This document contains security drawings and specifications for a federal construction project. The project involves building improvements at the Department of Veterans Affairs medical center in Bonham, Texas, including installation of security, electrical, telecommunications, and low-voltage systems. Key details of the project include requirements for access control, intrusion detection, video surveillance, radio communications, fire alarm, and networking equipment to be installed throughout the facility in accordance with VA and industry standards. Telecommunications rooms must be equipped with cable pathways, grounding infrastructure and terminals to support voice and data cabling as indicated.
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ELECTRICAL:
(AFF / AFG UNLESS
NOTED OTHERWISE)
84" 48" 48" 84" 48" 80" 60"
120" 60" 36" 48" 72" 48"
144" 18" 24" 26" 48" 48"
CEILING
48" 48" 18" 84"
AUDIBLE APPLIANCES (CENTERLINE)
ALARMS
ANNUNCIATOR PANELS
CLOCK OUTLETS (CENTERLINE)
CONTROLS (TOP)
EXIT SIGNS (WALL-MOUNTED, BOTTOM)
FIRE ALARM ANNUNCIATOR PANEL (DISPLAY)
FIRE ALARM BELL (EXTERIOR)
FIRE ALARM CONTROL PANEL / UNIT (DISPLAY)
INTERCOM (AREA ONLY)
INTERCOM (TOP)
PANELS & PANELBOARDS (TOP)
PULL STATION (HANDLE)
PHOTOCELLS
RECEPTACLES (BOTTOM)
RECEPTACLES (EXTERIOR)
RECEPTACLES (GARAGES)
RECEPTACLES IN EQUIPMENT ROOMS (TOP)
REMOTE INDICATING LIGHT (EQUIPMENT ROOMS)
REMOTE INDICATING LIGHT (FINISHED AREAS)
SAFETY SWITCHES & STARTERS
SWITCHES (TOP)
TELEPHONE/DATA/TV OUTLETS (BOTTOM)
VISIBLE APPLIANCES (CENTERLINE)
SECURITY SYMBOLS
DOOR AUTO-CLOSER
PANIC / DURESS BUTTON MOUNTED AT 48" A.F.F.
UNLESS NOTED OTHERWISE
ACCESS CONTROL CARD READER/KEYPAD
COMBINATION DEVICE
POSITION SWITCH
ELECTRIFIED LOCKING DEVICE, LATCH BOLT
MONITOR, AND DOOR POSITION SWITCH
ELECTRIFIED LOCKING DEVICE
INTRUSION DETECTION PASSIVE INFRARED MOTION
DETECTOR - WALL MOUNTED
DOOR AUTO-OPENER
ANTI-PROP DEVICE
REQUEST FOR EXIT/MOTION SENSOR
DOOR BELL PUSHBUTTON
DOOR CONTACT SWITCH - WIRED TO ACCESS
CONTROL SYSTEM ONLY UNLESS OTHERWISE
NOTED
DELAYED EGRESS
GLASS BREAK DETECTOR
GATE OPENER
INTRUSION DETECTION SYSTEM KEYPAD
RFID KEY TAG READER
MAGNETIC LOCKING DEVICE
SINGLE VIEW SECURITY CAMERA
DUAL VIEW SECURITY CAMERA
180-DEGREE PANORAMIC VIEW SECURITY CAMERA
270-DEGREE PANORAMIC/MULTI-IMAGE VIEW
SECURITY CAMERA
360-DEGREE PANORAMIC/MULTI-IMAGE VIEW
SECURITY CAMERA
SECURITY SURVEILLANCE TELEVISION LINE, MIN. 1"
RACEWAY
DESK MOUNTED RADIO PHONE
RECESSED WALL MOUNTED RADIO PHONE
MOUNTED AT 48" A.F.F. UNLESS NOTED OTHERWISE
SURFACE WALL MOUNTED RADIO PHONE MOUNTED
AT 48" A.F.F. UNLESS NOTED OTHERWISE
VIDEO SURVEILLANCE MONITOR STATION
ELECTRIC POWER TRANSFER
ELECTRIC LATCH RELEASE
AC
AD
AP
CR
RE
DB
DC
DE
DM
EL
EO
GB
GO
KP
KT
MD
ML
PB
SSTV
DR
RR
WR
M
EPT
ELR
DESCRIPTIONSYMBOL
ABBREVIATIONS
EIGHT POSITION, EIGHT CONTACT
ALARM ANNUNCIATOR PANEL
ABOVE FINISHED GRADE
ABOVE FINISHED FLOOR
AUTHORITY HAVING JURISDICTION
THE AMERICAN NATIONAL STANDARDS INSTITUTE
ARCHITECT
BATTERY
BOTTOM OF CABLE TRAY
BUILDING INDUSTRY CONSULTING SERVICE
INTERNATIONAL
8P8C
A
AAP
AFG
AFF
AHJ
ANSI
ARCH
B
BATT
BOCT
BICSI
CONDUIT
COMMUNITY ANTENNA TELEVISION
CLOSED CIRCUIT TELEVISION
CEILING
CEILING MOUNTED
COMPUTER MACHINE ROOM
COAXIAL CABLE
C
C
CATV
CCTV
CLG
CM
CMR
COAX
COMMUNICATIONCOMM
CONTINUE/ CONTINUOUSCONT
CENTERCTR
COPPERCU
D
DECIBEL OR DIRECT BURIALDB
DIRECT CURRENTDC
DEMOLISH/ DEMOLITIONDEMO
DIAMETERDIA
DIMENSIONDIM
DOME LIGHTDL
DRAWINGDWG
E
EACHEA
EXTRA HAZARDEH
ELEVATIONEL
ELEVATORELEV
EMERGENCYEMER
ELECTROMAGNETIC INTERFERENCEEMI
ELECTRICAL METALLIC TUBINGEMT
EQUIPMENTEQUIP
EQUIPMENTEQPM
EXISTING TO REMAINETR
EXISTINGEX
F
FIRE ALARMFA
FINISHED FLOOR ELEVATIONFFE
FLEXIBLE METALLIC CONDUITFLEX
FLOORFLR
FEETFT
FIBER-OPTICFO
G
GAUGEGA
GENERAL CONTRACTORGC
GROUNDGND
H
HORIZONTAL CABLE MANAGERHCM
HEIGHTHGT
HANDHOLEHH
HERTZHZ
I
INSIDE DIAMETERID
INTERMEDIATE DISTRIBUTION FRAMEIDF
INFRAREDIR
J
JUNCTION BOXJB
K
KILOWATTKW
L
LIGHT EMITTING DIODE
LINEAR FEET (FOOT)
LIGHT HAZARD
LOCAL OPERATING CONSOLE
LED
LF
LH
LOC
LOW VOLTAGELV
M
MASTER ANTENNA TELEVISION SYSTEMMATV
MAXIMUMMAX
METAL-CLADMC
MAIN DISTRIBUTION FRAMEMDF
MANHOLEMH
MINIMUMMIN
MOUNTEDMTD
MOUNTINGMTG
N
NOT APPLICABLENA
NATIONAL ELECTRICAL CODENEC
NATIONAL ELECTRICAL MANUFACTURERS
ASSOCIATION
NEMA
NATIONAL FIRE PROTECTION ASSOCIATIONNFPA
NOT IN CONTRACTNIC
NOT TO SCALENTS
O
ON CENTEROC
OUTSIDE DIAMETEROD
ORDINARY HAZARDOH
P
PUBLIC ADDRESSPA
PULL CORDPC
POWER OVER ETHERNETPOE
PATCH PANELPP
POWERPWR
R
RCDD
REGISTERED COMMUNICATIONS DISTRIBUTION
DESIGNER
REFLECTED CEILING PLANRCP
RECEPTACLERCPT
RECESSEDREC
REQUIREDREQD
RIGID GALVANIZED STEELRGS
ROOMRM
ROOT MEAN SQUARERMS
RACK UNITRU
S
SUPPLYS
SCHEDULESCHED
SMOKE DETECTORSD
SIMILARSIM
SPEAKERSP
SPECIFICATIONSPEC
SPEAKER/ STROBESP/ST
SQUARESQ
STROBEST
SHIELDED TWISTED PAIRSTP
SURFACESURF
SYSTEMSYST
T
