This file attachment is related to a federal contract opportunity for construction services. The solicitation number is 36C77624B0007 and is being issued by the Department of Veterans Affairs Technology Acquisition Center Austin. It is for EHRM construction services at the Bonham, Texas VA medical center, with a project number of 549A4-21-700. The opportunity type is a solicitation for VA-23-00092679. The 13MB file attachment contains technical drawings related to the construction project. Responses to the solicitation are due on an unspecified date. The award date and any pricing or set-aside terms are not included in this information.
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ABBREVIATIONS
STANDARD MOUNTING HEIGHTSANNOTATION
ELECTRICAL: (AFF, AFG UNLESS NOTED OTHERWISE)
CU
TELECOMMUNICATION PLAN NOTE CALL OUT
EQUIPMENT DESIGNATION TAG
NEW WORK TO EXISTING WORK CONNECTION POINT
IC
CATV
FO
D
S
IC
S
WAP
# / #TV
M
S
V
COMMUNICATIONS OUTLET, TYPE AS NOTED
COMMUNICATIONS OUTLET, FLOOR BOX, TYPE AS NOTED
WIRELESS ACCESS POINT, CEILING MOUNTED
COMMUNICATIONS OUTLET, CEILING MTD, TYPE AS NOTED
SPEAKER, WALL MOUNTED
SPEAKER, CEILING MOUNTED
TELECOMMUNICATIONS RACK, TWO-POST, FLOOR MOUNTED
GROUND BAR, TYPE AS NOTED
TELECOMMUNICATIONS ENCLOSURE, WALL MOUNTED
WIRE BASKET TRAY, TYPE AS NOTED
CABLE TELEVISION LINE
FIBEROPTIC LINE
COMMUNICATION CABLE PATHWAY
FIBER OPTIC BACKBONE PATHWAY "A"
DATA LINE
SPEAKER LINE
INTERCOM LINE
INTERCOM, "M" DENOTES MASTER STATION
VOLUME CONTROL, WALL MOUNTED
MULTI-SERVICE POWER POLE WITH POWER/DATA,
TYPE AS NOTED AND/OR SCHEDULED
MULTI-SERVICE FLOOR BOX/POKE-THRU WITH POWER/DATA,
TYPE AS NOTED AND/OR SCHEDULED
TELECOMMUNICATIONS CHANNEL RACK, 7'H x 19"W x 30"D, 4-POST, OPEN FRAME TYPE
SERVER CABINET, FLOOR MOUNTED
# = DATA, # = QUANTITY OF CABLES
#TV = CABLE TELEVISION, # = QUANTITY OF CABLES
= DATA, 2 CABLES
#TV = CABLE TELEVISION, # = QUANTITY OF CABLES
#V = VOICE, # = QUANTITY OF CABLES
= DATA, 2 CABLES
# = DATA, # = QUANTITY OF CABLES
TELECOMMUNICATIONS SYMBOLS
#TV = CABLE TELEVISION, # = QUANTITY OF CABLES
#V = VOICE, # = QUANTITY OF CABLES
M (CONT'D)
MV MEDIUM VOLTAGE
MVA MEGAVOLT-AMPERE
MW MEGAWATT
X
W
V
U
T
S
R
P
O
N
M
L
K
J
I
H
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FABL FIRE ALARM BELL
FABX FIRE ALARM BOX
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FI FILM ILLUMINATOR
FIXT FIXTURE
FLA FULL LOAD AMPS
FLEX FLEXIBLE METALLIC CONDUIT
FLUOR FLUORESCENT
FO FIBER-OPTIC
FP FIRE PROTECTION
FT FEET OR FOOT
FVNR FULL VOLTAGE NON-REVERSING
FVR FULL VOLTAGE REVERSING
G
F
E
D
EC EMPTY CONDUIT
EG EQUIPMENT GROUND
EL ELEVATION
ELEC ELECTRIC OR ELECTRICAL
ELEV ELEVATOR
EMCP EMER. MONITORING CONTROL PANEL
EMER EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
EPO EMERGENCY POWER OFF
ESMT EASEMENT
ETD EXISTING TO BE DEMOLISHED
ETR EXISTING TO REMAIN
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EXIST EXISTING
DB DECIBEL OR DIRECT BURIAL
DC DIRECT CURRENT
DCP DIMMER CONTROL PANEL
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLITION
DIAG DIAGRAM
DISC DISCONNECT
DISTR DISTRIBUTION
DISTR PNL DISTRIBUTION PANEL
DN DOWN
DPDT DOUBLE POLE, DOUBLE THROW
DPST DOUBLE POLE, SINGLE THROW
DRSW DOOR SWITCH
DS DISCONNECT SWITCH
DWG DRAWING
C CONDUIT
CAP CAPACITY
CAT CATALOG
CATV COMMUNITY ANTENNA TELEVISION
CCR CONTROL CONTACTOR
CCTV CLOSED CIRCUIT TELEVISION
cd CANDELA
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR FURNISHED/
CONTRACTOR INSTALLED
CF/OI CONTRACTOR FURNISHED/OWNER
INSTALLED
CFE CONTRACTOR FURNISHED
EQUIPMENT
CHW CHILLED WATER
CHWP CHILLED WATER PUMP
CKT CIRCUIT
CKT BRKR CIRCUIT BREAKER
CLF CURRENT LIMITING FUSE
CLG CEILING
CMU CONCRETE MASONRY UNIT
COAX COAX CABLE
COMM COMMUNICATION
CONC CONCRETE
CONT CONTINUE
CONTR CONTRACTOR
COORD COORDINATE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CU COPPER
CU FT CUBIC FEET
C
B
A
UFD UNDERFLOOR DUCT
UGND UNDERGROUND
UL UNDERWRITERS LABORATORY
UNO UNLESS NOTED OTHERWISE
UPS UNINTERRUPTIBLE POWER SUPPLY
UTIL UTILITY
V VOLT
VA VOLT AMPERE
VAR VOLT AMPERE REACTIVE
VCM VERTICAL CABLE MANAGER
VFD VARIABLE FREQUENCY DRIVE
VOLT VOLTAGE
TC TIME CLOCK
TEL TELEPHONE
TO TELECOMMUNICATIONS OUTLET
TR TELECOMMUNICATIONS ROOM
TV TELEVISION
TYP TYPICAL
RCP REFLECTED CEILING PLAN
RCPT RECEPTACLE
REC RECESSED
REQD REQUIRED
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT MEAN SQUARE
RU RACK UNIT
N NEUTRAL
NA NOT APPLICABLE
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS ASSOCIATION
NFPA NATIONAL FIRE PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NS NO SCALE
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OL OVERLOAD
MATV MASTER ANTENNA TELEVISION SYSTEM
MAX MAXIMUM
MC METAL-CLAD
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MG MOTOR GENERATOR
MH MANHOLE
MIN MINIMUM
MOCP MAXIMUM OVERCURRENT PROTECTION
MLO MAIN LUGS ONLY
MT MOUNT
MTD MOUNTED
MTG MOUNTING
KV KILOVOLT
KVA KILOVOLT AMPERE
KVAH KILOVOLT AMPERE PER HOUR
KVAR KILOVOLT AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
KWHM KILOWATT HOUR METER
JB JUNCTION BOX
J-BOX JUNCTION BOX
XFER TRANSFER
XFMR TRANSFORMER
XP EXPLOSION PROOF
LED LIGHT EMITTING DIODE
LF LINEAR FEET (FOOT)
LM LUMEN
LP LIGHT POLE
LPS LOW PRESSURE SODIUM
LRA LOCKED ROTOR AMPS
LTCP LOCAL TEMPERATURE CONTROL PANEL
LT LIGHT
LTG LIGHTING
LTG PNL LIGHTING PANEL
LTNG LIGHTNING
LV LOW VOLTAGE
W WATT
WAO WORK AREA OUTLET
WP WEATHERPROOF
IESNA ILLUMINATION ENGINEERING SOCIETY
OF NORTH AMERICA
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
INCAND INCANDESCENT
IR INFRARED
IWH INSTANTANEOUS WATER HEATER
G OR GND GROUND OR GENERATOR
GEN GENERATOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GTB GROUND TERMINAL BOX
SCC SHORT CIRCUIT CAPACITY
SES SERVICE ENTRANCE SECTION
SD SMOKE DETECTOR
SF SQUARE FOOT (FEET)
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SPEC SPECIFICATION
