Attachment 17 - Fire_Protection_Drawings.pdf

PDF 925 KB Posted

Attached to
Y1DZ--463-301 Construct Mental Health Building and Surface Parking Alaska (VA-22-00023262)
Solicitation number
36C77622B0047
Issued by

About this file

This document package includes construction drawings and specifications for a fire sprinkler system as well as details of a related federal contract opportunity for construction of a Mental Health Building and parking lot for the Department of Veterans Affairs in Alaska.

The construction drawings show the layout of the wet pipe fire sprinkler system for the new two-story Mental Health Building, including site plans, riser details, and sprinkler plans for each floor. Key elements of the system include a 6-inch domestic water entrance, 4-inch riser manifold, fire department connection, and sprinkler coverage for ordinary hazard Group 1 and light hazard areas. The federal contract opportunity is solicitation number 36C77622B0047 to provide design-build construction services for the Mental Health Building and surface parking area. The solicitation is issued by the VA Technology Acquisition Center in Austin, Texas, with responses due on an unspecified date.

View the file

Other files

File Type Posted
0005 Attachment 1 - Anchorage AK Wage Rates.pdf PDF
36C77622B0047 0005.docx DOCX document
0004 Attachment 1 -Construct Mental Health Facility Question Responses 2.pdf PDF
36C77622B0047 0004.docx DOCX document
36C77622B0047 0003.docx DOCX document
0003 Attachment 1 - Geotechnical Assessment - VA Anchorage Mental Health - Submitted.pdf PDF
0003 Attachment 3 - VA fire protection manual.pdf PDF
0003 Attachment 2 - Geotech and Environmental Assessment Bldg 100.pdf PDF
Amendment 0002 36C77622B0047.pdf PDF
0002 Alaska Mental Health Facility - Bidder Question Responses.pdf PDF
36C77622B0047 0001.pdf PDF
Attachment A - Site Visit Sign in - Alaska.pdf PDF
36C77622B0047 0001.docx DOCX document
Attachment 2 - Specifications-VOL_2.pdf PDF
Attachment 20 - Civil Drawings 3-4.pdf PDF
Attachment 6 - Gen Drawings 3-4.pdf PDF
Attachment 21 - Civil Drawings 4-4.pdf PDF
Attachment 19 - Civil Drawings 2-4.pdf PDF
Attachment 14 - Structural Drawings.pdf PDF
Attachment 24 - Limitations on Subcontracting - Construction.pdf PDF
Attachment 22 - JA Brand Name.pdf PDF
Attachment 18 - Civil Drawings 1-4.pdf PDF
Attachment 10 - Architectural Drawings 3-5.pdf PDF
Attachment 13 - Electrical Drawing.pdf PDF
Attachment 7 - Gen Drawings 4-4.pdf PDF
Attachment 8 - Architectural Drawings 1-5.pdf PDF
Attachment 5 - Gen Drawings 2-4.pdf PDF
Attachment 1 - Specifications-VOL_1.pdf PDF
Attachment 9 - Architectural Drawings 2-5.pdf PDF
Attachment 23 - COVID-19 Safety Protocols.pdf PDF
Attachment 4 - Gen Drawings 1-4.pdf PDF
Attachment 3 - Specifications-VOL_3.pdf PDF
36C77622B0047_1.docx DOCX document
Attachment 25 - Contractor Safety - Environmental Form.pdf PDF
Attachment 12 - Architectural Drawings 5-5.pdf PDF
Attachment 11 - Architectural Drawings 4-5.pdf PDF
Attachment 16 - Mechanical_Drawings.pdf PDF
Attachment 15 - Plumbing_Drawings.pdf PDF
Show all 38

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

99+30

0+0

1+0

2+0

103+00

+0

+0

6+0

7+0

+0

+8

FLOW SWITCH

TAMPER SWITCH

SCREWED OS&Y VALVE

FS

HORN/STROBE ASSEMBLY

FIRE DEPARTMENT CONNECTION

RISER LOCATION

H

TS

* DISTANCE PIPE FROM DECK

FLANGE

GROOVED ELBOW UP

GROOVED ELBOW DOWN

GROOVED COUPLING

SCREWED ELBOW DOWN

SCREWED ELBOW UP

GROOVED COUPLING ELBOW

SYMBOL DESCRIPTION

*ALTERNATE SPRINKLER TEMPERATURES MAYBE NOTED NEXT TO SYMBOL

(I.E. INT = INTERMEDIATE; HIGH = HIGH TEMPERATURE)