TELECOMMUNICATIONS ENCLOSURETE
TELECOMMUNICATIONS ENCLOSURE FACILITYTEF
TELEPHONETEL
TEMPERATURETEMP
TELECOMMUNICATIONS EQUIPMENT ROOMTER
TELECOMMUNICATIONS GROUNDING BUSSBARTGB
TIA TELECOMMUNICATIONS INDUSTRY ASSOCIATION
TMGB TELECOMMUNICATIONS MAIN GROUNDING BUSSBAR
TR TELECOMMUNICATIONS ROOM
TP TWISTED PAIR
TTB TELEPHONE TERMINAL BOARD
TYP TYPICAL
U
UNDERFLOOR DUCTUFD
UNDERGROUNDUGND
UNDERWRITERS LABORATORYUL
UNLESS NOTED OTHERWISEUNO
UNINTERRUPTIBLE POWER SUPPLYUPS
UTILITYUTIL
V
VERTICAL CABLE MANAGERVCM
W
WITHW/
WALL MOUNTEDWM
WITHOUTW/O
X
EXPLOSION PROOFXP
STANDARD MOUNTING HEIGHTS
PROJECT CODES AND STANDARDS
A. IBC 2015 – INTERNATIONAL BUILDING CODE
B. IEBC 2015 – INTERNATIONAL EXISTING BUILDING CODE
C. NFPA 70-2020 - NATIONAL ELECTRICAL CODE (NEC)
D. NFPA 99-2021 – HEALTH CARE FACILITIES CODE
E. NFPA 101-2021 – LIFE SAFETY CODE
F. VA PG-18-10 ELECTRICAL DESIGN MANUAL, DECEMBER 2019
G. VA PG-18-10 FIRE PROTECTION DESIGN MANUAL, JUNE 2021
H. VA PHYSICAL SECURITY & RESILIENCY DESIGN MANUAL,
(PSRDM) – JUNE 1, 2023 REVISION
I. VA OFFICE OF INFORMATION & TECHNOLOGY (OIT) DESIGN GUIDE,
FEBRUARY 2011
J. VA OFFICE OF INFORMATION & TECHNOLOGY (OIT)
INFRASTRUCTURE STANDARDS FOR TELECOMMUNICATIONS
SPACES, JUNE 1 2023
K. INFRASTRUCTURE STANDARDS FOR TELECOMMUNICATIONS
SPACES, AUGUST 2020
L. VA PG-18-10 TELECOMMUNICATIONS AND SPECIAL
TELECOMMUNICATIONS SYSTEMS DESIGN MANUAL, FEBRUARY
M. BICSI AND EIA/TIA STANDARDS AS DEFINED IN VA-18-10
GENERAL NOTES
1. DRAWING IS DIAGRAMMATIC IN NATURE AND IS NOT TO BE
CONSTRUED AS ALL INCLUSIVE; FIELD VERIFY EXISTING
CONDITIONS AND ADJUST WORK AS REQUIRED TO EXECUTE
SPECIFIED WORK.
2. FINAL LOCATION OF ALL DEVICES SHALL BE COORDINATED WITH
FINAL ROOM FURNITURE CONFIGURATIONS, ACCESSORIES,
SPACE INDICATED FOR SPECIFIC DUTY.
3. ALL ICT OUTLETS WITHIN OCCUPIED SPACES SHALL BE LOCATED
WITHIN 18" MAXIMUM FROM AN ELECTRICAL OUTLET; EXCEPTION:
ICT OUTLETS INDICATED FOR SPECIFIC DUTY.
4. ELECTRICAL OUTLETS INDICATED FOR REFERENCE PURPOSES
ONLY; REFER TO ELECTRICAL PLANS FOR ELECTRICAL
REQUIREMENTS.
5. ALL LOCATIONS OF CATV CABLE, TERMINATION AND COMMON
EQUIPMENT TO BE COORDINATED WITH CATV SERVICES
PROVIDER PRIOR TO INSTALLATION.
6. ALL CABLING SHALL BE ROUTED TO AND TERMINATED IN THE
TELECOMMUNICATIONS ROOM.
7. FILL CAPACITIES: CATEGORY FILL CAPACITIES SHALL BE BASED
ON AN O.D. OF .25" OR AN AREA OF .04909 SQ. IN./CABLE;
MAINTAIN A MINIMUM 25% SPARE CAPACITY IN ALL PATHWAYS;
CONDUIT FILL CAPACITIES MAXIMUM FILL = 30%; NON-
CONTINUOUS (J-HOOK) AND CONTINUOUS (CABLE TRAY)
SUPPORTS MAXIMUM FILL = 35.5% FILL (INCLUDING SPARE
CAPACITIES); SLEEVES <24" IN LENGTH MAXIMUM FILL = 75%; IF
CABLE IS PROVIDED WITH LARGER O.D. ADJUST PATHWAYS
ACCORDINGLY, ROUNDED UP TO THE NEXT TRADE SIZE.
8. ALL CABLING SHALL HAVE A MINIMUM 10' SERVICE-LOOP AT THE
COMMUNICATION ROOM.
9. ALL CABLING SHALL HAVE A MINIMUM 3' SERVICE LOOP AT THE
OUTLET OR DEVICE.
10. MOUNTING HEIGHTS FOR DEVICES SHALL BE MEASURED FROM
FINAL FINISH FLOOR TO CENTER OF BOX.
11. VERIFY MOUNTING HEIGHT OF ALL COMMUNICATIONS DEVICES
WITH ARCHITECTURAL ELEVATIONS PRIOR TO ROUGH-IN. WHERE
CONFLICTS EXIST, CONTRACTOR SHALL NOTIFY ENGINEER AND
ARCHITECT FOR RESOLUTION.
12. VERIFY THE LOCATIONS OF ALL FIREPROOFING PRIOR TO THE
INSTALLATION OF CONDUIT AND BACKBOXES.
13. IF FIELD CONDITIONS VARY FROM THE DRAWINGS, THE
CONTRACTOR SHALL DOCUMENT THE VARIATION AND REPORT IT
TO THE GENERAL CONTRACTOR FOR RESOLUTION WITH THE
ENGINEER OF RECORD.
14. COORDINATE THE INSTALLATION REQUIREMENTS OF SYSTEM
DEVICES, EQUIPMENT, PATHWAYS, AND OTHER COMPONENTS
WITH THE GENERAL CONTRACTOR AND OTHER BUILDING TRADES
PRIOR TO INSTALLATION.
15. COORDINATE GROUNDING REQUIREMENTS WITH THE
ELECTRICAL CONTRACTOR AND ENSURE THE COMMUNICATIONS
GROUNDING MEETS SYSTEM REQUIREMENTS AND TIA J-STD-607A
STANDARDS PRIOR TO ENERGIZING AND SYSTEMS EQUIPMENT.
16. THIS SITE IS AN ACTIVE WORKING ENVIRONMENT; SYSTEMS
SHALL NOT BE SHUTDOWN WITHOUT WRITTEN AUTHORIZATION;
ALL REQUESTS SHALL BE SUBMITTED IN WRITING A MINIMUM OF
TEN (10) WORKING-DAYS PRIOR TO PROPOSED ACTIVITY DATE OR
NEED UNLESS DIRECTED OTHERWISE.
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
CONSULTANTS:
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC ENGINEER
SPUR DESIGN
2519 MADISON AVE., STE. 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
RATED ENGINEERING
609 S. KELLY AVENUE, SUITE H2
EDMOND, OK 73003
(405) 856-2965
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TECH ENGINEER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STRUCT ENGINEER
STAND STRUCTURAL ENGINEERING
8234 ROBINSON STREET
OVERLAND PARK, KS 66204
(913) 214-2169
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. BR 2171 EXP. 09/30/2023
ENGR REG. NO. F-17591 EXP. 02/29/2024
STAMP:
Drawing Number
Building Number
BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.