SPST SINGLE POLE, SINGLE THROW
SURF SURFACE
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
P POLE
PA PUBLIC ADDRESS
PB PANELBOARD, PULL BOX, OR
PUSHBUTTON
PBPU PREFABRICATED BEDSIDE PATIENT UNIT
PCB POLYCHLORINATED BIPHENYL
PEC PHOTOELECTRIC CELL
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PNL PANEL
POD POWER OPERATED DAMPER
POE POWER OVER ETHERNET
PP PATCH PANEL
PT POTENTIAL TRANSFORMER
PTRV POWER TYPE ROOF VENTILATION
PVC POLYVINYL CHLORIDE (PLASTIC)
PWR POWER
1P SINGLE POLE
1PH SINGLE-PHASE
3P THREE POLE
3PH THREE-PHASE
3W THREE WIRE
4W FOUR WIRE
A/C AIR CONDITIONING
A/E ARCHITECT/ENGINEER
AAP ALARM ANNUNCIATOR PANEL
AC ALTERNATING CURRENT OR ARMORED
ACC ACCESSIBLE
ADDL ADDITIONAL
ADJ ADJACENT, ADJOINING
ADO AUTOMATIC DOOR OPENER
AF AMPERE FRAME OR AMP FUSE
AFC ABOVE FINISHED COUNTER, AUTOMATIC
FREQUENCY CONTROL, OR
AVAILABLE FAULT CURRENT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AH AMPERE HOUR
AHJ AUTHORITY HAVING JURISDICTION
AIC AMPERE INTERRUPTING CAPACITY
ALT ALTERNATE
AMB OR A AMBIENT
AMP AMPERE
ARCH ARCHITECT
ASC AMPS SHORT CIRCUIT
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AV AUDIO VISUAL
HCM HORIZONTAL CABLE MANAGER
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HZ HERTZ
BAT BATTERY
BC BARE COPPER
BD BOARD
BFF BELOW FINISH FLOOR
BIL BASIC INSULATION LEVEL
BLDG BUILDING
BLK BLOCK
BPIP BOILER PLANT
INSTRUMENTATION PANEL
BRKR BREAKER
BYP BY PASS
DETAIL REFERENCE
SECTION CUT DESIGNATION
EP-101
EP-101
FIBER OPTIC BACKBONE PATHWAY "B"
84" 48" 48" 84" 48" 80" 60"
120" 60" 36" 48" 72" 48"
144" 18" 24" 26" 48" 48"
CEILING
48" 48" 18" 84"
AUDIBLE APPLIANCES (CENTERLINE)
ALARMS
ANNUNCIATOR PANELS
CLOCK OUTLETS (CENTERLINE)
CONTROLS (TOP)
EXIT SIGNS (WALL-MOUNTED, BOTTOM)
FIRE ALARM ANNUNCIATOR PANEL (DISPLAY)
FIRE ALARM BELL (EXTERIOR)
FIRE ALARM CONTROL PANEL/UNIT (DISPLAY)
INTERCOM (AFEA ONLY)
INTERCOMS (TOP)
PANELS & PANELBOARDS (TOP)
PULL STATIONS (HANDLE)
PHOTOCELLS
RECEPTACLES (BOTTOM)
RECEPTACLES (EXTERIOR)
RECEPTACLES (GARAGES) RECEPTACLES IN
EQUIPMENT ROOMS (TOP) REMOTE INDICATING
LIGHT (EQUIPMENT ROOMS) REMOTE INDICATING
LIGHT (FINISHED AREAS) SAFETY SWITCHES &
STARTERS SWITCHES (TOP)
TELEPHONE/DATA/TV OUTLETS (BOTTOM)
VISIBLE APPLIANCES (CENTERLINE)
#W = WALL PHONE, 1 CABLE, # = QUANTITY OF CABLES
TE TELECOMMUNICATIONS ENCLOSURE
VERTICAL CABLE MANAGER, 6" WIDE, WITH DOORS
COMM
PATH-A
PATH-B
LADDER TRAY, TYPE AS NOTED
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
CONSULTANTS:
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. BR 2171 EXP. 09/30/2023
ENGR REG. NO. F-17591 EXP. 02/29/2024
STAMP:
Drawing Number
Building Number
/3
/2
5:
:3
PM
BONHAM VA MEDICAL CENTER
1201 E. 9TH STREET
BONHAM, TX 75418
SPUR #:No. REVISION DESCRIPTION DATE
Of
BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
C O
N
TR
O
LL
ED
U
N C
LA
SS
IF
IE
D
IN
FO
R
M
AT
IO
N
(C U
I)
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC ENGINEER
SPUR DESIGN
2519 MADISON AVE., STE. 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
RATED ENGINEERING
609 S. KELLY AVENUE, SUITE H2
EDMOND, OK 73003
(405) 856-2965
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TECH ENGINEER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
STRUCT ENGINEER
STAND STRUCTURAL ENGINEERING
8234 ROBINSON STREET
OVERLAND PARK, KS 66204
(913) 214-2169
COMMISSIONING
ES2
13401 N. SANTA FE AVE
OKLAHOMA CITY, OK 73114
(405) 528-4500
549A4-21-700BONHAM EHRM
INFRASTRUCTURE
UPGRADES
100% BID DOCUMENTS
07/07/2023 229
T-000
TELECOM SYMBOLS & ABBREVIATIONS
N/A
ASPEN NR
AutoCAD SHX Text
FRONT
T-300
T-300
241 SF / 100 SF
STORAGE
286 SF / 100 SF
STORAGE
86 SF / 100 SF
CLOSET
690 SF / 100 SF
PHONE ROOM
61 SF / 100 SF
CLOSET
18.5
DMARC PATHWAY "B"
TO BLDG 1 - LVL 5 DMARC.
IN SAME PATH AS FIBER
OPTIC BACKBONE "B"
VERTICAL FIBER
OPTIC PATHWAY "A"
FROM BLDG 1 - LVL 1
VERTICAL FIBER OPTIC
PATHWAY "B"
FROM BLDG 1 - LVL 1
T-300
T-300
TECHNOLOGY GENERAL NOTES
A. CONTRACTOR SHALL INCLUDE AN ADDITIONAL 10% OF CABLE DROPS IN THEIR BID FOR ADDS
FOUND DURING INSTALLATION.
B. ADDITIONAL PATCH PANEL CAPACITY SHALL BE PROVIDED TO ACCOUNT FOR 15% GROWTH OF
ADDITIONAL CABLE DROPS.
C. ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN IN PLACE AND OPERATIONAL UNTIL
FINAL CUT-OVER TO THE NEW CABLING.
D. EACH NEW WORK AREA OUTLET (WAO) LOCATION WILL CONSIST OF THE QUANTITY OF CAT6A CABLES AS DEPICTED ON THE PLANS. EACH CABLE WILL BE TERMINATED ON A 48-PORT CAT6A
PATCH PANEL IN IT'S DESIGNATED TR.
E. EXISTING WAO LOCATIONS SHALL BE RE-USED WHEREVER POSSIBLE.
F. LABEL FIBER CABLE GOING INTO EACH FIBER PATCH PANEL. ALL FIBER STRANDS WILL BE
TESTED UTILIZING AN OLTS AND AN OTDR PER THE TIER 2 STANDARD.
G. PROVIDE (1) EACH SMALL DIAMETER CAT6A PATCH CORD FOR EACH NEW DATA PORT. PROVIDE
VARIOUS LENGTHS AS REQUIRED FOR A NEAT AND ORDERLY INSTALLATION, UTILIZING THE
VERTICAL AND HORIZONTAL WIRE MANAGERS AS APPLICABLE. (SEE SPECIFICATIONS)
H. NEW FIRE-RATED SLEEVES SHALL BE INSTALLED LEAVING THE TR AND IN ALL FIRE-RATED
WALLS ALONG THE CABLE PATHWAYS.
I. EXISTING CONDUITS TO REMAIN.
J. EXISTING DATA RACK/RACKS TO REMAIN UNTIL AFTER CUT-OVER.
K. ENSURE THAT ALL GROUNDING AND BONDING IS COMPLETE. TWO SCREW BONDING LUGS NEED
TO BE INSTALLED TO BOND ALL METALLIC COMPONENTS OF THE RACK AND CABLE TRAY
SYSTEM, TO THE TELECOMMUNICATIONS SECONDARY BONDING BUSBAR.
L. AFTER CUT-OVER TO THE NEW CABLING, DEMOLISH ALL OLD DATA AND TELEPHONE CABLING
ALL THE WAY TO THE STATION END. ENSURE THAT ANY CABLES IN THE CEILING AREAS THAT
ARE FOR SYSTEMS OTHER THAN THE IT DATA AND TELEPHONE, ARE NOT DISTURBED. BLANK
OFF ANY UNUSED OLD DATA LOCATIONS. DEMOLISH ALL OLD PATCH PANELS AND ASSOCIATED
HARDWARE. ALL OTHER ANCILLARY RACK-MOUNTED EQUIPMENT, NOT RELATED TO IT DATA
AND TELEPHONE, TO BE RELOCATED TO A NEW RACK BY OIT PERSONNEL. FIRE-STOP ALL
EXISTING SLEEVES WHERE CABLING WAS REMOVED.
