This document is an addendum to a solicitation for the construction of an infill of Building 26 and renovation of specialty care clinics at the Robert J. Dole VA Medical Center. Key details include:

The addendum addresses several pre-bid questions, re-numbering of rooms and doors, and includes new specifications for high security fences and gates as well as cantilevered sliding vehicle gate systems. It provides updates to various sections of the project manual and construction drawings. The addendum is 66 pages and includes revisions to specifications for door hardware, fire suppression, and mechanical systems. The solicitation number is 36C77624R0027 and the project name is "Y1DZ--VHA MINOR CONSTRUCTION Project 589-704 Infill of Building 26 for Dental Clinics, New Police Office, and Renovate for Specialty Care Services".

View the file

Other files

File Type Posted
36C77624R0027 0005.docx DOCX document
SA031 - Pad Details.pdf PDF
S05-589-704 RFIs - Technical Questions_RESPONSES.docx DOCX document
36C77624R0027 0004.docx DOCX document
36C77624R0027 0003.docx DOCX document
36C77624R0027 0002.docx DOCX document
589-704 PreBid Sign In Sheet.pdf PDF
03 Volume 589-704 Spec v2.pdf PDF
36C77624R0027 0001.docx DOCX document
Final Geotech Report B26.pdf PDF
Attachment 15 Bldg 26 - Ground Floor - Asbestos Survey.pdf PDF
Attachment 12 02 Volume 589-704 Spec.pdf PDF
Attachment 19 - Site Visit Instructions.docx DOCX document
Attachment 9 08_100_ BID SET Electrical Drawings.pdf PDF
Attachment 3 02_100_ BID SET Civil Drawings.pdf PDF
Attachment 4 03_100_ BID SET Structural Drawings.pdf PDF
Attachment 11 01 Volume 589-704 Spec_R1.pdf PDF
Attachment 7 06_100_ BID SET Plumbing Drawings.pdf PDF
Attachment 2 01_100_ BID SET Environmental Drawings.pdf PDF
Attachment 14 Bldg 26 - First Floor - Asbestos Survey.pdf PDF
Attachment 13 03 Volume 589-704 Spec.pdf PDF
Attachment 16 Kansas Tax Language - 1.26.2023 - FINAL.docx DOCX document
Attachment 8 07_100_ BID SET Mechanical Drawings.pdf PDF
Attachment 6 05_100_ BID SET Fire Protection Drawings.pdf PDF
Attachment 17 WD Sedgwick 01192024.pdf PDF
Attachment 10 09_100_ BID SET Technology Drawings.pdf PDF
36C77624R0027_1.docx DOCX document
Attachment 18 - VA Handbook 6500.6 Appendix C.pdf PDF
Attachment 5 04_100_ BID SET Architectural Drawings.pdf PDF
Attachment 1 - 00_100_ BID SET General Drawings.pdf PDF
Show all 30

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ADDENDUM

PROJECT NUMBER 589-704 (2016)

PROJECT NAME Construct Infill of Building 26 and Renovate Specialty Care Clinics

ADDENDUM NUMBER 01

DATE March 18, 2024

SUBJECT Pre-Bid RFI Responses

A | 312 SW 25th St. Oklahoma City, OK 73109 P | 405.842.6100 E | howdy@spur-design.com W | spur-design.com

THE FOLLOWING MODIFICATIONS, ADDITIONS, AND DELETIONS ARE HEREBY MADE A PART OF THE CONTRACT DOCUMENTS.

SEAL:

GENERAL: This addendum addresses several pre-bid questions, re-numbering of rooms and doors. This addendum also includes new specifications for gate systems.

PROJECT MANUAL:

ARCHITECTURAL

A. 00 01 00 TABLE OF CONTENTS

1. Revised to include new sections.

B. 08 71 00 DOOR HARDWARE

1. 3.5 HARDWARE SETS

a. Door numbers corrected.

C. 32 31 40 HIGH SECURITY FENCES AND GATES

1. Include this specification in its entirety.

D. 34 75 13 CANTILEVERED SLIDING VEHICLE GATE SYSTEM

1. Include this specification in its entirety.

CONSTRUCTION DRAWINGS:

ARCHITECTURAL

A. AE401 – PHASE ONE-ENLARGED PLANS & INTERIOR ELEVATIONS

1. Plan and elevation title room numbers corrected.

B. AE402 – PHASE ONE-ENLARGED PLANS & INTERIOR ELEVATIONS

1. Plan and elevation title room numbers corrected.

C. AE403 – PHASE ONE-ENLARGED PLANS & INTERIOR ELEVATIONS

1. Plan and elevation title room numbers corrected.

A | 312 SW 25th St. Oklahoma City, OK 73109 P | 405.842.6100 E | howdy@spur-design.com W | spur-design.com

D. AE404 – PHASE ONE-ENLARGED PLANS & INTERIOR ELEVATIONS

1. Plan and elevation title room numbers corrected.

E. AE409 – PHASE TWO-ENLARGED PLANS & INTERIOR ELEVATIONS

1. Plan and elevation title room numbers corrected.

F. AE410 – PHASE TWO-ENLARGED PLANS & INTERIOR ELEVATIONS

1. Plan and elevation title room numbers corrected.

G. AE411 – PHASE TWO-ENLARGED PLANS & INTERIOR ELEVATIONS

1. Plan and elevation title room numbers corrected.

H. AE412 – PHASE TWO-ENLARGED PLANS & INTERIOR ELEVATIONS

1. Plan and elevation title room numbers corrected.

I. AE413 – PHASE TWO-ENLARGED PLANS & INTERIOR ELEVATIONS

1. Plan and elevation title room numbers corrected.

J. AE415 – PHASE TWO-ENLARGED PLANS & INTERIOR ELEVATIONS

2. Plan and elevation title room names corrected.

FIRE SUPPRESSION

A. XXXXXX

1. Xxxxxx

MECHANICAL

A. XXXXXXXX

1. Xxxx

TOTAL: 66 Pages 8 ½ x 11

ADD THE NUMBERS Pages [8 ½ x 11] [11 x 17] [30 x 42]

END OF ADDENDUM NO. 01

Construct Infill of Building 26 and Renovate Specialty Care Clinics

VA 589-704

Robert J. Dole VAMC

Addendum 01

04-01-22

08 71 00-1

DOOR HARDWARE

SECTION 08 71 00

DOOR HARDWARE

PART 1 - GENERAL

1.1 DESCRIPTION

Door hardware and related items necessary for complete installation and operation of doors.

1.2 RELATED WORK

Caulking: Section 07 92 00 JOINT SEALANTS.

Application of Hardware: Section 08 13 00, INTERIOR WOOD DOORS; Section

08 11 13, HOLLOW METAL DOORS AND FRAMES; Section 08 34 53, SECURITY DOORS AND

FRAMES; Section 08 71 13, AUTOMATIC DOOR OPERATORS; Section 13 49 00, RADIATION PROTECTION.

Finishes: Section 09 06 00, SCHEDULE FOR FINISHES.

Painting: Section 09 91 00, PAINTING.

Card Readers: Section 28 13 11, PHYSICAL ACCESS CONTROL SYSTEMS.

Electrical: Division 26, ELECTRICAL.

Fire Detection: Section 28 31 00, FIRE DETECTION AND ALARM.

1.3 GENERAL

All hardware shall comply with ABAAS, (Architectural Barriers Act

Accessibility Standard) unless specified otherwise.

Provide rated door hardware assemblies where required by most current version of the International Building Code (IBC).

Hardware for Labeled Fire Doors and Exit Doors: Conform to requirements of NFPA 80 for labeled fire doors and to NFPA 101 for exit doors, as well as to other requirements specified. Provide hardware listed by UL, except where heavier materials, large size, or better grades are specified herein under paragraph HARDWARE SETS. In lieu of UL labeling and listing, test reports from a nationally recognized testing agency may be submitted showing that hardware has been tested in accordance with UL test methods and that it conforms to

NFPA requirements.

