Attachment 1 - 00_100_ BID SET General Drawings.pdf
PDF 4 MB Posted
- Solicitation number
- 36C77624R0027
About this file
This solicitation is for a minor construction project to construct an infill of Building 26 for dental clinics, a new police office, and renovate space for specialty care services at the Robert J. Dole VA Medical Center in Wichita, Kansas. The solicitation number is 36C77624R0027 and was issued by the Department of Veterans Affairs Technology Acquisition Center located in Austin, Texas. The project scope involves excavating an existing courtyard to prepare for new construction, building an infill structure on the ground and first floors, interior construction for the ground floor canteen and first floor specialty care unit, limited renovation including a connecting corridor, replacing an emergency generator, ground floor dental clinic renovation, first floor specialty care renovation, construction of a ground floor police substation, and exterior service yard improvements.
View the file
Other files
Show all 30
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
N
AREA
PLAN
LOCATION
PLAN
N
PROJECT LOCATION
BUILDING 26
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
U.S. DEPARTMENT OF VETERANS AFFAIRS
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
KS ARCH REG. NO. A-930, EXP. 12/31/2023
KS ENGR REG. NO. E-2586, EXP. 12/31/2023
STRUCTURAL / CIVIL ENGINEER
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB / TECH ENGR
SPUR DESIGN
25219 MADISON AVENUE, SUITE 100
KANSAS CITY, MO 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT HEALTH & SAFETY
1139 OLIVE STREET,
ST. LOUIS, MO 63101
(314) 436-9492
HEALTHCARE PLANNER
INNOVA GROUP
3196 N. SWAN ROAD
TUCSON, AZ 85712
(520) 886-8650
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH ROAD, STE 1415
PANAMA CITY, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:SPUR #: 2016
/2
/2
:5 :0
A
M
G-000
COVER SHEET
ECO
1 OF 190AJS
100% BID SET
CONSTRUCT INFILL OF BUILDING 26 AND
RENOVATE SPECIALTY CARE CLINICS
VA PROJECT NUMBER: 589-704
CONSTRUCT INFILL OF
BUILDING 26 AND RENOVATE
SPECIALTY CARE CLINICS
12/21/2022
589-704
5500 EAST KELLOGG AVENUE
WICHITA, KANSAS 67218
ROBERT J. DOLE VA MEDICAL CENTER
5500 EAST KELLOGG AVENUE
WICHITA, KANSAS 67218
100% BID SET
SHEET INDEX
SEQUENCE NUMBER SHEET NAME
[08] ELECTRICAL
155 E-000 ELECTRICAL LEGEND
156 ED101 PHASE ONE - ELECTRICAL DEMOLITION GROUND FLOOR PLANS
157 ED102 PHASE ONE - ELECTRICAL DEMOLITION REFLECTED CEILING PLANS
158 ED103 PHASE TWO - ELECTRICAL DEMOLITION POWER FLOOR PLANS
159 ED104 PHASE TWO - ELECTRICAL DEMOLITION REFLECTED CEILING PLANS
160 ED601 ELECTRICAL ONE-LINE DIAGRAM - DEMOLITION / TEMPORARY POWER
161 EL101 PHASE ONE - ELECTRICAL LIGHTING PLANS
162 EL102 PHASE TWO - ELECTRICAL LIGHTING PLAN
163 EP101 PHASE ONE - ELECTRICAL POWER PLANS
164 EP102 PHASE TWO - ELECTRICAL POWER PLANS
165 EP103 PHASE THREE - ELECTRICAL SITE PLAN
166 EQ101 PHASE ONE - ELECTRICAL EQUIPMENT POWER PLANS
167 EQ102 PHASE TWO - ELECTRICAL EQUIPMENT POWER PLANS
168 E-401 PHASE ONE - ELECTRICAL ENLARGED PLANS
169 E-402 PHASE TWO - ELECTRICAL ENLARGED PLANS
170 E-501 POWER ELEVATIONS FOR TELECOMMUNICATION RACKS AND DUCT BANK
DETAILS
171 E-502 ELECTRICAL DETAILS
172 E-503 LIGHTING DETAILS AND CONTROLS
173 E-601 ELECTRICAL ONE-LINE DIAGRAM - NEW WORK
174 E-602 ELECTRICAL SCHEDULES
175 E-603 ELECTRICAL PANEL SCHEDULES
176 E-604 ELECTRICAL PANEL SCHEDULES
[09] TELECOMMUNICATION
177 T-000 TECHNOLOGY LEGEND
178 TD101 PHASE ONE - TECHNOLOGY DEMOLITION FLOOR PLAN
179 TD102 PHASE TWO - TECHNOLOGY DEMOLITION FLOOR PLAN
180 TI101 PHASE ONE - INTERCOM AND PUBLIC ADDRESS FLOOR PLANS
181 TI102 PHASE TWO - INTERCOM AND PUBLIC ADDRESS FLOOR PLANS
182 TN101 PHASE ONE - TECHNOLOGY FLOOR PLANS
183 TN102 PHASE TWO - TECHNOLOGY FLOOR PLANS
184 TY101 PHASE ONE - SECURITY FLOOR PLANS
185 TY102 PHASE TWO - SECURITY FLOOR PLANS
186 TY103 PHASE THREE - TECHNOLOGY SITE PLAN
187 T-401 ENLARGED TECHNOLOGY PLANS
188 T-501 TECHNOLOGY DETAILS
189 T-601 TECHNOLOGY RISER DIAGRAMS
190 T-602 TECHNOLOGY SCHEDULES
TOTAL SHEETS: 190
SHEET INDEX
SEQUENCE NUMBER SHEET NAME
[07] MECHANICAL
117 M-000 LEGEND AND ABBREVIATIONS
118 MHD101 GROUND FLOOR MECHANICAL DUCT DEMOLITION PLANS
119 MHD102 FIRST FLOOR MECHANICAL HVAC DUCT DEMOLITION PLAN
120 MHD103 SECOND FLOOR MECHANICAL HVAC DUCT DEMOLITION PLANS
121 MHD104 SERVICE YARD DEMOLITION PLAN
122 MHPD101 ROOF MECHANICAL HVAC DUCT AND PIPING DEMOLITION PLAN
123 MPD101 GROUND FLOOR MECHANICAL HVAC PIPING DEMOLITION PLANS
124 MPD102 FIRST FLOOR MECHANICAL HVAC PIPING DEMOLITION PLAN
125 MH101 GROUND FLOOR MECHANICAL DUCT PLANS
126 MH102 FIRST FLOOR MECHANICAL DUCT PLANS
127 MH103 SECOND FLOOR MECHANICAL DUCT PLANS
128 MH104 ROOF MECHANICAL DUCT PLANS
129 MH105 SERVICE YARD NEW WORK PLAN
130 MH106 GROUND FLOOR ZONING PLANS
131 MH107 FIRST FLOOR ZONING PLANS
132 MH108 GROUND FLOOR AIR PRESSURIZATION PLANS
133 MH109 FIRST FLOOR AIR PRESSURIZATION PLANS
134 MP101 GROUND FLOOR MECHANICAL HVAC PIPING PLAN
135 MP102 FIRST FLOOR MECHANICAL HVAC PIPING PLAN
136 MP103 SECOND FLOOR MECHANICAL HVAC PIPING PLAN
137 MP104 ROOF MECHANICAL HVAC PIPING PLAN
138 M-301 MECHANICAL SECTIONS
139 M-401 PHASE 1 AIR FLOW DIAGRAMS
140 M-402 PHASE 2 AIR FLOW DIAGRAMS
141 M-403 HYDRONIC FLOW DIAGRAMS
142 M-501 MECHANICAL DETAILS
143 M-502 MECHANICAL DETAILS
144 M-503 MECHANICAL DETAILS
145 M-504 MECHANICAL DETAILS
146 M-505 MECHANICAL DETAILS
147 M-601 MECHANICAL SCHEDULES
148 M-602 MECHANICAL SCHEDULES
149 M-701 MECHANICAL CONTROLS
150 M-702 MECHANICAL CONTROLS
151 M-703 MECHANICAL CONTROLS
152 M-704 MECHANICAL CONTROLS
153 M-705 MECHANICAL CONTROLS
154 M-706 MECHANICAL CONTROLS
SHEET INDEX
SEQUENCE NUMBER SHEET NAME
58 AE405 PHASE ONE - ENLARGED PLANS & INTERIOR ELEVATIONS
59 AE406 PHASE ONE - ENLARGED PLANS & INTERIOR ELEVATIONS
60 AE407 PHASE ONE - ENLARGED PLANS & INTERIOR ELEVATIONS
61 AE408 PHASE ONE - ENLARGED PLANS & INTERIOR ELEVATIONS
62 AE409 PHASE TWO - ENLARGED PLANS & INTERIOR ELEVATIONS
63 AE410 PHASE TWO - ENLARGED PLANS & INTERIOR ELEVATIONS
64 AE411 PHASE TWO - ENLARGED PLANS & INTERIOR ELEVATIONS
65 AE412 PHASE TWO - ENLARGED PLANS & INTERIOR ELEVATIONS
66 AE413 PHASE TWO - ENLARGED PLANS & INTERIOR ELEVATIONS
67 AE414 PHASE TWO - ENLARGED PLANS & INTERIOR ELEVATIONS
68 AE415 PHASE TWO - ENLARGED PLANS & INTERIOR ELEVATIONS
69 AE416 PHASE TWO - ENLARGED PLANS & INTERIOR ELEVATIONS
70 AE417 PHASE TWO - ENLARGED PLANS & INTERIOR ELEVATIONS
71 AE418 PHASE TWO - ENLARGED PLANS & INTERIOR ELEVATIONS
72 AE419 PHASE THREE - ENLARGED PLANS & INTERIOR ELEVATIONS
73 AE501 SECTION DETAILS
74 AE502 SECTION DETAILS
75 AE511 PLAN DETAILS
76 AE512 PLAN DETAILS
77 AE513 PLAN DETAILS
78 AE601 WINDOW ELEVATIONS, DOOR SCHEDULES & DETAILS
79 AF701 PHASE ONE - FINISH FLOOR PLANS
80 AF702 PHASE TWO & THREE - FINISH FLOOR PLANS