M. AFTER CUT-OVER, REMOVE ALL OLD IT FIBER OPTIC CABLING FROM THE TR ALL THE WAY BACK
TO THE SERVER DEMOLISH ALL ASSOCIATED HARDWARE AND TERMINATION EQUIPMENT.
ENSURE THAT ANY CABLING IN THE CEILING AREA THAT IS FOR OTHER SYSTEMS, IS NOT
DISTURBED.
N. ALL CATEGORY 6A STATION CABLING SHALL BE SUPPORTED USING A COMBINATION OF J-HOOKS
AND CABLE TRAYS (IF POSSIBLE) IN GENERAL PATHWAYS.
O. FIBER OPTIC BACKBONE CABLE TO BE FACTORY TERMINATED IN MCR. FIBER OPTIC BACKBONE CABLE TO BE FIELD TERMINATED IN TRs.
98 SF / 100 SF
T-301
T-301
T-301
T-301
T-301
T-301
T-301
T-301
CLOSET
CLOSET
113A
NEW TR
116A
NEW TR
VERTICAL FIBER
OPTIC PATHWAY "A"
TO BLDG 1 - LVL B
VERTICAL DMARC
PATH 'B' TO MCR
VERTICAL FIBER OPTIC
PATHWAY "B"
TO BLDG 1 - LVL B
DMARC PATHWAY "A"
FROM BLDG 29 - LVL 1.
TO BLDG 1 - LVL 5 DMARC.
IN SAME PATH AS FIBER
OPTIC BACKBONE "A"
HORIZONTAL FIBER
OPTIC PATHWAY "B"
TO BLDG 2 - LVL 1
HORIZONTAL FIBER OPTIC
PATHWAY "B"
TO BLDG 1 - LVL 1 - TR116A
HORIZONTAL FIBER OPTIC
PATHWAY "A"
TO BLDG 1 - LVL 1 - TR 116A.
HORIZONTAL FIBER OPTIC
MIXED PATHWAY ("A" & "B")
TO BLDG 29 - LVL 1.
T-302
64 WAOs
240 WAOs
144 SF / 100 SF
TECHNOLOGY LEGEND
WALL PHONE OUTLET CONTAINING (1) CATEGORY 6A UTP CABLE TERMINATED ONTO (1)
CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLOR TO BE BLUE.
TERMINATION SCHEME TO BE T568B.
WIRELESS ACCESS POINT CONTAINING (2) CATEGORY 6A UTP, GREEN, CABLE TERMINATED
ONTO (1) CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLOR TO BE BLUE.
TERMINATION SCHEME TO BE T568B.
4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (2) CATEGORY 6A UTP CABLES
TERMINATED ONTO (2) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR
TO BE BLUE. TERMINATION SCHEME TO BE T568B.
4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (3) CATEGORY 6A UTP CABLES
TERMINATED ONTO (3) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR
TO BE BLUE. TERMINATION SCHEME TO BE T568B.
4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (4) CATEGORY 6A UTP CABLES
TERMINATED ONTO (4) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR
TO BE BLUE. TERMINATION SCHEME TO BE T568B.
DMARC PATHWAY 'A'
DMARC PATHWAY 'B'
FIBER OPTIC BACKBONE PATHWAY 'A', INSIDE BLDGS.
FIBER OPTIC BACKBONE PATHWAY 'B', INSIDE BLDGS.
FIBER OPTIC BACKBONE PATHWAY 'A', OUTSIDE BLDGS.
FIBER OPTIC BACKBONE PATHWAY 'B', OUTSIDE BLDGS.
WAP
W
TECHNOLOGY KEYNOTES
VERIFY OR INSTALL HORIZONTAL PATHWAYS, BASKET TRAY (12" W, 4" H) ABOVE DROP CEILING
ALONG HALLWAY. INSTALL J-HOOKS IN AREAS WHERE BASKET TRAY IS INAPPROPRIATE.
INBOUND REDUNDANT FIBER BACKBONE 'A' CABLES FROM MDA-A IN SR/DC/MCR. INCLUDES (1)
24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLE FIELD TERMINATED WITH LC TYPE
CONNECTORS ON TR END & FACTORY PRE-TERMINATED ON MDA-A SIDE.
INBOUND REDUNDANT FIBER BACKBONE 'B' CABLES FROM MDA-B IN SR/DC/MCR. INCLUDES (1)
24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLE FIELD TERMINATED WITH LC TYPE
CONNECTORS ON TR END & FACTORY PRE-TERMINATED ON MDA-B SIDE.
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
CONSULTANTS:
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. BR 2171 EXP. 09/30/2023
ENGR REG. NO. F-17591 EXP. 02/29/2024
STAMP:
Drawing Number
Building Number
/3
/2
5:
:3
PM
BONHAM VA MEDICAL CENTER
1201 E. 9TH STREET
BONHAM, TX 75418
SPUR #:No. REVISION DESCRIPTION DATE
Of
BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
C O
N
TR
O
LL
ED
U
N C
LA
SS
IF
IE
D
IN
FO
R
M
AT
IO
N
(C U
I)
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC ENGINEER
SPUR DESIGN
2519 MADISON AVE., STE. 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
RATED ENGINEERING
609 S. KELLY AVENUE, SUITE H2
EDMOND, OK 73003
(405) 856-2965
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TECH ENGINEER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
STRUCT ENGINEER
STAND STRUCTURAL ENGINEERING
8234 ROBINSON STREET
OVERLAND PARK, KS 66204
(913) 214-2169
COMMISSIONING
ES2
13401 N. SANTA FE AVE
OKLAHOMA CITY, OK 73114
(405) 528-4500
549A4-21-700BONHAM EHRM
INFRASTRUCTURE
UPGRADES
100% BID DOCUMENTS
07/07/2023 229
T-100
BUILDING 1 - TELECOM PLANS
ASPEN NR
1/16" = 1'-0"
BLDG 1 - BASEMENT1 1/16" = 1'-0"
BLDG 1 - LEVEL 12
N N
SHEET TO BE PRINTED IN COLOR
T-301
T-301
FIBER OPTIC PATHWAY "B"
TO BLDG 1 - LVL 2
VERTICAL FIBER
OPTIC PATHWAY "A"
TO BLDG 1 - LVL 2
T-302
146 SF / 100 SF
NEW TR
CLOSET
317A
CLOSET
317B
FIRE RISER
300G
234 WAOs
T-301
T-301
FIBER OPTIC PATHWAY "B"
TO BLDG 1 - LVL 1
VERTICAL FIBER
OPTIC PATHWAY "A"
TO BLDG 1 - LVL 1
T-302
143 SF / 100 SF
NEW TR
CLOSET
FIRE RISER
200G
49 WAOs
T-301
T-301
VERTICAL FIBER
OPTIC PATHWAY "B"
TO BLDG 1 - LVL 3
VERTICAL FIBER
OPTIC PATHWAY "A"
TO BLDG 1 - LVL 3
T-302
149 SF / 100 SF
NEW TR
CLOSET
CLOSET
418A
FIRE RISER
400G
131 WAOs
VERTICAL FIBER
OPTIC PATHWAY "A"
TO BLDG 1 - LVL 5
NEW FP
CLOSET
T-302
T-302
VERTICAL FIBER
OPTIC PATHWAY "A"
TO BLDG 1 - LVL 4
FIBER OPTIC PATHWAY "B"
TO BLDG 1 - LVL 4
VERTICAL FIBER OPTIC
PATHWAY "B"
TO BLDG 1 - LVL 4
T-302
NEW SERVER
FIRE RISER
500E
64 WAOs
TECHNOLOGY GENERAL NOTES
A. CONTRACTOR SHALL INCLUDE AN ADDITIONAL 10% OF CABLE DROPS IN THEIR BID FOR ADDS
FOUND DURING INSTALLATION.
B. ADDITIONAL PATCH PANEL CAPACITY SHALL BE PROVIDED TO ACCOUNT FOR 15% GROWTH OF
ADDITIONAL CABLE DROPS.
C. ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN IN PLACE AND OPERATIONAL UNTIL
FINAL CUT-OVER TO THE NEW CABLING.
D. EACH NEW WORK AREA OUTLET (WAO) LOCATION WILL CONSIST OF THE QUANTITY OF CAT6A CABLES AS DEPICTED ON THE PLANS. EACH CABLE WILL BE TERMINATED ON A 48-PORT CAT6A
PATCH PANEL IN IT'S DESIGNATED TR.
E. EXISTING WAO LOCATIONS SHALL BE RE-USED WHEREVER POSSIBLE.
F. LABEL FIBER CABLE GOING INTO EACH FIBER PATCH PANEL. ALL FIBER STRANDS WILL BE
TESTED UTILIZING AN OLTS AND AN OTDR PER THE TIER 2 STANDARD.
