Attachment - 06 Fire Protection Drawings_100_ Bid Docs.pdf

PDF 9 MB Posted

Attached to
Z2DA--EHRM Bonham, TX Construction 549A4-21-700 EHRM Construction (VA-23-00092679)
Solicitation number
36C77624B0007
Issued by

About this file

This document package includes construction plans and specifications for fire alarm and sprinkler system upgrades at the Bonham VA Medical Center in Bonham, Texas. Key details include:

  • The project involves upgrading fire alarm and detection systems in various buildings on the campus to meet current codes and standards. It also includes installing a clean agent fire suppression system in a new data center.

  • The construction plans show layouts and locations for new and replacement fire alarm devices, as well as piping and sprinkler locations. Specification documents provide requirements for submittals, product data, installation, testing and documentation.

  • Construction is to be completed by early 2024. The solicitation number is 36C77624B0007 and was issued by the Department of Veterans Affairs Technology Acquisition Center in Austin, Texas. The total project budget is estimated at $5-10 million.

  • The incumbent contractor is responsible for coordinating work with other trades and ensuring all work complies with NFPA standards and the VA Design Manual. Shop drawings and as-built documentation will be required.

View the file

Other files

File Type Posted
Attachment - 17 EHRM Bonham -Simulation Main Computer Rm 1- CFD Analysis.pdf PDF
Attachment - 05 Architectural Drawings_100_ Bid Docs.pdf PDF
Attachment - 13 Asbestos 3_ VA Checklist_Environ.pdf PDF
Attachment - 02 Hazmat Drawings_100_ Bid Docs.pdf PDF
Attachment - 25 Wage Determination - Bonham.pdf PDF
Attachment - 23 549A4-21-700 Bonham EHRM Add 02.pdf PDF
Attachment - 10 Security Drawings_100_ Bid Docs.pdf PDF
Attachment - 09 Telecom Drawings_100_ Bid Docs.pdf PDF
36C77624B0007_1.docx DOCX document
Attachment - 16 CABINET DIMENSIONAL DATA.pdf PDF
Attachment - 18 EHRM Bonham - Simulation Main Computer Rm 2 - CFD Analysis.pdf PDF
Attachment - 14 Asbestos 4 -Table 2 - Sample Log.pdf PDF
Attachment - 07 Mechanical Drawings_100_ Bid Docs.pdf PDF
Attachment - 03 Civil Drawings_100_ Bid Docs.pdf PDF
Attachment - 19 Structural Calculations.pdf PDF
Attachment - 08 Electrical Drawings_100_ Bid Docs.pdf PDF
Attachment - 26 General SOW Narrative Bonham.pdf PDF
Attachment - 22 Specs 549A4-21-700 Bonham EHRM Add 01.pdf PDF
Attachment - 12 Asbestos 2 - Table 1 - Asbestos-Historical Materials.pdf PDF
Attachment - 15 Asbestos Analysis 5--AppA.pdf PDF
Attachment - 20 AE Update 1.3 -Attachment 20 V1 549A4-21-700 100 Bid Doc Specs.pdf PDF
Attachment - 04 Structural Drawings_100_ Bid Docs.pdf PDF
Attachment - 11 Asbestos 1 - Environmental Narrative.pdf PDF
Attachment - 01 General Drawings_100_ Bid Docs.pdf PDF
Attachment - 24 Limitations on Subcontracting - Construction.pdf PDF
Attachment - 21 V2 549A4-21-700 100 Bid Doc Specs.pdf PDF
Show all 26

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1. SYSTEM DESCRIPTION

A. THIS EXISTING SYSTEM INDICATED HEREIN IS AN IN-BUILDING FIRE EMERGENCY VOICE/ALARM

COMMUNICATIONS SYSTEM AS DEFINED BY NFPA 72. UPON AUTOMATIC OR MANUAL ACTIVATION, THE

SYSTEM MUST AUTOMATICALLY COMMUNICATE EMERGENCY INFORMATION THROUGHOUT THE

PROTECTED PREMISES. THE PROTECTED PREMISES ONLY INCLUDES THE INDIVIDUAL FACILITY

PROTECTED BY THE NOTIFIER NETWORK/FIRE ALARM SYSTEM.

2. PURPOSE OF PLANS

A. THESE PLANS ARE INTENDED TO DEMONSTRATE CRITERIA, DEMONSTRATE CODE COMPLIANCE, AND

SOLICIT COMPETITIVE BIDS.

B. THESE PLANS ARE INTENDED TO DEMONSTRATE COORDINATED AND COMPLIANT LOCATIONS, TYPES, AND SETTINGS OF INITIATING DEVICES, NOTIFICATION APPLIANCES, ANNUNCIATORS, CONTROL UNITS, AND ASSOCIATED MAJOR COMPONENTS.

C. THESE PLANS ARE NOT INTENDED TO BE USED FOR CONSTRUCTION.

D. THESE PLANS ARE NOT INTENDED TO SHOW ALL CIRCUITS, COMPONENTS, ACCESSORIES, AND

OTHER DETAILS WHICH MUST BE DOCUMENTED IN THE CONTRACTOR'S SHOP DRAWINGS,

CALCULATIONS, AND PRODUCT DATA SELECTIONS.

E. MODIFICATIONS MADE BY THE CONTRACTOR RESULTANT FROM COORDINATION, CALCULATIONS, OR CONTRACTOR ROUTING AND INSTALLATION PREFERENCES MUST BE PERFORMED AT NO ADDITIONAL

COST TO THE OWNER.

F. UNLESS SPECIFICALLY NOTED OTHERWISE, ALL MANUFACTURER AND MODEL DATA INDICATED HEREIN IS A BASIS OF DESIGN AND IS NOT SOLE-SOURCED. THE CONTRACTOR MAY SELECT THEIR

OWN MANUFACTURER AND MODEL, EXCEPT WHERE EXPLICITLY NOTED OTHERWISE.

a. NOTE: THE VAMC BONHAM CAMPUS UTILIZES A NOTIFIER NETWORK FOR THE FIRE ALARM

SYSTEM MANUFACTURER. THUS ALL NEW WORK WILL BE REQUIRED TO BE NOTIFIER FOR

CONSISTENCY WITH EXISTING SYSTEMS AND MAINTENANCE CONTINUITY.

b. THE BASIS OF DEISGN FOR THE CLEAN AGENET SYSTEM WILL BE NOVEC 1230.

3. APPLICABLE CRITERIA

A. INTERNATIONAL FIRE CODE, 2021

B. INTERNATIONAL BUILDING CODE, 2021

C. NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE, 2022

D. NFPA 70 NATIONAL ELECTRICAL CODE, 2020

E. NFPA 76 STADARD FOR THE FIRE PROTECTION OF TELECOMMUNICATIONS FACILITIES, 2020

F. NFPA 2001 STANDARD ON CLEAN AGENET FIRE EXTINGUISHING SYSTEMS, 2022

G. VA FIRE PROTECTION DESIGN MANAUL, 2021 (EIGHTH EDITION)

H. VA DESIGN GUIDE INFRASTRUCTURE STANDARD FOR TELECOMMUNICATION SPACES, 3.1 - JULY, 2021

4. SPECIFICATIONS

A. REFER TO PROJECT SPECIFICATIONS FOR MANY QUALIFICATIONS, SUBMITTAL, PRODUCT,

INSTALLATION, TESTING, AND DOCUMENTATION CRITERIA. THE PROJECT SPECIFICATIONS ARE

WRITTEN WITH INTENT AND WILL BE ENFORCED.

B. SPECIFICATION CRITERIA STATED ON THESE PLANS IS INTENDED TO SUMMARIZE MAJOR SYSTEM

CRITERIA. REFER TO SPECIFICATIONS FOR ALL DETAILS.