COMMISSIONING
ES2
13401 N. SANTA FE AVE
OKLAHOMA CITY, OK 73114
(405) 528-4500
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
C O
N T
R O
L L E
D U
N C
L A
S S
IF
IE
D I
N F
O R
M A
T
IO
N
C U
I)
/2
/2
:3 :1
A
M
100% BID DOCUMENTS
ABBREVIATIONS, SYMBOLS, LEGENDS,
& NOTES
JPH 210 OF 229KGH
BONHAM EHRM
INFRASTRUCTURE
UPGRADES
07/07/2023
549A4-21-700
BONHAM VA MEDICAL CENTER
1201 E. 9TH STREET
BONHAM, TX 75418
TY000
SPUR #: 2216No. REVISION DESCRIPTION DATE
TY401
TY401
TY401
TY401
A. DRAWING IS DIAGRAMMATIC IN NATURE AND IS NOT TO BE CONSTRUED
AS ALL INCLUSIVE; FIELD VERIFY EXISTING CONDITIONS AND ADJUST
WORK AS REQUIRED TO EXECUTE SPECIFIED WORK.
B. ELECTRICAL OUTLET/ DEVICES INDICATED ARE FOR COORDINATION &
REFERENCE PURPOSES; REFER TO ELECTRICAL, E-SERIES DRAWINGS
FOR ELECTRICAL WORK REQUIREMENTS AND SPECIFICATIONS.
C. THIS SITE IS AN ACTIVE WORKING ENVIRONMENT; SYSTEMS SHALL NOT
BE SHUTDOWN WITHOUT WRITTEN AUTHORIZATION; ALL REQUESTS
SHALL BE SUBMITTED IN WRITING A MINIMUM OF SEVEN (7) WORKING-
DAYS PRIOR TO PROPOSED ACTIVITY DATE OR NEED UNLESS DIRECTED
OTHERWISE.
D. SEE TY000 ABBREVIATIONS, SYMBOLS, LEGENDS, & NOTES FOR
SYMBOLS DEFINITION:
1. SYMBOLS GRAYED/ HALFTONE: INDICATED FOR REFERENCE
AND/OR INDICATING EXISTING UNLESS SPECIFICALLY NOTED
OTHERWISE.
2. SYMBOLS DASHED OR SPECIFICALLY KEYED NOTED: INDICATES
DEMOLITION WORK.
F. COORDINATE WORK AND PHASING SCHEDULE WITH THE
CONTRACTING OFFICER'S REPRESENTATIVE.
G. CONTRACTOR TO COORDINATE CABLE COLORS WITH THE VA
PRIOR TO PURCHASING AND INSTALLATION. GREEN CABLING FOR CAT6A
DATA, WHITE FOR TELEPHONE VOICE.
H. ALL CATEGORY-6A STATION CABLING SHALL BE SUPPORTED
USING A COMBINATION OF CONDUITS ALONG CABLE PATHWAY TO
NEW MCR.
I. COORDINATE SECURITY WORK WITH ALL OTHER TRADES. VERIFY ALL
EXISTING CONDITIONS BEFORE THE START OF WORK.
GENERAL NOTES
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
CONSULTANTS:
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC ENGINEER
SPUR DESIGN
2519 MADISON AVE., STE. 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
RATED ENGINEERING
609 S. KELLY AVENUE, SUITE H2
EDMOND, OK 73003
(405) 856-2965
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TECH ENGINEER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STRUCT ENGINEER
STAND STRUCTURAL ENGINEERING
8234 ROBINSON STREET
OVERLAND PARK, KS 66204
(913) 214-2169
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. BR 2171 EXP. 09/30/2023
ENGR REG. NO. F-17591 EXP. 02/29/2024
STAMP:
Drawing Number
Building Number
BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.
COMMISSIONING
ES2
13401 N. SANTA FE AVE
OKLAHOMA CITY, OK 73114
(405) 528-4500
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
C O
N T
R O
L L E
D U
N C
L A
S S
IF
IE
D I
N F
O R
M A
T
IO
N
C U
I)
/2
/2
:3 :2
A
M
100% BID DOCUMENTS
BUILDING 1 - REFERENCE PLANS
JPH 211 OF 229KGH
BONHAM EHRM
INFRASTRUCTURE
UPGRADES
07/07/2023
549A4-21-700
BONHAM VA MEDICAL CENTER
1201 E. 9TH STREET
BONHAM, TX 75418
TY101
SPUR #: 2216
N
1/16" = 1'-0"
BLDG 1 – LEVEL 11
N
1/16" = 1'-0"
BLDG 1 – BASEMENT2
No. REVISION DESCRIPTION DATE
TY401
TY401
TY401
TY401
TY401
TY401
TY402
TY402
A. DRAWING IS DIAGRAMMATIC IN NATURE AND IS NOT TO BE CONSTRUED
AS ALL INCLUSIVE; FIELD VERIFY EXISTING CONDITIONS AND ADJUST
WORK AS REQUIRED TO EXECUTE SPECIFIED WORK.
B. ELECTRICAL OUTLET/ DEVICES INDICATED ARE FOR COORDINATION &
REFERENCE PURPOSES; REFER TO ELECTRICAL, E-SERIES DRAWINGS
FOR ELECTRICAL WORK REQUIREMENTS AND SPECIFICATIONS.
C. THIS SITE IS AN ACTIVE WORKING ENVIRONMENT; SYSTEMS SHALL NOT
BE SHUTDOWN WITHOUT WRITTEN AUTHORIZATION; ALL REQUESTS
SHALL BE SUBMITTED IN WRITING A MINIMUM OF SEVEN (7) WORKING-
DAYS PRIOR TO PROPOSED ACTIVITY DATE OR NEED UNLESS DIRECTED
OTHERWISE.
D. SEE TY000 ABBREVIATIONS, SYMBOLS, LEGENDS, & NOTES FOR
SYMBOLS DEFINITION:
1. SYMBOLS GRAYED/ HALFTONE: INDICATED FOR REFERENCE
AND/OR INDICATING EXISTING UNLESS SPECIFICALLY NOTED
OTHERWISE.
2. SYMBOLS DASHED OR SPECIFICALLY KEYED NOTED: INDICATES
DEMOLITION WORK.
F. COORDINATE WORK AND PHASING SCHEDULE WITH THE
CONTRACTING OFFICER'S REPRESENTATIVE.
G. CONTRACTOR TO COORDINATE CABLE COLORS WITH THE VA
PRIOR TO PURCHASING AND INSTALLATION. GREEN CABLING FOR CAT6A
DATA, WHITE FOR TELEPHONE VOICE.
H. ALL CATEGORY-6A STATION CABLING SHALL BE SUPPORTED
USING A COMBINATION OF CONDUITS ALONG CABLE PATHWAY TO
NEW MCR.
I. COORDINATE SECURITY WORK WITH ALL OTHER TRADES. VERIFY ALL
EXISTING CONDITIONS BEFORE THE START OF WORK.
GENERAL NOTES
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
CONSULTANTS:
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC ENGINEER
SPUR DESIGN
2519 MADISON AVE., STE. 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
RATED ENGINEERING
609 S. KELLY AVENUE, SUITE H2
EDMOND, OK 73003
(405) 856-2965
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TECH ENGINEER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STRUCT ENGINEER
STAND STRUCTURAL ENGINEERING
8234 ROBINSON STREET
OVERLAND PARK, KS 66204
(913) 214-2169
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. BR 2171 EXP. 09/30/2023
ENGR REG. NO. F-17591 EXP. 02/29/2024
STAMP:
Drawing Number
Building Number
BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.
COMMISSIONING
ES2
13401 N. SANTA FE AVE
OKLAHOMA CITY, OK 73114
(405) 528-4500
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
C O
N T
R O
L L E
D U
N C
L A
S S
IF
IE
D I
N F
O R
M A
T
IO
N
C U
I)
/2
/2
:3 :2
A
M
100% BID DOCUMENTS
BUILDING 1 - REFERENCE PLANS
JPH 212 OF 229KGH
BONHAM EHRM
INFRASTRUCTURE
UPGRADES
07/07/2023
549A4-21-700
BONHAM VA MEDICAL CENTER
1201 E. 9TH STREET
BONHAM, TX 75418
TY102
SPUR #: 2216
N
1/16" = 1'-0"
BLDG 1 – LEVEL 32
N
1/16" = 1'-0"
BLDG 1 – LEVEL 21
N
1/16" = 1'-0"
BLDG 1 – LEVEL 43
N
1/16" = 1'-0"
BLDG 1 – LEVEL 54
TY403
TY403
TY403
TY403
TY403
TY403
A. DRAWING IS DIAGRAMMATIC IN NATURE AND IS NOT TO BE CONSTRUED
AS ALL INCLUSIVE; FIELD VERIFY EXISTING CONDITIONS AND ADJUST
WORK AS REQUIRED TO EXECUTE SPECIFIED WORK.