G. PROVIDE (1) EACH SMALL DIAMETER CAT6A PATCH CORD FOR EACH NEW DATA PORT. PROVIDE
VARIOUS LENGTHS AS REQUIRED FOR A NEAT AND ORDERLY INSTALLATION, UTILIZING THE
VERTICAL AND HORIZONTAL WIRE MANAGERS AS APPLICABLE. (SEE SPECIFICATIONS)
H. NEW FIRE-RATED SLEEVES SHALL BE INSTALLED LEAVING THE TR AND IN ALL FIRE-RATED
WALLS ALONG THE CABLE PATHWAYS.
I. EXISTING CONDUITS TO REMAIN.
J. EXISTING DATA RACK/RACKS TO REMAIN UNTIL AFTER CUT-OVER.
K. ENSURE THAT ALL GROUNDING AND BONDING IS COMPLETE. TWO SCREW BONDING LUGS NEED
TO BE INSTALLED TO BOND ALL METALLIC COMPONENTS OF THE RACK AND CABLE TRAY
SYSTEM, TO THE TELECOMMUNICATIONS SECONDARY BONDING BUSBAR.
L. AFTER CUT-OVER TO THE NEW CABLING, DEMOLISH ALL OLD DATA AND TELEPHONE CABLING
ALL THE WAY TO THE STATION END. ENSURE THAT ANY CABLES IN THE CEILING AREAS THAT
ARE FOR SYSTEMS OTHER THAN THE IT DATA AND TELEPHONE, ARE NOT DISTURBED. BLANK
OFF ANY UNUSED OLD DATA LOCATIONS. DEMOLISH ALL OLD PATCH PANELS AND ASSOCIATED
HARDWARE. ALL OTHER ANCILLARY RACK-MOUNTED EQUIPMENT, NOT RELATED TO IT DATA
AND TELEPHONE, TO BE RELOCATED TO A NEW RACK BY OIT PERSONNEL. FIRE-STOP ALL
EXISTING SLEEVES WHERE CABLING WAS REMOVED.
M. AFTER CUT-OVER, REMOVE ALL OLD IT FIBER OPTIC CABLING FROM THE TR ALL THE WAY BACK
TO THE SERVER DEMOLISH ALL ASSOCIATED HARDWARE AND TERMINATION EQUIPMENT.
ENSURE THAT ANY CABLING IN THE CEILING AREA THAT IS FOR OTHER SYSTEMS, IS NOT
DISTURBED.
N. ALL CATEGORY 6A STATION CABLING SHALL BE SUPPORTED USING A COMBINATION OF J-HOOKS
AND CABLE TRAYS (IF POSSIBLE) IN GENERAL PATHWAYS.
O. FIBER OPTIC BACKBONE CABLE TO BE FACTORY TERMINATED IN MCR. FIBER OPTIC BACKBONE CABLE TO BE FIELD TERMINATED IN TRs.
TECHNOLOGY LEGEND
WALL PHONE OUTLET CONTAINING (1) CATEGORY 6A UTP CABLE TERMINATED ONTO (1)
CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLOR TO BE BLUE.
TERMINATION SCHEME TO BE T568B.
WIRELESS ACCESS POINT CONTAINING (2) CATEGORY 6A UTP, GREEN, CABLE TERMINATED
ONTO (1) CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLOR TO BE BLUE.
TERMINATION SCHEME TO BE T568B.
4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (2) CATEGORY 6A UTP CABLES
TERMINATED ONTO (2) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR
TO BE BLUE. TERMINATION SCHEME TO BE T568B.
4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (3) CATEGORY 6A UTP CABLES
TERMINATED ONTO (3) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR
TO BE BLUE. TERMINATION SCHEME TO BE T568B.
4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (4) CATEGORY 6A UTP CABLES
TERMINATED ONTO (4) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR
TO BE BLUE. TERMINATION SCHEME TO BE T568B.
DMARC PATHWAY 'A'
DMARC PATHWAY 'B'
FIBER OPTIC BACKBONE PATHWAY 'A', INSIDE BLDGS.
FIBER OPTIC BACKBONE PATHWAY 'B', INSIDE BLDGS.
FIBER OPTIC BACKBONE PATHWAY 'A', OUTSIDE BLDGS.
FIBER OPTIC BACKBONE PATHWAY 'B', OUTSIDE BLDGS.
WAP
W
TECHNOLOGY KEYNOTES
VERIFY OR INSTALL HORIZONTAL PATHWAYS, BASKET TRAY (12" W, 4" H) ABOVE DROP CEILING
ALONG HALLWAY. INSTALL J-HOOKS IN AREAS WHERE BASKET TRAY IS INAPPROPRIATE.
INBOUND REDUNDANT FIBER BACKBONE 'A' CABLES FROM MDA-A IN SR/DC/MCR. INCLUDES (1)
24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLE FIELD TERMINATED WITH LC TYPE
CONNECTORS ON TR END & FACTORY PRE-TERMINATED ON MDA-A SIDE.
INBOUND REDUNDANT FIBER BACKBONE 'B' CABLES FROM MDA-B IN SR/DC/MCR. INCLUDES (1)
24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLE FIELD TERMINATED WITH LC TYPE
CONNECTORS ON TR END & FACTORY PRE-TERMINATED ON MDA-B SIDE.
1/16" = 1'-0"
BLDG 1 - LEVEL 32 1/16" = 1'-0"
BLDG 1 - LEVEL 21
1/16" = 1'-0"
BLDG 1 - LEVEL 43 1/16" = 1'-0"
BLDG 1 - LEVEL 54
N N
NN
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
CONSULTANTS:
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. BR 2171 EXP. 09/30/2023
ENGR REG. NO. F-17591 EXP. 02/29/2024
STAMP:
Drawing Number
Building Number
/3
/2
5:
:3
PM
BONHAM VA MEDICAL CENTER
1201 E. 9TH STREET
BONHAM, TX 75418
SPUR #:No. REVISION DESCRIPTION DATE
Of
BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
C O
N
TR
O
LL
ED
U
N C
LA
SS
IF
IE
D
IN
FO
R
M
AT
IO
N
(C U
I)
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC ENGINEER
SPUR DESIGN
2519 MADISON AVE., STE. 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
RATED ENGINEERING
609 S. KELLY AVENUE, SUITE H2
EDMOND, OK 73003
(405) 856-2965
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TECH ENGINEER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
STRUCT ENGINEER
STAND STRUCTURAL ENGINEERING
8234 ROBINSON STREET
OVERLAND PARK, KS 66204
(913) 214-2169
COMMISSIONING
ES2
13401 N. SANTA FE AVE
OKLAHOMA CITY, OK 73114
(405) 528-4500
549A4-21-700BONHAM EHRM
INFRASTRUCTURE
UPGRADES
100% BID DOCUMENTS
07/07/2023 229
T-101
BUILDING 1 - TELECOM PLANS
ASPEN NR
109 SF / 100 SF
100A
T-303
T-303
T-303
T-303
T-303 4 T-303
VERTICAL FIBER
OPTIC PATHWAY "B"
TO BLDG 2 - LVL 2
3 1
1 1 1
HORIZONTAL FIBER
OPTIC MIXED
PATHWAY ('A" & "B")
TO BLDG 1 - LVL 1
HORIZONTAL FIBER
OPTIC MIXED
PATHWAY ('A" & "B")
TO BLDG 3 - LVL 1
CLOSET
100C
197 SF / 100 SF
NEW TR
NEW TR
118 WAOs
118 WAOs
T-303
T-303
T-303
T-303
VERTICAL FIBER
OPTIC PATHWAY "B"
TO BLDG 2 - LVL 3
VERTICAL FIBER
OPTIC PATHWAY "A"
TO BLDG 2 - LVL 3
114 SF / 100 SF
NEW TR
CLOSET
VESTIBULE
201B
HAC
201A
234 WAOs
TECHNOLOGY GENERAL NOTES
A. CONTRACTOR SHALL INCLUDE AN ADDITIONAL 10% OF CABLE DROPS IN THEIR BID FOR ADDS
FOUND DURING INSTALLATION.
B. ADDITIONAL PATCH PANEL CAPACITY SHALL BE PROVIDED TO ACCOUNT FOR 15% GROWTH OF
ADDITIONAL CABLE DROPS.
C. ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN IN PLACE AND OPERATIONAL UNTIL
FINAL CUT-OVER TO THE NEW CABLING.
D. EACH NEW WORK AREA OUTLET (WAO) LOCATION WILL CONSIST OF THE QUANTITY OF CAT6A CABLES AS DEPICTED ON THE PLANS. EACH CABLE WILL BE TERMINATED ON A 48-PORT CAT6A
PATCH PANEL IN IT'S DESIGNATED TR.
