This document contains room data sheets for a proposed maintenance building as part of a major construction project for the Western New York National Cemetery in Pembroke, New York. The sheets provide requirements for over 20 individual rooms in the building, including corridors, workstations, a multi-purpose room, locker rooms, toilets, mechanical and electrical spaces, vehicle equipment areas, and a mezzanine. Each room sheet specifies the intended function, dimensions, finishes, fixtures, equipment, and other details. The related federal contract opportunity is a design-build solicitation from the Department of Veterans Affairs for the Phase 1C construction of the maintenance complex, with an anticipated award date still to be determined.
View the file
Other files
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Western New York National Cemetery Phase 1C Maintenance Complex Design Build RFP 936-002C Pembroke, NY 3.5.1. Maintenance Building
PART 3 - CHAPTER 6 - Page 1
3.5.1. Maintenance Building – Room Requirements
Pembroke, NY 3.5.1 Maintenance Building
3.5.1. Maintenance Building - Room Requirements
D-101 – CORRIDOR
Space Characteristics Function/adjacencies: CORRIDOR
Special Dimensions:
Ideal Plan Dimensions: 5’-6” WIDE Minimum Minimum Ceiling Height: 9’-0”
Acoustics: STC 45
Access: SEE ARCHITECTURAL PLAN DIAGRAM FOR PREFERRED ACCESS/ADJACENIES
Number of Occupants: n/a
Other/Special Requirements:
Uniformat Section
Description Qty Size Specific Requirements
C101001 FIXED PARTITIONS FROM FLOOR TO UNDERSIDE OF STRUCTURE
C102001 STANDARD INTERIOR
DOORS 1 3’ X 7’ HOLLOW METAL DOOR
C103004 IDENTIFYING DEVICES REQUIRED PUBLIC SIGNAGE
C103014 ENTRANCE FLOOR
GRILLES AND MATS WALK-OFF MAT
C301003 GYPSUM WALLBOARD
FINISHES PAINTED WALL FINISH
C302004 RESILIENT FLOOR
FINISHES SVT
C302007 WALL BASE FINISHES RUBBER WALL BASE
C303001 ACOUSTICAL CEILING
TILES & PANELS ACOUSTICAL CEILING TILE
D202002 VALVES & HYDRANTS VARIOUS ISOLATION VALVES
D304001 HEAT AND COOL PER LOAD CALCULATIONS
D4010 FIRE ALARM AND
DETECTION SYSTEMS SPEAKER/STROBE; PULL STATION; FIRE ALARM
ANNUNCIATOR PANEL; SMOKE DETECTOR
D5020 LIGHTING AND
BRANCH WIRING RECEPTACLES, DISCONNECT SWITCH FOR
MOTORS AND HVAC EQUIPMENT
D502002 LIGHTING EQUIPMENT RECESSED LED LIGHTING; SWITCHES; CEILING
OCCUPANCY SENSORS; EXIT SIGNS
D503001 TELECOMMUNICATION
SYSTEMS CEILING WIRELESS ACCESS POINT (WIFI)
Pembroke, NY 3.5.1 Maintenance Building
D-101 – CORRIDOR
Space Characteristics Function/adjacencies: CORRIDOR
Special Dimensions:
Ideal Plan Dimensions: 5’-6” WIDE Minimum Minimum Ceiling Height: 9’-0”
Acoustics: STC 45
Access: SEE ARCHITECTURAL PLAN DIAGRAM FOR PREFERRED ACCESS/ADJACENIES
Description Qty Size Specific Requirements
D503005 SECURITY SYSTEM MOTION DETECTORS; CARD READERS;
SECURITY CAMERAS; SECURITY KEYPAD
3.5.1. Maintenance Building - Room Requirements
D-102 – MULTIPLE WORKSTATIONS
Space Characteristics Function/adjacencies: WORK STATIONS
Special Dimensions:
Ideal Plan Dimensions: 13’-2” X 15’-6” Minimum Ceiling Height: 8’-0”
Acoustics: STC 45
Access: SEE ARCHITECTURAL PLAN DIAGRAM FOR PREFERRED ACCESS/ADJACENCIES
Number of Occupants: 2
Description Qty Size Specific Requirements
B202001 WINDOWS 3 EXTERIOR WINDOWS
C101001 FIXED PARTITIONS FROM FLOOR TO UNDERSIDE OF STRUCTURE
C102001 STANDARD INTERIOR
DOORS 1 3’ X 7’ SOLID WOOD CORE
C103004 IDENTIFYING DEVICES REQUIRED PUBLIC SIGNAGE
C301003 GYPSUM WALLBOARD
FINISHES PAINTED WALL FINISH
C302005 CARPETING CARPET
C302007 WALL BASE FINISHES RUBBER WALL BASE
C303001 ACOUSTICAL CEILING
TILES & PANELS ACOUSTICAL CEILING TILE
E202003 FREESTANDING
FURNITURE 3 TASK CHAIRS
E202003 FREESTANDING
FURNITURE 3 DESKS
D304001 HEAT AND COOL PER LOAD CALCULATIONS
D4010 FIRE ALARM AND
DETECTION SYSTEMS STROBE; PULL STATION; FIRE ALARM CONTROL
PANEL; SMOKE DETECTOR
D5020 LIGHTING AND
BRANCH WIRING RECEPTACLES, DISCONNECT SWITCH FOR
MOTORS AND HVAC EQUIPMENT
D-102 – MULTIPLE WORKSTATIONS
Space Characteristics Function/adjacencies: WORK STATIONS
Special Dimensions:
Ideal Plan Dimensions: 13’-2” X 15’-6” Minimum Ceiling Height: 8’-0”
Acoustics: STC 45
Access: SEE ARCHITECTURAL PLAN DIAGRAM FOR PREFERRED ACCESS/ADJACENCIES
Description Qty Size Specific Requirements
D502002 LIGHTING EQUIPMENT RECESSED LED LIGHTING; SWITCHES; CEILING
OCCUPANCY SENSORS
D503001 TELECOMMUNICATION
SYSTEMS PHONE AND DATA OUTLETS
