Attachment_2_GFO_Drawings.pdf
PDF 26 MB Posted
- Attached to
- Glennallen Field Office Flood Repairs
- Solicitation number
- 140L0626B0005
About this file
This is an architectural and engineering drawing set for the Glennallen Field Office Flood Damage Repair project in Glennallen, Alaska, prepared by Design Alaska and submitted to the Bureau of Land Management. The project scope encompasses repair and reconstruction of headquarters office facilities and utility infrastructure damaged during spring flooding in 2023, with primary work including building releveling, well house reconstruction, water and sewer system modifications, and electrical system upgrades to accommodate the new building elevations.
The construction documents specify compliance with 2021 International Building Code, 2021 International Mechanical Code, 2024 National Electrical Code, and 2021 International Existing Building Code. Key project elements include: demolition of existing floor structures within the well house while protecting the existing well casing; installation of new concrete floor slab with backfill; extension and modification of arctic pipe water service lines with electric heat trace to accommodate building elevation changes; reconstruction of waste piping systems with cast iron piping and no-hub couplings; reinforcement and adjustment of building foundation posts with welded steel extensions and threaded rod assemblies; installation of new electrical service disconnect and main distribution panel rated at 600 amps; relocation of lift station control panel and associated equipment above the flood elevation; and extension of electrical conduits and circuits throughout the site. The project also includes modifications to stairs, ramps, handrails, and guardrails to meet ADA accessibility standards following building releveling. The structural design utilizes light-framed wood shear walls as the seismic force-resisting system and specifies ASTM A572 Grade 50 structural steel for various connections and support structures. Construction is to be phased to maintain temporary operations and utilities for existing site users throughout the repair process.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1 View Name 1/8" = 1'-0"A101
Room name
GENERAL SYMBOLS
NAME
NUMBER
SHEET LOCATION
SCALE
TRUE NORTH
GRID LINE
ROOM NAME
ROOM NUMBER
PLAN NORTH
REVISION
SEE DISCIPLINES FOR SPECIFIC SYMBOLS
PROJECT TEAM
GOVERNMENT REPRESENTATIVE
BUREAU OF LAND MANAGEMENT
222 UNIVERSITY AVE.
FAIRBANKS, AK 99701
907 474-2207
DESIGNERS REPRESENTATIVE
DESIGN ALASKA
601 COLLEGE ROAD
FAIRBANKS, AK 99701
907 452-1241
VICINITY MAP
PROJECT LOCATION:
1865 GLENN HWY
GLENN HWY
SA
SH
A D
R
ALASKA MAP
PACIFIC OCEAN
ARCTIC OCEAN
BERING
SEA
KODIAK
ARCTIC CIRCLE
SEWARD
SITKA
JUNEAU
HAINES
WHITEHORSE YT
DAWSON YT
HAINES
JCT
HOMER
ANCHORAGE
EAGLE
CORDOVA
VALDEZ
GLENNALLEN
TOK
NORTH
POLE
FAIRBANKS
NENANA
TANANA CIRCLE
NOME
KOTZEBUE
UTQIAGVIK
(BARROW)
PRUDHOE BAY
U N
IT
ED
S
TA
TE
S
R U
SS
IA U
N
ITED
STATES
C
AN
AD
A
PROJECT
LOCATION
CODE INFORMATION
SCOPE OF WORK
REPAIR HEADQUARTERS OFFICE FACILITIES AND UTILITY
INFRASTRUCTURE DAMAGED THROUGH SPRING FLOODING THAT
OCCURRED IN 2023. INCLUDES RELEVELING HEADQUARTERS OFFICE
FACILITY.
GOVERNING CODES
INTERNATIONAL BUILDING CODE (IBC) 2021
INTERNATIONAL MECHANICAL CODE (IMC) 2021
NATIONAL ELECTRICAL CODE (NEC) 2024
INTERNATIONAL EXISTING BUILDING CODE (IEBC) 2021
AUTHORITY HAVING JURISDICTION
BUREAU OF LAND MANAGEMENT
CODE SUMMARY
OCCUPANCY TYPE : GROUP B
TYPE OF CONSTRUCTION: TYPE VB
BUILDING AREA: NO CHANGE
OCCUPANT LOAD: NO CHANGE
EGRESS REQUIREMENTS: NO CHANGE
BUILDING SPRINKLED: NO
IEBC WORK AREA REPAIRS
THE RECONSTRUCTION, REPLACEMENT OR RENEWAL OF ANY
EXISTING BUILDING FOR THE PURPOSE OF ITS MAINTENANCE OR TO
CORRECT DAMAGE.
U.S. DEPARTMENT OF THE INTERIOR
BUREAU OF LAND MANAGEMENT
NATIONAL SYSTEM OF PUBLIC LANDS
ISSUE DATE
COMM. NUMBER
DESIGNED BY
DRAWN BY
SCALE 0" 1"
Architects Engineers Surveyors 601 College Road Fairbanks AK 99701
907.452.1241 designalaska.comAECC511
NATIONAL SYSTEM OF PUBLIC LANDS
9/29/2025 3:48:45 PM
GENERAL
INFORMATION
G010
GFO FLOOD
DAMAGE REPAIR
902301
30 SEP 2025
GFO FLOOD DAMAGE REPAIR
GLENNALLEN, ALASKA
BUREAU OF LAND MANAGEMENT
GENERAL
G010 GENERAL INFORMATION
ARCHITECTURAL
A010 ARCHITECTURAL INFORMATION, EXTERIOR ASSEMBLIES, ROOM, AND MATERIAL SCHEDULE
A110 DEMOLITION PLAN - HEADQUARTERS OFFICE BUILDING
A210 RENOVATION PLAN - OVERALL - HEADQUARTERS OFFICE BUILDING
A510 VERTICAL CIRCULATION - DETAILS
STRUCTURAL
S010 GENERAL STRUCTURAL NOTES
S200 FOUNDATION PLAN - HEADQUARTERS OFFICE
MECHANICAL
M001 MECHANICAL ABBREVIATIONS, LEGENDS, AND SCHEDULES
M100 DEMOLITION PLANS AND DIAGRAMS
M200 SITE DOMESTIC WATER SYSTEM DIAGRAMS AND DETAILS
M201 LOG OFFICE MECHANICAL PLAN
M202 HEADQUARTERS OFFICE BUILDING MECHANICAL PLAN
ELECTRICAL
E001 LEGEND, SCHEDULES, AND NOTES
E111 SITE ELECTRICAL - DEMOLITION PLAN
E211 SITE ELECTRICAL - RENOVATION PLAN
E212 WELL HOUSE PLANS
E213 LOG OFFICE PLANS
E311 MDP DETAILS - DEMOLITION
E312 MDP DETAILS - RENOVATION
E313 LIFT STATION CONTROL PANEL DETAILS
E314 LIFT STATION EQUIPMENT H-FRAME DETAIL
E315 HEADQUARTERS OFFICE BUILDING - MISCELLANEOUS DETAILS
CIVIL
C110 EXISTING CONDITIONS
C210 SITE PLAN
C510 WATER PLAN AND PROFILE
C710 DETAILS
SHEET INDEX
T
T
LOG OFFICE
FFE = 1419.60'
ANNEX OFFICE
FFE = 1418.67'
WAREHOUSE
FFE = 1419.12'
MAINT. FFE = 1418.80
GAR. FFE = 1417.036
STORAGE
FFE = 1419.08'
STORAGE
HAZMAT
WELL HOUSE
FFE = 1417.11
BSMT = 1410.61
SEE NOTE 4 FOR WELL HOUSE WORK
GAS SHED
SHED
ABOVE GROUND
HEATING OIL TANK
ON BALLAST PAD
ANTENNA
LIFT STATION
141214
14271420
IN SERVICE,
UNDERGROUND
WATERLINE
HEADQUARTERS
OFFICE
BUILDING
FFE = 1420.66'
CONTRACTOR
STAGING AND
LAYDOWN AREA
REMOVE TEMPORARY, ABOVE
GROUND WATER SERVICE LINE
ABANDONED OR OUT OF
SERVICE UNDERGROUND
WATER LINES
FF=1418.57'
CACHE
9/29/2025 11:40 AM 902301 C110.DWG
902301
30 SEP 2025
COMM. NUMBER
ISSUE DATE
DESIGNED BY
DRAWN BY
1"0" SCALE
601 College Road Fairbanks AK 99701 907.452.1241
Architects SurveyorsEngineers
AECC511 designalaska.com
GFO FLOOD
DAMAGE REPAIR
U.S. DEPARTMENT OF THE INTERIOR
BUREAU OF LAND MANAGEMENT
NATIONAL SYSTEM OF PUBLIC LANDS
C110
CCD
CCD
EXISTING
CONDITIONS
EXISTING CONDITIONS AND DEMOLITION PLAN1
C110 SCALE: 1" = 20'
LEGEND
PRIMARY MONUMENT
REBAR W/ ALUMINUM CAP
SURVEY SPIKE
BORE HOLE
PROPERTY LINE
EASEMENT
EXISTING CONTOURS
ROOF OVERHANG
EDGE OF ASPHALT PAVEMENT
GRAVEL
CHAIN-LINK FENCE
SIGN
CULVERT
SWALE
DIRECTION OF WATER FLOW
WATER VALVE
HYDRANT
UNDERGROUND WATER LINE
ABOVE GROUND FUEL LINE
UNDERGROUND FUEL LINE
SEWER CLEANOUT
UNDERGROUND SEWER LINE
UNDERGROUND FORCE MAIN
UTILITY POLE
GUY ANCHOR
TRANSFORMER
JUNCTION BOX
HEAD BOLT OUTLET
LIGHT POLE
TELEPHONE PEDESTAL
ELECTRICAL MANHOLE
COMMUNICATIONS MANHOLE
OVERHEAD POWER LINE
UNDERGROUND POWER LINE
UNDERGROUND COMMUNICATION LINE
TREE LINE
DECIDUOUS TREE
CONIFEROUS TREE
NOTES:
1. TOPOGRAPHIC INFORMATION DEPICTED HERE IS PER A SITE
SURVEY PERFORMED IN 2023
2. EXISTING UNDERGROUND UTILITIES DEPICTED HERE ARE BASED
UPON FIELD LOCATES OF PRIVATE UTILITIES ON THE PROJECT
SITE.
3. CONTRACTOR IS RESPONSIBLE FOR LOCATING AND PROTECTING
ALL EXISTING UNDERGROUND UTILITIES WITHIN THE PROJECT
AREA THROUGHOUT THE PROJECT.
4. DEMOLISH EXISTING WOOD SUBFLOOR, AND FLOOR STRUCTURE
WITHIN WELL HOUSE. PROTECT THE EXISTING WELL CASING.
REGISTERED PROFESSIONA L ENGINEER
D E S I G N A
L A
S K
A
Charles Cutter Degerlund
No. CE124811
30 SEP 2025
T
LOG OFFICE
ANNEX OFFICE
HEADQUARTERS OFFICE BUILDING
WAREHOUSE
MAINT./GAR.
