About this file

This solicitation is for a minor construction project to construct an infill of Building 26 for dental clinics, a new police office, and renovate space for specialty care services at the Robert J. Dole VA Medical Center in Wichita, Kansas. The solicitation number is 36C77624R0027 and was issued by the Department of Veterans Affairs Technology Acquisition Center located in Austin, Texas. The project scope involves excavating an existing courtyard to prepare for new construction, building an infill structure on the ground and first floors, interior construction for the ground floor canteen and first floor specialty care unit, limited renovation including a connecting corridor, replacing an emergency generator, ground floor dental clinic renovation, first floor specialty care renovation, construction of a ground floor police substation, and exterior service yard improvements.

View the file

Other files

File Type Posted
36C77624R0027 0005.docx DOCX document
SA031 - Pad Details.pdf PDF
589-704 AE Addendum 01.pdf PDF
S05-589-704 RFIs - Technical Questions_RESPONSES.docx DOCX document
36C77624R0027 0004.docx DOCX document
36C77624R0027 0003.docx DOCX document
36C77624R0027 0002.docx DOCX document
589-704 PreBid Sign In Sheet.pdf PDF
03 Volume 589-704 Spec v2.pdf PDF
36C77624R0027 0001.docx DOCX document
Final Geotech Report B26.pdf PDF
Attachment 15 Bldg 26 - Ground Floor - Asbestos Survey.pdf PDF
Attachment 12 02 Volume 589-704 Spec.pdf PDF
Attachment 19 - Site Visit Instructions.docx DOCX document
Attachment 9 08_100_ BID SET Electrical Drawings.pdf PDF
Attachment 3 02_100_ BID SET Civil Drawings.pdf PDF
Attachment 4 03_100_ BID SET Structural Drawings.pdf PDF
Attachment 11 01 Volume 589-704 Spec_R1.pdf PDF
Attachment 7 06_100_ BID SET Plumbing Drawings.pdf PDF
Attachment 2 01_100_ BID SET Environmental Drawings.pdf PDF
Attachment 14 Bldg 26 - First Floor - Asbestos Survey.pdf PDF
Attachment 13 03 Volume 589-704 Spec.pdf PDF
Attachment 16 Kansas Tax Language - 1.26.2023 - FINAL.docx DOCX document
Attachment 8 07_100_ BID SET Mechanical Drawings.pdf PDF
Attachment 6 05_100_ BID SET Fire Protection Drawings.pdf PDF
Attachment 17 WD Sedgwick 01192024.pdf PDF
Attachment 10 09_100_ BID SET Technology Drawings.pdf PDF
36C77624R0027_1.docx DOCX document
Attachment 18 - VA Handbook 6500.6 Appendix C.pdf PDF
Attachment 5 04_100_ BID SET Architectural Drawings.pdf PDF
Show all 30

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

N

AREA

PLAN

LOCATION

PLAN

N

PROJECT LOCATION

BUILDING 26

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing #

U.S. DEPARTMENT OF VETERANS AFFAIRS

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

KS ARCH REG. NO. A-930, EXP. 12/31/2023

KS ENGR REG. NO. E-2586, EXP. 12/31/2023

STRUCTURAL / CIVIL ENGINEER

H2B, INC.

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECH / ELEC / PLUMB / TECH ENGR