D503005 SECURITY SYSTEM MOTION AND GLASS BRAKE DETECTORS
D-103 – CORRIDOR
Space Characteristics Function/adjacencies: CORRIDOR
Special Dimensions:
Ideal Plan Dimensions: 5’-0” WIDE Minimum Ceiling Height: 9’-0”
Acoustics: STC 45
Access: SEE ARCHITECTURAL PLAN DIAGRAM FOR PREFERRED ACCESS/ADJACENCIES
Description Qty Size Specific Requirements
C101001 FIXED PARTITIONS FROM FLOOR TO UNDERSIDE OF STRUCTURE
C102001 STANDARD INTERIOR
DOORS 1 3’ X 7’ HOLLOW METAL DOOR
C103004 IDENTIFYING DEVICES REQUIRED PUBLIC SIGNAGE
C103014 ENTRANCE FLOOR
GRILLES AND MATS WALK-OFF MAT
C301003 GYPSUM WALLBOARD
FINISHES PAINTED WALL FINISH
C302004 RESILIENT FLOOR
FINISHES SVT
C302007 WALL BASE FINISHES RUBBER WALL BASE
C303001 ACOUSTICAL CEILING
TILES & PANELS ACOUSTICAL CEILING TILE
D304001 HEAT AND COOL PER LOAD CALCULATIONS
D4010 FIRE ALARM AND
DETECTION SYSTEMS SPEAKER/STROBES; PULL STATION; FIRE ALARM
ANNUNCIATOR PANEL; SMOKE DETECTOR
D5020 LIGHTING AND
BRANCH WIRING RECEPTACLES, DISCONNECT SWITCH FOR
MOTORS AND HVAC EQUIPMENT
D502002 LIGHTING EQUIPMENT RECESSED LED LIGHTING; SWITCHES; CEILING
OCCUPANCY SENSORS; EXIT SIGNS
SYSTEMS CEILING WIRELESS ACCESS POINT (WIFI)
D-103 – CORRIDOR
Function/adjacencies: CORRIDOR
Special Dimensions:
Ideal Plan Dimensions: 5’-0” WIDE Minimum Ceiling Height: 9’-0”
Acoustics: STC 45
Access: SEE ARCHITECTURAL PLAN DIAGRAM FOR PREFERRED ACCESS/ADJACENCIES
Description Qty Size Specific Requirements
D503005 SECURITY SYSTEM MOTION DETECTORS; CARD READERS;
SECURITY CAMERAS; SECURITY KEYPAD
D-104 – JANITOR
Space Characteristics Function/adjacencies: JANITOR
Special Dimensions:
Ideal Plan Dimensions: 13’-2” X 8’-1” Minimum Ceiling Height: 8’-0”
Acoustics: STC 45
Access: SEE ARCHITECTURAL PLAN DIAGRAM FOR PREFERRED ACCESS/ADJACENCIES
Number of Occupants: 1
Other/Special Requirements: 1HR PARTITION RATING
Description Qty Size Specific Requirements
C101001 FIXED PARTITIONS FROM FLOOR TO UNDERSIDE OF STRUCTURE
C102003 FIRE DOORS 1 3’ X 7’ FIRE-RATED DOOR
C103012 FIRESTOPPING
PENETRATIONS
C103004 IDENTIFYING DEVICES REQUIRED PUBLIC SIGNAGE
C301003 GYPSUM WALLBOARD
FINISHES PAINTED WALL FINISH
C302004 RESILIENT FLOOR
FINISHES SVT
C302007 WALL BASE FINISHES RUBBER WALL BASE
C303001 ACOUSTICAL CEILING
TILES & PANELS ACOUSTICAL CEILING TILE
D304001 HEAT AND COOL PER LOAD CALCULATIONS
D4010 FIRE ALARM AND
DETECTION SYSTEMS SMOKE DETECTOR
D5020 LIGHTING AND
BRANCH WIRING RECEPTACLES, DISCONNECT SWITCH FOR
MOTORS AND HVAC EQUIPMENT
D502002 LIGHTING EQUIPMENT RECESSED LED LIGHTING; WALL OCCUPANCY
SENSORS SWITCH
D503005 SECURITY SYSTEM CARD READER
D-105 – FOREMAN
Space Characteristics Function/adjacencies: OFFICE
Special Dimensions:
Ideal Plan Dimensions: 10’-8” X 15’-8” Minimum Ceiling Height: 8’-0”
Acoustics: STC 45
Access: SEE ARCHITECTURAL PLAN DIAGRAM FOR PREFERRED ACCESS/ADJACENCIES
Description Qty Size Specific Requirements
B202001 WINDOWS 2 WINDOWS
C101001 FIXED PARTITIONS FROM FLOOR TO UNDERSIDE OF STRUCTURE
C102001 STANDARD INTERIOR
DOORS 1 3’ X 7’ SOLID WOOD CORE
C103004 IDENTIFYING DEVICES REQUIRED PUBLIC SIGNAGE
C301003 GYPSUM WALLBOARD
FINISHES PAINTED WALL FINISH
C302005 CARPETING CARPET
C302007 WALL BASE FINISHES RUBBER WALL BASE
C303001 ACOUSTICAL CEILING
TILES & PANELS ACOUSTICAL CEILNG TILE
E202003 FREESTANDING
FURNITURE 1 TASK CHAIR
E202003 FREESTANDING
FURNITURE 1 DESK
D304001 HEAT AND COOL PER LOAD CALCULATIONS
D5020 LIGHTING AND
BRANCH WIRING RECEPTACLES, DISCONNECT SWITCH FOR
MOTORS AND HVAC EQUIPMENT
D502002 LIGHTING EQUIPMENT RECESSED LED LIGHTING; WALL OCCUPANCY
SENSOR SWITCH
D-105 – FOREMAN
Function/adjacencies: OFFICE
Special Dimensions:
Ideal Plan Dimensions: 10’-8” X 15’-8” Minimum Ceiling Height: 8’-0”
Acoustics: STC 45
Access: SEE ARCHITECTURAL PLAN DIAGRAM FOR PREFERRED ACCESS/ADJACENCIES
Description Qty Size Specific Requirements
D503001 TELECOMMUNICATION
SYSTEMS PHONE AND DATA OUTLETS; CEILING WIRELESS
ACCESS POINT (WIFI)
D503005 SECURITY SYSTEM MOTION AND GLASS BRAKE DETECTORS;
SECURITY CAMERAS; SECURITY MONITOR
D-106 – MULTI-PURPOSE
Space Characteristics Function/adjacencies: MULTI-PURPOSE
Special Dimensions:
Ideal Plan Dimensions: 36’-7” X 15’-8” Minimum Ceiling Height: 9’-0”
Acoustics: STC 45
Access: SEE ARCHITECTURAL PLAN DIAGRAM FOR PREFERRED ACCESS/ADJACENIES
Number of Occupants: 4
Description Qty Size Specific Requirements
C101001 FIXED PARTITIONS FROM FLOOR TO UNDERSIDE OF STRUCTURE
