Attachment 19 - VASNHCS Project Manual Updated Final 20210310.pdf

PDF 11 MB Posted

Attached to
Y1BG--EHRM Infrastructure Upgrades Design Build - Reno Federal contract opportunity
Solicitation number
36C77621R0117
Issued by
Department of Veterans Affairs Technology Acquisition Center Austin

About this file

This solicitation is for a design-build project to upgrade telecommunications infrastructure at Veterans Affairs facilities in Reno, Nevada. The contractor shall relocate or remodel approximately 28 telecommunications rooms and 1 data center to meet the agency's IT standards, while maintaining operational IT services. The scope of work includes all labor, materials, tools, and services for design, pre-construction, construction, and closeout. The contractor must provide a turn-key solution in accordance with VA Office of Information and Technology and Eastern Health Region Medical Center infrastructure guidelines. The soliciting agency is the Department of Veterans Affairs Technology Acquisition Center located in Austin, Texas.

View the file

Other files for this federal contract opportunity

Other files attached to Y1BG--EHRM Infrastructure Upgrades Design Build - Reno, newest first.
File Type Posted
Attachment 1 - 001121 - VASNHCS RFP DB Narrative - Reno EHRM REV - 7-29-21.pdf PDF
36C77621R0117 0001.docx DOCX document
Technical Questions Phase 1 - FINAL - Reno EHRM.pdf PDF
Attachment 20 - Construction Wage Rates - Washoe County 7-2-21.pdf PDF
Attachment 12 - Physical Security and Resiliency Design Manual AppxA1.pdf PDF
Attachment 11 - Physical Security and Resiliency Design Manual 20210101.pdf PDF
Attachment 10 - OIT-Infrastructure Stds Telecomm Spaces V3.0 Aug 21 2020.pdf PDF
Attachment 23 - Contractor Safety - Environmental Form.docx DOCX document
Attachment 17 - Telecommunications Special Telecommunications Systems Design Manual Feb 2016.pdf PDF
Attachment 16 - SOCAMES 6 Design Alert 1 thru 4.pdf PDF
Attachment 15 - Physical Security and Resiliency Design Manual AppxB.xlsx XLSX spreadsheet
Attachment 6 - Manual for Preparation of Cost Estimates _ Related Documents.pdf PDF
Attachment 1 - 001121 - VASNHCS RFP DB Narrative - Reno EHRM 20210623.pdf PDF
Attachment 22 - Limitations on Subcontracting - Construction.docx DOCX document
Attachment 21 - Labor Wage Rates - Washoe County 5-21-21.pdf PDF
Attachment 13 - Physical Security and Resiliency Design Manual AppxA2.pdf PDF
Attachment 9 - OIT-Design Guide Templates-Critical Telecomm Spaces V1.0 27 Dec 2018.pdf PDF
Attachment 8 - OEHRM Site Infrastructure Requirements - V2.0.pdf PDF
Attachment 5 - Basic Guidance - Zone PDU Power Distribution.pdf PDF
Attachment 14 - Physical Security and Resiliency Design Manual AppxA3.xlsx XLSX spreadsheet
Attachment 4 - Basic Guidance - 208V Power Distribution White Paper.pdf PDF
Attachment 18 - VA Standards Alert 017 20201101.pdf PDF
Attachment 7 - OEHRM Infrastructure Readiness Playbook v2.0.pdf PDF
Attachment 3 - App A - Appendices B C D Project 654-20-700.pdf PDF
Attachment 2 - VASNHCS EHRM Specifications Final 20210623.pdf PDF
36C77621R0117_1.docx DOCX document
Show all 26

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

VISN 21 CM/PM Electronic Health

Records Modernization (EHRM) PHASE I Support Task

PO# 612C209

Sierra Nevada Health Care System Reno VA Medical Center

P R O J E C T C O N TA C T D I R E C T O R Y

Concourse Federal Group

123 S. Royal Street Alexandria, Virginia 22314

Tim Hower, Project Manager .........................................................................................thower@concousefederal.com

Lorena Alvarez.................................................................................................................IaIvarez@concousefederaI.com

Mike Olson .................................................................................................................... molson@concousefederal.com

Marshall Contino, Concourse A|E Vice President ........................................................ mcontino@concousefederal.com

DHE Engineering 3300 N. Central Ave. 3300 Tower Suite, 1520, Phoenix, AZ 85012

Rick Seger P.E., Principal, Electrical Engineer................................................................rseger@dheeng.com

Kory Young, EIT, Senior Mechanical Engineer.................................................................kyoung@dheeng.com

VA Reno Health Care System

David Law, Chief Engineer..............................................................................................David.Law2@va.gov

Steve Elliott, PE….............................................................................................................Steven.Elliott3@va.gov

Mark Vine, IT Specialist...................................................................................................Mark.Vine@va.gov

VHARENEllioS Text Box

VHARENEllioS Text Box Modified by COR, 3/8/2021.

Project Team Contributors

Overview

Vicinity Map/Building Addresses

Campus Map/Building Information

VAMC EHRM Fiber Distances

VASNHCS Bldg. 1:

First and Second Floor

Third and Fourth Floor

Fifth and Sixth Floor

VASNHCS Bldg. 1A:

First Floor Plan

VASNHCS Bldg. 1D:

First Floor Plan

Second Floor Plan

Third Floor Plan

Identification of Network Spaces

VASNHCS Bldg. 5:

First Floor Plan

Second Floor Plan

VASNHCS Bldg. 6:

First Floor Plan

Second Floor Plan

VASNHCS Bldg. 7:

First Floor Plan

VASNHCS Bldg. 8:

First Floor Plan

VASNHCS Bldg. 10:

Basement

First Floor Plan

VASNHCS Bldg. 12:

First Floor Plan

Second Floor Plan

Third Floor Plan

Fourth Floor Plan

Fifth Floor Plan

Sixth Floor Plan

Ta b l e o f C o n t e n t s

Network Space Design

Bldg. 1:

C1353

Design Matrix

Enlarged Plan – Existing

Bldg. 1:

C2355

Design Matrix

Enlarged Plan - Existing

Bldg. 1:

C3355

Design Matrix

Enlarged Plan - Existing

Bldg. 1:

C4355

Design Matrix

Enlarged Plan - Existing

Bldg. 1:

C5355

Design Matrix

Enlarged Plan - Existing

Bldg. 1:

C6359

Design Matrix

Enlarged Plan - Existing

Bldg. 1A:

D2456

Design Matrix

Enlarged Plan - Existing

Bldg. 1D:

G1585/G1576A

Design Matrix

Enlarged Plan - Existing

Bldg. 1D:

G1644

Design Matrix

Enlarged Plan - Existing

Bldg. 1D:

H1703

Design Matrix

Enlarged Plan – Existing

Bldg. 1D:

H2703

Design Matrix

Enlarged Plan - Existing

Bldg. 1D:

G2571 Design Matrix

Enlarged Plan – Existing

Bldg. 1D:

G3633

Design Matrix

Enlarged Plan - Existing

Bldg. 1D:

H3706

Design Matrix

Enlarged Plan - Existing

Bldg. 5:

K1778

Design Matrix

Enlarged Plan - Existing

Bldg. 5:

K2784A

Design Matrix

Enlarged Plan - Existing

Bldg. 6:

F1479

Design Matrix

Enlarged Plan - Existing

Bldg. 6:

F2476

Design Matrix

Enlarged Plan - Existing

Bldg. 7:

N217

Design Matrix

Enlarged Plan – Existing

Bldg. 8:

Boiler Plant Closet /N105

Design Matrix

Enlarged Plan - Existing

Network Space Design (cont’d)

Network Space Design (Cont’d)

Bldg. 10:

L0873

Design Matrix

Enlarged Plan - Existing

Bldg. 10:

L1826

Design Matrix

Enlarged Plan - Existing

Bldg. 10:

L1874

Design Matrix

Enlarged Plan - Existing

Bldg. 12:

B1169

Design Matrix

Enlarged Plan - Existing

Bldg. 12:

B2263

Design Matrix

Enlarged Plan - Existing

Bldg. 12:

B4196

Design Matrix

Enlarged Plan - Existing

Bldg. 12:

B5196

Design Matrix

Enlarged Plan - Existing

Bldg. 12:

B6197

Design Matrix

Enlarged Plan – Existing

On Campus Rooms

Not Visited By RFP Developer.

Scope Derived From Facility Self-

Assessment

Bldg. 12:

B3198

Design Matrix

Appendix A – Power Installation Example

Appendix B – Compliance Requirements

Appendix C – Rack Labeling Standard

Appendix

V i c i n i t y M a p B u i l d i n g A d d r e s s e s

I o a n n i s A . L o u g a r i s

V A M e d i c a l C e n t e r 9 7 5 K i r m a n A v e n u e R e n o , N V 8 9 5 0 2

VHARENEllioS Line

VHARENEllioS

PLEASE NOTE: The CBOCs are no longer part of this Design-Build project. Any references to work to be performed at the CBOCs in the RFP to DB Narrative, Specs, Project Manual or any other documentation in this solicitation/contract shall be disregarded.

C a m p u s M a p - R e n o M e d i c a l C e n t e r B u i l d i n g I n f o r m a t i o n

Bldg # ABBR Bldg Name Data Ctr Levels

12 Reno Medical Center 1 6

Bldg # ABBR Bldg Name TR Qty Levels

1 Reno Medical Center 6 6

1A Reno Medical Center 1 2

1D Reno Medical Center 7 3

4 Reno Medical Center 0 1

5 Reno Medical Center 2 2

6 Reno Medical Center 2 2

7 Reno Medical Center 1 1

8 Reno Medical Center 1 1

10 Reno Medical Center 3 1

12 Reno Medical Center 5 6

1A

1D

1D

8 7

VAMC FIBER DISTANCES

SIERRA NEVADA HEALTHCARE SYSTEM

RENO MEDICAL CENTER

Create redundant fiber feed from existing server room to each building and TR. Path to be diverse from existing fiber to preclude interruption to service.

Building Floor Room Distance From Existing

Server Room (FT) Notes Fiber type Conduit Type

1 1 C1353 403 24 strand mulitmode Interior - 4" EMT

1 2 C2355 378 24 strand mulitmode Interior - 4" EMT

1 3 C3355 338 24 strand mulitmode Interior - 4" EMT

1 4 C4355 376 24 strand mulitmode Interior - 4" EMT

1 5 C5355 388 24 strand mulitmode Interior - 4" EMT

1 6 C6359 394 24 strand mulitmode Interior - 4" EMT

1A 2 D2456 446 24 strand mulitmode Interior - 4" EMT

1D 1 G1585/G176A 337 Distance to new room 24 strand mulitmode Interior - 4" EMT

1D 1 G1644 444 24 strand mulitmode Interior - 4" EMT

1D 1 H1703 383 24 strand mulitmode Interior - 4" EMT

1D 2 H2703 399 24 strand mulitmode Interior - 4" EMT

1D 2 G2571 424 24 strand mulitmode Interior - 4" EMT

1D 3 G3633 426 Relocated from G3614 24 strand mulitmode Interior - 4" EMT

1D 3 H3706 388 24 strand mulitmode Interior - 4" EMT

5 1 K1778 502 24 strand mulitmode Interior - 4" EMT

5 2 K2784A 586 24 strand mulitmode Interior - 4" EMT

6 1 F1479 705 24 strand mulitmode Interior - 4" EMT

6 2 F2476 679 24 strand mulitmode Interior - 4" EMT

7 N217 552 Building east of campus 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

8 BP/N105 748 Building east of campus 24 strand single mode Exterior - Concrete encased 4" PVC or HDPE with (4)1" interducts. Interior - 4" EMT

10 B L0873 617 24 strand mulitmode Interior - 4" EMT

10 1 L1826 855 Relocated from L1908 24 strand mulitmode Interior - 4" EMT

10 1 L1874 678 24 strand mulitmode Interior - 4" EMT

12 1 B1169 211 24 strand mulitmode Interior - 4" EMT

12 2 B2263 Server Room 24 strand mulitmode Interior - 4" EMT

12 3 B3167 191 24 strand mulitmode Interior - 4" EMT

12 4 B4196 194 24 strand mulitmode Interior - 4" EMT

12 5 B5196 212 24 strand mulitmode Interior - 4" EMT

12 6 B6197 241 24 strand mulitmode Interior - 4" EMT

BLDG: 1 - RENO MEDICAL

CENTER

LEVEL: 1

SCALE: 1” = 40’

DATE: 07/14/2020

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

EXISTING TR LOCATION(S)

SIERRA NEVADA HEALTHCARE SYSTEM

RENO MEDICAL CENTER

EXISTING TR LOCATION(S)

SIERRA NEVADA HEALTHCARE SYSTEM

RENO MEDICAL CENTER

BLDG: 1 - RENO MEDICAL

CENTER

LEVEL: 2

SCALE: 1” = 40’

DATE: 07/14/2020

N N

REMEDIATE IN PLACE

TELECOMMUNICATION

ROOM C1353

EXPAND IN PLACE

TR

C2355A

EXISTING WALL AND CEILING

TO BE REMOVED TO UPGRADE

RACK & AC UNIT

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

I D E N T I F I C AT I O N O F N E T WO R K S PAC E S

BLDG: 1 - RENO MEDICAL

LEVEL: 3

SCALE: 1” = 40’