B. ELECTRICAL OUTLET/ DEVICES INDICATED ARE FOR COORDINATION &
REFERENCE PURPOSES; REFER TO ELECTRICAL, E-SERIES DRAWINGS
FOR ELECTRICAL WORK REQUIREMENTS AND SPECIFICATIONS.
C. THIS SITE IS AN ACTIVE WORKING ENVIRONMENT; SYSTEMS SHALL NOT
BE SHUTDOWN WITHOUT WRITTEN AUTHORIZATION; ALL REQUESTS
SHALL BE SUBMITTED IN WRITING A MINIMUM OF SEVEN (7) WORKING-
DAYS PRIOR TO PROPOSED ACTIVITY DATE OR NEED UNLESS DIRECTED
OTHERWISE.
D. SEE TY000 ABBREVIATIONS, SYMBOLS, LEGENDS, & NOTES FOR
SYMBOLS DEFINITION:
1. SYMBOLS GRAYED/ HALFTONE: INDICATED FOR REFERENCE
AND/OR INDICATING EXISTING UNLESS SPECIFICALLY NOTED
OTHERWISE.
2. SYMBOLS DASHED OR SPECIFICALLY KEYED NOTED: INDICATES
DEMOLITION WORK.
F. COORDINATE WORK AND PHASING SCHEDULE WITH THE
CONTRACTING OFFICER'S REPRESENTATIVE.
G. CONTRACTOR TO COORDINATE CABLE COLORS WITH THE VA
PRIOR TO PURCHASING AND INSTALLATION. GREEN CABLING FOR CAT6A
DATA, WHITE FOR TELEPHONE VOICE.
H. ALL CATEGORY-6A STATION CABLING SHALL BE SUPPORTED
USING A COMBINATION OF CONDUITS ALONG CABLE PATHWAY TO
NEW MCR.
I. COORDINATE SECURITY WORK WITH ALL OTHER TRADES. VERIFY ALL
EXISTING CONDITIONS BEFORE THE START OF WORK.
GENERAL NOTES
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
CONSULTANTS:
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC ENGINEER
SPUR DESIGN
2519 MADISON AVE., STE. 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
RATED ENGINEERING
609 S. KELLY AVENUE, SUITE H2
EDMOND, OK 73003
(405) 856-2965
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TECH ENGINEER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STRUCT ENGINEER
STAND STRUCTURAL ENGINEERING
8234 ROBINSON STREET
OVERLAND PARK, KS 66204
(913) 214-2169
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. BR 2171 EXP. 09/30/2023
ENGR REG. NO. F-17591 EXP. 02/29/2024
STAMP:
Drawing Number
Building Number
BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.
COMMISSIONING
ES2
13401 N. SANTA FE AVE
OKLAHOMA CITY, OK 73114
(405) 528-4500
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
C O
N T
R O
L L E
D U
N C
L A
S S
IF
IE
D I
N F
O R
M A
T
IO
N
C U
I)
/2
/2
:3 :2
A
M
100% BID DOCUMENTS
BUILDING 2 - REFERENCE PLAN
JPH 213 OF 229KGH
BONHAM EHRM
INFRASTRUCTURE
UPGRADES
07/07/2023
549A4-21-700
BONHAM VA MEDICAL CENTER
1201 E. 9TH STREET
BONHAM, TX 75418
TY103
SPUR #: 2216
N
1/16" = 1'-0"
BLDG 2 – LEVEL 11
N
1/16" = 1'-0"
BLDG 2 – LEVEL 22
TY403
TY403
TY403
TY403
A. DRAWING IS DIAGRAMMATIC IN NATURE AND IS NOT TO BE CONSTRUED
AS ALL INCLUSIVE; FIELD VERIFY EXISTING CONDITIONS AND ADJUST
WORK AS REQUIRED TO EXECUTE SPECIFIED WORK.
B. ELECTRICAL OUTLET/ DEVICES INDICATED ARE FOR COORDINATION &
REFERENCE PURPOSES; REFER TO ELECTRICAL, E-SERIES DRAWINGS
FOR ELECTRICAL WORK REQUIREMENTS AND SPECIFICATIONS.
C. THIS SITE IS AN ACTIVE WORKING ENVIRONMENT; SYSTEMS SHALL NOT
BE SHUTDOWN WITHOUT WRITTEN AUTHORIZATION; ALL REQUESTS
SHALL BE SUBMITTED IN WRITING A MINIMUM OF SEVEN (7) WORKING-
DAYS PRIOR TO PROPOSED ACTIVITY DATE OR NEED UNLESS DIRECTED
OTHERWISE.
D. SEE TY000 ABBREVIATIONS, SYMBOLS, LEGENDS, & NOTES FOR
SYMBOLS DEFINITION:
1. SYMBOLS GRAYED/ HALFTONE: INDICATED FOR REFERENCE
AND/OR INDICATING EXISTING UNLESS SPECIFICALLY NOTED
OTHERWISE.
2. SYMBOLS DASHED OR SPECIFICALLY KEYED NOTED: INDICATES
DEMOLITION WORK.
F. COORDINATE WORK AND PHASING SCHEDULE WITH THE
CONTRACTING OFFICER'S REPRESENTATIVE.
G. CONTRACTOR TO COORDINATE CABLE COLORS WITH THE VA
PRIOR TO PURCHASING AND INSTALLATION. GREEN CABLING FOR CAT6A
DATA, WHITE FOR TELEPHONE VOICE.
H. ALL CATEGORY-6A STATION CABLING SHALL BE SUPPORTED
USING A COMBINATION OF CONDUITS ALONG CABLE PATHWAY TO
NEW MCR.
I. COORDINATE SECURITY WORK WITH ALL OTHER TRADES. VERIFY ALL
EXISTING CONDITIONS BEFORE THE START OF WORK.
GENERAL NOTES
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
CONSULTANTS:
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC ENGINEER
SPUR DESIGN
2519 MADISON AVE., STE. 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
RATED ENGINEERING
609 S. KELLY AVENUE, SUITE H2
EDMOND, OK 73003
(405) 856-2965
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TECH ENGINEER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STRUCT ENGINEER
STAND STRUCTURAL ENGINEERING
8234 ROBINSON STREET
OVERLAND PARK, KS 66204
(913) 214-2169
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. BR 2171 EXP. 09/30/2023
ENGR REG. NO. F-17591 EXP. 02/29/2024
STAMP:
Drawing Number
Building Number
BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.
COMMISSIONING
ES2
13401 N. SANTA FE AVE
OKLAHOMA CITY, OK 73114
(405) 528-4500
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
C O
N T
R O
L L E
D U
N C
L A
S S
IF
IE
D I
N F
O R
M A
T
IO
N
C U
I)
/2
/2
:3 :2
A
M
100% BID DOCUMENTS
BUILDING 2 - REFERENCE PLAN
JPH 214 OF 229KGH
BONHAM EHRM
INFRASTRUCTURE
UPGRADES
07/07/2023
549A4-21-700
BONHAM VA MEDICAL CENTER
1201 E. 9TH STREET
BONHAM, TX 75418
TY104
SPUR #: 2216
N
1/16" = 1'-0"
BLDG 2 – LEVEL 31
N
1/16" = 1'-0"
BLDG 2 – LEVEL 42
TY404
TY404
TY405
TY405
TY404
TY404
TY404
TY404
A. DRAWING IS DIAGRAMMATIC IN NATURE AND IS NOT TO BE CONSTRUED
AS ALL INCLUSIVE; FIELD VERIFY EXISTING CONDITIONS AND ADJUST
WORK AS REQUIRED TO EXECUTE SPECIFIED WORK.
B. ELECTRICAL OUTLET/ DEVICES INDICATED ARE FOR COORDINATION &
REFERENCE PURPOSES; REFER TO ELECTRICAL, E-SERIES DRAWINGS
FOR ELECTRICAL WORK REQUIREMENTS AND SPECIFICATIONS.