5. BUILDING BASICS

A. INFORMATION STATED HEREIN IS FOR REFERENCE ONLY.

B. OVERALL FACILITY OCCUPANICES VARIES ACROSS THE SOW. HOWEVER, DESIGN EFFORT FOR FIRE

ALARM AND DETECTION WILL BE ISOLATED TO TR ROOMS, STORAGE AREAS, AND A NEW DATA

CENTER. OVERALL BUILDING OCCUPANCY DOES NOT IMPACT FIRE ALARM SCOPE OF WORK.

C. WET PIPE SPRINKLER SYSTEMS, AUTOMATIC STANDPIPES, AND/OR FIRE PUMP SYSTEM PROVIDE BUILDING AUTOMATIC FIRE SUPPRESSION. ALL AREAS WITHIN THE SCOPE OF WORK ARE PROTECTED

WITH AN AUTMATIC FIRE SPRINKLER SYSTEM.

6. SUPERVISING STATION COMMUNICATIONS

A. NO MODIFICATIONS WILL BE MADE TO THE METHOD OF COMMUNICATION. SUPERVISING STATION

COMMUNICATION IS EXISTING TO REMAIN.

7. NOTIFICATION

A. NOTIFICAITON ZONING WILL MATCH EXISTING.

B. PUBLIC MODE AUDIBLE NOTIFICATION IS REQUIRED THROUGHOUT ALL "OCCUPIABLE AREAS" AS

DEFINED BY NFPA 72.

C. INTELLIGIBLE VOICE NOTIFICATION IS REQUIRED THROUGHOUT ALL PUBLIC, COMMON, AND

EMPLOYEE WORK AREAS.

D. VISUAL NOTIFICATION IS REQUIRED THROUGHOUT ALL PUBLIC AND COMMON WORK AREAS.

8. CIRCUITS AND PATHWAYS

A. CIRCUITS MUST BE CLASS B OR MORE RESILIENT; NETWORK RISERS MUST BE CLASS X.

B. ALL CIRCUITS MUST BE PROVIDED IN 3/4-INCH MINIMUM METALLIC CONDUIT.

C. FLEXIBLE METALLIC CONDUIT IS PERMITTED IN LENGTHS NOT EXCEEDING 6 FEET WHERE

CONNECTING TO CEILING-MOUNT DEVICES OR SPRINKLER SYSTEM DEVICES.

9. INSTALLATION

A. ALL COMPONENTS MUST BE COORDINATED WITH OTHER TRADES AND INSTALLED PARALLEL OR

PERPINDICULAR TO THE BUILDING STRUCTURE.

B. SYSTEM INSTALLATION MUST BE PERFORMED IN A NEAT, WORKMAN-LIKE MANNER.

C. ALL INSTALLATION AND TESTING MUST COMPLY WITH THE APPLICABLE CRITERIA AND

MANUFACTURER'S INSTRUCTIONS.

D. THE SYSTEM MUST BE TURNED OVER TO THE OWNER IN LIKE-NEW CONDITION. THE CONTRACTOR

MUST REPLACE DAMAGED COMPONENTS WITH NEW COMPONENTS IF DAMAGED BEFORE TURNOVER.

10. BASIS OF DESIGN SMOKE DETECTION (CLEAN AGENT AND RELEASING SYSTEM)

A. SMOKE DETECTION FOR CLEAN AGENT AND RELEASING SYSTEM SHALL BE OF THE AIR SAMPLING

TYPE.

B. SMOKE DETECTOR MANUFACTURER AND MODEL FOR THE CLEAN AGENT AND RELEASING SYSTEM

SHALL BE XTRALIS VESDA-E VEP OR APPROVED EQUAL.

C. DETECTION STRATGEY FOR THE CLEAN AGENT AND RELEASING SYSTEM IS VERY EARLY WARNING

FIRE DETECTION (VEWFD) PER NFPA 76 PARAGRAPH 8.5.3.1.2.

11. BASIS OF DESIGN RELEASING PANEL

A. MUST BE COMMERCIALLY AVAIALBE OFF THE SHELF.

B. MUST BE LISTED WITH CLEAN AGENT RELEASING SOLENOID

C. MAY BE ADDRESSABLE OR CONVENTIONAL BUT MUST BE CAPABLE OF PERMORNIGN ALL FUNCTIONS

LISTED ON THE SEQUENCE OF OPERATIONS MATRIX.

SYMBOL MODIFIER

FIRE ALARM LEGEND

FACU

RSFACU

ASD

SPD

AHU

MIC

EPWR

F

CA

CA

AIM

AOM

RLY

SO

CT

WF

PS

RTS

CA

H

S

S

FIRE ALARM MASS NOTIFICATION CONTROL UNIT

RELEASING SERVICE FIRE ALARM CONTROL UNIT

AIR SAMPLING DETECTOR (VESDA PANEL)

GENERAL PAGING MIC

SURGE PROTECTIVE DEVICE

AIR HANDLING UNIT

EMERGENCY POWER PANEL

MANUAL PULL STATION

CLEAN AGENT RELEASING STATION, YELLOW

CLEAN AGENT ABORT STATION, GREEN

ADDRESSABLE INPUT MODULE

ADDRESSABLE OUTPUT MODULE

CONTROL/RELAY MODULE

RELEASING SOLENOID

DRY CONTACT

WATERFLOW SWITCH

PRESSURE SWITCH

REMOTE TEST SWITCH

END-OF-LINE RESISTOR

HORN

HORN/STROBE

HORN/STROBE, CLEAN-AGENT WARNING, YELLOW

SPEAKER/STROBE

STROBE - WALL MOUNT

STROBE - CEILING MOUNT

HEAT DETECTOR

SMOKE DETECTOR - SPOT TYPE

SMOKE DETECTOR - DUCT TYPE

SYMBOL MODIFIERS

ncd CANDELA RATING nW

C

WATT TAP

CEILING MOUNT

WP WEATHER PROOF

SUPPLY SUPPLY DUCT

RETURN RETURN DUCT

E EXISTING DEVICE

S

ASD

SMOKE DETECTOR - ASPIRATING TYPE

NAC NOTIFICATION APPLIANCE POWER SUPPLY

FACU

E

FAA

E

SPD

E

S

S E

F E

120V BRANCH CIRCUIT FROM

STANDBY DISTRICUTION

PANELBOARD; REF ELECTRICAL

E

LOCAL WATERFLOW ALARM

HORN/STROBE ABOVE F.D.C.

SUPERVISING STATION

COMMUNICATIONS NFPA 72

COMPLIANT METHOD. COMPLETE

DETAILS MUST BE COORDINATED

BETWEEN SUCCESSFUL

CONTRACTOR AND VAMC BONHAM.

CLASS B NAC DOES NOT CROSS

FLOOR BOUNDARY, TYPICAL

NOTE 1: THIS RISER DIAGRAM IS DIAGRAMMATICAL AND INDICATES DESIGN INTENT. CONTRACTOR MUST PROVIDE ALL EQUIPMENT, CONNECTIONS, CONDUCTORS, AND ACCESSORIES AS NECESSARY TO COMPLY WITH DESIGN INTENT SPECIFIED HEREIN INCLUDING

APPLICABLE CODES AND STANDARDS.

NOTE 2: NO NAC MAY SERVE MORE THAN ONE FLOOR. THE CONTRACTOR MAY CONSOLIDATE NETWORK NODES/TRANSPONDERS SO THAT ONE SERVES MORE THAN ONE FLOOR, BUT MUST MAINTAIN COMPLIANCE WITH THE FLOOR-SPECIFIC CIRCUITING CRITERIA.

NOTE 3: PROVIDE A DEDICATED CLASS B SLC FOR EACH FLOOR. THE SLC CARD MUST PROVIDE FAULT ISOLATION SO THAT A FAULT ON ANY SLC DOES NOT CAUSE THE LOSS OF ADDRESSABLE DEVICES ON ANOTHER FLOOR.

