2023
STRUCTURAL / CIVIL ENGINEER
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB / TECH ENGR
SPUR DESIGN
25219 MADISON AVENUE, SUITE 100
KANSAS CITY, MO 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT HEALTH & SAFETY
1139 OLIVE STREET,
ST. LOUIS, MO 63101
(314) 436-9492
HEALTHCARE PLANNER
INNOVA GROUP
3196 N. SWAN ROAD
TUCSON, AZ 85712
(520) 886-8650
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH ROAD, STE 1415
PANAMA CITY, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:SPUR #: 2016
/1
/2
:2 :0
P
M
FA102
FIRE ALARM AUDIBILITY PLAN - FIRST
FLOOR
SAB
90 OF 190BLS
100% BID SET
CONSTRUCT INFILL OF
BUILDING 26 AND RENOVATE
SPECIALTY CARE CLINICS
12/21/2022
589-704
5500 EAST KELLOGG AVENUE
WICHITA, KANSAS 67218
N
1/8" = 1'-0"
FIRE ALARM AUDIBILITY PLAN - FIRST FLOOR1
NO. REVISION DESCRIPTION DATE
The information on this document is preliminary or incomplete, not for
0.25W 15cd
0.25W15cd
0.25W 15cd
.2
W c d
.2
W c d
.2
W c d
0.25W 15cd
S
0.25W0.25W 15cd
.2
W c d
0.25W 15cd
0.25W 15cd 0.25W 15cd
.2
W c d
0.25W 30cd
0.5W30cd
0.5W 30cd0.5W 75cd
.5
W c d
S
0.25W
0.5W30cd 0.5W30cd
.5
W c d
.5
W c d
S
.5
W
S
.5
W
.5
W c d
.5
W c d
S
0.25W
.2
W c d
0.25W 15cd
F
S
0.25W
A B C D E F G H J K L M
DINING AREA
VENDOR
DINING AREA
037A
RETAIL STORE
RETAIL
STORAGE
CORRIDOR
KITCHEN
041A
DISH WASH
041A
SERVING LINE
037B
SAFE
038C
VCS CHIEF
OFFICE
038B
VCS OFFICE
038A
COOLER
044A
FREEZER
044B
FOOD STG
FOOD STG
WORKSTATIONS
HOLDING CELL
034 HOLDING CELL
GUEST
SERVICES
IT ROOM
HAC
ELEC
STORAGE
DENTAL
MECH
045 042
CLEAN
SUPPLY
SOILED
UTILITY
044 043
TRAY
STORAGE
STERILE
INSTRUMENTS
041 038
MOBILE
EQUIPMENT
MED
040 039
PAT TLT
X-RAY
STF TLT
WAITING
034A
CHECK-IN
KIOSK
034A
C3
CORRIDOR
C3
035A
RECEPTION
035A
035F
COPY /
SUPPLY
035F
035B
CHIEF
035B
WORKSTATIONS
DTR-8
059058
DTR-7
058057
DTR-6
057056
DTR-5
056055
DTR-4
055054
DTR-3
054053
DTR-2
053052
DTR-1
052051
LAB
A008
CAD/CAM
CART
A008 A007
EQUIP
A007 A006
LIFT
A006 A005
EQUIP
A005 A004
WC
A004 A003
EQUIP
A003 A002
EQUIP
A002 A001
CRASH
CART
A001
035D
LOUNGE
035D
035E
DRESSING
035E
035C
LOCKER
035C
VS
WF
VS
WF
FES
AOM
AOM
AOM ALARM
SUPERVISORY
TROUBLE
KEY PLAN
BLDG 26
BLDG 3 BLDG 1
BLDG 2BLDG 19
BLDG 61
BLDG 62
BLDG 29
N th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
KS ARCH REG. NO. A-930, EXP. 12/31/2023
KS ENGR REG. NO. E-2586, EXP. 12/31/2023
STRUCTURAL / CIVIL ENGINEER
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB / TECH ENGR
SPUR DESIGN
25219 MADISON AVENUE, SUITE 100
KANSAS CITY, MO 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT HEALTH & SAFETY
1139 OLIVE STREET,
ST. LOUIS, MO 63101
(314) 436-9492
HEALTHCARE PLANNER
INNOVA GROUP
3196 N. SWAN ROAD
TUCSON, AZ 85712
(520) 886-8650
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH ROAD, STE 1415
PANAMA CITY, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:SPUR #: 2016
/1
/2
:2 :0
P
M
FA103
FIRE ALARM PLAN - GROUND FLOOR
SAB
91 OF 190BLS
100% BID SET
CONSTRUCT INFILL OF
BUILDING 26 AND RENOVATE
SPECIALTY CARE CLINICS
12/21/2022
589-704
5500 EAST KELLOGG AVENUE
WICHITA, KANSAS 67218
N
1/8" = 1'-0"
FIRE ALARM PLAN - GROUND FLOOR1
NO. REVISION DESCRIPTION DATE
The information on this document is preliminary or incomplete, not for
0.25W15cd
.2
W c d
0.25W15cd
S
0.25W
.2
W c d
S
.2
W
.2
W c d
0.25W 15cd 0.25W 15cd
S
0.25W
.2
W c d
0.25W 15cd
0.5W 75cd 0.5W 75cd
.5
W c d
.5
W c d
0.25W15cd
.5
W c d
.5
W c d
0.5W75cd
0.25W15cd
0.25W 15cd
S
0.25W
S
0.25W
0.5W 15cd
A B C D E F G H J K L M
ELEC
IT ROOM
PROC TLT
123B
MED EQUIP
STORAGE
CORR.