C. THIS SITE IS AN ACTIVE WORKING ENVIRONMENT; SYSTEMS SHALL NOT
BE SHUTDOWN WITHOUT WRITTEN AUTHORIZATION; ALL REQUESTS
SHALL BE SUBMITTED IN WRITING A MINIMUM OF SEVEN (7) WORKING-
DAYS PRIOR TO PROPOSED ACTIVITY DATE OR NEED UNLESS DIRECTED
OTHERWISE.
D. SEE TY000 ABBREVIATIONS, SYMBOLS, LEGENDS, & NOTES FOR
SYMBOLS DEFINITION:
1. SYMBOLS GRAYED/ HALFTONE: INDICATED FOR REFERENCE
AND/OR INDICATING EXISTING UNLESS SPECIFICALLY NOTED
OTHERWISE.
2. SYMBOLS DASHED OR SPECIFICALLY KEYED NOTED: INDICATES
DEMOLITION WORK.
F. COORDINATE WORK AND PHASING SCHEDULE WITH THE
CONTRACTING OFFICER'S REPRESENTATIVE.
G. CONTRACTOR TO COORDINATE CABLE COLORS WITH THE VA
PRIOR TO PURCHASING AND INSTALLATION. GREEN CABLING FOR CAT6A
DATA, WHITE FOR TELEPHONE VOICE.
H. ALL CATEGORY-6A STATION CABLING SHALL BE SUPPORTED
USING A COMBINATION OF CONDUITS ALONG CABLE PATHWAY TO
NEW MCR.
I. COORDINATE SECURITY WORK WITH ALL OTHER TRADES. VERIFY ALL
EXISTING CONDITIONS BEFORE THE START OF WORK.
GENERAL NOTES
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
CONSULTANTS:
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC ENGINEER
SPUR DESIGN
2519 MADISON AVE., STE. 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
RATED ENGINEERING
609 S. KELLY AVENUE, SUITE H2
EDMOND, OK 73003
(405) 856-2965
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TECH ENGINEER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STRUCT ENGINEER
STAND STRUCTURAL ENGINEERING
8234 ROBINSON STREET
OVERLAND PARK, KS 66204
(913) 214-2169
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. BR 2171 EXP. 09/30/2023
ENGR REG. NO. F-17591 EXP. 02/29/2024
STAMP:
Drawing Number
Building Number
BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.
COMMISSIONING
ES2
13401 N. SANTA FE AVE
OKLAHOMA CITY, OK 73114
(405) 528-4500
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
C O
N T
R O
L L E
D U
N C
L A
S S
IF
IE
D I
N F
O R
M A
T
IO
N
C U
I)
/2
/2
:3 :2
A
M
100% BID DOCUMENTS
BUILDINGS 3, 4, 8, & 9 - REFERENCE
PLANS
JPH 215 OF 229KGH
BONHAM EHRM
INFRASTRUCTURE
UPGRADES
07/07/2023
549A4-21-700
BONHAM VA MEDICAL CENTER
1201 E. 9TH STREET
BONHAM, TX 75418
TY105
3, 4, 8, 9
SPUR #: 2216
N
1/16" = 1'-0"
BLDG 8 – LEVEL 13
N
1/16" = 1'-0"
BLDG 9 – LEVEL 14
N
1/16" = 1'-0"
BLDG 4 – LEVEL 22
N
1/16" = 1'-0"
BLDG 3 – LEVEL 21
TY405
TY405
TY405
TY405
TY405
TY405
A. DRAWING IS DIAGRAMMATIC IN NATURE AND IS NOT TO BE CONSTRUED
AS ALL INCLUSIVE; FIELD VERIFY EXISTING CONDITIONS AND ADJUST
WORK AS REQUIRED TO EXECUTE SPECIFIED WORK.
B. ELECTRICAL OUTLET/ DEVICES INDICATED ARE FOR COORDINATION &
REFERENCE PURPOSES; REFER TO ELECTRICAL, E-SERIES DRAWINGS
FOR ELECTRICAL WORK REQUIREMENTS AND SPECIFICATIONS.
C. THIS SITE IS AN ACTIVE WORKING ENVIRONMENT; SYSTEMS SHALL NOT
BE SHUTDOWN WITHOUT WRITTEN AUTHORIZATION; ALL REQUESTS
SHALL BE SUBMITTED IN WRITING A MINIMUM OF SEVEN (7) WORKING-
DAYS PRIOR TO PROPOSED ACTIVITY DATE OR NEED UNLESS DIRECTED
OTHERWISE.
D. SEE TY000 ABBREVIATIONS, SYMBOLS, LEGENDS, & NOTES FOR
SYMBOLS DEFINITION:
1. SYMBOLS GRAYED/ HALFTONE: INDICATED FOR REFERENCE
AND/OR INDICATING EXISTING UNLESS SPECIFICALLY NOTED
OTHERWISE.
2. SYMBOLS DASHED OR SPECIFICALLY KEYED NOTED: INDICATES
DEMOLITION WORK.
F. COORDINATE WORK AND PHASING SCHEDULE WITH THE
CONTRACTING OFFICER'S REPRESENTATIVE.
G. CONTRACTOR TO COORDINATE CABLE COLORS WITH THE VA
PRIOR TO PURCHASING AND INSTALLATION. GREEN CABLING FOR CAT6A
DATA, WHITE FOR TELEPHONE VOICE.
H. ALL CATEGORY-6A STATION CABLING SHALL BE SUPPORTED
USING A COMBINATION OF CONDUITS ALONG CABLE PATHWAY TO
NEW MCR.
I. COORDINATE SECURITY WORK WITH ALL OTHER TRADES. VERIFY ALL
EXISTING CONDITIONS BEFORE THE START OF WORK.
GENERAL NOTES
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
CONSULTANTS:
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC ENGINEER
SPUR DESIGN
2519 MADISON AVE., STE. 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
RATED ENGINEERING
609 S. KELLY AVENUE, SUITE H2
EDMOND, OK 73003
(405) 856-2965
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TECH ENGINEER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STRUCT ENGINEER
STAND STRUCTURAL ENGINEERING
8234 ROBINSON STREET
OVERLAND PARK, KS 66204
(913) 214-2169
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. BR 2171 EXP. 09/30/2023
ENGR REG. NO. F-17591 EXP. 02/29/2024
STAMP:
Drawing Number
Building Number
BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.
COMMISSIONING
ES2
13401 N. SANTA FE AVE
OKLAHOMA CITY, OK 73114
(405) 528-4500
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
C O
N T
R O
L L E
D U
N C
L A
S S
IF
IE
D I
N F
O R
M A
T
IO
N
C U
I)
/2
/2
:3 :2
A
M
100% BID DOCUMENTS
BUILDINGS 10, 11, & 12 - REFERENCE
PLANS
JPH 216 OF 229KGH
BONHAM EHRM
INFRASTRUCTURE
UPGRADES
07/07/2023
549A4-21-700
BONHAM VA MEDICAL CENTER
1201 E. 9TH STREET
BONHAM, TX 75418
TY106
10, 11, 12
SPUR #: 2216
N
1/16" = 1'-0"
BLDG 10 – LEVEL 11
N
1/16" = 1'-0"
BLDG 11 – LEVEL 12
N
1/16" = 1'-0"
BLDG 12 – LEVEL 23
TY406
TY406
TY406
TY406
A. DRAWING IS DIAGRAMMATIC IN NATURE AND IS NOT TO BE CONSTRUED
AS ALL INCLUSIVE; FIELD VERIFY EXISTING CONDITIONS AND ADJUST
WORK AS REQUIRED TO EXECUTE SPECIFIED WORK.
B. ELECTRICAL OUTLET/ DEVICES INDICATED ARE FOR COORDINATION &
REFERENCE PURPOSES; REFER TO ELECTRICAL, E-SERIES DRAWINGS
FOR ELECTRICAL WORK REQUIREMENTS AND SPECIFICATIONS.