E. EXISTING WAO LOCATIONS SHALL BE RE-USED WHEREVER POSSIBLE.
F. LABEL FIBER CABLE GOING INTO EACH FIBER PATCH PANEL. ALL FIBER STRANDS WILL BE
TESTED UTILIZING AN OLTS AND AN OTDR PER THE TIER 2 STANDARD.
G. PROVIDE (1) EACH SMALL DIAMETER CAT6A PATCH CORD FOR EACH NEW DATA PORT. PROVIDE
VARIOUS LENGTHS AS REQUIRED FOR A NEAT AND ORDERLY INSTALLATION, UTILIZING THE
VERTICAL AND HORIZONTAL WIRE MANAGERS AS APPLICABLE. (SEE SPECIFICATIONS)
H. NEW FIRE-RATED SLEEVES SHALL BE INSTALLED LEAVING THE TR AND IN ALL FIRE-RATED
WALLS ALONG THE CABLE PATHWAYS.
I. EXISTING CONDUITS TO REMAIN.
J. EXISTING DATA RACK/RACKS TO REMAIN UNTIL AFTER CUT-OVER.
K. ENSURE THAT ALL GROUNDING AND BONDING IS COMPLETE. TWO SCREW BONDING LUGS NEED
TO BE INSTALLED TO BOND ALL METALLIC COMPONENTS OF THE RACK AND CABLE TRAY
SYSTEM, TO THE TELECOMMUNICATIONS SECONDARY BONDING BUSBAR.
L. AFTER CUT-OVER TO THE NEW CABLING, DEMOLISH ALL OLD DATA AND TELEPHONE CABLING
ALL THE WAY TO THE STATION END. ENSURE THAT ANY CABLES IN THE CEILING AREAS THAT
ARE FOR SYSTEMS OTHER THAN THE IT DATA AND TELEPHONE, ARE NOT DISTURBED. BLANK
OFF ANY UNUSED OLD DATA LOCATIONS. DEMOLISH ALL OLD PATCH PANELS AND ASSOCIATED
HARDWARE. ALL OTHER ANCILLARY RACK-MOUNTED EQUIPMENT, NOT RELATED TO IT DATA
AND TELEPHONE, TO BE RELOCATED TO A NEW RACK BY OIT PERSONNEL. FIRE-STOP ALL
EXISTING SLEEVES WHERE CABLING WAS REMOVED.
M. AFTER CUT-OVER, REMOVE ALL OLD IT FIBER OPTIC CABLING FROM THE TR ALL THE WAY BACK
TO THE SERVER DEMOLISH ALL ASSOCIATED HARDWARE AND TERMINATION EQUIPMENT.
ENSURE THAT ANY CABLING IN THE CEILING AREA THAT IS FOR OTHER SYSTEMS, IS NOT
DISTURBED.
N. ALL CATEGORY 6A STATION CABLING SHALL BE SUPPORTED USING A COMBINATION OF J-HOOKS
AND CABLE TRAYS (IF POSSIBLE) IN GENERAL PATHWAYS.
O. FIBER OPTIC BACKBONE CABLE TO BE FACTORY TERMINATED IN MCR. FIBER OPTIC BACKBONE CABLE TO BE FIELD TERMINATED IN TRs.
TECHNOLOGY LEGEND
WALL PHONE OUTLET CONTAINING (1) CATEGORY 6A UTP CABLE TERMINATED ONTO (1)
CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLOR TO BE BLUE.
TERMINATION SCHEME TO BE T568B.
WIRELESS ACCESS POINT CONTAINING (2) CATEGORY 6A UTP, GREEN, CABLE TERMINATED
ONTO (1) CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLOR TO BE BLUE.
TERMINATION SCHEME TO BE T568B.
4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (2) CATEGORY 6A UTP CABLES
TERMINATED ONTO (2) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR
TO BE BLUE. TERMINATION SCHEME TO BE T568B.
4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (3) CATEGORY 6A UTP CABLES
TERMINATED ONTO (3) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR
TO BE BLUE. TERMINATION SCHEME TO BE T568B.
4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (4) CATEGORY 6A UTP CABLES
TERMINATED ONTO (4) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR
TO BE BLUE. TERMINATION SCHEME TO BE T568B.
DMARC PATHWAY 'A'
DMARC PATHWAY 'B'
FIBER OPTIC BACKBONE PATHWAY 'A', INSIDE BLDGS.
FIBER OPTIC BACKBONE PATHWAY 'B', INSIDE BLDGS.
FIBER OPTIC BACKBONE PATHWAY 'A', OUTSIDE BLDGS.
FIBER OPTIC BACKBONE PATHWAY 'B', OUTSIDE BLDGS.
WAP
W
TECHNOLOGY KEYNOTES
VERIFY OR INSTALL HORIZONTAL PATHWAYS, BASKET TRAY (12" W, 4" H) ABOVE DROP CEILING
ALONG HALLWAY. INSTALL J-HOOKS IN AREAS WHERE BASKET TRAY IS INAPPROPRIATE.
INBOUND REDUNDANT FIBER BACKBONE 'A' CABLES FROM MDA-A IN SR/DC/MCR. INCLUDES (1)
24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLE FIELD TERMINATED WITH LC TYPE
CONNECTORS ON TR END & FACTORY PRE-TERMINATED ON MDA-A SIDE.
INBOUND REDUNDANT FIBER BACKBONE 'B' CABLES FROM MDA-B IN SR/DC/MCR. INCLUDES (1)
24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLE FIELD TERMINATED WITH LC TYPE
CONNECTORS ON TR END & FACTORY PRE-TERMINATED ON MDA-B SIDE.
N
1/16" = 1'-0"
BLDG 2 - LEVEL 11
N
1/16" = 1'-0"
BLDG 2 - LEVEL 22
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
CONSULTANTS:
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. BR 2171 EXP. 09/30/2023
ENGR REG. NO. F-17591 EXP. 02/29/2024
STAMP:
Drawing Number
Building Number
/3
/2
5:
:3
PM
BONHAM VA MEDICAL CENTER
1201 E. 9TH STREET
BONHAM, TX 75418
SPUR #:No. REVISION DESCRIPTION DATE
Of
BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
C O
N
TR
O
LL
ED
U
N C
LA
SS
IF
IE
D
IN
FO
R
M
AT
IO
N
(C U
I)
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC ENGINEER
SPUR DESIGN
2519 MADISON AVE., STE. 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
RATED ENGINEERING
609 S. KELLY AVENUE, SUITE H2
EDMOND, OK 73003
(405) 856-2965
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TECH ENGINEER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
STRUCT ENGINEER
STAND STRUCTURAL ENGINEERING
8234 ROBINSON STREET
OVERLAND PARK, KS 66204
(913) 214-2169
COMMISSIONING
ES2
13401 N. SANTA FE AVE
OKLAHOMA CITY, OK 73114
(405) 528-4500
549A4-21-700BONHAM EHRM
INFRASTRUCTURE
UPGRADES
100% BID DOCUMENTS
07/07/2023 229
T-102
BUILDING 2 - TELECOM PLANS
T-303
T-303
T-303
T-303
VERTICAL FIBER
OPTIC PATHWAY "B"
TO BLDG 2 - LVL 4
VERTICAL FIBER
OPTIC PATHWAY "A"
TO BLDG 2 - LVL 4
CLOSET
128 SF / 100 SF
NEW TR
301A
CORRIDOR
CLOSET
301B
210 WAOs
T-303
T-304
T-303
T-304
VERTICAL FIBER
OPTIC PATHWAY "B"
VERTICAL FIBER
OPTIC PATHWAY "A"
CLOSET
132 SF / 100 SF
NEW TR
401A
CLOSET
401B
CORRIDOR
181 WAOs
TECHNOLOGY GENERAL NOTES
A. CONTRACTOR SHALL INCLUDE AN ADDITIONAL 10% OF CABLE DROPS IN THEIR BID FOR ADDS
FOUND DURING INSTALLATION.
B. ADDITIONAL PATCH PANEL CAPACITY SHALL BE PROVIDED TO ACCOUNT FOR 15% GROWTH OF
ADDITIONAL CABLE DROPS.
C. ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN IN PLACE AND OPERATIONAL UNTIL
FINAL CUT-OVER TO THE NEW CABLING.
D. EACH NEW WORK AREA OUTLET (WAO) LOCATION WILL CONSIST OF THE QUANTITY OF CAT6A CABLES AS DEPICTED ON THE PLANS. EACH CABLE WILL BE TERMINATED ON A 48-PORT CAT6A
PATCH PANEL IN IT'S DESIGNATED TR.
E. EXISTING WAO LOCATIONS SHALL BE RE-USED WHEREVER POSSIBLE.
F. LABEL FIBER CABLE GOING INTO EACH FIBER PATCH PANEL. ALL FIBER STRANDS WILL BE
TESTED UTILIZING AN OLTS AND AN OTDR PER THE TIER 2 STANDARD.
