ATTACHMENT 2 - DRAWINGS.pdf
PDF 14 MB Posted
- Attached to
- IFB to Add Alter Building 208
- Solicitation number
- W50S6Q24B0001
- Issued by
-
Department of the Army National Guard
About this file
This document appears to be Attachment 2 - Drawings related to Solicitation Number W50S6Q24B0001 for the IFB to Add Alter Building 208. The solicitation is issued by the Department of the Army National Guard to award a single firm fixed-price contract for services to renovate 14,193 SF of Building 208 and add an additional 3,000 SF at the 188th Wing in Fort Smith, Arkansas. The contract duration is expected to be 365 calendar days after notice to proceed. This project is set aside 100% for Woman Owned Small Businesses (WOSB), with a NAICS code of 236220 (Commercial and Institutional Building Construction) and a small business size standard of $45,000,000. The magnitude of construction is between $5,000,000 and $10,000,000. The pre-bid conference will be held on June 17, 2024, followed by a site visit. Bids are due by July 23, 2024. Offerors must be registered in the System for Award Management (SAM). The solicitation includes a limitation on subcontracting, whereby the prime contractor cannot pay more than 85% of the contract amount to subcontractors that are not similarly situated entities.
View the file
Other files
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Digitally signed by Jose G Matute
DN: CN=Jose G Matute, dnQualifier=A01410D00000189 41F5A4C900016D90,O=Gurri
Matute PA, C=US Date: 2024.05.14
17:36:51-04'00'
T ectonic Cop yright 2007
1 2 3 4 5 6 7 8 9 10 11 12 13 14
AA
Bx
C
F
K
L
EE
B
D
H H
J
H.1
10.3 11.7 12.7
(6 EQ SPACES)
31' - 0"
(4 EQ SPACES)
19' - 4"
(4 EQ SPACES)
19' - 4"
(6 EQ SPACES)
34' - 4"
104' - 0"
W18X40 W18X40
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
FACE OF CMU FACE OF CMU
W
X
1/ 8"
3'
W18X40 W21X50
D.B. ELEV. =
+11'-10" A.F.F.
D.B. ELEV. =
+13'-0 5/8" A.F.F.
S-501
S-501
S-501
S-501
S-501
S-501
S-501
0.
5:
0.
5:
S-501
S-602
SIM
10.2
(F
IE
LD
V
E R
IF
Y
/8
W
X
4' - 8"
5k 5k
B.O.S. = +8'-6" A.F.F.
EXISTING REINFORCED CONCRETE VAULT
LID TO BE CORE DRILLED TO ACCOMODATE
MECHANICAL, ELECTRICAL, PLUMBING AND
FIRE PROTECTION PENETRATIONS, SEE
2/S-102 FOR CORE DRILLING REQUIREMENTS
OPENING FOR ROOF ACCESS
HATCH, SEE 10/S-501 FOR
SUPPORT FRAME AND COORD
w/ ARCH FOR EXACT LOCATION
9k
9k
C J
CJCJCJCJCJ
C J
EXIST EXIST EXIST
23k
9k 9k 9k 9k 9k 9k 9k 9k 9k 9k 9k 9k
23k 15k 15k 26k 26k
9k 9k 9k 9k 9k
9k 9k 9k 9k 9k 9k 9k 9k 9k 9k 9k 9k 9k 9k 9k 9k 9k 9k9k
15k 15k
TYP
1' - 4"
S-102
S-102
(2) L4x4x1/4 BEAM
BRACE, TYP OF 3
DOAS-1
(750 LB),
REF MECH.
HSS4x4x1/4, TYP, HANG FROM
WITHIN 2" OF JOIST PANEL
POINT W/ MIN. 1/2"Ø ALLTHREAD
C J
C J
INDICATES SPAN DIRECTION OF
METAL DECK, SEE 1/S-501
INDICATES WELDED MOMENT
CONNECTION, SEE 4/S-501
W00X00
INDICATES WIDE FLANGE BEAM SIZE (A992)
0k 0k INDICATES MAXIMUM FACTORED END
REACTION IN KIPS
FRAMING LEGEND
INDICATES EXISTING BUILDING
TO REMAIN
± INDICATES DIMENSION TO BE
FIELD VERIFIED BY CONTRACTOR
INDICATES L4x4x5/16 WALL BRACE, SEE 9/S-501
INDICATES FRAMED OPENING IN
ROOF DECK, SEE 10/S-501
LARGER CORE DIA
MIN CTR TO CTR
SPACING = 1.5 MIN 2'-0" 8" +/-
CL CORECL CORE
3" 6"
C E
N T
E R
S 3"
MAX CORE DIA
1' - 2"
EXTEND REINF 6" PAST
EDGE OF CORE, TYP EA END
1/2" Ø x 4" NOMINAL EMBEDMENT
CONCRETE SCREW ANCHORS
PROVIDE L6x4x5/16 (LLV) ON EA
SIDE OF CORES THAT ARE
GREATER THAN 1'-0" IN DIAMETER
ANGLES SHALL RUN PLAN NORTH-
SOUTH (SHORT DIRECTION OF
VAULT), NO EXCEPTIONS
INSIDE FACE OF CONCRETE
WALL BELOW
OUTSIDE FACE OF LID EDGE
ROOF
14' - 3 1/2"
AE
T.O.COLUMN
13'-5"
B.O.BEAM
REF PLAN
L8x4 x 0'-6" W/ (1) 1/2"Ø
THRU BOLT IN 2" VERT.
SLOTTED HOLE
1/8
ANGLE
TO FRMG
L3x3x1/4
COLUMN
BRACE, TYP
1/8
EA. END
BEAM,
REF PLAN
COLUMN, REF
PLAN, TYP
EXIST.
JOIST, TYP
ROOF
14' - 3 1/2"
10 10.2
S-501
9 SIM,
TYP
ANGLES, REF
PLAN FOR SIZE
AND LOCATION
NEW BEAM,
REF PLAN
PROFESSIONAL
REGISTERED
ARKANSAS
ENGINEER
No. 21880
S T A T E O F
B L
A K
E
O R I E H O L L I N
G S
H E
A D
Project Number:
Designed By: Approved By:
Drafted By: Date:
Scale:
HKRZ222111
F o rt S m it h A rk an sa s
R E
V
D E
S C
R
IP
T
IO
N B
Y D
A T
E
8t h W in g
A rk an sa s
A ir
N at io na l G ua rd th
C iv il E n gi n ee r S q u ad ro n
L ei g h
A v e, F or t
S m it h
, A R
P h on e:
-5
3-
G U
R R
I M
A T
U T
E P
A
S
W th
C o u rt
S u it e
M ia m i F lo ri d a
T
F w w w .g u rr im a tu te .c o m
A R
C H
IT
E
C T
C R
O M
W E
L L
A R
C H
IT
E
C T
S E
N G
IN
E
E R
S
E a s t th
S tr e e t
L itt le R o c k A
R
T w w .c ro m w e ll.
c o m
E N
G
IN
E E
R
P R
IM
E
C O
N R
T R
A C
T H
O L D
E R
B U
IL
D
IN
G
A
D D
/A L
T E
R
R E
N O
V A
T
IO
N
AS NOTED
S-102
02-19-2024
MJ BH
SM
R O
O F
F R
A M
I N
G P
L A
N
02020202−−−−19191919−−−−2024202420242024
1/8" = 1'-0"
1 ROOF FRAMING PLAN
SCALE : 1/8" = 1'-0"
0 4 8 16
N
FINISHED FLOOR ELEV = 0'-0" (ASSUMED, SEE CIVIL FOR ACTUAL)
1" = 1'-0"
2 TYP OPENING IN EXISTING CONCRETE VAULT LID
A d d e n d u m
-1 -2
1/2" = 1'-0"
3 SECTION AT MOVEABLE PARTION WALL
1/2" = 1'-0"
4 SECTION AT BEAM BRACE
10.3
GRADE BEAM STEP,
SEE 7/S-301
SLAB ON GRADE,
SEE 1/S-301
1/2" ISOLATION JOINT
FILLER w/ SEALANT
CONT #4
#4 DOWEL
AT 48" O.C.
1'-6"
2'-8"
#4 DOWEL
AT 48" O.C.
1'-6"
2'-8"
1' - 0"
MIN
1' - 3"
1 1/2" NON-SHRINK
GROUT
CFS STUDS
HSS COLUMN,
SEE PLAN
1/2" ISOLATION JOINT
FILLER w/ SEALANT
CONT #4
SLAB ON GRADE,
SEE 1/S-301
CONC BLOCKOUT
BASE PLATE AND ANCHOR
RODS, SEE 2/S-302
INCREASE SIZE OF BLOCKOUT
AS REQ'D FOR CLEARANCE OF
BASE PLATES
RAISED COMPUTER FLOOR
NOT SHOWN FOR CLARITY
VARIES - SEE PLAN
FINISHED FLOOR
1'
1'
2'
12.7
GRADE BEAM STEP,
SEE 7/S-301
#4 DOWEL
AT 48" O.C.
1'-6"
2'-8"
1/2" ISOLATION JOINT
FILLER w/ SEALANT
CONT #4
SLAB ON GRADE,
SEE 1/S-301
CONC BLOCKOUT
BASE PLATE AND ANCHOR
RODS, SEE 2/S-302
INCREASE SIZE OF BLOCKOUT
AS REQ'D FOR CLEARANCE OF
BASE PLATES1' - 0"
MIN
1' - 3"
8" CMU, SEE 1/S-601
SLAB ON GRADE,
SEE 1/S-301
1/2" ISOLATION JOINT
FILLER w/ SEALANT
CONT #4
#4 DOWEL
AT 48" O.C.
1'-6"
2'-8"
1 1/2" NON-SHRINK GROUT
RAISED COMPUTER FLOOR
NOT SHOWN FOR CLARITY
VARIES - SEE PLAN
FINISHED FLOOR
1'
8" 1'
2'
12.7
8" 8" 8"
GB24A : 2' - 0"
NOTE:
FOR REINF,
SEE 1/S-304
4"
1/2" ISOLATION JOINT
FILLER w/ SEALANT
CONT #4
#4 DOWEL
AT 48" O.C.
1'-6"
3'-0"
CONT (4) #4
#4 DOWEL AT
24" O.C. CTR'D
IN STEM WALL
w/ STANDARD
HOOK AT ONE
END
8" CMU, SEE
1/S-601
8"
RAISED COMPUTER FLOOR
NOT SHOWN FOR CLARITY
VARIES - SEE PLAN
FINISHED FLOOR
2'
1'
2'
NOTE:
FOR REINF AT GRADE
BEAM T-INTERSECTIONS,
SEE 6B/S-301
10.3
8" 8" 8"
GB24A : 2' - 0"
NOTE:
FOR REINF AT GRADE
BEAM T-INTERSECTIONS,
SEE 6B/S-301
4" CFS STUDS
1/2" ISOLATION JOINT
FILLER w/ SEALANT
CONT #4
8"
#4 DOWEL
AT 48" O.C.
1'-6"
2'-4"
CONT (3) #4
#4 DOWEL AT 24" O.C.
CTR'D IN STEM WALL
w/ STANDARD HOOK AT
ONE END
RAISED COMPUTER FLOOR
NOT SHOWN FOR CLARITY
VARIES - SEE PLAN
FINISHED FLOOR
1'
1'
2'
CONT (3) #8 T&B
#3 TIES AT 12" O.C.
