Attachment - 09 Telecom Drawings_100_ Bid Docs.pdf

PDF 13 MB Posted

Attached to
Z2DA--EHRM Bonham, TX Construction 549A4-21-700 EHRM Construction (VA-23-00092679)
Solicitation number
36C77624B0007
Issued by

About this file

This file attachment is related to a federal contract opportunity for construction services. The solicitation number is 36C77624B0007 and is being issued by the Department of Veterans Affairs Technology Acquisition Center Austin. It is for EHRM construction services at the Bonham, Texas VA medical center, with a project number of 549A4-21-700. The opportunity type is a solicitation for VA-23-00092679. The 13MB file attachment contains technical drawings related to the construction project. Responses to the solicitation are due on an unspecified date. The award date and any pricing or set-aside terms are not included in this information.

View the file

Other files

File Type Posted
Attachment - 17 EHRM Bonham -Simulation Main Computer Rm 1- CFD Analysis.pdf PDF
Attachment - 05 Architectural Drawings_100_ Bid Docs.pdf PDF
Attachment - 13 Asbestos 3_ VA Checklist_Environ.pdf PDF
Attachment - 02 Hazmat Drawings_100_ Bid Docs.pdf PDF
Attachment - 25 Wage Determination - Bonham.pdf PDF
Attachment - 23 549A4-21-700 Bonham EHRM Add 02.pdf PDF
Attachment - 10 Security Drawings_100_ Bid Docs.pdf PDF
36C77624B0007_1.docx DOCX document
Attachment - 16 CABINET DIMENSIONAL DATA.pdf PDF
Attachment - 18 EHRM Bonham - Simulation Main Computer Rm 2 - CFD Analysis.pdf PDF
Attachment - 14 Asbestos 4 -Table 2 - Sample Log.pdf PDF
Attachment - 07 Mechanical Drawings_100_ Bid Docs.pdf PDF
Attachment - 03 Civil Drawings_100_ Bid Docs.pdf PDF
Attachment - 19 Structural Calculations.pdf PDF
Attachment - 08 Electrical Drawings_100_ Bid Docs.pdf PDF
Attachment - 26 General SOW Narrative Bonham.pdf PDF
Attachment - 22 Specs 549A4-21-700 Bonham EHRM Add 01.pdf PDF
Attachment - 06 Fire Protection Drawings_100_ Bid Docs.pdf PDF
Attachment - 12 Asbestos 2 - Table 1 - Asbestos-Historical Materials.pdf PDF
Attachment - 15 Asbestos Analysis 5--AppA.pdf PDF
Attachment - 20 AE Update 1.3 -Attachment 20 V1 549A4-21-700 100 Bid Doc Specs.pdf PDF
Attachment - 04 Structural Drawings_100_ Bid Docs.pdf PDF
Attachment - 11 Asbestos 1 - Environmental Narrative.pdf PDF
Attachment - 01 General Drawings_100_ Bid Docs.pdf PDF
Attachment - 24 Limitations on Subcontracting - Construction.pdf PDF
Attachment - 21 V2 549A4-21-700 100 Bid Doc Specs.pdf PDF
Show all 26

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ABBREVIATIONS

STANDARD MOUNTING HEIGHTSANNOTATION

ELECTRICAL: (AFF, AFG UNLESS NOTED OTHERWISE)

CU

TELECOMMUNICATION PLAN NOTE CALL OUT

EQUIPMENT DESIGNATION TAG

NEW WORK TO EXISTING WORK CONNECTION POINT

IC

CATV

FO

D

S

IC

S

WAP

# / #TV

M

S

V

COMMUNICATIONS OUTLET, TYPE AS NOTED

COMMUNICATIONS OUTLET, FLOOR BOX, TYPE AS NOTED

WIRELESS ACCESS POINT, CEILING MOUNTED

COMMUNICATIONS OUTLET, CEILING MTD, TYPE AS NOTED

SPEAKER, WALL MOUNTED

SPEAKER, CEILING MOUNTED

TELECOMMUNICATIONS RACK, TWO-POST, FLOOR MOUNTED

GROUND BAR, TYPE AS NOTED

TELECOMMUNICATIONS ENCLOSURE, WALL MOUNTED

WIRE BASKET TRAY, TYPE AS NOTED

CABLE TELEVISION LINE

FIBEROPTIC LINE

COMMUNICATION CABLE PATHWAY

FIBER OPTIC BACKBONE PATHWAY "A"

DATA LINE

SPEAKER LINE

INTERCOM LINE

INTERCOM, "M" DENOTES MASTER STATION

VOLUME CONTROL, WALL MOUNTED

MULTI-SERVICE POWER POLE WITH POWER/DATA,

TYPE AS NOTED AND/OR SCHEDULED

MULTI-SERVICE FLOOR BOX/POKE-THRU WITH POWER/DATA,

TYPE AS NOTED AND/OR SCHEDULED

TELECOMMUNICATIONS CHANNEL RACK, 7'H x 19"W x 30"D, 4-POST, OPEN FRAME TYPE

SERVER CABINET, FLOOR MOUNTED

# = DATA, # = QUANTITY OF CABLES

#TV = CABLE TELEVISION, # = QUANTITY OF CABLES

= DATA, 2 CABLES

#TV = CABLE TELEVISION, # = QUANTITY OF CABLES

#V = VOICE, # = QUANTITY OF CABLES

= DATA, 2 CABLES

# = DATA, # = QUANTITY OF CABLES

TELECOMMUNICATIONS SYMBOLS

#TV = CABLE TELEVISION, # = QUANTITY OF CABLES

#V = VOICE, # = QUANTITY OF CABLES

M (CONT'D)