FIRE SPRINKLER LEGEND

NEW UNDERGROUND FIRE SERVICE

NEW UNDERGROUND WATER MAIN/FIRE MAIN

EXISTING UNDERGROUND WATER MAIN/FIRE MAIN

ABOVE FINISHED FLOOR

ALL THREAD ROD

AUTOMATIC SPRINKLER

CUT IN FIELD

DOWN

FINISHED GRADE

GALVANIZED

GROOVE BOTH ENDS

GALVANIZED MALLEABLE IRON

GROOVE ONE END

OUTSIDE STEM & YOKE

RISER NIPPLE

THREAD BOTH ENDS

THREAD ONE END

THREAD AND GROOVE

UNLESS OTHERWISE NOTED

WITH

A.S.

ATR

AFF

CIF

DN

FG

GALV

GBE

GOE

GMI

OS&Y

RN

TBE

TOE

T&G

UON

W/

ELECTRIC BELL

SPRINKLER

FIRE HYDRANT

1.

2.

3.

4.

5.

GENERAL FIRE SPRINKLER NOTES:

WET PIPE SPRINKLER SYSTEM SHALL BE DESIGNED AND

INSTALLED IN ACCORDANCE WITH THE FOLLOWING CRITERIA.

HAZARDS FOR INDIVIDUAL AREAS ARE NOTED ON DRAWINGS:

SPRINKLER HEADS SHALL BE ORIFICE, STYLE AND TEMPERATURE TO MEET

CODE.

SYSTEM TESTS SHALL BE IN ACCORDANCE WITH SPECIFICATIONS

ORDINARY HAZARD GROUP 1 DESIGN CRITERIA:

DESIGN DENSITY: 0.15 GPM/SQ FT

DESIGN AREA: 1500 SQ FEET

250 HOSE ALLOWANCE

LIGHT HAZARD DESIGN CRITERIA:

DESIGN DENSITY: 0.10 GPM/SQ FT

DESIGN AREA: 1500 SQ FEET

100 HOSE ALLOWANCE

ALL VALVES ON THE RISERS AND TRIM PIPING, INCLUDING BUT NOT LIMITED TO

SECTIONAL VALVES, INSPECTOR'S TEST VALVE AND DRAIN VALVES TO BE

MARKED WITH PERMANENT TAGS OR SIGNS INDICATING THE VALVES NORMAL

OPERATING POSITION.

FIRE SPRINKLER SYSTEM SHALL COMPLY WITH THE FOLLOWING:

A. NFPA 13

B. NFPA 101

C. VA FIRE PROTECTION DESIGN MANUAL

OH-1

LH

6. PROVIDE SEISMIC BRACING AND SEISMIC RATED MATERIALS FOR FIRE

SPRINKLER SYSTEM.

7. DO NOT DISCHARGE WATER FROM FIRE HYDRANTS ONTO THE GROUND UNLESS

TEMPATURE IS ABOVE 40°F.

EXISTING FIRE

HYDRANT TO REMAIN

NEW FIRE HYDRANT

EXISTING FIRE

HYDRANT TO REMAIN

W

W

W

W

W

W

NEW ADDITION

EXISTING VA CLINIC AND OFFICE

NOT IN CONTRACT SCOPE OF WORK

NEW RISER

LOCATION

NEW FDC

NEW ELECTRIC

BELL

EXISTING FDC SHALL BE

PROVIDED WITH SIGN INDICATING

LOCATION OF REMOTE FDC

NEW 8" WATER LINE

Location

Issue Date

Project Number

Drawing Number

Project Title

Checked Drawn

Drawing Title

FACILITY

MANAGEMENT

SERVICE

(FMS)

Phase

Scale

Dwg.