81 AF711 INTERIOR FINISH LEGEND & SCHEDULES
82 AF712 INTERIOR DETAILS
83 AF713 SIGNAGE LEGEND
84 AF714 PHASE ONE - SIGNAGE PLANS
85 AF715 PHASE TWO & THREE- SIGNAGE PLANS
86 AF901 MILLWORK SECTIONS & DETAILS
87 AF902 MILLWORK SECTIONS & DETAILS
[05] FIRE PROTECTION
88 FA001 FIRE ALARM GENERAL NOTES, LEGEND, AND RISER DIAGRAM
89 FA101 FIRE ALARM AUDIBILITY PLAN - GROUND FLOOR
90 FA102 FIRE ALARM AUDIBILITY PLAN - FIRST FLOOR
91 FA103 FIRE ALARM PLAN - GROUND FLOOR
92 FA104 FIRE ALARM PLAN - FIRST FLOOR
93 FX001 FIRE SUPPRESSION GENERAL NOTES
94 FX101 FIRE SUPPRESSION HAZARD CLASSIFICATION PLAN - GROUND FLOOR
95 FX102 FIRE SUPPRESSION HAZARD CLASSIFICATION PLAN - FIRST FLOOR
[06] PLUMBING
96 P-000 PLUMBING LEGEND
97 P-100 PLUMBING OVERALL PLANS
98 PLD101 PHASE ONE - PLUMBING WASTE AND VENT DEMOLITION PLAN
99 PLD102 PHASE TWO - PLUMBING WASTE AND VENT DEMOLITION PLANS
100 PPD101 PHASE TWO - PLUMBING DOMESTIC WATER DEMOLITION PLANS
101 PGD101 PHASE ONE AND TWO - PLUMBING MEDICAL GAS DEMOLITION PLANS
102 PL101 PHASE ONE - PLUMBING WASTE AND VENT PLANS
103 PL102 PHASE TWO - PLUMBING WASTE AND VENT PLANS
104 PP102 PHASE TWO - PLUMBING DOMESTIC WATER PLAN
105 PP101 PHASE ONE - PLUMBING DOMESTIC WATER PLAN
106 PG101 PHASE ONE AND TWO - PLUMBING MEDICAL GAS PLANS
107 P-200 PLUMBING ROOF PLAN
108 P-401 PLUMBING ENLARGED PLANS
109 P-501 PLUMBING DETAILS
110 P-502 PLUMBING DETAILS
111 P-601 PLUMBING SCHEDULES
112 P-301 PLUMBING WASTE AND VENT ISOMETRICS - PHASE 1
113 P-302 PLUMBING WASTE AND VENT ISOMETRICS - PHASE 2
114 P-303 PLUMBING DOMESTIC WATER ISOMETRICS - PHASE 1
115 P-304 PLUMBING DOMESTIC WATER ISOMETRICS - PHASE 2
116 P-305 PLUMBING MEDGAS ISOMETRICS
SHEET INDEX
SEQUENCE NUMBER SHEET NAME
[00] GENERAL
1 G-000 COVER SHEET
2 GI001 GENERAL INFORMATION
3 GI011 PHASING PLANS
4 GI012 OCCUPANCY PLANS
5 GI013 LIFE SAFETY PLAN - GROUND FLOOR
6 GI014 LIFE SAFETY PLAN - FIRST FLOOR
[01] HAZARDOUS MATERIALS
7 HA000 ENVIRONMENTAL REMEDIATION - GENERAL NOTES
8 HA001 GROUND FLOOR - PHASE ONE - ENVIRONMENTAL REMEDIATION
9 HA002 GROUND FLOOR - PHASE TWO - ENVIRONMENTAL REMEDIATION
10 HA101 FIRST FLOOR - PHASE ONE - ENVIRONMENTAL REMEDIATION
11 HA102 FIRST FLOOR - PHASE TWO - ENVIRONMENTAL REMEDIATION
12 HA201 SECOND FLOOR - PHASE ONE - ENVIRONMENTAL REMEDIATION
13 HA301 ROOF - PHASE TWO - ENVIRNOMENTAL REMEDIATION
[02] CIVIL
14 CS-100 SITE LAYOUT
[03] STRUCTURAL
15 SA001 STRUCTURAL GENERAL NOTES
16 SA010 STRUCTURAL SPECIAL INSPECTIONS
17 SA011 STRUCTURAL SPECIAL INSPECTIONS
18 SA030 TYPICAL DETAILS - CONCRETE
19 SA050 TYPICAL DETAILS - STEEL
20 SA051 TYPICAL DETAILS - STEEL
21 SA052 TYPICAL DETAILS - CFMF
22 SA053 TYPICAL DETAILS - CFMF
23 SS101 SERVICE YARD PLAN/DETAILS
24 SD101 GROUND FLOOR DEMO PLAN
25 SD102 FIRST FLOOR DEMO PLAN
26 SB101 GROUND FLOOR/FOUNDATION PLAN
27 SB301 FOUNDATION DETAILS
28 SF102 FIRST FLOOR FRAMING PLAN
29 SF103 ROOF FRAMING PLAN
30 SF301 EXISTING BUILDING SECTIONS
31 SF501 FRAMING DETAILS
32 SF510 MECHANICAL PENTHOUSE PLAN
[04] ARCHITECTURAL
33 AD111 PHASE ONE - DEMOLITION PLANS
34 AD112 PHASE ONE - DEMOLITION REFLECTED CEILING PLANS
35 AD113 PHASE ONE - DEMOLITION EXTERIOR ELEVATIONS
36 AD121 PHASE TWO & THREE - DEMOLITION PLANS
37 AD122 PHASE TWO & THREE- DEMOLITION REFLECTED CEILING PLANS
38 AD123 PHASE TWO - DEMOLITION EXTERIOR ELEVATIONS
39 AE001 PARTITION TYPES
40 AE101 OVERALL REFERENCE PLAN - GROUND FLOOR
41 AE102 OVERALL REFERENCE PLAN - FIRST FLOOR
42 AE111 PHASE ONE - REFERENCE PLANS
43 AE112 PHASE ONE - DIMENSION PLANS
44 AE113 PHASE ONE - ROOF PLANS
45 AE114 PHASE ONE - REFLECTED CEILING PLANS
46 AE115 PHASE ONE - EQUIPMENT PLANS
47 AE121 PHASE TWO & THREE- REFERENCE PLANS
48 AE122 PHASE TWO & THREE - DIMENSION PLANS
49 AE123 PHASE TWO & THREE - REFLECTED CEILING PLANS
50 AE124 PHASE TWO & THREE - EQUIPMENT PLANS
51 AE125 PHASE FOUR - EXTERIOR SERVICE YARD PLAN, SECTION, AND ELEVATION
52 AE301 BUILDING SECTIONS
53 AE311 WALL SECTIONS
54 AE401 PHASE ONE - ENLARGED PLANS & INTERIOR ELEVATIONS
55 AE402 PHASE ONE - ENLARGED PLANS & INTERIOR ELEVATIONS
56 AE403 PHASE ONE - ENLARGED PLANS & INTERIOR ELEVATIONS
57 AE404 PHASE ONE - ENLARGED PLANS & INTERIOR ELEVATIONS
BID DEDUCT:
THE ADDITION AND REMODEL OF THE FIRST FLOOR SPECIALTY CARE UNIT IN BOTH THE INFILL AND RENOVATION PORTION OF THE PROJECT WILL BE USED TO MEET 20% OF THE TOTAL CONSTRUCTION COST AS
REQUIRED. BELOW IS A BREAKDOWN AS TO HOW IT AFFECTS EACH PHASE OF WORK:
• PHASE 1
1. AS A PART OF PHASE 1, THE COURTYARD INFILL STRUCTURE AND ENVELOPE AT EACH LEVEL WILL BE CONSTRUCTED WITH OR WITHOUT THE INCLUSION OF THE BID DEDUCT.
2. WITH THE BID DEDUCT, ALL INTERIOR WORK OF THE INFILL SCOPE FOR THE FIRST FLOOR SPECIALTY CARE ARE NOT BE CONSTRUCTED EXCEPT METAL STUD AND GYPSUM BOARD AT EXTERIOR WALL LOCATIONS THROUGHOUT THE SPACE. ADDITIONALLY, ALL PENETRATIONS AND SHAFTS FROM THE GROUND FLOOR TO THE ROOF ARE TO BE CONSTRUCTED. CHASES ARE TO BE PROVIDED WITHIN THE SPACE WHERE MECHANICAL AND PLUMBING EQUIPMENT NEED TO EXTEND FROM THE FIRST FLOOR UP THRU THE ROOF.
3. THE FIRST FLOOR SPECIALTY CARE SPACE IS THEN TO BE CONSIDERED “WARM SHELL SPACE”, WHICH MEANS THE SPACE WOULD BE FITTED WITH BASIC SERVICES (ACOUSTICAL CEILING, MINIMAL LIGHTING, MINIMAL PLUMBING, AND MINIMAL HVAC). THIS WOULD NOT INCLUDE INTERIOR WALLS, FLOORING, OR NEW EQUIPMENT FOR THIS AREA.
• PHASE 2
1. AS PART OF PHASE 2, ALL INTERIOR WORK WITHIN THE RENOVATION SCOPE FOR THE FIRST FLOOR SPECIALTY CARE ARE NOT TO BE CONSTRUCTED EXCEPT METAL STUD AND GYPSUM BOARD AT
EXTERIOR WALL LOCATION THROUHGOUT THE SPACE. NO WORK IS TO BE DONE TO THE EXISTING SPECIALTY CARE UNIT ON THE FIRST FLOOR. THIS WOULD INCLUDE THE REMODEL AS WELL AS NO NEW
EQUIPMENT FOR THE SPACE.
NO. REVISION DESCRIPTION DATE
ABBREVIATIONS CODES STANDARDS AND EXECUTIVE ORDERS
TOILET ROOM TURNING
RADIUS
CLEAR FLOOR SPACE
@ WATER CLOSET
5'-6"
6' -0
2'-6"
4' -0
2'-6"
4' -0
FIXTURE MOUNTING HEIGHTS AND CLEARANCES
18" MIN
M
IN
FRONT APPROACH,
PULL SIDE
36" MIN
M
IN
HINGE APPROACH,
PULL SIDE
HINGE APPROACH,
PULL SIDE
*12" MIN
M
IN
FRONT APPROACH,
PUSH SIDE
M
IN
HINGE APPROACH,
PUSH SIDE
22" MIN 24" MIN
*4 8"
M
IN
LATCH APPROACH,
PULL SIDE
24" MIN*4
2"
M
IN
LATCH APPROACH,
PUSH SIDE
*IF BOTH CLOSER
AND LATCH ARE
PROVIDED
*54" MIN IF CLOSER
IS PROVIDED
*48" IF CLOSER IS
PROVIDED
FRONT APPROACH,
PUSH SIDE
M
IN
42" MIN
M
IN
DOOR AND FIXTURE CLEARANCES
MATERIALS LEGEND
PURPOSE: THE PUBLIC BUILDINGS AMENDMENT ACT OF 1988, PUBLIC LAW (PUB. L.) 100-678 REQUIRES FEDERAL AGENCIES TO FOLLOW NATIONAL RECOGNIZED "MODEL" BUILDING CODES. THE FEDERAL PARTICIPATION IN THE DEVELOPMENT AND USE OF VOLUNTARY STANDARDS, OFFICE OF MANAGEMENT AND BUDGET (OMB) CIRCULAR A-119, REQUIRES ALL EXECUTIVE AGENCIES TO RELY ON VOLUNTARY STANDARDS, BOTH DOMESTIC AND INTERNATIONAL, WHENEVER FEASIBLE, AND TO PARTICIPATE IN VOLUNTARY STANDARD BODIES.