CONT #8 EA FACE
NOTE:
FOR REINF,
SEE 1/S-304
10.2 8 1/2"
EXISTING SLAB
ON GRADE
1'
1' - 0" +/-
EXISTING EDGE
OF SLAB STEP
EXISTING SLAB
ON GRADE
BASE PLATE,
SEE 2/S-302
(4) 3/4" DIA x 4" NOMINAL
EMBEDMENT CONCRETE
SCREW ANCHORS
HSS COLUMN,
SEE PLAN
EXISTING FINISHED
FLOOR ELEV 0'-0"
PROFESSIONAL
REGISTERED
ARKANSAS
ENGINEER
No. 21880
S T A T E O F
B L
A K
E
O R I E H O L L I N
G S
H E
A D
Project Number:
Designed By: Approved By:
Drafted By: Date:
Scale:
HKRZ222111
F o rt S m it h A rk an sa s
R E
V
D E
S C
R
IP
T
IO
N B
Y D
A T
E
8t h W in g
A rk an
N at io na l G th
C iv il E n gi n ee r S q u ad ro n
L ei g h
A v e, F or t
S m it h
, A R
P h on e:
-5
3-
R R
I M
A T
U T
E P
A
S
W th
C o u rt
S u it e
M ia m i F lo ri d a
T
F w w w .g u rr im a tu te .c o m
A R
C H
IT
E
C T
C R
O M
W E
L L
A R
C H
IT
E
C T
S E
N G
IN
E
E
E a s t th
S tr e e t
L itt le R o c k A
R
T w .c ro m w e ll.
c o m
E N
G
IN
E E
R
P R
IM
E
C O
N R
T R
A C
T H
O L D
E R
B U
IL
D
IN
G
A
D D
/A L
T E
R
R E
N O
V A
T
IO
N
AS NOTED
S-304
02-19-2024
MJ BH
SM
F O
U N
D A
T I O
N S
E C
T I O
N S
A N
D D
E T
A I L
S
02020202−−−−19191919−−−−2024202420242024
1" = 1'-0"
3 SECTION THRU SLAB STEP ALONG '10.3' @ COLUMN
1" = 1'-0"
4 SECTION THRU SLAB STEP ALONG '12.7' @ COLUMN
1" = 1'-0"
2 SECTION THRU SLAB STEP ALONG '12.7'
1" = 1'-0"
1 SECTION THRU SLAB STEP ALONG '10.3'
1" = 1'-0"
5 SECTION THRU OPERABLE PARTITION SUPPORT COLUMN
SCALE : 1" = 1'-0"
0 6" 1' 2'
SCALE : 1" = 1'-0"
0 6" 1' 2'
SCALE : 1" = 1'-0"
0 6" 1' 2'
SCALE : 1" = 1'-0"
0 6" 1' 2'
SCALE : 1" = 1'-0"
0 6" 1' 2'
A d d e n d u m
-1 -2
BRICK VENEER,
SEE ARCH
ROOF DECK,
SEE 1/S-501
CONT GALV L4x4x5/16
EDGE ANGLE
BEAM, SEE PLAN
TOP OF PARAPET ELEV.
+14'-4" A.F.F.
8" CMU BOND
BEAM
BOND BEAM ELEV.
+10'-8" A.F.F.
MASONRY BRICK
TIES AT 16" O.C.
8" CMU, SEE 1/S-601
8" CMU BOND
BEAM
INTERIOR FURRING,
SEE ARCH
BOND BEAM ELEV.
+12'-8" A.F.F.
8" CMU BOND
BEAM
1/2"ØX5" GALV. EMBED.
CONCRETE SCREW ANCHOR
@ 48"O.C. MAX. IN GROUTED
CELLS
D.B. ELEV.
SEE PLAN
FOR ADD'L BRG INFO,
SEE 2A & B/S-602
ISOMETRIC AT TYP SIDE LAP
A
#10x3/4" SELF DRILLING
SCREWS BETWEEN
SUPPORTS EVENLY SPACED
(3 MIN AT 36" O.C. MAX.)
TYP DECK FASTENING PATTERN PLAN
B
TOP OF SUPPORT
#10x3/4" SELF-DRILLING
SCREWS AT 6" O.C. AT EVERY
RIB AT EACH SUPPORT w/
36/7 PATTERN
CL SUPPORT (DECK SHALL
BE CONT. OVER THREE
SUPPORTS MIN.)
#10x3/4" SELF-
DRILLING SCREWS
AT 6" O.C.
PROVIDE FULL
RIB WIDTH
SIDELAP CONN. BETWEEN
SUPPORTS SEE 1B/S-501
SEE 1C/S-501 FOR
SECTION PROPERTIES
NOTES:
1.SECTION PROPERTIES SHOWN MAY VARY 10%.
2. DECK Fy = 33 ksi MIN.
SECTION PROPERTIES
1. EDGES OF SHEET SHALL BE COMPLETELY ENGAGED.
2. DECK GALVANIZING SHALL CONFORM TO ASTM a653 G60
C
LOCATION GAGE
(IN )
FT.
GALVANIZED
WEIGHT
LBS./SQ. FT.DIAPHRAGM
SHEAR VALUE
SnSpI
CL SUPPORT
PERIMETER EDGE
ANGLE OR SUPPORT
PERIMETER
SUPPORT
DEPTH
CL SUPPORT
#10x3/4" SELF-
DRILLING SCREWS
AT 6" O.C.
(IN )
FT.
(IN )
FT.
1.5B DECK
20 PLF AT 6'-0" SPAN 2.14 0.211 0.234 0.2471.5"ROOF DECK
3' - 0"
2 1/2" 3 1/2"
1/
2"
H.1
GAP
1"
STEEL BEAM,
SEE PLAN
(FIELD VERIFY)
1' - 9"
FACE OF EXIST
BUILDING
D.B. ELEV.
SEE PLAN
ROOF DECK, SEE 1/S-501
CONT GALV
L4x4x5/16 EDGE
ANGLE
(2) 3/8" STIFFENER
PLATES, EA SIDE
1/4
1/4 TYP BOTH
SIDES
SHOP FABRICATED SEAT:
PLATE THICKNESS AND
WIDTH TO MATCH BEAM
FLANGE. STEEL GRADE OF
PLATE TO MATCH BEAM
3 1/2" (MIN)
10"
5" (MIN), TYP
ALONG GRID
3/16
1/4
1/4
H.1
ROOF DECK, SEE 1/S-501
STEEL BEAM,
SEE PLAN
HSS COLUMN,
SEE PLAN
NOTE:
PERPENDICULAR GIRDER
AND CONNECTION NOT
SHOWN FOR CLARITY
COLUMN CAP
PLATE, SEE 4/S-501
GAP
1"
(FIELD VERIFY)
1' - 9"
FACE OF EXIST.
BUILDING
D.B. ELEV.
SEE PLAN
3/16
3 1/2" (MIN)
10"
1/4
1/4 TYP BOTH
SIDES
1/4
1/4
REF
FOR INFO NOT
SHOWN
/6 S-501
BRICK VENEER,
SEE ARCH
8" CMU, SEE 1/S-601
ROOF DECK,
SEE 1/S-501
L6x4x5/16 (LLV)
EDGE ANGLE
TOP OF PARAPET ELEV.
+14'-4" A.F.F.
8" CMU BOND
BEAM
MASONRY BRICK
TIES AT 16" O.C.
8" CMU BOND
BEAM
G R
O U
T S
O
LI
D
BOND BEAM ELEV.
+11'-4" A.F.F.
INTERIOR FURRING,
SEE ARCH
1/2"ØX5" EMBED.
CONCRETE SCREW
ANCHOR @ 48"O.C. MAX.
IN GROUTED CELLS
L4x4x5/16 @ 48"O.C. MAX.
FASTEN DECK TO
SUPPORTS @ 6"O.C. MAX.
w/ FASTENERS PER 1/S-501
3/16 3"
TYP
STEEL BEAM,
SEE PLAN
D.B. ELEV.
VARIES
PLATE 3/8x6 x 0'-6"
3/16
3/16
3/16 3"
3/16 3"
ALL AVAIL
C
SINGLE PLATE, SEE SCHEDULE
FOR THICKNESS AND NUMBER
OF BOLTS. USE SSL HORIZ.
TYP.
MIN. FILLET
WELD SIZE
SINGLE-PLATE CONNECTION DETAIL
3W14
BEAM SIZE
GIRDER, SEE PLAN
MIN. PLATE
THICKNESS
BEAM, SEE PLAN
L OF GIRDER
38.3k
CAPACITY
NOTES:
1. CAPACITY IS BASED ON LRFD DESIGN WITH STANDARD OR SHORT HORIZONTAL
SLOTTED HOLES. OVERSIZE OR VERTICAL SLOTTED HOLES ARE NOT ALLOWED.
FOR STANDARD HOLES MINIMUM PLATE THICKNESS SHALL BE USED.
2. NUMBER OF BOLTS SHOWN IS THE MINIMUM REQUIRED FOR CONNECTIONS
3. PREHEAT WELDS AS REQUIRED BY AISC.
4. BEAMS WITH LARGE COPES MAY REQUIRE WEB STIFFENER.
1/4" 3/16"
3" MAX.
M
IN
1/ 4"
M
IN
1/ 4"
3" C
E N
T E
R S
1 1/4" MIN.
1 1/2" MIN.
1/2"
BOLT SCHEDULE
NUMBER OF 3/4" Ø
H.S. BOLTS
AISC 14TH EDITION
SEE SCHEDULE
BEAM, SEE PLAN
HSS COLUMN, SEE PLAN
SINGLE-PLATE CONNECTION.
SEE SCHEDULE FOR THICKNESS
AND NUMBER OF BOLTS.
3" MAX
MIN
1 1/4"
MIN.
1 1/2"
MIN. FILLET
WELD SIZE
SINGLE-PLATE CONNECTION DETAIL
BEAM SIZE
MIN. PLATE
THICKNESS
CAPACITY
NOTES:
1. CAPACITY IS BASED ON LRFD DESIGN WITH STANDARD OR SHORT HORIZONTAL
SLOTTED HOLES AND A MAXIMUM HSS WIDTH TO THICKNESS RATIO OF 33.7.
OVERSIZE OR VERTICAL SLOTTED HOLES ARE NOT ALLOWED. FOR STANDARD
HOLES MINIMUM PLATE THICKNESS SHALL BE USED.
2. NUMBER OF BOLTS SHOWN IS THE MINIMUM REQUIRED FOR CONNECTIONS
3. PREHEAT WELDS AS REQUIRED BY AISC.
4. USE STANDARD HOLES ALONG BRACED FRAME OR MOMENT FRAME GRID LINES.
BOLT SCHEDULE
NUMBER OF 3/4" Ø
H.S. BOLTS
AISC 14TH EDITION
M
IN
1/ 4"
3" C
E N
T E
R S
M
IN
1/ 4"
SEE SCHEDULE
W21
W18
W16 4
5/16" 1/4"
5/16" 1/4"
1/4" 3/16"
80.2k
89.1k
52.0k
MOMENT CONN.
BEAM, SEE PLAN
HSS COLUMN, SEE PLAN
PLAN MARKS, TYP
TYP. T&B FLANGES
TYPICAL BEAM,
SEE PLAN
SHEAR CONN.,
SEE 2/S-501
COLUMN CAP PLATE,
MATCH THICKNESS AND
GRADE OF BEAM FLANGES
12.7
ROOF DECK,
SEE 1/S-501
STEEL BEAM,
SEE PLAN
8" CMU, SEE 1/S-601
STEEL BEAM,
SEE PLAN
SLOPED 8" CMU BOND
BEAM, SLOPE OF BOND
BEAM TO MATCH SLOPE
OF ROOF
L4x4x5/16 WALL BRACE
AT 48" O.C. ALONG
WALL'S LENGTH
1/4 AVAIL
1/4 ALL
TYP
3/16 3" MIN
TYP
INTERIOR FURRING,
SEE ARCH
(2) 1/2" DIA x 5" EMBED. CONCRETE
SCREW ANCHOR AT EA BRACE.