Hardware for application on metal and wood doors and frames shall be made to standard templates. Furnish templates to the fabricator of these items in sufficient time so as not to delay the construction.

The following items shall be of the same manufacturer, except as otherwise specified:

1. Mortise locksets.

Robert J. Dole VAMC

Addendum 01

04-01-22

08 71 00-2

DOOR HARDWARE

2. Hinges for hollow metal and wood doors.

3. Surface applied overhead door closers.

4. Exit devices.

1.4 WARRANTY

Automatic door operators shall be subject to the terms of FAR Clause

52.246-21, except that the Warranty period shall be two years in lieu of one year for all items except as noted below:

1. Locks, latchsets, and panic hardware: 5 years.

2. Door closers and continuous hinges: 10 years.

1.5 MAINTENANCE MANUALS

In accordance with Section 01 00 00, GENERAL REQUIREMENTS Article titled

"INSTRUCTIONS", furnish maintenance manuals and instructions on all door hardware. Provide installation instructions with the submittal documentation.

1.6 SUBMITTALS

Submittals shall be in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES. Submit 6 copies of the schedule per Section 01 33

23. Submit 2 final copies of the final approved schedules to VAMC Locksmith as record copies (VISN Locksmith if the VAMC does not have a locksmith).

Hardware Schedule: AHC certified hardware consultant to prepare and submit hardware schedule in the following form:

Hardware

Item

Quantity Size Reference

Publication

Type No.

Finish Mfr.

Name and

Catalog

No.

Key

Control

Symbols

UL Mark

(if fire rated and listed)

ANSI/BHMA

Finish

Designation

Samples and Manufacturers' Literature:

1. Samples: All hardware items (proposed for the project) that have not been previously approved by Builders Hardware Manufacturers

Association shall be submitted for approval. Tag and mark all items with manufacturer's name, catalog number and project number.

2. Samples are not required for hardware listed in the specifications by manufacturer's catalog number, if the contractor proposes to use the manufacturer's product specified.

Robert J. Dole VAMC

Addendum 01

04-01-22

08 71 00-3

DOOR HARDWARE

Certificate of Compliance and Test Reports: Submit certificates that hardware conforms to the requirements specified herein. Certificates shall be accompanied by copies of reports as referenced. The testing shall have been conducted either in the manufacturer's plant and certified by an independent testing laboratory or conducted in an independent laboratory, within four years of submittal of reports for approval.

1.7 DELIVERY AND MARKING

Deliver items of hardware to job site in their original containers, complete with necessary appurtenances including screws, keys, and instructions. Tag one of each different item of hardware and deliver to COR for reference purposes. Tag shall identify items by Project Specification number and manufacturer's catalog number. These items shall remain on file in

COR's office until all other similar items have been installed in project, at which time the COR will deliver items on file to Contractor for installation in predetermined locations on the project.

1.8 PREINSTALLATION MEETING

Convene a preinstallation meeting not less than 30 days before start of installation of door hardware. Require attendance of parties directly affecting work of this section, including Contractor and Installer, Architect, Project Engineer and VA Locksmith, Hardware Consultant, and Hardware

Manufacturer’s Representative. Review the following:

1. Inspection of door hardware.

2. Job and surface readiness.

3. Coordination with other work.

4. Protection of hardware surfaces.

5. Substrate surface protection.

6. Installation.

7. Adjusting.

8. Repair.

9. Field quality control.

10. Cleaning.

1.9 INSTRUCTIONS

Hardware Set Symbols on Drawings: Except for protective plates, door stops, mutes, thresholds and the like specified herein, hardware requirements for each door are indicated on drawings by symbols. Symbols for hardware sets consist of letters (e.g., "HW") followed by a number. Each number designates a set of hardware items applicable to a door type.

Robert J. Dole VAMC

Addendum 01

04-01-22

08 71 00-4

DOOR HARDWARE

Keying: All cylinders shall be keyed into existing Master Key System. Provide removable core cylinders that are removable only with a special key or tool without disassembly of knob or lockset. Cylinders shall be 7 pin type. Keying information shall be furnished at a later date by the COR.

1.10 APPLICABLE PUBLICATIONS

The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only. In text, hardware items are referred to by series, types, etc., listed in such specifications and standards, except as otherwise specified.

ASTM International(ASTM):

F883-13.................Padlocks

E2180-18................Standard Test Method for Determining the

Activity of Incorporated Antimicrobial Agent(s)

In Polymeric or Hydrophobic Materials

American National Standards Institute/Builders Hardware Manufacturers

Association (ANSI/BHMA):

A156.1-06...............Butts and Hinges

A156.2-03...............Bored and Pre-assembled Locks and Latches

A156.3-08...............Exit Devices, Coordinators, and Auto Flush Bolts

A156.4-08...............Door Controls (Closers)

A156.5-14...............Cylinders and Input Devices for Locks.

A156.6-05...............Architectural Door Trim

A156.8-05...............Door Controls-Overhead Stops and Holders

A156.11-14..............Cabinet Locks

A156.12-05 .............Interconnected Locks and Latches

A156.13-05..............Mortise Locks and Latches Series 1000

A156.14-07 .............Sliding and Folding Door Hardware

A156.15-06..............Release Devices-Closer Holder, Electromagnetic and Electromechanical

A156.16-08..............Auxiliary Hardware

A156.17-04 .............Self-Closing Hinges and Pivots

A156.18-06..............Materials and Finishes

A156.20-06 .............Strap and Tee Hinges, and Hasps

A156.21-09..............Thresholds

A156.22-05..............Door Gasketing and Edge Seal Systems

A156.23-04..............Electromagnetic Locks

Robert J. Dole VAMC

Addendum 01

04-01-22

08 71 00-5

DOOR HARDWARE

A156.24-03..............Delayed Egress Locking Systems

A156.25-07 .............Electrified Locking Devices

A156.26-06..............Continuous Hinges

A156.28-07 .............Master Keying Systems

A156.29-07 .............Exit Locks and Alarms

A156.30-03 .............High Security Cylinders

A156.31-07 .............Electric Strikes and Frame Mounted Actuators

A156.36-10..............Auxiliary Locks

A250.8-03...............Standard Steel Doors and Frames

National Fire Protection Association (NFPA):

80-22...................Fire Doors and Other Opening Protectives

101-21..................Life Safety Code

Underwriters Laboratories, Inc. (UL):

Building Materials Directory (2008)

PART 2 - PRODUCTS

2.1 BUTT HINGES

ANSI A156.1. Provide only three-knuckle hinges, except five-knuckle where the required hinge type is not available in a three-knuckle version

(e.g., some types of swing-clear hinges). The following types of butt hinges shall be used for the types of doors listed, except where otherwise specified:

1. Exterior Doors: Type A2112/A5112 for doors 900 mm (3 feet) wide or less and Type A2111/A5111 for doors over 900 mm (3 feet) wide. Hinges for exterior outswing doors shall have non-removable pins. Hinges for exterior fire-rated doors shall be of stainless steel material.

2. Interior Doors: Type A8112/A5112 for doors 900 mm (3 feet) wide or less and Type A8111/A5111 for doors over 900 mm (3 feet) wide.

Hinges for doors exposed to high humidity areas (shower rooms, toilet rooms, kitchens, janitor rooms, etc. shall be of stainless steel material.

Provide quantity and size of hinges per door leaf as follows:

1. Doors up to 1210 mm (4 feet) high: 2 hinges.

2. Doors 1210 mm (4 feet) to 2260 mm (7 feet 5 inches) high: 3 hinges minimum.

3. Doors greater than 2260 mm (7 feet 5 inches) high: 4 hinges.

4. Doors up to 900 mm (3 feet) wide, standard weight: 114 mm x 114 mm

(4-1/2 inches x 4-1/2 inches) hinges.