GENERAL: VA HAS ADOPTED THE LATEST EDITION OF THE FOLLOWING CODES AND STANDARDS AS A MINIMUM FOR ALL PROJECTS PERFORMED IN THE MODERNIZATION, ALTERATION, ADDITION, OR IMPROVEMENT OF ITS REAL PROPERTY AND THE CONSTRUCTION OF NEW STRUCTURES. VA DESIGN MANUALS AND MASTER SPECIFICATIONS SPECIFY OTHER CODES AND STANDARDS THAT VA FOLLOWS ON ITS PROJECTS:
• VA DIRECTIVES, DESIGN MANUALS, MASTER SPECIFICATIONS, VA NATIONAL CAD STANDARD APPLICATION GUIDE, AND OTHER GUIDANCE ON THE
TECHNICAL INFORMATION LIBRARY (TIL) (HTTP://WWW.CFM.VA.GOV/TIL/).
• 2021 INTERNATIONAL BUILDING CODE (IBC) (ONLY WHEN SPECIFICALLY REFERENCED IN VA DESIGN DOCUMENTS, SEE NOTES BELOW)
• 2021 INTERNATIONAL EXISTING BUILDING CODE (IEBC) (IF APPLICABLE)
• 2021 NFPA 101 LIFE SAFETY CODE (SEE NOTES BELOW)
• 2021 INTERNATIONAL FIRE CODE
• 2021 NFPA 5000 BUILDING CONSTRUCTION AND SAFETY CODE
• 2019 NFPA 900 BUILDING ENERGY CODE
• OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION (OSHA) STANDARDS.
• 2020 VA SEISMIC DESIGN REQUIREMENTS, H-18-8
• 2020 NATIONAL ELECTRICAL CODE (NEC)
• 2021 INTERNATIONAL PLUMBING CODE (IPC)
• 2016 SAFETY CODE FOR ELEVATORS AND ESCALATORS, AMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME) A 17.1.
• 2015 ARCHITECTURAL BARRIERS ACT (ABA) STANDARDS INCLUDING VA SUPPLEMENT, VA BARRIER FREE DESIGN STANDARD (PG-18-13)
• 2017 ANSI ICC A117.1 ACCESIBLE AND USABLE BUILDINGS AND FACILITIES
• 2019 BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE AND COMMENTARY, AMERICAN CONCRETE INSTITUTE AND COMMENTARY (ACI 318-19)
• 2017 STEEL CONSTRUCTION MANUAL (15TH EDITION), AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC)
• ENERGY POLICY ACT OF 2005 (EPACT)
• 2007 DOE INTERIM FINAL RULE: ENERGY CONSERVATION STANDARDS FOR NEW FEDERAL, COMMERCIAL AND MULTI-FAMILY HIGH-RISE RESIDENTIAL
BUILDINGS AND NEW LOW-RISE RESIDENTIAL BUILDINGS, 10 CFR PARTS 433, 434 AND 435.
• 2006 FEDERAL LEADERSHIP IN HIGH PERFORMANCE AND SUSTAINABLE BUILDINGS: MEMORANDUM OF UNDERSTANDING (MOU)
• 2018 EXECUTIVE ORDER 13834: EFFICIENT FEDERAL OPERATIONS
• 2021 THE PROVISIONS FOR CONSTRUCTION AND SAFETY SIGNS. STATED IN THE GENERAL REQUIREMENTS SECTION 010000 OF THE VA MASTER
CONSTRUCTION SPECIFICATION.
• 2019 VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY – ASHRAE STANDARD 62.1
• 2019 SAFETY STANDARD FOR REFRIGERATION SYSTEMS – ASHRAE STANDARD 15
LOCAL CODES: AS AN AGENCY OF THE FEDERAL GOVERNMENT, VA IS NOT SUBJECT TO LOCAL IMPOSITION OF CODE ENFORCEMENT PROCEDURES (DRAWING REVIEWS, BUILDING PERMITS, INSPECTIONS, FEES, ETC.). VA MUST FUNCTION AS THE AUTHORITY HAVING JURISDICTION (AHJ) AND THUS HAS THE RESPONSIBILITY TO GUARD PUBLIC HEALTH AND SAFETY THROUGH ENFORCING ITS ADOPTED CODES. HOWEVER, LOCAL AUTHORITIES SHOULD BE NOTIFIED ABOUT PLANNED PROJECTS AND GIVEN OPPORTUNITY TO REVIEW DRAWINGS PROVIDED THAT VA DOES NOT PAY FOR REVIEW OR INSPECTION FEES.
NOTES:
1. NFPA 101 PRIMARILY ADDRESSES LIFE SAFETY AND FIRE PROTECTION FEATURES WHILE THE IBC ADDRESSES A WIDE RANGE OF CONSIDERATIONS, INCLUDING, BUT NOT LIMITED TO, STRUCTURAL STRENGTH, SEISMIC STABILITY, SANITATION, ADEQUATE LIGHT AND VENTILATION, AND ENERGY CONSERVATION. VA BUILDINGS MUST MEET THE REQUIREMENTS OF NFPA 101 AND DOCUMENTS REFERENCED BY NFPA 101 IN ORDER TO COMPLY WITH THE ACCREDITATION REQUIREMENTS OF THE JOINT COMMISSION. THEREFORE, DESIGNS SHALL COMPLY WITH THE REQUIREMENTS OF THE LATEST EDITION OF NFPA 101 AND DOCUMENTS REFERENCED THEREIN. DESIGN FEATURES NOT ADDRESSED BY NFPA 101 OR DOCUMENTS REFERENCED THEREIN SHALL COMPLY WITH THE REQUIREMENTS OF THE LATEST EDITION OF THE IBC OR AS OTHERWISE ADDRESSED ABOVE IN THIS PROGRAM GUIDE.
FOR DESIGN FEATURES THAT ARE ADDRESSED BY BOTH THE IBC AS WELL AS NFPA 101 OR A DOCUMENT REFERENCED BY NFPA 101, THE REQUIREMENTS OF NFPA 101 OR THE DOCUMENT REFERENCED BY NFPA 101 SHALL BE USED EXCLUSIVELY (THIS APPLIES EVEN IF THE IBC REQUIREMENTS ARE
DIFFERENT).
2. CONFLICTS BETWEEN NATIONALLY RECOGNIZED CODES AND STANDARDS AND VA REQUIREMENTS – SHOULD A CONFLICT EXIST BETWEEN VA REQUIREMENTS AND VA ADOPTED NATIONALLY RECOGNIZED CODES AND STANDARDS, THE CONFLICT SHALL BE BROUGHT TO THE ATTENTION OF VA.
THE RESOLUTION OF THE CONFLICT SHALL BE MADE BY THE AUTHORITY HAVING JURISDICTION FOR VA TO ENSURE A CONSISTENCY SYSTEM WIDE.
ASHRAE 90.1 - 2019 EDITION
BUILDING LOCATION: WITCHITA, KS
CLIMATE ZONE (TABLE ANNEX 1-1): ZONE 4A
INTERIOR DESIGN CONDITIONS:
THE INTERIOR DESIGN TEMPERATURES FOR HEATING AND COOLING AS DEPICTED IN THE PROJECT DESIGN CONDITIONS SCHEDULE IN THE MECHANICAL CONTROL DRAWINGS SHALL BE THE MAXIMUM AND MINIMUM
VALUES FOR THE ASSOCIATED TEMPERATURE CONTROL ZONES.
BUILDING ENVELOPE REQUIREMENTS (TABLE 5.5-4):
ROOFS: REQUIRED: DESIGNED:
INSULATION ABOVE DECK R-30 c.i. R-30 c.i.
METAL BUILDINGS: R-19 + R-11 Ls or R-25 + R-8 Ls N/A
ATTIC AND OTHER: R-49 N/A
WALLS, ABOVE GRADE
MASS: R-9.5 c.i. N/A METAL BUILDING: R-0 + R-15.8 c.i. N/A STEEL-FRAMED: R-13 + R-7.5 c.i. R-13 + R-9 c.i.
WOOD-FRAMED AND OTHER: R-13 + R-3.8 c.i. or R-20 N/A
WALL, BELOW GRADE
BELOW-GRADE WALL: R-7.5 c.i. N/A
FLOORS
MASS: R-14.6 c.i. N/A
STEEL-FRAMED: R-30 N/A
WOOD-FRAMED AND OTHER: R-30 N/A
SLAB-ON-GRADE FLOORS
UNHEATED SLABS: R-15 FOR 24 in. N/A HEATED SLABS: R-20 for 24 in. N/A
OPAQUE DOORS
SWINGING: U-0.370 N/A
NONSWINGING: U-0.310 N/A
VERTICAL FENESTRATION, U-FACTOR
NON-METAL FRAMING (ALL): U-0.31 N/A
METAL FRAMING, FIXED: U-0.36 N/A
METAL FRAMING, OPERABLE: U-0.45 N/A
METAL FRAMING, ENTRANCE DOOR: U-0.63 N/A
SKYLIGHT, 0% TO 3% OF ROOF, U-FACTOR
ALL TYPES: U-0.50 N/A
ENERGY REQUIREMENTS
N
1. DRAWINGS ARE PART OF A COMPLETE DOCUMENTS SET. CONTRACTOR SHALL
CONFIRM ALL ITEMS REQUIRED BASED UPON THE OVERALL DESIGN INTENT OF
THE ENTIRE DOCUMENT SET.
2. CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS, PRIOR TO BEGINNING
ANY WORK, TO CONFIRM THE ACCURACY OF THE DRAWINGS AND REPORT ANY
DISCREPANCIES TO THE ARCHITECT. DO NOT SCALE THE DRAWINGS. FIELD
VERIFY ALL DIMENSIONS AND EXISTING STRUCTURAL CONDITIONS.
3. ALL AREAS NOT INVOLVED IN THE SCOPE OF WORK FOR THIS PROJECT SHALL BE
KEPT CLEAN AND FREE OF OBSTRUCTIONS AT ALL TIMES.
4. ERECT BARRICADES AND WARNING SIGNS TO DIVERT AND WARN PASSERS-BY OF
THE CONSTRUCTION WORK. PROVIDE DUST PROOFING ENCLOSURES TO
SEPARATE WORK AREAS FROM THE EXISTING FACILITIES.
5. ALL TRASH AND DEBRIS TO BE REMOVED ON A DAILY BASIS.
6. PROVIDE PROTECTION FOR ALL EXISTING SURFACES AND CONDITIONS TO
REMAIN IN PLACE DURING THE SCOPE OF WORK. SHOULD ANY DAMAGE OCCUR,
PATCH AND REPAIR ANY DAMAGE TO ADJACENT FINISHES TO MATCH EXISTING.
7. ANY DAMAGE CAUSED TO THE BUILDING OR OWNER EQUIPMENT SHALL BE
REPAIRED OR REPLACED BACK TO ITS ORIGINAL CONDITIONS AT NO ADDITIONAL
COST TO THE OWNER.
8. COVER ALL RETURN AIR GRILLES WITHIN THE AREA OF CONSTRUCTION TO
PREVENT PARTICULATE MATERIAL FROM EXHAUSTING INTO SURROUNDING
SPACES.
9. APPROPRIATE LIGHT FIXTURES SHALL BE TEMPORARILY SUSPENDED TO
PROVIDE ADEQUATE LIGHTING LEVELS FOR CONSTRUCTION.
10. CONTRACTOR AND SUBCONTRACTORS ARE REQUIRED TO COORDINATE WITH
OTHER DISCIPLINES TO INSTALL COMPLETE AND OPERATIONAL SYSTEMS.
DRAWINGS, AS A WHOLE, REPRESENT A COMPLETE SET AND DEPICT
REQUIREMENTS FOR COMPLETE AND OPERATIONAL SYSTEMS. INDIVIDUAL
DRAWINGS MAY NOT DEPICT COMPLETE AND ACCURATE INFORMATION TO
COORDINATE COMPLETE AND OPERATIONAL SYSTEMS, BUT DO SO AS AN ENTIRE
DOCUMENT TO BE REFERENCED WITH OTHER INDIVIDUAL DRAWINGS.
CONTRACTOR AND SUBCONTRACTORS ARE REQUIRED TO REFERENCE OTHER
SHEETS AND SPECIFICATIONS AS AN ENTIRE SET OF CONSTRUCTION
DOCUMENTS THAT REFLECT WORK REQUIRED TO ACHIEVE A COMPLETE AND
OPERATIONAL GOAL. LACK OF COORDINATION AND REVIEW OF DRAWINGS AND
SPECIFICATIONS AS AN ENTIRE DOCUMENT TO INSTALL COMPLETE AND
OPERATIONAL SYSTEMS, BEING OBVIOUS AND TYPICAL INDUSTRY STANDARD,
IDENTIFIED IN THE DRAWINGS AND SPECIFICATIONS, SHALL NOT BE IN ANY WAY
AN ADDITIONAL COST TO THE GOVERNMENT.
11. CONTRACTOR SHALL SUBMIT A REQUEST, IN WRITING, TO INTERRUPT ANY SUCH
SERVICES TO COR (CONTRACTING OFFICER’S REPRESENTATIVE) 48 HOURS IN
ADVANCE OF PROPOSED INTERRUPTION. REQUEST SHALL STATE REASON, DATE,
EXACT TIME OF, AND APPROXIMATE DURATION OF SUCH INTERRUPTION. MAJOR
INTERRUPTIONS OF ANY SYSTEM MUST BE REQUESTED, IN WRITING, AT LEAST 60
CALENDAR DAYS PRIOR TO THE DESIRED TIME AND SHALL BE PERFORMED AS
DIRECTED BY THE COR. MAJOR INTERRUPTIONS SHALL BE COORDINATED WITH
OTHER MAJOR INTERRUPTIONS AND MAY NOT BE SCHEDULED FOR ONE
DISCIPLINE MORE THAN TWICE THROUGHOUT THE OVERALL CONSTRUCTION
SCHEDULE UNLESS REQUESTED IN WRITING AND APPROVED BY THE COR.
CONTRACTOR WILL BE ADVISED, IN WRITING, OF APPROVAL OF REQUEST, OR OF
WHICH OTHER DATE AND/OR TIME SUCH INTERRUPTION WILL CAUSE THE LEAST
INCONVENIENCE TO OPERATIONS OF THE MEDICAL CENTER. INTERRUPTION TIME
APPROVED BY THE MEDICAL CENTER MAY OCCUR AT TIMES OTHER THAN
CONTRACTOR'S NORMAL WORKING HOURS. SCHEDULE INTERRUPTION MAY BE
ON WEEKENDS OR LATE HOURS AND MAY NOT BE AN ADDITIONAL COST TO THE
GOVERNMENT. COORDINATE ALL INTERRUPTIONS THAT MAY AFFECT THE
NORMAL OPERATION OF THE FACILITY WITH THE COR WHEN SUBMITTING THE
CONSTRUCTION SCHEDULE OR UPDATES TO THE CONSTRUCTION SCHEDULE.
12. NO ASBESTOS CONTAINING MATERIALS ARE TO BE USED ON THIS PROJECT.
SPUR DESIGN, THE A/E OF RECORD, CAN CERTIFY THAT NO ASBESTOS
CONTAINING BUILDING MATERIALS (ACBM) OR LEAD BASED PAINT (LBP)
PRODUCTS WERE DESIGNED/SPECIFIED AS BUILDING MATERIAL IN ANY OF THE
CONSTRUCTION DOCUMENTS.
13. ONCE EACH FLOOR OF THE COURTYARD INFILL PORTION OF THE SCOPE OF
WORK IS ENCLOSED, ALL CONNECTIONS, PENETRATIONS, AND OPENINGS
BETWEEN THE INFILL SCOPE OF WORK AND THE EXISTING BUILDING ARE TO BE
SEPARATED BY A 1 HOUR FIRE BARRIER. 1 HOUR FIRE BARRIER TO REMAIN AT
ALL CONNECTIONS, PENETRATIONS, AND OPENINGS UNTIL FIRE SUPPRESSION
SYSTEM IS INSTALLED AND OPERABLE.
13. REFER TO THE DESIGN BINDER FOR ICRA INFORMATION DOCUMENTATION.
GENERAL NOTES
AREA NAME
150 SF
A101
A101
SIM
00000
00.0
A101
1 1
A101
LEVEL NAME
00'-00"
00'-00"
4B
3A
ROOM NAME
000A
150 SF
/1 A101 X0000
ROOM TAG
AREA TAG
SPECIALTY EQUIPMENT TAG
DOOR TAG
KEYED NOTE TAG
WALL TAG
WINDOW TAG
A101
SIM
A101
SIM
REFERENCE SYMBOLS IDENTIFICATION TAGS
NOTE: NOT ALL ABBREVIATIONS OR SYMBOLS WILL BE UTILIZED FOR THIS PROJECT.
GRID HEAD AND
LINE
LEVEL INDICATOR
MATCH LINE AND
VIEW REFERENCE
NORTH ARROW W/
PROJECT NORTH
SPOT ELEVATION
DETAIL
SECTION
**48" MIN IF BOTH CLOSER
AND LATCH PROVIDED
WALL
SECTION
BUILDING
SECTION
DETAIL
ELEVATION
INTERIOR
ELEVATION
BUILDING
ELEVATION
1 1
6'- 0"
5'- 6"
BARIATRIC TOILET ROOM
TURNING RADIUS
CLEAR FLOOR SPACE
@ ADA LAVATORY
CLEAR FLOOR SPACE
@ ADA DRINKING
FOUNTAIN
4' -0
M
A X
4' -0
M
A X
2' -1
0" M
A X
2' -3
M
IN
1'-6" MIN
1. GENERAL CONTRACTOR TO PROVIDE METAL SUPPORT
BLOCKING FOR ALL WALL MOUNTED ACCESSORIES,
FIXTURES, AND EQUIPMENT.
2. PROVIDE ADA SUPPORT BRACKETS PLACED AT ALL OPEN
COUNTERTOPS - 36"-48" MAX ON CENTER.
3. SPECIFIED MAXIMUMS ARE MEASURED FROM AFTER
FINISHED FLOOR TO THE OPERABLE PART OF THE FIXTURE.
4. FIXTURES SHOWN ARE REPRESENTATIONAL ONLY. NOT ALL
FIXTURES MAY BE USED. REFER TO SPECIFICATIONS FOR
FIXTURE TYPES USED IN THIS PROJECT.
5. FIXTURES MAY OVERLAP WAINSCOT. WHERE APPLICABLE,
BACKING TO BE PROVIDED AS SHIM FOR FLUSH
APPLICATION. SHIM TO MATCH SCHEDULED WALL FINISH.
6" MAX
9" M
IN
SHOWER
DRINKING
FOUNTAIN
PAPER TOWEL
DISPENSER
SANITARY
NAPKIN
DISPENSER
4' -0
"M A
X
WASTE
RECEPTACLE
LAVATORY
WITH MIRROR
ON CENTER
WALL
4' -0
M
A X
SOAP
DISPENSER
2' -1
0" M
A X
T O
B .O
. R E
F
LE
C T
IV
E
S U
R F
A C
E
3' -4
M
A X
17 MIN
2' -3
M
IN
3' -0
M
A X
1'-6" MIN
WALL
2' -9
" 4' -0
M
IN
2'-0" MIN
8" MIN
WALL
LAVATORY
WITH APRON
1' -5
M
A X
1'-6" MIN
URINAL
WALL
1'-5" - 1'-7" (AMBULATORY)
1'-4" - 1'-6" (WHEELCHAIR)
CLEAR FLOOR
5'-6"
CLEAR FLOOR
6'-0"
3'-0" MIN
2' -9
3' -0
1'-0" MIN
3'-6" MIN 1'-0"MAX
4'-6" MIN
1' -5
'-7
1' -6
M
IN
A N
S I I
C C
A
7.