INSTALL IN GROUTED BOND BEAM
STORAGECOMMS
G A
P 2"
L6x4x5/16 (LLH) x 0'-6" LONG AT
EA BRACE
6"
6"
PLATE 3/8x6 x 0'-6" A
SECTION
B
PLAN
L5x5x3/8 - 0'-7" CLIP ANGLE
WELD TO BM OR JOIST
BEAM, SEE PLAN
L5x3x5/16 (LLV) WELD
TO CLIP ANGLE
FOR OPENING SIZE AND LOCATION
SEE ARCH, OR MECH DRAWINGS
BEAM, SEE PLAN
(APPLIES WHERE 9"<W<24")
CL BEAM
L5x3x5/16 (LLV)
W
1/4
TYP EA LEG
1/4
TYP EA LEG
3/16
TYP
OPEN
CL BEAM
PROFESSIONAL
REGISTERED
ARKANSAS
ENGINEER
No. 21880
S T A T E O F
B L
A K
E
O R I E H O L L I N
G S
H E
A D
Project Number:
Designed By: Approved By:
Drafted By: Date:
Scale:
HKRZ222111
F o rt S m it h A rk an sa s
R E
V
D E
S C
R
IP
T
IO
N B
Y D
A T
E
8t h W in g
A rk an
N at io na l G th
C iv il E n gi n ee r S q u ad ro n
L ei g h
A v e, F or t
S m it h
, A R
P h on e:
-5
3-
R R
I M
A T
U T
E P
A
S
W th
C o u rt
S u it e
M ia m i F lo ri d a
T
F w w w .g u rr im a tu te .c o m
A R
C H
IT
E
C T
C R
O M
W E
L L
A R
C H
IT
E
C T
S E
N G
IN
E
E
E a s t th
S tr e e t
L itt le R o c k A
R
T w .c ro m w e ll.
c o m
E N
G
IN
E E
R
P R
IM
E
C O
N R
T R
A C
T H
O L D
E R
B U
IL
D
IN
G
A
D D
/A L
T E
R
R E
N O
V A
T
IO
N
AS NOTED
S-501
02-19-2024
MJ BH
SM
R O
O F
F R
A M
I N
G S
E C
T I O
N S
A N
D D
E T
A I L
S
02020202−−−−19191919−−−−2024202420242024
1" = 1'-0"
5 TYP BEAM BRG AT CMU DETAIL
NOT TO SCALE
1 TYP 1.5B ROOF DECK ANCHORAGE
1" = 1'-0"
6 TYP BEAM BRG AT GIRDER DETAIL
1" = 1'-0"
7 TYP BEAM BRG AT COLUMN DETAIL
1" = 1'-0"
8 TYP BEAM PARALLEL TO CMU DETAIL
NOT TO SCALE
3 TYP SINGLE PLATE BEAM TO GIRDER CONN
NOT TO SCALE
2 TYP BEAM TO HSS COLUMN CONN
NOT TO SCALE
4 TYP BEAM TO HSS COLUMN MOMENT CONN
1" = 1'-0"
9 CMU WALL AT STEEL BEAM
1" = 1'-0"
10 TYPICAL FRAMING AT ROOF OPENING
SCALE : 1" = 1'-0"
0 6" 1' 2'
SCALE : 1" = 1'-0"
0 6" 1' 2'
SCALE : 1" = 1'-0"
0 6" 1' 2'
SCALE : 1" = 1'-0"
0 6" 1' 2'
SCALE : 1" = 1'-0"
0 6" 1' 2'
SCALE : 1" = 1'-0"
0 6" 1' 2'
A d d e n d u m
-1
-2
DN: CN=Jose G Matute, dnQualifier=A01410D000001894
1F5A4C900016D90,O=Gurri Matute PA, C=US Date: 2024.05.10
18:50:29-04'00'
DN: CN=Jose G Matute, dnQualifier=A01410D0000018
941F5A4C900016D90, O=Gurri Matute PA, C=US
18:50:06-04'00'
DN: CN=Jose G Matute, dnQualifier=A01410D00000189 41F5A4C900016D90,O=Gurri
Matute PA, C=US
18:49:40-04'00'
DN: CN=Jose G Matute, dnQualifier=A01410D00000189 41F5A4C900016D90,O=Gurri
Matute PA, C=US
18:48:52-04'00'
DN: CN=Jose G Matute, dnQualifier=A01410D00000189 41F5A4C900016D90,O=Gurri
Matute PA, C=US
18:50:54-04'00'
DN: CN=Jose G Matute, dnQualifier=A01410D00000189 41F5A4C900016D90,O=Gurri
Matute PA, C=US
18:49:14-04'00'
DN: CN=Jose G Matute, dnQualifier=A01410D00000189 41F5A4C900016D90,O=Gurri
Matute PA, C=US
18:48:24-04'00'
DN: CN=Jose G Matute, dnQualifier=A01410D0000018
941F5A4C900016D90, O=Gurri Matute PA, C=US
Date: 2024.05.14 07:45:36-04'00'
DN: CN=Jose G Matute, dnQualifier=A01410D00000189 41F5A4C900016D90,O=Gurri
Matute PA, C=US
18:47:32-04'00'
DN: CN=Jose G Matute, dnQualifier=A01410D00000189 41F5A4C900016D90,O=Gurri
Matute PA, C=US
18:47:05-04'00'
DN: CN=Jose G Matute, dnQualifier=A01410D0000018
941F5A4C900016D90, O=Gurri Matute PA, C=US
18:46:36-04'00'
DN: CN=Jose G Matute, dnQualifier=A01410D00000189 41F5A4C900016D90,O=Gurri
Matute PA, C=US
18:46:07-04'00'
DN: CN=Jose G Matute, dnQualifier=A01410D00000189 41F5A4C900016D90,O=Gurri
Matute PA, C=US
18:45:33-04'00'
ABORT SWITCH
CARBON DIOXIDE
CLEAN AGENT
DELUGE SPRINKLER
DRY CHEMICAL
EMERGENCY POWER OFF
FOAM
HALON
PREACTION SYSTEM
WATER MIST
WET CHEMICAL
AS
CO2
CA
DL
DC
EPO
F
HL
PRE
WM
WC
AMPLIFIER RACK
AUTONOMOUS CONTROL UNIT
BATTERY CABINET
COMBI. FIRE ALARM/MASS NOTIFICATION CONTROL
DIGITAL ALARM COMMUNICATOR TRANSMITTER
FIRE ALARM ANNUNCIATOR
FIRE ALARM CONTROL
FIRE SUPPRESSION CONTROL
GRAPHIC ANNUNCIATOR
LCD ANNUNCIATOR
LOCAL OPERATORS CONTROL WITH FIRE ALARM
ANNUNCIATOR
NOTIFICATION CIRCUIT POWER BOOSTER
PRE-ACTION SYSTEM
PRINTER
UNINTERRUPTABLE POWER SUPPLY
VOICE EVACUATION
APM
ACU
BATT
FMCP
DACT
FAA
FACP
FSCP
GAP
LCD
LOC
NAC
PRE
PRN
UPS
EVAC
CARBON DIOXIDE
CLEAN AGENT
DELUGE SPRINKLER
DRY CHEMICAL
FOAM
HALON
MANUAL
PULL STATION
WATER MIST
WET CHEMICAL
CO2
CA
DL
DC
F
HL
M P
WM
WC
NIC
PULL STATION TYPE
FIRE ALARM PULL STATION
F
FIRE ALARM ABORT SWITCH
TYPE
FIRE ALARM PANEL TYPE
FIRE ALARM ABORT SWITCH
F
FIRE ALARM CONTROL PANEL
PULL STATION ABBREVIATIONS:
ABORT SWITCH ABBREVIATIONS:
CONTROL PANELS ABBREVIATIONS:
NEW CONSTRUCTION FIRE
EQUIPMENT (TYPICAL TAG FOR ALL
NEW CONSTRUCTION)
FIRE ALARM EQUIPMENT FOR
DEMOLITION (TYPICAL FOR ALL
DEMOLITION TAGS)
EXISTING FIRE ALARM EQUIPMENT
(TYPICAL FOR ALL EXISTING TAGS)
* NOTE *
ALL GENERAL NOTES ON THIS SHEET ARE TO BE APPLIED TO
ALL OTHER DRAWINGS IN THIS SET. SYMBOLS AND ABBREVIATIONS
SHOWN ON THIS SHEET MAY OR MAY NOT BE USED IN THE
CONTAINED REFERENCE DRAWINGS.
OFFICE
SPACE TAG:
GENERAL SYMBOLS
FX001
DEMOLISH TO POINT INDICATED
PIPE CONTINUATION
AREA NOT IN CONTRACT
ITEM TO BE DEMOLISHED
EXISTING
POINT WHERE NEW CONNECTS TO
REVISION NUMBER SHOWN ON PLANS
NUMBER OF DETAIL ON SHEET
APPEARS
NUMBER OF SHEET WHERE DETAIL
KEYED NOTE
FIRE ALARM SHEET SET NOTE
ABBREVIATIONS
EQUIPMENT ABBREVIATIONS
VERY EARLY WARNING SMOKE
DETECTION
UNLESS NOTED OTHERWISE
UNDER SLAB
UNDER GROUND
TYPICAL
TOTAL STATIC PRESSURE
TEMPERATURE
TEMPERATURE DROP
TEMP. CONTROL PANEL
SYSTEM
THERMOSTAT
STANDARD
STAINLESS STEEL
SQUARE
STATIC PRESSURE STATION
STATIC PRESSURE
SLEEVE
SIMILAR
SMOKE DAMPER
SQUARE FOOT
REQUIRED
REDUCER
RECESSED
POTABLE WATER
LBS. PER SQ. IN. GAUGE
LBS. PER SQ. IN.
PRESS. REDUCING VALVE
PRIMARY
PRESSURE SWITCH
PRELIMINARY
PAIR
POST INDICATOR VALVE
PRESSURE DROP
OPENING
OXYGEN
NOT TO SCALE
NOT POTABLE
ASSOCIATION
NATIONAL FIRE PROTECTION
NOT IN CONTRACT
DEMANDING AREA
MOST HYDRAULICALY
MISCELLANEOUS
MINIMUM
MANUFACTURER
MOTORIZED DAMPER
MAXIMUM
MANUAL
MIXED AIR
LOW PRESSURE
LOCATION
LINEAL FOOT
POUNDS PER HOUR
POUND
LABORATORY
JOINT
INSPECTOR TEST CONNECT
INCHES WATER GAUGE
VEWSD
UNO
U/S U/G
TYP
TSP
TEMP
TD
TCP
SYS
T
STD
SS
SQ
SPS
SP
SLV
SIM
SD
SF
REQD
RED
REC
PW
PSIG
PSI
PRV
PRIM
PS
PREL
PR
PIV
PD
OPNG
O
NTS
NP
NFPA
MRA
MISC
MIN
MFR
MD
MAX
MAN
MA
LP
LOC
LF
LB/HR
LB
LAB
JT
ITC
INWG
INSULATION
INLET
INCH
HEATING
HIGH PRESSURE
HEAD
GALLONS PER MINUTE
GENERAL
GENERATOR
GALVANIZED
GALLON
FUTURE
FOOTING
FOOT/FEET
FLANGE
FLEXIBLE
FINS PER INCH
FIRE HOSE VALVE
FIRE HOSE STATION
FIRE DEPARTMENT VALVE
FIRE DAMPER
DEGREES FAHRENHEIT
EXTERNAL STATIC PRESSURE
EXPANSION JOINT
EXPANSION
EXISTING
EXHAUST HOOD
EMERGENCY COMM. SYSTEM
EACH
DRAWING
DOWN
DAMPER
DISCHARGE
DUCTILE IRON
DIAMETER
DOUBLE DETECTOR CK. ASSY.
DETECTOR CHECK ASSY.
DEGREE
CUBIC FEET
CENTER
CONTRACTING OFFICER'S REP.
COORDINATE
CONTINUE/CONTINUATION
CONCRETE
COMBINATION
COLUMN
CEILING
COMMON INTELLIGIBILITY SYS.
CAST IRON
CUBIC FEET PER MINUTE
CONSTANT FLOW CNTRL. VL.
CAPACITY
BETWEEN
BASEMENT
BUTTERFLY VALVE
BELOW FINISHED FLOOR
AUXILLARY DRAIN
AUTOMATIC
ARCHITECT/ARCHITECTURAL
ACCESS PANEL
ALUMINUM
ALARM VALVE
ALTERNATE
AUTHORITY HAVING JURISDICTION
ABOVE GROUND
ABOVE FINISHED FLOOR
ADDITIONAL
ADDENDUM
ACOUSTICAL
ABOVE
ABOVE BASE
AIR
ON ROOF
ROUND
AND
INSUL
INL
IN
HTG
H.P.
GPM
HD
GENL
GEN
GALV
GAL
FUT
FTG
FT
FLG
FLEX
FPI
FHV
FHR
FDV
FD
F°
ESP
EXPJT
EXP
EX
EAH
ECS
EA
DWG
DN
DMPR
DISCH
DI
DIA
DDCA
DCA
D/°
CUFT
CTR
COR
COORD
CONT
CONC
COMB
COL
CEG
CIS
CI
CFM
CFCV
CAP
BTWN
BSMT
BFV
BFF
AUX
AUTO
ARCH
AP
ALUM
ALV
ALT
AHJ
AG
AFF
ADDL
ADD
ACOUS
ABV
AB
A /R Ø
(D)FACP
(E)FACP
FACP
FIRE ALARM PHASING
FIRE ALARM DEVICES
C
S SPEAKER, 0.5 WATTS UNLESS NOTED OTHERWISE
CEILING MOUNT CLEAR STROBE, 15 CANDELA
UNLESS NOTED OTHERWISE
WALL MOUNT CLEAR STROBE, 15 CANDELA
UNLESS NOTED OTHERWISE
WALL MOUNT SPEAKER AND CLEAR STROBE, 15 CANDELA
UNLESS NOTED OTHERWISE, 0.5 WATTS UNLESS NOTED
OTHERWISE
CEILING MOUNT SPEAKER AND CLEAR STROBE, 15 CANDELA
UNLESS NOTED OTHERWISE, 0.5 WATTS UNLESS NOTED
OTHERWISE
F.A. ACCESS PANEL
F.A. MASS NOTIFICATION PNL.
