This document is a Common and Emergency Parts Inventory Recommendation and Tracking Sheet for boiler maintenance and operations in Miami. The sheet identifies 54 distinct spare parts with recommended par levels (inventory quantities) to be maintained on-site, along with a tracking column for recording in-house inventory levels.

The recommended spare parts encompass key boiler system components organized by functional category: fuel system components (gas and oil valves, filters, gaskets), ignition system parts (transformer, electrode, insulators), observation and measurement components (sight glasses, gauges, lenses), pump assemblies and seals (feedwater, condensate, and fuel oil pumps), control system components (pressure switches, transmitters, relays, modules), and boiler instrumentation (touchscreen panel, BMS annunciator, flame scanner, indicator bulbs). Par levels range from 1 to 6 units per part, with certain categories requiring multiples of specific types—for example, 2 of each relay type, 1 of each pressure transmitter type, and 12 indicator bulbs. The tracking sheet provides space for facilities personnel to record current in-house inventory quantities against recommended par levels, enabling maintenance staff to identify when parts must be reordered to maintain operational readiness and minimize equipment downtime.

View the file

Other files

File Type Posted
ATTACHMENT 2 - EMR.pdf PDF
ATTACHMENT 6 - VAAR 852.219-75 VA NOTICE OF LIMITATIONS ON SUBCONTRACTING.pdf PDF
ATTACHMENT 7 - Site Map.pdf PDF
ATTACHMENT 10 - Drawings 3 of 3.pdf PDF
ATTACHMENT 11 - Site Specific Health and Safety Plan For Contaminated Soil Contact.pdf PDF
ATTACHMENT 14 Yarway BlowOff Valve.pdf PDF
ATTACHMENT 23 Addendum 1 Section 232300 Refrigerant Piping.pdf PDF
ATTACHMENT 25 Addendum 1 Section 232113 Hydronic Pumps.pdf PDF
ATTACHMENT 30 VHA Master Specifications.pdf PDF
ATTACHMENT 33 - Boiler Safety Device Interim Safety Measure Form.pdf PDF
ATTACHMENT 34 - Miami Main Boiler Semi Annual Safety Device Testing Documentation.pdf PDF
ATTACHMENT 36 C - SARGENT 10X Line Catalog.pdf PDF
ATTACHMENT 3 - Specialized Experience Form.pdf PDF
ATTACHMENT 5 - Base Offer Price Breakdown.xlsx XLSX spreadsheet
ATTACHMENT 12 - Soil Management and Dust Control Plan.pdf PDF
ATTACHMENT 15 Architectural Narrative.pdf PDF
ATTACHMENT 17 Addendum 1.pdf PDF
ATTACHMENT 21 Addendum 1 Section 237300 Indoor Central Station Air Handling Units.pdf PDF
ATTACHMENT 28 Addendum 2 Section 232213 Steam and Condensate Heating Piping.pdf PDF
ATTACHMENT 38 - ICRA.pdf PDF
S02 - 36C24826R0090 - 03302026.pdf PDF
ATTACHMENT 1 - Wage Determination.pdf PDF
ATTACHMENT 4 - Past Performance Forms.pdf PDF
ATTACHMENT 8 - Drawings 1 of 3.pdf PDF
ATTACHMENT 9 - Drawings 2 of 3.pdf PDF
ATTACHMENT 16 - Physical Security Resiliency Design Manual - PSRDM.pdf PDF
ATTACHMENT 18 Addendum 1 Section 238216 Air Coils.pdf PDF
ATTACHMENT 20 Addendum 1 Section 238123 ComputerRoom AirConditioners.pdf PDF
ATTACHMENT 26 Addendum 1 Section 223500 Domestic Water Heat Exchangers.pdf PDF
ATTACHMENT 27 - Addendum 2.pdf PDF
ATTACHMENT 29 Addendum 2 Drawings.pdf PDF
ATTACHMENT 31 Section 099100 Painting.pdf PDF
ATTACHMENT 36 A - Electronic Key Project 546-23-106 Specs.pdf PDF
ATTACHMENT 36 B - SARGENT 10X Line Sell Sheet.pdf PDF
ATTACHMENT 37 - PCRA.pdf PDF
ATTACHMENT 13 - First Quarterly Groundwater Monitoring Report.pdf PDF
ATTACHMENT 19 Addendum 1 Section 238200 Convection Heating and Cooling Units.pdf PDF
ATTACHMENT 22 Addendum 1 Section 234000 HVAC Air Cleaning Devices.pdf PDF
ATTACHMENT 24 Addendum 1 Section 232113 Hydronic Piping.pdf PDF
Attachment 32 - DERM Letter.pdf PDF
ATTACHMENT 36 D - Medeco CLIQ Brochure.pdf PDF
Show all 41