1)
1' -3
M
IN
A D
A /A
B A
2' -9
'-0
WALL
WALL
4' -0
M
A X
WALL HOOK
6' -6
CLOCK
WALL
FINISHED FLOOR
FIRE EXTINGUISHER
CABINET
WEIGHT > 40LBS
FIRE EXTINGUISHER
CABINET
WEIGHT < 40LBS
4' -0
"M A
X
4' -0
M
A X
TOILET SEAT
COVER
DISPENSER
BABY
CHANGING
STATION
HANDRAILS AND
BUMPERGUARDS
6"
3' -0
M
A X
4"
6"
3"
6"
M
IN
1' -6
6" MAX
7" - 9" 11" MIN
17" - 25"
(ANSI ICC A117.1)
39"- 41"
(A N
S I I
C C
A
7.
1)
M
IN
(A N
S I I
C C
A
7.
1)
1"
3' -6
M
A X
5' -0
M
A X
FIBERGLASS BATT
INSULATION
RIGID INSULATION
CONCRETE / PRECAST
CONCRETE
EARTH / SOIL
SAND, EIFS FINISH, OR
PLASTER FINISH
GYPSUM BOARD FINISH
BRICK
CONCRETE MASONRY
UNIT
STONE / CAST STONE
GYPSUM BOARD SECTION
EXTERIOR SHEATHING
BOARD SECTION
PLYWOOD SECTION
A
ACB ACOUSTIC CEILING BAFFLE
ACP ACOUSTIC CEILING PANEL
ACST ACOUSTIC
ADA AMERICANS WITH DISABILITIES ACT
ACT ACOUSTICAL CEILING TILE
ADDL ADDITIONAL
ADDN ADDITION
ADJ ADJACENT, ADJOINING, OR
ADJUSTABLE
ADMIN ADMINISTRATION
AE ARCHITECT/ENGINEER
AF ACCESS FLOORING
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHJ AUTHORITY HAVING JURISDICTION
AIA AMERICAN INSTITUTE OF
ARCHITECTS
ALT ALTERNATE
ALT NO ALTERNATE NUMBER
ALUM ALUMINIUM (TRIM)
AMT AMOUNT
APPROX APPROXIMATE
ARCH ARCHITECT
ASC ABOVE SUSPENDED CEILING
AT ACOUSTIC CEILING TILE
AVG AVERAGE
B
BD BOARD
BLDG BUILDING
BLKG BLOCKING
BLT IN BUILT-IN
BOS BOTTOM OF STEEL
BOT BOTTOM
BRKT BRACKET
BTWN BETWEEN
C
CAB CABINET
CAV CAVITY
CBB CONCRETE BACKER BOARD
CD CONSTRUCTION DOCUMENTS
CFM CUBIC FEET PER MINUTE
CFS CUBIC FEET PER SECOND
CG CORNER GUARD
CH BD CHALK BOARD
CIP CAST-IN-PLACE
CJ CONTROL JOINT
CL CENTER LINE
CLG CEILING
CLG HT CEILING HEIGHT
CLR CLEAR
CMU CONCRETE MASONRY UNIT
CO CONTRACTING OFFICER
COL COLUMN
COMM COMMUNICATION
CONC CONCRETE
CONT CONTINUOUS
COORD COORDINATE
COR CONTRACTING OFFICER'S
REPRESENTATIVE
CP CONTRACTOR PROVIDED
CP/CI CONTRACTOR PROVIDED /
CONTRACTOR INSTALLED
CPT CAROET/CARPET TILE
CS CONCRETE SEALED
CSWK CASEWORK
CT CERAMIC TILE
CTB CERAMIC TILE BASE
CTR CENTER
CU FT CUBIC FEET
D
DBL DOUBLE
DEMO DEMOLITION
DEPT DEPARTMENT
DET DETAIL
DIA DIAMETER
DIR DIRECTION
DIST DISTANCE
DOC DOCUMENT
DR DOOR
DS DOWNSPOUT
DWG DRAWING
DWP DIMENSIONAL WALL PANEL
E
EA EACH
EJ EXPANSION JOINT
EL ELEVATION
ELEV ELEVATOR
ENTR ENTRANCE
EPY EPXOY FLOORING
EQ EQUAL
ETR EXISTING TO REMAIN
EX EXISTING
EXP EXPOSED
EXT EXTERIOR
F
FAB FABRIC
FED FEDERAL
FF FINISH FACE
FF EL FINISH FLOOR ELEVATION
FIN FINISH
FIN BS FINISH BOTH SIDES
FIN FLR FINISH FLOOR
FIN GR FINISH GRADE
FIXT FIXTURE
FLDG FOLDING
FLEX FLEXIBLE
FLG FLOORING
FLMT FLUSH MOUNT
FLR FLOOR
FOC FACE OF CONCRETE
FOM FACE OF MASONRY
FP FIRE PROTECTION
FR FIRE RESISTANT
FT FEET
FTG FOOTING
FV FIELD VERIFY
FWC FABRIC WALL COVERING
G
GDR GUARDRAIL
GL GLASS/GLAZING
GRAN GRANITE
GR FL GROUND FLOOR
GT GROUT
GSM GALVANIZED SHEET METAL
GYP BD GYPSUM BOARD
H
HDW HARDWARE
HEPA HIGH EFFICIENCY
PARTICULATE AIR (FILTER)
HM HOLLOW METAL
HORIZ HORIZONTAL
HR HANDRAIL
HT HEIGHT
I
IBC INTERNATIONAL BUILDING CODE
INSUL INSULATION
INT INTERIOR
ILO IN LIEU OF
J
J-BOX JUNCTION BOX
L
LAV LAVATORY
LBS POUND
LDG LANDING
LF LINEAR FEET (FOOT)
LIN LINEAR
LN LINOLEUM
LOC LOCATION
LT LIGHT
LVR LOUVER
LVT LUXURY VINYL TILE
M
MAT CARPET MAT / WALK-OFF MAT
MATL MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MEMB MEMBRANE
MFR MANUFACTURER
MID MIDDLE
MIL STD MILITARY STANDARD
MIN MINIMUM
MISC MISCELLANEOUS
MO MASONRY OPENING
MOD MODIFY
MTG MOUNTING
MTL METAL
MVBL MOVABLE
N
NA NOT APPLICABLE
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NTS NOT TO SCALE
O
OA OVERALL
OC ON CENTER
OD OUTSIDE DIAMETER
OPNG OPENING
OPP OPPOSITE
OPR OPERABLE
ORD OVERFLOW ROOF DRAIN
ORIG ORIGINAL
P
P PAINT
PA PUBLIC ADDRESS
PBD PARTICLE BOARD
PCF POUNDS PER CUBIC FOOT
PCT PERCENT
PERF PERFORATED
PERIM PERIMETER
PERP PERPENDICULAR
PL PROPERTY LINE
PLAM PLASTIC LAMINATE
PLBG PLUMBING
PNL PANEL
PR PAIR
PRB PROFILE BASE
PRKG PARKING
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PORCELAIN TILE
PWR POWER
Q
QA QUALITY ASSURANCE
QC QUALITY CONTROL
QTY QUANTITY
R
RAF RESILIENT ATHETIC FLOORING
RB RUBBER BASE/RESILIENT BASE
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
REC RECESSED
REF REFERENCE
REM REMOVABLE
REP REPAIR
REPL REPLACE
REQ REQUIRE
REQD REQUIRED
RES RESINOUS FLOORING
RES-W RESINOUS / EPOXY
WALL / CEILING
RF RUBBER FLOORING
RFG ROOFING
RM ROOM
RO ROUGH OPENING
RP RESIN PANEL
RSF RESILIENT SHEET FLOORING
RV ROOF VENT
RWC RIGID VINYL WALLCOVERING
S
SC SPECIALTY COATING
SD STATIC DISSIPATIVE
FLOORING/TILE
SCHED SCHEDULE
SECT SECTION
SF SQUARE FOOT (FEET)
SGL SINGLE
SIM SIMILAR
SJ SCORED JOINT
SLNT SEALANT
SM SHEET METAL
SPEC SPECIFICATION
SQ SQUARE
SQ IN SQUARE INCH
SQ YD SQUARE YARD
SS SOLID SURFACE
ST STONE
STD STANDARD
STOR STORAGE
SV SHEET VINYL (ROLLED OR TILE)
T
TEL TELEPHONE
TEMP TEMPORARY
TER TERRAZO
TOF TOP OF FOOTING/ FOUNDATION
TOM TOP OF MASONRY
TOS TOP OF SLAB/ STEEL
U
UNO UNLESS NOTED OTHERWISE
UTIL UTILITY
V
VAR VARIES
VC VA PROVIDED / CONTRACTOR
INSTALLED
VCT VINYL COMPOSITION TILE
VFAT VINYL FACED ACOUSTICLAL TILE
VP VENEERED PLASTER
VT VINYL TILE
VV VA PROVIDED / VA INSTALLED
VWC VINYL WALLCOVERING
VWF VINYL WALL FABRIC
W
W/ WITH
W/O WITHOUT
W/C WATER CLOSET
WC WHEELCHAIR
WD WOOD
WFAB WALL FABRIC
WPM WATERPROOF MEMBRANE
WSF WELDED SHEET FLOOR
X
X BRACE CROSS BRACE
PROJECT SCOPE LEGEND
AREAS OF WORK OUTSIDE OF
CURRENT PHASE OR OUTSIDE
OF PROJECT SCOPE.