F.A. ANNUNCIATOR PNL.
LOCAL OPERATOR CONSOLE
NON-RISING STEM VALVE
INSPECTOR'S TEST
PANEL
DOMESTIC WATER BOOST PUMP
DETECTOR CHECK ASSY.
DOUBLE DETECTOR CHECK ASSY.
FIRE HOSE STATION
FIRE ALARM
FIRE PUMP
FIRE DEPARTMENT CONTROL
FDCP
FMCP
FAA
LOC
NRSV
ITC
PNL
DBP
DCA
DDCA
FHR
F.A.
FPU
FDC
SPACE NAME
SPACE NUMBER
F
VS
WF
DH
E
AIM
P
S
SYMBOL DESCRIPTION
UV FLAME DETECTOR
DUCT SMOKE DETECTOR
(S-SUPPLY, R-RETURN)
HEAT DETECTOR (RATE OF RISE)
MANUAL PULL STATION (48" AFF UNLESS
NOTED OTHERWISE)
WATER FLOW SWITCH
VALVE SUPERVISORY (TAMPER) SWITCH
ELECTRIC BELL FOR WATER FLOW. INSTALL AT
9'+/- ABOVE FINISHED GRADE OR AS DIRECTED
BY FIRE MARSHAL.
DOOR HOLD OPEN MODULE. PROVIDE FIRE ALARM
LISTED HOLD-OPEN ASSEMBLY IF NOT CALLED
OUT IN DOOR HARDWARE SCHEDULE.
ADDRESSABLE MODULE (AIM - INPUT, AOM -
OUTPUT, AIO - INPUT/OUTPUT)
SPOT-TYPE SMOKE DETECTOR (P-PHOTOELECTRIC,
I-IONIZATION, SB-SOUNDER BASE 520Hz SQUARE WAVE, PRE-PHOTOELECTRIC AND PREACTION SYSTEM ACTIVATION)
SYMBOLS
S
S
0.5W
0.5W
0.5W
LED EMERGENCY MESSAGE TEXT SIGNET
FIRE DEPARTMENT RAPID ENTRY BOX AS
APPROVED BY THE BASE FIRE DEPARTMENT.
SURFACE MOUNT WITH TAMPER SWITCH.
K
CARBON MONOXIDE DETECTOR
HS KITCHEN HOOD SUPPRESSION SYSTEM
FIRE ALARM DEVICE MOUNTING NOTE
WALL MOUNTED VISUAL DEVICES TO BE LOCATED SUCH THAT THE ENTIRE
LENS OF THE STROBE IS BETWEEN 80" AND 96" AFF. ALL WALL MOUNTED
NOTIFICATION DEVICES SHALL BE MOUNTED AT THE SAME HEIGHT AFF TO
ACHIEVE A UNIFORM APPEARANCE OR AS DIRECTED BY THE A/E. WATTAGE
AND CANDELA ARE GUIDELINES. CONTRACTOR RESPONSIBLE FOR FINAL
SPACING AND TOTAL DEVICE POWER.
PS PRESSURE SWITCH
PREACTION PULL STATIONPRE
VALVEVL
1. A COMPLETED AND SIGNED RECORD (CERTIFICATE) OF COMPLETION FORM SHALL BE PROVIDED BY THE CONTRACTOR TO THE AHJ, OWNER, AND ARCHITECT/ENGINEER PRIOR TO COMMISSION TESTING. THIS CERTIFICATE SHALL CERTIFY THAT THE CONTRACTOR HAS PRE-TESTED EVERY DEVICE AND FUNCTION OF THE SYSTEM AND REPAIRED ANY DEFICIENCIES PRIOR TO THE COMMISSIONING TEST.
2. ALL SMOKE DETECTORS SHALL BE COMMISSIONED USING CANNED SMOKE OR A METHOD THAT WILL FUNCTIONALLY TEST THE SMOKE CHAMBER. THE USE OF MAGNETS FOR COMMISSION TESTING OF SMOKE DETECTORS IS STRICTLY PROHIBITED.
3. EACH AND EVERY DEVICE SHALL BE TESTED DURING COMMISSIONING AND PRIOR TO BEING TURNED OVER TO THE OWNER.
4. EACH NOTIFICATION CIRCUIT SHALL BE TESTED UNDER STANDBY/BATTERY POWER. END-OF-LINE VOLTAGE READINGS SHALL BE
TAKEN AT THE BOOSTER PANEL FOR CLASS "A" CIRCUITS. ANY CIRCUIT THAT MEASURES LESS THAN 20 VOLTS DC OR THE NAMEPLATE VOLTAGE, WHICHEVER IS HIGHER, SHALL BE CONSIDERED AS FAILING THE DESIGN. NOTE: SOME SYSTEMS INCORPORATING SYNCHRONIZING MODULES CAN IMPAIR RESULTS. IF THE MODULE CANNOT BE BYPASSED FOR VOLTAGE READINGS, THE MANUFACTURER SHOULD BE CONTACTED FOR GUIDANCE. WHEN VOLTAGE CANNOT BE MEASURED, CIRCUIT WIRE RESISTANCE READINGS AND DEVICE LOAD MAY BE COMPARED TO DESIGN CALCULATIONS (MAKE SURE CIRCUIT IS REMOVED FROM POWER SUPPLY WHEN OBTAINING WIRE RESISTANCE). ONLY A QUALIFIED TECHNICIAN EMPLOYED BY THE INSTALLING CONTRACTOR SHOULD PERFORM
THIS FUNCTION.
5. EACH CIRCUIT'S END-OF-LINE VOLTAGE SHALL BE DOCUMENTED FOR COMPARISON TO THE DESIGN END-OF-LINE CALCULATIONS.
1. ANY SMOKE DETECTOR THAT HAS BEEN INSTALLED PRIOR TO THE CONSTRUCTION CLEANUP OF ALL TRADES AND WITHOUT PRIOR WRITTEN APPROVAL OF THE CONTRACTING OFFICER SHALL BE MARKED IN A MANNER THAT WILL IDENTIFY IT FROM RE-USE AND SHALL BE REPLACED PRIOR TO COMMISSIONING OF THE SYSTEM OR TURNING OVER TO THE OWNER. SUCH DETECTORS SHALL BE REPLACED
AT THE SOLE EXPENSE OF THE INSTALLING CONTRACTOR.
2. DUCT DETECTORS SHALL BE MONITORED FOR INTEGRITY AND PROVIDE A SUPERVISORY SIGNAL AT THE FIRE ALARM PANEL. AIR HANDLER SYSTEMS SHALL BE RAN AND BLOWN OUT PRIOR TO INSTALLATION OF SMOKE DETECTORS.
3. FIRE ALARM AUDIBLE ALERT SIGNALS SHALL BE SET TO TEMPORAL CODE PER NFPA 72. EMERGENCY COMMUNICATION AUDIBLE CUES
SHALL TAKE PRECEDENCE AND OVERRIDE FIRE ALARM AND PA/MUSIC TONES.
4. INTELLIGIBILITY OF EMERGENCY COMMUNICATION MESSAGES SHALL BE PER NFPA 72 AND SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO MEET OR EXCEED. COMMISSION TESTING SHALL BE DONE PRIOR TO FINAL SYSTEM ACCEPTANCE TO VERIFY THAT
THE MINIMUM CIS SCORE OF 0.8 HAVE BEEN ACHIEVED.
5. UNLESS OTHERWISE NOTED THE FOLLOWING MINIMUM SURVIVABILITY CRITERIA SHALL BE MET: SIGNALING LINE CIRCUITS CLASS "B", AND NOTIFICATION CIRCUITS CLASS "B".
6. INITIATING DEVICES SHALL BE INDIVIDUALLY ADDRESSABLE.
7. EMERGENCY MESSAGES SHALL BE PROGRAMMED INTO THE FMCP AND CAPABLE OF RECEIVING EACH SIGNAL FROM AN EXTERNAL
SOURCE.
1. IN ACCORDANCE WITH 2019 NFPA 72, STROBES MAY BE MORE THAN 15 FEET OFF THE END OF A CORRIDOR WHEN ROOM SPACING
CRITERIA APPLIES USING THE APPROPRIATE CANDELA.
2. WALL MOUNTED SPEAKERS, STROBES, OR SPEAKER/STROBES SHALL BE AT 96" A.F.F. OR 6" BELOW THE CEILING, WHICHEVER IS
LOWER.
3. ALL SMOKE DETECTORS SHALL BE LOCATED WHERE THEY CAN BE READILY SERVICED.
4. ALL SMOKE DETECTORS SHALL BE CEILING MOUNTED OR WITHIN 12" OF THE CEILING.
5. SMOKE DETECTORS SHALL NOT BE INSTALLED WITHIN 3' OF AN AIR-SUPPLY OR RETURN GRILL PER MFG CRITERIA AND APPENDIX "A"
OF NFPA 72.
6. EACH POWER BOOSTER PANEL OR FIRE ALARM PANEL SHALL BE PROTECTED BY A SMOKE DETECTOR. WHEN PROVIDED, AREA
DETECTORS WITHIN THE SAME SPACE WILL SATISFY THIS REQUIREMENT.
7. AIR HANDLER SYSTEMS OVER 2,000 CFM SHALL BE PROVIDED WITH MEANS TO SHUT DOWN UPON THE DETECTION OF SMOKE. THESE
DETECTORS SHALL INITIATE A GENERAL FIRE ALARM.
8. DAMPER AND HVAC SMOKE DETECTORS SHALL BE PROVIDED BY THE FIRE ALARM CONTRACTOR, LISTED WITH THE FIRE ALARM
SYSTEM, AND INCORPORATE ADDRESSABLE MODULES.
9. WHERE APPLICABLE, SMOKE DETECTORS FOR AIR-HANDLER SHUT DOWN SHALL BE ON BOTH SUPPLY AND RETURN DUCTS.
10. WALL MOUNTED VISUAL DEVICES TO BE LOCATED SUCH THAT THE ENTIRE LENS OF THE STROBE IS BETWEEN 80" AND 96" AFF. ALL
WALL MOUNTED NOTIFICATION DEVICES SHALL BE MOUNTED AT THE SAME HEIGHT AFF TO ACHIEVE A UNIFORM APPEARANCE OR AS DIRECTED BY THE A/E. WATTAGE AND CANDELA ARE GUIDELINES. CONTRACTOR RESPONSIBLE FOR FINAL SPACING AND TOTAL DEVICE
POWER.
1. FIRE ALARM SYSTEM AND DEVICES SHALL BE INSTALLED TO THE LATEST EDITION OF NFPA 72, NFPA 70, NFPA 13, AND LOCAL
REQUIREMENTS.
2. ALL FIRE ALARM INSTALLATIONS, INCLUDING PULLING OF WIRE AND MOUNTING OF DEVICES, SHALL HAVE OVERSIGHT OF A NICET
LEVEL II FIRE ALARM TECHNICIAN OR HIGHER.
3. STROBES SHALL BE SYNCHRONIZED PER NFPA 72.
4. ALL FIRE ALARM/MNS CABLE SHALL BE RUN IN RED FACTORY COLORED CONDUIT.
5. THESE DESIGN DOCUMENTS PROVIDE GENERAL SPACING, LOCATION, AND COORDINATION CRITERIA. CONTRACTOR SHALL BE
RESPONSIBLE FOR CIRCUIT CONFIGURATION, SYSTEM PERFORMANCE, SOFTWARE CONFIGURATION, DEVICE PROGRAMMING, SYSTEM
COMMISSIONING, AND SYSTEM WARRANTY.
6. CONTRACTOR SHALL SUBMIT FIRE ALARM / MNS PLANS, DATA CUT-SHEETS, AND VOLTAGE DROP CALCULATIONS TO CONTRACTING
OFFICER FOR REVIEW AND APPROVAL BY THE A/E'S FPE PRIOR TO BEGINNING ANY WORK ON THE FA/MNS SYSTEM.
