The document provided appears to be a set of typical details for a concrete underground fuel storage tank pad for a federal construction project. The details include specifications for the reinforced concrete pad, including rebar size and spacing, finished grade, excavation, and tank strap hold down requirements. The document also includes a scale conversion legend and a list of project consultants.
The related federal contract opportunity is for a construction project designated as Y1DZ--VHA MINOR CONSTRUCTION Project 589-704, which involves infilling Building 26 to create new dental clinics and a police office, as well as renovating the building for specialty care services. The solicitation number is 36C77624R0027 and the procuring agency is the Department of Veterans Affairs Technology Acquisition Center Austin.
View the file
Other files
Show all 30
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1" M
IN
T Y
P
#5 REBAR AT 12"
OC EACH WAY
TOP & BOTTOM
1'
FINISHED GRADE
#6 REBAR AT 8"
OC EACH WAY
LINE EXCAVATION
WITH FILTER FABRIC
SLOPE OF EXCATION
DETERMINED BY SOIL
STABILITY (SEE
GEOTECHNICAL)
FILTER FABRIC
TANK STRAP HOLD
DOWN (SEE
MANUFACTURER)
UST-1 FUEL TANK
NOTE:
CONTRACTOR TO FIELD VERIFY
THE EXISTING CONDITIONS.
F'c = 4000PSI MINIMUM
CONCRETE STREGNTH
CONTRACTOR TO COORDINATE
WITH MEP & MANUFACTURER
FOR INFORMATION NTO SHOWN
TANK WIDTH/LENGTH + 1'-0" ALL AROUND
SLAB OPENING
(COORDINATE WITH
TANK
MANUFACTURER)
ALL AROUND
1' - 0" (TYP)
#5 @ 12" OC EA WAY T&B
EQUIPMENT
(SEE EQUIPMENT MANUF)
SEE ARCH / MEP
O R
M E
P
S E
E A
R C
H
3/4" CHAMFER
1" TYP
FILLER & SEALER
1'
COMPACTED SELECT FILL
NOTE:
CONTRACTOR SHALL COORDINATE
DIMENSIONS AND OTHER SPECIAL
REQUIREMENTS W/ EQUIPMENT MANUF
(1) #4 CONTINUOUS AT PERIMETER WITH (1) #4 X
4'-0" AT EXTERIOR CORNERS AND (1) #4 X 4'-0"
DIAGONAL AT RE-ENTRANT CORNERS
2"
4'- 0"
2'-0"
2' -0
EXTERIOR
CORNERS
RE-ENTRANT
CORNERS
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
KS ARCH REG. NO. A-930, EXP. 12/31/2021
KS ENGR REG. NO. E-2586, EXP. 12/31/2021
STRUCTURAL / CIVIL ENGINEER
H2B, INC. (FIRM REG #: E-3405)
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB / TECH ENGR
SPUR DESIGN
25219 MADISON AVENUE, SUITE 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT HEALTH & SAFETY
1139 OLIVE STREET,
ST. LOUIS, MO 63101
(314) 436-9492
HEALTHCARE PLANNER
INNOVA GROUP
3196 N. SWAN ROAD
TUCSON, AZ 85712
(520) 886-8650
PHYSCIAL SECURITY
FORCE PROTECT
3210 GULF BLVD, UNIT 304
BELLEAIR, FL 33786
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
/2
/2
:4 :5
P
M
SA031
TYPICAL DETAILS - CONCRETE
IG
JA
100% BID SET
CONSTRUCT INFILL OF
BUILDING 26 AND RENOVATE
SPECIALTY CARE CLINICS
03/22/2024
589-704
5500 EAST KELLOGG AVENUE
WICHITA, KANSAS 67218
3/4" = 1'-0"
UNDERGROUND LIQUID FUEL STORAGE TANK
NTS2
TYPICAL GENERATOR PAD
No. REVISION DESCRIPTION DATE