C. THIS SITE IS AN ACTIVE WORKING ENVIRONMENT; SYSTEMS SHALL NOT
BE SHUTDOWN WITHOUT WRITTEN AUTHORIZATION; ALL REQUESTS
SHALL BE SUBMITTED IN WRITING A MINIMUM OF SEVEN (7) WORKING-
DAYS PRIOR TO PROPOSED ACTIVITY DATE OR NEED UNLESS DIRECTED
OTHERWISE.
D. SEE TY000 ABBREVIATIONS, SYMBOLS, LEGENDS, & NOTES FOR
SYMBOLS DEFINITION:
1. SYMBOLS GRAYED/ HALFTONE: INDICATED FOR REFERENCE
AND/OR INDICATING EXISTING UNLESS SPECIFICALLY NOTED
OTHERWISE.
2. SYMBOLS DASHED OR SPECIFICALLY KEYED NOTED: INDICATES
DEMOLITION WORK.
F. COORDINATE WORK AND PHASING SCHEDULE WITH THE
CONTRACTING OFFICER'S REPRESENTATIVE.
G. CONTRACTOR TO COORDINATE CABLE COLORS WITH THE VA
PRIOR TO PURCHASING AND INSTALLATION. GREEN CABLING FOR CAT6A
DATA, WHITE FOR TELEPHONE VOICE.
H. ALL CATEGORY-6A STATION CABLING SHALL BE SUPPORTED
USING A COMBINATION OF CONDUITS ALONG CABLE PATHWAY TO
NEW MCR.
I. COORDINATE SECURITY WORK WITH ALL OTHER TRADES. VERIFY ALL
EXISTING CONDITIONS BEFORE THE START OF WORK.
GENERAL NOTES
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
CONSULTANTS:
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC ENGINEER
SPUR DESIGN
2519 MADISON AVE., STE. 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
RATED ENGINEERING
609 S. KELLY AVENUE, SUITE H2
EDMOND, OK 73003
(405) 856-2965
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TECH ENGINEER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STRUCT ENGINEER
STAND STRUCTURAL ENGINEERING
8234 ROBINSON STREET
OVERLAND PARK, KS 66204
(913) 214-2169
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. BR 2171 EXP. 09/30/2023
ENGR REG. NO. F-17591 EXP. 02/29/2024
STAMP:
Drawing Number
Building Number
BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.
COMMISSIONING
ES2
13401 N. SANTA FE AVE
OKLAHOMA CITY, OK 73114
(405) 528-4500
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
C O
N T
R O
L L E
D U
N C
L A
S S
IF
IE
D I
N F
O R
M A
T
IO
N
C U
I)
/2
/2
:3 :2
A
M
100% BID DOCUMENTS
BUILDING 24 - REFERENCE PLAN
JPH 217 OF 229KGH
BONHAM EHRM
INFRASTRUCTURE
UPGRADES
07/07/2023
549A4-21-700
BONHAM VA MEDICAL CENTER
1201 E. 9TH STREET
BONHAM, TX 75418
TY107
SPUR #: 2216
N
1/16" = 1'-0"
BLDG 24 – LEVEL 11
E X
IT
TY406
TY406
TY406
TY406
A. DRAWING IS DIAGRAMMATIC IN NATURE AND IS NOT TO BE CONSTRUED
AS ALL INCLUSIVE; FIELD VERIFY EXISTING CONDITIONS AND ADJUST
WORK AS REQUIRED TO EXECUTE SPECIFIED WORK.
B. ELECTRICAL OUTLET/ DEVICES INDICATED ARE FOR COORDINATION &
REFERENCE PURPOSES; REFER TO ELECTRICAL, E-SERIES DRAWINGS
FOR ELECTRICAL WORK REQUIREMENTS AND SPECIFICATIONS.
C. THIS SITE IS AN ACTIVE WORKING ENVIRONMENT; SYSTEMS SHALL NOT
BE SHUTDOWN WITHOUT WRITTEN AUTHORIZATION; ALL REQUESTS
SHALL BE SUBMITTED IN WRITING A MINIMUM OF SEVEN (7) WORKING-
DAYS PRIOR TO PROPOSED ACTIVITY DATE OR NEED UNLESS DIRECTED
OTHERWISE.
D. SEE TY000 ABBREVIATIONS, SYMBOLS, LEGENDS, & NOTES FOR
SYMBOLS DEFINITION:
1. SYMBOLS GRAYED/ HALFTONE: INDICATED FOR REFERENCE
AND/OR INDICATING EXISTING UNLESS SPECIFICALLY NOTED
OTHERWISE.
2. SYMBOLS DASHED OR SPECIFICALLY KEYED NOTED: INDICATES
DEMOLITION WORK.
F. COORDINATE WORK AND PHASING SCHEDULE WITH THE
CONTRACTING OFFICER'S REPRESENTATIVE.
G. CONTRACTOR TO COORDINATE CABLE COLORS WITH THE VA
PRIOR TO PURCHASING AND INSTALLATION. GREEN CABLING FOR CAT6A
DATA, WHITE FOR TELEPHONE VOICE.
H. ALL CATEGORY-6A STATION CABLING SHALL BE SUPPORTED
USING A COMBINATION OF CONDUITS ALONG CABLE PATHWAY TO
NEW MCR.
I. COORDINATE SECURITY WORK WITH ALL OTHER TRADES. VERIFY ALL
EXISTING CONDITIONS BEFORE THE START OF WORK.
GENERAL NOTES
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
CONSULTANTS:
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC ENGINEER
SPUR DESIGN
2519 MADISON AVE., STE. 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
RATED ENGINEERING
609 S. KELLY AVENUE, SUITE H2
EDMOND, OK 73003
(405) 856-2965
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TECH ENGINEER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STRUCT ENGINEER
STAND STRUCTURAL ENGINEERING
8234 ROBINSON STREET
OVERLAND PARK, KS 66204
(913) 214-2169
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. BR 2171 EXP. 09/30/2023
ENGR REG. NO. F-17591 EXP. 02/29/2024
STAMP:
Drawing Number
Building Number
BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.
COMMISSIONING
ES2
13401 N. SANTA FE AVE
OKLAHOMA CITY, OK 73114
(405) 528-4500
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
C O
N T
R O
L L E
D U
N C
L A
S S
IF
IE
D I
N F
O R
M A
T
IO
N
C U
I)
/2
/2
:3 :2
A
M
100% BID DOCUMENTS
BUILDING 24 - REFERENCE PLAN
JPH 218 OF 229KGH
BONHAM EHRM
INFRASTRUCTURE
UPGRADES
07/07/2023
549A4-21-700
BONHAM VA MEDICAL CENTER
1201 E. 9TH STREET
BONHAM, TX 75418
TY108
SPUR #: 2216
N
1/16" = 1'-0"
BLDG 24 – LEVEL 21
B2200
CORRIDOR
TY407
TY407
TY407
TY407
A. DRAWING IS DIAGRAMMATIC IN NATURE AND IS NOT TO BE CONSTRUED
AS ALL INCLUSIVE; FIELD VERIFY EXISTING CONDITIONS AND ADJUST
WORK AS REQUIRED TO EXECUTE SPECIFIED WORK.
B. ELECTRICAL OUTLET/ DEVICES INDICATED ARE FOR COORDINATION &
REFERENCE PURPOSES; REFER TO ELECTRICAL, E-SERIES DRAWINGS
FOR ELECTRICAL WORK REQUIREMENTS AND SPECIFICATIONS.
C. THIS SITE IS AN ACTIVE WORKING ENVIRONMENT; SYSTEMS SHALL NOT
BE SHUTDOWN WITHOUT WRITTEN AUTHORIZATION; ALL REQUESTS
SHALL BE SUBMITTED IN WRITING A MINIMUM OF SEVEN (7) WORKING-
DAYS PRIOR TO PROPOSED ACTIVITY DATE OR NEED UNLESS DIRECTED
OTHERWISE.
D. SEE TY000 ABBREVIATIONS, SYMBOLS, LEGENDS, & NOTES FOR
SYMBOLS DEFINITION:
1. SYMBOLS GRAYED/ HALFTONE: INDICATED FOR REFERENCE
AND/OR INDICATING EXISTING UNLESS SPECIFICALLY NOTED
OTHERWISE.
2. SYMBOLS DASHED OR SPECIFICALLY KEYED NOTED: INDICATES
DEMOLITION WORK.