Robert J. Dole VAMC

Addendum 01

04-01-22

08 71 00-6

DOOR HARDWARE

5. Doors over 900 mm (3 feet) to 1065 mm (3 feet 6 inches) wide, standard weight: 127 mm x 114 mm (5 inches x 4-1/2 inches).

6. Doors over 1065 mm (3 feet 6 inches) to 1210 mm (4 feet), heavy weight: 127 mm x 114 mm (5 inches x 4-1/2 inches).

7. Provide heavy-weight hinges where specified.

8. At doors weighing 330 kg (150 pounds) or more, furnish 127 mm (5 inch) high hinges.

See Articles "MISCELLANEOUS HARDWARE" and "HARDWARE SETS" for pivots and hinges other than butts specified above and continuous hinges specified below.

2.2 CONTINUOUS HINGES

ANSI/BHMA A156.26, Grade 1-600.

1. Listed under Category N in BHMA's "Certified Product Directory."

General: Minimum 0.120-inch- (3.0-mm-) thick, hinge leaves with minimum overall width of 4 inches (102 mm); fabricated to full height of door and frame and to template screw locations; with components finished after milling and drilling are complete

Continuous, Barrel-Type Hinges: Hinge with knuckles formed around a

Teflon-coated 6.35mm (0.25-inch) minimum diameter pin that extends entire length of hinge.

1. Base Metal for Exterior Hinges: Stainless steel.

2. Base Metal for Interior Hinges: Stainless steel.

3. Base Metal for Hinges for Fire-Rated Assemblies: Stainless steel.

4. Provide with non-removable pin (hospital tip option) at lockable outswing doors.

5. Where required to clear adjacent casing, trim, and wall conditions and allow full door swing, provide wide throw hinges of minimum width required.

6. Provide with manufacturer’s cut-outs for separate mortised power transfers and/or mortised automatic door bottoms where they occur.

7. Where thru-wire power transfers are integral to the hinge, provide hinge with easily removable portion to allow easy access to wiring connections.

8. Where models are specified that provide an integral wrap-around edge guard for the hinge edge of the door, provide manufacturer’s adjustable threaded stud and machine screw mechanism to allow the door to be adjusted within the wrap-around edge guard.

Robert J. Dole VAMC

Addendum 01

04-01-22

08 71 00-7

DOOR HARDWARE

2.3 DOOR CLOSING DEVICES

Closing devices shall be products of one manufacturer for each type specified.

2.4 OVERHEAD CLOSERS

Conform to ANSI A156.4, Grade 1.

Closers shall conform to the following:

1. The closer shall have minimum 50 percent adjustable closing force over minimum value for that closer and have adjustable hydraulic back check effective between 60 degrees and 85 degrees of door opening.

2. Where specified, closer shall have hold-open feature.

3. Size Requirements: Provide multi-size closers, sizes 1 through 6, except where multi-size closer is not available for the required application.

4. Material of closer body shall be forged or cast.

5. Arm and brackets for closers shall be steel, malleable iron or high strength ductile cast iron.

6. Where closers are exposed to the exterior or are mounted in rooms that experience high humidity, provide closer body and arm assembly of stainless steel material.

7. Closers shall have full size metal cover; plastic covers will not be accepted.

8. Closers shall have adjustable hydraulic back-check, separate valves for closing and latching speed, adjustable back-check positioning valve, and adjustable delayed action valve.

9. Provide closers with any accessories required for the mounting application, including (but not limited to) drop plates, special soffit plates, spacers for heavy-duty parallel arm fifth screws, bull-nose or other regular arm brackets, longer or shorter arm assemblies, and special factory templating. Provide special arms, drop plates, and templating as needed to allow mounting at doors with overhead stops and/or holders.

10. Closer arms or backcheck valve shall not be used to stop the door from overswing, except in applications where a separate wall, floor, or overhead stop cannot be used.

11. Provide parallel arm closers with heavy duty rigid arm.

Robert J. Dole VAMC

Addendum 01

04-01-22

08 71 00-8

DOOR HARDWARE

12. Where closers are to be installed on the push side of the door, provide parallel arm type except where conditions require use of top jamb arm.

13. Provide all surface closers with the same body attachment screw pattern for ease of replacement and maintenance.

14. All closers shall have a 1 ½” (38mm) minimum piston diameter.

2.5 DOOR STOPS

Conform to ANSI A156.16.

Provide door stops wherever an opened door or any item of hardware thereon would strike a wall, column, equipment or other parts of building construction. For concrete, masonry or quarry tile construction, use expansion shields for mounting door stops.

Where cylindrical locks with turn pieces or pushbuttons occur, equip wall bumpers Type L02251 (rubber pads having concave face) to receive turn piece or button.

Provide floor stops (Type L02141 or L02161) in office areas; Type L02121 x 3 screws into floor elsewhere. Wall bumpers, where used, must be installed to impact the trim or the door within the leading half of its width. Floor stops, where used, must be installed within 4-inches of the wall face and impact the door within the leading half of its width.

Where drywall partitions occur, use floor stops, Type L02141 or L02161 in office areas, Type L02121 elsewhere.

Provide stop Type L02011, as applicable for exterior doors. At outswing doors where stop can be installed in concrete, provide stop mated to concrete anchor set in 76mm (3-inch) core-drilled hole and filled with quick-setting cement.

Omit stops where floor mounted door holders are required and where automatic operated doors occur.

Provide appropriate roller bumper for each set of doors (except where closet doors occur) where two doors would interfere with each other in swinging.

Provide appropriate door mounted stop on doors in individual toilets where floor or wall mounted stops cannot be used.

Provide overhead surface applied stop Type C02541, ANSI A156.8 on patient toilet doors in bedrooms where toilet door could come in contact with the bedroom door.

Robert J. Dole VAMC

Addendum 01

04-01-22

08 71 00-9

DOOR HARDWARE

Provide door stops on doors where combination closer magnetic holders are specified, except where wall stops cannot be used or where floor stops cannot be installed within 4-inches of the wall.

Where the specified wall or floor stop cannot be used, provide concealed overhead stops (surface-mounted where concealed cannot be used).

2.6 OVERHEAD DOOR STOPS AND HOLDERS

Conform to ANSI Standard A156.8. Overhead holders shall be of sizes recommended by holder manufacturer for each width of door. Set overhead holders for 110 degree opening, unless limited by building construction or equipment. Provide Grade 1 overhead concealed slide type: stop-only at rated doors and security doors, hold-open type with exposed hold-open on/off control at all other doors requiring overhead door stops.

2.7 FLOOR DOOR HOLDERS

Conform to ANSI Standard A156.16. Provide extension strikes for Types

L01301 and L01311 holders where necessary.

2.8 LOCKS AND LATCHES

Conform to ANSI A156.2. Locks and latches for doors 45 mm (1-3/4 inch) thick or over shall have beveled fronts. Lock cylinders shall have not less than seven pins. Cylinders for all locksets shall be removable core type.

Cylinder shall be removable by special key or tool. Construct all cores so that they will be interchangeable into the core housings of all mortise locks, rim locks, cylindrical locks, and any other type lock included in the Great

Grand Master Key System. Disassembly of lever or lockset shall not be required to remove core from lockset. All locksets or latches on double doors with fire label shall have latch bolt with 19 mm (3/4 inch) throw, unless shorter throw allowed by the door manufacturer’s fire label. Provide temporary keying device or construction core to allow opening and closing during construction and prior to the installation of final cores.