MV MEDIUM VOLTAGE

MVA MEGAVOLT-AMPERE

MW MEGAWATT

X

W

V

U

T

S

R

P

O

N

M

L

K

J

I

H

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FABL FIRE ALARM BELL

FABX FIRE ALARM BOX

FACP FIRE ALARM CONTROL PANEL

FC FOOTCANDLE

FI FILM ILLUMINATOR

FIXT FIXTURE

FLA FULL LOAD AMPS

FLEX FLEXIBLE METALLIC CONDUIT

FLUOR FLUORESCENT

FO FIBER-OPTIC

FP FIRE PROTECTION

FT FEET OR FOOT

FVNR FULL VOLTAGE NON-REVERSING

FVR FULL VOLTAGE REVERSING

G

F

E

D

EC EMPTY CONDUIT

EG EQUIPMENT GROUND

EL ELEVATION

ELEC ELECTRIC OR ELECTRICAL

ELEV ELEVATOR

EMCP EMER. MONITORING CONTROL PANEL

EMER EMERGENCY

EMI ELECTROMAGNETIC INTERFERENCE

EMT ELECTRICAL METALLIC TUBING

ENCL ENCLOSURE

EPO EMERGENCY POWER OFF

ESMT EASEMENT

ETD EXISTING TO BE DEMOLISHED

ETR EXISTING TO REMAIN

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

EXIST EXISTING

DB DECIBEL OR DIRECT BURIAL

DC DIRECT CURRENT

DCP DIMMER CONTROL PANEL

DEG C DEGREES CELSIUS

DEG F DEGREES FAHRENHEIT

DEMO DEMOLITION

DIAG DIAGRAM

DISC DISCONNECT

DISTR DISTRIBUTION

DISTR PNL DISTRIBUTION PANEL

DN DOWN

DPDT DOUBLE POLE, DOUBLE THROW

DPST DOUBLE POLE, SINGLE THROW

DRSW DOOR SWITCH

DS DISCONNECT SWITCH

DWG DRAWING

C CONDUIT

CAP CAPACITY

CAT CATALOG

CATV COMMUNITY ANTENNA TELEVISION

CCR CONTROL CONTACTOR

CCTV CLOSED CIRCUIT TELEVISION

cd CANDELA

CD CONSTRUCTION DOCUMENTS

CF CONTRACTOR FURNISHED

CF/CI CONTRACTOR FURNISHED/

CONTRACTOR INSTALLED

CF/OI CONTRACTOR FURNISHED/OWNER

INSTALLED

CFE CONTRACTOR FURNISHED

EQUIPMENT

CHW CHILLED WATER

CHWP CHILLED WATER PUMP

CKT CIRCUIT

CKT BRKR CIRCUIT BREAKER

CLF CURRENT LIMITING FUSE

CLG CEILING

CMU CONCRETE MASONRY UNIT

COAX COAX CABLE

COMM COMMUNICATION

CONC CONCRETE

CONT CONTINUE

CONTR CONTRACTOR

COORD COORDINATE

CPT CONTROL POWER TRANSFORMER

CRI COLOR RENDERING INDEX

CT CURRENT TRANSFORMER

CTV CABLE TELEVISION

CU COPPER

CU FT CUBIC FEET

C

B

A

UFD UNDERFLOOR DUCT

UGND UNDERGROUND

UL UNDERWRITERS LABORATORY

UNO UNLESS NOTED OTHERWISE

UPS UNINTERRUPTIBLE POWER SUPPLY

UTIL UTILITY

V VOLT

VA VOLT AMPERE

VAR VOLT AMPERE REACTIVE

VCM VERTICAL CABLE MANAGER

VFD VARIABLE FREQUENCY DRIVE

VOLT VOLTAGE

TC TIME CLOCK

TEL TELEPHONE

TO TELECOMMUNICATIONS OUTLET

TR TELECOMMUNICATIONS ROOM

TV TELEVISION

TYP TYPICAL

RCP REFLECTED CEILING PLAN

RCPT RECEPTACLE

REC RECESSED

REQD REQUIRED

RGS RIGID GALVANIZED STEEL

RM ROOM

RMS ROOT MEAN SQUARE

RU RACK UNIT

N NEUTRAL

NA NOT APPLICABLE

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURERS ASSOCIATION

NFPA NATIONAL FIRE PROTECTION

ASSOCIATION

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NO NORMALLY OPEN

NS NO SCALE

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

OL OVERLOAD

MATV MASTER ANTENNA TELEVISION SYSTEM

MAX MAXIMUM

MC METAL-CLAD

MCA MINIMUM CIRCUIT AMPS

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDP MAIN DISTRIBUTION PANEL

MECH MECHANICAL

MG MOTOR GENERATOR

MH MANHOLE

MIN MINIMUM

MOCP MAXIMUM OVERCURRENT PROTECTION

MLO MAIN LUGS ONLY

MT MOUNT

MTD MOUNTED

MTG MOUNTING

KV KILOVOLT

KVA KILOVOLT AMPERE

KVAH KILOVOLT AMPERE PER HOUR

KVAR KILOVOLT AMPERE REACTIVE

KW KILOWATT

KWH KILOWATT HOUR

KWHM KILOWATT HOUR METER

JB JUNCTION BOX

J-BOX JUNCTION BOX

XFER TRANSFER

XFMR TRANSFORMER

XP EXPLOSION PROOF

LED LIGHT EMITTING DIODE

LF LINEAR FEET (FOOT)

LM LUMEN

LP LIGHT POLE

LPS LOW PRESSURE SODIUM

LRA LOCKED ROTOR AMPS

LTCP LOCAL TEMPERATURE CONTROL PANEL

LT LIGHT

LTG LIGHTING

LTG PNL LIGHTING PANEL

LTNG LIGHTNING

LV LOW VOLTAGE

W WATT

WAO WORK AREA OUTLET

WP WEATHERPROOF

IESNA ILLUMINATION ENGINEERING SOCIETY

OF NORTH AMERICA

IG ISOLATED GROUND

IMC INTERMEDIATE METAL CONDUIT

INCAND INCANDESCENT

IR INFRARED

IWH INSTANTANEOUS WATER HEATER

G OR GND GROUND OR GENERATOR

GEN GENERATOR

GFCI GROUND FAULT CIRCUIT INTERRUPTER

GTB GROUND TERMINAL BOX

SCC SHORT CIRCUIT CAPACITY

SES SERVICE ENTRANCE SECTION

SD SMOKE DETECTOR

SF SQUARE FOOT (FEET)

SHT SHEET

SI INTERNATIONAL SYSTEM OF UNITS

SPEC SPECIFICATION

SPST SINGLE POLE, SINGLE THROW

SURF SURFACE

SW SWITCH

SWBD SWITCHBOARD

SWGR SWITCHGEAR

P POLE

PA PUBLIC ADDRESS

PB PANELBOARD, PULL BOX, OR

PUSHBUTTON

PBPU PREFABRICATED BEDSIDE PATIENT UNIT

PCB POLYCHLORINATED BIPHENYL

PEC PHOTOELECTRIC CELL

PED PEDESTAL

PEND PENDANT

PF POWER FACTOR

PH PHASE

PNL PANEL

POD POWER OPERATED DAMPER

POE POWER OVER ETHERNET

PP PATCH PANEL

PT POTENTIAL TRANSFORMER

PTRV POWER TYPE ROOF VENTILATION

PVC POLYVINYL CHLORIDE (PLASTIC)

PWR POWER

1P SINGLE POLE

1PH SINGLE-PHASE

3P THREE POLE

3PH THREE-PHASE

3W THREE WIRE

4W FOUR WIRE

A/C AIR CONDITIONING

A/E ARCHITECT/ENGINEER

AAP ALARM ANNUNCIATOR PANEL

AC ALTERNATING CURRENT OR ARMORED

ACC ACCESSIBLE

ADDL ADDITIONAL

ADJ ADJACENT, ADJOINING

ADO AUTOMATIC DOOR OPENER

AF AMPERE FRAME OR AMP FUSE

AFC ABOVE FINISHED COUNTER, AUTOMATIC

FREQUENCY CONTROL, OR

AVAILABLE FAULT CURRENT

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AH AMPERE HOUR

AHJ AUTHORITY HAVING JURISDICTION

AIC AMPERE INTERRUPTING CAPACITY

ALT ALTERNATE

AMB OR A AMBIENT

AMP AMPERE

ARCH ARCHITECT

ASC AMPS SHORT CIRCUIT

AT AMPERE TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AV AUDIO VISUAL

HCM HORIZONTAL CABLE MANAGER

HID HIGH INTENSITY DISCHARGE

HOA HAND-OFF-AUTOMATIC

HP HORSEPOWER

HT HEIGHT

HZ HERTZ

BAT BATTERY

BC BARE COPPER

BD BOARD

BFF BELOW FINISH FLOOR

BIL BASIC INSULATION LEVEL

BLDG BUILDING

BLK BLOCK

BPIP BOILER PLANT

INSTRUMENTATION PANEL

BRKR BREAKER

BYP BY PASS

DETAIL REFERENCE

SECTION CUT DESIGNATION

EP-101

EP-101

FIBER OPTIC BACKBONE PATHWAY "B"

84" 48" 48" 84" 48" 80" 60"

120" 60" 36" 48" 72" 48"

144" 18" 24" 26" 48" 48"

CEILING

48" 48" 18" 84"

AUDIBLE APPLIANCES (CENTERLINE)

ALARMS

ANNUNCIATOR PANELS

CLOCK OUTLETS (CENTERLINE)

CONTROLS (TOP)

EXIT SIGNS (WALL-MOUNTED, BOTTOM)

FIRE ALARM ANNUNCIATOR PANEL (DISPLAY)

FIRE ALARM BELL (EXTERIOR)

FIRE ALARM CONTROL PANEL/UNIT (DISPLAY)

INTERCOM (AFEA ONLY)

INTERCOMS (TOP)

PANELS & PANELBOARDS (TOP)

PULL STATIONS (HANDLE)

PHOTOCELLS

RECEPTACLES (BOTTOM)

RECEPTACLES (EXTERIOR)

RECEPTACLES (GARAGES) RECEPTACLES IN

EQUIPMENT ROOMS (TOP) REMOTE INDICATING

LIGHT (EQUIPMENT ROOMS) REMOTE INDICATING

LIGHT (FINISHED AREAS) SAFETY SWITCHES &

STARTERS SWITCHES (TOP)

TELEPHONE/DATA/TV OUTLETS (BOTTOM)

VISIBLE APPLIANCES (CENTERLINE)

#W = WALL PHONE, 1 CABLE, # = QUANTITY OF CABLES

TE TELECOMMUNICATIONS ENCLOSURE

VERTICAL CABLE MANAGER, 6" WIDE, WITH DOORS

COMM

PATH-A

PATH-B

LADDER TRAY, TYPE AS NOTED

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

CONSULTANTS:

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. BR 2171 EXP. 09/30/2023

ENGR REG. NO. F-17591 EXP. 02/29/2024

STAMP:

Drawing Number

Building Number

/3

/2

5:

:3

PM

BONHAM VA MEDICAL CENTER

1201 E. 9TH STREET

BONHAM, TX 75418

SPUR #:No. REVISION DESCRIPTION DATE

Of

BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C O

N

TR

O

LL

ED

U

N C

LA

SS

IF

IE

D

IN

FO

R

M

AT

IO

N

(C U

I)

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC ENGINEER

SPUR DESIGN

2519 MADISON AVE., STE. 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

RATED ENGINEERING

609 S. KELLY AVENUE, SUITE H2

EDMOND, OK 73003

(405) 856-2965

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TECH ENGINEER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

STRUCT ENGINEER

STAND STRUCTURAL ENGINEERING

8234 ROBINSON STREET

OVERLAND PARK, KS 66204

(913) 214-2169

COMMISSIONING

ES2

13401 N. SANTA FE AVE

OKLAHOMA CITY, OK 73114

(405) 528-4500

549A4-21-700BONHAM EHRM

INFRASTRUCTURE

UPGRADES

100% BID DOCUMENTS

07/07/2023 229

T-000

TELECOM SYMBOLS & ABBREVIATIONS

N/A

ASPEN NR

AutoCAD SHX Text

FRONT

T-300

T-300

241 SF / 100 SF

STORAGE

286 SF / 100 SF

STORAGE

86 SF / 100 SF

CLOSET

690 SF / 100 SF

PHONE ROOM

61 SF / 100 SF

CLOSET

18.5

DMARC PATHWAY "B"

TO BLDG 1 - LVL 5 DMARC.

IN SAME PATH AS FIBER

OPTIC BACKBONE "B"

VERTICAL FIBER

OPTIC PATHWAY "A"

FROM BLDG 1 - LVL 1

VERTICAL FIBER OPTIC

PATHWAY "B"

FROM BLDG 1 - LVL 1

T-300

T-300

TECHNOLOGY GENERAL NOTES

A. CONTRACTOR SHALL INCLUDE AN ADDITIONAL 10% OF CABLE DROPS IN THEIR BID FOR ADDS

FOUND DURING INSTALLATION.