PLAN NORTH
TRUE NORTH
1'-3" th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
KS ARCH REG. NO. A-930, EXP. 12/31/2023
KS ENGR REG. NO. E-2586, EXP. 12/31/2023
STRUCTURAL / CIVIL ENGINEER
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB / TECH ENGR
SPUR DESIGN
25219 MADISON AVENUE, SUITE 100
KANSAS CITY, MO 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT HEALTH & SAFETY
1139 OLIVE STREET,
ST. LOUIS, MO 63101
(314) 436-9492
HEALTHCARE PLANNER
INNOVA GROUP
3196 N. SWAN ROAD
TUCSON, AZ 85712
(520) 886-8650
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH ROAD, STE 1415
PANAMA CITY, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:SPUR #: 2016
/2
/2
:5 :0
A
M
GI001
GENERAL INFORMATION
ECO
2 OF 190AJS
100% BID SET
CONSTRUCT INFILL OF
BUILDING 26 AND RENOVATE
SPECIALTY CARE CLINICS
12/21/2022
589-704
5500 EAST KELLOGG AVENUE
WICHITA, KANSAS 67218
DN
A
UP
PHASE 1 - INFILL STRUCTURE AND NEW CONSTRUCTION
PHASE 2 - CONSTRUCT
SPECIALTY CARE RENOVATION
BLDG 61
BLDG 29BLDG 62
B
B62
B
B
B
B
B
B
B
B29
B3
BLDG 26
PHASING PLAN LEGEND
PHASE 1 - NEW INFILL CONSTRUCTION & LIMITED RENOVATION
• EXCAVATE COURTYARD IN PREPARATION FOR NEW CONSTRUCTION
• CONSTRUCT COURTYARD INFILL STRUCTURE AND SHELL FOR GROUND
FLOOR AND FIRST FLOOR
• CONSTRUCT NEW INTERIOR CONSTRUCTION & RENOVATION FOR
GROUND FLOOR CANTEEN
• CONSTRUCT NEW INTERIOR CONSTRUCTION FOR FIRST FLOOR
SPECIALTY CARE WITHIN NEW INFILL STRUCTURE (BID DEDUCT OPTION)
• CONSTRUCT LIMITED INTERIOR RENOVATION INCLUDING THE BUILDING
61 CONNECTING CORRIDOR
• REPLACE EMERGENCY GENERATOR
PHASE 2 - GROUND FLOOR AND FIRST FLOOR RENOVATION
• CONSTRUCT GROUND FLOOR DENTAL CLINIC RENOVATION
• CONSTRUCT FIRST FLOOR SPECIALTY CARE RENOVATION
(BID DEDUCT OPTION)
PHASE 3 - POLICE SUBSTATION
• CONSTRUCT GROUND FLOOR POLICE SUBSTATION
PHASE 4 - EXTERIOR IMPROVEMENTS SERVICE YARD
• CONSTRUCT NORTHEAST SERVICE YARD (OR MAINTENANCE FENCE IN
EVENT OF SERVICE YARD BID DEDUCT)
• REFERENCE SHEET AE201 FOR MORE INFORMATION AND FULL SCOPE
PHASE 1 - INFILL
STRUCTURE AND NEW
CONSTRUCTION
PHASE 1 - CONSTRUCT
CANTEEN RENOVATION SCOPE
PHASE 2 - CONSTRUCT DENTAL CLINIC RENOVATION
BLDG 61
BLDG 29BLDG 62
B
B62
B
B
B
B
B
B
B
B29
B3
BLDG 26
SERVICE
YARD
E001
PHASE 1
PHASE 3
PHASE 4
BLDG 26
TRUE NORTH
GROUND FLOOR CANTEEN (INFILL)
FIRST FLOOR SPECIALTY CARE (INFILL)
(BID DEDUCT OPTION)
BLDG 61
BLDG 61
BLDG 26
TRUE NORTH
GROUND FLOOR DENTAL CLINIC RENOVATION
FIRST FLOOR SPECIALTY CARE RENOVATION
(BID DEDUCT OPTION)
PHASING AND PROJECT SCOPE LEGEND
AREAS OF WORK OUTSIDE OF CURRENT PHASE OR OUTSIDE OF PROJECT
SCOPE SHOWN. REFERENCE GI011 - PHASING PLANS FOR MORE INFORMATION.
BLDG 61
BLDG 26
TRUE NORTH
GROUND FLOOR POLICE SUBSTATION RENOVATION
BLDG 61
BLDG 26
TRUE NORTH
GROUND FLOOR EXTERIOR SERVICE YARD
PHASE 4 - EXTERIOR SERVICE YARD
KEY PLAN - GROUND FLOOR & FIRST FLOOR
BLDG 26BLDG 61
BLDG 29
BLDG 03PHASE ONE
N
KEY PLAN - GROUND FLOOR AND FIRST FLOOR
BLDG 26
BLDG 61
BLDG 29
BLDG 03
PHASE TWO
N
PHASE THREE
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
KS ARCH REG. NO. A-930, EXP. 12/31/2023
KS ENGR REG. NO. E-2586, EXP. 12/31/2023
STRUCTURAL / CIVIL ENGINEER
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB / TECH ENGR
SPUR DESIGN
25219 MADISON AVENUE, SUITE 100
KANSAS CITY, MO 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT HEALTH & SAFETY
1139 OLIVE STREET,
ST. LOUIS, MO 63101
(314) 436-9492
HEALTHCARE PLANNER
INNOVA GROUP
3196 N. SWAN ROAD
TUCSON, AZ 85712
(520) 886-8650
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH ROAD, STE 1415
PANAMA CITY, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:SPUR #: 2016
/2
/2
:5 :1
A
M
GI011
PHASING PLANS
ECO
3 OF 190AJS
100% BID SET
CONSTRUCT INFILL OF
BUILDING 26 AND RENOVATE
SPECIALTY CARE CLINICS
12/21/2022
589-704
5500 EAST KELLOGG AVENUE
WICHITA, KANSAS 67218
N
1/16" = 1'-0"
FIRST FLOOR - PHASING PLAN - OVERALL2
N
1/16" = 1'-0"
GROUND FLOOR - PHASING PLAN - OVERALL1
PHASE 1 - NEW CONSTRUCTION & LIMITED RENOVATIONPHASE 2 - DENTAL CLINIC RENOVATIONPHASE 3 - POLICE SUBSTATION
ISOMETRIC PHASING DIAGRAMS3
FD
SFD
S
A
ASSEMBLY, CONCENTRATED
ASSEMBLY, KITCHEN
ASSEMBLY, LESS CONCENTRATED
BUSINESS
MERCANTILE, STREET FLOOR
STORAGE USE, OTHER
B61
B26
B3
B29
B62
BUSINESS
14560 SF
BUSINESS
4482 SF
ASSEMBLY, LESS
CONCENTRATED
2662 SF
ASSEMBLY, KITCHEN
1720 SF
STORAGE USE,
OTHER
528 SF
BUSINESS
295 SF
MERCANTILE, STREET
FLOOR
1591 SF
STORAGE USE,
OTHER
1791 SF
BUSINESS
22005 SF
BUSINESS
13686 SF
BUSINESS
7768 SF
STORAGE USE,
OTHER
441 SF
STORAGE USE,
OTHER
456 SF
STORAGE USE,
OTHER
238 SF
STORAGE USE,
OTHER
379 SF
STORAGE USE,
OTHER
298 SF
STORAGE USE,
OTHER
373 SF
STORAGE USE,
OTHER
292 SF
STORAGE USE,
OTHER
305 SF
B61 B26
B3
B29
B62
BUSINESS
9123 SF
ASSEMBLY,
CONCENTRATED
1542 SF
BUSINESS
11229 SF
BUSINESS
25449 SF
STORAGE USE,
OTHER
1147 SF
BUSINESS
10316 SF
BUSINESS
6032 SF
BUSINESS
673 SF
KEY PLAN
BLDG 26
BLDG 3 BLDG 1
BLDG 2BLDG 19
BLDG 61
BLDG 62
BLDG 29
N
PHASE FOUR
SERVICE YARD
EXISTING BUILDING HEIGHT: BUILDING 26
3 STORIES, APPROX. 35'-0" HEIGHT
BUILDING AREA:
AREA LIMITATION: 69,000 SQUARE FEET (2021 IBC TABLE 506.2)
GROUND FLOOR 22,720 GROSS SQUARE FEET
FIRST FLOOR 22,720 GROSS SQUARE FEET
SECOND FLOOR 17,590 GROSS SQUARE FEET
TOTAL 63,030 GROSS SQUARE FEET
NFPA 101-2021 CHAPTER 7- TABLE 7.3.1.2 OCCUPANT LOADS
NFPA 101-2021 CHAPTER 7- 7.2.1.2.3.2) MINIMIM DOOR LEAF WIDTH
MINIMUM DOOR OPENING WIDTH OF 32"
NFPA 101-2021 CHAPTER 7- TABLE 7.3.3.1 CAPACITY FACTORS
NFPA 220-2021 CHAPTER 4- TABLE 4.1.1
CONSTRUCTION TYPE: TYPE II (000)
FIRE RESISTANCE RATINGS
COLUMNS: 0 HR
BEAM, GIRDERS, TRUSSES: 0 HR
FLOOR/CEILING ASSEMBLIES: 0 HR
ROOF/CEILING ASSEMBLIES: 0 HR
EXTERIOR NON-BEARING WALLS: 0 HR
INTERIOR NON-BEARING WALLS: 0 HR
FIRE-RESISTIVE REQUIREMENTS:
NON COMBUSTIBLE MATERIALS FOR STRUCTURAL FRAME, FLOORS, ROOF DECK, EXTERIOR
NON-BEARING WALLS, INTERIOR NON-BEARING WALLS (U.N.O. AT EXTERIOR)
NFPA 101-2021 CHAPTERS 12, 36, 38, 39 & 42 TRAVEL DISTANCE
NFPA 101-2021 CHAPTERS 12, 36, 38, 39, & 42 COMMON PATH OF TRAVEL
NFPA 101-2021 CHAPTERS 12, 36, 38, 39 & 42 DEAD END CORRIDOR
PROTECTED AREAS: STORAGE ROOMS/CLEAN/SOILED:
PER VA FIRE PROTECTION DESIGN MANUAL 3.1.A, STORAGE ROOMS ARE HAZARDOUS AREAS.
PER NFPA 101: 39.3.2.1, HAZARDOUS AREAS SHALL BE PROTECTED AS STATED IN SECTION 8.7.
PER NFPA 101: 8.7, ANY AREA HAVING A DEGREE OF HAZARD GREATER THAN THAT NORMAL
TO THE GENERAL OCCUPANCY SHALL BE PROVIDED BY ONE OF THE FOLLOWING:
• 1 HR FIRE BARRIER OR PROTECTING THE AREA WITH AUTOMATIC EXTINGUISHING SYSTEM
• SPRINKLER PROTECTION PROVIDED.
SMOKE COMPARTMENTALIZATION: NOT REQUIRED FOR BUSINESS OCCUPANCIES, NOT PROVIDED.
FIRE ALARM SYSTEM: REQUIRED / PROVIDED AUTOMATIC SYSTEM.
STANDPIPES: NOT REQUIRED / NOT PROVIDED.