STORAGE
STORAGE
HAZMAT
GAS SHED
SHED
ANTENNA
LIFT STATION
SEE NOTE 3
141214
14271420
NEW WATER SERVICE
COMBINED SUPPLY AND
RETURN LINES
CONNECT TO (E)
WELL HOUSE
SEE NOTE 3
C710
CACHE
C710
9/29/2025 3:27 PM 902301 C210.DWG
902301
30 SEP 2025
COMM. NUMBER
ISSUE DATE
DESIGNED BY
DRAWN BY
1"0" SCALE
601 College Road Fairbanks AK 99701 907.452.1241
Architects SurveyorsEngineers
AECC511 designalaska.com
GFO FLOOD
DAMAGE REPAIR
U.S. DEPARTMENT OF THE INTERIOR
BUREAU OF LAND MANAGEMENT
NATIONAL SYSTEM OF PUBLIC LANDS
C210
CCD
CCD
SITE PLAN
SITE PLAN1
C210 SCALE: 1" = 20'
NOTES:
1. EXISTING UTILITIES ARE SHOWN AS FADED LINE TYPES
2. INDEPENDENT WATER SERVICE LINES AND SHARED WATER
CIRCULATION LINES WITHIN THE SAME INSULATED CARRIER PIPE
ARE SHOWN HERE DIAGRAMMATICALLY AS A SINGLE LINE.
3. NEW WORK WITHIN THE WELL HOUSE WILL CONSIST OF REMOVAL
OF THE EXISTING FLOOR AND FLOOR STRUCTURE, BACK FILL OF
THE EXISTING CONFINED SPACE BELOW THE FLOOR STRUCTURE,
AND PLACEMENT OF CONCRETE FLOOR SLAB.
4. REMOVE AND REINSTALL OR TEMPORARILY SUPPORT
MECHANICAL EQUIPMENT WITHIN THE WELL HOUSE THAT IS
SUPPORTED BY THE EXISTING FLOOR.
5. EQUIPMENT TO REMAIN THAT IS PRESENTLY WITHIN THE
CONFINED SPACE OF THE WELL HOUSE SHALL BE REMOVED AND
RELOCATED TO A LOCATION ABOVE THE NEW FINISHED FLOOR.
6. ADJUST FINISH GRADE AT STAIRS AND RAMPS AS NEEDED TO
PROVIDE LEVEL LANDINGS AFTER BUILDING RE LEVELING.
LONGITUDINAL SLOPE, IN THE DIRECTION OF TRAVEL SHALL NOT
EXCEED 5%. TRANSVERSE SLOPE PERPENDICULAR TO THE
DIRECTION OF TRAVEL SHALL NOT EXCEED 2%.
REGISTERED PROFESSIONA L ENGINEER
D E S I G N A
L A
S K
A
Charles Cutter Degerlund
LOG OFFICE
ANNEX OFFICE
HEADQUARTERS OFFICE
BUILDING
WATER SERVICE
LATERALS AND
SHARED RETURN LINE
WITHIN A SINGLE
CARRIER PIPE
EXISTING
UNDERGROUND
WATERLINES
BP: 0+00.00
PI: 1+54.70
E P
: 1 +6
9.
1+70
0+00
0+50
1+00
1+50
C710
CONNECT TO BUILDING
PLUMBING PER
MECHANICAL
-0+15 0+00 0+50 1+00 1+50 2+00 2+50
WATERLINE,
DEPTH
UNKNOWN
ACTIVE
SEWER,
DEPTH
UNKNOWN
2" HDPE ARCTIC PIPE
EXISTING GRADE
EXISTING
ELECTRICAL
LINE
EXISTING
COMM
LINE
EXISTING
COMM
LINE
EXISTING
COMM
LINE EXISTING
ELECTRICAL
LINE
EXISTING
ELECTRICAL
LINE
EXISTING
COMM
LINE
EXISTING
ELECTRICAL
LINE
WELL HOUSE
S
TA
. 0 +0
0.
FA
C
E O
F W
E
LL
H O
U S
E
DIVERSION POINT
OF LOG OFFICE
WATERLINE
CONNECT TO
EXISTING WATER
SUPPLY, PER
MECHANICAL
CONNECT TO EXISTING
BUILDING WATER
SERVICE. SEE
MECHANICAL.
SUSPEND FROM SUB-FLOOR
STRUCTURE PER MECHANICAL
EXTEND WATERLINE BENEATH
EXISTING FOUNDATION FOOTER
9/29/2025 3:27 PM 902301 C510 - WATERLINE PLAN AND PROFILE.DWG
902301
30 SEP 2025
COMM. NUMBER
ISSUE DATE
DESIGNED BY
DRAWN BY
1"0" SCALE
601 College Road Fairbanks AK 99701 907.452.1241
Architects SurveyorsEngineers
AECC511 designalaska.com
GFO FLOOD
DAMAGE REPAIR
U.S. DEPARTMENT OF THE INTERIOR
BUREAU OF LAND MANAGEMENT
NATIONAL SYSTEM OF PUBLIC LANDS
C510
CCD
CCD
WATER PLAN AND
PROFILE
WATER LINE PROFILE2
C510 SCALE: HORZ. 1"=20' VERT. 1" = 2'
WATER LINE PLAN1
C510 SCALE: 1" = 20'
LOG OFFICE
1. WATER SERVICE PIPES SHALL HAVE
A LEVEL OR POSITIVE GRADE FROM
THE WATER MAIN TO THE BUILDING
(NO HUMPS OR DIPS) TO PREVENT
AIR TRAPS.
GENERAL NOTES:
REGISTERED PROFESSIONA L ENGINEER
D E S I G N A
L A
S K
A
Charles Cutter Degerlund
9/29/2025 12:05 PM 902301 C710.DWG
902301
30 SEP 2025
COMM. NUMBER
ISSUE DATE
DESIGNED BY
DRAWN BY
1"0" SCALE
601 College Road Fairbanks AK 99701 907.452.1241
Architects SurveyorsEngineers
AECC511 designalaska.com
GFO FLOOD
DAMAGE REPAIR
U.S. DEPARTMENT OF THE INTERIOR
BUREAU OF LAND MANAGEMENT
NATIONAL SYSTEM OF PUBLIC LANDS
C710
CBP
CCD
DETAILS
ARCTIC PIPE SECTIONS1
C710 NO SCALE
4" HDPE ARCTIC PIPE
INSULATION
HDPE OUTER PIPE
DCW SUPPLY
SECTION A-A
DCW RETURN
HEAT TRACE CHANNEL
ELEC HEATING CABLE
PER ELECTRICAL
WELL HOUSE SUB FLOOR SECTION2
C710 NO SCALE
4"
CONCRETE
SLAB
STRUCTURAL FILL OR
FLOWABLE FILL
PROTECT EXISTING INTERIOR
WALL, PLYWOOD TO REMAIN.
(E) EXTERIOR LOGS (TYP.)
6x6 W2.1xW2.1 WWF
PROTECT WELL CASING DURING
BACK FILL AND FLOOR SLAB CONSTRUCTION
(E) WELL HOUSE FOUNDATION
SEE MECHANICAL SHEETS
FOR PLUMBING CHANGES
WITHIN WELL HOUSE
ISOLATION JOINT
MATERIAL (TYP.)
REGISTERED PROFESSIONA L ENGINEER
D E S I G N A
L A
S K
A
Charles Cutter Degerlund
No. CE124811
30 SEP 2025
FINISH FLOOR ELEVATION
SHALL MATCH TOP OF
EXISTING CONCRETE
FOUNDATION ELEVATION AT
ENTRY DOOR THRESHOLD.
WATERLINE TO LOG OFFICE
EXISTING GRADE
CONCRETE
MATERIAL LEGEND
RIGID MINERAL FIBER
EXISTING
CONSTRUCTION
NO ARCHITECTURAL WORK
THIS AREA
ARCHITECTURAL SYMBOL
LEGEND
150 SF
Room Name
DETAIL NAME
DETAIL NUMBER
SHEET LOCATION
DETAIL SCALE
TRUE NORTH
GRID LINE
ROOM NAME
ROOM NUMBER
PLAN NORTH
DETAIL NUMBER
SHEET LOCATION
SIMILAR
REVISION
SPOT ELEVATION
SEE OTHER DISCIPLINES FOR ADDITIONAL SYMBOLS
KEYED NOTE
DOOR TAG
A100
A100
EXTERIOR ELEVATION
SHEET LOCATION
DETAIL NUMBER
INTERIOR ELEVATION
SHEET LOCATION
DETAIL NUMBER
DETAIL NUMBER 4
A
BUILDING SECTION
DETAIL NUMBER
SHEET LOCATION
SIMILAR
WALL SECTION
WINDOW TYPE
ROOM AREA
1/8" = 1'-0" View Name
1/4" / 1'-0"SPOT SLOPE
101ROOM NUMBER
A101
SIM
A101
SIM
101A
1. SEE OTHER DISCIPLINES FOR ADDITIONAL ABBREVIATIONS.
2. SEE ASSEMBLY TYPES FOR HYPHENATED ASSEMBLY TAGS
(I.E. C-A1, W01-3A, AND WX-3A).
3. SEE MATERIAL SCHEDULE FOR HYPHENATED MATERIAL TAGS
(I.E. ACT-1, CPT-1, AND RB-1).
4. SEE ROOM AND DOOR SCHEDULE FOR SPECIFIC RELEVANT
ABBREVIATIONS.
5. SOME ABBREVIATIONS LISTED BELOW MAY NOT BE USED IN
THIS PROJECT.
(E) EXISTING
FV FIELD VERIFY
GYP GYPSUM BOARD
IBC INTERNATIONAL BUILDING CODE
MAX MAXIMUM
MFR MANUFACTURER
MFSD MANUFACTURER'S STANDARD
MIN MINIMUM
NIC NOT IN CONTRACT
OC ON CENTER
PLY PLYWOOD
Reff EFFECTIVE R-VALUE
SPEC SPECIFICATION
TBD TO BE DETERMINED
TYP TYPICAL
UL UNDERWRITERS LABORATORY
VTR VENT THROUGH ROOF
ARCHITECTURAL STANDARD
ABBREVIATIONS
FX-A1
FLOOR ASSEMBLY CATEGORY - FUNCTION
FLOOR ASSEMBLY MODIFIER
FLOOR ASSEMBLY CATEGORY - FUNCTION
FLOORS ON GRADE OR THOSE COMPRISING THE EXTERIOR
ENVELOPE OF THE BUILDING ARE CONSIDERED EXTERIOR.
PROJECTS MAY NOT INCLUDE ALL ASSEMBLY CATEGORIES.
FX FLOOR - EXTERIOR
FLOOR BUILDING ENVELOPE DESIGNATION
A SLAB ON GRADE
B RAISED FLOOR
C OTHER
FLOOR ASSEMBLY MODIFIER
NUMBERS REPRESENT DESCRIPTIONS OF ASSEMBLY
TYPES. THE BELOW ARE COMMONLY USED EXAMPLES.
SEE ASSEMBLY TYPES FOR ADDITIONAL MODIFIERS.
1 TYPICAL
EXTERIOR ASSEMBLY TAG
LEGEND - FLOOR
FLOOR BUILDING ENVELOPE DESIGNATION
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
M.
N.
O.
P.
Q.
R.
S.
ARCHITECTURAL NOTES DESCRIBE WORK COMPRISING
THE ENTIRE ARCHITECTURAL DISCIPLINE.
SHEET NOTES DESCRIBE WORK COMPRISING THE ENTIRE
SHEET ON WHICH THE NOTES APPEAR INCLUDING
SHEETS ON WHICH THE NOTES ARE REFERENCED.
CONSTRUCTION DOCUMENTS ARE PREPARED FOR THE
PURPOSES OF COMMUNICATING DESIGN INTENT.
DRAWINGS ARE GRAPHIC REPRESENTATIONS CONVEYING
THE QUANTITATIVE EXTENT AND RELATIONSHIP BETWEEN
PROJECT ELEMENTS.
