Attachment_2__Drawings.pdf

PDF 45 MB Posted

Attached to
BROCK RESERVOIR GATE REPLACEMENT/REPAIRS Federal contract opportunity
Solicitation number
140R3026R0004
Issued by
Department of the Interior Bureau of Reclamation

About this file

This document is a comprehensive set of technical drawings for the Warren H. Brock Reservoir Gate Replacement project, detailing electrical, cathodic protection, and structural modifications across multiple sheets. The drawings specify the replacement of 11 existing cast iron gates with 316L stainless steel slide gates across multiple structures, including detailed installation plans for gate replacements at Inlet/Outlet Structures No. 1 and No. 2, Transition/Trashrack Gate Structure, and Pipe Inlet Structure.

The technical drawings comprehensively cover electrical infrastructure, including single-line diagrams, cable and conduit schedules, site conduit plans, and grounding specifications. The project involves replacing existing equipment such as engine generators, transforming electrical systems, installing new cathodic protection systems, and modifying communication infrastructure. Key technical elements include vertical and horizontal impressed current anode installations, junction box placements, cable routing, and specific modifications to gate structures, with precise specifications for conduit types, cable sizes, and installation methodologies across the reservoir's various structural components.

View the file

Other files for this federal contract opportunity

Other files attached to BROCK RESERVOIR GATE REPLACEMENT/REPAIRS, newest first.
File Type Posted
Sol_140R3026R0004_Amd_0005.pdf PDF
Revised_Page_L-15_0004.pdf PDF
Sol_140R3026R0004_Amd_0004.pdf PDF
140R3026R0004_-_Questions_from_Site_Visit_0004.pdf PDF
Specifications_01_46_00_0003.pdf PDF
Specifications_31_01_10_0003.pdf PDF
423-D-60247-Cell_1_Option_0003.pdf PDF
Rodney_Hunt_Shop_Drawings_0003.pdf PDF
140R3026R0004_-_Site_Visit_Sign-In_Sheet_0003.pdf PDF
SF_1442_0003.pdf PDF
Attachment_8_Key_Subcontractor_Specialized_Experience_0003.pdf PDF
Sol_140R3026R0004_Amd_0003.pdf PDF
Specifications_35_23_11_0003.pdf PDF
Revised_Page_L-12_0003.pdf PDF
Sol_140R3026R0004_Amd_0002.pdf PDF
Attachment_1A_Statement_of_Work_0002.pdf PDF
Sol_140R3026R0004_Amd_0001.pdf PDF
Solicitation_No__140R3026R0004_0001.pdf PDF
Attachment_5_Performance_Bond_SF25.pdf PDF
Attachment_9_Subcontracting_Plan_Template.pdf PDF
Attachment_7_-_Past_Performanc_Questionnaire.pdf PDF
Attachment_4_Bid_Bond_SF24.pdf PDF
Sol_140R3026R0004.pdf PDF
Attachment_3_Wage_Determination_CA20260002.pdf PDF
Attachment_1_Specifications.pdf PDF
Attachment_6_DI-137_Release_of_Claims.pdf PDF
Attachment_5_Payment_Bond_SF25A.pdf PDF
Attachment_8_Subcontracting_Plan_Template.docx DOCX document
Show all 28

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Mexicali

San Diego

Los Angeles

San Jose

Fresno

Sacramento

San Francisco

CALIFORNIA

NEVADA

ARIZONA

MEXICO

Carson City

Phoenix

Las Vegas

Boulder City

Yuma

Rough and Ready

Brawley

El Centro

Mexicali

Yuma Calexico

All American Canal

Coachella Canal

Ferguson Lake

Imperial Reservoir

Salton Sea

MEXICO

UNITED STATES

ARIZONA

CALIFORNIA

UNITED STATES

MEXICO

All American Canal

Coachella Canal

Coachella Turnout (Not detailed)

Warren H. Brock Reservoir Drop 2 Inlet Canal

Contractor designed Cofferdam

60238

A

LW

A

YS

T H

IN

K

S A

FE

TY

SHEET

D

C

B

A

D

C

B

A

B U

R

EA

U O

F R

EC

LA

M

A

TI

O N

U .S

D

EP

A R

TM

EN

T

O F

TH

E

IN

TE

R

IO

R

C A D

S

YS

TE

M

A ut oC A D

5.

0S

LM

S T

EC

H

C A D

F

IL

EN

A M

E

3- D

-6

-R

D -1

.D W

G

LA

S T

S A V

ED

D A

TE

-1 1-

LA

S T

S A V

ED

B Y

A M

A R N

ER

¦D_DT¦

¦STATUS¦

C O

LO

R A D

O R

IV

ER

F R O

N T

W O

R K A

N D

L

EV

EE

S

YS

TE

M

W A R R

EN

H

B R O

C K R

ES

ER

V O

IR

G

A

TE

R

EP

LA

C

EM

EN

T, C A

TH

O D

IC

P

R O

TE

C

TI

O N

A N

D E

LE

C

TR

IC

A L

M O

D

IF

IC

A

TI

O N

S

LOCATION MAP

DENVER, CO

423-D-60236

DESIGNED

DRAWN

CHECKED

TECH. APPR.

APPROVED

ADMIN APPROVAL -

£TT£

£AT£

£AA£

£TA£

J L MENA

J L MENA

J THOMAS

KEY MAP

NO SCALE

VICINITY MAP

NO SCALE

See Vicinity Map LEGEND

Interstate Highway State Highway System

Unimproved Road Canal United States / Mexico Border

Improved Road

Body of Water

LOCATION MAP

See Location Map

NO SCALE

NOTES

1. Drop 2 Inlet Canal is the canal of interest and drawn with more detail than other surrounding canals.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