7. NO FA/MNS DOCUMENTS/PLANS SHALL BE USED FOR INSTALLATION OF THIS SYSTEM UNLESS THEY CONTAIN THE REVIEW AND
APPROVAL STAMP FROM THE A/E'S FPE AND APPROVAL FROM THE COR. THE COR HAS THE AUTHORITY TO STOP ANY WORK UNTIL
SUCH PLANS ARE ON SITE AND IN USE.
8. FIRE ALARM AND MASS NOTIFICATION SPECIFICATIONS CONTAIN VERY DETAILED INFORMATION ABOUT THIS SYSTEM AND SHALL BE
FOLLOWED, ON-SITE AND AVAILABLE DURING ANY CONSTRUCTION.
9. SECONDARY POWER PERFORMANCE TO MEET NFPA 72. 24 HOURS OF STANDBY POWER FOLLOWED BY 15 MINUTES OF ALARM FOR ALL CONNECTED DEVICES AT MAXIMUM LOAD. SECONDARY POWER FOR THE SYSTEM SHALL ALSO BE DESIGNED TO OPERATE MAXIMUM CONNECTED ALARM LOAD FOR 60 MINUTES IMMEDIATELY FOLLOWING DISCONNECTION OF PRIMARY POWER.
10. SPEAKER CIRCUITS TO BE 70V TYPICAL. OTHER CIRCUITS TO BE 24V TYPICAL. PROFESSIONAL
REGISTERED
ARKANSAS
ENGINEER
No. 19823
S T A T E O F
J O
H N W O R S H
A
M
Project Number:
Designed By: Approved By:
Drafted By: Date:
Scale:
HKRZ222111
F o rt S m it h A rk an sa s
R E
V
D E
S C
R
IP
T
IO
N B
Y D
A T
E
8t h W in g
A rk an
N at io na l G th
C iv il E n gi n ee r S q u ad ro n
L ei g h
A v e, F or t
S m it h
, A R
P h on e:
-5
3-
R R
I M
A T
U T
E P
A
S
W th
C o u rt
S u it e
M ia m i F lo ri d a
T
F w w w .g u rr im a tu te .c o m
A R
C H
IT
E
C T
C R
O M
W E
L L
A R
C H
IT
E
C T
S E
N G
IN
E
E
E a s t th
S tr e e t
L itt le R o c k A
R
T w .c ro m w e ll.
c o m
E N
G
IN
E E
R
P R
IM
E
C O
N R
T R
A C
T H
O L D
E R
B U
IL
D
IN
G
A
D D
/A L
T E
R
R E
N O
V A
T
IO
N
AS NOTED
FA001
02-19-2024
WL JW
WL
F I R
E A
L A
R M
L E
G E
N D
A N
D N
O T
E S
02020202−−−−19191919−−−−2024202420242024FIRE ALARM ACCEPTANCE TESTING
FIRE ALARM PERFORMANCE NOTES
FIRE ALARM LOCATION AND SPACING
FIRE ALARM GENERAL NOTES
A d d e n d u m
-1 -2
SPEAKERS
NEW FACP WITH
INTEGRATED MNS
(ADDITIONAL
ZONES IF
SPECIFIED
ELSEWHERE)
POWER
BOOSTER
IF USED
ZONE
CLASS "B"
BATTERY
CABINET
STROBES - CLEAR LENS
STROBE
REMOTE
POWER
SUPPLY
120VAC
ZONE
POWER
BOOSTER
IF USED
SIGNALING LINE CIRCUIT
XYZ XYZ XYZ XYZ XYZ XYZ XYZ
MASS NOTIFICATION MESSAGE CENTER(S) - LOCAL
OPERATOR'S CONSOLE WITH 8 PRE-RECORDED
MESSAGE BUTTONS AND HVAC SHUT-DOWN BUTTON
120-VAC
DEDICATED
CIRCUIT PER
NFPA 72
= ISOLATION MODULE,IM = CONTROL MODULE,CM
120VAC BATTERY
CABINET
REMOTE
MIC
TELEPHONE
INTERFACE
CONTROL FUNCTIONS (DOOR
RELEASE, HVAC AND HVLS FAN
SHUTDOWN, ETC)
MONACO
TRANSMITTER
CABINET
BATTERY
DEVICES AND
SYMBOLS SHOWN
NOT SPECIFIC TO
THIS PROJECT
IM CM
AUX INPUT MODULE FOR PHONE AND
REMOTE PUBLIC ADDRESS INPUT
AUX
THIS IS A TYPICAL RISER DETAIL. ALTHOUGH THE NUMBER OF
DEVICES MAY VARY BY PROJECT, THE FUNCTION AND FEATURE OF
EACH DEVICE INDICATED IS MANDATORY FOR THIS PROJECT.
THIS VOICE NOTIFICATION SYSTEM SHALL SERVE AS A FIRE ALARM
NOTIFICATION SYSTEM AND A MASS NOTIFICATION SYSTEM. A
COMBINATION VOICE EVACUATION TYPE FIRE ALARM/MASS
NOTIFICATION PANEL SHALL BE USED.
DEVICES SHALL HAVE WHITE TRIM, CLEAR STROBE, AND LABELED
"ALERT."
STROBES SHALL ONLY ACTIVATE UPON EMERGENCY NOTIFICATION
FUNCTIONS.
NO STROBES SHALL FLASH UPON ACTIVATION OF BUILDING PAGING
FUNCTIONS. STROBES SHALL BE SYNCHRONIZED.
MASS NOTIFICATION FUNCTIONS SHALL OVERRIDE ALL OTHER
FUNCTIONS INCLUDING FIRE FUNCTIONS. UPON ACTIVATION OF
MASS NOTIFICATION SYSTEM, MESSAGE PRIORITY SHALL DICTATE
THE MESSAGE BEING BRAODCAST. NON-FIRE MESSAGES SHALL
SOUND FOR 10 MINUTES. FIRE ALARM NOTIFICATION MESSAGE
SHALL SOUND UNTIL SILENCED AT FACP OR SYSTEM RESET. MNS
MESSAGES SHALL OVERIDE BUILDING PAGING AND BACKGROUND
MUSIC FUNCTIONS.
CONTRACTOR TO PROVIDE ADDITIONAL BOOSTER PANELS AND
AMPLIFIERS AS NEEDED BASED ON SELECTED PRODUCTS
LOADING, VOLTAGE DROP CALCULATIONS AND CIRCUIT
CONFIGURATION.
SYSTEM SHALL BE INSTALLED AND TESTED FOR SPEECH
INTELLIGIBILITY IN ACCORDANCE WITH UFC 3-600-01, 4-021-01, AND
NFPA 72 APPENDIX "A" USING APPROPRIATE CALIBRATED FIELD
MEASURING DEVICES.
AUDIBLE TONES SHALL PRECEDE EMERGENCY MESSAGES. MASS
NOTIFICATION VERBIAGE AND TONES SHALL BE PER BASE
STANDARDS.
SURGE SUPPRESSION SHALL BE INSTALLED ON EACH 120-VAC AND
TELEPHONE CIRCUIT.
ISOLATION MODULES AND ADDRESSABLE CONTROL/RELAY
MODULES SHALL BE INSTALLED PER MANUFACTURER
INSTRUCTIONS TO PROTECT EACH CIRCUIT.
MASS NOTIFICATION HVAC SHUT-DOWN BUTTON AND CONTROLS
SHALL SHUT-DOWN HVAC UNITS, BATHROOM EXHAUST FANS,
KITCHEN HOODS, AND HVLS FANS.
A NEW MONACO TRANSCEIVER SHALL BE UTILIZED TO TRANSMIT
TO THE EXISTING MONACO D-21 CENTRAL RECIEVING SYSTEM.
LIGHTNING
ARRESTOR
ANTENNA
XYZ
CLASS "B"
CLASS "B"
(SMOKE) (PULL)
VS
(TAMPERS) (FLOW)
VS WF
CLASS "B"
CD CD CD CDCD
FS
EXISTING FIRE ALARM TO BE COMPLETELY REMOVED AND A
NEW FA/MNS TO BE INSTALLED.
OUTPUT TO TEXTUAL
VISUAL MESSAGES
PROFESSIONAL
REGISTERED
ARKANSAS
ENGINEER
No. 19823
S T A T E O F
J O
H N W O R S H
A
M
Project Number:
Designed By: Approved By:
Drafted By: Date:
Scale:
HKRZ222111
F o rt S m it h A rk an sa s
R E
V
D E
S C
R
IP
T
IO
N B
Y D
A T
E
8t h W in g
A rk an
N at io na l G th
C iv il E n gi n ee r S q u ad ro n
L ei g h
A v e, F or t
S m it h
, A R
P h on e:
-5
3-
R R
I M
A T
U T
E P
A
S
W th
C o u rt
S u it e
M ia m i F lo ri d a
T
F w w w .g u rr im a tu te .c o m
A R
C H
IT
E
C T
C R
O M
W E
L L
A R
C H
IT
E
C T
S E
N G
IN
E
E
E a s t th
S tr e e t
L itt le R o c k A
R
T w .c ro m w e ll.
c o m
E N
G
IN
E E
R
P R
IM
E
C O
N R
T R
A C
T H
O L D
E R
B U
IL
D
IN
G
A
D D
/A L
T E
R
R E
N O
V A
T
IO
N
AS NOTED
FA501
02-19-2024
Designer Checker
Author
F I R
E A
L A
R M
D E
T A
I L
S
02020202−−−−19191919−−−−2024202420242024
A d d e n d u m
-1 -2
B
FX401
FX401
FIRE RISER ROOM
EXISTING MECH.
E X
IS
T
IN
G
T E
L
M A
IN
T
E N
A N
C E
EXISTING ELECTRICAL
13 14
VS
VS
VS
VS PS
PS
AIM AIM
AIM
VS
WF
FX401
FX401
UP-OVER-DOWN TYPICAL FOUR TIMES.
PROVIDE 6" DIAMETER CORE DRILL
AT EACH VERTICAL PENETRATION IN
THE TOP/ LID OF THE EXISTING VAULT.
NEW WET-PIPE SYSTEM CROSS MAIN
PROFESSIONAL
REGISTERED
ARKANSAS
ENGINEER
No. 19823
S T A T E O F
J O
H N W O R S H
A
M
Project Number:
Designed By: Approved By:
Drafted By: Date:
Scale:
HKRZ222111
F o rt S m it h A rk an sa s
R E
V
D E
S C
R
IP
T
IO
N B
Y D
A T
E
8t h W in g
A rk an
N at io na l G th
C iv il E n gi n ee r S q u ad ro n
L ei g h
A v e, F or t
S m it h
, A R
P h on e:
-5
3-
R R
I M
A T
U T
E P
A
S
W th
C o u rt
S u it e
M ia m i F lo ri d a
T
F w w w .g u rr im a tu te .c o m
A R
C H
IT
E
C T
C R
O M
W E
L L
A R
C H
IT
E
C T
S E
N G
IN
E
E
E a s t th
S tr e e t
L itt le R o c k A
R
T w .c ro m w e ll.
c o m
E N
G
IN
E E
R
P R
IM
E
C O
N R
T R
A C
T H
O L D
E R
B U
IL
D
IN
G
A
D D
/A L
T E
R
R E
N O
V A
T
IO
N
AS NOTED
FX401
02-19-2024
GS JW
GS
F I R
E P
R O
T E
C T
I O
N E
N L
A R
G E
D P
L A
N S
02020202−−−−19191919−−−−2024202420242024
1/2" = 1'-0"1
ENLARGED PLAN AT FIRE PROTECTION RISER ROOM
NOT TO SCALE2
ELEVATION VIEW OF FIRE PROTECTION RISER
NOT TO SCALE3
ELEVATION VIEW OF FIRE PROTECTION RISER
N
NOT TO SCALE4
3D VIEW OF FIRE PROTECTION RISER
SCALE : 1/2" = 1'-0"
0 1 2 4
NOT TO SCALE5
3D VIEW OF BRANCH LINE PIPES ENTERING EXISTING VAULT
RISER LEGEND:
1. NEW 6" FIRE PROTECTION UNDERGROUND. SAW-CUT AND REMOVE
EXISTING FLOOR AS REQUIRED TO INSTALL NEW LEAD-IN. LOCATE
VERTICAL LEAD-IN AT 1'- 0" OFF EACH WALL IN EXISTING ROOM TO ENSURE
CLEARANCES REQUIRED BY UFC ARE PROVIDED AND MAINTAINED.