SPECIFICATIONS ARE WRITTEN REPRESENTATIONS
CONVEYING THE QUALITATIVE REQUIREMENTS OF
PROJECT ELEMENTS.
CONTRACTOR IS RESPONSIBLE FOR PROVIDING A
COMPLETE AND FINISHED PRODUCT FULFILLING THE
INTENT OF THE CONSTRUCTION DOCUMENTS.
THE TERM 'NEW' MAY BE USED TO DISTINGUISH NEW
FROM EXISTING IN SOME INSTANCES. OMISSION OF THE
TERM 'NEW' IS NOT NECESSARILY AN INDICATION THAT
THE ELEMENT IS EXISTING.
THE TERM 'ALL' MAY BE USED TO CLARIFY SCOPE.
OMISSION OF THE TERM 'ALL' IS NOT NECESSARILY AN
INDICATION THAT THE SCOPE IS LIMITED.
SEE GENERAL CODE INFORMATION AND CODE PLAN.
COORDINATE ARCHITECTURAL WORK WITH CIVIL,
STRUCTURAL, MECHANICAL, ELECTRICAL, AND OTHER
DISCIPLINES.
SEE STRUCTURAL FOR SPECIFIC INFORMATION
REGARDING LOAD BEARING MEMBERS, MECHANICAL
FASTENERS, MASTIC ADHESION, AND STRUCTURE.
PATCH, REPAIR, AND REFINISH EXISTING SURFACES TO
REMAIN, AFFECTED BY WORK.
DIMENSIONS AT EXISTING CONSTRUCTION ARE
MEASURED FROM FACE OF EXISTING FINISH UNLESS
NOTED OTHERWISE.
DIMENSIONS AT NEW CONSTRUCTION ARE MEASURED
FROM FACE OF FRAMING UNLESS NOTED OTHERWISE.
CONFIRM DIMENSIONS INDICATED WITH 'FIELD VERIFY'
AND/ OR 'FV' PRIOR TO WORK.
DIMENSIONS INDICATED AS 'CLEAR' REQUIRE MINIMUM
CLEARANCE MEASURED TO FINISHED FACES, UNLESS
NOTED OTHERWISE.
DIMENSIONS INDICATED WITH '+/-' BRING THE
CONTRACTOR'S ATTENTION TO AREAS WITH FLEXIBILITY
GREATER THAN ADJACENT AREAS NOT OTHERWISE
INDICATED.
CONFIRM MANUFACTURERS' INSTALLATION
INSTRUCTIONS CONFORM TO SPECIFIED TOLERANCES.
SEE DETAILS FOR DIMENSION AND LEVEL REFERENCE
POINTS.
ARCHITECTURAL NOTES
A010
THIS REFERENCE INDICATES LOCATION OF INFORMATION IN A
TYPICAL PROJECT. THIS PROJECT MAY VARY FROM THE
REPRESENTATION BELOW. SEE THE SHEET INDEX FOR SPECIFIC
SHEET SEQUENCE.
A0 SHEETS INFORMATION, ASSEMBLIES, SCHEDULES
A1 SHEETS PHASING, EXISTING, DEMOLITION
A2 SHEETS FLOOR AND ROOF PLANS
A3 SHEETS EXTERIOR ELEVATIONS (NOT USED)
A4 SHEETS SECTIONS (NOT USED)
A5 SHEETS VERTICAL CIRCULATION
A6 SHEETS FIRE RESISTIVE AND EXTERIOR DETAILS (NOT USED)
A7 SHEETS INTERIOR DESIGN PLANS (NOT USED)
A8 SHEETS INTERIOR ELEVATIONS (NOT USED)
A9 SHEETS INTERIOR DESIGN DETAILS (NOT USED)
THE TWO CHARACTER ALPHANUMERIC DESIGNATIONS REPRESENT
ALL SHEETS IN THE SERIES. FOR EXAMPLE, 'A1 SHEETS' DESCRIBES
A100 THROUGH A199.
ARCHITECTURAL SHEET
SEQUENCE
1'-0"
1'-0"
GRID
1'-0"
CLEAR
8 3/8" 1'-0"
GRID TO GRID
GRID TO WALL
NEW WALL STUD TO
NEW WALL STUD
NEW WALL STUD TO
EXISTING WALL FINISH
EXISTING WALL FINISH TO
EXISTING WALL FINISH.
FIELD VERIFY.
REQUIRED CLEARANCE TO
FINISHED FACES, MINIMUM
UNLESS NOTED OTHERWISE
FIELD VERIFY EXISTING
CONDITIONS
FX-B1 FLOOR EXTERIOR - RAISED - HEADQUARTERS OFFICE BUILDING
EXTERIOR
INTERIOR FINISH PER ROOM SCHEDULE
R-30 MINERAL WOOL BATT INSULATION
(E) VAPOR BARRIER
(E) 2" CONCRETE
(E) 1/2" PLYWOOD
(E) 14" WOOD I JOIST
STAPLE CONTINUOUS CHICKEN WIRE
BETWEEN JOIST WEBS TO HOLD
INSULATION UP. MAINTAIN INSULATION
FLUSH WITH UNDERSIDE OF FLOORING
SUBSTRATE.
A.
B.
C.
A.
1 - TYPICAL
ASSEMBLIES ARE DIAGRAMS ONLY, DO NOT SCALE.
ASSEMBLIES DESCRIBE MATERIALS AND THEIR
RELATIONSHIP WITHIN A GIVEN CEILING, FLOOR, ROOF, OR
WALL. PENETRATIONS, JOINTS, FINISHES, AND
INTERSECTIONS BETWEEN ASSEMBLIES ARE NOT SHOWN.
SEE FLOOR PLANS FOR ASSEMBLY LOCATIONS.
2 - BUILDING ENVELOPE
SEE SPEC DIVISION 07 AND RELATED SPEC SECTIONS.
EXTERIOR ASSEMBLY NOTES
EXISTING CONSTRUCTION
ASSEMBLY TYPE LEGEND
ROOM SCHEDULE NOTES
A.
B.
C.
D.
SEE MATERIAL SCHEDULE FOR FINISH INFORMATION.
SEE ASSEMBLY TYPES FOR FINISH SUBSTRATES.
PROVIDE FINISHES TO FULL HEIGHT OF WALL UNLESS
NOTED OTHERWISE.
PATCH AND REPAIR EXISTING SURFACES DAMAGED BY
WORK. MATCH ADJACENT FINISHES. PAINT BEYOND
DAMAGED AREA EXTENDING FROM CORNER TO CORNER
OF AFFECTED SURFACES.
1. NOT USED
ROOM SCHEDULE REMARKS
MATERIAL SCHEDULE NOTES
A. THE MATERIAL SCHEDULE PROVIDES A BASIS OF DESIGN.
SEE SPECIFICATIONS FOR PRODUCT INFORMATION,
PERFORMANCE CRITERIA, AND ACCEPTABLE
ALTERNATIVE MANUFACTURERS.
1.
MISCELLANEOUS
NOT USED
MATERIAL SCHEDULE REMARKS
A. ARCHITECTURAL PAINTS AND COATINGS APPLIED TO
INTERIOR ELEMENTS MUST NOT EXCEED THE VOC
CONTENT LIMITS ESTABLISHED IN GREEN SEAL STANDARD
GS-11 AS OF 20 MAY 1993.
LOW EMITTING
LE-
U.S. DEPARTMENT OF THE INTERIOR
BUREAU OF LAND MANAGEMENT
NATIONAL SYSTEM OF PUBLIC LANDS
ISSUE DATE
COMM. NUMBER
DESIGNED BY
DRAWN BY
SCALE 0" 1"
Architects Engineers Surveyors 601 College Road Fairbanks AK 99701
907.452.1241 designalaska.comAECC511
NATIONAL SYSTEM OF PUBLIC LANDS
9/29/2025 4:00:47 PM
JB
KCV
ARCHITECTURAL
INFORMATION,
EXTERIOR
ASSEMBLIES,
ROOM, AND
MATERIAL
SCHEDULE
A010
GFO FLOOD
DAMAGE REPAIR
902301
30 SEP 2025
1 1/2" = 1'-0"A010
1 INTERIOR DETAIL - TYPICAL - DIMENSION REFERENCE POINT CONVENTIONS
HEADQUARTERS OFFICE BUILDING ROOM SCHEDULE
ROOM FLOOR WALL CEILING ROOM
NUMBER NAME FINISH BASE FINISH
ASSEMBLY
TYPE FINISH HEIGHT REMARKS NUMBER
100 VESTIBULE EXIST EXIST PNT-50 EXIST PNT-80 EXIST 100
101 PUBLIC / MAPS EXIST EXIST PNT-50 EXIST PNT-80 EXIST 101
102 BREAK ROOM EXIST EXIST PNT-50 EXIST PNT-80 EXIST 102
103 CONFERENCE ROOM EXIST EXIST PNT-50 EXIST PNT-80 EXIST 103
104 COMPUTER / TELE ROOM EXIST EXIST PNT-50 EXIST PNT-80 EXIST 104
105 MECH ROOM EXIST EXIST PNT-50 EXIST PNT-80 EXIST 105
106 MEN'S RESTROOM EXIST EXIST PNT-50 EXIST PNT-80 EXIST 106
107 WOMEN'S RESTROOM EXIST EXIST PNT-50 EXIST PNT-80 EXIST 107
108 JANITOR'S CLOSET EXIST EXIST PNT-50 EXIST PNT-80 EXIST 108
109 MAIL ROOM EXIST EXIST PNT-50 EXIST PNT-80 EXIST 109
110 OFFICE EXIST EXIST PNT-50 EXIST PNT-80 EXIST 110
111 OFFICE EXIST EXIST PNT-50 EXIST PNT-80 EXIST 111
112 OFFICE EXIST EXIST PNT-50 EXIST PNT-80 EXIST 112
113 MANAGER'S OFFICE EXIST EXIST PNT-50 EXIST PNT-80 EXIST 113
114 CORRIDOR EXIST EXIST PNT-50 EXIST PNT-80 EXIST 114
115 CORRIDOR EXIST EXIST PNT-50 EXIST PNT-80 EXIST 115
116 OFFICE EXIST EXIST PNT-50 EXIST PNT-80 EXIST 116
118 OFFICE EXIST EXIST PNT-50 EXIST PNT-80 EXIST 118
119 OFFICE EXIST EXIST PNT-50 EXIST PNT-80 EXIST 119
120 OFFICE EXIST EXIST PNT-50 EXIST PNT-80 EXIST 120
121 OFFICE EXIST EXIST PNT-50 EXIST PNT-80 EXIST 121
MATERIAL SCHEDULE
SPEC TYPE DESCRIPTION LOCATION
BASIS OF DESIGN REMARKS
TYPEMANUFACTURER MODEL COLOR
LOW
EMITTING MISCELLANEOUS
09 90 00 - FINISHES - PAINTING AND COATING
09 91 23 PNT-50 INTERIOR PAINT - WALL PER ROOM SCHEDULE SHERWIN WILLIAMS PROMAR 200 INTERIOR LATEX MATCH EXISTING LE-A PNT-50 09 91 23 PNT-80 INTERIOR PAINT - CEILING PER ROOM SCHEDULE SHERWIN WILLIAMS PROMAR 200 INTERIOR LATEX MATCH EXISTING LE-A PNT-80
AKAF AL
TS
TA E O
49 TH
S
JAMES D. BARTLETT
No. A10413
D E S I G N
A L A
S K A
REG ISTERED PROFESSIONAL ARCHITE
CT30 SEP 2025
A.