TEAM SPACE
122A VESTIBULE
122B
PAT. TLT
CPAP STG
IT ROOM
STAFF TLT
MEDICATION
PROCEDURE
ROOM
123A
PFT
126A
PFT TLT
126A
SOILED UTILITY
HAC
O2, EMPTY
129A
O2, FULL
129B
EXAM SP-16
CLEAN UTILITY
STG
141B STG
143B
EXAM SP-17
EXAM SP-16
EXAM SP-16
EXAM SP-16
EXAM SP-16
EXAM SP-16
EXAM SP-16
EXAM SP-16
EXAM SP-16
EXAM SP-16
EXAM SP-16
EXAM SP-16
LOUNGE /
LOCKER
116 112
GI EXAM
112 110
GI EXAM
110 108
GI /
RHEUM
108 106
GI /
RHEUM
106 104
NEURO
104 102
NEURO
CORRIDOR
CORRIDOR
STF TLT
GI /
RHEUM
113 111
GI EXAM
111 107
NEURO
107 105
PAT TLT
CORRIDOR
CLEAN
UTILITY
A100
SCALE
A100
100A
SHARED
WAITING
100A
TEAM
SPACE 1
100B
RECEPTION
100B
STAIR
A101
ALCOVE
A101
A102
CRASH
CART
A102 RECEPTION
100C
KEY PLAN
BLDG 26
BLDG 3 BLDG 1
BLDG 2BLDG 19
BLDG 61
BLDG 62
BLDG 29
N th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
KS ARCH REG. NO. A-930, EXP. 12/31/2023
KS ENGR REG. NO. E-2586, EXP. 12/31/2023
STRUCTURAL / CIVIL ENGINEER
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB / TECH ENGR
SPUR DESIGN
25219 MADISON AVENUE, SUITE 100
KANSAS CITY, MO 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT HEALTH & SAFETY
1139 OLIVE STREET,
ST. LOUIS, MO 63101
(314) 436-9492
HEALTHCARE PLANNER
INNOVA GROUP
3196 N. SWAN ROAD
TUCSON, AZ 85712
(520) 886-8650
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH ROAD, STE 1415
PANAMA CITY, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:SPUR #: 2016
/1
/2
:2 :0
P
M
FA104
FIRE ALARM PLAN - FIRST FLOOR
SAB
92 OF 190BLS
100% BID SET
CONSTRUCT INFILL OF
BUILDING 26 AND RENOVATE
SPECIALTY CARE CLINICS
12/21/2022
589-704
5500 EAST KELLOGG AVENUE
WICHITA, KANSAS 67218
N
1/8" = 1'-0"
FIRE ALARM PLAN - FIRST FLOOR1
NO. REVISION DESCRIPTION DATE
The information on this document is preliminary or incomplete, not for
1. THE DESIGN AND INSTALLATION OF THE FIRE PROTECTION, FIRE
SUPPRESSION SYSTEM MUST BE IN ACCORDANCE WITH U.S.