INSTALL RODDING AND THRUST BLOCKING. SEE CIVIL FOR CONTINUATION.
2. SLEEVE AND LINK SEAL AS REQUIRED BY UFC.
3. 6" DOUBLE DETECTOR CHECK ASSEMBLY WITH GROOVED-END BUTTERFLY
CONTROL VALVES AND SUPERVISORY SWITCHES.
4. 4" GROOVED-END BUTTERFLY CONTROL VALVE FOR FORWARD FLOW TEST
ASSEMBLY. VALVE TO BE SUPERVISED NORMALLY CLOSED.
5. 4 x 2½ x 2½ FORWARD FLOW TEST ASSEMBLY WITH CAPS & CHAINS.
ASSEMBLY TO BE PLAIN BRASS FINISH. ROUTE PIPE ON EXTERIOR FACE OF
WALL DUE TO INTERIOR SPACE CONSTRAINTS. ANCHOR TO WALL WITH
UNISTRUT AND PIPE CLAMPS. PROVIDE SIGNAGE EQUAL TO "FORWARD
FLOW TEST" OR "TEST HYDRANT".
6. 6" MANIFOLD.
7. ADJUSTABLE PIPE STAND WITH U-BOLT. NOTICE: PROVIDE COMMERCIALLY
MANUFACTURED SADDLE WITH U-BOLT. NO HOME-MADE, BACK OF SHOP
PIPES STANDS USING SMALL BORE PIPE, WASHERS, ALL-THREAD ROD,
RISER CLAMPS, ETC., SHALL BE ALLOWED!!
8. NITROGEN GENERATOR - WALL MOUNTED. PROVIDE 120VAC/ 1-PHASE/
60HZ. NITROGEN GENERATOR REQUIRED BY UFC. USE FOR BOTH
PREACTION AND DRY-PIPE SYSTEMS.
9. DRY-PIPE VALVE WITH GROOVED-END BUTTERFLY CONTROL VALVE &
SUPERVISORY SWITCH, TRIM SET, PRESSURE SWITCHES, AIR
MAINTENANCE DEVICE, PRESSURE GAUGES AND MAIN DRAIN.
10. RISER CHECK VALVE WITH GROOVED-END BUTTERFLY CONTROL VALVE &
SUPERVISORY SWITCH, TRIM SET, PRESSURE GAUGES AND MAIN DRAIN.
11. FIRE DEPARTMENT CONNECTION PIPING AND GROOVED-END CHECK
VALVE. CHECK VALVE TO HAVE REMOVABLE FACE PLATE.
12. PRE-ASSEMBLED PREACTION SYSTEM IN CABINET. ASSEMBLY TO BE
COMPLETE WITH CONTROL VALVE, PREACTION VALVE, TRIM SET, MAIN
DRAIN, AIR COMPRESSOR, RELEASING PANEL, ELECTRIC/ PNEUMATIC
ACTUATION, ELECTRICAL LOAD CENTER, AIR MAINTENANCE DEVICE AND
ALL NECESSARY ACCESSORIES & APPURTENANCES. NOTE: PROVIDE
OPTIONAL, ADDITIONAL CONTROL VALVE LOCATED ABOVE PREACTION
VALVE AS PART OF THE PRE-ASSEMBLED PACKAGE FROM THE
MANUFACTURER.
13. WET-PIPE SYSTEM FEED MAIN.
14. FIRE DEPARTMENT CONNECTION MAIN.
15. DRY-PIPE SYSTEM FEED MAIN.
16. PREACTION SYSTEM FEED MAIN.
17. WATER FLOW SWITCH.
NOTICE: COMBINE ALL MAIN DRAINS AND PIPE THROUGH EXTERIOR WALL VIA
ONE PENETRATION.
A d d e n d u m
-1 -2
FINISHED CEILING FULLY CONCEALED SPRINKLER HEAD
WITH WHITE SCREW-ON COVER PLATE
1" DROP
BELL
REDUCER
BRANCH LINE
TEE FITTING 1" ARM OVER
1" DROP
CONCEALED DRY PENDENT
SPRINKLER HEAD W/ BLACK
OR CHROME COVER PLATE.
BRANCH LINE
PLUG
BRANCH LINE
TEE FITTING
BRASS UPRIGHT
SPRINKLER HEAD
1" PIPING
BELL REDUCER
BRANCH LINE
TEE FITTING
BRASS UPRIGHT
SPRINKLER HEAD
PIPE OR
FLEXIBLE
SPRINKLER
DROP
HORIZONTAL SPRINKLER
HEAD WITH SEMI-RECESSED
ESCUTCHEON
WALL
BELL REDUCER
BRASS UPRIGHT
SPRINKLER HEAD
THREADED TEE
U-BOLT
U-BOLT
NUT
HEAD GUARD
BRASS UPRIGHT
SPRINKLER HEAD
BRANCH
LINE PIPING
THREADED 90° ELBOW
U-BOLT
NUT
HEAD GUARD
PENDENT
SPRINKLER HEAD
THREADED TEE
FINISHED CEILINGFASTENER
(TYPICAL)
HEAD GUARD
BRANCH
LINE PIPING
NUT
1" ARMOVER
BRANCH LINE
SPRINKLER HEAD AS SPECIFIED
FINISHED CEILING
1" DROP
BELL
REDUCER
1" NIPPLE
CONCRETE SLAB OR
STRUCTURE
1-5/8" TALL UNI-STRUT
SPRINKLER
SYSTEM PIPE
CONCRETE
FASTENER
U-BOLT OR SIMILAR ATTACHMENT
CAPABLE OF RESTRAINING FIRE
PROTECTION PIPES UNDER
PRESSURE AND FLOW.
TOP BEAM CLAMP
WITH RETAINER
STRAP
STEEL BEAM OR
BAR JOIST
SET SCREW AND
LOCKNUT
ALL THREAD
ROD SIZED PER
NFPA 13
SPRINKLER PIPE
ADJUSTABLE
HANGER RING
CONCRETE
STRUCTURE
EXPANSION OR
DROP-IN ANCHOR
ALL THREAD
ROD SIZED
PER NFPA 13
SPRINKLER
PIPE
HANGER
RING
PROFESSIONAL
REGISTERED
ARKANSAS
ENGINEER
No. 19823
S T A T E O F
J O
H N W O R S H
A
M
Project Number:
Designed By: Approved By:
Drafted By: Date:
Scale:
HKRZ222111
F o rt S m it h A rk an sa s
R E
V
D E
S C
R
IP
T
IO
N B
Y D
A T
E
8t h W in g
A rk an
N at io na l G th
C iv il E n gi n ee r S q u ad ro n
L ei g h
A v e, F or t
S m it h
, A R
P h on e:
-5
3-
R R
I M
A T
U T
E P
A
S
W th
C o u rt
S u it e
M ia m i F lo ri d a
T
F w w w .g u rr im a tu te .c o m
A R
C H
IT
E
C T
C R
O M
W E
L L
A R
C H
IT
E
C T
S E
N G
IN
E
E
E a s t th
S tr e e t
L itt le R o c k A
R
T w .c ro m w e ll.
c o m
E N
G
IN
E E
R
P R
IM
E
C O
N R
T R
A C
T H
O L D
E R
B U
IL
D
IN
G
A
D D
/A L
T E
R
R E
N O
V A
T
IO
N
AS NOTED
FX501
02-19-2024
GS JW
GS
F I R
E P
R O
T E
C T
I O
N D
E T
A I L
S
02020202−−−−19191919−−−−2024202420242024
NOT TO SCALE1
CONCEALED SPRINKLER HEAD DETAIL
NOT TO SCALE2
DRY PENDENT SPRINKLER ON RETURN BEND DETAIL
NOT TO SCALE3
UPRIGHT SPRINKLER HEAD DETAIL
NOT TO SCALE4
UPRIGHT SPRINKLER HEAD ON 1" SPRIG
NOT TO SCALE5
RECESSED HORIZONTAL SIDEWALL SPRINKLER HEAD DETAIL
NOT TO SCALE6
HEAD GUARD DETAILS
NOT TO SCALE7
RETURN BEND DETAIL
NOT TO SCALE8
UNISTRUT SUPPORT DETAIL
NOT TO SCALE9
TOP BEAM CLAMP HANGER DETAIL
NOT TO SCALE10
CONCRETE HANGER DETAIL
A d d e n d u m
-1 -2
PROFESSIONAL
REGISTERED
ARKANSAS
ENGINEER
No. 9395
C H
R I S
T O P H E R R .
B
O R
N E
S T A T E O F
Project Number:
Designed By: Approved By:
Drafted By: Date:
Scale:
HKRZ222111
F o rt S m it h A rk an sa s
R E
V
D E
S C
R
IP
T
IO
N B
Y D
A T
E
8t h W in g
A rk an
N at io na l G th
C iv il E n gi n ee r S q u ad ro n
L ei g h
A v e, F or t
S m it h
, A R
P h on e:
-5
3-
R R
I M
A T
U T
E P
A
S
W th
C o u rt
S u it e
M ia m i F lo ri d a
T
F w w w .g u rr im a tu te .c o m
A R
C H
IT
E
C T
C R
O M
W E
L L
A R
C H
IT
E
C T
S E
N G
IN
E
E
E a s t th
S tr e e t
L itt le R o c k A
R
T w .c ro m w e ll.