B. ADDITIONAL PATCH PANEL CAPACITY SHALL BE PROVIDED TO ACCOUNT FOR 15% GROWTH OF

ADDITIONAL CABLE DROPS.

C. ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN IN PLACE AND OPERATIONAL UNTIL

FINAL CUT-OVER TO THE NEW CABLING.

D. EACH NEW WORK AREA OUTLET (WAO) LOCATION WILL CONSIST OF THE QUANTITY OF CAT6A CABLES AS DEPICTED ON THE PLANS. EACH CABLE WILL BE TERMINATED ON A 48-PORT CAT6A

PATCH PANEL IN IT'S DESIGNATED TR.

E. EXISTING WAO LOCATIONS SHALL BE RE-USED WHEREVER POSSIBLE.

F. LABEL FIBER CABLE GOING INTO EACH FIBER PATCH PANEL. ALL FIBER STRANDS WILL BE

TESTED UTILIZING AN OLTS AND AN OTDR PER THE TIER 2 STANDARD.

G. PROVIDE (1) EACH SMALL DIAMETER CAT6A PATCH CORD FOR EACH NEW DATA PORT. PROVIDE

VARIOUS LENGTHS AS REQUIRED FOR A NEAT AND ORDERLY INSTALLATION, UTILIZING THE

VERTICAL AND HORIZONTAL WIRE MANAGERS AS APPLICABLE. (SEE SPECIFICATIONS)

H. NEW FIRE-RATED SLEEVES SHALL BE INSTALLED LEAVING THE TR AND IN ALL FIRE-RATED

WALLS ALONG THE CABLE PATHWAYS.

I. EXISTING CONDUITS TO REMAIN.

J. EXISTING DATA RACK/RACKS TO REMAIN UNTIL AFTER CUT-OVER.

K. ENSURE THAT ALL GROUNDING AND BONDING IS COMPLETE. TWO SCREW BONDING LUGS NEED

TO BE INSTALLED TO BOND ALL METALLIC COMPONENTS OF THE RACK AND CABLE TRAY

SYSTEM, TO THE TELECOMMUNICATIONS SECONDARY BONDING BUSBAR.

L. AFTER CUT-OVER TO THE NEW CABLING, DEMOLISH ALL OLD DATA AND TELEPHONE CABLING

ALL THE WAY TO THE STATION END. ENSURE THAT ANY CABLES IN THE CEILING AREAS THAT

ARE FOR SYSTEMS OTHER THAN THE IT DATA AND TELEPHONE, ARE NOT DISTURBED. BLANK

OFF ANY UNUSED OLD DATA LOCATIONS. DEMOLISH ALL OLD PATCH PANELS AND ASSOCIATED

HARDWARE. ALL OTHER ANCILLARY RACK-MOUNTED EQUIPMENT, NOT RELATED TO IT DATA

AND TELEPHONE, TO BE RELOCATED TO A NEW RACK BY OIT PERSONNEL. FIRE-STOP ALL

EXISTING SLEEVES WHERE CABLING WAS REMOVED.

M. AFTER CUT-OVER, REMOVE ALL OLD IT FIBER OPTIC CABLING FROM THE TR ALL THE WAY BACK

TO THE SERVER DEMOLISH ALL ASSOCIATED HARDWARE AND TERMINATION EQUIPMENT.

ENSURE THAT ANY CABLING IN THE CEILING AREA THAT IS FOR OTHER SYSTEMS, IS NOT

DISTURBED.

N. ALL CATEGORY 6A STATION CABLING SHALL BE SUPPORTED USING A COMBINATION OF J-HOOKS

AND CABLE TRAYS (IF POSSIBLE) IN GENERAL PATHWAYS.

O. FIBER OPTIC BACKBONE CABLE TO BE FACTORY TERMINATED IN MCR. FIBER OPTIC BACKBONE CABLE TO BE FIELD TERMINATED IN TRs.

98 SF / 100 SF

T-301

T-301

T-301

T-301

T-301

T-301

T-301

T-301

CLOSET

CLOSET

113A

NEW TR

116A

NEW TR

VERTICAL FIBER

OPTIC PATHWAY "A"

TO BLDG 1 - LVL B

VERTICAL DMARC

PATH 'B' TO MCR

VERTICAL FIBER OPTIC

PATHWAY "B"

TO BLDG 1 - LVL B

DMARC PATHWAY "A"

FROM BLDG 29 - LVL 1.

TO BLDG 1 - LVL 5 DMARC.

IN SAME PATH AS FIBER

OPTIC BACKBONE "A"

HORIZONTAL FIBER

OPTIC PATHWAY "B"

TO BLDG 2 - LVL 1

HORIZONTAL FIBER OPTIC

PATHWAY "B"

TO BLDG 1 - LVL 1 - TR116A

HORIZONTAL FIBER OPTIC

PATHWAY "A"

TO BLDG 1 - LVL 1 - TR 116A.

HORIZONTAL FIBER OPTIC

MIXED PATHWAY ("A" & "B")

TO BLDG 29 - LVL 1.

T-302

64 WAOs

240 WAOs

144 SF / 100 SF

TECHNOLOGY LEGEND

WALL PHONE OUTLET CONTAINING (1) CATEGORY 6A UTP CABLE TERMINATED ONTO (1)

CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLOR TO BE BLUE.

TERMINATION SCHEME TO BE T568B.

WIRELESS ACCESS POINT CONTAINING (2) CATEGORY 6A UTP, GREEN, CABLE TERMINATED

ONTO (1) CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLOR TO BE BLUE.

TERMINATION SCHEME TO BE T568B.

4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (2) CATEGORY 6A UTP CABLES

TERMINATED ONTO (2) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR

TO BE BLUE. TERMINATION SCHEME TO BE T568B.

4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (3) CATEGORY 6A UTP CABLES

TERMINATED ONTO (3) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR

TO BE BLUE. TERMINATION SCHEME TO BE T568B.

4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (4) CATEGORY 6A UTP CABLES

TERMINATED ONTO (4) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR

TO BE BLUE. TERMINATION SCHEME TO BE T568B.

DMARC PATHWAY 'A'

DMARC PATHWAY 'B'

FIBER OPTIC BACKBONE PATHWAY 'A', INSIDE BLDGS.

FIBER OPTIC BACKBONE PATHWAY 'B', INSIDE BLDGS.

FIBER OPTIC BACKBONE PATHWAY 'A', OUTSIDE BLDGS.

FIBER OPTIC BACKBONE PATHWAY 'B', OUTSIDE BLDGS.

WAP

W

TECHNOLOGY KEYNOTES

VERIFY OR INSTALL HORIZONTAL PATHWAYS, BASKET TRAY (12" W, 4" H) ABOVE DROP CEILING

ALONG HALLWAY. INSTALL J-HOOKS IN AREAS WHERE BASKET TRAY IS INAPPROPRIATE.

INBOUND REDUNDANT FIBER BACKBONE 'A' CABLES FROM MDA-A IN SR/DC/MCR. INCLUDES (1)

24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLE FIELD TERMINATED WITH LC TYPE

CONNECTORS ON TR END & FACTORY PRE-TERMINATED ON MDA-A SIDE.

INBOUND REDUNDANT FIBER BACKBONE 'B' CABLES FROM MDA-B IN SR/DC/MCR. INCLUDES (1)

24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLE FIELD TERMINATED WITH LC TYPE

CONNECTORS ON TR END & FACTORY PRE-TERMINATED ON MDA-B SIDE.

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

CONSULTANTS:

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. BR 2171 EXP. 09/30/2023

ENGR REG. NO. F-17591 EXP. 02/29/2024

STAMP:

Drawing Number

Building Number

/3

/2

5:

:3

PM

BONHAM VA MEDICAL CENTER

1201 E. 9TH STREET

BONHAM, TX 75418

SPUR #:No. REVISION DESCRIPTION DATE

Of

BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C O

N

TR

O

LL

ED

U

N C

LA

SS

IF

IE

D

IN

FO

R

M

AT

IO

N

(C U

I)

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC ENGINEER

SPUR DESIGN

2519 MADISON AVE., STE. 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

RATED ENGINEERING

609 S. KELLY AVENUE, SUITE H2

EDMOND, OK 73003

(405) 856-2965

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TECH ENGINEER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

STRUCT ENGINEER

STAND STRUCTURAL ENGINEERING

8234 ROBINSON STREET

OVERLAND PARK, KS 66204

(913) 214-2169

COMMISSIONING

ES2

13401 N. SANTA FE AVE

OKLAHOMA CITY, OK 73114

(405) 528-4500

549A4-21-700BONHAM EHRM

INFRASTRUCTURE

UPGRADES

100% BID DOCUMENTS

07/07/2023 229

T-100

BUILDING 1 - TELECOM PLANS

ASPEN NR

1/16" = 1'-0"

BLDG 1 - BASEMENT1 1/16" = 1'-0"

BLDG 1 - LEVEL 12

N N

SHEET TO BE PRINTED IN COLOR

T-301

T-301

FIBER OPTIC PATHWAY "B"

TO BLDG 1 - LVL 2

VERTICAL FIBER

OPTIC PATHWAY "A"