Revisions: Date:

of xx

100% CONSTRUCTION

DOCUMENTS

A/E: STAMP

COFFMAN ENGINEERS

800 F STREET

ANCHORAGE, AK 99501

907-276-6664

ELIOT JORDON, PE

VA FORM 08 -

A

B

C

D

E

321 4 5 6 7 8 9 10 11 12

321 4 5 6 7 8 9 10 11 12

F

G

H

1/24/2020INITIAL PROJECT ASSESSMENT

5/20/202035% SUBMITTAL

7/31/2020

10/26/2020

65% SUBMITTAL

95% SUBMITTAL

12/07/2020100% CONSTRUCTION DOCUMENTS

As indicated

FP100

463-301

DEC. 07, 2020 ELJ SEW

FIRE SPRINKLER SITE

PLAN AND LEGEND

MENTAL HEALTH BUILDING

AND PARKING LOT

AVAHS Muldoon Clinic

1201 N. MULDOON RD, ANCHORAGE AK

- SCALE:FP100 1" = 60'-0"FP100

FIRE SPRINKLER REFERENCE SITE PLAN11

1"=60'-0" 6030 120 1800

T S

TA

E

A K

AF ALO

49 TH

S

REG IST ER ED PR O F E S S IO NA L ENG IN

EER

ELIOT L. JORDAN

No. FP136078

800 F. Street Anchorage, AK 99501

AECC249

907-276-6664

COFFMAN ENGINEERS

Dec 18, 2020

RISER LEGEND:

6" DOUBLE CHECK VALVE ASSEMBLY WITH FLANGED OS&Y VALVES AND

TAMPER SWITCHES - PROVIDE (2) "CONTROL VALVE" SIGNS WITH CHAIN

FOR THE OS&Y VALVES.

4" RISER MANIFOLD WITH FLOW SWITCH, TEST AND DRAIN VALVE,

PRESSURE GAUGE AND PRESSURE RELIEF VALVE - SIGNAGE TO BE

PROVIDED - "INSPECTORS TEST" AND "MAIN DRAIN" WORDING.

MAIN DRAIN THROUGH WALL.

PIPE STAND.

FDC CONNECTION TO EXTERIOR WALL

A

B

C

D

E

B

A

DD

C

E

NEW 8" WATER LINE, SEE CIVIL

DRAWINGS FOR CONTINUATION

GENERAL NOTES:

1. PIPE SIZES MAY BE REDUCED BASED UPON

HYDRAULIC CALCULATIONS

Location

Issue Date

Project Number

Drawing Number

Project Title

Checked Drawn

Drawing Title

FACILITY

MANAGEMENT

SERVICE

(FMS)

Phase

Scale

Dwg.

Revisions: Date:

of xx

100% CONSTRUCTION

DOCUMENTS

A/E: STAMP

COFFMAN ENGINEERS

800 F STREET

ANCHORAGE, AK 99501

907-276-6664

ELIOT JORDON, PE

VA FORM 08 -

A

B

C

D

E

321 4 5 6 7 8 9 10 11 12

321 4 5 6 7 8 9 10 11 12

F

G

H

1/24/2020INITIAL PROJECT ASSESSMENT

5/20/202035% SUBMITTAL

7/31/2020

10/26/2020

65% SUBMITTAL

95% SUBMITTAL

12/07/2020100% CONSTRUCTION DOCUMENTS

As indicated

FP101

463-301

DEC. 07, 2020 ELJ SEW

FIRE SPRINKLER RISER

DETAIL

MENTAL HEALTH BUILDING

AND PARKING LOT

AVAHS Muldoon Clinic

1201 N. MULDOON RD, ANCHORAGE AK

- SCALE:FP101 1/2" = 1'-0"FP101

FIRE SPRINKLER RISER DETAIL11

NOT TO SCALE

T S

TA

E

A K

AF ALO

49 TH

S

REG IST ER ED PR O F E S S IO NA L ENG IN

EER

ELIOT L. JORDAN

No. FP136078

800 F. Street Anchorage, AK 99501

AECC249

907-276-6664

W9

W0

S90S120S150S180S210S240S270S300

FP101

6" DOMESTIC WATER

ENTRANCE.