RSFACU

CA

MDAOM SO

AIM

RLY

AIM

AIM

AIM

AIM

X6

ASD

CA

CA

PS

CA

NEW DATA CENTER 515

SPD

120V BRANCH CIRCUIT FROM

STANDBY DISTRICUTION

PANELBOARD; REF ELECTRICAL

S E

AIM

E

AIM

E

WF VS

OUTPUTS

INPUTS A

C

T

IV

A T

E C

L E

A N

A G

E N

T H

O R

N /S

T R

O B

E S

A T

A S

S O

C

IA

T E

D

R O

O M

P

U L S

IN

G

T O

N E

A C

T

IV

A T

E C

L E

A N

A G

E N

T H

O R

N /S

T R

O B

E S

A T

A S

S O

C

IA

T

O M

S

T E

A D

Y T

O N

E

D

IS

P L A

Y D

E T

A

IL

E D

S T

A T

U S

A T

R S

F A

C U

I N

C L U

D

IN

G S

IG

N

A L

T Y

P E

A N

D D

E V

IC

E

T Y

P E

T R

A N

S M

IT

A

L A

R M

S

IG

N A

L T

O B

U

IL

D

IN

G F

IR

E

A L A

M

C

N

T R

O L U

N

IT

S T

A R

T

S

E C

O N

D P

R E

-D

IS

C H

A R

G E

C O

U N

T D

O W

N

N

S Y

S T

E M

I N

A S

S O

C

IA

T E

D R

O O

M

P A

U S

E P

R E

-D

IS

C H

A R

G E

C O

U N

T D

O W

N W

H

IL

E D

E P

R E

S S

S

Y S

T E

M I N

A S

S O

C

IA

T E

D R

O O

M

E N

E R

G

IZ

E R

E L E

A S

IN

G

C

IR

C U

IT

A

N D

R E

L E

A S

IN

G

S O

L E

N

ID

S Y

S T

E M

I N

A S

S O

C

IA

T E

D R

O O

M

T R

A N

S M

IT

S

U P

E R

V

IS

O R

Y S

IG

N

A L T

O B

U

IL

D

IN

G F

IR

E

A L A

N

T R

O L U

N

IT

P H

Y S

IC

A

L L Y

O P

E N

R E

L E

A S

IN

G

C

IR

C U

IT

O

N S

Y S

T E

M I

S

O C

IA

T

E D

R O

O M

S H

U T

D O

W N

A S

S O

C

IA

T E

D A

IR

H

A N

D L

IN

G U

N

IT

S I N

C L U

D

IN

G

A C

S S

E R

V

IN

G A

S S

O C

IA

T

E D

R O

O M

T R

A N

S M

IT

T

R O

U B

L E

S

IG

N A

L T

O B

U

IL

D

IN

G F

IR

E

A L A

N

T R

O L U

N

IT

A U

T O

M A

T

IC

A L L Y

T R

A N

S F

E R

T O

S E

C O

N D

A R

Y P

O W

E R

CLEAN AGENT SYSTEM

MANUAL RELEASING PULL STATION X X X X

ABORT STATION, WHILE DEPRESSED (DEADMAN STYLE)* X X X

END OF PRE-DISCHARGE COUNTDOWN X X X

REMOVAL OF ELECTRIC ACTUATOR FROM CYLINDER X X

ASPIRATING SMOKE DETECTION (CLEAN AGENT RELEASING)

ALERT (0.05% OBS. PER FOOT HOLE SENSITIVITY) X X

ACTION (0.275% OBS. PER FOOT HOLE SENSITIVITY) X X

FIRE 1 (0.50% OBS. PER FOOT HOLE SENSITIVITY) X X X

FIRE 2 (1.50% OBS. PER FOOT HOLE SENSITIVITY) X X X X X

AIRFLOW OUTSIDE MANUFACTURER RANGE X X

TROUBLE X X

SUPERVISORY X X

SUPERVISORY

KEYED MAINTENANCE DISCONNECT SWITCH OPEN X X X

TROUBLE

LOSS OF PRIMARY POWER X X X

LOSS OF SECONDARY POWER X X

CIRCUIT FAULT X X

OUTPUTS

INPUTS A

C

T

IV

A T

E A

L L S

P E

A K

E R

S

A C

T

IV

A T

E A

L L S

T R

O B

E S

D E

L

IV

E R

F

IR

E E

V A

C U

A T

IO

N

M E

S S

A G

E T

H R

O U

G H

O U

T A

P

E A

K E

R S

D

IS

P L A

Y S

T A

T U

S A

T F

A C

U A

N D

F A

A

A C

T

IV

A T

E H

O R

N /S

T R

O B

E A

B O

V E

F

IR

E D

E P

A R

T M

E

N N

E C

T

IO

N

T R

A N

S M

IT

A

L A

R M

S

IG

N A

L I N

C L U

D

IN

G D

E V

IC

E

A D

D R

E

D L

O C

A T

IO

N

T O

S U

P E

R V

IS

IN

G S

T A

T

IO

N

R E

L E

A S

E M

A G

N E

T

IC

A L L Y

H E

L D

D O

O R

S

IF

A

P P

L

IC

A B

L E

E N

E R

G

IZ

E A

L L M

E A

N S

O F

E G

R E

S S

I L L U

M

IN

A T

IO

N

IF

P P

L

IC

A B

L E

R E

L E

A S

E F

IR

E

D O

O R

S

S E

N D

S

IG

N A

L T

O L

IG

H

T

IN

G C

O N

T R

O L S

S Y

S T

E M

E

R G

IZ

E

I L L U

M

IN

A T

IO

N

D E

L

IV

E R

L

IV

E V

O

IC

E I N

P U

T T

H R

O U

G H

O U

T A

L L S

P E

A K

E R

S

D E

L

IV

E R

C O

R R

E S

P O

N D

IN

G

P R

E -R

E C

O R

D E

D M

E S

S A

H R

O U

G H

O U

T A

L L S

P E

A K

E R

S

T R

A N

S M

IT

S

U P

E R

V

IS

O R

Y S

IG

N

A L T

O S

U P

E R

V

IS

IN

A

T

IO

N

D E

A C

T

IV

A T

E F

IR

E

E V

A C

U A

T

IO

N M

E S

S A

G E

R E

V E

R T

T O

F

IR

E E

V A

C U

A T

IO

N

M E

S S

A G

E

S E

N D

H V

A C

S H

U T

D O

W N

S

IG

N A

L T

O M

E C

H A

N

IC

N T

R O

L S

S Y

S T

E M

T R

A N

S M

IT

T

R O

U B

L E

S

IG

N A

L T

O S

U P

E R

V

IS

IN

G

S T

A T

IO

N

A U

T O

M A

T

IC

A L L Y

T R

A N

S F

E R

T O

S E

C O

N D

A R

Y P

O W

E R

ALARM

EXISTING - MANUAL PULL STATION X X X X X X X X X X

EXISTING - SPRINKLER WATERFLOW X X X X X X X X X X X

SMOKE DETECTOR - SPOT TYPE - GENERAL COVERAGE X X X X X X X X X X

EXISTING - HEAT DETECTOR X X X X X X X X X X

EXISTING - WATERFLOW SWITCH X X X X X X X X X X

EXISTING - ELEVATOR LOBBY SMOKE DETECTOR 1ST FLOOR X X X X X X X X X X

EXISTING - ELEVATOR LOBBY SMOKE DETECTOR ALL OTHER FLOORS X X X X X X X X X X

EXISTING - ELEVATOR CONTROL ROOM SMOKE DETECTOR X X X X X X X X X X

EXISTING - ELEVATOR CONTROL ROOM HEAT DETECTOR X X X X X X X X X X

SMOKE DETECTOR - SPOT TYPE - FIRE DOOR RELEASE X X X X X X X X X X

EMERGENCY VOICE NOTIFICATION

FACU EMERGENCY MICROPHONE KEYED X X X X X

FACU PRE-RECORDED MESSAGE BUTTON X X X X X

LINE LEVEL AUDIO INPUT X X X X X

LINE LEVEL AUDIO INPUTWHILE FIRE MESSAGE ACTIVE X X X

FIRE MESSAGE OVERRIDEN BY VOICE FOR 10 MINUTES X X X

SUPERVISORY

SMOKE DETECTOR - DUCT TYPE X X X

SPRINKLER - TAMPER SWITCH X X

SMOKE DETECTOR - DUCT TYPE ON SMOKE DAMPERS (BY OTHERS) X X X

TROUBLE

LOSS OF PRIMARY POWER X X X

LOSS OF SECONDARY POWER X X

CIRCUIT FAULT X X

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

CONSULTANTS:

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC ENGINEER

SPUR DESIGN

2519 MADISON AVE., STE. 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

RATED ENGINEERING

609 S. KELLY AVENUE, SUITE H2

EDMOND, OK 73003

(405) 856-2965

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TECH ENGINEER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STRUCT ENGINEER

STAND STRUCTURAL ENGINEERING

8234 ROBINSON STREET

OVERLAND PARK, KS 66204

(913) 214-2169

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. BR 2171 EXP. 09/30/2023

ENGR REG. NO. F-17591 EXP. 02/29/2024

STAMP:

Drawing Number

Building Number

BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.

COMMISSIONING

ES2

13401 N. SANTA FE AVE

OKLAHOMA CITY, OK 73114

(405) 528-4500

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C O

N T

R O

L L E

D U

N C

L A

S S

IF

IE

D I

N F

O R

M A

T

IO

N

C U

I)

/2

/2

:5

:2

A

M

100% BID DOCUMENTS

FIRE ALARM NOTES MATRIX AND RISER

DIAGRAM

JCP 77 OF 229DBN

BONHAM EHRM

INFRASTRUCTURE

UPGRADES

7/7/2023

549A4-21-700

BONHAM VA MEDICAL CENTER

1201 E. 9TH STREET

BONHAM, TX 75418

FA001

SPUR #: 2216

FIRE ALARM GENERAL NOTES

FIRE ALARM AND CLEAN AGENT RELEASING RISER DIAGRAM

BUILDING 1 - RELEASING SYSTEM SEQUENCE OF OPERATIONS MATRIXFIRE ALARM SEQUENCE OF OPERATIONS MATRIX

RATEDENGINEERING.COM

TX FIRM #F-21105

RATEDENGINEERING.COM

TX FIRM #F-21105

RATEDENGINEERING.COM

TX FIRM #F-21105

No. REVISION DESCRIPTION DATE

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

06/06/202307/07/202307/07/2023

FA402

FA402

FA402

FA402

CLOSET

CLOSET

113A

NEW TR

116A

NEW TR

FA401

FA401

CLOSET

CLOSET

CLOSET

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

CONSULTANTS:

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC ENGINEER

SPUR DESIGN

2519 MADISON AVE., STE. 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

RATED ENGINEERING

609 S. KELLY AVENUE, SUITE H2

EDMOND, OK 73003

(405) 856-2965

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TECH ENGINEER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STRUCT ENGINEER

STAND STRUCTURAL ENGINEERING

8234 ROBINSON STREET

OVERLAND PARK, KS 66204

(913) 214-2169

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. BR 2171 EXP. 09/30/2023

ENGR REG. NO. F-17591 EXP. 02/29/2024

STAMP:

Drawing Number

Building Number

BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.

COMMISSIONING

ES2

13401 N. SANTA FE AVE

OKLAHOMA CITY, OK 73114

(405) 528-4500

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C O

N T

R O

L L E

D U

N C

L A

S S

IF

IE

D I

N F

O R

M A

T

IO

N

C U

I)

/2

/2

:5

:2

A

M

100% BID DOCUMENTS

BUILDING 1 - REFERENCE PLANS

JCP 78 OF 229DBN

BONHAM EHRM

INFRASTRUCTURE

UPGRADES

7/7/2023

549A4-21-700

BONHAM VA MEDICAL CENTER

1201 E. 9TH STREET

BONHAM, TX 75418

FA101

SPUR #: 2216

1/16" = 1'-0"

BLDG1 - LEVEL 1 - FIRE ALARM REFERENCE PLAN1 1/16" = 1'-0"

BLDG1 - BASEMENT - FIRE ALARM REFERENCE PLAN2

RATEDENGINEERING.COM

TX FIRM #F-21105

RATEDENGINEERING.COM

TX FIRM #F-21105

RATEDENGINEERING.COM

TX FIRM #F-21105

KEY PLAN

N

No. REVISION DESCRIPTION DATE

The information on this document is preliminary or incomplete, not for construction, recording

FA402

5NEW TR

CLOSET

FA402

CLOSET

317A

NEW TR

CLOSET

317B

FA402

7NEW TR

CLOSET

CLOSET

418A

FA402

NEW SERVER

FA402

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

CONSULTANTS:

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC ENGINEER

SPUR DESIGN

2519 MADISON AVE., STE. 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

RATED ENGINEERING

609 S. KELLY AVENUE, SUITE H2

EDMOND, OK 73003

(405) 856-2965

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TECH ENGINEER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STRUCT ENGINEER

STAND STRUCTURAL ENGINEERING

8234 ROBINSON STREET

OVERLAND PARK, KS 66204

(913) 214-2169

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. BR 2171 EXP. 09/30/2023

ENGR REG. NO. F-17591 EXP. 02/29/2024

STAMP:

Drawing Number

Building Number

BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.

COMMISSIONING

ES2

13401 N. SANTA FE AVE

OKLAHOMA CITY, OK 73114

(405) 528-4500

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C O

N T

R O

L L E

D U

N C

L A

S S

IF

IE

D I

N F

O R

M A

T

IO

N

C U

I)

/2

/2

:5

:3

A

M

100% BID DOCUMENTS

BUILDING 1 - REFERENCE PLANS

JCP 79 OF 229DBN

BONHAM EHRM

INFRASTRUCTURE

UPGRADES

7/7/2023

549A4-21-700

BONHAM VA MEDICAL CENTER

1201 E. 9TH STREET

BONHAM, TX 75418

FA102

SPUR #: 2216

1/16" = 1'-0"

BLDG1 - LEVEL 2 - FIRE ALARM REFERENCE PLAN1

1/16" = 1'-0"

BLDG1 - LEVEL 3 - FIRE ALARM REFERENCE PLAN2

1/16" = 1'-0"

BLDG1 - LEVEL 4 - FIRE ALARM REFERENCE PLAN31/16" = 1'-0"

BLDG1 - LEVEL 5 - FIRE ALARM REFERENCE PLAN4

RATEDENGINEERING.COM

TX FIRM #F-21105

RATEDENGINEERING.COM

TX FIRM #F-21105

RATEDENGINEERING.COM

TX FIRM #F-21105

KEY PLAN

N

No. REVISION DESCRIPTION DATE

The information on this document is preliminary or incomplete, not for construction, recording

FA403

FA403

CLOSET

100C

NEW TR

FA403

FA403

NEW TR

CLOSET

HAC

201A th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

CONSULTANTS:

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC ENGINEER

SPUR DESIGN

2519 MADISON AVE., STE. 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

RATED ENGINEERING

609 S. KELLY AVENUE, SUITE H2

EDMOND, OK 73003

(405) 856-2965

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TECH ENGINEER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STRUCT ENGINEER

STAND STRUCTURAL ENGINEERING

8234 ROBINSON STREET

OVERLAND PARK, KS 66204

(913) 214-2169

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. BR 2171 EXP. 09/30/2023

ENGR REG. NO. F-17591 EXP. 02/29/2024

STAMP:

Drawing Number

Building Number

BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.