TO BLDG 1 - LVL 2

T-302

146 SF / 100 SF

NEW TR

CLOSET

317A

CLOSET

317B

FIRE RISER

300G

234 WAOs

T-301

T-301

FIBER OPTIC PATHWAY "B"

TO BLDG 1 - LVL 1

VERTICAL FIBER

OPTIC PATHWAY "A"

TO BLDG 1 - LVL 1

T-302

143 SF / 100 SF

NEW TR

CLOSET

FIRE RISER

200G

49 WAOs

T-301

T-301

VERTICAL FIBER

OPTIC PATHWAY "B"

TO BLDG 1 - LVL 3

VERTICAL FIBER

OPTIC PATHWAY "A"

TO BLDG 1 - LVL 3

T-302

149 SF / 100 SF

NEW TR

CLOSET

CLOSET

418A

FIRE RISER

400G

131 WAOs

VERTICAL FIBER

OPTIC PATHWAY "A"

TO BLDG 1 - LVL 5

NEW FP

CLOSET

T-302

T-302

VERTICAL FIBER

OPTIC PATHWAY "A"

TO BLDG 1 - LVL 4

FIBER OPTIC PATHWAY "B"

TO BLDG 1 - LVL 4

VERTICAL FIBER OPTIC

PATHWAY "B"

TO BLDG 1 - LVL 4

T-302

NEW SERVER

FIRE RISER

500E

64 WAOs

TECHNOLOGY GENERAL NOTES

A. CONTRACTOR SHALL INCLUDE AN ADDITIONAL 10% OF CABLE DROPS IN THEIR BID FOR ADDS

FOUND DURING INSTALLATION.

B. ADDITIONAL PATCH PANEL CAPACITY SHALL BE PROVIDED TO ACCOUNT FOR 15% GROWTH OF

ADDITIONAL CABLE DROPS.

C. ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN IN PLACE AND OPERATIONAL UNTIL

FINAL CUT-OVER TO THE NEW CABLING.

D. EACH NEW WORK AREA OUTLET (WAO) LOCATION WILL CONSIST OF THE QUANTITY OF CAT6A CABLES AS DEPICTED ON THE PLANS. EACH CABLE WILL BE TERMINATED ON A 48-PORT CAT6A

PATCH PANEL IN IT'S DESIGNATED TR.

E. EXISTING WAO LOCATIONS SHALL BE RE-USED WHEREVER POSSIBLE.

F. LABEL FIBER CABLE GOING INTO EACH FIBER PATCH PANEL. ALL FIBER STRANDS WILL BE

TESTED UTILIZING AN OLTS AND AN OTDR PER THE TIER 2 STANDARD.

G. PROVIDE (1) EACH SMALL DIAMETER CAT6A PATCH CORD FOR EACH NEW DATA PORT. PROVIDE

VARIOUS LENGTHS AS REQUIRED FOR A NEAT AND ORDERLY INSTALLATION, UTILIZING THE

VERTICAL AND HORIZONTAL WIRE MANAGERS AS APPLICABLE. (SEE SPECIFICATIONS)

H. NEW FIRE-RATED SLEEVES SHALL BE INSTALLED LEAVING THE TR AND IN ALL FIRE-RATED

WALLS ALONG THE CABLE PATHWAYS.

I. EXISTING CONDUITS TO REMAIN.

J. EXISTING DATA RACK/RACKS TO REMAIN UNTIL AFTER CUT-OVER.

K. ENSURE THAT ALL GROUNDING AND BONDING IS COMPLETE. TWO SCREW BONDING LUGS NEED

TO BE INSTALLED TO BOND ALL METALLIC COMPONENTS OF THE RACK AND CABLE TRAY

SYSTEM, TO THE TELECOMMUNICATIONS SECONDARY BONDING BUSBAR.

L. AFTER CUT-OVER TO THE NEW CABLING, DEMOLISH ALL OLD DATA AND TELEPHONE CABLING

ALL THE WAY TO THE STATION END. ENSURE THAT ANY CABLES IN THE CEILING AREAS THAT

ARE FOR SYSTEMS OTHER THAN THE IT DATA AND TELEPHONE, ARE NOT DISTURBED. BLANK

OFF ANY UNUSED OLD DATA LOCATIONS. DEMOLISH ALL OLD PATCH PANELS AND ASSOCIATED

HARDWARE. ALL OTHER ANCILLARY RACK-MOUNTED EQUIPMENT, NOT RELATED TO IT DATA

AND TELEPHONE, TO BE RELOCATED TO A NEW RACK BY OIT PERSONNEL. FIRE-STOP ALL

EXISTING SLEEVES WHERE CABLING WAS REMOVED.

M. AFTER CUT-OVER, REMOVE ALL OLD IT FIBER OPTIC CABLING FROM THE TR ALL THE WAY BACK

TO THE SERVER DEMOLISH ALL ASSOCIATED HARDWARE AND TERMINATION EQUIPMENT.

ENSURE THAT ANY CABLING IN THE CEILING AREA THAT IS FOR OTHER SYSTEMS, IS NOT

DISTURBED.

N. ALL CATEGORY 6A STATION CABLING SHALL BE SUPPORTED USING A COMBINATION OF J-HOOKS

AND CABLE TRAYS (IF POSSIBLE) IN GENERAL PATHWAYS.

O. FIBER OPTIC BACKBONE CABLE TO BE FACTORY TERMINATED IN MCR. FIBER OPTIC BACKBONE CABLE TO BE FIELD TERMINATED IN TRs.

TECHNOLOGY LEGEND

WALL PHONE OUTLET CONTAINING (1) CATEGORY 6A UTP CABLE TERMINATED ONTO (1)

CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLOR TO BE BLUE.

TERMINATION SCHEME TO BE T568B.

WIRELESS ACCESS POINT CONTAINING (2) CATEGORY 6A UTP, GREEN, CABLE TERMINATED

ONTO (1) CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLOR TO BE BLUE.

TERMINATION SCHEME TO BE T568B.

4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (2) CATEGORY 6A UTP CABLES

TERMINATED ONTO (2) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR

TO BE BLUE. TERMINATION SCHEME TO BE T568B.

4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (3) CATEGORY 6A UTP CABLES

TERMINATED ONTO (3) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR

TO BE BLUE. TERMINATION SCHEME TO BE T568B.

4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (4) CATEGORY 6A UTP CABLES

TERMINATED ONTO (4) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR

TO BE BLUE. TERMINATION SCHEME TO BE T568B.

DMARC PATHWAY 'A'

DMARC PATHWAY 'B'

FIBER OPTIC BACKBONE PATHWAY 'A', INSIDE BLDGS.

FIBER OPTIC BACKBONE PATHWAY 'B', INSIDE BLDGS.

FIBER OPTIC BACKBONE PATHWAY 'A', OUTSIDE BLDGS.

FIBER OPTIC BACKBONE PATHWAY 'B', OUTSIDE BLDGS.

WAP

W

TECHNOLOGY KEYNOTES

VERIFY OR INSTALL HORIZONTAL PATHWAYS, BASKET TRAY (12" W, 4" H) ABOVE DROP CEILING

ALONG HALLWAY. INSTALL J-HOOKS IN AREAS WHERE BASKET TRAY IS INAPPROPRIATE.

INBOUND REDUNDANT FIBER BACKBONE 'A' CABLES FROM MDA-A IN SR/DC/MCR. INCLUDES (1)

24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLE FIELD TERMINATED WITH LC TYPE

CONNECTORS ON TR END & FACTORY PRE-TERMINATED ON MDA-A SIDE.

INBOUND REDUNDANT FIBER BACKBONE 'B' CABLES FROM MDA-B IN SR/DC/MCR. INCLUDES (1)

24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLE FIELD TERMINATED WITH LC TYPE

CONNECTORS ON TR END & FACTORY PRE-TERMINATED ON MDA-B SIDE.

1/16" = 1'-0"

BLDG 1 - LEVEL 32 1/16" = 1'-0"

BLDG 1 - LEVEL 21

1/16" = 1'-0"

BLDG 1 - LEVEL 43 1/16" = 1'-0"

BLDG 1 - LEVEL 54

N N

NN

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

CONSULTANTS:

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. BR 2171 EXP. 09/30/2023

ENGR REG. NO. F-17591 EXP. 02/29/2024

STAMP:

Drawing Number

Building Number

/3

/2

5:

:3

PM

BONHAM VA MEDICAL CENTER

1201 E. 9TH STREET

BONHAM, TX 75418

SPUR #:No. REVISION DESCRIPTION DATE

Of

BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C O

N

TR

O

LL

ED

U

N C

LA

SS

IF

IE

D

IN

FO

R

M

AT

IO

N

(C U

I)

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC ENGINEER

SPUR DESIGN

2519 MADISON AVE., STE. 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

RATED ENGINEERING

609 S. KELLY AVENUE, SUITE H2

EDMOND, OK 73003

(405) 856-2965

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TECH ENGINEER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

STRUCT ENGINEER

STAND STRUCTURAL ENGINEERING

8234 ROBINSON STREET

OVERLAND PARK, KS 66204

(913) 214-2169

COMMISSIONING

ES2

13401 N. SANTA FE AVE

OKLAHOMA CITY, OK 73114

(405) 528-4500

549A4-21-700BONHAM EHRM

INFRASTRUCTURE

UPGRADES

100% BID DOCUMENTS

07/07/2023 229

T-101

BUILDING 1 - TELECOM PLANS

ASPEN NR

109 SF / 100 SF

100A

T-303

T-303

T-303

T-303

T-303 4 T-303

VERTICAL FIBER

OPTIC PATHWAY "B"

TO BLDG 2 - LVL 2

3 1

1 1 1

HORIZONTAL FIBER

OPTIC MIXED

PATHWAY ('A" & "B")

TO BLDG 1 - LVL 1

HORIZONTAL FIBER

OPTIC MIXED

PATHWAY ('A" & "B")

TO BLDG 3 - LVL 1

CLOSET

100C

197 SF / 100 SF

NEW TR

NEW TR

118 WAOs

118 WAOs

T-303

T-303

T-303

T-303

VERTICAL FIBER

OPTIC PATHWAY "B"

TO BLDG 2 - LVL 3

VERTICAL FIBER

OPTIC PATHWAY "A"

TO BLDG 2 - LVL 3

114 SF / 100 SF

NEW TR

CLOSET

VESTIBULE

201B

HAC

201A

234 WAOs

TECHNOLOGY GENERAL NOTES

A. CONTRACTOR SHALL INCLUDE AN ADDITIONAL 10% OF CABLE DROPS IN THEIR BID FOR ADDS

FOUND DURING INSTALLATION.