In addition to above requirements, locks and latches shall comply with following requirements:

1. Mortise Lock and Latch Sets: Conform to ANSI/BHMA A156.13. Mortise locksets shall be series 1000, minimum Grade

2. All locksets and latchsets, except on designated doors in Psychiatric

(Mental Health) areas, shall have lever handles fabricated from cast stainless steel. Provide sectional (lever x rose) lever design matching facility standard. No substitute lever material shall be accepted. All locks and latchsets shall be furnished with 122.55 mm

Robert J. Dole VAMC

Addendum 01

04-01-22

08 71 00-10

DOOR HARDWARE

(4-7/8-inch) curved lip strike and wrought box. At outswing pairs with overlapping astragals, provide flat lip strip with 21mm (7/8-inch) lip-to-center dimension. Lock function F02 shall be furnished with emergency tools/keys for emergency entrance. All lock cases installed on lead lined doors shall be lead lined before applying final hardware finish. Furnish armored fronts for all mortise locks.

Where mortise locks are installed in high-humidity locations or where exposed to the exterior on both sides of the opening, provide non-ferrous mortise lock case.

3. Cylindrical Lock and Latch Sets: levers shall meet ADA (Americans with Disabilities Act) requirements. Cylindrical locksets shall be series 4000 Grade I. All locks and latchsets shall be furnished with

122.55 mm (4-7/8-inch) curved lip strike and wrought box. At outswing pairs with overlapping astragals, provide flat lip strip with 21mm

(7/8-inch) lip-to-center dimension. Provide lever design to match design selected by Architect or to match existing lever design.

Where two turn pieces are specified for lock F76, turn piece on inside knob shall lock and unlock inside knob, and turn piece on outside knob shall unlock outside knob when inside knob is in the locked position. (This function is intended to allow emergency entry into these rooms without an emergency key or any special tool.)

4. Auxiliary locks shall be as specified under hardware sets and conform to ANSI A156.36.

2.9 ELECTROMAGNETIC LOCKS

ANSI/BHMA A156.23; electrically powered, of strength and configuration indicated; with electromagnet attached to frame and armature plate attached to door. Listed under Category E in BHMA's "Certified Product Directory."

1. Type: Full exterior or full interior, as required by application indicated.

2. Strength Ranking: 1000 pound force (4448 N).

3. Inductive Kickback Peak Voltage: Not more than 0 V.

4. Residual Magnetism: Not more than 4 pound force (18 N) to separate door from magnet.

Delayed-Egress Locks: BHMA A156.24. Listed under Category G in BHMA's

"Certified Product Directory".

Robert J. Dole VAMC

Addendum 01

04-01-22

08 71 00-11

DOOR HARDWARE

1. Means of Egress Doors: Lock releases within 15 seconds after applying a force not more than 15 pound force (67 N) for not more than 3 seconds, as required by NFPA 101.

2. Security Grade: Activated from secure side of door by initiating device.

3. Movement Grade: Activated by door movement as initiating device.

4. The lock housing shall not project more than 4-inches (101mm) from the underside of the frame head stop.

2.10 ELECTRIC STRIKES

ANSI/ BHMA A156.31 Grade 1.

General: Use fail-secure electric strikes at fire-rated doors.

2.11 KEYS

Stamp all keys with change number and key set symbol. Furnish keys in quantities as follows:

Locks/Keys Quantity

Cylinder locks 2 keys each

Cylinder lock change key blanks

100 each different key way

Master-keyed sets 6 keys each

Grand Master sets 6 keys each

Great Grand Master set 5 keys

Control key 2 keys

2.12 ARMOR PLATES, KICK PLATES, MOP PLATES AND DOOR EDGING

Conform to ANSI Standard A156.6.

Provide protective plates as specified below:

1. Kick plates, mop plates and armor plates of metal, Type J100 series.

2. Provide kick plates and mop plates where specified. Kick plates shall be 254 mm (10 inches) or 305 mm (12 inches) high. Mop plates shall be

152 mm (6 inches) high. Both kick and mop plates shall be minimum

1.27 mm (0.050 inches) thick. Provide kick and mop plates beveled on all 4 edges (B4E). On push side of doors where jamb stop extends to floor, make kick plates 38 mm (1-1/2 inches) less than width of door, except pairs of metal doors which shall have plates 25 mm (1 inch) less than width of each door. Extend all other kick and mop plates to within 6 mm (1/4 inch) of each edge of doors. Kick and mop plates

Robert J. Dole VAMC

Addendum 01

04-01-22

08 71 00-12

DOOR HARDWARE

shall butt astragals. For jamb stop requirements, see specification sections pertaining to door frames.

3. Kick plates and/or mop plates are not required on following door sides:

a. Armor plate side of doors;

b. Exterior side of exterior doors;

c. Closet side of closet doors;

4. Armor plates for doors are listed under Article "Hardware Sets".

Armor plates shall be thickness as noted in the hardware set, 875 mm

(35 inches) high and 38 mm (1-1/2 inches) less than width of doors, except on pairs of metal doors. Provide armor plates beveled on all 4 edges (B4E). Plates on pairs of metal doors shall be 25 mm (1 inch) less than width of each door. Where top of intermediate rail of door is less than 875 mm (35 inches) from door bottom, extend armor plates to within 13 mm (1/2 inch) of top of intermediate rail. On doors equipped with panic devices, extend armor plates to within 13 mm (1/2 inch) of panic bolt push bar.

5. Where louver or grille occurs in lower portion of doors, substitute stretcher plate and kick plate in place of armor plate. Size of stretcher plate and kick plate shall be 254 mm (10 inches) high.

6. Provide stainless steel edge guards where so specified at wood doors.

Provide mortised type instead of surface type except where door construction and/or ratings will not allow. Provide edge guards of bevel and thickness to match wood door. Provide edge guards with factory cut-outs for door hardware that must be installed through or extend through the edge guard. Provide full-height edge guards except where door rating does not allow; in such cases, provide edge guards to height of bottom of typical lockset armor front. Forward edge guards to wood door manufacturer for factory installation on doors.

2.13 EXIT DEVICES

Conform to ANSI Standard A156.3. Exit devices shall be Grade 1; type and function are specified in hardware sets. Provide flush with finished floor strikes for vertical rod exit devices in interior of building. Trim shall have cast satin stainless steel lever handles of design similar to locksets, unless otherwise specified. Provide key cylinders for keyed operating trim and, where specified, cylinder dogging.

Robert J. Dole VAMC

Addendum 01

04-01-22

08 71 00-13

DOOR HARDWARE

Surface vertical rod panics shall only be provided less bottom rod;

provide fire pins as required by exit device and door fire labels. Do not provide surface vertical rod panics at exterior doors.

Concealed vertical rod panics shall be provided less bottom rod at interior doors, unless lockable or otherwise specified; provide fire pins as required by exit device and door fire labels. Where concealed vertical rod panics are specified at exterior doors, provide with both top and bottom rods.

Where removable mullions are specified at pairs with rim panic devices, provide mullion with key-removable feature.

At non-rated openings with panic hardware, provide panic hardware with key cylinder dogging feature.

Exit devices for fire doors shall comply with Underwriters Laboratories, Inc., requirements for Fire Exit Hardware. Submit proof of compliance.

2.14 FLUSH BOLTS (LEVER EXTENSION)

Conform to ANSI A156.16. Flush bolts shall be Type L24081 unless otherwise specified. Furnish proper dustproof strikes conforming to ANSI

A156.16, for flush bolts required on lower part of doors.

Lever extension manual flush bolts shall only be used at non-fire-rated pairs for rooms only accessed by maintenance personnel.

Face plates for cylindrical strikes shall be rectangular and not less than 25 mm by 63 mm (1 inch by 2-1/2 inches).

Friction-fit cylindrical dustproof strikes with circular face plate may be used only where metal thresholds occur.

Provide extension rods for top bolt where door height exceeds 2184 mm (7 feet 2 inches).

