Attachment - 17 EHRM Bonham -Simulation Main Computer Rm 1- CFD Analysis.pdf
PDF 9 MB Posted
- Solicitation number
- 36C77624B0007
About this file
This CFD analysis report details simulations conducted for the Main Computer Room of the VA medical center in Bonham, TX. The analysis modeled one 70kW CRAC unit operating at full capacity to cool fully-loaded data center equipment in an initial room temperature of 85 degrees Fahrenheit. Over a 10-minute transient simulation, the average room temperature dropped to 74 degrees Fahrenheit with inlet temperatures to racks ranging from 64 to 77 degrees Fahrenheit and outlet temperatures of 82 to 86 degrees Fahrenheit. The simulation determined that a single unit at full output could sufficiently cool the space and equipment. Key metrics analyzed included temperature distributions, airflow vectors, component temperatures, and fluid forces on walls. Accompanying visuals depict results from various viewpoints and planes.
The related federal contract opportunity is for construction services for EHRM projects at the VA medical center in Bonham, TX, solicited by the VA Technology Acquisition Center in Austin under solicitation number 36C77624B0007. The opportunity involves construction of a new MCR and aims to incorporate the thermal analysis findings to adequately cool IT infrastructure as the facility is built out.
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EHRM BONHAM - MCR –
ONE UNIT FULL CAPACITY
CFD ANALYSIS
Prepared by: Spur Design, BAJ
Date: Monday, June 19, 2023
Spur Design
EHRM Bonham - MCR - CFD Analysis.cfdst Prepared by: Blake Juett
Page 1 Generated with Autodesk CFD 2021
Report Contents
Summary _________________________________________________________________________________________________ 2
Description ________________________________________________________________________________________________________2
Design 1___________________________________________________________________________________________________ 3
One Unit Full Capacity ____________________________________________________________________________________________3
Materials ________________________________________________________________________________________________________3
Boundary Conditions __________________________________________________________________________________________5
Initial Conditions _______________________________________________________________________________________________5
Mesh _____________________________________________________________________________________________________________6
Physics __________________________________________________________________________________________________________7
Solver Settings __________________________________________________________________________________________________7
Convergence ____________________________________________________________________________________________________7
Results __________________________________________________________________________________________________________8
Decision Center _________________________________________________________________________________________ 11
Summary Images ________________________________________________________________________________________________ 11
XY Plane Temperature Billboard – View 1 __________________________________________________________________ 11
XY Plane Temperature Billboard – View 2 __________________________________________________________________ 12
YZ Plane Temperature Billboard – View 1 __________________________________________________________________ 13
YZ Plane Temperature Billboard – View 2 __________________________________________________________________ 14
Airflow Streamer – View 1 ___________________________________________________________________________________ 15
Airflow Streamer – View 2 ___________________________________________________________________________________ 16
Page 2 Generated with Autodesk CFD 2021
Summary
DESCRIPTION
This report contains the results and images from a CFD simulation of the Main Computer Room
(MCR) for the VA medical center in Bonham, TX. This report displays the findings from a simulation of a MCR using of one 70kW CRAC unit at full capacity to cool data center equipment running at full load. The initial temperature of the room was set to 85 degrees Fahrenheit. This was a transient analysis that ran for roughly 10 minutes. At the end of the 10 minutes the average room temperature was 74 degrees Fahrenheit. Inlet temperatures into the racks ranged from 64 degrees Fahrenheit to 77 degrees Fahrenheit. Outlet temperatures out of the racks ranged from
82 to 86 degrees Fahrenheit. The simulation found that one unit running at full capacity was sufficient in cooling the space and the equipment.
Page 3 Generated with Autodesk CFD 2021
Design 1
Length units foot
Coordinate system Cartesian 3D
ONE UNIT FULL CAPACITY
MATERIALS
Page 4 Generated with Autodesk CFD 2021
NAME ASSIGNED TO PROPERTIES
Air Volume
Density Equation of State
Viscosity 1.817e-05 Pa-s
Conductivity 0.02563 W/m-K
Specific heat 1004.0 J/kg-K
Compressibility 1.4
Emissivity 1.0
Wall roughness 0.0 meter
Phase Vapor Pressure
Stainless Steel
(304)
Part1.1-CRU-514-2
Part1.1-CRU-514-1
Part1.Coils - 1
X-Direction Piecewise Linear
Y-Direction Same as X-dir.
Z-Direction Same as X-dir.
Density 8.0 g/cm3
Specific heat 0.5 J/g-K
Emissivity 0.54
Transmissivity 0.0
Electrical resistivity 7.2e-05 ohm-cm
Glass Wool Part1.1-517-001
Part1.1-517-002
X-Direction 0.038 W/m-K
Z-Direction Same as X-dir.