G. PROVIDE (1) EACH SMALL DIAMETER CAT6A PATCH CORD FOR EACH NEW DATA PORT. PROVIDE
VARIOUS LENGTHS AS REQUIRED FOR A NEAT AND ORDERLY INSTALLATION, UTILIZING THE
VERTICAL AND HORIZONTAL WIRE MANAGERS AS APPLICABLE. (SEE SPECIFICATIONS)
H. NEW FIRE-RATED SLEEVES SHALL BE INSTALLED LEAVING THE TR AND IN ALL FIRE-RATED
WALLS ALONG THE CABLE PATHWAYS.
I. EXISTING CONDUITS TO REMAIN.
J. EXISTING DATA RACK/RACKS TO REMAIN UNTIL AFTER CUT-OVER.
K. ENSURE THAT ALL GROUNDING AND BONDING IS COMPLETE. TWO SCREW BONDING LUGS NEED
TO BE INSTALLED TO BOND ALL METALLIC COMPONENTS OF THE RACK AND CABLE TRAY
SYSTEM, TO THE TELECOMMUNICATIONS SECONDARY BONDING BUSBAR.
L. AFTER CUT-OVER TO THE NEW CABLING, DEMOLISH ALL OLD DATA AND TELEPHONE CABLING
ALL THE WAY TO THE STATION END. ENSURE THAT ANY CABLES IN THE CEILING AREAS THAT
ARE FOR SYSTEMS OTHER THAN THE IT DATA AND TELEPHONE, ARE NOT DISTURBED. BLANK
OFF ANY UNUSED OLD DATA LOCATIONS. DEMOLISH ALL OLD PATCH PANELS AND ASSOCIATED
HARDWARE. ALL OTHER ANCILLARY RACK-MOUNTED EQUIPMENT, NOT RELATED TO IT DATA
AND TELEPHONE, TO BE RELOCATED TO A NEW RACK BY OIT PERSONNEL. FIRE-STOP ALL
EXISTING SLEEVES WHERE CABLING WAS REMOVED.
M. AFTER CUT-OVER, REMOVE ALL OLD IT FIBER OPTIC CABLING FROM THE TR ALL THE WAY BACK
TO THE SERVER DEMOLISH ALL ASSOCIATED HARDWARE AND TERMINATION EQUIPMENT.
ENSURE THAT ANY CABLING IN THE CEILING AREA THAT IS FOR OTHER SYSTEMS, IS NOT
DISTURBED.
N. ALL CATEGORY 6A STATION CABLING SHALL BE SUPPORTED USING A COMBINATION OF J-HOOKS
AND CABLE TRAYS (IF POSSIBLE) IN GENERAL PATHWAYS.
O. FIBER OPTIC BACKBONE CABLE TO BE FACTORY TERMINATED IN MCR. FIBER OPTIC BACKBONE CABLE TO BE FIELD TERMINATED IN TRs.
TECHNOLOGY LEGEND
WALL PHONE OUTLET CONTAINING (1) CATEGORY 6A UTP CABLE TERMINATED ONTO (1)
CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLOR TO BE BLUE.
TERMINATION SCHEME TO BE T568B.
WIRELESS ACCESS POINT CONTAINING (2) CATEGORY 6A UTP, GREEN, CABLE TERMINATED
ONTO (1) CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLOR TO BE BLUE.
TERMINATION SCHEME TO BE T568B.
4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (2) CATEGORY 6A UTP CABLES
TERMINATED ONTO (2) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR
TO BE BLUE. TERMINATION SCHEME TO BE T568B.
4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (3) CATEGORY 6A UTP CABLES
TERMINATED ONTO (3) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR
TO BE BLUE. TERMINATION SCHEME TO BE T568B.
4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (4) CATEGORY 6A UTP CABLES
TERMINATED ONTO (4) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR
TO BE BLUE. TERMINATION SCHEME TO BE T568B.
DMARC PATHWAY 'A'
DMARC PATHWAY 'B'
FIBER OPTIC BACKBONE PATHWAY 'A', INSIDE BLDGS.
FIBER OPTIC BACKBONE PATHWAY 'B', INSIDE BLDGS.
FIBER OPTIC BACKBONE PATHWAY 'A', OUTSIDE BLDGS.
FIBER OPTIC BACKBONE PATHWAY 'B', OUTSIDE BLDGS.
WAP
W
TECHNOLOGY KEYNOTES
VERIFY OR INSTALL HORIZONTAL PATHWAYS, BASKET TRAY (12" W, 4" H) ABOVE DROP CEILING
ALONG HALLWAY. INSTALL J-HOOKS IN AREAS WHERE BASKET TRAY IS INAPPROPRIATE.
INBOUND REDUNDANT FIBER BACKBONE 'A' CABLES FROM MDA-A IN SR/DC/MCR. INCLUDES (1)
24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLE FIELD TERMINATED WITH LC TYPE
CONNECTORS ON TR END & FACTORY PRE-TERMINATED ON MDA-A SIDE.
INBOUND REDUNDANT FIBER BACKBONE 'B' CABLES FROM MDA-B IN SR/DC/MCR. INCLUDES (1)
24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLE FIELD TERMINATED WITH LC TYPE
CONNECTORS ON TR END & FACTORY PRE-TERMINATED ON MDA-B SIDE.
N
1/16" = 1'-0"
BLDG 2 - LEVEL 31
N
1/16" = 1'-0"
BLDG 2 - LEVEL 42
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
CONSULTANTS:
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. BR 2171 EXP. 09/30/2023
ENGR REG. NO. F-17591 EXP. 02/29/2024
STAMP:
Drawing Number
Building Number
/3
/2
5:
:3
PM
BONHAM VA MEDICAL CENTER
1201 E. 9TH STREET
BONHAM, TX 75418
SPUR #:No. REVISION DESCRIPTION DATE
Of
BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
C O
N
TR
O
LL
ED
U
N C
LA
SS
IF
IE
D
IN
FO
R
M
AT
IO
N
(C U
I)
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC ENGINEER
SPUR DESIGN
2519 MADISON AVE., STE. 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
RATED ENGINEERING
609 S. KELLY AVENUE, SUITE H2
EDMOND, OK 73003
(405) 856-2965
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TECH ENGINEER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
STRUCT ENGINEER
STAND STRUCTURAL ENGINEERING
8234 ROBINSON STREET
OVERLAND PARK, KS 66204
(913) 214-2169
COMMISSIONING
ES2
13401 N. SANTA FE AVE
OKLAHOMA CITY, OK 73114
(405) 528-4500
549A4-21-700BONHAM EHRM
INFRASTRUCTURE
UPGRADES
100% BID DOCUMENTS
07/07/2023 229
T-103
BUILDING 2 - TELECOM PLANS
153 SF / 100 SFOFFICE
T-304
T-304
WAP WAP
WAP
WAP WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
4 4
W
W
W
W
VERTICAL FIBER
OPTIC PATHWAY "B"
TO BLDG 3 - LVL 2
VERTICAL FIBER
OPTIC PATHWAY "A"
TO BLDG 3 - LVL 2
HORIZONTAL FIBER
OPTIC MIXED
PATHWAY ('A" & "B")
TO BLDG 24 - LVL 1
HORIZONTAL FIBER
OPTIC MIXED
PATHWAY ('A" & "B")
TO BLDG 2 - LVL 1 NEW TR
135B
135A
T-304
T-304
8 WAP
WAP
WAP
WAP
WAP
WAP
VERTICAL FIBER
OPTIC PATHWAY "B"
TO BLDG 4 - LVL 2
STORAGE
106A
VERTICAL FIBER
OPTIC PATHWAY "A"
TO BLDG 4 - LVL 2
T-304
T-304
WAP
WAP
WAP
WAP
WAP
WAP
W
W2 2
2 2
W
W
W
CARPENTRY
SHOP
107A
EX. COMM
NEW TE
107A
126 SF / 100 SF
T-305
T-305
WAP
WAP
WAP
WAP
3 3
NEW TR
T-304
T-304
WAP
WAP
WAPWAP
WAP 22
2 2
VERTICAL FIBER
OPTIC PATHWAY "B"
TO BLDG 4 - LVL 1
161 SF / 100 SF
NEW TR
VERTICAL FIBER
OPTIC PATHWAY "A"
TO BLDG 4 - LVL 1
T-304
T-304
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
W
W
VERTICAL FIBER
OPTIC PATHWAY "B"
FROM BLDG 3 - LVL 1
VERTICAL FIBER
OPTIC PATHWAY "A"
TO BLDG 3 - LVL 1
129 SF / 100 SF
NEW TR
201B
CLOSET
201C
T-305
47 SF
CLOSET
114F
T-305
TECHNOLOGY GENERAL NOTES
A. CONTRACTOR SHALL INCLUDE AN ADDITIONAL 10% OF CABLE DROPS IN THEIR BID FOR ADDS
FOUND DURING INSTALLATION.