SPUR DESIGN

25219 MADISON AVENUE, SUITE 100

KANSAS CITY, MO 64108

(913) 369-7200

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT HEALTH & SAFETY

1139 OLIVE STREET,

ST. LOUIS, MO 63101

(314) 436-9492

HEALTHCARE PLANNER

INNOVA GROUP

3196 N. SWAN ROAD

TUCSON, AZ 85712

(520) 886-8650

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH ROAD, STE 1415

PANAMA CITY, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:SPUR #: 2016

/2

/2

:5 :0

A

M

G-000

COVER SHEET

ECO

1 OF 190AJS

100% BID SET

CONSTRUCT INFILL OF BUILDING 26 AND

RENOVATE SPECIALTY CARE CLINICS

VA PROJECT NUMBER: 589-704

CONSTRUCT INFILL OF

BUILDING 26 AND RENOVATE

SPECIALTY CARE CLINICS

12/21/2022

589-704

5500 EAST KELLOGG AVENUE

WICHITA, KANSAS 67218

ROBERT J. DOLE VA MEDICAL CENTER

5500 EAST KELLOGG AVENUE

WICHITA, KANSAS 67218

100% BID SET

SHEET INDEX

SEQUENCE NUMBER SHEET NAME

[08] ELECTRICAL

155 E-000 ELECTRICAL LEGEND

156 ED101 PHASE ONE - ELECTRICAL DEMOLITION GROUND FLOOR PLANS

157 ED102 PHASE ONE - ELECTRICAL DEMOLITION REFLECTED CEILING PLANS

158 ED103 PHASE TWO - ELECTRICAL DEMOLITION POWER FLOOR PLANS

159 ED104 PHASE TWO - ELECTRICAL DEMOLITION REFLECTED CEILING PLANS

160 ED601 ELECTRICAL ONE-LINE DIAGRAM - DEMOLITION / TEMPORARY POWER

161 EL101 PHASE ONE - ELECTRICAL LIGHTING PLANS

162 EL102 PHASE TWO - ELECTRICAL LIGHTING PLAN

163 EP101 PHASE ONE - ELECTRICAL POWER PLANS

164 EP102 PHASE TWO - ELECTRICAL POWER PLANS

165 EP103 PHASE THREE - ELECTRICAL SITE PLAN

166 EQ101 PHASE ONE - ELECTRICAL EQUIPMENT POWER PLANS

167 EQ102 PHASE TWO - ELECTRICAL EQUIPMENT POWER PLANS

168 E-401 PHASE ONE - ELECTRICAL ENLARGED PLANS

169 E-402 PHASE TWO - ELECTRICAL ENLARGED PLANS

170 E-501 POWER ELEVATIONS FOR TELECOMMUNICATION RACKS AND DUCT BANK

DETAILS

171 E-502 ELECTRICAL DETAILS

172 E-503 LIGHTING DETAILS AND CONTROLS

173 E-601 ELECTRICAL ONE-LINE DIAGRAM - NEW WORK

174 E-602 ELECTRICAL SCHEDULES

175 E-603 ELECTRICAL PANEL SCHEDULES

176 E-604 ELECTRICAL PANEL SCHEDULES

[09] TELECOMMUNICATION

177 T-000 TECHNOLOGY LEGEND

178 TD101 PHASE ONE - TECHNOLOGY DEMOLITION FLOOR PLAN

179 TD102 PHASE TWO - TECHNOLOGY DEMOLITION FLOOR PLAN

180 TI101 PHASE ONE - INTERCOM AND PUBLIC ADDRESS FLOOR PLANS

181 TI102 PHASE TWO - INTERCOM AND PUBLIC ADDRESS FLOOR PLANS

182 TN101 PHASE ONE - TECHNOLOGY FLOOR PLANS

183 TN102 PHASE TWO - TECHNOLOGY FLOOR PLANS

184 TY101 PHASE ONE - SECURITY FLOOR PLANS

185 TY102 PHASE TWO - SECURITY FLOOR PLANS

186 TY103 PHASE THREE - TECHNOLOGY SITE PLAN

187 T-401 ENLARGED TECHNOLOGY PLANS

188 T-501 TECHNOLOGY DETAILS

189 T-601 TECHNOLOGY RISER DIAGRAMS

190 T-602 TECHNOLOGY SCHEDULES

TOTAL SHEETS: 190

SHEET INDEX

SEQUENCE NUMBER SHEET NAME

[07] MECHANICAL

117 M-000 LEGEND AND ABBREVIATIONS

118 MHD101 GROUND FLOOR MECHANICAL DUCT DEMOLITION PLANS

119 MHD102 FIRST FLOOR MECHANICAL HVAC DUCT DEMOLITION PLAN

120 MHD103 SECOND FLOOR MECHANICAL HVAC DUCT DEMOLITION PLANS

121 MHD104 SERVICE YARD DEMOLITION PLAN

122 MHPD101 ROOF MECHANICAL HVAC DUCT AND PIPING DEMOLITION PLAN

123 MPD101 GROUND FLOOR MECHANICAL HVAC PIPING DEMOLITION PLANS

124 MPD102 FIRST FLOOR MECHANICAL HVAC PIPING DEMOLITION PLAN

125 MH101 GROUND FLOOR MECHANICAL DUCT PLANS

126 MH102 FIRST FLOOR MECHANICAL DUCT PLANS

127 MH103 SECOND FLOOR MECHANICAL DUCT PLANS

128 MH104 ROOF MECHANICAL DUCT PLANS

129 MH105 SERVICE YARD NEW WORK PLAN

130 MH106 GROUND FLOOR ZONING PLANS

131 MH107 FIRST FLOOR ZONING PLANS

132 MH108 GROUND FLOOR AIR PRESSURIZATION PLANS

133 MH109 FIRST FLOOR AIR PRESSURIZATION PLANS

134 MP101 GROUND FLOOR MECHANICAL HVAC PIPING PLAN

135 MP102 FIRST FLOOR MECHANICAL HVAC PIPING PLAN

136 MP103 SECOND FLOOR MECHANICAL HVAC PIPING PLAN

137 MP104 ROOF MECHANICAL HVAC PIPING PLAN

138 M-301 MECHANICAL SECTIONS

139 M-401 PHASE 1 AIR FLOW DIAGRAMS

140 M-402 PHASE 2 AIR FLOW DIAGRAMS

141 M-403 HYDRONIC FLOW DIAGRAMS

142 M-501 MECHANICAL DETAILS

143 M-502 MECHANICAL DETAILS

144 M-503 MECHANICAL DETAILS

145 M-504 MECHANICAL DETAILS

146 M-505 MECHANICAL DETAILS

147 M-601 MECHANICAL SCHEDULES

148 M-602 MECHANICAL SCHEDULES

149 M-701 MECHANICAL CONTROLS

150 M-702 MECHANICAL CONTROLS

151 M-703 MECHANICAL CONTROLS

152 M-704 MECHANICAL CONTROLS

153 M-705 MECHANICAL CONTROLS

154 M-706 MECHANICAL CONTROLS

SHEET INDEX

SEQUENCE NUMBER SHEET NAME

58 AE405 PHASE ONE - ENLARGED PLANS & INTERIOR ELEVATIONS

59 AE406 PHASE ONE - ENLARGED PLANS & INTERIOR ELEVATIONS

60 AE407 PHASE ONE - ENLARGED PLANS & INTERIOR ELEVATIONS

61 AE408 PHASE ONE - ENLARGED PLANS & INTERIOR ELEVATIONS

62 AE409 PHASE TWO - ENLARGED PLANS & INTERIOR ELEVATIONS

63 AE410 PHASE TWO - ENLARGED PLANS & INTERIOR ELEVATIONS

64 AE411 PHASE TWO - ENLARGED PLANS & INTERIOR ELEVATIONS

65 AE412 PHASE TWO - ENLARGED PLANS & INTERIOR ELEVATIONS

66 AE413 PHASE TWO - ENLARGED PLANS & INTERIOR ELEVATIONS

67 AE414 PHASE TWO - ENLARGED PLANS & INTERIOR ELEVATIONS

68 AE415 PHASE TWO - ENLARGED PLANS & INTERIOR ELEVATIONS

69 AE416 PHASE TWO - ENLARGED PLANS & INTERIOR ELEVATIONS

70 AE417 PHASE TWO - ENLARGED PLANS & INTERIOR ELEVATIONS

71 AE418 PHASE TWO - ENLARGED PLANS & INTERIOR ELEVATIONS

72 AE419 PHASE THREE - ENLARGED PLANS & INTERIOR ELEVATIONS

73 AE501 SECTION DETAILS

74 AE502 SECTION DETAILS

75 AE511 PLAN DETAILS

76 AE512 PLAN DETAILS

77 AE513 PLAN DETAILS

78 AE601 WINDOW ELEVATIONS, DOOR SCHEDULES & DETAILS

79 AF701 PHASE ONE - FINISH FLOOR PLANS

80 AF702 PHASE TWO & THREE - FINISH FLOOR PLANS

81 AF711 INTERIOR FINISH LEGEND & SCHEDULES

82 AF712 INTERIOR DETAILS

83 AF713 SIGNAGE LEGEND

84 AF714 PHASE ONE - SIGNAGE PLANS

85 AF715 PHASE TWO & THREE- SIGNAGE PLANS

86 AF901 MILLWORK SECTIONS & DETAILS

87 AF902 MILLWORK SECTIONS & DETAILS

[05] FIRE PROTECTION

88 FA001 FIRE ALARM GENERAL NOTES, LEGEND, AND RISER DIAGRAM

89 FA101 FIRE ALARM AUDIBILITY PLAN - GROUND FLOOR

90 FA102 FIRE ALARM AUDIBILITY PLAN - FIRST FLOOR

91 FA103 FIRE ALARM PLAN - GROUND FLOOR

92 FA104 FIRE ALARM PLAN - FIRST FLOOR

93 FX001 FIRE SUPPRESSION GENERAL NOTES

94 FX101 FIRE SUPPRESSION HAZARD CLASSIFICATION PLAN - GROUND FLOOR

95 FX102 FIRE SUPPRESSION HAZARD CLASSIFICATION PLAN - FIRST FLOOR

[06] PLUMBING

96 P-000 PLUMBING LEGEND

97 P-100 PLUMBING OVERALL PLANS

98 PLD101 PHASE ONE - PLUMBING WASTE AND VENT DEMOLITION PLAN

99 PLD102 PHASE TWO - PLUMBING WASTE AND VENT DEMOLITION PLANS

100 PPD101 PHASE TWO - PLUMBING DOMESTIC WATER DEMOLITION PLANS

101 PGD101 PHASE ONE AND TWO - PLUMBING MEDICAL GAS DEMOLITION PLANS

102 PL101 PHASE ONE - PLUMBING WASTE AND VENT PLANS

103 PL102 PHASE TWO - PLUMBING WASTE AND VENT PLANS

104 PP102 PHASE TWO - PLUMBING DOMESTIC WATER PLAN

105 PP101 PHASE ONE - PLUMBING DOMESTIC WATER PLAN

106 PG101 PHASE ONE AND TWO - PLUMBING MEDICAL GAS PLANS

107 P-200 PLUMBING ROOF PLAN

108 P-401 PLUMBING ENLARGED PLANS

109 P-501 PLUMBING DETAILS

110 P-502 PLUMBING DETAILS

111 P-601 PLUMBING SCHEDULES

112 P-301 PLUMBING WASTE AND VENT ISOMETRICS - PHASE 1

113 P-302 PLUMBING WASTE AND VENT ISOMETRICS - PHASE 2

114 P-303 PLUMBING DOMESTIC WATER ISOMETRICS - PHASE 1

115 P-304 PLUMBING DOMESTIC WATER ISOMETRICS - PHASE 2

116 P-305 PLUMBING MEDGAS ISOMETRICS

SHEET INDEX

SEQUENCE NUMBER SHEET NAME

[00] GENERAL

1 G-000 COVER SHEET

2 GI001 GENERAL INFORMATION

3 GI011 PHASING PLANS

4 GI012 OCCUPANCY PLANS

5 GI013 LIFE SAFETY PLAN - GROUND FLOOR

6 GI014 LIFE SAFETY PLAN - FIRST FLOOR

[01] HAZARDOUS MATERIALS

7 HA000 ENVIRONMENTAL REMEDIATION - GENERAL NOTES

8 HA001 GROUND FLOOR - PHASE ONE - ENVIRONMENTAL REMEDIATION

9 HA002 GROUND FLOOR - PHASE TWO - ENVIRONMENTAL REMEDIATION

10 HA101 FIRST FLOOR - PHASE ONE - ENVIRONMENTAL REMEDIATION

11 HA102 FIRST FLOOR - PHASE TWO - ENVIRONMENTAL REMEDIATION

12 HA201 SECOND FLOOR - PHASE ONE - ENVIRONMENTAL REMEDIATION

13 HA301 ROOF - PHASE TWO - ENVIRNOMENTAL REMEDIATION

[02] CIVIL

14 CS-100 SITE LAYOUT

[03] STRUCTURAL

15 SA001 STRUCTURAL GENERAL NOTES

16 SA010 STRUCTURAL SPECIAL INSPECTIONS

17 SA011 STRUCTURAL SPECIAL INSPECTIONS

18 SA030 TYPICAL DETAILS - CONCRETE

19 SA050 TYPICAL DETAILS - STEEL

20 SA051 TYPICAL DETAILS - STEEL

21 SA052 TYPICAL DETAILS - CFMF

22 SA053 TYPICAL DETAILS - CFMF

23 SS101 SERVICE YARD PLAN/DETAILS

24 SD101 GROUND FLOOR DEMO PLAN

25 SD102 FIRST FLOOR DEMO PLAN

26 SB101 GROUND FLOOR/FOUNDATION PLAN

27 SB301 FOUNDATION DETAILS

28 SF102 FIRST FLOOR FRAMING PLAN

29 SF103 ROOF FRAMING PLAN

30 SF301 EXISTING BUILDING SECTIONS

31 SF501 FRAMING DETAILS

32 SF510 MECHANICAL PENTHOUSE PLAN

[04] ARCHITECTURAL

33 AD111 PHASE ONE - DEMOLITION PLANS

34 AD112 PHASE ONE - DEMOLITION REFLECTED CEILING PLANS

35 AD113 PHASE ONE - DEMOLITION EXTERIOR ELEVATIONS

36 AD121 PHASE TWO & THREE - DEMOLITION PLANS

37 AD122 PHASE TWO & THREE- DEMOLITION REFLECTED CEILING PLANS

38 AD123 PHASE TWO - DEMOLITION EXTERIOR ELEVATIONS

39 AE001 PARTITION TYPES

40 AE101 OVERALL REFERENCE PLAN - GROUND FLOOR

41 AE102 OVERALL REFERENCE PLAN - FIRST FLOOR

42 AE111 PHASE ONE - REFERENCE PLANS

43 AE112 PHASE ONE - DIMENSION PLANS

44 AE113 PHASE ONE - ROOF PLANS

45 AE114 PHASE ONE - REFLECTED CEILING PLANS

46 AE115 PHASE ONE - EQUIPMENT PLANS

47 AE121 PHASE TWO & THREE- REFERENCE PLANS

48 AE122 PHASE TWO & THREE - DIMENSION PLANS

49 AE123 PHASE TWO & THREE - REFLECTED CEILING PLANS

50 AE124 PHASE TWO & THREE - EQUIPMENT PLANS

51 AE125 PHASE FOUR - EXTERIOR SERVICE YARD PLAN, SECTION, AND ELEVATION

52 AE301 BUILDING SECTIONS

53 AE311 WALL SECTIONS

54 AE401 PHASE ONE - ENLARGED PLANS & INTERIOR ELEVATIONS

55 AE402 PHASE ONE - ENLARGED PLANS & INTERIOR ELEVATIONS

56 AE403 PHASE ONE - ENLARGED PLANS & INTERIOR ELEVATIONS

57 AE404 PHASE ONE - ENLARGED PLANS & INTERIOR ELEVATIONS

BID DEDUCT:

THE ADDITION AND REMODEL OF THE FIRST FLOOR SPECIALTY CARE UNIT IN BOTH THE INFILL AND RENOVATION PORTION OF THE PROJECT WILL BE USED TO MEET 20% OF THE TOTAL CONSTRUCTION COST AS

REQUIRED. BELOW IS A BREAKDOWN AS TO HOW IT AFFECTS EACH PHASE OF WORK:

• PHASE 1

1. AS A PART OF PHASE 1, THE COURTYARD INFILL STRUCTURE AND ENVELOPE AT EACH LEVEL WILL BE CONSTRUCTED WITH OR WITHOUT THE INCLUSION OF THE BID DEDUCT.

2. WITH THE BID DEDUCT, ALL INTERIOR WORK OF THE INFILL SCOPE FOR THE FIRST FLOOR SPECIALTY CARE ARE NOT BE CONSTRUCTED EXCEPT METAL STUD AND GYPSUM BOARD AT EXTERIOR WALL LOCATIONS THROUGHOUT THE SPACE. ADDITIONALLY, ALL PENETRATIONS AND SHAFTS FROM THE GROUND FLOOR TO THE ROOF ARE TO BE CONSTRUCTED. CHASES ARE TO BE PROVIDED WITHIN THE SPACE WHERE MECHANICAL AND PLUMBING EQUIPMENT NEED TO EXTEND FROM THE FIRST FLOOR UP THRU THE ROOF.

3. THE FIRST FLOOR SPECIALTY CARE SPACE IS THEN TO BE CONSIDERED “WARM SHELL SPACE”, WHICH MEANS THE SPACE WOULD BE FITTED WITH BASIC SERVICES (ACOUSTICAL CEILING, MINIMAL LIGHTING, MINIMAL PLUMBING, AND MINIMAL HVAC). THIS WOULD NOT INCLUDE INTERIOR WALLS, FLOORING, OR NEW EQUIPMENT FOR THIS AREA.

• PHASE 2

1. AS PART OF PHASE 2, ALL INTERIOR WORK WITHIN THE RENOVATION SCOPE FOR THE FIRST FLOOR SPECIALTY CARE ARE NOT TO BE CONSTRUCTED EXCEPT METAL STUD AND GYPSUM BOARD AT

EXTERIOR WALL LOCATION THROUHGOUT THE SPACE. NO WORK IS TO BE DONE TO THE EXISTING SPECIALTY CARE UNIT ON THE FIRST FLOOR. THIS WOULD INCLUDE THE REMODEL AS WELL AS NO NEW

EQUIPMENT FOR THE SPACE.

