Attachment_2_Table 3. CLB TANC Split AFSM Load Rev 13 02062026.pdf

PDF 114 KB Posted

Attached to
AV Equipment Upgrade for Split Conference Rooms
Solicitation number
N6426726Q5012
Issued by

About this file

This document is a technical specification table for Team Submarine Conference Room Upgrades detailing network and audiovisual infrastructure requirements across multiple architecture boxes in two classified conference rooms (201/4W-333 and 201/4W-334).

The specification encompasses network connectivity, audiovisual systems, and power infrastructure for two separate AFSM (Architecture Framework System Module) installations. For Room 201/4W-333, Architecture Box 0242-04 (AF1) includes network connections at the center conference table supporting VOIP, vIPer, and itinerant laptop connectivity via CAT6 RJ-45 connectors requiring hard disconnects, along with 120 VAC 20-amp power. Architecture Boxes AV1 through AV6 specify wall-mounted audiovisual systems including video transmission to 85-inch and 65-inch liquid crystal displays, DMPS3 equipment cabinets with cross-connects, classified workstations with SIPR network connectivity via fiber optic (FL SC) connectors, and Crestron control systems. The second room (201/4W-334) contains identical specifications under Architecture Box 0242-02 (AF8) with corresponding AV boxes (AV8 through AV13). Side wall connections are specified in Architecture Boxes 0242-05 (AF7) and 0242-06 (AF14) for both rooms, providing itinerant laptop video ports, USB webcam connectivity, and additional Crestron touchscreen connections. All network cables requiring hard disconnects are routed to either Facilities or Integrator responsibilities, while classified SIPR connections utilize NMCI Network Support with fiber-to-copper converters. Power requirements are consistently specified as 120 VAC 20-amp circuits, either existing or newly installed adjacent to equipment locations.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Table 3. Team Submarine Conference Room Upgrades - CLB TANC Split AFSM Load Rev 12

Arch. Box No.

Arch. Box

Type Arch. Box Port No.

Location Cable Function Cable Type Connector Type Hard Disconnect Surface Required

Remarks

0242-04 (AF1) AFSM 201/4W-333 - Center, conference table D1 VOIP NIPR NTWK CAT6 RJ-45 Y Facilities D2 vIPer NIPR NTWK CAT6 RJ-45 Y Facilities D3 Itinerant Laptop non-NNPI NIPR NTWK CAT6 RJ-45 Y Facilities P1 Itinerant Laptop U-NNPI NIPR NTWK CAT6 RJ-45 Y Facilities

- Power 120 VAC 20 Amp 2-gang NEMA 20 N Existing

AV1 AFSM 201/4W-333 - Center, conference table AV-only AFSM D1 Itinerant Laptop U-NNPI Video CAT6 RJ-45 Y Integrator, HD TXC 4KZ 101 D2 Itinerant Laptop non-NNPI Video CAT6 RJ-45 Y Integrator, HD TXC 4KZ 101 D3 UC-SB1-CAM Room USB Webcam CAT6 RJ-45 Y Integrator, USB-EXT-3-LOCAL P1 Crestron TS-1070-GV-B-S to DMPS3 CAT6 RJ-45 Y Integrator

- Power 120 VAC 20 Amp 2-gang NEMA 20 N Existing, Panel RP-41-8

AV2 Wall mount 201/4W-333 - West wall, RPG/Studio X50

2.a. RPG 500 SIPR VTC VLAN NTWK FL SC Y NMCI Network Support, FL-Cu Converter

- Power 120 VAC 20 Amp 1-gang NEMA 20 N Adjacent 120 VAC 20 Amp Duplex

AV3 Wall mount 201/4W-333 - NW corner, DMPS3 Equipment Cabinet

3.a. 70.7 V Audio Analog to Ovhd. Speakers Tw pair 20 Ga. Phoenix Y Integrator

3.b. DMPS3 Video to Local Presentation 85" LSD -

AV5

CAT6 RJ-45 Y Integrator, HD TXC 4KZ 101

3.c. DMPS3 Video to Teams 65" LSD - AV6 CAT6 RJ-45 Y Integrator, HD TXC 4KZ 101

3.d. DMPS3 Video to SKVM Input 1 - Internal HDMI HDMI N Integrator, connection internal to equip. rack