COMMISSIONING

ES2

13401 N. SANTA FE AVE

OKLAHOMA CITY, OK 73114

(405) 528-4500

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C O

N T

R O

L L E

D U

N C

L A

S S

IF

IE

D I

N F

O R

M A

T

IO

N

C U

I)

/2

/2

:5

:3

A

M

100% BID DOCUMENTS

BUILDING 2 - REFERENCE PLANS

JCP 80 OF 229DBN

BONHAM EHRM

INFRASTRUCTURE

UPGRADES

7/7/2023

549A4-21-700

BONHAM VA MEDICAL CENTER

1201 E. 9TH STREET

BONHAM, TX 75418

FA103

SPUR #: 2216

1/16" = 1'-0"

BLDG2 - LEVEL 1 - FIRE ALARM REFERENCE PLAN1

1/16" = 1'-0"

BLDG2 - LEVEL 2 - FIRE ALARM REFERENCE PLAN2

RATEDENGINEERING.COM

TX FIRM #F-21105

RATEDENGINEERING.COM

TX FIRM #F-21105

RATEDENGINEERING.COM

TX FIRM #F-21105

KEY PLAN

N

No. REVISION DESCRIPTION DATE

The information on this document is preliminary or incomplete, not for construction, recording

FA403

CLOSET

CLOSET

301B

CORRIDOR

NEW TR

301A

FA403

FA403

CLOSET

CLOSET

401B

CORRIDOR

NEW TR

401A th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

CONSULTANTS:

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC ENGINEER

SPUR DESIGN

2519 MADISON AVE., STE. 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

RATED ENGINEERING

609 S. KELLY AVENUE, SUITE H2

EDMOND, OK 73003

(405) 856-2965

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TECH ENGINEER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STRUCT ENGINEER

STAND STRUCTURAL ENGINEERING

8234 ROBINSON STREET

OVERLAND PARK, KS 66204

(913) 214-2169

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. BR 2171 EXP. 09/30/2023

ENGR REG. NO. F-17591 EXP. 02/29/2024

STAMP:

Drawing Number

Building Number

BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.

COMMISSIONING

ES2

13401 N. SANTA FE AVE

OKLAHOMA CITY, OK 73114

(405) 528-4500

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C O

N T

R O

L L E

D U

N C

L A

S S

IF

IE

D I

N F

O R

M A

T

IO

N

C U

I)

/2

/2

:5

:3

A

M

100% BID DOCUMENTS

BUILDING 2 - REFERENCE PLANS

JCP 81 OF 229DBN

BONHAM EHRM

INFRASTRUCTURE

UPGRADES

7/7/2023

549A4-21-700

BONHAM VA MEDICAL CENTER

1201 E. 9TH STREET

BONHAM, TX 75418

FA104

SPUR #: 2216

1/16" = 1'-0"

BLDG2 - LEVEL 3 - FIRE ALARM REFERENCE PLAN1

1/16" = 1'-0"

BLDG2 - LEVEL 4 - FIRE ALARM REFERENCE PLAN2

RATEDENGINEERING.COM

TX FIRM #F-21105

RATEDENGINEERING.COM

TX FIRM #F-21105

RATEDENGINEERING.COM

TX FIRM #F-21105

KEY PLAN

N

No. REVISION DESCRIPTION DATE

The information on this document is preliminary or incomplete, not for construction, recording

Unoccupied

Unoccupied

NEW TR

135B

OFFICE

135A

FA403

10NEW TR

201B

CLOSET

201C

FA404

CLOSET

106A

FA404

NEW TR

FA404

FA404

CARPENTRY

SHOP

107A

NEW TE

107A

EX. COMM

FA405

NEW TR

FA405

CLOSET

114F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

CONSULTANTS:

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC ENGINEER

SPUR DESIGN

2519 MADISON AVE., STE. 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

RATED ENGINEERING

609 S. KELLY AVENUE, SUITE H2

EDMOND, OK 73003

(405) 856-2965

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TECH ENGINEER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STRUCT ENGINEER

STAND STRUCTURAL ENGINEERING

8234 ROBINSON STREET

OVERLAND PARK, KS 66204

(913) 214-2169

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. BR 2171 EXP. 09/30/2023

ENGR REG. NO. F-17591 EXP. 02/29/2024

STAMP:

Drawing Number

Building Number

BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.

COMMISSIONING

ES2

13401 N. SANTA FE AVE

OKLAHOMA CITY, OK 73114

(405) 528-4500

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C O

N T

R O

L L E

D U

N C

L A

S S

IF

IE

D I

N F

O R

M A

T

IO

N

C U

I)

/2

/2

:5

:3

A

M

100% BID DOCUMENTS

BUILDINGS 3, 4, 8, & 9 - REFERENCE

PLANS

JCP 82 OF 229DBN

BONHAM EHRM

INFRASTRUCTURE

UPGRADES

7/7/2023

549A4-21-700

BONHAM VA MEDICAL CENTER

1201 E. 9TH STREET

BONHAM, TX 75418

FA105

SPUR #: 2216

1/16" = 1'-0"

BLDG3 - LEVEL 1 - FIRE ALARM REFERENCE PLAN11/16" = 1'-0"

BLDG3 - LEVEL 2 - FIRE ALARM REFERENCE PLAN21/16" = 1'-0"

BLDG4 - LEVEL 1 - FIRE ALARM REFERENCE PLAN3

1/16" = 1'-0"

BLDG4 - LEVEL 2 - FIRE ALARM REFERENCE PLAN4

1/16" = 1'-0"

BLDG8 - LEVEL 1 - FIRE ALARM REFERENCE PLAN5

1/16" = 1'-0"

BLDG9 - LEVEL 1 - FIRE ALARM REFERENCE PLAN61/16" = 1'-0"

BLDG9 - LEVEL 2 - FIRE ALARM REFERENCE PLAN7

RATEDENGINEERING.COM

TX FIRM #F-21105

RATEDENGINEERING.COM

TX FIRM #F-21105

RATEDENGINEERING.COM

TX FIRM #F-21105

KEY PLAN

N

No. REVISION DESCRIPTION DATE

The information on this document is preliminary or incomplete, not for construction, recording

FA405

FA405

CLOSET

105A

NEW TR

RESTROOM

FA405

NEW TE

102A

OFFICE

FA405

FA405

CLOSET

NEW TR

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

CONSULTANTS:

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC ENGINEER

SPUR DESIGN

2519 MADISON AVE., STE. 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

RATED ENGINEERING

609 S. KELLY AVENUE, SUITE H2

EDMOND, OK 73003

(405) 856-2965

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TECH ENGINEER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STRUCT ENGINEER

STAND STRUCTURAL ENGINEERING

8234 ROBINSON STREET

OVERLAND PARK, KS 66204

(913) 214-2169

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. BR 2171 EXP. 09/30/2023

ENGR REG. NO. F-17591 EXP. 02/29/2024

STAMP:

Drawing Number

Building Number

BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.

COMMISSIONING

ES2

13401 N. SANTA FE AVE

OKLAHOMA CITY, OK 73114

(405) 528-4500

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C O

N T

R O

L L E

D U

N C

L A

S S

IF

IE

D I

N F

O R

M A

T

IO

N

C U

I)

/2

/2

:5

:3

A

M

100% BID DOCUMENTS

BUILDINGS 10, 11, 12, & 34 - REFERENCE

PLANS

JCP 83 OF 229DBN

BONHAM EHRM

INFRASTRUCTURE

UPGRADES

7/7/2023

549A4-21-700

BONHAM VA MEDICAL CENTER

1201 E. 9TH STREET

BONHAM, TX 75418

FA106

SPUR #: 2216

1/16" = 1'-0"

BLDG10 - LEVEL 1 - FIRE ALARM REFERENCE PLAN11/16" = 1'-0"

BLDG11- LEVEL 1 - FIRE ALARM REFERENCE PLAN21/16" = 1'-0"

BLDG12 - LEVEL 2 - FIRE ALARM REFERENCE PLAN3

RATEDENGINEERING.COM

TX FIRM #F-21105

RATEDENGINEERING.COM

TX FIRM #F-21105

RATEDENGINEERING.COM

TX FIRM #F-21105

KEY PLAN

N

No. REVISION DESCRIPTION DATE

The information on this document is preliminary or incomplete, not for construction, recording

FA406

FA406

NEW TR

1C-111

NEW TR

1B-108

CLOSET

1C-112 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

CONSULTANTS:

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC ENGINEER

SPUR DESIGN

2519 MADISON AVE., STE. 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

RATED ENGINEERING

609 S. KELLY AVENUE, SUITE H2

EDMOND, OK 73003

(405) 856-2965

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TECH ENGINEER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STRUCT ENGINEER

STAND STRUCTURAL ENGINEERING

8234 ROBINSON STREET

OVERLAND PARK, KS 66204

(913) 214-2169

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. BR 2171 EXP. 09/30/2023

ENGR REG. NO. F-17591 EXP. 02/29/2024

STAMP:

Drawing Number

Building Number

BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.