B. ADDITIONAL PATCH PANEL CAPACITY SHALL BE PROVIDED TO ACCOUNT FOR 15% GROWTH OF
ADDITIONAL CABLE DROPS.
C. ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN IN PLACE AND OPERATIONAL UNTIL
FINAL CUT-OVER TO THE NEW CABLING.
D. EACH NEW WORK AREA OUTLET (WAO) LOCATION WILL CONSIST OF THE QUANTITY OF CAT6A CABLES AS DEPICTED ON THE PLANS. EACH CABLE WILL BE TERMINATED ON A 48-PORT CAT6A
PATCH PANEL IN IT'S DESIGNATED TR.
E. EXISTING WAO LOCATIONS SHALL BE RE-USED WHEREVER POSSIBLE.
F. LABEL FIBER CABLE GOING INTO EACH FIBER PATCH PANEL. ALL FIBER STRANDS WILL BE
TESTED UTILIZING AN OLTS AND AN OTDR PER THE TIER 2 STANDARD.
G. PROVIDE (1) EACH SMALL DIAMETER CAT6A PATCH CORD FOR EACH NEW DATA PORT. PROVIDE
VARIOUS LENGTHS AS REQUIRED FOR A NEAT AND ORDERLY INSTALLATION, UTILIZING THE
VERTICAL AND HORIZONTAL WIRE MANAGERS AS APPLICABLE. (SEE SPECIFICATIONS)
H. NEW FIRE-RATED SLEEVES SHALL BE INSTALLED LEAVING THE TR AND IN ALL FIRE-RATED
WALLS ALONG THE CABLE PATHWAYS.
I. EXISTING CONDUITS TO REMAIN.
J. EXISTING DATA RACK/RACKS TO REMAIN UNTIL AFTER CUT-OVER.
K. ENSURE THAT ALL GROUNDING AND BONDING IS COMPLETE. TWO SCREW BONDING LUGS NEED
TO BE INSTALLED TO BOND ALL METALLIC COMPONENTS OF THE RACK AND CABLE TRAY
SYSTEM, TO THE TELECOMMUNICATIONS SECONDARY BONDING BUSBAR.
L. AFTER CUT-OVER TO THE NEW CABLING, DEMOLISH ALL OLD DATA AND TELEPHONE CABLING
ALL THE WAY TO THE STATION END. ENSURE THAT ANY CABLES IN THE CEILING AREAS THAT
ARE FOR SYSTEMS OTHER THAN THE IT DATA AND TELEPHONE, ARE NOT DISTURBED. BLANK
OFF ANY UNUSED OLD DATA LOCATIONS. DEMOLISH ALL OLD PATCH PANELS AND ASSOCIATED
HARDWARE. ALL OTHER ANCILLARY RACK-MOUNTED EQUIPMENT, NOT RELATED TO IT DATA
AND TELEPHONE, TO BE RELOCATED TO A NEW RACK BY OIT PERSONNEL. FIRE-STOP ALL
EXISTING SLEEVES WHERE CABLING WAS REMOVED.
M. AFTER CUT-OVER, REMOVE ALL OLD IT FIBER OPTIC CABLING FROM THE TR ALL THE WAY BACK
TO THE SERVER DEMOLISH ALL ASSOCIATED HARDWARE AND TERMINATION EQUIPMENT.
ENSURE THAT ANY CABLING IN THE CEILING AREA THAT IS FOR OTHER SYSTEMS, IS NOT
DISTURBED.
N. ALL CATEGORY 6A STATION CABLING SHALL BE SUPPORTED USING A COMBINATION OF J-HOOKS
AND CABLE TRAYS (IF POSSIBLE) IN GENERAL PATHWAYS.
O. FIBER OPTIC BACKBONE CABLE TO BE FACTORY TERMINATED IN MCR. FIBER OPTIC BACKBONE CABLE TO BE FIELD TERMINATED IN TRs.
TECHNOLOGY LEGEND
WALL PHONE OUTLET CONTAINING (1) CATEGORY 6A UTP CABLE TERMINATED ONTO (1)
CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLOR TO BE BLUE.
TERMINATION SCHEME TO BE T568B.
WIRELESS ACCESS POINT CONTAINING (2) CATEGORY 6A UTP, GREEN, CABLE TERMINATED
ONTO (1) CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLOR TO BE BLUE.
TERMINATION SCHEME TO BE T568B.
4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (2) CATEGORY 6A UTP CABLES
TERMINATED ONTO (2) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR
TO BE BLUE. TERMINATION SCHEME TO BE T568B.
4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (3) CATEGORY 6A UTP CABLES
TERMINATED ONTO (3) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR
TO BE BLUE. TERMINATION SCHEME TO BE T568B.
4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (4) CATEGORY 6A UTP CABLES
TERMINATED ONTO (4) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR
TO BE BLUE. TERMINATION SCHEME TO BE T568B.
DMARC PATHWAY 'A'
DMARC PATHWAY 'B'
FIBER OPTIC BACKBONE PATHWAY 'A', INSIDE BLDGS.
FIBER OPTIC BACKBONE PATHWAY 'B', INSIDE BLDGS.
FIBER OPTIC BACKBONE PATHWAY 'A', OUTSIDE BLDGS.
FIBER OPTIC BACKBONE PATHWAY 'B', OUTSIDE BLDGS.
WAP
W
TECHNOLOGY KEYNOTES
VERIFY OR INSTALL HORIZONTAL PATHWAYS, BASKET TRAY (12" W, 4" H) ABOVE DROP CEILING
ALONG HALLWAY. INSTALL J-HOOKS IN AREAS WHERE BASKET TRAY IS INAPPROPRIATE.
INBOUND REDUNDANT FIBER BACKBONE 'A' CABLES FROM MDA-A IN SR/DC/MCR. INCLUDES (1)
24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLE FIELD TERMINATED WITH LC TYPE
CONNECTORS ON TR END & FACTORY PRE-TERMINATED ON MDA-A SIDE.
INBOUND REDUNDANT FIBER BACKBONE 'B' CABLES FROM MDA-B IN SR/DC/MCR. INCLUDES (1)
24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLE FIELD TERMINATED WITH LC TYPE
CONNECTORS ON TR END & FACTORY PRE-TERMINATED ON MDA-B SIDE.
N
1/16" = 1'-0"
BLDG 3 - LEVEL 11
N
1/16" = 1'-0"
BLDG 4 - LEVEL 13
N
1/16" = 1'-0"
BLDG 8 - LEVEL 15
N
1/16" = 1'-0"
BLDG 9 - LEVEL 16
N
1/16" = 1'-0"
BLDG 4 - LEVEL 24
N
1/16" = 1'-0"
BLDG 3 - LEVEL 22
N
1/16" = 1'-0"
BLDG 9 - LEVEL 27
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
CONSULTANTS:
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. BR 2171 EXP. 09/30/2023
ENGR REG. NO. F-17591 EXP. 02/29/2024
STAMP:
Drawing Number
Building Number
/3
/2
5:
:3
PM
BONHAM VA MEDICAL CENTER
1201 E. 9TH STREET
BONHAM, TX 75418
SPUR #:No. REVISION DESCRIPTION DATE
Of
BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
C O
N
TR
O
LL
ED
U
N C
LA
SS
IF
IE
D
IN
FO
R
M
AT
IO
N
(C U
I)
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC ENGINEER
SPUR DESIGN
2519 MADISON AVE., STE. 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
RATED ENGINEERING
609 S. KELLY AVENUE, SUITE H2
EDMOND, OK 73003
(405) 856-2965
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TECH ENGINEER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
STRUCT ENGINEER
STAND STRUCTURAL ENGINEERING
8234 ROBINSON STREET
OVERLAND PARK, KS 66204
(913) 214-2169
COMMISSIONING
ES2
13401 N. SANTA FE AVE
OKLAHOMA CITY, OK 73114
(405) 528-4500
549A4-21-700BONHAM EHRM
INFRASTRUCTURE
UPGRADES
100% BID DOCUMENTS
07/07/2023 229
T-104
BUILDING 3, 4, 8 & 9 - TELECOM PLANS
3, 4, 8 & 9
127 SF
NEW TR
EX.
T-305
T-305
T-305
T-305
WAPWAP
WAP
WAP
WAP
WAP
WAP WAP
WAP
3 3
4 44
3 3
W
3 3
CLOSET
105A
RESTROOM
HORIZONTAL FIBER OPTIC
MIXED PATHWAY ('A' & 'B')
BETWEEN BLDG 10 - LVL 1.