F. COORDINATE WORK AND PHASING SCHEDULE WITH THE
CONTRACTING OFFICER'S REPRESENTATIVE.
G. CONTRACTOR TO COORDINATE CABLE COLORS WITH THE VA
PRIOR TO PURCHASING AND INSTALLATION. GREEN CABLING FOR CAT6A
DATA, WHITE FOR TELEPHONE VOICE.
H. ALL CATEGORY-6A STATION CABLING SHALL BE SUPPORTED
USING A COMBINATION OF CONDUITS ALONG CABLE PATHWAY TO
NEW MCR.
I. COORDINATE SECURITY WORK WITH ALL OTHER TRADES. VERIFY ALL
EXISTING CONDITIONS BEFORE THE START OF WORK.
GENERAL NOTES
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
CONSULTANTS:
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC ENGINEER
SPUR DESIGN
2519 MADISON AVE., STE. 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
RATED ENGINEERING
609 S. KELLY AVENUE, SUITE H2
EDMOND, OK 73003
(405) 856-2965
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TECH ENGINEER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STRUCT ENGINEER
STAND STRUCTURAL ENGINEERING
8234 ROBINSON STREET
OVERLAND PARK, KS 66204
(913) 214-2169
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. BR 2171 EXP. 09/30/2023
ENGR REG. NO. F-17591 EXP. 02/29/2024
STAMP:
Drawing Number
Building Number
BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.
COMMISSIONING
ES2
13401 N. SANTA FE AVE
OKLAHOMA CITY, OK 73114
(405) 528-4500
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
C O
N T
R O
L L E
D U
N C
L A
S S
IF
IE
D I
N F
O R
M A
T
IO
N
C U
I)
/2
/2
:3 :3
A
M
100% BID DOCUMENTS
BUILDING 29 - REFERENCE PLAN
JPH 219 OF 229KGH
BONHAM EHRM
INFRASTRUCTURE
UPGRADES
07/07/2023
549A4-21-700
BONHAM VA MEDICAL CENTER
1201 E. 9TH STREET
BONHAM, TX 75418
TY109
SPUR #: 2216
N
1/16" = 1'-0"
BLDG 29 – LEVEL 11
A. DRAWING IS DIAGRAMMATIC IN NATURE AND IS NOT TO BE CONSTRUED
AS ALL INCLUSIVE; FIELD VERIFY EXISTING CONDITIONS AND ADJUST
WORK AS REQUIRED TO EXECUTE SPECIFIED WORK.
B. ELECTRICAL OUTLET/ DEVICES INDICATED ARE FOR COORDINATION &
REFERENCE PURPOSES; REFER TO ELECTRICAL, E-SERIES DRAWINGS
FOR ELECTRICAL WORK REQUIREMENTS AND SPECIFICATIONS.
C. THIS SITE IS AN ACTIVE WORKING ENVIRONMENT; SYSTEMS SHALL NOT
BE SHUTDOWN WITHOUT WRITTEN AUTHORIZATION; ALL REQUESTS
SHALL BE SUBMITTED IN WRITING A MINIMUM OF SEVEN (7) WORKING-
DAYS PRIOR TO PROPOSED ACTIVITY DATE OR NEED UNLESS DIRECTED
OTHERWISE.
D. SEE TY000 ABBREVIATIONS, SYMBOLS, LEGENDS, & NOTES FOR
SYMBOLS DEFINITION:
1. SYMBOLS GRAYED/ HALFTONE: INDICATED FOR REFERENCE
AND/OR INDICATING EXISTING UNLESS SPECIFICALLY NOTED
OTHERWISE.
2. SYMBOLS DASHED OR SPECIFICALLY KEYED NOTED: INDICATES
DEMOLITION WORK.
F. COORDINATE WORK AND PHASING SCHEDULE WITH THE
CONTRACTING OFFICER'S REPRESENTATIVE.
G. CONTRACTOR TO COORDINATE CABLE COLORS WITH THE VA
PRIOR TO PURCHASING AND INSTALLATION. GREEN CABLING FOR CAT6A
DATA, WHITE FOR TELEPHONE VOICE.
H. ALL CATEGORY-6A STATION CABLING SHALL BE SUPPORTED
USING A COMBINATION OF CONDUITS ALONG CABLE PATHWAY TO
NEW MCR.
I. COORDINATE SECURITY WORK WITH ALL OTHER TRADES. VERIFY ALL
EXISTING CONDITIONS BEFORE THE START OF WORK.
GENERAL NOTES
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
CONSULTANTS:
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC ENGINEER
SPUR DESIGN
2519 MADISON AVE., STE. 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
RATED ENGINEERING
609 S. KELLY AVENUE, SUITE H2
EDMOND, OK 73003
(405) 856-2965
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TECH ENGINEER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STRUCT ENGINEER
STAND STRUCTURAL ENGINEERING
8234 ROBINSON STREET
OVERLAND PARK, KS 66204
(913) 214-2169
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. BR 2171 EXP. 09/30/2023
ENGR REG. NO. F-17591 EXP. 02/29/2024
STAMP:
Drawing Number
Building Number
BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.
COMMISSIONING
ES2
13401 N. SANTA FE AVE
OKLAHOMA CITY, OK 73114
(405) 528-4500
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
C O
N T
R O
L L E
D U
N C
L A
S S
IF
IE
D I
N F
O R
M A
T
IO
N
C U
I)
/2
/2
:3 :3
A
M
100% BID DOCUMENTS
BLDG 1 - SECURITY ENLARGED PLANS
JPH 220 OF 229KGH
BONHAM EHRM
INFRASTRUCTURE
UPGRADES
07/07/2023
549A4-21-700
BONHAM VA MEDICAL CENTER
1201 E. 9TH STREET
BONHAM, TX 75418
TY400
SPUR #: 2216
SECURITY KEYNOTES#
N
1/4" = 1'-0"
BLDG 1 - BASEMENT - 17 - DEMO1
N
1/4" = 1'-0"
BLDG 1 - BASEMENT - 15 - DEMO2
1 EXISTING SECURITY DEVICES AND ASSOCIATED CABLING TO BE REMOVED
BACK TO SOURCE.
DM
RE
EL CR
CR
DM
EL
RE
GB
CR
DM
EL
RE
GB
DM
EL
RE
CR
GB
CR
DM
EL
RE
GB
POLICE LOCKER
116A
NEW TR
116A
C-01
TY500
A
-1
OFFICE
NEW TR
C-01
160-1
TY500
EX. DENTAL LOBBY
EX. COMM
NEW TR
CLOSET
C-01
-1
TY500
EX. EXAM
EX. COMM
317A
NEW TR
CLOSET
317B
CLOSET
317A
C-01
-1
TY500
EX. COMM
EX. EXAM
CLOSET
NEW TR
CLOSET
418A
C-01
-1
TY500
A. DRAWING IS DIAGRAMMATIC IN NATURE AND IS NOT TO BE CONSTRUED
AS ALL INCLUSIVE; FIELD VERIFY EXISTING CONDITIONS AND ADJUST
WORK AS REQUIRED TO EXECUTE SPECIFIED WORK.
B. ELECTRICAL OUTLET/ DEVICES INDICATED ARE FOR COORDINATION &
REFERENCE PURPOSES; REFER TO ELECTRICAL, E-SERIES DRAWINGS
FOR ELECTRICAL WORK REQUIREMENTS AND SPECIFICATIONS.
C. THIS SITE IS AN ACTIVE WORKING ENVIRONMENT; SYSTEMS SHALL NOT
BE SHUTDOWN WITHOUT WRITTEN AUTHORIZATION; ALL REQUESTS
SHALL BE SUBMITTED IN WRITING A MINIMUM OF SEVEN (7) WORKING-
DAYS PRIOR TO PROPOSED ACTIVITY DATE OR NEED UNLESS DIRECTED
OTHERWISE.
D. SEE TY000 ABBREVIATIONS, SYMBOLS, LEGENDS, & NOTES FOR
SYMBOLS DEFINITION:
1. SYMBOLS GRAYED/ HALFTONE: INDICATED FOR REFERENCE
AND/OR INDICATING EXISTING UNLESS SPECIFICALLY NOTED
OTHERWISE.