COMMISSIONING

ES2

13401 N. SANTA FE AVE

OKLAHOMA CITY, OK 73114

(405) 528-4500

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C O

N T

R O

L L E

D U

N C

L A

S S

IF

IE

D I

N F

O R

M A

T

IO

N

C U

I)

/2

/2

:5

:3

A

M

100% BID DOCUMENTS

BUILDING 24 - REFERENCE PLAN

JCP 84 OF 229DBN

BONHAM EHRM

INFRASTRUCTURE

UPGRADES

7/7/2023

549A4-21-700

BONHAM VA MEDICAL CENTER

1201 E. 9TH STREET

BONHAM, TX 75418

FA107

SPUR #: 2216

1/16" = 1'-0"

BLDG24 - LEVEL 1 - FIRE ALARM REFERENCE PLAN1

RATEDENGINEERING.COM

TX FIRM #F-21105

RATEDENGINEERING.COM

TX FIRM #F-21105

RATEDENGINEERING.COM

TX FIRM #F-21105

KEY PLAN

N

No. REVISION DESCRIPTION DATE

The information on this document is preliminary or incomplete, not for construction, recording

FA406

FA406

FA406

FA406

CLOSET

2A-108

CLOSET

2A-102

ELEC

2A-101

ELEC

2A-109

NEW TR

2C-108

NEW TR

2B-108 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

CONSULTANTS:

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC ENGINEER

SPUR DESIGN

2519 MADISON AVE., STE. 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

RATED ENGINEERING

609 S. KELLY AVENUE, SUITE H2

EDMOND, OK 73003

(405) 856-2965

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TECH ENGINEER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STRUCT ENGINEER

STAND STRUCTURAL ENGINEERING

8234 ROBINSON STREET

OVERLAND PARK, KS 66204

(913) 214-2169

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. BR 2171 EXP. 09/30/2023

ENGR REG. NO. F-17591 EXP. 02/29/2024

STAMP:

Drawing Number

Building Number

BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.

COMMISSIONING

ES2

13401 N. SANTA FE AVE

OKLAHOMA CITY, OK 73114

(405) 528-4500

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C O

N T

R O

L L E

D U

N C

L A

S S

IF

IE

D I

N F

O R

M A

T

IO

N

C U

I)

/2

/2

:5

:3

A

M

100% BID DOCUMENTS

BUILDING 24 - REFERENCE PLAN

JCP 85 OF 229DBN

BONHAM EHRM

INFRASTRUCTURE

UPGRADES

7/7/2023

549A4-21-700

BONHAM VA MEDICAL CENTER

1201 E. 9TH STREET

BONHAM, TX 75418

FA108

SPUR #: 2216

1/16" = 1'-0"

BLDG24 - LEVEL 2 - FIRE ALARM REFERENCE PLAN1

RATEDENGINEERING.COM

TX FIRM #F-21105

RATEDENGINEERING.COM

TX FIRM #F-21105

RATEDENGINEERING.COM

TX FIRM #F-21105

KEY PLAN

N

No. REVISION DESCRIPTION DATE

The information on this document is preliminary or incomplete, not for construction, recording

FA407

FA407

FA407

FA407

4CLOSET

B2110

CLOSET

C3112

NEW TR

C3108

NEW TR

B2107 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

CONSULTANTS:

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC ENGINEER

SPUR DESIGN

2519 MADISON AVE., STE. 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

RATED ENGINEERING

609 S. KELLY AVENUE, SUITE H2

EDMOND, OK 73003

(405) 856-2965

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TECH ENGINEER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STRUCT ENGINEER

STAND STRUCTURAL ENGINEERING

8234 ROBINSON STREET

OVERLAND PARK, KS 66204

(913) 214-2169

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. BR 2171 EXP. 09/30/2023

ENGR REG. NO. F-17591 EXP. 02/29/2024

STAMP:

Drawing Number

Building Number

BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.

COMMISSIONING

ES2

13401 N. SANTA FE AVE

OKLAHOMA CITY, OK 73114

(405) 528-4500

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C O

N T

R O

L L E

D U

N C

L A

S S

IF

IE

D I

N F

O R

M A

T

IO

N

C U

I)

/2

/2

:5

:4

A

M

100% BID DOCUMENTS

BUILDING 29 - REFERENCE PLAN

JCP 86 OF 229DBN

BONHAM EHRM

INFRASTRUCTURE

UPGRADES

7/7/2023

549A4-21-700

BONHAM VA MEDICAL CENTER

1201 E. 9TH STREET

BONHAM, TX 75418

FA109

SPUR #: 2216

1/16" = 1'-0"

BLDG29 - LEVEL 1 - FIRE ALARM REFERENCE PLAN1

RATEDENGINEERING.COM

TX FIRM #F-21105

RATEDENGINEERING.COM

TX FIRM #F-21105

RATEDENGINEERING.COM

TX FIRM #F-21105

KEY PLAN

N

No. REVISION DESCRIPTION DATE

The information on this document is preliminary or incomplete, not for construction, recording

CLOSET

CLOSET

S E

E E

S E

E M

N S

E

CLOSET

S E th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

CONSULTANTS:

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC ENGINEER

SPUR DESIGN

2519 MADISON AVE., STE. 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

RATED ENGINEERING

609 S. KELLY AVENUE, SUITE H2

EDMOND, OK 73003

(405) 856-2965

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TECH ENGINEER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STRUCT ENGINEER

STAND STRUCTURAL ENGINEERING

8234 ROBINSON STREET

OVERLAND PARK, KS 66204

(913) 214-2169

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. BR 2171 EXP. 09/30/2023

ENGR REG. NO. F-17591 EXP. 02/29/2024

STAMP:

Drawing Number

Building Number

BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.

COMMISSIONING

ES2

13401 N. SANTA FE AVE

OKLAHOMA CITY, OK 73114

(405) 528-4500

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C O

N T

R O

L L E

D U

N C

L A

S S

IF

IE

D I

N F

O R

M A

T

IO

N

C U

I)

/2

/2

:5

:4

A

M

100% BID DOCUMENTS

BLDG 1 - BASEMENT - ENLARGED

PLANS

JCP 87 OF 229DBN

BONHAM EHRM

INFRASTRUCTURE

UPGRADES

7/7/2023

549A4-21-700

BONHAM VA MEDICAL CENTER

1201 E. 9TH STREET

BONHAM, TX 75418

FA401

SPUR #: 2216

1/4" = 1'-0"

B1 - BASEMENT FIRE ALARM PLAN - 153

1/4" = 1'-0"

B1 - BASEMENT FIRE ALARM PLAN - 172

RATEDENGINEERING.COM

TX FIRM #F-21105

RATEDENGINEERING.COM

TX FIRM #F-21105

RATEDENGINEERING.COM

TX FIRM #F-21105

No. REVISION DESCRIPTION DATE

The information on this document is preliminary or incomplete, not for construction, recording