& BLDG 29 - LVL 1.
HORIZONTAL FIBER OPTIC
MIXED PATHWAY ('A' & 'B')
BETWEEN BLDG 10 - LVL 1.
& BLDG 9 - LVL 1.
2 3
W
W
2 WAP
T-305
T-305
112 SF
NEW TR
T-305
T-305 13 14
2 2 2 2
WAPWAP
VERTICAL FIBER
OPTIC PATHWAY "B"
TO BLDG 12 - LVL 1
VERTICAL FIBER
OPTIC PATHWAY "A"
TO BLDG 12 - LVL 1
CLOSET
WAP
WAP
WAPWAPWAP
4 4 4
VERTICAL FIBER
OPTIC PATHWAY "B"
TO BLDG 12 - LVL 2
VERTICAL FIBER
OPTIC PATHWAY "A"
TO BLDG 12 - LVL 2
TECHNOLOGY GENERAL NOTES
A. CONTRACTOR SHALL INCLUDE AN ADDITIONAL 10% OF CABLE DROPS IN THEIR BID FOR ADDS
FOUND DURING INSTALLATION.
B. ADDITIONAL PATCH PANEL CAPACITY SHALL BE PROVIDED TO ACCOUNT FOR 15% GROWTH OF
ADDITIONAL CABLE DROPS.
C. ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN IN PLACE AND OPERATIONAL UNTIL
FINAL CUT-OVER TO THE NEW CABLING.
D. EACH NEW WORK AREA OUTLET (WAO) LOCATION WILL CONSIST OF THE QUANTITY OF CAT6A CABLES AS DEPICTED ON THE PLANS. EACH CABLE WILL BE TERMINATED ON A 48-PORT CAT6A
PATCH PANEL IN IT'S DESIGNATED TR.
E. EXISTING WAO LOCATIONS SHALL BE RE-USED WHEREVER POSSIBLE.
F. LABEL FIBER CABLE GOING INTO EACH FIBER PATCH PANEL. ALL FIBER STRANDS WILL BE
TESTED UTILIZING AN OLTS AND AN OTDR PER THE TIER 2 STANDARD.
G. PROVIDE (1) EACH SMALL DIAMETER CAT6A PATCH CORD FOR EACH NEW DATA PORT. PROVIDE
VARIOUS LENGTHS AS REQUIRED FOR A NEAT AND ORDERLY INSTALLATION, UTILIZING THE
VERTICAL AND HORIZONTAL WIRE MANAGERS AS APPLICABLE. (SEE SPECIFICATIONS)
H. NEW FIRE-RATED SLEEVES SHALL BE INSTALLED LEAVING THE TR AND IN ALL FIRE-RATED
WALLS ALONG THE CABLE PATHWAYS.
I. EXISTING CONDUITS TO REMAIN.
J. EXISTING DATA RACK/RACKS TO REMAIN UNTIL AFTER CUT-OVER.
K. ENSURE THAT ALL GROUNDING AND BONDING IS COMPLETE. TWO SCREW BONDING LUGS NEED
TO BE INSTALLED TO BOND ALL METALLIC COMPONENTS OF THE RACK AND CABLE TRAY
SYSTEM, TO THE TELECOMMUNICATIONS SECONDARY BONDING BUSBAR.
L. AFTER CUT-OVER TO THE NEW CABLING, DEMOLISH ALL OLD DATA AND TELEPHONE CABLING
ALL THE WAY TO THE STATION END. ENSURE THAT ANY CABLES IN THE CEILING AREAS THAT
ARE FOR SYSTEMS OTHER THAN THE IT DATA AND TELEPHONE, ARE NOT DISTURBED. BLANK
OFF ANY UNUSED OLD DATA LOCATIONS. DEMOLISH ALL OLD PATCH PANELS AND ASSOCIATED
HARDWARE. ALL OTHER ANCILLARY RACK-MOUNTED EQUIPMENT, NOT RELATED TO IT DATA
AND TELEPHONE, TO BE RELOCATED TO A NEW RACK BY OIT PERSONNEL. FIRE-STOP ALL
EXISTING SLEEVES WHERE CABLING WAS REMOVED.
M. AFTER CUT-OVER, REMOVE ALL OLD IT FIBER OPTIC CABLING FROM THE TR ALL THE WAY BACK
TO THE SERVER DEMOLISH ALL ASSOCIATED HARDWARE AND TERMINATION EQUIPMENT.
ENSURE THAT ANY CABLING IN THE CEILING AREA THAT IS FOR OTHER SYSTEMS, IS NOT
DISTURBED.
N. ALL CATEGORY 6A STATION CABLING SHALL BE SUPPORTED USING A COMBINATION OF J-HOOKS
AND CABLE TRAYS (IF POSSIBLE) IN GENERAL PATHWAYS.
O. FIBER OPTIC BACKBONE CABLE TO BE FACTORY TERMINATED IN MCR. FIBER OPTIC BACKBONE CABLE TO BE FIELD TERMINATED IN TRs.
TECHNOLOGY LEGEND
WALL PHONE OUTLET CONTAINING (1) CATEGORY 6A UTP CABLE TERMINATED ONTO (1)
CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLOR TO BE BLUE.
TERMINATION SCHEME TO BE T568B.
WIRELESS ACCESS POINT CONTAINING (2) CATEGORY 6A UTP, GREEN, CABLE TERMINATED
ONTO (1) CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLOR TO BE BLUE.
TERMINATION SCHEME TO BE T568B.
4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (2) CATEGORY 6A UTP CABLES
TERMINATED ONTO (2) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR
TO BE BLUE. TERMINATION SCHEME TO BE T568B.
4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (3) CATEGORY 6A UTP CABLES
TERMINATED ONTO (3) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR
TO BE BLUE. TERMINATION SCHEME TO BE T568B.
4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (4) CATEGORY 6A UTP CABLES
TERMINATED ONTO (4) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR
TO BE BLUE. TERMINATION SCHEME TO BE T568B.
DMARC PATHWAY 'A'
DMARC PATHWAY 'B'
FIBER OPTIC BACKBONE PATHWAY 'A', INSIDE BLDGS.
FIBER OPTIC BACKBONE PATHWAY 'B', INSIDE BLDGS.
FIBER OPTIC BACKBONE PATHWAY 'A', OUTSIDE BLDGS.
FIBER OPTIC BACKBONE PATHWAY 'B', OUTSIDE BLDGS.
WAP
W
TECHNOLOGY KEYNOTES
VERIFY OR INSTALL HORIZONTAL PATHWAYS, BASKET TRAY (12" W, 4" H) ABOVE DROP CEILING
ALONG HALLWAY. INSTALL J-HOOKS IN AREAS WHERE BASKET TRAY IS INAPPROPRIATE.
INBOUND REDUNDANT FIBER BACKBONE 'A' CABLES FROM MDA-A IN SR/DC/MCR. INCLUDES (1)
24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLE FIELD TERMINATED WITH LC TYPE
CONNECTORS ON TR END & FACTORY PRE-TERMINATED ON MDA-A SIDE.
INBOUND REDUNDANT FIBER BACKBONE 'B' CABLES FROM MDA-B IN SR/DC/MCR. INCLUDES (1)
24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLE FIELD TERMINATED WITH LC TYPE
CONNECTORS ON TR END & FACTORY PRE-TERMINATED ON MDA-B SIDE.
N
1/16" = 1'-0"
BLDG 10 - LEVEL 11
N
1/16" = 1'-0"
BLDG 11 - LEVEL 12
N
1/16" = 1'-0"
BLDG 12 - LEVEL 24
N
1/16" = 1'-0"
BLDG 34 - LEVEL 15
N
1/16" = 1'-0"
BLDG 12 - LEVEL 13
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
CONSULTANTS:
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. BR 2171 EXP. 09/30/2023
ENGR REG. NO. F-17591 EXP. 02/29/2024
STAMP:
Drawing Number
Building Number
/3
/2
5:
:3
PM
BONHAM VA MEDICAL CENTER
1201 E. 9TH STREET
BONHAM, TX 75418
SPUR #:No. REVISION DESCRIPTION DATE
Of
BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
C O
N
TR
O
LL
ED
U
N C
LA
SS
IF
IE
D
IN
FO
R
M
AT
IO
N
(C U
I)
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC ENGINEER
SPUR DESIGN
2519 MADISON AVE., STE. 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
RATED ENGINEERING
609 S. KELLY AVENUE, SUITE H2
EDMOND, OK 73003
(405) 856-2965
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TECH ENGINEER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
STRUCT ENGINEER
STAND STRUCTURAL ENGINEERING
8234 ROBINSON STREET
OVERLAND PARK, KS 66204
(913) 214-2169
COMMISSIONING
ES2
13401 N. SANTA FE AVE
OKL…