2.15 DOOR PULLS WITH PLATES

Conform to ANSI A156.6. Pull Type J401, 152 mm CTC (6 inches CTC) length by 19 mm (3/4 inches) diameter minimum with plate Type J302, 90 mm by 381 mm

(3-1/2 inches by 15 inches), unless otherwise specified. Provide pull with projection of 57.2 mm (2 1/4 inches) minimum and a clearance of 38.1 mm (1 1/2 inches) minimum. Cut plates of door pull plate for cylinders, or turn pieces where required.

2.16 PUSH PLATES

Conform to ANSI A156.6. Metal, Type J302, 203 mm (8 inches) wide by

406.4 mm (16 inches) high. Provide metal Type J302 plates 102 mm (4 inches) wide by 406.4 mm (16 inches) high where push plates are specified for doors

Robert J. Dole VAMC

Addendum 01

04-01-22

08 71 00-14

DOOR HARDWARE

with stiles less than 203 mm (8 inches) wide. Cut plates for cylinders, and turn pieces where required.

2.17 COMBINATION PUSH AND PULL PLATES

Conform to ANSI 156.6. Type J303, stainless steel 3 mm (1/8 inch) thick, 80 mm (3-1/3 inches) wide by 800 mm (16 inches) high), top and bottom edges shall be rounded. Secure plates to wood doors with 38 mm (1-1/2 inch) long No.

12 wood screws. Cut plates for turn pieces, and cylinders where required. Pull shall be mounted down.

2.18 COORDINATORS

Conform to ANSI A156.16. Coordinators, when specified for fire doors, shall comply with Underwriters Laboratories, Inc., requirements for fire door hardware. Coordinator may be omitted on exterior pairs of doors where either door will close independently regardless of the position of the other door.

Coordinator may be omitted on interior pairs of non-labeled open where open back strike is used. Open back strike shall not be used on labeled doors.

Paint coordinators to match door frames, unless coordinators are plated.

Provide bar type coordinators, except where gravity coordinators are required at acoustic pairs. For bar type coordinators, provide filler bars for full width and, as required, brackets for push-side surface mounted closers, overhead stops, and vertical rod panic strikes.

2.19 THRESHOLDS

Conform to ANSI A156.21, mill finish extruded aluminum, except as otherwise specified. In existing construction, thresholds shall be installed in a bed of sealant with ¼-20 stainless steel machine screws and expansion shields. In new construction, embed aluminum anchors coated with epoxy in concrete to secure thresholds. Furnish thresholds for the full width of the openings.

For thresholds at elevators entrances see other sections of specifications.

At exterior doors and any interior doors exposed to moisture, provide threshold with non-slip abrasive finish.

Provide with miter returns where threshold extends more than 12 mm (0.5 inch) beyond face of frame.

2.20 WEATHERSTRIPS (FOR EXTERIOR DOORS)

Conform to ANSI A156.22. Air leakage shall not to exceed 0.50 CFM per foot of crack length (0.000774m3/s/m).

Robert J. Dole VAMC

Addendum 01

04-01-22

08 71 00-15

DOOR HARDWARE

2.21 MISCELLANEOUS HARDWARE

Access Doors (including Sheet Metal, Screen and Woven Wire Mesh Types):

Except for fire-rated doors and doors to Temperature Control Cabinets, equip each single or double metal access door with Lock Type E07213, conforming to

ANSI A156.11. Key locks as directed. Ship lock prepaid to the door manufacturer. Hinges shall be provided by door manufacturer.

Cylinders for Various Partitions and Doors: Key cylinders same as entrance doors of area in which partitions and door occur, except as otherwise specified. Provide cylinders to operate locking devices where specified for following partitions and doors:

1. Fire-rated access doors-Engineer's key set.

Mutes: Conform to ANSI A156.16. Provide door mutes or door silencers

Type L03011 or L03021, depending on frame material, of white or light gray color, on each steel or wood door frame, except at fire-rated frames, lead-lined frames and frames for sound-resistant, lightproof and electromagnetically shielded doors. Furnish 3 mutes for single doors and 2 mutes for each pair of doors, except double-acting doors. Provide 4 mutes or silencers for frames for each Dutch type door. Provide 2 mutes for each edge of sliding door which would contact door frame.

2.22 FINISHES

Exposed surfaces of hardware shall have ANSI A156.18, finishes as specified below. Finishes on all hinges, pivots, closers, thresholds, etc., shall be as specified below under "Miscellaneous Finishes." For field painting

(final coat) of ferrous hardware, see Section 09 91 00, PAINTING.

626 or 630: All surfaces on exterior and interior of buildings, except where other finishes are specified.

Miscellaneous Finishes:

1. Hinges --exterior doors: 626 or 630.

2. Hinges --interior doors: 652 or 630.

3. Pivots: Match door trim.

4. Door Closers: Factory applied paint finish. Dull or Satin Aluminum color.

5. Thresholds: Mill finish aluminum.

6. Cover plates for floor hinges and pivots: 630.

7. Other primed steel hardware: 600.

Robert J. Dole VAMC

Addendum 01

04-01-22

08 71 00-16

DOOR HARDWARE

Hardware Finishes for Existing Buildings: U.S. Standard finishes shall match finishes of hardware in (similar) existing spaces except where otherwise specified.

Anti-microbial Coating: All hand-operated hardware (levers, pulls, push bars, push plates, paddles, and panic bars) shall be provided with an anti-microbial/anti-fungal coating that has passed ASTM E2180 tests. Coating to consist of ionic silver (Ag+). Silver ions surround bacterial cells, inhibiting growth of bacteria, mold, and mildew by blockading food and respiration supplies.

2.23 BASE METALS

Apply specified U.S. Standard finishes on different base metals as following:

Finish Base Metal

652 Steel

626 Brass or bronze

630 Stainless steel

PART 3 - EXECUTION

3.1 HARDWARE HEIGHTS

For existing buildings locate hardware on doors at heights to match existing hardware. The Contractor shall visit the site, verify location of existing hardware and submit locations to VA COR for approval.

Hardware Heights from Finished Floor:

1. Exit devices centerline of strike (where applicable) 1024 mm (40-5/16 inches).

2. Locksets and latch sets centerline of strike 1024 mm (40-5/16 inches).

3. Deadlocks centerline of strike 1219 mm (48 inches).

4. Hospital arm pull 1168 mm (46 inches) to centerline of bottom supporting bracket.

5. Centerline of door pulls to be 1016 mm (40 inches).

6. Push plates and push-pull shall be 1270 mm (50 inches) to top of plate.

7. Push-pull latch to be 1024 mm (40-5/16 inches) to centerline of strike.

8. Locate other hardware at standard commercial heights. Locate push and pull plates to prevent conflict with other hardware.

Robert J. Dole VAMC

Addendum 01

04-01-22

08 71 00-17

DOOR HARDWARE

3.2 INSTALLATION

Closer devices, including those with hold-open features, shall be equipped and mounted to provide maximum door opening permitted by building construction or equipment. Closers shall be mounted on side of door inside rooms, inside stairs, and away from corridors. At exterior doors, closers shall be mounted on interior side. Where closers are mounted on doors they shall be mounted with hex nuts and bolts; foot shall be fastened to frame with machine screws.

Hinge Size Requirements:

Door Thickness Door Width Hinge Height

45 mm (1-3/4 inch) 900 mm (3 feet) and less 113 mm (4-1/2 inches)

45 mm (1-3/4 inch) Over 900 mm (3 feet) but not more than 1200 mm (4 feet)

125 mm (5 inches)

35 mm (1-3/8 inch)

(hollow core wood doors)

Not over 1200 mm (4 feet) 113 mm (4-1/2 inches)

Hinge leaves shall be sufficiently wide to allow doors to swing clear of door frame trim and surrounding conditions.

Where new hinges are specified for new doors in existing frames or existing doors in new frames, sizes of new hinges shall match sizes of existing hinges; or, contractor may reuse existing hinges provided hinges are restored to satisfactory operating condition as approved by COR. Existing hinges shall not be reused on door openings having new doors and new frames.