B.
C.
CONSTRUCTION DOCUMENTS DESCRIBE TYPICAL
DEMOLITION WORK. CONTRACTOR IS RESPONSIBLE FOR
PROVIDING SPECIFIC DEMOLITION WORK REQUIRED TO
ACCOMMODATE NEW WORK.
SEE CIVIL, STRUCTURAL, MECHANICAL, AND ELECTRICAL
DOCUMENTS FOR ADDITIONAL DEMOLITION REQUIREMENTS.
EXISTING STRUCTURAL SYSTEMS INCLUDING COLUMNS,
BEAMS, AND STRUCTURAL WALLS TO REMAIN UNLESS
OTHERWISE INDICATED IN STRUCTURAL DOCUMENTS.
DEMOLITION NOTES
DEMOLITION LEGEND
EXISTING CONSTRUCTION
EXISTING WALL AND DOOR TO REMAIN
EXISTING WALL AND WINDOW TO REMAIN
KEYNOTES
ONCE LEVELING IS COMPLETE, PATCH, REPAIR, REPLACE,
AND PREPARE AREAS OF SETTLEMENT DAMAGE. THIS
INCLUDES BUT NOT LIMITED TO, DOOR OPENINGS,
WINDOW OPENINGS, GYPSUM LID, CORRIDOR WALLS.
ONCE LEVELING IS COMPLETE, INSPECT WINDOW AND
REPAIR ASSEMBLY TO PROVIDE SEALED ASSEMBLY.
WINDOW TO BE ADJUSTED FOR FULL OPERABILITY.
MODIFY STAIRS, RAMPS, DECKS, AND RELATED ITEMS AS
REQUIRED TO ACCOMMODATE BUILDING LEVELING.
REMOVE BATT INSULATION AND VAPOR BARRIER AT
UNDERSIDE OF FLOOR ASSEMBLY.
PREPARE SURFACES PER ROOM SCHEDULE.
DEMOLISH EXISTING STAIR AND HANDRAILS. LANDING TO
REMAIN AND BE MODIFIED AS NEEDED TO
ACCOMMODATE NEW WORK.
CONFERENCE
ROOM
BREAK
ROOM
PUBLIC /
MAPS
VESTIBULE
CORRIDOR
CORRIDOR
WOMEN'S
RESTROOM
MEN'S
RESTROOM
JANITOR'S
CLOSET
MAIL ROOM
109 OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
MANAGER'S
OFFICE
COMPUTER /
TELE ROOM
MECH ROOM
EXERC.
OFFICE
OFFICE
WINDOW; TYPICAL
CORRIDOR; TYPICAL DOOR; TYPICAL
STAIR AT CORRIDOR 114
STAIRS AT CORRIDOR 115
STAINLESS STEEL HANDRAIL
PRESSURE TREATED GUARDRAIL
DN
DN
D N
DN
DN
FUEL TANK PER
MECHANICAL
63 U.S. DEPARTMENT OF THE INTERIOR
BUREAU OF LAND MANAGEMENT
NATIONAL SYSTEM OF PUBLIC LANDS
ISSUE DATE
COMM. NUMBER
DESIGNED BY
DRAWN BY
SCALE 0" 1"
Architects Engineers Surveyors 601 College Road Fairbanks AK 99701
907.452.1241 designalaska.comAECC511
NATIONAL SYSTEM OF PUBLIC LANDS
9/29/2025 4:00:50 PM
JB
KCV
DEMOLITION PLAN
- HEADQUARTERS
OFFICE BUILDING
A110
GFO FLOOD
DAMAGE REPAIR
902301
30 SEP 2025
HEADQUARTERS OFFICE BUILDING
ANNEX OFFICE
LOG OFFICEWELL HOUSE
KEYPLAN
3/16" = 1'-0"A110
1 DEMOLITION PLAN - HEADQUARTERS OFFICE BUILDING - 1ST FLOOR - OVERALL
AKAF AL
TS
TA E O
49 TH
S
JAMES D. BARTLETT
No. A10413
D E S I G N
A L A
S K A
ARCHITECTURAL PLAN NOTES
A.
B.
C.
D.
SEE ARCHITECTURAL INFORMATION SHEETS FOR
ABBREVIATIONS, LEGENDS, SHEET SEQUENCE, AND
GENERAL NOTES FOR ARCHITECTURAL WORK.
SEE ARCHITECTURAL INFORMATION SHEETS FOR
ASSEMBLY TYPES.
ARCHITECTURAL OVERALL PLANS SHOW SPATIAL
RELATIONSHIPS FOR THE BUILDING AS A WHOLE.
CONSTRUCTION COMPONENTS MAY BE SIMPLIFIED OR
OMITTED FOR CLARITY.
SEE DETAIL FOR
DIMENSION REFERENCE
POINT CONVENTIONS.
A010
ARCHITECTURAL PLAN LEGEND
NO ARCHITECTURAL WORK THIS AREA
EXISTING WALL AND EXISTING DOOR
EXISTING WORK TO REMAIN
KEYNOTES
PROVIDE INSULATION PER FLOOR ASSEMBLY FX-B1. 1
MODIFY / EXTEND EXISTING HAND RAILS / GUARDRAILS /
STAIRS AS NEEDED TO ACCOMMODATE NEW WORK.
CONFERENCE
ROOM
BREAK
ROOM
PUBLIC /
MAPS
EXERC.
COMPUTER /
TELE ROOM
MECH ROOM
CORRIDOR
JANITOR'S
CLOSET
MEN'S
RESTROOM
WOMEN'S
RESTROOM
MAIL ROOM
109 OFFICE
OFFICE
OFFICE
OFFICE
CORRIDOR
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
MANAGER'S
OFFICE
113VESTIBULE
DN
DN
.1
ROOF LINE ABOVE
DN
CANOPY
ABOVE
CANOPY
ABOVE
FUEL TANK PER
MECHANICAL
GRAVEL LANDING
PER CIVIL
DN
DN
FV
30'-0"
FV
39'-11 1/2"
FV30
'-0
FV
'-1
/8
CANOPY
ABOVE
EXISTING
6'-2 3/4"
NEW
6'-5"
8 RISERS @ 6.5" = 4'-4"
7 TREADS @ 11" = 6'-5"
A510
U.S. DEPARTMENT OF THE INTERIOR
BUREAU OF LAND MANAGEMENT
NATIONAL SYSTEM OF PUBLIC LANDS
ISSUE DATE
COMM. NUMBER
DESIGNED BY
DRAWN BY
SCALE 0" 1"
Architects Engineers Surveyors 601 College Road Fairbanks AK 99701
907.452.1241 designalaska.comAECC511
NATIONAL SYSTEM OF PUBLIC LANDS
9/29/2025 4:00:51 PM
JB
KCV
RENOVATION
PLAN - OVERALL -
HEADQUARTERS
OFFICE BUILDING
A210
GFO FLOOD
DAMAGE REPAIR
902301
30 SEP 2025
HEADQUARTERS OFFICE BUILDING
ANNEX OFFICE
LOG OFFICEWELL HOUSE
KEYPLAN
3/16" = 1'-0"A210
1 RENOVATION PLAN - HEADQUARTERS OFFICE BUILDING - 1ST FLOOR - OVERALL
AKAF AL
TS
TA E O
49 TH
S
JAMES D. BARTLETT
No. A10413
D E S I G N
A L A
S K A
VERTICAL CIRCULATION NOTES
A. SEE ARCHITECTURAL PLANS FOR ADDITIONAL INFORMATION.
FLIGHT SHALL
NOT HAVE A
VERTICAL RISE
GREATER THAN
12'-0" BETWEEN
FLOOR LEVELS
OR LANDINGS.
STAIR WIDTH
SHALL NOT BE
LESS THAN 44".
SEE IBC 2021
SECTION 1011.2
FOR EXCEPTIONS
STAIRWAY HEADROOM
MUST BE NO LESS
THAN 80" AT ANY
POINT.
THE TOLERANCE
BETWEEN THE LARGEST
AND SMALLEST RISER
HEIGHT OR BETWEEN
THE LARGEST AND
SMALLEST TREAD DEPTH
SHALL NOT EXCEED 3/8"
THE WIDTH OF
LANDINGS
SHALL NOT BE
LESS THAN
THE WIDTH OF
STAIRWAYS
SERVED.
VE
R
TI
C
AL
R
IS
E
HORIZONTAL RUN LANDINGLANDING
W
AL
KI
N
G S
U R
FA
C
E
LA
N D
IN
G
W
ID
TH
DOWN
W
AL
KI
N
G S
U R
FA
C
E
ST
AI
R
W
AY
W
ID
TH
UP
SECTION
PLAN
R
IS
ER
TREAD
H
EA
D R
O O
M
SEE DETAIL FOR
HANDRAIL
SEE DETAIL FOR
GUARDRAIL
A510
RISER/ TREAD/ NOSING
SHOWN DIAGRAMMATICALLY
A510
" M
IN
IM
U M
EQ
EQ
EQ
EQ
EQ
EQ +/-
FROM A HEIGHT OF 36" TO 42", GUARDS
SHALL NOT HAVE OPENINGS WHICH
ALLOW PASSAGE OF A SPHERE
REQUIRED GUARDS SHALL NOT HAVE
OPENINGS WHICH ALLOW PASSAGE OF A
SPHERE 4" IN DIAMETER FROM THE WALKING
SURFACE TO THE REQUIRED GUARD HEIGHT.
THE TRIANGULAR OPENINGS AT THE OPEN
SIDES OF A STAIR FORMED BY THE RISER,
TREAD, AND BOTTOM RAIL, SHALL NOT ALLOW
PASSAGE OF A SPHERE 6" IN DIAMETER.
SEE DETAIL
FOR
HANDRAIL
4 3/8" IN DIAMETER.