DATE: 07/14/2020

EXISTING TR LOCATION(S)

SIERRA NEVADA HEALTHCARE SYSTEM

RENO MEDICAL CENTER

EXISTING TR LOCATION(S)

SIERRA NEVADA HEALTHCARE SYSTEM

RENO MEDICAL CENTER

BLDG: 1 - RENO MEDICAL

CENTER

LEVEL: 4

SCALE: 1” = 40’

DATE: 07/14/2020

N N

REMEDIATE IN PLACE

TELECOMMUNICATION

ROOM C3355

REMEDIATE IN PLACE

IT CLOSET

COMMUNICATIONS

C4355

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

BLDG: 1 RENO MEDICAL

LEVEL: 5

SCALE: 1” = 40’

DATE: 07/14/2020

EXISTING TR LOCATION(S)

SIERRA NEVADA HEALTHCARE SYSTEM

RENO MEDICAL CENTER

EXISTING TR LOCATION(S)

SIERRA NEVADA HEALTHCARE SYSTEM

RENO MEDICAL CENTER

BLDG: 1 RENO MEDICAL

CENTER

LEVEL: 6

SCALE: 1”=40’

DATE: 07/14/2020

N N

REMEDIATE IN PLACE

TR

C6359REMEDIATE IN PLACE

IT CLOSET

C5355

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

EXISTING TR LOCATION(S)

RENO MEDICAL CENTER

BLDG: 1 A - RENO MEDICAL

CENTER

LEVEL: 1

SCALE: 1/16” = 1’0”

DATE: 07/14/2020

N

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

RENO MEDICAL CENTER

BLDG: 1 D - RENO MEDICAL

CENTER

LEVEL: 1

SCALE: 1/32” = 1’-0”

DATE: 07/14/2020

N

REMEDIATE IN PLACE

G1644

REMEDIATE IN PLACE

H1703

TELE-COMMUNICATION

G1585

RELOCATE TO G1576A

RELOCATE G1585 TO G1576A

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

RENO MEDICAL CENTER

BLDG: 1 D - RENO MEDICAL

CENTER

LEVEL: 2

SCALE: 1/32” = 1’-0”

DATE: 07/14/2020

N

REMEDIATE IN PLACE

G2571

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

FOR RELOCATED TR

REMEDIATE IN PLACE

H2703

RENO MEDICAL CENTER

BLDG: 1 D - RENO MEDICAL

CENTER

LEVEL: 3

SCALE: 1/32” = 1’-0”

DATE: 07/14/2020

N

TEL

G3614

RELOCATE TO G3633

G3633

SIM COMM ALCOVE

H3706

REMEDIATE IN PLACE

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

RENO MEDICAL CENTER

BLDG: 5 - RENO MEDICAL

CENTER

LEVEL: 1

SCALE: 1/32” = 1’-0”

DATE: 07/14/2020

N

IT CLOSET

K1778

REMEDIATE IN PLACE

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

RENO MEDICAL CENTER

BLDG: 5 - RENO MEDICAL

CENTER

LEVEL: 2

SCALE: 1/32” = 1’-0”

DATE: 07/14/2020

N

IT CLOSET

K2784A

REMEDIATE IN PLACE

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

RENO MEDICAL CENTER

BLDG: 6 - RENO MEDICAL

CENTER

LEVEL: 1

SCALE: 1/16” = 1’-0”

DATE: 07/14/2020

N

IT

F1479

REMEDIATE IN

PLACE

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

RENO MEDICAL CENTER

BLDG: 6 - RENO MEDICAL

CENTER

LEVEL: 2

SCALE: 1/16” = 1’-0”

DATE: 07/14/2020

N

IT

F2476

REMEDIATE IN

PLACE

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

RENO MEDICAL CENTER

BLDG: 7 - RENO MEDICAL

CENTER

LEVEL: 1

SCALE: 3/32” = 1’-0”

DATE: 07/14/2020

N

OIT

N217

REMEDIATE

IN PLACE

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

RENO MEDICAL CENTER

BLDG: 8 - RENO MEDICAL

CENTER

LEVEL: 1

SCALE: 1/16” = 1’-0”

DATE: 07/14/2020

N

CLOSET

BOILER ROOM

CLOSET/N105

REMEDIATE IN PLACE

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

RENO MEDICAL CENTER

BLDG: 1 0 - RENO MEDICAL

CENTER

LEVEL: BASEMENT

SCALE: 1/32” = 1’-0”

DATE: 07/14/2020

N

CLOSET

IDF

L0873

REMEDIATE IN PLACE

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

RENO MEDICAL CENTER

BLDG: 1 0 - RENO MEDICAL

CENTER

LEVEL: 1

SCALE: 1/32” = 1’-0”

DATE: 07/14/2020

N

TELE

L1908

RELOCATE TO L1826

NEW

LOCATION

L1826

TELE

L1874

REMEDIATE IN PLACE

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

RENO MEDICAL CENTER

BLDG: 1 2 - RENO MEDICAL

CENTER

LEVEL: 1

SCALE: 1/32” = 1’-0”

DATE: 07/14/2020

N

IT CLOSET

B1169

REMEDIATE IN PLACE

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

RENO MEDICAL CENTER

BLDG: 1 2 - RENO MEDICAL

CENTER

LEVEL: 2

SCALE: 1/32” = 1’-0”

DATE: 07/14/2020

N

SERVER ROOM

B2263

REMEDIATE IN PLACE

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

RENO MEDICAL CENTER

BLDG: 1 2 - RENO MEDICAL

CENTER

LEVEL: 3

SCALE: 1/32” = 1’-0”

DATE: 07/14/2020

N

NOTE: ROOM NOT VISITED BY RFP DEVELOPER.

SCOPE DERIVED FROM FACILITY SELF-ASSESSMENT.