GENERAL

SHEET

NO. DRAWING NO. CONTENT DETAIL

1 423-D-60236 LOCATION MAP

2 423-D-60237 DRAWING INDEX

3 423-D-60238 CONTRACTOR USE AREAS PLAN

4 423-D-60239 GENERAL SCOPE OF WORK GENERAL PLAN

GATES

SHEET

NO. DRAWING NO. CONTENT DETAIL

5 423-D-60240 120"x120" STAINLESS STEEL

SLIDE GATE INSTALLATION - SECTIONS

6 423-D-60241 120"x84" STAINLESS STEEL

SLIDE GATE INSTALLATION - SECTIONS

CATHODIC PROTECTION SYSTEMS

SHEET

NO. DRAWING NO. CONTENT DETAIL

7 423-D-60242 IMPRESSED CURRENT CATHODIC

PROTECTION SYSTEM

FOREBAY/AFTERBAY GENERAL

LAYOUT

8 423-D-60243 IMPRESSED CURRENT CATHODIC

PROTECTION SYSTEM

ANODE, CONDUIT, AND

JUNCTION BOX INSTALLATION

DETAILS

9 423-D-60244 IMPRESSED CURRENT CATHODIC

PROTECTION SYSTEM

ANODE, CONDUIT, AND

JUNCTION BOX INSTALLATION

DETAILS

10 423-D-60245 IMPRESSED CURRENT CATHODIC

PROTECTION SYSTEM

ANODE, CONDUIT, AND

JUNCTION BOX INSTALLATION

DETAILS

11 423-D-60246 IMPRESSED CURRENT CATHODIC

PROTECTION SYSTEM

ANODE, CONDUIT, AND

JUNCTION BOX INSTALLATION

DETAILS

12 423-D-60247 IMPRESSED CURRENT CATHODIC

PROTECTION SYSTEM

GATE AND THIMBLE STRUCTURE

CONNECTION DETAILS

13 423-D-60248 IMPRESSED CURRENT CATHODIC

PROTECTION SYSTEMS

CONDUIT LINE DIAGRAM AND

MASTER BOND BOX DETAILS

14 423-D-60249 GALVANIC ANODE CATHODIC

PROTECTION SYSTEM

ANODE, CONDUIT, AND

JUNCTION BOX DETAILS

INFORMATION DRAWINGS

SHEET

NO. DRAWING NO. CONTENT DETAIL

25 423-D-635 RESERVOIR AND INLET/OUTLET

AREA DETAILED PLAN

26 423-D-642

DROP 2 INLET CANAL,

RESERVOIR, PIPE CROSSING, &

OUTLET CANAL

GENERAL PLAN

27 423-D-644 STATION 4+11.42 TO STATION

23+00 PLAN AND PROFILE

28 423-D-660 STATION 411.42 TO STATION

342+00 SECTIONS AND DETAILS

29 423-D-661 CANAL WASTEWAY PLAN AND SECTION

30 423-D-698 FOREBAY/AFTERBAY GENERAL PLAN AND SECTION

31 423-D-699 INLET/OUTLET STRUCTURE PARTIAL PLAN AND DETAIL

32 423-D-704 PIPE INLET STRUCTURE

CONCRETE OUTLINE PLAN,

SECTIONS, AND DETAILS

33 423-D-705 PIPE OUTLET TRANSITION SITE AND EARTHWORK PLAN AND

SECTIONS

34 423-D-712 TRANSITION/TRASHRACK/GATE

STRUCTURE

TRASHRACK AND BRIDGE DECK

PLAN

35 423-D-737 ACCESS ROAD TO POWERPLANT PLAN, PROFILE, AND ALIGNMENT

TABLES

36 423-D-764 INLET/OUTLET STRUCTURE

MISCELLANEOUS METALWORK

AND W-BEAM GUARDRAIL

GRATED WALKWAYS - PLAN AND

SECTIONS

37 423-D-765 TRANSITION/TRASHRACK/GATE

STRUCTURE

MISCELLANEOUS METALWORK

AND W-BEAM GUARDRAIL

GRATED WALKWAYS - PLAN AND

SECTIONS

38 423-D-766 PIPE INLET STRUCTURE

MISCELLANEOUS METALWORK

AND W-BEAM GUARDRAIL

GRATED WALKWAYS - PLAN AND

SECTIONS

39 423-D-772

WATER LEVEL SENSOR

MOUNTING POLE AND

FOUNDATION

MISCELLANEOUS METALWORK

ELEVATION, SECTIONS AND

DETAILS

40 423-D-777 OPEN WATER CATHODIC

PROTECTION TYPICAL ANODE RESTRAINTS

41 423-D-778 ACCESS RAMP AT RESERVOIR

SECTION C 3+48 PLAN AND SECTIONS

42 423-D-780 ACCESS RAMP AT RESERVOIR

STATION E 164+24 PLAN AND SECTIONS

43 423-D-782 EQUIPMENT BUILDING ENGINE-

GENERATOR SET PLAN AND SECTIONS

44 423-D-785 WATER LEVEL SYSTEM SENSOR

MOUNTING PLAN-SECTIONS-DETAIL

45 423-D-789 RESERVOIR STOPLOGS INSTALLATION-ASSEMBLY-

DETAILS

46 423-D-792 STOPLOG SEATS AND GUIDES PLANS-INSTALLATION-

ASSEMBLIES

47 423-D-793 STOPLOG SEATS AND GUIDES SECTIONS AND DETAILS

48 423-D-794 RESERVOIR STOPLOG LIFTING

BEAM INSTALLATION AND ASSEMBLY

49 423-D-799 STOPLOG SEATS AND GUIDES PLAN-ASSEMBLY-SECTION-

DETAILS

50 423-D-809 CONTROL BUILDING FLOOR PLAN

51 423-D-811 CONTROL BUILDING ELEVATIONS

52 423-D-812 CONTROL BUILDING BUILDING SECTIONS

53 423-D-814 CONTROL BUILDING DOOR/LOUVER SCHEDULES AND

DETAILS

54 423-D-821 ELECTRICAL INSTALLATION

ELECTRICAL DISTRIBUTION

SINGLE LINE DIAGRAM DHA &

DHB PANELBOARD SCHEDULES

55 423-D-822 ELECTRICAL INSTALLATION FOREBAY/AFTERBAY AREA

CONDUIT PLAN

56 423-D-823 ELECTRICAL INSTALLATION FOREBAY/AFTERBAY AREA GATE

STRUCTURES CONDUIT PLAN

57 423-D-839 ELECTRICAL INSTALLATION BURIED CONDUIT AS-BUILT

KEY MAP

58 423-D-840 ELECTRICAL INSTALLATION BURIED CONDUIT AS-BUILT

ELEC-1

ELECTRICAL

SHEET

NO. DRAWING NO. CONTENT DETAIL

15 423-D-60250 MICROWAVE RADIO

COMMUNICATION SYSTEMS NETWORK DIAGRAM

16 423-D-60251 SITE SINGLE LINE DIAGRAM

17 423-D-60252 SITE CABLE AND CONDUIT SCHEDULE

18 423-D-60253 SITE

CABLE AND CONDUIT SCHEDULE

(CONT)

19 423-D-60254 MAIN PANEL DHA AND LIGHTING

PANEL DHB PANEL SCHEDULES

20 423-D-60255 SITE CONDUIT PLAN

21 423-D-60256 GATE STRUCTURES CONDUIT PLAN

22 423-D-60257 BROCK CONTROL BUILDING LIGHTING AND RECEPTACLE PLAN

23 423-D-60258 BROCK CONTROL BUILDING GROUNDING PLAN

24 423-D-60259 BROCK CONTROL BUILDING WIREWAY PLAN

STANDARD DRAWINGS

SHEET

NO. DRAWING NO. CONTENT DETAIL

76 40-D-4334 ELECTRICAL INSTALLATION TYPICAL GROUNDING DETAILS

77 40-D-4335 ELECTRICAL INSTALLATION TYPICAL GROUNDING DETAILS

78 40-D-4753 ELECTRICAL INSTALLATION

TYPICAL GROUNDING DETAILS

FOR SWITCHYARDS AND

SUBSTATIONS

79 40-D-6182 ELECTRICAL INSTALLATION TYPICAL CABLE TRENCH

GROUNDING

80 40-D-6234 STANDARD DESIGNS STANDARD NAMEPLATES

81 40-D-6592 PIPE GUARDRAILS TOP MOUNTED

PIPE GUARDRAILS

ELEVATION, SECTIONS, AND

DETAILS

82 40-D-7094 ELECTRICAL INSTALLATION CONDUIT CLAMP AND CONDUIT

SUPPORTS TYPICAL DETAILS

83 40-D-7102

DRAWING BORDER, SAMPLE

TITLE BLOCK, AND SIGNATURE

LINES

84 104-D-757 ELECTRICAL INSTALLATION DESIGNATIONS AND SYMBOLS

85 104-D-1033 ELECTRICAL INSTALLATION COLOR CODE IDENTIFICATION

CONTROL CABLES

86 104-D-1150 ELECTRICAL INSTALLATION

DEVICE DESIGNATIONS AND

SYMBOLS TO BE USED ON

SINGLE-LINE AND SCHEMATIC

DIAGRAM

87 104-D-1165 MAIN CONTROL BOARD CSA -

PANEL 7R WIRING DIAGRAM

88 104-D-60001 BREAKER CONTROL SCHEMATIC DIAGRAM

INFORMATION DRAWINGS

SHEET

NO. DRAWING NO. CONTENT DETAIL

59 423-D-841 ELECTRICAL INSTALLATION BURIED CONDUIT AS-BUILT

ELEC-2

60 423-D-842 ELECTRICAL INSTALLATION BURIED CONDUIT AS-BUILT

ELEC-3

61 423-D-843 ELECTRICAL INSTALLATION BURIED CONDUIT AS-BUILT

ELEC-4

62 423-D-844 ELECTRICAL INSTALLATION BURIED CONDUIT AS-BUILT

ELEC-5

63 423-D-845 ELECTRICAL INSTALLATION BURIED CONDUIT AS-BUILT

ELEC-6

64 423-D-846 ELECTRICAL INSTALLATION BURIED CONDUIT AS-BUILT

ELEC-7

65 423-D-847 ELECTRICAL INSTALLATION BURIED CONDUIT AS-BUILT

ELEC-8

66 423-D-848 ELECTRICAL INSTALLATION BURIED CONDUIT AS-BUILT

ELEC-9

67 423-D-849 ELECTRICAL INSTALLATION BURIED CONDUIT AS-BUILT

ELEC-10

68 423-D-850 ELECTRICAL INSTALLATION BURIED CONDUIT AS-BUILT

ELEC-11

69 423-D-851 ELECTRICAL INSTALLATION BURIED CONDUIT AS-BUILT

ELEC-12

70 423-D-852 ELECTRICAL INSTALLATION BURIED CONDUIT AS-BUILT

ELEC-13

71 423-D-853 ELECTRICAL INSTALLATION BURIED CONDUIT AS-BUILT

ELEC-14

72 423-D-854 ELECTRICAL INSTALLATION BURIED CONDUIT AS-BUILT

ELEC-15

73 423-D-855 ELECTRICAL INSTALLATION BURIED CONDUIT AS-BUILT

ELEC-16

74 423-D-856 ELECTRICAL INSTALLATION BURIED CONDUIT AS-BUILT

ELEC-17

75 423-D-857 ELECTRICAL INSTALLATION CONTROL BUILDING EXTERNAL

CONDUIT & WIREWAY PLAN

GENERAL NOTES

1. Warren H. Brock Reservoir was previously known as "Drop 2 Storage Reservoir". References to "Drop

2 Storage Reservoir" may appear in the drawing set and in Information Drawings.

A

LW

A

YS

T H

IN

K

S A

FE

TY

SHEET

D

C

B

A

D

C

B

A

B U

R

EA

U O

F R

EC

LA

M

A

TI

O N

U .S

D

EP

A R

TM

EN

T

O F

TH

E

IN

TE

R

IO

R

C A D

S

YS

TE

M

A ut oC A D

5.

0S

LM

S T

EC

H

C A D

F

IL

EN

A M

E

3- D

-6

-R

D -1

.D W

G

LA

S T

S A V

ED

D A

TE

-1 1-

LA

S T

S A V

ED

B Y

A M

A R N

ER

¦D_DT¦

¦STATUS¦

C O

LO

R A D

O R

IV

ER

F R O

N T

W O

R K A

N D

L

EV

EE

S

YS

TE

M

W A R R

EN

H

B R O

C K R

ES

ER

V O

IR

G

A

TE

R

EP

LA

C

EM

EN

T, C A

TH

O D

IC

P

R O

TE

C

TI

O N

A N

D E

LE

C

TR

IC

A L

M O

D

IF

IC

A

TI

O N

S

DRAWING INDEX

DENVER, CO

423-D-60237

DESIGNED

DRAWN

CHECKED

TECH. APPR.