B. ADDITIONAL PATCH PANEL CAPACITY SHALL BE PROVIDED TO ACCOUNT FOR 15% GROWTH OF

ADDITIONAL CABLE DROPS.

C. ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN IN PLACE AND OPERATIONAL UNTIL

FINAL CUT-OVER TO THE NEW CABLING.

D. EACH NEW WORK AREA OUTLET (WAO) LOCATION WILL CONSIST OF THE QUANTITY OF CAT6A CABLES AS DEPICTED ON THE PLANS. EACH CABLE WILL BE TERMINATED ON A 48-PORT CAT6A

PATCH PANEL IN IT'S DESIGNATED TR.

E. EXISTING WAO LOCATIONS SHALL BE RE-USED WHEREVER POSSIBLE.

F. LABEL FIBER CABLE GOING INTO EACH FIBER PATCH PANEL. ALL FIBER STRANDS WILL BE

TESTED UTILIZING AN OLTS AND AN OTDR PER THE TIER 2 STANDARD.

G. PROVIDE (1) EACH SMALL DIAMETER CAT6A PATCH CORD FOR EACH NEW DATA PORT. PROVIDE

VARIOUS LENGTHS AS REQUIRED FOR A NEAT AND ORDERLY INSTALLATION, UTILIZING THE

VERTICAL AND HORIZONTAL WIRE MANAGERS AS APPLICABLE. (SEE SPECIFICATIONS)

H. NEW FIRE-RATED SLEEVES SHALL BE INSTALLED LEAVING THE TR AND IN ALL FIRE-RATED

WALLS ALONG THE CABLE PATHWAYS.

I. EXISTING CONDUITS TO REMAIN.

J. EXISTING DATA RACK/RACKS TO REMAIN UNTIL AFTER CUT-OVER.

K. ENSURE THAT ALL GROUNDING AND BONDING IS COMPLETE. TWO SCREW BONDING LUGS NEED

TO BE INSTALLED TO BOND ALL METALLIC COMPONENTS OF THE RACK AND CABLE TRAY

SYSTEM, TO THE TELECOMMUNICATIONS SECONDARY BONDING BUSBAR.

L. AFTER CUT-OVER TO THE NEW CABLING, DEMOLISH ALL OLD DATA AND TELEPHONE CABLING

ALL THE WAY TO THE STATION END. ENSURE THAT ANY CABLES IN THE CEILING AREAS THAT

ARE FOR SYSTEMS OTHER THAN THE IT DATA AND TELEPHONE, ARE NOT DISTURBED. BLANK

OFF ANY UNUSED OLD DATA LOCATIONS. DEMOLISH ALL OLD PATCH PANELS AND ASSOCIATED

HARDWARE. ALL OTHER ANCILLARY RACK-MOUNTED EQUIPMENT, NOT RELATED TO IT DATA

AND TELEPHONE, TO BE RELOCATED TO A NEW RACK BY OIT PERSONNEL. FIRE-STOP ALL

EXISTING SLEEVES WHERE CABLING WAS REMOVED.

M. AFTER CUT-OVER, REMOVE ALL OLD IT FIBER OPTIC CABLING FROM THE TR ALL THE WAY BACK

TO THE SERVER DEMOLISH ALL ASSOCIATED HARDWARE AND TERMINATION EQUIPMENT.

ENSURE THAT ANY CABLING IN THE CEILING AREA THAT IS FOR OTHER SYSTEMS, IS NOT

DISTURBED.

N. ALL CATEGORY 6A STATION CABLING SHALL BE SUPPORTED USING A COMBINATION OF J-HOOKS

AND CABLE TRAYS (IF POSSIBLE) IN GENERAL PATHWAYS.

O. FIBER OPTIC BACKBONE CABLE TO BE FACTORY TERMINATED IN MCR. FIBER OPTIC BACKBONE CABLE TO BE FIELD TERMINATED IN TRs.

TECHNOLOGY LEGEND

WALL PHONE OUTLET CONTAINING (1) CATEGORY 6A UTP CABLE TERMINATED ONTO (1)

CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLOR TO BE BLUE.

TERMINATION SCHEME TO BE T568B.

WIRELESS ACCESS POINT CONTAINING (2) CATEGORY 6A UTP, GREEN, CABLE TERMINATED

ONTO (1) CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLOR TO BE BLUE.

TERMINATION SCHEME TO BE T568B.

4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (2) CATEGORY 6A UTP CABLES

TERMINATED ONTO (2) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR

TO BE BLUE. TERMINATION SCHEME TO BE T568B.

4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (3) CATEGORY 6A UTP CABLES

TERMINATED ONTO (3) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR

TO BE BLUE. TERMINATION SCHEME TO BE T568B.

4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (4) CATEGORY 6A UTP CABLES

TERMINATED ONTO (4) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR

TO BE BLUE. TERMINATION SCHEME TO BE T568B.

DMARC PATHWAY 'A'

DMARC PATHWAY 'B'

FIBER OPTIC BACKBONE PATHWAY 'A', INSIDE BLDGS.

FIBER OPTIC BACKBONE PATHWAY 'B', INSIDE BLDGS.

FIBER OPTIC BACKBONE PATHWAY 'A', OUTSIDE BLDGS.

FIBER OPTIC BACKBONE PATHWAY 'B', OUTSIDE BLDGS.

WAP

W

TECHNOLOGY KEYNOTES

VERIFY OR INSTALL HORIZONTAL PATHWAYS, BASKET TRAY (12" W, 4" H) ABOVE DROP CEILING

ALONG HALLWAY. INSTALL J-HOOKS IN AREAS WHERE BASKET TRAY IS INAPPROPRIATE.

INBOUND REDUNDANT FIBER BACKBONE 'A' CABLES FROM MDA-A IN SR/DC/MCR. INCLUDES (1)

24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLE FIELD TERMINATED WITH LC TYPE

CONNECTORS ON TR END & FACTORY PRE-TERMINATED ON MDA-A SIDE.

INBOUND REDUNDANT FIBER BACKBONE 'B' CABLES FROM MDA-B IN SR/DC/MCR. INCLUDES (1)

24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLE FIELD TERMINATED WITH LC TYPE

CONNECTORS ON TR END & FACTORY PRE-TERMINATED ON MDA-B SIDE.

N

1/16" = 1'-0"

BLDG 2 - LEVEL 11

N

1/16" = 1'-0"

BLDG 2 - LEVEL 22

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

CONSULTANTS:

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. BR 2171 EXP. 09/30/2023

ENGR REG. NO. F-17591 EXP. 02/29/2024

STAMP:

Drawing Number

Building Number

/3

/2

5:

:3

PM

BONHAM VA MEDICAL CENTER

1201 E. 9TH STREET

BONHAM, TX 75418

SPUR #:No. REVISION DESCRIPTION DATE

Of

BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C O

N

TR

O

LL

ED

U

N C

LA

SS

IF

IE

D

IN

FO

R

M

AT

IO

N

(C U

I)

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC ENGINEER

SPUR DESIGN

2519 MADISON AVE., STE. 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

RATED ENGINEERING

609 S. KELLY AVENUE, SUITE H2

EDMOND, OK 73003

(405) 856-2965

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TECH ENGINEER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

STRUCT ENGINEER

STAND STRUCTURAL ENGINEERING

8234 ROBINSON STREET

OVERLAND PARK, KS 66204

(913) 214-2169

COMMISSIONING

ES2

13401 N. SANTA FE AVE

OKLAHOMA CITY, OK 73114

(405) 528-4500

549A4-21-700BONHAM EHRM

INFRASTRUCTURE

UPGRADES

100% BID DOCUMENTS

07/07/2023 229

T-102

BUILDING 2 - TELECOM PLANS

T-303

T-303

T-303

T-303

VERTICAL FIBER

OPTIC PATHWAY "B"

TO BLDG 2 - LVL 4

VERTICAL FIBER

OPTIC PATHWAY "A"

TO BLDG 2 - LVL 4

CLOSET

128 SF / 100 SF

NEW TR

301A

CORRIDOR

CLOSET

301B

210 WAOs

T-303

T-304

T-303

T-304

VERTICAL FIBER

OPTIC PATHWAY "B"

VERTICAL FIBER

OPTIC PATHWAY "A"

CLOSET

132 SF / 100 SF

NEW TR

401A

CLOSET

401B

CORRIDOR

181 WAOs

TECHNOLOGY GENERAL NOTES

A. CONTRACTOR SHALL INCLUDE AN ADDITIONAL 10% OF CABLE DROPS IN THEIR BID FOR ADDS

FOUND DURING INSTALLATION.