C103004 IDENTIFYING DEVICES REQUIRED PUBLIC SIGNAGE
C103008 COUNTERS SOLID SURFACE COUNTER AT LAVATORIES WITH
BACK SPLASHES
C301003 GYPSUM WALLBOARD
FINISHES PAINTED WALL FINISH
C302004 RESILIENT FLOOR
FINISHES SVT
C302007 WALL BASE FINISHES RUBBER WALL BASE
C303001 ACOUSTICAL CEILING
TILES & PANELS ACOUSTICAL CEILING TILE
C103003 MARKER BOARDS &
TACK BOARDS 2 1 WHITE BOARD, 1 TACK BOARD
C103009 CABINETS
E202003 FREESTANDING
FURNITURE 18 STACKING CHAIRS
E202003 FREESTANDING
FURNITURE 4 SQUARE TABLES
E202003 FREESTANDING
FURNITURE 2 RECTANGLE TABLES
E202003 FREESTANDING
FURNITURE 2 VENDING MACHINES
D-106 – MULTI-PURPOSE
Function/adjacencies: MULTI-PURPOSE
Special Dimensions:
Ideal Plan Dimensions: 36’-7” X 15’-8” Minimum Ceiling Height: 9’-0”
Acoustics: STC 45
Access: SEE ARCHITECTURAL PLAN DIAGRAM FOR PREFERRED ACCESS/ADJACENIES
Number of Occupants: 4
Description Qty Size Specific Requirements
D201004 SINKS 1 DOUBLE BASIN STAINLESS STEEL
D304001 HEAT AND COOL PER LOAD CALCULATIONS
D4010 FIRE ALARM AND
DETECTION SYSTEMS SPEAKER/STROBE
D5020 LIGHTING AND
BRANCH WIRING RECEPTACLES, DISCONNECT SWITCH FOR
MOTORS AND HVAC EQUIPMENT
D502002 LIGHTING EQUIPMENT RECESSED AND UNDERCABINET LED LIGHTING;
SWITCHES; CEILING OCCUPANCY SENSORS
D503001 TELECOMMUNICATION
D503005 SECURITY SYSTEM MOTION AND GLASS BRAKE DETECTORS
D-109- BOOT HOLDING/WASH
Space Characteristics Function/adjacencies: BOOT STORAGE/WASHING
Special Dimensions:
Ideal Plan Dimensions: 7’-9” X 5’-9” Minimum Ceiling Height: 9’-0”
Acoustics: STC 45
Access: SEE ARCHITECTURAL PLAN DIAGRAM FOR PREFERRED ACCESS/ADJACENCIES
Description Qty Size Specific Requirements
C101001 FIXED PARTITIONS FROM FLOOR TO UNDERSIDE OF STRUCTURE
C102001 STANDARD INTERIOR
DOORS 1 3’0” X 7’0” HOLLOW METAL DOOR
C102007 INTERIOR DOOR
HARDWARE LOCKSET AND CLOSER
C103004 IDENTIFYING DEVICES REQUIRED PUBLIC/STAFF BATHROOM
SIGNAGE/PLAQUES
C103014 ENTRANCE FLOOR
GRILLES AND MATS 1 WALK OFF MATT
C301003 GYPSUM WALLBOARD
FINISHES PAINTED WALL FINISH
C302004 RESILIENT FLOOR
FINISHES SVT
C302007 WALL BASE FINISHES RUBBER WALL BASE
C303001 ACOUSTICAL CEILING
TILES & PANELS ACOUSTICAL CEILING TILE
D202002 VALVES & HYDRANTS 1 3/4" INTERIOR WALL HYDRANT
D203003 FLOOR DRAINS 1 STANDARD ELECTRONIC TRAP PRIMER
D304001 HEAT AND COOL PER LOAD CALCULATIONS
D304007 BATHROOM EXHUAST
D-109- BOOT HOLDING/WASH
Function/adjacencies: BOOT STORAGE/WASHING
Special Dimensions:
Ideal Plan Dimensions: 7’-9” X 5’-9” Minimum Ceiling Height: 9’-0”
Acoustics: STC 45
Access: SEE ARCHITECTURAL PLAN DIAGRAM FOR PREFERRED ACCESS/ADJACENCIES
Description Qty Size Specific Requirements
D5020 LIGHTING AND
BRANCH WIRING RECEPTACLE
D502002 LIGHTING EQUIPMENT RECESSED LED LIGHTING; CEILING OCCUPANCY
SENSORS
D503005 SECURITY SYSTEM GLASS BRAKE DETECTORS
D-110 – ELECTRICAL
Space Characteristics Function/adjacencies: ELECTRICAL
Special Dimensions:
Ideal Plan Dimensions: 13’-11” X 10’-6” Minimum Ceiling Height: 8’-0”
Acoustics: STC 45
Access: SEE ARCHITECTURAL PLAN DIAGRAM FOR PREFERRED ACCESS/ADJACENCIES
Description Qty Size Specific Requirements
C101001 FIXED PARTITIONS FROM FLOOR TO UNDERSIDE OF STRUCTURE
C102001 STANDARD INTERIOR
DOORS 1 3’ X 7’ HOLLOW METAL DOOR
C103004 IDENTIFYING DEVICES REQUIRED PUBLIC SIGNAGE
C302007 WALL BASE FINISHES RUBBER WALL BASE
C302004 RESILIENT FLOOR
FINISHES SVT
C303090 OTHER CEILING &
CEILING FINISHES EXPOSED CEILING
D304001 HEAT AND COOL PER LOAD CALCULATIONS
D304007 EXHUAST
VENTILATION PER CALCULATION
D4010 FIRE ALARM AND
DETECTION SYSTEMS STROBE; FIRE ALARM CONTROL PANEL; SMOKE
DETECTOR
D5020 LIGHTING AND
BRANCH WIRING
RECEPTACLES, DISCONNECT SWITCH FOR
MOTORS AND HVAC EQUIPMENT; ELECTRICAL
DISTRIBUTION EQUIPMENT
D502002 LIGHTING EQUIPMENT SURFACE STRIP LED LIGHTING; TIME-SWITCH
D503001 TELECOMMUNICATION
D503005 SECURITY SYSTEM CARD READER
3.5.1 Maintenance Building - Room Requirements
D-112 – PARTS AND TOOL STORAGE
Space Characteristics Function/adjacencies: STORAGE
Special Dimensions:
Ideal Plan Dimensions: 14’-3” X 15’-8” Minimum Ceiling Height: 9’-0”
Acoustics: STC 45
Access: SEE ARCHITECTURAL PLAN DIAGRAM FOR PREFERRED ACCESS/ADJACENCIES
Description Qty Size Specific Requirements
C101001 FIXED PARTITIONS FROM FLOOR TO UNDERSIDE OF STRUCTURE
C102001 STANDARD INTERIOR
DOORS 2 3’ X 7’ HOLLOW METAL DOOR
C102006 INTERIOR GATES 1 CHAIN LINK GATE AND FENCE
C103004 IDENTIFYING DEVICES REQUIRED PUBLIC SIGNAGE