c o m
E N
G
IN
E E
R
P R
IM
E
C O
N R
T R
A C
T H
O L D
E R
B U
IL
D
IN
G
A
D D
/A L
T E
R
R E
N O
V A
T
IO
N
AS NOTED
P-601
19 FEB 2024
JP JY
JP
P L
U M
B I N
G S
C H
E D
U L
E S
19 FEB 202419 FEB 202419 FEB 202419 FEB 2024
PLUMBING FIXTURE
ID
BASIS OF DESIGN PIPE SERVICE SIZES
TRAP
DESCRIPTIONMFR & MODEL ACCESSORIES COLD HOT WASTE INDIRECT VENT
LV-1
LAVATORY OFFSET GRID STRAINER,
CARRIER,
FAUCET
1/2” 1/2” 2”
2” 1-1/4" LAVATORY - ABA COMPLIANT, 18-1/4"x20-1/2"x38"H, WALL HUNG, WHITE VITREOUS CHINA, FRONT OVERFLOW, TWO FAUCET HOLES ON 4" CENTERS, FAUCET - 0.5 GPM, MANUAL, SINGLE LEVER, LEAD FREE, 4" SPOUT, DUAL HOT/COLD SUPPLY ON 4" CENTERS, INTEGRAL THERMOSTATIC MIXING ABOVE DECK, CARRIER - CONCEALED ARM WALL CARRIER
SK-1
SINK OFFSET BASKET STRAINER,
P-TRAP,
SUPPLY STOP VALVES,
PROVIDE SUPPLY STOP VALVES FOR ALL ADJACENT PLUMBING
ACCESSORIES,
GARBAGE DISPOSAL 120V/60Hz/1PH, 6.3 FLA, 1/2 HP
1/2” 1/2” 2”
2” 1-1/2"
SINK - ABA COMPLIANT, 19-1/2"19"7-1/2"D, 1 COMPARTMENT, SELF RIMMING, 18 GAUGE TYPE 302 STAINLESS STEEL, ONE HOLE ON DECK, FAUCET - 2.0 GPM, CHROME PLATED LEAD FREE, 8-1/2" SWING SPOUT, DECK MTD, SINGLE LEVER HANDLE, PULL-OUT SPRAY, DUAL HOT/COLD SUPPLY, GARBAGE DISPOSAL
SK-2
SINK OFFSET FLAT STAINLESS STEEL STRAINER,
P-TRAP,
SUPPLY STOP VALVES,
FAUCET
1/2” 1/2” 2”
2” 1-1/2"
SINK - ABA COMPLIANT, 18-1/2"x18-1/2"x5-3/8"D, 1 COMPARTMENT (16"x16"x5-3/8"D), UNDERMOUNT, 18 GAUGE TYPE 302 STAINLESS STEEL, CENTER DRAIN OUTLETS, FAUCET - 2.2 GPM, CHROME PLATED LEAD FREE, 8-13/16" GOOSENECK SWING SPOUT, DECK MTD, 4" WRIST BLADES, CONCEALED DUAL HOT/COLD SUPPLY, 8" FIXED CENTERS
SK-3
SINK OFFSET BASKET STRAINER,
P-TRAP,
SUPPLY STOP VALVES,
FAUCET,
GARBAGE DISPOSAL 5 120V/60Hz/1PH, 6.3 FLA, 1/2 HP
1/2” 1/2” 2”
2” 1-1/2"
SINK - 29"18"7-5/8"D, 2 COMPARTMENT, SELF RIMMING, 18 GAUGE TYPE 302 STAINLESS STEEL, ONE HOLE ON DECK, FAUCET - 2.0 GPM, CHROME PLATED LEAD FREE, 8-1/2" REACH, DECK
MTD, SINGLE LEVER HANDLE, PULL-OUT SPRAY, DUAL HOT/COLD SUPPLY, GARBAGE DISPOSAL
SK-4
SINK OFFSET FLAT STAINLESS STEEL STRAINER,
P-TRAP,
SUPPLY STOP VALVES,
FAUCET,
EMERGENCY EYE WASH,
THERMOSTATIC MIXING VALVE
1/2” 1/2” 2”
2” 1-1/2"
SINK - ABA COMPLIANT, 18-1/2"x18-1/2"x5-3/8"D, 1 COMPARTMENT (16"x16"x5-3/8"D), UNDERMOUNT, 18 GAUGE TYPE 302 STAINLESS STEEL, CENTER DRAIN OUTLETS, FAUCET - 2.2 GPM, CHROME PLATED LEAD FREE, 8-13/16" GOOSENECK SWING SPOUT, DECK MTD, 4" WRIST BLADES, CONCEALED DUAL HOT/COLD SUPPLY, 8" FIXED CENTERS, ADJACENT TO SINK
COUNTER MOUNTED EMERGENCY EYEWASH WITH THERMOSTATIC MIXING VALVE
EWC-1
ELECTRIC WATER COOLER P-TRAP,
SUPPLY STOP VALVE,
CARRIER,
GFCI RECEPTACLE, 120V/60Hz/1PH, 4.4 FLA, 450 RATED WATTS, 1/4
HP COMPRESSOR
1/2” --- 2”
2” 1-1/2"
ELECTRIC WATER COOLER - ABA COMPLIANT, 18-5/8"x17-5/8"x38-13/16"H, BARRIER FREE, LEAD FREE, FLEXIBLE ONE PIECE BUBBLER, 8 GPH OF 50F WATER AT 90°F AMBIENT AND 80°F INLET WATER, MECHANICAL PUSH-BUTTON ACTIVATION WITH ANTI-MICROBIAL PUSH PADS, EXTERNAL STREAM HEIGHT ADJUSTMENT, POWDER COATED GALVANIZED CABINET, BOTTLE FILLER WITH HANDS FREE ACTIVATION, BUILT IN FILTER MONITOR AND BOTTLE COUNTER
JS-1
JANITOR'S SINK RUBBER HOSE AND HANGER,
MOP HANGER,
(2) SPLASH PANELS
3/4” 3/4” 3”
2” 3" MOP SINK - 24" x 24" x 10", FLOOR MTD, PRECAST TERAZZO, STAINLESS STEEL CAPS, FAUCET - CHROME PLATED LEAD FREE, VACUUM BREAKER, PAIL HOOK, 6" WRIST BLADE CONTROLS, 3/4" HOSE THREADED OUTLET, COMPRESSION CARTRIDGES WITH SPRING CHECK VALVES, UPPER SUPPORT ROD
FPWH-1
FROST PROOF HOSE BIB
3/4” --- ---
FREEZEPROOF WALL HYDRANT - SIZE FOR WALL THICKNESS+4", RED BRASS VALVE BODY, 3/8" SOLID BRASS OPERATING ROD, HARDENED STAINLESS STEEL STEM, ONE PIECE VALVE PLUNGER, COPPER CASTING TUBES, DRAIN PORT UNDER NOZZLE, 3/4" HOSE CONNECTION W/ HIGH FLOW DOUBLE CHECK BACKFLOW PREVENTER, ADJUSTABLE WALL CLAMP
UC-1
UTILITY CONNECTION BOX
1/2” --- ---
UTILITY CONNECTION BOX - FIRE RATED WHITE POWDER COATED 20 GAUGE STEEL WALL BOX, BOTTOM SUPPLY VALVE, LEAD FREE BRASS, QUARTER TURN, SWEAT INLET
CONNECTION, INTEGRAL HAMMER ARESSTOR
WATER HAMMER ARRESSTOR, SEAMLESS COPPER CONSTRUCTION, POLYPROPYLENE PISTON, (2) EPDM ORINGS, MNPT CONNECTION, MAX. PRESS. 350 PSI, MAX. TEMP. 250°F, PROVIDE PROPERLY SIZED WATER HAMMER ARRESSTORS AND LOCATE ON PIPING IMMEDIATELY UPSTREAM OF ALL QUICK CLOSING VALVES (E.G. FLUSH VALVES, DISHWASHER, ICE
MAKERS, SOLENOID VALVES, ETC.)
WATER HAMMER ARRESTOR
P.D.I. UNITS A B C D E F
FIXTURE UNITS 1-11 12-32 33-60 61-113 114-154 155-330
PLUMBING EQUIPMENT
ID
BASIS OF DESIGN
UTILITY CONNECTIONS
ELECTRICAL
DESCRIPTIONMANUFACTURER & MODEL CONNECTION TYPE VOLTAGE PHASE POWER AMPS
GWH-1 WATER HEATER
1"CW, 1"HW
1/2"G, CD, TANK DRAIN,
4" VENT
HARDWIRED WITH
GFCI PROTECTION
120 V 1 --- --- NATURAL GAS WATER HEATER - MEDIUM DUTY TANK TYPE, 60 MBH INPUT, 48 GAL STORAGE, 79 GPH @ 70°F RISE, 21-3/4"DIAx61-3/4"H
CP-1
DOMESTIC
RECIRCULATING PUMP
3/4" HWR
RECEPTACLE WITH
GFCI PROTECTION
120 V 1 52 .46 RECIRCULATING PUMP - 1 GPM @ 5' HEAD - LEAD FREE BRONZE BODY, 150 PSI WORKING PRESSURE, 40F MINIMUM OPERATING TEMPERATURE
PLUMBING ACCESSORY
ID
BASIS OF DESIGN
Utility Connections DESCRIPTIONMANUFACTURER & MODEL
ET-1 EXPANSION TANK 3/4" CW EXPANSION TANK - 2.1 GAL TOTAL CAPACITY, 150 PSI WORKING PRESSURE, 10"DIA x 10-3/8" H, 3/4" NPT THREADED CONNECTION, 21 LBS, PROVIDE FULL PORT ISOLATION BALL VALVE AT CONNECTION TO CW
RPZA-1 BACKFLOW PREVENTER 3/4"CW REDUCED PRESSURE ZONE ASSEMBLY - 3/4 INCH, LEAD FREE CAST COPPER SILICON ALLOY, MODULAR, COMPACT DESIGN, REPLACEABLE SEATS, IN VERTICAL POSITION
TBV BALANCING VALVE SAME AS PIPE BEING
SERVED
BALANCING VALVE - SAME SIZE AS LINE, THERMOSTATIC, AUTOMATIC ACTUATION, LEAD FREE STAINLESS STEEL CONSTRUCTION, 110°F HWR, 5°F DELTA T, INCLUDES UNION WITH INTEGRAL CHECK VALVE, FULL PORT BALL VALVES IMMEDIATELY UPSTREAM AND DOWNSTREAM OF BALANCING VALVE
WCO WALL CLEAN OUT SAME AS PIPE BEING
SERVED
WALL CLEANOUT - SAME SIZE AS LINE, MAX. 4 INCH, CAST IRON FERRULE W/ ABS PLUG, SQUARE STAINLESS STEEL SECURE ACCESS COVER AND FRAME, COUNTERSUNK CORNER SCREWS
FCO FLOOR CLEAN OUT SAME AS PIPE BEING
SERVED
FLOOR CLEANOUT - SAME SIZE AS LINE, MAX. 4", HEAVY DUTY CAST IRON, FERRULE, THREADED ADJUSTABLE HOUSING, INTEGRAL CLAMPING COLLAR, ABS PLUG, 6-3/4"DIA ROUND SCORIATED SECURE TOP WITH SATIN NICKEL-BRONZE FINISH
A
D D
E N
D U
M
-1 -2
1 2 3 4 5 6 7 8 9 10 11 12 13 14
Bx
C
F
K
L
E
B
D
H
J
H.1
10.3 11.7 12.7
IV-1
RV-1
10.2
PROFESSIONAL
REGISTERED
ARKANSAS
ENGINEER
No. 9395
C H
R I
S
T O P H E R R .
B
O R
N E
S T A T E O F
Project Number:
Designed By: Approved By:
Drafted By: Date:
Scale:
HKRZ222111
F o rt S m it h A rk an sa s
R E
V
D E
S C
R
IP
T
IO
N B
Y D
A T
E
8t h W in g
A rk an
N at io na l G th C iv il E n gi n ee r S q u ad ro n
L ei gh A v e, F o rt
S m it h
A
R
P ho ne : 4
-5
3-
R R
I M
A T
U T
E P
A
S
W th
C o u rt
S u it e
M ia m i F lo ri d a
T
F w w w .g u rr im a tu te .c o m
A R
C H
IT
E
C T
C R
O M
W E
L L
A R
C H
IT
E
C T
S E
N G
IN
E
E
E a s t th
S tr e e t
L itt le R o c k A
R
T w .c ro m w e ll.
c o m
E N
G
IN
E E
R
P R
IM
E
C O
N R
T R
A C
T H
O L D
E R
B U
IL
D
IN
G
A
D D
/A L
T E
R
R E
N O
V A
T
IO
N
AS NOTED
MH102
02-19-2024
JP CB
JP
R O
O F
M E
C H
A N
I C
A L
P L
A N
02020202−−−−19191919−−−−2024202420242024
0 4 8 16 1/8" = 1'-0"1
ROOF MECHANICAL PLAN
GENERAL NOTES
1 REFER TO SHEET M-001 FOR MECHANICAL NOTES,
ABBREVIATIONS, AND LEGEND SYMBOLS.
2 ALL CONDENSATE DRAIN PIPING TO HAVE A MINIMUM
CONTINUOUS SLOPE OF 1/8'' PER FOOT.
3 ALL CONDENSATE DRAIN PIPING SHALL BE COPPER.
4 REFER TO MP SHEETS FOR THERMOSTAT AND OTHER
CONTROL DEVICE LOCATIONS.
N
A d d e n d u m
-1
-2
KEYED NOTES
1 INSTALL IV-1 WITH ROOFCURB MATCHING ROOF PITCH. ENSURE
WATERTIGHT ROOF SEAL.
2 INSTALL RV-1 WITH ROOFCURB MATCHING ROOF PITCH. ENSURE
WATERTIGHT ROOF SEAL.
1 2 3 4 5 6 7 8
Bx
C
F
K
L
E
B
D
H
J
H.1
AHU-6
AHU-4
AHU-3
AHU-2AHU-1
14/12 R/A
12/12 S/A
6Ø O/A
14/12 O/A
/1
/A
14/14 S/A
AHU-5
AHU-18
AHU-7
OPTOMETRY
OPTOMETRIST
TECH
RECEPTION
COMMS
CLOSET
VITALS/EKG/PFT
128EXAM ROOM 3
EXAM ROOM 4
MEDICAL
BREAK ROOM
DENTAL XRAY
& EXAM ROOM
CASE
MANAGER'S
OFFICE
EXAM ROOM 1
NURSE'S
OFFICE
MEDICS
OFFICE
EXAM ROOM 2
CASE
MANAGER'S
OFFICE
FULL TIME
PROVIDER'S
OFFICE
AUDIOLOGY
DENTAL
OFFICES
WAITING
LOBBY
CORRIDOR
EXISTING
WOMENS TLT.
EXISTING
MENS TLT.
MAO OFFICE
CASE
MANAGER'S
OFFICE
MULTI MEDIA
JAN. CL.