3.e. DMPS3 Control to Crestron TS-1070-GV-B-S

AV1 - AFSM

CAT6 RJ-45 Y Integrator, DM link

3.f. DMPS3 Control to Crestron TS-1070-GV-B-S AV7 - Side

CAT6 RJ-45 Y Integrator, DM link

3.g. AV1 - AFSM Itinerant Laptop U-NNPI Video to

DMPS3

CAT6 RJ-45 Y Integrator, HD RXC 4KZ 101

3.h. AV1 - AFSM Itinerant Laptop non-NNPI Video to DMPS3

CAT6 RJ-45 Y Integrator, HD RXC 4KZ 101

3.i. AV7 - Side Itinerant Laptop U-NNPI Video to

DMPS3

CAT6 RJ-45 Y

Integrator, HD RXC 4KZ 101

3.j. AV7 -Side Itinerant Laptop non-NNPI Video to

DMPS3

CAT6 RJ-45 Y Integrator, HD RXC 4KZ 101

3.k. DMPS3 333 System Cross-connect to DMPS3 334 - Internal - CC1

CAT6 RJ-45 Y Integrator, DM out to DM in

3.l. DMPS3 334 System Cross-connect to DMPS3 333 - Internal - CC2

CAT6 RJ-45 Y Integrator, DM out to DM in

- Power 120 VAC 20 Amp 2-gang NEMA 20 N Adjacent 120 VAC 20 Amp Duplex

AV4 Wall mount 201/4W-333 - NW corner, Driver Workstation, SKVM

4.a. Classified Workstation SIPR NTWK FL SC Y NMCI Network Support, FL-Cu Converter

- Power 120 VAC 20 Amp 2-gang NEMA 20 N Adjacent 120 VAC 20 Amp Duplex

AV5 Wall mount 201/4W-333 - North wall, center, Local Presentation 85" LSD;

Crestron UC-SB1-CAM Room USB

5.a. DMPS3 Video to 85" LSD CAT6 RJ-45 Y Integrator, HD RXC 4KZ 101

5.b. UC-SB1-CAM Room USB Webcam Video out to conference table

CAT6 RJ-45 Y Integrator, USB-EXT-3-REMOTE

- Power 120 VAC 20 Amp 2-gang NEMA 20 N Adjacent 120 VAC 20 Amp Duplex

AV6 Wall mount 201/4W-333 - East wall, center, Teams Presentation 65" LSD

6.a. DMPS3 Video to 65" LSD CAT6 RJ-45 Y Integrator, HD RXC 4KZ 101 6.b. Power 120 VAC 20 Amp 1-gang NEMA 20 N Adjacent 120 VAC 20 Amp Duplex

[0242-05] (AF7) Wall mount 201/4W-333 - North wall, Side Wall Network Connections Presumptive I/O numbering

D1 VOIP NIPR NTWK CAT6 RJ-45 Y Facilities D2 vIPer NIPR NTWK CAT6 RJ-45 Y Facilities D3 Itinerant Laptop non-NNPI NIPR NTWK CAT6 RJ-45 Y Facilities P1 Itinerant Laptop U-NNPI NIPR NTWK CAT6 RJ-45 Y Facilities

- Power 120 VAC 20 Amp 2-gang NEMA 20 N Integrator

AV7 Wall mount 201/4W-333 - North Wall, Side Wall AV Connections

7.a. Itinerant Laptop U-NNPI Video CAT6 RJ-45 Y Integrator, HD TXC 4KZ 101 7.b. Itinerant Laptop non-NNPI Video CAT6 RJ-45 Y Integrator, HD TXC 4KZ 101 7.c. UC-SB1-CAM Room USB Webcam CAT6 RJ-45 Y Integrator, USB-EXT-3-LOCAL 7.d. Crestron TS-1070-GV-B-S to DMPS3 CAT6 RJ-45 Y Integrator

- Power 120 VAC 20 Amp 2-gang NEMA 20 N Integrator 0242-02 (AF8) AFSM 201/4W-334 - Center, conference table

D1 VOIP NIPR NTWK CAT6 RJ-45 Y Facilities D2 vIPer NIPR NTWK CAT6 RJ-45 Y Facilities D3 Itinerant Laptop non-NNPI NIPR NTWK CAT6 RJ-45 Y Facilities P1 Itinerant Laptop U-NNPI NIPR NTWK CAT6 RJ-45 Y Facilities

- Power 120 VAC 20 Amp 2-gang NEMA 20 N Existing

AV8 AFSM 201/4W-334 - Center, conference table AV-only AFSM D1 Itinerant Laptop U-NNPI Video CAT6 RJ-45 Y Integrator, HD TXC 4KZ 101 D2 Itinerant Laptop non-NNPI Video CAT6 RJ-45 Y Integrator, HD TXC 4KZ 101 D3 UC-SB1-CAM Room USB Webcam CAT6 RJ-45 Y Integrator, USB-EXT-3-LOCAL P1 Crestron TS-1070-GV-B-S to DMPS3 CAT6 RJ-45 Y Integrator