APPROVED

ADMIN APPROVAL

£TT£

£AT£

£AA£

£TA£

J L MENA

J L MENA

J THOMAS

Water level tower

Access ramp (-778)

Water level tower

Inlet/outlet structures Soil cement apron

Soil cement apronContractor staging area

Wasteway (-661)

Drop 2 Inlet Canal

Forebay/Afterbay

Access ramp (-780)

Perimeter fence

Perimeter fence

DETAIL

60238

Main entrance

Buried outlet pipe

General work area

Reservoir Cell No. 2 Reservoir Cell No. 1

NO SCALE

Contractor shall not use this area

Transiton/Trashrack Structure

Pipe Inlet Structure

Reservoir Cell No. 2

Existing Evan Hewes Highway

Perimeter fence

Reservoir Cell No. 1

PLAN

60238

Drop 2 Inlet Canal

Government storage area

60238

Drop 2 Outlet Canal

Drop 2 (Not detailed)

All American Canal

Interstate Highway 8

60236

Cofferdam borrow area

NO SCALE

DETAIL

60238

Access road

Drop 2 Outlet Canal

Pipe Outlet Transition Structure stoplog slots (-705), (-792), (-793)

CL Buried outlet pipes

NO SCALE

Contractor Staging Area

General Work Area

Contractor No Use Area

LEGEND - CONTRACTOR USE AREAS

Cofferdam Borrow Area

Existing detailed feature

LEGEND - DRAWING SET LINEWORK

Centerline

Existing concrete

Buried or hidden feature

Nonshrink grout

A

LW

A

YS

T H

IN

K

S A

FE

TY

SHEET

D

C

B

A

D

C

B

A

B U

R

EA

U O

F R

EC

LA

M

A

TI

O N

U .S

D

EP

A R

TM

EN

T

O F

TH

E

IN

TE

R

IO

R

C A D

S

YS

TE

M

A ut oC A D

5.

0S

LM

S T

EC

H

C A D

F

IL

EN

A M

E

3- D

-6

-R

D -1

.D W

G

LA

S T

S A V

ED

D A

TE

-1 1-

LA

S T

S A V

ED

B Y

A M

A R N

ER

¦D_DT¦

¦STATUS¦

C O

LO

R A D

O R

IV

ER

F R O

N T

W O

R K A

N D

L

EV

EE

S

YS

TE

M

W A R R

EN

H

B R O

C K R

ES

ER

V O

IR

G

A

TE

R

EP

LA

C

EM

EN

T, C A

TH

O D

IC

P

R O

TE

C

TI

O N

A N

D E

LE

C

TR

IC

A L

M O

D

IF

IC

A

TI

O N

S

CONTRACTOR USE

AREAS

PLAN

DENVER, CO

423-D-60238

DESIGNED

DRAWN

CHECKED

TECH. APPR.

APPROVED

ADMIN APPROVAL -

£TT£

£AT£

£AA£

£TA£

J L MENA

J L MENA

GENERAL PLAN

Water level tower (-772)

Inlet/Outlet Structure No. 2 Inlet/Outlet Structure No. 1

Multiple rectifiers and master bond boxes

Transition Trashrack Structure

Provide new guardrails at open sections. See Note 3

Control Building

Communication Tower

Stoplog Storage

Pipe Inlet Structure

1a

1b1b

1c

Bubbler cabinet Bubbler cabinet

Water level tower (-772)

Water level tower (-772)

5 5

REFERENCE

NO. REFERENCE FEATURE GENERAL SCOPE REFERENCE DRAWINGS

1a 1b 1c

Transition Trashrack Structure Inlet/Outlet Structures No. 1 and 2

Pipe Inlet Structure

* Remove existing cast iron slide gates and actuators.

* Install new stainless steel slide gates and actuators.

* Blast and recoat thimbles and stoplog guides.

* Install new CP equipment.

* Install new guardrails (Transition Trashrack Structure).

GATES: 423-D-60240 and -60241 CP: 423-D-60242 thru -60249

POWER: 423-D-60255, -60256

GUARDRAILS: 40-D-6592

2 Water level towers

* Remove existing solar panels and equipment on tower.

* Remove and replace staff gauge.

* Blast and recoat ladder and water level tower.

* Install new water level measurement equipment.

* Provide power to new water level measurement equipment.

WATER TOWER: 423-D-772

POWER: 423-D-60255

3 Control Building

* Remove and replace existing engine generator and transfer switch.

ENGINE GENERATOR: 423-D-60251

ELECTRICAL: 423-D-60258, -60259

BUILDING: 423-D-809, -811, -812, -814

4 Communications Tower

* Remove and replace existing security camera. COMMUNICATION: 423-D-60250

5 Stoplogs & Stoplog Slots

* Pipe Outlet CP work requires stoplog installation.

* Gate removal and installation may require use of stoplogs if work conducted outside of outage.

* Gate leakage testing requires use of stoplogs.

STOPLOG: 423-D-789, -792, -793, -794, -799

GENERAL SCOPE OF WORK NOTES

1. General Scope of Work table provides a broad description of work to be performed at each reference feature. It is not intended to be all inclusive.

2. General Scope of Work table provides reference to certain drawings. It is not intended to be all inclusive and it may be useful to reference additional Informational Drawings.

3. An approximately 6-ft section on each end of the canal needs guardrails. Actual length of guardrail sections needs to be field verified. Provide in accordance with drawing 40-D-6592 and specifications.

A

LW

A

YS

T H

IN

K

S A

FE

TY

SHEET

D

C

B

A

D

C

B

A

B U

R

EA

U O

F R

EC

LA

M

A

TI

O N

U .S

D

EP

A R

TM

EN

T

O F

TH

E

IN

TE

R

IO

R

C A D

S

YS

TE

M

A ut oC A D

5.

0S

LM

S T

EC

H

C A D

F

IL

EN

A M

E

3- D

-6

-R

D -1

.D W

G

LA

S T

S A V

ED

D A

TE

-1 1-

LA

S T

S A V

ED

B Y

A M

A R N

ER

¦D_DT¦

¦STATUS¦

C O

LO

R A D

O R

IV

ER

F R O

N T

W O

R K A

N D

L

EV

EE

S

YS

TE

M

W A R R

EN

H

B R O

C K R

ES

ER

V O

IR

G

A

TE

R

EP

LA

C

EM

EN

T, C A

TH

O D

IC

P

R O

TE

C

TI

O N

A N

D E

LE

C

TR

IC

A L

M O

D

IF

IC

A

TI

O N

S

GENERAL SCOPE OF

WORK

GENERAL PLAN

DENVER, CO

423-D-60239

DESIGNED

DRAWN

CHECKED

TECH. APPR.

APPROVED

ADMIN APPROVAL -

£TT£

£AT£

£AA£

£TA£

J L MENA

J L MENA

FLOW

3'-6"

INLET/OUTLET STRUCTURE NO. 1

INLET/OUTLET STRUCTURE NO. 2

TRANSITION/TRASHRACK/GATE STRUCTURE

CL Slide Gate No. 3

CL Slide Gate No. 2

CL Slide Gate No. 1

B

SECTION

0 4' 8' 16'

B

B

AA

AA

AA

CL 120" x 120" Fabricated stainless steel Slide Gate No. 3

A

SECTION

0 4' 8' 16'

Symmetrical about structure CL

Inlet/Outlet Structures CL El 138.00 Transition/Trashrack/Gate Structure CL El 145.50

Inlet/Outlet Structures El 133.00

Transition/Trashrack/Gate Structure El 140.50

CL Stem

PLAN

0 4' 8' 16'

New 120" x 120" self-contained fabricated stainless steel slide gates.

Contractor to field verify all existing structure and thimble dimensions for new gate installation Provide isolation gasket between existing cast iron thimble and new stainless steel gate frame. See (-60247) and specifications

Remove and dispose existing 120"x120" cast iron slide gates, operators, and appurtenant equipment. Provide new 120"x120" self-contained fabricated stainless steel slide gate with motor-operated pedestal lift, stem, stem guides, and anchor bolts as required.

Maximum seating and unseating head to gate CL = 20-ft.

CL 120" x 120"

Fabricated stainless steel Slide Gate No. 2

CL 120" x 120" Fabricated stainless steel Slide Gate No. 1

Motor operator

El 161.50 2'-0"*

Contractor to verify space between wall and grating, see (-764 and -765). Cover gap with floor plating or floor grating, customized to suit new gates. Concept shown in Detail 1

60240

New stainless steel anchors to avoid contact with existing wall reinforcement.

See notes

2'-0" approx 1'-6"approx

Chip away existing grout/concrete to allow removal of existing gates and installation of new gates. Chip to approximate dimensions noted, or as recommended by gate manufacturer. Repair with non-shrink grout after gate installation

Contractor designed stem protecting hard cover placed between gate frame yoke and upper stem guide.