EXISTING
LOUNGE
IMMUNIZATIONS
& LAB OFFICE
SEL OFFICE
CUBICLE AREA
ENTRY
CORRIDOR
COMMANDER'S
OFFICE
C
8C
D
6Ø E/A
8Ø E/A8Ø E/A
12/14 R/A
12/12 R/A
B
/1
O
/A
BU-6
8/10 O/A 6Ø O/A
16/12 R/A
Ø
6Ø O/A
Ø
Ø
8A
10Ø
6Ø 8Ø8 Ø
6Ø O/A
Ø
O
8Ø
8Ø
10Ø
10Ø O/A
17/17 R/A
/1
S
/A
8Ø
Ø
O
/A
8Ø 6 Ø
8Ø S/A
8Ø
8A
8Ø
6A
8/8
Ø
6A
B
12/10 R/A
H
H
Ø
Ø
8Ø
6A
8A
8A
8A 1508A
14/12 S/A
6Ø 8Ø
10/10 S/A
8Ø 8Ø
16/14 R/A14/12 R/A
B
B
10B
8B
8Ø
6Ø
10/12 R/A8/10 R/A
B
B
Ø
6Ø
6Ø 6Ø
8A
6A
6A
10A
8/12 S/A 8/8 S/A
8Ø
B
12/10 R/A
B
8ØB
B
8Ø
8/10 R/A
8A
8A
10Ø
8A
6A
6A
8A
6A
6A
8A
6Ø
6Ø 12/12 S/A10/10 S/A
8/10 S/A
6/8
B
B
Ø
12/10 R/A
B
Ø
Ø
B
6/8
B
B
6Ø
6Ø
/1
8Ø
8Ø 8Ø
8Ø
8A
8A
8A
8A
B
Ø
8A
10/8
8A
8A
6A
8/10
14/12 S/A
8Ø
8Ø
6A
6A
10A
10/10
6Ø
B
B
8Ø8Ø 10/10
B
Ø
Ø
O
6Ø
10Ø
B
8 B
8Ø
6A
6A
10A
12/12 S/A
10A
6Ø O/A
B
6Ø
12Ø
8/12 S/A
Ø
Ø
B
10/10 O/A
8/8 O/A
12/12 O/A
SOUND
BOOTH
CSS
FIRST
SERGEANT'S
OFFICE
2 2 2
FCU-1
10Ø
6Ø
8Ø
6Ø O/A
B
Ø
8Ø
PROFESSIONAL
REGISTERED
ARKANSAS
ENGINEER
No. 9395
C H
R I
S
T O P H E R R .
B
O R
N E
S T A T E O F
Project Number:
Designed By: Approved By:
Drafted By: Date:
Scale:
HKRZ222111
F o rt S m it h A rk an sa s
R E
V
D E
S C
R
IP
T
IO
N B
Y D
A T
E
8t h W in g
A rk an
N at io na l G th C iv il E n gi n ee r S q u ad ro n
L ei gh A v e, F o rt
S m it h
A
R
P ho ne : 4
-5
3-
R R
I M
A T
U T
E P
A
S
W th
C o u rt
S u it e
M ia m i F lo ri d a
T
F w w w .g u rr im a tu te .c o m
A R
C H
IT
E
C T
C R
O M
W E
L L
A R
C H
IT
E
C T
S E
N G
IN
E
E
E a s t th
S tr e e t
L itt le R o c k A
R
T w .c ro m w e ll.
c o m
E N
G
IN
E E
R
P R
IM
E
C O
N R
T R
A C
T H
O L D
E R
B U
IL
D
IN
G
A
D D
/A L
T E
R
R E
N O
V A
T
IO
N
AS NOTED
MH401
02-19-2024
JP CB
JP
E N
L A
R G
E D
M E
C H
A N
I C
A L
P L
A N
S
02020202−−−−19191919−−−−2024202420242024
0 4 8 16 3/16" = 1'-0"1
MEDICAL SIDE ENLARGED MECHANICAL PLAN N
KEYED NOTES
1 EXHAUST AIR SIDEWALL GRILLE INSTALLED APROXIMATELY
11'-6'' AFF.
2 REFER TO SHEET MH402 FOR CONTINUATION.
3 RECOMMENDED CLEARANCE. TYPICAL FOR ALL AIR
HANDLING UNITS.
4 MOUNT 2'x2' CEILING CASSETTE ONTO GRID. SUPPORT FROM
STRUCTURE ABOVE.
5 BALANCE OUTSIDE AIR SERVING MULTI-POSITION AIR
HANDLING UNIT AHU-1 TO 55 CFM.
6 BALANCE OUTSIDE AIR SERVING MULTI-POSITION AIR
HANDLING UNIT AHU-2 TO 70 CFM.
7 BALANCE OUTSIDE AIR SERVING MULTI-POSITION AIR
HANDLING UNIT AHU-3 TO 225 CFM.
8 BALANCE OUTSIDE AIR SERVING MULTI-POSITION AIR
HANDLING UNIT AHU-4 TO 40 CFM.
9 BALANCE OUTSIDE AIR SERVING MULTI-POSITION AIR
HANDLING UNIT AHU-5 TO 205 CFM.
10 BALANCE OUTSIDE AIR SERVING MULTI-POSITION AIR
HANDLING UNIT AHU-6 TO 100 CFM.
11 BALANCE OUTSIDE AIR SERVING MULTI-POSITION AIR
HANDLING UNIT AHU-7 TO 110 CFM.
12 BALANCE OUTSIDE AIR SERVING MULTI-POSITION AIR
HANDLING UNIT AHU-18 TO 40 CFM.
GENERAL NOTES
1 REFER TO SHEET M-001 FOR MECHANICAL NOTES,
ABBREVIATIONS, AND LEGEND SYMBOLS.
2 ALL CONDENSATE DRAIN PIPING TO HAVE A MINIMUM
CONTINUOUS SLOPE OF 1/8'' PER FOOT.
3 ALL CONDENSATE DRAIN PIPING SHALL BE COPPER.
4 REFER TO MP SHEETS FOR THERMOSTAT AND OTHER
CONTROL DEVICE LOCATIONS.
A d d e n d u m
-1
-2
ES
CO
A
6 7 8 9 10 11 12 13 14
Bx
C
F
K
L
E
B
D
H
J
H.1
11.7
(E)PTAC (E)PTAC
(E)LOUVER(E)LOUVER
DOAS-1
CRU-1 CRU-2
14/12 S/A
12/12 O/A
/1
S
/A
PROVIDE MAN BARS
AHU-8
AHU-9
AHU-10
AHU-12
AHU-11
AHU-13
AHU-14
AHU-16
AHU-15
UH-1
BU-1 BU-2 BU-3 BU-4
AHU-17
BU-5
24/12 O/A 14/12 O/A14/12 O/A
10Ø E/A
8Ø E/A
6Ø E/A
20Ø O/A
FIRE RISER
ROOM
EXISTING
ELECTRICAL
EXISTING
MECH.
KMI OFFICE
BASE DATA
CENTER
CC OFFICE
COMMANDER'S
OFFICE
SMALL
CONFERENCE
STORAGE
STORAGE
EXISTING TEL
MAINTENANCE
SUPERINTENDENT'S
OFFICE
CHIEF'S
OFFICE
CORRIDOR
SUPPORT
STAFF
SERVER
WORKSPACE
VESTIBULE
CONFERENCE
ROOM
COMMS
BREAKROOM
COMM
STORAGE
WORKBENCH
AREA
OPEN OFFICE
OFFICE
12/6C
D
10/10
8A
B
B
B
14/14 R/A
6Ø O
/A
6/10 O/A
16/10 R/A
14/10 S/A
8Ø
8/10
8Ø
8Ø
8Ø
8Ø O
/A
6Ø O/A
8Ø 8Ø8Ø
8Ø
8Ø O
/A
8Ø
/1
R
/A
10Ø R/A
12/12 R/A
/1
R
/A
8Ø
17/15 R/A
/1
R
/A
8/12 S/A
10/10 S/A
10/10 R/A
/1
R
/A
8Ø 8Ø
8Ø
8Ø
8Ø E/A
8Ø
EF-1
10/10
8A 110 8A
8A
8A
8A
8A
8A
Ø
Ø
8A
8A
8A
8Ø
10/10 S/A
8Ø
8Ø
8A
8A
8A
12Ø
6Ø O
/A
/1
S
/A
/1
8A
8A
8A
14Ø
8Ø
12/10 8/10
B
B
8B
8B
8B
8A
8A
8A
8A
6A
8Ø 8Ø
6A
6A
6A
6Ø 6Ø
6Ø 8/10 S/A 8/8
10A
Ø
H
6Ø O/A
8A
8A
8A
8A
8Ø
8Ø
8Ø
8Ø
8/
E
6/6
E
6/6
E
6/6
12/10 S/A
10/10
6/8
B
8Ø
B
8Ø O
/A
B
12B
6Ø O/A
B
10Ø
Ø
10/10 O/A 8/10 O/A
E
18/10
/1
S
/A
E
6/6
M-502
6Ø O
/A
8/10 E/A
6 6
12Ø
7 7
10/10 S/A 10/6 S/A
8Ø8Ø8Ø8Ø
6Ø O
/A
13 14 15
M-502
6Ø O/A
-G
DOAS-1
M 23
M 23
-F
10.2
PROFESSIONAL
REGISTERED
ARKANSAS
ENGINEER
No. 9395
C H
R I S
T O P H E R R .
B
O R
N E
S T A T E O F
Project Number:
Designed By: Approved By:
Drafted By: Date:
Scale:
HKRZ222111
F o rt S m it h A rk an sa s
R E
V
D E
S C
R
IP
T
IO
N B
Y D
A T
E
8t h W in g
A rk an
N at io na l G th C iv il E n gi n ee r S q u ad ro n
L ei gh A v e, F o rt
S m it h
A
R
P ho ne : 4
-5
3-
R R
I M
A T
U T
E P
A
S
W th
C o u rt
S u it e
M ia m i F lo ri d a
T
F w w w .g u rr im a tu te .c o m
A R
C H
IT
E
C T
C R
O M
W E
L L
A R
C H
IT
E
C T
S E
N G
IN
E
E
E a s t th
S tr e e t
L itt le R o c k A
R
T w .c ro m w e ll.
c o m
E N
G
IN
E E
R
P R
IM
E
C O
N R
T R
A C
T H
O L D
E R
B U
IL
D
IN
G
A
D D
/A L
T E
R
R E
N O
V A
T
IO
N
AS NOTED
MH402
02-19-2024
JP CB
JP
E N
L A
R G
E D
M E
C H
A N
I C
A L
P L
A N
S
02020202−−−−19191919−−−−2024202420242024
0 4 8 16 3/16" = 1'-0"1
COMM SIDE ENLARGED MECHANICAL PLAN N
GENERAL NOTES
1 REFER TO SHEET M-001 FOR MECHANICAL NOTES,
ABBREVIATIONS, AND LEGEND SYMBOLS.
2 ALL CONDENSATE DRAIN PIPING TO HAVE A MINIMUM
CONTINUOUS SLOPE OF 1/8'' PER FOOT.
3 ALL CONDENSATE DRAIN PIPING SHALL BE COPPER.
4 REFER TO MP SHEETS FOR THERMOSTAT AND OTHER
CONTROL DEVICE LOCATIONS.
KEYED NOTES
1 MOUNT INLINE EXHAUST FAN APPROXIMATELY 11'-0'' AFF. COORDINATE AROUND OUTSIDE AIR
DUCTWORK.
2 OSA DUCT UP TO INTAKE VENTILATOR. ROUTE AROUND EXISTING STRUCTURE IF NECESSARY. SEE SHEET
MH102 FOR CONTINUATION.
3 REFER TO SHEET MH401 FOR CONTINUATION.
4 GRILLES IN ELECTRICAL ROOM MOUNTED APPROXIMATELY 11'-0''.
5 MOUNT UNIT HEATER WALL MOUNTED APPROXIMATELY 7'-6'' AFF.
6 RECOMMENDED CLEARANCE. TYPICAL FOR ALL AIR HANDLING UNITS.
7 RECOMMENDED CLEARANCE FOR CRAC UNIT.
8 ALL CABLING IN PLENUM ABOVE FOR THE BASE DATA CENTER SHALL BE PLENUM RATED.
9 RECOMMENDED CLEARANCE FOR DOAS UNIT.
10 EXHAUST AIR DUCT UP TO RELIEF VENTILATOR. SEE SHEET MH102 FOR CONTINUATION.
11 BALANCE OUTSIDE AIR SERVING MULTI-POSITION AIR HANDLING UNIT AHU-8 TO 200 CFM.
12 BALANCE OUTSIDE AIR SERVING MULTI-POSITION AIR HANDLING UNIT AHU-9 TO 75 CFM.
13 BALANCE OUTSIDE AIR SERVING…
This is the start of the file's text. The full file is on GovTribe.