DEPARTMENT OF VETERANS AFFAIRS FIRE PROTECTION DESIGN
MANUAL, EIGHTH EDITION, JUNE 2021; NFPA 13: STANDARD FOR THE
INSTALLATION OF SPRINKLER SYSTEMS, 2022 EDITION; NFPA 14:
STANDARD FOR THE INSTALLATION OF STANDPIPE AND HOSE SYSTEMS,
2019 EDITION.
2. THIS INFORMATION HAS BEEN PREPARED TO PROVIDE GUIDANCE FOR
BIDDING. THE CONTRACTOR SHALL BE THE ENGINEER OF RECORD. THE
FIRE PROTECTION CONTRACTOR SHALL BE FULLY RESPONSIBLE FOR
PROVIDING A COMPLETE AND FULLY OPERABLE SYSTEM WHICH SHALL
BE IN STRICT ACCORDANCE WITH PROJECT SPECIFICATIONS AND
APPLICABLE CODES AND STANDARDS. THE WORK THAT IS INDICATED IN
THIS DOCUMENT IS AN OVERVIEW OF THE PROJECT, INTENDED TO
ESTABLISH THE MINIMUM SCOPE REQUIREMENTS FOR THE PROJECT AS
WELL AS THE CONTRACTOR’S RESPONSIBILITIES. THE CONTRACTOR
SHALL SUBMIT A COMPLETE SET OF WORKING DRAWINGS, EQUIPMENT,
AND CALCULATIONS TO THE OWNER’S REPRESENTATIVE AND AHJ FOR
REVIEW AND APPROVAL PRIOR TO FABRICATION AND INSTALLATION
WITH THEIR ENGINEERS SEAL.
3. PRIOR TO BEGINNING ANY CONSTRUCTION, THE CONTRACTOR SHALL BE
RESPONSIBLE FOR VERIFICATION OF ALL DIMENSIONS, MEASUREMENTS
AND LOCATIONS OF EXISTING FACILITIES, UTILITIES, EQUIPMENT AND
OTHER EXISTING CONDITIONS WHICH MAY AFFECT CONSTRUCTION.
BASE CIVIL ENGINEERING HAS MADE EVERY ATTEMPT TO VERIFY THIS
INFORMATION. HOWEVER, IN THE EVENT OF DISCREPANCIES BETWEEN
THE DRAWINGS AND ACTUAL FIELD CONDITIONS, CONTACT THE
CONTRACTING OFFICER IMMEDIATELY.
4. SPRINKLER CONTRACTOR SHALL COORDINATE LOCATIONS OF FIRE
PROTECTION COMPONENTS INCLUDING PIPING, ALARMS, DRAINS,
SPRINKLERS, TEST POINTS, ETC., WITH ALL ARCHITECTURAL,
STRUCTURAL, MECHANICAL, AND ELECTRICAL COMPONENTS.
OBSTRUCTIONS TO SPRINKLER DISCHARGE SHALL BE CONSIDERED
DURING INSTALLATION. DO NOT INSTALL SPRINKLER PIPING BELOW
EQUIPMENT OR WITHIN CLEARANCE SPACES FOR MECHANICAL AND
ELECTRICAL EQUIPMENT. SPRINKLERS SHALL BE INSTALLED UNDER
OBSTRUCTIONS IN ACCORDANCE WITH NFPA 13.
5. MATERIALS AND ACCESSORIES NECESSARY MUST BE INSTALLED IN
ACCORDANCE WITH THE APPLICABLE NFPA CODES AND STANDARDS,
PROJECT SPECIFICATIONS, AND BE UL LISTED OR FM APPROVED FOR
FIRE PROTECTION USE, UNLESS OTHERWISE NOTED.
6. ALL VALVES INSIDE TO BE PROVIDED WITH ELECTRONIC TAMPER
SWITCHES WIRED TO THE FACU. VALVES IN NORMAL CLOSED POSITION
SHALL BE PROVIDED WITH TAMPER TO ACTIVATE IN THREE TURNS OR
LESS. ALL VALVES OUTSIDE TO BE ELECTRONICALLY MONITORED BY
FIRE ALARM.
7. ALL HANGERS MUST BE PROVIDED AND INSTALLED IN ACCORDANCE
WITH NFPA 13 AND PROJECT SPECIFICATIONS.
8. LOCATION AND INSTALLATION OF PIPE SUPPORTS (HANGERS, VERTICAL
RESTRAINTS, AND GUIDES) SHALL MEET THE REQUIREMENTS OF NFPA 13
AND THE SPECIAL LISTING REQUIREMENTS (IF APPLICABLE) OF THE PIPE
AND SUPPORTS.