Coordinate preparation for hinge cut-outs and screw-hole locations on doors and frames.

Hinges Required Per Door:

Door Description Number butts

Doors 1500 mm (5 ft) or less in height 2 butts

Doors over 1500 mm (5 ft) high and not over 2280 mm

(7 ft 6 in) high

3 butts

Doors over 2280 mm (7 feet 6 inches) high 4 butts

Dutch type doors 4 butts

Doors with spring hinges 1370 mm (4 feet 6 inches) high or less

2 butts

Doors with spring hinges over 1370 mm (4 feet 6 inches) 3 butts

Robert J. Dole VAMC

Addendum 01

04-01-22

08 71 00-18

Fastenings: Suitable size and type and shall harmonize with hardware as to material and finish. Provide machine screws and lead expansion shields to secure hardware to concrete, ceramic or quarry floor tile, or solid masonry.

Fiber or rawl plugs and adhesives are not permitted. All fastenings exposed to weather shall be of nonferrous metal.

After locks have been installed; show in presence of COR that keys operate their respective locks in accordance with keying requirements. (All keys, Master Key level and above shall be sent Registered Mail to the Medical

Center Director along with the bitting list. Also a copy of the invoice shall be sent to the COR for his records.) Installation of locks which do not meet specified keying requirements shall be considered sufficient justification for rejection and replacement of all locks installed on project.

3.3 FINAL INSPECTION

Installer to provide letter to VA Resident/Project Engineer that upon completion, installer has visited the Project and has accomplished the following:

1. Re-adjust hardware.

2. Evaluate maintenance procedures and recommend changes or additions, and instruct VA personnel.

3. Identify items that have deteriorated or failed.

4. Submit written report identifying problems.

3.4 DEMONSTRATION

Demonstrate efficacy of mechanical hardware and electrical, and electronic hardware systems, including adjustment and maintenance procedures, to satisfaction of Resident/Project Engineer and VA Locksmith.

3.5 HARDWARE SETS

Following sets of hardware correspond to hardware symbols shown on drawings. Only those hardware sets that are shown on drawings will be required. Disregard hardware sets listed in specifications but not shown on drawings.

Hardware Consultant working on a project will be responsible for providing additional information regarding these hardware sets. The numbers shown in the following sets come from BHMA standards.

Robert J. Dole VAMC

Addendum 01

04-01-22

08 71 00-19

Hardware Group No. 001 For use on Door #(s):

001.1 001.5

EACH TO HAVE:

QTY DESCRIPTION CATALOG NUMBER FINISH MFR

1 EA SFIC CYLINDER MORTISE/RIM AS REQUIRED. 626 FAL

1 EA PERMANENT CORE AS REQ TO MATCH EXISTING KEY

SYSTEM

EA NOTE REMAINDER OF HARDWARE BY

DOOR MFR.

-COORDINATE HARDWARE WITH DOOR MFR.

REFER SECTIONS 32 31 40 AND 34 75 13 FOR ADDITIONAL INFORMATION

Hardware Group No. 003

039A024

EACH TO HAVE:

QTY DESCRIPTION CATALOG NUMBER FINISH MFR

1 EA SFIC CYLINDER MORTISE/RIM AS REQUIRED. 626 FAL

1 EA PERMANENT CORE AS REQ TO MATCH EXISTING KEY

SYSTEM

EA NOTE REMAINDER OF HARDWARE BY

DOOR MFR.

-COORDINATE HARDWARE WITH DOOR MFR.

Hardware Group No. 103

038B026A

EACH TO HAVE:

QTY DESCRIPTION CATALOG NUMBER FINISH MFR

3 EA HINGE 5BB1 4.5 X 4.5 652 IVE

1 EA DORMITORY/EXIT LOCK MA571H DG 626 FAL

1 EA PERMANENT CORE AS REQ TO MATCH EXISTING KEY

SYSTEM

1 EA WALL STOP WS406/407CCV 630 IVE

3 EA SILENCER SR64 GRY IVE

Robert J. Dole VAMC

Addendum 01

04-01-22

08 71 00-20

DOOR HARDWARE

Hardware Group No. 201 For use on Door #(s):

046B 129A OK

EACH TO HAVE:

QTY DESCRIPTION CATALOG NUMBER FINISH MFR

3 EA HINGE 5BB1 4.5 X 4.5 652 IVE

1 EA STOREROOM LOCK MA581H DG 626 FAL

1 EA PERMANENT CORE AS REQ TO MATCH EXISTING KEY

SYSTEM

1 EA SURFACE CLOSER SC81 REG/PA AS REQ X MTG

BRKT, SPCR & PLATE AS REQ

689 FAL

1 EA KICK PLATE 8400 10" X 2" LDW B-CS 630 IVE

1 EA GASKETING 488SBK PSA BK ZER

Hardware Group No. 201C

129B OK

EACH TO HAVE:

QTY DESCRIPTION CATALOG NUMBER FINISH MFR

3 EA HINGE 5BB1 4.5 X 4.5 652 IVE

1 EA STOREROOM LOCK MA581H DG 626 FAL

1 EA PERMANENT CORE AS REQ TO MATCH EXISTING KEY

SYSTEM

1 EA SURFACE CLOSER SC81 SS X MTG BRKT, SPCR &

PLATE AS REQ

689 FAL

1 EA KICK PLATE 8400 10” X 2” LDW B-CS 630 IVE

Robert J. Dole VAMC

Addendum 01

04-01-22

08 71 00-21

DOOR HARDWARE

Hardware Group No. 201W For use on Door #(s):

019041

EACH TO HAVE:

QTY DESCRIPTION CATALOG NUMBER FINISH MFR

3 EA HINGE 5BB1HW 5 X 4.5 652 IVE

1 EA STOREROOM LOCK MA581H DG 626 FAL

1 EA PERMANENT CORE AS REQ TO MATCH EXISTING KEY

SYSTEM

1 EA SURFACE CLOSER SC81 REG/PA AS REQ X MTG

BRKT, SPCR & PLATE AS REQ

689 FAL

1 EA KICK PLATE 8400 10" X 2" LDW B-CS 630 IVE

Hardware Group No. 203

013038 023043

EACH TO HAVE:

QTY DESCRIPTION CATALOG NUMBER FINISH MFR

3 EA HINGE 5BB1 4.5 X 4.5 652 IVE

1 EA STOREROOM LOCK MA581H DG 626 FAL

1 EA PERMANENT CORE AS REQ TO MATCH EXISTING KEY

SYSTEM

Robert J. Dole VAMC

Addendum 01

04-01-22

08 71 00-22

DOOR HARDWARE

Hardware Group No. 204 For use on Door #(s):

201 OK

EACH TO HAVE:

QTY DESCRIPTION CATALOG NUMBER FINISH MFR

2 EA CONT. HINGE 112XY 628 IVE

1 SET AUTO FLUSH BOLT FB31P 630 IVE

1 EA DUST PROOF STRIKE DP2 626 IVE

1 EA STOREROOM LOCK MA581H DG 626 FAL

1 EA PERMANENT CORE AS REQ TO MATCH EXISTING KEY

SYSTEM

2 EA SURFACE CLOSER SC81 SS X MTG BRKT, SPCR &

PLATE AS REQ

689 FAL

2 EA KICK PLATE 8400 10” X 1” LDW B-CS 630 IVE

1 EA RAIN DRIP 142AA AA ZER

1 SET GASKETING 328AA-S H & J AA ZER

2 SET MEETING STILE 328AA-S (2PCS/SET) AA ZER

1 EA ASTRAGAL PROVIDED WITH HM DOOR

2 EA DOOR SWEEP 8198AA AA ZER

1 EA THRESHOLD 65A-223 A ZER

2 EA DOOR CONTACT 679-05 AS REQ WHT SCE

EA NOTE BALANCE OF HARDWARE BY

BUILDING MANUFACTURER

-SET 204 IS FOR PRICING PURPOSES ONLY. DOOR NOT SEEN ON FLOOR PLAN.