NO. REVISION DESCRIPTION DATE

ABBREVIATIONS CODES STANDARDS AND EXECUTIVE ORDERS

TOILET ROOM TURNING

RADIUS

CLEAR FLOOR SPACE

@ WATER CLOSET

5'-6"

6' -0

2'-6"

4' -0

2'-6"

4' -0

FIXTURE MOUNTING HEIGHTS AND CLEARANCES

18" MIN

M

IN

FRONT APPROACH,

PULL SIDE

36" MIN

M

IN

HINGE APPROACH,

PULL SIDE

HINGE APPROACH,

PULL SIDE

*12" MIN

M

IN

FRONT APPROACH,

PUSH SIDE

M

IN

HINGE APPROACH,

PUSH SIDE

22" MIN 24" MIN

*4 8"

M

IN

LATCH APPROACH,

PULL SIDE

24" MIN*4

2"

M

IN

LATCH APPROACH,

PUSH SIDE

*IF BOTH CLOSER

AND LATCH ARE

PROVIDED

*54" MIN IF CLOSER

IS PROVIDED

*48" IF CLOSER IS

PROVIDED

FRONT APPROACH,

PUSH SIDE

M

IN

42" MIN

M

IN

DOOR AND FIXTURE CLEARANCES

MATERIALS LEGEND

PURPOSE: THE PUBLIC BUILDINGS AMENDMENT ACT OF 1988, PUBLIC LAW (PUB. L.) 100-678 REQUIRES FEDERAL AGENCIES TO FOLLOW NATIONAL RECOGNIZED "MODEL" BUILDING CODES. THE FEDERAL PARTICIPATION IN THE DEVELOPMENT AND USE OF VOLUNTARY STANDARDS, OFFICE OF MANAGEMENT AND BUDGET (OMB) CIRCULAR A-119, REQUIRES ALL EXECUTIVE AGENCIES TO RELY ON VOLUNTARY STANDARDS, BOTH DOMESTIC AND INTERNATIONAL, WHENEVER FEASIBLE, AND TO PARTICIPATE IN VOLUNTARY STANDARD BODIES.

GENERAL: VA HAS ADOPTED THE LATEST EDITION OF THE FOLLOWING CODES AND STANDARDS AS A MINIMUM FOR ALL PROJECTS PERFORMED IN THE MODERNIZATION, ALTERATION, ADDITION, OR IMPROVEMENT OF ITS REAL PROPERTY AND THE CONSTRUCTION OF NEW STRUCTURES. VA DESIGN MANUALS AND MASTER SPECIFICATIONS SPECIFY OTHER CODES AND STANDARDS THAT VA FOLLOWS ON ITS PROJECTS:

• VA DIRECTIVES, DESIGN MANUALS, MASTER SPECIFICATIONS, VA NATIONAL CAD STANDARD APPLICATION GUIDE, AND OTHER GUIDANCE ON THE

TECHNICAL INFORMATION LIBRARY (TIL) (HTTP://WWW.CFM.VA.GOV/TIL/).

• 2021 INTERNATIONAL BUILDING CODE (IBC) (ONLY WHEN SPECIFICALLY REFERENCED IN VA DESIGN DOCUMENTS, SEE NOTES BELOW)

• 2021 INTERNATIONAL EXISTING BUILDING CODE (IEBC) (IF APPLICABLE)

• 2021 NFPA 101 LIFE SAFETY CODE (SEE NOTES BELOW)

• 2021 INTERNATIONAL FIRE CODE

• 2021 NFPA 5000 BUILDING CONSTRUCTION AND SAFETY CODE

• 2019 NFPA 900 BUILDING ENERGY CODE

• OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION (OSHA) STANDARDS.

• 2020 VA SEISMIC DESIGN REQUIREMENTS, H-18-8

• 2020 NATIONAL ELECTRICAL CODE (NEC)

• 2021 INTERNATIONAL PLUMBING CODE (IPC)

• 2016 SAFETY CODE FOR ELEVATORS AND ESCALATORS, AMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME) A 17.1.

• 2015 ARCHITECTURAL BARRIERS ACT (ABA) STANDARDS INCLUDING VA SUPPLEMENT, VA BARRIER FREE DESIGN STANDARD (PG-18-13)

• 2017 ANSI ICC A117.1 ACCESIBLE AND USABLE BUILDINGS AND FACILITIES

• 2019 BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE AND COMMENTARY, AMERICAN CONCRETE INSTITUTE AND COMMENTARY (ACI 318-19)

• 2017 STEEL CONSTRUCTION MANUAL (15TH EDITION), AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC)

• ENERGY POLICY ACT OF 2005 (EPACT)

• 2007 DOE INTERIM FINAL RULE: ENERGY CONSERVATION STANDARDS FOR NEW FEDERAL, COMMERCIAL AND MULTI-FAMILY HIGH-RISE RESIDENTIAL

BUILDINGS AND NEW LOW-RISE RESIDENTIAL BUILDINGS, 10 CFR PARTS 433, 434 AND 435.

• 2006 FEDERAL LEADERSHIP IN HIGH PERFORMANCE AND SUSTAINABLE BUILDINGS: MEMORANDUM OF UNDERSTANDING (MOU)

• 2018 EXECUTIVE ORDER 13834: EFFICIENT FEDERAL OPERATIONS

• 2021 THE PROVISIONS FOR CONSTRUCTION AND SAFETY SIGNS. STATED IN THE GENERAL REQUIREMENTS SECTION 010000 OF THE VA MASTER

CONSTRUCTION SPECIFICATION.

• 2019 VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY – ASHRAE STANDARD 62.1

• 2019 SAFETY STANDARD FOR REFRIGERATION SYSTEMS – ASHRAE STANDARD 15

LOCAL CODES: AS AN AGENCY OF THE FEDERAL GOVERNMENT, VA IS NOT SUBJECT TO LOCAL IMPOSITION OF CODE ENFORCEMENT PROCEDURES (DRAWING REVIEWS, BUILDING PERMITS, INSPECTIONS, FEES, ETC.). VA MUST FUNCTION AS THE AUTHORITY HAVING JURISDICTION (AHJ) AND THUS HAS THE RESPONSIBILITY TO GUARD PUBLIC HEALTH AND SAFETY THROUGH ENFORCING ITS ADOPTED CODES. HOWEVER, LOCAL AUTHORITIES SHOULD BE NOTIFIED ABOUT PLANNED PROJECTS AND GIVEN OPPORTUNITY TO REVIEW DRAWINGS PROVIDED THAT VA DOES NOT PAY FOR REVIEW OR INSPECTION FEES.

NOTES:

1. NFPA 101 PRIMARILY ADDRESSES LIFE SAFETY AND FIRE PROTECTION FEATURES WHILE THE IBC ADDRESSES A WIDE RANGE OF CONSIDERATIONS, INCLUDING, BUT NOT LIMITED TO, STRUCTURAL STRENGTH, SEISMIC STABILITY, SANITATION, ADEQUATE LIGHT AND VENTILATION, AND ENERGY CONSERVATION. VA BUILDINGS MUST MEET THE REQUIREMENTS OF NFPA 101 AND DOCUMENTS REFERENCED BY NFPA 101 IN ORDER TO COMPLY WITH THE ACCREDITATION REQUIREMENTS OF THE JOINT COMMISSION. THEREFORE, DESIGNS SHALL COMPLY WITH THE REQUIREMENTS OF THE LATEST EDITION OF NFPA 101 AND DOCUMENTS REFERENCED THEREIN. DESIGN FEATURES NOT ADDRESSED BY NFPA 101 OR DOCUMENTS REFERENCED THEREIN SHALL COMPLY WITH THE REQUIREMENTS OF THE LATEST EDITION OF THE IBC OR AS OTHERWISE ADDRESSED ABOVE IN THIS PROGRAM GUIDE.

FOR DESIGN FEATURES THAT ARE ADDRESSED BY BOTH THE IBC AS WELL AS NFPA 101 OR A DOCUMENT REFERENCED BY NFPA 101, THE REQUIREMENTS OF NFPA 101 OR THE DOCUMENT REFERENCED BY NFPA 101 SHALL BE USED EXCLUSIVELY (THIS APPLIES EVEN IF THE IBC REQUIREMENTS ARE

DIFFERENT).

2. CONFLICTS BETWEEN NATIONALLY RECOGNIZED CODES AND STANDARDS AND VA REQUIREMENTS – SHOULD A CONFLICT EXIST BETWEEN VA REQUIREMENTS AND VA ADOPTED NATIONALLY RECOGNIZED CODES AND STANDARDS, THE CONFLICT SHALL BE BROUGHT TO THE ATTENTION OF VA.

THE RESOLUTION OF THE CONFLICT SHALL BE MADE BY THE AUTHORITY HAVING JURISDICTION FOR VA TO ENSURE A CONSISTENCY SYSTEM WIDE.

ASHRAE 90.1 - 2019 EDITION

BUILDING LOCATION: WITCHITA, KS

CLIMATE ZONE (TABLE ANNEX 1-1): ZONE 4A

INTERIOR DESIGN CONDITIONS:

THE INTERIOR DESIGN TEMPERATURES FOR HEATING AND COOLING AS DEPICTED IN THE PROJECT DESIGN CONDITIONS SCHEDULE IN THE MECHANICAL CONTROL DRAWINGS SHALL BE THE MAXIMUM AND MINIMUM

VALUES FOR THE ASSOCIATED TEMPERATURE CONTROL ZONES.

BUILDING ENVELOPE REQUIREMENTS (TABLE 5.5-4):

ROOFS: REQUIRED: DESIGNED:

INSULATION ABOVE DECK R-30 c.i. R-30 c.i.

METAL BUILDINGS: R-19 + R-11 Ls or R-25 + R-8 Ls N/A

ATTIC AND OTHER: R-49 N/A

WALLS, ABOVE GRADE

MASS: R-9.5 c.i. N/A METAL BUILDING: R-0 + R-15.8 c.i. N/A STEEL-FRAMED: R-13 + R-7.5 c.i. R-13 + R-9 c.i.