9. THE INSPECTOR'S TEST VALVES MUST BE LOCATED NO MORE THAN 7
FEET AFF.
10. APPLICABLE UL CONSTRUCTION DETAILS AND SYSTEMS SHALL BE USED
WHERE FIRE RATED BARRIERS ARE PENETRATED BY SPRINKLER PIPING.
11. ALL VALVES (DRAINS, INSPECTOR'S TEST, CONTROL) MUST BE
IDENTIFIED AS REQUIRED BY NFPA 13.
12. PIPING MUST BE ARRANGED FOR FLUSHING. READILY REMOVABLE
FITTINGS MUST BE PROVIDED AT THE END OF ALL CROSS MAINS.
13. ALL PENDENT SPRINKLERS MUST BE INSTALLED IN THE CENTER OF THE
CEILING TILES.
14. DRAINS MUST BE LOCATED TO PROVIDE DRAINAGE IN ACCORDANCE
WITH NFPA 13. ALL DRAINS AND TEST CONNECTIONS MUST DISCHARGE
TO THE EXTERIOR OF THE BUILDING ON TO A SPLASH BLOCK OR
PAVEMENT, AND SHALL NOT DISCHARGE ACROSS PATHS OF EGRESS.
15. ALL SPRINKLER SYSTEM ALARM INITIATING AND SUPERVISORY DEVICES
MUST BE CONNECTED TO THE FIRE ALARM SYSTEM.
16. ADDITIONAL SPRINKLERS MAY BE REQUIRED UNDER DUCT WORK TO
PROVIDE ADEQUATE COVERAGE PER NFPA 13.
17. A LISTED RELIEF VALVE MUST BE PROVIDED IN ACCORDANCE WITH NFPA
13, SECTION 8.1.2 FOR THE SPRINKLER SYSTEM.
18. THIS BUILDING WILL HAVE A WET PIPE AUTOMATIC SPRINKLER SYSTEM
WHICH WILL REQUIRE ALL AREAS OF THE BUILDING TO BE MAINTAINED
ABOVE 40 DEGREES F.
19. PROVIDE SPRINKLER PROTECTION WITHIN ALL COMBUSTIBLE
CONCEALED SPACES.
20. INSTALL NEW CHECK VALVES, WATERFLOW SWITCHES, AND
INSPECTOR'S TEST CONNECTIONS WITH PRESSURE RELIEF VALVE.
FIRE SUPPRESSION GENERAL NOTES
TO PLAN
SOUTH FIRE
RISER
TO PLAN
NORTH FIRE
RISER
EXISITNG
UNDERGROUND
LEAD-IN
NEW ABOVE
GROUND FIRE
WATER SUPPLY
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
KS ARCH REG. NO. A-930, EXP. 12/31/2023
KS ENGR REG. NO. E-2586, EXP. 12/31/2023
STRUCTURAL / CIVIL ENGINEER
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB / TECH ENGR
SPUR DESIGN
25219 MADISON AVENUE, SUITE 100
KANSAS CITY, MO 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT HEALTH & SAFETY
1139 OLIVE STREET,
ST. LOUIS, MO 63101
(314) 436-9492
HEALTHCARE PLANNER
INNOVA GROUP
3196 N. SWAN ROAD
TUCSON, AZ 85712
(520) 886-8650
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH ROAD, STE 1415
PANAMA CITY, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:SPUR #: 2016
/1
/2
:2 :0
P
M
FX001
FIRE SUPPRESSION GENERAL NOTES
SAB
93 OF 190BLS
100% BID SET
CONSTRUCT INFILL OF
BUILDING 26 AND RENOVATE
SPECIALTY CARE CLINICS
12/21/2022
589-704
5500 EAST KELLOGG AVENUE
WICHITA, KANSAS 67218
SCALE: NONE1
FIRE RISER ONE-LINE DIAGRAM
NO. REVISION DESCRIPTION DATE
The information on this document is preliminary or incomplete, not for
BLDG 3 BLDG 1
BLDG 2BLDG 19
BLDG 61
BLDG 62
BLDG 29
N
A B C D E F G H J K L M
DINING AREA
VENDOR
DINING AREA
037A
RETAIL STORE
RETAIL
STORAGE
CORRIDOR
KITCHEN
041A
DISH WASH
041A
SERVING LINE
037B
SAFE
038C
VCS CHIEF
OFFICE
038B
VCS OFFICE
038A
COOLER
044A
FREEZER
044B
FOOD STG
FOOD STG
WORKSTATIONS
GUEST
SERVICES
IT ROOM
HAC
ELEC
STORAGE
DENTAL
MECH
045 042
CLEAN
SUPPLY
SOILED
UTILITY
044 043
TRAY
STORAGE
STERILE
INSTRUMENTS
041 038
MOBILE
EQUIPMENT
MED
040 039
PAT TLT
X-RAY
STF TLT
WAITING
034A
CHECK-IN
KIOSK
034A 034B
WC ALC.