TREAD (WALKING SURFACE)
RISER
SEE PLANS FOR ACTUAL
STAIR LAYOUTS
LANDING (WALKING SURFACE)
A510
1 1/2" DIAMETER HANDRAIL WITH 1
1/2" CLEARANCE FROM WALL AND 1
1/2" CLEARANCE FROM HORIZONTAL
PROJECTIONS BELOW RAIL
EXTEND HANDRAIL HORIZONTALLY 1'-0"
BEYOND TOP NOSING FOR RETURN TO
LANDING SURFACE, GUARD, OR WALL
EQ EQ
" T
O
8"
EXTEND HANDRAIL ALONG
SLOPE ONE TREAD DISTANCE
HORIZONTALLY BEYOND
BOTTOM NOSING FOR RETURN
TO LANDING SURFACE,
GUARD, OR WALL
SEE DETAIL
FOR
GUARDRAIL
SEE PLANS FOR ACTUAL
STAIR LAYOUTS
TREAD (WALKING SURFACE)
RISER
LANDING (WALKING SURFACE)
1'-0"
1' -0
1' -0
A510
U.S. DEPARTMENT OF THE INTERIOR
BUREAU OF LAND MANAGEMENT
NATIONAL SYSTEM OF PUBLIC LANDS
ISSUE DATE
COMM. NUMBER
DESIGNED BY
DRAWN BY
SCALE 0" 1"
Architects Engineers Surveyors 601 College Road Fairbanks AK 99701
907.452.1241 designalaska.comAECC511
NATIONAL SYSTEM OF PUBLIC LANDS
9/29/2025 4:00:51 PM
JB
KCV
VERTICAL
CIRCULATION -
DETAILS
A510
GFO FLOOD
DAMAGE REPAIR
902301
30 SEP 2025
1/2" = 1'-0"A510
1 VERTICAL CIRCULATION DIAGRAM - STAIR PER IBC 2021 SECT 1011
3/4" = 1'-0"A510
VERTICAL CIRCULATION DIAGRAM - GUARDRAIL PER IBC
2021 SECT 1015 (RAMP SIMILAR)
3/4" = 1'-0"A510
VERTICAL CIRCULATION DIAGRAM - HANDRAIL PER ANSI
A117.1 (RAMP SIMILAR)
AKAF AL
TS
TA E O
49 TH
S
JAMES D. BARTLETT
No. A10413
D E S I G N
A L A
S K A
GENERAL STRUCTURAL NOTES
A. DESIGN CRITERIA
1. BUILDING CODE........................................................................................ 2021 IBC (INTERNATIONAL BUILDING CODE)
GOVERNING JURISDICTION.................................................................... BUREAU OF LAND MANAGEMENT
2. DEAD LOADS
FLOOR DEAD LOAD.................................................................... 20 PSF ROOF DEAD LOAD...................................................................... 25 PSF
3. LIVE LOADS
FLOOR LIVE LOAD (HQ OFFICE) .............................................. 100 PSF (LOBBY AND CORRIDOR) FLOOR LIVE LOAD (HQ OFFICE) .............................................. 50 PSF (OFFICES)
4. SNOW LOADS
FLAT ROOF SNOW LOAD Pf .................................................... 60 PSF (AS-BUILT LOADING)
5. WIND LOADS
ULTIMATE DESIGN WIND SPEED VULT..................................... 113 MPH
NOMINAL DESIGN WIND SPEED VASD...................................... 88 MPH
RISK CATEGORY ....................................................................... II EXPOSURE ................................................................................. B
INTERNAL PRESSURE COEFFICIENT ..................................... 0.18
6. SEISMIC LOADS
SS ............................................................................................... 0.97 S1 ............................................................................................... 0.45 SDS ............................................................................................. 0.78 SD1 ............................................................................................. 0.57
R (LIGHT-FRAMED WOOD SHEAR WALLS)............................. 6.5
CS (LIGHT-FRAMED WOOD SHEAR WALLS)............................. 0.12
SITE CLASS................................................................................. D (DEFAULT)
SEISMIC DESIGN CATEGORY.................................................. D
RISK CATEGORY ....................................................................... II IMPORTANCE FACTOR............................................................. 1.0
BASIC SEISMIC FORCE RESISTING SYSTEM
HQ OFFICE....................................................... LIGHT-FRAMED WOOD SHEAR WALLS
DESIGN BASE SHEAR
HQ OFFICE.................................................................... 40 KIPS ANALYSIS PROCEDURE........................................................... EQUIVALENT LATERAL FORCE METHOD
B. STRUCTURAL STEEL
1. ALL STRUCTURAL STEEL WIDE FLANGE MEMBERS SHALL BE ASTM A572 - GRADE 50 (Fy = 50 KSI) OR A992 (Fy
= 50 KSI).
2. SQUARE/RECTANGULAR HOLLOW STRUCTURAL SECTIONS (HSS) SHALL CONFORM TO ASTM A500 GRADE C
(Fy = 50 KSI).
3. ROUND HSS SHALL CONFORM TO ASTM A500 GRADE C (Fy = 46 KSI).
4. PIPE SHALL CONFORM TO ASTM A53 GRADE B (Fy = 35 KSI).
5. ANGLES, PLATES, AND CHANNELS SHALL BE ASTM A572 (Fy = 50 KSI) UNLESS NOTED OTHERWISE.
6. ALL STRUCTURAL STEEL SHALL BE DETAILED AND FABRICATED IN ACCORDANCE WITH THE LATEST EDITION
OF THE AISC STEEL CONSTRUCTION MANUAL.
7. BOLTED CONNECTIONS SHALL BE ACCOMPLISHED WITH TENSION-CONTROLLED HIGH-STRENGTH BOLTS
CONFORMING TO ASTM F3125 GRADE F1852 (A325-TC) IN STANDARD HOLES UNLESS NOTED OTHERWISE.
8. ALL BOLTED CONNECTIONS SHALL BE PRE-TENSIONED UNLESS NOTED OTHERWISE.
9. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE CONTROL OF ALL ERECTION PROCEDURES AND
SEQUENCES WITH REGARD TO TEMPERATURE DIFFERENTIALS.
10. WELDING SHALL BE PERFORMED WITH E70XX ELECTRODES. WELDING SHALL BE DONE BY QUALIFIED
WELDERS AND SHALL CONFORM TO THE AWS D1.1 STRUCTURAL WELDING CODE-STEEL, LATEST EDITION.
ALL WELDS ARE INTENDED TO BE CONTINUOUS UNLESS NOTED OTHERWISE.
11. FIELD WELDS NOTED THROUGHOUT THE CONTRACT DOCUMENTS ARE ACCEPTABLE LOCATIONS FOR FIELD
WELDING AT THE CONTRACTOR'S OPTION. FIELD WELDS MAY BE PERFORMED IN THE SHOP.
12. COMPLETE JOINT PENETRATION WELDS ON STRUCTURAL STEEL SHALL CONFORM TO THE FOLLOWING
ADDITIONAL REQUIREMENTS:
A. WELDING SHALL BE PERFORMED IN ACCORDANCE WITH A WELDING PROCEDURE SPECIFICATION
(WPS) AS REQUIRED IN AWS D1.1 AND APPROVED BY THE ENGINEER OF RECORD. WELDS SHALL BE MADE WITH FILLER METALS MEETING THE REQUIREMENTS SPECIFIED IN AWS D1.8 CLAUSE 6.3
B. WELDS DESIGNATED AS DEMAND CRITICAL SHALL BE MADE WITH FILLER METALS MEETING THE
REQUIREMENTS SPECIFIED IN AWS D1.8 CLAUSE 6.3
C. WOOD CONSTRUCTION
1. FRAME LUMBER FRAME LUMBER EXPOSED TO WEATHER SHALL BE TREATED HEM FIR NO. 2 OR BETTER/
EQUAL RATED FOR APPLICABLE USE EXPOSURE.
2. GLUED LAMINATED BEAMS SHALL BE AYC 20F-V12, AND SHALL MEET THE FOLLOWING MINIMUM CRITERIA:
• Fb = 2,000 PSI
• E = 1,500,000 PSI
3. BOLTS USED IN WOOD CONNECTIONS SHALL BE ASTM A307.
4. FASTENERS IN PRESERVATIVE-TREATED WOOD SHALL BE OF HOT DIPPED ZINC-COATED GALVANIZED
STEEL, STAINLESS STEEL, SILICON BRONZE OR COPPER. THE COATING WEIGHTS FOR ZINC-COATED
FASTENERS SHALL BE IN ACCORDANCE WITH ASTM A153.
5. A PROTECTIVE COATING SHALL BE APPLIED TO FIELD-CUT ENDS OF TREATED, EXTERIOR-USE WOOD
CONSISTENT WITH ITS NATURAL FINISH.
6. FRAMING AND FASTENERS NOT SHOWN SHALL CONFORM WITH IBC CHAPTER 23 TABLE 2304.10.2.
7. CUTTING, DRILLING, AND NOTCHING OF CONVENTIONAL LIGHT LUMBER FRAMING SHALL COMPLY WITH THE
FOLLOWING IBC STANDARDS:
A. WALL FRAMING: 2308.5.8 THRU 2308.5.10
B. FLOOR JOISTS: 2308.4.2.4
D. GENERAL
1. CONTRACTOR IS TO FIELD VERIFY ALL DIMENSIONS AND ELEVATIONS TO MATCH NEW CONSTRUCTION TO
EXISTING CONSTRUCTION.
2. THE STRUCTURAL CONSTRUCTION DOCUMENTS REPRESENT THE FINISHED STRUCTURE. THEY DO NOT
INDICATE THE METHOD OR SEQUENCE OF CONSTRUCTION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR AND PROVIDE ALL MEASURES NECESSARY TO PROTECT THE STRUCTURE DURING CONSTRUCTION.
SUCH MEASURES SHALL INCLUDE, BUT NOT BE LIMITED TO: BRACING, SHORING FOR LOADS DUE TO CONSTRUCTION EQUIPMENT, ETC. THE STRUCTURAL ENGINEER SHALL NOT BE RESPONSIBLE FOR THE CONTRACTOR'S MEANS, METHODS, TECHNIQUES, SEQUENCES FOR PROCEDURE OF CONSTRUCTION, OR THE SAFETY PRECAUTIONS AND THE PROGRAMS INCIDENT THERETO (NOR SHALL OBSERVATION VISITS TO
THE SITE INCLUDE INSPECTION OF THESE ITEMS).
3. STRUCTURAL DRAWINGS ARE A PORTION OF THE CONTRACT DOCUMENTS AND ARE INTENDED TO BE USED WITH ARCHITECTURAL, CIVIL, MECHANICAL, AND ELECTRICAL DRAWINGS. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING THE REQUIREMENTS FROM THESE DISCIPLINES INTO THEIR SHOP
DRAWINGS AND WORK.
4. CONTRACTOR SHALL BE RESPONSIBLE FOR THE DESIGN AND IMPLEMENTATION OF ALL SCAFFOLDING, BRACING AND SHORING.
5. CONSTRUCTION MATERIALS SHALL BE SPREAD OUT IF PLACED ON FRAMED CONSTRUCTION. LOADS SHALL
NOT EXCEED THE DESIGN LIVE LOAD.
6. ESTABLISH AND VERIFY ALL OPENINGS AND INSERTS FOR ARCHITECTURAL, MECHANICAL, PLUMBING AND
ELECTRICAL WITH THE APPROPRIATE TRADES, DRAWINGS AND SUBCONTRACTORS PRIOR TO
CONSTRUCTION.
7. DO NOT USE SCALED DIMENSIONS TAKEN FROM STRUCTURAL DRAWINGS. CONTACT STRUCTURAL
ENGINEER IF DIMENSIONAL INFORMATION IS MISSING.
8. ANY ENGINEERING DESIGN PROVIDED BY OTHERS AND SUBMITTED FOR REVIEW SHALL BEAR THE SEAL OF
A PROFESSIONAL ENGINEER REGISTERED IN THE STATE OF ALASKA.