See specifications

Stem bellows

CC

D 60241

C 60241

DETAIL

0 6'' 1' 2'

2'-0"*

Contractor to verify space between wall and grating, see (-764 and -765). Cover gap with floor plating or floor grating, cutting around operator support mounting plate. No open space shall be larger than 2". Plating or grating shall be flush with other grating

Floor plating or floor grating with supports

Operator pedestal mounting support

Operator support pedestal

Stem

For Inlet/Outlet Structures No.1 and No. 2 Grating, see (-764)

For Transition/Trashrack/Gate Structure Grating, see (-765)

(CONCEPT)

INFORMATION DRAWINGS

DROP 2 STORAGE RESERVOIR CANAL AND STRUCTURE

INLET/OUTLET STRUCTURE

PARTIAL PLAN AND DETAIL 423-D-699

TRANSITION/TRASHRACK/GATE STRUCTURE

TRASHRACK AND BRIDGE DECK PLAN 423-D-712

INLET/OUTLET STRUCTURE

MISCELLANEOUS METALWORK AND W-BEAM GUARDRAIL

GRATED WALKWAYS - PLAN AND SECTIONS 423-D-764

TRANSITION/TRASHRACK/GATE STRUCTURE

MISCELLANEOUS METALWORK AND W-BEAM GUARDRAIL

GRATED WALKWAYS - PLAN AND SECTIONS 423-D-765

NOTES

1. Dimensions annotated with asterisk (*) are to be field verified.

2. Fabricated stainless steel slide gate dimensions and spacing shall be in accordance with the gate manufacturer's standards and specifications.

3. Drawings show conceptual representation of gate installation. Gate manufacturer may provide alternate design and installation methods for approval.

4. Three structures with three slide gates and motor-operators at each structure.

5. Determine anchor locations using non-destructive methods (e.g., Ground

Penetrating Radar) to avoid interference with existing rebar.

6. Stem protection hard cover concept provided. Contractor may submit different design for approval.

REFERENCE DRAWINGS

WARREN H. BROCK RESERVOIR

PIPE INLET STRUCTURE

120"x84" STAINLESS STEEL SLIDE GATE

INSTALLATION - SECTIONS 423-D-60241

INLET/OUTLET NO. 1, NO. 2, TRANSITION/TRASHRACK/GATE

AND PIPE INLET STRUCTURES

IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM

GATE AND THIMBLE STRUCTURE CONNECTION

DETAILS 423-D-60247

C

DETAIL (CONCEPT)

Field verify. May vary by structure

Stem 316 SS Stem

Cover

Post-installed anchors. See notes

NOT TO SCALE

Provide hinges to allow stem cover to open for access

A

LW

A

YS

T H

IN

K

S A

FE

TY

SHEET

D

C

B

A

D

C

B

A

B U

R

EA

U O

F R

EC

LA

M

A

TI

O N

U .S

D

EP

A R

TM

EN

T

O F

TH

E

IN

TE

R

IO

R

C A D

S

YS

TE

M

A ut oC A D

4.

2S

LM

S T

EC

H

C A D

F

IL

EN

A M

E

3- D

-6

-R

D -1

.D W

G

LA

S T

S A V

ED

D A

TE

-1 2-

LA

S T

S A V

ED

B Y

JM

EN

A

¦D_DT¦

¦STATUS¦

C O

LO

R A D

O R

IV

ER

F R O

N T

W O

R K A

N D

L

EV

EE

S

YS

TE

M

W A R R

EN

H

B R O

C K R

ES

ER

V O

IR

IN

LE

T/

O U

TL

ET

S

TR

U C

TU

R E

N O

1, N O

2, A N

D

TR

A N

S

IT

IO

N

T R A S H

R A C K S

TR

U

C

TU

R E

120"X120" STAINLESS

STEEL SLIDE GATE

INSTALLATION-SECTIONS

DENVER, CO

423-D-60240

2025-11-21

TH

IS

D R A W

IN

G

S U

PE

R S

ED

ES

D

R A W

IN

G

3-

D -5

-1 1-

R

EV

N O

¦R_DT¦ £RA£

D

R ev is ed g at e nu m be ri ng t o m at ch h ow g at es ar e nu m be re d in t he f ie ld

DESIGNED

DRAWN

CHECKED

TECH. APPR.

APPROVED

ADMIN APPROVAL

£TT£

£AT£

£AA£

£TA£

J L MENA

J L MENA

J THOMAS

Quiniones, Andres J P.E.

Hayley, Allison R P.E.

B

AA

Stem bellows

PLAN

0 4' 8' 16'

B

SECTION

0 4' 8' 16' A

SECTION

0 4' 8' 16'

3'-6"

Motor operator

El 161.50

60241

CL Slide Gate No. 1

CL Slide Gate No. 2

Gate CL El 134.50

Provide isolation gasket between existing cast iron thimble and new stainless steel gate frame. See (-60247) and specifications

Remove and dispose existing 120"x84" cast iron slide gates, operators, and appurtenant equipment. Provide new 120"x84" self-contained fabricated stainless steel slide gate with motor-operated pedestal lift, stem, stem guides, and anchor bolts as required.

Maximum seating and unseating head to gate CL = 20-ft.

Chip away existing grout/concrete to allow removal of existing gates and installation of new gates. Chip to approximate dimensions noted, or as recommended by gate manufacturer. Repair with non-shrink grout after gate installation

CL Stem

El 161.50

New 120" x 84" self-contained fabricated stainless steel slide gates. Contractor to field verify all existing structure and thimble dimensions for new gate installation

FLOW

Symmetrical about structure CL

CL 120" x 84" Fabricated stainless steel Slide Gate No. 1

CL 120" x 84" Fabricated stainless steel Slide Gate No. 2

2'-0"*

Contractor to verify space between wall and grating, see (-766). Cover gap with floor plating or floor grating, customized to suit new gates. Concept shown in Detail 1

El 131.00

Stem guide as required.

See specifications

New stainless steel anchors to avoid contact with existing wall reinforcement. See notes

PIPE INLET STRUCTURE

2'-0" approx.

1'-6" approx.

Contractor designed stem protecting hard cover placed between gate frame yoke and upper stem guide. See specifications

C 60240

AA

D

C

DETAIL

0 6'' 1' 2'

2'-0"*

Contractor to verify space between wall and grating, see (-766). Cover gap with floor plating or floor grating, cutting around operator support mounting plate. No open space shall be larger than 2". Plating or grating shall be flush with other grating

Floor plating or floor grating with supports

Operator pedestal mounting support

Operator support pedestal

Stem

Pipe Inlet Structure Grating, see (-766)

(CONCEPT)

INFORMATION DRAWINGS

DROP 2 STORAGE RESERVOIR CANAL AND STRUCTURE

PIPE INLET STRUCTURE

CONCRETE OUTLINE PLAN, SECTIONS AND

DETAILS 423-D-704

MISCELLANEOUS METALWORK AND W-BEAM

GUARDRAIL GRATED WALKWAYS - PLAN AND

SECTIONS 423-D-766

NOTES

1. Dimensions annotated with asterisk (*) are to be field verified.

2. Fabricated stainless steel slide gate dimensions and spacing shall be in accordance with the gate manufacturer's standards and specifications.

3. Drawings show a conceptual representation of gate installation.

Gate manufacturer may provide alternate design and installation methods for approval.

4. Determine anchor locations using non-destructive methods (e.g., Ground Penetrating Radar) to avoid interference with existing rebar.

REFERENCE DRAWINGS

WARREN H. BROCK RESERVOIR

INLET/OUTLET NO. 1, NO. 2, AND TRANSITION TRASHRACK

STRUCTURE

120"x120" STAINLESS STEEL SLIDE GATE

INSTALLATION-SECTIONS 423-D-60240

INLET/OUTLET NO. 1, NO. 2, TRANSITION/TRASHRACK/

GATE AND PIPE INLET STRUCTURES

IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM

GATE AND THIMBLE STRUCTURE CONNECTION

DETAILS 423-D-60247

D

SECTION

NOT TO SCALE

(CONCEPT)

C

SECTION

NOT TO SCALE

(CONCEPT)

Stainless steel gate frame

Gasket

Embedded cast iron thimble

Stainless steel gate leaf

Seal

Isolation sleeve and washer. See (-60247)

Stainless steel anchor

Stainless steel anchor

Design the gate frame to provide sufficient clearance from the structure wall for alignment and adjustment.

After final positioning, place a minimum of 1 inch of grout.

A

LW

A

YS

T H

IN

K

S A

FE

TY

SHEET

D

C

B

A

D

C

B

A

B U

R

EA

U O

F R

EC

LA

M

A

TI

O N

U .S

D

EP

A R

TM

EN

T

O F

TH

E

IN

TE

R

IO

R

C A D

S

YS

TE

M

A ut oC A D

4.