WOOD-FRAMED AND OTHER: R-13 + R-3.8 c.i. or R-20 N/A

WALL, BELOW GRADE

BELOW-GRADE WALL: R-7.5 c.i. N/A

FLOORS

MASS: R-14.6 c.i. N/A

STEEL-FRAMED: R-30 N/A

WOOD-FRAMED AND OTHER: R-30 N/A

SLAB-ON-GRADE FLOORS

UNHEATED SLABS: R-15 FOR 24 in. N/A HEATED SLABS: R-20 for 24 in. N/A

OPAQUE DOORS

SWINGING: U-0.370 N/A

NONSWINGING: U-0.310 N/A

VERTICAL FENESTRATION, U-FACTOR

NON-METAL FRAMING (ALL): U-0.31 N/A

METAL FRAMING, FIXED: U-0.36 N/A

METAL FRAMING, OPERABLE: U-0.45 N/A

METAL FRAMING, ENTRANCE DOOR: U-0.63 N/A

SKYLIGHT, 0% TO 3% OF ROOF, U-FACTOR

ALL TYPES: U-0.50 N/A

ENERGY REQUIREMENTS

N

1. DRAWINGS ARE PART OF A COMPLETE DOCUMENTS SET. CONTRACTOR SHALL

CONFIRM ALL ITEMS REQUIRED BASED UPON THE OVERALL DESIGN INTENT OF

THE ENTIRE DOCUMENT SET.

2. CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS, PRIOR TO BEGINNING

ANY WORK, TO CONFIRM THE ACCURACY OF THE DRAWINGS AND REPORT ANY

DISCREPANCIES TO THE ARCHITECT. DO NOT SCALE THE DRAWINGS. FIELD

VERIFY ALL DIMENSIONS AND EXISTING STRUCTURAL CONDITIONS.

3. ALL AREAS NOT INVOLVED IN THE SCOPE OF WORK FOR THIS PROJECT SHALL BE

KEPT CLEAN AND FREE OF OBSTRUCTIONS AT ALL TIMES.

4. ERECT BARRICADES AND WARNING SIGNS TO DIVERT AND WARN PASSERS-BY OF

THE CONSTRUCTION WORK. PROVIDE DUST PROOFING ENCLOSURES TO

SEPARATE WORK AREAS FROM THE EXISTING FACILITIES.

5. ALL TRASH AND DEBRIS TO BE REMOVED ON A DAILY BASIS.

6. PROVIDE PROTECTION FOR ALL EXISTING SURFACES AND CONDITIONS TO

REMAIN IN PLACE DURING THE SCOPE OF WORK. SHOULD ANY DAMAGE OCCUR,

PATCH AND REPAIR ANY DAMAGE TO ADJACENT FINISHES TO MATCH EXISTING.

7. ANY DAMAGE CAUSED TO THE BUILDING OR OWNER EQUIPMENT SHALL BE

REPAIRED OR REPLACED BACK TO ITS ORIGINAL CONDITIONS AT NO ADDITIONAL

COST TO THE OWNER.

8. COVER ALL RETURN AIR GRILLES WITHIN THE AREA OF CONSTRUCTION TO

PREVENT PARTICULATE MATERIAL FROM EXHAUSTING INTO SURROUNDING

SPACES.

9. APPROPRIATE LIGHT FIXTURES SHALL BE TEMPORARILY SUSPENDED TO

PROVIDE ADEQUATE LIGHTING LEVELS FOR CONSTRUCTION.

10. CONTRACTOR AND SUBCONTRACTORS ARE REQUIRED TO COORDINATE WITH

OTHER DISCIPLINES TO INSTALL COMPLETE AND OPERATIONAL SYSTEMS.

DRAWINGS, AS A WHOLE, REPRESENT A COMPLETE SET AND DEPICT

REQUIREMENTS FOR COMPLETE AND OPERATIONAL SYSTEMS. INDIVIDUAL

DRAWINGS MAY NOT DEPICT COMPLETE AND ACCURATE INFORMATION TO

COORDINATE COMPLETE AND OPERATIONAL SYSTEMS, BUT DO SO AS AN ENTIRE

DOCUMENT TO BE REFERENCED WITH OTHER INDIVIDUAL DRAWINGS.

CONTRACTOR AND SUBCONTRACTORS ARE REQUIRED TO REFERENCE OTHER

SHEETS AND SPECIFICATIONS AS AN ENTIRE SET OF CONSTRUCTION

DOCUMENTS THAT REFLECT WORK REQUIRED TO ACHIEVE A COMPLETE AND

OPERATIONAL GOAL. LACK OF COORDINATION AND REVIEW OF DRAWINGS AND

SPECIFICATIONS AS AN ENTIRE DOCUMENT TO INSTALL COMPLETE AND

OPERATIONAL SYSTEMS, BEING OBVIOUS AND TYPICAL INDUSTRY STANDARD,

IDENTIFIED IN THE DRAWINGS AND SPECIFICATIONS, SHALL NOT BE IN ANY WAY

AN ADDITIONAL COST TO THE GOVERNMENT.

11. CONTRACTOR SHALL SUBMIT A REQUEST, IN WRITING, TO INTERRUPT ANY SUCH

SERVICES TO COR (CONTRACTING OFFICER’S REPRESENTATIVE) 48 HOURS IN

ADVANCE OF PROPOSED INTERRUPTION. REQUEST SHALL STATE REASON, DATE,

EXACT TIME OF, AND APPROXIMATE DURATION OF SUCH INTERRUPTION. MAJOR

INTERRUPTIONS OF ANY SYSTEM MUST BE REQUESTED, IN WRITING, AT LEAST 60

CALENDAR DAYS PRIOR TO THE DESIRED TIME AND SHALL BE PERFORMED AS

DIRECTED BY THE COR. MAJOR INTERRUPTIONS SHALL BE COORDINATED WITH

OTHER MAJOR INTERRUPTIONS AND MAY NOT BE SCHEDULED FOR ONE

DISCIPLINE MORE THAN TWICE THROUGHOUT THE OVERALL CONSTRUCTION

SCHEDULE UNLESS REQUESTED IN WRITING AND APPROVED BY THE COR.

CONTRACTOR WILL BE ADVISED, IN WRITING, OF APPROVAL OF REQUEST, OR OF

WHICH OTHER DATE AND/OR TIME SUCH INTERRUPTION WILL CAUSE THE LEAST

INCONVENIENCE TO OPERATIONS OF THE MEDICAL CENTER. INTERRUPTION TIME

APPROVED BY THE MEDICAL CENTER MAY OCCUR AT TIMES OTHER THAN

CONTRACTOR'S NORMAL WORKING HOURS. SCHEDULE INTERRUPTION MAY BE

ON WEEKENDS OR LATE HOURS AND MAY NOT BE AN ADDITIONAL COST TO THE

GOVERNMENT. COORDINATE ALL INTERRUPTIONS THAT MAY AFFECT THE

NORMAL OPERATION OF THE FACILITY WITH THE COR WHEN SUBMITTING THE

CONSTRUCTION SCHEDULE OR UPDATES TO THE CONSTRUCTION SCHEDULE.

12. NO ASBESTOS CONTAINING MATERIALS ARE TO BE USED ON THIS PROJECT.

SPUR DESIGN, THE A/E OF RECORD, CAN CERTIFY THAT NO ASBESTOS

CONTAINING BUILDING MATERIALS (ACBM) OR LEAD BASED PAINT (LBP)

PRODUCTS WERE DESIGNED/SPECIFIED AS BUILDING MATERIAL IN ANY OF THE

CONSTRUCTION DOCUMENTS.

13. ONCE EACH FLOOR OF THE COURTYARD INFILL PORTION OF THE SCOPE OF

WORK IS ENCLOSED, ALL CONNECTIONS, PENETRATIONS, AND OPENINGS

BETWEEN THE INFILL SCOPE OF WORK AND THE EXISTING BUILDING ARE TO BE

SEPARATED BY A 1 HOUR FIRE BARRIER. 1 HOUR FIRE BARRIER TO REMAIN AT

ALL CONNECTIONS, PENETRATIONS, AND OPENINGS UNTIL FIRE SUPPRESSION

SYSTEM IS INSTALLED AND OPERABLE.

13. REFER TO THE DESIGN BINDER FOR ICRA INFORMATION DOCUMENTATION.

GENERAL NOTES

AREA NAME

150 SF

A101

A101

SIM

00000

00.0

A101

1 1

A101

LEVEL NAME

00'-00"

00'-00"

4B

3A

ROOM NAME

000A

150 SF

/1 A101 X0000

ROOM TAG

AREA TAG

SPECIALTY EQUIPMENT TAG

DOOR TAG

KEYED NOTE TAG

WALL TAG

WINDOW TAG

A101

SIM

A101

SIM

REFERENCE SYMBOLS IDENTIFICATION TAGS

NOTE: NOT ALL ABBREVIATIONS OR SYMBOLS WILL BE UTILIZED FOR THIS PROJECT.

GRID HEAD AND

LINE

LEVEL INDICATOR

MATCH LINE AND

VIEW REFERENCE

NORTH ARROW W/

PROJECT NORTH

SPOT ELEVATION

DETAIL

SECTION

**48" MIN IF BOTH CLOSER

AND LATCH PROVIDED

WALL

SECTION

BUILDING

SECTION

DETAIL

ELEVATION

INTERIOR

ELEVATION

BUILDING

ELEVATION

1 1

6'- 0"

5'- 6"

BARIATRIC TOILET ROOM

TURNING RADIUS

CLEAR FLOOR SPACE

@ ADA LAVATORY

CLEAR FLOOR SPACE

@ ADA DRINKING

FOUNTAIN

4' -0

M

A X

4' -0

M

A X

2' -1

0" M

A X

2' -3

M

IN

1'-6" MIN

1. GENERAL CONTRACTOR TO PROVIDE METAL SUPPORT

BLOCKING FOR ALL WALL MOUNTED ACCESSORIES,

FIXTURES, AND EQUIPMENT.

2. PROVIDE ADA SUPPORT BRACKETS PLACED AT ALL OPEN

COUNTERTOPS - 36"-48" MAX ON CENTER.

3. SPECIFIED MAXIMUMS ARE MEASURED FROM AFTER

FINISHED FLOOR TO THE OPERABLE PART OF THE FIXTURE.

4. FIXTURES SHOWN ARE REPRESENTATIONAL ONLY. NOT ALL

FIXTURES MAY BE USED. REFER TO SPECIFICATIONS FOR

FIXTURE TYPES USED IN THIS PROJECT.

5. FIXTURES MAY OVERLAP WAINSCOT. WHERE APPLICABLE,

BACKING TO BE PROVIDED AS SHIM FOR FLUSH

APPLICATION. SHIM TO MATCH SCHEDULED WALL FINISH.