C301003 GYPSUM WALLBOARD
FINISHES PAINTED WALL FINISH
C302004 RESILIENT FLOOR
FINISHES SVT
C302007 WALL BASE FINISHES RUBBER WALL BASE
C303001 ACOUSTICAL CELING
TILES & PANELS ACOUSTICAL CEILING TILE
D304001 HEAT AND COOL PER LOAD CALCULATIONS
D4010 FIRE ALARM AND
DETECTION SYSTEMS SMOKE DETECTOR
D5020 LIGHTING AND
BRANCH WIRING RECEPTACLES, DISCONNECT SWITCH FOR
MOTORS AND HVAC EQUIPMENT
D502002 LIGHTING EQUIPMENT RECESSED LED LIGHTING; SWITCHES; CEILING
OCCUPANCY SENSORS
D-112 – PARTS AND TOOL STORAGE
Function/adjacencies: STORAGE
Special Dimensions:
Ideal Plan Dimensions: 14’-3” X 15’-8” Minimum Ceiling Height: 9’-0”
Acoustics: STC 45
Access: SEE ARCHITECTURAL PLAN DIAGRAM FOR PREFERRED ACCESS/ADJACENCIES
Description Qty Size Specific Requirements
D-113 – TELECOM
Space Characteristics Function/adjacencies: TELECOM
Special Dimensions:
Ideal Plan Dimensions: 13’-11” X 7’-6” Minimum Ceiling Height: 8’-0”
Acoustics: STC 45
Access: SEE ARCHITECTURAL PLAN DIAGRAM FOR PREFERRED ACCESS/ADJACENIES
Description Qty Size Specific Requirements
C101001 FIXED PARTITIONS FROM FLOOR TO UNDERSIDE OF STRUCTURE
C102001 STANDARD INTERIOR
DOORS 1 3’ X 7’ HOLLOW METAL DOOR
C103004 IDENTIFYING DEVICES REQUIRED PUBLIC SIGNAGE
C301003 GYPSUM WALLBOARD
FINISHES PAINTED WALL FINISH
C302004 RESILIENT FLOOR
FINISHES SVT
C302007 WALL BASE FINISHES RUBBER WALL BASE
C303090 OTHER CEILING &
CEILING FINISHES EXPOSED CEILING
D304001 HEAT AND COOL COOLING ONLY. PER LOAD CALCULATIONS
D4010 FIRE ALARM AND
DETECTION SYSTEMS STROBE; SMOKE DETECTOR
D5020 LIGHTING AND
BRANCH WIRING RECEPTACLES, DISCONNECT SWITCH FOR
MOTORS AND HVAC EQUIPMENT
D502002 LIGHTING EQUIPMENT SURFACE STRIP LED LIGHTING; TIME-SWITCH
D503001 TELECOMMUNICATION
SYSTEMS PHONE AND DATA OUTLETS; RACKS; CABINETS;
UPS; PATCH PANELS; PDUS
D503005 SECURITY SYSTEM CARD READERS; SECURITY CAMERAS; SECURITY
CONTROL PANEL; NVRS
D-114 – WOMEN’S LOCKER
Space Characteristics Function/adjacencies: FEMALE LOCKER FACILITIES
Special Dimensions:
Ideal Plan Dimensions: 14’-8” X 8’-1” Minimum Ceiling Height: 9’-0”
Acoustics: STC 45
Access: SEE ARCHITECTURAL PLAN DIAGRAM FOR PREFERRED ACCESS/ADJACENIES
Description Qty Size Specific Requirements
C101001 FIXED PARTITIONS FROM FLOOR TO UNDERSIDE OF STRUCTURE
C103004 IDENTIFYING DEVICES REQUIRED PUBLIC/STAFF BATHROOM
SIGNAGE/PLAQUES
C103005 LOCKERS 4 LOCKERS 15” W X 18” D
C301003 GYPSUM WALLBOARD
FINISHES PAINTED WALL FINISH
C302004 RESILIENT FLOOR
FINISHES SVT
C302007 WALL BASE FINISHES RUBBER WALL BASE
C303002 GYPSUM WALLBOARD
CEILING FINISHES GYPSUM WALLBOARD CEILING
D203003 FLOOR DRAINS 1 STANDARD PROVIDE SLAB/FLOOR SLOPE TO FLOOR DRAIN
AND TRAP PRIMER TO FLOOR DRAIN
D304001 HEAT AND COOL PER LOAD CALULATIONS
D304007 BATHROOM EXHUAST PER CALULATIONS
D4010 FIRE ALARM AND
DETECTION SYSTEMS SPEAKER/STROBE
D5020 LIGHTING AND
BRANCH WIRING RECEPTACLES, DISCONNECT SWITCH FOR
MOTORS AND HVAC EQUIPMENT
D502002 LIGHTING EQUIPMENT RECESSED LED LIGHTING; SWITCHES; CEILING
OCCUPANCY SENSORS
D-114 – WOMEN’S LOCKER
Function/adjacencies: FEMALE LOCKER FACILITIES
Special Dimensions:
Ideal Plan Dimensions: 14’-8” X 8’-1” Minimum Ceiling Height: 9’-0”
Acoustics: STC 45
Access: SEE ARCHITECTURAL PLAN DIAGRAM FOR PREFERRED ACCESS/ADJACENIES
E201003 SEATING (FIXED) 1 FIXED BENCH
D-116 – WOMEN’S TOILET
Space Characteristics Function/adjacencies: FEMALE TOILET FACILITIES
Special Dimensions:
Ideal Plan Dimensions: 17’-9” X 10’-0” Minimum Ceiling Height: 9’-0”
Acoustics: STC 45
Access: SEE ARCHITECTURAL PLAN DIAGRAM FOR PREFERRED ACCESS/ADJACENIES
Description Qty Size Specific Requirements
C101001 FIXED PARTITIONS FROM FLOOR TO UNDERSIDE OF STRUCTURE
C102001 STANDARD INTERIOR
DOORS 1 3’0” X 7’0” SOLID CORE WOOD DOOR
C102007 INTERIOR DOOR
HARDWARE LOCKSET AND CLOSER
C103001
COMPARTMENTS,
CUBICLES AND TOILET
PARTITIONS
1 SOLID PHENOLIC TOILET COMPARTMENTS
C103002 TOILET & BATH
ACCESSORIES
PAPER TOWEL HOLDER WITH WASTE
RECEPTACLE
SOAP DISPENSERS AT EACH LAVATOR, WALL
MOUNTED
MIRROR AT EACH LAVATORY
C103004 IDENTIFYING DEVICES REQUIRED PUBLIC/STAFF BATHROOM
SIGNAGE/PLAQUES
C103008 COUNTERS SOLID SURFACE COUNTER AT LAVATORIES WITH
BACK AND SIDE SPLASHES
C302001 TILE FLOOR FINISHES 12” X 12” CERAMIC FLOOR TILE
C301003 GYPSUM WALLBOARD
FINISHES PAINTED WALL FINISH
C302007 TILE WALL BASE
FINISHES 6” HIGH
MIN. CERAMIC TILE COVE BASE
C303002 GYPSUM WALLBOARD