2S

LM

S T

EC

H

C A D

F

IL

EN

A M

E

3- D

-6

-R

D -1

.D W

G

LA

S T

S A V

ED

D A

TE

-1 2-

LA

S T

S A V

ED

B Y

JM

EN

A

¦D_DT¦

¦STATUS¦

C O

LO

R A D

O R

IV

ER

F R O

N T

W O

R K A

N D

L

EV

EE

S

YS

TE

M

W A R R

EN

H

B R O

C K R

ES

ER

V O

IR

PI

PE

I N

LE

T

S

TR

U C

TU

R E

120"X84" STAINLESS

STEEL SLIDE GATE

INSTALLATION-SECTIONS

DENVER, CO

423-D-60241

2025-11-21

DESIGNED

DRAWN

CHECKED

TECH. APPR.

APPROVED

ADMIN APPROVAL -

£TT£

£AT£

£AA£

£TA£

J L MENA

J L MENA

J THOMAS

Quiniones, Andres J P.E.

Hayley, Allison R P.E.

Mechanical Engineer

TH

IS

D R A W

IN

G

S U

PE

R S

ED

ES

D

R A W

IN

G

3-

D -5

-1 1-

R

EV

N O

¦R_DT¦ £RA£

D

A dd ed b ol t he ad t o

S ec tio n

V ie w C a nd ad ju st ed n ut lo ca tio n.

LEGEND - CONDUIT LINEWORK

Existing buried and exposed cable conduit

A

LW

A

YS

T H

IN

K

S A

FE

TY

SHEET

D

C

B

A

D

C

B

A

B U

R

EA

U O

F R

EC

LA

M

A

TI

O N

U .S

D

EP

A R

TM

EN

T

O F

TH

E

IN

TE

R

IO

R

C A D

S

YS

TE

M

A ut oC A D

5.

0S

LM

S T

EC

H

C A D

F

IL

EN

A M

E

3- D

-6

-R

D -1

.D W

G

LA

S T

S A V

ED

D A

TE

-1 2-

LA

S T

S A V

ED

B Y

A M

A R N

ER

¦D_DT¦

¦STATUS¦

C O

LO

R A D

O R

IV

ER

F R O

N T

W O

R K A

N D

L

EV

EE

S

YS

TE

M

W A R R

EN

H

B R O

C K R

ES

ER

V O

IR

IN

LE

T/

O U

TL

ET

N O

1, N O

2, T R A N

S

IT

IO

N

TR

A S H

R A C K /G

A

TE

A N

D P

IP

E

IN

LE

T S

TR

U C

TU

R

ES

IMPRESSED CURRENT

CATHODIC PROTECTION

SYSTEM

FOREBAY/AFTERBAY

GENERAL LAYOUT

DENVER, CO

423-D-60242

2025-12-15

DESIGNED

DRAWN

CHECKED

TECH. APPR.

APPROVED

ADMIN APPROVAL

£TT£

£AT£

£AA£

£TA£

Daryl Little

Daryl Little

Avery Schilt

SCALE: NOT TO SCALE

PLAN - IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM GENERAL LAYOUT

1. Anodes are to be installed vertically on the upstream side of Transition/Trashrack/Gate Structure gates in slotted PVC impressed current anode conduit.

2. Anodes are to be installed horizontally on the upstream side of Inlet/Outlet Structure No. 1, Inlet/Outlet Structure No. 2, and Pipe Inlet Structure gates in slotted PVC impressed current anode conduit.

3. Anodes are to be installed horizontally on the downstream side of Transition/Trashrack/Gate Structure, Inlet/Outlet Structure No. 1, and Inlet/Outlet Structure No. 2 gates in slotted PVC impressed current anode conduit.

4. Junction box details listed in specification Section 26 42 00.

5. Label front of junction box in accordance with detail in sheet (-60248).

6. Rectifier power provided in conduit 42 and 45 as indicated on drawing sheet (-60252).

7. Cathodic protection system components are not to scale for visualization.

NOTES

IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM

ANODE, CONDUIT, AND JUNCTION BOX INSTALLATION DETAILS.................423-D-60243 ANODE, CONDUIT, AND JUNCTION BOX INSTALLATION DETAILS.................423-D-60244 ANODE, CONDUIT, AND JUNCTION BOX INSTALLATION DETAILS.................423-D-60245 ANODE, CONDUIT, AND JUNCTION BOX INSTALLATION DETAILS.................423-D-60246 CONDUIT LINE DIAGRAM AND MASTER BOND BOX DETAILS........................423-D-60248

BROCK SITE

CABLE AND CONDUIT SCHEDULE.............................................................423-D-60252 CONDUIT PLAN......................................................................................423-D-60255

GATE STRUCTURES

CONDUIT PLAN......................................................................................423-D-60256

REFERENCE DRAWINGSMATERIAL EXPLANATION

Item Description

Junction box NEMA 3R junction box (sized for number and size of cables)

Impressed current anode

De Nora LIDA mixed metal oxide tubular anode 3.1/122 (1.22" x 48"); or equal, with factory-installed cable

Impressed current anode conduit

2" diameter minimum, schedule 80 PVC with slot pattern, see (-60243)

Rectifier Primary rectifier (existing Forebay/Afterbay Rectifier - 20V/10A)

Rectifier Secondary rectifier (existing Reservoir #2 Rectifier - 20V/5A)

Inlet/Outlet Structure No. 2

Rectifiers and master bond boxes, see (-60248)

Control building

Pipe Inlet Structure

Water level sensor, see (-777 and -785)

Transition/Trashrack/ Gate Structure

60243

60243

Water level sensor, see (-777 and -785)

Water level sensor, see (-777 and -785)

60243

Existing buried cable conduits

60243

Inlet/Outlet Structure No. 1

60245

60244

60243

60246

Stoplog storage area

Concrete structure

DROP 2 STORAGE RESERVOIR CANAL AND STRUCTURES

OPEN WATER CATHODIC PROTECTION

TYPICAL ANODE RESTRAINTS....................................................................423-D-777

WATER LEVEL SYSTEM

SENSOR MOUNTINGS

PLAN-SECTIONS-DETAIL........................................................................423-D-785

INFORMATION DRAWINGS

60243

A

4"

54"

2"

1"

4"

4"

18'

2"

1"

4"

54"

Galvanized anode cable conduit

LEGEND - CONDUIT LINEWORK

CPVC anode cable conduit Galvanized structure cable conduit Existing buried and exposed cable conduit

A

LW

A

YS

T H

IN

K

S A

FE

TY

SHEET

D

C

B

A

D

C

B

A

B U

R

EA

U O

F R

EC

LA

M

A

TI

O N

U .S

D

EP

A R

TM

EN

T

O F

TH

E

IN

TE

R

IO

R

C A D

S

YS

TE

M

A ut oC A D

5.

0S

LM

S T

EC

H

C A D

F

IL

EN

A M

E

3- D

-6

-R

D -1

.D W

G

LA

S T

S A V

ED

D A

TE

-1 2-

LA

S T

S A V

ED

B Y

D

LI

TT

LE

¦D_DT¦

¦STATUS¦

C O

LO

R A D

O R

IV

ER

F R O

N T

W O

R K A

N D

L

EV

EE

S

YS

TE

M

W A R R

EN

H

B R O

C K R

ES

ER

V O

IR

TR

A N

S

IT

IO

N

/T R A S H

R A C K /G

A

TE

S

TR

U C

TU

R E

IMPRESSED CURRENT

CATHODIC PROTECTION

SYSTEM

ANODE, CONDUIT, AND

JUNCTION BOX

INSTALLATION DETAILS

DENVER, CO

423-D-60243

2025-12-16

DESIGNED

DRAWN

CHECKED

TECH. APPR.

APPROVED

ADMIN APPROVAL

£TT£

£AT£

£AA£

£TA£

Daryl Little

Daryl Little

Avery Schilt

Metal grating not shown

Continuity bond cables (typ.)

SCALE: NOT TO SCALE

PLAN - IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM

Stoplog guide (typ.) Anode cable conduit (typ.)

Stoplog guide

Gate and thimble not shown

Structure cable conduit (thimbles and stoplog guides)

Gate and thimble not shown

60243

1. Anodes are to be installed vertically on the upstream side of gates (minimum of 6 feet from gates) in slotted PVC impressed current anode conduit with slotted side pointed away from concrete wall towards stoplog guides and gates.

2. Anodes are to be installed horizontally on the downstream side of gates (minimum of 14 feet from thimbles) in slotted PVC impressed current anode conduit with slotted side pointed away from concrete energy dissipator and floor towards stoplog guides and thimbles.

3. Impressed current anode conduit shall be anchored to concrete wall/floor at each end and twice in the middle with conduit straps and concrete anchors to prevent loss during high flow conditions.

4. Gate and thimble structure connections shall be made in accordance with connection details in sheet (-60247).

5. Junction box details listed in specification Section 26 42 00.

6. Label front of junction box in accordance with diagram in sheet (-60248).

7. Replace damaged continuity bond cables on stoplog guides.

8. Anode and structure cable conduits shall be anchored to concrete every 5 feet for vertical segments and 10 feet for horizontal segments using conduit straps and concrete anchors or pre-existing Unistrut.