Hardware Group No. 301

005B035E

EACH TO HAVE:

QTY DESCRIPTION CATALOG NUMBER FINISH MFR

3 EA HINGE 5BB1 4.5 X 4.5 652 IVE

1 EA PRIVACY LOCK MA311 OCCUPIED/VACANT DGM 626 FAL

1 EA SURFACE CLOSER SC81 REG/PA AS REQ X MTG

BRKT, SPCR & PLATE AS REQ

689 FAL

1 EA KICK PLATE 8400 10” X 2” LDW B-CS 630 IVE

Robert J. Dole VAMC

Addendum 01

04-01-22

08 71 00-23

DOOR HARDWARE

Hardware Group No. 341 For use on Door #(s):

009036 114 125

EACH TO HAVE:

QTY DESCRIPTION CATALOG NUMBER FINISH MFR

3 EA HINGE 5BB1 4.5 X 4.5 652 IVE

1 EA PRIVACY LOCK MA311 OCCUPIED/VACANT DGM 626 FAL

1 EA SURFACE CLOSER SC81 REG/PA AS REQ X MTG

BRKT, SPCR & PLATE AS REQ

689 FAL

1 EA KICK PLATE 8400 10" X 2" LDW B-CS 630 IVE

Hardware Group No. 343SW

015039 105 123B 126B

EACH TO HAVE:

QTY DESCRIPTION CATALOG NUMBER FINISH MFR

3 EA HINGE 5BB1HW 5 X 4.5 652 IVE

1 EA PRIVACY LOCK MA311 OCCUPIED/VACANT DGM 626 FAL

1 EA OH STOP 900S SERIES X SIZE & MOUNTING

AS REQ

630 GLY

1 EA KICK PLATE 8400 10" X 2" LDW B-CS 630 IVE

Hardware Group No. 343W

146OK

EACH TO HAVE:

QTY DESCRIPTION CATALOG NUMBER FINISH MFR

3 EA HINGE 5BB1HW 5 X 4.5 652 IVE

1 EA PRIVACY LOCK MA311 OCCUPIED/VACANT DGM 626 FAL

1 EA KICK PLATE 8400 10” X 2” LDW B-CS 630 IVE

Robert J. Dole VAMC

Addendum 01

04-01-22

08 71 00-24

DOOR HARDWARE

Hardware Group No. 401 For use on Door #(s):

005C035D 116

EACH TO HAVE:

QTY DESCRIPTION CATALOG NUMBER FINISH MFR

3 EA HINGE 5BB1 4.5 X 4.5 652 IVE

1 EA PASSAGE SET MA101 DG 626 FAL

1 EA SURFACE CLOSER SC81 REG/PA AS REQ X MTG

BRKT, SPCR & PLATE AS REQ

689 FAL

1 EA KICK PLATE 8400 10" X 2" LDW B-CS 630 IVE

Hardware Group No. 503

042025B 043025A

EACH TO HAVE:

QTY DESCRIPTION CATALOG NUMBER FINISH MFR

3 EA HINGE 5BB1 4.5 X 4.5 652 IVE

1 EA CLASSROOM LOCK MA561H DG 626 FAL

1 EA PERMANENT CORE AS REQ TO MATCH EXISTING KEY

SYSTEM

Hardware Group No. 603SW

008059 010058 012057 014056 016055 018054

020053 022052 123AOK 126AOK

EACH TO HAVE:

QTY DESCRIPTION CATALOG NUMBER FINISH MFR

3 EA HINGE 5BB1HWSC 5 652 IVE

1 EA PUSH/PULL LATCH HL6 5" A 626 SCH

1 EA OH STOP 900S SERIES X SIZE & MOUNTING

AS REQ

630 GLY

1 EA KICK PLATE 8400 10" X 2" LDW B-CS 630 IVE

Robert J. Dole VAMC

Addendum 01

04-01-22

08 71 00-25

DOOR HARDWARE

Hardware Group No. 603W For use on Door #(s):

102 104 106 107 108 110

111 112 113 130 131 132

133 134 136 137 138 139

140 141A 143A 144 145 OK

EACH TO HAVE:

QTY DESCRIPTION CATALOG NUMBER FINISH MFR

3 EA HINGE 5BB1HWSC 5 652 IVE

1 EA PUSH/PULL LATCH HL6 5” A 626 SCH

1 EA KICK PLATE 8400 10” X 2” LDW B-CS 630 IVE

Hardware Group No. 711A

001OK

EACH TO HAVE:

QTY DESCRIPTION CATALOG NUMBER FINISH MFR

1 EA CONT. HINGE 112XY 628 IVE

1 EA PANIC HARDWARE 25-R-NL-OP-SNB 626 FAL

1 EA PERMANENT CORE AS REQ TO MATCH EXISTING KEY

SYSTEM

1 EA SFIC RIM CYLINDER C953-7CCA 626 FAL

1 EA 90 DEG OFFSET PULL 8190EZHD 10” O IVE

1 EA SURFACE CLOSER SC81 REG/PA AS REQ X MTG

BRKT, SPCR & PLATE AS REQ

689 FAL

1 EA SEALS BY FRAME SUPPLIER

Robert J. Dole VAMC

Addendum 01

04-01-22

08 71 00-26

DOOR HARDWARE

Hardware Group No. 738R For use on Door #(s):

045C1

EACH TO HAVE:

QTY DESCRIPTION CATALOG NUMBER FINISH MFR

2 EA CONT. HINGE 112XY 628 IVE

2 EA FIRE EXIT HARDWARE F-25-C-WDC-L-BE-LBR-DANE-SNB 626 FAL

2 EA SURFACE CLOSER SC81 REG/PA AS REQ X MTG

BRKT, SPCR & PLATE AS REQ

689 FAL

2 EA KICK PLATE 8400 10" X 1" LDW B-CS 630 IVE

2 EA FIRE/LIFE WALL MAG SEM7800 SERIES AS REQ 689 LCN

1 SET MEETING STILE 328AA-S (2PCS/SET) AA ZER

1 EA GASKETING 488SBK PSA BK ZER

-WIRE THE MAGNETIC HOLD OPENS TO THE FIRE ALARM SYSTEM TO RELEASE UPON

ACTIVATION OF THE FIRE ALARM SYSTEM.

Hardware Group No. C711C

148 149 OK

EACH TO HAVE:

QTY DESCRIPTION CATALOG NUMBER FINISH MFR

1 EA CONT. HINGE 112XY EPT 628 IVE

1 EA POWER TRANSFER EPT10 CON 689 VON

1 EA ELEC FIRE EXIT

HARDWARE

RX-MEL-F-25-R-NL-CON-SNB 626 FAL

1 EA PERMANENT CORE AS REQ TO MATCH EXISTING KEY

SYSTEM

1 EA SFIC MORTISE CYLINDER C987-7CCA AS REQ. 626 FAL

1 EA SURFACE CLOSER SC81 SS X MTG BRKT, SPCR &

PLATE AS REQ

689 FAL

1 EA KICK PLATE 8400 10" X 1" LDW B-CS 630 IVE

1 EA GASKETING 488SBK PSA BK ZER

2 EA HARNESS (1 IN DOOR & 1

IN FRAME)

ALLEGION CONNECT TYPE &

LENGTH AS REQ

SCH

2 EA HARNESS (TO POWER

SUPPLY)

CON-6W - CONNECTION LEADS SCH

1 EA CREDENTIAL READER BY SECURITY CONTRACTOR

2 EA DOOR CONTACT 679-05 AS REQ WHT SCE

1 EA POWER SUPPLY PS902 900-2RS-FA LGR SCE

-INGRESS BY THE CARD READER OR KEY OVERRIDE.

-FREE EGRESS AT ALL TIMES BY PANIC DEVICE.