B. ADDITIONAL PATCH PANEL CAPACITY SHALL BE PROVIDED TO ACCOUNT FOR 15% GROWTH OF

ADDITIONAL CABLE DROPS.

C. ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN IN PLACE AND OPERATIONAL UNTIL

FINAL CUT-OVER TO THE NEW CABLING.

D. EACH NEW WORK AREA OUTLET (WAO) LOCATION WILL CONSIST OF THE QUANTITY OF CAT6A CABLES AS DEPICTED ON THE PLANS. EACH CABLE WILL BE TERMINATED ON A 48-PORT CAT6A

PATCH PANEL IN IT'S DESIGNATED TR.

E. EXISTING WAO LOCATIONS SHALL BE RE-USED WHEREVER POSSIBLE.

F. LABEL FIBER CABLE GOING INTO EACH FIBER PATCH PANEL. ALL FIBER STRANDS WILL BE

TESTED UTILIZING AN OLTS AND AN OTDR PER THE TIER 2 STANDARD.

G. PROVIDE (1) EACH SMALL DIAMETER CAT6A PATCH CORD FOR EACH NEW DATA PORT. PROVIDE

VARIOUS LENGTHS AS REQUIRED FOR A NEAT AND ORDERLY INSTALLATION, UTILIZING THE

VERTICAL AND HORIZONTAL WIRE MANAGERS AS APPLICABLE. (SEE SPECIFICATIONS)

H. NEW FIRE-RATED SLEEVES SHALL BE INSTALLED LEAVING THE TR AND IN ALL FIRE-RATED

WALLS ALONG THE CABLE PATHWAYS.

I. EXISTING CONDUITS TO REMAIN.

J. EXISTING DATA RACK/RACKS TO REMAIN UNTIL AFTER CUT-OVER.

K. ENSURE THAT ALL GROUNDING AND BONDING IS COMPLETE. TWO SCREW BONDING LUGS NEED

TO BE INSTALLED TO BOND ALL METALLIC COMPONENTS OF THE RACK AND CABLE TRAY

SYSTEM, TO THE TELECOMMUNICATIONS SECONDARY BONDING BUSBAR.

L. AFTER CUT-OVER TO THE NEW CABLING, DEMOLISH ALL OLD DATA AND TELEPHONE CABLING

ALL THE WAY TO THE STATION END. ENSURE THAT ANY CABLES IN THE CEILING AREAS THAT

ARE FOR SYSTEMS OTHER THAN THE IT DATA AND TELEPHONE, ARE NOT DISTURBED. BLANK

OFF ANY UNUSED OLD DATA LOCATIONS. DEMOLISH ALL OLD PATCH PANELS AND ASSOCIATED

HARDWARE. ALL OTHER ANCILLARY RACK-MOUNTED EQUIPMENT, NOT RELATED TO IT DATA

AND TELEPHONE, TO BE RELOCATED TO A NEW RACK BY OIT PERSONNEL. FIRE-STOP ALL

EXISTING SLEEVES WHERE CABLING WAS REMOVED.

M. AFTER CUT-OVER, REMOVE ALL OLD IT FIBER OPTIC CABLING FROM THE TR ALL THE WAY BACK

TO THE SERVER DEMOLISH ALL ASSOCIATED HARDWARE AND TERMINATION EQUIPMENT.

ENSURE THAT ANY CABLING IN THE CEILING AREA THAT IS FOR OTHER SYSTEMS, IS NOT

DISTURBED.

N. ALL CATEGORY 6A STATION CABLING SHALL BE SUPPORTED USING A COMBINATION OF J-HOOKS

AND CABLE TRAYS (IF POSSIBLE) IN GENERAL PATHWAYS.

O. FIBER OPTIC BACKBONE CABLE TO BE FACTORY TERMINATED IN MCR. FIBER OPTIC BACKBONE CABLE TO BE FIELD TERMINATED IN TRs.

TECHNOLOGY LEGEND

WALL PHONE OUTLET CONTAINING (1) CATEGORY 6A UTP CABLE TERMINATED ONTO (1)

CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLOR TO BE BLUE.

TERMINATION SCHEME TO BE T568B.

WIRELESS ACCESS POINT CONTAINING (2) CATEGORY 6A UTP, GREEN, CABLE TERMINATED

ONTO (1) CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLOR TO BE BLUE.

TERMINATION SCHEME TO BE T568B.

4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (2) CATEGORY 6A UTP CABLES

TERMINATED ONTO (2) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR

TO BE BLUE. TERMINATION SCHEME TO BE T568B.

4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (3) CATEGORY 6A UTP CABLES

TERMINATED ONTO (3) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR

TO BE BLUE. TERMINATION SCHEME TO BE T568B.

4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (4) CATEGORY 6A UTP CABLES

TERMINATED ONTO (4) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR

TO BE BLUE. TERMINATION SCHEME TO BE T568B.

DMARC PATHWAY 'A'

DMARC PATHWAY 'B'

FIBER OPTIC BACKBONE PATHWAY 'A', INSIDE BLDGS.

FIBER OPTIC BACKBONE PATHWAY 'B', INSIDE BLDGS.

FIBER OPTIC BACKBONE PATHWAY 'A', OUTSIDE BLDGS.

FIBER OPTIC BACKBONE PATHWAY 'B', OUTSIDE BLDGS.

WAP

W

TECHNOLOGY KEYNOTES

VERIFY OR INSTALL HORIZONTAL PATHWAYS, BASKET TRAY (12" W, 4" H) ABOVE DROP CEILING

ALONG HALLWAY. INSTALL J-HOOKS IN AREAS WHERE BASKET TRAY IS INAPPROPRIATE.

INBOUND REDUNDANT FIBER BACKBONE 'A' CABLES FROM MDA-A IN SR/DC/MCR. INCLUDES (1)

24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLE FIELD TERMINATED WITH LC TYPE

CONNECTORS ON TR END & FACTORY PRE-TERMINATED ON MDA-A SIDE.

INBOUND REDUNDANT FIBER BACKBONE 'B' CABLES FROM MDA-B IN SR/DC/MCR. INCLUDES (1)

24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLE FIELD TERMINATED WITH LC TYPE

CONNECTORS ON TR END & FACTORY PRE-TERMINATED ON MDA-B SIDE.

N

1/16" = 1'-0"

BLDG 2 - LEVEL 31

N

1/16" = 1'-0"

BLDG 2 - LEVEL 42

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

CONSULTANTS:

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. BR 2171 EXP. 09/30/2023

ENGR REG. NO. F-17591 EXP. 02/29/2024

STAMP:

Drawing Number

Building Number

/3

/2

5:

:3

PM

BONHAM VA MEDICAL CENTER

1201 E. 9TH STREET

BONHAM, TX 75418

SPUR #:No. REVISION DESCRIPTION DATE

Of

BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C O

N

TR

O

LL

ED

U

N C

LA

SS

IF

IE

D

IN

FO

R

M

AT

IO

N

(C U

I)

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC ENGINEER

SPUR DESIGN

2519 MADISON AVE., STE. 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

RATED ENGINEERING

609 S. KELLY AVENUE, SUITE H2

EDMOND, OK 73003

(405) 856-2965

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TECH ENGINEER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

STRUCT ENGINEER

STAND STRUCTURAL ENGINEERING

8234 ROBINSON STREET

OVERLAND PARK, KS 66204

(913) 214-2169

COMMISSIONING

ES2

13401 N. SANTA FE AVE

OKLAHOMA CITY, OK 73114

(405) 528-4500

549A4-21-700BONHAM EHRM

INFRASTRUCTURE

UPGRADES

100% BID DOCUMENTS

07/07/2023 229

T-103

BUILDING 2 - TELECOM PLANS

153 SF / 100 SFOFFICE

T-304

T-304

WAP WAP

WAP

WAP WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

4 4

W

W

W

W

VERTICAL FIBER

OPTIC PATHWAY "B"

TO BLDG 3 - LVL 2

VERTICAL FIBER

OPTIC PATHWAY "A"

TO BLDG 3 - LVL 2

HORIZONTAL FIBER

OPTIC MIXED

PATHWAY ('A" & "B")

TO BLDG 24 - LVL 1

HORIZONTAL FIBER

OPTIC MIXED

PATHWAY ('A" & "B")

TO BLDG 2 - LVL 1 NEW TR

135B

135A

T-304

T-304

8 WAP

WAP

WAP

WAP

WAP

WAP

VERTICAL FIBER

OPTIC PATHWAY "B"

TO BLDG 4 - LVL 2

STORAGE

106A

VERTICAL FIBER

OPTIC PATHWAY "A"

TO BLDG 4 - LVL 2

T-304

T-304

WAP

WAP

WAP

WAP

WAP

WAP

W

W2 2

2 2

W

W

W

CARPENTRY

SHOP

107A

EX. COMM

NEW TE

107A

126 SF / 100 SF

T-305

T-305

WAP

WAP

WAP

WAP

3 3

NEW TR

T-304

T-304

WAP

WAP

WAPWAP

WAP 22

2 2

VERTICAL FIBER

OPTIC PATHWAY "B"

TO BLDG 4 - LVL 1

161 SF / 100 SF

NEW TR

VERTICAL FIBER

OPTIC PATHWAY "A"

TO BLDG 4 - LVL 1

T-304

T-304

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

W

W

VERTICAL FIBER

OPTIC PATHWAY "B"

FROM BLDG 3 - LVL 1

VERTICAL FIBER

OPTIC PATHWAY "A"

TO BLDG 3 - LVL 1

129 SF / 100 SF

NEW TR

201B

CLOSET

201C

T-305

47 SF

CLOSET

114F

T-305

TECHNOLOGY GENERAL NOTES

A. CONTRACTOR SHALL INCLUDE AN ADDITIONAL 10% OF CABLE DROPS IN THEIR BID FOR ADDS

FOUND DURING INSTALLATION.