LIFE SAFETY CODE ANALYSIS
LIFE SAFETY LEGEND
FEC FIRE EXTINGUISHER CABINET
EXIT LIGHT / SIGN
NOT IN SCOPE
BUILDING EXIT
EGRESS PATH 1 HR FIRE RATED PARTITION
S T
A
IR000
DOOR CAPACITY TAG (STAIR)
OCCUPANCY AREA LEGEND
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
KS ARCH REG. NO. A-930, EXP. 12/31/2023
KS ENGR REG. NO. E-2586, EXP. 12/31/2023
STRUCTURAL / CIVIL ENGINEER
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB / TECH ENGR
SPUR DESIGN
25219 MADISON AVENUE, SUITE 100
KANSAS CITY, MO 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT HEALTH & SAFETY
1139 OLIVE STREET,
ST. LOUIS, MO 63101
(314) 436-9492
HEALTHCARE PLANNER
INNOVA GROUP
3196 N. SWAN ROAD
TUCSON, AZ 85712
(520) 886-8650
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH ROAD, STE 1415
PANAMA CITY, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:SPUR #: 2016
/2
/2
:5 :2
A
M
GI012
OCCUPANCY PLANS
ECO
4 OF 190AJS
100% BID SET
CONSTRUCT INFILL OF
BUILDING 26 AND RENOVATE
SPECIALTY CARE CLINICS
12/21/2022
589-704
5500 EAST KELLOGG AVENUE
WICHITA, KANSAS 67218
N
1/32" = 1'-0"
GROUND FLOOR- OCCUPANCY PLAN1
N
1/32" = 1'-0"
FIRST FLOOR - OCCUPANCY PLAN2
PLUMBING FIXTURE REQUIREMENTS
OCCUPANT TYPE OCCUPANT LOAD
WATER CLOSETS LAVATORY
MALE FEMALE MALE FEMALE
BLDG 26
FIRST FLOOR
BUSINESS 351 5 5 4 4
GROUND FLOOR
BUSINESS 341 5 5 4 4
ASSEMBLY, CONCENTRATED 12.2.6.2- SHALL NOT EXCEED 250'-0"
ASSEMBLY, KITCHEN 12.2.6.2- SHALL NOT EXCEED 250'-0"
ASSEMBLY, LESS CONCENTRATED 12.2.6.2- SHALL NOT EXCEED 250'-0"
BUSINESS 38.2.6.3- SHALL NOT EXCEED 300'-0"
MERCANTILE, STREET FLOOR 36.2.6.2- SHALL NOT EXCEED 250'-0"
STORAGE USE, OTHER 42.2.6- SHALL NOT EXCEED 400'-0"
ASSEMBLY, CONCENTRATED 7 7 NET SF/PERSON
ASSEMBLY, KITCHEN 100 100 NET SF/PERSON
ASSEMBLY, LESS CONCENTRATED 15 15 NET SF/PERSON
BUSINESS 150 150 NET SF/PERSON
MERCANTILE, STREET FLOOR 30 30 NET SF/PERSON
STORAGE USE, OTHER 500 500 NET SF/PERSON
ASSEMBLY, CONCENTRATED 12.2.5.2- 20’-0” <50 OCCUPANTS / 75’-0” >50 OCCUPANTS
ASSEMBLY, KITCHEN 12.2.5.2- 20’-0” <50 OCCUPANTS / 75’-0” >50 OCCUPANTS
ASSEMBLY, LESS CONCENTRATED 12.2.5.2- 20’-0” <50 OCCUPANTS / 75’-0” >50 OCCUPANTS
BUSINESS 38.2.5.2.1- SHALL NOT EXCEED 100'-0"
MERCANTILE, STREET FLOOR 36.2.5.2- SHALL NOT EXCEED 100'-0"
STORAGE USE, OTHER 42.2.5- SHALL NOT EXCEED 100'-0"
ASSEMBLY, CONCENTRATED 12.2.5.3- SHALL NOT EXCEED 20'-0"
ASSEMBLY, KITCHEN 12.2.5.3- SHALL NOT EXCEED 20'-0"
ASSEMBLY, LESS CONCENTRATED 12.2.5.3- SHALL NOT EXCEED 20'-0"
BUSINESS 38.2.5.3.1- SHALL NOT EXCEED 50'-0"
MERCANTILE, STREET FLOOR 36.2.5.3.1- SHALL NOT EXCEED 50'-0"
STORAGE USE, OTHER 42.2.5- SHALL NOT EXCEED 100'-0"
OCCUPANT LOAD PER NFPA 101-2021
OCCUPANT TYPE
PER TABLE 7.3.1.2.
AREA
OCC. LOAD
FACTOR IN SF
OCC. LOAD
BLDG 62
GROUND FLOOR
BUSINESS 7768 SF 150 SF 52
STORAGE USE, OTHER 820 SF 500 SF 2
8588 SF 53
FIRST FLOOR
BUSINESS 673 SF 150 SF 4
673 SF 4
OCCUPANT LOAD PER NFPA 101-2021
OCCUPANT TYPE
PER TABLE 7.3.1.2.
AREA
OCC. LOAD
FACTOR IN SF
OCC. LOAD
BLDG 61
GROUND FLOOR
BUSINESS 22005 SF 150 SF 147
STORAGE USE, OTHER 2247 SF 500 SF 4
24252 SF 151
FIRST FLOOR
BUSINESS 25449 SF 150 SF 170
STORAGE USE, OTHER 1147 SF 500 SF 2
26596 SF 172
OCCUPANT LOAD PER NFPA 101-2021
OCCUPANT TYPE
PER TABLE 7.3.1.2.
AREA
OCC. LOAD
FACTOR IN SF
OCC. LOAD
BLDG 29
GROUND FLOOR
BUSINESS 13686 SF 150 SF 91
STORAGE USE, OTHER 671 SF 500 SF 1
14356 SF 93
FIRST FLOOR
BUSINESS 10316 SF 150 SF 69
10316 SF 69
OCCUPANT LOAD PER NFPA 101-2021
OCCUPANT TYPE
PER TABLE 7.3.1.2.
AREA
OCC. LOAD
FACTOR IN SF
OCC. LOAD
BLDG 26
GROUND FLOOR
ASSEMBLY, KITCHEN 1720 SF 100 SF 17
ASSEMBLY, LESS CONCENTRATED 2662 SF 15 SF 177
BUSINESS 14855 SF 150 SF 99
MERCANTILE, STREET FLOOR 1591 SF 30 SF 53
STORAGE USE, OTHER 1058 SF 500 SF 2
21885 SF 349
FIRST FLOOR
ASSEMBLY, CONCENTRATED 1542 SF 7 SF 220
BUSINESS 20351 SF 150 SF 136
21893 SF 356
OCCUPANT LOAD PER NFPA 101-2021
OCCUPANT TYPE
PER TABLE 7.3.1.2.
AREA
OCC. LOAD
FACTOR IN SF
OCC. LOAD
BLDG 3
GROUND FLOOR
BUSINESS 4482 SF 150 SF 30
STORAGE USE, OTHER 305 SF 500 SF 1
4788 SF 30
FIRST FLOOR
BUSINESS 6032 SF 150 SF 40
6032 SF 40
OCCUPANT TYPE
LEVEL COMPONENTS
(WIDTH/PERSON)
STAIRWAYS
(WIDTH/PERSON)
ASSEMBLY, CONCENTRATED .2" .3"
ASSEMBLY, KITCHEN .2" .3"
ASSEMBLY, LESS CONCENTRATED .2" .3"
BUSINESS .2" .3"
MERCANTILE, STREET FLOOR .2" .3"
STORAGE USE, OTHER .2" .3"
B C D E F G
S T
A
IR
S T
A
IR
O T
H E
R
O T
H E
R
O T
H E
R
S T
A
IR
S T
A
IR
O T
H E
R
S T
A
IR
O T
H E
R
B
B62
B
B
B
B
B
B
B
B29
B3
H J K L M
TRAVEL DISTANCE = 204' - 0"
TRAVEL DISTANCE = 118' - 2"
TRAVEL DISTANCE = 185' - 1"
TRAVEL DISTANCE = 229' - 2"
FEC FEC
FEC
FEC
885 SF @ 15 NET = 57 OCC.
1352 SF @ 15 NET = 91 OCC.
TRAVEL DISTANCE = 208' - 8"
STAIR
FEC
12'-0" 19'-0" 19'-0" 19'-0" 19'-0" 19'-0" 7'-0" 12'-0" 13'-10 1/2" 5'-1 1/2" 12'-2"
'-4
8'
-4
'-6
7'
-9
7' -1
1/
2" 7'
-9
/2
7' -9
/2
7'
-1
1/ 2"
7' -9
'-4
8' -6
'-4
STAIR
FEC FEC
A
157'-2"
3'
-2
WORKSTATIONS
001A
WORKSTATIONS
001A
GUEST
SERVICES
HOLDING
CELL
001B
HOLDING
CELL
001B
HOLDING
CELL
001C
HOLDING
CELL
001C
FREEZER
025D
FOOD STG
025A
COOLER
025C
FOOD STG
025B
KITCHEN
CORRIDOR
C1
RETAIL
STORAGE
024A
RETAIL
STORE
DINING AREA
SAFE
026B
VCS CHIEF
OFFICE
026A
VCS OFFICE
DINING AREA
VENDOR
022A
CORRIDOR
C2
VESTIBULE
032A
LAB
DTR-1
DTR-2
DTR-3
DTR-4
DTR-5
DTR-6
DTR-7
DTR-8
CHIEF
035B
WORKSTATIONS
RECEPTION
035A
COPY /
SUPPLY
035F
LOCKER
035C
DRESSING
035E LOUNGE
035D
IT ROOM
HAC
DENTAL
MECH
STORAGE
ELEC
CLEAN
SUPPLY
STERILE
EQUIPMENT
MOBILE
EQUIPMENT
X-RAY
WAITING
CHECK-IN
KIOSK
034A
WC ALC.