IT

B3198

REMEDIATE IN PLACE

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

RENO MEDICAL CENTER

BLDG: 1 2 - RENO MEDICAL

CENTER

LEVEL: 4

SCALE: 1/32” = 1’-0”

DATE: 07/14/2020

N

CLOSET

B4196

REMEDIATE IN PLACE

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

RENO MEDICAL CENTER

BLDG: 1 2 - RENO MEDICAL

CENTER

LEVEL: 5

SCALE: 1/32” = 1’-0”

DATE: 07/14/2020

N

TELE EQUIP

B5196

REMEDIATE IN PLACE

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

RENO MEDICAL CENTER

BLDG: 1 2 - RENO MEDICAL

CENTER

LEVEL: 6

SCALE: 1/32” = 1’-0”

DATE: 07/14/2020

N

TELE EQUIP

B6197

REMEDIATE IN PLACE

LEGEND

LOCATION OF EXISTING

TR /DC

POTENTIAL LOCATION

N E T WO R K S PAC E D E S I G N

C1353

RENO MEDICAL CENTER

BLDG: 1 - RENO MEDICAL

CENTER

LEVEL: 1

SCALE: 1/4” = 1’-0”

DATE: 07/14/2020

N

ROOM NO. C1353 CLOSET

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

Cooling inadequate Needs dedicated HVAC unit

X Cooling inadequate Needs modifications to existing HVAC systems

X Room Temperature/Humidity

Monitoring Inadequate

Room needs new COMBINATION temperature and humidity monitoring and/or controls from BMS

X Rack Temperature/Humidity

Monitoring Inadequate

Rack needs one (1) new temperature monitoring sensors, humidity sensor, and controls from BMS

Piping over equipment Relocate piping or pipe trough

X UPS Central Monitoring BACnet conversion

No condensate leak detection Needs condensate leak detection

Remote Controlled battery thermostat Wired thermostat

X Micro condensate pump Commercial condensate pump

NOTES: AC MODEL DISCONTINUED.

C O

O

LI

N G

C2355

RENO MEDICAL CENTER

BLDG: 1 - RENO MEDICAL

CENTER

LEVEL: 2

SCALE: 1/4” = 1’-0”

DATE: 07/14/2020

WALL AND CEILING TO BE

REMOVED TO UPGRADE

RACK AND A/C UNIT

ROOM NO. C2355 CLOSET

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

Cooling inadequate Needs dedicated HVAC unit

X Cooling inadequate Needs modifications to existing HVAC systems

X Room Temperature/Humidity

Monitoring Inadequate

Room needs new COMBINATION temperture and humidity monitoring and/or controls from BMS

X Rack Temperature/Humidity

Monitoring Inadequate

Rack needs one (1) new temperature monitoring sensors, humidity sensor, and controls from BMS

Piping over equipment Relocate piping or pipe trough

X UPS Central Monitoring BACnet conversion

No condensate leak detection Needs condensate leak detection

Remote Controlled battery thermostat Wired thermostat

X Micro condensate pump Commercial condensate pump

NOTES: AC MODEL DISCONTINUED. ROOM WILL BE ENLARGED TO ACCOMMODATE AN ADDITIONAL RACK.

C O

O

LI

N G

ROOM NO. C2355 CLOSET

E le ct ri ca l

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

X

Insufficient redundant power connections for network equipment.

Provide (2) 30A, 208V, 5 wire

NEMA L21-30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone PDU

X Insuficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

Missing grounding bus bar Install copper grounding bus bar

X Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per

VA Telecommunications and

Special Telecommunications

Systems Design Manual

X

TR ground bar not connected to

Telecom Main Ground Bar

(TMGB) in the data room

Provide grounding cable to MDF ground bar.

X

No telecommunications bonding backbone to other TR grounding bars

Provide grounding conductor to nearest TR per VA

Telecommunications and Special

Telecommunications Systems

Design Manual

C a b li n g

Inadaquate fiber optic cabling to

TR

Install new as required

X Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A

Approximate number of cables =

700. Approximate total cable length = 115,500’

X Horizontal cable run not to exceed 292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-

260' (70-80M) N

TR

C3355

RENO MEDICAL CENTER

BLDG: 1 - RENO MEDICAL

CENTER

LEVEL: 3

SCALE: 1/4” = 1’-0”

DATE: 07/14/2020

ROOM NO. C3355 OFFICE

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

Cooling inadequate Needs dedicated HVAC unit

X Cooling inadequate Needs modifications to existing HVAC systems

X Room Temperature/Humidity

Monitoring Inadequate

Room needs new COMBINATION temperture and humidity monitoring and/or controls from BMS

X Rack Temperature/Humidity

Monitoring Inadequate

Rack needs one (1) new temperature monitoring sensors, humidity sensor, and controls from BMS

Piping over equipment Relocate piping or pipe trough

X UPS Central Monitoring BACnet conversion

No condensate leak detection Needs condensate leak detection

Remote Controlled battery thermostat Wired thermostat

X Micro condensate pump Commercial condensate pump

NOTES: AC MODEL DISCONTINUED.

C O

O

LI

N G

ROOM NO. C3355 CLOSET

E le ct ri ca l

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

X

Insufficient redundant power connections for network equipment.

Provide (2) 30A, 208V, 5 wire

NEMA L21-30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone PDU

X Insufficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

Missing grounding bus bar Install copper grounding bus bar

X Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per

VA Telecommunications and

Special Telecommunications

Systems Design Manual

X

TR ground bar not connected to

Telecom Main Ground Bar

(TMGB) in the data room

Provide grounding cable to MDF ground bar.

X

No telecommunications bonding backbone to other TR grounding bars

Provide grounding conductor to nearest TR per VA

Telecommunications and Special

Telecommunications Systems

Design Manual

C a b li n g

Inadequate fiber optic cabling to

TR

Install new as required

X Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A.

Approximate number of cables =

972. Approximate total cable length = 160,400'

X Horizontal cable run not to exceed 292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-

260' (70-80M) N

C4355

RENO MEDICAL CENTER

BLDG: 1 - RENO MEDICAL

CENTER

LEVEL: 4

SCALE: 1/4” = 1’-0”

DATE: 07/14/2020

ROOM NO. C4355 OFFICE

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

Cooling inadequate Needs dedicated HVAC unit

X Cooling inadequate Needs modifications to existing HVAC systems

X Room Temperature/Humidity

Monitoring Inadequate

Room needs new COMBINATION temperture and humidity monitoring and/or controls from BMS

X Rack Temperature/Humidity

Monitoring Inadequate

Rack needs one (1) new temperature monitoring sensors, humidity sensor, and controls from BMS

Piping over equipment Relocate piping or pipe trough

X UPS Central Monitoring BACnet conversion

No condensate leak detection Needs condensate leak detection

Remote Controlled battery thermostat Wired thermostat

X Micro condensate pump Commercial condensate pump

NOTES: DUCT PENETRATION THRU WALLS NEEDS TO BE FIRE CAULKED. AC UNIT DISCONTINUED.

C O

O

LI

N G

ROOM NO. C4355 CLOSET

E le ct ri ca l

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

X

Insufficient redundant power connections for network equipment.

Provide (2) 30A, 208V, 5 wire

NEMA L21-30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone PDU

X Insufficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

Missing grounding bus bar Install copper grounding bus bar

X Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per

VA Telecommunications and

Special Telecommunications

Systems Design Manual

X

TR ground bar not connected to

Telecom Main Ground Bar

(TMGB) in the data room

Provide grounding cable to MDF ground bar.

X

No telecommunications bonding backbone to other TR grounding bars

Provide grounding conductor to nearest TR per VA

Telecommunications and Special

Telecommunications Systems

Design Manual

C a b li n g

Inadequate fiber optic cabling to

TR

Install new as required

X Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A.