-ANTI-PROP ALARM BY SECURITY CONTRACTOR.

Robert J. Dole VAMC

Addendum 01

04-01-22

08 71 00-27

DOOR HARDWARE

Hardware Group No. C714 For use on Door #(s):

001.6

EACH TO HAVE:

QTY DESCRIPTION CATALOG NUMBER FINISH MFR

2 EA CONT. HINGE 112XY EPT 628 IVE

2 EA POWER TRANSFER EPT10 CON 689 VON

1 EA ELEC PANIC HARDWARE RX-MEL-25-C-DT-CON-SNB 626 FAL

1 EA ELEC PANIC HARDWARE RX-MEL-25-C-NL-CON-SNB 626 FAL

1 EA SFIC CYLINDER MORTISE/RIM AS REQUIRED. 626 FAL

1 EA PERMANENT CORE AS REQ TO MATCH EXISTING KEY

SYSTEM

2 EA SURFACE CLOSER SC81 SS X MTG BRKT, SPCR &

PLATE AS REQ

689 FAL

2 EA KICK PLATE 8400 10" X 1" LDW B-CS 630 IVE

1 SET GASKETING 328AA-S H & J AA ZER

1 SET MEETING STILE 328AA-S (2PCS/SET) AA ZER

2 EA DOOR SWEEP 8198AA AA ZER

1 EA THRESHOLD 65A-223 A ZER

4 EA HARNESS (1 IN DOOR & 1

IN FRAME)

ALLEGION CONNECT TYPE &

LENGTH AS REQ

SCH

2 EA HARNESS (TO POWER

SUPPLY)

CON-6W - CONNECTION LEADS SCH

1 EA CREDENTIAL READER BY SECURITY CONTRACTOR

2 EA DOOR CONTACT 679-05 AS REQ WHT SCE

1 EA POWER SUPPLY PS902 900-2RS LGR SCE

-INGRESS BY THE CARD READER OR KEY OVERRIDE.

-FREE EGRESS AT ALL TIMES BY EXIT DEVICE.

HARDWARE SET FOR DOUBLE-LEAF DOOR AT SERVICE YARD E001

Robert J. Dole VAMC

Addendum 01

04-01-22

08 71 00-28

DOOR HARDWARE

Hardware Group No. CE201 For use on Door #(s):

003035 006035B 017040 038A026 038C026B 109OK

109AOK 122BOK 141BOK 143BOK

EACH TO HAVE:

QTY DESCRIPTION CATALOG NUMBER FINISH MFR

3 EA HINGE 5BB1 4.5 X 4.5 652 IVE

1 EA STOREROOM LOCK MA581H DG 626 FAL

1 EA PERMANENT CORE AS REQ TO MATCH EXISTING KEY

SYSTEM

1 EA ELECTRIC STRIKE 6211 FSE DS CON 630 VON

1 EA LOCK GUARD LG14 OR AS REQ

(OMIT AT INSWING DOORS)

630 IVE

1 EA SURFACE CLOSER SC81 REG/PA AS REQ X MTG

BRKT, SPCR & PLATE AS REQ

689 FAL

1 EA KICK PLATE 8400 10” X 2” LDW B-CS 630 IVE

1 EA WALL STOP WS406/407CCV 630 IVE

1 EA GASKETING 488SBK PSA BK ZER

1 EA HARNESS (TO POWER

SUPPLY)

CON-192P SCH

1 EA CREDENTIAL READER BY SECURITY CONTRACTOR

1 EA DOOR CONTACT 679-05 AS REQ WHT SCE

1 EA POWER SUPPLY PS902 900-FA VON

1 EA DUAL TECH (PIR & RADAR)

REX SENSOR

BY SECURITY CONTRACTOR

-INGRESS BY THE CARD READER OR KEY OVERRIDE.

-FREE EGRESS AT ALL TIMES BY INSIDE LEVER.

-AT FIRE-RATED DOORS, WIRE THE ELECTRIC STRIKE TO THE FIRE ALARM SYSTEM TO

BECOME FAIL-SECURE UPON ACTIVATION OF THE FIRE ALARM SYSTEM.

Robert J. Dole VAMC

Addendum 01

04-01-22

08 71 00-29

DOOR HARDWARE

Hardware Group No. CE201.1 For use on Door #(s):

124OK

EACH TO HAVE:

QTY DESCRIPTION CATALOG NUMBER FINISH MFR

3 EA HINGE 5BB1 4.5 X 4.5 652 IVE

1 EA STOREROOM LOCK MA581H DG 626 FAL

1 EA PERMANENT CORE AS REQ TO MATCH EXISTING KEY

SYSTEM

1 EA ELECTRIC STRIKE 6211 FSE DS CON 630 VON

1 EA LOCK GUARD LG14 OR AS REQ

(OMIT AT INSWING DOORS)

630 IVE

1 EA SURFACE CLOSER SC81 REG/PA AS REQ X MTG

BRKT, SPCR & PLATE AS REQ

689 FAL

1 EA KICK PLATE 8400 10” X 2” LDW B-CS 630 IVE

1 EA WALL STOP WS406/407CCV 630 IVE

1 EA GASKETING 488SBK PSA BK ZER

1 EA ANTI-PROP ALARM BY SECURITY CONTRACTOR B/O

1 EA HARNESS (TO POWER

SUPPLY)

CON-192P SCH

1 EA CREDENTIAL READER BY SECURITY CONTRACTOR

1 EA DOOR CONTACT 679-05 AS REQ WHT SCE

1 EA MOTION SENSOR SCANII 12/24 VDC WHT SCE

1 EA POWER SUPPLY PS902 900-FA VON

-INGRESS BY THE CARD READER OR KEY OVERRIDE.

-FREE EGRESS AT ALL TIMES BY INSIDE LEVER.

Robert J. Dole VAMC

Addendum 01

04-01-22

08 71 00-30

DOOR HARDWARE

Hardware Group No. CE201C For use on Door #(s):

027046 109BOK 122AOK

EACH TO HAVE:

QTY DESCRIPTION CATALOG NUMBER FINISH MFR

3 EA HINGE 5BB1 4.5 X 4.5 652 IVE

1 EA STOREROOM LOCK MA581H DG 626 FAL

1 EA PERMANENT CORE AS REQ TO MATCH EXISTING KEY

SYSTEM

1 EA ELECTRIC STRIKE 6211 FSE DS CON 630 VON

1 EA LOCK GUARD LG14 OR AS REQ

(OMIT AT INSWING DOORS)

630 IVE

1 EA SURFACE CLOSER SC81 SS X MTG BRKT, SPCR &

PLATE AS REQ

689 FAL

1 EA KICK PLATE 8400 10” X 2” LDW B-CS 630 IVE

1 EA GASKETING 488SBK PSA BK ZER

1 EA HARNESS (TO POWER

SUPPLY)

CON-192P SCH

1 EA CREDENTIAL READER BY SECURITY CONTRACTOR

1 EA DOOR CONTACT 679-05 AS REQ WHT SCE

1 EA MOTION SENSOR SCANII 12/24 VDC WHT SCE

1 EA POWER SUPPLY PS902 900-FA VON

-INGRESS BY THE CARD READER OR KEY OVERRIDE.

-FREE EGRESS AT ALL TIMES BY INSIDE LEVER.

-WIRE THE ELECTRIC STRIKE TO THE FIRE ALARM SYSTEM TO BECOME FAIL-SECURE UPON

Robert J. Dole VAMC

Addendum 01

04-01-22

08 71 00-31

DOOR HARDWARE

Hardware Group No. CE201CW For use on Door #(s):

029048

EACH TO HAVE:

QTY DESCRIPTION CATALOG NUMBER FINISH MFR

3 EA HINGE 5BB1HW 5 X 4.5 652 IVE

1 EA STOREROOM LOCK MA581H DG 626 FAL

1 EA…