This document provides room requirements for a pole barn storage structure to be constructed as part of the Western New York National Cemetery Phase 1C Maintenance Complex project. The pole barn should have a minimum ceiling height as noted on project plans and preferred access/adjacencies as shown on the architectural plan diagram. Lighting should include wet listed enclosed LED strip lights controlled by ceiling mounted occupancy sensors. Three general purpose GFI outlets in weatherproof in-use enclosures are also required. The related federal contract opportunity is solicitation number 36C10F23R0012 for the major construction project of the Western New York National Cemetery Phase 1C in Pembroke, New York being conducted by the Department of Veterans Affairs Office of Construction and Facilities Management.
View the file
Other files
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Western New York National Cemetery Phase 1C Maintenance Complex Design Build RFP 936-002C Pembroke, NY 3.5.2. Pole Barn
PART 3 - CHAPTER 6 - Page 1
3.5.2. Pole Barn Storage Structure – Room Requirements
Western New York National Cemetery Phase 1C Maintenance Complex Design Build RFP 936-002C Pembroke, NY 3.5.2. Pole Barn
3.5.2. Pole Barn - Room Requirements
F-101 – POLE BARN
Space Characteristics Function/adjacencies: STORAGE
Special Dimensions:
Ideal Plan Dimensions: 95’-0” X 25’-10” Minimum Ceiling Height: As noted on plans
Acoustics: n/a
Access: SEE ARCHITECTURAL PLAN DIAGRAM FOR PREFERRED ACCESS/ADJACENIES
Number of Occupants: n/a
Other/Special Requirements:
Uniformat Section
Description Qty Size Specific Requirements
C103004 IDENTIFYING DEVICES REQUIRED PUBLIC SIGNAGE
D502002 LIGHTING EQUIPMENT WET LISTED ENCLOSED LED STRIP LIGHT
D502002 LIGHTING CONTROL CEILING MOUNTED OCCUPANCY SENSOR
D5020 POWER EQUIPMENT GENERAL PURPOSE GFI OUTLETS IN
WEATHERPROOF IN-USE TYPE ENCLOSURE.
| 3.7.1 Room Data Fly Sheet- Pole Barn |
| F-101_POLE BARN_ROOM REQUIREMENTS |
| Uniformat Section |