Approximate number of cables =

743. Approximate total cable length = 122,600'

X Horizontal cable run not to exceed 292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-

C5355

RENO MEDICAL CENTER

BLDG: 1 - RENO MEDICAL

CENTER

LEVEL: 5

SCALE: 1/4” = 1’-0”

DATE: 07/14/2020

ROOM NO. C5355 OFFICE

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

Cooling inadequate Needs dedicated HVAC unit

X Cooling inadequate Needs modifications to existing HVAC systems

X Room Temperature/Humidity

Monitoring Inadequate

Room needs new COMBINATION temperture and humidity monitoring and/or controls from BMS

X Rack Temperature/Humidity

Monitoring Inadequate

Rack needs one (1) new temperature monitoring sensors, humidity sensor, and controls from BMS

Piping over equipment Relocate piping or pipe trough

X UPS Central Monitoring BACnet conversion

No condensate leak detection Needs condensate leak detection

Remote Controlled battery thermostat Wired thermostat

X Micro condensate pump Commercial condensate pump

NOTES: AC MODEL DISCONTINUED.

C O

O

LI

N G

ROOM NO. C5355 CLOSET

E le ct ri ca l

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

X

Insufficient redundant power connections for network equipment.

Provide (2) 30A, 208V, 5 wire

NEMA L21-30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone PDU

X Insufficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

Missing grounding bus bar Install copper grounding bus bar

X Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per

VA Telecommunications and

Special Telecommunications

Systems Design Manual

TR ground bar not connected to

Telecom Main Ground Bar

(TMGB) in the data room

Provide grounding cable to MDF ground bar.

X

No telecommunications bonding backbone to other TR grounding bars

Provide grounding conductor to nearest TR per VA

Telecommunications and Special

Telecommunications Systems

Design Manual

C a b li n g

Inadequate fiber optic cabling to

TR

Install new as required

X Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A.

Approximate number of cables =

608. Approximate total cable length = 100,300'

X Horizontal cable run not to exceed 292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-

C6359

RENO MEDICAL CENTER

BLDG: 1 - RENO MEDICAL

CENTER

LEVEL: 6

SCALE: 1/4” = 1’-0”

DATE: 07/14/2020

ROOM NO. C6359 CLOSET

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

Cooling inadequate Needs dedicated HVAC unit

X Cooling inadequate Needs modifications to existing HVAC systems

X Room Temperature/Humidity

Monitoring Inadequate

Room needs new COMBINATION temperture and humidity monitoring and/or controls from BMS

X Rack Temperature/Humidity

Monitoring Inadequate

Rack needs one (1) new temperature monitoring sensors, humidity sensor, and controls from BMS

Piping over equipment Relocate piping or pipe trough

X UPS Central Monitoring BACnet conversion

No condensate leak detection Needs condensate leak detection

Remote Controlled battery thermostat Wired thermostat

X Micro condensate pump Commercial condensate pump

NOTES: AC MODEL DISCONTINUED.

C O

O

LI

N G

ROOM NO. C6359 CLOSET

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

X

Insufficient redundant power connections for network equipment.

Provide (2) 30A, 208V, 5 wire

NEMA L21-30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone PDU

X Insufficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

Missing grounding bus bar Install copper grounding bus bar

X Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per

VA Telecommunications and

Special Telecommunications

Systems Design Manual

X

TR ground bar not connected to

Telecom Main Ground Bar

(TMGB) in the data room

Provide grounding cable to MDF ground bar.

X

No telecommunications bonding backbone to other TR grounding bars

Provide grounding conductor to nearest TR per VA

Telecommunications and Special

Telecommunications Systems

Design Manual

C a b li n g

X Inadequate fiber optic cabling to

TR

Install new as required

X Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A.

Approximate numbers of cables =

288. Approximate total cable length = 47,600’

X Horizontal cable run not to exceed 292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-

260' (70-80M) N

TR

D2456

RENO MEDICAL CENTER

BLDG: 1 A - RENO MEDICAL

CENTER

LEVEL: 2

SCALE: 1/4” = 1’0”

DATE: 07/14/2020

ROOM NO. D2456 CLOSET

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

Cooling inadequate Needs dedicated HVAC unit

X Cooling inadequate Needs modifications to existing HVAC systems

X Room Temperature/Humidity

Monitoring Inadequate

Room needs new COMBINATION temperture and humidity monitoring and/or controls from BMS

X Rack Temperature/Humidity

Monitoring Inadequate

Rack needs one (1) new temperature monitoring sensors, humidity sensor, and controls from BMS

Piping over equipment Relocate piping or pipe trough

X UPS Central Monitoring BACnet conversion

No condensate leak detection Needs condensate leak detection

X Remote Controlled battery thermostat

Wired thermostat

X Micro condensate pump Commercial condensate pump

NOTES: AC MODEL DISCONTINUED.

C O

O

LI

N G

ROOM NO. D2456 CLOSET

E le ct ri ca l

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

X

Insufficient redundant power connections for network equipment.

Provide (2) 30A, 208V, 5 wire

NEMA L21-30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone PDU

X Insufficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

Missing grounding bus bar Install copper grounding bus bar

X Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per

VA Telecommunications and

Special Telecommunications

Systems Design Manual

X

TR ground bar not connected to

Telecom Main Ground Bar

(TMGB) in the data room

Provide grounding cable to MDF ground bar.

X

No telecommunications bonding backbone to other TR grounding bars

Provide grounding conductor to nearest TR per VA

Telecommunications and Special

Telecommunications Systems

Design Manual

C a b li n g

Inadequate fiber optic cabling to

TR

Install new as required

Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A.

X Horizontal cable run not to exceed 292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-

260' (70-80M)

N

G1585 (Moving to G1576A)

RENO MEDICAL CENTER

ROOM NO. G1576A CLOSET

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

X Cooling inadequate Needs dedicated HVAC unit

Cooling inadequate Needs modifications to existing HVAC systems

X Room Temperature/Humidity

Monitoring Inadequate

Room needs new COMBINATION temperture and humidity monitoring and/or controls from BMS

X Rack Temperature/Humidity

Monitoring Inadequate

Rack needs one (1) new temperature monitoring sensors, humidity sensor, and controls from BMS

Piping over equipment Relocate piping or pipe trough

X UPS Central Monitoring BACnet conversion

No condensate leak detection Needs condensate leak detection

Remote Controlled battery thermostat Wired thermostat

Micro condensate pump Commercial condensate pump

NOTES: RELOCATE EXISTING KELE CONDENSATE LEAK DETECTOR.

C O

O

LI

N G

ROOM NO. G1585/G1567A CLOSET

E le ct ri ca l

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

X

Insufficient redundant power connections for network equipment.