PER ARCH
2X6 PICKETS AT 9 1/2" OC,
MAX
CLR
1 1/2"
CONTINUOUS 2X6 RAIL AND CAP
(2) 3/8"Ø X 3 1/2" LAG SCREW
W/ STD WASHER, EA
BALUSTER
CLEAR
1 1/2"
P E
R A
R C
H
STAIR TREAD PER ARCH
3-1/8"x12" AYC GLULAM
PER ARCH
PER
ARCH
M
IN
4"
PT 4X12 TIMBERS
GALVANIZED L4X4X1/4X1'-4"
ATTACH TO TIMBER SLEEPERS W/ (4) SDS25400 SCREWS
ATTACH TO STRINGER W/ (2) 5/8"Ø THROUGH BOLTS
4 1/2"
(6) SDS25300 SCREWS,
SPACED AS SHOWN
3/4" GAP
1/4" WELDED KICK PLATE, 2" MAX GAP AT TOP
OMIT KICK PLATE AT TOP TREAD
1 1/2"
3/16
3/16
TYP
/2
1/4" PLATE, TYP
3/4"Ø A325
THROUGH BOLT
GUARDRAILS NOT SHOWN FOR CLARITY
U.S. DEPARTMENT OF THE INTERIOR
BUREAU OF LAND MANAGEMENT
NATIONAL SYSTEM OF PUBLIC LANDS
ISSUE DATE
COMM. NUMBER
DESIGNED BY
DRAWN BY
SCALE 0" 1"
Architects Engineers Surveyors
601 College Road Fairbanks AK 99701
907.452.1241 designalaska.comAECC511
NATIONAL SYSTEM OF PUBLIC LANDS
9/30/2025 1:34:27 PM
SMM
SMM
GENERAL
STRUCTURAL
NOTES
S010
GFO FLOOD
DAMAGE REPAIR
902301
30 AUG 2025
CONTINUOUS PERIODIC
IBC CODE
REFERENCE
CODE or STANDARD
REFERENCE
FREQUENCYSYSTEM or MATERIAL
INSPECTION
REMARKS
PERIODIC: SPECIAL INSPECTION BY THE SPECIAL INSPECTOR WHO IS INTERMITTENTLY PRESENT WHERE THE WORK TO BE INSPECTED HAS BEEN OR IS BEING
PERFORMED.
CONTINUOUS: SPECIAL INSPECTION BY THE SPECIAL INSPECTOR WHO IS PRESENT WHEN AND WHERE THE WORK TO BE INSPECTED IS BEING PERFORMED.
THE FOLLOWING STRUCTURAL ITEMS REQUIRE SPECIAL INSPECTION PER IBC SECTIONS 1704-1707.
SEE PROJECT SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS FOR INSPECTION AND TESTING THAT ARE NOT PART OF SPECIAL INSPECTIONS.
SPECIAL INSPECTIONS
COMPLETE JOINT PENETRATION
WELDS
1705.2.1 AISC 360 N5.5 X
ALL WELDS TO BE VISUALLY INSPECTED PER
AWS D1.1 6.9
ULTRASONIC TESTING (UT) IS REQUIRED FOR
CJP WELDS IN BUTT JOINTS.
NO PROHIBITED WELDS HAVE BEEN
ADDED WITHOUT THE APPROVAL OF
THE EOR
1705.2.1 AISC 360-16: TABLE N5.4-3 X
REPAIR ACTIVITIES 1705.2.1 AISC 360-16: TABLE N5.4-3 X
BACKING REMOVED AND WELD TABS
REMOVED
1705.2.1 AISC 360-16: TABLE N5.4-3 X REMOVE TABS IF REQUIRED
K-AREA 1705.2.1 AISC 360-16: TABLE N5.4-3 X
INSPECT WELDED DOUBLER PLATES,
CONTINUITY PLATES OR STIFFENERS. LOOK
FOR CRACKS WITHIN 3IN OF WELDS
ARC STRIKES 1705.2.1 AISC 360-16: TABLE N5.4-3 X
WELDS MEET VISUAL ACCEPTANCE
CRITERIA
1705.2.1
AISC 360-16: N5.4, TABLE
N5.4-3 X
SIZE, LENGTH, AND LOCATION OF
WELDS
1705.2.1 AISC 360-16: TABLE N5.4-3 X
WELDS CLEANED 1705.2.1 AISC 360-16: TABLE N5.4-3 X
DOCUMENT ACCEPTANCE OR
REJECTION WELDED JOINT OR
MEMBER
1705.2.1
AISC 360-16: TABLE N5.6-3,
TABLE N5.4-3
X
AFTER BOLTING/WELDING
WPS FOLLOWED PLAN FOR
ENVIRONMENTAL CONDITIONS
AISC 360-16: TABLE N5.4-2 X
WIND SPEED WITHIN LIMITS, PRECIPITATION
AND TEMPERATURE
NO WELDING OVER CRACKED TACK
WELDS
AISC 360-16: TABLE N5.4-2 X
CONTROL AND HANDLING OF
WELDING CONSUMABLES
1705.2.1
AISC 360-16: TABLE N5.4-2 X
ITEMS INCLUDE: PACKAGING AND EXPOSURE
CONTROL
DURING BOLTING/WELDING
FIT-UP OF FILLET AND GROOVE
WELDS
AISC 360-16: TABLE N5.4-1 X
JOINT PREPARATIONS, DIMENSIONS,
CLEANLINESS, TACKING, BACKING TYPE AND
FIT
WELDER IDENTIFICATION SYSTEM AISC 360-16: TABLE N5.4-1 X
THE FABRICATOR OR ERECTOR SHALL
MAINTAIN A SYSTEM BY WHICH A WELDER
WHO HAS WELDED A JOINT OR MEMBER CAN
BE IDENTIFIED
MATERIAL IDENTIFICATION AISC 360-16: TABLE N5.4-1 X TYPE/GRADE
MANUFACTURER CERTIFICATIONS
FOR WELDING CONSUMABLES
AVAILABLE
AISC 360-16: TABLE N5.4-1 X
WPS AVAILABLE AISC 360-16: TABLE N5.4-1 X
WELDER QUALIFICATION RECORDS
AND CONTINUITY RECORDS
1705.2.1
AISC 360-16: TABLE N5.4-1 X
PRIOR TO BOLTING/WELDING
FABRICATORS
1704.2.5
1704.2.5.1
AISC 360-16: N6 X
SPECIAL INSPECTION IS REQUIRED FOR
STRUCTURAL LOAD-BEARING MEMBERS AND
ASSEMBLIES FABRICATED ON THE PREMISES
OF A FABRICATOR'S SHOP
NOTE: SPECIAL INSPECTION IS NOT
REQUIRED WHERE THE WORK IS DONE ON
THE PREMISES OF A FABRICATOR
REGISTERED AND APPROVED TO PERFORM
SUCH WORK WITHOUT SPECIAL INSPECTION
FABRICATORS
DIVISION #05 - STRUCTURAL STEEL
1" = 1'-0"S010
2 HQ OFFICE - TYPICAL STAIR
1" = 1'-0"S010
1 HQ OFFICE - STAIR RAILING CONSTRUCTION
A K
AF AL
T S
TA
E
O
49 TH
S
Samuel M. Mitchell
CE 219520
D E
S I G
N
A L
A S
K A
R E
G
IS
T
ER
ED
PROFESS IONAL
EN
G
IN
E E
R
30-SEP-2025
S200
__________TYP ALL
(E) POSTS
(E) W18X46(E) W18X46
(E) W18X46
(E) W16X31
UNLESS NOTED
OTHERWISE
(E) DECK TIMBERS
3-1/8x15 AYC GLB
NOTES:
EXISTING FLOOR JOISTS ARE HUNG FROM TOP FLANGE OF FLOOR BEAMS.
JOISTS NOT SHOWN FOR CLARITY
F
IE
L D
V E
R
IF
Y A
L L
D
IM
E N
S
IO
N S
/4
12' - 11 1/4" 16' - 5 1/4"
19' - 6 1/4" 18' - 8 1/4" 12' - 0"
/4
/4
15' - 4" 18' - 8 1/4" 12' - 0"
REPLACE (E) 3/8"Ø SCREW ANCHORS AT RAMP POST
BASE PLATES WITH 3/8"ØX7" GALVANIZED WEDGE
ANCHORS WITH MIN 4-1/2" EXPOSED THREADS, TYPICAL
7 LOCATIONS.
NOTE: SHIM STACKS ARE NOT REQUIRED AT THESE
LOCATIONS UNLESS RAMP IS FOUND TO BE OUT OF
ADA TOLERANCES FOLLOWING BUILDING RELEVELING
LEGEND:
AUG 2024 ELEVATION RELATIVE TO BENCHMARK
BENCHMARK
0.0"
(-)1.2" (-)3.6" (-)6.2" (-)6.5" (-)7.0"
(-)2.0" (-)4.0" (-)6.6" (-)10.0"
(-)11.3"
(+)0.8"
(+)1.9"
(+)0.8"
(+)0.8"
(+)3.0"
(+)2.3"
(-)0.5" (-)4.3" (-)9.4" (-)10.2"
(-)1.1"
(-)0.5"
(+)0.7"
(+)0.7"(+)0.5"
(+)0.6"(+)0.6"
(+)1.8"
HSS ENTRY DECK SUPPORT
POSTS, (6) TOTAL
HSS ENTRY RAMP SUPPORT
POSTS, (7) TOTAL
(CONTRACTOR SHALL VERIFY CURRENT CONDITIONS
PRIOR TO FABRICATING ADJUSTABLE ASSEMBLIES)
S010
S010
DEMOLISH (E) STAIR AND
REPLACE, THIS LOCATION ONLY
(E) HSS8X8X1/2 FOUNDATION POST, VERIFY
(E) HSS8X8X1/2 FOUNDATION
POST, VERIFY
HSS 8X8X1/2 POST EXTENSION WHERE
ELEVATION INCREASE ≥ 3" PER PLAN.
VERIFY SECTION TO MATCH EXISTING POST
(E) FOUNDATION
3/16
TYP
1" Ø F1554 GR. 55
THREADED ROD
0' - 10"
CJP
/2
1 1/2"
SHIM STACK MADE OF (12)
PL1/4"X10"X1'-2"
NOTES:
1. CJP WELDS SHALL HAVE ULTRASONIC TESTING COMPLETED PER SPECIAL INSPECTION
REQUIREMENTS ON S010. TEST RESULTS SHALL BE SUBMITTED TO OWNER FOR REVIEW.
2. ALL PLATES SHOWN SHALL BE ASTM GRADE 50.
3. ALL THREADED ROD TO BE GRADE 55 UNLESS NOTED OTHERWISE.
4. ALL BUILDING AND ENTRY POSTS TO BE RETROFITTED WITH SHIM STACK SHOWN. POST
EXTENSION ONLY REQUIRED WHERE HEIGHT INCREASE EXCEEDS 3".
PL3/4", T&B
PROVIDE THREADED RODS WITH
MIN 9" EXTRA THREAD LENGTH FOR
FUTURE ADJUSTMENT
U.S. DEPARTMENT OF THE INTERIOR
BUREAU OF LAND MANAGEMENT
NATIONAL SYSTEM OF PUBLIC LANDS
ISSUE DATE
COMM. NUMBER
DESIGNED BY
DRAWN BY
SCALE 0" 1"
Architects Engineers Surveyors
601 College Road Fairbanks AK 99701
907.452.1241 designalaska.comAECC511
NATIONAL SYSTEM OF PUBLIC LANDS
9/30/2025 1:34:28 PM
SMM
SMM
FOUNDATION
PLAN -
HEADQUARTERS
OFFICE
S200
GFO FLOOD
DAMAGE REPAIR
902301
30 SEP 2025
1/8" = 1'-0"S200
1 HQ OFFICE - FOUNDATION PLAN
GENERAL STRUCTURAL SHEET NOTES
1. SEE CIVIL DESIGN DRAWINGS FOR FINISH FLOOR ELEVATIONS.
2. ENTRY DECK AND RAMP POSTS WERE NOT INCLUDED IN 2024 BUILDING ELEVATION SURVEY.
ORIGINAL TOP OF POST ELEVATIONS VARY FROM THE BENCHMARK AND SHALL BE
CHECKED BY THE CONTRACTOR TO PROVIDE DECK AND RAMPS LEVELNESS AND SLOPES
WITHIN ADA TOLERANCES AND LIMITS.