B. ADDITIONAL PATCH PANEL CAPACITY SHALL BE PROVIDED TO ACCOUNT FOR 15% GROWTH OF

ADDITIONAL CABLE DROPS.

C. ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN IN PLACE AND OPERATIONAL UNTIL

FINAL CUT-OVER TO THE NEW CABLING.

D. EACH NEW WORK AREA OUTLET (WAO) LOCATION WILL CONSIST OF THE QUANTITY OF CAT6A CABLES AS DEPICTED ON THE PLANS. EACH CABLE WILL BE TERMINATED ON A 48-PORT CAT6A

PATCH PANEL IN IT'S DESIGNATED TR.

E. EXISTING WAO LOCATIONS SHALL BE RE-USED WHEREVER POSSIBLE.

F. LABEL FIBER CABLE GOING INTO EACH FIBER PATCH PANEL. ALL FIBER STRANDS WILL BE

TESTED UTILIZING AN OLTS AND AN OTDR PER THE TIER 2 STANDARD.

G. PROVIDE (1) EACH SMALL DIAMETER CAT6A PATCH CORD FOR EACH NEW DATA PORT. PROVIDE

VARIOUS LENGTHS AS REQUIRED FOR A NEAT AND ORDERLY INSTALLATION, UTILIZING THE

VERTICAL AND HORIZONTAL WIRE MANAGERS AS APPLICABLE. (SEE SPECIFICATIONS)

H. NEW FIRE-RATED SLEEVES SHALL BE INSTALLED LEAVING THE TR AND IN ALL FIRE-RATED

WALLS ALONG THE CABLE PATHWAYS.

I. EXISTING CONDUITS TO REMAIN.

J. EXISTING DATA RACK/RACKS TO REMAIN UNTIL AFTER CUT-OVER.

K. ENSURE THAT ALL GROUNDING AND BONDING IS COMPLETE. TWO SCREW BONDING LUGS NEED

TO BE INSTALLED TO BOND ALL METALLIC COMPONENTS OF THE RACK AND CABLE TRAY

SYSTEM, TO THE TELECOMMUNICATIONS SECONDARY BONDING BUSBAR.

L. AFTER CUT-OVER TO THE NEW CABLING, DEMOLISH ALL OLD DATA AND TELEPHONE CABLING

ALL THE WAY TO THE STATION END. ENSURE THAT ANY CABLES IN THE CEILING AREAS THAT

ARE FOR SYSTEMS OTHER THAN THE IT DATA AND TELEPHONE, ARE NOT DISTURBED. BLANK

OFF ANY UNUSED OLD DATA LOCATIONS. DEMOLISH ALL OLD PATCH PANELS AND ASSOCIATED

HARDWARE. ALL OTHER ANCILLARY RACK-MOUNTED EQUIPMENT, NOT RELATED TO IT DATA

AND TELEPHONE, TO BE RELOCATED TO A NEW RACK BY OIT PERSONNEL. FIRE-STOP ALL

EXISTING SLEEVES WHERE CABLING WAS REMOVED.

M. AFTER CUT-OVER, REMOVE ALL OLD IT FIBER OPTIC CABLING FROM THE TR ALL THE WAY BACK

TO THE SERVER DEMOLISH ALL ASSOCIATED HARDWARE AND TERMINATION EQUIPMENT.

ENSURE THAT ANY CABLING IN THE CEILING AREA THAT IS FOR OTHER SYSTEMS, IS NOT

DISTURBED.

N. ALL CATEGORY 6A STATION CABLING SHALL BE SUPPORTED USING A COMBINATION OF J-HOOKS

AND CABLE TRAYS (IF POSSIBLE) IN GENERAL PATHWAYS.

O. FIBER OPTIC BACKBONE CABLE TO BE FACTORY TERMINATED IN MCR. FIBER OPTIC BACKBONE CABLE TO BE FIELD TERMINATED IN TRs.

TECHNOLOGY LEGEND

WALL PHONE OUTLET CONTAINING (1) CATEGORY 6A UTP CABLE TERMINATED ONTO (1)

CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLOR TO BE BLUE.

TERMINATION SCHEME TO BE T568B.

WIRELESS ACCESS POINT CONTAINING (2) CATEGORY 6A UTP, GREEN, CABLE TERMINATED

ONTO (1) CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLOR TO BE BLUE.

TERMINATION SCHEME TO BE T568B.

4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (2) CATEGORY 6A UTP CABLES

TERMINATED ONTO (2) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR

TO BE BLUE. TERMINATION SCHEME TO BE T568B.

4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (3) CATEGORY 6A UTP CABLES

TERMINATED ONTO (3) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR

TO BE BLUE. TERMINATION SCHEME TO BE T568B.

4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (4) CATEGORY 6A UTP CABLES

TERMINATED ONTO (4) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR

TO BE BLUE. TERMINATION SCHEME TO BE T568B.

DMARC PATHWAY 'A'

DMARC PATHWAY 'B'

FIBER OPTIC BACKBONE PATHWAY 'A', INSIDE BLDGS.

FIBER OPTIC BACKBONE PATHWAY 'B', INSIDE BLDGS.

FIBER OPTIC BACKBONE PATHWAY 'A', OUTSIDE BLDGS.

FIBER OPTIC BACKBONE PATHWAY 'B', OUTSIDE BLDGS.

WAP

W

TECHNOLOGY KEYNOTES

VERIFY OR INSTALL HORIZONTAL PATHWAYS, BASKET TRAY (12" W, 4" H) ABOVE DROP CEILING

ALONG HALLWAY. INSTALL J-HOOKS IN AREAS WHERE BASKET TRAY IS INAPPROPRIATE.

INBOUND REDUNDANT FIBER BACKBONE 'A' CABLES FROM MDA-A IN SR/DC/MCR. INCLUDES (1)

24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLE FIELD TERMINATED WITH LC TYPE

CONNECTORS ON TR END & FACTORY PRE-TERMINATED ON MDA-A SIDE.

INBOUND REDUNDANT FIBER BACKBONE 'B' CABLES FROM MDA-B IN SR/DC/MCR. INCLUDES (1)

24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLE FIELD TERMINATED WITH LC TYPE

CONNECTORS ON TR END & FACTORY PRE-TERMINATED ON MDA-B SIDE.

N

1/16" = 1'-0"

BLDG 3 - LEVEL 11

N

1/16" = 1'-0"

BLDG 4 - LEVEL 13

N

1/16" = 1'-0"

BLDG 8 - LEVEL 15

N

1/16" = 1'-0"

BLDG 9 - LEVEL 16

N

1/16" = 1'-0"

BLDG 4 - LEVEL 24

N

1/16" = 1'-0"

BLDG 3 - LEVEL 22

N

1/16" = 1'-0"

BLDG 9 - LEVEL 27

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

CONSULTANTS:

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. BR 2171 EXP. 09/30/2023

ENGR REG. NO. F-17591 EXP. 02/29/2024

STAMP:

Drawing Number

Building Number

/3

/2

5:

:3

PM

BONHAM VA MEDICAL CENTER

1201 E. 9TH STREET

BONHAM, TX 75418

SPUR #:No. REVISION DESCRIPTION DATE

Of

BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C O

N

TR

O

LL

ED

U

N C

LA

SS

IF

IE

D

IN

FO

R

M

AT

IO

N

(C U

I)

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC ENGINEER

SPUR DESIGN

2519 MADISON AVE., STE. 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

RATED ENGINEERING

609 S. KELLY AVENUE, SUITE H2

EDMOND, OK 73003

(405) 856-2965

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TECH ENGINEER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

STRUCT ENGINEER

STAND STRUCTURAL ENGINEERING

8234 ROBINSON STREET

OVERLAND PARK, KS 66204

(913) 214-2169

COMMISSIONING

ES2

13401 N. SANTA FE AVE

OKLAHOMA CITY, OK 73114

(405) 528-4500

549A4-21-700BONHAM EHRM

INFRASTRUCTURE

UPGRADES

100% BID DOCUMENTS

07/07/2023 229

T-104

BUILDING 3, 4, 8 & 9 - TELECOM PLANS

3, 4, 8 & 9

127 SF

NEW TR

EX.