034B
C3
CORRIDOR
C3 035A
RECEPTION
035A
035F
COPY /
SUPPLY
035F
035B
CHIEF
035B
WORKSTATIONS
DTR-8
059058
DTR-7
058057
DTR-6
057056
DTR-5
056055
DTR-4
055054
DTR-3
054053
DTR-2
053052
DTR-1
LAB
A008
CAD/CAM
CART
A008 A007
EQUIP
A007 A006
LIFT
A006 A005
EQUIP
A005 A004
WC
A004 A003
EQUIP
A003 A002
EQUIP
A002 A001
CRASH
CART
A001
035D
LOUNGE
035D
035E
DRESSING
035E
035C
LOCKER
035C
SECURITY
HAZARD CLASSIFICATION LEGEND
LIGHT HAZARD
(0.10 GPM/FT² OVER 1,500 FT² WITH
250 GPM EXTERIOR HOSE DEMAND)
OUT OF SCOPE
EXISTING FIRE SUPPRESSION RISER
PIPING CONTINUATION
EXISTING FIRE SUPPRESSION PIPING
NEW FIRE SUPPRESSION PIPING
ORDINARY HAZARD I
(0.15 GPM/FT² OVER 1,500 FT² WITH
250 GPM EXTERIOR HOSE DEMAND)
ORDINARY HAZARD II
(0.20 GPM/FT² OVER 1,500 FT² WITH
250 GPM EXTERIOR HOSE DEMAND)
FIRE SUPPRESSION SYSTEM BOUNDARY
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
KS ARCH REG. NO. A-930, EXP. 12/31/2023
KS ENGR REG. NO. E-2586, EXP. 12/31/2023
STRUCTURAL / CIVIL ENGINEER
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB / TECH ENGR
SPUR DESIGN
25219 MADISON AVENUE, SUITE 100
KANSAS CITY, MO 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT HEALTH & SAFETY
1139 OLIVE STREET,
ST. LOUIS, MO 63101
(314) 436-9492
HEALTHCARE PLANNER
INNOVA GROUP
3196 N. SWAN ROAD
TUCSON, AZ 85712
(520) 886-8650
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH ROAD, STE 1415
PANAMA CITY, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:SPUR #: 2016
/1
/2
:2 :1
P
M
FX101
FIRE SUPPRESSION HAZARD
CLASSIFICATION PLAN - GROUND
FLOOR
SAB
94 OF 190BLS
100% BID SET
CONSTRUCT INFILL OF
BUILDING 26 AND RENOVATE
SPECIALTY CARE CLINICS
12/21/2022
589-704
5500 EAST KELLOGG AVENUE
WICHITA, KANSAS 67218
N
1/8" = 1'-0"
FIRE SUPPRESSION HAZARD CLASSIFICATION PLAN -
GROUND FLOOR1
SHEET KEYNOTES
MARK KEYNOTE
01 WHERE FEASABLE, THE IT ROOM SHALL HAVE 18"
CLEARANCE ABOVE EQUIPMENT TO SPRINKLER
PIPING IN ACCORDANCE WITH APPLICABLE CODES
AND STANDARDS. WHERE EXISTING
CONSTRUCTION ROOM HEIGHT LIMITATIONS
OCCUR, 18" CLEARANCE MAY NOT BE ACHIEVABLE.
IN ADDITION, BUILT-IN TROUGHS AND/OR LEAK
DETECTION IN ACCORDANCE WITH NFPA 70 SHALL
BE PROVIDED TO PROTECT IT EQUIPMENT FROM
ANY WET-PIPE SPRINKLER LEAKAGE.