3. CONTRACTOR SHALL FIELD VERIFY AND ACCOUNT FOR ALL DIFFERENTIAL ELEVATIONS TO
PROVIDE A LEVEL STRUCTURE UPON COMPLETION OF CONSTRUCTION.
4. ADJUSTABLE STEEL FABRICATIONS SHALL BE COATING WITH THE FOLLOWING SEQUENCE:
A. BASE COAT: (1 CT) ZINC CLAD II PLUS
B. INTERMEDIATE COAT: (1 CT) MACROPOXY 646
C. TOP COAT: (1 CT) ACROLON 218 HS POLYURETHANE, SEMIGLOSS. COLOR TO MATCH
EXISTING HQ OFFICE POST ASSEMBLIES. TAKE COLOR MATCH SAMPLE FROM
UNFADED PORTION AND SUBMIT WITH STEEL FABRICATION SHOP DRAWINGS.
5. ALL HARDWARE (WASHERS, NUTS, THREADED ROD, ETC.) SHALL BE GALVANIZED.
1" = 1'-0"S200
2 HQ OFFICE - ADJUSTABLE BRACKET
A K
AF AL
T S
TA
E
O
49 TH
S
Samuel M. Mitchell
CE 219520
D E
S I G
N
A L
A S
K A
R E
G
IS
T
ER
ED
PROFESS IONAL
EN
G
IN
E E
R
30-SEP-2025
MECHANICAL SYMBOLS
CONNECTION TO EXISTING
DUCT FLOW ARROW
PIPE FLOW ARROW
PIPE CONNECTION
PIPE ELBOW TURNED DOWN
PIPE ELBOW TURNED UP
PIPE TEE DOWN
UNION
PIPE CAP
PIPE BREAK
NC C
NO
ISOLATION VALVE
CHECK VALVE
BALANCE VALVE
PRESSURE RELIEF VALVE
PRESSURE REDUCING VALVE
STRAINER
DRAIN VALVE
HOSE BIBB
THERMOMETER
THERMOSTAT
SENSOR
PUMP
PRESSURE GAUGE
AIR VENT
PRESSURE & TEMPERATURE
TEST PORT
2-WAY CONTROL VALVE
3-WAY CONTROL VALVE
S
T
MECHANICAL LINETYPES
ABBREVIATION LINETYPE
W
V
CW
HW
RHW
GHS
GHR
FOS
FOR
EXISTING PIPING/DUCTWORK/
EQUIPMENT TO BE REMOVED
EXISTING TO BE REMOVED
EXISTING
FUEL OIL RETURN
FUEL OIL SUPPLY
GLYCOL HEATING RETURN
GLYCOL HEATING SUPPLY
RECIRCULATED HOT WATER
HOT WATER
COLD WATER
VENT
WASTE
FULL NAME
MECHANICAL TAG LEGEND
PIPE TAG 6" GHS SYSTEM ABBREVIATION
NOMINAL PIPE SIZE
WELL HOUSE ELECTRIC UNIT HEATER SCHEDULE
SYMBOL FAN
CFM
MIN
CAPACITY
(MBH)
ELECTRICAL
DATA
OPERATING
WEIGHT (LBS)
ECUH-1 300 12 4 KW
16.7A 240/1/60
40 1. SURFACE MOUNTED WITH WHITE ENCLOSURE COLOR.
2. PROVIDE WITH 24V CONTROL RELAY AND 24V REMOTE WALL
MOUNTED THERMOSTAT ADJUSTABLE FOR 45°F TO 90°F SETPOINT.
AREA SERVED
WELL HOUSE
REMARKSBASIS OF
DESIGN
QMARK
CDF542
U.S. DEPARTMENT OF THE INTERIOR
BUREAU OF LAND MANAGEMENT
NATIONAL SYSTEM OF PUBLIC LANDS
ISSUE DATE
COMM. NUMBER
DESIGNED BY
DRAWN BY
SCALE 0" 1"
Architects Engineers Surveyors
601 College Road Fairbanks AK 99701
907.452.1241 designalaska.comAECC511
NATIONAL SYSTEM OF PUBLIC LANDS
9/30/2025 1:36:59 PM
MPC
ERM
MECHANICAL
ABBREVIATIONS,
LEGENDS, AND
SCHEDULES
M001
GFO FLOOD
DAMAGE REPAIR
902301
30 SEP 2025
ABBREVIATION FULL NAME
# NUMBER
& AND
(E) EXISTING
@ AT
A AIR
AFF ABOVE FINISHED FLOOR
AGT AVERAGE GLYCOL TEMPERATURE
AHU AIR HANDLING UNIT
APD AIR PRESSURE DROP
APPR APPROVED
APPROX APPROXIMATE
ARCH ARCHITECTURAL
ASSOC ASSOCIATED
AUTO AUTOMATIC
BAL BALANCING
BFF BELOW FINISHED FLOOR
BFP BACKFLOW PREVENTER
C COMMON
CI CAST IRON
CO CLEAN OUT
Cv VALVE COEFFICIENT
CW COLD WATER
DB DECIBEL
DB DRY BULB
DI DUCTILE IRON
DIA DIAMETER
DN DOWN
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EF EXHAUST FAN
EGT ENTERING GLYCOL TEMPERATURE
ELEC ELECTRICAL
ESP EXTERNAL STATIC PRESSURE
EWT ENTERING WATER TEMPERATURE
EXIST EXISTING
FC FORWARD CURVED
FCO FLOOR CLEAN OUT
FD FLOOR DRAIN
FLA FULL LOAD AMPERAGE
FLEX FLEXIBLE
GA GAUGE
GALV GALVANIZED
GFCI GOVERNMENT FURNISHED, CONTRACTOR
INSTALLED
GFGI GOVERNMENT FURNISHED, GOVERNMENT
INSTALLED
GHR GLYCOL HEATING RETURN
GHS GLYCOL HEATING SUPPLY
GHS&R GLYCOL HEATING SUPPLY AND RETURN
GI GALVANIZED IRON
ABBREVIATION FULL NAME
HB HOSE BIBB
HW HOT WATER
ID INSIDE DIAMETER
IE INVERT ELEVATION
INSUL INSULATION
IPS IRON PIPE SIZE
LAT LEAVING AIR TEMPERATURE
LGT LEAVING GLYCOL TEMPERATURE
LWT LEAVING WATER TEMPERATURE
MAX MAXIMUM
MECH MECHANICAL
MIN MINIMUM
MTR MOTOR
NC NORMALLY CLOSED
NC NOISE CRITERIA
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NPSH NET PUMP SUCTION HEAD
OA OUTSIDE AIR
OAT OUTSIDE AIR TEMPERATURE
OBVD OPPOSED BLADE VOLUME DAMPER
OC ON CENTER
OD OUTSIDE DIAMETER
OSA OUTSIDE AIR
P&T PRESSURE AND TEMPERATURE
PD PRESSURE DROP
PH PHASE
PRDV PRESSURE REDUCING VALVE
PRV PRESSURE RELIEF VALVE
RA RETURN AIR
RHW RECIRCULATING HOT WATER
RPM REVOLUTIONS PER MINUTE
S/M SHEET METAL
S/S START/STOP
SIM SIMILAR
SP STATIC PRESSURE
SPEC SPECIFICATIONS
TDH TOTAL DYNAMIC HEAD
THW TEMPERED HOT WATER
TP TRAP PRIMER
TYP TYPICAL
V VENT
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VOL VOLUME
VTR VENT THROUGH ROOF
W WASTE
W/ WITH
W/O WITHOUT
WB WET BULB
WCO WALL CLEAN OUT
WHA WATER HAMMER ARRESTOR
MECHANICAL ABBREVIATIONS
A K
AF AL
T S
T A E O
49 TH
S
R E
G
ISTERED
PROFESS IONAL
ENG
IN
E
E R
D E
S I G
N
A L
A S
K
A30 SEP 2025
Marcus P. Curley
ME 14660
DEMOLISH BASEBOARD
HEATER, CONDUIT, AND
THERMOSTAT
(E) TEMP WATER LINE, NO LONGER IN PLACE
(E) 3/4" CW TO HOSE BIBBS TO REMAIN, 2 TOTAL
DEMOLISH EXHAUST FAN AND
DUCTING
REMOVE AND
STORE FOR REUSE
TANK AND STAND
WATER STAIN
REPRESENTS FLOOD
ELEVATION
(E) WELL HEAD, REMOVE WELL
PUMP AND PIPING TO
ACCOMMODATE WELL HEAD
MODIFICATIONS
3/4" CW TO UNDERFLOOR FOR HW
BUILDING SERVICE
M100
DEMOLISH HALON
SUPPRESSION UNIT
DEMOLISH HALON
SUPPRESSION UNIT
(E) WELL HEAD, REMOVE
AND STORE WELL PUMP
(E) ELECTRICAL
PANEL
DEMOLISH ELECTRIC BASEBOARD
(E) HOSE BIBBS TO REMAIN
REMOVE AND STORE FOR REUSE
PRESSURE TANK, STAND, AND PRESSURE
SWITCH
DEMOLISH EXHAUST FAN
AND DUCTWORK
DEMOLISH 3/4"
PEX PIPING
EXISTING GRADE SURFACE
BELOW FLOOR
CONFINED
SPACE
ARCTIC PIPE
TO HQ TO
REMAIN
3/4" CW HOSE
BIBBS TO REMAIN
ABANDONED ARCTIC PIPE
W/ SERVICE LINE
(E) PRESSURE TANK
REMOVE AND STORE FOR REUSE
(E) WELL
1" CW
DEMOLISH PIPING WITHIN
BUILDING FOOTPRINT
1" CW TO HQ
BUILDING
3/4" CW
ABANDONED CIRC
PUMP, 3 TOTAL
EXISTING CRAWLSPACE
SOIL SURFACE
U.S. DEPARTMENT OF THE INTERIOR
BUREAU OF LAND MANAGEMENT
NATIONAL SYSTEM OF PUBLIC LANDS
ISSUE DATE
COMM. NUMBER
DESIGNED BY
DRAWN BY
SCALE 0" 1"
Architects Engineers Surveyors
601 College Road Fairbanks AK 99701
907.452.1241 designalaska.comAECC511
NATIONAL SYSTEM OF PUBLIC LANDS
9/30/2025 1:37:00 PM
MPC
ERM
DEMOLITION
PLANS AND
DIAGRAMS
M100
GFO FLOOD
DAMAGE REPAIR
902301
30 SEP 2025
HEADQUARTERS OFFICE BUILDING
ANNEX OFFICE
LOG OFFICEWELL HOUSE
KEYPLAN
A
B
C
M100 NO SCALE
2 WELL HOUSE DEMOLITION PHOTO
M100 NO SCALE
4 HQ OFFICE MECHANICAL ROOM HALON UNIT
M100 NO SCALE
5 HQ OFFICE COMM ROOM HALON UNIT
GENERAL NOTES
1. REMOVE ALL ABANDONED PUMPS AND PIPING WITHIN WELL HOUSE UNDER
FLOOR SPACE.
2. CAP ALL OPEN ENDED PIPING PENETRATING THE EXISTING FOUNDATION WALL
WITH CODE COMPLIANT PIPE FITTINGS
3. EXISTING WELL PUMP IS A GOULDS 10HS07422C, 3/4 HORSEPOWER WITH TWO
WIRE CONNECTION. SALVAGE EXISTING WELL PUMP CONTROLLER FOR REUSE
AND REINSTALLATION. PRIOR TO REMOVAL, CONTRACTOR SHALL TAKE PHOTOS
AND SUBMIT TO PROJECT MANAGER DOCUMENTING EXISTING CONTROLLER
CONDITIONS.