034B
STF TLT
PAT TLT
MEDICATION
TRAY
STORAGE
SOILED
UTILITY
CAD/CAM
CART
A008
EQUIP
A007
LIFT
A006
EQUIP
A005
WC
A004
EQUIP
A003
EQUIP
A002
CRASH CART
A001
CORRIDOR
C3
ELECTRICAL
SECURITY
KEY PLAN
BLDG 26
BLDG 3 BLDG 1
BLDG 2BLDG 19
BLDG 61
BLDG 62
BLDG 29
N
PHASE FOUR
SERVICE YARD
EXISTING BUILDING HEIGHT: BUILDING 26
3 STORIES, APPROX. 35'-0" HEIGHT
BUILDING AREA:
AREA LIMITATION: 69,000 SQUARE FEET (2021 IBC TABLE 506.2)
GROUND FLOOR 22,720 GROSS SQUARE FEET
FIRST FLOOR 22,720 GROSS SQUARE FEET
SECOND FLOOR 17,590 GROSS SQUARE FEET
TOTAL 63,030 GROSS SQUARE FEET
NFPA 101-2021 CHAPTER 7- TABLE 7.3.1.2 OCCUPANT LOADS
NFPA 101-2021 CHAPTER 7- 7.2.1.2.3.2) MINIMIM DOOR LEAF WIDTH
MINIMUM DOOR OPENING WIDTH OF 32"
NFPA 101-2021 CHAPTER 7- TABLE 7.3.3.1 CAPACITY FACTORS
NFPA 220-2021 CHAPTER 4- TABLE 4.1.1
CONSTRUCTION TYPE: TYPE II (000)
FIRE RESISTANCE RATINGS
COLUMNS: 0 HR
BEAM, GIRDERS, TRUSSES: 0 HR
FLOOR/CEILING ASSEMBLIES: 0 HR
ROOF/CEILING ASSEMBLIES: 0 HR
EXTERIOR NON-BEARING WALLS: 0 HR
INTERIOR NON-BEARING WALLS: 0 HR
FIRE-RESISTIVE REQUIREMENTS:
NON COMBUSTIBLE MATERIALS FOR STRUCTURAL FRAME, FLOORS, ROOF DECK, EXTERIOR
NON-BEARING WALLS, INTERIOR NON-BEARING WALLS (U.N.O. AT EXTERIOR)
NFPA 101-2021 CHAPTERS 12, 36, 38, 39 & 42 TRAVEL DISTANCE
NFPA 101-2021 CHAPTERS 12, 36, 38, 39, & 42 COMMON PATH OF TRAVEL
NFPA 101-2021 CHAPTERS 12, 36, 38, 39 & 42 DEAD END CORRIDOR
PROTECTED AREAS: STORAGE ROOMS/CLEAN/SOILED:
PER VA FIRE PROTECTION DESIGN MANUAL 3.1.A, STORAGE ROOMS ARE HAZARDOUS AREAS.
PER NFPA 101: 39.3.2.1, HAZARDOUS AREAS SHALL BE PROTECTED AS STATED IN SECTION 8.7.
PER NFPA 101: 8.7, ANY AREA HAVING A DEGREE OF HAZARD GREATER THAN THAT NORMAL
TO THE GENERAL OCCUPANCY SHALL BE PROVIDED BY ONE OF THE FOLLOWING:
• 1 HR FIRE BARRIER OR PROTECTING THE AREA WITH AUTOMATIC EXTINGUISHING SYSTEM
• SPRINKLER PROTECTION PROVIDED.
SMOKE COMPARTMENTALIZATION: NOT REQUIRED FOR BUSINESS OCCUPANCIES, NOT PROVIDED.
FIRE ALARM SYSTEM: REQUIRED / PROVIDED AUTOMATIC SYSTEM.
STANDPIPES: NOT REQUIRED / NOT PROVIDED.
LIFE SAFETY CODE ANALYSIS
LIFE SAFETY LEGEND
FEC FIRE EXTINGUISHER CABINET
EXIT LIGHT / SIGN
NOT IN SCOPE
BUILDING EXIT
EGRESS PATH 1 HR FIRE RATED PARTITION
S T
A
IR000
DOOR CAPACITY TAG (STAIR)
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
KS ARCH REG. NO. A-930, EXP. 12/31/2023
KS ENGR REG. NO. E-2586, EXP. 12/31/2023
STRUCTURAL / CIVIL ENGINEER
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB / TECH ENGR
SPUR DESIGN
25219 MADISON AVENUE, SUITE 100
KANSAS CITY, MO 64108
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT HEALTH & SAFETY
1139 OLIVE STREET,
ST. LOUIS, MO 63101
(314) 436-9492
HEALTHCARE PLANNER
INNOVA GROUP
3196 N. SWAN ROAD
TUCSON, AZ 85712
(520) 886-8650
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH ROAD, STE 1415
PANAMA CITY, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:SPUR #: 2016
/2
/2
:5 :2
A
M
GI013
LIFE SAFETY PLAN - GROUND FLOOR
ECO
5 OF 190AJS
100% BID SET
CONSTRUCT INFILL OF
BUILDING 26 AND RENOVATE
SPECIALTY CARE CLINICS
12/21/2022
589-704
5500 EAST KELLOGG AVENUE
WICHITA, KANSAS 67218
N
1/8" = 1'-0"
GROUND FLOOR - LIFE SAFETY PLAN1
ASSEMBLY, CONCENTRATED 7 7 NET SF/PERSON
ASSEMBLY, KITCHEN 100 100 NET SF/PERSON
ASSEMBLY, LESS CONCENTRATED 15 15 NET SF/PERSON
BUSINESS 150 150 NET SF/PERSON
MERCANTILE, STREET FLOOR 30 30 NET SF/PERSON
STORAGE USE, OTHER 500 500 NET SF/PERSON
OCCUPANT TYPE
LEVEL COMPONENTS
(WIDTH/PERSON)
STAIRWAYS
(WIDTH/PERSON)
ASSEMBLY, CONCENTRATED .2" .3"
ASSEMBLY, KITCHEN .2" .3"
ASSEMBLY, LESS CONCENTRATED .2" .3"
BUSINESS .2" .3"
MERCANTILE, STREET FLOOR .2" .3"
STORAGE USE, OTHER .2" .3"
ASSEMBLY, CONCENTRATED 12.2.6.2- SHALL NOT EXCEED 250'-0"
ASSEMBLY, KITCHEN 12.2.6.2- SHALL NOT EXCEED 250'-0"
ASSEMBLY, LESS CONCENTRATED 12.2.6.2- SHALL NOT EXCEED 250'-0"
BUSINESS 38.2.6.3- SHALL NOT EXCEED 300'-0"
MERCANTILE, STREET FLOOR 36.2.6.2- SHALL NOT EXCEED 250'-0"
STORAGE USE, OTHER 42.2.6- SHALL NOT EXCEED 400'-0"
ASSEMBLY, CONCENTRATED 12.2.5.2- 20’-0” <50 OCCUPANTS / 75’-0” >50 OCCUPANTS
ASSEMBLY, KITCHEN 12.2.5.2- 20’-0” <50 OCCUPANTS / 75’-0” >50 OCCUPANTS
ASSEMBLY, LESS CONCENTRATED 12.2.5.2- 20’-0” <50 OCCUPANTS / 75’-0” >50 OCCUPANTS
BUSINESS 38.2.5.2.1- SHALL NOT EXCEED 100'-0"
MERCANTILE, STREET FLOOR 36.2.5.2- SHALL NOT EXCEED 100'-0"
STORAGE USE, OTHER 42.2.5- SHALL NOT EXCEED 100'-0"
ASSEMBLY, CONCENTRATED 12.2.5.3- SHALL NOT EXCEED 20'-0"
ASSEMBLY, KITCHEN 12.2.5.3- SHALL NOT EXCEED 20'-0"
ASSEMBLY, LESS CONCENTRATED 12.2.5.3- SHALL NOT EXCEED 20'-0"
BUSINESS 38.2.5.3.1- SHALL NOT EXCEED 50'-0"
MERCANTILE, STREET FLOOR 36.2.5.3.1- SHALL NOT EXCEED 50'-0"
STORAGE USE, OTHER 42.2.5- SHALL NOT EXCEED 100'-0"
A
B C D E F G
S T
A
IR
S T
A
IR
S T
A
IR
S T
A
IR
S T
A
IR
BLDG 61
BLDG 29BLDG 62
B
B62
B
B
B
B
B
B
B
B29
B3
BLDG 26
H J K L M
TRAVEL DISTANCE = 236' - 10"
T R
A V
E L
D
IS
T A
N C
E
FEC
FEC
1539 SF @ 15 NET = 103
S T
A
IR
FEC
SHARED
WAITING
100A
NEURO
NEURO
GI / RHEUM
GI / RHEUM
GI EXAM
GI EXAM
LOUNGE /
LOCKER
CLEAN
UTILITY
PAT TLT
NEURO
TEAM SPACE 1
GI EXAM
GI / RHEUM
CORRIDOR
CORRIDOR
PROC TLT
123B
MED EQUIP
STORAGE
PROCEDURE
ROOM
123A
MED
PFT
126A
PFT TLT
126B
SOILED
UTILITY
HAC
RENAL
HOME
OXYGEN
RENAL
RENAL
134 136
PULM / SLEEP PULM / SLEEP
PULM / SLEEP
CPAP CONS.
FLEX EXAM
CPAP STG
147PAT. TLT
VESTIBULE
122B
CPAP CONS.
141A
CPAP CONS.
143A
PULM / SLEEP
RENAL
CLEAN
UTILITY
RENAL
TEAM SPACE
122A
STF TLT
STG
141B STG
143B
CORR.
O2, FULL
129B
O2, EMPTY
129A
RECEPTION
100B
IT ROOM
ELEC
STF TLT
FEC
FEC
FEC
FEC
FEC
12'-0" 19'-0" 19'-0" 19'-0" 19'-0" 19'-0" 7'-0" 12'-0" 13'-10 1/2" 5'-1 1/2" 12'-2"
'-4
8'
-4
'-6
7'
-9
7' -1
1/
2" 7'
-9
/2
7' -9
/2
7'
-1
1/ 2"
7' -9
'-4
8' -6
'-4
A
157'-2"
3'
-2
KEY PLAN
BLDG 26
BLDG 3 BLDG 1
BLDG 2BLDG 19
BLDG 61
BLDG 62
BLDG 29
N
PHASE FOUR
SERVICE YARD
EXISTING BUILDING HEIGHT: BUILDING 26
3 STORIES, APPROX. 35'-0" HEIGHT
BUILDING AREA:
AREA LIMITATION: 69,000 SQUARE FEET (2021 IBC TABLE 506.2)
GROUND FLOOR 22,720 GROSS SQUARE FEET
FIRST FLOOR 22,720 GROSS SQUARE FEET
SECOND FLOOR 17,590 GROSS SQUARE FEET
TOTAL 63,030 GROSS SQUARE FEET
NFPA 101-2021 CHAPTER 7- TABLE 7.3.1.2 OCCUPANT LOADS
NFPA 101-2021 CHAPTER 7- 7.2.1.2.3.2) MINIMIM DOOR…