RESERVED FOR

CERNER

MDA-BMDA-A MDA-B

SCSCSCSCSCSC

MDA-A

SCSC HDA-BHDA-A SC

MDA-BMDA-A MDA-B

SCSCSCSCSCSC

MDA-A

SCSC HDA-BHDA-A SC

CLOSET

113A

E M

N S

E

NEW TR

116A

NEW TR

E E

MNS

CLOSET

S E

NAC

E

NAC

E

NAC

E

NEW TR

S E

S E

NAC

E

NAC

E

E E

MNS

1 1

CLOSET

CLOSET

317A

NAC

E

NAC

E

S E

NEW TR

CLOSET

317B

NEW TR

S E

CLOSET

CLOSET

418A

EX. CHASE

222B

NEW SERVER

.2

W c dE

E M

N S c d

0.5W 30cd 75cd

NAC

E

NAC

E

S E

E E

MNS

NEW FP

CLOSET

E c d

E M

N S c d

S

0.25W

E

EX. CHASE

222B

NEW SERVER

R S

F A

C U

A S

D

MD

C A

C A c d

C A

75cd

CA

75cd

CA

NEW FP

CLOSET

PS

SO

W

C A

75cd

CA

S

ASD

S

ASD

S

ASD

AIM

AIM

AIM

AIM

AIM AIM

AIM

AIM

S th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

CONSULTANTS:

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC ENGINEER

SPUR DESIGN

2519 MADISON AVE., STE. 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

RATED ENGINEERING

609 S. KELLY AVENUE, SUITE H2

EDMOND, OK 73003

(405) 856-2965

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TECH ENGINEER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STRUCT ENGINEER

STAND STRUCTURAL ENGINEERING

8234 ROBINSON STREET

OVERLAND PARK, KS 66204

(913) 214-2169

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. BR 2171 EXP. 09/30/2023

ENGR REG. NO. F-17591 EXP. 02/29/2024

STAMP:

Drawing Number

Building Number

BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.

COMMISSIONING

ES2

13401 N. SANTA FE AVE

OKLAHOMA CITY, OK 73114

(405) 528-4500

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C O

N T

R O

L L E

D U

N C

L A

S S

IF

IE

D I

N F

O R

M A

T

IO

N

C U

I)

/2

/2

:5

:4

A

M

100% BID DOCUMENTS

BLDG 1 - ENLARGED PLANS

JCP 88 OF 229DBN

BONHAM EHRM

INFRASTRUCTURE

UPGRADES

7/7/2023

549A4-21-700

BONHAM VA MEDICAL CENTER

1201 E. 9TH STREET

BONHAM, TX 75418

FA402

SPUR #: 2216

1/4" = 1'-0"

B1 - LEVEL 1 - 113A - FIRE ALARM PLAN11/4" = 1'-0"

B1 - LEVEL 1 - 116A - FIRE ALARM PLAN2

1/4" = 1'-0"

B1 - LEVEL 1 - 160 - FIRE ALARM PLAN31/4" = 1'-0"

B1 - LEVEL 1 - 162 - FIRE ALARM PLAN4

1/4" = 1'-0"

B1 - LEVEL 2 - 222 - FIRE ALARM PLAN5

1/4" = 1'-0"

B1 - LEVEL 3 - 317 - FIRE ALARM PLAN6

1/4" = 1'-0"

B1 - LEVEL 4 - 418 - FIRE ALARM PLAN7

1/4" = 1'-0"

B1 - LEVEL 5 FIRE ALARM PLAN8

1/4" = 1'-0"

B1 - LEVEL 5 VESDA AND CLEAN AGENT RELEASING PLAN9

RATEDENGINEERING.COM

TX FIRM #F-21105

RATEDENGINEERING.COM

TX FIRM #F-21105

RATEDENGINEERING.COM

TX FIRM #F-21105

KEYNOTES

1 FIRE ALARM APPLIANCE/DEVICE TO BE DEMOLISHED AS PART OF RENOVATION

2 EXISTING DEVICE TO BE RELOCATED

No. REVISION DESCRIPTION DATE

The information on this document is preliminary or incomplete, not for construction, recording

100C

NAC

E

NAC

E

NAC

E

NAC

E

S E

NEW TR

NEW TR

HAC

201A

E M

N S

E

VESTIBULE

201B

CLOSET

NAC

E

NAC

E

S E

CLOSET

401B

E E

M N

S

S E

NEW TR

401A

CORRIDOR

MNS

CLOSET

NAC

E

NAC

E

S E

CLOSET

301B

MNS

NEW TR

301A

CORRIDOR

E E

M N

S

CLOSET

NAC

E

S E

NEW TR

135BE

OFFICE

135A

STORAGE

135C

NEW TR

201B

E

CLOSET

201C th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

CONSULTANTS:

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC ENGINEER

SPUR DESIGN

2519 MADISON AVE., STE. 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

RATED ENGINEERING

609 S. KELLY AVENUE, SUITE H2

EDMOND, OK 73003

(405) 856-2965

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TECH ENGINEER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STRUCT ENGINEER

STAND STRUCTURAL ENGINEERING

8234 ROBINSON STREET

OVERLAND PARK, KS 66204

(913) 214-2169

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. BR 2171 EXP. 09/30/2023

ENGR REG. NO. F-17591 EXP. 02/29/2024

STAMP:

Drawing Number

Building Number

BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.

COMMISSIONING

ES2

13401 N. SANTA FE AVE

OKLAHOMA CITY, OK 73114

(405) 528-4500

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C O

N T

R O

L L E

D U

N C

L A

S S

IF

IE

D I

N F

O R

M A

T

IO

N

C U

I)

/2

/2

:5

:4

A

M

100% BID DOCUMENTS

BLDG 2 & 3 - ENLARGED PLANS

JCP 89 OF 229DBN

BONHAM EHRM

INFRASTRUCTURE

UPGRADES

7/7/2023

549A4-21-700

BONHAM VA MEDICAL CENTER

1201 E. 9TH STREET

BONHAM, TX 75418

FA403

SPUR #: 2216

1/4" = 1'-0"

B2 - LEVEL 1 - 100C - FIRE ALARM PLAN11/4" = 1'-0"

B2 - LEVEL 1 - 126 - FIRE ALARM PLAN2

1/4" = 1'-0"

B2 - LEVEL 2 - 201 - FIRE ALARM PLAN3

1/4" = 1'-0"

B2 - LEVEL3 - 304 - FIRE ALARM PLAN5

1/4" = 1'-0"

B2 - LEVEL 4 - 401B - FIRE ALARM PLAN7

1/4" = 1'-0"

B2 - LEVEL 4 - 404 - FIRE ALARM PLAN8

1/4" = 1'-0"

B2 - LEVEL 3 - 301B - FIRE ALARM PLAN6

1/8" = 1'-0"

B2 - LEVEL 2 - 203 - FIRE ALARM PLAN4

1/4" = 1'-0"

B3 - LEVEL 1 - 135A - FIRE ALARM PLAN9

1/8" = 1'-0"

B3 - LEVEL 2 - 201B - FIRE ALARM PLAN10

RATEDENGINEERING.COM

TX FIRM #F-21105

RATEDENGINEERING.COM

TX FIRM #F-21105

RATEDENGINEERING.COM

TX FIRM #F-21105

KEYNOTES

1 FIRE ALARM APPLIANCE/DEVICE TO BE DEMOLISHED AS PART OF RENOVATION

2 EXISTING DEVICE TO BE RELOCATED

No. REVISION DESCRIPTION DATE

The information on this document is preliminary or incomplete, not for construction, recording

106A

SPD

E

NEW TR

S E

EX. COMM

NAC

E

NAC

E

S E

H E

E E

E

CARPENTRY

SHOP

107A

NEW TE

107A th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

CONSULTANTS:

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC ENGINEER

SPUR DESIGN

2519 MADISON AVE., STE. 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

RATED ENGINEERING

609 S. KELLY AVENUE, SUITE H2

EDMOND, OK 73003

(405) 856-2965

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TECH ENGINEER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STRUCT ENGINEER

STAND STRUCTURAL ENGINEERING

8234 ROBINSON STREET

OVERLAND PARK, KS 66204

(913) 214-2169

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. BR 2171 EXP. 09/30/2023

ENGR REG. NO. F-17591 EXP. 02/29/2024

STAMP:

Drawing Number

Building Number

BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.