Provide (2) 30A, 208V, 5 wire

NEMA L21-30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone PDU

X Insufficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

X Missing grounding bus bar Install copper grounding bus bar

X Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per

VA Telecommunications and

Special Telecommunications

Systems Design Manual

X

TR ground bar not connected to

Telecom Main Ground Bar

(TMGB) in the data room

Provide grounding cable to MDF ground bar.

X

No telecommunications bonding backbone to other TR grounding bars

Provide grounding conductor to nearest TR per VA

Telecommunications and Special

Telecommunications Systems

Design Manual

C a b li n g

X Inadequate fiber optic cabling to

TR

Install new as required

X Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A.

Approximate number of cables =

500. Approximate total cable length = 82,500’

X Horizontal cable run not to exceed 292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-

260' (70-80M)

BLDG: 1 D - RENO MEDICAL

CENTER

LEVEL: 1

SCALE: 1/4” = 1’0”

DATE: 07/14/2020

G1644

RENO MEDICAL CENTER

ROOM NO. G1644 CLOSET

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

X Cooling inadequate Needs dedicated HVAC unit

Cooling inadequate Needs modifications to existing HVAC systems

X Room Temperature/Humidity

Monitoring Inadequate

Room needs new COMBINATION temperture and humidity monitoring and/or controls from BMS

X Rack Temperature/Humidity

Monitoring Inadequate

Rack needs one (1) new temperature monitoring sensors, humidity sensor, and controls from BMS

Piping over equipment Relocate piping or pipe trough

X UPS Central Monitoring BACnet conversion

No condensate leak detection Needs condensate leak detection

Remote Controlled battery thermostat Wired thermostat

Micro condensate pump Commercial condensate pump

NOTES: CURRENTLY SERVED BY HOUSE AIR.

C O

O

LI

N G

ROOM NO. G1644 CLOSET

E le ct ri ca l

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

X

Insufficient redundant power connections for network equipment.

Provide (2) 30A, 208V, 5 wire

NEMA L21-30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone PDU

X Insufficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

X Missing grounding bus bar Install copper grounding bus bar

X Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per

VA Telecommunications and

Special Telecommunications

Systems Design Manual

X

TR ground bar not connected to

Telecom Main Ground Bar

(TMGB) in the data room

Provide grounding cable to MDF ground bar.

X

No telecommunications bonding backbone to other TR grounding bars

Provide grounding conductor to nearest TR per VA

Telecommunications and Special

Telecommunications Systems

Design Manual

C a b li n g

Inadequate fiber optic cabling to

TR

Install new as required

X Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A.

Approximate number of cables =

500. Approximate total cable length = 82,500’

X Horizontal cable run not to exceed 292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-

260' (70-80M)

BLDG: 1 D - RENO MEDICAL

CENTER

LEVEL: 1

SCALE: 1/4” = 1’0”

DATE: 07/14/2020

H1703

RENO MEDICAL CENTER

ROOM NO. H1703 CLOSET

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

Cooling inadequate Needs dedicated HVAC unit

Cooling inadequate Needs modifications to existing HVAC systems

X Room Temperature/Humidity

Monitoring Inadequate

Room needs new COMBINATION temperture and humidity monitoring and/or controls from BMS

X Rack Temperature/Humidity

Monitoring Inadequate

Rack needs one (1) new temperature monitoring sensors, humidity sensor, and controls from BMS

X Piping over equipment Relocate piping or pipe trough

X UPS Central Monitoring BACnet conversion

X No condensate leak detection Needs condensate leak detection

Remote Controlled battery thermostat Wired thermostat

Micro condensate pump Commercial condensate pump

NOTES: REQUIRES CONDENSATE PAN WITH PAN LEAK DETECTOR.

C O

O

LI

N G

ROOM NO. H1703 CLOSET

E le ct ri ca l

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

X

Insufficient redundant power connections for network equipment.

Provide (2) 30A, 208V, 5 wire

NEMA L21-30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone PDU

X Insufficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

X Missing grounding bus bar Install copper grounding bus bar

X Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per

VA Telecommunications and

Special Telecommunications

Systems Design Manual

X

TR ground bar not connected to

Telecom Main Ground Bar

(TMGB) in the data room

Provide grounding cable to MDF ground bar.

X

No telecommunications bonding backbone to other TR grounding bars

Provide grounding conductor to nearest TR per VA

Telecommunications and Special

Telecommunications Systems

Design Manual

C a b li n g

Inadequate fiber optic cabling to

TR

Install new as required

Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A

X Horizontal cable run not to exceed 292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-

260' (70-80M)

BLDG: 1 D - RENO MEDICAL

CENTER

LEVEL: 1

SCALE: 1/4” = 1’0”

DATE: 07/14/2020

H2703

RENO MEDICAL CENTER

ROOM NO. H2703

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

X Cooling inadequate Needs dedicated HVAC unit

Cooling inadequate

No air conditioning in closet. Have TAB technician determine if the air handler can accommodate TR cfm. Otherwise, provide new HVAC unit as shown above.

X Room Temperature/Humidity

Monitoring Inadequate

Room needs new COMBINATION temperture and humidity monitoring and/or controls from BMS

X Rack Temperature/Humidity

Monitoring Inadequate

Rack needs one (1) new temperature monitoring sensors, humidity sensor, and controls from BMS

Piping over equipment Relocate piping or pipe trough

X UPS Central Monitoring BACnet conversion

No condensate leak detection Needs condensate leak detection

Remote Controlled battery thermostat Wired thermostat

Micro condensate pump Commerciall condensate pump

NOTES: THIS IS A VERY SMALL CLOSET UNDER 20 SF MONITORS 3 MRIs. SUGGEST USING HOUSE AIR.

C O

O

LI

N G

ROOM NO. H2703 CLOSET

E le ct ri ca l

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

X

Insufficient redundant power connections for network equipment.

Provide (2) 30A, 208V, 5 wire

NEMA L21-30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone PDU

X Insufficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

X Missing grounding bus bar Install copper grounding bus bar

X Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per

VA Telecommunications and

Special Telecommunications

Systems Design Manual

X

TR ground bar not connected to

Telecom Main Ground Bar

(TMGB) in the data room

Provide grounding cable to MDF ground bar.

X

No telecommunications bonding backbone to other TR grounding bars

Provide grounding conductor to nearest TR per VA

Telecommunications and Special

Telecommunications Systems

Design Manual

C a b li n g

Inadequate fiber optic cabling to

TR

Install new as required

X Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A.