CEILING FINISHES GYPSUM WALLBOARD CEILING
D201001 WALL MOUNTED FLUSH
VALVE 1 STANDARD HANDICAPPED/ADA HARD WIRED SENSOR
FLUSH VALVE
D-116 – WOMEN’S TOILET
Function/adjacencies: FEMALE TOILET FACILITIES
Special Dimensions:
Ideal Plan Dimensions: 17’-9” X 10’-0” Minimum Ceiling Height: 9’-0”
Acoustics: STC 45
Access: SEE ARCHITECTURAL PLAN DIAGRAM FOR PREFERRED ACCESS/ADJACENIES
Description Qty Size Specific Requirements
D201003 COUNTERTOP
LAVATORY 1 STANDARD
PUBLIC HANDICAPPED/ADA, HARD WIRED
SENSOR FAUCET WITH PROTECTIVE PIPE
COVERING FOR EXPOSED BELOW RIM PIPING
AND ACCESSORIES
D202002 FLOW CONTROL VALVE 1
D203003 FLOOR DRAINS 1 3” OUTLET WITH TRAP SEAL PRIMER CONNECTION
D304001 HEAT AND COOL PER LOAD CALCULATIONS
D304007 BATHROOM EXHAUST PER CALCULATIONS
D4010 FIRE ALARM AND
DETECTION SYSTEMS STROBE
D5020 LIGHTING AND BRANCH
WIRING GFCI RECEPTACLES, DISCONNECT SWITCH FOR
MOTORS AND HVAC EQUIPMENT
D502002 LIGHTING EQUIPMENT RECESSED AND VANITY LED LIGHTING;
SWITCHES; CEILING OCCUPANCY SENSORS
E201090 OTHER FIXED INTERIOR
FURNISHINGS 1 BOOT WARMER
D-117 - Men’s Toilet Space Characteristics Function/adjacencies: MALE TOILET FACILITIES
Special Dimensions:
Ideal Plan Dimensions: 24’-10” X 10’-0” Minimum Ceiling Height: 9’-0”
Acoustics: STC 45
Access: SEE ARCHITECTURAL PLAN DIAGRAM FOR PREFERRED ACCESS/ADJACENCIES
Description Qty Size Specific Requirements
C101001 FIXED PARTITIONS FROM FLOOR TO UNDERSIDE OF STRUCTURE
C102001 STANDARD INTERIOR
DOORS 1 3’0” X 7’0” SOLID CORE WOOD DOOR
C102007 INTERIOR DOOR
HARDWARE LOCKSET AND CLOSER
C103001
COMPARTMENTS,
CUBICLES AND TOILET
PARTITIONS
4 SOLID PHENOLIC TOILET COMPARTMENTS (1
URINAL, 3 STALLS)
C103002 TOILET & BATH
ACCESSORIES
PAPER TOWEL HOLDER WITH WASTE
RECEPTACLE
SOAP DISPENSERS AT EACH LAVATOR, WALL
MOUNTED
MIRROR AT EACH LAVATORY
C103004 IDENTIFYING DEVICES REQUIRED PUBLIC/STAFF BATHROOM
SIGNAGE/PLAQUES
C103008 COUNTERS SOLID SURFACE COUNTER AT LAVATORIES WITH
BACK AND SIDE SPLASHES
C302001 TILE FLOOR FINISHES 12” X 12” CERAMIC FLOOR TILE
C301003 GYPSUM WALLBOARD
FINISHES PAINTED WALL FINISH
C302007 TILE WALL BASE FINISHES 6” HIGH
MIN. CERAMIC TILE COVE BASE
C303002 GYPSUM WALLBOARD
CEILING FINISHES GYPSUM WALLBOARD CEILING
D201001 FLOOR MOUNTED FLUSH
VALVE 3 HANDICAPPED/ADA, HARD WIRED SENSOR
OPERATED
D-117 - Men’s Toilet
Function/adjacencies: MALE TOILET FACILITIES
Special Dimensions:
Ideal Plan Dimensions: 24’-10” X 10’-0” Minimum Ceiling Height: 9’-0”
Acoustics: STC 45
Access: SEE ARCHITECTURAL PLAN DIAGRAM FOR PREFERRED ACCESS/ADJACENCIES
Description Qty Size Specific Requirements
D201002 WALL MOUNTED FLUSH
VALVE URINAL 2 STANDARD HANDICAPPED/ADA, HARD WIRED SENSOR
OPERATED
D201003 COUNTERTOP LAVATORY 2 STANDARD HANDICAPPED/ADA, HARD WIRED SENSOR
OPERATED
D203003 FLOOR DRAINS 1 STANDARD
PROVIDE SLAB/FLOOR SLOPE TO FLOOR DRAIN
AND PRESSURE DROP ACTIVATED TRAP PRIMER
TO FLOOR DRAIN
D304001 HEAT AND COOL PER LOAD CALCULATIONS
D304007 BATHROOM EXHUAST PER CALCULATIONS
D4010 FIRE ALARM AND
DETECTION SYSTEMS STROBE
D5020 LIGHTING AND BRANCH
WIRING GFCI RECEPTACLES, DISCONNECT SWITCH FOR
MOTORS AND HVAC EQUIPMENT
D502002 LIGHTING EQUIPMENT RECESSED AND VANITY LED LIGHTING;
SWITCHES; CEILING OCCUPANCY SENSORS
E201090 OTHER FIXED INTERIOR
FURNISHINGS 1 BOOT WARMER
D-118 – MEN’S LOCKER
Space Characteristics Function/adjacencies: MALE LOCKER FACILITIES
Special Dimensions:
Ideal Plan Dimensions: 27’-10” X 8’-1” Minimum Ceiling Height: 9’-0”
Acoustics: STC 45
Access: SEE ARCHITECTURAL PLAN DIAGRAM FOR PREFERRED ACCESS/ADJACENCIES
Description Qty Size Specific Requirements
C101001 FIXED PARTITIONS FROM FLOOR TO UNDERSIDE OF STRUCTURE
C103004 IDENTIFYING DEVICES REQUIRED PUBLIC/STAFF BATHROOM
SIGNAGE/PLAQUES
C103005 LOCKERS 14 15” W X 18” D LOCKERS
C301003 GYPSUM WALLBOARD
FINISHES PAINTED WALL FINISH
C302004 RESILIENT FLOOR
FINISHES SVT
C302007 WALL BASE FINISHES RUBBER WALL BASE
C303002 GYPSUM WALLBOARD
CEILING FINISHES GYPSUM WALLBOARD CEILING
D201005 SHOWER 1 MODULAR ADA COMPLIANT ROLL-IN
ENCLOSURE
D203003 FLOOR DRAINS 1 STANDARD PROVIDE SLAB/FLOOR SLOPE TO FLOOR DRAIN
AND TRAP PRIMER TO FLOOR DRAIN
D304001 HEAT AND COOL PER LOAD CALCULATIONS
D304007 BATHROOM EXHUAST PER CALCULATIONS
D4010 FIRE ALARM AND
DETECTION SYSTEMS SPEAKER/STROBE
D5020 LIGHTING AND
D-118 – MEN’S LOCKER
Function/adjacencies: MALE LOCKER FACILITIES
Special Dimensions:
Ideal Plan Dimensions: 27’-10” X 8’-1” Minimum Ceiling Height: 9’-0”
Acoustics: STC 45
Access: SEE ARCHITECTURAL PLAN DIAGRAM FOR PREFERRED ACCESS/ADJACENCIES
Description Qty Size Specific Requirements
D502002 LIGHTING EQUIPMENT RECESSED LED LIGHTING; SWITCHES; CEILING
OCCUPANCY SENSORS
E201003 SEATING (FIXED) 1 FIXED BENCH
D-119 – WORK AREA
Space Characteristics Function/adjacencies: WORK AREA
Special Dimensions:
Ideal Plan Dimensions: 15’-0” X 9’-0” Minimum Ceiling Height: 8’-0”
Acoustics: STC 45
Access: SEE ARCHITECTURAL PLAN DIAGRAM FOR PREFERRED ACCESS/ADJACENCIES
Description Qty Size Specific Requirements
B202001 WINDOWS 4 EXTERIOR WINDOWS
C101001 FIXED PARTITIONS FROM FLOOR TO UNDERSIDE OF STRUCTURE
C102001 STANDARD INTERIOR
DOORS 1 3’ X 7’ HOLLOW METAL DOOR
C103004 IDENTIFYING DEVICES REQUIRED PUBLIC SIGNAGE
C301003 GYPSUM WALLBOARD
FINISHES PAINTED WALL FINISH
C302004 RESILIENT FLOOR
FINISHES SVT
C302007 WALL BASE FINISHES RUBBER WALL BASE
C303001 ACOUSTICAL CEILING
TILES & PANELS ACOUSTICAL CEILING TILE
D304001 HEAT AND COOL PER LOAD CALCULATIONS
D4010 FIRE ALARM AND
DETECTION SYSTEMS STROBE
D5020 LIGHTING AND
BRANCH WIRING RECEPTACLES, DISCONNECT SWITCH FOR
MOTORS AND HVAC EQUIPMENT
D502002 LIGHTING EQUIPMENT SURFACE STRIP LED LIGHTING; SWITCHES;
CEILING OCCUPANCY SENSORS
D-120 – MECHANICAL
Space Characteristics Function/adjacencies: MECHANICAL
Special Dimensions:
Ideal Plan Dimensions: 23’-2” X 10’-5” Minimum Ceiling Height: 8’-0”
Acoustics: STC 45
Access: SEE ARCHITECTURAL PLAN DIAGRAM FOR PREFERRED ACCESS/ADJACENCIES
Description Qty Size Specific Requirements
C101001 FIXED PARTITIONS FROM FLOOR TO UNDERSIDE OF STRUCTURE
C102003 FIRE DOORS 1 3’ X 7’ FIRE-RATED DOOR
C103012 FIRESTOPPING
PENETRATIONS
C103004 IDENTIFYING DEVICES REQUIRED PUBLIC SIGNAGE
C301003 GYPSUM WALLBOARD
FINISHES PAINTED WALL FINISH
C302007 WALL BASE FINISHES RUBBER WALL BASE
C302006 MASONRY & STONE
FLOORING CONCRETE FLOOR
C303001 ACOUSTICAL CEILING
TILES & PANELS ACOUSTICAL CEILING TILE
D304001 HEAT AND COOL PER LOAD CALCULATIONS
D502001 BRANCH WIRING
D502002 LIGHTING EQUIPMENT
D203003 FLOOR DRAINS 1 4” FLOOR DRAIN WITH ELECTRONIC TRAP SEAL
PRIMER CONNECTION
D4010 FIRE ALARM AND
DETECTION SYSTEMS SPEAKER/STROBE; SMOKE AND HEAT DETECTOR
D5020 LIGHTING AND RECEPTACLES, DISCONNECT SWITCH FOR
D-120 – MECHANICAL
Function/adjacencies: MECHANICAL
Special Dimensions:
Ideal Plan Dimensions: 23’-2” X 10’-5” Minimum Ceiling Height: 8’-0”
Acoustics: STC 45
Access: SEE ARCHITECTURAL PLAN DIAGRAM FOR PREFERRED ACCESS/ADJACENCIES
Description Qty Size Specific Requirements
BRANCH WIRING MOTORS AND HVAC EQUIPMENT
D502002 LIGHTING EQUIPMENT SURFACE STRIP LED LIGHTING; TIME-SWITCH
D503001 TELECOMMUNICATION
SYSTEMS PHONE AND DATA OUTLETS; CEILING WIRELESS
ACCESS POINT (WIFI)
D503005 SECURITY SYSTEM CARD READERS
D-121 – VEHICLE EQUIP
Space Characteristics Function/adjacencies: VEHICLE EQUIPMENT
Special Dimensions:
Ideal Plan Dimensions: 73’-8” X 49’-8” Minimum Ceiling Height: n/a
Acoustics: STC 45
Access: SEE ARCHITECTURAL PLAN DIAGRAM FOR PREFERRED ACCESS/ADJACENCIES
Number of Occupants: 10
Description Qty Size Specific Requirements
B203004 OVERHEAD AND ROLL-
UP DOORS 3 11’ X 12’ GARAGE DOORS
C101001 FIXED PARTITIONS FROM FLOOR TO UNDERSIDE OF STRUCTURE
C103004 IDENTIFYING DEVICES REQUIRED PUBLIC SIGNAGE
C103007 FIRE EXTINGUISHER
CABINET 1
C103090 OTHER INTERIOR
SPECIALTIES 1 VEHICLE LIFT - OFCI
C201001 INTERIOR AND
EXTERIOR STAIRS 2 INDUSTRIAL METAL STAIRS
C201090
STAIR HANDRAILS,
GUARDRAILS, AND
ACCESSORIES
C301001 CONCRETE WALL
FINISHES PAINTED CMU TO A HEIGHT OF 12’-0”
C301090 OTHER WALL
FINISHES METAL PANEL ABOVE 12’-0”
C302007 WALL BASE FINISHES RUBBER WALL BASE
C302006 MASONRY & STONE
FLOORING CONCRETE FLOOR
C303090 OTHER CEILING &
CEILING FINISHES EXPOSED CEILING/PAINT
D203003 FLOOR DRAINS 4” HEAVY DUTY TRACTOR TYPE WITH SEDIMENT
BUCKET
D-121 – VEHICLE EQUIP
Function/adjacencies: VEHICLE EQUIPMENT
Special Dimensions:
Ideal Plan Dimensions: 73’-8” X 49’-8” Minimum Ceiling Height: n/a
Acoustics: STC 45
Access: SEE ARCHITECTURAL PLAN DIAGRAM FOR PREFERRED ACCESS/ADJACENCIES
Number of Occupants: 10
Description Qty Size Specific Requirements
D209005 COMPRESSED AIR
SYSTEM ” SEE ROOM DATA SHEET FOR MECHANICAL
ROOM
D209005 COMPRESSED AIR
SYSTEM 1/2" COMPRESSED AIR OUTLETS
D304001 HEAT AND COOL PER LOAD CALCULATIONS
D304007 DEDICATED VEHICLE
EXHAUST PER CALCULATIONS