2. SYMBOLS DASHED OR SPECIFICALLY KEYED NOTED: INDICATES
DEMOLITION WORK.
F. COORDINATE WORK AND PHASING SCHEDULE WITH THE
CONTRACTING OFFICER'S REPRESENTATIVE.
G. CONTRACTOR TO COORDINATE CABLE COLORS WITH THE VA
PRIOR TO PURCHASING AND INSTALLATION. GREEN CABLING FOR CAT6A
DATA, WHITE FOR TELEPHONE VOICE.
H. ALL CATEGORY-6A STATION CABLING SHALL BE SUPPORTED
USING A COMBINATION OF CONDUITS ALONG CABLE PATHWAY TO
NEW MCR.
I. COORDINATE SECURITY WORK WITH ALL OTHER TRADES. VERIFY ALL
EXISTING CONDITIONS BEFORE THE START OF WORK.
GENERAL NOTES
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
CONSULTANTS:
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC ENGINEER
SPUR DESIGN
2519 MADISON AVE., STE. 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
RATED ENGINEERING
609 S. KELLY AVENUE, SUITE H2
EDMOND, OK 73003
(405) 856-2965
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TECH ENGINEER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STRUCT ENGINEER
STAND STRUCTURAL ENGINEERING
8234 ROBINSON STREET
OVERLAND PARK, KS 66204
(913) 214-2169
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. BR 2171 EXP. 09/30/2023
ENGR REG. NO. F-17591 EXP. 02/29/2024
STAMP:
Drawing Number
Building Number
BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.
COMMISSIONING
ES2
13401 N. SANTA FE AVE
OKLAHOMA CITY, OK 73114
(405) 528-4500
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
C O
N T
R O
L L E
D U
N C
L A
S S
IF
IE
D I
N F
O R
M A
T
IO
N
C U
I)
/2
/2
:3 :3
A
M
100% BID DOCUMENTS
BLDG 1 - SECURITY ENLARGED PLANS
JPH 221 OF 229KGH
BONHAM EHRM
INFRASTRUCTURE
UPGRADES
07/07/2023
549A4-21-700
BONHAM VA MEDICAL CENTER
1201 E. 9TH STREET
BONHAM, TX 75418
TY401
SPUR #: 2216
N
1/4" = 1'-0" REF: 1/ TY101
BLDG 1 - LEVEL 1 - 116A - DEMO1
N
1/4" = 1'-0" REF: 1/ TY101
BLDG 1 - LEVEL 1 - 116A - NEW2
N
1/4" = 1'-0" REF: 1/ TY101
BLDG 1 - LEVEL 1 - 160 - DEMO3
N
1/4" = 1'-0" REF: 1/ TY101
BLDG 1 - LEVEL 1 - 160 - NEW4
N
1/4" = 1'-0"
BLDG 1 - LEVEL 2 - 222 & 222A - DEMO5
N
1/4" = 1'-0"
BLDG 1 - LEVEL 2 - 221 & 222 - NEW6
N
1/4" = 1'-0"
BLDG 1 - LEVEL 3 - 317 & 317A - DEMO7
N
1/4" = 1'-0"
BLDG 1 - LEVEL 3 - 317 & 317A - NEW8
N
1/4" = 1'-0"
BLDG 1 - LEVEL 4 - 417 & 418 - DEMO9
N
1/4" = 1'-0"
BLDG 1 - LEVEL 4 - 417 & 418 - NEW10
SECURITY KEYNOTES
1 EXISTING SECURITY DEVICES AND ASSOCIATED CABLING TO BE REMOVED
BACK TO SOURCE.
2 PROVIDE ELECTRIFIED MORTISE LOCK WITH STRIKE AND INTEGRAL
REQUEST TO EXIT.
3 PROVIDE FIXED, MOTION-ACTIVATED CAMERA TIED INTO SECURITY
CONTROL CENTER (SCC), NOTIFYING SCC IMMEDIATELY WHEN ROOM IS
ENTERED AND RECORDING TO NVR WHEN ACTIVATED.
4 PROVIDE GLASS BREAK DETECTORS ON NEW TR WINDOWS TIED INTO
SECURITY CONTROL CENTER (SCC).
CR
GBGBGBGB
GB
GB
PB
EL
RE
PB
PB
PB
DM
EL
RE 1
1 1 1 1
EX. STORAGE
515A
EX. STORAGE
514A
STORAGE
515B
EX. DIRTY UTILITY
EX. OFFICE
EX. COMM
STORAGE
515C
EX. CHASE
CLOSET
NEW SERVER
NEW FP
CLOSET
C-01
514-1
TY500
6 6 6
A. DRAWING IS DIAGRAMMATIC IN NATURE AND IS NOT TO BE CONSTRUED
AS ALL INCLUSIVE; FIELD VERIFY EXISTING CONDITIONS AND ADJUST
WORK AS REQUIRED TO EXECUTE SPECIFIED WORK.
B. ELECTRICAL OUTLET/ DEVICES INDICATED ARE FOR COORDINATION &
REFERENCE PURPOSES; REFER TO ELECTRICAL, E-SERIES DRAWINGS
FOR ELECTRICAL WORK REQUIREMENTS AND SPECIFICATIONS.
C. THIS SITE IS AN ACTIVE WORKING ENVIRONMENT; SYSTEMS SHALL NOT
BE SHUTDOWN WITHOUT WRITTEN AUTHORIZATION; ALL REQUESTS
SHALL BE SUBMITTED IN WRITING A MINIMUM OF SEVEN (7) WORKING-
DAYS PRIOR TO PROPOSED ACTIVITY DATE OR NEED UNLESS DIRECTED
OTHERWISE.
D. SEE TY000 ABBREVIATIONS, SYMBOLS, LEGENDS, & NOTES FOR
SYMBOLS DEFINITION:
1. SYMBOLS GRAYED/ HALFTONE: INDICATED FOR REFERENCE
AND/OR INDICATING EXISTING UNLESS SPECIFICALLY NOTED
OTHERWISE.
2. SYMBOLS DASHED OR SPECIFICALLY KEYED NOTED: INDICATES
DEMOLITION WORK.
F. COORDINATE WORK AND PHASING SCHEDULE WITH THE
CONTRACTING OFFICER'S REPRESENTATIVE.
G. CONTRACTOR TO COORDINATE CABLE COLORS WITH THE VA
PRIOR TO PURCHASING AND INSTALLATION. GREEN CABLING FOR CAT6A
DATA, WHITE FOR TELEPHONE VOICE.
H. ALL CATEGORY-6A STATION CABLING SHALL BE SUPPORTED
USING A COMBINATION OF CONDUITS ALONG CABLE PATHWAY TO
NEW MCR.
I. COORDINATE SECURITY WORK WITH ALL OTHER TRADES. VERIFY ALL
EXISTING CONDITIONS BEFORE THE START OF WORK.
GENERAL NOTES
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
CONSULTANTS:
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC ENGINEER
SPUR DESIGN
2519 MADISON AVE., STE. 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
RATED ENGINEERING
609 S. KELLY AVENUE, SUITE H2
EDMOND, OK 73003
(405) 856-2965
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TECH ENGINEER
ASPEN COMMUNICATIONS, LLC
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STRUCT ENGINEER
STAND STRUCTURAL ENGINEERING
8234 ROBINSON STREET
OVERLAND PARK, KS 66204
(913) 214-2169
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. BR 2171 EXP. 09/30/2023
ENGR REG. NO. F-17591 EXP. 02/29/2024
STAMP:
Drawing Number
Building Number
BUILDING 34 NOT SPRINKLERED. ALL OTHER BUILDINGS FULLY SPRINKLERED.
COMMISSIONING
ES2
13401 N. SANTA FE AVE
OKLAHOMA CITY, OK 73114
(405) 528-4500
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
C O
N T
R O
L L E
D U
N C
L A
S S
IF
IE
D I
N F
O R
M A
T
IO
N
C U
I)
/2
/2
:3 :3
A
M
100% BID DOCUMENTS
BLDG 1 - SECURITY ENLARGED PLANS
JPH 222 OF 229KGH
BONHAM EHRM
INFRASTRUCTURE
UPGRADES
07/07/2023
54…