Density 24.0 kg/m3
Specific heat 700.0 J/kg-K
Emissivity 0.8
Transmissivity 0.0
Electrical resistivity 40000000000000.0
Aluminum
Alloy (6063)
Part1.MDA-B
Part1.MDA-A
Part1.SC - 9
Part1.SC - 7
Part1.SC - 5
Part1.SC - 3
Part1.HDA-A
Part1.SC - 1
Part1.SC - 2
Part1.SC - 4
Part1.SC - 6
Part1.SC - 8
Part1.HDA-B
Part1.MDA-A (1)
Part1.MDA-B (1)
X-Direction 218.0 W/m-K
Z-Direction Same as X-dir.
Density 2.7 g/cm3
Specific heat 0.9 J/g-K
Emissivity 0.2
Transmissivity 0.0
Electrical resistivity 2.99e-06 ohm-cm
Page 5 Generated with Autodesk CFD 2021
Stainless Steel
(304)
Part1.1-CRU-514-2
Part1.1-CRU-514-1
Part1.Coils - 1
X-Direction Piecewise Linear
Z-Direction Same as X-dir.
Density 8.0 g/cm3
Specific heat 0.5 J/g-K
Emissivity 0.54
Transmissivity 0.0
Electrical resistivity 7.2e-05 ohm-cm
DS070 - Full
Cap
Part1.Coils - 2
Flow 9000.0 ft3/min
Heat Transfer Heat Input/Extraction
BOUNDARY CONDITIONS
TYPE ASSIGNED TO
Total Heat Generation(3500 W) Part1.MDA-B
Part1.MDA-A
Part1.SC - 9
Part1.SC - 7
Part1.SC - 5
Part1.SC - 3
Part1.SC - 1
Part1.SC - 2
Part1.SC - 4
Part1.SC - 6
Part1.SC - 8
Part1.MDA-A (1)
Part1.MDA-B (1)
Total Heat Generation(2800 W) Part1.HDA-A
Part1.HDA-B
Film Coefficient(3.5
BTU/ft2/h/F, 100 Fahrenheit)
Surface:128
Surface:129
Surface:130
Surface:133
Surface:134
Surface:171
INITIAL CONDITIONS
TYPE ASSIGNED TO
Temperature(85 Fahrenheit) Volume
Page 6 Generated with Autodesk CFD 2021
MESH
Automatic Meshing Settings
Surface refinement 0
Gap refinement 0
Resolution factor 1.0
Edge growth rate 1.1
Minimum points on edge 2
Points on longest edge 10
Surface limiting aspect ratio 20
Mesh Enhancement Settings
Mesh enhancement 1
Enhancement blending 0
Number of layers 3
Layer factor 0.45
Layer gradation 1.05
Meshed Model
Number of Nodes 44924
Number of Elements 169068
Page 7 Generated with Autodesk CFD 2021
PHYSICS
Flow On
Compressibility Incompressible
Heat Transfer On
Auto Forced Convection Off
Gravity Components 0.0, 0.0, -32.174
Radiation On
Scalar No scalar
Turbulence On
SOLVER SETTINGS
Solution mode Transient
Solver computer MyComputer
Intelligent solution control Off
Advection scheme ADV 5
Turbulence model k-epsilon
CONVERGENCE
Iterations run 600
Solve time 703 seconds
Solver version 21.0.20201120
Energy Balance
Fluid Energy Balance Information (numerical) energy out - 2.4542 Btu/s heat transfer due to sources in 0.0 Btu/s heat transfer from wall to fluid 39.557 Btu/s mdotin x cp x (tout - tin) -64.858 Btu/s radiation heat balance 0.0 4.0969
Solid Energy Balance Information heat transfer due to sources in 48.39 Btu/s heat transfer from exterior to 0.50716 Btu/s heat transfer from fluid to solid -39.557 Btu/s
Mass Balance
IN OUT
Mass flow 0.0 0.0
Volume flow 0.0 f^3/s 0.0 f^3/s
Page 8 Generated with Autodesk CFD 2021
RESULTS
Inlets and Outlets inlet 1 (heat exchanger outlet - part 2) inlet bulk pressure 7.09059 psf inlet bulk temperature 52.342 F inlet mach number 0.00932077 mass flow in 0.360849 minimum x,y,z of 0.0 node near minimum 5.0 reynolds number 258657.0 surface id 23.0 volume flow in 150.0 f^3/s inlet 2 (heat exchanger inlet - part 2) inlet bulk pressure 6.49373 psf inlet bulk temperature 76.1682 F inlet mach number 0.00911119 mass flow in -0.344805 minimum x,y,z of 0.0