02 CONTRACTOR TO DEMOLISH EXISTING FIRE RISER.
REBUILD NEW FIRE RISER TO BE FED FROM ABOVE
GROUND MAIN FROM PLAN SOUTH SIDE OF
BUILDING AND SERVE THE PLAN NORTH (EAST)
SIDE OF THE BUIDLING. NEW ABOVEGROUND
PIPING MUST BE CONNECTED TO FIRE SPRINKLER
RISER PRIOR TO DISCONNECTION OF EXISTING
UNDERGROUND PIPING. CONTRACTOR TO
COORDINATE WITH VA PERSONNEL IN REGARDS TO
FIRE SPRNIKLER IMPAIRMENT DURING
CONSTRUCTION. CONTRACTOR TO FIELD VERIFY
EXACT LOCATIONS OF NEW PIPING AND TIE-INS
PRIOR TO ANY CONSTRUCTION.
03 CONTRACTOR TO CONNECT TO EXISTING FIRE
SPRINKLER PIPING. CONTRACTOR TO FIELD VERIFY
EXACT LOCATION PRIOR TO ANY WORK.
04 EXISTING FIRE SPRINKLER RISER IS CURRENTLY
BEING FED FROM UNDERGROUND PIPING. PER
REQUEST FROM THE VA, CONTRACTOR TO
REPLACE ALL EXISITING FIRE SUPPRESSION
VALVES IN GROUND FLOOR PLAN SOUTH STAIR.
CONTRACTOR TO COORDINATE WITH VA
PERSONNEL IN REGARDS TO FIRE SPRINKLER
IMPAIRMENT DURING CONSTRUCTION.
CONTRACTOR TO FIELD VERIFY EXACT LOCATIONS
OF NEW PIPING AND TIE-INS PRIOR TO ANY
CONSTRUCTION.
05 CONTRACTOR TO REMOVE EXISTING HOSE
STATION AND EXISTING FDC PIPING AND
CONNECTION. CONTRACTOR TO FIELD VERIFY
EXACT LOCATION OF FDC, HOSE CONNECTION AND
PIPING PRIOR TO CONSTRUCTION.
06 CONTRACTOR TO PROIVDE SPRINKLER
PROTECTION VIA DRY PENDENT SPINRKLERS IN
FREEZER AND COOLER. CONTRACTOR TO
COORDINATE PENETRATION LOCATIONS WITH
OWNER IN FIELD PRIOR TO CONSTRUCTION.
THIS AREA SUPPLIED
BY PLAN SOUTH
(WEST) FIRE RISER
THIS AREA SUPPLIED
BY PLAN NORTH
(EAST) FIRE RISER
THIS AREA SUPPLIED
BY PLANT SOUTH
(WEST) FIRE RISER
PLAN NORTH (EAST)
FIRE RISER
PLAN SOUTH (WEST)
FIRE RISER
NO. REVISION DESCRIPTION DATE
The information on this document is preliminary or incomplete, not for
BLDG 3 BLDG 1
BLDG 2BLDG 19
BLDG 61
BLDG 62
BLDG 29
N
HAZARD CLASSIFICATION LEGEND
LIGHT HAZARD
(0.10 GPM/FT² OVER 1,500 FT² WITH
250 GPM EXTERIOR HOSE DEMAND)
OUT OF SCOPE
EXISTING FIRE SUPPRESSION RISER
PIPING CONTINUATION
EXISTING FIRE SUPPRESSION PIPING
NEW FIRE SUPPRESSION PIPING
ORDINARY HAZARD I
(0.15 GPM/FT² OVER 1,500 FT² WITH
250 GPM EXTERIOR HOSE DEMAND)
ORDINARY HAZARD II
(0.20 GPM/FT² OVER 1,500 FT² WITH
250 GPM EXTERIOR HOSE DEMAND)
FIRE SUPPRESSION SYSTEM BOUNDARY
A B C D E F G H J K L M
ELEC
IT ROOM
PROC TLT
123B
MED EQUIP
STORAGE
CORR.