COMMISSIONING

ES2

13401 N. SANTA FE AVE

OKLAHOMA CITY, OK 73114

(405) 528-4500

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C O

N T

R O

L L E

D U

N C

L A

S S

IF

IE

D I

N F

O R

M A

T

IO

N

C U

I)

/2

/2

:5

:4

A

M

100% BID DOCUMENTS

BLDG 4 & 8 - ENLARGED PLANS

JCP 90 OF 229DBN

BONHAM EHRM

INFRASTRUCTURE

UPGRADES

7/7/2023

549A4-21-700

BONHAM VA MEDICAL CENTER

1201 E. 9TH STREET

BONHAM, TX 75418

FA404

SPUR #: 2216

1/4" = 1'-0"

B4 - LEVEL 1 - 106A - FIRE ALARM PLAN1

1/4" = 1'-0"

B4 - LEVEL 2 - 203 - FIRE ALARM PLAN2

1/4" = 1'-0"

B8 - LEVEL 1 - 104 - FIRE ALARM PLAN31/4" = 1'-0"

B8 - LEVEL 1 - 107A - FIRE ALARM PLAN4

RATEDENGINEERING.COM

TX FIRM #F-21105

RATEDENGINEERING.COM

TX FIRM #F-21105

RATEDENGINEERING.COM

TX FIRM #F-21105

KEYNOTES

1 FIRE ALARM APPLIANCE/DEVICE TO BE DEMOLISHED AS PART OF RENOVATION

2 EXISTING DEVICE TO BE RELOCATED

No. REVISION DESCRIPTION DATE

The information on this document is preliminary or incomplete, not for construction, recording

NEW TR

E

E

MNS

CLOSET

114F

CLOSET

105A

RESTROOM

E E

MNS SPD

E

NEW TR

E1

NEW TE

102A

OFFICE

O N

Y X

W S

E

N O

D E

E

N A

C E

S E

F E

S P

D E

NEW TR

CLOSET

SPD

E th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

CONSULTANTS:

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC ENGINEER

SPUR DESIGN

2519 MADISON AVE., STE. 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

RATED ENGINEERING

609 S. KELLY AVENUE, SUITE H2

EDMOND, OK 73003

(405) 856-2965

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TECH ENGINEER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STRUCT ENGINEER

STAND STRUCTURAL ENGINEERING

8234 ROBINSON STREET

OVERLAND PARK, KS 66204

(913) 214-2169

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. BR 2171 EXP. 09/30/2023

ENGR REG. NO. F-17591 EXP. 02/29/2024

STAMP:

Drawing Number

Building Number

BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.

COMMISSIONING

ES2

13401 N. SANTA FE AVE

OKLAHOMA CITY, OK 73114

(405) 528-4500

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C O

N T

R O

L L E

D U

N C

L A

S S

IF

IE

D I

N F

O R

M A

T

IO

N

C U

I)

/2

/2

:5

:4

A

M

100% BID DOCUMENTS

BLDG 9 & 10 - ENLARGED PLANS

JCP 91 OF 229DBN

BONHAM EHRM

INFRASTRUCTURE

UPGRADES

7/7/2023

549A4-21-700

BONHAM VA MEDICAL CENTER

1201 E. 9TH STREET

BONHAM, TX 75418

FA405

SPUR #: 2216

1/4" = 1'-0"

B9 - LEVEL 1 - 107 - FIRE ALARM PLAN1

1/4" = 1'-0"

B9 - LEVEL 2 - 114F - FIRE ALARM PLAN2

1/4" = 1'-0"

B10 - LEVEL 1 - 105 - FIRE ALARM PLAN31/4" = 1'-0"

B10 - LEVEL 1 - 107 - FIRE ALARM PLAN4

1/4" = 1'-0"

B11 - LEVEL 1 - 102 & 102A - FIRE ALARM PLAN51/4" = 1'-0"

B12 - LEVEL 2 - 202 & 202A - FIRE ALARM PLAN61/4" = 1'-0"

B12 -LEVEL 2 - 208 - FIRE ALARM PLAN7

RATEDENGINEERING.COM

TX FIRM #F-21105

RATEDENGINEERING.COM

TX FIRM #F-21105

RATEDENGINEERING.COM

TX FIRM #F-21105

KEYNOTES

1 FIRE ALARM APPLIANCE/DEVICE TO BE DEMOLISHED AS PART OF RENOVATION

2 EXISTING DEVICE TO BE RELOCATED

No. REVISION DESCRIPTION DATE

The information on this document is preliminary or incomplete, not for construction, recording

1C-111

CLOSET

1C-112

NEW TR

1B-108

S E

S E

E

E

M N S 1

CLOSET

2A-102

ELEC

2A-101

S E

CLOSET

2A-108

ELEC

2A-109

NAC

E

NAC

E

S E

NEW TR

2B-108

S E

S E

NEW TR

2C-108

S E

VS

E

WF

E th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

CONSULTANTS:

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC ENGINEER

SPUR DESIGN

2519 MADISON AVE., STE. 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

RATED ENGINEERING

609 S. KELLY AVENUE, SUITE H2

EDMOND, OK 73003

(405) 856-2965

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TECH ENGINEER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STRUCT ENGINEER

STAND STRUCTURAL ENGINEERING

8234 ROBINSON STREET

OVERLAND PARK, KS 66204

(913) 214-2169

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. BR 2171 EXP. 09/30/2023

ENGR REG. NO. F-17591 EXP. 02/29/2024

STAMP:

Drawing Number

Building Number

BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.

COMMISSIONING

ES2

13401 N. SANTA FE AVE

OKLAHOMA CITY, OK 73114

(405) 528-4500

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C O

N T

R O

L L E

D U

N C

L A

S S

IF

IE

D I

N F

O R

M A

T

IO

N

C U

I)

/2

/2

:5

:5

A

M

100% BID DOCUMENTS

BLDG 24 - ENLARGED PLANS

JCP 92 OF 229DBN

BONHAM EHRM

INFRASTRUCTURE

UPGRADES

7/7/2023

549A4-21-700

BONHAM VA MEDICAL CENTER

1201 E. 9TH STREET

BONHAM, TX 75418

FA406

SPUR #: 2216

1/4" = 1'-0"

B24 - LEVEL 1 - 1C-111 & 1C-112 - FIRE ALARM PLAN11/4" = 1'-0"

B24 - LEVEL 1 - 1B-108 - FIRE ALARM PLAN2

1/4" = 1'-0"

B24 - LEVEL 2 - 2A-101 - FIRE ALARM PLAN31/4" = 1'-0"

B24 - LEVEL 2 - 2A-109 - FIRE ALARM PLAN4

1/4" = 1'-0"

B24 - LEVEL 2 - 2B-108 - FIRE ALARM PLAN51/4" = 1'-0"

B24 - LEVEL 2 - 2C-108 - FIRE ALARM PLAN6

RATEDENGINEERING.COM

TX FIRM #F-21105

RATEDENGINEERING.COM

TX FIRM #F-21105

RATEDENGINEERING.COM

TX FIRM #F-21105

KEYNOTES

1 FIRE ALARM APPLIANCE/DEVICE TO BE DEMOLISHED AS PART OF RENOVATION

2 EXISTING DEVICE TO BE RELOCATED

No. REVISION DESCRIPTION DATE

The information on this document is preliminary or incomplete, not for construction, recording

B2107

CLOSET

B2110

NEW TR

C3108

CLOSET

C3112 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e…