9. CPVC anode conduit shall be anchored to concrete every 2.5 feet to prevent loss during high flow conditions.

10. Cable identification for all cables terminating in junction boxes and bond boxes in accordance with detail in sheet (-60246).

11. Cathodic protection system components are not to scale for visualization.

NOTES

IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM

FOREBAY/AFTERBAY GENERAL LAYOUT.....................................................423-D-60242 ANODE, CONDUIT, AND JUNCTION BOX INSTALLATION DETAILS.................423-D-60246 GATE AND THIMBLE STRUCTURE CONNECTION DETAILS.............................423-D-60247 CONDUIT LINE DIAGRAM AND MASTER BOND BOX DETAILS........................423-D-60248

REFERENCE DRAWINGS

MATERIAL EXPLANATION

Item Description

Junction box NEMA 3R junction box, 12"H x 12"W x 6"D (sized for number and size of cables)

Continuity bond cable #6 AWG or larger stranded copper with HMWPE sheathing (black)

Structure cable #6 AWG or larger stranded copper with HMWPE sheathing (black)

Structure header cable

#6 AWG or larger stranded copper with HMWPE sheathing (black)

Impressed current anode cable

#10 AWG or larger stranded copper with HMWPE sheathing (red if available)

Anode header cable #6 AWG or larger stranded copper with HMWPE sheathing (black)

Impressed current anode

De Nora LIDA mixed metal oxide tubular anode 3.1/122 (1.22" x 48"); or equal, with factory-installed cable

Impressed current anode conduit

2" diameter minimum, schedule 80 PVC with slot pattern rotated 180 degrees around conduit

Concrete conduit anchors

16" dia x 2 14" long Tapcon+ or equal

Conduit straps Stainless steel, sized for diameter of conduit

Anode cable conduit 1" diameter minimum, schedule 80 CPVC (below typical water elevations)

Anode cable conduit 1" diameter minimum, galvanized RMC or flexible conduit (above typical water elevations) Structure cable conduit 1" diameter minimum, galvanized RMC or flexible conduit

Anode cable conduit (typ.)

60243

Existing buried conduits to master structure and anode boxes

60243

60243

60243

60243

60243

60243

Stoplog guide

Continuity bond cables

Structure cable conduits (thimble/ stoplog guides and gate)

Anode cable conduit (typ.) (below metal grating)

Structure cable conduit (gates)

Continuity bond cables (typ.)

Buss bar (typ.)

Shunt (typ.)

Variable resistor

(typ.)

Anode cable (typ.)

Structure cable (typ.)

Anode cable conduits

Structure cable conduits

To master anode bond box

To master structure bond box

SCALE: NOT TO SCALE (60242, 60248)

JUNCTION BOX DETAIL

Connection to cable conduit

Slot pattern to rotate 180 degrees around conduit

Cap

SCALE: NOT TO SCALE (60242, 60244, 60245, 60246)

IMPRESSED CURRENT ANODE

CONDUIT DETAIL

Structure header cableAnode header cable

SCALE: NOT TO SCALE

A

IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM

Connection to cable conduit

Slot pattern to rotate 180 degrees around conduit

Cap

SCALE: NOT TO SCALE (60242)

IMPRESSED CURRENT ANODE

CONDUIT DETAIL

Structure cable conduit (stoplog guides)

Structure cable conduit (stoplog guides)

Anode cable CPVC conduit (typ.)

AutoCAD SHX Text

ANODES

AutoCAD SHX Text

GATES

AutoCAD SHX Text #1

AutoCAD SHX Text #2

AutoCAD SHX Text #3

AutoCAD SHX Text #4

AutoCAD SHX Text #5

AutoCAD SHX Text

ANODES

AutoCAD SHX Text #1

AutoCAD SHX Text #2

AutoCAD SHX Text #3

AutoCAD SHX Text #4

AutoCAD SHX Text #5

GUIDES/THIMBLES

Galvanized anode cable conduit

LEGEND - CONDUIT LINEWORK

CPVC anode cable conduit Galvanized structure cable conduit Existing buried and exposed cable conduit

A

LW

A

YS

T H

IN

K

S A

FE

TY

SHEET

D

C

B

A

D

C

B

A

B U

R

EA

U O

F R

EC

LA

M

A

TI

O N

U .S

D

EP

A R

TM

EN

T

O F

TH

E

IN

TE

R

IO

R

C A D

S

YS

TE

M

A ut oC A D

5.

0S

LM

S T

EC

H

C A D

F

IL

EN

A M

E

3- D

-6

-R

D -1

.D W

G

LA

S T

S A V

ED

D A

TE

-1 2-

LA

S T

S A V

ED

B Y

D

LI

TT

LE

¦D_DT¦

¦STATUS¦

C O

LO

R A D

O R

IV

ER

F R O

N T

W O

R K A

N D

L

EV

EE

S

YS

TE

M

A Z

C A

C A

LI

FO

R N

IA

W A R R

EN

H B

R O

C K R

ES

ER

V O

IR

IN

LE

T/ O

U

TL

ET

S

TR

U

C

TU

R E

N O

IMPRESSED CURRENT

CATHODIC PROTECTION

SYSTEM

ANODE, CONDUIT, AND

JUNCTION BOX

INSTALLATION DETAILS

DENVER, CO

423-D-60244

DESIGNED

DRAWN

CHECKED

TECH. APPR.

APPROVED

ADMIN APPROVAL

£TT£

£AT£

£AA£

£TA£

Daryl Little

Daryl Little

Avery Schilt

Guardrail and metal grating not shown

Continuity bond cables (typ.)

SCALE: NOT TO SCALE

PLAN - IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM

Stoplog guide (typ.)

Anode cable conduit (typ.)

Stoplog guide (typ.)

Gate and thimble not shown

Guardrail and metal grating not shown

Structure cable conduit (gates)

Structure cable conduit (thimbles)

Gate and thimble not shown

Existing buried conduits from Transition/Trashrack Gate Structure and Control Building

60243

60243

60243

1. Anodes are to be installed horizontally in slotted PVC impressed current anode conduit with slotted side pointed away from concrete wall or floor towards stoplog guides and gates.

1.1. Anodes shall be installed a minimum of 20 feet from gates or thimbles.

2. Impressed current anode conduit shall be anchored to concrete wall/floor at each end and twice in the middle with conduit straps and concrete anchors to prevent loss during high flow conditions.

4. Gate and thimble structure connections shall be made in accordance with connection details in sheet

(-60247).

5. Junction box details listed in specification Section 26 42 00.

6. Label front of junction box in accordance with diagram in sheet (-60248).

7. Replace damaged continuity bond cables on stoplog guides.

8. Anode and structure cable conduits shall be anchored to concrete every 5 feet for vertical segments and 10 feet for horizontal segments using conduit straps and concrete anchors or pre-existing Unistrut.

9. CPVC anode conduit shall be anchored to concrete every 2.5 feet to prevent loss during high flow conditions.

10. Cable identification for all cables terminating in junction boxes and bond boxes in accordance with detail in sheet (-60246).

11. Cathodic protection system components are not to scale for visualization.

NOTES

IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM

FOREBAY/AFTERBAY GENERAL LAYOUT.....................................................423-D-60242 ANODE, CONDUIT, AND JUNCTION BOX INSTALLATION DETAILS.................423-D-60243 ANODE, CONDUIT, AND JUNCTION BOX INSTALLATION DETAILS.................423-D-60246 GATE AND THIMBLE STRUCTURE CONNECTION DETAILS.............................423-D-60247 CONDUIT LINE DIAGRAM AND MASTER BOND BOX DETAILS........................423-D-60248

REFERENCE DRAWINGS

MATERIAL EXPLANATION

Item Description

Junction box NEMA 3R junction box, 12"H x 12"W x 6"D (sized for number and size of cables)

Continuity bond cable #6 AWG or larger stranded copper with HMWPE sheathing (black)

Structure cable #6 AWG or larger stranded copper with HMWPE sheathing (black)

Structure header cable

#6 AWG or larger stranded copper with HMWPE sheathing (black)

Impressed current anode cable

#10 AWG or larger stranded copper with HMWPE sheathing (red if available)

Anode header cable #6 AWG or larger stranded copper with HMWPE sheathing (black)

Impressed current anode

De Nora LIDA mixed metal oxide tubular anode 3.1/122 (1.22" x 48"); or equal, with factory-installed cable

Impressed current anode conduit

2" diameter minimum, schedule 80 PVC with slot pattern, see (-60243)

Concrete conduit anchors

16" dia x 2 14" long Tapcon+ or equal

Conduit straps Stainless steel, sized for diameter of conduit

Anode cable conduit 1" diameter minimum, schedule 80 CPVC (below typical water elevations)

Anode cable conduit 1" diameter minimum, galvanized RMC or flexible conduit (above typical water elevations) Structure cable conduit 1" diameter minimum, galvanized RMC or flexible conduit

60243

60243

60243

Existing buried conduits to rectifiers and master structure and anode boxes

Existing buried conduits to forebay/afterbay side of structure

Existing buried conduits to reservoir side of structure

Existing structure, anode, and power cable conduits

Buss bar (typ.)

Shunt (typ.)

Variable resistor

(typ.)

Anode cable (typ.)