D4010 FIRE ALARM AND
DETECTION SYSTEMS SPEAKER/STROBE; PULL STATIONS
D5020 LIGHTING AND
BRANCH WIRING RECEPTACLES, DISCONNECT SWITCH FOR
MOTORS AND HVAC EQUIPMENT
D502002 LIGHTING EQUIPMENT HIGH BAY LED LIGHTING; SWITCHES; EXIT SIGN
D503001 TELECOMMUNICATION
SYSTEMS PHONE AND DATA OUTLETS; CEILING WIRELESS
ACCESS POINT (WIFI)
D503005 SECURITY SYSTEM
MOTION AND GLASS BRAKE DETECTORS; CARD
READERS; SECURITY CAMERAS; DOOR
CONTACTS FOR OVERHEAD DOORS
D-122 – VEHICLE EQUIP STORAGE
Space Characteristics Function/adjacencies: VEHICLE EQUIPMENT STORAGE
Special Dimensions:
Ideal Plan Dimensions: 20’-0” X 10’ - 8" Minimum Ceiling Height: n/a
Acoustics: STC 45
Access: SEE ARCHITECTURAL PLAN DIAGRAM FOR PREFERRED ACCESS/ADJACENIES
Description Qty Size Specific Requirements
C101001 FIXED PARTITIONS FROM FLOOR TO UNDERSIDE OF STRUCTURE
C12001 STANDARD INTERIOR
DOORS 2 3’ X 7’
C103004 IDENTIFYING DEVICES REQUIRED PUBLIC SIGNAGE
C103007 FIRE EXTINGUISHER
CABINET 1
C301001 CONCRETE WALL
FINISHES PAINTED CMU TO A HEIGHT OF 12’-0”
C301090 OTHER WALL
FINISHES METAL PANEL ABOVE 12’-0”
C302007 WALL BASE FINISHES RUBBER WALL BASE
C302006 MASONRY & STONE
FLOORING CONCRETE FLOOR
C303090 OTHER CEILING &
CEILING FINISHES EXPOSED CEILING/PAINT
D203003 FLOOR DRAINS 1 4” HEAVY DUTY TRACTOR TYPE GRATE WITH
SEDIMENT BUCKET
D304001 HEAT AND COOL PER LOAD CALCULATIONS
D4010 FIRE ALARM AND
DETECTION SYSTEMS SPEAKER/STROBE
D5020 LIGHTING AND
D-122 – VEHICLE EQUIP STORAGE
Function/adjacencies: VEHICLE EQUIPMENT STORAGE
Special Dimensions:
Ideal Plan Dimensions: 20’-0” X 10’ - 8" Minimum Ceiling Height: n/a
Acoustics: STC 45
Access: SEE ARCHITECTURAL PLAN DIAGRAM FOR PREFERRED ACCESS/ADJACENIES
D502002 LIGHTING EQUIPMENT HIGH BAY LED LIGHTING; SWITCHES; EXIT SIGN
D-123 – WASH BAY
Space Characteristics Function/adjacencies: WASH BAY
Special Dimensions:
Ideal Plan Dimensions: 17’-2” X 49’-8” Minimum Ceiling Height: n/a
Acoustics: STC 45
Access: SEE ARCHITECTURAL PLAN DIAGRAM FOR PREFERRED ACCESS/ADJACENIES
Number of Occupants: 3
Description Qty Size Specific Requirements
B203004 OVERHEAD AND ROLL-
UP DOORS 1 11’ X 12’ GARAGE DOORS
C101001 FIXED PARTITIONS FROM FLOOR TO UNDERSIDE OF STRUCTURE
C12001 STANDARD INTERIOR
DOORS 2 3’ X 7’
C103004 IDENTIFYING DEVICES REQUIRED PUBLIC SIGNAGE
C301001 CONCRETE WALL
FINISHES PAINTED CMU TO A HEIGHT OF 12’-0”
C301090 OTHER WALL
FINISHES METAL PANEL ABOVE 12’-0”
C302007 WALL BASE FINISHES RUBBER WALL BASE
C302006 MASONRY & STONE
FLOORING CONCRETE FLOOR
C303090 OTHER CEILING &
CEILING FINISHES EXPOSED CEILING/PAINT
D202090 OTHER DOMESTIC
WATER SUPPLY 1 1”
1” CW CONNECTION TO POWER WASH
EQUIPMENT ROUTED THROUGH REDUCED
PRESSURE ZONE BACKFLOW PREVENTER
D203002 FLOOR DRAINS 4” 14” WIDE TRENCH DRAIN WITH HEAVY DUTY
TRACTOR GRATE AND SEDIMENT BUCKET
D209005 COMPRESSED AIR
SYSTEM SEE “MECHANICAL ROOM” DESCRIPTION IF
SYSTEM IS REQUIRED FOR THIS ROOM
D209005 COMPRESSED AIR
SYSTEM OUTLETS
D-123 – WASH BAY
Function/adjacencies: WASH BAY
Special Dimensions:
Ideal Plan Dimensions: 17’-2” X 49’-8” Minimum Ceiling Height: n/a
Acoustics: STC 45
Access: SEE ARCHITECTURAL PLAN DIAGRAM FOR PREFERRED ACCESS/ADJACENIES
Description Qty Size Specific Requirements
D304001 HEAT AND COOL PER LOAD CALCULATIONS
D304007 EXHUAST
VENTILATION PER CALCULATIONS
D4010 FIRE ALARM AND
DETECTION SYSTEMS WEATHERPROOF SPEAKER/STROBE; PULL
STATIONS
D5020 LIGHTING AND
BRANCH WIRING
GFI RECEPTACLES IN WEATHERPROOF
ENCLOSURE, DISCONNECT SWITCH FOR
MOTORS AND HVAC EQUIPMENT
D502002 LIGHTING EQUIPMENT HIGH BAY LED LIGHTING; SWITCHES; EXIT SIGN
D503005 SECURITY SYSTEM
MOTION AND GLASS BRAKE DETECTORS; CARD
READERS; SECURITY CAMERAS; DOOR
CONTACTS FOR OVERHEAD DOORS
D-201 – MEZZANINE
Space Characteristics Function/adjacencies: MEZZANINE
Special Dimensions:
Ideal Plan Dimensions: 16’-9” X 38’-9” Minimum Ceiling Height: n/a
Acoustics: STC 45
Access: SEE ARCHITECTURAL PLAN DIAGRAM FOR PREFERRED ACCESS/ADJACENCIES
Description Qty Size Specific Requirements
C101001 FIXED PARTITIONS FROM FLOOR TO UNDERSIDE OF STRUCTURE
C103004 IDENTIFYING DEVICES REQUIRED PUBLIC SIGNAGE
C102003 FIRE DOORS 1 3’ X 7’ FIRE-RATED DOOR
C103012 FIRESTOPPING
PENETRATIONS
C101004
INTERIOR
GUARDRAILS AND
SCREENS
METAL GUARDRAIL AT MEZZANINE
C201001 INTERIOR AND
EXTERIOR STAIRS 2 INDUSTRIAL METAL STAIRS
C201090
STAIR HANDRAILS,
GUARDRAILS, AND
ACCESSORIES
D202003 DOMESTIC WATER
