Attachment_3_-_Dry_Water_Based_Fire_Sprinkler_Systems.pdf
PDF 138 KB Posted
- Attached to
- Fire Alarm Suppression Backflow Inspect Maintain Federal contract opportunity
- Solicitation number
- 140P8326Q0017
About this file
This is Attachment 2 to RFQ 140P8326Q0017 for Mount Rainier National Park, detailing inspection, testing, maintenance, and repair requirements for dry and water-based fire sprinkler systems.
The work scope requires contractors to provide inspection, testing, maintenance, and repair services for fire sprinkler systems across multiple buildings at Mount Rainier National Park, all performed in compliance with NFPA 25 (2011), NPS Standards, and the Scope of Work. The park maintains 7 dry pipe sprinkler systems located at buildings including the Paradise Employee Ski Dorm, Paradise Guide House, Nisqually Entrance Office, Longmire Radio Shop/Electric Shop, Longmire Emergency Operations Center, Longmire Carpenter/Sign Shops, and Paradise Jackson Visitor Center. Additionally, the park operates 12 wet pipe sprinkler systems (11 original plus 1 added per Contracting Officer Representative direction) serving various facilities including the Tahoma Woods Education Center, Sunrise Visitor Center, Tahoma Woods Apartments, White River Dormitory, Longmire Macy Dorm, Sunrise Block Houses, and Carbon River Thompson House. All systems were last inspected on 11/15/2024. Contractors must submit written inspection and testing reports using official NPS forms (Wet Pipe ITM AS-1, Dry Pipe ITM AS-2, Fire Pump Annual Performance Test FP-1A, Fire Pump Annual Test Summary FP-1B, Backflow Test BF-1, and Standpipe & Hose ITM SH-1) after each service visit. Additional requirements include inspecting and testing all backflow prevention assemblies, performing obstruction investigations per NFPA 25, and managing impairments following proper procedures. Contractors must collect and properly dispose of all test water, antifreeze solution, and additives off-site in compliance with Federal, State, and local wastewater regulations, documenting disposal methods and quantities. Park access varies by location, with year-round access to Tahoma Woods and Nisqually, seasonal access requiring chains from November 1 to May 1 at Longmire and Paradise, and summer-only access to Ohanapecosh, White River, Sunrise, and Thompson House (mid-July through October).
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Attachment_7_Questions_and_Answers_140P8326Q0014_MORA_Fire_Alarm_Suppression_Backflow_-_Copy_0001.pdf | ||
| Sol_140P8326Q0017_Amd_0001.pdf | ||
| Attachment_6_Wage_Determination_0001.pdf | ||
| Attachment_2___Fire_Detection___Notification_Systems.pdf | ||
| Sol_140P8326Q0017.pdf | ||
| Attachment_1-_Statement_of_Work.pdf | ||
| Attachment_4___Backflow__Prevention_Inventory_Table.pdf | ||
| Attachment_5_-_Longmire_Fire_Alarm_-_Pull_Box_and_EOC_Panel_Zone_Summary.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RFQ 140P8326Q0017 Mount Rainier National Park
Attachment 2
ATTACHMENT 2 – DRY & WATER-BASED FIRE SPRINKLER SYSTEMS
Inspection, Testing, Maintenance & Repairs
Counts are based on the most current Park information at the time of release. Conditions discovered during service may vary. Date of last inspection / test is listed under building name.
All inspection, testing, maintenance, and repair shall comply with:
NFPA 25 (2011), NPS Standards, and the Scope of Work.
A. REPORTING REQUIREMENTS
Requirement Description
Written Reports Contractor shall prepare written inspection/testing reports using official National Park Service (NPS) forms and submit all completed forms after each service visit.
Required Forms
• Wet Pipe ITM (AS-1) • Dry Pipe ITM (AS-2) • Fire Pump Annual Performance Test (FP-1A) • Fire Pump Annual Test Summary (FP- 1B) • Backflow Test (BF-1) • Standpipe & Hose ITM (SH-1)
Backflow Prevention Assemblies
All backflow assemblies associated with sprinkler systems must be inspected/tested per NFPA 25 (2011) and the SOW.