- Power 120 VAC 20 Amp 2-gang NEMA 20 N Existing, Panel RP-41-2

AV9 Wall mount 201/4W-334 - West wall, Poly RPG/Studio X50

9.a. RPG 500 SIPR VTC VLAN NTWK FL SC Y NMCI Network Support, FL-Cu Converter

- Power 120 VAC 20 Amp 1-gang NEMA 20 N Adjacent 120 VAC 20 Amp Duplex

AV10 Wall mount 201/4W-334 - SW corner, DMPS3 Equipment Cabinet - Internal

10.a. 70.7 V Audio Analog to Ovhd. Speakers Tw pair 20 Ga. Phoenix Y Integrator

10.b. DMPS3 Video to Local Presentation 85" LSD -

AV12

CAT6 RJ-45 Y Integrator, HD TXC 4KZ 101

10.c. DMPS3 Video to Teams 65" LSD - AV13 CAT6 RJ-45 Y Integrator, HD TXC 4KZ 101

10.d. DMPS3 Video to SKVM Input 1 - Internal HDMI HDMI N Integrator, connection internal to equip. rack

10.e. DMPS3 Control to Crestron TS-1070-GV-B-S -

AV8 AFSM

CAT6 RJ-45 Y Integrator, DM link

10.f. DMPS3 Control to Crestron TS-1070-GV-B-S - AV14 Side

CAT6 RJ-45 Y Integrator, DM link

10.f. AV8- AFSM Itinerant Laptop U-NNPI Video to

DMPS3

CAT6 RJ-45 Y Integrator, HD RXC 4KZ 101

10.g. AV8 - AFSM Itinerant Laptop non-NNPI Video to DMPS3

CAT6 RJ-45 Y Integrator, HD RXC 4KZ 101

10.h. AV14 - Side Itinerant Laptop U-NNPI Video to

DMPS3

CAT6 RJ-45 Y Integrator, HD RXC 4KZ 101

10.i. AV14 - Side Itinerant Laptop non-NNPI Video to DMPS3

CAT6 RJ-45 Y Integrator, HD RXC 4KZ 101

10.j. DMPS3 333 System Cross-connect to DMPS3 334 - Internal - CC1

CAT6 RJ-45 Y Integrator, DM out to DM in

10.k. DMPS3 334 System Cross-connect to DMPS3 333 - Internal - CC2

CAT6 RJ-45 Y Integrator, DM out to DM in

- Power 120 VAC 20 Amp 2-gang NEMA 20 N Adjacent 120 VAC 20 Amp Duplex

AV11 Wall mount 201/4W-334 - SW corner, Driver Workstation, SKVM

11.a. Classified Workstation SIPR NTWK FL SC Y NMCI Network Support, FL-Cu Converter

- Power 120 VAC 20 Amp 2-gang NEMA 20 N Adjacent 120 VAC 20 Amp Duplex

AV12 Wall mount 201/4W-334 - South wall, center, Local Presentation 85" LSD;

Crestron UC-SB1-CAM Room USB

12.a. DMPS3 Video to 85" LSD CAT6 RJ-45 Y Integrator, HD RXC 4KZ 101

12.b. UC-SB1-CAM Room USB Webcam Video out to Conference table

CAT6 RJ-45 Y Integrator, USB-EXT-3-Remote

- Power 120 VAC 20 Amp 2-gang NEMA 20 N Adjacent 120 VAC 20 Amp Duplex

AV13 Wall mount 201/4W-334 - East wall, center, Teams Presentation 65" LSD

13.a. DMPS3 Video to 65" LSD CAT6 RJ-45 Y Integrator, HD RXC 4KZ 101

- Power 120 VAC 20 Amp 1-gang NEMA 20 N Adjacent 120 VAC 20 Amp Duplex

[0242-06] (AF14) Wall mount 201/4W-334 - South Wall, Side Wall Network Connections Presumptive I/O numbering

D1 VOIP NIPR NTWK CAT6 RJ-45 Y Facilities D2 vIPer NIPR NTWK CAT6 RJ-45 Y Facilities D3 Itinerant Laptop non-NNPI NIPR NTWK CAT6 RJ-45 Y Facilities P1 Itinerant Laptop U-NNPI NIPR NTWK CAT6 RJ-45 Y Facilities

- Power 120 VAC 20 Amp 2-gang NEMA 20 N Integrator

AV14 Wall mount 201/4W-334 - South Wall, Side Wall AV Connections

14.a. Itinerant Laptop U-NNPI Video CAT6 RJ-45 Y Integrator, HD TXC 4KZ 101 14.b. Itinerant Laptop non-NNPI Video CAT6 RJ-45 Y Integrator, HD TXC 4KZ 101 14.c. UC-SB1-CAM Room USB Webcam CAT6 RJ-45 Y Integrator, USB-EXT-3-LOCAL 14.d. Crestron TS-1070-GV-B-S to DMPS3 CAT6 RJ-45 Y Integrator

- Power 120 VAC 20 Amp 2-gang NEMA 20 N Integrator

Attachment_2_Table 3. CLB TANC Split AFSM Load Rev 13 02062026.xlsx