TEAM SPACE
122A VESTIBULE
122B
PAT. TLT
CPAP STG
IT ROOM
STAFF TLT
MEDICATION
PROCEDURE
ROOM
123A
PFT
126A
PFT TLT
126A
SOILED UTILITY
HAC
O2, EMPTY
129A
O2, FULL
129B
EXAM SP-16
CLEAN UTILITY
STG
141B STG
143B
EXAM SP-17
EXAM SP-16
EXAM SP-16
EXAM SP-16
EXAM SP-16
EXAM SP-16
EXAM SP-16
EXAM SP-16
EXAM SP-16
EXAM SP-16
EXAM SP-16
EXAM SP-16
LOUNGE /
LOCKER
GI EXAM
GI EXAM
110 108
GI /
RHEUM
108 106
GI /
RHEUM
106 104
NEURO
104 102
NEURO
CORRIDOR
CORRIDOR
STF TLT
GI /
RHEUM
113 111
GI EXAM
111 107
NEURO
107 105
PAT TLT
CORRIDOR
CLEAN
UTILITY
A100
SCALE
A100
100A
SHARED
WAITING
100A
TEAM
SPACE 1
109 100B
RECEPTION
100B164
STAIR
A101
ALCOVE
A101
A102
CRASH
CART
A102
RECEPTION
100C th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
KS ARCH REG. NO. A-930, EXP. 12/31/2023
KS ENGR REG. NO. E-2586, EXP. 12/31/2023
STRUCTURAL / CIVIL ENGINEER
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB / TECH ENGR
SPUR DESIGN
25219 MADISON AVENUE, SUITE 100
KANSAS CITY, MO 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT HEALTH & SAFETY
1139 OLIVE STREET,
ST. LOUIS, MO 63101
(314) 436-9492
HEALTHCARE PLANNER
INNOVA GROUP
3196 N. SWAN ROAD
TUCSON, AZ 85712
(520) 886-8650
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH ROAD, STE 1415
PANAMA CITY, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:SPUR #: 2016
/1
/2
:2 :1
P
M
FX102
FIRE SUPPRESSION HAZARD
CLASSIFICATION PLAN - FIRST FLOOR
SAB
95 OF 190BLS
100% BID SET
CONSTRUCT INFILL OF
BUILDING 26 AND RENOVATE
SPECIALTY CARE CLINICS
12/21/2022
589-704
5500 EAST KELLOGG AVENUE
WICHITA, KANSAS 67218
N
1/8" = 1'-0"
FIRE SUPPRESSION HAZARD CLASSIFICATION PLAN -
FIRST FLOOR1
SHEET KEYNOTES
MARK KEYNOTE
01 WHERE FEASABLE, THE IT ROOM SHALL HAVE 18"
CLEARANCE ABOVE EQUIPMENT TO SPRINKLER PIPING
IN ACCORDANCE WITH APPLICABLE CODES AND
STANDARDS. WHERE EXISTING CONSTRUCTION ROOM
HEIGHT LIMITATIONS OCCUR, 18" CLEARANCE MAY NOT
BE ACHIEVABLE. IN ADDITION, BUILT-IN TROUGHS
AND/OR LEAK DETECTION IN ACCORDANCE WITH NFPA
70 SHALL BE PROVIDED TO PROTECT IT EQUIPMENT
FROM ANY WET-PIPE SPRINKLER LEAKAGE.
GENERAL NOTE: FIRST FLOOR HAS FIRE
SUPPRESSION PIPING WITH ORANGE POLY PIPE.
PER VA DIRECTION, FIRE PROTECTION
CONTRACTOR TO REMOVE POLY PIPE AND
REPLACE WITH HARD PIPE ONLY. CONTRACTOR
TO FIELD VERIFY LOCATION OF EXISTING POLY
PIPING PRIOR TO ANY CONSTRUCTION.
CONTRACTOR TO COORDINATE REMOVAL WITH
VA.
THIS AREA SUPPLIED
BY PLAN SOUTH
(WEST) FIRE RISER
THIS AREA SUPPLIED
BY PLAN NORTH
(EAST) FIRE RISER
PLAN NORTH (EAST)
FIRE RISER
PLAN SOUTH (WEST)
FIRE RISER
NO. REVISION DESCRIPTION DATE
The information on this document is preliminary or incomplete, not for
| Sheets |
| FA001 - FIRE ALARM GENERAL NOTES, LEGEND, AND RISER DIAGRAM |
| FA101 - FIRE ALARM AUDIBILITY PLAN - GROUND FLOOR |
| FA102 - FIRE ALARM AUDIBILITY PLAN - FIRST FLOOR |
| FA103 - FIRE ALARM PLAN - GROUND FLOOR |
| FA104 - FIRE ALARM PLAN - FIRST FLOOR |
| FX001 - FIRE SUPPRESSION GENERAL NOTES |
| FX101 - FIRE SUPPRESSION HAZARD CLASSIFICATION PLAN - GROUND FLOOR |
| FX102 - FIRE SUPPRESSION HAZARD CLASSIFICATION PLAN - FIRST FLOOR |