6" MAX

9" M

IN

SHOWER

DRINKING

FOUNTAIN

PAPER TOWEL

DISPENSER

SANITARY

NAPKIN

DISPENSER

4' -0

"M A

X

WASTE

RECEPTACLE

LAVATORY

WITH MIRROR

ON CENTER

WALL

4' -0

M

A X

SOAP

DISPENSER

2' -1

0" M

A X

T O

B .O

. R E

F

LE

C T

IV

E

S U

R F

A C

E

3' -4

M

A X

17 MIN

2' -3

M

IN

3' -0

M

A X

1'-6" MIN

WALL

2' -9

" 4' -0

M

IN

2'-0" MIN

8" MIN

WALL

LAVATORY

WITH APRON

1' -5

M

A X

1'-6" MIN

URINAL

WALL

1'-5" - 1'-7" (AMBULATORY)

1'-4" - 1'-6" (WHEELCHAIR)

CLEAR FLOOR

5'-6"

CLEAR FLOOR

6'-0"

3'-0" MIN

2' -9

3' -0

1'-0" MIN

3'-6" MIN 1'-0"MAX

4'-6" MIN

1' -5

'-7

1' -6

M

IN

A N

S I I

C C

A

7.

1)

1' -3

M

IN

A D

A /A

B A

2' -9

'-0

WALL

WALL

4' -0

M

A X

WALL HOOK

6' -6

CLOCK

WALL

FINISHED FLOOR

FIRE EXTINGUISHER

CABINET

WEIGHT > 40LBS

FIRE EXTINGUISHER

CABINET

WEIGHT < 40LBS

4' -0

"M A

X

4' -0

M

A X

TOILET SEAT

COVER

DISPENSER

BABY

CHANGING

STATION

HANDRAILS AND

BUMPERGUARDS

6"

3' -0

M

A X

4"

6"

3"

6"

M

IN

1' -6

6" MAX

7" - 9" 11" MIN

17" - 25"

(ANSI ICC A117.1)

39"- 41"

(A N

S I I

C C

A

7.

1)

M

IN

(A N

S I I

C C

A

7.

1)

1"

3' -6

M

A X

5' -0

M

A X

FIBERGLASS BATT

INSULATION

RIGID INSULATION

CONCRETE / PRECAST

CONCRETE

EARTH / SOIL

SAND, EIFS FINISH, OR

PLASTER FINISH

GYPSUM BOARD FINISH

BRICK

CONCRETE MASONRY

UNIT

STONE / CAST STONE

GYPSUM BOARD SECTION

EXTERIOR SHEATHING

BOARD SECTION

PLYWOOD SECTION

A

ACB ACOUSTIC CEILING BAFFLE

ACP ACOUSTIC CEILING PANEL

ACST ACOUSTIC

ADA AMERICANS WITH DISABILITIES ACT

ACT ACOUSTICAL CEILING TILE

ADDL ADDITIONAL

ADDN ADDITION

ADJ ADJACENT, ADJOINING, OR

ADJUSTABLE

ADMIN ADMINISTRATION

AE ARCHITECT/ENGINEER

AF ACCESS FLOORING

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AHJ AUTHORITY HAVING JURISDICTION

AIA AMERICAN INSTITUTE OF

ARCHITECTS

ALT ALTERNATE

ALT NO ALTERNATE NUMBER

ALUM ALUMINIUM (TRIM)

AMT AMOUNT

APPROX APPROXIMATE

ARCH ARCHITECT

ASC ABOVE SUSPENDED CEILING

AT ACOUSTIC CEILING TILE

AVG AVERAGE

B

BD BOARD

BLDG BUILDING

BLKG BLOCKING

BLT IN BUILT-IN

BOS BOTTOM OF STEEL

BOT BOTTOM

BRKT BRACKET

BTWN BETWEEN

C

CAB CABINET

CAV CAVITY

CBB CONCRETE BACKER BOARD

CD CONSTRUCTION DOCUMENTS

CFM CUBIC FEET PER MINUTE

CFS CUBIC FEET PER SECOND

CG CORNER GUARD

CH BD CHALK BOARD

CIP CAST-IN-PLACE

CJ CONTROL JOINT

CL CENTER LINE

CLG CEILING

CLG HT CEILING HEIGHT

CLR CLEAR

CMU CONCRETE MASONRY UNIT

CO CONTRACTING OFFICER

COL COLUMN

COMM COMMUNICATION

CONC CONCRETE

CONT CONTINUOUS

COORD COORDINATE

COR CONTRACTING OFFICER'S

REPRESENTATIVE

CP CONTRACTOR PROVIDED

CP/CI CONTRACTOR PROVIDED /

CONTRACTOR INSTALLED

CPT CAROET/CARPET TILE

CS CONCRETE SEALED

CSWK CASEWORK

CT CERAMIC TILE

CTB CERAMIC TILE BASE

CTR CENTER

CU FT CUBIC FEET

D

DBL DOUBLE

DEMO DEMOLITION

DEPT DEPARTMENT

DET DETAIL

DIA DIAMETER

DIR DIRECTION

DIST DISTANCE

DOC DOCUMENT

DR DOOR

DS DOWNSPOUT

DWG DRAWING

DWP DIMENSIONAL WALL PANEL

E

EA EACH

EJ EXPANSION JOINT

EL ELEVATION

ELEV ELEVATOR

ENTR ENTRANCE

EPY EPXOY FLOORING

EQ EQUAL

ETR EXISTING TO REMAIN

EX EXISTING

EXP EXPOSED

EXT EXTERIOR

F

FAB FABRIC

FED FEDERAL

FF FINISH FACE

FF EL FINISH FLOOR ELEVATION

FIN FINISH

FIN BS FINISH BOTH SIDES

FIN FLR FINISH FLOOR

FIN GR FINISH GRADE

FIXT FIXTURE

FLDG FOLDING

FLEX FLEXIBLE

FLG FLOORING

FLMT FLUSH MOUNT

FLR FLOOR

FOC FACE OF CONCRETE

FOM FACE OF MASONRY

FP FIRE PROTECTION

FR FIRE RESISTANT

FT FEET

FTG FOOTING

FV FIELD VERIFY

FWC FABRIC WALL COVERING

G

GDR GUARDRAIL

GL GLASS/GLAZING

GRAN GRANITE

GR FL GROUND FLOOR

GT GROUT

GSM GALVANIZED SHEET METAL

GYP BD GYPSUM BOARD

H

HDW HARDWARE

HEPA HIGH EFFICIENCY

PARTICULATE AIR (FILTER)

HM HOLLOW METAL

HORIZ HORIZONTAL

HR HANDRAIL

HT HEIGHT

I

IBC INTERNATIONAL BUILDING CODE

INSUL INSULATION

INT INTERIOR

ILO IN LIEU OF

J

J-BOX JUNCTION BOX

L

LAV LAVATORY

LBS POUND

LDG LANDING

LF LINEAR FEET (FOOT)

LIN LINEAR

LN LINOLEUM

LOC LOCATION

LT LIGHT

LVR LOUVER

LVT LUXURY VINYL TILE

M

MAT CARPET MAT / WALK-OFF MAT

MATL MATERIAL

MAX MAXIMUM

MECH MECHANICAL

MEMB MEMBRANE

MFR MANUFACTURER

MID MIDDLE

MIL STD MILITARY STANDARD

MIN MINIMUM

MISC MISCELLANEOUS

MO MASONRY OPENING

MOD MODIFY

MTG MOUNTING

MTL METAL

MVBL MOVABLE

N

NA NOT APPLICABLE

NIC NOT IN CONTRACT

NO NUMBER

NOM NOMINAL

NTS NOT TO SCALE

O

OA OVERALL

OC ON CENTER

OD OUTSIDE DIAMETER

OPNG OPENING

OPP OPPOSITE

OPR OPERABLE

ORD OVERFLOW ROOF DRAIN

ORIG ORIGINAL

P

P PAINT

PA PUBLIC ADDRESS

PBD PARTICLE BOARD

PCF POUNDS PER CUBIC FOOT

PCT PERCENT

PERF PERFORATED

PERIM PERIMETER

PERP PERPENDICULAR

PL PROPERTY LINE

PLAM PLASTIC LAMINATE

PLBG PLUMBING

PNL PANEL

PR PAIR

PRB PROFILE BASE

PRKG PARKING

PSF POUNDS PER SQUARE FOOT

PSI POUNDS PER SQUARE INCH

PT PORCELAIN TILE

PWR POWER

Q

QA QUALITY ASSURANCE

QC QUALITY CONTROL

QTY QUANTITY

R

RAF RESILIENT ATHETIC FLOORING

RB RUBBER BASE/RESILIENT BASE

RCP REFLECTED CEILING PLAN

RD ROOF DRAIN

REC RECESSED

REF REFERENCE

REM REMOVABLE

REP REPAIR

REPL REPLACE

REQ REQUIRE

REQD REQUIRED

RES RESINOUS FLOORING

RES-W RESINOUS / EPOXY

WALL / CEILING

RF RUBBER FLOORING

RFG ROOFING

RM ROOM

RO ROUGH OPENING

RP RESIN PANEL

RSF RESILIENT SHEET FLOORING

RV ROOF VENT

RWC RIGID VINYL WALLCOVERING

S

SC SPECIALTY COATING

SD STATIC DISSIPATIVE

FLOORING/TILE

SCHED SCHEDULE

SECT SECTION

SF SQUARE FOOT (FEET)

SGL SINGLE

SIM SIMILAR

SJ SCORED JOINT

SLNT SEALANT

SM SHEET METAL

SPEC SPECIFICATION

SQ SQUARE

SQ IN SQUARE INCH

SQ YD SQUARE YARD

SS SOLID SURFACE

ST STONE

STD STANDARD

STOR STORAGE

SV SHEET VINYL (ROLLED OR TILE)

T

TEL TELEPHONE

TEMP TEMPORARY

TER TERRAZO

TOF TOP OF FOOTING/ FOUNDATION

TOM TOP OF MASONRY

TOS TOP OF SLAB/ STEEL

U

UNO UNLESS NOTED OTHERWISE

UTIL UTILITY

V

VAR VARIES

VC VA PROVIDED / CONTRACTOR

INSTALLED

VCT VINYL COMPOSITION TILE

VFAT VINYL FACED ACOUSTICLAL TILE

VP VENEERED PLASTER

VT VINYL TILE

VV VA PROVIDED / VA INSTALLED

VWC VINYL WALLCOVERING

VWF VINYL WALL FABRIC

W

W/ WITH

W/O WITHOUT

W/C WATER CLOSET

WC WHEELCHAIR

WD WOOD

WFAB WALL FABRIC

WPM WATERPROOF MEMBRANE

WSF WELDED SHEET FLOOR

X

X BRACE CROSS BRACE

PROJECT SCOPE LEGEND

AREAS OF WORK OUTSIDE OF

CURRENT PHASE OR OUTSIDE

OF PROJECT SCOPE.

PLAN NORTH

TRUE NORTH

1'-3" th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

KS ARCH REG. NO. A-930, EXP. 12/31/2023

KS ENGR REG. NO. E-2586, EXP. 12/31/2023

STRUCTURAL / CIVIL ENGINEER

H2B, INC.