Page 9 Generated with Autodesk CFD 2021 node near minimum 18.0 reynolds number 247157.0 surface id 24.0 total mass flow in 0.0160442 total vol. flow in 0.00334594 f^3/s volume flow in -149.997 f^3/s inlet 1 (heat exchanger outlet - part 2) inlet bulk pressure 7.09059 psf inlet bulk temperature 52.342 F inlet mach number 0.00932077 mass flow in 0.360849 minimum x,y,z of 0.0 node near minimum 5.0 reynolds number 258657.0 surface id 23.0 volume flow in 150.0 f^3/s
Field Variable Results
VARIABLE MAX MIN
cond 0.0349583 B/f-s-R 4.11001e-06 B/f-s-R dens 15.5086 lbf-s^2/f^4 0.00222363 lbf-s^2/f^4 econd 0.0593352 B/f-s-R 0.0 B/f-s-R emiss 1.0 0.0 evisc 0.020048 lbf-s/f^2 0.0 lbf-s/f^2 gent 602.215 1/s 0.0145279 1/s press 7.19775 psf 0.0 psf ptotl 7.57063 psf 0.0 psf scal1 0.0 0.0 seebeck 0.0 V/K 0.0 V/K shgc 0.0 0.0 spech 7.71567 B-f/lbf-s^2R 3.84246 B-f/lbf-s^2R temp 100.909 F 55.342 F transmiss 0.0 0.0 turbd 753.229 f^2/s^3 1.49389e-07 f^2/s^3 turbk 106.502 f^2/s^2 3.79148e-10 f^2/s^2 ufactor 0.0 0.0 visc 3.79148e-07 lbf-s/f^2 0.0 lbf-s/f^2 vx vel 8.69385 f/s -37.1593 f/s vy vel 35.7109 f/s -11.6361 f/s vz vel 10.8389 f/s -37.7388 f/s wrough 0.0 f 0.0 f
Page 10 Generated with Autodesk CFD 2021
Component Thermal Summary
PART MINIMUM
TEMPERATURE
MAXIMUM
TEMPERATURE
VOLUME AVERAGED
TEMPERATURE
Part1.1-CRU-514-2 55.342 80.2455 72.375
Part1.Coils - 2 0 0 0
Part1.MDA-B 68.266 82.7425 76.8078
Part1.MDA-A 70.9232 82.5556 76.8648
Part1.SC - 9 74.4534 85.4609 78.6439
Part1.SC - 7 73.3556 86.5423 80.0479
Part1.SC - 5 74.3476 86.5073 80.3858
Part1.SC - 3 76.0896 86.4799 80.6594
Part1.HDA-A 75.3606 83.0263 76.9208
Part1.1-517-001 55.342 100.126 86.8117
Part1.1-517-002 66.174 100.909 90.4619
Part1.SC - 1 72.3593 86.4691 80.0547
Part1.SC - 2 76.4927 86.4003 80.7167
Part1.SC - 4 77.0326 86.3984 80.5235
Part1.SC - 6 74.8967 86.5321 80.2708
Part1.SC - 8 73.5307 86.5543 79.8667
Part1.HDA-B 64.2455 83.0721 75.0263
Part1.MDA-A (1) 67.6527 82.6822 76.8685
Part1.MDA-B (1) 65.8973 82.538 76.5788
Part1.1-CRU-514-1 73.5457 80.5604 75.2292
Part1.Coils - 1 74.531 81.8478 75.3625
Volume 55.342 86.3419 73.679
Fluid Forces on Walls pressx 0.9841 pounds pressy -0.52438 pounds pressz -0.21 pounds shearx -0.01630 pounds sheary -0.010503 pounds shearz -0.034964 pounds
Page 11 Generated with Autodesk CFD 2021
Decision Center
SUMMARY IMAGES
XY PLANE TEMPERATURE BILLBOARD – VIEW 1
Temperature Distribution with Directional Airflow Vectors.
Page 12 Generated with Autodesk CFD 2021
XY PLANE TEMPERATURE BILLBOARD – VIEW 2
Page 13 Generated with Autodesk CFD 2021
YZ PLANE TEMPERATURE BILLBOARD – VIEW 1
Page 14 Generated with Autodesk CFD 2021
YZ PLANE TEMPERATURE BILLBOARD – VIEW 2
Page 15 Generated with Autodesk CFD 2021
AIRFLOW STREAMER – VIEW 1
Directional Airflow Streamers Colored by Temperature.
Page 16 Generated with Autodesk CFD 2021
AIRFLOW STREAMER – VIEW 2
Directional Airflow Streamers Colored by Temperature.