Approximate number of cables =

300. Approximate total cable length = 49,500’

X Horizontal cable run not to exceed 292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-

260' (70-80M)

BLDG: 1 D - RENO MEDICAL

CENTER

LEVEL: 2

SCALE: 1/4” = 1’0”

DATE: 07/14/2020

G2571

RENO MEDICAL CENTER

ROOM NO. G2605 CLOSET

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

Cooling inadequate Needs dedicated HVAC unit

Cooling inadequate Needs modifications to existing HVAC systems

X Room Temperature/Humidity

Monitoring Inadequate

Room needs new COMBINATION temperture and humidity monitoring and/or controls from BMS

X Rack Temperature/Humidity

Monitoring Inadequate

Rack needs one (1) new temperature monitoring sensors, humidity sensor, and controls from BMS

Piping over equipment Relocate piping or pipe trough

X UPS Central Monitoring BACnet conversion

No condensate leak detection Needs condensate leak detection

Remote Controlled battery thermostat Wired thermostat

Micro condensate pump Commercial condensate pump

C O

O

LI

N G

ROOM NO. G2605 CLOSET

E le ct ri ca l

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

X

Insufficient redundant power connections for network equipment.

Provide (2) 30A, 208V, 5 wire

NEMA L21-30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone PDU

X Insuficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

Missing grounding bus bar Install copper grounding bus bar

X Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per

VA Telecommunications and

Special Telecommunications

Systems Design Manual

TR ground bar not connected to

Telecom Main Ground Bar

(TMGB) in the data room

Provide grounding cable to MDF ground bar.

No telecommunications bonding backbone to other TR grounding bars

Provide grounding conductor to nearest TR per VA

Telecommunications and Special

Telecommunications Systems

Design Manual

C a b li n g

Inadaquate fiber optic cabling to

TR

Install new as required

X Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A.

Approximate number of cables =

460. Approximate total cable length = 75,900’

X Horizontal cable run not to exceed 292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-

260' (70-80M)

BLDG: 1 D - RENO MEDICAL

CENTER

LEVEL: 2

SCALE: 1/4” = 1’0”

DATE: 07/14/2020

N

VHARENEllioS

G2571

G3633

RENO MEDICAL CENTER

ROOM NO. G3633

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

X Cooling inadequate Needs dedicated HVAC unit

Cooling inadequate Needs modifications to existing HVAC systems

X Room Temperature/Humidity

Monitoring Inadequate

Room needs new COMBINATION temperture and humidity monitoring and/or controls from BMS

X Rack Temperature/Humidity

Monitoring Inadequate

Rack needs one (1) new temperature monitoring sensors, humidity sensor, and controls from BMS

Piping over equipment Relocate piping or pipe trough

X UPS Central Monitoring BACnet conversion

No condensate leak detection Needs condensate leak detection

Remote Controlled battery thermostat Wired thermostat

Micro condensate pump Commercial condensate pump

C O

O

LI

N G

ROOM NO. G3614 CLOSET (MOVING TO G3633)

E le ct ri ca l

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

X

Insufficient redundant power connections for network equipment.

Provide (2) 30A, 208V, 5 wire

NEMA L21-30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone PDU

X Insufficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

X Missing grounding bus bar Install copper grounding bus bar

X Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per

VA Telecommunications and

Special Telecommunications

Systems Design Manual

X

TR ground bar not connected to

Telecom Main Ground Bar

(TMGB) in the data room

Provide grounding cable to MDF ground bar.

X

No telecommunications bonding backbone to other TR grounding bars

Provide grounding conductor to nearest TR per VA

Telecommunications and Special

Telecommunications Systems

Design Manual

C a b li n g

X Inadequate fiber optic cabling to

TR

Install new as required

X Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A.

Approximate number of cables =

608. Approximate total cable length = 77,300'

X Horizontal cable run not to exceed 292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-

260' (70-80M)

BLDG: 1 D - RENO MEDICAL

CENTER

LEVEL: 3

SCALE: 1/4” = 1’0”

DATE: 07/14/2020

H3706

RENO MEDICAL CENTER

ROOM NO. H3706 CLOSET

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

X Cooling inadequate Needs dedicated HVAC unit

Cooling inadequate Needs modifications to existing HVAC systems

X Room Temperature/Humidity

Monitoring Inadequate

Room needs new COMBINATION temperture and humidity monitoring and/or controls from BMS

X Rack Temperature/Humidity

Monitoring Inadequate

Rack needs one (1) new temperature monitoring sensors, humidity sensor, and controls from BMS

Piping over equipment Relocate piping or pipe trough

X UPS Central Monitoring BACnet conversion

No condensate leak detection Needs condensate leak detection

Remote Controlled battery thermostat Wired thermostat

Micro condensate pump Commercial condensate pump

NOTES: CURRENTLY SERVED BY HOUSE AIR.

C O

O

LI

N G

ROOM NO. H3706 CLOSET

E le ct ri ca l

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

X

Insufficient redundant power connections for network equipment.

Provide (2) 30A, 208V, 5 wire

NEMA L21-30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone PDU

X Insufficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

Missing grounding bus bar Install copper grounding bus bar

X Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per

VA Telecommunications and

Special Telecommunications

Systems Design Manual

TR ground bar not connected to

Telecom Main Ground Bar

(TMGB) in the data room

Provide grounding cable to MDF ground bar.

No telecommunications bonding backbone to other TR grounding bars

Provide grounding conductor to nearest TR per VA

Telecommunications and Special

Telecommunications Systems

Design Manual

C a b li n g

Inadequate fiber optic cabling to

TR

Install new as required

Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A

X Horizontal cable run not to exceed 292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-

260' (70-80M)

BLDG: 1 D - RENO MEDICAL

CENTER

LEVEL: 3

SCALE: 1/4” = 1’0”

DATE: 07/14/2020

K1778

RENO MEDICAL CENTER

ROOM NO. K1778 CLOSET

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

Cooling inadequate Needs dedicated HVAC unit

Cooling inadequate This unit is undersized by 1/4 to 1/2 ton.

Advise replacing as shown above.

X Room Temperature/Humidity

Monitoring Inadequate

Room needs new COMBINATION temperture and humidity monitoring and/or controls from BMS

X Rack Temperature/Humidity

Monitoring Inadequate

Rack needs one (1) new temperature monitoring sensors, humidity sensor, and controls from BMS

Piping over equipment Relocate piping or pipe trough

X UPS Central Monitoring BACnet conversion

No condensate leak detection Needs condensate leak detection

X Remote Controlled battery thermostat

Wired thermostat

X Micro condensate pump Commercial condensate pump

NOTES: AC MODEL DISCONTINUED.

C O

O

LI

N G

ROOM NO. K1778 CLOSET

E le ct ri ca l

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

X

Insufficient redundant power connections for network equipment.