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECH / ELEC / PLUMB / TECH ENGR

SPUR DESIGN

25219 MADISON AVENUE, SUITE 100

KANSAS CITY, MO 64108

(913) 369-7200

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT HEALTH & SAFETY

1139 OLIVE STREET,

ST. LOUIS, MO 63101

(314) 436-9492

HEALTHCARE PLANNER

INNOVA GROUP

3196 N. SWAN ROAD

TUCSON, AZ 85712

(520) 886-8650

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH ROAD, STE 1415

PANAMA CITY, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:SPUR #: 2016

/2

/2

:5 :0

A

M

GI001

GENERAL INFORMATION

ECO

2 OF 190AJS

100% BID SET

CONSTRUCT INFILL OF

BUILDING 26 AND RENOVATE

SPECIALTY CARE CLINICS

12/21/2022

589-704

5500 EAST KELLOGG AVENUE

WICHITA, KANSAS 67218

DN

A

UP

PHASE 1 - INFILL STRUCTURE AND NEW CONSTRUCTION

PHASE 2 - CONSTRUCT

SPECIALTY CARE RENOVATION

BLDG 61

BLDG 29BLDG 62

B

B62

B

B

B

B

B

B

B

B29

B3

BLDG 26

PHASING PLAN LEGEND

PHASE 1 - NEW INFILL CONSTRUCTION & LIMITED RENOVATION

• EXCAVATE COURTYARD IN PREPARATION FOR NEW CONSTRUCTION

• CONSTRUCT COURTYARD INFILL STRUCTURE AND SHELL FOR GROUND

FLOOR AND FIRST FLOOR

• CONSTRUCT NEW INTERIOR CONSTRUCTION & RENOVATION FOR

GROUND FLOOR CANTEEN

• CONSTRUCT NEW INTERIOR CONSTRUCTION FOR FIRST FLOOR

SPECIALTY CARE WITHIN NEW INFILL STRUCTURE (BID DEDUCT OPTION)

• CONSTRUCT LIMITED INTERIOR RENOVATION INCLUDING THE BUILDING

61 CONNECTING CORRIDOR

• REPLACE EMERGENCY GENERATOR

PHASE 2 - GROUND FLOOR AND FIRST FLOOR RENOVATION

• CONSTRUCT GROUND FLOOR DENTAL CLINIC RENOVATION

• CONSTRUCT FIRST FLOOR SPECIALTY CARE RENOVATION

(BID DEDUCT OPTION)

PHASE 3 - POLICE SUBSTATION

• CONSTRUCT GROUND FLOOR POLICE SUBSTATION

PHASE 4 - EXTERIOR IMPROVEMENTS SERVICE YARD

• CONSTRUCT NORTHEAST SERVICE YARD (OR MAINTENANCE FENCE IN

EVENT OF SERVICE YARD BID DEDUCT)

• REFERENCE SHEET AE201 FOR MORE INFORMATION AND FULL SCOPE

PHASE 1 - INFILL

STRUCTURE AND NEW

CONSTRUCTION

PHASE 1 - CONSTRUCT

CANTEEN RENOVATION SCOPE

PHASE 2 - CONSTRUCT DENTAL CLINIC RENOVATION

BLDG 61

BLDG 29BLDG 62

B

B62

B

B

B

B

B

B

B

B29

B3

BLDG 26

SERVICE

YARD

E001

PHASE 1

PHASE 3

PHASE 4

BLDG 26

TRUE NORTH

GROUND FLOOR CANTEEN (INFILL)

FIRST FLOOR SPECIALTY CARE (INFILL)

(BID DEDUCT OPTION)

BLDG 61

BLDG 61

BLDG 26

TRUE NORTH

GROUND FLOOR DENTAL CLINIC RENOVATION

FIRST FLOOR SPECIALTY CARE RENOVATION

(BID DEDUCT OPTION)

PHASING AND PROJECT SCOPE LEGEND

AREAS OF WORK OUTSIDE OF CURRENT PHASE OR OUTSIDE OF PROJECT

SCOPE SHOWN. REFERENCE GI011 - PHASING PLANS FOR MORE INFORMATION.

BLDG 61

BLDG 26

TRUE NORTH

GROUND FLOOR POLICE SUBSTATION RENOVATION

BLDG 61

BLDG 26

TRUE NORTH

GROUND FLOOR EXTERIOR SERVICE YARD

PHASE 4 - EXTERIOR SERVICE YARD

KEY PLAN - GROUND FLOOR & FIRST FLOOR

BLDG 26BLDG 61

BLDG 29

BLDG 03PHASE ONE

N

KEY PLAN - GROUND FLOOR AND FIRST FLOOR

BLDG 26

BLDG 61

BLDG 29

BLDG 03

PHASE TWO

N

PHASE THREE

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

KS ARCH REG. NO. A-930, EXP. 12/31/2023

KS ENGR REG. NO. E-2586, EXP. 12/31/2023

STRUCTURAL / CIVIL ENGINEER

H2B, INC.

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECH / ELEC / PLUMB / TECH ENGR

SPUR DESIGN

25219 MADISON AVENUE, SUITE 100

KANSAS CITY, MO 64108

(913) 369-7200

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT HEALTH & SAFETY

1139 OLIVE STREET,

ST. LOUIS, MO 63101

(314) 436-9492

HEALTHCARE PLANNER

INNOVA GROUP

3196 N. SWAN ROAD

TUCSON, AZ 85712

(520) 886-8650

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH ROAD, STE 1415

PANAMA CITY, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:SPUR #: 2016

/2

/2

:5 :1

A

M

GI011

PHASING PLANS

ECO

3 OF 190AJS

100% BID SET

CONSTRUCT INFILL OF

BUILDING 26 AND RENOVATE

SPECIALTY CARE CLINICS

12/21/2022

589-704

5500 EAST KELLOGG AVENUE

WICHITA, KANSAS 67218

N

1/16" = 1'-0"

FIRST FLOOR - PHASING PLAN - OVERALL2

N

1/16" = 1'-0"

GROUND FLOOR - PHASING PLAN - OVERALL1

PHASE 1 - NEW CONSTRUCTION & LIMITED RENOVATIONPHASE 2 - DENTAL CLINIC RENOVATIONPHASE 3 - POLICE SUBSTATION

ISOMETRIC PHASING DIAGRAMS3

FD

SFD

S

A

ASSEMBLY, CONCENTRATED

ASSEMBLY, KITCHEN

ASSEMBLY, LESS CONCENTRATED

BUSINESS

MERCANTILE, STREET FLOOR

STORAGE USE, OTHER

B61

B26

B3

B29

B62

BUSINESS

14560 SF

BUSINESS

4482 SF

ASSEMBLY, LESS

CONCENTRATED

2662 SF

ASSEMBLY, KITCHEN

1720 SF

STORAGE USE,

OTHER

528 SF

BUSINESS

295 SF

MERCANTILE, STREET

FLOOR

1591 SF

STORAGE USE,

OTHER

1791 SF

BUSINESS

22005 SF

BUSINESS

13686 SF

BUSINESS

7768 SF

STORAGE USE,

OTHER

441 SF

STORAGE USE,

OTHER

456 SF

STORAGE USE,

OTHER

238 SF

STORAGE USE,

OTHER

379 SF

STORAGE USE,

OTHER

298 SF

STORAGE USE,

OTHER

373 SF

STORAGE USE,

OTHER

292 SF

STORAGE USE,

OTHER

305 SF

B61 B26

B3

B29

B62

BUSINESS

9123 SF

ASSEMBLY,

CONCENTRATED

1542 SF

BUSINESS

11229 SF

BUSINESS

25449 SF

STORAGE USE,

OTHER

1147 SF

BUSINESS

10316 SF

BUSINESS

6032 SF

BUSINESS

673 SF

KEY PLAN

BLDG 26

BLDG 3 BLDG 1

BLDG 2BLDG 19

BLDG 61

BLDG 62

BLDG 29

N

PHASE FOUR

SERVICE YARD

EXISTING BUILDING HEIGHT: BUILDING 26

3 STORIES, APPROX. 35'-0" HEIGHT

BUILDING AREA:

AREA LIMITATION: 69,000 SQUARE FEET (2021 IBC TABLE 506.2)

GROUND FLOOR 22,720 GROSS SQUARE FEET

FIRST FLOOR 22,720 GROSS SQUARE FEET

SECOND FLOOR 17,590 GROSS SQUARE FEET

TOTAL 63,030 GROSS SQUARE FEET

NFPA 101-2021 CHAPTER 7- TABLE 7.3.1.2 OCCUPANT LOADS

NFPA 101-2021 CHAPTER 7- 7.2.1.2.3.2) MINIMIM DOOR LEAF WIDTH

MINIMUM DOOR OPENING WIDTH OF 32"

NFPA 101-2021 CHAPTER 7- TABLE 7.3.3.1 CAPACITY FACTORS

NFPA 220-2021 CHAPTER 4- TABLE 4.1.1

CONSTRUCTION TYPE: TYPE II (000)

FIRE RESISTANCE RATINGS

COLUMNS: 0 HR

BEAM, GIRDERS, TRUSSES: 0 HR

FLOOR/CEILING ASSEMBLIES: 0 HR

ROOF/CEILING ASSEMBLIES: 0 HR

EXTERIOR NON-BEARING WALLS: 0 HR

INTERIOR NON-BEARING WALLS: 0 HR

FIRE-RESISTIVE REQUIREMENTS:

NON COMBUSTIBLE MATERIALS FOR STRUCTURAL FRAME, FLOORS, ROOF DECK, EXTERIOR

NON-BEARING WALLS, INTERIOR NON-BEARING WALLS (U.N.O. AT EXTERIOR)

NFPA 101-2021 CHAPTERS 12, 36, 38, 39 & 42 TRAVEL DISTANCE

NFPA 101-2021 CHAPTERS 12, 36, 38, 39, & 42 COMMON PATH OF TRAVEL

NFPA 101-2021 CHAPTERS 12, 36, 38, 39 & 42 DEAD END CORRIDOR

PROTECTED AREAS: STORAGE ROOMS/CLEAN/SOILED:

PER VA FIRE PROTECTION DESIGN MANUAL 3.1.A, STORAGE ROOMS ARE HAZARDOUS AREAS.

PER NFPA 101: 39.3.2.1, HAZARDOUS AREAS SHALL BE PROTECTED AS STATED IN SECTION 8.7.

PER NFPA 101: 8.7, ANY AREA HAVING A DEGREE OF HAZARD GREATER THAN THAT NORMAL

TO THE GENERAL OCCUPANCY SHALL BE PROVIDED BY ONE OF THE FOLLOWING:

• 1 HR FIRE BARRIER OR PROTECTING THE AREA WITH AUTOMATIC EXTINGUISHING SYSTEM

• SPRINKLER PROTECTION PROVIDED.