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

138-82

Common and Emergency Parts Inventory Recommendation and Tracking Sheet List of Recommended Spare Parts and Par Levels (Miami)

Part Recommended Par Level Automatic Shutoff Gas Valve (Maxon) 1

Main Gas Normally Open Vent Valve (ASCO) 1

Pilot Gas Normally Closed Shutoff Valve (ASCO) 1

Pilot Gas Normally Open Vent Valve (ASCO) 1

Automatic Shutoff Oil Valve (ASCO) 1

Gaskets for Gas Filters 3

Filter Element for Gas Filter 3

Gasket for Oil Filter Housing 3

Oil Filter Element 3

Ignitor Transformer 1

Igniter High Voltage Lead 1

Igniter Electrode 1

Ignitor Standoff Insulators 1

Complete Boiler Hand- Hole and Man-Hole Gasket Sets 6

Clear Lens for Observation Port 3

Shaded Lens for Observation Port 3

Gage/Sight Glass 3

Gage / Sight Glass Gasket Sets 3

Atomizing Air Compressor Oil (1 Gallon) 1

Atomizing Air Compressor Intake Filter Element 3

Boiler Feedwater Control Valve 1

Boiler Feedwater Valve Actuator 1

Feedwater Pump Rotating Parts Assembly 1

Condensate Pump Rotating Parts Assembly 1

Fuel Oil Pump Mechanical Seal Set 1

Fuel Oil Pump Gasket Set 1

Backpressure Control Regulator 1

Master Control Steam Pressure Transmitter 1

Electric Power Drive Unit / Actuator 1

Current BMS 1

Current BMS Annunciator 1

Flame Scanner 1

Control Panel Indicator Bulb 12

Control Relays 2 of each type

Pressure Transmitter 1 of each type

Pilot Gas Pressure Switch 1

Low Gas Pressure Switch 1

High Gas Pressure Switch 1

Low Propane Pressure Switch 1

High Propane Pressure Switch 1

CAPS Switch 1

List of Recommended Spare Parts and Par Levels (Miami)

Part Recommended Par Level PAPS Switch 1

Furnace Pressure Switch 1

Boiler Control Touchscreen Panel 1

Boiler Input Module 1

Boiler Output Module 1

Recommended Spare Parts Inventory Tracking Sheet (Miami)

Part Recommended Par Level

In House Inventory

Automatic Shutoff Gas Valve (Maxon)

Main Gas Normally Open Vent Valve

(ASCO)

Pilot Gas Normally Closed Shutoff Valve (ASCO)

Pilot Gas Normally Open Vent Valve

(ASCO)

Automatic Shutoff Oil Valve (ASCO) 1

Gaskets for Gas Filters 3

Filter Element for Gas Filter 3

Gasket for Oil Filter Housing 3

Oil Filter Element 3

Ignitor Transformer 1

Igniter High Voltage Lead 1

Igniter Electrode 1

Ignitor Standoff Insulators 1

Complete Boiler Hand- Hole and Man-Hole Gasket Sets

Clear Lens for Observation Port 3

Shaded Lens for Observation Port 3

Gage/Sight Glass 3

Gage / Sight Glass Gasket Sets 3

Boiler Feedwater Control Valve 1

Boiler Feedwater Valve Actuator 1

Feedwater Pump Rotating Parts Assembly

Condensate Pump Rotating Parts Assembly

Fuel Oil Pump Mechanical Seal Set 1

Fuel Oil Pump Gasket Set 1

Backpressure Control Regulator 1

Master Control Steam Pressure Transmitter

Electric Power Drive Unit / Actuator Unit

BMS (Burner Management System) 1

BMS Annunciator 1

Recommended Spare Parts Inventory Tracking Sheet (Miami)

Part Recommended Par Level

In House Inventory

Flame Scanner 1

Control Panel Indicator Bulb 12

Control Relays 2 of each type

Pressure Transmitter 1 of each type

Pilot Gas Pressure Switch 1

Low Gas Pressure Switch 1

High Gas Pressure Switch 1

Low Propane Pressure Switch 1

High Propane Pressure Switch 1

CAPS Switch 1

PAPS Switch 1

Furnace Pressure Switch 1

Boiler Control Touchscreen Panel 1

Boiler Control Input Module 1

Boiler Control Output Module 1