4" TO WET SYSTEM

OH-1

OPEN TO STRUCTURE ABOVE

OPEN TO STRUCTURE ABOVE

OH-1OH-1

OH-1

LH

LH

LH

PROVIDE SPRINKLER AT BOTTOM OF

SHAFT IN ACCORDANCE WITH NFPA 13,

SIDEWALL SPRINKLER SHALL BE NOT

MORE THAN 2 FT ABOVE SHAFT FLOOR.

CHECK VALVE

OPEN TO STRUCTURE ABOVE, PROVIDE

SPRINKLERS UNDER ANY DUCTWORK

WIDER THAN 4 FT.

HALLWAY IS SERVED BY

EXISTING SPRINKLER SYSTEM

EXISTING NON-ACCESSIBLE

RATED SHAFT FOR

PLUMBING CONVEYANCE

P-3

1A300

1A301

1A401

1A402

1A403

STAIR

ELEVATOR

ELEVATOR

MACHINE RM.

SPRINKLER

RISER

STORAGE

MECHANICAL

INTERSTITIAL

SPACE

Location

Issue Date

Project Number

Drawing Number

Project Title

Checked Drawn

Drawing Title

FACILITY

MANAGEMENT

SERVICE

(FMS)

Phase

Scale

Dwg.

Revisions: Date:

of xx

100% CONSTRUCTION

DOCUMENTS

A/E: STAMP

COFFMAN ENGINEERS

800 F STREET

ANCHORAGE, AK 99501

907-276-6664

ELIOT JORDON, PE

VA FORM 08 -

A

B

C

D

E

321 4 5 6 7 8 9 10 11 12

321 4 5 6 7 8 9 10 11 12

F

G

H

1/24/2020INITIAL PROJECT ASSESSMENT

5/20/202035% SUBMITTAL

7/31/2020

10/26/2020

65% SUBMITTAL

95% SUBMITTAL

12/07/2020100% CONSTRUCTION DOCUMENTS

1/8" = 1'-0"

FP201

463-301

DEC. 07, 2020 ELJ SEW

FIRST FLOOR FIRE

SPRINKLER PLAN

MENTAL HEALTH BUILDING

AND PARKING LOT

AVAHS Muldoon Clinic

1201 N. MULDOON RD, ANCHORAGE AK

PLAN

NORTH

0 8' 16' 24'2' 6'4' 1/8" = 1'-0"

- SCALE:FP201 1/8" = 1'-0"FP201

FIRST FLOOR FIRE SPRINKLER PLAN11

T S

TA

E

A K

AF ALO

49 TH

S

REG IST ER ED PR O F E S S IO NA L ENG IN

EER

ELIOT L. JORDAN

No. FP136078

800 F. Street Anchorage, AK 99501

AECC249

907-276-6664

SS

K3

K5

K7

K1

K0

K2

K3

K5

K7

KJ

KH

KG

KF

KE KD KC KAA

KBKCKDKE

K1

KFKGKJ

KE

KH

K0

K2

K4

K-A

S296

W9

W0

S90S120S150S180S210S240S270

LH

LH

OH-1

LH

LH

LH

LH LH

LH

LH

LH

LH

LH

LH

LH LH LH LH LH

LHOH-1

LH

LH

LH

LHLH

LH

LH

LH

LH

LH

LH LH LH LH LH

LH

LH

LH

LH

LH

LHLHLHLH

LH

LH

LH LH LH LH

LH

LH

LH

LH

LH LH

LH

LH

SPRINKLER NOT REQUIRED

AT TOP OF SHAFT PER NFPA

13 9.3.6.6, SHAFT

IS CONSTRUCTED OF NON

COMBUSTIBLE MATERIAL.