SMOKE COMPARTMENTALIZATION: NOT REQUIRED FOR BUSINESS OCCUPANCIES, NOT PROVIDED.

FIRE ALARM SYSTEM: REQUIRED / PROVIDED AUTOMATIC SYSTEM.

STANDPIPES: NOT REQUIRED / NOT PROVIDED.

LIFE SAFETY CODE ANALYSIS

LIFE SAFETY LEGEND

FEC FIRE EXTINGUISHER CABINET

EXIT LIGHT / SIGN

NOT IN SCOPE

BUILDING EXIT

EGRESS PATH 1 HR FIRE RATED PARTITION

S T

A

IR000

DOOR CAPACITY TAG (STAIR)

OCCUPANCY AREA LEGEND

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

KS ARCH REG. NO. A-930, EXP. 12/31/2023

KS ENGR REG. NO. E-2586, EXP. 12/31/2023

STRUCTURAL / CIVIL ENGINEER

H2B, INC.

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECH / ELEC / PLUMB / TECH ENGR

SPUR DESIGN

25219 MADISON AVENUE, SUITE 100

KANSAS CITY, MO 64108

(913) 369-7200

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT HEALTH & SAFETY

1139 OLIVE STREET,

ST. LOUIS, MO 63101

(314) 436-9492

HEALTHCARE PLANNER

INNOVA GROUP

3196 N. SWAN ROAD

TUCSON, AZ 85712

(520) 886-8650

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH ROAD, STE 1415

PANAMA CITY, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:SPUR #: 2016

/2

/2

:5 :2

A

M

GI012

OCCUPANCY PLANS

ECO

4 OF 190AJS

100% BID SET

CONSTRUCT INFILL OF

BUILDING 26 AND RENOVATE

SPECIALTY CARE CLINICS

12/21/2022

589-704

5500 EAST KELLOGG AVENUE

WICHITA, KANSAS 67218

N

1/32" = 1'-0"

GROUND FLOOR- OCCUPANCY PLAN1

N

1/32" = 1'-0"

FIRST FLOOR - OCCUPANCY PLAN2

PLUMBING FIXTURE REQUIREMENTS

OCCUPANT TYPE OCCUPANT LOAD

WATER CLOSETS LAVATORY

MALE FEMALE MALE FEMALE

BLDG 26

FIRST FLOOR

BUSINESS 351 5 5 4 4

GROUND FLOOR

BUSINESS 341 5 5 4 4

ASSEMBLY, CONCENTRATED 12.2.6.2- SHALL NOT EXCEED 250'-0"

ASSEMBLY, KITCHEN 12.2.6.2- SHALL NOT EXCEED 250'-0"

ASSEMBLY, LESS CONCENTRATED 12.2.6.2- SHALL NOT EXCEED 250'-0"

BUSINESS 38.2.6.3- SHALL NOT EXCEED 300'-0"

MERCANTILE, STREET FLOOR 36.2.6.2- SHALL NOT EXCEED 250'-0"

STORAGE USE, OTHER 42.2.6- SHALL NOT EXCEED 400'-0"

ASSEMBLY, CONCENTRATED 7 7 NET SF/PERSON

ASSEMBLY, KITCHEN 100 100 NET SF/PERSON

ASSEMBLY, LESS CONCENTRATED 15 15 NET SF/PERSON

BUSINESS 150 150 NET SF/PERSON

MERCANTILE, STREET FLOOR 30 30 NET SF/PERSON

STORAGE USE, OTHER 500 500 NET SF/PERSON

ASSEMBLY, CONCENTRATED 12.2.5.2- 20’-0” <50 OCCUPANTS / 75’-0” >50 OCCUPANTS

ASSEMBLY, KITCHEN 12.2.5.2- 20’-0” <50 OCCUPANTS / 75’-0” >50 OCCUPANTS

ASSEMBLY, LESS CONCENTRATED 12.2.5.2- 20’-0” <50 OCCUPANTS / 75’-0” >50 OCCUPANTS

BUSINESS 38.2.5.2.1- SHALL NOT EXCEED 100'-0"

MERCANTILE, STREET FLOOR 36.2.5.2- SHALL NOT EXCEED 100'-0"

STORAGE USE, OTHER 42.2.5- SHALL NOT EXCEED 100'-0"

ASSEMBLY, CONCENTRATED 12.2.5.3- SHALL NOT EXCEED 20'-0"

ASSEMBLY, KITCHEN 12.2.5.3- SHALL NOT EXCEED 20'-0"

ASSEMBLY, LESS CONCENTRATED 12.2.5.3- SHALL NOT EXCEED 20'-0"

BUSINESS 38.2.5.3.1- SHALL NOT EXCEED 50'-0"

MERCANTILE, STREET FLOOR 36.2.5.3.1- SHALL NOT EXCEED 50'-0"

STORAGE USE, OTHER 42.2.5- SHALL NOT EXCEED 100'-0"

OCCUPANT LOAD PER NFPA 101-2021

OCCUPANT TYPE

PER TABLE 7.3.1.2.

AREA

OCC. LOAD

FACTOR IN SF

OCC. LOAD

BLDG 62

GROUND FLOOR

BUSINESS 7768 SF 150 SF 52

STORAGE USE, OTHER 820 SF 500 SF 2

8588 SF 53

FIRST FLOOR

BUSINESS 673 SF 150 SF 4

673 SF 4

OCCUPANT LOAD PER NFPA 101-2021

OCCUPANT TYPE

PER TABLE 7.3.1.2.

AREA

OCC. LOAD

FACTOR IN SF

OCC. LOAD

BLDG 61

GROUND FLOOR

BUSINESS 22005 SF 150 SF 147

STORAGE USE, OTHER 2247 SF 500 SF 4

24252 SF 151

FIRST FLOOR

BUSINESS 25449 SF 150 SF 170

STORAGE USE, OTHER 1147 SF 500 SF 2

26596 SF 172

OCCUPANT LOAD PER NFPA 101-2021

OCCUPANT TYPE

PER TABLE 7.3.1.2.

AREA

OCC. LOAD

FACTOR IN SF

OCC. LOAD

BLDG 29

GROUND FLOOR

BUSINESS 13686 SF 150 SF 91

STORAGE USE, OTHER 671 SF 500 SF 1

14356 SF 93

FIRST FLOOR

BUSINESS 10316 SF 150 SF 69

10316 SF 69

OCCUPANT LOAD PER NFPA 101-2021

OCCUPANT TYPE

PER TABLE 7.3.1.2.

AREA

OCC. LOAD

FACTOR IN SF

OCC. LOAD

BLDG 26

GROUND FLOOR

ASSEMBLY, KITCHEN 1720 SF 100 SF 17

ASSEMBLY, LESS CONCENTRATED 2662 SF 15 SF 177

BUSINESS 14855 SF 150 SF 99

MERCANTILE, STREET FLOOR 1591 SF 30 SF 53

STORAGE USE, OTHER 1058 SF 500 SF 2

21885 SF 349

FIRST FLOOR

ASSEMBLY, CONCENTRATED 1542 SF 7 SF 220

BUSINESS 20351 SF 150 SF 136

21893 SF 356

OCCUPANT LOAD PER NFPA 101-2021

OCCUPANT TYPE

PER TABLE 7.3.1.2.

AREA

OCC. LOAD

FACTOR IN SF

OCC. LOAD

BLDG 3

GROUND FLOOR

BUSINESS 4482 SF 150 SF 30

STORAGE USE, OTHER 305 SF 500 SF 1

4788 SF 30

FIRST FLOOR

BUSINESS 6032 SF 150 SF 40

6032 SF 40

OCCUPANT TYPE

LEVEL COMPONENTS

(WIDTH/PERSON)

STAIRWAYS

(WIDTH/PERSON)

ASSEMBLY, CONCENTRATED .2" .3"

ASSEMBLY, KITCHEN .2" .3"

ASSEMBLY, LESS CONCENTRATED .2" .3"

BUSINESS .2" .3"

MERCANTILE, STREET FLOOR .2" .3"

STORAGE USE, OTHER .2" .3"

B C D E F G

S T

A

IR

S T

A

IR

O T

H E

R

O T

H E

R

O T

H E

R

S T

A

IR

S T

A

IR

O T

H E

R

S T

A

IR

O T

H E

R

B

B62

B

B

B

B

B

B

B

B29

B3

H J K L M

TRAVEL DISTANCE = 204' - 0"

TRAVEL DISTANCE = 118' - 2"

TRAVEL DISTANCE = 185' - 1"

TRAVEL DISTANCE = 229' - 2"

FEC FEC

FEC

FEC

885 SF @ 15 NET = 57 OCC.

1352 SF @ 15 NET = 91 OCC.

TRAVEL DISTANCE = 208' - 8"

STAIR

FEC

12'-0" 19'-0" 19'-0" 19'-0" 19'-0" 19'-0" 7'-0" 12'-0" 13'-10 1/2" 5'-1 1/2" 12'-2"

'-4

8'

-4

'-6

7'

-9

7' -1

1/

2" 7'

-9

/2

7' -9

/2

7'

-1

1/ 2"

7' -9

'-4

8' -6

'-4

STAIR

FEC FEC

A

157'-2"

3'

-2

WORKSTATIONS

001A

WORKSTATIONS

001A

GUEST

SERVICES

HOLDING

CELL

001B

HOLDING

CELL

001B

HOLDING

CELL

001C

HOLDING

CELL

001C

FREEZER

025D

FOOD STG

025A

COOLER

025C

FOOD STG

025B

KITCHEN

CORRIDOR

C1

RETAIL

STORAGE

024A

RETAIL

STORE

DINING AREA

SAFE

026B

VCS CHIEF

OFFICE

026A

VCS OFFICE

DINING AREA

VENDOR

022A

CORRIDOR

C2

VESTIBULE

032A

LAB

DTR-1

DTR-2

DTR-3

DTR-4

DTR-5

DTR-6

DTR-7

DTR-8

CHIEF

035B

WORKSTATIONS

RECEPTION

035A

COPY /

SUPPLY

035F

LOCKER

035C

DRESSING

035E LOUNGE

035D

IT ROOM

HAC

DENTAL

MECH

STORAGE

ELEC

CLEAN

SUPPLY

STERILE

EQUIPMENT

MOBILE

EQUIPMENT

X-RAY

WAITING

CHECK-IN

KIOSK

034A

WC ALC.