EQUIPMENT 2 WATER HEATERS: PROPANE FUEL TYPE
D202003 DOMESTIC WATER
EQUIPMENT BACKFLOW PREVENTERS
D202003 DOMESTIC WATER
EQUIPMENT 1 DOMESTIC HOT WATER RECIRCULATION PUMP
AND EXPANSION TANK
D202003 DOMESTIC WATER
EQUIPMENT 1 LOW PRESSURE DROP THJERMOSTATIC HOT
WATER MASTER MIXING VALVE
D209005
COMPRESSED AIR
SYSTEM (NON-
BREATHING)
AIR DRYER, RECEIVER TANK(S) AND OIL/WATER
SEPERATOR
D-201 – MEZZANINE
Function/adjacencies: MEZZANINE
Special Dimensions:
Ideal Plan Dimensions: 16’-9” X 38’-9” Minimum Ceiling Height: n/a
Acoustics: STC 45
Access: SEE ARCHITECTURAL PLAN DIAGRAM FOR PREFERRED ACCESS/ADJACENCIES
Description Qty Size Specific Requirements
D203003 FLOOR DRAINS 1 4” FLOOR DRAIN WITH ELECTRONIC TRAP SEAL
PRIMER CONNECTION
C301001 CONCRETE WALL
FINISHES PAINTED CMU TO A HEIGHT OF 12’-0”
C301090 OTHER WALL
FINISHES METAL PANEL ABOVE 12’-0”
C302007 WALL BASE FINISHES RUBBER WALL BASE
C302006 MASONRY & STONE
FLOORING CONCRETE FLOOR
C303090 OTHER CEILING &
CEILING FINISHES EXPOSED CEILING/PAINT
D304001 HEAT AND COOL PER LOAD CALCULATIONS
D4010 FIRE ALARM AND
DETECTION SYSTEMS SPEAKER/STROBE; PULL STATION
D5020 LIGHTING AND
BRANCH WIRING RECEPTACLES, DISCONNECT SWITCH FOR
MOTORS AND HVAC EQUIPMENT
D502002 LIGHTING EQUIPMENT PENDANT STRIP LED LIGHTING; TIME-SWITCH;
CEILING OCCUPANCY SENSORS; EXIT SIGN
D503001 TELECOMMUNICATION
SYSTEMS PHONE AND DATA OUTLETS; CEILING WIRELESS
ACCESS POINT (WIFI)
D503005 SECURITY SYSTEM SECURITY CAMERAS
D-202 - SHOWER
Space Characteristics Function/adjacencies: SHOWER FACILITIES
Special Dimensions:
Ideal Plan Dimensions: 7’-9” X 9’-5” Minimum Ceiling Height: 9’-0”
Acoustics: STC 45
Access: SEE ARCHITECTURAL PLAN DIAGRAM FOR PREFERRED ACCESS/ADJACENIES
Description Qty Size Specific Requirements
C101001 FIXED PARTITIONS FROM FLOOR TO UNDERSIDE OF STRUCTURE
C102001 STANDARD INTERIOR
DOORS 1 3’0” X 7’0” SOLID CORE WOOD DOOR
C102007 INTERIOR DOOR
HARDWARE LOCKSET AND CLOSER
C103004 IDENTIFYING DEVICES REQUIRED PUBLIC/STAFF BATHROOM
SIGNAGE/PLAQUES
C302001 TILE FLOOR FINISHES 12” X 12” CERAMIC FLOOR TILE
C301003 GYPSUM WALLBOARD
FINISHES PAINTED WALL FINISH
C302007 TILE WALL BASE
FINISHES 6” HIGH
MIN. CERAMIC TILE COVE BASE
C303002 GYPSUM WALLBOARD
CEILING FINISHES GYPSUM WALLBOARD CEILING
D201005 SHOWERS/TUBS 1
D203003 FLOOR DRAINS STANDARD PRESSURE DROP ACTIVATED TRAP PRIMER
D304001 HEAT AND COOL PER LOAD CALCULATIONS
D304007 BATHROOM EXHUAST PER CALCULATIONS
D4010 FIRE ALARM AND
DETECTION SYSTEMS STROBE
D-202 - SHOWER
Function/adjacencies: SHOWER FACILITIES
Special Dimensions:
Ideal Plan Dimensions: 7’-9” X 9’-5” Minimum Ceiling Height: 9’-0”
Acoustics: STC 45
Access: SEE ARCHITECTURAL PLAN DIAGRAM FOR PREFERRED ACCESS/ADJACENIES
Description Qty Size Specific Requirements
D5020 LIGHTING AND BRANCH
WIRING GFCI RECEPTACLES, DISCONNECT SWITCH FOR
MOTORS AND HVAC EQUIPMENT
D502002 LIGHTING EQUIPMENT RECESSED WET LISTED LED LIGHTING;
SWITCHES; CEILING OCCUPANCY SENSORS
| 3.5.1 Room Data flysheet_MB |
| D-101_CORRIDOR_ROOM REQUIREMENTS |
| Uniformat Section |
| D-102_MULTIPLE WORKSTATIONS_ROOM REQUIREMENTS |
| Uniformat Section |
| D-103_CORRIDOR_ROOM REQUIREMENTS |
| Uniformat Section |
| D-104_JANITOR_ROOM REQUIREMENTS |
| Uniformat Section |
| D-105_FOREMAN_ROOM REQUIREMENTS |
| Uniformat Section |
| D-106_MULTI-PURPOSE ROOM_ROOM REQUIREMENTS |
| Uniformat Section |
| D-109_BOOT HOLDING-WASH_ROOM REQUIREMENTS |
| Uniformat Section |
| D-110_ELECTRICAL_ROOM REQUIREMENTS |
| Uniformat Section |
| D-112_PARTS AND TOOL STORAGE_ROOM REQUIREMENTS |
| Uniformat Section |
| D-113_TELECOM_ROOM REQUIREMENTS |
| Uniformat Section |
| D-114_WOMENS LOCKER ROOM_ROOM REQUIREMENTS |
| Uniformat Section |
| D-116_WOMENS TOILET ROOM_ROOM REQUIREMENTS |
| Uniformat Section |
| D-117_MENS TOILET ROOM_ROOM REQUIREMENTS |
| Uniformat Section |
| D-118_MENS LOCKER ROOM_ROOM REQUIREMENTS |
| Uniformat Section |
| D-119_WORK AREA_ROOM REQUIREMENTS |
| Uniformat Section |
| D-120_MECHANICAL_ROOM REQUIREMENTS |
| Uniformat Section |
| D-121_VEHICLE EQUP_ROOM REQUIREMENTS |
| Uniformat Section |
| D-122_VEHICLE EQUP STORAGE_ROOM REQUIREMENTS |
| Uniformat Section |
| D-123_WASH BAY_ROOM REQUIREMENTS |
| Uniformat Section |
| D-201_MEZZANINE_ROOM REQUIREMENTS |
| Uniformat Section |
| D-202_SHOWER_ROOM REQUIREMENTS |
| Uniformat Section |
File details come from the government source that posted it. Updated .