LH

HALLWAY IS SERVED BY EXISTING SPRINKLER SYSTEM

2A304

MULTI-STATION

WORK ROOM

2A306

CONSULTATION

ROOM

2A308

EXAM

ROOM

2A309

EXAM

ROOM

2A305

MULTI-STATION

WORK ROOM

2A307

GROUP

THERAPY

2A302

STORAGE

2A400

ELECTRICAL

P-3

ELEVATOR

STAIR

2A354

CHECK

OUT

2A353

CHECK

IN

2A352

WAITING AREA

2A310

MH

CHIEF

2A311

OFFICE

COUNSELOR

2A313

SUPERVISOR

OFFICE

2A312

SUPERVISOR

OFFICE

2A315

OFFICE

COUNSELOR

2A317

CONSULTATION

OFFICE

2A321

CONSULTATION

OFFICE

C2-2C

CORRIDOR

2A322

OFFICE

COUNSELOR

2A319

MULTI-STATION

WORK ROOM

C2-2G

CORRIDOR

2A314

CONSULTATION

OFFICE

2A323

CONSULTATION

OFFICE

2A320

SUPERVISOR

OFFICE

C2-2B

CORRIDOR

C2-2A

CORRIDOR

C2-2

CORRIDOR

C2-2E

CORRIDOR

C2-2F

CORRIDOR

C2-2C

CORRIDOR2A318

STAFF

TOILET

2A325

PATIENT

TOILET

2A324

PATIENT

TOILET

2A327

CONSULTATION

OFFICE

2A329

CONSULTATION

OFFICE

2A331

OFFICE

COUNSELOR

2A333

CONSULTATION

OFFICE

2A335

CONSULTATION

OFFICE

2A336

CONSULTATION

OFFICE

2A334

CONSULTATION

OFFICE

2A332

EXAM

2A330

EXAM

2A348

EXAM

2A346

EXAM

2A344

CONSULTATION

OFFICE

2A342

CONSULTATION

OFFICE

2A338

MULTI-STATION

WORK ROOM

2A339

BREAK ROOM2A340

STAFF

TOILET

2A341

STORAGE

2A343

CONSULTATION

OFFICE

2A345

CONSULTATION

OFFICE

2A347

CONSULTATION

OFFICE

2A349

TELEHEALTH

MEDICINE

2A350

TELEHEALTH

MEDICINE

2A351

IT/DATA

2A326

JANITOR

2A328

STORAGE

Location

Issue Date

Project Number

Drawing Number

Project Title

Checked Drawn

Drawing Title

FACILITY

MANAGEMENT

SERVICE

(FMS)

Phase

Scale

Dwg.

Revisions: Date:

of xx

100% CONSTRUCTION

DOCUMENTS

A/E: STAMP

COFFMAN ENGINEERS

800 F STREET

ANCHORAGE, AK 99501

907-276-6664

ELIOT JORDON, PE

VA FORM 08 -

A

B

C

D

E

321 4 5 6 7 8 9 10 11 12

321 4 5 6 7 8 9 10 11 12

F

G

H

1/24/2020INITIAL PROJECT ASSESSMENT

5/20/202035% SUBMITTAL

7/31/2020

10/26/2020

65% SUBMITTAL

95% SUBMITTAL

12/07/2020100% CONSTRUCTION DOCUMENTS

1/8" = 1'-0"

FP202

463-301

DEC. 07, 2020 ELJ SEW

SECOND FLOOR FIRE

SPRINKLER PLAN

MENTAL HEALTH BUILDING

AND PARKING LOT

AVAHS Muldoon Clinic

1201 N. MULDOON RD, ANCHORAGE AK

PLAN

NORTH

0 8' 16' 24'2' 6'4' 1/8" = 1'-0"

- SCALE:FP202 1/8" = 1'-0"FP202

SECOND FLOOR FIRE SPRINKLER PLAN11

T S

TA

E

A K

AF ALO

49 TH

S

REG IST ER ED PR O F E S S IO NA L ENG IN

EER

ELIOT L. JORDAN

No. FP136078

800 F. Street Anchorage, AK 99501

AECC249

907-276-6664

Sheets
FP100 - FIRE SPRINKLER SITE PLAN AND LEGEND
FP101 - FIRE SPRINKLER RISER DETAIL
FP201 - FIRST FLOOR FIRE SPRINKLER PLAN
FP202 - SECOND FLOOR FIRE SPRINKLER PLAN

File details come from the government source that posted it. Updated .