034B

STF TLT

PAT TLT

MEDICATION

TRAY

STORAGE

SOILED

UTILITY

CAD/CAM

CART

A008

EQUIP

A007

LIFT

A006

EQUIP

A005

WC

A004

EQUIP

A003

EQUIP

A002

CRASH CART

A001

CORRIDOR

C3

ELECTRICAL

SECURITY

KEY PLAN

BLDG 26

BLDG 3 BLDG 1

BLDG 2BLDG 19

BLDG 61

BLDG 62

BLDG 29

N

PHASE FOUR

SERVICE YARD

EXISTING BUILDING HEIGHT: BUILDING 26

3 STORIES, APPROX. 35'-0" HEIGHT

BUILDING AREA:

AREA LIMITATION: 69,000 SQUARE FEET (2021 IBC TABLE 506.2)

GROUND FLOOR 22,720 GROSS SQUARE FEET

FIRST FLOOR 22,720 GROSS SQUARE FEET

SECOND FLOOR 17,590 GROSS SQUARE FEET

TOTAL 63,030 GROSS SQUARE FEET

NFPA 101-2021 CHAPTER 7- TABLE 7.3.1.2 OCCUPANT LOADS

NFPA 101-2021 CHAPTER 7- 7.2.1.2.3.2) MINIMIM DOOR LEAF WIDTH

MINIMUM DOOR OPENING WIDTH OF 32"

NFPA 101-2021 CHAPTER 7- TABLE 7.3.3.1 CAPACITY FACTORS

NFPA 220-2021 CHAPTER 4- TABLE 4.1.1

CONSTRUCTION TYPE: TYPE II (000)

FIRE RESISTANCE RATINGS

COLUMNS: 0 HR

BEAM, GIRDERS, TRUSSES: 0 HR

FLOOR/CEILING ASSEMBLIES: 0 HR

ROOF/CEILING ASSEMBLIES: 0 HR

EXTERIOR NON-BEARING WALLS: 0 HR

INTERIOR NON-BEARING WALLS: 0 HR

FIRE-RESISTIVE REQUIREMENTS:

NON COMBUSTIBLE MATERIALS FOR STRUCTURAL FRAME, FLOORS, ROOF DECK, EXTERIOR

NON-BEARING WALLS, INTERIOR NON-BEARING WALLS (U.N.O. AT EXTERIOR)

NFPA 101-2021 CHAPTERS 12, 36, 38, 39 & 42 TRAVEL DISTANCE

NFPA 101-2021 CHAPTERS 12, 36, 38, 39, & 42 COMMON PATH OF TRAVEL

NFPA 101-2021 CHAPTERS 12, 36, 38, 39 & 42 DEAD END CORRIDOR

PROTECTED AREAS: STORAGE ROOMS/CLEAN/SOILED:

PER VA FIRE PROTECTION DESIGN MANUAL 3.1.A, STORAGE ROOMS ARE HAZARDOUS AREAS.

PER NFPA 101: 39.3.2.1, HAZARDOUS AREAS SHALL BE PROTECTED AS STATED IN SECTION 8.7.

PER NFPA 101: 8.7, ANY AREA HAVING A DEGREE OF HAZARD GREATER THAN THAT NORMAL

TO THE GENERAL OCCUPANCY SHALL BE PROVIDED BY ONE OF THE FOLLOWING:

• 1 HR FIRE BARRIER OR PROTECTING THE AREA WITH AUTOMATIC EXTINGUISHING SYSTEM

• SPRINKLER PROTECTION PROVIDED.

SMOKE COMPARTMENTALIZATION: NOT REQUIRED FOR BUSINESS OCCUPANCIES, NOT PROVIDED.

FIRE ALARM SYSTEM: REQUIRED / PROVIDED AUTOMATIC SYSTEM.

STANDPIPES: NOT REQUIRED / NOT PROVIDED.

LIFE SAFETY CODE ANALYSIS

LIFE SAFETY LEGEND

FEC FIRE EXTINGUISHER CABINET

EXIT LIGHT / SIGN

NOT IN SCOPE

BUILDING EXIT

EGRESS PATH 1 HR FIRE RATED PARTITION

S T

A

IR000

DOOR CAPACITY TAG (STAIR)

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

KS ARCH REG. NO. A-930, EXP. 12/31/2023

KS ENGR REG. NO. E-2586, EXP. 12/31/2023

STRUCTURAL / CIVIL ENGINEER

H2B, INC.

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECH / ELEC / PLUMB / TECH ENGR

SPUR DESIGN

25219 MADISON AVENUE, SUITE 100

KANSAS CITY, MO 64108

(913) 369-7200

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT HEALTH & SAFETY

1139 OLIVE STREET,

ST. LOUIS, MO 63101

(314) 436-9492

HEALTHCARE PLANNER

INNOVA GROUP

3196 N. SWAN ROAD

TUCSON, AZ 85712

(520) 886-8650

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH ROAD, STE 1415

PANAMA CITY, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:SPUR #: 2016

/2

/2

:5 :2

A

M

GI013

LIFE SAFETY PLAN - GROUND FLOOR

ECO

5 OF 190AJS

100% BID SET

CONSTRUCT INFILL OF

BUILDING 26 AND RENOVATE

SPECIALTY CARE CLINICS

12/21/2022

589-704

5500 EAST KELLOGG AVENUE

WICHITA, KANSAS 67218

N

1/8" = 1'-0"

GROUND FLOOR - LIFE SAFETY PLAN1

ASSEMBLY, CONCENTRATED 7 7 NET SF/PERSON

ASSEMBLY, KITCHEN 100 100 NET SF/PERSON

ASSEMBLY, LESS CONCENTRATED 15 15 NET SF/PERSON

BUSINESS 150 150 NET SF/PERSON

MERCANTILE, STREET FLOOR 30 30 NET SF/PERSON

STORAGE USE, OTHER 500 500 NET SF/PERSON

OCCUPANT TYPE

LEVEL COMPONENTS

(WIDTH/PERSON)

STAIRWAYS

(WIDTH/PERSON)

ASSEMBLY, CONCENTRATED .2" .3"

ASSEMBLY, KITCHEN .2" .3"

ASSEMBLY, LESS CONCENTRATED .2" .3"

BUSINESS .2" .3"

MERCANTILE, STREET FLOOR .2" .3"

STORAGE USE, OTHER .2" .3"

ASSEMBLY, CONCENTRATED 12.2.6.2- SHALL NOT EXCEED 250'-0"

ASSEMBLY, KITCHEN 12.2.6.2- SHALL NOT EXCEED 250'-0"

ASSEMBLY, LESS CONCENTRATED 12.2.6.2- SHALL NOT EXCEED 250'-0"

BUSINESS 38.2.6.3- SHALL NOT EXCEED 300'-0"

MERCANTILE, STREET FLOOR 36.2.6.2- SHALL NOT EXCEED 250'-0"

STORAGE USE, OTHER 42.2.6- SHALL NOT EXCEED 400'-0"

ASSEMBLY, CONCENTRATED 12.2.5.2- 20’-0” <50 OCCUPANTS / 75’-0” >50 OCCUPANTS

ASSEMBLY, KITCHEN 12.2.5.2- 20’-0” <50 OCCUPANTS / 75’-0” >50 OCCUPANTS

ASSEMBLY, LESS CONCENTRATED 12.2.5.2- 20’-0” <50 OCCUPANTS / 75’-0” >50 OCCUPANTS

BUSINESS 38.2.5.2.1- SHALL NOT EXCEED 100'-0"

MERCANTILE, STREET FLOOR 36.2.5.2- SHALL NOT EXCEED 100'-0"

STORAGE USE, OTHER 42.2.5- SHALL NOT EXCEED 100'-0"

ASSEMBLY, CONCENTRATED 12.2.5.3- SHALL NOT EXCEED 20'-0"

ASSEMBLY, KITCHEN 12.2.5.3- SHALL NOT EXCEED 20'-0"

ASSEMBLY, LESS CONCENTRATED 12.2.5.3- SHALL NOT EXCEED 20'-0"

BUSINESS 38.2.5.3.1- SHALL NOT EXCEED 50'-0"

MERCANTILE, STREET FLOOR 36.2.5.3.1- SHALL NOT EXCEED 50'-0"

STORAGE USE, OTHER 42.2.5- SHALL NOT EXCEED 100'-0"

A

B C D E F G

S T

A

IR

S T

A

IR

S T

A

IR

S T

A

IR

S T

A

IR

BLDG 61

BLDG 29BLDG 62

B

B62

B

B

B

B

B

B

B

B29

B3

BLDG 26

H J K L M

TRAVEL DISTANCE = 236' - 10"

T R

A V

E L

D

IS

T A

N C

E

FEC

FEC

1539 SF @ 15 NET = 103

S T

A

IR

FEC

SHARED

WAITING

100A

NEURO

NEURO

GI / RHEUM

GI / RHEUM

GI EXAM

GI EXAM

LOUNGE /

LOCKER

CLEAN

UTILITY

PAT TLT

NEURO

TEAM SPACE 1

GI EXAM

GI / RHEUM

CORRIDOR

CORRIDOR

PROC TLT

123B

MED EQUIP

STORAGE

PROCEDURE

ROOM

123A

MED

PFT

126A

PFT TLT

126B

SOILED

UTILITY

HAC

RENAL

HOME

OXYGEN

RENAL

RENAL

134 136

PULM / SLEEP PULM / SLEEP

PULM / SLEEP

CPAP CONS.

FLEX EXAM

CPAP STG

147PAT. TLT

VESTIBULE

122B

CPAP CONS.

141A

CPAP CONS.

143A

PULM / SLEEP

RENAL

CLEAN

UTILITY

RENAL

TEAM SPACE

122A

STF TLT

STG

141B STG

143B

CORR.

O2, FULL

129B

O2, EMPTY

129A

RECEPTION

100B

IT ROOM

ELEC

STF TLT

FEC

FEC

FEC

FEC

FEC

12'-0" 19'-0" 19'-0" 19'-0" 19'-0" 19'-0" 7'-0" 12'-0" 13'-10 1/2" 5'-1 1/2" 12'-2"

'-4

8'

-4

'-6

7'

-9

7' -1

1/

2" 7'

-9

/2

7' -9

/2

7'

-1

1/ 2"

7' -9

'-4

8' -6

'-4

A

157'-2"

3'

-2

KEY PLAN

BLDG 26

BLDG 3 BLDG 1

BLDG 2BLDG 19

BLDG 61

BLDG 62

BLDG 29

N

PHASE FOUR

SERVICE YARD

EXISTING BUILDING HEIGHT: BUILDING 26

3 STORIES, APPROX. 35'-0" HEIGHT

BUILDING AREA:

AREA LIMITATION: 69,000 SQUARE FEET (2021 IBC TABLE 506.2)

GROUND FLOOR 22,720 GROSS SQUARE FEET

FIRST FLOOR 22,720 GROSS SQUARE FEET

SECOND FLOOR 17,590 GROSS SQUARE FEET

TOTAL 63,030 GROSS SQUARE FEET

NFPA 101-2021 CHAPTER 7- TABLE 7.3.1.2 OCCUPANT LOADS

NFPA 101-2021 CHAPTER 7- 7.2.1.2.3.2) MINIMIM DOOR…