Provide (2) 30A, 208V, 5 wire

NEMA L21-30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone PDU

X Insufficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

X Missing grounding bus bar Install copper grounding bus bar

X Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per

VA Telecommunications and

Special Telecommunications

Systems Design Manual

X

TR ground bar not connected to

Telecom Main Ground Bar

(TMGB) in the data room

Provide grounding cable to MDF ground bar.

X

No telecommunications bonding backbone to other TR grounding bars

Provide grounding conductor to nearest TR per VA

Telecommunications and Special

Telecommunications Systems

Design Manual

C a b li n g

Inadequate fiber optic cabling to

TR

Install new as required

Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A

X Horizontal cable run not to exceed 292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-

260' (70-80M)

BLDG: 5 - RENO MEDICAL

CENTER

LEVEL: 1

SCALE: 1/4” = 1’0”

DATE: 07/14/2020

K2784A

RENO MEDICAL CENTER

ROOM NO. K2784A CLOSET

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

Cooling inadequate Needs dedicated HVAC unit

Cooling inadequate This unit is undersized by 1/4 to 1/2 ton.

Advise replacing as shown above.

X Room Temperature/Humidity

Monitoring Inadequate

Room needs new COMBINATION temperture and humidity monitoring and/or controls from BMS

X Rack Temperature/Humidity

Monitoring Inadequate

Rack needs one (1) new temperature monitoring sensors, humidity sensor, and controls from BMS

Piping over equipment Relocate piping or pipe trough

X UPS Central Monitoring BACnet conversion

No condensate leak detection Needs condensate leak detection

X Remote Controlled battery thermostat

Wired thermostat

Micro condensate pump Commercial condensate pump

NOTES: AC MODEL DISCONTINUED.

C O

O

LI

N G

ROOM NO. K2784A CLOSET

E le ct ri ca l

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

X

Insufficient redundant power connections for network equipment.

Provide (2) 30A, 208V, 5 wire

NEMA L21-30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone PDU

X Insufficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

Missing grounding bus bar Install copper grounding bus bar

X Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per

VA Telecommunications and

Special Telecommunications

Systems Design Manual

TR ground bar not connected to

Telecom Main Ground Bar

(TMGB) in the data room

Provide grounding cable to MDF ground bar.

No telecommunications bonding backbone to other TR grounding bars

Provide grounding conductor to nearest TR per VA

Telecommunications and Special

Telecommunications Systems

Design Manual

C a b li n g

Inadequate fiber optic cabling to

TR

Install new as required

Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A

X Horizontal cable run not to exceed 292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-

260' (70-80M)

BLDG: 5 - RENO MEDICAL

CENTER

LEVEL: 2

SCALE: 1/4” = 1’0”

DATE: 07/14/2020

F1479

RENO MEDICAL CENTER

ROOM NO. F1479 CLOSET

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

Cooling inadequate Needs dedicated HVAC unit

Cooling inadequate Needs modifications to existing HVAC systems

X Room Temperature/Humidity

Monitoring Inadequate

Room needs new COMBINATION temperture and humidity monitoring and/or controls from BMS

X Rack Temperature/Humidity

Monitoring Inadequate

Rack needs one (1) new temperature monitoring sensors, humidity sensor, and controls from BMS

Piping over equipment Relocate piping or pipe trough

X UPS Central Monitoring BACnet conversion

No condensate leak detection Needs condensate leak detection

X Remote Controlled battery thermostat

Wired thermostat

Micro condensate pump Commercial condensate pump

C O

O

LI

N G

ROOM NO. F1479 CLOSET

E le ct ri ca l

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

X

Insufficient redundant power connections for network equipment.

Provide (2) 30A, 208V, 5 wire

NEMA L21-30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone PDU

X Insufficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

Missing grounding bus bar Install copper grounding bus bar

X Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per

VA Telecommunications and

Special Telecommunications

Systems Design Manual

TR ground bar not connected to

Telecom Main Ground Bar

(TMGB) in the data room

Provide grounding cable to MDF ground bar.

No telecommunications bonding backbone to other TR grounding bars

Provide grounding conductor to nearest TR per VA

Telecommunications and Special

Telecommunications Systems

Design Manual

C a b li n g

Inadequate fiber optic cabling to

TR

Install new as required

Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A

X Horizontal cable run not to exceed 292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-

260' (70-80M)

BLDG: 6 - RENO MEDICAL

CENTER

LEVEL: 1

SCALE: 1/4” = 1’0”

DATE: 07/14/2020

F2476

RENO MEDICAL CENTER

ROOM NO. F2476 CLOSET

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

Cooling inadequate Needs dedicated HVAC unit

Cooling inadequate Needs modifications to existing HVAC systems

X Room Temperature/Humidity

Monitoring Inadequate

Room needs new COMBINATION temperture and humidity monitoring and/or controls from BMS

X Rack Temperature/Humidity

Monitoring Inadequate

Rack needs one (1) new temperature monitoring sensors, humidity sensor, and controls from BMS

Piping over equipment Relocate piping or pipe trough

X UPS Central Monitoring BACnet conversion

No condensate leak detection Needs condensate leak detection

X Remote Controlled battery thermostat

Wired thermostat

Micro condensate pump Commercial condensate pump

C O

O

LI

N G

ROOM NO. F2476 CLOSET

E le ct ri ca l

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

X

Insufficient redundant power connections for network equipment.

Provide (2) 30A, 208V, 5 wire

NEMA L21-30R receptacles, each power from an independent power source, mounted near the equipment rack containing the zone PDU

X Insufficient UPS power backup.

Provide UPS with minimum 20 minute run time capacity and redundant, hot swappable batteries.

Missing grounding bus bar Install copper grounding bus bar

X Inadequate grounding connections to metal objects in TR

Provide bonding conductors to non-energized metal surfaces per

VA Telecommunications and

Special Telecommunications

Systems Design Manual

X

TR ground bar not connected to

Telecom Main Ground Bar

(TMGB) in the data room

Provide grounding cable to MDF ground bar.

X

No telecommunications bonding backbone to other TR grounding bars

Provide grounding conductor to nearest TR per VA

Telecommunications and Special

Telecommunications Systems

Design Manual

C a b li n g

Inadequate fiber optic cabling to

TR

Install new as required

Horizontal and/or patch data cabling below minimum Cat 5e.

Replace all cabling with Cat 6A

X Horizontal cable run not to exceed 292 feet

Conduct diamond analysis to verify maximum horizontal distance does not exceed 230-

260' (70-80M)

BLDG: 6 - RENO MEDICAL

CENTER

LEVEL: 2

SCALE: 1/4” = 1’0”

DATE: 07/14/2020

N217

RENO MEDICAL CENTER

ROOM NO. N217 STORAGE

"X" EXISTING ISSUES RECOMMENDED SOLUTIONS

Cooling inadequate Needs dedicated HVAC unit

This is the start of the file's text. The full file is on GovTribe.