Impairments (Emergency / Preplanned)
All impairment procedures must follow NFPA 25 (2011) to minimize risk and outage duration.
Obstruction Investigations
Contractor shall perform obstruction investigations in accordance with NFPA 25 (2011).
B. DRY PIPE FIRE SPRINKLER SYSTEMS
Total: 7 Dry Risers
Building # Location / Description System Type
Reference No.
QTRS P301
11/15/2024 Paradise Employee "SKI" Dorm* Dry Pipe 19895
BLDG P602
11/15/2024 Paradise Guide House* Dry Pipe 19890
BLDG N001
11/15/2024 Nisqually Entrance Office* Dry Pipe 19531
BLDG L203
11/15/2024 Longmire Radio Shop / Electric Shop* Dry Pipe 19484
BLDG L216
11/15/2024
Longmire Emergency Operations Center
(EOC)*
Dry Pipe 52591
BLDG L214
11/15/2024 Longmire Carpenter / Sign Shops* Dry Pipe 19498
BLDG P003
11/15/2024 Paradise Jackson Visitor Center* Dry Pipe 92159
C. WET PIPE FIRE SPRINKLER SYSTEMS
Total: 11 Wet Risers + L-006 Added Per COR Direction
Building # Location / Description System Type Subtype / Notes Ref.
No.
BLDG T207
Tahoma Woods Education Center*
Wet Pipe (Antifreeze)
Antifreeze Loop 73345
Building # Location / Description System Type Subtype / Notes Ref.
No.
11/15/2024
QTRS T115
11/15/2024
Tahoma Woods Temp Curatorial*
Wet Pipe Residential 13R 19924
QTRS T116
11/15/2024
Tahoma Woods Temp Curatorial Admin*
Wet Pipe Residential 13R 19925
QTRS S002
11/15/2024 Sunrise North Block House
Wet Pipe (Antifreeze)
Antifreeze Loop 19900
BLDG S003
11/15/2024 Sunrise Visitor Center
Wet Pipe (Antifreeze)
Antifreeze Loop 19901
QTRS T117
11/15/2024 Tahoma Woods Apartments*
Wet Pipe (Antifreeze)
Residential 13D 94998
QTRS T118
11/15/2024 Tahoma Woods Apartments*
Wet Pipe (Antifreeze)
Residential 13D 95000
QTRS W222
11/15/2024 White River Dormitory Wet Pipe
Standard Wet System
86087
BLDG L101
11/15/2024 Longmire Macy Dorm*
Wet Pipe (Antifreeze)
Antifreeze Loop 19409
QTRS S001
11/15/2024 Sunrise South Block House
Wet Pipe (Antifreeze)
Antifreeze Loop 19899
BLDG C210
11/15/2024
Carbon River Thompson House*
Wet Pipe Residential 13R 226057
BLDG L-006 Longmire Community Building Wet Pipe Not Available 19405
Building # Location / Description System Type Subtype / Notes Ref.
No.
Not Available
D. WATER-BASED SYSTEM OPERATIONS
Requirement Description
Collection & Disposal of Water/Fluids
Contractor shall collect all test water, antifreeze solution, or additives and transport off-site for proper disposal. No discharging to ground, drains, or waterways is permitted.
Environmental Compliance
Disposal shall comply with all Federal, State, and local wastewater regulations.
Documentation Contractor must include disposal method, quantities, and locations in final reports.
E. PARK ACCESS & SEASONAL CONDITIONS
Area Access Notes
Tahoma Woods Located in Ashford – year-round access.
Nisqually ~5 miles east of Ashford – year-round.
Longmire ~22 miles from Ashford – chains required Nov 1–May 1.
Paradise ~30 miles from Ashford – chains required Nov 1–May 1.
Ohana (Ohanapecosh) Off SR-123 – open Spring through Fall only.
White River Off SR-410 – Summer only.
Sunrise Approximately 25 miles beyond White River – Summer only.
Area Access Notes
Thompson House (Carbon River)
Off SR-165 – Open mid-July through October.
File details come from the government source that posted it. Updated .