Structure cable (typ.)

Anode cable conduits

Structure cable conduits

To master anode bond box

To master structure bond box

SCALE: NOT TO SCALE (60242, 60248)

JUNCTION BOX DETAIL

60244

Structure header cableAnode header cable

SCALE: NOT TO SCALE

B

IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM

Anode cable conduit (typ.)

Anode cable galvanized conduit (typ.)

Anode cable CPVC conduit

(typ.)

AutoCAD SHX Text

ANODES

AutoCAD SHX Text

GATES

AutoCAD SHX Text #1

AutoCAD SHX Text #2

AutoCAD SHX Text #3

AutoCAD SHX Text #4

AutoCAD SHX Text

ANODES

AutoCAD SHX Text #1

AutoCAD SHX Text #2

AutoCAD SHX Text #3

AutoCAD SHX Text #4

C

Galvanized anode cable conduit

LEGEND - CONDUIT LINEWORK

CPVC anode cable conduit Galvanized structure cable conduit Existing buried and exposed cable conduit

A

LW

A

YS

T H

IN

K

S A

FE

TY

SHEET

D

C

B

A

D

C

B

A

B U

R

EA

U O

F R

EC

LA

M

A

TI

O N

U .S

D

EP

A R

TM

EN

T

O F

TH

E

IN

TE

R

IO

R

C A D

S

YS

TE

M

A ut oC A D

5.

0S

LM

S T

EC

H

C A D

F

IL

EN

A M

E

3- D

-6

-R

D -1

.D W

G

LA

S T

S A V

ED

D A

TE

-1 2-

LA

S T

S A V

ED

B Y

D

LI

TT

LE

¦D_DT¦

¦STATUS¦

C O

LO

R A D

O R

IV

ER

F R O

N T

W O

R K A

N D

L

EV

EE

S

YS

TE

M

W A R R

EN

H

B R O

C K R

ES

ER

V O

IR

IN

LE

T/ O

U

TL

ET

S

TR

U

C

TU

R E

N O

IMPRESSED CURRENT

CATHODIC PROTECTION

SYSTEM

ANODE, CONDUIT, AND

JUNCTION BOX

INSTALLATION DETAILS

DENVER, CO

423-D-60245

DESIGNED

DRAWN

CHECKED

TECH. APPR.

APPROVED

ADMIN APPROVAL

£TT£

£AT£

£AA£

£TA£

Daryl Little

Daryl Little

Avery Schilt

SCALE: NOT TO SCALE

PLAN - IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM

1. Anodes are to be installed horizontally in slotted PVC impressed current anode conduit with slotted side pointed away from concrete wall or floor towards stoplog guides and gates.

1.1. Anodes shall be installed a minimum of 20 feet from gates or thimbles.

2. Impressed current anode conduit shall be anchored to concrete wall/floor at each end and twice in the middle with conduit straps and concrete anchors to prevent loss during high flow conditions.

4. Gate and thimble structure connections shall be made in accordance with connection details in sheet

(-60247).

5. Junction box details listed in specification Section 26 42 00.

6. Label front of junction box in accordance with diagram in sheet (-60248).

7. Replace damaged continuity bond cables on stoplog guides.

8. Anode and structure cable conduits shall be anchored to concrete every 5 feet for vertical segments and 10 feet for horizontal segments using conduit straps and concrete anchors or pre-existing Unistrut.

9. CPVC anode conduit shall be anchored to concrete every 2.5 feet to prevent loss during high flow conditions.

10. Cable identification for all cables terminating in junction boxes and bond boxes in accordance with detail in sheet (-60246).

11. Cathodic protection system components are not to scale for visualization.

NOTES

IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM

FOREBAY/AFTERBAY GENERAL LAYOUT.....................................................423-D-60242 ANODE, CONDUIT, AND JUNCTION BOX INSTALLATION DETAILS.................423-D-60243 ANODE, CONDUIT, AND JUNCTION BOX INSTALLATION DETAILS.................423-D-60246 GATE AND THIMBLE STRUCTURE CONNECTION DETAILS.............................423-D-60247 CONDUIT LINE DIAGRAM AND MASTER BOND BOX DETAILS........................423-D-60248

REFERENCE DRAWINGS

MATERIAL EXPLANATION

Item Description

Junction box NEMA 3R junction box, 12"H x 12"W x 6"D (sized for number and size of cables)

Continuity bond cable #6 AWG or larger stranded copper with HMWPE sheathing (black)

Structure cable #6 AWG or larger stranded copper with HMWPE sheathing (black)

Structure header cable

#6 AWG or larger stranded copper with HMWPE sheathing (black)

Impressed current anode cable

#10 AWG or larger stranded copper with HMWPE sheathing (red if available)

Anode header cable #6 AWG or larger stranded copper with HMWPE sheathing (black)

Impressed current anode

De Nora LIDA mixed metal oxide tubular anode 3.1/122 (1.22" x 48"); or equal, with factory-installed cable

Impressed current anode conduit

2" diameter minimum, schedule 80 PVC with slot pattern, see (-60243)

Concrete conduit anchors

16" dia x 2 14" long Tapcon+ or equal

Conduit straps Stainless steel, sized for diameter of conduit

Anode cable conduit 1" diameter minimum, schedule 80 CPVC (below typical water elevations)

Anode cable conduit 1" diameter minimum, galvanized RMC or flexible conduit (above typical water elevations)

Structure cable conduit

1" diameter minimum, galvanized RMC or flexible conduit

Continuity bond cables (typ.)

Stoplog guide (typ.)

Anode cable conduit (typ.)

Guardrail and metal grating not shown

Structure cable conduit (gates)

Structure cable conduit (thimbles)

Gate and thimble not shown

Existing buried conduits to master structure and anode boxes

60243

60243

60243

60243

Guardrail and metal grating not shown

Stoplog guide (typ.)

Gate and thimble not shown

60243

Anode cable galvanized conduit (typ.)

60243

Existing buried conduits to forebay/afterbay side of structure

Existing buried conduits to reservoir side of structure

Existing buried anode and structure conduits from Pipe Inlet Gate Structure

Existing structure and anode cable conduits

Buss bar (typ.)

Shunt (typ.)

Variable resistor

(typ.)

Anode cable (typ.)

Structure cable (typ.)

Anode cable conduits

Structure cable conduits

To master anode bond box

To master structure bond box

SCALE: NOT TO SCALE (60242, 60248)

JUNCTION BOX DETAIL60245

Structure header cableAnode header cable

SCALE: NOT TO SCALE

C

IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM

Anode cable CPVC conduit

(typ.)

AutoCAD SHX Text

ANODES

AutoCAD SHX Text

GATES

AutoCAD SHX Text #1

AutoCAD SHX Text #2

AutoCAD SHX Text #3

AutoCAD SHX Text #4

AutoCAD SHX Text

ANODES

AutoCAD SHX Text #1

AutoCAD SHX Text #2

AutoCAD SHX Text #3

AutoCAD SHX Text #4

D STEP 1. Grind structure connection area (3"x3") to bare shiny metal and clean.

STEP 2. Strip insulation from wire. Attach sleeve.

STEP 3. Hold mold firmly with opening away from operator & ignite with flint gun.

STEP 4. Remove slag from connection and peen weld for soundness.

STEP 5. Cover connection and exposed structure surface with a bituminuus coating compound.

NOTE: Procedure shown above is to be used as a general guide only.

Consult manufacturer's literature for specific installation instructions.

Bond cable or structure cable to junction box

Hold handle

Graphite cover

Starting powder

Metal welding powder

Metal disc

Graphite mold

Cable

Structure

Structure surface

Exothermic weld

Mastic Weld cap

Copper sleeve

Galvanized anode cable conduit

LEGEND - CONDUIT LINEWORK

CPVC anode cable conduit Galvanized structure cable conduit Existing buried and exposed cable conduit

A

LW

A

YS

T H

IN

K

S A

FE

TY

SHEET

D

C

B

A

D

C

B

A

B U

R

EA

U O

F R

EC

LA

M

A

TI

O N

U .S

D

EP

A R

TM

EN

T

O F

TH

E

IN

TE

R

IO

R

C A D

S

YS

TE

M

A ut oC A D

5.

0S

LM

S T

EC

H

C A D

F

IL

EN

A M

E

3- D

-6

-R

D -1

.D W

G

LA

S T

S A V

ED

D A

TE

-1 2-

LA

S T

S A V

ED

B Y

D

LI

TT

LE

¦D_DT¦

¦STATUS¦

C O

LO

R A D

O R

IV

ER

F R O

N T

W O

R K A

N D

L

EV

EE

S

YS

TE

M

W A R R

EN

H

B R O

C K R

ES

ER

V O

IR

PI

PE

I N

LE

T

S

TR

U C

TU

R E

IMPRESSED CURRENT

CATHODIC PROTECTION

SYSTEM

ANODE, CONDUIT, AND

JUNCTION BOX

INSTALLATION DETAILS

DENVER, CO

423-D-60246

DESIGNED

DRAWN

CHECKED

TECH. APPR.