4. DISPOSE OF HALON PRIMER CHARGE AND HALON IN ACCORDANCE WITH EPA
REGULATIONS. DISCHARGE TO ATMOSPHERE IS PROHIBITED.
5. PROJECT WORK WILL BE PHASED. REFER TO DIV 01 SPECIFICATIONS FOR
PHASING REQUIREMENTS AND TEMPORARY FACILITIES TO SUPPORT THE
EXISTING USERS AND SITE.
M100 NO SCALE
1 WELL HOUSE DEMOLITION PLAN
M100 NO SCALE
3 WELL HOUSE UNDER FLOOR DEMOLITION DETAIL
A K
AF AL
T S
T A E O
49 TH
S
R E
G
ISTERED
PROFESS IONAL
ENG
IN
E
E R
D E
S I G
N
A L
A S
K A9-30-2025
DOMESTIC COLD WATER TO BUILDING
FIXTURES AND EQUIPMENT
BUILDING FINISHED
FLOOR
PROVIDE ACCESS PANEL WHERE VALVES
ARE CONCEALED WITHIN AN INTERIOR WALL
ARCTIC PIPE SYSTEM
PROVIDE ELECTRIC HEAT TRACE POWERED
FROM BUILDING SERVED BY WATER LINE
CHECK VALVE WITH BACK PRESSURE RELIEF
LABEL VALVE WITH "BUILDING COLD WATER
SHUTOFF VALVE" IN MINIMUM 1/8" HIGH TEXT
SEAL FLOOR PENETRATION AIRTIGHT
SECURE PIPES AND VALVES TO STRUCTURE
SEE ELECTRICAL FOR ADDITIONAL
HEAT TRACE REQUIREMENTS
PROVIDE LIGHTED END SEAL ON
WELL HOUSE END OF HEAT TRACE
ROUTE HEAT TRACE THROUGH CHANNEL
WITHIN ARCTIC PIPE INSULATION
EXTEND SERVICE PIPE ABOVE FLOOR
SERVICE PIPE
EXTEND WELL CASING AND RISER TO MINIMUM 12" ABOVE
FLOOD ELEVATION, MATCH EXISTING MATERIALS
3/4" CW TO EXTERIOR EXISTING HOSE BIBBS
HEADQUARTERS OFFICE BUILDING
ANNEX OFFICE
LOG OFFICE
EXISTING BURIED WATER SERVICE ARCTIC PIPE
SEWER LINE ARCTIC BOX
EXISTING SEWER ARCTIC BOX
EXISTING CRAWLSPACE
SOIL SURFACE
SLEEVE WELL CASING WITH STEEL PIPE, FILL ANNULAR
SPACE WITH CEMENT GROUT OR BENTONITE CLAY
FIT WELL CASING WITH SANITARY SEAL, WATERTIGHT
CAP WITH SCREENED VENT, MONITOR 6WPSM OR EQUAL
EXTEND EXISTING ARCTIC PIPING AND HEAT
TRACE ABOVE FINISHED FLOOR, OFFSET
EXTENSION HORIZONTALLY AS NEEDED
M200
EXTEND ARCTIC PIPING ABOVE WELL
HOUSE FINISHED FLOOR
SEE CIVIL DRAWINGS FOR ROUTING AND DETAILS
FOR BURIED WATER SERVICE ARCTIC PIPING
PS
40/60 PSI
PRESSURE
SWITCH
EXISTING GRADE SURFACE
3/4" CW
ELECTRIC HEAT TRACE SERVED FROM LOG OFFICE,
PROVIDE LIGHTED END SEAL IN WELL HOUSE
EXISTING SCHEDULE 40 STEEL
WELL CASING
COLD WATER UP TO LOG OFFICE
BACKFILL TO 6" BELOW BOTTOM
OF EXISTING FLOOR JOISTS
EXTEND SLEEVE TO MINIMUM 24" BELOW
EXISTING CRAWLSPACE SOIL SURFACE
EXTEND SLEEVE TO MINIMUM
12" ABOVE FINISHED FLOOR
REINSTALL EXISTING
PRESSURE TANK AND STAND
PROVIDE HIGH FLOW FILTER
HOUSING AND 4.5" DIAMETER,
1 MICRON FILTER, PENTAIR
BIG CLEAR #10 OR EQUAL
1" CW
3/4" CW
3/4" CW
1" CW
PROVIDE 1-1/2", 16GA, STRAP. INSTALL AT THIRD
POINTS AND SECURE TO EXISTING WALL W/ 1-5/8"
CHANNEL STRUT ANCHORED TO MIN 3 STUDS
ET-2
HEADQUARTERS
ARCTIC PIPE
WELL
LOG OFFICE
ARCTIC PIPE
TWO FROST FREE
HOSE BIBBS
ELECTRICAL PANEL
ECUH-1
REINSTALL EXISTING WELL
PUMP CONTROLLER
U.S. DEPARTMENT OF THE INTERIOR
BUREAU OF LAND MANAGEMENT
NATIONAL SYSTEM OF PUBLIC LANDS
ISSUE DATE
COMM. NUMBER
DESIGNED BY
DRAWN BY
SCALE 0" 1"
Architects Engineers Surveyors
601 College Road Fairbanks AK 99701
907.452.1241 designalaska.comAECC511
NATIONAL SYSTEM OF PUBLIC LANDS
9/30/2025 1:37:01 PM
MPC
ERM
SITE DOMESTIC
WATER SYSTEM
DIAGRAMS AND
DETAILS
M200
GFO FLOOD
DAMAGE REPAIR
902301
30 SEP 2025
HEADQUARTERS OFFICE BUILDING
ANNEX OFFICE
LOG OFFICEWELL HOUSE
KEYPLAN
A
B
C
GENERAL NOTES
1. PROTECT THROUGH CONSTRUCTION OF NEW WELL HOUSE THE EXISTING WELL
AND THE ARCTIC PIPE SERVING THE HEADQUARTERS OFFICE BUILDING.
2. EXISTING WELL PUMP IS LOCATED APPROXIMATELY SIXTY FEET BELOW EXISTING
WELL HEAD. REMOVE EXISTING PUMP AND PROVIDE NEW ELECTRICAL
CONDUCTORS AND RISER PIPE TO MATCH EXTENDED WELL CASING.
3. NEW AND EXISTING SERVICE LINE PIPING TO BE HYDROSTATICALLY PRESSURE
TESTED AND DISINFECTED, PER SPECIFICATION 33 11 00. TEST WATER AT
HEADQUARTERS OFFICE BUILDING LAVATORY, ANNEX LAVATORY, AND LOG
OFFICE LAVATORY FOR BACTERIOLOGICAL TESTING PER PROJECT
SPECIFICATIONS.
4. PROJECT WORK WILL BE PHASED. REFER TO DIV 01 SPECIFICATIONS FOR
PHASING REQUIREMENTS AND TEMPORARY FACILITIES TO SUPPORT THE
EXISTING USERS AND SITE.
M200 NO SCALE
2 TYPICAL BUILDING WATER SERVICE AND SERVICE CIRCULATION DETAIL
M200 NO SCALE
1 SITE DOMESTIC WATER SYSTEM PIPING DIAGRAM
M200 1/2" = 1'-0"
3 WELL HOUSE FLOOR PLAN
A K
AF AL
T S
T A E O
49 TH
S
R E
G
ISTERED
PROFESS IONAL
ENG
IN
E
E R
D E
S I G
N
A L
A S
K A9-30-2025
WASTE LINE W/IN ARCTIC PIPE, ROUTE ABOVE GRADE
BELOW STRUCTURE, PLACE ON PRESSURE TREATED
CRIBBING
SLOPE WASTE LINE ARCTIC
PIPE BELOW GRADE
BUILDING WATER ENTRANCE ABOVE FLOOR
M200
M201
COLD WATER SERVICE
ARCTIC PIPE
CONNECT TO EXISTING
COLD WATER
ARCTIC BOX HOUSING VERTICAL OFFSET, SIMILAR
TO HEADQUARTERS OFFICE BUILDING
CONNECT TO EXISTING SEWER BELOW GRADE
M200
CLEANOUT CAP
GRADE
ARCTIC PIPE ON SLEEPERS
BENEATH BUILDING
UNDERFLOOR SOFFIT
FINISHED FLOOR
BUILDING COLD WATER
SERVICE PIPING
SLEEPERS, MAXIMUM 6' ON CENTER
PROVIDE EPDM FLASHING TO SEAL
ARCTIC PIPE TO SOFFIT
U.S. DEPARTMENT OF THE INTERIOR
BUREAU OF LAND MANAGEMENT
NATIONAL SYSTEM OF PUBLIC LANDS
ISSUE DATE
COMM. NUMBER
DESIGNED BY
DRAWN BY
SCALE 0" 1"
Architects Engineers Surveyors
601 College Road Fairbanks AK 99701
907.452.1241 designalaska.comAECC511
NATIONAL SYSTEM OF PUBLIC LANDS
9/30/2025 1:37:02 PM
MPC
ERM
LOG OFFICE
MECHANICAL
PLAN
M201
GFO FLOOD
DAMAGE REPAIR
902301
30 SEP 2025
M201 1/4" = 1'-0"
1 LOG OFFICE MECHANICAL PLAN
HEADQUARTERS OFFICE BUILDING
ANNEX OFFICE
LOG OFFICEWELL HOUSE
KEYPLAN
M201 NO SCALE
2 LOG OFFICE WATER SERVICE ARCTIC PIPE DETAIL
A K
AF AL
T S
T A E O
49 TH
S
R E
G
ISTERED
PROFESS IONAL
ENG
IN
E
E R
D E
S I G
N
A L
A S
K A9-30-2025
EXISTING 3/4" COLD WATER WITHIN
ARCTIC PIPE BELOW GRADE
M202
PROVIDE CW EXTENSION TO
ACCOMMODATE BUILDING LEVELING
M202
(E) BURIED FUEL OIL SUPPLY LINE
EXISTING WASTE PIPE ENCLOSURE,
ADD EXTENSION OF WASTE PIPING
EXISTING COLD WATER UP WITHIN
INTERIOR WALL TO FIXTURES
PROVIDE SINGLE WALL FUEL OIL PIPE EXTENSION ABOVE GRADE
WITH JOG IN PIPING TO ALLOW FUTURE FOUNDATION ADJUSTMENT
COLD WATER WITHIN FLOOR ASSEMBLY TO HOSE BIBB
WELL WATER UP TO MANIFOLD
EXISTING BOILER
COLD WATER TO HUMIDIFIER
M202
EXISTING WELL WATER WITHIN FLOOR ASSEMBLY
GRADE
FINISHED FLOOR
EXTEND ARCTIC PIPE TO SUPPORT BUILDING
ELEVATION CHANGE, MATCH EXISTING HDPE
ARCTIC PIPE TYPE AND INSULATION THICKNESS
UNDERFLOOR SOFFIT
UP TO EXISTING COLD WATER MANIFOLD
PROVIDE EPDM FLASHING TO
SEAL ARCTIC PIPE TO SOFFIT
EXISTING COLD WATER
ARCTIC PIPE
EXISTING BUILDING WASTE PIPING,
RAISED WITH HQ OFFICE
EXISTING WASTE ARCTIC PIPING WITH
HEAT TRACE AT GRADE
PROVIDE CAST IRON WASTE PIPING
WITH NO-HUB COUPLINGS
EXIS…