T-305

T-305

T-305

T-305

WAPWAP

WAP

WAP

WAP

WAP

WAP WAP

WAP

3 3

4 44

3 3

W

3 3

CLOSET

105A

RESTROOM

HORIZONTAL FIBER OPTIC

MIXED PATHWAY ('A' & 'B')

BETWEEN BLDG 10 - LVL 1.

& BLDG 29 - LVL 1.

HORIZONTAL FIBER OPTIC

MIXED PATHWAY ('A' & 'B')

BETWEEN BLDG 10 - LVL 1.

& BLDG 9 - LVL 1.

2 3

W

W

2 WAP

T-305

T-305

112 SF

NEW TR

T-305

T-305 13 14

2 2 2 2

WAPWAP

VERTICAL FIBER

OPTIC PATHWAY "B"

TO BLDG 12 - LVL 1

VERTICAL FIBER

OPTIC PATHWAY "A"

TO BLDG 12 - LVL 1

CLOSET

WAP

WAP

WAPWAPWAP

4 4 4

VERTICAL FIBER

OPTIC PATHWAY "B"

TO BLDG 12 - LVL 2

VERTICAL FIBER

OPTIC PATHWAY "A"

TO BLDG 12 - LVL 2

TECHNOLOGY GENERAL NOTES

A. CONTRACTOR SHALL INCLUDE AN ADDITIONAL 10% OF CABLE DROPS IN THEIR BID FOR ADDS

FOUND DURING INSTALLATION.

B. ADDITIONAL PATCH PANEL CAPACITY SHALL BE PROVIDED TO ACCOUNT FOR 15% GROWTH OF

ADDITIONAL CABLE DROPS.

C. ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN IN PLACE AND OPERATIONAL UNTIL

FINAL CUT-OVER TO THE NEW CABLING.

D. EACH NEW WORK AREA OUTLET (WAO) LOCATION WILL CONSIST OF THE QUANTITY OF CAT6A CABLES AS DEPICTED ON THE PLANS. EACH CABLE WILL BE TERMINATED ON A 48-PORT CAT6A

PATCH PANEL IN IT'S DESIGNATED TR.

E. EXISTING WAO LOCATIONS SHALL BE RE-USED WHEREVER POSSIBLE.

F. LABEL FIBER CABLE GOING INTO EACH FIBER PATCH PANEL. ALL FIBER STRANDS WILL BE

TESTED UTILIZING AN OLTS AND AN OTDR PER THE TIER 2 STANDARD.

G. PROVIDE (1) EACH SMALL DIAMETER CAT6A PATCH CORD FOR EACH NEW DATA PORT. PROVIDE

VARIOUS LENGTHS AS REQUIRED FOR A NEAT AND ORDERLY INSTALLATION, UTILIZING THE

VERTICAL AND HORIZONTAL WIRE MANAGERS AS APPLICABLE. (SEE SPECIFICATIONS)

H. NEW FIRE-RATED SLEEVES SHALL BE INSTALLED LEAVING THE TR AND IN ALL FIRE-RATED

WALLS ALONG THE CABLE PATHWAYS.

I. EXISTING CONDUITS TO REMAIN.

J. EXISTING DATA RACK/RACKS TO REMAIN UNTIL AFTER CUT-OVER.

K. ENSURE THAT ALL GROUNDING AND BONDING IS COMPLETE. TWO SCREW BONDING LUGS NEED

TO BE INSTALLED TO BOND ALL METALLIC COMPONENTS OF THE RACK AND CABLE TRAY

SYSTEM, TO THE TELECOMMUNICATIONS SECONDARY BONDING BUSBAR.

L. AFTER CUT-OVER TO THE NEW CABLING, DEMOLISH ALL OLD DATA AND TELEPHONE CABLING

ALL THE WAY TO THE STATION END. ENSURE THAT ANY CABLES IN THE CEILING AREAS THAT

ARE FOR SYSTEMS OTHER THAN THE IT DATA AND TELEPHONE, ARE NOT DISTURBED. BLANK

OFF ANY UNUSED OLD DATA LOCATIONS. DEMOLISH ALL OLD PATCH PANELS AND ASSOCIATED

HARDWARE. ALL OTHER ANCILLARY RACK-MOUNTED EQUIPMENT, NOT RELATED TO IT DATA

AND TELEPHONE, TO BE RELOCATED TO A NEW RACK BY OIT PERSONNEL. FIRE-STOP ALL

EXISTING SLEEVES WHERE CABLING WAS REMOVED.

M. AFTER CUT-OVER, REMOVE ALL OLD IT FIBER OPTIC CABLING FROM THE TR ALL THE WAY BACK

TO THE SERVER DEMOLISH ALL ASSOCIATED HARDWARE AND TERMINATION EQUIPMENT.

ENSURE THAT ANY CABLING IN THE CEILING AREA THAT IS FOR OTHER SYSTEMS, IS NOT

DISTURBED.

N. ALL CATEGORY 6A STATION CABLING SHALL BE SUPPORTED USING A COMBINATION OF J-HOOKS

AND CABLE TRAYS (IF POSSIBLE) IN GENERAL PATHWAYS.

O. FIBER OPTIC BACKBONE CABLE TO BE FACTORY TERMINATED IN MCR. FIBER OPTIC BACKBONE CABLE TO BE FIELD TERMINATED IN TRs.

TECHNOLOGY LEGEND

WALL PHONE OUTLET CONTAINING (1) CATEGORY 6A UTP CABLE TERMINATED ONTO (1)

CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLOR TO BE BLUE.

TERMINATION SCHEME TO BE T568B.

WIRELESS ACCESS POINT CONTAINING (2) CATEGORY 6A UTP, GREEN, CABLE TERMINATED

ONTO (1) CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLOR TO BE BLUE.

TERMINATION SCHEME TO BE T568B.

4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (2) CATEGORY 6A UTP CABLES

TERMINATED ONTO (2) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR

TO BE BLUE. TERMINATION SCHEME TO BE T568B.

4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (3) CATEGORY 6A UTP CABLES

TERMINATED ONTO (3) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR

TO BE BLUE. TERMINATION SCHEME TO BE T568B.

4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (4) CATEGORY 6A UTP CABLES

TERMINATED ONTO (4) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR

TO BE BLUE. TERMINATION SCHEME TO BE T568B.

DMARC PATHWAY 'A'

DMARC PATHWAY 'B'

FIBER OPTIC BACKBONE PATHWAY 'A', INSIDE BLDGS.

FIBER OPTIC BACKBONE PATHWAY 'B', INSIDE BLDGS.

FIBER OPTIC BACKBONE PATHWAY 'A', OUTSIDE BLDGS.

FIBER OPTIC BACKBONE PATHWAY 'B', OUTSIDE BLDGS.

WAP

W

TECHNOLOGY KEYNOTES

VERIFY OR INSTALL HORIZONTAL PATHWAYS, BASKET TRAY (12" W, 4" H) ABOVE DROP CEILING

ALONG HALLWAY. INSTALL J-HOOKS IN AREAS WHERE BASKET TRAY IS INAPPROPRIATE.

INBOUND REDUNDANT FIBER BACKBONE 'A' CABLES FROM MDA-A IN SR/DC/MCR. INCLUDES (1)

24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLE FIELD TERMINATED WITH LC TYPE

CONNECTORS ON TR END & FACTORY PRE-TERMINATED ON MDA-A SIDE.

INBOUND REDUNDANT FIBER BACKBONE 'B' CABLES FROM MDA-B IN SR/DC/MCR. INCLUDES (1)

24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLE FIELD TERMINATED WITH LC TYPE

CONNECTORS ON TR END & FACTORY PRE-TERMINATED ON MDA-B SIDE.

N

1/16" = 1'-0"

BLDG 10 - LEVEL 11

N

1/16" = 1'-0"

BLDG 11 - LEVEL 12

N

1/16" = 1'-0"

BLDG 12 - LEVEL 24

N

1/16" = 1'-0"

BLDG 34 - LEVEL 15

N

1/16" = 1'-0"

BLDG 12 - LEVEL 13

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

CONSULTANTS:

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. BR 2171 EXP. 09/30/2023

ENGR REG. NO. F-17591 EXP. 02/29/2024

STAMP:

Drawing Number

Building Number

/3

/2

5:

:3

PM

BONHAM VA MEDICAL CENTER

1201 E. 9TH STREET

BONHAM, TX 75418

SPUR #:No. REVISION DESCRIPTION DATE

Of

BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C O

N

TR

O

LL

ED

U

N C

LA

SS

IF

IE

D

IN

FO

R

M

AT

IO

N

(C U

I)

CIVIL ENGINEER

OLSSON

550 ST LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC ENGINEER

SPUR DESIGN

2519 MADISON AVE., STE. 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

RATED ENGINEERING

609 S. KELLY AVENUE, SUITE H2

EDMOND, OK 73003

(405) 856-2965

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

TECH ENGINEER

ASPEN COMMUNICATIONS, LLC

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

STRUCT ENGINEER

STAND STRUCTURAL ENGINEERING

8234 ROBINSON STREET

OVERLAND PARK, KS 66204

(913) 214-2169

COMMISSIONING

ES2

13401 N. SANTA FE AVE

OKL…