APPROVED

ADMIN APPROVAL

£TT£

£AT£

£AA£

£TA£

Daryl Little

Daryl Little

Avery Schilt

Guardrail and metal grating not shown

Continuity bond cables

SCALE: NOT TO SCALE

PLAN - IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM

Stoplog guide (typ.)

Anode cable galvanized conduit (typ.)

Stoplog guide

Gate and thimble not shown

Guardrail and metal grating not shown

Structure cable conduit (gates)

Structure cable conduit (thimbles)

Gate and thimble not shown

Existing buried conduits to master structure and anode boxes

60243

60243

60243

1. Anodes are to be installed horizontally in slotted PVC impressed current anode conduit with slotted side pointed away from concrete wall or floor towards stoplog guides and gates.

1.1. Anodes shall be installed a minimum of 20 feet and maximum of 30 feet from gates or thimbles.

2. Impressed current anode conduit shall be anchored to concrete wall/floor at each end and twice in the middle with conduit straps and concrete anchors to prevent loss during high flow conditions.

4. Gate and thimble structure connections shall be made in accordance with connection details in sheet

(-60247).

5. Junction box details listed in specification Section 26 42 00.

6. Label front of junction box in accordance with diagram in sheet (-60248).

7. Replace damaged continuity bond cables on stoplog guides.

8. Anode and structure cable conduits shall be anchored to concrete every 5 feet for vertical segments and 10 feet for horizontal segments using conduit straps and concrete anchors or pre-existing Unistrut.

9. CPVC anode conduit shall be anchored to concrete every 2.5 feet to prevent loss during high flow conditions.

10. Cable identification for all cables terminating in junction boxes and bond boxes in accordance with detail.

Cover cable I.D. with clear heat-shrink tubing.

11. Cathodic protection system components are not to scale for visualization.

NOTES

IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM

FOREBAY/AFTERBAY GENERAL LAYOUT.....................................................423-D-60242 ANODE, CONDUIT, AND JUNCTION BOX INSTALLATION DETAILS.................423-D-60243 GATE AND THIMBLE STRUCTURE CONNECTION DETAILS.............................423-D-60247 CONDUIT LINE DIAGRAM AND MASTER BOND BOX DETAILS........................423-D-60248

REFERENCE DRAWINGS

MATERIAL EXPLANATION

Item Description

Junction box NEMA 3R junction box, 12"H x 12"W x 6"D (sized for number and size of cables)

Continuity bond cable #6 AWG or larger stranded copper with HMWPE sheathing (black)

Structure cable #6 AWG or larger stranded copper with HMWPE sheathing (black)

Structure header cable

#6 AWG or larger stranded copper with HMWPE sheathing (black)

Impressed current anode cable

#10 AWG or larger stranded copper with HMWPE sheathing (red if available)

Anode header cable #6 AWG or larger stranded copper with HMWPE sheathing (black)

Impressed current anode

De Nora LIDA mixed metal oxide tubular anode 3.1/122 (1.22" x 48"); or equal, with factory-installed cable

Impressed current anode conduit

2" diameter minimum, schedule 80 PVC with slot pattern, see (-60243)

Concrete conduit anchors

16" dia x 2 14" long Tapcon+ or equal

Conduit straps Stainless steel, sized for diameter of conduit

Anode cable conduit 1" diameter minimum, schedule 80 CPVC (below typical water elevations)

Anode cable conduit 1" diameter minimum, galvanized RMC or flexible conduit (above typical water elevations) Structure cable conduit 1" diameter minimum, galvanized RMC or flexible conduit

Exothermic weld mold CS-36 type mold #M-144 manufactured by ThermOweld; or equal

Exothermic weld metal

15CP weld metal manufactured by ThermOweld; or equal

Exothermic weld cap Ci themOcap PC manufactured by ThermOweld; or equal

Anode cable galvanized conduit

Buss bar (typ.)

Shunt (typ.)

Variable resistor

(typ.)

Anode cable (typ.)

Structure cable (typ.)

Anode cable conduits

Structure cable conduits

To master anode bond box

To master structure bond box

SCALE: NOT TO SCALE

CABLE IDENTIFICATION DETAIL

SCALE: NOT TO SCALE

EXOTHERMIC WELD DETAIL

SCALE: NOT TO SCALE (60242, 60248)

JUNCTION BOX DETAIL

60246

Cable identification (cable # or structure I.D.)

Cable lead Ring terminal (as required)

CABLE #XX

Cover I.D. label with clear heat-shrink tubing

Structure header cableAnode header cable

SCALE: NOT TO SCALE

D

IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM

Anode cable CPVC conduit (typ.)

Anode cable CPVC conduit

AutoCAD SHX Text

ANODES

AutoCAD SHX Text

GATES

AutoCAD SHX Text #1

AutoCAD SHX Text #2

AutoCAD SHX Text

ANODES

AutoCAD SHX Text #1

AutoCAD SHX Text #2

G F

E

F

E

G

LEGEND - CONDUIT LINEWORK

Galvanized structure cable conduit CPVC structure cable conduit

A

LW

A

YS

T H

IN

K

S A

FE

TY

SHEET

D

C

B

A

D

C

B

A

B U

R

EA

U O

F R

EC

LA

M

A

TI

O N

U .S

D

EP

A R

TM

EN

T

O F

TH

E

IN

TE

R

IO

R

C A D

S

YS

TE

M

A ut oC A D

5.

0S

LM

S T

EC

H

C A D

F

IL

EN

A M

E

3- D

-6

-R

D -1

.D W

G

LA

S T

S A V

ED

D A

TE

-1 2-

LA

S T

S A V

ED

B Y

D

LI

TT

LE

¦D_DT¦

¦STATUS¦

C O

LO

R A D

O R

IV

ER

F R O

N T

W O

R K A

N D

L

EV

EE

S

YS

TE

M

W A R R

EN

H

B R O

C K R

ES

ER

V O

IR

IN

LE

T/

O U

TL

ET

N O

1, N O

2, T R A N

S

IT

IO

N

TR

A S H

R A C K /G

A

TE

A N

D P

IP

E

IN

LE

T S

TR

U C

TU

R

ES

IMPRESSED CURRENT

CATHODIC PROTECTION

SYSTEM

GATE AND THIMBLE

STRUCTURE

CONNECTION DETAILS

DENVER, CO

423-D-60247

DESIGNED

DRAWN

CHECKED

TECH. APPR.

APPROVED

ADMIN APPROVAL

£TT£

£AT£

£AA£

£TA£

Daryl Little

Daryl Little

Avery Schilt

SCALE: NOT TO SCALE

PROFILE - PIPE INLET STRUCTURE

SCALE: NOT TO SCALE

E

GATE CABLE CONNECTION DETAIL

SCALE: NOT TO SCALE

PROFILE - TRANSITION/TRASHRACK/GATE STRUCTURE AND INLET/OUTLET STRUCTURES

SCALE: NOT TO SCALE

F

THIMBLE CABLE CONNECTION DETAIL

MATERIAL EXPLANATION

Item Description

Structure cable #6 AWG or larger stranded copper with HMWPE sheathing (black)

Structure cable conduit

1" diameter minimum (sized for number of cables), galvanized RMC or flexible conduit (for cables from structures to junction boxes)

Concrete conduit anchors

16" dia x 2 14" long Tapcon+ or equal

Conduit straps Stainless steel, sized for diameter of conduit

Isolation washer Phenolic or epoxy glass sized for the anchor bolts

Isolation sleeve Mylar, polyethylene, phenolic, or epoxy glass sized for the anchor bolts and holes

1. Anchor bolt installation details in accordance with drawings and Specification sections 26 42 00 and 35 23 11.

2. All anchor bolts attaching the gate frame to the thimble shall be isolated from the frame using isolation sleeves and washers.

3. One of the isolated anchor bolts connected to each thimble shall be used for the structure cable connection in accordance with the connection detail F. All other gate frame/thimble bolts shall follow general isolation detail G.

4. One of the non-isolated anchor bolts connected to each gate frame shall be used for the structure cable connection in accordance with the connection detail E.

5. Structure cable conduits shall be anchored to concrete every 5 feet for vertical segments and 10 feet for horizontal segments using conduit straps and concrete anchors or pre-existing Unistrut.

6. Cathodic protection system components are not to scale for visualization.

SCALE: NOT TO SCALE

G

GENERAL BOLT ISOLATION DETAIL

120" X 120" STAINLESS STEEL SLIDE GATE

INSTALLATION-SECTIONS......................................................................423-D-60240

120" X 84" STAINLESS STEEL SLIDE GATE

INSTALLATION-SECTIONS......................................................................423-D-60241

REFERENCE DRAWINGS

Thimble and gate structure cables galvanized conduits

Guardrail and metal grating not shown

Embedded cast iron thimble

Stainless steel gate frame Stainless steel gate frame

Grout

Gasket

Stainless steel stud anchor, see (-60240 and -60241)

Structure cable w/ crimped tongue ring connector

To gate structure conduit

Stainless steel stud anchor, see (-60240 and -60241)

Structure cable w/ crimped tongue ring connector

To thimble structure conduit

Isolation washer

Isolation sleeve

Guardrail…

This is the start of the file's text. The full file is on GovTribe.